- 05000285/LER-1983-001, Forwards LER 83-001/03L-0 (← links)
- ML20069K065 (redirect page) (← links)
- 05000285/LER-1983-003 (redirect page) (← links)
- 05000285/LER-1983-012-03, /03L-0:on 831122,during Performance of Monthly Surveillance Test,Pressure Indicator D/Pic-905 Operated Erratically.Caused by Blown Power Supply Fuse.Fuse Replaced (← links)
- 05000285/LER-1983-011-03, /03L-0:on 831111,diesel Generator DG-1 Failed to Field Flash During Surveillance Test.Caused by Damaged Relay Socket & Circuit Rectifying Diodes.Zener Diode Replaced & Regulator Adjusted (← links)
- 05000285/LER-1983-010-03, /03L-0:on 831031,during Surveillance Test ST-ESF-5,Bliss Eagle Timer S1-1A on Sequencer S1-2 Failed to Time Out within Prescribed Limit.Caused by Dirty Operating Mechanism.Timer Replaced (← links)
- 05000285/LER-1983-008-03, Diesel Generator DG-2 Failed to Flash & Control Room Had No Indication That Diesel Up to Operating Speed.Caused by Failure of Modified Panalarm,Model 70-PCD-25 (← links)
- 05000285/LER-1983-009-03, /03L-0:on 831012,channel a Control Room Indicator Associated W/Reactor Coolant Loop RC-2A Flow Failed High. Caused by Intermittently Failing Transmitter Due to Bad Amplifier.Transmitter Replaced (← links)
- 05000285/LER-1983-007-03, /03L-0:on 830722,reactor Protective Sys Channel B Axial Power Distribution Positive Trip Setpoint Found Out of Spec Tolerance in Nonconservative Direction.Caused by Failure of Dual Potentiometer Module (← links)
- 05000285/LER-1983-004-03, Pressure Switches A/PC-742-1 & A/PC-742-2 Found Initiating/Actuating Above 5 Psig.Caused by Instrument Drift.Switches Recalibr (← links)
- 05000285/LER-1983-013-03, /03L-0:on 831215,during Surveillance Test ST-ESF-3,pressure Switches A/PC-742-1 & A/PC-742-2 Found Inoperable.Caused by Instrument Drift.Switches Recalibr (← links)
- 05000285/LER-1983-006-03, /03L-0:on 830714,reactor Protective Sys Channel D Axial Shape Index Internal Tilt Pretrip Setpoint Drifted Out of Spec.Caused by Faulty Bell & Howell Dual Potentiometer Module.Module Replaced (← links)
- 05000285/LER-1983-005-03, /03L-0:on 830709,channel B of Reactor Protective Sys Axial Power Distribution Negative Setpoint Observed Fluctuating in Nonconservative Direction.Caused by Failed Bell & Howell Potentiometer Module 384612-001 (← links)
- 05000285/LER-1983-001-03, /03L-0:on 830119,during Refueling Outage,Setpoint for One Pressurizer Code Safety Relief Valve Found Beyond Tech Specs.Caused by Instrument Drift.Valve Readjusted (← links)
- 05000285/LER-1983-003-01, /01T-0:on 830405,Tech Spec Heatup & Cooldown Curves in Use Since Dec 1979 Found to Be 12 Degrees Nonconservative.Caused by Baseline Curve Info Supplied in 1979 Being Inadequately Defined.Curve Being Revised (← links)