- ML19340E256 (redirect page) (← links)
- ML19340E257 (← links)
- 05000285/LER-1980-031-03, /03L-0:on 801207,during Normal Operation,Leak Developed in Weld Connecting Demineralized Water Flush Line to Discharge Manifold of Charging Pump.Caused by Probable Piping Vibration.Crack Repaired & Pump Returned to Svc (← links)
- 05000285/LER-1980-031, Forwards LER 80-031/03L-0 (← links)
- 05000285/LER-1980-031-03, /03L-0:on 801207,during Normal Operation,Leak Developed in Weld Connecting Demineralized Water Flush Line to Discharge Manifold of Charging Pump.Caused by Probable Piping Vibration.Crack Repaired & Pump Returned to Svc (← links)
- 05000285/LER-1980-031 (redirect page) (← links)
- 05000285/LER-1980-026-03, /03L-0:on 801030,AB-1 Matrix Relay Failed to Trip Clutch Power Supplies.Caused by Failure of Matrix Circuit to Break Contact.Relay Replaced & Applicable Surveillance Test Performed to Demonstrate Operability (← links)
- 05000285/LER-1980-026, Forwards LER 80-026/03L-0 (← links)
- 05000285/LER-1980-024-03, /03L-0:on 800926,while Completing Repairs on B Charging Pump,A Charging Pump Became Inoperable.Caused by Packing Cooling Pump Failure.Motor Replaced (← links)
- 05000285/LER-1980-024, Forwards LER 80-024/03L-0 (← links)
- 05000285/LER-1980-022-03, /03L-0:on 800911,during Safety Injection Actuation Signal Surveillance test,86B/VIAS Lockout Failed to Trip. Caused by Burned Coil.Coil Replaced W/Spare & Tested Satisfactorily for Proper Operation (← links)
- 05000285/LER-1980-022, Forwards LER 80-022/03L-0 (← links)
- 05000285/LER-1980-020-03, /03L-0:on 800905,axial Power Distribution Setpoints on D Channel Discovered Out of Tolerance in Nonconservative Direction.Caused by Dependent Setpoint Selection Switch Failure.Switch Cleaned & Returned to Svc (← links)
- 05000285/LER-1980-020, Forwards LER 80-020/03L-0 (← links)
- 05000285/LER-1980-017-03, /03L-0:on 800804,during Normal Power Operation, Personnel Discovered Setpoint Selector Switches for RMO-61, Particulate Radiation Monitor,In Wrong Position.Caused by Personnel Error While Performing Test on Radiation Monitor (← links)
- 05000285/LER-1980-017, Forwards LER 80-017/03L-0 (← links)
- 05000285/LER-1980-018-03, /03L-0:on 800808,while Attempting to Monitor Gas Space on Vct,Inadvertent Release of Radioactive Matl to Auxiliary Bldg Environ Occurred.Caused by Deteriorated Surgical Tubing on Gas Analyzer.Tubing Replaced (← links)
- 05000285/LER-1980-018, Forwards LER 80-018/03L-0 (← links)
- 05000285/LER-1980-014-03, /03L-0:on 800709,transformer T4 of Diesel Generator 1 Failed.Caused by Shorted Coil.Transformer Replaced (← links)
- 05000285/LER-1980-014, Forwards LER 80-014/03L-0 (← links)
- 05000285/LER-1980-013-03, /03L-0:on 800707,during Normal Power Operation, Noted That Channel a Dc Sequencer SI-1 Had de-energized on-auto Light.Caused by Sequencer Circuitry Failure Due to Faulty Relay (← links)
- 05000285/LER-1980-013, Forwards LER 80-013/03L-0 (← links)
- 05000285/LER-1980-012-03, /03L-0:on 800708,during Performance of ST-RPS-3, F.2,discovered That Trip Unit 3 Setpoints Had Drifted Out of Spec in Nonconservative Direction.Caused by Normal Setpoint Drift.Setpoints Adjusted (← links)
- 05000285/LER-1980-015-03, /03L-0:on 800710,during Insp,Noted That Trip Unit Setpoints on C Channel Had Become Positive Rather than Negative.Caused by Failure of 15-volt Power Supply for Trip Unit 4.Unit Calibr (← links)
- 05000285/LER-1980-015, Forwards LER 80-015/03L-0 (← links)
- 05000285/LER-1980-007-01, /01T-0:on 800430,penetration Cable Splices for Containment Ventilation Fans Found to Lack Documentation for LOCA Qualification.Splices Will Be Coated w/LOCA-qualified Sealant (← links)
- 05000285/LER-1980-016-03, /03L-0:on 800621,weld on Suction Side of Pump CH-1B in Demineralized Water Flush Line Cracked.Caused by Vibration of Piping in Svc.Crack Was Ground Out & Rewelded Using Certified Procedure & Line Tested (← links)
- 05000285/LER-1980-011, Forwards LER 80-011/03L-0 (← links)
- 05000285/LER-1980-010-01, /01T-0:on 800516,during Cold Pressure Test,Leakage Discovered at Gasket Joint Between Pump Casing & Pump Cover on Reactor Coolant Pumps RC-3A,3B & 3C.Closure Studs Corroded by Boric Acid.Leaks Caused by Deteriorated Gaskets (← links)
- 05000285/LER-1980-010, Forwards LER 80-010/01T-0 (← links)
- 05000285/LER-1980-006-01, /01T-0:on 800415,as Required by IE Bulletin 79-01B,util Has Been Obtaining & Reviewing Test Data on Electrical Equipment.Samples Failed to Meet Acceptance Criteria.Caused by Steam & Moisture in Environ (← links)