05000382/FIN-2016008-03
From kanterella
Revision as of 08:56, 25 September 2017 by StriderTol (talk | contribs) (Created page by program invented by Mark Hawes)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Finding | |
---|---|
Title | Failure to Include Appropriate Quantitative Acceptance Criteria for the Reconstituted Feedwater/Emergency Feedwater Monitoring Plan Associated with Steam Generator Replacement Induced Vibration |
Description | The team identified a finding of very low safety significance and associated non-cited violation of 10 CFR Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, for the licensees failure to include appropriate quantitative accept an cecriteria for determining that important activities have been satisfactorily accomplished. Specifically, the licensees reconstituted feedwater and emergency feedwater system monitoring plan, which was created to monitor both systems vibrations following the sites steam generators replacement, did not include a range for acceptable vibration levels for all The team identified a finding of very low safety significance and associated non-cited violation of 10 CFR Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, for the licensees failure to include appropriate quantitative acceptance criteria for determining that important activities have been satisfactorily accomplished. Specifically, the licensees reconstituted feedwater and emergency feedwater system monitoring plan, which was created to monitor both systems vibrations following the sites steam generators replacement, did not include a range for acceptable vibration levels for all |
Site: | Waterford |
---|---|
Report | IR 05000382/2016008 Section 4OA2 |
Date counted | Dec 31, 2016 (2016Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | D Merzke E Ruesch F Ramirez G George M Hayes T Hipschman |
Violation of: | 10 CFR 50 Appendix B Criterion V |
CCA | P.3, Resolution |
INPO aspect | PI.3 |
' | |
Finding - Waterford - IR 05000382/2016008 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Waterford) @ 2016Q4
Self-Identified List (Waterford)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||