Pages that link to "05000285/LER-1981-008, Forwards LER 81-008/03L-0"
Jump to navigation
Jump to search
The following pages link to 05000285/LER-1981-008, Forwards LER 81-008/03L-0:
Displayed 12 items.
- ML20010H853 (redirect page) (← links)
- ML20010H854 (← links)
- 05000285/LER-1981-008-03, /03L-0:on 810813,86B/CRHS (Containment Radiation High Signal) Lockout Relay Failed to Actuate When RM-062 Was Placed in Alarm,Resulting in Failure of 86B1/CRHS Relay to Actuate.Caused by Dirt in Relay Latching Mechanism (← links)
- 05000285/LER-1981-008, Forwards LER 81-008/03L-0 (← links)
- 05000285/LER-1981-008, Forwards LER 81-008/03L-1 (redirect page) (← links)
- ML20041F627 (redirect page) (← links)
- 05000285/LER-1981-011-03, /03L-0:on 811113,containment Isolation Valves Opened & Ventilation Process Initiated W/Containment Air Monitor RM-050/051 Inoperable.Caused by Personnel Error. Valves Closed (← links)
- 05000285/LER-1981-011, Forwards LER 81-011/03L-0 (← links)
- 05000285/LER-1981-004-01, /01T-0:on 810430,personnel Air Lock Door Seals Leak Rate Exceeded Allowable Rate.Caused by Mechanical Door Seals Not Sealing Properly.Seals Repaired (← links)
- 05000285/LER-1981-009-03, /03L-0:on 810924,during Shutdown,Cooling Fan/Coil Placed in Svc for Containment Air Cooling.Pressurized Leak Developed When Coil End Plug Blew Out.Caused by Stripped Threads on Loosely Installed Thread End Plug (← links)
- 05000285/LER-1981-009, Forwards LER 81-009/03L-0 (← links)
- 05000285/LER-1981-008 (redirect page) (← links)
- 05000285/LER-1981-008-03, /03L-0:on 810813,86B/CRHS (Containment Radiation High Signal) Lockout Relay Failed to Actuate When RM-062 Was Placed in Alarm,Resulting in Failure of 86B1/CRHS Relay to Actuate.Caused by Dirt in Relay Latching Mechanism (← links)
- 05000285/LER-1981-006-03, /03L-0:on 810624,reactor Protection Sys Nuclear Power Recorder Channel B Trip Setpoints Determined to Be Nonconservative.Caused by Faulty Temp Change Power Calculation Due to Grounded Hot Leg Temp Loop (← links)
- 05000285/LER-1981-004, Forwards Revised Attachment 3 to LER 81-04 Re Tech Spec 2.01.Since startup,34 Maint Orders Written on Single Pal Door Seal Failures (← links)
- 05000285/LER-1981-005-03, /03L-0:on 810423,dc Sequencer Timers AC-3A (Component Cooling Water Pump) & AC-102A (Raw Water Pump) Failed to Time Out within Prescribed Limit.Cause Unknown Mechanisms Satisfactorily Inspected (← links)
- 05000285/LER-1981-005, Forwards LER 81-005/03L-0 (← links)
- 05000285/LER-1981-003-01, /01T-0:on 810428,MSIVs HCV-1041A/HCV-10242A Failed Closed Upon Loss of All 125 Volt Dc Power Feeding Bus A1-41B.Caused by Damaged Cable on 100 Amp Switch.Switch & Cable Replaced.All Breaker Panel Lugs Checked for Tightness (← links)
- 05000285/LER-1981-002-01, /01T-0:on 810413,during Normal Operation at 65% Power,Notification Received of Defect in Certain Foxboro Transmitters.Transmitters Have Capacitor Amplifier Which May Fail Due to Heat During Operation or After LOCA (← links)
- 05000285/LER-1981-002, Forwards LER 81-002/01T-0 (← links)
- 05000285/LER-1981-001-01, /01T-0:on 810114,discovered That FT-236 Changing Header Flow Lacks Complete Info to Qualify for Harsh Radiation Svc Required by IE Bulletin 79-01B.Caused by Incomplete Matls List.Transmitter Will Be Replaced (← links)