Pages that link to "05000285/LER-1981-010, Forwards LER 81-010/03L-0"
Jump to navigation
Jump to search
The following pages link to 05000285/LER-1981-010, Forwards LER 81-010/03L-0:
Displayed 14 items.
- 05000285/LER-1981-010-03, /03L-0:on 811027,D/LC-383-1 Left & Right Switches & D/LC-383-2 Left & Right Switches Found Out of Setpoint Tolerances.Caused by D Channel Level Switches Drifting Out of Calibr for Unknown Reasons.Switches Recalibr (← links)
- ML20033C894 (redirect page) (← links)
- 05000285/LER-1981-010 (redirect page) (← links)
- 05000285/LER-1981-009-03, /03L-0:on 810924,during Shutdown,Cooling Fan/Coil Placed in Svc for Containment Air Cooling.Pressurized Leak Developed When Coil End Plug Blew Out.Caused by Stripped Threads on Loosely Installed Thread End Plug (← links)
- 05000285/LER-1981-009, Forwards LER 81-009/03L-0 (← links)
- 05000285/LER-1981-008, Forwards LER 81-008/03L-0 (← links)
- 05000285/LER-1981-006-03, /03L-0:on 810624,reactor Protection Sys Nuclear Power Recorder Channel B Trip Setpoints Determined to Be Nonconservative.Caused by Faulty Temp Change Power Calculation Due to Grounded Hot Leg Temp Loop (← links)
- 05000285/LER-1981-004, Forwards Revised Attachment 3 to LER 81-04 Re Tech Spec 2.01.Since startup,34 Maint Orders Written on Single Pal Door Seal Failures (← links)
- 05000285/LER-1981-005-03, /03L-0:on 810423,dc Sequencer Timers AC-3A (Component Cooling Water Pump) & AC-102A (Raw Water Pump) Failed to Time Out within Prescribed Limit.Cause Unknown Mechanisms Satisfactorily Inspected (← links)
- 05000285/LER-1981-005, Forwards LER 81-005/03L-0 (← links)
- 05000285/LER-1981-003-01, /01T-0:on 810428,MSIVs HCV-1041A/HCV-10242A Failed Closed Upon Loss of All 125 Volt Dc Power Feeding Bus A1-41B.Caused by Damaged Cable on 100 Amp Switch.Switch & Cable Replaced.All Breaker Panel Lugs Checked for Tightness (← links)
- 05000285/LER-1981-002-01, /01T-0:on 810413,during Normal Operation at 65% Power,Notification Received of Defect in Certain Foxboro Transmitters.Transmitters Have Capacitor Amplifier Which May Fail Due to Heat During Operation or After LOCA (← links)
- 05000285/LER-1981-002, Forwards LER 81-002/01T-0 (← links)
- 05000285/LER-1981-001-01, /01T-0:on 810114,discovered That FT-236 Changing Header Flow Lacks Complete Info to Qualify for Harsh Radiation Svc Required by IE Bulletin 79-01B.Caused by Incomplete Matls List.Transmitter Will Be Replaced (← links)