Finding | |
---|---|
Title | Fire Hazards Analysis Report Incorrectly Described Rooms 511 and 512 as being Continuously Staffed |
Description | The inspectors identified a finding of very-low safety significance (Green), and associated Non-Cited Violation of License Condition 2.C.(4) for the licensees failure to implement and maintain the Fire Protection Program as described in the Updated Final Safety Analysis Report. Specifically, the current Fire Hazards Analysis Report incorrectly listed rooms 511 and 512 as not requiring a separate fire watch, for fire protection impairments, because the rooms were incorrectly assumed to be continuously staffed or visible to the continuously staffed area. The licensee entered this issue into their Corrective Action Program and updated the Fire Hazards Analysis Report to reflect the current operating practice and deleted rooms 511 and 512 from the list of rooms that were continuously staffed. The inspectors determined that the performance deficiency was more-than-minor because if left uncorrected, it could become a more significant safety concern for the failure to maintain the defense-in-depth element for the Fire Protection Program. The lack of fire watches degraded the ability to recognize conditions which could either increase the likelihood of a fire or the severity of a fire. The finding was representative of a low degradation and screened as having very low safety significance (Green) in Task 1.3.1 of IMC 0609, Appendix F. The finding did not have a cross-cutting aspect associated with it because it was not reflective of current performance. |
Site: | Davis Besse |
---|---|
Report | IR 05000346/2016009 Section 1R05 |
Date counted | Dec 31, 2016 (2016Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05 |
Inspectors (proximate) | A Dahbur A Shaikh I Hafeez R Daley |
Violation of: | License Condition - Fire Protection |
INPO aspect | |
' | |
Finding - Davis Besse - IR 05000346/2016009 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Davis Besse) @ 2016Q4