{{Adams | number = ML16147A202 | issue date = 04/29/2016 | title = Seabrook Station, Revision 17 to Updated Final Safety Analysis Report, Fire Protection of Safe Shutdown Capability (10CFR50, Appendix R) | author name = | author affiliation = NextEra Energy Seabrook, LLC | addressee name = | addressee affiliation = NRC/NRR | docket = 05000443 | license number = | contact person = | case reference number = SBK-L-16048 | package number = ML16260A369 | document type = Fire Protection Plan, Updated Final Safety Analysis Report (UFSAR) | page count = 756 }}

Text

{{#Wiki_filter:SEABROOK STATION Fire Protection of Safe Shutdown Capability (10CFR50, Appendix R) Revision 1 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Introduction Rev. 5Section 1 Page 1-1 INTRODUCTION General Design Criterion 3, "Fire Protection," of Appendix A, "General Design Criteria for Nuclear Power Plants," to 10 CF R Part 50" Licensing of Producti on and Utilizatio n Facilities" requires that structures, systems and components important to safety shall be designed and located to minimize, consistent with other safety requirements, the probability and effects of fires. Appendix R, "Fire Protection Program for Nuclear Power Facilities Opera ting Prior to January 1, 1979" to 10 CFR Part 50 was issued on Novemb er 19, 1980 (45 FR 76602). Paragraph III.G, "Fire Protection of Safe Shutdow n Capability," requires that fire damage be limited so that: a. One train of systems necessary to achieve and maintain hot shutdown conditions from either the control room or emergenc y control station(s) is free of fire damage; and b. Systems necessary to achieve and maintain cold shutdown from either the control room or emergency control station(s) can be repaired within 72 hours. This requires each licensee to assess those areas of the plant"....where cables or equipment, including associated non-safety circuits that could prevent operation or cause maloperation due to hot shorts, open circuits, or shorts to ground of redundant trains of systems necessary to achieve and maintain hot shutdown conditions are located in the same fire area..." The regulation establishes separation requirements for areas outside of primary containment and inside noninerted containment. Appendix R, paragraph III.L, "Alternative and Dedicated Shutdown Capability," establishes the following performance goals for the shutdown functions: a. The reactivity control function shall be capable of achieving and maintaining cold shutdown reactivity conditions. b. The reactor coolant makeup function shall be capable of maintaining the reactor coolant level within level i ndication in the pressurizer. c. The reactor heat removal function shall be capable of achieving and maintaining decay heat removal. d. The process monitoring function shall be capable of providing di rect readings of the process variables necessary to perform and control the above functions. e. The supporting functions shall be cap able of providing process cooling, lubrication, etc., necessary to permit operation of the equipment used for Safe Shutdown functions. Branch Technical Position CMEB 9.5-1 "Guidelines for Fire Protection for Nuclear Power Plants," Rev. 2, July 1981 reiterates the above requirements in Section C.5.b and C.5.c. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Introduction Rev. 5Section 1 Page 1-2 By letters dated March 16, 1981 (from R.L. Tedesco to W.C. Tallman) and September 30, 1981 (from D.G. Eisenhut to W.C. Tallman) the Nuclear Regulatory Commission (NRC) transmitted "Request for Additional Information, Seabrook Station, Units 1 & 2, Fire Protection Program, Power System." This document requested New Hampshire Yankee (NHY) to provide information relative to the equipment and cabling required to achieve and maintain hot and/or cold shutdown. By letter dated July 27, 1982 (from F.J. Miraglia to W.C. Tallman) the NRC transmitted Auxiliary System Branch RAI's. By letter of May 15, 1981 (SBN-160), NHY committed itself to undertaking a comprehensive program to address the concerns identified in the NRC letters. This report and appendix detail the program a nd the analyses and evaluations emanating from it. The "Report" is comprised of the following: 1. An "Introduction" section.

2. A "Report Preparation/Maintenance" section which summarizes the program utilized to perform the Safe Shutdown Capability review and to maintain the safe shutdown capability as plant modifications are implemented. 3. Safe Shutdown Capability 3.1 The "Discussion of Bases and Positi ons" section provide s a discussion of the bases and positions established fo r the review of the safe shutdown performance goals. 3.2 The "Main Control Room Safe Shut down" Section provides a discussion of the Shutdown Locations, Functions/Systems which satisfy the performance goals; a Safe Shutdown Equipment List; and an analysis and evaluation of each fire area. 3.3 The "Alternative Safe Shutdown Using Remote Safe Shutdown Facilities" discusses the bases and positions established for the review; a review of the Alternative Safe Shutdown capabilities; an Alternative Safe Shutdown Equipment List; and an an alysis and evaluation. 3.4 The "Alternative Safe Shutdown - Emergency Feedwater Pumphouse Fire" section discusses the location and shutdown capabilities, and an analysis and evaluation of this fire area. 3.5 The "High-Low Pressure Interfaces" s ection provides a general discussion, a list of interfaces, a High Low Pressure Interface Safe Shutdown Equipment List and an analysis and evaluation. 3.6 The "Associated Circuits" section provides a definition of associated circuits of concern and a discussion of the me thodology used to address the various types of associated circuits.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Introduction Rev. 5Section 1 Page 1-3 3.7 The "Deviations from 1OCFR50 Appendix R" section lists all deviations resulting from the shutdown analysis. The "Appendix" is comprised of the follo wing sections which support the report: I. A "P&I Diagrams (Typical)" section which contains photographs of typical marked P&I Diagrams utilized in the review. II. A "Schematic Diagrams & Cable Diagrams (Typical)" section which contains copies of typical drawings utilized in the review. III. An "Equipment Lists (Tables)" section which contains the tables that list all equipment required for performance of the Safe Shutdown functions. IV. A "Raceway Arrangement Drawings (Typical)" section which contains photographs of typical marked raceway drawings utilized in the review.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Report Preparation Rev. 13 Section 2 Page 2-1 REPORT PREPARATION/MAINTENANCE To establish a methodical course of action and provide guidance to the various organizations required to support the initial development of the Safe Shutdown Capability program, UE&C procedure TP -2 (NHY Procedure 38160) titled "Procedure for Review and Report Preparation for 10 CFR Part 50 Appendix R, Fire Protection of Safe Shutdown Capability " was prepared. The salient points of this procedure are as described in Sections 2.1 to 2.8. As modifications are implemented to the plant, the effect of these modifications to this report must be evaluated. The evaluation process is as described in Section 2.9. 2.1 DETERMINATION OF FIRE AREAS/ZONES The fire areas/zones are as delineated in "Fire Protection Program Evaluation and Comparison to Branch Technical Position APCSB 9.5 -1, Appendix A " or as determined by the Responsible Engineer. 2.2 DETERMINATION OF SAFE SHUTDOWN SYSTEMS The Safe Shutdown systems were determined by considering the minimum performance goals established in Appendix R, Paragraph III.L.2, and utilizing the following sources for guidance: 2.2.1 Final Safety Analysis Report - Seabrook Station 2.2.2 Fire Protection Program Evaluation and Comparison to Branch Technical Position APCSB 9.5 -1, Appendix A 2.2.3 Station Operating Procedure No. OS1200.01 "Safe Shutdown and Cooldown from the Main Control Room " 2.2.4 Station Operating Procedure No. OS1200.02 "Safe Shutdown and Cooldown from the Remote Safe Shutdown Facilities " 2.2.5 United Engineers & Constructors Inc. Engineering 2.2.6 Yankee Atomic Electric Co. Engineering 2.2.7 New Hampshire Yankee Engineering

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Report Preparation Rev. 13 Section 2 Page 2-2 2.3 DETERMINATION OF SAFE SHUTDOWN EQUIPMENT The minimum equipment necessary to perform the Safe Shutdown function was determined by utilizing the following sources: 2.3.1 Final Safety Analysis Report - Seabrook Station 2.3.2 Fire Protection Program Evaluation and Comparison to Branch Technical Position APCSB 9.5 -1, Appendix A 2.3.3 Station Operating Procedure No. OS1200.01 "Safe Shutdown and Cooldown from the Main Control Room " 2.3.4 Station Operating Procedure No. OS1200.02 "Safe Shutdown from the Remote Safe Shutdown Facilities " 2.3.5 Piping and Instrumentation (P&I) Diagrams 2.3.6 United Engineers & Constructors Inc. Engineering 2.3.7 Yankee Atomic Electric Co. Engineering 2.3.8 New Hampshire Yankee Engineering Sets of P&I Diagrams and One -Line Diagrams were marked to indicate hot standby equipment and cold shutdown equipment for main control room shutdown and remote safe shutdown. Train A equipment was marked in red, and Train B equipment was marked in green. Photographs of typical marked P&I Diagrams are contained in Appendix Section I. 2.4 DETERMINATION OF SAFE SHUTDOWN CABLES Considering the equipment defined and utilizing their related electrical schematic diagrams and cable schematics, the cables required for Safe Shutdown were determined. The raceways through which these cables were routed were determined; and then their associated fire area/zone(s) were determined. To document the review, the "10 CFR 50 - Appendix R, Safe Shutdown Equipment List" was prepared from data gathered in this review. Copies of typical schematic diagrams and cable schematics are contained in Appendix Section II. Copies of the safe shutdown equipment lists are contained in Appendix Section III.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Report Preparation Rev. 13 Section 2 Page 2-3 The equipment required for fire safe shutdown can be divided into supporting equipment and supported equipment. For example, CC -TE-2197 is supporting equipment for CC pump trip and CC-P-11A/C are the corresponding supported equipment. Supported equipment tag numbers are typically listed in the Appendix III Equipment Tables - "Equipment Id No. " column and represent the major components used to perform each safe shutdown function. Supporting equipment tag numbers are typically not listed in the "Equipment Id No. " column but should be listed in the "Supporting Control and Instrumentation Equipment " columns. The following guidance should be used for lisiting supported and supporting equipment tag numbers in the Appendix R Report Section 3 Tabulations and for assigning the descriptions for CASP cables. The tag number for supporting equipment should be listed in the tabulation for the fire zone/area in which the equipment is located with an "X" in the equipment column and an "X" in the cable column. For other fire zones/areas which contain just the cable for the supporting equipment, the cable should be accounted for with an "X" in the cable column using the tag number of the supported equipment. The safe shutdown analysis for each fire zone/area should discuss the impact of fire damage to the supporting equipment cables and equipment in terms of the impact on operation of the supported equipment. The cable "description " in CASP for supporting equipment cables should be the support ed equipment tag number. Note that this specific guidance was added to the Report in 2013 to address future Report changes but was typically applied in the past. 2.5 COMPUTER INPUT AND REPORTS The following data were input to UE&C 's "NRC Emergency Shutdown Program NRCESP " Program No. EL -130: a. Listing of Raceways and their Associated Fire Zones

b. Listing of Cables (from Safe Shutdown Equipment Lists)

The following output reports were generated using the NRC Emergency Shutdown Programs:

c. Listing of Fire Areas/Zones
d. Safe Shutdown Cables using CASP A Format
e. Safe Shutdown Raceways and Associated Cables by Fire Zone
f. Safe Shutdown Raceways and Cables
g. Cables with Associated Fire Zones Copies of the input data and output reports were contained in Appendix Section V.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Report Preparation Rev. 13 Section 2 Page 2-4 2.6 DETERMINATION OF SAFE SHUTDOWN RACEWAYS Utilizing the "Safe Shutdown Raceways and Associated Cables by Fire Zone " computer report, a set of raceway arrangement drawings was marked as follows: 2.6.1 Train A raceways, boxes, and termination equipment were marked in red. 2.6.2 Train B raceways, boxes, and terminating equipment were marked in green. 2.6.3 Equipment which is manually operated or disabled was marked in orange. A "D" was placed beside equipment to be disabled. An "M" was placed beside equipment needed to be manually operated. 2.6.4 Rated fire walls and barriers were marked in black. Photographs of typical marked raceway arrangement drawings are contained in Appendix Section IV. 2.7 ANALYSIS OF RACEWAYS AND EQUIPMENT TO SATISFY APPENDIX R REQUIREMENTS 2.7.1 Each fire area/zone that contained Safe Shutdown equipment or cables was reviewed to determine if Appendix R, Paragraph III.G.2 separation requirements were satisfied. 2.7.2 If the Appendix R requirements were not satisfied, further analysis was performed to determine the effects of a hot short circuit, short circuit, open circuit, ground or other equipment failure. 2.7.3 If the Safe Shutdown function was affected by a hot short circuit, short circuit, open circuit, ground or other equipment failure, then the following analysis to satisfy the Appendix R requirements was provided: 2.7.3.1 Analysis which documented that the in situ and transient combustibles were insufficient to cause a fire which affected the redundant trains of equipment and cables. 2.7.3.2 A three-hour fire barrier or a one-hour barrier and sprinklers between the redundant equipment or cables. 2.7.3.3 Rerouted the redundant cable out of the fire area/zones, or provided twenty feet of separation and sprinklers in the area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Report Preparation Rev. 13 Section 2 Page 2-5 2.7.3.4 Provided an alternative or dedicated safe shutdown equipment or system (See Section 3.3 and 3.4). 2.7.3.5 Requested a deviation from the 10 CFR 50, Appendix R requirements based on the combustibles in the fire area/zone, the spatial separation and the protective measures provided.

(See Section 3.7). 2.8 HIGH-LOW PRESSURE INTERFACES A list was prepared of the high

-low pressure interfaces and the lines with two or more electrically operated valves which could open and potentially cause a LOCA. A review was performed in the same manner as discussed in Section 2.4 and 2.5 utilizing this list. An analysis and evaluation were then performed.

(See Section 3.5) 2.9 MODIFICATION EVALUATION As plant modifications are implemented, their effect on the analysis contained in this report must be evaluated to ensure that the safe shutdown capability in the event of a fire is maintained. This evaluation will consider the UFSAR, this Appendix R Report, Supporting Documentation and the latest issue of design documents. If necessary, appropriate markups of documents will be included in the design change package to reflect any change in the Appendix R safe shutdown analysis.

The UE&C computer programs described in Section 2.5 are no longer available. New computer programs were written to produce the following reports to support the analysis contained in this report and evaluation of modifications:

a. List of Areas/Zones
b. List of Raceways and Associated Fire Zones
c. List of Cables w/Event Indicators
d. Safe Shutdown Raceways and Associated Cables by Fire Zone
e. Safe Shutdown Raceways and Cables
f. Cables with Associated Fire Zones Copies of these reports are contained in Appendix R supporting documentation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-1 SAFE SHUTDOWN CAPABILITY 3.1 DISCUSSION OF BASES AND POSITIONS 3.1.1 General 10 CFR Part 50 Appendix R, Paragraph III.G.1 requires that fire damage be limited so that:

a. One train of systems necessary to achieve and maintain hot standby condition from either the control room or emergency control station(s) is free of fire damage; and
b. Systems necessary to achieve and maintain cold shutdown from either the control room or emergency control station(s) can be repaired within 72 hours. Based on requiremen t "a" above, the design basis of Seabrook Station is that one train of systems necessary to achieve and maintain hot standby from the control room or the emergency control stations (hereafter designated the remote safe shutdown facilities) is free of fire damage. Under this basis, Appendix R, Paragraph III.G.2 and III.G.3 will apply to the safe shutdown paths controlled from the main control room or the remote safe shutdown facilities. Any deviations from the III.G.2 and III.G.3 criteria will be with respect to the main control room or the remote safe shutdown facilities and is addressed in Sections 3.2.7, 3.3.9, 3.4.3 and in the List of Deviations Section 3.7 of this report. For fires in some areas of plant, alternative shutdown capabilities are provided as discussed in Sections 3.3 and 3.4.

This Section defines the bases and positions utilized in determining and reviewing the shutdown capabilities that will satisfy the requirements of Paragraph III.G. These capabilities can be utilized to safely shut down the reactor in the event of a fire in any area/zone of the plant. 3.1.2 Safe Shutdown "Safe Shutdown " for purposes of the review is defined as a capability to bring the reactor from a 100 percent power operating condition to a "cold shutdown " condition. Included in this are conditions "hot standby, " "hot shutdown, " "cold shutdown, " and maintenance of "cold shutdown. " SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-2 The design basis event for safe shutdown is a postulated fire in a specific fire area/zone with or without the loss of offsite power (LOOP). This design basis was used for the original Appendix R Report preparation. The LOOP was assumed to occur whether the specific fire being analyzed caused it or not. The diesel generators (DGs) were analyzed to both automatically start and load, and not automatically start and load. An engineering evaluation prepared in 2007, documented that this was a conservative design basis since Appendix R does not require an arbitrary LOOP for non-alternate shutdown fire areas/zones (i.e., for shutdown control from the main control room). For future safe shutdown analyses, offsite power can be credited to remain available for

non-alternate shutdown fire areas/zones if the cables required to support offsite power are not damaged by the fire (i.e., an arbitrary LOOP need not be assumed). This approach provides greater analysis flexibility. No other design basis event (e.g. seismic or LOCA) is considered to occur coincident with the fire event. The safe shutdown functions shall assure the following:

a. No fuel clad damage. b. No rupture of any primary coolant boundary.
c. No rupture of containment boundary.
d. Reactor coolant system process variables shall be within those predicted for a loss of normal AC power.
e. Achievement of cold shutdown conditions within 72 hours and maintenance of cold shutdown conditions thereafter.

3.1.3 Redundancy

To assure a safe shutdown capability pre -fire, two redundant trains (Train A and Train B) of equipment are provided for each safe shutdown function. Each train contains a complete complement of the equipment, cabling, instrumentation and controls necessary to perform the safe shutdown functions. In several instances a single mechanical equipment is common to both trains (i.e., condensate storage tank, mechanical manual valves, piping, HVAC ducts, etc.). Single failure is not assumed to occur except to equipment that is damaged by the fire.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-3 3.1.4 Determination of Safe Shutdown Functions The safe shutdown functions are determined by considering the performance goals established in Appendix R, Paragraph III.L.2. The systems or portions of systems necessary to satisfy safe shutdown are subsequently determined. 3.1.5 Determination of Safe Shutdown Equipment Safe shutdown systems are the systems required to achieve the performance goals listed in Section 1. The equipment for these systems can be divided by function as Hot Standby (Reactor tripped and T -Avg above 350F) and Cold Shutdown (Reactor tripped/and cool down of the Reactor Coolant System T -Avg equal to or below 200F). The following criteria are used to determine the equipment required for safe shutdown:

a. The equipment is required to operate to permit a safe shutdown system to perform its safe shutdown function.
b. The equipment

's maloperation can prevent a safe shutdown system from performing the safe shutdown function.

c. The equipment is a process or electrical boundary for a safe shutdown system.

3.1.6 Safe Shutdown System Boundaries The safe shutdown system process boundaries are established by the following devices:

a. Normally closed manual valve
b. Check valve
c. Electrically operated safe shutdown valve
d. Root valve on small instrument lines to non

-safe shutdown instruments

e. Relief valve
f. Redundant valves on high

-low pressure boundaries

g. Boundary valve between a safe shutdown process line and a non

-Safe Shutdown process line which if it is an incorrect position will not affect the operation of the Safe Shutdown system.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-4 The safe shutdown electrical system boundaries are established by the following devices:

h. Isolation device (i.e., coordinated circuit breaker, fuse, transducer, etc.)
i. "Remote Local

" selector switch Cables isolated by "Remote-Local" selector switches or other isolation devices are not included in the review. 3.1.7 Manual Operator Actions Manual operator actions must satisfy the following considerations:

a. Sufficient manpower and time is available to perform all required manual actions.
b. There is accessibility to the equipment to perform the manual action either during or after the fire.

3.1.8 Spurious Operation The evaluation of the effects of spurious equipment operation on safe shutdown functions considers the effects of hot short circuits, short circuits, open circuits and grounds. The effects of hot short circuits are considered on the following:

a. Energized 120V ac grounded circuits
b. De-energized 120V ac grounded circuits
c. Energized 120V ac ungrounded circuits
d. Energized 125V dc ungrounded circuits Hot short circuits are not considered for disabled (tripped power supply) 3

-phase 480 Volt ac circuits, ungrounded 1 -phase 120 Volt ac circuits and ungrounded 125 Volt dc circuits as these would require multiple hot shorts in the correct sequence to cause a device to function. These are considered incredible events. The effects of short circuits, open circuits and grounds are considered for all circuits evaluated for spurious operation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-5 The above discussion does not provide all of the criteria used for evaluating spurious component operations during the original Appendix R Report preparation. An engineering evaluation prepared in 2007 reviewed various Seabrook, NRC, and industry documents to re -create the circuit analysis methodology bases used for the fire safe shutdown analyses that was not included in the above discussion. The following documents the added methodology criteria. The analyses shall consider fire induced damage to any and all unprotected cables in the fire area/zone being analyzed. Each cable failure shall be considered individually, one -at-a-time, and the effects of any spurious operation(s) evaluated. If the effect is unacceptable (ex. loss of inventory), then operator actions, or other corrective actions (see Section 2.7), are specified to mitigate the effects of the spurious operation. If the effect is acceptable, then additional sequential cable failures and resultant spurious operations of same function components must also be considered (ex. spurious opening of other normally closed series valves in a potential diversion flow path). If their effects are unacceptable, then appropriate preventative/disabling operator actions (ex. open a circuit breaker) are specified to prevent the unacceptable condition. Mitigating and preventative/disabling actions that rely on electrical power, ex. MOV operation, can not credit components with unprotected cables in the fire area/zone being analyzed. The basis described in the previous paragraph is typically referred to in the industry as any-and-all, one-at-a-time. In addition, it will be assumed that the loss of function from fire damage to unprotected cables within a fire area cable will prevent the effected components from operating to support safe shutdown but any resulting state changes will be evaluated as spurious operations following the above criteria of one -at-a-time. Also, a protective device state change from a short circuit (open a fuse or trip a circuit breaker) will be considered a spurious operation and will be evaluated following the above criteria of one -at-a-time including any end component state changes, ex., loss of control power to a normally energized solenoid operated valve (SOV) would cause the SOV to change state as a spurious operation. For Seabrook, failure of an individual cable typically only causes spurious operation of one component although there are exceptions where one cable failure can cause spurious operation of multiple components.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-6 The complete circuit for each equipment tag typically consists of multiple cables routed through many fire zones. It is expected that applying the failure modes to some cables in a circuit may not actually result in a spurious operation of the corresponding equipment. However, it appears that the original safe shutdown analyses conservatively assumed that every cable failure would cause spurious operation of the supported component(s) since there was no evidence found in the original analyses of credit being taken for analyzing specific conductor interactions as the basis for concluding that there was no resulting spurious operation. For future safe shutdown analyses, it is acceptable to use circuit analysis to demonstrate that a fire -induced cable failure can not cause a spurious operation. These circuit analyses should be included in appropriate engineering documents. Operator actions to mitigate spurious component operation must meet the criteria provided in Section 3.1.7 on manpower, timing and accessibility considering the system effect of the corresponding spurious operation. Preventative/disabling operator actions should be documented in a procedure and be able to be completed in a reasonable time consistent with completion of time critical mitigating actions. Automatic signals can be credited if their circuits are included in the analysis to ensure that their cables are free of fire damage for the fire areas which credit the signals. Automatic signals with unprotected cables in a fire zone must be analyzed to fail to operate or spuriously operate because of fire-induced cable damage. The automatic signals must also be analyzed to operate as designed if the system conditions caused by the fire (ex. low level, high flow, loss of power, etc.) would initiate the automatic function to ensure that the automatic actuation is not detrimental to safe shutdown. The review assumes that all conductors within multi -conductor cables would short, open or ground due to a fire. Cable to cable interactions are not considered credible events because of the

thermoset cable insulation used at Seabrook Station. 3.1.9 Disabled (tripped power supply) Equipment To prevent spurious operations of valves and other equipment which are normally aligned in their safe shutdown position, the operators will trip the power supplies to these devices upon reaching the RSS facilities.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-7 3.1.10 Fire Areas The "Fire Protection Program Evaluation and Comparison to Branch Technical Position APCSB 9.5-1, Appendix A" report establishes fire areas and zones for purposes of fire detection and protection. Although these zones are satisfactory for fire detection and protection, they do not in all cases satisfy Appendix R requirements. To assure that the Appendix R separation requirements are satisfied, zones containing redundant equipment which do not satisfy the requirements are grouped and analyzed to provide assurance that safe shutdown can be achieved. An example of this is containment which has three zones: C -F-l-Z, C-F-2-Z and C-F-3-Z. As there is no 3 -hour rated barrier between zones, they have been considered as one fire area. The delineation of the fire areas and zones which have been combined into a fire area is in Section 3.2.7. 3.1.11 Emergency Lighting Emergency lighting units per Appendix R, Paragraph III J are provided with at least an 8 -hour battery powered supply or diesel generator backed essential lighting (See letter SBN -932, dated January 27, 1986, Deviation No. 10) in all areas needed for operation of safe shutdown equipment and in access and egress routes. In areas where actions are required after eight hours and actions are needed during a cooldown, 8 -hour battery powered supplied lights are not provided. Repairs per Appendix R III G.l.b, will be implemented to provide required illumination for required cooldown actions. 3.1.12 Repairs for Cold Shutdown For cold shutdown, the following equipment will require replacement of control fuses which will be available in the Train B switchgear room.

a. EAH-FN-31B b. RC-V87 c. RC-V88 d. RH-P-8B e. SI-V17 f. SI-V47 In the event that emergency bus EDE

-SWG-5 is not available, a temporary power connection will be provided from EDE -MCC-621 to the RC -V88 MCC cubicle.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-8 In the event that PCCW cooling is lost to containment due to loss of containment instrument air causing inboard PCCW isolation valve closure, IA -V530 will be manually opened via a pneumatic jumper to supply outside containment instrument air to containment instrument air to reopen the inboard PCCW isolation valves to reestablish PCCW cooling flow to support containment habitability.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-1 3.2 MAIN CONTROL ROOM SAFE SHUTDOWN 3.2.1 Main Control Room Safe Shutdown Locations Safe shutdown will be accomplished with control from the main control room (MCR), utilizing the safe shutdown equipment and depending on the location of the fire, a combination of the following locations:

a. Train A Switchgear Room
b. Train B Switchgear Room
c. Diesel Generator Room A
d. Diesel Generator Room B
e. Primary Auxiliary Building El. 25

'-0" Boric Acid Storage Tank Area

f. Primary Auxiliary Building El. 7

'-0" Charging Pump Rooms

g. Containment
h. Equipment Train A Vault (Vault #1)
i. Equipment Train B Vault (Vault #2)
j. Mechanical Penetration Area
k. Emergency Feedwater Pump Building
l. Condensate Storage Tank
m. Control Room HVAC Equipment and Duct Area
n. Non-Essential Switchgear Room
o. Turbine Building Actions from the various areas would be of the following types: manual valve actuations, manual damper actuations, tripping of power supplies, opening of doors to provide air flow for cooling, realign power supplies, and/or manipulation of control switches.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-2 The term "prompt action " refers to an action taken after receipt of a valid fire alarm in the main control room. The term "expeditious action" or "expeditiously " refers to an action taken quickly upon entry into the applicable safe shutdown procedure. These type actions are considered to be completed prior to a spurious operation of the equipment operated by the prompt and expeditious

actions. Therefore, no associated timing calculation is required for these actions. 3.2.2 Safe Shutdown Functions for Hot Standby The following are PWR equipment necessary for hot standby: 3.2.2.1 Reactor Coolant (RC) Inventory and Pressure Control To compensate for miscellaneous RC system leakage, RC pump seal leakage and cooldown volume shrink, portions of the chemical and volume control (CS) system including centrifugal charging pumps, boric acid transfer pumps, and a borated water supply, either the refueling water storage tank (RWST) or the boric acid tanks (BAT) are used. The injection path to the RC system will be either through the seal injection flow path or the high head injection flow path. The preferred seal injection path requires that a flow control valve (CS -FCV-121) and that a minimum of two of the four seal injection valves (CS -V154, CS-V158, CS-V162 or CS -V166) be operable. Additionally, the normal charging flow path to the RC system is isolated. This can be accomplished by use of any one of three functionally redundant valves (CS -V142, CS-V143 or CS-HCV-182). Should the seal injection path not be operable, e.g., due to spurious closure of a flow path valve (CS -FCV-121) the high head injection flow path (SI -V138 or SI -V139) can be utilized initially to maintain hot standby by batch charging from the RWST to maintain pressurizer level. Should SI -V-138 or SI -V-139 spuriously open, the charging pump may have to be stopped to prevent overfill of the pressurizer. During cooldown as RC system pressure decreases, it is necessary to provide a flow restricted path to prevent charging pump cavitation. This is due to the limited flow capability from the BAT. If the high head injection path cannot be isolated at this time and/or if the flow controlled path through CS -FCV-121 is not operable, a capability is provided to manually align and throttle the charging pumps to the seal injection flow paths. The necessary operator actions and valve alignments are unique for each fire area where these flow paths are affected and are described in the analysis for each area. RC pump seal cooling is provided by a redundant thermal barrier cooling system. Should the redundant thermal barrier system not be available, the seals will be cooled by the seal injection capability. On a long term basis, seal injection will be restored. The reactor coolant pumps (RCPs) are stopped from the main control board. Circuit analysis shows that the RCPs can not spuriously restart due to fire -induced cable damage.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-3 The RC system pressure is controlled by use of a portion of the RC system which includes the pressurizer heaters (Group A and B) to increase pressure and the pressurizer power operated relief valves (PORV) which depressurize the RC system by discharging reactor coolant fluid to the pressurizer relief tank (PRT). Considering worst case scenarios for spurious actuation of affected equipment, the required times for operator actions regarding RC inventory and pressure control for safe shutdown from the main control room are provided below: Action Time Close PORV block valve Prompt Isolate letdown 15 minutes Swap charging pump suction from VCT to RWST 15.4 minutes. Should SI -V138, SI-V139, or CS -HCV-182 spuriously open, this action must be completed no later than 5.0 minutes following letdown line isolation. Trip RCPs 10 minutes Open a PORV to reduce pressurizer pressure in the event of spurious pressurizer heater operation or trip

pressurizer heaters 23 minutes Start a charging pump, or open a high head safety injection valve SI -V-138 or SI -V-139 if normal charging pump path is not available 31.1 minutes Isolate charging flow, except for seal injection 35.4 minutes Trip spuriously operating containment building spray pumps 46 minutes Trip spuriously operating SI pump < 4 hours, prior to commencement of plant cooldown Isolate the potential diversion path from the BAT to the RWST, or align BAT for gravity feed.

<4 hours, prior to commencement of plant cooldown

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-4 Action Time Align BAT for makeup source

<4 hours, prior to commencement of plant cooldown 3.2.2.2 Reactivity Control Reactivity for hot standby at normal operating temperature (not) is provided by insertion of the control rods. Reactivity conditions required for cooldown and maintaining cold shutdown are provided by a portion of the chemical and volume control (CS) system which includes a centrifugal charging pump taking suction from the BAT

's either utilizing the gravity flow path or the boric acid transfer pumps. During cooldown, the borated water source must be the BAT volume until exp ended to at least the point that the volume injected or a boron sample demonstrates that sufficient shutdown margin for cold shutdown has been achieved, at which time the RWST would be aligned. If gravity feed from the BAT is used, the RWST must be isolated. Considering worst case scenarios for spurious actuation of affected equipment, the required times for operator actions regarding reactivity control for safe shutdown from the main control room are provided below: Action Time Trip the Reactor Expeditiously Provide borated water from the BATs, via boric acid transfer pump or gravity feed

<4 hours, prior to commencement of plant cooldown Isolate boric acid flow diversion path
<4 hours, prior to commencement of plant cooldown

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-5 3.2.2.3 Decay Heat Removal The reactor coolant (RC) system temperature is controlled by use of portions of the feedwater (FW) system and the main steam (MS) system. The main steam safety/relief valves will maintain a heat dump capability. The steam generator water inventory is controlled by operating the motor driven emergency feedwater pump, the start -up feedwater pump, and associated valves. Inventory for the emergency feedwater is from the condensate storage tank. Long term water capability exists using a temporary connection between the suction of the turbine driven emergency feed pump and the fire protection system but is not required to meet Appendix R requirement. This temporary connection back feeds to the CST which supplies water to the startup feedwater pump and the motor driven emergency feedwater pump. To assure main steam system integrity the MSIV 's and MSIV bypass valves are maintained closed. The MSIV bypass valves are normally locked closed and depowered with breakers locked open to preclude spurious opening. Decay heat transfer is made possible by natural convection flow in the RC system. Considering worst case scenarios for spurious actuation of affected equipment, the required times for operator actions regarding decay heat removal for safe shutdown from the main control room are provided below: Action Time Isolate the MSIVs Expeditiously following a reactor trip Place the mode selector switches for the ASDVs to the closed position Prompt Gain Control of excessive Emergency Feedwater Flow 20 minutes Start motor driven EFW pump or startup feedwater pump to preclude steam generator dry out - normal power operation 39 minutes Start motor driven EFW pump or startup feedwater pump to preclude steam generator dry out - low power operation 75 minutes Time to bypass the startup feed pump low suction trip 4 hours SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-6 Action Time Time allotted for operator actions to preclude emptying CO tank to accommodate RHR Cut -in, and ultimately achieve cold safe shutdown within 72 hours 9 hours; 4 hours at hot standby plus

5 hours cooldown to RHR Cut -in 3.2.2.4 Process Monitoring Instrumentation is provided at the main control room for monitoring the following process variables:

a. Steam generator emergency feedwater flow
b. Reactor coolant loop hot and cold leg temperatures
c. Steam generator wide

-range level

d. Steam generator pressure
e. Pressurizer level
f. Pressurizer pressure
g. Wide-range neutron monitoring (excore)
h. Primary component cooling water temperature
i. Boric acid tank level
j. Condensate storage tank level 3.2.2.5 Service Water The service water system will supply cooling water to the primary component cooling water system, diesel generators, and if required, fire protection system. Service water supply will be from the service water pumps taking suction from the tunnels to the ocean. If necessary, transfer to the cooling towers utilizing the cooling tower fans, cooling tower pumps and associated motor-operated transfer valves can be accomplished automatically on low service water pump discharge header pressure or manually from the main control room. If a manual transfer to the cooling tower is in effect and a loss of offsite power occurs, cooling tower operation automatically resumes upon restoration of electrical power.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-7 3.2.2.6 Primary Component Cooling Water (CC) The CC system is utilized to maintain cooling water to the charging pumps, RHR pumps, RHR heat exchangers, containment structure cooling units, containment enclosure cooling units and reactor coolant pumps (RCP) thermal barrier heat exchanger. The PCCW pumps, temperature control valves, RCP thermal barrier cooling pumps, and inboard and outboard containment isolation valves are necessary for system operations. 3.2.2.7 Sampling Sampling of the reactor coolant system is not required at hot standby and cold shutdown conditions since make -up during cool -down will only be provided to the RCS from the boric acid tanks (two) which are maintained at 4 wt% boric acid. During all phases of cooldown, the core will be maintained to the shutdown margin greater than or equal to the limit specified in the Core Operating Limits Report (COLR). 3.2.2.8 Diesel-Generator Building Air Handling (DAH) The DAH system is utilized to maintain long -term habitability and equipment protection for the diesel-generator rooms. The DAH system includes the fans and dampers for air handling in these areas. 3.2.2.9 Containment Enclosure Air Handling (EAH) The EAH system is utilized to maintain long -term habitability of the mechanical penetration area, and provides equipment cooling in the charging pump rooms, and the hydrogen analyzer and electrical room. The EAH system includes the coolers, fans, and dampers required for air handling in these areas. 3.2.2.10 Emergency Feedwater Pumphouse Air Handling (EPA) The EPA system is utilized to maintain long -term habitability and equipment protection in the emergency feedwater pump building. The EPA system includes the fans and dampers required for air handling in this area. 3.2.2.11 Primary Auxiliary Building Air Handling (PAH) Portions of the PAH system are utilized to maintain long -term habitability and equipment protection in the PCCW area of the primary auxiliary building. The PAH system includes the fans and dampers required for ventilation in this area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-8 3.2.2.12 Service Water Air Handling (SWA) Portions of the SWA system are utilized for equipment protection in the SW pump house electrical control rooms. The SWA system includes the fans and dampers required for air handling in these areas. 3.2.2.13 Electrical Distribution Emergency (EDE) Portions of the EDE system are required to power the various pumps, fans, valves, etc. required for Safe Shutdown. Included in the EDE system are the 4160 Volt ac emergency switchgear, 460 Volt ac emergency unit substations and motor control centers, the uninterruptible power supplies, the static transfer switches, 120 Volt ac vital distribution panels, 125 Volt dc batteries, battery chargers, and 125 Volt dc distribution panels. 3.2.2.14 Diesel-Generators (DG) The diesel -generators provide power to the emergency electrical distribution system upon loss of off-site power. The DG system includes the diesels, generators, control panels, engine -driven auxiliaries fuel oil transfer pumps, starting air compressors and backup operating air compressors. 3.2.2.15 Safeguard Actuation System The safeguard actuation system could be actuated, depending on the fire area. A portion of this system is used to deactivate the system for recovery. 3.2.2.16 Service Air (SA) and Instrument Air (IA) Portions of the SA and IA systems are required for air operated valves and dampers necessary for safe shutdown. 3.2.2.17 Control Building Air Handling (CBA) The CBA system is used to maintain Control Building habitability and equipment protection. The CBA system is comprised of a non -safety related chilled water system that can be aligned to either safety related air handling unit and two redundant safety related chilled water systems, which are aligned to their corresponding safety related air handling units. Each chilled water system includes its own packages chiller and circulating pumps. The air handling units include cooling coils (safety related and non -safety related), fans, dampers. Fires that could disable either safety related train of Control Room cooling are discussed in applicable fire area analysis.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-9 3.2.2.18 Communication The Gaitronics or radio systems are used to announce the fire event and dispatch the fire brigade. The Gaitronics system is also used to provide a fire alarm. For shutdown from the main control room (MCR), most of the operator actions are actually performed in the MCR where face -to-face communication would be used. When field actions are required, an operator would: a) be dispatched to take the required action, b) go to the field and take the action, and c) then return to the MCR and report the action completed. No other communication methods are credited for shutdown controlled from the main control room. Radios and Gaitronics are not credited but would be used as additional means of communication, if not damaged by the fire. 3.2.3 Safe Shutdown Function for Cooldown The following equipment in addition to that which is listed in Section 3.2.2 is necessary for cooldown. 3.2.3.1 Decay Heat Removal In addition to equipment discussed in Section 3.2.2.3, the steam generator atmospheric relief valves will be used for cooldown until the residual heat removal (RH) system can be used. The residual heat removal system will be the long term heat sink at the end of cooldown. An RH pump will be operated along with various control, manual and motor operated valves. Also, the startup feedpump low suction pressure trip must also be bypassed prior to commencing cooldown. 3.2.3.2 Containment Building Air Handling (CAH) The CAH system is utilized to maintain habitability of containment for manual operation of the RHR and SI isolation valves. The CAH system includes six containment cooling units and their associated fans. 3.2.3.3 Sample System For cold shutdown, the operator will draw a manual sample from RH system to verify boron concentration before line -up to RCS. The operator will use manual valves in RH system.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-10 3.2.4 Manual Operator Actions The following equipment may require manual operation outside the MCR.

a. Control Building dampers CBA

-DP-24A, CBA-DP-24B, CBA-DP-24C, CBA-DP-24D, CBA-DP-24E, CBA-DP-24F, CBA-DP-52, CBA-DP-26A, CBA-DP-26B. b. Switchgear room fans CBA -FN-19, CBA-FN-20, CBA-FN-32 and CBA -FN-33. c. Component cooling water valves CC -V122, CC-V168, CC-V175, CC-V257 and CC-V272 d. CVC tank isolation valves CS -LCV-112B and CS -LCV-112C (RSS Panels).

e. RWST suction to charging pump valves CS

-LCV-112D and CS -LCV-112E (RSS panel) f. Charging pumps discharge and bypass valves CS -V210, CS-V219, CS-V220 and CS-V221. g. Boric acid tank level CS -LT-7464 (RSS panel)

h. Boric acid tank valves CS

-V410, CS-V416, CS-V423, CS-V426, CS-V431, CS-V437, CS-V439, CS-V442 and CS -V1207 i. Diesel generators DG -DG-1A and DG -DG-1B (DG panels)

j. RHR inlet isolation valves RC

-V22, RC-V23, RC-V87 and RC -V88 k. RHR sampling valves RH -V8 and RH -V44 l. RH heat exchanger to CS/SI pump isolation valves RH -V35 and RH -V36 m. Instrument air cross connect valves IA -V50 and IA -V530. n. Safety injection accumulator isolation valves SI -V3, SI-V32 o. PAB fans PAH-FN-42A and PAH -FN-42B (RSS panels)

p. Control building doors C119, C300, C310, C311 and C312.
q. Start-up feedpump low suction pressure trip bypass switch (FW

-CS-4233). r. Realign the suction of the start -up feedpump (CO -V-142). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-11 s. Realign the power supply of the start -up feedpump from Bus ED -SWG-4 to Bus EDE-SWG-5 (if not already aligned to Bus EDE-SWG-5). t. Not used Equipment CBA -DP-24D, CBA-DP-24E, CBA-DP-24F, CS-V210, CS-V219, CS-V220, CS-V221, CS-V410, CS-V416, CS-V423, CS-V431, CS-V437, CS-V439, CS-V442, CS-V1207, CO-V142, IA-V50, RH-V8 and RH -V44 are not electrically operated; hence, they have no cables. Electrical operation of IA -V530 is not credited so its cables are not analyzed. 3.2.5 Disabled (tripped power supply) Equipment The following equipment may require disabling:

a. Primary component cooling valves CC

-V1092, CC -V1095, CC -V1101 and CC-V1109 b. Chemical and volume control valves CS -FCV-110A, -111A, -110B, -111B CS-V154, CS-V158, CS-V162, CS-V166, CS-V175, CS-V176, CS-V196 and CS-V197 c. Not used.

d. Emergency buses EDE

-SWG-5 and EDE -SWG-6 (control power)

e. Emergency Feedwater Control Valves FW

-FV-4214A,B; FW -FV-4224A,B, FW-FV-4234A,B and FW -FV-4244A,B f. Atmospheric relief valves MS -PV-3001, MS-PV-3002, MS-PV-3003 and MS-PV-3004 g. Not used.

h. Reactor coolant valves RC

-V122, RC-V124, RC-V323, RC-FV-2881, RC-LCV-459*, RC-LCV-460*, RC-PCV-456A and RC -PCV-456B i. Pressurizer heaters Group C, Group D and Control Group

j. Reactor coolant pumps RC

-P-1A, RC-P-1B, RC-P-1C, RC-P-1D k. Residual heat removal valves RH -V14, RH-V26, RH-V32, RH-V35, RH-V36, RH-V70, RH-HCV-607* and RH -FCV-619* l. Safety injection valves SI -V158 and SI -V159 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-12 m. Service water valves SW -V15, SW-V16*, SW-V18*, SW-V19, SW-V20, SW-V23, SW-V25, SW-V34 and SW -V54 n. Engineered safety features actuation system logic cabinets

o. Service water pump permissive logics Those valves noted with an asterisk (*) fail to their safe shutdown position upon de

-energization. 3.2.6 Safe Shutdown Equipment List Tables that list all equipment, including instrumentation and vital support systems equipment, required to achieve hot standby or cold shutdown from the main control room are provided in Appendix III. However, analysis can be also provided to justify not listing components and cables in Appendix III. The tables provide the following information for each equipment listed:

a. A column which notes whether the equipment is required for hot standby or cold shutdown.
b. A column which defines each equipment

's location by fire zone/area.

c. A column which defines each equipment

's redundant counterpart.

d. A column which lists each equipment

's essential cabling. For each cable 's routing by fire zone/area see computer report, "Cables with Associated Fire Zones " (Main Control Room Safe Shut -down). e. The table also delineates the following additional information:

1) P & I Diagram Drawing No.
2) Physical Location Drawing No.
3) Power Supply
4) Electrical Node Number
5) Supporting Control and Instrumentation Equipment
6) Electrical Schematic Drawing No.
7) Electrical Cable Schematic Drawing No.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-13 8) Supporting Systems

9) Remarks Separate tables are furnished for each of the safe shutdown functions. In several instances a safe shutdown function requires components from several systems to perform its safe shutdown function.

In order to simplify the tabulation, the following are not listed: manual valves in the process flow path; mechanical check valves which provide a safe shutdown system boundary; normally closed manual valves which provide a safe shutdown system boundary; mechanical relief valves; and root valves on small instrument lines. The review of these valves is documented by the marked P & I Diagrams. Tables are provided for the following functions which satisfy the performance goals stated in Appendix R, Paragraph III.L.2. Function Table No. Decay Heat Removal 3.1.3.1 Reactor Coolant Inventory and Pressure Control 3.1.3.2 Reactivity Control 3.1.3.3 Process Monitoring 3.1.3.4 Safeguard Actuation System 3.1.3.5 Cold Shutdown 3.1.3.6 Service Water 3.1.3.7 Primary Component Cooling Water 3.1.3.8 Containment Building Air Handling 3.1.3.9 Control Building Air Handling 3.1.3.10 Diesel Generator Building Air Handling 3.1.3.11 Containment Enclosure Air Handling 3.1.3.12 Emergency Feedwater Pumphouse Air Handling 3.1.3.13 Primary Auxiliary Building Air Handling 3.1.3.14 Service Water Air Handling 3.1.3.15 Service/Instrument Air 3.1.3.16 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-14 Function Table No. Electrical Distribution Emergency 3.1.3.17 Diesel Generators 3.1.3.18 3.2.7 Analysis and Evaluation of Fire Areas Provided on the following pages is a tabulation of the safe shutdown equipment and safe shutdown cabling contained in a fire area. The Train A and Train B redundant equipment are depicted, and an "X" is shown in the tabulation if equipment and/or cables are located in the fire area. If redundant trains of equipment are affected by a fire in the area, an analysis is provided on an area, equipment or system basis for the effects of a fire in this area. An evaluation is provided as to whether the Appendix R requirements or safe shutdown requirements are satisfied. If a deviation from Appendix R requirements exists, this deviation is justified by analysis. The following fire areas and associated fire zones have been considered in this review: Building Fire Area Fire Zones Tabulation Containment C-F-1-Z, C-F-2-Z, C-F-3-Z 3.2.7.1 Control Building -El. 21'-6" CB-F-1A-A - 3.2.7.2 Control Building -El. 21'-6" CB-F-1B-A - 3.2.7.3 Control Building -El. 21'-6" CB-F-1D-A - 3.2.7.4 Control Building -El. 21'-6" CB-F-1E-A - 3.2.7.5 Control Building -El. 21'-6" CB-F-1F-A - 3.2.7.6 Control Building -El. 21'-6" CB-F-1G-A - 3.2.7.7 Control Building -El. 50'-0" CB-F-2A-A - 3.2.7.8 Control Building -El. 50'-0" CB-F-2B-A - 3.2.7.9 Control Building -El. 50'-0" CB-F-2C-A - 3.2.7.10 Control Building -El. 75'-0" CB-F-3A-A - 3.2.7.11 Control Building -El. 75'-0" CB-F-3B-A - 3.2.7.12 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-15 Building Fire Area Fire Zones Tabulation Control Building -El. 75'-0" CB-F-3C-A - 3.2.7.13 Intentionally left blank 3.2.7.14 Control Building -Stairwell CB-F-S1 3.2.7.15 Control Building -Stairwell CB-F-S2 3.2.7.16 Containment Fan Encl. Area and Containment Annulus/ CE-F-l-Z, PP-F-1A-Z, PP-F-2A-Z, PP-F-3A-Z, 3.2.7.17 Mechanical Penetration Area PP-F-1B-Z, PP-F-2B-Z, PP-F-3B-Z, PP-F-4B-Z PP-F-5B-Z Condensate Storage Area CST-F-1-0 3.2.7.18 Intentionally left blank 3.2.7.19 Intentionally left blank 3.2.7.20 Cooling Tower -El. 22'-0" CT-F-1C-A 3.2.7.21 Cooling Tower -El. 22'-0" CT-F-1D-A 3.2.7.22 Intentionally left blank 3.2.7.23 Cooling Tower -El. 46'-0" CT-F-2B-A 3.2.7.24 Cooling Tower, Fans CT-F-3-0 3.2.7.25 Duct Bank -ET to SW DCT-F-1A 3.2.7.26 Duct Bank -ET to SW DCT-F-1B 3.2.7.27 Duct Bank -PAB to CT DCT-F-2A 3.2.7.28 Duct Bank -PAB to CT DCT-F-2B 3.2.7.29 Duct Bank -CB to PAB DCT-F-3B 3.2.7.30 Duct Bank -East MUA DCT-F-4A 3.2.7.31 Duct Bank -East MUA DCT-F-4B 3.2.7.32 Duct Bank -West MUA DCT-F-5A 3.2.7.33 Duct Bank -West MUA DCT-F-5B 3.2.7.34 Duct Bank -SWPH to CW DCT-F-6 3.2.7.35 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-16 Building Fire Area Fire Zones Tabulation Duct Bank -TB to CST DCT-F-7 3.2.7.36 Diesel Gen. Bldg. -El(-)16'-0" DG-F-1A-A - 3.2.7.37 Diesel Gen. Bldg. -El (-)16'-0" DG-F-1B-A - 3.2.7.38 Diesel Gen. Bldg. -El 21'-6" DG-F-2A-A - 3.2.7.39 Diesel Gen. Bldg. -El 21'-6" DG-F-2B-A - 3.2.7.40 Diesel Gen. Bldg. -El 51'-6" - DG-F-3A-Z DG-F-3B-Z 3.2.7.41 Diesel Gen. Bldg. -El 51'-6" DG-F-3C-A - 3.2.7.42 Diesel Gen. Bldg. -El 51'-6" DG-F-3D-A - 3.2.7.43 Diesel Gen. Bldg. -El 51'-6" DG-F-3E-A - 3.2.7.44 Diesel Gen. Bldg. -El 51'-6" DG-F-3F-A - 3.2.7.45 Diesel Gen. Bldg. -Stairwell DG-F-S1 3.2.7.46 Diesel Gen. Bldg. -Stairwell DG-F-S2 3.2.7.47 Emer. Feedwater Pump Bldg. EFP-F-1-A - 3.2.7.48 Electrical Tunnel ET-F-1A-A - 3.2.7.49 Electrical Tunnel ET-F-1B-A - 3.2.7.50 Electrical Tunnel ET-F-1C-A - 3.2.7.51 Electrical Tunnel ET-F-1D-A - 3.2.7.52 Electrical Tunnel Stairwell ET-F-S1 3.2.7.53 Fire Pump House FPH-F-1A-A - 3.2.7.54 Fire Pump House FPH-F-1B-A - 3.2.7.55 Fire Pump House FPH-F-1C-A - 3.2.7.56 Fuel Storage Bldg. -El 51'-6" FSB-F-1-A - 3.2.7.57 East Mainsteam & Feedwater Pipe Chase - MS-F-1A-Z MS-F-2A-Z MS-F-3A-Z MS-F-4A-Z MS-F-5A-Z 3.2.7.58 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-17 Building Fire Area Fire Zones Tabulation West Mainsteam & Feedwater Pipe Chase - MS-F-1B-Z MS-F-2B-Z MS-F-3B-Z 3.2.7.59 East Air Make -Up Pit MUA-F-1 3.2.7.60 Intentionally left blank

- - 3.2.7.61 Non-Essential Swgr. Room
- NES-F-1A-Z 3.2.7.62 Primary Auxiliary Building 

- El. 7'-0" - PAB-F-1A-Z PAB-F-1B-Z 3.2.7.63*

3.2.7.64* Primary Auxiliary Building - El. 7'-0" - PAB-F-1F-Z 3.2.7.65* Primary Auxiliary Building - El. 7'-0" - PAB-F-1J-Z 3.2.7.66* Primary Auxiliary Building - El. 7'-0" - PAB-F-1K-Z 3.2.7.67* Primary Auxiliary Building - El. 25'-0" - PAB-F-2A-Z 3.2.7.68* Primary Auxiliary Building - El. 25'-0" - PAB-F-2B-Z 3.2.7.69* Primary Auxiliary Building - El. 25'-0" - PAB-F-2C-Z 3.2.7.70* Primary Auxiliary Building - El. 53'-0" - PAB-F-3A-Z 3.2.7.71* Primary Auxiliary Building - El. 53'-0" - PAB-F-3B-Z 3.2.7.72* Primary Auxiliary Building - El. 81'-0" - PAB-F-4-Z 3.2.7.73* Primary Auxiliary Building - El. 7'-0" PAB-F-1C-A - 3.2.7.74 Primary Auxiliary Building - El. 7'-0" PAB-F-1D-A - 3.2.7.75 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-18 Building Fire Area Fire Zones Tabulation Primary Auxiliary Building - El. 7'-0" PAB-F-1E-A - 3.2.7.76 Primary Auxiliary Building - Electrical Chase PAB-F-1G-A - 3.2.7.77 Primary Auxiliary Building - Stairwell PAB-F-S1 3.2.7.78 Primary Auxiliary Building - Stairwell PAB-F-S2 3.2.7.79 Equipment Vault -Train B (Vault 2)

- RHR-F-1A-Z RHR-F-1C-Z RHR-F-2A-Z RHR-F-3A-Z RHR-F-4A-Z 3.2.7.80 Equipment Vault

-Train A (Vault 1)

- RHR-F-1B-Z RHR-F-1D-Z RHR-F-2B-Z RHR-F-3B-Z RHR-F-4B-Z 3.2.7.81 Circulating Water Pump House SW-F-1A-Z 3.2.7.82 Service Water Pump House SW-F-1B-A  3.2.7.83 Service Water Pump House SW-F-1C-A  3.2.7.84 Service Water Pump House SW-F-1D-A  3.2.7.85 Service Water Pump House SW-F-1E-Z 3.2.7.86 Intake & Discharge Structure SW-F-2-0  3.2.7.87 Turbine Building TB-F-1A-Z TB-F-1C-Z TB-F-2-Z TB-F-3-Z 3.2.7.88 Turbine Building TB-F-1B-A  3.2.7.89 Tank Farm TF-F-1-0 3.2.7.90 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-19   Building Fire Area Fire Zones Tabulation Waste Process Building W-F-1A-Z W-F-1B-Z W-F-1K-Z W-F-2A-Z W-F-2B-Z W-F-2C-Z W-F-2D-Z W-F-2E-Z 3.2.7.91
  • All primary auxiliary building fire zones containing safe shutdown equipment and/or cables have been combined into one fire area for analysis purposes.

Tabulation 3.2.7.1 Containment Fire Area: C-F-1-Z, C-F-2-Z, C-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CAH-AC-1C x CAH-AC-1A x CAH-FN-1C x x CAH-FN-1A x x CAH-AC-1E x CAH-AC-1B x CAH-FN-1E x x CAH-FN-1B x x CAH-AC-1F x CAH-AC-1D x CAH-FN-1F x x CAH-FN-1D x x CAH-JV3-43 x x CAH-JV7-43 x x CAH-JV4-43 x x CAH-JV8-43 x x CAH-JV5-43 x x CAH-JV6-43 x x CC-FISL-2124 x x CC-FISL-2122 x x CC-FISL-2223 x x CC-FISL-2123 x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-20 Containment Fire Area: C-F-1-Z, C-F-2-Z, C-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-FISL-2224 x x CC-FISL-2222 x x CC-LT-2172-1 x CC-LT-2192-1 x CC-LT-2172-2 x CC-LT-2192-2 x CC-LT-2172-3 x CC-LT-2192-3 x CC-LT-2272-1 x CC-LT-2292-1 x CC-LT-2272-2 x CC-LT-2292-2 x CC-LT-2272-3 x CC-LT-2292-3 x CC-E-153A x CC-E-153B x CC-P-322A x x CC-P-322B x x CC-V57 x x CC-V176 x x CC-V121 x x CC-V256 x x CC-FISHL-2147 x x CC-FISHL-2247 x x CC-FISHL-2248 x x CC-FISHL-2148 x x CC-V428 x CC-V439 x CC-V395 x CC-V438 x CC-TK-196 x CC-TK-196 x ED-JX2-42 x x ED-JX3-42 x x ED-MM-163H x x ED-MM-163E x x ED-PP-8B x x ED-X-16A x x IA-D-2A x x IA-D-2B x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-21 Containment Fire Area: C-F-1-Z, C-F-2-Z, C-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable IA-J97-42 x x IA-J98-42 x x SA-C-4A x x SA-C-4B x x SA-CP-134A x x SA-CP-134B x x CS-V10 x x CS-V168 x x CS-V28 x x CS-V44 x x CS-V59 x x CS-V177 x x CS-V185 x x CS-V175 x x CS-V176 x x CS-V145 x x RC-LCV-459 x x RC-LCV-460 x x RC-FV-2881 x x RC-V323 x x RC-E-10 x x RC-E-10 x x EDE-TBX-X47 x x EDE-TBX-X44 x x RC-E-11A x RC-E-11B x RC-E-11C x RC-E-11D x RC-P-1A x RC-P-1B x RC-P-1C x RC-P-1D x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-22 Containment Fire Area: C-F-1-Z, C-F-2-Z, C-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RC-PCV-456A x x RC-PCV-456B x x RC-V122 x x RC-V124 x x EDE-TBX-X56 x x EDE-TBX-X35 x x RC-TK-11 x RC-TK-11 x RC-V23 x x RC-V22 x x RC-V88 x x RC-V87 x x SI-V3 x x SI-FV-2475 x x SI-FV-2476 x x SI-V32 x x SI-FV-2477 x x SI-FV-2486 x x SI-FV-2482 x x SI-V17 x x SI-FV-2483 x x SI-FV-2495 x x SI-V47 x x SI-FV-2496 x x SI-V158 x x SI-V159 x x RH-V35 x RH-V36 x SB-V1 x x SB-V3 x x SB-V5 x x SB-V7 x x FW-LT-501 x x FW-LT-519 x x FW-LT-503 x x FW-LT-537 x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-23 Containment Fire Area: C-F-1-Z, C-F-2-Z, C-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-LT-529 x x FW-LT-502 x x FW-LT-548 x x FW-LT-504 x x NI-NE-6690 x x NI-NE-6691 x x EDE-TBX-XP8 x x EDE-TBX-XP9 x x RC-LT-459 x x RC-LT-460 x x RC-PT-455 x x RC-PT-456 x x RC-PT-457 x x RC-PT-458 x x RC-TE-413A x x IC-TE-XX x x RC-TE-423A x x RC-TE-433A x x RC-TE-443A x x IC-MM-173 x x EDE-TBX-X40 x x EDE-TBX-X48 x x EDE-TBX-X94 x x RC-TE-413B x x RC-TE-423B x x RC-TE-433B x x RC-TE-443B x x EDE-TBX-X14 x x EDE-TBX-X86 x x EDE-TBX-X52 x x EDE-TBX-X69 x x Electrical x x Electrical x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-24 Containment Fire Area: C-F-1-Z, C-F-2-Z, C-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable Penetrations Penetrations MM-IR-1 x x MM-IR-2 x x MM-IR-3 x x MM-IR-4 x x MM-IR-4 x x MM-IR-6 x x MM-IR-8 x x MM-IR-7A x x MM-IR-7A x x B. Analysis 1. General Area Analysis The following protective measures are inherent in the existing containment design:

a. The significant in situ combustibles are limited to the reactor coolant pump lubricating oil, hydraulic snubbers, cables in trays, and EPDM rubber (debris interceptor trim).
b. An oil collection system is provided for the reactor coolant pumps.
c. Each hydraulic snubber contains 3.5 gallons of a high flash point, high auto ignition point silicon

-based hydraulic fluid. The snubbers are designed to withstand an SSE without failure. Even if leaks were to develop, studies performed at Factory Mutual Research Corporation have shown that a heat flux of 16 kW/M2 is necessary to ignite a high flash point hydraulic fluid similar to the silicon based fluid. It would require the introduction of a transient combustible to containment to provide this heat flux.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-25 d. Containment is inaccessible during normal operation with the exception of operator tours. Because of this, transient combustibles are not considered as a fire hazard. This absence of transient combustibles removes the ignition source for the cables, the hydraulic fluid, and the EPDM rubber.

e. Prior to plant start

-up administrative controls will assure the removal of transient combustibles which could be brought into containment during plant shutdowns.

f. Charcoal filter CAH

-F-8 has an early fire detection system internal to the filter.

2. System Analysis
a. Containment Structure Cooling Units CAH

-AC-1A through 1F (Fans CAH-FN-1A through 1F, Speed Changers CAH -JV3-43 through CAH -JV8-43 and CC Flow Switches CC -FISL 2122 through CC -FISL-2224) Cables for the redundant cooling unit fans, speed changers and flow switches are routed through trays and conduits from the penetration where they enter containment to the cooling units. The trays are separated by concrete floors except between Columns 2 and 4, Columns 5 and 6, Columns 7 and 8, Columns 12 and 13, Columns 14 and 15, and Columns 17 and 18 where there is grating. Between Columns 2 and 4, the Train B trays are a minimum of 12 ' above floor elevation ( -) 26'-0" and a maximum of 19 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 11 ' above the grating elevation 0 '-0". There is a minimum of 18 ' of vertical separation between the redundant trays. Even if the redundant trays are affected by a fire, only two Train B and one Train A cooling unit could be affected, the other three cooling units would continue to be operable. Between Columns 5 and 6, the Train B trays are a minimum of 14' above floor elevation ( -) 26'-0" and a maximum of 19 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 18 ' above the grating elevation 0 '-0". There is a minimum of 24 ' of vertical separation between the redundant trays. Even if the redundant trays were affected by a fire, only one Train A and one Train B cooling units could be affected; the other four cooling units would continue to be operable. Between Columns 7 and 8, only one Train A cooling units ' cables are routed. There are no Train B cooling units ' cables at this location.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-26 Between Columns 12 and 13, only one Train A and one Train B cooling units ' cables are routed. The other four cooling units would continue to be operable. Between Columns 14 and 15, the Train B trays are a minimum of 19 ' above floor elevation ( -) 26'-0" and a maximum of 21 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 17 ' above the grating elevation 0 '-0". There is a minimum of 22 ' of vertical separation between the redundant trays. Even if the redundant trays were affected by a fire, the only two Train A and one Train B cooling unit could be affected. The other three cooling units would continue to be operable. Between Columns 17 and 18, the Train B trays are a minimum of 12 ' above floor elevation ( -) 26'-0" and a maximum of 19 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 11 ' above the grating elevation 0 '-0". There is a minimum of 18 ' of vertical separation between the redundant trays. Even if the redundant trays were affected by a fire, only two Train A and one Train B cooling units could be affected; the other three cooling units would continue to be operable. A maximum of three containment structure cooling units (CAH) are needed to maintain habitability of the containment. This can be any combination of Train A and B units. At all points discussed above where Train A and B cables are run near each other without concrete floor separation, there is a minimum of 18 ' of vertical separation, with the Train B cables a minimum of 12 ' off the floor. This vertical separation, the height of the cable from the floor and the lack of combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. Additionally, a fire at any of these points would affect a maximum of three out of six units, leaving three to cool containment.

b. Thermal Barrier Pumps CC

-P-322A and CC -P-322B Cables for the redundant thermal barrier pumps are routed through trays and conduits from the penetration where they enter containment to the pumps at elevation ( -) 26'-0". The trays are separated by concrete floors except between Columns 17 and 18 where there is a grating. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-27 Between Columns 17 and 18, the Train B trays are a minimum of 12 ' above floor elevation ( -) 26'-0" and a maximum of 19 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 11 ' above the grating elevation 0 '-0". There is a minimum of 18 ' of vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in trays. The conduit to the Train A pump is routed such that there is a minimum of 6 ' horizontal separation from the Train B tray that contains the redundant cable. The conduit is run approximately 22 ' above elevation ( -) 26'-0" to the point that it drops down to the Train A pump. The pump is located 6 ' above elevation (-) 26'-0" between Columns 17 and 18. The Train A pump is separated from the tray containing the cable to the Train B pump by a horizontal distance of 6 ' and a vertical distance of 9 '. In addition there are two totally enclosed instrument trays below the Train B tray. Should the thermal barrier cooling be unavailable, the redundant seal injection cooling capability located in other plant fire areas will satisfy the safe shutdown requirements. The separation height of cable from the floor and lack of in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. The redundant seal cooling satisfies the safe shutdown requirements.

c. Component Cooling Isolation Valves CC

-V57, CC-121, CC-V176, CC-V256 Cables for the redundant valves are routed through trays and conduits from the penetration where they enter containment to the valves on the west side of containment at elevation 4 '-0". The trays are separated by a concrete floor, except between Columns 17 and 18 and between Columns 14 and 15 where there is grating. Between Columns 17 and 18, the Train B trays are a minimum of 12 ' above floor elevation ( -) 26'-0" and a maximum of 19 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 11 ' above the grating elevation 0 '-0". There is a minimum of 18 ' of vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the trays.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-28 Between Columns 14 and 15, the Train B trays are a minimum of 19 ' above floor elevation ( -) 26'-0" and a maximum of 21 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 17 ' above the grating elevation 0 '-0". There is a minimum of 22 ' of vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the trays. The Train A valves CC -V57 and CC -V121 are located between Columns 14 and 15 approximately 4 ' above the grating elevation 0 '-0". The cables for the Train B valves CC -V176 and CC -V256 are routed in trays which are a minimum of 19 ' above floor elevation ( -) 26'-0". There is a minimum of 8 ' vertical separation between the Train B trays and the Train A valves. The only in situ combustibles at this location are the cables in the trays. The Train B valves CC -V176 and CC -V256 are located between Columns 12 and 13 approximately 4 ' above the grating elevation 0 '-0". Although the cables for the redundant Train A valves are not in this location, the power cables for Train A containment structure cooling unit CAH -AC-1E are routed in this area such that a fire could impact four of the six cooling units. However, the cables are routed in tray 19' above the grating elevation 0 '-0" and then in conduit to the cooling unit. There is a vertical separation of approximately 15 ' between valves CC -V176 and CC-V256 and the Train A trays. The only in situ combustibles at this location are the cables in the tray. One set of redundant valves is needed to provide component cooling water to one train of containment structure cooling units. Between Columns 17 and 18, the vertical separation is 18 ' with the lower cables 12' off the floor. The separation and height of cable from the floor provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. Between Columns 14 and 15, there is a vertical separation of 27 ', with the lower cables 19 ' off the floor. There is a minimum separation of 8 ' between the Train A valves and the Train B cables, with the Train B cables 19 ' off the floor. The separation, height of cable from the floor and lack of in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-29 Between Columns 12 and 13, there is a vertical separation of 15 ' between the Train B valves and the Train A cable. The valves are 30 ' off the floor (Elevation (-) 26'-0"). The separation, height of the valves off the floor and lack of in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. d. Component Cooling Head Tank Level Transmitters CC -LT-2172-1, 2, 3, CC-LT-2272-1, 2, 3, CC -LT-2192-1, 2, 3, CC -LT-2292-1, 2, 3 and Associated Flow Switches CC -FISHL-2147, CC-FISHL-2248, CC-FISHL-2247, CC-FISHL-2148 Cables associated with CC heat tank level transmitters which affect the Loop B outboard isolation valves CC -V175 and CC -V257 are routed in the same trays as the Loop A inboard isolation valves CC -V57 and CC -V121. Failures in these cables could cause total loss of PCCW to containment by initiation of a spurious

lo-lo head tank level signal. Loop B PCCW can be re -established by transferring control of valves CC -V175 and CC-V257 to local control at the RSS panel in fire area CB-F-1A-A. This removes the lo -lo head tank level isolation function and allows operators to re -open the valves. Cables associated with CC head tank level transmitters which affect the Loop A

outboard isolation valves CC -V122 and CC -V168 are routed in proximity to trays containing cables for the Loop B inboard isolation valves CC -V176 and CC-V256. Failures in these cables could cause total loss of PCCW to containment by initiation of a spurious l o-lo head tank level signal. Loop A PCCW can be re -established by transferring control of valves CC -V122 and CC-V168 to local control at the RSS panel in fire area CB -F-1B-A. This removes the lo-lo head tank level isolation function and allows operators to re-open the valves. The provision of a capability to isolate the affected portion of the circuit and

re-position the valves from another fire area satisfies the safe shutdown requirements.

e. Thermal Barrier Isolation Valves CC

-V395, CC-V428, CC-V438, CC-V439 Valves CC -V395, CC-V428, CC-V438 and CC -V439 are normally open valves which must remain open for safe shutdown. The valves are permanently disabled in the open position. The disabling of the above valves satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-30 f. Air Compressors and Dryers SA -C-4A, SA-C-4B, IA-D-2A, IA-D-2B and Associated Distribution Panels, Control Panels and Contactors The air compressors and their associated dryers located at elevation 0 '-0" are required only for instrument air to the primary component cooling water containment isolation valves. These valves are required to remain operable only for containment entry when manual operation of the safety injection accumulator isolation valves SI -V3, SI-V17, SI-V32, and SI -V47 and RHR inlet isolation valves RC -V22, RC-V23, RC-V87 and RC -V88 is required. The redundant air compressors and dryers are within 4 ' of one another. The Train B cables are routed in conduit from the compressors through the floor to the Train B trays. The Train B cable is routed in conduit from the air dryer to the power panel. The only in situ combustibles at this location are the cables in trays. A cross connection to the plant instrument air system is provided to back up the containment instrument air system in the event of a compressor failure. Containment isolation is provided by an air operated, fail closed valve (outboard) and a check valve (inboard). The outboard valve is operable from the Main Control Board. The cross connection is not relied upon to achieve hot/cold shutdown for containment fires and is only described here due to its potential use as a backup. The cable and control circuits are not considered Appendix R equipment and are, therefore, not listed in the respective tables. The Train A cables to valves SI -V3 and RC -V88 are routed in power and control trays a minimum of 17 ' above floor elevation 0 '-0" in the vicinity of the Train B air compressor and dryer. The trays are effectively shielded from the compressor and dryer by a 5 ' wide by 3 ' high steel ventilation duct located 8 ' above the floor between the compressor/dryer and the trays. Should the cables to valve SI-V3 fail, the accumulator can be vented by use of Train B valves SI -FV-2475 and SI-FV-2476. Further discussion of the separation between these cables is provided in Paragraph "n". Failure of the cables to RC -V88 will not prevent safe shutdown as functionally redundant valve RC -V23 will still be operable. The Train A cables to valve RC -V23 are routed in tray and conduit a minimum of 20' horizontal from the Train B air compressors and dryers and are separated by a concrete floor when they are in proximity to the equipment. The Train B cables to valves SI -V47, RC-V22 and RC -V87 are routed in trays which are separated from the Train A air compressor and dryer by a concrete floor. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-31 The cables to Train A Valve SI -V32 and Train B valve SI -V17 are routed on the opposite side of containment from the air compressors. The separation distance, radiant shielding provided by ventilation duct and lack of in situ combustibles between the air compressors/dryers and the cabling for the valves that must remain operable should the redundant compressors/dryers be damaged due to a fire provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. g. RC Pump Seal Water Isolation Valves CS -V10, CS-V28, CS-V44, CS-V59, CS-V168, and CS - Charging to RC Isolation Valves CS -V177, CS-V185 Valve CS-V168 is a normally open valve which should remain open for safe shutdown. Spurious isolation of the Train B valve CS -V168 could result in loss of RC inventory through the upstream relief valve, if CS -V10, CS-V28, CS-V44 and CS-V59 cannot be closed. This inventory is directed to the PRT and is therefore, non -recoverable. However, the postulated flow rate (12 gpm) coupled with the RCS volume shrink over the cooldown period to 350F (approximately 5 hours) is within the capabilities of the boric acid tanks. Cooldown below 350F to cold shutdown can be accomplished using the RWST. Shutdown margin is assured in all phases of this cooldown. The safe shutdown requirements are satisfied.

h. Letdown Isolation Valves CS

-V175, CS-V176, CS-V145, RC-LCV-459, RC-LCV-460 1) Excess Letdown Line Functionally redundant Train B series valves CS -V175 and CS -V176 are normally closed and remain closed for safe shutdown. The spurious opening of one valve will not prevent safe shutdown. The operators will prevent further spurious operation by tripping the power supply breakers for CS -V175 and CS -V176 at the Train B switchgear room (Fire Area: CB -F-1B-A). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-32 2) Normal Letdown Line Functionally redundant Train A series valves CS -V145, RC-LCV-459 and RC-LCV-460 are normally open and are required to close for safe shutdown. CS -V145 can be closed from the main control room. Should this valve not close due to spurious operation, the operators can close either RC -LCV-459 or RC -LCV-460 by tripping their power supply breakers at the Train A switchgear room (Fire Area: CB -F-1A-A). This will prevent further spurious operation. The capability to isolate the letdown flow paths and mitigate spurious operations from outside the fire area satisfies the safe shutdown requirements.

i. Charging Pump Test Line Isolation Valves SI

-158, SI-159 On spurious operation of either of the normally closed, fail closed valves SI -V158 (Train B) or SI-V159 (Train A), the operators will isolate the high head injection path by closing SI -V138 and SI -V139. Charging will then be accomplished utilizing the seal injection path through valves CS -V154, CS-V158, CS-V162 and CS-V166 located in Fire Zones PP -F-1A-Z and PP-F-5B-Z. The operators can close SI-V158 and SI -V159 by tripping their power supply breakers in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The capability to provide charging to the RC System through a minimum of one flow path satisfies the safe shutdown requirements.

j. Head Vent Valves RC

-FV-2881 and RC -V323 Functionally redundant Train B series valves RC -FV-2881 and RC -V323 are normally closed and remain closed for safe shutdown. The spurious opening of one valve will not prevent safe shutdown. The operators will prevent further spurious operation by tripping the power supply breakers for RC -FV-2881 and RC-V323 at the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-33 k. Pressurizer Heaters RC -E-10 and Terminal Boxes EDE -TBX-X44, EDE-TBX-X47 Cables for the redundant pressurizer heaters are routed through trays from the penetration where they enter containment to the heaters at the pressurizer. The trays are separated by concrete floors and walls from the penetration to a point 20 ' from the pressurizer except between Columns 2 and 3 where there is grating. Between Columns 2 and 3, the Train B cables are routed in trays which are a minimum of 10 ' above floor elevation ( -) 26'-0". The Train A cables are routed in trays a minimum of 18 ' above the grating elevation 0 '-0". There is a minimum of 25' vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the trays. In the area near the entrance to the pressurizer cubicle, the Train B trays are 12 ' above floor Elevation ( -) 26'-0. There is a spatial separation of approximately 6 ' between the redundant trays. The only in situ combustibles at this location are the cables in the trays. The Train A trays are 8 '-4" above the floor and the Train B trays are 18 '-6" above the floor at the entrance of the pressurizer cubicle. This is a vertical separation between redundant trays of over 8 '. Inside the cubicle, the cables are routed in enclosed wireways up to the point where they are routed to the individual pressurizer heater connections. The heaters are located over 20 ' above the floor. There are no in situ combustibles in the pressurizer heater cubicle. The containment is a controlled entry area and the fire loading is very low. The use of transient combustibles is strictly controlled. Where the grating exists, the cables of interest are separated vertically by 25 ' minimum. The lower set of cables are at least 10, off the floor. This separation and the height of the cable from the floor provide acceptable fire protection and provide protection equivalent to the technical requirement of Appendix R. At the area near the entrance to the pressurizer cubicle, there is a spatial separation of 6' between the cables of interest. There are no in situ combustibles. Access to this area is extremely limited during power operation. The separation, lack of combustibles and limited access provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-34 At the entrance to the pressurizer and inside, the case is the same, with the additional factor being the routing of the cables in enclosed wireways up to the point where they are routed to the individual pressurizer heater conditions. The separation, lack of combustibles, limited access and routing of the cables in wireways provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. l. Pressurizer Relief Valves, RC-PCV-456A, RC-PCV-456B, RC-V122 and RC-V124 Cables for the pressurizer relief valves are routed in trays and conduits from the penetration where they enter containment to the valves on the top of the pressurizer. The trays are separated by a concrete floor except between Columns 2 and 4; between Columns 5 and 6; and between Columns 7 and 8 where there is grating. Between Columns 2 and 4, the Train B cables are routed in trays which are a minimum of 10 ' above floor Elevation ( -) 26'-0". Other trays containing Train B cables are located up to 16 ' above floor Elevation ( -) 26'-0". The Train A cables are routed in trays a minimum of 18 ' above the grating Elevation 0 '-0". There is a minimum of 25 ' vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the trays. Between Columns 5 and 6, the Train B trays are a minimum of 14 ' above floor Elevation ( -) 26'-0" and a maximum of 19 ' above floor Elevation ( -) 26'-0". The Train A trays are a minimum of 18 ' above the grating Elevation 0 '-0". There is a minimum of 24 ' vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in trays; three pints of oil in 15 HP RC drain tank pump motor contributing 56,250 Btu fire load; and five pounds of grease in 3 HP containment sump pump motors contributing 90,000 Btu fire load. Between Columns 7 and 8, the Train B trays are a minimum of 13 ' above floor Elevation ( -) 26'-0" and a maximum of 19 ' above floor Elevation (-) 26'-0". The Train A trays are a minimum of 16 ' above the grating Elevation 0 '-0". There is a minimum of 23 ' of vertical separation between the redundant trays. The only situ combustibles at this location are the cables in trays.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-35 At the pressurizer, the cables are routed in conduit on opposite outside walls of the pressurizer enclosure with a minimum horizontal separation of approximately

15'. The Train A cables are routed in the area of reactor coolant pump C. Near the top of the pressurizer, the conduits enter the pressurizer cubicle and are routed on opposite sides of the cubicle over to the valves. The redundant valves are separated by 2 ' on the top of the pressurizer. There are no in situ combustibles at the top of the pressurizer. Between Columns 2 and 4 and 7 and 8, there is a minimum vertical separation of 23' between Train A and B cables. The Train B cables area minimum of 10 ' off the floor. The separation, height off the floor and lack of in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. Between Columns 5 and 6, there is a vertical separation of 25 ' with the lower cables 14 ' off the floor. The combustibles are in two motors. The separation, height off the floor, and the enclosure of combustibles in the motors provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. At the pressurizer, the cables are routed in conduit on opposite sides of the pressurizer cubicle. At the top of the pressurizer where the valves are located, there is no access during operation and there are no in situ combustibles. Adequate fire protection is provided and provides protection equivalent to the technical requirements of Appendix R. RC-PCV-456A is a normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an over -cooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an

unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V122. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV and the block valve by tripping their power supplies in the Train A switchgear room (Fire Area:

CB-F-1A-A). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-36 RC-PCV-456B is normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an over -cooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V124. For all fires, that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under this condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV and the block valve by tripping their power supplies in the Train B switchgear room (Fire area:

CB-F-1B-A). m. RHR Isolation Valves RC -V22, RC-V23, RC-V87, RC-V88 RHR isolation valves are permanently disabled in the closed position. Redundant valves RC -V23 and RC -V88 are separated by 25 ' with no intervening combustibles other than cables in trays. Redundant valves RC -V22 and RC -V87 are separated by 3 '. These valves are not needed until 9 hours into the event and are only required to be opened for cold shutdown. This can be accomplished manually, if required. Therefore, no fire protection other than the existing separation is needed. Protection equivalent to the technical requirements of Appendix R is provided.

n. Accumulator Tank Outlet Isolation Valve SI

-V3 and Vent Valves SI -FV-2475, SI-FV-2476 Cables for the redundant valves are routed through trays and conduits from the penetration where they enter containment to the valves. The trays are separated by concrete floor except between Columns 17 and 18 where there is grating. The Train A valve SI -V3 is located near column 17 at Elevation ( -) 26'-0" and the Train B, valves SI -FV-2475 and SI -FV-2476 are located near column 16 at Elevation 0'-0". The accumulator isolation valve is separated from its redundant vent valves by approximately 20 ' horizontal with an intervening concrete floor.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-37 At Elevation ( -) 26'-0" the cables to the redundant valves are in proximity such that a fire could affect operation of both trains of equipment. However, the same fire will not prevent the operation of the Train A equipment necessary for containment habitability. These valves are not required to reach or maintain hot standby. They are required to be closed before going to cold shutdown. These valves will be manually closed, if required, prior to decreasing reactor pressure below 600 psig. Prior to this time the accumulators are prevented from injection by reactor pressure acting against a check valve. Manual operation of the isolation valve is only necessary if both the valve circuit and the redundant vent valves are rendered inoperable by the fire. This manual operation can be delayed as much as 9 hours into the event. At Elevation 0 '-0" the cables to the redundant valves are in proximity such that a fire could affect operation of both trains of equipment. Additionally, the redundant air compressors/dryers necessary for containment habitability are in the same area. As discussed above, the valves are not required for 9 hours. To assure that one train of valves can be operated from the MCR or locally, a radiant energy shield is provided around the Train B vent valves and their related cables in the area of the air compressors. The horizontal separation distance between the redundant valves provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. The provision of a capability to manually operate the accumulator isolation valve satisfies the safe shutdown requirements.

o. Accumulator Tank Outlet Isolation Valve SI

-V32 and Vent Valves SI -FV-2477, SI-FV-2486 Cables for redundant valves are routed through trays and conduits from the penetration where they enter containment to the valves. The trays are separated by concrete floors except between Columns 2 and 4; between Columns 5 and 6 and between Columns 7 and 8 where there is grating. Between Columns 2 and 4, the Train B cables are routed in trays which are a minimum of 10 ' above floor Elevation ( -) 26'-0". Other trays containing Train B cables are located up to 16 ' above floor Elevation ( -) 26'-0". The Train A cables are routed in trays a minimum of 18 ' above the grating Elevation 0 '-0". There is a minimum of 25 ' vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the trays.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-38 Between Columns 5 and 6, the Train B trays are a minimum of 14 ' above floor Elevation ( -) 26'-0" and a maximum of 19 ' above floor Elevation ( -) 26'-0". The Train A trays are a minimum of 18 ' above the grating Elevation 0 '-0". There is a minimum of 24 ' of vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in trays; three pints of oil in 15 HP RC drain tank pump motor contributing 56, 250 Btu fire load; and five pounds of grease in 3 HP containment sump pump motors contributing 90,000 Btu fire load. Between Columns 7 and 8, the Train B trays are a minimum of 13 ' above floor Elevation ( -) 26'-0" and a maximum of 19 ' above floor Elevation ( -) 26'-0". The Train A trays are a minimum of 16 ' above the grating Elevation 0 '-0". There is a minimum of 23 ' of vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in trays. The Train A Valve SI -V32 is located near column 8 at Elevation ( -) 26'-0" and the Train B valves SI -FV-2477 and SI -FV-2486 are located near column 7 at Elevation 0 '-0". The accumulator isolation valve is separated from its redundant vent valves by approximately 20 ' horizontal with an intervening concrete floor. Between Columns 7 and 8 at Elevation ( -) 26'-0" the cables are in proximity such that a fire could affect operation of both trains of equipment. However, the same fire will not prevent operation of the Train A or Train B equipment necessary for containment habitability. These valves are not required to reach or maintain hot standby. They are required to be closed before going to cold shutdown. These valves will be manually closed, if required, prior to decreasing reactor pressure below 600 psig. Prior to this time the accumulators are prevented from injection by reactor pressure acting against a check valve. Manual operation of the isolation valve is only necessary if both the valve circuit and the redundant vent valves are rendered inoperable by the fire. This manual operation can be delayed as much as 9 hours into the event. Between Columns 2 and 4 and 7 and 8, there is a minimum vertical separation of 23' between Train A and B cables. The Train B cables are a minimum of 10 ' off the floor. The separation, height off the floor and lack of in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-39 Between Columns 5 and 6, there is a vertical separation of 25 ' with the lower cables 14 ' off the floor. The combustibles are in two motors. The separation, height off the floor, and the enclosure of combustibles in the motors provide acceptable fire protection and provides protection equivalent to the technical requirements of Appendix R. At the valves, the horizontal separation between the redundant valves provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. The provision of a capability to manually operate the accumulator isolation valve satisfies the safe shutdown requirements.

p. Accumulator Tank Outlet Isolation Valve SI

-V17 and Vent Valves SI -FV-2482, SI-FV-2483 Cables for the redundant valves are routed through trays and conduits from the penetration where they enter containment to the valves. The trays are separated by concrete floors except between Columns 2 and 4. Between Columns 2 and 4, the Train B cables are routed in trays which are a minimum of 10 ' above floor Elevation ( -) 26'-0. Other trays containing Train B cables are located up to 16 ' above floor Elevation ( -) 26'-0". The Train A cables are routed in trays a minimum of 18 ' above the grating Elevati on 0'-0". There is a minimum of 25 ' vertical separation between the redundant trays. The only in situ combustible at this location are the cables in the trays. The Train B valve SI -V17 is located near column 3 at Elevation ( -) 26'-0" and the Train A valves SI-FV-2482 and SI -FV-2483 are located near column 4 at Elevation 0 '-0". The accumulator isolation valve is separated from its redundant vent valves by approximately 20 ' horizontal separation with an intervening concrete floor. Between Columns 2 and 4 there is a minimum vertical separation of 25 ' between Train A and B cables. The Train B cables are a minimum of 10 ' off the floor. The separation, height off the floor and lack of in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. At the valves, the horizontal separation between the redundant valves and the intervening concrete floor provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-40 q. Accumulator Tank Outlet Isolation Valve SI -V47 and Vent Valves SI -FV-2495 and SI-FV-2496 Cables for the redundant valves are routed through trays and conduits from the penetrations where they enter containment to the valves. The trays are separated by concrete floor except between Columns 17, and 18, between Columns 14 and 15 and between Columns 12 and 13. Between Columns 17 and 18, the Train B trays are a minimum of 12 ' above floor elevation ( -) 26'-0" and a maximum of 19 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 11 ' above the grating elevation 0 '-0". There is a minimum of 18 ' of vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the tray

s. Between Columns 14 and 15, the Train B trays are a minimum of 19

' above floor elevation ( -) 26'-0" and a maximum of 21 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 17 ' above the grating elevation 0 '-0". There is a minimum of 22' of vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the trays. Between Columns 12 and 13, the Train B cables are routed in trays which are a minimum of 20 ' above floor Elevation ( -) 26'-0". The Train A cables are routed in tray and conduit a minimum of 19 ' above the grating Elevation 0 '-0". There is a minimum of 20 ' vertical separation between the redundant cables. The only in situ combustible at this location are the cables in the trays. The Train B valve SI -V47 is located near column 12 at Elevation ( -) 26'-0" and the Train A valves SI -FV-2495 and SI -FV-2496 are located near column 13 at Elevation 0 '-0". The accumulator isolation valve is separated from its redundant vent valves by approximately 20 ' horizontal separation with an intervening concrete floor. Between Columns 17 and 18, the vertical separation is 18 ' with the lower cables 12' off the floor. The separation and height of cable from the floor provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-41 Between Columns 14 and 15, there is a vertical separation of 27 ', with the lower cables 19 ' off the floor. There is a minimum separation of 8 ' between the Train A valves and the Train B cables, with the Train B cables 19 ' off the floor. The separation, height of cable from the floor and lack of in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. Between column 12 and 13, there is a vertical separation of 20 ' with the lower cables 20 ' off the floor. The separation and height of cable from the floor provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. At the valves, the horizontal separation between the redundant valves and the intervening concrete floor provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. r. RH Heat Exchanger to CS/SI Pump Isolation Valves RH -V35, RH-V36 Cables for the redundant valves RH -V35 and RH -V36 are routed in proximity to one another in the area of the valves RC -V22, RC-V23, RV-V87 and RV -V88. Valves RH -V35 and RH -V36 are normally closed and their position is in consequential during all modes of plant operation with the exception of cooldown below 350F when the RH system is placed in operation. At that time it is necessary to assure that the valves remain closed. Should one of the valves open spuriously, the operators can disable its power supply in either the Train A or Train B switchgear room (Fire Areas: CB -F-1A-A or CB-F-1B-A) and manually reposition the valves located in the equipment vaults (Fire Zone: RHR -F-4B-Z or RHR-F-2A-Z). Manual operation of the valves can be delayed as much as 9 hours into the event. Therefore, no fire protection other than the existing separation is needed. The provision of a capability to mitigate the spurious operation of the valves outside the fire area satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-42 s. Steam Generator Blowdown Isolation Valves SB -V1, SB-V3, SB-V5, SB-V7 One Train (Train A) of the SG Blowdown isolation valves and their related cables are located in containment. The redundant train (Train B) valves SB -V9, SB-V10, SB-V11 and SB -V12 are located in the main steam and feedwater pipe chase (Fire Zone: MS -F-1B-Z). The Appendix R separation requirements are satisfied.

t. Steam Generator Level Transmitters FW

-LT-501, FW-LT-502, FW-LT-503, FW-LT-504, FW-LT-519, FW-LT-529, FW-LT-537, FW-LT-548 Cables for redundant steam generator level transmitters are routed through enclosed trays and conduits from the penetration where they enter containment to the level transmitters. As only two steam generators are required for safe shutdown, any combinations of two transmitters will satisfy the safe shutdown requirements. At the penetrations in containment the four Train A transmitter cables are separated from the four Train B transmitter cables by a concrete floor. From the penetrations the cables separate such that two Train A and two Train B transmitter cables are routed on each side of the containment up to the transmitters. The transmitters are located approximately 75 ' apart with intervening walls. The separation between redundant transmitters and their cables provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. u. Excore Nuclear Instrumentation NI -NE-6690 and NI -NE-6691 and Terminal Boxes EDE -TBX-XP8, EDE-TBX-XP9 Cables for the redundant nuclear instrumentation are routed through conduit from the penetration where they enter containment to the instruments in the reactor pit. The conduits are separated by concrete floors and walls or by a minimum of 20 ' from the penetration to the reactor pit. The only intervening combustibles between the redundant conduits are cables in trays. The conduits enter the pit approximately 3 ' apart and again separate to turn to their respective instruments, which are 16 ' apart. Because of high radiation, the pit is inaccessible during normal operation. Other than the cable in conduit, the fire loading in this area is zero. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-43 The containment is a controlled entry area and the fire loading is very low. The use of transient combustibles is strictly controlled. The minimum of 20 ' separation and the routing of cables in conduit provide acceptable fire protection in the general containment area. At the entrance to the pit and inside it, the separation, routing of cables in conduit and inaccessibility of the pit due to high radiation, provide acceptable protection and provide protection equivalent to the technical requirements of Appendix R. v. Pressurizer Level Transmitters RC -LT-459, RC-LT-460 Cables for redundant level transmitters are routed in enclosed tray and conduit from the penetration where they enter containment to the level transmitters at Elevation 0 '-0". The trays are separated by concrete floor except between Columns 2 and 4, Columns 5 and 6 and Columns 7 and 8 where there is grating. Between Columns 2 and 4, the Train B trays are a minimum of 8 ' above floor Elevation ( -) 26'-0" and the Train A trays are a minimum of 12 ' above grating Elevation 0 '-0". There is a minimum of 23 ' vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the trays. Between Columns 5 and 6, the Train B trays are a minimum of 14 ' above floor Elevation ( -) 26'-0" and the Train A trays are a minimum of 18 ' above grating Elevation 0 '-0". There is a minimum of 29 ' vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in trays: three pints of oil in 15 HP RC drain tank pump motor contributing 56,250 Btu fire load; and five pounds of grease in 3 HP containment sump pump motors contributing 90,000 Btu fire load. Between Columns 7 and 8, the Train B trays and conduit are a minimum of 14 ' above floor Elevation ( -) 26'-0" and the Train A trays are a minimum of 14 ' above grating Elevation 0 '-0". There is a minimum of 20 ' of vertical separation between the redundant raceways. The only in situ combustibles at this location are the cables in the trays.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-44 The redundant level transmitters are located 6 ' above the floor at Elevation 0 '-0". They are separated by approximately 1 '-0" horizontally. The Train B transmitter is enclosed in a non -combustible radiant energy shield. The cable to the Train A transmitter is routed in conduit from the enclosed instrumentation tray located 14 ' above the grating Elevation 0 '-0" to the transmitter. The cable to the Train B transmitter is routed in conduit from the enclosed instrumentation tray located 15 ' above floor Elevation ( -) 26'-0" to the level transmitter. The conduit is protected by a radiant energy shield above Elevation 0 '-0" until it enters the enclosure formed by the non -combustible radiant energy shield for RC -LT-460. The combustibles in the area are limited to cables in one stack of open trays (3 trays high) between elevations ( -) 12'-8" and (-) 7'-4" approximately 13 ' above floor Elevation ( -) 26'-0" and one stack of open trays (4 trays high) between elevations 16'-8" and 20'-8" approximately 16 ' above grating Elevation 0 '-0". The separation, height of the tray off of the floor, enclosure of combustibles in the motors and provision of a radiant energy shield provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. w. Pressurizer Pressure Transmitters RC -PT-455, RC-PT-456, RC-PT-457, and RC-PT-458 Redundant channels ' of pressurizer pressure instruments and cables are located in proximity. Spurious operation of two channels will initiate safety injection and containment isolation phase A signals. The operators will have the capability to terminate SI after 1 minute by use of the manual reset and block switch and terminate containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B Switchgear Rooms (Fire Areas: CB-F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-45 x. Reactor Coolant Hot Leg Temperature Elements, RC -TE-413A through RC-TE-443B, IC-TE-1 through IC -TE-58, IC-MM-173 and Terminal Boxes EDE-TBX-X40, EDE-TBX-X48, EDE-TBX-X94 Cables for redundant RC hot leg temperature elements are routed through enclosed trays and conduits from the penetration where they enter containment to the temperature elements. As only one hot leg temperature is required for safe shutdown, any of the TE 's can satisfy the safe shutdown requirements. As the TE's are at various locations around the containment, there is a minimum of 20 ' of separation except for the penetration area. At the Train A penetration area, all hot leg TE cables could fail. This function can also be performed by the Train B incore thermocouples IC -TE-1 through IC -TE-58 which are separated from the Train A penetration area by concrete walls and floors. The separation between redundant temperature monitoring capabilities and their associated cables provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. y. Reactor Coolant Cold Leg Temperature Elements RC -TE-413B through RC-TE-443B and Terminal Boxes EDE -TBX-X14 through EDE -TBX-X69 Cables for redundant RC cold leg temperature elements are routed through enclosed trays and conduits from the penetration where they enter containment to the temperature elements. As only one cold leg temperature is required for safe shutdown any one of the TE's can satisfy the safe shutdown requirements except for the penetration area. At the Train B penetration area, all cold leg TE cables could fail. This function can also be performed by the steam generator pressure instruments because cold leg temperature approximates the saturation temperature corresponding to secondary pressure. These pressure transmitters FW -PT-514, FW-PT-525, FW-PT-534 and FW -PT-545 are located in Fire Zones MS -F-3A-Z and MS-F-1B-Z. The provision of a capability to permit RC temperature monitoring outside the fire area satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-46 C. Evaluation Deviations from the Appendix R, Paragraph III.G.2 separation requirements exist in containment and have been described above and analyzed in detail. These deviations are justified based on the analyses and our assertion that additional modifications would not enhance fire protection safety which has been insured by the protective measures listed in the "General Area Analysis " and the "System Analysis ". Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CAH-FN-1C x CAH-FN-1E x CAH-FN-1F x CBA-DP-21A x CBA-DP-24A x CBA-DP-24B x CBA-DP-24C x CBA-DP-26A x CBA-E-230A x CBA-FN-14A x CBA-FN-19 x CBA-FN-20 x CBA-FN-21A x CBA-P-434A x CBA-P-435A x CBS-P-9A x CC-LT-2172-1 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-47 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-LT-2172-2 x CC-LT-2172-3 x CC-LT-2272-1 x CC-LT-2272-2 x CC-LT-2272-3 x CC-P-11A x CC-P-11C x CC-P-322A x CC-TE-2171 x CC-TV-2171-1 x CC-TV-2171-2 x CC-V57 x CC-V121 x CC-V175 x CC-V257 x CC-V145 x CC-V1101 x CC-V1109 x CO-LT-4096 x CP-CP-111 x x CP-CP-111 x x CS-FT-121 x CS-FCV-110A x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-48 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-FCV-111A x CS-FCV-110B x CS-FCV-111B x CS-FCV-121 x CS-HCV-182 x CS-LCV-112B x CS-LCV-112D x CS-LT-102 x CS-P-2A x CS-P-2B (1) (1) CS-P-3A x CS-V10 x CS-V28 x CS-V44 x CS-V59 x CS-V142 x CS-V154 x CS-V158 x CS-V162 x CS-V166 x CS-V167 x CS-V196 x CS-V460 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-49 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable (1) CS-P-2B and its cables are not actually located in this fire area. However, CS -P-2B is listed because it is potentially affected via a systems interaction. See Analysis Section B.13. DAH-DP-16A x DAH-FN-25A x DAH-FN-26A x DAH-CP-295 x DG-CP-75A x DG-CP-79 x x DG-CP-907A x DG-DG-1A x DG-P-38A x DG-C-2A x EAH-FN-5A x EAH-FN-31A x EAH-FN-174A x ED-X-14J x ED-BC-2A x ED-BC-2B x ED-I-4 x ED-PP-122B x x ED-PP-3C x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-50 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable ED-US-11 x x ED-US-23 x x EDE-B-1A x EDE-B-1C x EDE-BC-1A x x EDE-BC-1C x x EDE-CP-1E x x EDE-CP-227 x x EDE-CP-229 x x EDE-CP-248 x x EDE-I-1A x x EDE-I-1C x x EDE-I-1E x x EDE-MCC-511 x EDE-MCC-512 x x EDE-MCC-513 x EDE-MCC-514 x EDE-MCC-515 x x EDE-MCC-521 x x EDE-MCC-522 x x EDE-MCC-523 x EDE-MCC-531 x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-51 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-MM-578 x x EDE-MM-583 x x EDE-MM-585 x x EDE-PP-1A x x EDE-PP-1C x x EDE-PP-1E x x EDE-PP-11E x x EDE-PP-111A x x EDE-PP-112A x x EDE-PP-113A x x EDE-SWG-5 x x EDE-SWG-11A x x EDE-SWG-11C x x EDE-US-51 x x EDE-US-52 x x EDE-US-53 x x EPA-DP-371 x EPA-DP-373 x EPA-FN-47A x FW-FV-4214A x FW-FV-4224A x FW-FV-4234A x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-52 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-FV-4244A x FW-P-113 x FW-P-161 x FW-V156 x FW-V163 x MS-PV-3001 x MS-PV-3002 x MS-PV-3003 x MS-PV-3004 x MS-V86 x MS-V88 x MS-V90 x MS-V92 x MM-CP-1 x MM-CP-3 x MM-CP-7 x MM-CP-12 x MM-CP-108A x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-53 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MM-CP-152A x MM-CP-153 x MM-CP-297A x NI-NE-6690 x NI-NM-6690 x x NI-MM-6690J x x PAH-DP-35A x PAH-DP-36A x PAH-DP-43A x PAH-DP-357 x PAH-FN-42A x RC-E-10 (Group A) x RC-P-1A x RC-P-1B x RC-P-1C x RC-P-1D x RC-PCV-456A x RC-V23 x RC-V88 x RC-V122 x RC-E-10 (Group C,D Control) x RH-FCV-618 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-54 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RH-HCV-606 x RH-P-8A x RH-V14 x RH-V35 x RH-V70 x SA-SKD-137A x SA-C-4A x SI-FV-2482 x SI-FV-2483 x SI-FV-2495 x SI-FV-2496 x SI-P-6A x SI-V3 x SI-V32 x SI-V138 x SI-PT-937 x SW-FN-51A x SW-P-41A x SW-P-41C x SW-P-110A x SW-V2 x SW-V4 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-55 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-V15 x SW-V16 x SW-V20 x SW-V22 x SW-V34 x SW-V54 x SW-V56 x SW-V74 x SW-V139 x SWA-DP-66 x SWA-FN-71 x SWA-FN-40A x B. Analysis 1. General Systems/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown equipment and cables. The redundant Train B safe shutdown equipment and cables are located in fire area CB -F-1B-A. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-56 2. Containment Spray Pump CBS -P-9A This pump is not required for safe shutdown, however; a fire could cause a spurious start. The operators will terminate operation of the CBS pump either by tripping and locking out the motor 's circuit breaker from the MCR or by removing all power from the 4160V emergency bus E5. The safe shutdown requirements are satisfied.

3. Component Cooling Water Containment Isolation Valves CC

-V57, CC-V121, CC-V175, CC-V257 and Head Tank Level Transmitters CC -LT-2172-1, 2, 3, CC-LT-2272-1, 2, 3 A fire could cause loss of all PCCW to containment by spurious closure of the PCCW Loop B outboard isolation valves CC -V175 and CC -V257. One train of PCCW is required to maintain containment habitable for manual valve operations. PCCW is also required for cooling air compressor SA -C-4B. Should all PCCW be isolated, the operators will immediately trip the Train B air compressor SA-C-4B to preclude operating the compressor without cooling. As the containment instrument air pressure decays without SA -C-4B operating, the PCCW Loop B inboard isolation valves will close. The operators will manually reopen the PCCW Loop B outboard isolation valves CC-V175 and CC -V257 in the mechanical penetration fire area (Fire Zone: PP-F-4B-Z). The operators will then manually open IA -V530 to connect the outside containment Loop B instrument air to the inside containment instrument air system. Once containment instrument air is restored, the PCCW Loop B inboard isolation valves will reopen to reestablish PCCW cooling to the air compressor and to the Train B containment structure coolers. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-57 4. Reactor Trip Switchgear CP -CP-111 Redundant trains of cables and equipment are located in proximity. These breakers are tripped from the MCR as an initial operator action; however, a fire in the area of the reactor trip switchgear could prevent operation of both trains of tripping capability. Should this occur the operators can remove power from the reactor trip MG sets by tripping the switching station breakers that supply power to the UAT and RAT causing a loss of offsite power to the station. This trip can be initiated from the MCR as the switching station breaker control circuits are not routed through this fire area. The removal of power from the MG sets will, after a short time delay to allow for coastdown, result in de -energizing the reactor trip solenoids and; hence, insertion of the control rods. The safe shutdown requirements are satisfied.

5. Charging Pump Flow Control Valve CS

-FCV-121 and Flow Transmitter CS-FT-121 Under normal conditions, charging is accomplished by utilizing the control valve

CS-FCV-121 and its associated transmitter. Spurious closure of this valve could isolate the seal injection path. In this event the operators will utilize the high head injection path for hot standby charging flow by opening the Train B valve SI-V139. The cables, controls and equipment required for operation of SI -V139 are not contained in the fire area. For cooldown, the operators will manually align the Train B charging pump discharge and bypass valves (CS -V219 and CS -V220) to the seal injection flow path and throttle the bypass valve as required. This operator action can be delayed for up to four (4) hours. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-58 6. RC Pump Seal Water Isolation Valves CS -V10, CS-V28, CS-V44, CS-V59 and CS-V167 Valve CS-V167 is a normally open valve which should remain open for safe shutdown. Spurious isolation of the Train A valve CS -V167 could result in loss of RC inventory through the upstream relief valve. This inventory is directed to the PRT and is therefore, non -recoverable. Additionally, cables for the functionally redundant Train A valves CS -V10, CS-V28, CS-V44 and CS -V59 are routed in proximity. However, the postulated flow rate (12 GPM) coupled with the RCS volume shrink over the cooldown period to 350F (approximately 5 hours) is within the capabilities of the boric acid tanks. Cooldown below 350F to cold shutdown can be accomplished using the RWST. Shutdown margin is assured in all phases of this cooldown. The safe shutdown requirements are satisfied.

7. RC Pump Seal Injection Isolation Valves CS

-V154, CS-V158, CS-V162 and CS-V166 Under normal conditions, these valves are utilized for the seal injection flow path. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by removing power from the 4160V emergency bus E5. MCC E512, which powers these valves, is fed from emergency bus E5. These valves provide a redundant RC pump seal cooling capability to the safety grade thermal barrier seal cooling. Cables, controls and equipment required for the Train B thermal barrier seal cooling capability are not contained in this fire area. The Appendix R separation requirements are satisfied.

8. SI-CS Suction Cross Connection Valve CS

-V460 Valve CS-V460 is a normally closed Train A valve which is required to remain closed for cooldown. Should this valve open spuriously, the functionally redundant Train B valve CS -V475 can be closed from the MCR. Cables and controls for valve CS -V475 are not located in this fire area. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-59 9. Tower Actuation Logic EDE -CP-248 Failures in TA logic cables or equipment could initiate a spurious tower actuation signal which would transfer Train A service water cooling capability from the pumphouse to the cooling towers. The transfer will not interrupt Train A service water nor will it have any impact on Train B service water. This failure does not prevent safe shutdown. The safe shutdown requirements are satisfied.

10. 4160V Switchgear EDE

-SWG-5 Although this equipment is not required for safe shutdown for fire in this area, there are many loads powered from it whose spurious operation could affect safe shutdown should they remain powered. For any fire in the Train A switchgear room that has a potential to impact safe shutdown, the operators will trip and lockout all ac power supplies (UAT, RAT, DG) to the bus from the MCR. To assure that breakers cannot spuriously reclose, the UAT and RAT breaker dc control power will be disabled at the disabling panel and the DG breaker control power will be disabled at the DG control panel both in the Train A diesel generator room (Fire Area DG -F-2A-A). Should the capability to trip the power supplies not be available due to prior loss of the dc control power, the operators can remove power by tripping the switching station breakers that supply power to the UAT and RAT causing a loss of offsite power to the station. This trip can be initiated from the MCR as the switching station breaker control circuits are not routed through this fire area. Subsequent to this loss of offsite power, the 4160V emergency switchgear bus E6 and Train B power will be supplied by the Train B diesel generator. The safe shutdown requirements are satisfied.

11. Emergency Feedwater Pump Control Valves FW

-FV-4214A, FW -FV-4224A, FW-FV-4234A and FW -FV-4244A These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by removing power from the 4160V emergency bus E5. MCC E515, which powers these valves, is fed from emergency bus E5. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-60 12. Atmospheric Relief Valves MS -PV-3001, MS-PV-3002, MS-PV-3003, MS-PV-3004 Valves MS -PV-3001, MS-PV-3002, MS-PV-3003 and MS -PV-3004 are normally closed valves. A fire would prevent operation of the Train A capabilities provided for opening and closing these valves. However, the fire would not affect the Train B capabilities and the valves will be operable for safe shutdown. Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire

that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affected air solenoids will be de -energized from the disabling panel located in Train A diesel generator room (Fire Area: DG -F-2A-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

13. Volume Control Tank Isolation Valve CS

-LCV-112B and CS-LCV-112D, and Charging Pump CS -P-2A & CS-P-2B Volume control tank (VCT) isolation valves CS -LCV-112B & -112C are normally open to provide a suction path from the VCT to the normally operating charging pump (CS -P-2A or -2B). These valves must stay open until RWST valve CS-LCV-112D or -112E is manually opened to provide a charging pump suction path from the RWST, or the boric acid tanks are manually aligned as a charging pump suction source. Spurious closure of a VCT isolation valve caused by a hot short would interrupt suction flow to the operating charging pump causing it to be damaged. If the standby charging pump has cables in the same area then its operation can also be degraded. The result would be no charging system flow. Since this fire area contains cables for CS -LCV-112B and CS -P-2A, this condition is potentially applicable for the system alignment with CS -P-2A the standby pump and CS -P-2B the operating pump.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-61 There is an electrical interlock that automatically opens opposite train RWST valve 1-CS-LCV-112E if VCT valve 1 -CS-LCV-112B is not full open (i.e., spuriously closes). The cables, controls and equipment required for automatically opening RWST valve 1 -CS-LCV-112E are not contained in this fire area. The open RWST valve provides a suction path so operating charging pump CS -P-2B will not be damaged. Since charging flow is available, the safe shutdown requirements are satisfied.

14. Not Used. 15. Reactor Coolant Pumps RC

-P-1A, RC-P-1B, RC-P-1C and RC -P-1D Cables required for trip of the RC pumps are routed through this fire area. These breakers are tripped from the MCR as an initial operator action; however, fire in this area could prevent this trip. Should this occur the operators will either trip the RC pump circuit breakers locally (Fire Area: NES -F-1A-Z) or by removing power from the RC pump motors by tripping the switching station breakers which supply power to the UAT and RAT, thus causing a loss of offsite power to the station. This trip can be initiated from the MCR as the switching station breaker control circuits are not routed through this fire area. The safe shutdown requirements are satisfied.

16. Pressurizer Relief Valves RC-PCV-456A, RC-V122 RC-PCV-456A is a normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC

-V122. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV by placing the PORV main control board control switch to the closed position. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-62 17. RHR Isolation Valves RC -V23, RC-V88 RHR isolation valves are permanently disabled in the closed position. For entry into RHR shutdown cooling valve RC -V88 must be opened. This can be accomplished manually by entry into containment, if required. This manual

operation can be delayed as much as 9 hours into the event. The safe shutdown requirements are satisfied.

18. Safety Injection Pump SI

-P-6A This pump is not required for safe shutdown; however, a fire could cause a spurious start. The operators will terminate operation of the SI pump either by tripping and locking out the motor 's circuit breaker from the MCR or by removing all power from the 4160V emergency bus E5. The safe shutdown requirements are satisfied.

19. Cooling Tower Fan SW

-F-51A, Pump SW -P-110A, Valves SW -V54, SW-V56, SW-V139, Fans SWA -FN-69 and Dampers SWA -DP-66 and SWA -FN-71 During normal plant operation, the service water pumphouse is utilized for plant cooling. The cooling towers are considered a redundant capability which may be utilized for a limited period of time during the year (e.g., tunnel heat treating). Should a fire occur during this time period the operators can utilize the Train B service water pumphouse capability. The cables, controls and equipment required for the Train B service water pumphouse capability are not contained in this fire area. The Appendix R separation requirements are satisfied.

20. Pressurizer Heaters Group C, Group D, Control Group This equipment is not required for safe shutdown; however, a fire could cause spurious operations. The operators will terminate operation of the pressurizer heaters, or mitigate the condition by tripping the heaters

' circuit breaker, by tripping off -site power from the control room, or by reducing pressure by opening a PORV. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-63 21. Containment Pressure Transmitter SI -PT-937 A cable for one channel of containment pressure instrumentation is routed through this fire area. This channel inputs to 2 out of 3 and 2 out of 4 logics which initiate protective actions. A spurious signal from one channel is not sufficient to initiate the logic and perform the protective action; hence, a failure in this cable will not prevent safe shutdown. The safe shutdown requirements are satisfied.

22. Containment Enclosure Isolation Damper, PAH

-DP-35A, PAH-DP-36A Cables for dampers PAH -DP-35A and PAH -DP-36A are routed through this area. Under normal operation both dampers are open. If both dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in the recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. Independent operation of either damper (one open and one closed) could cause an air flow problem in EAH system. This

assumes that both redundant dampers (PAH -DP-35B and PAH -DP-36B) are in their normal open position since they would not be affected by a fire in this area. Both dampers are powered from a single Train A power supply. The circuit design is such that a spurious signal will cause both dampers to operate together either both open (normal mode) or both closed (recirculation mode). The safe shutdown requirements are satisfied.

23. Control Room Air Conditioning The non-safety related chilled water system, which is powered from a non

-safety related power supply, is normally running and aligned to either the A Train or the B Train Control Building Air Conditioning System fan unit. During normal plant operation, with the non -safety subsystem aligned for Control Room cooling on the A Train fan unit, the control switch on the MCB for the safety related train will be aligned for AUTO operation. On a loss of offsite power, the non -safety chilled water subsystem will be shut down and an automatic start sequence will be

initiated via the emergency diesel generator load sequencer to restart the AC unit and start the A Train safety chiller.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-64 In the event the A Train of the CBA fails to start, operator actions, prompted by high Control Room temperature, are assumed to secure the failed chiller and associated equipment and start the B Train. All controls for the recovery are in the Control Room. The safe shutdown requirements are satisfied.

24. Boration/Dilution Flow Control Valves, CS

-FCV-110A, -111A, -110B, -111B This area contains cables for CS -FCV-110A, -111A, -110B, -111B. Spurious opening of these valves in conjunction with spurious start of a boric acid transfer pump or reactor makeup water pump may divert boric acid from the reactor coolant system affecting cold shutdown reactivity control, or result in an unplanned dilution affecting hot standby and cold shutdown reactivity control. The operators isolate the diversion flow by closing CS -FCV-110B and -111B using the main control board control switches. The operators isolate the dilution flow by closing CS -LCV-112C using the main control board control switch. The safe shutdown requirements are satisfied.

25. Charging Pump CS

-P-2A and High Head Injection Valve SI -V-138 Either charging pump CS -P-2A or CS-P-2B is normally operating. High head injection valve SI -V-138 is normally closed. If SI-V-138 spuriously opens, CS-P-2A and CS -P-2B need to be stopped to isolate charging flow to prevent pressurizer overfill. If CS-P-2A can not be stopped from the main control room because its cables are routed through this fire area, then power will be removed from Emergency Bus E5 to stop the pump (see Item 10 analysis). A fire in this area does not affect the capability to trip CS -P-2B from the main control room. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-65 Tabulation 3.2.7.3 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CAH-FN-1A x CAH-FN-1B x CAH-FN-1D x CBA-DP-21B x CBA-DP-26B x CBA-E-230B x CBA-FN-14B x CBA-FN-21B x CBA-FN-32 x CBA-FN-33 x CBA-P-434B x CBA-P-435B x CBS-P-9B x CC-LT-2192-1 x CC-LT-2192-2 x CC-LT-2192-3 x CC-LT-2292-1 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-66 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-LT-2292-2 x CC-LT-2292-3 x CC-P-11B x CC-P-11D x CC-P-322B x CC-TE-2271 x CC-TV-2271-1 x CC-TV-2271-2 x CC-V122 x CC-V168 x CC-V176 x CC-V256 x CC-V272 x CC-V1092 x CC-V1095 x CP-CP-111 x CS-LCV-112C x CS-LCV-112E x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-67 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-LT-7464 x CS-P-2A (1) (1) CS-P-2B x CS-P-3B x CS-V143 x CS-V168 x CS-V175 x CS-V176 x CS-V197 x CS-V426 x CS-V461 x CS-V475 x DAH-DP-16B x DAH-FN-25B x DAH-FN-26B x DAH-CP-296 x (1) CS-P-2A and its cables are not actually located in this fire area. However, CS -P-2A is listed because it is potentially affected via a systems interaction. See Analysis Section B.19. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-68 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable DG-CP-76A x DG-CP-80 x x DG-CP-907B x DG-DG-1B x DG-P-38B x DG-C-2B x EAH-FN-5B x EAH-FN-31B x EAH-FN-174B x ED-X-16A x EDE-B-1B x EDE-B-1D x EDE-BC-1B x x EDE-BC-1D x x EDE-CP-1F x x EDE-CP-228 x x EDE-CP-230 x x EDE-CP-249 x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-69 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-I-1B x x EDE-I-1D x x EDE-I-1F x x EDE-MCC-612 x x EDE-MCC-614 x EDE-MCC-611 x EDE-MCC-615 x x EDE-MCC-621 x x EDE-MCC-622 x x EDE-MCC-631 x x EDE-MM-580 x x EDE-PP-1B x x EDE-PP-1D x x EDE-PP-1F x x EDE-PP-11F x x EDE-PP-111B x x EDE-PP-112B x x EDE-PP-113B x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-70 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-SWG-6 x x EDE-SWG-11B x x EDE-SWG-11D x x EDE-US-61 x x EDE-US-62 x x EDE-US-63 x x EPA-DP-372 x EPA-DP-374 x EPA-FN-47B x FW-FV-4214B x FW-FV-4224B x FW-FV-4234B x FW-FV-4244B x FW-P-37B x FW-V347 x IA-SKD-18B x MM-CP-2 x MM-CP-4 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-71 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MM-CP-13 x MM-CP-108B x x MM-CP-152B x MM-CP-486B x MM-CP-297B x MS-CP-183 x x MS-CP-185 x x MS-PV-3001 x MS-PV-3002 x MS-PV-3003 x MS-PV-3004 x MS-V86 x MS-V88 x Ms-V90 x MS-V92 x NI-NE-6691 x NI-NM-6691 x x NI-NM-6691J x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-72 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable PAH-DP-35B x PAH-DP-36B x PAH-DP-43B x PAH-DP-358 x PAH-FN-42B x RC-E-10 (Group B) x RC-FV-2881 x RC-PCV-456B x RC-V22 x RC-V87 x RC-V124 x RC-V323 x RH-FCV-619 x RH-HCV-607 x RH-P-8B x RH-V26 x RH-V32 x RH-V36 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-73 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SA-SKD-137B x SA-C-4B x SI-FV-2475 x SI-FV-2476 x SI-FV-2477 x SI-FV-2486 x SI-P-6B x SI-V17 x SI-V47 x SI-V139 x SI-V158 x SW-P-41B x SW-P-41D x SW-V5 x SW-V18 x SW-V19 x SW-V23 x SW-V25 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-74 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-V29 x SW-V31 x SWA-FN-40B x B. ANALYSIS 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A safe shutdown equipment and cables are located in fire area CB -F-1A-A. The Appendix R separation requirements are satisfied.

2. Containment Spray Pump CBS

-P-9B This pump is not required for safe shutdown, however, a fire could cause a spurious start. The operators will terminate operation of the CBS pump either by tripping and locking out the motor 's circuit breaker from MCR or by removing all power from the 4160V emergency Bus E6. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-75 3. Component Cooling Water Containment Isolation Valves CC -V122, CC-V168, CC-V176, CC-V256 and Head Tank Level Transmitters CC -LT-2192-1, 2, 3, CC-LT-2292-1, 2, 3 A fire could cause loss of all PCCW to containment by spurious closure of the PCCW Loop B outboard isolation valves CC -V122 and CC -V168. One train of PCCW is required to maintain containment habitable for manual valve operations. PCCW is also required for cooling the air compressor SA -C-4A. Should all PCCW be isolated, the operators will immediately trip the Train A air compressor SA-C-4A to preclude operating the compressor without cooling. As the containment instrument air pressure decays without SA -C-4A operating, the PCCW Loop B inboard isolation valves will close. The operators will manually reopen the PCCW Loop A outboard isolation valves CC-V-122 and CC -V-168 in the mechanical penetration fire area (Fire Zone: PP-F-4B-Z). The operators will then manually open IA -V50 to connect the outside containment Loop A instrument air to the outside containment Loop B instrument air. The operators will then manually open IA -V530 to connect the outside containment Loop B instrument air to the inside containment instrument air system. Once containment instrument air is restored, the PCCW Loop A inboard isolation valves will reopen to reestablish cooling to the air compressor and to the Train A containment structure coolers. The safe shutdown requirements are satisfied.

4. RC Pump Seal Water Isolation Valve CS

-V168 Valve CS-V168 is a normally open valve which should remain open for safe shutdown. Spurious isolation of the Train B valve could result in RC inventory loss through the upstream relief valves. This inventory is directed to the PRT and is therefore, non -recoverable. To preclude this loss of inventory, redundant isolation capability is provided for the RC pump seal return lines by means of Train A valves CS -V10, CS-V28, CS-V44 and CS -V59. The cables, controls and equipment required for the operation of CS -V10, CS-V28, CS-V44 and CS -V59 are not contained in this fire area. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-76 5. Excess Letdown Isolation Valves CS -V175 and CS -V176 Cables for functionally redundant fail closed valves CS -V175 and CS -V176 are routed in proximity. These valves are normally closed and remain closed for safe shutdown. Should either valve spuriously open, the operators will mitigate the spurious operation by disabling the power supply to CS -V175 at the disabling panel in the Train B diesel generator room (Fire Area: DG -F-2B-A). The safe shutdown requirements are satisfied.

6. Charging Pump Test Line Isolation Valve SI

-V158 On spurious operation of the normally closed, fail closed valves SI -V158 (Train B), the operators will maintain the normally closed high head injection path valves SI -V138 and SI -V139 closed. Charging will be accomplished utilizing the seal injection flow path through valves CS -FCV-121, CS-V154, CS-V158, CS-V162 and CS -V166. The cables controls and equipment required for operation of these valves are not contained in the fire area. The capability to provide charging to the RC System through a minimum of one flow path satisfies the safe shutdown requirements.

7. BAT to Charging Pump Isolation Valve CS

-V426 Valve CS-V426 is a normally closed valve which is opened to provide a path from the boric acid tanks to the charging pump suction. This path is required to begin cooldown. In the event that this valve is inoperable, the operators can provide a redundant path by manually positioning valves in the boric acid tank room (Fire Zone: PAB -F-2B-Z). The operators can maintain the plant in hot standby for the time required to perform this manual action. The safe shutdown requirements are satisfied.

8. SI-CS Suction Cross Connection Valves CS

-V461, CS-V475 Cables for valves CS -V461 and CS -V475 are located in proximity. Prior to beginning cooldown, the normally closed valve CS -V461 valve should remain closed or the functionally redundant valve CS -V475 should be closed. The isolation of this path will prevent the potential loss of boric acid tank inventory to the RWST during cooldown. In the event of a spurious valve operation which renders this flow path open, the plant can be maintained in hot standby for as long as 4 hours.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-77 Should this area be inaccessible due to the fire or should the operators desire to initiate the cooldown sooner than 4 hours, a gravity feed can be established from the boric acid tanks to the charging pumps. As the BAT head is lower than that required to return inventory to the RWST, there would be no loss of BAT inventory through this path and the position of these valves would be inconsequential. The safe shutdown requirements are satisfied.

9. Tower Actuation Logic EDE

-CP-249 Failures in TA logic cables or equipment could initiate a spurious tower actuation signal which would transfer Train B service water cooling capability from the pumphouse to the cooling towers. The transfer will not interrupt Train B service water nor will it have any impact on Train A service water. This failure does not prevent safe shutdown. The safe shutdown requirements are satisfied.

10. 4160V Switchgear EDE

-SWG-6 Although this equipment is not required for safe shutdown for fire in this area, there are many loads powered from it whose spurious operation could affect safe shutdown should they remain powered. For any fire in the Train B switchgear room that has a potential to impact safe shutdown, the operators will trip and lockout all ac power supplies (UAT, RAT, DG) to the bus from the MCR. To assure that breakers cannot spuriously reclose, the UAT and RAT breaker dc control power will be disabled at the disabling panel and the DG breaker control power will be disabled at the DG control panel, both in the Train B diesel generator room (Fire Area: DG -F-2B-A). Should the capability to trip the power supplies not be available due to prior loss of the dc control power, the operators can remove power by tripping the switching station breakers that supply power to the UAT and RAT causing a loss of offsite power to the station. This trip can be initiated from the MCR as the switching station breaker control circuits are not routed through this fire area. Subsequent to this loss of offsite power, the 4160V emergency switchgear bus E5 and Train A power will be supplied by the Train A diesel generator. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-78 11. Emergency Feedwater Pump Control Valves FW -FV-4214B, FW -FV-4224B, FW-FV-4234B and FW -FV-4244B These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by removing power from the 4160V emergency bus E6. MCC E615, which powers these valves, is fed from emergency bus E6. The safe shutdown requirements are satisfied.

12. Atmospheric Relief Valves MS

-PV-3001, MS-PV-3002, MS-PV-3003, MS-PV-3004 Valves MS -PV-3001, MS-PV-3002, MS-PV-3003 and MS -PV-3004 are normally closed valves. A fire would prevent operation of the Train B capabilities provided for opening and closing these valves. However, the fire would not affect the Train A capabilities and the valves will be operable for safe shutdown. Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affecte d air solenoids will be de -energized from the disabling panel located in Train B diesel generator room (Fire Area: DG -F-2B-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-79 13. Reactor Vent Valves RC -FV-2881, RC-V323 Functionally redundant series valves RC -FV-2881 (fail closed) and RC -V-323 are normally closed and remain closed for safe shutdown. The spurious opening of one valve will not prevent safe shutdown. The operators will prevent spurious opening of this path by disabling the power supply to valve RC -FV-2881 at the disabling panel in the Train B diesel generator room (Fire Area: DG -F-2B-A). The safe shutdown requirements are satisfied.

14. Pressurizer Relief Valves RC

-PCV-456B, RC-V124 RC-PCV-456B is normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V124. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV by placing the PORV main control board control switch to the closed position. The safe shutdown requirements are satisfied.

15. RHR Isolation Valves RC

-V22, RC-V87 RHR isolation valves are permanently disabled in the closed position. For entry into RHR shutdown cooling valve RC -V22 must be opened. This can be accomplished by entry into containment, if required. This manual operation can be delayed as much as 9 hours into the event. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-80 16. Safety Injection Pump SI -P-6B This pump is not required for safe shutdown; however, a fire could cause a spurious start. The operators will terminate operation of SI pump either by tripping and locking out the motor 's circuit breaker from the MCR or by removing all power from the 4160V emergency bus E6. The safe shutdown requirements are satisfied. 17. Containment Enclosure Isolation Damper, PAH -DP-35B, PAH-DP-36B Cables for dampers PAH -DP-35B and PAH -DP-36B are routed through this area. Under normal operation both dampers are open. If both dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in the recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. Independent operation of either damper (one open and one closed) could cause an air flow problem in EAH system. This assumes that both redundant dampers (PAH -DP-35A and PAH -DP-36A) are in their normal open position since they would not be affected by a fire in this area. Both dampers are powered from a single Train B power supply. The circuit design is such that a spurious signal will cause both dampers to operate together, either both open (normal mode) or both closed (recirculation mode). The safe shutdown requirements are satisfied.

18. Control Room Air Conditioning The non-safety related chilled water system, which is powered from a non

-safety related power supply, is normally running and aligned to either the A Train or the B Train Control Building Air Conditioning System fan unit. During normal plant operation, with the non -safety subsystem aligned for Control Room cooling on the B Train fan unit, the control switch on the MCB for the safety related train will be aligned for AUTO operation. On a loss of offsite power, the non -safety chilled water subsystem will be shut down and an automatic start sequence will be initiated via the emergency diesel generator load sequencer to restart the AC unit and start the B Train safety chiller. In the event the B Train of the CBA fails to start, operator actions, prompted by high Control Room temperature, are assumed to secure the failed chiller and associated equipment and start the A Train. All controls for the recovery are in the Control Room. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-81 19. Volume Control Tank Isolation Valve CS -LCV-112C and CS-LCV-112E, and Charging Pump CS -P-2A & CS-P-2B Volume control tank (VCT) isolation valves CS -LCV-112B & -112C are normally open to provide a suction path from the VCT to the normally operating charging pump (CS -P-2A or -2B). These valves must stay open until RWST valve CS-LCV-112D or -112E is manually opened to provide a charging pump suction path from the RWST, or the boric acid tanks are manually aligned as a charging pump suction source. Spurious closure of a VCT isolation valve caused by a hot short would interrupt suction flow to the operating charging pump causing it to be damaged. If the standby charging pump has cables in the same area then its operation can also be degraded. The result would be no charging system flow. Since this fire area contains cables for CS -LCV-112C and CS -P-2B, this condition is applicable for the system alignment with CS -P-2B the standby pump and the CS -P-2A the operating pump. There is an electrical interlock that automatically opens opposite train RWST valve 1-CS-LCV-112D if VCT valve 1 -CS-LCV-112C is not full open (i.e., spuriously closes). The cables, controls and equipment required for automatically opening RWST valve 1 -CS-LCV-112D are not contained in this fire area. The open RWST valve provides a suction path so operating charging pump CS -P-2A will not be damaged. Since charging flow is available, the safe shutdown requirements are satisfied.

20. Charging Pump CS

-P-2B and High head Injection Valve SI -V-139 Either charging pump CS -P-2A or CS-P-2B is normally operating. High head injection valve SI -V-139 is normally closed. If SI -V-139 spuriously opens, CS-P-2A and CS -P-2B need to be stopped to isolate charging flow to prevent pressurizer overfill. If CS -P-2B can not be stopped from the main control room because its cables are routed through this fire area, then power will be removed from Emergency Bus E6 to stop the pump (see Item 10 analysis). A fire in this area does not affect the capability to trip CS -P-2A from the main control room. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-82 Tabulation 3.2.7.4 Control Building - El. 21' -6" Fire Area - CB-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-B-1A x x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area CB -F-1F-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-83 Tabulation 3.2.7.5 Control Building - El. 21' -6" Fire Area - CB-F-1E-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-B-1C x x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area CB -F-1G-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-84 Tabulation 3.2.7.6 Control Building - El. 21' -6" Fire Area - CB-F-1F-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-B-1B x x B. Analysis All equipment and cables are Train B. The redundant Train A equipment and cables are in Fire Area CB -F-1D-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-85 Tabulation 3.2.7.7 Control Building - El. 21' -6" Fire Area - CB-F-1G-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-B-1D x x B. Analysis All equipment and cables are Train B. The redundant Train A equipment and cables are in Fire Area CB -F-1E-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-86 Tabulation 3.2.7.8 Control Building - El. 50' -0" Fire Area - CB-F-2A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable Cables for all systems required for Train A Safe Shutdown. Cables for all systems required for Train B Safe Shutdown. B. Analysis This area contains cables for redundant equipment required for safe shutdown. For a fire in this area, the operators will proceed with a controlled evacuation of the MCR and establishment of control from the RSS facilities. Details of the systems and equipment required for the alternative safe shutdown utilizing the RSS facilities are contained in Section 3.3. C. Evaluation The use of the RSS facilities satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-87 Tabulation 3.2.7.9 Control Building - El. 50' -0" Fire Area - CB-F-2B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CBA-DP-21A x x CBA-DP-24A x x CBA-DP-24B x x CBA-DP-24C x x CBA-DP-26A x CBA-DP-52 x CBA-E-230A x CBA-FN-14A x CBA-FN-19 x x CBA-FN-20 x x CBA-FN-21A x x CBA-FN-211A x CBA-PDS-21206 A1/A2 x CBA-TIC-5571 x DG-CP-79 x FW-FV-4214A x FW-FV-4224A x FW-FV-4234A x FW-FV-4244A x MM-CP-152A x MM-CP-153 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-88 Control Building - El. 50' -0" Fire Area - CB-F-2B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MM-CP-297A x RC-LCV-459 x RC-PCV-456A x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown equipment and cables. The redundant Train B equipment and cables are located in fire area CB -F-2C-A. The Appendix R separation requirements are satisfied.

2. Recirculation Damper CBA

-DP-52 Cables for damper CBA -DP-52 are routed through this area. This damper is normally closed and is required to remain closed for safe shutdown if only one main control room ventilation fan is operating. In the event of a spurious opening of the damper, the operators will isolate and bleed the air line to the dampers air operator and manually re -close the damper by means of a handwheel. The damper and its air supplies are located in the main control room HVAC equipment and duct area (Fire Area: CB -F-3B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-89 3. Process Control Cabinets MM -CP-153, MM-CP-297A Power cables for PCC cabinets MM -CP-153 and MM-CP-297A are routed through this fire area. The loss of power to these cabinets will result in loss of CST level transmitter CO -LT-4096 and FW -LT-4252 and emergency feedwater flow transmitters FW -FT-4214-2 and FW-FT-4234-2. The Train B CST level transmitter FW -LT-4257 is not affected by a fire in this area. Additionally, the emergency feedwater flow to two steam generators will be available along with steam generator level for all four steam generators. The Appendix R separation requirements are satisfied.

4. Normal Letdown Isolation Valve RC

-LCV-459 Cables for valve RC -LCV-459 are routed in this fire area. The cables, controls and equipment for functionally redundant valve CS -V145 are not contained in this area and; hence, will be available for safe shutdown. The Appendix R separation requirements are satisfied.

5. Control Room Air Conditioning The non-safety related chilled water system, which is powered from a non

-safety related power supply, is normally running and aligned to either the A Train or the B Train Control Building Air Conditioning System fan unit. During normal plant operation, with the non -safety subsystem aligned for Control Room cooling on the A Train fan unit, the control switch on the MCB for the safety related train will be aligned for AUTO operation. On a loss of offsite power, the non -safety chilled water subsystem will be shut down and an automatic start sequence will be initiated via the emergency diesel generator load sequencer to restart the AC unit and start the A Train safety chiller. In the event the A Train of the CBA fails to start, operator actions, prompted by high Control Room temperature, are assumed to secure the failed chiller and associated equipment and start the B Train. All controls for the recovery are in the Control Room. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-90 6. Emergency Feedwater Pump Control Valves FW -FV-4214A, FW -FV-4224A, FW-FV-4234A, FW -FV-4244A These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train A switchgear room (Fire Area: CB -F-1A-A). The safe shutdown requirements are satisfied.

7. Pressurizer Power Operated Relief Valve (PORV) RC

-PCV-456A A cable for RC -PCV-456A is routed in this area. Failure of this cable cannot cause the PORV to spuriously open, so the RCS pressure boundary is maintained. The safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-91 Tabulation 3.2.7.10 Control Building - El. 50' -0" Fire Area - CB-F-2C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CBA-DP-21B x x CBA-DP-24D x CBA-DP-24E x CBA-DP-24F x CBA-DP-26B x CBA-E-230B x CBA-FN-14B x CBA-FN-21B x x CBA-FN-32 x x CBA-FN-33 x x CBA-FN-211B x CBA-PDS-21206 B1/B2 x CBA-TIC-5572 x DG-CP-76A x DG-DG-1B x DG-CP-80 x EDE-SWG-6 x FW-FV-4214B x FW-FV-4224B x FW-FV-4234B x FW-FV-4244B x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-92 Control Building - El. 50' -0" Fire Area - CB-F-2C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MM-CP-13 x MM-CP-297B x RC-FV-2881 x RC-PCV-456B x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A equipment and cables are located in fire areas CB -F-2B-A and other fire areas. The Appendix R separation requirements are satisfied.

2. Main Control Room Cooling Equipment CBA

-E-230A, CBA -E-230B, CBA-DP-26A, CBA-DP-26B, CBA-FN-14A, CBA-FN-14B, CBA-FN-211A, CBA-FN-211B, CBA -PDS-21206A1/A2, CBA -PDS-21206B1/B2, CBA-TCV-21200A, CBA -TCV-21200B The control building Train B mechanical room - south is a Class 1 area which for safe shutdown has a primary function of providing protection for the Train B air handling equipment for the Train B switchgear rooms and battery rooms. The area is approximately 26 ft. long by 43 ft. wide by 23 ft. high with floor area of 1120 sq. ft. and volume of 25,800 cu. ft. The in situ combustibles consist of cables in trays.

There are a total of three cable trays which run horizontally through the area. When stacked, the trays run three high with the bottom tray being an enclosed instrument tray. There is approximately 200 ft. of uncovered cable tray containing a total of approximately 50 cables. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-93 Detectors are provided throughout the area. The cable for the Train A cooling equipment is routed in a conduit and box with a one-hour, fire -rated barrier. The only exception is at an interference with two HVAC duct hangers where the one -hour wrap is butted up to the hangers and pyrocrete is installed for heat transfer protection. The conduit and box are approximately 20 ft. above the floor. There are a total of eight cables in tray within 20 ft. horizontal of the barriered conduit. The redundant Train B cables are routed in tray a minimum of 25 ft. from the barriered conduit. The spatial separation, the height above the floor, the routing of one train of cables in conduit with a one -hour, fire -rated barrier and considering the limited in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III.G.2.c "in addition to 1 hour fire barrier, and automatic fire suppression system shall be installed", has been approved. 2a. Control Room Air Conditioning The non-safety related chilled water system, which is powered from a non -safety related power supply, is normally running and aligned to either the A Train or the B Train Control Building Air Conditioning System fan unit. During normal plant operation, with the non -safety subsystem aligned for Control Room cooling on the B Train fan unit, the control switch on the MCB for the safety related train will be aligned for AUTO operation. On a loss of offsite power, the non -safety chilled water subsystem will be shut down and an automatic start sequence will be initiated via the emergency diesel generator load sequencer to restart the AC unit and start the B Train safety chiller. In the event the B Train of the CBA fails to start, operator actions, prompted by high Control Room temperature, are assumed to secure the failed chiller and associated equipment and start the A Train. All controls for the recovery are in the Control Room. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-94 3. Process Protection Cabinet MM -CP-13 The power cable for the PPC cabinet MM -CP-13 is routed through this fire area. The loss of power to this cabinet will prevent opening of valves RC -V22 and RC-V87. These valves are required to be opened for cooldown below 350F when the RH System is placed in operation. Should the cable damage be such that valves cannot be operated from the MCR, the affected portion of the circuit can be isolated at the RSS panel in the Train B switchgear room (Fire Area: CB-F-1B-A) and the valves repositioned for safe shutdown. The safe shutdown requirements are satisfied.

4. Process Control Cabinet MM

-CP-297B The power cable for PCC cabinet MM -CP-297B is routed through this fire area. The loss of power to this cabinet will result in loss of CST level transmitter FW-LT-4257 and emergency feedwater flow transmitters FW -FT-4224-2 and FW-FT-4244-2. The Train A CST level transmitter FW -LT-4252 is not affected by a fire in this area. Additionally, the emergency feedwater flow to two steam generators will be available along with steam generator level for all four steam generators. The Appendix R separation requirements are satisfied.

5. Reactor Vent Valve RC

-FV-2881 A cable for the normally closed, fail closed valve RC -FV-2881 is routed through this fire area. The spurious opening of this valve will not prevent safe shutdown as functionally redundant valve RC -V323 is normally closed and has no cables, controls, or equipment in this fire area so it cannot spuriously open. The Appendix R separation requirements are satisfied.

6. Emergency Feedwater Pump Control Valves FW

-FV-4214B, FW -FV-4224B, FW-FV-4234B, FW -FV-4244B These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-95 7. Pressurizer Power Operated Relief Valve (PORV) RC -PCV-456B A cable for RC -PCV-456B is routed in this area. Failure of this cable cannot cause the PORV to spuriously open, so the RCS pressure boundary is maintained. The safe shutdown requirements are satisfied. C. Evaluation Deviations from Appendix R, Paragraph III.G.2, separation requirements exist in the Control Building El. 50 '-0" for the CBA System and have been discussed and analyzed above. A deviation from Appendix R, Paragraph III.G.2.c, "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", is requested. These deviations are justified based on the analysis and our assertion that additional modifications would not enhance fire protection safety. For the remainder of the systems affected in this analysis, the safe shutdown requirements and the Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-96 Tabulation 3.2.7.11 Control Building - El. 75' -0" Fire Area - CB-F-3A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable Cables for all systems required for Train A Safe Shutdown. Cables for all systems required for Train B Safe Shutdown. B. Analysis This area contains cables for redundant equipment required for safe shutdown. For a fire in this area, the operators will proceed with a controlled evacuation of the MCR and establishment of control from the RSS facilities. Details of the systems and equipment required for the alternative safe shutdown utilizing the RSS facilities are contained in Section 3.3. C. Evaluation The use of the RSS facilities satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-97 Tabulation 3.2.7.12 Control Building - El. 75' -0" Fire Area - CB-F-3B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CBA-CP-177 x x CBA-CP-178 x x CBA-DP-26A x x CBA-DP-26B x x CBA-E-230A x CBA-E-230B x CBA-FN-14A x x CBA-FN-14B x x CBA-FN-211A x CBA-FN-211B x CBA-DP-52 x x CBA-PDS-21206 A1/A2 x CBA-PDS-21206 B1/B2 x CBA-PDSH-5305 x x CBA-TCV-21200B x x CBA-PDSH-5306 x x CBA-TC-21200B x CBA-TCV-21200A x x CBA-TC-21200A x DG-CP-79 x DG-CP-80 x MM-CP-152A x MM-CP-153 x MM-CP-297A x MM-CP-297B x B. Analysis This area contains cables for redundant equipment required for safe shutdown. For a fire in this area, the operators will proceed with a controlled evacuation of the MCR and establishment of control from the RSS facilities. The main control room may also become uninhabitable because of smoke from a fire in this area. Details of the systems and equipment required for the alternative safe shutdown utilizing the RSS facilities are contained in Section 3.3. C. Evaluation The use of the RSS facilities satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-98 Tabulation 3.2.7.13 Control Building - El. 75' -0" Computer Room Fire Area - CB-F-3C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-99 Tabulation 3.2.7.14 This page intentionally left blank.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-100 Tabulation 3.2.7.15 Control Building - Stairwell Fire Area - CB-F-S1-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-101 Tabulation 3.2.7.16 Control Building - Stairwell Fire Area - CB-F-S2-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-102 Tabulation 3.2.7.17 Containment Enclosure Fan Area And Containment Annulus / Mechanical Penetration Area Fire Area - CE-F-l-Z, PP-F-1A-Z, PP-F-1B-Z, PP-F-2A-Z, PP-F-2B-Z, PP-F-3A-Z, PP-F-3B-Z, PP-F-4B-Z, PP-F-5B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-V175 x x CC-V122 x x CC-V257 x x CC-V168 x x CC-V1101 x x CC-V1092 x x CC-V1109 x x CC-V1095 x x CS-V142 x x CS-V143 x x CS-V154 x x CS-V158 x x CS-V162 x x CS-V166 x x CS-V167 x x EAH-AC-2A x EAH-AC-2B x EAH-FN-5A x x EAH-FN-5B x x EAH-FN-31A x x EAH-FN-31B x x EAH-DP-3A x x EAH-DP-3B x x EAH-DP-25A x x EAH-DP-25B x x EDE-TBX-YC3 x x EDE-TBX-YB3 x x PAH-DP-35B x x PAH-DP-36B x x RC-FV-2894 x x RC-FV-2896 x x RC-V23 x RC-V22 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-103 Containment Enclosure Fan Area And Containment Annulus / Mechanical Penetration Area Fire Area - CE-F-l-Z, PP-F-1A-Z, PP-F-1B-Z, PP-F-2A-Z, PP-F-2B-Z, PP-F-3A-Z, PP-F-3B-Z, PP-F-4B-Z, PP-F-5B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RC-V88 x RC-V87 x RH-V14 x x RH-V26 x x RH-V70 x x RH-V32 x x RH-V35 x RH-V36 x EDE-TBX-Y32 x x EDE-TBX-Y35 x x CBS-V8 x x CBS-V14 x x SI-V138 x x SI-V139 x x SI-PT-937 x x SI-PT-936 x x B. Analysis 1. General Area Analysis

a. Mechanical Penetration Area (PP

-F-XX-Z) The mechanical penetration area is a Class 1 concrete structure which for safe shutdown has a primary purpose of protecting the containment isolation valves for component cooling, charging pumps and RHR. The area is sectioned into compartments, separated by concrete walls, with small openings for access. This configuration would most probably limit a fire caused by transient combustibles to one zone in the area. The area contains no in situ combustibles with the exception of cable in trays. Only Train A safe shutdown cables are routed in trays. All Train B safe shutdown cables are in conduits. Personnel access to the radioactive areas will be limited to operator tours. Detectors are provided throughout the area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-104 b. Containment Fan Enclosure Area and Containment Annulus (CE -F-l-Z) The containment fan enclosure area is a Class 1 concrete structure which for safe shutdown has a primary function of providing protection for the redundant cooling and air handling equipment for the RHR, CBS, SI equipment vaults; the charging pump rooms; and the mechanical penetration area. The area is approximately 112 feet long by 21 feet wide by 29'-6" high with a floor area of 3000 sq. ft. and volume of 90,000 cu. ft. The in situ combustibles consist of cables in trays and charcoal in filters and fiberglass ladders. There are a total of seven cable trays which are stacked four high for the Train A trays and three high for the Train B trays. The bottom tray in each stack is an enclosed instrumentation cable tray. The trays are a minimum of 13'-6" above the floor. There is approximately 275 lineal ft. of uncovered cable tray containing a total of 80 cables. With the exception of three cables, the Train B cables for the fans are routed in one -hour, fire-rated barriered conduits from the point where they enter the area to the equipment. The charcoal filters which contain 1050 lbs. of charcoal each are not required for safe shutdown nor are they within 30 ft. of the cooling units. The units have an early fire detection system internal to the units. Detectors are provided throughout the area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-105 2. System/Equipment Analysis

a. Component Cooling Isolation Valves CC

-V175, CC-V257, CC-V122, CC-V168 The redundant component cooling containment isolation valves CC -V175, CC-V257, CC-V122 and CC -V168 are located in proximity. These valves are normally open and remain open for safe shutdown. The valves are provided with dual coil solenoids that must be energized to close the valves. The operators can prevent spurious operation by tripping the power supply breakers at the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). It should be noted, however, that these valves are required to remain operable only for containment entry when manual operation of the safety injection isolation valves SI -V3, SI-V17, SI-V32 and SI -V47 and the reactor coolant - RHR isolation valves RC-V22, RC-V23, RC-V87 and RC -V88 is required. Cables for these valves are not routed through this fire area; hence the valves would be operable from the main control room or the RSS control panels and containment entry would not be required. The safe shutdown requirements are satisfied.

b. Thermal Barrier Containment Isolation Valves CC

-V1101, CC -V1109, CC-V1092, CC -V1095 The redundant thermal barrier containment isolation valves CC -V1101, CC-V1109, CC -V1092, CC -V1095 are located in the same fire area. The redundant valves are in separate fire zones separated by a concrete wall. These valves are normally open and remain open for safe shutdown. The operators will prevent spurious operation of more than one valve by tripping the power supply breakers for these valves at the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-106 c. Charging Line Isolation Valves CS -V142, CS-V143 The redundant charging line isolation valves CS -V142 and CS -V143 are located in the same fire area. These valves are normally open and at least one valve is required to be closed for safe shutdown. The functionally redundant valve CS -HCV-182 is not located in this fire area; hence, it can be closed to isolate the normal charging line. The Appendix R separation requirements are satisfied.

d. Seal Injection Isolation Valves: CS

-V154, CS-V158, CS-V162, CS-V166 and High Head Injection Valves SI -V138, SI-V139 Under normal conditions, the seal injection isolation valves CS -V154, CS-V158, CS-V162 and CS -V166 are utilized for the seal injection flow path. Spurious closure of one of these valves will not prevent safe shutdown. The operators will prevent further spurious operations by tripping the power supply breakers in the Train A switchgear room (Fire Area: CB-F-1A-A). The high head injection valves SI -V138 and SI -V139 are normally closed valves which may be opened to provide a redundant hot standby charging path. If the seal injection path is available, the position of these valves during hot standby is inconsequential. On cooldown, the operators will either close or maintain closed the high head injection path. If the high head injection path cannot be isolated, a capability is provided to manually align and throttle the charging pumps to the seal injection flow paths. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-107 e. RC Pump Seal Water Isolation Valve CS -V167 Valve CS-V167 is a normally open valve that should remain open for safe shutdown. Spurious isolation of the Train A valve could result in loss of inventory through the upstream relief valve. This inventory is directed to the PRT and is, therefore, non -recoverable. To preclude this loss of inventory, functionally redundant isolation capability is provided by the RC pump seal return lines by means of Train A valves CS -V10, CS-V28, CS-V44 and CS -V59 and the excess letdown line by means of normally closed, fail closed valves CS -V175 or CS -V176. The cables, controls and equipment required for operation of valves CS -V10, CS-V28, CS-V44, CS-V59, CS-V175 and CS -V176 are not contained in this fire area. The Appendix R separation requirements are satisfied.

f. Containment Enclosure Cooling Units EAH

-AC-2A, EAH-AC-2B; Fans EAH-FN-5A, EAH-FN-5B; Dampers EAH -DP-3A, EAH-DP-3B and Terminal Boxes EDE -TBX-YC3, EDE-TBX-YB3 The redundant cooling units EAH -AC-2A and EAH -AC-2B are totally enclosed fiberglass insulated steel units which house the motor, fan and cooling coils. The units are separated by 8 ft. of clear space and the fan motors EAH -FN-5A and EAH -FN-5B are approximately 25 ft. apart. During normal operation only one cooling unit is required to operate. An analysis has shown that a worst case fire caused by burning five (5) gallons of heptane between the cooling units can affect potentially one cooling unit. All Train B cables required for operation of the cooling unit EAH -AC-2B are routed in one -hour, fire -rated barriered conduits from the rated fire wall where they enter the fire area to the equipment. The spatial separation, the routing of one train of cables in a conduit with a one-hour, fire -rated barrier, the limited in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-108 g. Containment Enclosure Return Fans EAH -FN-31A, EAH-FN-31B and Dampers EAH -DP-25A and EAH -DP-25B. The redundant return fans EAH -FN-31A and EAH -FN-31B are located 20 ft. above the floor and are an integral part of the HVAC ducts (one in each duct). These fans are required to maintain the equipment vaults habitable for entry if manual operations are required to place RHR into operation for cold shutdown. A fire in the containment enclosure fire zone CE -F-1-Z will not prevent operation from the MCR of any equipment necessary for RHR operation; hence, habitability of the equipment vaults is not required. Analysis and field testing has confirmed that the containment enclosure supply fan EAH -FN-5A or EAH -FN-5B is sufficient to maintain the equipment vaults below the equipment 's qualified temperatures. The safe shutdown requirements are satisfied.

h. Containment Enclosure Isolation Damper, PAH

-DP-35B, PAH-DP-36B Cables for dampers PAH -DP-35B and PAH -DP-36B are routed through this area. Under normal operation both dampers are open. If both dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in the recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. Independent operation of either damper (one open and one closed) could cause an air flow problem in EAH system. This assumes that both redundant dampers (PAH -DP-35A and PAH -DP-36A) are in their normal open position since they would not be affected by a fire in this area. Both dampers are powered from a single Train B power supply. The circuit design is such that a spurious signal will cause both dampers to operate together, either both open (normal mode) or both closed (recirculation mode). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-109 i. RHR Isolation Valves RC -V22, RC-V23, RC-V87, RC-V88 and Sample Valves RC -FV-2894, RC-FV-2896 Redundant cables associated with the position indicating lights for the RHR isolation valves are contained in this area. Failure of these circuits will not prevent the operators from opening the valves for entry into cold shutdown. Although this indication is desirable, other means are available to confirm RH system operability (e.g. RH Pump Flow). The safe shutdown requirements are satisfied.

j. H Pump to Cold Leg Isolation Valves RH

-V14, RH-V26 Valves RH -V14 and RH -V26 are normally open valves which are required to remain open for RH systems operation (cold shutdown). These valves and their related cables are in proximity. If either valve spuriously closes, the operators will prevent further spurious operation of the redundant valve by tripping the power supply breakers in either the Train A or Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

k. RH Pump to Hot Leg Isolation Valves RH

-V70, RH-V32 Valves RH -V70 and RH -V32 are normally closed valves which are required to remain closed for RH system operation (cold shutdown). These valves and their related cables are in proximity. If either valve spuriously opens, the operators will prevent further spurious operation of the redundant valve by tripping the power supply breakers in either the Train A or Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-110 l. RH Heat Exchanger to CS/SI Pump Isolation Valves RH-V35, RH-V36, Containment Sump Isolation Valves CBS -V8, CBS-V14 and Terminal Boxes EDE -TBX-Y32, EDE-TBX-Y35 Cables for the redundant valves RH -V35 and RH -V36 are routed in proximity to one another. Valves RH -V35 and RH -V36 are normally closed and their position is inconsequential during all modes of plant operation with the exception of cooldown below 350F when the RH system is placed in operation. At that time it is necessary to assure that the valves remain closed. Should one of the valves open spuriously the operators can disable its power supply in either the Train A or Train B switchgear rooms (Fire Areas: CB -F-1A-A or CB-F-1B-A) and manually reposition the valves located in the equipment vaults (Fire Zone RHR-F-4B-Z or RHR-F-2-A-Z). Manual operation of the valves can be delayed as much as 9 hours into the event. Therefore, no fire protection other than the existing separation is needed. The provision of a capability to mitigate the spurious operation of the valves outside the fire area satisfies the safe shutdown requirements.

m. Containment Pressure Transmitters SI

-PT-936, SI-PT-937 Redundant channels of containment pressure instruments and cables are located in proximity. Spurious operation of these channels will initiate containment spray and containment isolation Phase B. The operators will have the capability to terminate these protective actions by use of manual reset switches. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -1F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-111 C. Evaluation Deviations from the Appendix R, Paragraph III.G.2 separation requirements exist in the containment fan enclosure area and the mechanical penetration area, and have been discussed and analyzed above. A deviation for Appendix R, Paragraph III G.2c, "in addition to a 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved. These deviations are justified based on the analysis and our assertion that additional modifications would not enhance fire protection safety.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-112 Tabulation 3.2.7.18 Condensate Storage Tank Fire Area - CST-F-1-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CO-LT-4096 x x CO-TK-25 x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area EFW -F-l-A. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-113 Tabulation 3.2.7.19 This page intentionally left blank.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-114 Tabulation 3.2.7.20 This page intentionally left blank.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-115 Tabulation 3.2.7.21 Cooling Tower - El. 22'-0" Fire Area - CT-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-MCC-641 x x EDE-SWG-6 x SW-P-41B x SW-P-41D x SW-V25 x B. Analysis All equipment and cables are Train B. Thus Train B service water supplied either by the service water pumps or cooling tower pumps are not available due to a fire in this area. The redundant Train A equipment and cables are in Fire Area CT -F-1D-A, separated from this area by a 3 -hour fire wall. Train A service water, normally supplied by Train A service water pump is available. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-116 Tabulation 3.2.7.22 Cooling Tower - El. 22'-0" Fire Area - CT-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-MCC-513 x x SW-FN-51A x SW-P-41A x SW-P-41C x SW-P-110A x SW-V54 x SW-V56 x SW-V139 x SWA-DP-64B x SWA-DP-66 x SWA-FN-64 x SWA-FN-71 x SWA-L-28 x SWA-TSH-5669 x x B. Analysis All equipment and cables are Train A. Thus Train A service water supplied either by the service water pumps or cooling tower pump are not available due to a fire in this area. The redundant Train B equipment and cables are in Fire Area CT -F-1C-A, separated from this area by a 3 -hour fire wall. Train B service water, normally supplied by Train B service water pump is available. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-117 Tabulation 3.2.7.23 This page intentionally left blank

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-118 Tabulation 3.2.7.24 Cooling Tower - El. 46'-0" Fire Area - CT-F-2B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-FN-51A x SW-P-41A x SW-P-41B x SW-P-41C x SW-P-41D x SW-P-110A x x SW-V54 x x SW-V25 x x SW-V55 x SW-V56 x x SW-V139 x SWA-DP-66 x x SWA-FN-64 x x SWA-FN-71 x x SWA-TSH-5667 x x B. Analysis Redundant equipment and cables are located in the same fire area. The plant will normally be operating on service water pumps SW -P-41A, B, C, and D. These pumps are located in the service water pump house which is a separate area (Fire Area: SW -F-1E-Z). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-119 This area contains valves SW -V25 and SW -V54 which are normally closed. The spurious opening of SW -V25 would divert B Train service water flow to the cooling tower thus reducing cooling flow to the diesel generator and PCCW heat exchangers. Spurious opening of SW -V54 would result in the same condition for the A Train service water system. The operators will prevent further spurious operation of the redundant valve by tripping the power supply breakers for EDE -MCC-513 at the 480 Volt Unit Substation E51 (Fire Area: CB -F-1A-A) for SW -V54 and the EDE -US-64 supply breaker at 4160 Switchgear E6 (Fire Area: CB -F-1B-A) for valve SW -V25. Thus, one train of service water capability is assured. Permissive logic for redundant SW pumps could prevent the redundant SW pumps from being started (Note: one pump of each Train is normally running). The operators will prevent spurious operation of the permissive logic by tripping the power supply breakers at the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). This area contains cooling tower fan SW -F-51A, pump SW -P110A, valves SW -V54, SW-V55, SW-V56, SW-V139, fans SWA -FN-64, SWA-FN-71, damper SWA -DP-66 and switch SWA -TSH-5667. The cooling towers are considered a redundant capability which may be utilized for a limited period of time during the year (e.g., tunnel heat treating). Should a fire occur during this time period the operators can utilize the Train B service water pumphouse capability. The cables, controls and equipment required for the Train B service water pumphouse capability are not contained in this fire area. C. Evaluation The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-120 Tabulation 3.2.7.25 Cooling Tower - Fans Fire Area - CT-F-3-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-FN-51A x x SW-V139 x x B. Analysis All equipment and cables are Train A. However, the fire in this area does not affect the Train A or Train B service water pumps and associated equipment (located in Fire Area SW-F-1E-Z) which will normally be operating. Safe shutdown is not affected. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-121 Tabulation 3.2.7.26 Duct Bank - ET To SW-0" Fire Area - DCT-F-1A-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-CP-248 x EDE-MCC-514 x SW-P-41A x SW-P-41C x SW-PT-8272 x SW-PT-8273 x SW-PT-8274 x SW-V2 x SW-V22 x SWA-FN-40A x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area DCT -F-1B-0. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-122 Tabulation 3.2.7.27 Duct Bank - ET To SW Fire Area - DCT-F-1B-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-CP-249 x EDE-MCC-614 x SW-P-41B x SW-P-41D x SW-PT-8282 x SW-PT-8283 x SW-PT-8284 x SW-V29 x SW-V31 x SWA-FN-40B x B. Analysis All equipment and cables are Train B. The redundant Train A equipment and cables are in Fire Area DCT -F-1A-0. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-123 Tabulation 3.2.7.28 Duct Bank - PAB To CT Fire Area - DCT-F-2A-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-MCC-513 x SW-FN-51A x SW-P-41A x SW-P-41C x SW-P-110A x SW-V54 x SW-V56 x SW-V139 x SWA-DP-66 x SWA-FN-64 x SWA-FN-71 x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area DCT -F-2B-0 and other plant fire areas. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-124 Tabulation 3.2.7.29 Duct Bank - PAB To CT Fire Area - DCT-F-2B-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-SWG-6 x SW-P-41B x SW-P-41D x SW-V25 x B. Analysis All equipment and cables are Train B. The redundant Train A equipment and cables are in Fire Area DCT -F-2A-0. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-125 Tabulation 3.2.7.30 Duct Bank - CB to PAB Fire Area - DCT-F-3B-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-P-11B x CC-P-11D x CC-TE-2271 x CC-TV-2271-1 x CC-TV-2271-2 x CC-V122 x CC-V168 x CC-V1092 x CC-V1095 x CS-LCV-112C x CS-LCV-112E x CS-LT-7464 x CS-P-2A (1) (1) CS-P-2B x CS-P-3B x CS-V143 x CS-V197 x EAH-FN-5B x EAH-FN-31B x EDE-SWG-6 x PAH-DP-43B x (1) CS-P-2A and its cables are not actually located in this fire area. However, CS -P-2A is listed because it is potentially affected via a systems interaction. See Analysis Section B.4.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-126 Duct Bank - CB to PAB Fire Area - DCT-F-3B-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable PAH-DP-358 x PAH-FN-42B x RC-V22 x RC-V87 x SI-V139 x SW-P-41B x SW-P-41D x SW-V5 x SW-V18 x SW-V19 x SW-V23 x SW-V25 x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown cables. The redundant Train A safe shutdown cables are located in Fire Area PAB -F-1G-A. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-127 2. Component Cooling Water Pumps CC -P-11B, CC-P-11D and Component Cooling Water Containment Isolation Valves CC -V122, CC-V168 A fire could cause loss of all PCCW to Containment. It should be noted, however, that these valves are required to remain operable only for containment entry when manual operation of the safety injection isolation valves SI -V3, SI-V17, SI-V32 and SI -V47 and the reactor coolant - RHR isolation valves RC-V22, RC-V23, RC-V87 and RC -V88 are required. Cables for these valves are not routed through this fire area; hence, the valves would be operable from the main control room or the RSS control panels and containment entry would not be required. The safe shutdown requirements are satisfied.

3. RHR Isolation Valves RC

-V22, RC-V87 Redundant cables associated with the position indicating lights for the RH R isolation valves are contained in this area. Failure of these circuits will not prevent the operators from opening the valves for entry into cold shutdown. Although this indication is desirable, other means are available to confirm RH System operability (e.g. RH Pump Flow). The safe shutdown requirements are satisfied.

4. Volume Control Tank Isolation Valve CS

-LCV-112C and Charging Pump CS-P-2A & CS-P-2B Volume control tank (VCT) isolation valves CS -LCV-112B & -112C are normally open to provide a suction path from the VCT to the normally operating charging pump (CS -P-2A or -2B). These valves must stay open until RWST valve CS-LCV-112D or -112E is manually opened to provide a charging pump suction path from the RWST, or the boric acid tanks are manually aligned as a charging pump suction source. Spurious closure of a VCT isolation valve caused by a hot short would interrupt suction flow to the operating charging pump causing it to be damaged. If the standby charging pump has cables in the same area then its operation can also be prevented. The result would be no charging system flow. Since this fire area contains cables for CS -LCV-112C and CS -P-2B, this condition is potentially applicable for the system alignment with CS -P-2B the standby pump and CS -P-2A the operating pump.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-128 The CS-LCV-112C circuit design prevents spurious valve closure from hot shorts as follows. The field cable conductors for the motor control center (MCC) contactor close coil circuit are in different cables than the 120 V "hot" circuit conductors eliminating the hot short failure mode within the cables. Cable-to-cable hot shorts need not be postulated for thermoset cable insulation as used at Seabrook. Since CS -LCV-112C will not spuriously close, CS -P-2A as the operating charging pump will not be damaged. Also, the CS -LCV-112C and CS-P-2B cables are routed in separate concrete encased conduits within the duct bank so that one fire can not damage both the valve and the standby pump cables. Since charging flow is available, the safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-129 Tabulation 3.2.7.31 East MUA Fire Area - DCT-F-4A-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-130 Tabulation 3.2.7.32 East MUA Fire Area - DCT-F-4B-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-131 Tabulation 3.2.7.33 East MUA Fire Area - DCT-F-5A-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-132 Tabulation 3.2.7.34 East MUA Fire Area - DCT-F-5B-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-133 Tabulation 3.2.7.35 Duct Bank - SWPH To CW Fire Area - DCT-F-6-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-134 Tabulation 3.2.7.36 Duct Bank - TB To CST Fire Area - DCT-F-7-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CO-LT-4096 x B. Analysis Train A cable is located in this area. The redundant cable and equipment is located in fire area EFW-F-1-A. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-135 Tabulation 3.2.7.37 Diesel Generator Building - El. (-) 16'-0" Fire Area - DG-F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable DG-P-38A x x DG-S-5A x DG-TK-26A x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area DG -F-1B-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-136 Tabulation 3.2.7.38 Diesel Generator Building - El. (-) 16'-0" Fire Area - DG-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable DG-P-38B x x DG-S-5B x DG-TK-26B x B. Analysis All equipment and cables are Train B. The redundant Train A equipment and cables are in Fire Area DG -F-1A-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-137 Tabulation 3.2.7.39 Diesel Generator Building - El. 21'-6" Fire Area - DG-F-2A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CBA-E-230A x CBA-P-434A x CBA-P-435A x DAH-DP-16A x x DAH-FN-25A x DAH-FN-26A x x DAH-TB-5529-1 x x DAH-TE-5529-1 x x DAH-TT-5529-1 x x DAH-CP-295 x x DG-C-2A x x DG-C-18A x x DG-CP-36 x x DG-CP-75A x x DG-CP-75B x x DG-CP-907A x x DG-DG-1A x x DG-P-38A x DG-SKD-17A x x DG-TBX-HF7 x x DG-TK-45A x DG-TK-45B x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-138 Diesel Generator Building - El. 21'-6" Fire Area - DG-F-2A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable ED-I-4 x EDE-MCC-511 x x EDE-SWG-5 x FW-FV-4214A x FW-FV-4224A x FW-FV-4234A x FW-FV-4244A x MM-CP-12 x MM-CP-297A x MM-CP-450A x x MS-PV-3001 x MS-PV-3003 x RC-LCV-459 x RC-PCV-456A x SW-V16 x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown equipment and cables. The redundant Train B equipment and cables are located in fire area DG -F-2B-A. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-139 2. Process Protection Cabinet MM -CP-12 The power cables for the PPC cabinet MM -CP-12 is routed through this fire area. The loss of power to this cabinet will prevent opening of valves RC -V23 and RC-V88. Valve RC -V88 is required to be opened for cooldown below 350F when the RH system is placed in operation. Should the cable damage be such that valves cannot be operated from the MCR, the affected portion of the circuit can be isolated at the RSS panel in the Train A switchgear room (Fire Area: CB -F-1A-A) and the valves repositioned for safe shutdown. The safe shutdown requirements are satisfied.

3. Process Control Cabinet MM

-CP-297A The power cable for PCC cabinet MM -CP-297A is routed through this fire area. The loss of power to this cabinet will result in loss of CST level transmitter FW-LT-4252 and emergency feedwater flow transmitters FW -FT-4214-2 and, FW-FT-4234-2. The Train B CST level transmitter FW -LT-4257 is not affected by a fire in this area. Additionally, the emergency feedwater flow to two steam generators will be available along with steam generator level for all four steam generators. The Appendix R separation requirements are satisfied.

4. Normal Letdown Isolation Valve RC

-LCV-459 Cables for valve RC -LC-459 are routed in this fire area. The cables, controls, and equipment for functionally redundant valve CS -V145 are not contained in this area and; hence, will be available for safe shutdown. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-140 5. Pressurizer Power Operated Relief Valve RC -PCV-456A RC-PCV-456A is a normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V122. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV by tripping its power supply in the Train A switchgear room (Fire Area: CB -F-1A-A). The safe shutdown requirements are satisfied.

6. Control Room Air Conditioning The non-safety related chilled water system, which is powered from a non

-safety related power supply, is normally running and aligned to either the A Train or the B Train Control Building Air Conditioning System fan unit. During normal plant operation, with the non-safety subsystem aligned for Control Room cooling on the A Train fan unit, the control switch on the MCB for the safety related train will be aligned for AUTO operation. On a loss of offsite power, the non -safety chilled water subsystem will be shut down and an automatic start sequence will be initiated via the emergency diesel generator load sequencer to restart the AC unit and start the A Train safety chiller. In the event the A Train of the CBA fails to start, operator actions, prompted by high Control Room temperature, are assumed to secure the failed chiller and associated equipment and start the B Train. All controls for the recovery are in the Control Room. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-141 7. Emergency Feedwater Pump Control Valves FW-FV-4214A, FW -FV-4224A, FW-FV-4234A, FW -FV-4244A These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train A switchgear room (Fire Area: CB -F-1A-A). The safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-142 Tabulation 3.2.7.40 Diesel Generator Building - El. 21'-6" Fire Area - DG-F-2B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CBA-P-434B x CBA-P-435B x DAH-DP-16B x x DAH-FN-25B x DAH-FN-26B x x DAH-TB-5530-1 x x DAH-TE-5530-1 x x DAH-TT-5530-1 x x DAH-CP-296 x x DG-C-2B x x DG-C-18B x x DG-CP-37 x x DG-CP-76A x x DG-CP-76B x x DG-CP-907B x x DG-DG-1B x x DG-P-38B x DG-SKD-17B x x DG-TBX-HF8 x x DG-TK-45C x DG-TK-45D x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-143 Diesel Generator Building - El. 21'-6" Fire Area - DG-F-2B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-MCC-611 x x EDE-SWG-6 x FW-FV-4214B x FW-FV-4224B x FW-FV-4234B x FW-FV-4244B x MM-CP-13 x MM-CP-450B x x MS-PV-3002 x MS-PV-3004 x RC-FV-2881 x RC-PCV-456B x SW-V18 x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A equipment and cables are located in fire area DG -F-2A-A and other fire areas. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-144 2. Process Protection Cabinet MM -CP-13 The power cables for the PPC cabinet MM -CP-13 are routed through this fire area. The loss of power to this cabinet will prevent opening of valves RC -V22 and RC-V87. Valve RC -V22 is required to be opened for cooldown below 350F when the RH System is placed in operation. Should the cable damage be such that the valves cannot be operated from the MCR, the affected portion of the circuit can be isolated at the RSS panel in the Train B switchgear room (Fire Area: CB-F-1B-A) and the valves repositioned for safe shutdown. The safe shutdown requirements are satisfied.

3. Reactor Vent Valve RC

-FV-2881 A cable for the normally closed, fail closed valve RC -FV-2881 is routed through this fire area. The spurious opening of this valve will not prevent safe shutdown as functionally redundant valve RC -V323 is normally closed and has no cables, controls, or equipment in this fire area so it cannot spuriously open. The Appendix R separation requirements are satisfied.

4. Pressurizer Power Operated Relief Valve RC

-PCV-456B RC-PCV-456B is a normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V124. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under this condition, the initial short will not cause depressurization. To prevent subsequent

spurious operations, the operators will de -energize the PORV by tripping its power supply in the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-145 5. Control Room Air Conditioning The non-safety related chilled water system, which is powered from a non -safety related power supply, is normally running and aligned to either the A Train or the B Train Control Building Air Conditioning System fan unit. During normal plant operation, with the non -safety subsystem aligned for Control Room cooling on the B Train fan unit, the control switch on the MCB for the safety related train will be aligned for AUTO operation. On a loss of offsite power, the non -safety chilled water subsystem will be shut down and an automatic start sequence will be initiated via the emergency diesel generator load sequencer to restart the AC unit and start the B Train safety chiller. In the event the B Train of the CBA fails to start, operator actions, prompted by high Control Room temperature, are assumed to secure the failed chiller and associated equipment and start the A Train. All controls for the recovery are in the Control Room. The safe shutdown requirements are satisfied.

6. Emergency Feedwater Pump Control Valve s FW-FV-4214B, FW

-FV-4224B, FW-FV-4234B, FW -FV-4244B These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-146 Tabulation 3.2.7.41 Diesel Generator Building - El. 51'-6" Fire Area - DG-F-3A-Z, DG-F-3B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CBA-E-230A x x CBA-E-230B x x CBA-FN-211A x x CBA-FN-211B x x CBA-P-434A x x CBA-P-434B x x CBA-P-435A x x CBA-P-435B x x CBA-PDS-21202A x x CBA-PDS-21202B x x CBA-PDS-21206 A1/A2 x x CBA-PDS-21206 B1/B2 x x DAH-FN-25A x x DAH-FN-25B x x DAH-FISH-5529 x x DAH-FISH-5530 x x DG-CP-76A x DG-DG-1B x EDE-SWG-6 x MM-CP-13 x RC-LCV-459 x RC-FV-2881 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-147 B. Analysis 1. General Area Analysis The diesel generator mechanical equipment room is a Class 1 area which for safe shutdown has a primary function of providing protection for the redundant air handling equipment for the diesel generator rooms. The area is approximately 86 ft long by 37 ft. wide by 26 ft. high with a floor area of 3200 sq. ft. and volume of 83,000 cu. ft. The in situ combustibles consist of cables in trays, 7 gallons of oil in equipment, and fiberglass ladders. There are a total of six cable trays which run horizontally and vertically through the area. When stacked the trays are run three high with the bottom tray being an enclosed instrumentation cable tray. There is approximately 375 ft. of uncovered cable tray containing a total of approximately 80 cables. Detectors are provided throughout the area. An analysis has shown that a worst case fire caused by burning 3.5 gallons of oil will not affect the operation of the Safe Shutdown equipment.

2. System/Equipment Analysis
a. Main Control Room Cooling CBA

-E-230A, CBA -E-230B, CBA-FN-211A, CBA -FN-211B, CBA -P-434A, CBA -P-435A, CBA-P-434B, CBA -P-435B, CBA -PDS-21202A, CBA -PDS-21202B, CBA-PDS-21206A1/A2, CBA -PDS-21206B1/B2 The redundant control room cooling equipment and cables are located in the same fire area. A fire in this area can cause total loss of this cooling capability. Should this occur, the operators will utilize the evaporator fans CBA-FN-14A, 14B to supply outside air into the control room. These fans and their cables are not in this fire area. An air inlet and exhaust path, utilizing these fans, can be established by opening certain doors in the control room complex which will allow air to enter into the fan intake plenum from the south stairwell and exhaust the control room via the double doors to the turbine building. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-148 b. Diesel Generator Room Cooling DAH-FN-25A, DAH-FN-25B, DAH-FISH-5529, DAH -FISH-5530 The Safe Shutdown cables for the fans and flow switches are routed in barriered conduit from the floor where they enter the area to the equipment (a distance of approximately 20 feet or less). The one -hour, fire -rated barrier is reduced at two locations or stops approximately two feet from the equipment because of access or potential interference. The redundant fans and dampers are separated by approximately 28 feet with the only intervening combustible being approximately 44 cables in three vertical/horizontal Train B trays and approximately 33 cables in two horizontal Train A trays. The Train A and Train B trays are separated by 8 ft. The redundant flow switches and associated conduits are separated by 45 ft. with the above trays containing the only intervening combustibles. The spatial separation, the routing of both trains of cables in separate conduits with a one -hour, fire -rated barrier and the limited in situ combustibles provide acceptable fire protection equivalent to the technical requirements of Appendix R. Note: A deviation was requested and granted for not installing suppression in this location. Since that deviation was granted the following conservative changes have been made, the electrically operated supply dampers have been changed to back draft dampers and the supply fan flow switch interlock with the exhaust fan has been removed. Cables for the flow switch are still routed in barriered conduit because their failure could effect the control circuit for the supply fan. These changes do not adversely effect the basis of the deviation.

c. Diesel Generator Control DG

-CP-76A, DG-DG-1B, EDE-SWG-6 The cables for control panels DG -CP-76A and DG -DG-1B are located in this area. Failure of these cables will render the Train B diesel inoperable from the main control room. The operators can re -establish Train B diesel operability by transferring control to the RSS panel located in the Train B diesel room (Fire Area: DG -F-2B-A). Operation of the diesel from the RSS panel will also allow re -establishing emergency power to EDE-SWG-6 by isolation of the faulted main control room cables. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-149 d. Process Protection Cabinet MM -CP-13 The power cable for the PPC cabinet MM -CP-13 is routed through this fire area. The loss of power to this cabinet will prevent opening of valves RC-V22 and RC -V87. These valves are required to be opened for cooldown below 350F when the RH system is placed in operation. Should the cable damage be such that valves cannot be operated from the MCR, the affected portion of the circuit can be isolated at the RSS panel in the Train B switchgear room (Fire Area: CB -F-1B-A) and the valves repositioned for safe shutdown. The safe shutdown requirements are satisfied.

e. Normal Letdown Isolation Valve RC

-LCV-459 Cables for valve RC -LCV-459 are routed in this fire area. The cables, controls and equipment for functionally redundant valve CS -V145 are not contained in this area and; hence, will be available for safe shutdow

n. The Appendix R separation requirements are satisfied.
f. Reactor Vent Valve RC

-FV-2881 A cable for the normally closed, fail closed valve RC -FV-2881 is routed through this fire area. The spurious opening of this valve will not prevent safe shutdown as functionally redundant valve RC -V323 is normally closed and has no cables, controls, or equipment in this fire area so it cannot spuriously open. The Appendix R separation requirements are satisfied. C. Evaluation Deviations from the Appendix R, Paragraph III.G.2 separation requirements exist in the diesel generator building El. 51 '-6" for the DAH system and have been discussed and analyzed above. A deviation from Appendix R, Paragraph III G.2c, "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved. These deviations are justified based on the analysis and our assertion that additional modifications would not enhance fire protection safety. For the remainder of the systems affected in this analysis, the safe shutdown requirements and the Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-150 Tabulation 3.2.7.42 Diesel Generator Building - El. 51'-6" Fire Area -DG-F-3C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable DG-LS-FLC x x DG-P-38A x DG-TK-46A x DG-TK-78A x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area DG -F-3D-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-151 Tabulation 3.2.7.43 Diesel Generator Building - El. 51'-6" Fire Area -DG-F-3D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable DG-LS-FLC x x DG-P-38B x DG-TK-46B x DG-TK-78B x B. Analysis All equipment and cables are Train B. The redundant Train A equipment and cables are in Fire Area DG -F-3C-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-152 Tabulation 3.2.7.44 Diesel Generator Building - El. 51'-6" Fire Area -DG-F-3E-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable DG-F-36A x DG-MM-8A x B. Analysis There are no safe shutdown cables in this fire area. Only mechanical equipment for DG-A is contained in this fire area. The redundant equipment is contained in fire area DG-F-3F-A. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-153 Tabulation 3.2.7.45 Diesel Generator Building - El. 51'-6" Fire Area -DG-F-3F-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable DG-F-36B x DG-MM-8B x B. Analysis There are no safe shutdown cables in this fire area. Only mechanical equipment for DG-B is contained in this fire area. The redundant equipment is contained in fire area DG-F-3E-A. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-154 Tabulation 3.2.7.46 Diesel Generator Building - Stairwell (N) Fire Area -DG-F-S1-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-155 Tabulation 3.2.7.47 Diesel Generator Building

- Stairwell (S)

Fire Area -DG-F-S2-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-156 Tabulation 3.2.7.48 Emergency Feedwater Pump Building Fire Area - EFP-F-1-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EPA-TSH-5430 x x EPA-TSH-5431 x x EPA-FN-47A x x EPA-FN-47B x x EPA-DP-371 x x EPA-DP-372 x x EPA-DP-373 x x EPA-DP-374 x x MM-IR-49 x x MM-IR-50 x x FW-FT-4214-2 x x FW-FT-4224-2 x x FW-FT-4224-4 x x FW-FT-4214-4 x x FW-FT-4234-2 x x FW-FT-4244-2 x x FW-FT-4244-4 x x FW-FT-4234-4 x x FW-FV-4214A x x FW-FV-4214B x x FW-FV-4224A x x FW-FV-4224B x x FW-FV-4234A x x FW-FV-4234B x x FW-FV-4244A x x FW-FV-4244B x x FW-P-37B x x FW-LT-4252 x x FW-LT-4257 x x FW-V347 x x B. Analysis The emergency feedwater pump building is a Class 1 concrete structure which for Safe Shutdown has a primary function of providing protection for the motor driven feedwater pump and valves. The area is approximately 79 ft. long by 28 ft. wide by 18 ft. high with a floor area of 2400 sq. ft. and a volume of 43,000 cu. ft.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-157 The in situ combustibles consist of six gallons of oil in the turbine drive of emergency feedwater pump FW -P-37A and 27 pounds of plastic in a 10 ft. step and 24 ft. extension ladder. An analysis of the Design basis Fire for this combustible is contained in the "Fire Protection Program Evaluation and Comparison to Branch Technical Position APCSB-9.5-1 Appendix A. All cables are routed in conduit. Detectors are provided throughout the area.

See Section 3.4 for a discussion of the operator response for a fire in this area.

The eight emergency feed pump control valves are separated such that valves FW-FV-4214A, B and FW-FV-4244A, B are separated by 60 feet from valves FW-FV-4224A, B and FW -FV-4234A, B. See Section 3.4 for more discussion of these valves. The redundant fans and dampers are in separate steel enclosures located 11 ft. above the floor, and separated b y 1'-6". The temperature switches are separated by over 20 '. The redundant CST Level transmitters FW -LT-4252 and FW -LT-4257 are separated by 16'. The motor driven emergency feedwater pump and recirculation valve FW -V347 are located in this fire area. For a fire in this area, the start -up feedwater pump FW -P-113 (SUFP) and start -up to EFW valves FW -V156 and FW -V163 will be utilized to satisfy the safe shutdown requirements. The SUFP low suction pressure trip must also be bypassed prior to commencing cooldown. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-158 During no -load and low load plant operations, the SUFP is aligned to non -emergency Bus 4 to provide its startup and shutdown functions. After the SUFP completes its startup function, its power supply will be transferred to emergency Bus E5 as plant power is increased. The SUFP will remain aligned to Bus E5 during 100% power operation. As power is decreased in preparation for a plant shutdown, the SUFP power supply will be transferred back to Bus

4. If the SUFP is required to perform its EFW contingency function in response to a fire that disables the Train B emergency feedwater pump, while aligned to Bus 4 coincident with a loss of offsite power, it will have to be manually transferred to Bus E5 and manually started. SUFP operation will be controlled by operating procedures including selection of the appropriate power supply and verification of adequate power supply capacity prior to starting the SUFP on the emergency diesel generator.

The main control room would not have to be evacuated for a fire in this area; hence, the operators would have the capability to control and monitor all the equipment which is powered from the electrical distribution emergency system and would be required for a safe shutdown. Additional details on the alternative safe shutdown capability are contained in Section 3.4. C. Evaluation A deviation from the requirements of Appendix R, Paragraph III.G.3 requiring the installation of fixed suppression in an area for which alternative safe shutdown capability has been developed exists in the emergency feedwater pump building. This deviation is justified based on our assertion that additional modifications would not enhance plant safety which has been insured by the alternative shutdown capability discussed in Section 3.4 and Tabulation 3.4.3.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-159 Tabulation 3.2.7.49 Electrical Tunnel Fire Area - ET-F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CAH-FN-1C x CAH-FN-1E x CAH-FN-1F x CC-LT-2172-1 x CC-LT-2172-2 x CC-LT-2172-3 x CC-LT-2272-1 x CC-LT-2272-2 x CC-LT-2272-3 x CC-P-322A x CC-V57 x CC-V121 x EDE-MM-582 x x ED-X-14J x x ED-PP-8J x x SA-C-4A x CS-V10 x CS-V28 x CS-V44 x CS-V59 x CS-V145 x RC-LCV-459 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-160 Electrical Tunnel Fire Area - ET-F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RC-LCV-460 x RC-E-10 x RC-PP-6A x x RC-PCV-456A x RC-V122 x RC-V23 x RC-V88 x SI-V159 x SI-V3 x SI-V32 x SI-FV-2482 x SI-FV-2483 x SI-FV-2495 x SI-FV-2496 x RH-V35 x FW-FV-4214A x FW-FV-4224A x FW-FV-4234A x FW-FV-4244A x MS-V86 x MS-V88 x MS-V90 x MS-V92 x MS-PV-3002 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-161 Electrical Tunnel Fire Area - ET-F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MS-PV-3003 x SB-V1 x SB-V3 x SB-V5 x SB-V7 x EAH-FN-174A x EDE-CP-248 x EDE-MCC-514 x EPA-FN-47A x EPA-DP-371 x EPA-DP-373 x SW-P-41A x SW-P-41C x SW-V2 x SW-V22 x SW-PT-8272 x SW-PT-8273 x SW-PT-8274 x SWA-FN-40A x FW-LT-501 x FW-LT-503 x FW-LT-529 x FW-LT-548 x FW-PT-524 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-162 Electrical Tunnel Fire Area - ET-F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-PT-526 x FW-PT-534 x FW-PT-536 x FW-LT-4252 x FW-FT-4214-2 x FW-FT-4224-4 x FW-FT-4234-2 x FW-FT-4244-4 x NI-NE-6690 x NI-NT-6690 x x RC-LT-459 x RC-PT-405 x RC-PT-455 x RC-PT-457 x RC-TE-413A x RC-TE-423A x RC-TE-433A x RC-TE-443A x SI-PT-935 x Electrical Penetrations x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-163 B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown equipment and cables. The redundant Train B safe shutdown equipment and cables are located in fire area ET -F-1C-A. The Appendix R safe shutdown requirements are satisfied.

2. Component Cooling Water Isolation Valves CC

-V57, CC-V121, and Head Tank Level Transmitters CC -LT-2172-1, 2, 3, CC -LT-2272-1, 2, 3 Cables associated with head tank level transmitters which affect the Loop B outboard isolation valves CC -V175 and CC -V257 are routed in the same trays as the Loop A inboard isolation valves CC -V57 and CC -V121. Failures in these cables could cause total loss of PCCW to containment by initiation of a spurious

lo-lo head tank level signal. Loop B PCCW can be re -established by transferring control of valves CC -V175 and CC -V257 to local control at the RSS panel in fire area CB-F-1A-A. This removes the lo -lo head tank level isolation function and allows operators to re -open the valves. The safe shutdown requirements are satisfied.

3. RC Pump Seal Water Isolation Valves CS

-V10, CS-V28, CS-V44, CS-V59 The safe shutdown function of these valves is to isolate seal return in the event that valve CS -V168 spuriously closes due to a fire. As cabling for CS-V168 is not routed through this area, the position of these valves is inconsequential and will not prevent safe shutdown. The safe shutdown requirements are satisfied.

4. Letdown Isolation Valves CS

-V145, RC-LCV-459, RC-LCV-460 Functionally redundant Train A series valves CS -V145, RC-LCV-459 and RC-LCV-460 are normally open and are required to close for safe shutdown. CS-V145 can be closed from the main control room. Should this valve not close due to spurious operation, the operators can close either RC-LCV-459 or RC-LCV-460 by tripping their power supply breakers at the Train A switchgear room (Fire Area: CB -F-1A-A). This will prevent further spurious operation. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-164 5. Charging Pump Test Line Isolation Valve SI-V159 On spurious operation of the normally closed, fail closed valve SI -V159 (Train A), the operators will maintain the normally closed high head injection path valves SI -V138 and SI -V139 closed. Charging will be accomplished utilizing the seal injection flow path through valves CS -FCV-121, CS-V154, CS-V158, CS-V162 and CS -V166. The cables, controls and equipment required for operation of these valves are not contained in the fire area. The capability to provide charging to the RC System through a minimum of one flow path satisfies the safe shutdown requirements.

6. RHR Isolation Valves RC

-V23, RC-V88 RHR isolation valves are permanently disabled in the closed position. For entry into RHR shutdown cooling, valve RC -V88 must be opened. These valves are not required until 9 hours into the event. This can be accomplished manually by entry into containment, if required. The safe shutdown requirements are satisfied.

7. Emergency Feedwater Pump Control Valves FW

-FV-4214A, FW -FV-4224A, FW-FV-4234A, FW-FV-4244A These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train A switchgear room (Fire Area: CB -F-1A-A). The safe shutdown requirements are satisfied.

8. Main Steam Isolation Valves MS

-V86, MS-V88, MS-V90, MS-V92 Failure of the Train A cables will not prevent safe shutdown as the redundant Train B cables required for MSIV closure are routed in Fire Area ET -F-1C-A. The Appendix R separation requirements are satisfied.

9. Not used SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-165 10. Atmospheric Relief Valves MS

-PV-3002, MS-PV-3003 and Associated Solenoids Valves MS -PV-3002 and MS -PV-3003 are normally closed valves. A fire would prevent operation of the Train A capabilities provided for opening and closing these valves. However, the fire would not affect the Train B capabilities and the valves will be operable for safe shutdown. Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affected air solenoids will be de -energized from the distribution panels located in Train A switchgear room (Fire Area: CB -F-1A-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

11. Tower Actuation Logic Pressure Transmitters SW

-PT-8272, SW-PT-8273, SW-PT-8274 Failure in this cable could initiate a spurious tower actuation signal which would transfer Train A service water cooling capability from the pumphouse to the cooling towers. This transfer will not significantly interrupt Train A service Water cooling nor will it have any impact on Train B service water. This failure does not prevent safe shutdown. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-166 12. Main Steam Pressure Transmitters FW -PT-524, FW-PT-526, FW-PT-534, FW-PT-536 Redundant channels of main steam pressure cables are located in proximity. Spurious operation of the channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after 1 minute by use of the manual reset block switch and terminate the containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CS -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

13. Steam Generator Level Transmitters FW

-LT-501, FW-LT-503, FW-LT-529, FW-LT-548 Cables for transmitters FW -LT-501, FW-LT-503, FW-LT-529, FW-LT-548 are located in the same fire area. A Fire could cause loss of indication for all four steam generators. However, the same fire would not affect the redundant level transmitters FW -LT-502, FW-LT-504, FW-LT-519 and FW -LT-537. The Appendix R separation requirements are satisfied.

14. Emergency Feedwater Flow Transmitters FW

-FT-4214-2, FW-FT-4224-4, FW-FT-4234-2, FW-FT-4244-4 Failure in this cable could cause spurious closure of one emergency feedwater line. The logic will prevent isolation of additional lines. This leaves three steam generators available for heat removal; hence, safe shutdown is not affected. Although, failure in this cable could also cause loss of flow indication on two emergency feedwater lines, steam generator operability can be monitored by use of SG level indication. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-167 15. Condensate Storage Tank Level FW-LT-4252 All cables are Train A. The Train B level transmitter FW -LT-4257 will be available. In addition, the cables for CST level transmitter CO -LT-4096 are not routed through this area. The safe shutdown requirements are satisfied.

16. Pressurizer Pressure Transmitters RC

-PT-455, RC-PT-457 Redundant channels of pressurizer pressure cables are located in proximity. Spurious operation of two channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after 1 minute by use of the manual reset and block switch and terminate the containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B Switchgear Rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

17. Reactor Coolant Temperature Elements RC

-TE-413A, RC-TE-423A, RC-TE-433A, RC-TE-443A All hot leg RC temperature element cables are routed through this area; however,

this function can also be performed by the Train B incore thermocouples IC-TE-XX. The cables for these thermocouples are routed through the Train B electrical tunnel (Fire Area: ET -F-1C-A). The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-168 18. Pressurizer Relief Valves RC -PCV-456A, RC-V122 RC-PCV-456A is a normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V122. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV and the block valve by tripping their power supplies in the Train A switchgear room (Fire Area:

CB-F-1A-A). The safe shutdown requirements are required.

19. Containment Pressure Transmitter SI

-PT-935 A cable for one channel of containment pressure instrumentation is routed through this fire area. This channel inputs to 2 out of 3 and 2 out of 4 logics which initiate protective actions. A spurious signal from one channel is not sufficient to initiate the logic and perform the protective action; hence, a failure in this cable will not prevent safe shutdown. The safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-169 Tabulation 3.2.7.50 Electrical Tunnel Fire Area - ET-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CAH-FN-1C x CAH-FN-1E x CAH-FN-1F x CC-LT-2172-1 x CC-LT-2172-2 x CC-LT-2172-3 x CC-LT-2272-1 x CC-LT-2272-2 x CC-LT-2272-3 x CC-P-322A x CC-V57 x CC-V121 x ED-X-14J x SA-C-4A x CS-V10 x CS-V28 x CS-V44 x CS-V59 x CS-V145 x RC-LCV-459 x RC-LCV-460 x RC-E-10 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-170 Electrical Tunnel Fire Area - ET-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RC-PCV-456A x RC-V122 x RC-V23 x RC-V88 x SI-V138 x SI-V159 x SI-V3 x SI-V32 x SI-FV-2482 x SI-FV-2483 x SI-FV-2495 x SI-FV-2496 x RH-V35 x FW-FV-4214A x FW-FV-4224A x FW-FV-4234A x FW-FV-4244A x FW-V156 x MS-V86 x MS-V88 x MS-V90 x MS-V92 x MS-PV-3001 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-171 Electrical Tunnel Fire Area - ET-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MS-PV-3002 x MS-PV-3003 x MS-PV-3004 x SB-V1 x SB-V3 x SB-V5 x SB-V7 x EAH-FN-174A x EDE-CP-248 x EDE-MCC-514 x EPA-FN-47A x EPA-DP-371 x EPA-DP-373 x SW-P-41A x SW-P-41C x SW-V2 x SW-V22 x SW-PT-8272 x SW-PT-8273 x SW-PT-8274 x SWA-FN-40A x FW-LT-501 x FW-LT-503 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-172 Electrical Tunnel Fire Area - ET-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-LT-529 x FW-LT-548 x FW-PT-514 x FW-PT-524 x FW-PT-526 x FW-PT-534 x FW-PT-536 x FW-PT-544 x FW-LT-4252 x FW-FT-4214-2 x FW-FT-4224-4 x FW-FT-4234-2 x FW-FT-4244-4 x NI-NE-6690 x RC-LT-459 x RC-PT-405 x RC-PT-455 x RC-PT-457 x RC-TE-413A x RC-TE-423A x RC-TE-433A x RC-TE-443A x SI-PT-935 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-173 B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown equipment and cables. The redundant Train B safe shutdown equipment and cables are located in fire area ET -F-1C-A. The Appendix R safe shutdown requirements are satisfied.

2. Component Cooling Water Isolation Valves CC

-V57, CC-V121 and Head Tank Level Transmitters CC -LT-2172-1, 2, 3, CC -LT-2272-1, 2, 3 Cables associated with head tank level transmitters which affect the Loop B outboard isolation valves CC -V175 and CC -V257 are routed in the same trays as the Loop A inboard isolation valves CC -V57 and CC -V121. Failures in these cables could cause total loss of PCCW to containment by initiation of a spurious lo-lo head tank level signal. Loop B PCCW can be re -established by transferring control of valves CC -V175 and CC -V257 to local control at the RSS panel in fire area CB-F-1A-A. This removes the lo -lo head tank level isolation function and allows operators to re -open the valves. The safe shutdown requirements are satisfied.

3. RC Pump Seal Water Isolation Valves CS

-V10, CS-V28, CS-V44, CS-V59 The safe shutdown function of these valves is to isolate seal return in the event that valve CS-V168 spuriously closes due to a fire. As cabling for CS -V168 is not routed through this area, the position to these valves is inconsequential. The safe shutdown requirements are satisfied.

4. Letdown Isolation Valves CS

-V145, RC-LCV-459, RC-LCV-460 Functionally redundant Train A series valves CS -V145, RC-LCV-459 and RC-LCV-460 are normally open and are required to close for safe shutdown. CS-V145 can be closed from the main control room. Should this valve not close due to spurious operation, the operators can close either RC -LCV-459 or RC-LCV-460 by tripping their power supply breakers at the Train A switchgear room (Fire Area: CB -F-1A-A). This will prevent further spurious operation. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-174 5. Charging Pump Test Line Isolation Valve SI -V159 On spurious operation of the normally closed, fail closed valve SI -V159 (Train A), the operators will maintain the normally closed high head injection path valves SI -V138 and SI -V139 closed. Charging will then be accomplished utilizing the seal injection path through valves CS -FCV-121, CS-V154, CS-V158, CS-V162 and CS -V166. The cables, controls and equipment required for operation of these valves are not contained in the fire area. The capability to provide charging to the RC system through a minimum of one flow path satisfies the safe shutdown requirements.

6. RHR Isolation Valves RC

-V23, RC-V88 RHR isolation valves are permanently disabled in the closed position. For entry into RHR shutdown cooling, valve RC -V88 must be opened. These valves are not required until 9 hours into the event. This can be accomplished manually by entry into containment, if required. The safe shutdown requirements are satisfied.

7. Emergency Feedwater Pump Control Valves FW

-FV-4214A, FW-FV-4224A, FW-FV-4234A, FW -FV-4244A These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train A switchgear room (Fire Area CB -F-1A-A). The safe shutdown requirements are satisfied.

8. Not used 9. Main Steam Isolation Valves MS

-V86, MS-V88, MS-V90, MS-V92 Failure of the Train A cables will not prevent safe shutdown as the redundant Train B cables required for MSIV closure are routed in Fire Area ET -F-1C-A. The Appendix R separation requirements are satisfied.

10. Not used SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-175 11. Atmospheric Relief Valves MS

-PV-3001, MS-PV-3002, MS-PV-3003, MS-PV-3004 Valves MS -PV-3001, MS-PV-3002, MS-PV-3003 and MS -PV-3004 are normally closed valves. A fire would prevent operation of the Train A capabilities provided for opening and closing these valves. However, the fire would not affect the Train B capabilities and the valves will be operable for safe shutdown. Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affected air solenoids will be de -energized from the distribution panel located in Train A switchgear room (Fire Area: CB -F-1A-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

12. Tower Actuation Logic Pressure Transmitters SW

-PT-8272, SW-PT-8273, SW-PT-8274 Failure in this cable could initiate a spurious tower actuation signal which would transfer Train A service water cooling capability from the pumphouse to the cooling towers. This transfer will not significantly interrupt Train A service water cooling nor will it have any impact on Train B service water. This failure does not prevent safe shutdown. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-176 13. Main Steam Pressure Transmitters FW -PT-514, FW-PT-524, FW-PT-526, FW-PT-534, FW-PT-536, FW-PT-544 Redundant channels of main steam pressure cables are located in proximity. Spurious operation of the channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after one (1) minute by use of the manual reset and block switch and terminate the containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear room (Fire Areas: CB -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

14. Steam Generator Level Transmitters FW

-LT-501, FW-LT-503, FW-LT-529, FW-LT-548 Cables for transmitters FW -LT-501, FW-LT-503, FW-LT-529 and FW -LT-548 are located in the same fire area. A fire could cause loss of indication for all four steam generators. However, the same fire would not affect the redundant level transmitters FW -LT-502, FW-LT-504, FW-LT-519 and FW -LT-537. The Appendix R separation requirements are satisfied. 15. Emergency Feedwater Flow Transmitter FW -FT-4214-2, FW-FT-4234-2 Failure in this cable could cause spurious closure of one emergency feedwater line. The logic will prevent isolation of additional lines. This leaves three steam generators available for heat removal; hence, safe shutdown is not affected. Although failure in this cable could also cause loss of flow indication on two emergency feedwater lines, steam generator operability can be monitored by use of SG level indication. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-177 16. Condensate Storage Tank Level FW -LT-4252 All cables are Train A. The Train B level transmitter FW -LT-4257 will be available. In addition, the cables for CST level transmitter CO -LT-4096 are not routed through this area . The Appendix R separation requirements are satisfied.

17. Pressurizer Pressure Transmitters RC

-PT-455, RC-PT-457 Redundant channels of pressurizer pressure cables are located in proximity. Spurious operation of two channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after 1 minute by use of the manual reset and block switch and terminate the containment isolation by use to the manual reset switch. All ESF equipment

which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

18. Reactor Coolant Temperature Elements RC

-TE-413A, RC-TE-423A, RC-TE-433A, RC-TE-443A All hot leg RC temperature element cables are routed through this area; however, this function can also be performed by the Train B incore thermocouples

IC-TE-XX. The cables for these thermocouples are routed through the Train B electrical tunnel (Fire Area: ET -F-1C-A). The Appendix R separation requirements are satisfied.

19. Containment Pressure Transmitter SI

-PT-935 A cable for one channel of containment pressure instrumentation is routed through this fire area. This channel inputs to 2 out of 3 and 2 out of 4 logics which initiate protective actions. A spurious signal from one channel is not sufficient to initiate the logic and perform the protective action; hence, a failure in this cable will not prevent safe shutdown. The safe shutdown requirements are satisfied. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-178 20. Pressurizer Relief Valves RC -PCV-456A, RC-V122 RC-PCV-456A is normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V122. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV and the block valve by tripping their power supplies in the Train A switchgear room (Fire Area:

CB-F-1A-A). The safe shutdown requirements are satisfied.

21. High Head Safety Injection Valve SI

-V-138 SI-V-138 is a normally closed valve which may be opened to provide a redundant hot standby charging path. The functionally redundant Train B valve SI -V-139 is available to perform this function. Should SI -V-138 spuriously open, the charging pump may have to be stopped to prevent overfill of the pressurizer. The safe shutdown requirements are satisfied. C. EVALUATION The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-179 Tabulation 3.2.7.51 Electrical Tunnel Fire Area - ET-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CAH-FN-1A x CAH-FN-1B x CAH-FN-1D x CC-LT-2192-1 x CC-LT-2192-2 x CC-LT-2192-3 x CC-LT-2292-1 x CC-LT-2292-2 x CC-LT-2292-3 x CC-P-322B x CC-V122 x CC-V256 x EDE-MM-584 x x ED-PP-8B x ED-X-16A x SA-C-4B x CS-V168 x CS-V175 x CS-V176 x RC-FV-2881 x RC-V323 x RC-E-10 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-180 Electrical Tunnel Fire Area - ET-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RC-PP-6B x x RC-PCV-456B x RC-V124 x RC-V23 x RC-V22 x RC-V88 x RC-V87 x SI-V158 x SI-V17 x SI-V47 x SI-FV-2475 x SI-FV-2476 x SI-FV-2477 x SI-FV-2486 x RH-V36 x FW-FV-4214B x FW-FV-4224B x FW-FV-4234B x FW-FV-4244B x FW-P-37B x FW-V347 x MS-V88 x MS-V90 x MS-PV-3002 x MS-PV-3003 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-181 Electrical Tunnel Fire Area - ET-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EAH-FN-174B x EDE-CP-249 x EDE-MCC-614 x EPA-FN-47B x EPA-DP-372 x EPA-DP-374 x SW-P-41B x SW-P-41D x SW-V29 x SW-V31 x SW-PT-8282 x SW-PT-8283 x SW-PT-8284 x SWA-FN-40B x FW-LT-502 x FW-LT-504 x FW-LT-519 x FW-LT-537 x FW-PT-525 x FW-PT-535 x FW-LT-4257 x FW-FT-4214-4 x FW-FT-4224-2 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-182 Electrical Tunnel Fire Area - ET-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-FT-4234-4 x FW-FT-4244-2 x NI-NE-6691 x NI-NT-6691 x x RC-LT-460 x RC-PT-405 x x RC-PT-403 x x RC-PT-456 x RC-PT-458 x IC-TE-XX x MM-CP-486B x RC-TE-413B x RC-TE-423B x RC-TE-433B x RC-TE-443B x SI-PT-935 x x SI-PT-934 x x Electrical Penetrations x x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A safe shutdown equipment and cables are located in fire area ET -F-1A-A. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-183 2. Component Cooling Water Isolation Valves CC -V176, CC-V256 and Head Tank Level Transmitters CC -LT-2192-1, 2, 3, CC -LT-2292-1, 2, 3 Cables associated with head tank level transmitters which affect the Loop A outboard isolation valves CC -V122 and CC -V168 are routed in the same trays as the Loop B inboard isolation valves CC -V176 and CC -V256. Failures in these cables could cause total loss of PCCW to containment by initiation of a spurious lo-lo heat tank level signal. Loop A PCCW can be re -established by transferring control of valves CC -V122 and CC -V168 to local control at the RSS panel in fire area CB-F-1B-A. This removes the lo -lo head tank level isolation function and allows operators to re -open the valves. The safe shutdown requirements are satisfied.

3. RC Pump Seal Water Isolation Valve CS

-V168 Valve CS-V168 is a normally open valve which should remain open for safe shutdown. Spurious isolation of the Train B valve could result in RC inventory loss through the upstream relief valves. This inventory is directed to the PRT and is therefore, non -recoverable. To preclude this loss of inventory, redundant isolation capability is provided for the RC pump seal return lines by means of Train A valves CS -V10, CS-V28, CS-V44 and CS -V59. The cables, controls and equipment required for the operation of CS -V10, CS-V28, CS-V44 and CS -V59 are not contained in this fire area. The safe shutdown requirements are satisfied.

4. Letdown Isolation Valves CS

-V175, CS-V176 Functionally redundant Train B series valves CS -V175 and CS -V176 are normally closed and remain closed for safe shutdown. The spurious opening of one valve will not prevent safe shutdown. The operators will prevent further spurious operation by tripping the power supply breakers for CS -V175 and CS -V176 at the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-184 5. Charging Pump Test Line Isolation Valve SI -V158 On spurious operation of the normally closed, fail closed valve SI -V158 (Train B), the operators will maintain the normally closed high head injection path valves SI-V138 and SI -V139 closed. Charging will be accomplished utilizing the seal injection path through valves CS -FCV-121, CS-V154, CS-V158, CS-V162 and CS-V166. The cables, controls and equipment required for operation of their valves are not contained in the fire area. The capability to provide charging to the RC system through a minimum of one flow path satisfies the safe shutdown requirements.

6. Head Vent Valves RC-FV-2881 and RC

-V323 Functionally redundant Train B series valves RC -FV-2881 and RC -V323 are normally closed and remain closed for safe shutdown. The spurious opening of one valve will not prevent safe shutdown. The operators will prevent further spurious operation by tripping the power supply breakers for RC -FV-2881 and RC-V323 at the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

7. RHR Isolation Valves RC

-V22, RC-V23, RC-V87, RC-V88 RHR isolation valves are permanently disabled in the closed position. For entry into RHR shutdown cooling, valves RC -V22 and RC -V23 must be opened. This can be accomplished manually by entry into containment, if required. This manual operation can be delayed as much as 9 hours into the event. The safe shutdown requirements are satisfied.

8. Emergency Feedwater Pump Control Valves FW

-FV-4214B, FW -FV-4224B, FW-FV-4234B, FW -FV-4244B These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-185 9. Main Steam Isolation Valves MS -V88, MS-V90 Failure of the Train B cables will not prevent safe shutdown as the redundant Train A cables required for MSIV closure are routed in Fire Area ET -F-1A-A. The Appendix R separation requirements are satisfied.

10. Atmospheric Relief Valves MS

-PV-3002, MS-PV-3003 Valves MS -PV-3002 and MS -PV-3003 are normally closed valves. A fire would prevent operation of the Train B capabilities provided for opening and closing these valves. However, the fire would not affect the Train A capabilities and the valves will be operable for safe shutdown. Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affected air solenoids will be de -energized from the distribution panel located in Train B switchgear room (Fire Area: CB -F-1B-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

11. Tower Activation Logic Pressure Transmitters SW

-PT-8282, SW-PT-8283, SW-PT-8284 Failure in this cable could initiate a spurious tower actuation signal which would transfer one train of service water cooling capability from the pumphouse to the cooling towers. This transfer will not significantly interrupt Train B service water cooling nor will it have any impact on Train A service water. This failure does not prevent safe shutdown. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-186 12. Main Steam Pressure Transmitters FW -PT-525, FW-PT-535 A cable for one channel of main steam pressure instrumentation is routed through this fire area. This channel inputs to 2 out of 3 logics which initiate protective actions. A spurious signal from the one channel is not sufficient to initiate the logic. Hence, a failure in this cable will not prevent safe shutdown. The safe shutdown requirements are satisfied.

13. Steam Generator Level Transmitters FW

-LT-502, FW-LT-504, FW-LT-519, FW-LT-537 Cables for transmitters FW -LT-502, FW-LT-504, FW-LT-519, FW-LT-537 are located in the same fire area. A fire could cause loss of indication for all four steam generators. However, the same fire would not affect the redundant level transmitters FW -LT-501, FW-LT-503, FW-LT-529 and FW -LT-548. The Appendix R separation requirements are satisfied.

14. Emergency Feedwater Flow Transmitter FW

-FT-4214-4, FW-FT-4224-2, FW-FT-4234-4, FW-FT-4244-2 Failure in this cable could cause spurious closure of one emergency feedwater line. The logic will prevent isolation of additional lines. This leaves three steam generators available for heat removal; hence, safe shutdown is not affected. Although, failure in this cable could also cause loss of flow indication on two emergency feedwater lines, steam generator operability can be monitored by use of SG level indication. The safe shutdown requirements are satisfied.

15. Condensate Storage Tank Level FW

-LT-4257 All cables are Train B. The Train A level transmitter FW -LT-4252 will be available. In addition, the cables for CST level transmitter CO -LT-4096 are not routed through this area.

The Appendix R separation requirements are satisfied. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-187 16. Reactor Pressure RC -PT-403, RC-PT-405 Redundant reactor pressure instruments and cables are contained in this area. This function can also be performed by functionally redundant pressurizer pressure transmitters RC -PT-455 or RC -PT-457 routed through Fire Area ET-F-1A-A. The Appendix R separation requirements are satisfied.

17. Pressurizer Pressure Transmitters RC

-PT-456, RC-PT-458 Redundant channels of pressurizer pressure cables are located in proximity. Spurious operation of two channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after 1 minute by use of the manual reset and block switch and terminate the containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

18. Reactor Coolant Temperature RC

-TE-413B, RC-TE-423B, RC-TE-433B, RC-TE-443B All cold leg RC temperature element cables are routed through this area; however, this function can also be performed by the Train A steam generator pressure transmitters FW -PT-514, FW-PT-524, FW-PT-534, FW-PT-544 because cold leg temperature approximated the saturation temperature corresponding to secondary pressure. The cables for these PT 's are routed through fire area ET -F-1A-A. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-188 19. Pressurizer Relief Valves RC -PCV-456B, RC-V124 RC-PCV-456B is normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V124. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV and the block valve by tripping their power supplies in Train B switchgear room (Fire Area:

CB-F-1A-A). The safe shutdown requirements are satisfied.

20. Containment Pressure Transmitters SI

-PT-934, SI-PT-935 Redundant channels of containment pressure instruments and cables are located in proximity. Spurious operation of these channels will initiate safety injection, containment spray and containment isolation Phase A and Phase B. The operators will have the capability to terminate the SI after 1 minute by use of manual reset and block switches and terminate the containment spray and containment isolation by use of manual reset switches. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -1F-1A-A and CB-F-1B-A). Provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-189 Tabulation 3.2.7.52 Electrical Tunnel Fire Area - ET-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CAH-FN-1A x CAH-FN-1B x CAH-FN-1D x CC-LT-2192-1 x CC-LT-2192-2 x CC-LT-2192-3 x CC-LT-2292-1 x CC-LT-2292-2 x CC-LT-2292-3 x CC-P-322B x CC-V176 x CC-V256 x ED-X-16A x SA-C-4B x CS-V168 x CS-V175 x CS-V176 x PAH-DP-35B x PAH-DP-36B x RC-FV-2881 x RC-V323 x RC-E-10 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-190 Electrical Tunnel Fire Area - ET-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RC-PCV-456B x RC-V124 x RC-V22 x RC-V87 x SI-V139 x SI-V158 x SI-V17 x SI-V47 x SI-FV-2475 x SI-FV-2476 x SI-FV-2477 x SI-FV-2486 x RH-V36 x FW-FV-4214B x FW-FV-4224B x FW-FV-4234B x FW-FV-4244B x FW-P-37B x FW-V-347 x MS-V86 x MS-V88 x MS-V90 x MS-V92 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-191 Electrical Tunnel Fire Area - ET-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MS-PV-3001 x MS-PV-3002 x MS-PV-3003 x MS-PV-3004 x SB-V9 x SB-V10 x SB-V11 x SB-V12 x EAH-FN-174B x EDE-CP-249 x EDE-MCC-614 x EPA-FN-47B x EPA-DP-372 x EPA-DP-374 x SW-P-41B x SW-P-41D x SW-V29 x SW-V31 x SW-PT-8282 x SW-PT-8283 x SW-PT-8284 x SWA-FN-40B x CS-LT-106 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-192 Electrical Tunnel Fire Area - ET-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-LT-502 x FW-LT-504 x FW-LT-519 x FW-LT-537 x FW-PT-515 x FW-PT-516 x FW-PT-525 x FW-PT-535 x FW-PT-545 x FW-PT-546 x FW-LT-4257 x FW-FT-4214-4 x FW-FT-4224-2 x FW-FT-4234-4 x FW-FT-4244-2 x NI-NE-6691 x RC-LT-460 x RC-PT-403 x RC-PT-456 x RC-PT-458 x IC-TE-XX x MM-CP-486B x RC-TE-413B x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-193 Electrical Tunnel Fire Area - ET-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RC-TE-423B x RC-TE-433B x RC-TE-443B x SI-PT-934 x SI-PT-936 x MM-CP-2 x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A safe shutdown equipment and cables are located in fire area ET -F-1A-A. The Appendix R separation requirements are satisfied.

2. Component Cooling Water Isolation Valves CC

-V176, CC-V256 and Head Tank level Transmitters CC -LT-2192-1, 2, 3 and CC -LT-2292-1, 2, 3 Cables associated with head tank level transmitters which affect the Loop A outboard isolation valves CC -V122 and CC -V168 are routed in the same trays as the Loop B inboard isolation valves CC -V176 and CC -V256. Failures in these cables could cause total loss of PCCW to containment by initiation of a spurious lo-lo heat tank level signal. Loop A PCCW can be re -established by transferring control of valves CC -V122 and CC -V168 to local control at the RSS panel in fire area CB-F-1B-A. This removes the lo -lo head tank level isolation function and allows operators to re -open the valves. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-194 3. RC Pump Seal Water Isolation Valve CS -V168 Valve CS-V168 is a normally open valve which should remain open for safe shutdown. Spurious isolation of the Train B valve could result in RC inventory loss through the upstream relief valves. This inventory is directed to the PRT and is therefore, non -recoverable. To preclude this loss of inventory, redundant isolation capability is provided for the RC pump seal return lines by means of Train A valves CS -V10, CS-V28, CS-V44 and CS -V59 and the excess letdown line by means of either normally closed, fail closed valves CS -V175 or CS -V176. The cables, controls and equipment required for the operation of CS-V10, CS-V28, CS-V44 and CS -V59 are not contained in this fire area. The cables for valves CS -V175 and CS -V176 are routed in the same trays as the cables for CS-V168. To prevent the spurious closure of CS -V168 or the spurious opening of CS-V175 or CS-V176, the operators will trip their power supply breakers in the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

4. Letdown Isolation Valves CS

-V175, CS-V176 Functionally redundant Train B series valves CS -V175 and CS -V176 are normally closed and remain closed for safe shutdown. The spurious opening of one valve will not prevent safe shutdown. The operators will prevent further spurious operation by tripping the power supply breakers for CS -V175 and CS -V176 at the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

5. Charging Pump Test Line Isolation Valve SI

-V158 On spurious operation of the normally closed, fail closed valve SI -V158 (Train B), the operators will maintain the normally closed high head injection path valves SI-V138 and SI -V139 closed. Charging will be accomplished utilizing the seal injection path through valves CS -FCV-121, CS-V154, CS-V158, CS-V162 and CS-V166. The cables, controls and equipment required for operation of these valves are not contained in the fire area. The capability to provide charging to the RC System through a minimum of one flow path satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-195 6. Head Vent Valves RC -FV-2881 and RC -V323 Functionally redundant Train B series valves RC -FV-2881 and RC -V323 are normally closed and remain closed for safe shutdown. The spurious opening of one valve will not prevent safe shutdown. The operators will prevent further spurious operation by tripping the power supply breakers for RC -FV-2881 and RC-V323 at the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

7. RHR Isolation Valves RC

-V-22, RC-V87 RHR isolation valves are permanently disabled in the closed position. For entry into RHR shutdown cooling, valve RC -V22 must be opened. This can be accomplished manually by entry into containment, if required. This manual operation can be delayed as much as 9 hours into the event. The safe shutdown requirements are satisfied. 8. Emergency Feedwater Pump Control Valves FW -FV-4214B, FW -FV-4224B, FW-FV-4234B, FW -FV-4244B These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

9. Main Steam Isolation Valves MS

-V86, MS-V88, MS-V90, MS-V92 Failure of the Train B cables will not prevent safe shutdown as the redundant Train A cables required for MSIV closure are routed in Fire Area ET -F-1A-A. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-196 10. Atmospheric Relief Valves MS -PV-3001, MS-PV-3002, MS-PV-3003, MS-PV-3004 Valves MS -PV-3001, MS-PV-3002, MS-PV-3003, and MS -PV-3004 are normally closed valves. A fire would prevent operation of the Train B capabilities provided for opening and closing these valves. However, the fire would not affect the Train A capabilities and the valves will be operable for safe shutdown. Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affected air solenoids will be de -energized from the distribution panel located in Train B switchgear room (Fire Area: CB -F-1B-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

11. Tower Activation Logic Pressure Transmitters SW

-PT-8282, SW-PT-8283, SW-PT-8284 Failure in this cable could initiate a spurious tower actuation signal which would transfer one train of service water cooling capability form the pumphouse to the cooling towers. This transfer will not significantly interrupt Train B service water cooling nor will it have any impact on Train A service water. This failure does not prevent safe shutdown. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-197 12. Steam Generator Level Transmitters FW -LT-502, FW-LT-504, FW-LT-519, FW-LT-537 Cables for transmitters FW -LT-502, FW-LT-504, FW-LT-519, FW-LT-537 are located in the same fire area. A Fire could cause loss of indication for all four steam generators. However, the same fire would not affect the redundant level transmitters FW-LT-501, FW-LT-503, FW-LT-529 and FW -LT-548. The Appendix R separation requirements are satisfied.

13. Main Steam Pressure Transmitters FW

-PT-515, FW-PT-516, FW-PT-525, FW-PT-535, FW-PT-545, FW-PT-546 Redundant channels of main steam pressure cables are located in proximity. Spurious operation of the channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after 1 minute by use of the manual reset and block switch and terminate the containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

14. Emergency Feedwater Flow Transmitters FW

-FT-4214-4, FW-FT-4224-2, FW-FT-4234-4, FW-FT-4244-2 Failure in this cable could cause spurious closure of one emergency feedwater line. The logic will prevent isolation of additional lines. This leaves three steam generators available for heat removal; hence, safe shutdown is not affected. Although failure in this cable could also cause loss of flow indication on two emergency feedwater lines, steam generator perability can be monitored by use of SG level indication. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-198 15. Condensate Storage Tank Level FW -LT-4257 All cables are Train B. The Train A level transmitter FW -LT-4252 will be available. In addition, the cables for CST level transmitter CO -LT-4096 are not routed through this area. The Appendix R separation requirements are satisfied.

16. Pressurizer Pressure Transmitters RC

-PT-456, RC-PT-458 Redundant channels of pressurizer pressure cables are located in proximity. Spurious operation of two channels will initiate a safety injection signal. The operators will have the capability to terminate SI after 1 minute by use of the manual reset and block switch. All SI equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

17. Reactor Coolant Temperature RC

-TE-413B, RC-TE-423B, RC-TE-433B, RC-TE-443B All cold leg RC temperature element cables are routed through this area; however, this function can also be performed by the Train A steam generator pressure transmitters FW -PT-514, FW-PT-524, FW-PT-534, FW-PT-544 because cold leg temperature approximates the saturation temperature corresponding to secondary pressure. The cables for these PT 's are routed through fire area ET -F-1A-A. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-199 18. Containment Pressure Transmitters SI -PT-934, SI-PT-936 Redundant channels of containment pressure instruments and cables are located in proximity. Spurious operation of these channels will initiate safety injection, containment spray and containment isolation Phase A and Phase B. The operators will have the capability to terminate the SI after 1 minute by use of manual reset a nd block switches and terminate the containment spray and containment isolation by use of manual reset switches. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

19. Process Protection System Cabinet MM

-CP-2 Failure of cable will cause loss of power supply to Channel II process protection system cabinet and related instrumentation. The power supplies to redundant channel PPC are routed through other fire areas and; hence, the PPC 's will perform their safe shutdown function. The Appendix R separation requirements are satisfied.

20. Pressurizer Relief Valves RC

-PCV-456B, RC-V124 RC-PCV-456B is a normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC-V122. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de-energize the PORV and the block valve by tripping their power supply in the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-200 21. Containment Enclosure Isolation Damper, PAH -DP-35B, PAH-DP-36B Cables for dampers PAH -DP-35B and PAH -DP-36B are routed through this area. Under normal operation both dampers are open. If both dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in the recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. Independent operation of either damper (one open and one closed) could cause an air flow problem in EAH system. This assumes that redundant dampers (PAH -DP-35A and PAH -DP-36A) are in their normal open position since they would not be affected by a fire in this area. Both dampers are powered from a single Train B power supply. The circuit design is such that a spurious signal will cause both dampers to operate together, either both open (normal mode) or both closed (recirculation mode).

The safe shutdown requirements are satisfied.

22. High Head Safety Injection Valve SI

-V-139 SI-V-139 is a normally closed valve which may be opened to provide a redundant hot standby charging path. The functionally redundant Train A valve SI -V-138 is available to perform this function. Should SI -V-139 spuriously open, the charging pump may have to be stopped to prevent overfill of the pressurizer. The safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-201 Tabulation 3.2.7.53 Electrical Tunnel - Stairwell Fire Area - ET-F-S1-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-202 Tabulation 3.2.7.54 Fire Pump House Fire Area - FPH-F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-203 Tabulation 3.2.7.55 Fire Pump House Fire Area - FPH-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-204 Tabulation 3.2.7.56 Fire Pump House Fire Area - FPH-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-205 Tabulation 3.2.7.57 Fuel Storage Building Fire Area - FSB-F-l-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-206 Tabulation 3.2.7.58 East Main Steam and Feedwater Pipe Chase Fire Area - MS-F-1A-Z, MS-F-2A-Z, MS-F-3A-Z, MS-F-4A-Z, MS-F-5A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EAH-FN-174A x x EAH-FN-174B x x EAH-TSH-5136 x x EAH-TSH-5763 x x EDE-MCC-514 x FW-PT-524 x x FW-PT-535 x x FW-PT-526 x x FW-PT-534 x x FW-PT-525 x x FW-PT-536 x x MM-IR-51A x x MM-IR-51B x x MS-PY-3002-1,2 x x MS-PY-3002-5,6 x x MS-PY-3002-3,4 x x MS-PV-3002 x x MS-PV-3002 x x MS-PY-3003-1,2 x x MS-PY-3003-3,4 x x MS-PY-3003-5,6 x x MS-PV-3003 x x MS-PV-3003 x x MS-V86 x MS-V92 x MS-V88 x x MS-V88 x x MS-V90 x x MS-V90 x x MS-CP-182 x x MS-CP-184 x x EDE-CP-248 x SW-P-41A x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-207 East Main Steam and Feedwater Pipe Chase Fire Area - MS-F-1A-Z, MS-F-2A-Z, MS-F-3A-Z, MS-F-4A-Z, MS-F-5A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-P-41C x SW-V2 x SW-V22 x SW-PT-8272 x SW-PT-8273 x SW-PT-8274 x SWA-FN-40A x B. ANALYSIS 1. General Area Analysis The east MS & FW pipe chase is a concrete structure 74 '-9" long by 16 '-3" wide by 57' high with a floor area of 1220 sq. ft. and a volume of 69,540 cu. ft. The area contains no in situ combustibles other than cables in trays and fiberglass ladders. There is one stack of three cable trays. The bottom tray is an enclosed instrument level tray located approximately 1 '-6" above the floor. The other trays are open ladder type trays which are located approximately 10 ' above the floor. The zone contains approximately 140 lineal ft. of ladder type tray. Detectors are provided throughout the area. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-208 2. System Analysis

a. Containment Enclosure Ventilation Fans EAH

-FN-174A, EAH -FN-174B and Temperature Switches, EAH -TSH-5136, EAH -TSH-5763. Redundant ventilation fans and related cables are located in proximity. The purpose of these fans is to provide cooling for the Train A MSIV logic cabinets and the main steam pressure instrumentation. The failure of these fans will not prevent safe shutdown as the Train B logic cabinets and the main steam pressure transmitters FW -PT-514 and FW -PT-545 are not in the same fire area. The Train B logic cabinets are in the Train B switchgear room (Fire Area CB -F-1B-A) and the main steam pressure transmitters FW-PT-514 and FW -PT-545 are located in the west main steam and feedwater pipe chase (Fire Zone MS -F-1B-Z). These logic cabinets and pressure transmitters will perform their safe shutdown function. The Appendix R separation requirements are satisfied.

b. 460 Volt Motor Control Center EDE

-MCC-514 All cables are Train A. The redundant Train B cables are in Fire Area DCT-F-1B-0. The Appendix R separation requirements are satisfied.

c. Main Steam Pressure Transmitters FW

-PT-524, FW-PT-525, FW-PT-526, FW-PT-534, FW-PT-535, FW-PT-536 and Instrument Racks, MM-IR-51A, MM-IR-51B. Redundant channels of main steam pressure instruments and cables are located in proximity. Spurious operation of the channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after one (1) minute by use of the manual reset and block switch and terminate the containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B Switchgear Rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-209 Additionally main steam line pressure transmitters FW -PT-525 and FW-PT-534 utilized for process monitoring are located in the same fire areas. A fire could cause loss of indication from both main steam line pressure transmitters. However, the same fire would not affect pressure transmitters FW -PT-514 and FW -PT-545 which are functionally redundant and are located in the west main steam and feedwater pipe chase. (Fire Area: MS-F-1B-Z). These pressure transmitters and their associated atmospheric relief valves MS -PV-3001 and MS -PV-3004 will perform their safe shutdown function. The Appendix R separation requirements are satisfied.

d. Atmospheric Relief Valves MS

-PV-3002, MS-PV-3003 and Associated Solenoids. Valves MS -PV-3002 and MS -PV-3003 are normally closed valves. A fire could prevent operation of these valves. However, the same fire would not prevent the operation of valves MS -PV-3001 and MS -PV-3004 which are in the west main steam and feedwater pipe chase (Fire Area: MS -F-1B-Z, MS-F-2B-Z). Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affected air solenoids will be de -energized from the distribution panels located in Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-210 e. Main Steam Isolation Valves (MSIV) MS -V88 and MS -V90 and Logic Cabinet MS -CP-182, MS-CP-184. The valves MS -V88 and MS -V90 have no redundant counterpart, but they are supplied with redundant control capabilities. The Train A cables are routed in tray and conduit to the MSIV 's and their respective Train A logic cabinets. The Train B cables are routed in conduit on the opposite side of the MS & FW pipe chase. Their is a minimum horizontal separation of 10 ' up to the point that the conduits must run to the valves. The Train B conduits are routed approximately 15 ' above the floor. The MSIV 'S, connection boxes and electrical equipment are located approximately 25 ' above the floor. The Train B conduits are a minimum of 20 ' above the floor at the point they are in proximity to the Train A conduits. The Train A and Train B controls are on opposite sides of the MSIV approximately 2 ' apart. These valves are closed as an initial operator action. Should an MSIV reopen due to spurious operation (loss of power to both trains), the operators will isolate all feedwater to its respective steam generator and allow the SG to dry out. In the worst case this condition could occur to both MSIV 'S. The two steam generators and their associated MSIV 's in the west main steam and feedwater pipe chase (Fire Area: MS -F-1B-Z, MS-F-2B-Z) will be available for safe shutdown. The safe shutdown requirements are satisfied.

f. Main Steam Isolation Valves (MSIV) MS

-V86 and MS -V92 Valves MS -V86 and MS -V92 receive logic signals from both the Train A and the Train B MSIV logic cabinets. The cables and equipment in this Fire Area are associated with the Train A logic. The Train B logic cables and equipment are not routed through this fire area; hence, they will perform their safety function (MSIV trip). The Appendix R separation requirements are satisfied.

g. Not used.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-211 h. Service Water Pumps SW -P-41A and SW -P-41C All cables are Train A. The redundant Train B cables are in Fire Area DCT-F-1B-0. The Appendix R separation requirements are satisfied.

i. Service Water Valves SW

-V2 and SW -V22 All cables are Train A. The redundant Train B cables are in Fire Area DCT-F-1B-0. The Appendix R separation requirements are satisfied.

j. Tower Activation Logic Pressure Transmitters SW

-PT-8272, SW-PT-8273, SW-PT-8274 and Tower Actuation Panel EDE -CP-248 Failure in this cable could initiate a spurious tower actuation signal which would transfer one train of service water cooling capability from the pumphouse to the cooling towers. This transfer will not significantly interrupt Train A service water cooling nor will it have any impact on Train B service water. This failure does not prevent safe shutdown. The safe shutdown requirements are satisfied.

k. Service Water Air Handling Fan SWA

-FN-40A All cables are Train A. The redundant Train B cables are in Fire Area DCT-F-1B-0. The Appendix R separation requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-212 Tabulation 3.2.7.59 West Main Steam and Feedwater Pipe Chase Fire Area - MS-F-1B-Z, MS-F-2B-Z, MS-F-3B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-PT-514 x x FW-PT-545 x x FW-PT-544 x x FW-PT-515 x x FW-V156 x x FW-PT-516 x x FW-PT-546 x x MM-IR-52A x x MM-IR-52B x x MS-PY-3001-1, 2 x x MS-PY-3001-3, 4 x x MS-PY-3001-5, 6 x x MS-PV-3001 x x MS-PV-3001 x x MS-PY-3004-1, 2 x x MS-PY-3004-5, 6 x x MS-PY-3004-3, 4 x x MS-PV-3004 x x MS-PV-3004 x x MS-V86 x x MS-V86 x x MS-V92 x x MS-V92 x x SB-V9 x x SB-V10 x x SB-V11 x x SB-V12 x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-213 B. Analysis 1. General Area Analysis The west MS & FW pipe chase is a concrete structure 66 '-9" long by 14 ' wide by 57 ' high with a floor area of 935 sq. ft. and a volume of 64,700 cu. ft. The only in situ combustibles contained in the area consist of one gallon of oil in the steam recirculation pump for a fire loading of 150,000 Btu 's and fiberglass ladders for a fire loading of 1,586,000 Btu 's. There are no cables in trays. Detectors are provided throughout the area.

2. System/Equipment Analysis
a. Main Steam Pressure Transmitters FW

-PT-514, FW-PT-515, FW-PT-516, FW-PT-544, FW-PT-545, FW-PT-546 and Instrument Racks, MM-IR-52A, MM-IR-52B. Redundant channels of main steam pressure instruments and cables are located in proximity. Spurious operation of the channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after 1 minute by use of the manual reset and block switch and terminate containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). Additionally main steam line pressure transmitters FW -PT-514 and FW-PT-545 utilized for process monitoring are located in the same fire areas. A fire could cause loss of indication from both main steam line pressure transmitters. However, the same fire would not affect pressure transmitters FW -PT-525 and FW -PT-534 which are functionally redundant and are located in the east main steam and feedwater pipe chase. (Fire Area:

MS-F-3A-Z). These pressure transmitters and their associated atmospheric relief valves MS -PV-3002 and MS -PV-3003 will perform their safe shutdown function. The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-214 b. Atmospheric Relief Valves MS -PV-3001, MS-PV-3004 and Associated Solenoids. Valves MS -PV-3001 and MS -PV-3004 are normally closed valves. A fire could prevent operation of these valves. However, the same fire would not prevent the operation of valves MS -PV-3002 and MS -PV-3003 which are in the west main steam and feedwater pipe chase (Fire Areas: MS -F-1A-Z, MS-F-2A-Z). Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affected air solenoids will be de -energized from the distribution panels located in Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-215 c. Main Steam Isolation Valves (MSIV) MS -V86 and MS -V92 The valves MS -V86 and MS -V92 have no redundant counterpart, but they are supplied with redundant control capabilities. The Train A and Train B conduits are on opposite sides of the west MS & FW pipe chase with a minimum horizontal separation of 10 ' up to the point that the conduits must run to the valves. The MSIV connection boxes and electrical equipment are located approximately 25 ' above the floor. The Train B conduits are a minimum of 20 ' above the floor at the point they are in proximity to the Train A conduits. The Train A and Train B controls are on opposite sides of the MSIV approximately 2 ' apart. These valves are closed as an initial operator action. Should an MSIV reopen due to spurious operation (loss of power to both trains), the operators will isolate all feedwater to its respective steam generator and allow the SG to dry out. In the worst case this condition could occur to both MSIV 'S. The two steam generators and their associated MSIV 's in the east main steam and feedwater pipe chase (Fire Areas: MS -F-1A-Z and MS-F-2A-Z) will be available for safe shutdown. The safe shutdown requirements are satisfied.

d. Not used.

C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-216 Tabulation 3.2.7.60 East Air Make -Up Pit Fire Area - MUA-F-1-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-217 Tabulation 3.2.7.61 This page intentionally left blank.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-218 Tabulation 3.2.7.62 Non-Essential Switchgear Room Fire Area - NES-F-1A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable ED-CP-532 x x ED-I-4 x x ED-PP-5 x x ED-PP-121B x x ED-PP-122A x ED-SWG-l x x ED-SWG-2 x x ED-US-11 x ED-US-23 x EDE-SWG-5 x FW-P-113 x FW-P-161 x MM-CP-153 x RC-P-1A x RC-P-1B x RC-P-1C x RC-P-1D x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-219 B. Analysis Loss of ED -I-4, ED-PP-5, ED-CP-532, MM-CP-153 will cause loss of CST level instrumentation CO -LT-4096. Redundant equipment is located in fire area EFP -F-1-A. RC pump switchgear control power (ED -SWG-l and ED-SWG-2) is lost. The RC pump switchgear is located in the fire area. The operator will trip the pumps by tripping offsite power from the control room. Pressurizer heaters C, D and control group control power (ED -US-11 and ED -US-23) will be lost due to this fire. If the heaters require tripping, an operator will do so manually in the Train A switchgear room (Fire Area: CB -F-1A-A). Alternatively, the operator can reduce pressure by opening a PORV. Redundant heaters are available with control power from the emergency DC bus. Cables from EDE -SWG-5 are located in this fire area. Loss of one cable could cause loss of offsite power which is acceptable since both diesel generators are available. C. Evaluation The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-220 Tabulation 3.2.7.63 Primary Auxiliary Building Fire Area - PAB-F-1A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-P-11B x CC-P-11D x CC-TE-2271 x CC-TV-2271-1 x CC-TV-2271-2 x CC-V122 x CC-V168 x CC-V1092 x CC-V1095 x CS-E-5A x CS-E-5B x CS-FCV-121 x SI-V139 x CS-FT-121 x x CS-HCV-182 x x MM-IR-17 x x CS-LCV-112C x CS-LCV-112E x CS-LT-7464 x CS-P-2A x CS-P-2B x CS-P-3B x CS-V143 x CS-V196 x CS-V197 x EAH-FN-5B x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-221 Primary Auxiliary Building Fire Area - PAB-F-1A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EAH-FN-31B x EDE-SWG-6 x EDE-MCC-513 x PAH-DP-43B x PAH-DP-358 x PAH-FN-42B x RC-V22 x RC-V87 x SW-FN-51A x SW-P-41A x SW-P-41B x SW-P-41C x SW-P-41D x SW-P-110A x SW-V5 x SW-V18 x SW-V19 x SW-V23 x SW-V54 x SW-V25 x SW-V56 x SW-V139 x SWA-DP-66 x SWA-FN-64 x SWA-FN-71 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-222 B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-223 Tabulation 3.2.7.64 Primary Auxiliary Building Fire Area - PAB-F-1B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-224 Tabulation 3.2.7.65 Primary Auxiliary Building Fire Area - PAB-F-1F-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-225 Tabulation 3.2.7.66 Primary Auxiliary Building Fire Area - PAB-F-lJ-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-V175 x CC-V257 x CS-FCV-121 x x CS-FY-121B x x CS-V158 x CS-V196 x x CS-V197 x x RC-V23 x RC-V88 x SI-PT-937 x SI-PT-936 x SI-V138 x B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-226 Tabulation 3.2.7.67 Primary Auxiliary Building Fire Area - PAB-F-lK-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-LCV-112B x CS-LCV-112C x CS-LCV-112D x CS-LCV-112E x PAH-DP-43A x x PAH-DP-43B x x PAH-DP-357 x PAH-DP-358 x PAH-FN-42A x PAH-FN-42B x SW-V4 x x SW-V5 x x SW-V74 x x B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-227 Tabulation 3.2.7.68 Primary Auxiliary Building Fire Area - PAB-F-2A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-FCV-110A x CS-FCV-111A x CS-FCV-110B x CS-FCV-111B x CS-LT-102 x CS-LT-106 x CS-P-3A x CS-V426 x EAH-FN-5B x EDE-MCC-513 x PAH-DP-35A x x PAH-DP-35B x PAH-DP-36A x PAH-DP-36B x PAH-DP-43A x PAH-DP-357 x PAH-FN-42A x SW-FN-51A x SW-P-41A x SW-P-41C x SW-P-110A x SW-V54 x SW-V56 x SW-V139 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-228 Primary Auxiliary Building Fire Area - PAB-F-2A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SWA-DP-66 x SWA-FN-64 x SWA-FN-71 x B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-229 Tabulation 3.2.7.69 Primary Auxiliary Building Fire Area - PAB-F-2B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-FCV-110A x x CS-FCV-111A x x CS-FCV-110B x x CS-FCV-111B x x CS-LT-102 x x CS-LT-106 x x CS-LT-7464 x x CS-P-3A x x CS-P-3B x x CS-V426 x x CS-V410 x CS-V410 x CS-V416 x CS-V416 x CS-V431 x CS-V423 x CS-V437 x CS-V1207 x CS-V439 x CS-V439 x CS-V442 x CS-V442 x CS-TK-4A x CS-TK-4B x PAH-DP-43A x PAH-DP-357 x PAH-FN-42A x B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-230 Tabulation 3.2.7.70 Primary Auxiliary Building Fire Area - PAB-F-2C-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-LT-2172-1 x CC-LT-2192-1 x CC-LT-2172-2 x CC-LT-2192-2 x CC-LT-2172-3 x CC-LT-2192-3 x CC-LT-2272-1 x CC-LT-2292-1 x CC-LT-2272-2 x CC-LT-2292-2 x CC-LT-2272-3 x CC-LT-2292-3 x CC-P-11A x x CC-P-11B x x CC-P-11C x x CC-P-11D x x CC-TE-2171 x x CC-TE-2271 x x CC-TE-2197 x x CC-TE-2297 x x CC-TV-2171-1 x x CC-TV-2271-1 x x CC-TV-2171-2 x x CC-TV-2271-2 x x CC-TY-2171 x x CC-TY-2271 x x MM-IR-93 x x CC-E-17A x CC-E-17B x CS-FT-121 x CS-FCV-110A x CS-FCV-111A x CS-FCV-110B x CS-FCV-111B x CS-FCV-121 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-231 Primary Auxiliary Building Fire Area - PAB-F-2C-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-HCV-182 x CS-LT-102 x CS-LT-106 x CS-LT-7464 x CS-LCV-112B x CS-LCV-112C x CS-LCV-112D x CS-LCV-112E x CS-P-2A x CS-P-3A x CS-P-3B x CS-V196 x CS-V426 x EDE-MCC-513 x EAH-FN-5A x EAH-FN-5B x EAH-FN-31A x EAH-FN-31B x PAH-DP-35A x PAH-DP-35B x PAH-DP-36A x x PAH-DP-36B x PAH-DP-43A x PAH-DP-43B x PAH-DP-357 x x PAH-DP-358 x x PAH-FN-42A x x PAH-FN-42B x x PAH-TSH-5391 x x PAH-TSH-5393 x x SW-FN-51A x SW-P-41A x SW-P-41C x SW-P-110A x SW-V4 x SW-V5 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-232 Primary Auxiliary Building Fire Area - PAB-F-2C-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-V15 x SW-V16 x SW-V18 x SW-V20 x x SW-V19 x x SW-V34 x x SW-V23 x x SW-V54 x SW-V56 x SW-V74 x SW-V139 x SWA-DP-66 x SWA-FN-64 x SWA-FN-71 x B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-233 Tabulation 3.2.7.71 Primary Auxiliary Building Fire Area - PAB-F-3A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-LT-2172-1 x x CC-LT-2192-1 x x CC-LT-2172-2 x x CC-LT-2192-2 x x CC-LT-2172-3 x x CC-LT-2192-3 x x CC-LT-2272-1 x CC-LT-2292-1 x CC-LT-2272-2 x CC-LT-2292-2 x CC-LT-2272-3 x CC-LT-2292-3 x EDE-TBX-YH4 x x EDE-TBX-YH5 x x CC-TK-19A x CC-TK-19B x CS-FCV-110A x CS-FCV-111A x CS-FCV-110B x CS-FCV-111B x CS-LCV-112B x CS-LCV-112D x DG-E-42A x DG-E-42B x SW-V4 x SW-V5 x SW-V15 x x SW-V17 x SW-V16 x x SW-V18 x x B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-234 Tabulation 3.2.7.72 Primary Auxiliary Building Fire Area - PAB-F-3B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-LT-2272-1 x x CC-LT-2292-1 x x CC-LT-2272-2 x x CC-LT-2292-2 x x CC-LT-2272-3 x x CC-LT-2292-3 x x CS-FCV-110A x CS-FCV-111A x CS-FCV-110B x CS-FCV-111B x CS-LCV-112B x x CS-LCV-112C x x CS-LCV-112D x CS-LCV-112E x B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-235 Tabulation 3.2.7.73 Primary Auxiliary Building Fire Area - PAB-F-4-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire zone. C. Evaluation The Appendix R separation requirements do not apply to this zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-236 PAB Zone Primary Auxiliary Building Zone Analysis And Evaluation B. Analysis 1. General Area Analysis

a. The PAB is a Class 1 concrete structure which contains the above listed equipment and cable required for safe shutdown. The PAB has been divided into several zones for fire protection analysis, with intervening walls, floors and ceilings of poured concrete.
b. The significant in situ combustibles consist of 0.2 gallon of oil in each of the two boron injection pumps; 1.0 gallon of oil in the monorail crane hoists; 1.0 gallon of oil in each of the two chiller pumps; 0.25 gallon of oil in each of the two reactor makeup water pumps; 1.0 pound of grease in each of the two boric acid transfer pumps; 1.0 gallon of oil in each of the four primary component cooling pumps; 0.5 gallon of oil in each of the two flash tank distillate pumps; 32,500 lbs. of charcoal within filters PAH-F-16 and CAP

-F-40 and 19,000 pounds of insulation for cables in trays. The analysis of the in situ fire load provided by the cable in trays is contained in the "Zone Analyses ". An analysis of the Design Basis Fires for the remaining combustibles is contained in the "Fire Protection Program Evaluation of Comparison to Branch Technical Position APCSB

9.5-1, Appendix A" and is summarized as follows:

1) Elevation 7'-0" and Below a) Fire Zone PAB

-F-1A-Z Total fire loading for 6.0 gallons of oil is 900,000 Btu (chiller pumps CS -P-7A, and CS -P-7B and reactor makeup water pumps RMW -P-16A and RMW -P-16B), and the fire loading for fiberglass ladders is (28 pounds plastic) 364,000 Btu. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-237 b) Fire Zone PAB -F-1J-Z Limited in situ combustibles in pumps. c) Fire Zone PAB -F-1K-Z No combustibles

2) Elevation 25

'-0" a) Fire Zone PAB -F-2A-Z Total fire load for fiberglass ladders is (71 pounds plastic) 923,000 Btu . b) Fire Zone PAB-F-2B-Z Total fire loading for 2.0 pounds of grease is 36,000 Btu (boric acid transfer pumps CS -P-3A and CS -P-3B). c) Fire Zone PAB -F-2C-Z Total fire loading for 5.25 gallons of oil is 787,500 Btu (PCCW pumps CC -P-11A, 11B, 11C and 11D; 31/2 ton monorail crane hoist CS -CR-13; 41/2 ton monorail crane hoist CS-CR-5; boron injection pumps SI -P-4A and SI -P-4B). 3) Elevation 53 '-0" a) Fire Zone PAB -F-3A-Z Total fire loading for 1.0 gallon of oil is 150,000 Btu (flash tank distillate pumps SB -P-171A and SB -P-171B). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-238 b) Fire Zone PAB -F-3B-Z Total fire loading for 0.5 gallon of oil is 75,000 Btu (41/2 ton monorail crane hoist CS -CR-6) and for 50 pounds of Class A material is 400,000 Btu and for fiberglass ladders is (71 pounds plastic) 923,000 Btu. See "Fire Protection Program Evaluation and Comparison to Branch Technical Position APCSB 9.5 -1 Appendix A" for analysis of 6600 lbs. of charcoal in CAP -F-40. c. The Train A safe shutdown cables are routed in trays. The Train B safe shutdown cables are routed in conduits with a one -hour, fire -rated barrier from the fire area boundary where they enter the PAB to the fire area boundary where they exit or the equipment at which they terminate, except as discussed in the zone analyses.

d. Detectors are provided in all zones of the PAB with the exception of Fire Zones PAB

-F-1B-Z, PAB-F-1F-Z and PAB -F-1K-Z. e. Suppression is provided in Fire Zone PAB -F-2C-Z. Details are provided in the zone analysis.

f. Early fire detection by use of carbon monoxide detectors within the

charcoal filter CAP -F-40 is provided.

g. Volume control tank (VCT) isolation valves CS

-LCV-112B & -112C are normally open to provide a suction path from the VCT to the normally operating charging pump (CS -P-2A or -2B). These valves must stay open until RWST valve CS -LCV-112D or -112E is manually opened to provide a charging pump suction path from the RWST, or the boric acid tanks are manually aligned as a charging pump suction source. Spurious closure of a VCT isolation valve caused by a hot short would interrupt suction flow to the operating charging pump causing it to be damaged. If the standby charging pump has cables in the same area then its operation can also be degraded. The result would be no charging system flow. The following PAB fire zones have been combined into one fire area for analysis purposes: PAB-F-1A-Z, PAS-F-1J-Z, PAB-F-1K-Z, PAB-F-2A-Z, PAB-F-2B-Z, PAB-F-2C-Z, PAB-F-3A-Z, and PAB -F-3B-Z. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-239 Since this combined fire area contains cables for CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B, this condition is potentially applicable for the system alignment with either combination of CS -P-2A and CS-P-2B as the standby pump and operating pump. The CS-LCV-112B and CS -LCV-112C circuit design prevents spurious valve closure from hot shorts as follows. The field cable conductors for the motor control center (MCC) contactor close coil circuit are in different cables than the 120 V "hot" circuit conductors eliminating the hot short failure mode within the cables. Cable -to-cable hot shorts need not be postulated for thermoset cable insulation as used at Seabrook. Also, the barriered conduit for CS -LCV-112C prevents Train B cable damage. Since CS-LCV-112B and CS -LCV-112C will not spuriously close, CS-P-2A or -2B as the operating charging pump will not be damaged.

2. Zone Analyses
a. Fire Zone PAB

-F-1A-Z (Tabulation 3.2.7.63)

1) Specific Zone Analysis This zone at Elevation 7

'-0" and (-) 2'-0" of the PAB is bounded by concrete floors, ceilings and walls with penetrations to other zones. The zone is approximately 140 ' long by 75 ' wide by 16 ' high with a floor area of 5200 sq. ft. and a volume of 81,600 cu ft. All Train B Safe Shutdown cables are routed in conduit with a one -hour, fire-rated barrier. Combustibles are limited to 6.0 gallons of oil for a fire loading of 900,000 Btu and 28 pounds of plastic (fiberglass ladders) for a fire loading of 364,000 Btu with a total fire loading of 248 Btu per sq. ft. of floor area. Detectors are provided throughout the zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-240 2) System Analyses a) Primary Component Cooling Water (CC) System This zone contains cable routed in barriered conduits for temperature element CC -TE-2271; pumps CC -P-11B and CC-P-11D; and valves CC -TV-2271-1, CC-TV-2272-2, CC-V122, CC-V168, CC-V1092 and CC -V1095. This equipment is all Train B. There is no redundant Train A CC system equipment or cables in this fire zone. b) Chemical and Volume Control (CS) System This zone contains cables routed in barriered conduits for pumps CS-P-2B and CS -P-3B; and valves CS -LCV-112C, CS-LCV-112E, CS-V143 and CS -V197. Cables for the Train A pump CS-P-2A which is redundant to pump CS -P-2B are routed in tray and conduit that is 10 ' above floor Elevation 7 '-0" in the area that the pump cables are in proximity. See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g. Cables for the Train A Valve CS -FCV-121 and transmitter CS-FT-121 which provide a redundant charging flow path to valve SI -V139 are routed in tray and conduit in proximity to the barriered conduit containing the cables for SI-V139. Cables for the Train A valve CS -V196 are routed in tray and conduit in proximity to the barriered conduits containing the cables for the Train B Valve CS -V197. c) Containment Enclosure Air Handling (EAH) System This zone contains cables routed in barriered conduits for fans EAH-FN-5B and EAH -FN-31B. This equipment is all Train B. There is no redundant Train A EAH system equipment or cables in this fire zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-241 d) Electrical Distribution - Emergency (EDE) System This zone contains Train B cables routed in barriered conduits for the 4160V switchgear EDE -SWG-6. There are no functionally redundant cables in this area. The Train A EDE-MCC-513 cable has functionally redundant cables located in other fire areas. e) PAB Handling (PAH) System This zone contains cables routed in barriered conduits for dampers PAH -DP-43B, PAH-DP-358 and fan PAH-FN-42B. This equipment is Train B. There is no redundant Train A PAH system equipment or cables in this fire zone. f) Reactor Coolant (RC) System This zone contains cables routed in barriered conduits for valves RC -V22 and RC -V87. The cables are part of the position indicating light circuit for valves that have been permanently disabled. Failures in this circuit will not prevent opening of the valves for cold shutdown. g) Safety Injection (SI) System This zone contains cables routed in barriered conduits for valve SI-V139. This equipment is Train B. The redundant cables and equipment are as discussed in b) above.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-242 h) Service Water (SW) System This zone contains cables routed in barriered conduits for Train B pumps SW -P-41B and SW -P-41D and valves SW-V5, SW-V18, SW-V19, SW-V23 and SW -V25. The only exception is at an interference with an HVAC duct support where the one -hour wrap is reduced and pyrocrete is installed for heat transfer protection. Cables for Train A pumps SW-P-41A and SW -P-41C and valve SW -54, which are redundant to pumps SW -P-41B and SW -P-41D and valve SW-V25 are routed in tray that is 9 ' above the floor Elevation 7 '-0" except at the entrance to the duct bank to the cooling towers where it is 3 '-6" above floor Elevation 7'-0". There is approximately 8 ' of horizontal separation between the Train B barriered conduit and the Train A tray. For the other Train A cables routed in this zone, the

redundant cables and equipment are contained in other fire areas. i) Service Water Air Handling (SWA) System All cables are Train A, the redundant cables are located in other fire areas.

3) Summary For CC, EAH, and PAH systems above, the routing of the Trai n B cables in conduit with a one

-hour, fire -rated barrier; the absence of Train A equipment and cables; and considering the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation for Appendix R, Paragraph III G.2c. "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed, " has been approved.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-243 For CS and SI systems above, the routing of the Train B cables in conduit with a one -hour, fire -rated barrier; the 10 ' height of the tray and conduit above the floor; and considering the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements and

Appendix R. A deviation for Appendix R, Paragraph III G.2c "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed, " is requested. For SW system above, the routing of the Train B cables in conduit with a one -hour, fire -rated barrier; the 8 ' of separation between the Train A tray and the Train B conduit; and considering the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation for Appendix R, Paragraph III G.2c "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed, " is requested. For RC system above, the safe shutdown requirements are satisfied. For EDE and SWA systems above the Appendix R separation requirements are satisfied.

b. Fire Zone PAB

-F-1J-Z (Tabulation 3.2.7.66)

1) Specific Zone Analysis This zone at Elevation (

-) 6'-0" and (-) 26'-0" of the PAB is bounded by concrete floors, ceiling and walls with penetrations to other zones. The zone is approximately 96 ' long by 75 ' wide by 11 ' to 18' high with floor area of 1980 sq. ft. and a volume of 23,782 cu. ft. All Train B safe shutdown cables are routed in conduit with a one-hour, fire -rated barrier. Combustibles are limited to cables in open trays with a total fire loading of 500 Btu per sq. ft. and limited in situ combustibles in pumps. Detectors are provided throughout the zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-244 2) System Analyses a) Primary Component Cooling Water (CC) System This zone contains cables routed in tray for the Train A valves CC -V175 and CC -V257. The tray is minimum of 10' above floor elevation ( -) 26'-0". Only 6 linear feet of the tray is in the zone. The redundant Train B cables are routed in barriered conduit above floor elevation ( -) 8'-0" in Fire Zone PAB -F-1Z-Z, which is approximately 18 ' horizontally above the Train A cables with an intervening concrete floor. b) Chemical and Volume Control (CS) Syst em This zone contains equipment and cables in conduit required for operation of Train A Valve CS -FCV-121 which provides a redundant charging flow path to Train B Valve SI-V139. The redundant Train B cables are routed in barriered conduit in Fire Zone PAB -F-1A-Z and are separated from the Train A cables by concrete floors and walls. Valve CS-V158 provides redundant seal cooling capabilities to the safety grade thermal barrier cooling. Cables, controls and equipment for the Train A thermal barrier cooling capability are not contained in the PAB fire area and will be available for safe shutdown. Redundant valves CS -V196 and CS -V197 are located in the same fire zone and are separated by approximately 3 ' horizontal separation. These valves are normally open

valves that remain open for Safe Shutdown. The spurious closure for one valve will not prevent shutdown. The operators will prevent further spurious operation by tripping the power supply breakers at the Train A or Train B switchgear rooms (Fire Areas: CB -F-1A-A or CB-F-1B-A). See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-245 c) Reactor Coolant (RC) System This zone contains cables routed in tray for the Train A valves RC -V23 and RC-V88. The cables are part of the position indicating light circuit for valves that have been permanently disabled. Failures in this circuit will not prevent the opening of the valves for cold shutdown. d) Safety Injection (SI) System This zone contains cables routed in tray for the Train B valve SI-V139. The tray is a minimum of 10 ' above floor Elevation ( -) 26'-0". Only six lineal feet of the tray is in the zone. The redundant Train B cables are routed in barriered conduit above floor Elevation (-) 8'-0" in Fire Zone PAB-F-1A-Z, which is approximately 18 ' horizontally above the Train A cables with an intervening concrete floor. Redundant channels of containment pressure (SI -PT-936 and SI-PT-937) cables are located in proximity. Spurious operation of these channels will initiate containment spray and containment isolation Phase B. The operators will have the capability to terminate these protective actions by use of manual reset switches. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB-F-1A-A and CB-F-1B-A). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-246 3) Summary For CC and SI systems above, the routing of the Train B cables in conduit with a one -hour, fire -rated barrier; the height of the Train A an B raceways, the provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area; and considering the low combustibles loading in the zone provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III G.2.c "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved. For CS system above, the routing of the Train B cables in conduit with a one -hour, fire -rated barrier; and the low combustibles loading in the zone provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III G.2.c in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved. For RC system above, the safe shutdown requirements are satisfied.

c. Fire Zone PAB

-F-1K-Z (Tabulation 3.2.7.67)

1) Specific Zone Analysis This zone between Elevation (

-) 6'-0" and roof Elevation 81 '-0" of the PAB is bounded by concrete floors, ceilings and walls with penetrations to other zones. The zone is approximately 68 ' long by 9' wide by 75 ' high with a floor area of 4,620 sq. ft. and a volume of 75,370 cu. ft. There is no tray in the zone and all cables are routed in conduit. All Train B safe shutdown cables are routed in conduit with a one-hour, fire -rated barrier. There are no in situ combustibles in the zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-247 2) System Analyses a) Chemical and Volume Control (CS) System This zone contains cables routed in conduit for Train A valves CS -LCV-112B and CS -LCV-112D. The Train B cables for their redundant counterpart valves CS-LCV-112C and CS -LCV-112E are routed in barriered conduit in the zone. There is 13 ' horizontal separation between the conduits containing the redundant cables. See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g. b) PAB Air Handling (PAH System) This zone contains cables routed in conduit to Train A damper PAH -DP-43A. The Train B cables to redundant damper PAH -DP-43B are routed in barriered conduit in the zone. The only exception to the barrier is a short length of flexible conduit whose wrapping would interfere with the damper operator. The dampers are located approximately 15' above the floor. The area containing the dampers is a concrete and steel enclosed air plenum with limited access and no combustibles. These dampers and the fans which they control are not needed unless the main ventilation system is lost due to loss of off-site power or unless the temperature in the PCCW area exceeds 40C (104F). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-248 c) Service Water (SW) System This zone contains cables routed in conduit for Train A valve SW-V4. The Train B cables for its redundant counterpart valve SW-V5 are routed in barriered conduit in the zone. The only exception to the barrier is one cable which runs in flexible conduit between a limit switch on valve SW-V5 to its motor operator. There is 8 ' horizontal separation between the barriered conduit for valve SW -V5 and valve SW -V4. There is 16 ' horizontal separation between the redundant valves. The valves are located approximately 15 ' above floor Elevation 53 '-0" and 3' above platform Elevation 65 '-0. This zone also contains cables routed in conduit for Train A valve SW-V74. The position of this valve is only important when the Train A cooling tower capabilities are in use at which time the valve should be closed and should remain closed. In the event this valve opens spuriously, the operators can either transfer the Train A service water to the pumphouse or utilize the Train B service water system. This satisfies the safe shutdown requirements.

3) Summary For the CS system above, the routing of the Train B cables in conduit with a one

-hour, fire-rated barrier; the spatial separation between the Train A and Train B conduits; and considering the absence of in situ combustibles in the zone provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III G.2.c "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-249 For the PAH system above, the routing of the Train B cables in conduit with a one -hour, fire-rated barrier; the height of the dampers above the floor; the absence of in situ combustibles in the zone and the fact that a fire in the area could not cause loss of off-site power, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III.G.2 has been approved. For the SW system above, the routing of the Train B cables in conduit with a one -hour, fire -rated barrier; the horizontal separation of 8 ' between conduit and valve and 16 ' between the valves themselves; the height of the valves from the floor; and considering the absence of in situ combustibles in the zone provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III G.2.c "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved.

d. Fire Zone PAB

-F-2A-Z (Tabulation 3.2.7.68)

1) Specific Zone Analysis This zone at Elevation 25

'-0" of the PAB is bounded by concrete floor, ceiling and walls (South and East) and is contiguous to fire zones PAB -F-2B-Z and PAB -F-2C-Z. The northern boundary consists of partial height concrete walls and an 11 ' wide access passage. The western boundary consists of full height concrete walls and metal partitions. There are penetrations for tray, ducts, and pipes to other fire zones. The zone is approximately 44 ' long by 39' wide by 26 ' high with a floor area of 1550 sq. ft and a volume of 40,000 cu ft. No safe shutdown equipment is contained in the zone, only safe shutdown cables. Combustibles are 71 pounds of plastic (fiberglass ladders) for a total fire loading of 596 Btu per sq. ft. of floor area and limited in situ combustibles. This is classed as a low fire load. Detectors are provided throughout the zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-250 2) System Analyses a) Chemical and Volume Control (CS) System This zone contains cables routed in tray for the redundant boric acid tank level transmitters CS -LT-102 and CS-LT-106. These tank levels are only required once cooldown has been initiated. Should both transmitter cables be damaged by a fire, the operators can utilize the Train B level transmitter CS -LT-7464. This transmitter and its associated cable are not contained in this fire zone. The indicator for this transmitter is located at the RSS panel in the Train B switchgear room (Fire Area: CB -F-1B-A). This zone contains cables routed in tray and conduit for the boric acid pump CS -P-3A and for the boric acid to charging pumps isolation valve CS -V426. Cables for the redundant Train B boric acid pump CS -P-3B are routed in barriered conduits in Fire Zones PAB -F-2B-Z and PAB -F-2C-Z. Valve CS-V426 has no electrically operated redundant counterpart. Should the valve be damaged by a fire, the operator will establish a gravity path from the BAT 's to the charging pump suction by the repositioning to manual valves in the boric acid pump room (Fire Zone PAB-F-2B-Z). These valves are not required to be operated until boric acid is required for shutdown reactivity. This would be up to four hours into the event. See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-251 This zone contains cables for CS-FCV-110A, -111A, -110B, -111B. Spurious opening of these valves in conjunction with spurious start of a boric acid transfer pump or reactor makeup water pump may divert boric acid from the reactor coolant system affecting cold shutdown reactivity control, or result in an unplanned dilution affecting hot standby and cold shutdown reactivity control. The operators isolate the diversion flow by closing

CS-FCV-110B & -111B using the main control board control switches. The operators isolate the dilution flow by closing CS -LCV-112B or CS -LCV-112C using the main control board control switch. b) Containment Enclosure Air Handling (EAH) System This zone contains cable routed in barriered conduit for the Train B fan EAH -FN-5B. The cables for the redundant Train A fan EAH -FN-5A are routed in trays in fire zone PAB-F-2C-Z. There is approximately 16 ' horizontal separation between the barriered conduit and the redundant tray. c) Electrical Distribution Emergency (EDE) System All cables are Train A. The functionally redundant cables are located in other fire areas.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-252 d) PAB Air Handling (PAH) System Cables and equipment for outboard isolation dampers PAH-DP-35A and PAH -DP-36A and inboard isolation dampers PAH -DP-35B and PAH -DP-36B are routed in trays and conduits in proximity to one another. Under normal operation both outboard and both inboard dampers are open. If both outboard or both inboard dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. If the outboard dampers and the inboard dampers operate independently such that either the supply or the exhaust path but not both are isolated, there could be an air flow problem in EAH system. Outboard dampers are powered from a single Train A power supply. Inboard dampers are powered from a single Train B power supply. The circuit design for the outboard and inboard dampers is such that a spurious signal in either or both circuits will cause both outboard and inboard dampers to operate together, either both open (normal mode) or both closed (recirculation mode). This zone contains cables routed in tray for the Train A fan PAH-FN-42A and damper PAH -DP-357. The cables for the redundant Train B fan PAH -FN-42B and damper PAH-DP-358 are routed in barriered conduit in fire zone PAB-F-2C-Z. There is greater than 50 ' of horizontal separation between the tray and the redundant barriered conduit. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-253 e) Service Water (SW) System This zone contains cable routed in tray for the Train A pumps SW-P-41A and SW -P-41C and valve SW -V54. The cables for the redundant Train B pumps SW -P-41B and SW-P-41D and valve SW -V25 are routed in barriered conduits in fire zone PAB -F-1A-Z. There is approximately 25' of horizontal separation between the tray and the redundant barriered conduits. For the other Train A cables routed in this zone, the redundant cables and equipment are contained in other fire areas. f) Service Water Air Handling (SWA) System All cable are Train A, the redundant cables are located in other fire areas.

3) Summary For the CS system above, the provision of a manual valve alignment capability that is not required for up to four hours into the event satisfies the safe shutdown requirements. Also, the capability to isolate the boric acid diversion flow and the dilution flow using the main control board control switches satisfies the safe shutdown requirements.

For the EAH, PAH and SW systems above, the routing of the Train B cables in a one -hour, fire -rated barrier; the horizontal separation of 16 ', 25' and 50' respectively; and the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III.G.2.c, "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved. For the EDE and SWA systems above, the Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-254 e. Fire Zone PAB -F-2B-Z (Tabulation 3.2.7.69)

1) Specific Zone Analysis This zone at Elevation 25

'-0" of the PAB is bounded by concrete floor, ceiling and walls (South and West) and is contiguous to fire zones PAB -F-2A-Z and PAB -F-2C-Z. The northern and eastern boundaries consists of full height concrete walls and metal partitions. There are penetrations for tray, ducts and pipes to other fire zones. The zone is approximately 28 ' long by 37 ' wide by 16 ' high with a floor area of 1300 sq. ft. and a volume of 33,800 sq. ft. Combustibles are limited to 2.0 pounds of grease for a fire loading of 36,000 Btu and cables in open trays for a total fire loading of 6000 Btu per sq. ft. of floor area. Detectors are provided throughout the zone.

2) System Analyses a) Chemical and Volume Control (CS) System The redundant boric acid tank level transmitters CS

-LT-102 and CS-LT-106 are located in the same fire zone. Should both transmitters be unavailable due to fire damage, the operators can utilize the Train B level transmitter CS-LT-7464. This transmitter and its associated cable are contained in this fire zone. The indicator for this transmitter is located on the RSS panel in the Train B switchgear room (Fire Area: CB -F-1B-A). Should all level transmitters be unavailable, the operators will open the cross-connect valve s CS-V437 and CS -V1207 and boric acid tank isolation valves CS -V410 and CS -V416 allowing charging pump suction from both boric acid tanks. The combined inventory of the two tanks is sufficient to complete the cooldown thus eliminating the need for tank level monitoring.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-255 Redundant boric acid pumps CS -P-3A and CS -P-3B and the valve CS -V426 are located in the same fire zone. Should both pumps or the valve be damaged by the fire, th e operators will establish a gravity flow path from the BAT 's to the charging pump suction by repositioning of manual valves in the fire zone. Valves CS -V410, CS-V416, CS-V437, CS-V1207, CS-V439 and CS -V442 are manual valves required for gravity feed from the boric acid tanks to the charging pumps or cross-connecting the boric acid tanks in response to a loss of level indication. These valves are not required to be operated until boric acid is required for shutdown reactivity. This would be upon commencement of cooldown, up to four hours into the event, and the valves would then be accessible for manual operation. During this time the plant would be maintained in hot standby with RC inventory makeup provided by the RWST. See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g.

This zone contains cables for CS-FCV-110A, -111A, -110B, -111B and the valves. Spurious opening of these valves in conjunction with spurious start of a boric acid transfer pump or reactor makeup water pump may divert boric acid from the reactor coolant system affecting cold shutdown reactivity control, or result in an unplanned dilution affecting hot standby and cold shutdown reactivity control. The operators isolate the diversion flow by closing CS -FCV-110B & -111B using the main control board control switches. The operators isolate the dilution flow by closing CS -LCV-112B or CS-LCV-112C using the main control board control switch.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-256 b) PAB Air Handling (PAH) System This zone contains cables routed in tray and conduit for the Train A fan PAH -FN-42A and dampers PAH -DP-43A and PAH-DP-357. The cables for the redundant Train B fan PAH-FN-42B and dampers PAH -DP-43B and PAH-DP-358 are routed in barriered conduit in fire zone PAB-F-2C-Z. There is 4 ' horizontal separation between the Train A raceways and the Train B equipment and barriered conduit. The Train A trays are a minimum of 8 ' above floor Elevation 25 '-0". A total of 3 trays exist in the stack with the bottom tray an enclosed instrument level tray containing no Safe Shutdown cables. The Train B damper PAH-DP-358 is located approximately 18 ' above floor Elevation 25 '-0". 3) Summary For the CS system above, the provision of a manual valve alignment capability that is not required for up to four hours into the event satisfies the safe shutdown requirements. Also, the capability to isolate the boric acid diversion flow and the dilution flow using the main control board control switches satisfies the safe shutdown requirements. For the PAH system above, the routing of the Train B cables in conduit with a one -hour, fire -rated barrier in another zone of the PAB; the 4 ' horizontal between the Train A and Train B equipment; the 8 ' height of the tray above the floor; and considering the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III G.2.c. "in addition to 1 hour fire barrier, automatic fire suppression system shall be installed ", has been approved.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-257 f. Fire Zone PAB -F-2C-Z (Tabulation 3.2.7.70)

1) Specific Zone Analysis This zone at Elevation 25

'-0" of the PAB is bounded by concrete floors, ceilings and walls (North, East and West) and is contiguous to fire zones PAB -F-2A-Z and PAB -F-2B-Z to the South. The southern boundary consists of full height partitions, full and partial height concrete walls and an 11' wide access passage. There are penetrations for tray, ducts and pipes to other fire zones. The zone is approximately 100 ' long by 75 ' wide by 26 ' high with a floor area of 7,200 sq. ft. and a volume of 187,000 cu. ft. The trays installed at Elevation 25 '-0" are in stacks five and six high by four wide, as a worst case, with a minimum of 4 ' between the Train A and Train B stacks. There are several areas where the trays have vertical drops through the floor. With a limited number of exceptions, the trays are a minimum of 10 ' above the floor. Metal covers are provided around the vertical trays near column lines 2 and C. The in situ combustibles are limited to cables in open trays which provide a fire load of 16,000 Btu per square foot of floor area; the boron injection pumps which contain 0.25 gallons of oil are a fire loading of 37,500 Btu; the primary component cooling water pumps CC-P-11A, 11B, 11C and 11D containing a total of four gallons of oil for a fire loading of 600,000 Btu; 41/2 ton monorail crane hoist CS -CR-5 containing 0.5 gallons of oil for a fire loading of 75,000 Btu; and 31/2 ton monorail crane hoist CS -CR-13 containing 0.5 gallons of oil for a fire loading of 75,000 Btu. The concentrated fire load in this zone is 30,000 Btu per squar e foot of tray. Because of the concentrated fire load, we have installed sprinklers to control transient fires in the area of the trays. To protect the PCCW pumps against a fire from a transient combustible, we have installed a pre -action system, using high temperature heads over the pumps and the surrounding area. Spray shields will be installed over the PCCW pump motors. Detectors are provided throughout the zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-258 2) System Analyses a) Primary Component Cooling Water (CC) System The redundant Primary Component Cooling Water (PCCW) pumps are located in the same fire area. The CC System is configured such that there are two 100% capacity PCCW pumps in each train either of which can be utilized for safe shutdown. The spatial separation between Train A pump CC-P-11A and Train B pump CC -P-11D is in excess of 20' with a metal partition between them. The spatial separation between Train A pump CC -P-11C and Train B pump CC-P-11B is in excess of 20 ' with a metal partition between them. The cables to the Train B pumps are routed in barriered conduit from the point they enter the PAB to the pump motors. The conduits are barriered in the vicinity of the Train B pumps. The Train B pumps have a spatial separation of 25 ' from the Train A trays and 15 ' from the Train B trays. The redundant PCCW heat exchanger valves CC-TV-2171-1, 2 and CC -TV-2271-1, 2 and their associated controls and instrument rack MM -IR-93 are located in the same fire area. The cables for the Train B valves CC -TV-2271-1 and CC-TV-2271-2 and the Train B controllers are routed in barriered conduits. The only exception is a reduction in the barriers at the controllers and valves due to interference with instrument lines. The redundant valves are mounted approximately 20 ' above the floor with a minimum separation of 2 '. The controllers are wall and instrument rack mounted and are separated by approximately 20 '. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-259 The redundant temperature elements CC -TE-2171, CC-TE-2197 and CC -TE-2271, CC-TE-2297 are located in the same fire area. The cable for one of the redundant Train B temperature elements is routed in a barriered conduit. The trip logic is a 2 out of 2 logic. The redundant temperature elements have a horizontal separation of approximately 8 ' and are mounted on 24 " component cooling water pipes approximately 20 ' above the floor. Cables for the redundant head tank level transmitters are in proximity. Failures in these cables could initiate a spurious

lo-lo-head tank level isolation signal. This in turn would result in closure of the PCCW containment isolation valves. These valves are only required when it is necessary to maintain containment habitable for containment entry to manually operate the RHR isolation valves and the SI accumulator isolation valves. The circuitry for these valves is not affected by a fire in this area; hence, they would be operable from the MCR. Therefore, the spurious operation of these transmitters will not prevent safe shutdown. b) Chemical and Volume Control (CS) System This zone contains cables in tray required for operation of Train A valve CS -FCV-121, which provides one of the required hot standby charging flow paths. The redundant Train B valve SI -V139 cables are routed in barriered conduit in Fire Zone PAB -F-1A-Z and are separated from the Train A cables by concrete floors. For cooldown, the operators will manually align the Train B charging pump discharge and bypass valves (CS-V219 and CS -V220) to the seal injection flow path and throttle the bypass valve as required. This operator action can be delayed for up to of 4 hours into the event. This zone contains cables in barriered conduit for the charging to RCS isolation valve CS -V143. The cables for the redundant valve CS -V142 are not contained in this fire area. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-260 This zone contains cables routed in tray for the redundant boric acid tank level transmitters CS -LT-102 and CS-LT-106. These tank levels are only required once cooldown has been initiated. Should both transmitter cables be damaged by a fire, the operators can utilize the Train B level transmitter CS -LT-7464. This transmitter 's cable is contained in this fire zone. The indicator for this transmitter is located at the RSS panel in the Train B switchgear room (Fire Area: CB -F-1B-A). Should all level transmitters be unavailable, the operators will open th e cross-connect valve CS -V437 allowing charging pump suction from both boric acid tanks. The combined inventory of the two tanks is sufficient to complete the cooldown thus eliminating the need for tank level monitoring. This zone contains cables routed in tray and conduit for the redundant boric acid pumps CS -P-3A and CS -P-3B and for the valve CS -V426. Should both pumps or the valves be damaged by a fire, the operator will establish a gravity path from the BAT 's to the charging pump suction by the repositioning of manual valves in the boric acid pump room (Fire Zone PAB -F-2B-Z). Some of these valves are also required to cross -connect the boric acid tanks in response to a loss of level indication (see above discussion). These valves are not required to be operated until boric acid is required for shutdown reactivity. This would not be required for up to four hours into the event. This zone contains cables routed in tray and conduit for the Train A charging pump CS-P-2A. The cable for the redundant Train B pump CS -P-2B are routed in a barriered conduit in Fire Zone PAB -F-1A-Z. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-261 The zone contains cables routed in tray and conduit for the redundant valves CS -LCV-112B, CS-LCV-112D, CS-LCV-112C and CS -LCV-112E. The cables for valves CS-LCV-112C and CS -LCV-112E are routed in barriered conduits. The only exception is at an interference with fire detectors where the one -hour wrap is reduced to allow air flow to the detector. At the point of the reduced one -hour wrap, there is a minimum of 20 ' of horizontal separation to functionally redundant cables. See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g.

This zone contains cables for CS-FCV-110A, -111A, -110B, -111B. Spurious opening of these valves may divert boric acid from the reactor coolant system affecting cold shutdown reactivity control, or result in an unplanned dilution affecting hot standby and cold shutdown reactivity control. The operators isolate the diversion flow by tripping the control circuit power supply breaker to close CS -FCV-110B & -111B (valves fail closed). The operators isolate the dilution flow by closing

CS-LCV-112C using the main control board control switch. This zone contains cables routed in trays for valve CS-V196. The cables for the redundant Train B valve CS-V197 are routed in a barrier conduit in Fire Zone PAB-F-1A-Z. c) Containment Enclosure Air Handling (EAH) System The cables for the redundant fans EAH -FN-5A and EAH-FN-5B, are routed in tray and conduits in the same area. All the Train B fan cables are routed in barriered conduits, which are separated from the Train A cables by a minimum of 18 '. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-262 Cables for redundant equipment vault return fans EAH-FN-31A and EAH -FN-31B are routed in trays and conduits in proximity to one another. These fans are required to maintain the equipment vaults habitable for entry if manual operations are required to place RHR into operation for cold shutdown. A fire in the PAB fire area will not prevent operation from the MCR of any equipment necessary for RHR operation; hence, habitability of the equipment vaults is not required. Analysis and field testing has confirmed that the containment enclosure supply fans EAH-FN-5A and EAH-FN-5B are sufficient to maintain the equipment vaults below the equipment 's qualified temperatures. d) Electrical Distribution Emergency (EDE) System All cables are Train A. The functionally redundant cables are located in other fire areas. e) PAB Air Handling (PAH) System Cables and equipment for outboard isolation dampers (PAH-DP-35A and PAH -DP-36A and inboard isolation dampers PAH -DP-35B and PAH -DP-36B are routed in trays and conduits in proximity to one another. Under normal operation both outboard and both inboard dampers are open. If both outboard or both inboard dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in recirculation mode. The normal and recirculation modes for EAH system operation both satisfy

the safe shutdown function. If the outboard dampers and the inboard dampers operate independently such that either the supply or the exhaust path but not both are isolated, there could be an air flow problem in EAH system.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-263 Outboard dampers are powered from a single Train A power supply. Inboard dampers are powered from a single Train B power supply. The circuit design for the outboard and inboard dampers is such that a spurious signal in either or both circuits will cause both outboard and inboard dampers to operate together, either both open (normal mode) or both closed (recirculation mode). The redundant PAH fans (PAH -FN-42A and PAH-FN-42B) and dampers (PAH -DP-43A, PAH-DP-357, PAH-DP-43B and PAH -DP-358) are in proximity. The fans and dampers are inside separate metal enclosures located approximately 15 ' above the floor. The Train B fan and damper cables are routed in barriered conduits. The only exception to the barrier is short lengths of flexible conduit whose wrapping would interfere with damper

operator PAH -DP-358. There are no cable trays in the vicinity of the fans and dampers. The only in situ combustibles in the vicinity are in the PCCW pumps which are separated from the fans and dampers by greater than 20 ' horizontally and the monorail crane hoist. These fans are not needed unless the main ventilation system is lost due to the loss of off -site power or unless the temperature in the immediate area exceeds 40C (104F). The redundant temperature switches PAH -TSH-5391 and PAH-TSH-5393 and conduits containing their cables are located in proximity. Failure of these switches or their cables could prevent operation of fans PAH -FN-42A and PAH-FN-42B. Should the switches or cables fail, the operators can isolate the affected portion of the circuit at the RSS facilities in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A) and restart the fans.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-264 f) Service Water (SW) System This zone contains cables routed in tray for the Train A pumps SW-P-11A and SW -P-11C and valve SW -V54. The redundant Train B pumps and valve cables are routed in a barriered conduit in Fire Zone PAB -F-1A-Z which is separated from this zone by an intervening concrete floor. The cables for redundant valves SW -V4, SW-V16, SW-V5 and SW-V18, are located in the same fire zone. These valves may be required to reposition to isolate secondary component cooling water or for DG cooling. The Train B valves SW -V5 and SW -V18 cables are routed in barriered conduits and are separated from the Train A cables by greater than 30' horizontally. There are no cable trays or other in situ combustibles in the vicinity of Train B conduits. The cables for redundant valves SW -V-15 and SW -V17 are located in the same fire zone. These valves are normally in their safe shutdown position to provide cooling to the PCCW heat exchangers. In addition, the circuit breaker for

SW-V17 is administratively controlled off so the valve cannot spuriously close. If SW -V15 spuriously closes, SW-V17 is still open to provide the Train B PCCW heat exchanger cooling function. Redundant valves SW -V20, SW-V34 and SW -V19, SW-V23 are located in the same fire zone. Operators for valves SW -V34 and SW -V23 are approximately 5 ' above floor Elevation 25 '-0" and operators for valves SW -V20 and SW-V19 are approximately 10' above floor Elevation 25'-0". The redundant valves are separated by approximately 16 ' horizontally. There are no cable trays in the vicinity of the valves. The only in situ combustibles in the vicinity are the PCCW pumps which are separated from the Train A valves by greater than 16 ' horizontally. The valves are in Safe Shutdown position. The operators will prevent spurious operation by tripping the power supply breakers at the Train A and Train B Switchgear Rooms (Fire Area: CB -F-1A-A and CB-F-1B-A). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-265 For the other Train A cables routed in this zone, the redundant cables and equipment are contained in other fire areas. g) Service Water Air Handling (SWA) System All cables are Train A. The redundant functionally cables are located in other fire areas. 3) Summary For the CC system above, the routing of the Train B cables in conduit with a one -hour, fire -rated barrier; the spatial separation; and the provision of the sprinkler system, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. For the CS system charging pumps and the related CS and SI valves above, the routing of the Train B cables in conduit with a

one-hour, fire -rated barrier and the provision of suppression in the area of the trays and the PCCW pumps, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. For the CS system transmitters, boric acid pumps and related valve above, the provision of a manual valve alignment capability that is not required for up to four hours into the event satisfies the safe shutdown requirements. Also, the capability to isolate the boric acid diversion flow by tripping the control circuit power supply breaker and isolate the dilution flow using the main control board control switches satisfies the safe shutdown requirements. For the EAH system supply fans above, the routing of Train B cables in conduit with a one -hour, fire -rated barrier and the provision of suppression in the area of the trays and the PCCW pumps, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. For the EAH system return fans above, the safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-266 For the PAH dampers above, the safe shutdown requirements are satisfied. For the PAH fans and related dampers above, the routing of the Train B cables in conduits with a one -hour, fire -rated barrier; the height of the fans off the floor; the lack of combustibles in the area of the fans and the fact that a fire in the area could not cause loss of offsite power, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. For the PAH temperature switches above, the safe shutdown requirements are satisfied. For the SW system above, the routing of the Train B cables in a conduit with a one -hour, fire -rated barrier; the spatial separation and the provision of the sprinkler system, provide acceptable fire protection and provide protection equivalent to the technical requirement of Appendix R. For the EDE and SWA systems above, the Appendix R separation requirements are satisfied.

g. Fire Zone PAB

-F-3A-Z (Tabulation 3.2.7.71)

1) Specific Zone Analysis This zone at Elevation 53

'-0" of the PAB is bounded by concrete floor, ceiling and walls (North, East and West) and is contiguous to fire zone PAB -F-3B-Z to the South. The southern boundary consists of a full height partition wall. There are penetrations for tray, ducts and pipes to other fire zones. The zone is approximately 53 ' long by 75 ' wide by 26 ' high with a floor area of 4000 sq. ft. and a volume of 103,400 cu. ft. Combustibles are limited to 1.0 gallon of oil for a fire loading of 150,000 Btu and cables in open trays for a total fire loading of 3000 Btu per sq. ft. of floor area. Detectors are provided throughout the zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-267 2) System Analyses a) Primary Component Cooling Water (CC) System Redundant transmitters and cables for head tank level logic are in proximity. Failures in these transmitters or cables could initiate a spurious lo -lo head tank level isolation signal. This in turn, would result in closure of the PCCW containment isolation valves. These valves are only required when it is necessary to maintain containment habitable for containment entry to manually operate the RHR isolation valves and the SI accumulator isolation valves. The circuitry for these valves is not affected by a fire in this area; hence they would be operable from the MCR. Therefore, the spurious operation of these transmitters will not prevent safe shutdown. b) Chemical and Volume Control (CS) System This zone contains cables routed in tray for the Train A valves CS-LCV-112B and CS-LCV-112D. The Train B cables are routed in barriered conduits in fire zone PAB-F-3B-Z. See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g. This zone contains cables for CS-FCV-110A, -111A, -110B, -111B. Spurious opening of these valves in conjunction with spurious start of boric acid transfer pump or reactor makeup water pump may divert boric acid from the reactor coolant system affecting cold shutdown reactivity control, or result in an unplanned dilution affecting hot standby and cold shutdown reactivity control. The operators isolate the diversion flow by closing

CS-FCV-110B & -111B using the main control board control switches. The operators isolate the dilution flow by closing CS -LCV-112C using the main control board control switch. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-268 c) Service Water (SW) System This zone contains Train A valves SW -V15 and SW -V16 and cables for Train A valve SW -V4. Also contained in this zone are the redundant Train B valves SW -V17 and SW-V18 and cables for valve SW -V5. Redundant valves SW -V15 and SW -V17 are in the Safe Shutdown position. In addition, the circuit breaker for SW-V17 is administratively controlled off so the valve cannot spuriously close. If SW -V15 spuriously closes, SW-V17 is still open to provide the Train B PCCW heat exchanger cooling function. For conservatism, the operators will prevent further spurious operation by tripping the SW -V15 power supply breaker in the Train A switchgear room (Fire Area: CB -F-1A-A). Redundant diesel generator jacket water heat exchanger valves SW -V16 and SW-V18 are normally closed and are required to open for operation of the diesel generators.

De-energizing the solenoids will open the valves. If SW-V16 or SW -V18 spuriously closes, SW to the respective train DG would be isolated. The other train DG

would still be available. Also, a fire in this area does not cause a loss -of-offsite power. To prevent further spurious operation, the operators will trip the valves ' power supply breakers in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The Train A cables for valve SW -V4 are routed in trays and conduit. The trays and conduit are a minimum of 10 ' above floor Elevation 53 '-0". The Train B cables for valve SW-V5 are routed in barriered conduits. The Train A and Train B raceways are separated by greater than 25 '. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-269 3) Summary For the CC system above, the safe shutdown requirements are satisfied. For the CS system above, the routing of the Train B cables in conduit with a one -hour, fire rated barrier in another fire zone and considering the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III G.2.c, "in addition to one (1) hour fire barrier, an automatic fire suppression system shall be installed ", has been approved. Also, the capability to isolate the boric acid diversion flow and the dilution flow using the main control board control switches satisfies the safe shutdown requirements. For the SW system above, the routing of the Train B cables in a conduit with a one -hour, fire -rated barrier; the spatial separation; the disabling capabilities in another fire area; and considering the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III G.2.c, "in addition to one (1) hour fire barrier, an automatic fire suppression system shall be installed ", has bee n approved.

h. Fire Zone PAB

-F-3B-Z (Tabulation 3.2.7.72)

1) Specific Zone Analysis This zone at Elevation 53

'-0" of the PAB is bounded by concrete floor, ceiling and walls (South, East and West) and is contiguous to fire zone PAB -F-3A-Z to the North. The northern boundary consists of a full height partition wall. There are penetrations for ducts and pipes to other fire zones. The zone is approximately 88 ' long by 75 ' wide by 26 ' high with a floor area of 6500 sq. ft. and a volume of 168,200 cu. ft.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-270 Combustibles are limited to 71 pounds of plastic (fiberglass ladders) for a fire loading of 923,000 Btu, 0.5 gallon of oil for a fire loading of 75,000 Btu, 50 pounds of Class A material for a fire loading of 400,000 Btu for a total fire loading of 1602 Btu per sq. ft. of floor area. See "Fire Protection Program Evaluation and Comparison to Branch Technical Position APCSB 9.5 -1 Appendix A" for the analysis of 6600 lbs. of charcoal in CAP-F-40. Detectors are provided throughout the zone.

2) System Analysis a) Primary Component Cooling Water (CC) System Redundant transmitters and cables for head tank level logic are in proximity. Failures in these transmitters or cables could initiate a spurious lo

-lo head tank level isolation signal. This in turn would result in closure of the PCCW containment isolation valves. These valves are only required when it is necessary to maintain containment habitable for containment entry to manually operate the RHR isolation valves and the SI accumulator isolation valves. The circuitry for these valves is not affected by a fire in this area; hence, they would be operable from the MCR. Therefore, the spurious operation of these transmitters will not prevent safe shutdown. b) Chemical and Volume Control (CS) System The redundant volume control tank isolation valves

CS-LCV-112B and CS -LCV-112C are located in the same fire area. The valves are in separate concrete cells with concrete walls and a solid controlled access door between them. There are no in situ combustibles or cables in trays in the cells. The cables for the Train B valve CS-LCV-112C are routed in barriered conduits. See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-271 This zone contains cables for the redundant RWST suction valves CS -LCV-112D and CS -LCV-112E. These cables are part of a circuit that will automatically open the opposite train RWST valve if a VCT valve is not full open (i.e., spuriously closes). Since the VCT valves do not spuriously close for a fi re in this zone, the automatic open circuit is not required. The automatic open circuit is supplied from a separate circuit, i.e., not the RWST MOV control circuit, so failure of these cables does not affect the ability to manually open the RWST valves as part of transferring charging pump suction from the VCT to the RWST. This zone contains cables for

CS-FCV-110A, -111A, -110B, -111B. Spurious opening of these valves in conjunction with spurious start of a boric acid transfer pump or reactor makeup water pump may divert boric acid from the reactor coolant system affecting cold shutdown reactivity control, or result in an unplanned dilution affecting hot standby and cold shutdown reactivity control. The operators isolate the diversion flow by closing CS-FCV-110B & -111B using the main control board control switches. The operators isolate the dilution flow by closing CS -LCV-112C using their main control board control switch.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-272 3) Summary For the CC system above, the safe shutdown requirements are satisfied. For the CS system above, the routing of the Train B cables in a one-hour, fire -rated barrier; the separation between the valves; the absence of in situ combustibles in the cells; and considering the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R Paragraph III G.2.c, "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved. Also, the capability to isolate the boric acid diversion flow and the dilution flow using the main control board control switches satisfies the safe shutdown requirements. C. Evaluation Deviations from the Appendix R, Paragraph III.G.2 separation requirements exist in the Primary Auxiliary Building fire zones PAB -F-1A-Z, PAB-F-1J-Z, PAB-F-1K-Z, PAB-F-2A-Z, PAB-F-2B-Z, PAB-F-2C-Z, PAB-F-3A-Z and PAB-F-3B-Z. These deviations are justified based on the above analyses and our assertion that additional modifications would not enhance fire protection safety.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-273 Tabulation 3.2.7.74 Primary Auxiliary Building Fire Area - PAB-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-P-2A x x CS-PS-7467-1 x x CS-V210 x CS-V221 x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area PAB -F-1D-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-274 Tabulation 3.2.7.75 Primary Auxiliary Building Fire Area - PAB-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-P-2B x x CS-PS-7468-1 x x CS-V219 x CS-V220 x B. Analysis All equipment and cables are Train B. The redundant Train A equipment and cables are in Fire Area PAB -F-1C-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-275 Tabulation 3.2.7.76 Primary Auxiliary Building Fire Area - PAB-F-1E-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-FCV-121 x CS-FI-121B x x CS-FT-121 x B. Analysis Cables and equipment necessary for operation of valve CS -FCV-121 are contained in this fire area. This valve is part of the seal injection flow path. The cables and equipment for valves SI -V-138 and SI -V-139 which are part of the functionally redundant high head injection path are not contained in this fire area; hence they will be available for hot standby. For cooldown, the operators will manually align the charging pump discharge and bypass valves (CS -V210, CS-V221 or CS -V219, CS-V220) to the seal injection flow path and throttle the bypass valves as required. C. Evaluation The safe shutdown requirements and the Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-276 Tabulation 3.2.7.77 Primary Auxiliary Building Fire Area - PAB-F-1G-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-LT-2172-1 x CC-LT-2192-1 x CC-LT-2172-2 x CC-LT-2192-2 x CC-LT-2172-3 x CC-LT-2192-3 x CC-LT-2272-1 x CC-LT-2292-1 x CC-LT-2272-2 x CC-LT-2292-2 x CC-LT-2272-3 x CC-LT-2292-3 x CC-P-11A x CC-P-11C x CC-TE-2171 x CC-TV-2171-1 x CC-TV-2171-2 x CC-V145 x CC-V272 x CC-V175 x CC-V257 x CC-V1101 x CC-V1109 x CS-FT-121 x CS-FCV-110A x CS-FCV-111A x CS-FCV-110B x CS-FCV-111B x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-277 Primary Auxiliary Building Fire Area - PAB-F-1G-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-FCV-121 x CS-HCV-182 x CS-LCV-112B x CS-LCV-112D x CS-LT-102 x CS-LT-106 x CS-P-2A x CS-P-2B (1) (1) CS-P-3A x CS-V142 x CS-V154 x CS-V158 x CS-V162 x CS-V166 x CS-V167 x CS-V196 x CS-V426 x CS-V460 x CS-V475 x CS-V461 x EAH-FN-5A x EAH-FN-31A x EDE-MCC-513 x PAH-DP-35A x PAH-DP-35B x PAH-DP-36A x PAH-DP-36B x PAH-DP-43A x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-278 Primary Auxiliary Building Fire Area - PAB-F-1G-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable PAH-DP-357 x PAH-FN-42A x (1) CS-P-2B and its cables are not actually located in this fire area. However, CS -P-2B is listed because it is potentially affected via a systems interaction. See Analysis Section B.18. RC-V23 x RC-V22 x RC-V88 x RC-V87 x RH-FCV-618 x RH-FCV-619 x RH-HCV-606 x RH-HCV-607 x RH-V14 x RH-V26 x RH-V35 x RH-V36 x RH-V70 x RH-V32 x SI-PT-937 x SI-PT-936 x SI-V138 x SW-FN-51A x SW-P-41A x SW-P-41C x SW-P-110A x SW-V4 x SW-V15 x SW-V16 x SW-V20 x SW-V34 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-279 Primary Auxiliary Building Fire Area - PAB-F-1G-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-V54 x SW-V56 x SW-V74 x SW-V139 x SWA-DP-66 x SWA-FN-64 x SWA-FN-71 x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown cables. The redundant Train B safe shutdown cables are located in fire area DCT -F-3B-0 and other fire areas. The Appendix R separation requirements are satisfied.

2. PCCW Head Tank level Transmitters CC

-LT-2172-1, 2, 3; CC -LT-2272-1, 2, 3; CC-LT-2192-1, 2, 3, CC -LT-2292-1, 2, 3 Cables for the redundant head tank level transmitters are in proximity. Failures in these cables could initiate a spurious lo -lo-head tank level isolation signal. This in turn would result in closure of the PCCW containment isolation valves. These valves are only required when it is necessary to maintain containment habitable for containment entry to manually operate the RHR isolation valves and the SI accumulator isolation valves. The circuitry for these valves is not affected by a fire in this area; hence, they would be operable from the MCR. Therefore, the spurious operation of these transmitters will not prevent safe shutdown. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-280 3. Component Cooling Water Pumps CC -P-11A, CC-P-11C and Component Cooling Water Containment Isolation Valves CC -V175, CC-V257 A fire could cause loss of all PCCW to containment. It should be noted, however, that these valves are required to remain operable only for containment entry when manual operation of the safety injection isolation valves SI -V3, SI-V17, SI-V32 and SI-V47 and the reactor coolant - RHR isolation valves RC -V22, RC-V23, RC-V87 and RC -V88 are required. Cables for these valves are not routed through this fire area; hence, the valves would be operable from the main control room or the RSS control panels and containment entry would not be required. The safe shutdown requirements are satisfied.

4. RHR Heat Exchanger Outlet Valves CC

-V145, CC-V272 Cables for redundant valves CC -V145 and CC -V272 are routed in proximity to one another. The valves are normally open to their shutdown cooling position and their position is inconsequential until the plant is cooled down to 350F and the RH system is placed in operation. At that time, it is necessary to assure that the valve supplying PCCW to the operational RH train is opened. This can be accomplished manually if required in the appropriate equipment vault. Manual operation can be delayed as much as 9 hours into the event. Therefore, no fire protection other than the existing separation is needed. The provision of a capability to position the valve outside the fire area satisfies the safe shutdown requirements.

5. Charging Pump Discharge Valve CS

-FCV-121 This zone contains cables in tray required for operation of Train A valves

CS-FCV-121, which provides one of the required hot standby charging flow paths. The redundant Train B SI-V139 cables are located in Fire Area DCT-F-3B-0. For cooldown, the operators will manually align the Train B charging pump discharge and bypass valves (CS -V219 and CS -V220) to the seal injection flow path and throttle the bypass valve as required. This operator action can be delayed for up to of 4 hours. The Appendix R separation and safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-281 6. Boric Acid Tank Level Transmitter CS -LT-102, CS-LT-106 This zone contains cables routed in tray for the redundant boric acid tank level transmitters CS -LT-102 and CS -LT-106. These tank levels are only required once cooldown has been initiated. Should both transmitter cables be damaged by a fire, the operators can utilize the Train B level transmitter CS -LT-7464 whose cable is not routed through this fire area. The indicator for this transmitter is located at the RSS panel in the Train B switchgear room (Fire Area: CB -F-1B-A). The provision of a redundant transmitter with its cable routed in another fire area satisfies the safe shutdown requirements.

7. Seal Injection Isolation Valves CS

-V154, CS-V158, CS-V162 and CS -V166 Under normal conditions, the seal injection isolation valves CS -V154, CS-V158, CS-V162 and CS -V166 are utilized for the seal injection flow path. Spurious closure of one of these valves will not prevent safe shutdown. The operators will prevent further spurious operations by tripping the power supply breakers in the Train A switchgear room (Fire Area: CB -F-1A-A). The safe shutdown requirements are satisfied.

8. RC Pump Seal Water Isolation Valve CS

-V167 Valve CS-V167 is a normally open valve which should remain open for safe shutdown. Spurious isolation of this Train A valve could result in loss of RC inventory through the upstream relief valve. This inventory is directed to the PRT and is therefore, non -recoverable. To preclude this loss of inventory, functionally redundant isolation capability is provided by the RC pump seal return lines by means of Train A valves CS -V10, CS-V28, CS-V44, and CS -V59. The cables, controls and equipment required for operation of valves CS -V10, CS-V28, CS-V44, and CS -V59, are not contained in this fire area. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-282 9. BAT to Charging Pump Isolation Valve CS -V426 Valve CS-V426 is a normally closed valve which is opened to provide a path from the boric acid tanks to the charging pump suction. This path is required to begin cooldown. In the event that this valve is inoperable, the operators can provide a redundant path by manually positioning valves in the boric acid tank room (Fire Area: PAB -F-2B-Z). The operators can maintain the plant in hot standby for the time required to perform this manual action. The safe shutdown requirements are satisfied.

10. SI-CS Suction Cross Connection Valves CS

-V460, CS-V461, CS-V475 Valves CS -V460, CS-V461 and CS -V475 are located in proximity. Prior to beginning cooldown the normally closed CS -V460 and CS -V461 valves should remain closed or the functionally redundant valve CS -V475 should be closed. The isolation of this path will prevent loss of boric acid tank inventory to the RWST during cooldown. In the event of a spurious valve operation which renders this flow path open, the plant can be maintained in hot standby for as long as 4 hours. Should the operators desire to initiate the cooldown sooner than 4 hours, a gravity feed can be established from the boric acid tanks to the charging pumps. As the BAT head is lower than that required to return inventory to the RWST, there would be no loss of BAT inventory through this path and the position of these valves would be inconsequential. The safe shutdown requirements are satisfied.

11. Containment Enclosure Isolation Damper, PAH

-DP-35A, PAH-DP-36A, PAH-DP-35B, PAH-DP-36B Cables for outboard isolation dampers PAH -DP-35A and PAH -DP-36A and inboard isolation dampers PAH -DP-35B and PAH -DP-36B are routed in trays and conduits in proximity to one another. Under normal operation both outboard and both inboard dampers are open. If both outboard or both inboard dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. If the outboard dampers and the inboard dampers operate independently such that either the supply or the exhaust path but not both are isolated, there could be an air flow problem in EAH system. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-283 Outboard dampers are powered from a single Train A power supply. Inboard dampers are powered from a single Train B power supply. The circuit design for the outboard and inboard dampers is such that a spurious signal in either or both circuits will cause both outboard and inboard dampers to operate together, either both open (normal mode) or both closed (recirculation mode). The safe shutdown requirements are satisfied.

12. RHR Isolation Valves RC

-V22, RC-V23, RC-V87, RC-V88 Cables for redundant valves are located in proximity. As the RHR isolation valves are permanently disabled in the closed position, failures in the cables cannot cause a spurious operation. Valves RC -V87 and RC -V88 are required to be opened for cooldown below 350F when the RH system is placed in operation. Should the cable damage be such that the valves cannot be operated from the MCR, the affected portion of the circuit can be isolated at the RSS panels in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A) and the valves repositioned for safe shutdown. The safe shutdown requirements are satisfied.

13. RHR Heat Exchanger Outlet Flow Control and Bypass Flow Control Valves RH-FCV-618, RH-HCV-606, RH-FCV-619, RH-HCV-607 Cables for the redundant flow control valves are routed in proximity. The RH-HCV-606 and RH

-HCV-607 valves are normally closed and are required to open whereas the RH -FCV-618 and RH -FCV-619 are normally open and are required to close. These valves are only required to operate when the RH system is placed in operation (cold shutdown). The valves have air operators controlled by dc solenoids. These solenoids when deenergized vent the air from the operators and cause the valves to fail to their safe shutdown position. In the event this positioning cannot be performed in the MCR, the operators will position these valves by tripping the power supply breakers in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-284 14. RH Pump to Cold Leg Isolation Valves RH -V14, RH-V26 Cables for redundant valves RH -V14 and RH -V26 are routed in proximity. These valves are normally open valves which are required to remain open for RH systems operation (cold shutdown). If one of the valves spuriously closes, the operators will prevent further spurious operation of these valves by tripping the power supply breakers in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

15. RH Pump to Hot Leg Isolation Valves RH

-V70, RH-V32 Cables for redundant valves RH -V70 and RH -V32 are routed in proximity. These valves are normally closed valves which are required to remain closed for RH system operation (cold shutdown). If one of the valves spuriously opens, the operators will prevent further spurious operation of these valves by tripping the power supply breakers in the Train A and Train B switchgear rooms (Fire Areas: CB-F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

16. RH Heat Exchanger to CS/SI Pump Isolation Valves RH-V35, RH-V36 Cables for the redundant valves RH

-V35 and RH -V36 are routed in proximity. Valves RH -V35 and RH -V36 are normally closed and their position is inconsequential until the plant is cooled down to 350F and the RH system is placed in operation. At that time it is necessary to assure that the valves remain closed. Should one of the valves open spuriously the operators can disable its power supply in either the Train A or Train B switchgear rooms (Fire Areas: CB-F-1A-A or CB-F-1B-A) and manually reposition the valves located in the equipment vaults (Fire Zone RHR -F-4B-Z or RHR-F-2A-Z). Manual operation of the valves can be delayed as much as 9 hours into the event. Therefore, no fire protection other than the existing separation is needed. The provision of a capability to mitigate the spurious operation of the valves outside the fire area satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-285 17. Containment Pressure Transmitters SI -PT-936, SI-PT-937 Redundant channels of containment pressure cables are located in proximity. Spurious operation of these channels will initiate containment spray and containment isolation Phase B. The operators will have the capability to terminate these protective actions by use of manual reset switches. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB-F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

18. Volume Control Tank Isolation Valve CS

-LCV-112B and Charging Pump CS-P-2A & CS-P-2B Volume control tank (VCT) isolation valves CS -LCV-112B & -112C are normally open to provide a suction path from the VCT to the normally operating charging pump (CS -P-2A or -2B). These valves must stay open until RWST valve CS-LCV-112D or -112E is manually opened to provide a charging pump suction path from the RWST, or the boric acid tanks are manually aligned as a charging pump suction source. Spurious closure of a VCT isolation valve caused by a hot short would interrupt suction flow to the operating charging pump

causing it to be damaged. If the standby charging pump has cables in the same area then its operation can also be degraded. The result would be no charging system flow. Since this fire area contains cables for CS -LCV-112B and CS -P-2A, this condition is potentially applicable for the system alignment with CS -P-2A the standby pump and CS -P-2B the operating pump. The CS-LCV-112B circuit design prevents spurious valve closure from hot shorts as follows. The field cable conductors for the motor control center (MCC) contactor close coil circuit are in different cables than the 120 V "hot" circuit conductors eliminating the hot short failure mode within the cables. Cable-to-cable hot shorts need not be postulated for thermoset cable insulation as used at Seabrook. Since CS -LCV-112B will not spuriously close, CS -P-2B as the operating charging pump will not be damaged. Since charging flow is available, the safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-286 19. Boration/Dilution Flow Control Valves, CS -FCV-110A, -111A, -110B, -111B This area contains cables for CS -FCV-110A, -111A, -110B, -111B. Spurious opening of these valves in conjunction with spurious start of a boric acid transfer pump or reactor makeup water pump may divert boric acid from the reactor coolant system affecting cold shutdown reacivity control, or result in an unplanned dilution affecting hot standby and cold shutdown reactivity control. The operators isolate the diversion flow by closing CS -FCV-110B and -111B using the main control board control switches. The operators isolate the dilution flow by closing CS -LCV-112C using the main control broad switch. The safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-287 Tabulation 3.2.7.78 Primary Auxiliary Building - Stairwell (N) Fire Area - PAB-F-S1-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-288 Tabulation 3.2.7.79 Primary Auxiliary Building - Stairwell (S) Fire Area - PAB-F-S2-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-289 Tabulation 3.2.7.80 Equipment Vault - Train B (Vault #2) Fire Area - RHR-F-1A-Z, RHR-F-1C-Z, RHR-F-2A-Z, RHR-F-3A-Z, RHR-F-4A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-V272 x x CS-V461 x CS-V475 x RC-V22 x RC-V88 x RC-V87 x RH-E-9B x RH-HCV-607 x x RH-FCV-619 x x RH-P-8B x x RH-V26 x RH-V32 x RH-V35 x RH-V36 x x RH-V44 x SI-V89 x x SI-V89 x x B. Analysis 1. General Systems/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A safe shutdown equipment and cables are located in Train A Vault (Vault #1) (Fire Areas: RHR -F-1B-Z, RHR-F-1D-Z, RHR-F-2B-Z, RHR-F-3B-Z, RHR-F-4B-Z) or other fire areas. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-290 2. SI-CS Suction Cross Connection Valves CS -V461, CS-V475 Valves CS -V461 and CS-V475 are located in proximity. Prior to beginning cool down the normally closed valve CS -V461 should remain closed or the functionally redundant valve CS -V475 should be closed. The isolation of this path will prevent loss of boric acid tank inventory to the RWST during cooldown. In the event of a spurious valve operation, which renders this flow path open, the plant can be maintained in hot standby for as long as 4 hours. Should this area be inaccessible due to the fire or should the operators desire to initiate the cooldown sooner than 4 hours, a gravity feed can be established from the boric acid tanks to the charging pumps. As the BAT head is lower than that required to return inventory to the RWST, there would be no loss of BAT inventory through this path and the position of these valves would be inconsequential. The safe shutdown requirements are satisfied.

3. RHR Isolation Valves RC

-V22, RC-V87, RC-V88 Cables, for functionally redundant valves are located in proximity. As the RHR isolation valves are permanently disabled in the closed position, failures in the cables cannot cause a spurious operation. Valve RC -V22 is required to be opened for cool down below 350F when the RH System is placed in operation. Should the cable damage be such that the valve cannot be operated from the MCR, the affected portion of the circuit can be isolated at the RSS panel in the Train B switchgear room (Fire Area: CB -F-1B-A) and the valve repositioned for safe shutdown. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-291 4. RH Heat Exchanger to CS/SI Pump Isolation Valves RH -V35 and RH -V36 and SI Isolation Valve SI -V89 Cables for the redundant valves RH -V35 and RH -V36 are routed in proximity to one another. Valves RH -V35 and RH -V36 are normally closed and their position is inconsequential during all modes of plant operation with the exception of cooldown below 350F when the RH System is placed in operation. At that time, it is necessary to insure that the valves remain closed. Should valve RH -V35 open spuriously, the operators can disable its power supply in the Train A switchgear room (Fire Area: CB -F-1A-A) and manually reposition the valves located in the Equipment Vault - Train A (Vault #1) (Fire Zone: RHR -F-4B-Z). Manual operation of the valve can be delayed as much as 9 hours into the event. Therefore, no fire protection other than the existing separation is needed. The provision of a capability to mitigate the spurious operation of the valve outside the fire area satisfies the safe shutdown requirements. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-292 Tabulation 3.2.7.81 Equipment Vault - Train A (Vault #1) Fire Area - RHR-F-1B-Z, RHR-F-1D-Z, RHR-F-2B-Z, RHR-F-3B-Z, RHR-F-4B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-V145 x x CC-V1101 x CC-V1109 x CS-V142 x CS-V154 x CS-V162 x CS-V166 x CS-V167 x CS-V460 x x CS-V475 x x CS-V461 x x RC-V23 x RC-V22 x RC-V88 x RH-E-9A x RH-HCV-606 x x RH-FCV-618 x x RH-P-8A x x RH-V8 x RH-V14 x RH-V35 x x RH-V36 x RH-V70 x SI-V90 x x SI-V90 x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-293 Equipment Vault - Train A (Vault #1) Fire Area - RHR-F-1B-Z, RHR-F-1D-Z, RHR-F-2B-Z, RHR-F-3B-Z, RHR-F-4B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SI-V93 x x SI-V93 x x SI-V138 x MM-IR-14 x x B. ANALYSIS 1. General Systems/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown equipment and cables. The redundant Train B safe shutdown equipment and cables are located in equipment Vault Train B (Vault #2) (Fire Areas: RHR -F-1A-Z, RHR-F-1C-Z, RHR-F-2A-Z, RHR-F-3A-Z, RHR-F-4A-Z) or other fire areas. The Appendix R separation requirements are satisfied.

2. `Seal Injection Isolation Valves CS

-V154, CS-V162 and C S-V166 Under normal conditions, the seal injection isolation valves CS -V154, CS-V158, CS-V162 and CS -V166 are utilized for the seal injection flow path, spurious closure of one of these valves will not prevent safe shutdown. The operators will prevent further spurious operations by tripping the power supply breakers in the Train A switchgear room (Fire Area: CB -F-1A-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-294 3. RC Pump Seal Water Isolation Valve CS -V167 Valve CS-V167 is a normally open valve which should remain open for safe shutdown. Spurious isolation of this Train A valve could result in loss of RC inventory through the upstream relief valve. This inventory is directed to the PRT and is therefore, non -recoverable. To preclude this loss of inventory, functionally redundant isolation capability is provided by the RC pump seal return lines by means of Train A valves CS -V10, CS-V28, CS-V44, and CS -V59 and the excess letdown line by means of normally closed, fail closed valves CS -V175 or CS-V176. The cables, controls and equipment required for operation of valves CS-V10, CS-V28, CS-V44, CS-V59, CS-V175 and CS -V176 are not contained in this fire area. The Appendix R separation requirements are satisfied.

4. SI-CS Suction Cross Connection Valves CS

-V460, CS-V461, CS-V475 Valves CS -V460, CS-V461 and CS -V475 are located in proximity. Prior to beginning cooldown the normally closed CS -V460 and CS -V461 valves should remain closed or the functionally redundant valve CS -V475 should be closed. The isolation of this path will prevent loss of boric acid tank inventory to the RWST during cooldown. In the event of a spurious valve operation which renders this flow path open, the plant can be maintained in hot standby for as long as 4 hours. Should this area be inaccessible due to the fire or should the operators desire to initiate the cooldown sooner than 4 hours, a gravity feed can be established from the boric acid tanks to the charging pumps. As the BAT head is lower than that required to return inventory to the RWST, there would be no loss of BAT inventory through this path and the position of these valves would be inconsequential. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-295 5. RHR Isolation Valves RC -V22, RC-V23, RC-V88 Cables for redundant valves are located in proximity. As the RHR isolation valves are permanently disabled in the closed position, failures in the cables cannot cause a spurious operation. Valve RC -V88 is required to be opened for cooldown below 350F when the RH system is placed in operation. Should the cable damage be such that the valve cannot be operated from the MCR, the affected portion of the circuit can be isolated at the RSS panel in the Train A switchgear room (Fire Area: CB -F-1A-A) and the valve repositioned for safe shutdown. The safe shutdown requirements are satisfied.

6. RH Heat Exchanger to CS/SI Pump Isolation Valves RH

-V35, RH-V36 and SI Isolation Valves SI -V90, SI-V93 Cables for the redundant valves RH -V35 and RH -V36 are routed in proximity to one another. Valves RH -V35 and RH-V36 are normally closed and their position is inconsequential during all modes of plant operation with the exception of cooldown below 350F when the RH System is placed in operation. At that time, it is necessary to assure that valve RH -V36 remains closed. Should valve RH-V36 open spuriously, the operators can disable its power supply in the Train B switchgear room (Fire Area: CB -F-1B-A) and manually reposition the valve located in the equipment Vault Train B (Vault #2) (Fire Zone: RHR-F-2A-Z). Manual operation of the valve can be delayed as much as 9 hours into the event. Therefore, no fire protection other than the existing separation is needed. The provision of a capability to mitigate the spurious operation of the valves outside the fire area satisfies the safe shutdown requirements. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-296 Tabulation 3.2.7.82 Circulating Water Pump House Fire Area - SW-F-1A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-297 Tabulation 3.2.7.83 Service Water Pump House Fire Area - SW-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-CP-248 x EDE-MCC-514 x x SW-P-41A x SW-P-41C x SW-PT-8272 x SW-PT-8273 x SW-PT-8274 x SW-V2 x SW-V22 x SWA-FN-40A x SWA-FN-40B x SWA-TSH-5614-1 x x SWA-TSH-5615-2 x x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown equipment and cables. The redundant Train B equipment and cables are located in fire area SW -F-1C-A separated from this area by a 3 -hour fire wall.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-298 2. Service Water Pump House Electrical Room Fans SWA -FN-40A, SWA-FN-40B and Temperature Switches SWA -TSH-5614-1, SWA-TSH-5615-2 This area contains the electrical rooms ' supply fans SW -FN-40A and SW -FN-40B temperature switches whose failure could cause increase in temperature in the electrical rooms. This could result in the loss of electrical distribution equipment necessary for operation of both Train A and Train B service water equipment. In the event this occurs, the cooling towers will be utilized. This transfer can be initiated from the MCR manually or automatically with Train B tower actuation. The cables, controls and equipment required for operation of the cooling towers are not contained in the fire area. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-299 Tabulation 3.2.7.84 Service Water Pump House Fire Area - SW-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-CP-249 x EDE-MCC-614 x x SW-P-41B x SW-P-41D x SW-PT-8282 x SW-PT-8283 x SW-PT-8284 x SW-V29 x SW-V31 x SWA-FN-40A x SWA-FN-40B x SWA-TSH-5614-2 x x SWA-TSH-5615-1 x x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A equipment and cables are located in fire area SW -F-1B-A separated from this area by a 3 -hour fire wall.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-300 2. Service Water Pump House Electrical Room Fans SWA -FN-40A, SWA-FN-40B and Temperature Switches SWA -TSH-5614-2, SWA-TSH-5615-1 This area contains the electrical rooms ' supply fans SW -FN-40A and SW -FN-40B temperature switches whose failure could cause increase in temperature in the electrical rooms. This could result in the loss of electrical distribution equipment necessary for operation of both Train A and Train B service water equipment. In the event this occurs, the cooling towers will be utilized. This transfer can be initiated from the MCR manually or automatically with Train B tower actuation. The cables, controls and equipment required for operation of the cooling towers are not contained in the fire area. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-301 Tabulation 3.2.7.85 Service Water Pump House Fire Area - SW-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SWA-FN-40A x x SWA-FN-40B x x B. Analysis Service water pump house electrical rooms ' fans SWA-FN-40A and SWA -FN-40B are in this fire area. They cool the SW electrical control rooms Train A and B. Loss of cooling would cause a heat up in these rooms which may damage electrical distribution equipment for both trains of the Service Water pumps. Loss of the normally operating service water pumps would cause a "TA" actuation signal to transfer the system to the cooling towers which are not affected by the fire. The transfer is not affected by the fire or by the loss o f cooling due to the fire. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-302 Tabulation 3.2.7.86 Service Water Pump House Fire Area - SW-F-1E-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-CP-248 x EDE-CP-249 x MM-IR-73 x x MM-IR-73 x x SW-P-41A x x SW-P-41B x x SW-P-41C x x SW-P-41D x x SW-PT-8272 x x SW-PT-8282 x x SW-PT-8273 x x SW-PT-8283 x x SW-PT-8274 x x SW-PT-8284 x x SW-V2 x x SW-V29 x x SW-V22 x x SW-V31 x x B. Analysis A fire in this zone could affect all four service water pumps and their associated discharge valves. Two of the four pumps would normally be operating. A fire in this area will not affect the operability of the cooling tower and its associated fans, pumps and valves for utilization in satisfying safe shutdown. Transfer to the cooling towers will be either automatic by a "TA" actuation generated by low discharge service water pump pressure or by manual actuation from the Main Control Room. Automatic transfer is actuated by SW-PT-8272, 8273, 8274, 8282, 8283, 8284 which are in this fire zone. Loss of the pressure transmitters or their associated instrument racks due to fire will also cause transfer. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-303 Tabulation 3.2.7.87 Intake And Discharge Structure Fire Area - SW-F-2-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-V44 x SW-V63 x B. Analysis Valves SW -V44, SW-V63 are normally open valves which should remain open for safe shutdown. The valves are permanently disabled in the open position. C. Evaluation The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-304 Tabulation 3.2.7.88 Turbine Building Fire Area - TB-F-1A-Z, TB-F-1C-Z, TB-F-2-Z, TB-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CBA-DP-24A x CBA-DP-24B x CBA-DP-24C x CO-LT-4096 x ED-B-2A x ED-B-2B x ED-BC-2A x x ED-BC-2B x x ED-I-4 x ED-PP-121B x ED-PP-122A x x ED-PP-122B x ED-SWG-12A x x ED-SWG-12B x x EDE-MCC-523 x x EDE-SWG-5 x EDE-SWG-6 x FP-CP-558 x x FW-P-113 x x FW-P-161 x x FW-V163 x x IA-SKD-18A x IA-SKD-18B x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-305 Turbine Building Fire Area - TB-F-1A-Z, TB-F-1C-Z, TB-F-2-Z, TB-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MM-IR-33A x x SA-V92 x x SA-V93 x x SA-TK-23A x SA-TK-23B x SA-SKD-137A x x SA-SKD-137B x x SY-CP-84 x x SY-CP-84 x x SY-CP-85 x x SY-CP-85 x x SY-CP-86 x x SY-CP-86 x x SCC-FV-7050 x x SCC-FV-7050 x x SY-CP-87 x x SY-CP-87 x x SCC-FV-7050A-1 x x SCC-FV-7050A-1 x x SCC-FV-7050A-2 x x SCC-FV-7050A-2 x x SCC-PCV-7035 x B. Analysis 1. Control Building Air Handling (CBA) System Dampers CBA -DP-24A, B, C and Fire Protection Panel FP -CP-558 All equipment and cables are Train A, the redundant Train B equipment are located in fire area CB -F-2B-A, separated from this area by a 3 -hour fire wall. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-306 2. Condensate Storage Tank (CST) Level Transmitter CO -LT-4096 Cables for CO -LT-4096 and its instrument bus (ED -I-4) are located in this fire area. Redundant cable and equipment is located in the EFW Pump House (fire area EFW-F-l-A). The Appendix R separation requirements are satisfied.

3. Battery Chargers ED

-BC-2A & ED-BC-2B, Batteries ED -B-2A & ED-B-2B, Switchgear ED -SWG-12A & ED-SWG-12B, and Power Panels ED -PP-121B & ED-PP-122A Loss of these buses could cause loss of RC Pump Control Power. The operator will manually trip the switchgear in the non -essential switchgear room (Fire Area: NES-F-1A-Z). Pressurizer heaters C, D and control group control power could be lost. If the heaters require tripping, an operator will manually trip them in the Train A switchgear room (Fire Area: CB -F-1A-A). Alternatively, the operator can reduce pressure by operating a PORV. Redundant heaters are available with control power from the emergency DC buses. The safe shutdown requirements are satisfied.

4. Electrical Distribution Emergency (EDE) System (4160 Swgr. E5, E6; Control Panels SY

-CP-84, 85, 86, 87, and 460V MCC E523) Redundant equipment and cables for the 4160 switchgear are located in the same fire area. A short circuit in this equipment or cables can cause a trip of the 4160V emergency switchgear E5 and E6 incoming line breakers from the UAT and RAT, resulting in loss of the offsite power supply. Loss of the offsite power supply will require starting of the diesel generators. The emergency buses will be powered from the diesel generators. This is the design base for safe shutdown. The safe shutdown requirements are satisfied. For the 460V MCC 's all equipment and cables are Train A, the functionally redundant Train B cables and equipment are located in fire area CB -F-1B-A, separated from this area by a 3 -hour fire wall. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-307 5. Instrument Air (IA) System Redundant equipment and cables for instrument air dryers are located in the same fire area. Dryers IA -SKD-18A and IA -SKD-18B provide instrument air for the primary component cooling water system containment isolation valves, Train A and Train B switchgear room dampers CBA -DP-24A, B, C, D, E, F, and MCR dampers CBA-DP-26A and CBA-DP-26B. Component cooling water to containment is required to maintain containment habitability. For a fire in this area, containment entry is not required as operators have the capability to operate safety injection accumulator isolation valves SI -V3, SI-V17, SI-V32 and SI -V47 and RHR isolation valves RC -V22, RC-V23, RC-V87 and RC -V88 from the main control room (Fire Area: CB-F-3A-A) or the RSS control panels (Fire Areas: CB -F-1A-A and CB-F-1B-A), separated from this area by a 3 -hour fire wall. The operators have the capability to manually position the Main Control Room air conditioning condenser units face and bypass dampers in the Diesel Generator Building HVAC equipment area (Fire Areas DG -F-3A-Z & DG-F-3B-Z). As these dampers fail "as is", this action would only be required to maintain long term habitability required by 9 hours into the event. Therefore, the air dryers are not required for safe shutdown for a fire in this area. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-308 6. Service Air (SA) System Redundant equipment and cables for the service air system and secondary component cooling system with its tie -in to the fire protection system are located in the same fire area. Compressor skids SA -SKD-137A and SA -SKD-137B and their associated equipment provide instrument air for the primary component cooling water system containment isolation valves, and MCR dampers CBA -DP-26A and CBA-DP-26B. Component cooling water to containment is required to maintain containment habitability. For a fire in this area, containment entry is not required as operators have the capability to operate safety injection accumulator isolation valves

SI-V3, SI-V17, SI-V32 and SI -V47 and RHR isolation valves RC -V22, RC-V23, RC-V87 and RC -V88 from the main control room (Fire Areas: CB -F-3A-A) or the RSS control panels (Fire Areas: CB -F-1A-A and CB-F-1B-A), separated from this area by a 3 -hour fire wall. The operators have the capability to manually position the MCR dampers in the Control Room HVAC Room (Fire Area: CB -F-3B-A), separated from this area by a 3 -hour fire wall. The operators have the capability to manually position the switchgear room dampers in the control building mechanical equipment rooms (Fire Areas: CB -F-2B-A and CB-F-2C-A). As the Train A and Train B switchgear room intake and recirculation dampers fail "as is" and the exhaust damper fails open, this action would only be required to maintain long term habitability required by 9 hours into the event. Therefore, the SA system is not required for safe shutdown for a fire in this area. The safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-309 Tabulation 3.2.7.89 Turbine Building Fire Area - TB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable ED-B-2A x x ED-B-2B x x B. Analysis Fire in this area will cause loss of DC power Bus ED -SWG-12B. Loss of this bus will cause loss of CST level instrumentation CO -LT-4096. Redundant equipment is located in fire area EFW -F-1A. Also RC pump switchgear control power is lost. When the RCP 's are required to be tripped (during cooldown) the operator will manually trip them in the non -essential switchgear room (Fire Area: NES -F-1A-Z). Pressurizer Heaters C, D, and control group control power will be lost. An operator, if the heaters require tripping, will do so in the Train A switchgear room (Fire Area: CB -F-1A-A). Alternatively, the operator can reduce pressure by operating a PORV. Redundant heaters are available with control power from the emergency DC bus. C. Evaluation The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-310 Tabulation 3.2.7.90 Tank Farm Fire Area - T-F-1-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-LCV-112B x CS-LCV-112C x CS-LCV-112D x x CS-LCV-112E x x B. Analysis Redundant valves CS -LCV-112D and CS -LCV-112E are located in the same fire area. The cables for VCT isolation valves CS -LCV-112B and CS -LCV-112C, are also located in this fire area. These are normally open valves. A fire in this area will prevent opening the normally closed RWST to charging pump isolation valves from the control room. The normally open VCT isolation valves may experience a loss of control power but can not spuriously close as described below. A fire in this area does not affect the normal charging, letdown, and boric acid makeup functions so safe shutdown can be achieved and maintained using a charging pump aligned to the VCT through CS -LCV-112 B & -112C. The RWST is not needed for this normal shutdown so the inability to open CS -LCV-112D & -112E does not affect safe shutdown. If there was a need to use the RWST, the RWST valves could be manually opened, and the VCT isolation valves could be closed from the RSS panels or manually closed. Volume control tank (VCT) isolation valves CS -LCV-112B & -112C are normally open to provide a suction path from the VCT to the normally operating charging pump (CS-P-2A or -2B). These valves must stay open to provide a charging pump suction path from the VCT. Spurious closure of a VCT isolation valve caused by a hot short would interrupt suction flow to the operating charging pump causing it to be damaged. If the standby charging pump has cables in the same area then its operation can also be degraded. The result would be no charging system flow. Since this fire area does not contain cables for CS -P-2A or CS-P-2B, this condition is not applicable to this fire zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-311 Furthermore, the CS -LCV-112B and -112C circuit design prevents spurious valve closure from hot shorts as follows. The field cable conductors for the motor control center (MCC) contactor close coil circuit are in different cables from the 120 V "hot" circuit conductors eliminating the hot short failure mode within the cables. Cable -to-cable hot shorts need not be postulated for thermoset cable insulation as used at Seabrook. Since

CS-LCV-112B and -112C will not spuriously close, CS-P-2A or -2B as the operating charging pump will not be damaged. C. Evaluation The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-312 Tabulation 3.2.7.91 Waste Building Fire Area - W-F-1A-Z, W-F-1B-Z, W-F-1K-Z, W-F-2A-Z, W-F-2B-Z, W-F-2C-Z, W-F-2D-Z, W-F-2E-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-1 3.3 ALTERNATIVE SAFE SHUTDOWN USING REMOTE SAFE SHUTDOWN FACILITIES 3.3.1 General Remote safe shutdown (RSS) is a design feature which allows plant shutdown from locations other than the main control room in the event of a fire or other condition which requires evacuation of the main control room. The fire areas of concern are the main control room, control room HVAC room, and the cable spreading room. Remote safe shutdown contains the necessary complement of systems and equipment required to satisfy the performance goals delineated in Appendix R, Paragraph III.L.2. Technical Specification (T/S) 3/4.3.3.5 requires surveillance testing of selected equipment used for safe shutdown from outside the Control Room at Remote Safe Shutdown (RSS) locations. The required equipment is listed in Table 3.3 -9. The selection criteria for the Transfer Switch/Control Circuit portion of the table is the primary equipment which has remote/local selector switches and is required to perform the reactor coolant system inventory and pressure control, reactivity control, and decay heat removal functions to achieve and maintain hot standby. For Appendix R shutdown, only one train of equipment (safety or non -safety related) is required; redundancy is not a requirement. Seabrook is a hot standby safe shutdown design basis plant (see UFSAR Section 5.4.7.2.i). Support equipment, and equipment required only to achieve and maintain cold shutdown, are not required to be included in the T/S table. Process monitoring instruments also have surveillance requirements. 3.3.2 Safe Shutdown Control Locations Normally safe shutdown will be accomplished from the main control room, utilizing the safe shutdown equipment along with other equipment which may be available to the operators. Upon detection of a fire, the fire brigade will be dispatched to the affected area and a determination will be made as to the severity of the fire. If it is determined that the fire has a potential for impacting safe shutdown from the main control room, the operators will proceed with a planned evacuation of the main control room and manning of the Train B remote safe shutdown control panel (MM-CP-108B) and man the following remote safe shutdown (RSS) facilities as necessary:

a. Train B Switchgear Room (Switchgear E6, and various Unit Substations, Motor Control Centers (MCC) and Distribution Panels) and RSS Aux Panel in Electrical Tunnel B. b. Train A Switchgear Room (MM

-CP-108A, Switchgear E5, and various Unit Substations, Motor Control Centers (MCC), and Distribution Panels) and RSS Aux Panel in Electrical Tunnel A . SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-2 c. Diesel Generator Room A

d. Diesel Generator Room B
e. Primary Auxiliary Building El. 53

'-0" Primary Component Coolant Water Heat Exchanger Area

f. Primary Auxiliary Building El. 25

'-0" Boric Acid Tank Area

g. Primary Auxiliary Building El. 7

'-0" Train B Charging Pump Room

h. Control Building Mechanical Equipment Rooms

- El. 50'-0" i. Equipment Vault - Train B (Vault #2)

j. Condensate Storage Tank
k. Non-Essential Switchgear Room The term "prompt action

" refers to an action taken after receipt of a valid fire alarm in the main control room. The term "expeditious action " or "expeditiously " refers to an action taken quickly upon entry into the applicable safe shutdown procedure. These type actions are considered to be completed prior to a spurious operation of the equipment operated by the prompt and expeditious actions. Therefore, no associated timing calculation is required for these actions. 3.3.3 Safe Shutdown Functions for Hot Standby The following are equipment necessary for Hot Standby:

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-3 3.3.3.1 Reactor Coolant (RC) Inventory and Pressure Control To compensate for miscellaneous RC system leakage, RC pump seal leakage and cooldown volume shrink, portions of the chemical and volume control (CS) system including centrifugal charging pumps, boric acid transfer pumps, and a borated water supply, either the refueling water storage tank (RWST) or the boric acid tanks (BAT) are used. The injection path to the RC system will be either through the seal injection flow path or the high head injection flow path. The preferred seal injection path requires that a flow control valve (CS -FCV-121) and that a minimum of two of the four seal injection valves (CS -V154, CS-V158, CS-V162 or CS -V166) be operable. Additionally, the normal charging flow to the RC system is isolated. This can be accomplished by temporarily stopping a charging pump to prevent overfill of the pressurizer. It can also be accomplished by use of any one of two functionally redundant but non -credited valves (CS -V142 or CS -V143). Should the seal injection path not be operable e.g., due to spurious closure of a flowpath valve (CS-FCV-121), the high head injection flow path (SI -V138 or SI -V139) can be utilized initially to maintain hot standby by batch charging from the RWST to maintain pressurizer level. During cooldown as RC system pressure decreases, it is necessary to provide a flow restricted path to prevent charging pump cavitation. This is due to the limited flow capability from the BAT. If the high head injection path cannot be isolated at this time and/or if the flow controlled path through CS -FCV-121 is not operable, a capability is provided to manually align and throttle the charging pumps to the seal injection flow paths. The necessary operator actions and valve alignments are unique for each fire area where these flow paths are affected and are described in the analysis for each area. RC pump seal cooling is provided by a redundant thermal barrier cooling system. Should the redundant thermal barrier system not be available, the seals will be cooled by the seal injection capability. A control room or cable spreading room fire can result in a temporary loss of all cooling to the RCP seals. The operator action to accomplish restoration of cooling to the seals is to restore power to an emergency bus, restart of a thermal barrier cooling pump and a CC water pump. Then, a charging pump and SW pump are started for long term seal cooling via seal cooling, as well as inventory control. The operator action to restore RCP seal cooling is accomplished prior to the time that there would be potential damage to the seals. The reactor coolant pumps (RCPs) are stopped from the main control board prior to evacuating the main control room. Circuit analysis shows that the RCPs can not spuriously restart due to fire -induced cable damage. The RC system pressure is controlled by use of a portion of the RC system which includes the pressurizer heaters (Group A and B) to increase pressure and the pressurizer power operated relief

valves (PORV) which depressurize the RC system by discharging reactor coolant fluid to the pressurizer relief tank (PRT).

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-4 Considering worst case scenarios for spurious actuation of affected equipment, the required times for operator actions regarding RC inventory and pressure control for safe shutdown from the remote safe shutdown facilities are provided below: Action Time Close PORV block valve Prompt Open the RWST outlet valves Prompt Place the standby charging pump in pull -to-lock Prompt Restore RCP seal cooling 9.9 to 19.8 minutes, depending on the highest RCP seal rate Trip RCPs 10 minutes Restore cooling to charging pump oil cooler

9.6 minutes

Isolate letdown 15 minutes Swap charging pump suction from VCT to RWST 15.4 minutes. Should SI -V138, SI-V139, or CS -HCV-182 spuriously open, this action must be completed no later than 5.0 minutes following letdown line isolation. Restore SW to emergency diesel generators 17.6 minutes Open a PORV to reduce pressurizer pressure in the event of spurious pressurizer heater operation or trip pressurizer heaters 23 minutes Start a charging pump, or open a high head safety injection valve SI -V-138 or SI -V-139 if normal charging pump path is not available 31.1 minutes Isolate charging flow, except for seal injection 35.4 minutes Trip spuriously operating containment building spray pumps 46 minutes Trip spuriously operating SI pump

<4 hours, prior to commencement of plant cooldown

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-5 Action Time Isolate the potential diversion path from the BAT to the RWST or align BAT for gravity feed.

<4 hours, prior to commencement of plant cooldown Align BAT for makeup source
<4 hours, prior to commencement of plant cooldown 3.3.3.2  Reactivity Control Reactivity for hot standby at normal operating temperature (NOT) is provided by insertion of the control rods. Reactivity conditions required for cooldown and maintaining cold shutdown are provided by a portion of the chemical and volume control (CS) system which includes a centrifugal charging pump taking suction from the BAT

's. During cooldown, the borated source must be the BAT volume until expended to at least the point that the volume injected or a boron sample demonstrates that sufficient shutdown margin for cold shutdown has been achieved, at which time the RWST would be aligned. The credited path for boration is gravity feed with the RWSP isolated. The boric acid transfer pumps can be used if available. Considering worst case scenarios for spurious actuation of affected equipment, the required times for operator actions regarding reactivity control for safe shutdown from the remote safe shutdown facilities are provided below: Action Time Trip the Reactor Expeditiously Provide borated water from the BATs, via boric acid transfer pump or gravity feed.

<4 hours, prior to commencement of plant cooldown Isolate boric acid flow diversion path.
<4 hours, prior to commencement of plant cooldown

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-6 3.3.3.3 Decay Heat Removal The reactor coolant (RC) system temperature is controlled by use of portions of the feedwater (FW) system and the main steam (MS) system. The main steam safety/relief valves will maintain a heat dump capability. The steam generator water inventory is controlled by operating the motor driven emergency feedwater pump and associated emergency feedwater control valves. Inventory for the emergency feedwater is from the condensate storage tank. Long term water capability exists using a temporary connection between the suction of the emergency feed pumps and the fire protection system but is not required to meet Appendix R requirements. To assure main steam system integrity the MSIV 's and MSIV bypass are maintained closed. The MSIV bypass valves are normally locked closed and depowered with breakers locked open to preclude spurious opening. Decay heat transfer is made possible by natural convection flow in the RC System. Considering worst case scenarios for spurious actuation of affected equipment, the required times for operator actions regarding decay heat removal for safe shutdown from the remote safe shutdown facilities are provided below: Action Time Isolate MSIVs Expeditiously following a reactor trip Place the mode selector switches for the ASDVs to the closed position Prompt Gain Control of excessive Emergency Feedwater Flow 20 minutes Start motor driven EFW pump to preclude steam generator dry out 39 minutes Time allotted for operator actions to preclude emptying CO tank to accommodate RHR Cut -in, and ultimately achieve cold safe shutdown within 72 hours 9 hours; 4 hours at hot standby plus

5 hours cooldown to RHR Cut -in 3.3.3.4 Process Monitoring Instrumentation is provided at the Train B remote safe shutdown control panel for monitoring the following process variables:

a. Steam generator emergency feedwater flow
b. Reactor coolant loop hot and cold leg temperatures

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-7 c. Steam generator wide -range level

d. Steam generator pressure
e. Pressurizer level
f. Pressurizer pressure
g. Wide-range neutron monitoring (excore)
h. Primary component cooling water temperature
i. Boric acid tank level
j. Condensate storage tank level (local)

Instrumentation is also provided at the Train A remote safe shutdown control panel for monitoring the following process variables:

a. Steam generator emergency feedwater flow
b. Steam generator wide-range level Note that other instrumentation is provided at the Train A remote safe shutdown control panel but is not credited for Appendix R fire safe shutdown.

3.3.3.5 Service Water The service water system will supply cooling water to the primary component cooling water system, diesel generators, and if required, fire protection system. Service water supply will be from the service water pumps taking suction from the tunnels to the ocean. Section 3.3.3.1 provides the required times for operator actions, based on worst case scenarios for spurious actuation. 3.3.3.6 Primary Component Cooling Water (CC) The CC system is utilized to maintain cooling water to the charging pumps, RH pumps, RH heat exchangers, and reactor coolant pumps (RCP) thermal barrier heat exchanger. The PCCW pumps, temperature control valves, and RCP thermal barrier cooling pumps are necessary for system operations. Section 3.3.3.1 provides the required times for operator actions, based on worst case scenarios for spurious actuation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-8 3.3.3.7 Sampling Sampling of the reactor coolant system is not required at hot standby and cold shutdown conditions since make -up during cool -down will only be provided to the RCS from the boric acid tanks (two) which are maintained at 4 wt% boric acid. During all phases of cool -down, the core will be maintained to the shutdown margin greater than or equal to the limit specified in the Core Operating Limits Report (COLR). 3.3.3.8 Diesel-Generator Building Air Handling (DAH) The DAH system is utilized to maintain long -term habitability and equipment protection for the diesel-generator rooms. The DAH system includes the fans and dampers for air handling in these areas. 3.3.3.9 Containment Enclosure Air Handling (EAH) The EAH system is utilized to maintain long-term habitability of the mechanical penetration area, and provide equipment cooling in the charging pump rooms, and the hydrogen analyzer and electrical room. The EAH system includes the coolers, fans, and dampers required for air handling in these areas. 3.3.3.10 Emergency Feedwater Pumphouse Air Handling (EPA) The EPA system is utilized to maintain long -term habitability and equipment protection in the emergency feedwater pump building. The EPA system includes the fans and dampers required for air handling in this area. 3.3.3.11 Primary Auxiliary Building Air Handling (PAH) Portions of the PAH system are utilized to maintain long -term habitability and equipment protection in the PCCW area of the primary auxiliary building. The PAH system includes the fans and dampers required for ventilation in this area. 3.3.3.12 Service Water Air Handling (SWA) Portions of the SWA system are utilized for equipment protection in the SW pump house electrical control rooms. The SWA system includes the fans and dampers required for air handling in these areas. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-9 3.3.3.13 Electrical Distribution Emergency (EDE) Portions of the EDE system are required to power the various pumps, fans, valves, etc. required for safe shutdown. Included in the EDE system are the 4160 Volt ac emergency switchgear, 460 Volt ac emergency unit substations and motor control centers, the uninterruptible power supplies, 120 Volt ac vital distribution panels, 125 Volt dc batteries, battery chargers, and 125 Volt dc distribution panels. 3.3.3.14 Diesel-Generators (DG) The diesel -generators provide power to the electrical distribution emergency system upon loss of off-site power. The DG system includes the diesel, generators, control panels, engine -driven auxiliaries, fuel oil transfer pumps, starting air compressors and backup operating air compressors. 3.3.3.15 Safeguard Actuation System The safeguard actuation system could be actuated. A portion of this system is used to deactivate the system for recovery. 3.3.3.16 Communication The Gaitronics or radio systems are used to announce the fire event, dispatch the fire brigade, and to dispatch an NSO to perform local actions in the emergency diesel generator rooms. The Gaitronics system is also used to provide a fire alarm. Face -to-face communications is used to dispatch a control room operator (CRO) to the Train B switchgear room to perform local actions. A sound powered telephone loop (SPC) is provided for the CRO and NSO to communicate between the switchgear and the diesel generator rooms. Headsets or handsets are stored at these RSS locations for operator use. All actions required to achieve and maintain hot standby are taken in these areas. When field actions are required to commence cooldown, and achieve and maintain cold shutdown, an operator would: a) be dispatched to take the required action, b) go to the field and take the action, and c) then return and report the action completed. The RSS SPC loop also includes two SPC jacks in the RHR equipment vaults. Radios and Gaitronics are not credited but would be used as additional means of communications, if not damaged by the fire. 3.3.4 Safe Shutdown Functions for Cooldown The following equipment in addition to that which is listed in Section 3.3.3 are necessary for cooldown.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-10 3.3.4.1 Decay Heat Removal In addition to equipment discussed in Section 3.3.3.3, the steam generator atmospheric relief valves will be used for cooldown until the residual heat removal (RH) system can be used. The residual heat removal system will be the long term heat sink at the end of cooldown. An RH pump will be operated along with various control, manual and motor operated valves. 3.3.4.2 Sample System For cold shutdown, the operators will draw a manual sample from RH system to verify boron concentration before li ne-up to RCS. The operator will use manual valves in RH system. 3.3.5 Initial Operator Actions Remote safe shutdown procedures will require that prior to main control room evacuation the reactor, the main steam isolation valves, and the reactor coolant pumps be tripped, thus establishing a hot standby condition. Closure of the pressurizer PORV 's block valves, placing the switches for the ASDVs to the closed position, placing the standby centrifugal charging pump in pull -to-lock, and opening the RWST outlet valves to the charging pump suction will be accomplished from the main control board after alarm confirmation (promptly) to prevent over cooling situations from either the primary or secondary side of the plant and ensuring proper RCS inventory control. Additionally, capabilities to trip the four MSIV 'S, the four RCP 's and the pressurizer PORV 's and atmospheric relief valves exist outside the main control room. After a confirmed fire alarm for a main control room or cable spreading room fire, a control room operator (CRO) and nuclear systems operator (NSO) are dispatched to the Train B switchgear and emergency diesel generator rooms to take actions as directed by procedure. In the time interval required for the operators to evacuate the main control room and man the RSS facilities, decay heat removal is accomplished automatically by the steam generator safety valves. No other function is required initially to maintain a decay heat sink for the reactor. Upon arrival at the RSS facilities, the operators will transfer control capability to the RSS facility by means of "Remote-Local" selector switches at the RSS locations and take the actions necessary to maintain control of the RCS inventory and pressure, and decay heat removal functions within the time frames described in sections 3.3.3.1 and 3.3.3.3. Control of the Train B Diesel Generator will be taken and if a Loss of Offsite Power (LOOP) occurs, clear and load EDE -SWG-6 to support safe shutdown. The operators will also trip the power supplies for engineered safety features actuation system (ESFAS) logic and cooling tower actuation logic to prevent inadvertent activation of these functions. The operators will then disable (trip power supply breakers) all equipment which is properly positioned in its safe shutdown position. Any additional recovery actions needed to maintain hot standby or to start a cooldown will be completed if inadvertent safeguard operation, tower actuation or "HOT SHORT " actuation occurs.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-11 3.3.6 Manual Operator Actions The following equipment may require manual operation:

1. Mechanical room dampers CBA

-DP-24A, CBA-DP-24B, CBA-DP-24C, CBA-DP-24D, CBA-DP-24E and CBA -DP-24F. 2. Component cooling water valves CC -V145 and CC -V272. 3. Charging pump discharge and bypass valves CS -V210, CS-V219, CS-V220 and CS-V221. 4. RHR sampling valves RH -V8 and RH -V44. 5. Boric acid tank gravity feed valves CS -V410, CS-V416, CS-V437, CS-V439, CS-V442, and CS -V1207. The cables for valves CC -V145 and CC -V272 are not included in the review. Equipment CBA-DP-24D, CBA-DP-24E, CBA-DP-24F, CS-V210, CS-V219, CS-V220, CS-V221, CS-V410, CS-V416, CS-V437, CS-V439, CS-V442, CS-V1207, RH -V8, and RH -V44, are not electrically operated; hence, they have no cables. 3.3.7 Disabled (tripped power supply) Equipment The following equipment will be disabled:

a. Containment spray pumps CBS

-P-9A and CBS -P-9B b. Primary component cooling valves CC -V1092, CC -V1095, CC -V1101 and CC-V1109. c. Chemical and volume control valves CS -V154, CS-V158, CS-V162, CS-V166, CS-V167, CS-V168, CS-V175, CS-V176, CS-V196, CS-V197, CS-V460, CS-V461, CS-FCV-110A, -111A, -110B, -111B. d. Not used.

e. Main steam atmospheric relief valves MS

-PV-3001, MS-PV-3003 (Train B power supply) and MS -PV-3002, MS-PV-3004 (Train A power supply).

f. Not Used.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-12 g. Reactor coolant valves RC -V323, RC-FV-2881, RC-LCV-459* and RC-LCV-460* h. Pressurizer heaters Group C, Group D and Control Group

i. Residual heat removal valves RH

-V14, RH-V26, RH-V32, RH-V35, RH-V36, RH-V70, RH-HCV-606, RH-HCV-607, RH-FCV-618, and RH -FCV-619 j. Steam generator blowdown valves SB -V9*, SB-V10*, SB-V11* and SB -V12* k. Safety injection valves SI -V158 and SI -V159 l. Safety injection pumps SI -P-6A and SI -P-6B m. Service water valves SW -V15, SW-V16*, SW-V18*, SW-V20, SW-V23, and SW-V34. n. Engineered safety features -actuation system logic cabinets

o. Tower actuation logics The valves noted with an asterisk (*) fail to their safe shutdown position upon de

-energization. 3.3.8 Safe Shutdown Equipment List Tables that list all equipment, including instrumentation and vital support systems equipment required to achieve hot standby or cold shutdown using the RSS facilities are provided in Appendix III. However, analysis can be also provided to justify not listing components and cables in Appendix III. The tables provide the following requested information for each equipment listed: a) A column which notes whether the equipment is required for hot standby or cold shutdown. b) A column which defines each equipment 's location by fire zone/area. c) A column which defines each equipment 's redundant counterpart. d) A column which lists each equipment 's essential cabling. e) The table also delineates the following additional information:

1) P & I Diagram Drawing No.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-13 2) Physical Location Drawing No.

3) Power Supply 4) Electrical Node Number
5) Supporting Control and Instrumentation Equipment
6) Electrical Schematic Drawing No.
7) Electrical Cable Schematic Drawing No.
8) Supporting Systems
9) Remarks Separate tables are furnished for each of the safe shutdown functions. In several instances a safe shutdown function requires components from several systems to perform its safe shutdown function.

Appendix R Section III.L requires that only one train of equipment necessary to achieve and maintain hot standby must be available from alternate or dedicated RSS shutdown facilities. Redundancy is not required. Equipment required to achieve and maintain cold shutdown can be repaired within 72 hours. For Seabrook, the preferred RSS shutdown equipment is Train B. The

Train B RSS equipment with R/L selector and control switches have redundant control circuit fuses. This ensures that the local control circuit will still be operable in case the MCR control circuit blows the circuit fuse before control is transferred to local. For conservatism, redundant Train A equipment is typically listed in the RSS equipment lists in Appendix III, for example, both the Train A and the Train B charging pumps are listed whereas only one (Train B) is required to provide the safe shutdown function. This Train A equipment is desired, but not required, for safe shutdown. In some cases the Train A equipment is not listed just for conservative redundancy but is actually required for safe shutdown, for example, the SI accumulator isolation valves where there are two Train A and two Train B required valves. In order to simplify the tabulation, the following are not listed: manual valves in the process flow path; mechanical check valves which provide a Safe Shutdown system boundary; normally closed manual valves which provide a Safe Shutdown system boundary; mechanical relief valves; and root valves on small instrument lines. The review of these valves is documented by the marked P & I Diagrams. Tables are provided for the following functions which satisfy the performance goals stated in Appendix R, Paragraph III.L.2 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-14 Function Table No. Decay Heat Removal 3.1.3.1 Reactor Coolant Inventory and Pressure Control 3.1.3.2 Reactivity Control 3.1.3.3 Process Monitoring 3.1.3.4 Safeguard Actuation System 3.1.3.5 Cold Shutdown 3.1.3.6 Service Water 3.1.3.7 Primary Component Cooling Water 3.1.3.8 (Deleted) 3.1.3.9 Control Building Air Handling 3.1.3.10 Diesel Generator Building Air Handling 3.1.3.11 Containment Enclosure Air Handling 3.1.3.12 Emergency Feedwater Pumphouse Air Handling 3.1.3.13 Primary Auxiliary Building Air Handling 3.1.3.14 Service Water Air Handling 3.1.3.15 (Deleted) 3.1.3.16 Electrical Distribution Emergency 3.1.3.17 Diesel Generators 3.1.3.18 Communication 3.1.3.19 3.3.9 Analysis and Evaluation of Fire Areas An evaluation is provided as to whether the Appendix R requirements or safe shutdown requirement are satisfied. If a deviation from Appendix R requirements exists, this deviation is justified by Analysis. The following fire areas are considered: Building Fire Area Tabulation Control Bldg. - El. 50'-0" Cable Spreading Room CB-F-2A-A 3.3.9.1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-15 Building Fire Area Tabulation Control Bldg. - El. 75'-0" Main Control Room CB-F-3A-A 3.3.9.2 Control Bldg. - El. 75'-0" HVAC Equipment & Duct Area CB-F-3B-A 3.3.9.3 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-16 Tabulation 3.3.9.1 Control Building - El. 50'-0" Cable Spreading Room Fire Area: CB-F-2A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable PAH-DP-35A X PAH-DP-35B X PAH-DP-36A X PAH-DP-36B X B. Analysis The cable spreading room fire area CB -F-2A-A does not contain any cables or equipment which are required for safe shutdown from the RSS facilities except for the equipment listed. 1. Containment Enclosure Isolation Damper, PAH -DP-35A, PAH-DP-36A, PAH-DP-35B, PAH-DP-36B Cables for outboard isolation dampers PAH -DP-35A and PAH -DP-36A and inboard isolation dampers PAH -DP-35B and PAH -DP-36B are routed in trays and conduits in proximity to one another. Under normal operation both outboard and both inboard dampers are open. If both outboard or both inboard dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. If the outboard dampers and the inboard dampers operate independently such that either the supply or the exhaust path but not both are isolated, there could be an air flow problem in EAH system. Outboard dampers are powered from a single Train A power supply. Inboard dampers are powered from a single Train B power supply. The circuit design for the outboard and inboard dampers is such that a spurious signal in either or both circuits will cause both outboard and inboard dampers to operate together, either both open (normal mode) or both closed (recirculation mode). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-17 A fixed fire suppression system in accordance with Appendix R, Paragraph III.G.3 has been provided. Detectors are provided throughout the area. C. Evaluation The Appendix R Paragraphs III.G.3 and III.L. alternative shutdown capability requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-18 Tabulation 3.3.9.2 Control Building - El. 75'-0" Main Control Room Fire Area: CB-F-3A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable PAH-DP-35A X PAH-DP-35B X PAH-DP-36A X PAH-DP-36B X B. Analysis The Main Control Room fire area CB -F-3A-A does not contain any cables or equipment which are required for safe shutdown from the RSS facilities except for the equipment listed. 1. Containment Enclosure Isolation Damper, PAH -DP-35A, PAH-DP-36A, PAH-DP-35B, PAH-DP-36B Cables for outboard isolation dampers PAH -DP-35A and PAH-DP-36A and inboard isolation dampers PAH -DP-35B and PAH -DP-36B are routed in trays and conduits in proximity to one another. Under normal operation both outboard and both inboard dampers are open. If both outboard or both inboard dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. If the outboard dampers and the inboard dampers operate independently such that either the supply or the exhaust path but not both are isolated, there could be an air flow problem in EAH system. Outboard dampers are powered from a single Train A power supply. Inboard dampers are powered from a single Train B power supply. The circuit design for the outboard and inboard dampers is such that a spurious signal in either or both circuits will cause both outboard and inboard dampers to operate together, either both open (normal mode) or both closed (recirculation mode). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-19 A fixed fire suppression system in accordance with Appendix R Paragraph III.G.3 has not been provided in this continually manned area. Detectors are provided throughout the area. C. Evaluation The Appendix R Paragraph s III.L alternative shutdown capability requirements are satisfied. Deviations from Appendix R, Paragraph III.G.3, fixed fire suppression requirement, exist in the main control room. This deviation is justified based on the analysis and our assertion that additional modification would not enhance fire protection safety.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-20 Tabulation 3.3.9.3 Control Building - El. 75'-0" HVAC Equipment & Duct Area Fire Area: CB-F-3B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis The HVAC Equipment and Duct Area CB -F-3B-A does not contain any cables or equipment which are required for safe shutdown from the RSS facilities. A fixed fire suppression system in accordance with Appendix R Paragraph III.G.3 has not been provided in this area which contains equipment required for the main control room ventilation system. Detectors are provided throughout the area. Carbon monoxide detectors are provided in CBA -F-38 and CBA -F-8038 for early charcoal fire detection. C. Evaluation The Appendix R Paragraphs III.L alternative shutdown capability requirements are satisfied. Deviations from Appendix R, Paragraph III.G.3, fixed fire suppression requirement, exist in the HVAC equipment and duct area. This deviation is justified based on the analysis and our assertion that additional modification would not enhance protection safety.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.4 Page 3.4-1 3.4 ALTERNATIVE SAFE SHUTDOWN - EMERGENCY FEEDWATER PUMPHOUSE FIRE A fire in this area disables both emergency feedwater (EFW) pumps, associated EFW flow control valves, and related instrumentation. An immediate plant trip in response to this fire event is not desirable since this would place a demand on the EFW system which may not be available. Instead, plant operation will be maintained stable at 100% power conditions using the normal feedwater system while the fire event is assessed and appropriate mitigating actions are determined. The plant will not be perturbed by any action, including a power change, that might result in a plant trip and demand on the EFW system. If it is determined that plant shutdown is warranted, th en normal procedures will be used eliminating an EFW system demand. This approach is consistent with the Technical Specification 3/4.7.1.2 Bases. Plant shutdown using normal procedures does not require use of the EFW system so the time critical operator action response times related to the EFW system do not apply (see Section 3.2.2.3) for this fire area. If an immediate plant shutdown was required, then the startup feedwater pump (SUFP) would be used to provide the EFW function. Since both EFW trains are disabled by a fire in this area, this is considered an alternate shutdown capability area. Safe shutdown would be controlled from the main control room. Since this is not the preferred response, immediate plant shutdown is considered a beyond design basis condition analyzed for defense in depth. If the EFW flow control valves are disabled, then the EFW pumps may have to be tripped to control excessive EFW flow. The SUFP and its valves can provide throttled flow to prevent overfill/over cooling conditions. Since this is a beyond design basis, defense in depth, response, the time critical operator action response times related to the EFW system do not apply for this fire area. The following analysis evaluates the beyond design bases response of shutdown controlled from the main control room with an immediate plant trip using the SUFP to provide the EFW function. Plant shutdown using normal procedures does not require use of equipment in this fire area so no further analysis of normal shutdown is required. 3.4.1 Main Control Room Safe Shutdown Safe shutdown will be accomplished with control from the main control room, utilizing the safe shutdown equipment in the following locations:

a. Non-Essential Switchgear Area
b. Condensate Storage Tank Valve Room (CST)
c. Train A Switchgear Room
d. Train B Switchgear Room
e. Turbine Building SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.4 Page 3.4-2 Actions required in the additional areas would be to realign the suction of the startup feedpump; realign the power supply of the startup feedpump from Bus ED

-SWG-4 to Bus EDE -SWG-5 (if offsite power is not available and not already aligned to Bus EDE-SWG-5); bypass the startup feedpump low suction pressure trip (prior to commencing cooldown) and trip the power supply breakers for the feedwater flow control valves. Safe shutdown will then be performed from the main control room. 3.4.2 Safe Shutdown Equipment List Tables that list all equipment, including instrumentation and vital support systems equipment, required to achieve hot standby and cold shutdown are provided in Appendix III. The tables provide the following requested information for each equipment listed.

a. A column which notes whether the equipment is required for hot standby and cold shutdown.
b. A column which defines each equipment

's location by fire zone/area.

c. A column which defines each equipment

's redundant counterpart.

d. A column which lists each equipment

's essential cabling.

e. The table also delineates the following additional information:
1) P & I Diagram Drawing No.
2) Physical Location Drawing No.
3) Power Supply
4) Electrical Node Number
5) Supporting Control and Instrumentation Equipment
6) Electrical Schematic Drawing No.
7) Electrical Cable Schematic Drawing No.
8) Supporting Systems
9) Remarks SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.4 Page 3.4-3 Separate tables are furnished for each of the safe shutdown functions. In several instances a safe shutdown function requires components from several systems to perform its safe shutdown function.

In order to simplify the tabulation, the following are not listed: manual valves in the process flow path; mechanical check valves which provide a Safe Shutdown system boundary; normally closed manual valves which provide a Safe Shutdown system boundary; mechanical relief valves; and root valves on small instrument lines. The review of these valves is documented by the marked P

& I Diagrams.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.4 Page 3.4-4 3.4.3 Analysis and Evaluation of Fire Area EFP -F-l-A, Emergency Feedwater Pump Bldg. A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-FT-4214-2 x x FW-FT-4214-4 x x FW-FT-4224-4 x x FW-FT-4224-2 x x FW-FT-4234-2 x x FW-FT-4234-4 x x FW-FT-4244-4 x x FW-FT-4244-2 x x FW-FV-4214A x x FW-FV-4214B x x FW-FV-4224A x x FW-FV-4224B x x FW-FV-4234A x x FW-FV-4234B x x FW-FV-4244A x x FW-FV-4244B x x B. Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A safe shutdown equipment and cables are located in other fire areas. Additional details on the fire protection measures and physical separation for this fire area are contained in Tabulation 3.2.7.48. Redundant emergency feedwater flow control valves and associated flow transmitters which are part of the alternative shutdown capability are located in the fire area. These valves are normally open valves and remain open for the initial phases of safe shutdown. Only two steam generators are required to satisfy the safe shutdown requirements: hence, only two valves on each of two lines need to be disabled (e.g., FW -FV-4214A, FW-FV-4214B, FW -FV-4224A and FW -FV-4224B). The operators will prevent additional spurious operations by tripping the power supply breakers for these valves in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). C. Evaluation A deviation from the Appendix R, Paragraph III.L.3 requirements exists in the emergency feedwater pump building. This deviation is justified based on the analysis and our assertion that additional modifications would not enhance fire protection safety.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.5 Page 3.5-1 3.5 HIGH LOW PRESSURE INTERFACES 3.5.1 List of Interfaces The following is a list of the high -low pressure interfaces connected to the reactor coolant system (RCS). 3.5.1.1 Chemical and Volume Control System (CS)

a. Excess letdown line
b. Normal letdown line
c. Reactor coolant pumps seal bleedoff lines 3.5.1.2 Residual Heat Removal (RH) System 3.5.1.3 Pressurizer Power Operated Relief Valves (PORV) 3.5.1.4 Reactor Vessel Head Vent 3.5.2 High-Low Pressure Interface Safe Shutdown Equipment List A list of all high

-low pressure interface valves is provided in Appendix, Section III. The table provides the following requested information for each equipment listed:

a. A column which notes whether the equipment is required for hot and/or cold shutdown.
b. A column which defines each equipment

's location by fire zones/area.

c. A column which defines each equipment

's redundant counterpart.

d. A column which lists each equipment

's essential cabling. For each cable 's routing by fire zone/area, see computer report "Cables with Associated Fire Zones " in the Appendix, Section V.G (High -Low Pressure Interface Reports).

e. The table also delineates the following additional information:
1) P & I Diagram Drawing No.
2) Physical Location Drawing No.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.5 Page 3.5-2 3) Power Supply

4) Electrical Node Number
5) Supporting Control and Instrumentation Equipment
6) Electrical Schematic Drawing No.
7) Electrical Cable Schematic Drawing No.
8) Supporting Systems
9) Remarks 3.5.3 Review and Analysis A review of each of the lines listed in subsection 3.5.1 is provided to identify lines which could open and cause a LOCA.

The flow through each high -low interface path will be evaluated. If the flow is less then the capacity of one charging pump, then the open path is not considered a LOCA and no further circuit analysis is required. The effect of the flow on system operation would still need to be evaluated. If the flow exceeds the capacity of one charging pump, then further circuit analysis is required per the criteria in Section 3.1.8 to demonstrate that spurious valve operation can not result in an open path. A specific flow value may not be documented for cases where it is obviously unacceptable (ex. RHR/RCS isolation valves). Alternatively, a circuit analysis per the criteria in Section 3.1.8 can be used to demonstrate that spurious valve operation cannot result in an open high -low interface path so no flow analysis is needed. 3.5.3.1 Chemical and Volume Control System

a. Excess letdown line The high-low pressure interface is downstream of control valve CS

-HCV-123. This is a normally closed, fail close diaphragm valve. Upstream of CS -HCV-123 are two normally closed, fail close diaphragm valves, CS -V175 and CS -V176. Spurious opening of one valve will not open the path and prevent safe shutdown. The operators will prevent further spurious openings by tripping the 125 Volt dc power supply breaker for valves CS -V175 and CS -V176 in the Train B switchgear room. An additional disabling capability exists at the disabling panel for CS -V-175 in the Train B diesel generator room (Fire Area: DG -F-2B-A) should the primary capability be inaccessible due to a fire in the switchgear room.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.5 Page 3.5-3 b. Normal letdown line The high-low pressure interface is downstream of parallel valves CS -HCV-189 and CS-HCV-190 (letdown flow control valves). These valves are motor operated drag valves. Upstream of CS -HCV-189 and CS -HCV-190 are fail close diaphragm valves CS -V145, RC-LCV-459, and RC-LCV-460. CS-HCV-189 or 190 failing full open results in a maximum flow rate that exceeds the charging pump capability . To isolate this path, the operator will close CS -V-145, RC-LCV-459 or RC-LCV-460. RC-LCV-459 and RC -LCV-460 can also be closed by tripping a circuit breaker at the 125 Volt distribution panels in the A Train switchgear room (Fire Area: CB -F-1A-A). An additional disabling capability exists in the Train A diesel generator room (Fire Area: DG -F-2A-A) for RC-LCV-459. c. Reactor coolant pumps seal bleedoff lines The high-low pressure interface is downstream of valves CS -V44 (Loop 3), CS -V59 (Loop 4), CS -V10 (Loop 1), CS -V28 (Loop 2). These valves are fail open diaphragm valves. However, these valves are not used for pressure reduction. The RCP seals are the pressure reduction device. If the bleedoff line is isolated downstream of the high/low interface, the pressure would equalize across the seals and pressurize the bleed lines. The low pressure portion of the bleedoff line is protected with relief valves CS -V173, CS-V794, and CS -V250. Bleedoff from the RCP seals will equal a maximum of 12 GPM either discharging to the reactor drain tank (RDT) if containment isolation valves CS -V168 or CS-V167 (normally open motor operated valves) close or to the charging pump suction. RCS fluid to the RDT is not recoverable but will be made up by flow to the charging suction from BAT or RWST. 3.5.3.2 Residual Heat Removal System The high-low pressure interface is downstream of motor operated valves (MOV) RV -V23 (Loop 1) and RC-V88 (Loop 4). Upstream of each MOV is MOV RC -V22 and RC -V87. All four valves are normally closed when the RCS is above RHR design pressure of 600 psig and interlocked to prevent opening when RCS pressure is above 365 psig. During normal operation these normally closed MOV 's will also be deenergized at their respective motor control center, thus there is no possibility of a short circuit, or hot short circuit opening the valves. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.5 Page 3.5-4 3.5.3.3 Pressurizer Power Operated Relief Valves The high-low pressure interface is downstream of paralleled valves RC -PCV-456A and RCV-PCV-456B. These valves are normally closed, fail closed solenoid operated valves. Upstream of each of these valves are the PORV block valves RC-V122 and RC -V124. These MOV's are normally open. Since the PORV block valves are normally open MOVs and will be closed for all fires which could cause spurious PORV operation, a hot short to the control logic or power to the PORV or block valves will not cause PORV blowdown. The operators will prevent the opening of the solenoid operated valves RC -PCV-456A and RC-PCV-456B by tripping their respective power supply breakers in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). An additional disabling capability exists in the Train A and Train B diesel generator rooms (Fire Areas: DG -F-2A-A and DG-F-2B-A) respectively should the primary capability be inaccessible due to a fire in the switchgear room. 3.5.3.4 Reactor Vessel Head Vent The high-low pressure interface is downstream of valve, RC -V323. This is a normally closed MOV. Upstream of RC -V323 is a normally closed, solenoid valve, RC -FV-2881. Spurious opening of one valve will not open the path. The operators will prevent further spurious openings by disabling the normally closed MOV RC -V323 and solenoid RC -FV-2881 at the motor control center and 125 volt dc distribution panel, respectively, in the B Train switchgear room (Fire Area: CB-F-1B-A). An additional disabling capability exists for RC-FV-2881 in the Train B diesel generator room (Fire Area: DG -F-2B-A) should the primary capability be inaccessible due to a fire in the switchgear room.

3.5.4 Evaluation

3.5.4.1 Chemical and Volume Control System

a. Excess letdown line The safe shutdown requirements are satisfied.
b. Normal letdown line The safe shutdown requirements are satisfied
c. Reactor coolant pumps seal bleedoff lines The safe shutdown requirements are satisfied

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.5 Page 3.5-5 3.5.4.2 Residual Heat Removal System The safe shutdown requirements are satisfied. 3.5.4.3 Pressurizer Power Operated Relief Valves The safe shutdown requirements are satisfied. 3.5.4.4 Reactor Vessel Head Vent The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.6 Page 3.6-1 3.6 ASSOCIATED CIRCUITS 3.6.1 Definition of Associated Circuits of Concern Circuits other than those directly required for the safe shutdown functions which have the potential to affect or prevent post -fire safe shutdown are considered associated circuits of concern. Associated circuits of concern are defined as those cables (Class 1E and non -Class 1E) that: a. Have a physical separation less than that required by Section III.G.2 of Appendix R, and b. Have one of the following:

1) a common power source with the safe shutdown equipment (redundant or alternative) and the power source is not electrically protected from the circuit of concern by coordinated breakers, fuses or similar devices, or
2) a connection to circuits of equipment whose spurious operation would adversely affect the safe shutdown capability (e.g., RHR/RCS isolation valves, PORVS, steam atmospheric dump valves, etc.), or
3) a common enclosure (e.g., panel) with the shutdown cables (redundant or alternative) and a) are not electrically protected by circuit breakers, fuses or similar devices, or b) will allow propagation of fire into the common enclosure.

3.6.2 Discussion of Methodology Sections 3.6.2.1, 3.6.2.2 and 3.6.2.3 in conjunction with Figure 3.6-1 describes the methodology utilized to address the following types of associated circuits:

a. Common power source
b. Spurious operation
c. Common enclosure

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.6 Page 3.6-2 3.6.2.1 Common Power Source As stated in FSAR Section 8.3.1.4, all non -Class 1E circuits are associated relative to electrical separation with either Train A or Train B in accordance with the provisions of FSAR Appendix 8A Section 4.5a. Based on these design consideration s, associated circuits can be powered from the Class 1E electrical distribution emergency (EDE) system or from the

non-Class 1E electrical distribution (ED) system and further may be routed in the same raceways and terminate in the same enclosure as Class 1E circuits. Although all safe shutdown circuits are powered from the EDE system, not all safe shutdown circuits are considered to be Class 1E. There are no Safe shutdown circuits, which require electrical power to operate, powered from the ED system. Associated circuits that are powered from the EDE system, and are associated with the safe shutdown circuits by a common power supply, are protected by a coordinated circuit breaker and; hence, are not considered to be associated circuits of concern. The above design considerations eliminates as associated circuits of concern all circuits which have no deleterious impact on safe shutdown. 3.6.2.2 Spurious Operation The review of each system required to satisfy the safe shutdown functions included all valves necessary to operate the system or maintain the system process boundaries. This assures that the safe shutdown system will operate as designed. If valves or other equipment from one train (i.e., Train A) are required for operation or could prevent operation of the other train (i.e., Train B), then additional reviews are performed to determine the failure modes and provide manual actions or operations of other equipment that would prevent the spurious operation from affecting safe shutdown. An example of this is the primary component cooling water containment isolation function which requires that both Train A and Train B valves remain open. The inboard containment isolation valve is the same train as the pumps which supply primary component cooling water while the outboard valve is of the opposite train but could be operated manually upon loss of power or damage to electrical circuit. To prevent the spurious operation of various safety injection system valves, containment isolation valves and service water valves, the engineered safety features actuation system logic and the tower actuation logic are disabled by tripping their power supplies after a control room evacuation. In several instances (e.g., RHR/RCS isolation valves), the power supplies are permanently disabled (breaker tripped and locked out) to prevent spurious operation. The spurious operation of valves protecting high -low pressure interfaces is discussed in Section 3.5. See Section 3.1.8 for criteria to evaluate components for spurious operation . SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.6 Page 3.6-3 3.6.2.3 Common Enclosures The deleterious effects of fire on associated circuits in common enclosures is eliminated by the following three design considerations:

a. Coordinated circuit breakers, fuses or similar devices will assure that the associated circuit failure does not prevent the redundant train from performing its safe shutdown function. b. The cables are qualified to IEEE Standard 383; hence, the propagation of the fire from one train to the redundant train in another fire area/zone is very unlikely.
c. Train and channel separation for cable routing is assured by a computerized cable routing program which does not allow cables with different circuit code assignments to be routed in the same raceways.

Based on the above design considerations, associated circuits in common enclosures are not considered associated circuits of concern. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 5 Section 3.7 Page 3.7-1 3.7 DEVIATIONS FROM 10CFR50 APPENDIX R Fire Area Section Located In Report Equipment/System Type Of Deviation From Appendix C-F-1-Z/C-F-2-Z/ 3.2.7.1 B.2.c CC-V-57, 121, 176, 256 III.G.2.d C-F-3-Z 3.2.7.1 B.2.k Pressurizer Heaters III.G.2.d 3.2.7.1 B.2.l RC-PCV-456A, B III.G.2.d 3.2.7.1 B.2.n SI-V3, SI-FV-2475, 2476 III.G.2.d 3.2.7.1 B.2.o SI-V32, SI-FV-2477, 2486 III.G.2.d 3.2.7.1 B.2.p SI-V-17, SI-FV-2482, 2483 III.G.2.d 3.2.7.1 B.2.q SI-V-47, SI-FV-2495, 2496 III.G.2.d 3.2.7.1 B.2.u NI-NE-6690, 6691 III.G.2.d 3.2.7.1 B.2.v RC-LT-459, 460 III.G.2.d 3.2.7.1 B.2.x RC Hot Leg Temp. III.G.2.d CB-F-2C-A 3.2.7.10.B.2 CBA III.G.2.c Auto Fire Suppression CB-F-3A-A 3.3.9.2 Control Room/RSS III.G.3 - Fixed Fire Suppression CB-F-3B-A 3.3.9.3 HVAC Equipment & Duct Area - Control Room III.G.3 - Fixed Fire Suppression CE-F-1A-Z/ 3.2.7.17 B.f EAH-AC-2A, -2B, EAH-FN-5A, III.G.2.b - Separation 20 ' PP-F-XX-Z -5B, EAH-DP-3A, -3B III.G.2.c - Auto Fire Suppression DG-F-3A-Z/ 3.2.7.41 B.2.b DAH-FN-25A, -25B III.G.2.b - Separation 20 ' DG-F-3B-Z III.G.2.c - Auto Fire Suppression

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 5 Section 3.7 Page 3.7-2 Fire Area Section Located In Report Equipment/System Type Of Deviation From Appendix EFP-F-1-A 3.2.7.48 EFW Room III.G.3 - Fixed Fire Suppression 3.4.3 EFW Room III.L.3 - Independence PAB-F-1A-Z* 3.2.7.63 CC, CS, EAH, PAH, SI, SW III.G.2.c - Auto Fire Suppression PAB-F-1J-Z* 3.2.7.66 CC, SI, CS III.G.2.c - Auto Fire Suppression PAB-F-1K-Z* 3.2.7.67 CS, SW, PAH III.G.2.b - Separation 20 ' III.G.2.c - Auto Fire Suppression PAB-F-2A-Z* 3.2.7.68 EAH, PAH, SW III.G.2.c - Auto Fire Suppression PAB-F-2B-Z* 3.2.7.69 PAH III.G.2.c - Auto Fire Suppression PAB-F-2C-Z* 3.2.7.70 PAH III.G.2.b - Separation 20 ' PAB-F-3A-Z* 3.2.7.71 CS, SW III.G.2.c - Auto Fire Suppression PAB-F-3B-Z* 3.2.7.72 CS III.G.2.c - Auto Fire Suppression

  • Denotes Group of Fire Zones which form one Fire Area in PAB. In addition to the deviations requested, a general deviation to the requirements at III.G.2.a is requested for this area.

ASSOCIATED CIRCUITS OF CONCERN APPENDIX R Figure 3.6-1

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -1 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 FW-P-113 Start-up Feedwater Pump CO-20426 A 310326 TB-F-1A-Z X X X - M12 FW-A93-52 4160 V AC Circuit Breaker A93 CB-F-1A-A A47-A93 A47-A93/1 A47-A93/2 A47-A93/3 A47-N12 A47-P82 310844 A93a A93g A93b A93h A93c A93d A47a A47g EDE-SWG-5 CBA-FN-19 CBA-FN-20 FW-P-37B FW-A93-FU Fuses A93 CB-F-1A-A FW-CS-4268-1 Control Switch with Indication F60 CB-F-3A-A FW-SS-4268 Selector Switch A47 NES-F-1A-Z FW-A93-CS Test Control Switch A93 CB-F-1A-A FW-A93-G,R,W Indicating Lights A93 CB-F-1A-A A93-F60/1 A93-F60/2 A93-F60/3 A93-F60/4 A93-ED7 A93-G8L A93-HR2 G8L-P2V (Non-CASP) EDE-A53-94-2 Bus Undervoltage A53 CB-F-1A-A FW-A93-R1 Auxiliary Relay A93 CB-F-1A-A FW-PSLH-PS5 Lube Oil Pressure Switch P82 TB-F-1A-Z FW-A93-PS5X Pressure Switch Auxiliary Relay A93 CB-F-1A-A FW-A93-52S Mechanically Operated Contact A93 CB-F-1A-A FW-A93-52H Truck Operated Contact A93 CB-F-1A-A FW-A93-62 P85 Starting Blocking Time Delay Relay A93 CB-F-1A-A FW-ED7-2 Pre-Lube Pump Starting Auxiliary Time Delay Relay ED7 TB-F-2A-Z FW-A93-86 Lockout Relay A93 CB-F-1A-A FW-A93-TD2 Lockout Relay Test Device A93 CB-F-1A-A FW-A93-CT Current Transformers 300/5A A93 CB-F-1A-A FW-A93-TD1 CT Test Device A93 CB-F-1A-A FW-A93-50/51 Inst./Time Overcurrent Relays ØA, ØC A93 CB-F-1A-A FW-A93-AM Ammeter A93 CB-F-1A-A FW-A93-AS Ammeter Switch A93 CB-F-1A-A FW-A93-ATR Transducer A93 CB-F-1A-A FW-AM-4268-1 Ammeter F60 CB-F-3A-A FW-A47-52 4160 V AC Circuit Breaker A47 NES-F-1A-Z FW-A93-51GS Ground Sensor Relay A93 CB-F-1A-A FW-PSL-4233-2 Pressure Switch Low Suction P2V TB-F-1A-Z FW-A93-R2 Auxiliary Relay A93 CB-F-1A-A FW-HR2-RMO EPS Manual Override Relay (K27 ) HR2 CB-F-1A-A FW-CS-4233 Suction Pressure Bypass Switch G8L TB-F-1A-Z

. 1. This equipment is mechanical with no electrical requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -2 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 FW-P-161 Start-up Feedwater Pump FW-P-113 Prelube Pump CO-20426 A 310326 TB-F-1A-Z X X X - NU0 FW-CN1-52 460 V AC Circuit Breaker CN1 TB-F-2-Z CNA-NU0 CN1-F60 CN1-F81 A47-F60/4 EA1-F60 F60-FB7/5 310844 CN1a CN1c EDE-MCC-523 None FW-CN1-FU Fuse CN1 TB-F-2-Z FW-CS-4268 Control Switch with Indication F60 CB-F-3A-A FW-SS-4268 Selector Switch A47 NES-F-1A-Z FW-CS-4268-1 Control Switch with Indication F60 CB-F-3A-A FW-CS-4278 Control Switch F60 CB-F-3A-A FW-ED7-2 Pump Starting Time Delay Relay ED7 TB-F-2-Z FW-PSLH-PS4 Lube Oil Pressure Switch P81 TB-F-1A-Z FW-CN1-42 Motor Starter CN1 TB-F-2-Z FW-CN1-49 Overload Relays CN1 TB-F-2-Z FW-FB7-K620A SSPS Output Relay FB7 CB-F-3A-A FW-ED7-3 Time Delay Relay ED7 TB-F-2-2 FW-J8K-K5R, S, T GE MK Vle TMR Relay J8K TB-F-2-Z EA1-J9M/1 J8M-J9M FW-J9K-K5R, S, T GE MK Vle TMR Relay J9K TB-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -3 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 FW-FV-4214A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2E FW-B3V-52 460 V AC Circuit Breaker B3V CB-F-1A-A B3V-V2E B3V-V2E/1 E3C-G2G G2G-V2E E3C-F51 F51-G2G B3V-G5X B3V-G5X/1 E3C-FN6 F51-FN6 FN6-G5X FN6-G5X/1 310844 B3Va B3Vd B3ve CBA-FN-19 CBA-FN-20 EDE-MCC-515 FW-FV-4214B FW-B3V-FU Fuse B3V CB-F-1A-A FW-CS-4214-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4214-A Selector Switch G2G CB-F-1A-A FW-SS-4214-A1 Selector Switch G5X DG-F-2A-A FW-CS-4214-A1 Control Switch with Indication F51 CB-F-3A-A FW-B3V-42/O,C Motor Starters B3V CB-F-1A-A FW-B3V-49 Overload Relays B3V CB-F-1A-A FW-ZS-4214-A Valve Position Switch V2E EFP-F-1-A FW-FN6-4214AX Auxiliary Relay FN6 CB-F-2B-A FW-FN6-MSO-1 Auxiliary Relay FN6 CB-F-2B-A FW-FN6-R1A Auxiliary Relay FN6 CB-F-2B-A FW-E3P-62-1 Timing Relay E3P CB-F-1A-A FW-E3C-R1 Auxiliary Relay (FYY-4214-2) E3C CB-F-1A-A FW-E3P-62-2 Timing Relay E3P CB-F-1A-A FW-E3C-R2 Auxiliary Relay (FYY-4224-4) E3C CB-F-1A-A FW-E3P-62-3 Timing Relay E3P CB-F-1A-A FW-E3C-R3 Auxiliary Relay (FYY-4234-2) E3C CB-F-1A-A FW-E3P-62-4 Timing Relay E3P CB-F-1A-A FW-E3C-R4 Auxiliary Relay (FYY-4244-4) E3C CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -4 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 FW-FV-4214B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2J FW-B3Z-52 460 V AC Circuit Breaker B3Z CB-F-1B-A B3Z-V2J B3Z-V2J/1 E3D-G2J G2J-V2J E3D-F51 F51-G2J B3Z-G2J B3Z-G5Y B3Z-G5Y/1 E3D-FN7 F51-FN7 FN7-G5Y FN7-G5Y/1 310844 B3Za B3Zd B3Ze CBA-FN-32 CBA-FN-33 EDE-MCC-615 FW-FV-4214A FW-B3Z-FU Fuse B3Z CB-F-1B-A FW-CS-4214-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4214-B Selector Switch G2J CB-F-1B-A FW-SS-4214-B1 Selector Switch G5Y DG-F-2B-A FW-CS-4214-B1 Control Switch with Indication F51 CB-F-3A-A FW-B3Z-42/O,C Motor Starters B3Z CB-F-1B-A FW-B3Z-49 Overload Relays B3Z CB-F-1B-A FW-ZS-4214-B Valve Position Switch V2J EFP-F-1-A FW-FN7-4214BX Auxiliary Relay FN7 CB-F-2C-A FW-FN7-MSO-1 Auxiliary Relay FN7 CB-F-2C-A FW-FN7-R1B Auxiliary Relay FN7 CB-F-2C-A FW-E3Q-62-1 Timing Relay E3Q CB-F-1B-A FW-E3D-R1 Auxiliary Relay (FYY-4214-4) E3D CB-F-1B-A FW-E3Q-62-2 Timing Relay E3Q CB-F-1B-A FW-E3D-R2 Auxiliary Relay (FYY-4224-2) E3D CB-F-1B-A FW-E3Q-62-3 Timing Relay E3Q CB-F-1B-A FW-E3D-R3 Auxiliary Relay (FYY-4234-4) E3D CB-F-1B-A FW-E3Q-62-4 Timing Relay E3Q CB-F-1B-A FW-E3D-R4 Auxiliary Relay (FYY-4244-2) E3D CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -5 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 FW-FV-4224A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2F FW-B3W-52 460 V AC Circuit Breaker B3W CB-F-1A-A B3W-V2F B3W-V2F/1 E3C-G2G/1 G2G-V2F E3C-F51/1 F51-G2G/1 B3W-G5X B3W-G5X/1 E3C-FN6/1 F51-FN6/1 FN6-G5X/2 FN6-G5X/3 310844 B3Wa B3Wd B3We CBA-FN-19 CBA-FN-20 EDE-MCC-515 FW-FV-4224B FW-B3W-FU Fuse B3W CB-F-1A-A FW-CS-4224-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4224-A Selector Switch G2G CB-F-1A-A FW-SS-4224-A1 Selector Switch G5X DG-F-2A-A FW-CS-4224-A1 Control Switch with Indication F51 CB-F-3A-A FW-B3W-42/O,C Motor Starters B3W CB-F-1A-A FW-B3W-49 Overload Relays B3W CB-F-1A-A FW-ZS-4224-A Valve Position Switch V2F EFP-F-1-A FW-FN6-4224AX Auxiliary Relay FN6 CB-F-2B-A FW-FN6-MSO-2 Auxiliary Relay FN6 CB-F-2B-A FW-FN6-R2A Auxiliary Relay FN6 CB-F-2B-A FW-E3C-R1 Auxiliary Relay (FYY-4214-2) E3C CB-F-1A-A FW-E3C-R2 Auxiliary Relay (FYY-4224-4) E3C CB-F-1A-A FW-E3C-R3 Auxiliary Relay (FYY-4234-2) E3C CB-F-1A-A FW-E3C-R4 Auxiliary Relay (FYY-4244-4) E3C CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -6 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 FW-FV-4224B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2K FW-B4A-52 460 V AC Circuit Breaker B4A CB-F-1B-A B4A-V2K B4A-V2K/1 E3D/G2J/1 G2J-V2K E3D-F51/1 F51-G2J/1 B4A-G2J B4A-G5Y B4A-G5Y/1 E3D-FN7/1 F51-FN7/1 FN7-G5Y/2 FN7-G5Y/3 310844 B4Aa B4Ad B4Ae CBA-FN-32 CBA-FN-33 EDE-MCC-615 FW-FV-4224A FW-B3W-FU Fuse B4A CB-F-1B-A FW-CS-4224-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4224-B Selector Switch G2J CB-F-1B-A FW-SS-4224-B1 Selector Switch G5Y DG-F-2B-A FW-CS-4224-B1 Control Switch with Indication F51 CB-F-3A-A FW-B4A-42/O,C Motor Starters B4A CB-F-1B-A FW-B4A-49 Overload Relays B4A CB-F-1B-A FW-ZS-4224-B Valve Position Switch V2K EFP-F-1-A FW-FN7-4224BX Auxiliary Relay FN7 CB-F-2C-A FW-FN7-MSO-2 Auxiliary Relay FN7 CB-F-2C-A FW-FN7-R2B Auxiliary Relay FN7 CB-F-2C-A FW-E3D-R1 Auxiliary Relay (FYY-4214-4) E3D CB-F-1B-A FW-E3Q-62-1 Timing Relay E3Q CB-F-1B-A FW-E3D-R2 Auxiliary Relay (FYY-4224-2) E3D CB-F-1B-A FW-E3Q-62-2 Timing Relay E3Q CB-F-1B-A FW-E3D-R3 Auxiliary Relay (FYY-4234-4) E3D CB-F-1B-A FW-E3Q-62-3 Timing Relay E3Q CB-F-1B-A FW-E3D-R4 Auxiliary Relay (FYY-4244-2) E3D CB-F-1B-A FW-E3Q-62-4 Timing Relay E3Q CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -7 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 FW-FV-4234A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2G FW-B3X-52 460 V AC Circuit Breaker B3X CB-F-1A-A B3X-V2G B3X-V2G/1 G2G-V2G E3C-G2G/2 E3C-F51/2 F51-G2G/2 B3X-G5X B3X-G5X/1 E3C-FN6/2 F51-FN6/2 FN6-G5X/4 FN6-G5X/5 310844 B3Xa B3Xd B3Xe CBA-FN-19 CBA-FN-20 EDE-MCC-515 FW-FV-4234B FW-B3X-FU Fuse B3X CB-F-1A-A FW-CS-4234-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4214-A Selector Switch G2G CB-F-1A-A FW-SS-4214-A1 Selector Switch G5X DG-F-2A-A FW-CS-4234-A1 Control Switch with Indication F51 CB-F-3A-A FW-B3X-42/O,C Motor Starters B3X CB-F-1A-A FW-B3X-49 Overload Relays B3X CB-F-1A-A FW-ZS-4234-A Valve Position Switch V2G EFP-F-1-A FW-FN6-4234AX Auxiliary Relay FN6 CB-F-2B-A FW-FN6-MSO-3 Auxiliary Relay FN6 CB-F-2B-A FW-FN6-R3A Auxiliary Relay FN6 CB-F-2B-A FW-E3C-R1 Auxiliary Relay (FYY-4214-2) E3C CB-F-1A-A FW-E3P-62-1 Timing Relay E3Q CB-F-1A-A FW-E3C-R2 Auxiliary Relay (FYY-4224-4) E3C CB-F-1A-A FW-E3P-62-2 Timing Relay E3Q CB-F-1A-A FW-E3C-R3 Auxiliary Relay (FYY-4234-2) E3C CB-F-1A-A FW-E3P-62-3 Timing Relay E3Q CB-F-1A-A FW-E3C-R4 Auxiliary Relay (FYY-4244-4) E3C CB-F-1A-A FW-E3P-62-4 Timing Relay E3Q CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -8 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 8 FW-FV-4234B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2L FW-B4B-52 460 V AC Circuit Breaker B4B CB-F-1B-A B4B-V2L B4B-V2L/1 E3D/G2J/2 G2J-V2L E3D-F51/2 F51-G2J/2 B4B-G2J B4B-G5Y B4B-G5Y/1 E3D-FN7/2 F51-FN7/2 FN7-G5Y/4 FN7-G5Y/5 310844 B4Ba B4Bd B4Be CBA-FN-32 CBA-FN-33 EDE-MCC-615 FW-FV-4234A FW-B4B-FU Fuse B4B CB-F-1B-A FW-CS-4234-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4214-B Selector Switch G2J CB-F-1B-A FW-SS-4214-B1 Selector Switch G5Y DG-F-2B-A FW-CS-4234-B1 Control Switch with Indication F51 CB-F-3A-A FW-B4B-42/O,C Motor Starters B4B CB-F-1B-A FW-B4B-49 Overload Relays B4B CB-F-1B-A FW-ZS-4234-B Valve Position Switch V2L EFP-F-1-A FW-FN7-4234BX Auxiliary Relay FN7 CB-F-2C-A FW-FN7-MSO-3 Auxiliary Relay FN7 CB-F-2C-A FW-FN7-R3B Auxiliary Relay FN7 CB-F-2C-A FW-E3D-R1 Auxiliary Relay (FYY-4214-4) E3D CB-F-1B-A FW-E3D-R2 Auxiliary Relay (FYY-4224-2) E3D CB-F-1B-A FW-E3D-R3 Auxiliary Relay (FYY-4234-4) E3D CB-F-1B-A FW-E3D-R4 Auxiliary Relay (FYY-4244-2) E3D CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -9 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 FW-FV-4244A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2H FW-B3Y-52 460 V AC Circuit Breaker B3Y CB-F-1A-A B3Y-V2H B3Y-V2H/1 E3C-G2G/3 G2G-V2H E3C-F51/3 F51-G2G/3 B3Y-G5X B3Y-G5X/1 E3C-FN6/3 F51-FN6/3 FN6-G5X/6 FN6-G5X/7 310844 B3Ya B3Yd B3Ye CBA-FN-19 CBA-FN-20 EDE-MCC-515 FW-FV-4244B FW-B3Y-FU Fuse B3Y CB-F-1A-A FW-CS-4244-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4224-A Selector Switch G2G CB-F-1A-A FW-SS-4224-A1 Selector Switch G5X DG-F-2A-A FW-CS-4244-A1 Control Switch with Indication F51 CB-F-3A-A FW-B3Y-42/O,C Motor Starters B3Y CB-F-1A-A FW-B3Y-49 Overload Relays B3Y CB-F-1A-A FW-ZS-4244-A Valve Position Switch V2H EFP-F-1-A FW-FN6-4244AX Auxiliary Relay FN6 CB-F-2B-A FW-FN6-MSO-4 Auxiliary Relay FN6 CB-F-2B-A FW-FN6-R4A Auxiliary Relay FN6 CB-F-2B-A FW-E3C-R1 Auxiliary Relay (FYY-4214-2) E3C CB-F-1A-A FW-E3P-62-1 Timing Relay E3P CB-F-1A-A FW-E3C-R2 Auxiliary Relay (FYY-4224-4) E3C CB-F-1A-A FW-E3P-62-2 Timing Relay E3P CB-F-1A-A FW-E3C-R3 Auxiliary Relay (FYY-4234-2) E3C CB-F-1A-A FW-E3P-62-3 Timing Relay E3P CB-F-1A-A FW-E3C-R4 Auxiliary Relay (FYY-4244-4) E3C CB-F-1A-A FW-E3P-62-4 Timing Relay E3P CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -10 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 10 FW-FV-4244B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2M FW-B4C-52 460 V AC Circuit Breaker B4C CB-F-1B-A B4C-V2M B4C-V2M/1 E3D/G2J/3 GJ2-V2M E3D-F51/3 F51-G2J/3 B4C-G2J B4C-G5Y B4C-G5Y/1 E3D-FN7/3 F51-FN7/3 FN7-G5Y/6 FN7-G5Y/7 310844 B4Ca B4Cd B4Ce CBA-FN-32 CBA-FN-33 EDE-MCC-615 FW-FV-4244A FW-B4C-FU Fuse B4C CB-F-1B-A FW-CS-4244-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4224-B Selector Switch G2J CB-F-1B-A FW-SS-4224-B1 Selector Switch G5Y DG-F-2B-A FW-CS-4244-B1 Control Switch with Indication F51 CB-F-3A-A FW-B4C-42/O,C Motor Starters B4C CB-F-1B-A FW-B4C-49 Overload Relays B4C CB-F-1B-A FW-ZS-4244-B Valve Position Switch V2M EFP-F-1-A FW-FN7-4244BX Auxiliary Relay FN7 CB-F-2C-A FW-FN7-MSO-4 Auxiliary Relay FN7 CB-F-2C-A FW-FN7-R4B Auxiliary Relay FN7 CB-F-2C-A FW-E3D-R1 Auxiliary Relay (FYY-4214-4) E3D CB-F-1B-A FW-E3Q-62-1 Timing Relay E3Q CB-F-1B-A FW-E3D-R2 Auxiliary Relay (FYY-4224-2) E3D CB-F-1B-A FW-E3Q-62-2 Timing Relay E3Q CB-F-1B-A FW-E3D-R3 Auxiliary Relay (FYY-4234-4) E3D CB-F-1B-A FW-E3Q-62-3 Timing Relay E3Q CB-F-1B-A FW-E3D-R4 Auxiliary Relay (FYY-4244-2) E3D CB-F-1B-A FW-E3Q-62-4 Timing Relay E3Q CB-F-1B-A 11 FW-V-156 Start-up Feed Pump to EFW Header Valve FW-20688 A 310589 MS-F-1B-Z X X X - V3L FW-B4S-52 460 V AC Circuit Breaker B4S CB-F-1A-A B4S-V3L B4S-V3L/1 B4S-F60 B4S-F60/1 310844 B4Sa B4Sc CBA-FN-19 CBA-FN-20 EDE-MCC-531 None FW-F4S-FU Fuse B4S CB-F-1A-A FW-CS-4261 Control Switch with Indication F60 CB-F-3A-A FW-B4S-42/O,C Motor Starters B4S CB-F-1A-A FW-B4S-49 Overload Relays B4S CB-F-1A-A FW-ZS-V156 Valve Position and Open/Close Torque Switches V3L MS-F-1B-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -11 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 12 FW-V-163 Start-up Feed Pump Bypass to EFW Pump Valve FW-20687 A 310326 TB-F-1A-Z X X X - V3M FW-C2R-52 460 V AC Circuit Breaker C2R TB-F-2A-Z C2R-V3M C2R-V3M/1 C2R-F60 310844 C2Ra C2Rc EDE-MCC-523 None FW-C2R-FU Fuse C2R TB-F-2A-Z FW-CS-4262 Control Switch with Indication F60 CB-F-3A-A FW-C2R-42/O,C Motor Starter C2R TB-F-2A-Z FW-C2R-49 Overload Relays C2R TB-F-2A-Z FW-ZS-V163 Valve Position and Open/Close Torque Switches V3M TB-F-1A-Z 13 FW-E3C Emergency Feedwater Valves Train "A" Vital Controls Relay Compt. (MCC -515) - A 310442 CB-F-1A-A X X X - E3C FW-E3E-52 120 V AC Circuit Breaker E3E CB-F-1A-A E3C-FK0 E3C-F56 E3C-FN6/4 FK0-FN6 FK0-FN6/1 310844 E3E/1a, 1e E3E/1c CBA-FN-19 CBA-FN-20 EDE-MCC-515 120 V AC Distribution Panel None FW-E3C-R1 Auxiliary Relay (FYY-4214-2) E3C CB-F-1A-A FW-E3C-R2 Auxiliary Relay (FYY-4224-4) E3C CB-F-1A-A FW-E3C-R3 Auxiliary Relay (FYY-4234-2) E3C CB-F-1A-A FW-E3C-R4 Auxiliary Relay (FYY-4244-4) E3C CB-F-1A-A FW-CS-4241-A1 Control Switch F51 CB-F-3A-A FW-CS-4224-A1 Control Switch F51 CB-F-3A-A FW-CS-4234-A1 Control Switch F51 CB-F-3A-A FW-CS-4244-A1 Control Switch F51 CB-F-3A-A MM-CP-279 "A" Train BOP -PCC FK0 CB-F-3A-A 14 FW-E3D Emergency Feedwater Valves Train "B" Vital Controls Relay Compt. (MCC -615) - B 310442 CB-F-1B-A X X X - E3D FW-E3F-52 120 V AC Circuit Breaker E3F CB-F-1B-A E3D-FL2 E3D-F51/4 E3D-FN7/4 FL2-FN7 FL2-FN7/1 310844 E3F/1a, 1e E3F/1c CBA-FN-32 CBA-FN-33 EDE-MCC-615 120 V AC Distribution Panel None FW-E3D-R1 Auxiliary Relay (FYY-4214-4) E3D CB-F-1B-A FW-E3D-R2 Auxiliary Relay (FYY-4224-2) E3D CB-F-1B-A FW-E3D-R3 Auxiliary Relay (FYY-4234-4) E3D CB-F-1B-A FW-E3D-R4 Auxiliary Relay (FYY-4244-2) E3D CB-F-1B-A FW-CS-4241-B1 Control Switch F51 CB-F-3A-A FW-CS-4224-B1 Control Switch F51 CB-F-3A-A FW-CS-4234-B1 Control Switch F51 CB-F-3A-A FW-CS-4234-B1 Control Switch F51 CB-F-3A-A MM-CP-279B "B" Train BOP-PCC FL2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -12 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 FW-FT-4214-2 RC-E-11A Emergency Feedwater Header Flow Transmitter FW-20688 A 310708 EFP-F-1-A X X X - GL3 MM-CP-297A "A" Train BOP Process Control Panel FK0 CB-F-3A-A FK0-GL3 310844 FP 72179 FK0a MM-CP-297A FW-LT-501 16 FW-FT-4214-4 RC-E-11A Emergency Feedwater Header Flow Transmitter FW-20688 B 310708 EFP-F-1A-A X X X - GL4 MM-CP-297B Train "B" BOP Process Control Panel FL2 CB-F-3A-A FL2-GL4 310844 FP 72181 FL2a 17 FW-FT-4224-4 RC-E-11B Emergency Feedwater Header Flow Transmitter FW-20688 A 310708 EFP-F-1A-A X X X - GL3 MM-CP-297A Train "A" BOP Process Control Panel FK0 CB-F-3A-A FK0-GL3 310844 FP 72179 FK0a 18 FW-FT-4224-2 RC-E-11B Emergency Feedwater Header Flow Transmitter FW-20688 B 310708 EFP-F-1A-A X X X - GL4 MM-CP-297B Train "B" BOP Process Control Panel FL2 CB-F-3A-A FL2-GL4 310844 FP 72181 FL2a MM-CP-297B FW-LT-502 19 FW-FT-4234-2 RC-E-11C Emergency Feedwater Header Flow Transmitter FW-20688 A 310708 EFP-F-1A-A X X X - GL3 MM-CP-297A Train "A" BOP Process Control Panel FK0 CB-F-3A-A FK0-GL3 310844 FP 72179 FK0a MM-CP-297A FW-LT-503 20 FW-FT-4234-4 RC-E-11C Emergency Feedwater Header Flow Transmitter FW-20688 B 310708 EFP-F-1A-A X X X - GL4 MM-CP-297B Train "B" BOP Process Control Panel FL2 CB-F-3A-A FL2-GL4 310844 FP 72181 FL2a 21 FW-FT-4244-4 RC-E-11D Emergency Feedwater Header Flow Transmitter FW-20688 A 310708 EFP-F-1A-A X X X - GL3 MM-CP-297A Train "A" BOP Process Control Panel FK0 CB-F-3A-A FK0-GL3 310844 FP 72179 FK0a 22 FW-FT-4244-2 RC-E-11D Emergency Feedwater Header Flow Transmitter FW-20688 B 310708 EFP-F-1A-A X X X - GL4 MM-CP-297B Train "B" BOP Process Control Panel FL2 CB-F-3A-A FL2-GL4 310844 FP 72181 FL2a MM-CP-297B FW-LT-504 23 FW-LT-501 RC-E-11A SG Wide Range Level Transmitter FW-20686 A 310576 C-F-1-Z X X X - R1D FW-LQY-501 Signal Converter FA1 CB-F-3A-A FA1-H44 H44-R1D F56-FA1 310942 FP 55315 FA1h Sh. 13 MM-CP-1 FW-LI-501 Level Indicator F51 CB-F-3A-A EDE-MM-120 Electrical Penetration H44 C-F-2-Z, ET-F-1A-A MM-CP-1 PPC #1 FA1 CB-F-3A-A 24 FW-LT-502 RC-E-11B SG Wide Range Level Transmitter FW-20686 B 310576 C-F-1-Z X X X - R1E FW-LQY-502 Signal Converter FA2 CB-F-3A-A FA2-H55 H55-R1E F56-FA2/1 310942 FP 55316 FA2h Sh. 13 MM-CP-2 FW-LI-502 Level Indicator F51 CB-F-3A-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A MM-CP-2 PPC #2 FA2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -13 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 25 FW-LT-503 RC-E-11C SG Wide Range Level Transmitter FW-20686 A 310577 C-F-1-Z X X X - R1F FW-LQY-503 Signal Converter FA3 CB-F-3A-A FA3-H47/1 H47-R1F F56-FA3/2 310942 FP 55317 FA3h Sh. 13 MM-CP-3 FW-LI-503 Level Indicator F51 CB-F-3A-A EDE-MM-123 Electrical Penetration H47 C-F-2-Z, ET-F-1A-A MM-CP-3 PPC #3 FA3 CB-F-3A-A 26 FW-LT-504 RC-E-11D SG Wide Range Level Transmitter FW-20686 B 310577 C-F-1-Z X X X - R1G FW-LQY-504 Signal Converter FA4 CB-F-3A-A FA4-H52/1 H52-R1G F56-FA4 310942 FP 55318 FA4h Sh. 13 MM-CP-4 FW-LI-504 Level Indicator F51 CB-F-3A-A EDE-MM-128 Electrical Penetration H52 C-F-1-Z, ET-F-1C-A MM-CP-4 PPC #4 FA4 CB-F-3A-A - 27 CO-V-142 Condensate Tank Emergency Outlet Valve CO-20426 A 310248 202319 CST-F-1-0 X X - - - - - - - - - - - Note 1 28 CO-LT-4096 CO-TK-25 Condenser Storage Tank Level CO-20426 A 310828 CST-F-1 X X - R53 CO-LI-4096 Level Indicator F61 CB-F-3A-A FJ7-R53 F66-FJ8 310953 FJ7f FJ7g MM-CP-153 MM-CP-153 BOP-PCC FJ7 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-1 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CS-V-175 CS-20722 B 310577 C-F-1-Z X X X X L95 CS-E95/2-72 125 V DC Circuit Breaker E95 CB-F-1B-A CBA-FN-32 CBA-FN-33 CS-V176 Note 1 Excess Letdown

Line Isolation

Valve CS-CS-7418 Control Switch with Indication F41 CB-F-3A-A 310891 E95/2a E95/2c E95/2d CS-E4D-FU Fuses E4D CB-F-1B-A CS-SS-7418 Selector Switch G5Y DG-F-2B-A E95-E4D F48-G5Y F48-H39/3 GE5-H39/1 GE5-L95/1 E4D-F48 F48-H39/2 CS-FY-7418 Pilot Solenoid GE5 C-F-1-Z CS-ZS-V175 Valve Position Switch L95 C-F-1-Z EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A 2 CS-V-176 CS-20722 B 310577 C-F-1-Z X X X X LA5 CS-E95/4-72 125 V DC Circuit Breaker E95 CB-F-1B-A CBA-FN-32 CBA-FN-33 CS-V175 Note 1 Excess Letdown

Line Isolation

Valve CS-CS-7417 Control Switch with Indication F41 CB-F-3A-A CS-FY-7417 Pilot Solenoid GE5 C-F-1-Z 310891 E95/4a E95/4d E95/4b E95/4e E95/4f CS-ZS-V176 Valve Position Switch LA5 C-F-1-Z F48-H39/1 GE5-H39/5 E95-E4D/1 E4D-F26 F48-H39 GE5-H39/4 GE5-LA5/1 CS-E4D-FU Fuses E4D CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A 3 RC-LCV-459 RC-20843 A 310577 C-F-1-Z X X X X L99 RC-E89/17-72 125 V DC Circuit Breaker E89 CB-F-1A-A CBA-FN-19 CBA-FN-20 RC-LCV-460 Note 1 RC-CS-459 Control Switch with Indication F40 CB-F-3A-A 310882 E89/17a E89/17c E89/17d RC-LY-459B Pilot Solenoid GE5 C-F-1-Z Regen. Heat

Exchanger Letdown

Isolation Valve

(Outside Missile

Barrier) RC-ZS-LCV-459 Valve Position Switch L99 C-F-1-Z CS-ZS-V145 Valve Position Switch LH2 C-F-1-Z F40-H36 GE5-L99 GE5-H36/2 GE5-LH2/1 L99-LH2 F40-FB1/2 F40-G5X E4F-G5X E89-34F/8 RC-LY/459-CX1 Level Auxiliary Relay FB1 CB-F-3A-A RC-E4F-FU Fuses E4F CB-F-1A-A RC-SS-459 Selector Switch G5X DG-F-2A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A 4 RC-LCV-460 RC-20843 A 310577 C-F-1-Z X X X X LF7 RC-E89/1-72 125 V DC Circuit Breaker E89 CB-F-1A-A CBA-FN-19 CBA-FN-20 RC-LCV-459 Note 1 RC-CS-460 Control Switch with Indication F40 CB-F-3A-A Regen. Heat

Exchanger Letdown

Isolation Valve

(Inside Missile

Barrier) RC-LY-460E Pilot Solenoid GE4 C-F-1-Z 310882 E89/1b E89/1d E89/1e E89/1f RC-ZS-LCV-460 Valve Position Switch LF7 C-F-1-Z GE4-H36 GE4-LF7/1 E89-E4F E4F-F40 F40-FB1 F40-H36/1 F40-H36/3 GE4-LH2 RC-LY/460-DX1 Level Auxiliary Relay FB1 CB-F-3A-A FC-E4F-FU Fuses E4F CB-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A CS-ZS-V145 Valve Position Switch LH2 C-F-1-Z

.1. Electrical power and air are not required for support since the valve fails closed. 2. During normal operation, the valve is in its hot shutdown position. To prevent spurious operation, this equipment is permanently disabled (circuit breaker tripped). 
3. These valves are fail open diaphragm valves. See Section 3.5.3.1.c for analysis.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-2 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 RC-FV-2881 RC-20845 B 310581 C-F-3-Z X X X X U04 RC-E88/1-72 125 V Circuit Breaker E88 CB-F-1B-A RC-V323 Note 1 Reactor Head

Vent. Sol. Valve RC-CS-2881 Control Switch with Indication F31 CB-F-3A-A CBA-FN-32

CBA-FN-33

RC-FV-2881 Solenoid Valve U04 C-F-3-Z 310882 E88/1g E88/1d E88/1e E88/1f RC-GNO-R7 Auxiliary Relay GN0 CB-F-1B-A E88-E4C/4 E4C-GN0/5 F31-GN0 F31-G5Y F31-H41/1 H41/UO4 RC-ZS-FV-2881 Valve Position Switch UO4 C-F-3-Z RC-E4C-FU Fuses E4C CB-F-1B-A RC-SS-2881 Selector Switch G5Y DG-F-2B-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A H39-U04 F26-H39 6 RC-V-323 Reactor Head Venting Valve RC-20845 B 310581 C-F-3-Z X X X - VB2 RC-BV9-52-1 460 V AC Circuit Breaker BV9 CB-F-1B-A CBA-FN-32 CBA-FN-33 RC-FV-2881 RC-BV9-52-2 460 V AC Circuit Breaker BV9 CB-F-1B-A 310882 BV9a BV9c BV9d RC-CS-2885 Control Switch with Indication F31 CB-F-3A-A RC-BV9-42-1(0) Motor Starter (Open) BV9 CB-F-1B-A BV9-F31 BV9-H41 BV9-H15 F31-H41/2 H41-VB2 H41-VB2/1 H15-VB2 RC-BV9-42-1(C) Motor Starter (Close) BV9 CB-F-1B-A RC-BV9-42-2 Motor Starter BV9 CB-F-1B-A RC-BV9-49-1 Overload Relay BV9 CB-F-1B-A RC-BV9-49-2 Overload Relay BV9 CB-F-1B-A RC-ZS-V323 Valve Position Switch and Valve Open/Close

Torque Switches VB2 C-F-3-Z EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A RC-BV9-FU Fuse BV9 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-3 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 RC-V-22 RHR Inlet Isolation Valve RC-20841 B 310582 C-F-1-Z D D X - V27 RC-B54-52-1 460 V AC Circuit Breaker B54 CB-F-1B-A RC-V-23 Note 2 RC-B54-52-2 460 V AC Circuit Breaker B54 CB-F-1B-A 310882 B54a B54c B54d RC-CS-7302-1 Control Switch With Indication F20 CB-F-3A-A RC-CS-7302-2 Control Switch With Indication G2J CB-F-1B-A RC-SS-7302 Selector Switch G2J CB-F-1B-A RC-B54-42-1(0) Motor Starter (Open) B54 CB-F-1B-A B54-G2J B54-G2J/1 B54-H24 B54-H39 B54-V53 F20-G2J H24-V27 H39-V27 F20-FF9/2 RC-B54-42-1(C) Motor Starter (Close) B54 CB-F-1B-A RC-B54-42-2 Motor Starter B54 CB-F-1B-A RC-B54-49-1 Overload Relay B54 CB-F-1B-A RC-B54-49-2 Overload Relay B54 CB-F-1B-A RC-FF9-K-734B SSPC Output Relay FF9 CB-F-3A-A RC-ZS-7302B Valve Position Switch and Valve Open/Close

Torque Switches V27 C-F-1-Z RH-ZS-2465B RH-V35 Position Switch V53 RHR-F-4B-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-ZL-7302-1 Pilot Light G2J CB-F-1B-A RC-ZL-7302-2 Pilot Light F20 CB-F-3A-A RC-B54-FU Fuse B54 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-4 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 8 RC-V-23 RHR Inlet Isolation Valve RC-20841 A 310576 C-F-1-Z D D X - V25 RC-B53-52-1 460 V AC Circuit Breaker B53 CB-F-1A-A RC-V-22 Note 2 RC-B53-52-2 460 V AC Circuit Breaker B53 CB-F-1A-A 310882 B53a B53c B53d RC-CS-7303-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-7303-2 Control Switch with Indication G2G CB-F-1A-A B53-G2G B53-G2G/1 B53-H19 B53-H36 B53-V53 F20-G2G F20-FF8/2 H19-V25 H36-V25/2 RC-SS-7303 Selector Switch G2G CB-F-1A-A RC-ZL-7303-1 Pilot Light G2G CB-F-1A-A RC-ZL-7303-2 Pilot Light F20 CB-F-3A-A RC-B53-42-1(O) Motor Starter (Open) B53 CB-F-1A-A RC-B53-42-1(C) Motor Starter (Close) B53 CB-F-1A-A RC-B53-42-2 Motor Starter B53 CB-F-1A-A RC-B53-49-1 Overload Relay B53 CB-F-1A-A RC-B53-49-2 Overload Relay B53 CB-F-1A-A RC-FF8-K-734A SSPS Output Relay FF8 CB-F-3A-A RC-ZS-V23 Valve Position Switch and Valve Open/Close

Torque Switches V25 C-F-1-Z RH-ZS-2465A RH-V35 Position Switch V53 RHR-F-4B-Z EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-B53-FU Fuse B54 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-5 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 RC-V-87 RHR Inlet Isolation Valve RC-20844 B 310582 C-F-1-Z D D X - V26 RC-B61-52-1 460 V AC Circuit Breaker B61 CB-F-1B-A RC-V-88 Note 2 RC-B61-52-2 460 V AC Circuit Breaker B61 CB-F-1B-A 310882 B61a B61c B61d RC-CS-7310-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-7310-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7310 Selector Switch G2J CB-F-1B-A B61-G2J B61-G2J/1 B61-H24 B61-H39 B61-V54 F20-G2J/1 F20-FF9/1 H24-V26 H39-V26/2 RC-ZL-7310-1 Pilot Light G2J CB-F-1B-A RC-ZL-7310-2 Pilot Light F20 CB-F-3A-A RC-B61-42-1(0) Motor Starter (Open) B61 CB-F-1B-A RC-B61-42-1(C) Motor Starter (Close) B61 CB-F-1B-A RC-B61-42-2 Motor Starter B61 CB-F-1B-A RC-B61-49-1 Overload Relay B61 CB-F-1B-A RC-B61-49-2 Overload Relay B61 CB-F-1B-A RC-FF9-K-734B SSPS Output Relay FF9 CB-F-3A-A RC-ZS-V87 Valve Position Switch and Valve Open/Close

Torque Switches V26 C-F-1-Z RH-ZS-2466B RH-E-9B to SI Pump Isolation Valve

RH-V36 Position

Switch V54 RHR-F-2A-Z EDE-MM-100 Electrical Penetration H24 C-F-2-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-2-Z, ET-F-1C-A RC-B61-FU Fuse B61 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-6 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 10 RC-V-88 RHR Inlet Isolation Valve RC-20844 A 310577 C-F-1-Z D D X - V28 RC-B62-52-1 460 V AC Circuit Breaker B62 CB-F-1A-A RC-V-87 Note 2 RC-B62-52-2 460 V AC Circuit Breaker B62 CB-F-1A-A 310882 B62a B62c B62d RC-CS-7311-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-7311-2 Control Switch with Indication G2G CB-F-1A-A B62-G2G B62-G2G/1 B62-H19 B62-H36 B62-V54 F20-G2G/1 F20-FF8/3 H19-V28 H36-V28 RC-SS-7311 Selector Switch G2G CB-F-1A-A RC-ZL-7311-1 Pilot Light G2G CB-F-1A-A RC-ZL-7311-2 Pilot Light F20 CB-F-3A-A RC-B62-42-1(O) Motor Starter (Open) B62 CB-F-1A-A RC-B62-42-1(C) Motor Starter (Close) B62 CB-F-1A-A RC-B62-42-2 Motor Starter B62 CB-F-1A-A RC-B62-49-1 Overload Relay B62 CB-F-1A-A RC-B62-49-2 Overload Relay B62 CB-F-1A-A RC-FF9-K-734A SSPS Output Relay FF8 CB-F-3A-A RC-ZS-7311A Valve Position Switch and Valve Open/Close

Torque Switches V28 C-F-1-Z RH-ZS-2466A RH-E-9B to SI Pump Isolation Valve

RH-V36 Position

Switch V54 RHR-F-2A-Z EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-B62-FU Fuse B62 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-7 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 RC-PCV-456A RC-20846 A 310581 C-F-3-Z X X X X LD3 RC-E87/19-72 125 V DC Circuit Breaker E87 CB-F-1A-A RC-V122 Note 1 RC-E-10 Pressurizer

Relief Control

Valve RC-CS-456A-1 Control Switch with Indication F31 CB-F-3A-A 310882 E87/19a E87/19c E87/19d CBA-FN-19

CBA-FN-20 DAH-FN-25A

DAH-FN-26A RC-CS-456A-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-456A-1 Selector Switch G81 CB-F-1A-A RC-PCV-456A-20 Solenoid Operated Valve LD3 C-F-3-Z RC-ZS-PCV-456A Valve Position Switch LD3 C-F-3-Z F38-FB1/2 F38-G81/1 G81-H35 H35-X56/2 LD3-X56 E87-E4A/4 E4A-J3M G5X-J3M H18-J3M H18-LD3 G81-J3M F38-G5X RC-PY-405CX Auxiliary Relay FB1 CB-F-3A-A RC-PY-455EX Auxiliary Relay FB1 CB-F-3A-A RC-PY-458BX Auxiliary Relay FB1 CB-F-3A-A RC-TY-413KX Auxiliary Relay FB1 CB-F-3A-A RC-SS-456A-2 Selector Switch G5X DG-F-2A-A RC-J3M-42 125 V DC Contactor J3M DG-F-2A-A RC-E4A-FU Fuses E4A CB-F-1A-A EDE-TBX-X56 Terminal Box X56 C-F-3-Z EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-8 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 12 RC-PCV-456B RC-20846 B 310581 C-F-3-Z X X X X LD4 RC-E88/19-72 125 V DC Circuit Breaker E88 CB-F-1B-A RC-V124 Note 1 RC-E-10 Pressurizer

Relief Control

Valve RC-CS-456B-1 Control Switch with Indication F31 CB-F-3A-A 310882 E88/19a E88/19c E88/19d RC-CS-456B-2 Control Switch with Indication GZ0 CB-F-1B-A CBA-FN-32

CBA-FN-33 DAH-FN-25B

DAH-FN-26B RC-SS-456B-1 Selector Switch GZ0 CB-F-1B-A RC-PCV-456B-20 Solenoid Operated Valve LD4 C-F-3-Z RC-ZS-PCV-456B Valve Position Switch LD4 C-F-3-Z RC-FT0-KA7 Isolation Relay FT0 CB-F-3A-A F31-FT0/2 F31-GZ0/2 GZ0-H39 H39-X35 LD4-X35 GZ0-J3P E88-E4C/7 E4C-J3P G5Y-J3P H24-J3P H24-LD4 E4C-GZ0/2 F31-G5Y/1 RC-SS-456B-1 Selector Switch G5Y DG-F-2B-A RC-J3P-42 125 V DC Contactor J3P DG-F-2B-A RC-E4C-FU Fuses E4C CB-F-1B-A EDE-TBX-X35 Terminal Box X35 C-F-3-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A 13 RC-V-122 RC-20846 A 310581 C-F-3-Z X X X - V01 RC-B97-52-1 460 V AC Circuit Breaker B97 CB-F-1A-A RC-PCV-456A RC-E-10 Pressurizer

Relief Isolation

Valve RC-B97-52-2 460 V AC Circuit Breaker B97 CB-F-1A-A 310882 B97a B97c B97e B97d EDE-MCC-521 CBA-FN-19

CBA-FN-20 RC-CS-7313-1 Control Switch with Indication F31 CB-F-3A-A RC-CS-7313-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-7313 Selector Switch G81 CB-F-1A-A B97-H18 B97-H35 ED1-F38 H18-V01 H35-X56 V01-X56 F38-G81/2 F38-G81/3 B97-G81 B97-G81/1 RC-B97-FU Fuse B97 CB-F-1A-A RC-B97-42-1(O) Motor Starter (Open) B97 CB-F-1A-A RC-B97-42-1(C) Motor Starter (Close) B97 CB-F-1A-A RC-B97-42-2 Motor Starter B97 CB-F-1A-A RC-B97-49-1 Overload Relay B97 CB-F-1A-A RC-B97-49-2 Overload Relay B97 CB-F-1A-A RC-ZS-V122 Valve Position Switch and Valve Open/Close

Torque Switches V01 C-F-3-Z RC-ED1-R1 Auxiliary Relay ED1 CB-F-1A-A EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A EDE-TBX-X56 Terminal Box X56 C-F-3-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-9 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 14 RC-V-124 RC-20846 B 310581 C-F-3-Z X X X - V02 RC-B98-52-1 460 V AC Circuit Breaker B98 CB-F-1B-A RC-PCV-456B RC-E-10 Pressurizer

Relief Control

Valve RC-B98-52-2 460 V AC Circuit Breaker B98 CB-F-1B-A RC-CS-7314-1 Control Switch with Indication F31 CB-F-3A-A 310882 B98a B98c B98e B98d EDE-MCC-621 CBA-FN-32

CBA-FN-33 RC-CS-7314-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-7314 Selector Switch GZ0 CB-F-1B-A RC-B98-42-1(O) Motor Starter (Open) B98 CB-F-1B-A B98-H15 B98-H41 F31-FT0/1 H15-V02 H41-X35 V02-X35 B98-GZ0 B98-GZ0/1 F31-GZ0/5 F31-GZ0/6 B98/GZ0/2 RC-B98-42-1(C) Motor Starter (Close) B98 CB-F-1B-A C-B98-42-2 Motor Starter B98 CB-F-1B-A RC-B98-49-1 Overload Relay B98 CB-F-1B-A RC-B98-49-2 Overload Relay B98 CB-F-1B-A RC-ZS-V124 Valve Position Switch and Valve Open/Close

Torque Switches V02 C-F-3-Z RC-FT0-KA6 Isolation Relay FT0 CB-F-3A-A EDE-MM-91 Electrical Penetration H15 C-F-2-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A EDE-TBX-X35 Terminal Box X35 C-F-3-Z RC-B98-FU Fuses B98 CB-F-1B-A 15 CS-V-10 Reactor Coolant Pump Seal Leakoff

Isolation Valve CS-20726 A 310576 C-F-1-Z X X X X LA6 Note 3 16 CS-V-28 Reactor Coolant Pump Seal Leakoff

Isolation Valve CS-20726 A 310576 C-F-1-Z X X X X LA7 Note 3 17 CS-V-44 Reactor Coolant Pump Seal Leakoff

Isolation Valve CS-20726 A 310583 C-F-1-Z X X X X LA8 Note 3 18 CS-V-59 Reactor Coolant Pump Seal Leakoff

Isolation Valve CS-20726 A 310577 C-F-1-Z X X X X LA9 Note 3

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50. Appendix R P & I Diagrams (Typical) Rev 5 Appendix I Page I-1 P & I DIAGRAMS (TYPICAL) This section originally contained photographs of the marked P & I Diagrams for the decay heat removal safe shutdown function. These drawings were typical of the P & I Diagrams which were marked for each safe shutdown function and not all inclusive, thus they have been removed from this appendicies. The typical diagrams included in this section were only to show the methodology used for the original report preparation and were not in tended to be updated for report revisions. The latest design documents, not these typical drawings, should be used to evaluate the Safe Shutdown Capability. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50. Appendix R Schematic Diagrams & Cable Schematics (Typical) Rev 5 Appendix II Page II-1 Schematic Diagrams & Cable Schematics (Typical) This section originally contained drawings that were typical of those which were marked for each safe shutdown function. The typical drawings in cluded in this section were only to show the methodology used for the original report preparation. These typical drawings were not intended to be updated for report revision. The original drawings were provided to show marked-up electrical schematic diagrams, cable schematics, and cable tables for the Train A decay heat removal safe shutdown function. The drawings were marked by shading and by cross-hatching. The equipment and cables which were shaded were isolated by a "Local Remote" selector switch or other isolation device and were not considered for further review. The equipment and cables which have been cross-hatched were analyzed, and it was determined that there was no effect on safe shutdown capability. These equipment and cables were not considered for further review. The latest design documents, not these typical drawings, should be used to evaluate the Safe Shutdown Capability. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Equipment Lists (Tables) Rev. 10 Appendix III Page III-1 Equipment Lists (Tables) This section contains the following tables which list all equipment required for performance of the safe shutdown function. Main Control Room Function Table Number Decay Heat Removal MCR 3.1.3.1 Reactor Coolant Inventory and Pressure Control MCR 3.1.3.2 Reactivity Control MCR 3.1.3.3 Process Monitoring MCR 3.1.3.4 Safeguard Actuation System MCR 3.1.3.5 Cold Shutdown MCR 3.1.3.6 Service Water MCR 3.1.3.7 Primary Component Cooling Water MCR 3.1.3.8 Containment Building Air Handling MCR 3.1.3.9 Control Building Air Handling MCR 3.1.3.10 Diesel Generator Building Air Handling MCR 3.1.3.11 Containment Enclosure Air Handling MCR 3.1.3.12 Emergency Feedwater Pumphouse Air Handling MCR 3.1.3.13 Primary Auxiliary Building Air Handling MCR 3.1.3.14 Service Water Air Handling MCR 3.1.3.15 Service/Instrument Air MCR 3.1.3.16 Electrical Distribution Emergency MCR 3.1.3.17 Diesel Generators MCR 3.1.3.18

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Equipment Lists (Tables) Rev. 10 Appendix III Page III-2 Alternative Safe Shutdown Function Table Number Decay Heat Removal RSS 3.1.3.1 Reactor Coolant Inventory and Pressure Control RSS 3.1.3.2 Reactivity Control RSS 3.1.3.3 Process Monitoring RSS 3.1.3.4 Safeguards Actuation RSS 3.1.3.5 Cold Shutdown RSS 3.1.3.6 Service Water RSS 3.1.3.7 Primary Component Cooling Water RSS 3.1.3.8 Deleted RSS 3.1.3.9 Control Building Air Handling RSS 3.1.3.10 Diesel Generator Building Air Handling RSS 3.1.3.11 Containment Enclosure Air Handling RSS 3.1.3.12 Emergency Feedwater Pumphouse Air Handling RSS 3.1.3.13 Primary Auxiliary Building Air Handling RSS 3.1.3.14 Service Water Air Handling RSS 3.1.3.15 Deleted RSS 3.1.3.16 Electrical Distribution Emergency RSS 3.1.3.17 Diesel Generators RSS 3.1.3.18 Communication RSS 3.1.3.19 Emergency Feedwater Pumphouse Building 3.2.3 High-Low Pressure Boundaries 3.3.2 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -1 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CO-TK-25 Condensate Storage Tank CO-20426 A/B 310248 CST-F-1-0 X X - - - - - - - - - - - - Note 1 2 FW-P-113 Start-Up Feedwater Pump CO-20426 A 310326 TB-F-1A-Z X X X - N12 FW-A93-52 4160 V AC Circuit Breaker A93 CB-F-1A-1 A47-A93 A47-A93/1 A47-A93/2 A47-A93/3 A47-N12 A47-P82 A93-F60/1 A93-F60/2 A93-F60/3 A93-F50/4 A93-ED7 A93-G8L A93-HR2 G8L-P2V (Non-CASP) 310844 A93a A93g A93b A93h A93c A93d A47a A47g EDE-SWG-5 CBA-FN-19 CBA-FN-20 FW-P-37B FW-A93-FU Fuses A93 CB-F-1A-A FW-CS-4268-1 Control Switch with Indication F60 CB-F-3A-A FW-SS-4268 Selector Switch A47 NES-F-1A-Z FW-A93-CS Test Control Switch A93 CB-F-1A-A FW-A93-G, R, W Indicating Lights A93 CB-F-1A-A EDE-A53-94-2 Bus Undervoltage A53 CB-F-1A-A FW-A93-R1 Auxiliary Relay A93 CB-F-1A-A FW-PSLH-PS5 Lube Oil Pressure Switch P82 TB-F-1A-Z FW-A93-PS5X Pressure Switch Auxiliary Relay A93 CB-F-1A-A FW-A93-52S Mechanically Operated Contact A93 CB-F-1A-A FW-A93-52H Truck-Operated Contact A93 CB-F-1A-A FW-A93-62 PS5 Starting Blocking Time Delay Relay A93 CB-F-1A-A FW-ED7-2 Prelube Pump Starting Auxiliary Time Delay Relay ED7 TB-F-2-Z FW-A93-R2 Auxiliary Relay A93 CB-F-1A-A FW-A93-86 Lockout Relay A93 CB-F-1A-A FW-A93-TD2 Lockout Relay Test Device A93 CB-F-1A-A FW-A93-CT Current Transformers 300/5A A93 CB-F-1A-A FW-A93-TD1 CT Test Device A93 CB-F-1A-A FW-A93-50/51 Inst/Time Overcurrent Relays øA, øC A93 CB-F-1A-A FW-A93-AM Ammeter A93 CB-F-1A-A FW-A93-AS Ammeter Switch A93 CB-F-1A-A FW-A93-ATR Transducer A93 CB-F-1A-A FW-AM-4268-1 Ammeter F60 CB-F-3A-A

. NOTES 1. The equipment is mechanical with no electrical requirement.
2. Air is not needed to position or to reposition the valve for safe shutdown.
3. During normal operation, this equipment is in its safe shutdown position (locked closed) with its circuit breaker administratively controlled locked open (off) to prevent its spurious operation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -2 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 FW-P-113 Start-Up Feedwater Pump FW-A47-52 4160 V AC Circuit Breaker A47 NES-F-1A-Z (Continued) FW-A93-S1GS Ground Sensor Relay A93 CB-F-1A-A FW-PSL-4233-2 Pressure Switch Low Suction P2V TB-F-1A-Z FW-CS-4233 Suction Pressure Bypass Switch G8L TB-F-1A-Z FW-HR2-RMO EPS Manual Override Relay (K27) HR2 CB-F-1A-A 3 FW-P-161 Start-Up Feedwater Pump FW-P-113 Prelube Pump CO-20426 A 310326 TB-F-1A-Z X X X - NU0 FW-CN1-52 460 V AC Circuit Breaker CN1 TB-F-2-Z CN1-NUO CN1-F60 CN1-P81 A47-F60/4 EA1-F60 F60-FB7/5 310884 CN1a CN1c EDE-MCC-523 None FW-CN1-FU Fuse CN1 TB-F-2-Z FW-CS-4268 Control Switch with Indication F60 CB-F-3A-A FW-SS-4268 Selector Switch A47 NES-F-1A-Z FW-CS-4268-1 Control Switch with Indication F60 CB-F-3A-A FW-CS-4278 Control Switch F60 CB-F-3A-A FW-ED7-2 Pump Starting Time Delay Relay ED7 TB-F-2-Z FW-PSLH-PS4 Lube Oil Pressure Switch P81 TB-F-1A-Z FW-CN1-42 Motor Starter CN1 TB-F-2-Z FW-CN1-49 Overload Relays CN1 TB-F-2-Z FW-FB7-K620A SSPS Output Relay FB7 CB-F-3A-A FW-ED7-3 Time Delay Relay ED7 TB-F-2-2 FW-J8K-K5R, S, T GE MK Vle TMR Relay J8K TB-F-2-Z EA1-J9M/1 J8M-J9M FW-J9K-K5R, S, T GE MK Vle TMR Relay J9K TB-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -3 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 FW-V-156 Start-Up Feed Pump to EFW Header Valve FW-20688 A 310589 MS-F-1B-Z X X X - V3L FW-B4S-52 460 V AC Circuit Breaker B4S CB-F-1A-A B4S-V3L B4S-V3L/1 B4S-F60 B4S-F60/1 310844 B4Sa B4Sc CBA-FN-19 CBA-FN-20 EDE-MCC-531 None FW-B4S-FU Fuse B4S CB-F-1A-A FW-CS-4261 Control Switch with Indication F60 CB-F-3A-A FW-B4S-42/0,C Motor Starters B4S CB-F-1A-A FW-B4S-49 Overload Relays B4S CB-F-1A-A FW-ZS-V156 Valve Position and Open/Close Torque Switches V3L MS-F-1B-Z 4A FW-V-163 Start-Up Feed Pump Bypass to EFW Pump Valve FW-20687 A 310326 TB-F-1A-Z X X X - V3M FW-C2R-52 460 V AC Circuit Breaker C2R TB-F-2-Z C2R-V3M C2R-V3M/1 C2R-F60 310884 CN1a CN1c EDE-MCC-523 None FW-C2R-FU Fuse C2R TB-F-2-Z FW-CS-4262 Control Switch with Indication F60 CB-F-3A-A FW-C2R-42/0,C Motor Starter C2R TB-F-2-Z FW-C2R-49 Overload Relays C2R TB-F-2-Z FW-ZS-V163 Valve Position and Open/Close Torque Switches V3M TB-F-1A-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -4 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 FW-P-37B Emergency Feed Pump FW-20688 B 310708 EFP-F-1-A X X X - N14 FW-A80-52 4160 V AC Circuit Breaker A80 CB-F-1B-A A80-N14 A80-F66/1 A80-F66/2 A80-HR4 FBO-HR4 FBO-FT0/1 310844 A80a A80h A80b A80c A80d CBA-FN-32 CBA-FN-33 EPA-FN-47B EDE-SWG-6 FW-P-113 FW-A80-FU Fuses A80 CB-F-1B-A FW-A80-R Auxiliary Relay A80 CB-F-1B-A FW-CS-4255-2 Control Switch A80 CB-F-1B-A FW-SS-4255 Selector Switch A80 CB-F-1B-A EDE-A73-94-1B Bus Under Voltage Relay A73 CB-F-1B-A FW-A80-86 Lockout Relay A80 CB-F-1B-A FW-A80-52H Truck-Operated Contact A80 CB-F-1B-A FW-A80-50/51 Instrument/Time Overcurrent Relays øA, øC A80 CB-F-1B-A FW-A80-AM Ammeter A80 CB-F-1B-A FW-A80-AS Ammeter Switch A80 CB-F-1B-A FW-A80-CT Current Transformers (200/5) A80 CB-F-1B-A FW-A80-TD1 CT Test Device A80 CB-F-1B-A FW-A80-ATR Transducer A80 CB-F-1B-A FW-A80-TD2 Lockout Relay Test Device A80 CB-F-1B-A FW-A80-G,R,W,A Indicating Lights A80 CB-F-1B-A FW-A80-52Z Time Delay Relay A80 CB-F-1B-A FW-A80-51GS Ground Sensor Relay A80 CB-F-1B-A FW-CS-4255-1 Control Switch F60 CB-F-3A-A FW-EPS-SR6 Emergency Power Sequencer HR0 CB-F-1B-A FW-EPS-PR1,RMO Emergency Power Sequencer HR4 CB-F-1B-A FW-FB0-K615B,K640B Auxiliary Relays FB0 CB-F-3A-A EDE-FT0-KA24 Isolation Relay FT0 CB-F-3A-A 5A FW-V347 Emergency Feedwater Recirculating Valve FW-20688 B 310708 EFP-F-1-A X X X - V4P FW-C3T-52 460 V AC Circuit Breaker C3T CB-F-1B-A C3T-V4P C3T-V4P/1 C3T-G2J F66-G2J/6 310884 CN1a CN1c EDE-MCC-523 None FW-C3T-FU Fuses C3T CB-F-1B-A FW-CS-4369-2 Control Switch with Indication G2J CB-F-1B-A MS-SS-3064 Selector Switch G2J CB-F-1B-A FW-C3T-42/0,C Motor Starters C3T CB-F-1B-A FW-C3T-49 Overload Relays C3T CB-F-1B-A FW-ZS-V347 Valve Position Switch V4P EFP-F-1-A FW-CS-4369-1 Control Switch with Indication F60 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -5 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 FW-FV-4214A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2E FW-B3V-52 460 V AC Circuit Breaker B3V CB-F-1A-A B3V-V2E B3V-V2E/1 E3C-G2G G2G-V2E B3V-G5X B3V-G5X/1 E3C-FN6 F51-FN6 FN6-G5X FN6-G5X/1 310844 B3Va B3Vd B3Ve CBA-FN-19 CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-FV-4214-B FW-B3V-FU Fuse B3V CB-F-1A-A FW-CS-4214-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4214-A Selector Switch G2G CB-F-1A-A FW-SS-4214-A1 Selector Switch G5X DG-F-2A-A FW-FN6-MSO-1 Auxiliary Relay FN6 CB-F-2B-A FW-B3V-42/0,C Motor Starters B3V CB-F-1A-A FW-B3V-49 Overload Relays B3V CB-F-1A-A FW-ZS-4214-A Valve Position Switch V2E EFP-F-1-A FW-FN6-4214AX Auxiliary Relay FN6 CB-F-2B-A FW-CS-4214-A1 Control Switch with Indication F51 CB-F-3A-A E3C-F51 F51-G2G FW-E3C-R1,R2,R3,R4 Auxiliary Relays E3C CB-F-1A-A E3C-FK0 E3C-FN6/4 FK0-FN6 FK0-FN6/1 E3E/1a, 1e E3E/1c FW-E3P-62-1 Timing Relay E3P CB-F-1A-A FW-E3P-62-2 Timing Relay E3P CB-F-1A-A FW-E3P-62-3 Timing Relay E3P CB-F-1A-A FW-E3P-62-4 Timing Relay E3P CB-F-1A-A FW-FN6-R1A Auxiliary Relay FN6 CB-F-2B-A MM-CP-297A "A" Train BOP -PCC FKO CB-F-3A-A E3C-F56 F56-FK0 F86-FK0 FK0-GL3 310952 FK0a FW-FR-4214 Flow Recorder F86 CB-F-3A-A FW-FT-4214-2 Flow Transmitter GL3 EFP-F-1A-A FW-FI-4214-2 Flow Indicators F56 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -6 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 FW-FV-4214B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2J FW-B3Z-52 460 V AC Circuit Breaker B3Z CB-F-1B-A B3Z-V2J B3Z-V2J/1 E3D-G2J G2J-V2J B3Z-G2J B3Z-G5Y B3Z-G5Y/1 E3D-FN7 F51-FN7 FN7-G5Y FN7-G5Y/1 310844 B3Za B3Zd B3Ze CBA-FN-32 CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-FV-4214-A FW-B3Z-FU Fuse B3Z CB-F-1B-A FW-CS-4214-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4214-B Selector Switch G2J CB-F-1B-A FW-SS-4214-B1 Selector Switch G5Y DG-F-2B-A FW-FN7-MSO-1 Auxiliary Relay FN7 CB-F-2C-A FW-B3Z-42/0,C Motor Starters B3Z CB-F-1B-A FW-B3Z-49 Overload Relays B3Z CB-F-1B-A FW-ZS-4214-B Valve Position Switch V2J EFP-F-1-A FW-FN7-4214BX Auxiliary Relay FN7 CB-F-2C-A FW-CS-4214-B1 Control Switch with Indication F51 CB-F-3A-A E3D-F51 F51-G2J FW-E3D-R1,R2,R3,R4 Auxiliary Relays E3D CB-F-1B-A E3D-FL2 E3D-FN7/4 FL2-FN7 FL2-FN7/1 E3F/1a, 1e E3F/1c FW-E3Q-62-1 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-2 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-3 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-4 Timing Relay E3Q CB-F-1B-A FW-FN7-R1B Auxiliary Relay FN7 CB-F-2C-A FW-FT-4214-4 Flow Transmitter GL4 EFP-F-1A-A E3D-F51/4 310952 FL2a MM-CP-297B "B" Train BOP -PCC FL2 CB-F-3A-A FL2-GL4 8 FW-FV-4224A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2F FW-B3W-52 460 V AC Circuit Breaker B3W CB-F-1A-A B3W-V2F B3W-V2F/1 E3C-G2G/1 G2G-V2F B3W-G5X B3W-G5X/1 E3C-FN6/1 F51-FN6/1 FN6-G5X/2 FN6-G5X/3 310844 B3Wa B3Wd B3We CBA-FN-19 CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-FV-4224-B FW-B3W-FU Fuse B3W CB-F-1A-A FW-CS-4224-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4224-A Selector Switch G2G CB-F-1A-A FW-SS-4224-A1 Selector Switch G5X DG-F-2A-A FW-FN6-MSO-2 Auxiliary Relay FN6 CB-F-2B-A FW-B3W-42/0,C Motor Starters B3W CB-F-1A-A FW-B3W-49 Overload Relays B3W CB-F-1A-A FW-ZS-4224-A Valve Position Switch V2F EFP-F-1-A FW-FN6-4224AX Auxiliary Relay FN6 CB-F-2B-A FW-CS-4224-A1 Control Switch with Indication F51 CB-F-3A-A E3C-F51/1 F51-G2G/1 FW-E3C-R1,R2,R3,R4 Auxiliary Relays E3C CB-F-1A-A E3C-FK0 E3C-F56 E3C-FN6/4 FK0-FN6 FK0-FN6/1 E3E/1a, 1e E3E/1c FW-E3P-62-1 Timing Relay E3P CB-F-1A-A FW-E3P-62-2 Timing Relay E3P CB-F-1A-A FW-E3P-62-3 Timing Relay E3P CB-F-1A-A FW-E3P-62-4 Timing Relay E3P CB-F-1A-A FW-FN6-R2A Auxiliary Relay FN6 CB-F-2B-A FW-FT-4224-4 Flow Transmitter GL3 EFP-F-1A-A 310952 FK0a MM-CP-297A "A" Train BOP -PCC FK0 CB-F-3A-A FK0-GL3 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -7 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 FW-FV-4224B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2K FW-B4A-52 460 V AC Circuit Breaker B4A CB-F-1B-A B4A-V2K B4A-V2K/1 E3D-G2J/1 G2G-V2K B4A-G2J B4A-G5Y B4A-G5Y/1 E3D-FN7/1 F51-FN7/1 FN7-G5Y/2 FN7-G5Y/3 310844 B4Aa B4Ad B4Ae CBA-FN-32 CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-FV-4224-A FW-B4A-FU Fuse B4A CB-F-1B-A FW-CS-4224-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4224-B Selector Switch G2J CB-F-1B-A FW-SS-4224-B1 Selector Switch G5Y DG-F-2B-A FW-FN7-MSO-2 Auxiliary Relay FN7 CB-F-2C-A FW-B4A-42/0,C Motor Starters B4A CB-F-1B-A FW-B4A-49 Overload Relays B4A CB-F-1B-A FW-ZS-4224-B Valve Position Switch V2K EFP-F-1-A FW-FN7-4224BX Auxiliary Relay FN7 CB-F-2C-A FW-CS-4224-B1 Control Switch with Indication F51 CB-F-3A-A E3D-F51/1 F51-G2J/1 FW-E3D-R1,R2,R3,R4 Auxiliary Relays E3Q CB-F-1B-A E3D-FL2 E3D-F51/4 E3D-FN7/4 FL2-FN7 FL2-FN7/1 E3F/1a, 1e E3F/1c FW-E3Q-62-1 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-2 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-3 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-4 Timing Relay E3Q CB-F-1B-A FW-FN7-R2B Auxiliary Relay FN7 CB-F-2C-A MM-CP-297B "B" Train BOP -PCC FL2 CB-F-3A-A 310952 FL2a FW-FR-4224 Flow Recorder F86 CB-F-3A-A F56-FL2 F88-FL2 FL2-GL4 FW-FT-4224-2 Flow Transmitter GL4 EFP-F-1A-A FW-FI-4224-2 Flow Indicator F56 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -8 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 10 FW-FV-4234A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2G FW-B3X-52 460 V AC Circuit Breaker B3X CB-F-1A-A B3X-V2G B3X-V2G/1 G2G-V2G E3C-G2G/2 B3X-G5X B3X-G5X/1 E3C-FN6/2 F51-FN6/2 FN6-G5X/4 FN6-G5X/5 310844 B3Xa B3Xd B3Xe CBA-FN-19 CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-FV-4234-B FW-B3X-FU Fuse B3X CB-F-1A-A FW-CS-4234-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4214-A Selector Switch G2G CB-F-1A-A FW-SS-4214-A1 Selector Switch G5X DG-F-2A-A FW-FN6-MSO-3 Auxiliary Relay FN6 CB-F-2B-A FW-B3X-42/0,C Motor Starters B3X CB-F-1A-A FW-B3X-49 Overload Relays B3X CB-F-1A-A FW-ZS-4234-A Valve Position Switch V2G EFP-F-1-A FW-FN6-4234AX Auxiliary Relay FN6 CB-F-2B-A FW-CS-4234-A1 Control Switch with Indication F51 CB-F-3A-A E3C-F51/2 F51-G2G/2 FW-E3C-R1,R2,R3,R4 Auxiliary Relays E3C CB-F-1A-A E3C-FK0 E3C-FN6/4 FK0-FN6 FK0-FN6/1 E3E/1a, 1e E3E/1c FW-E3P-62-1 Timing Relay E3P CB-F-1A-A FW-E3P-62-2 Timing Relay E3P CB-F-1A-A FW-E3P-62-3 Timing Relay E3P CB-F-1A-A FW-E3P-62-4 Timing Relay E3P CB-F-1A-A FW-FN6-R3A Auxiliary Relay FN6 CB-F-2B-A MM-CP-297A "A" Train BOP-PCC FK0 CB-F-3A-A E3C-F56 FK0-GL3 F56-FK0 F86-KF0 310952 FK0a FW-FR-4214 Flow Recorder F86 CB-F-3A-A FW-FT-4234-2 Flow Transmitter GL3 EFP-F-1A-A FW-FI-4234-2 Flow Indicator F56 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -9 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 FW-FV-4234B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2L FW-B4B-52 460 V AC Circuit Breaker B4B CB-F-1B-A B4B-V2L B4B-V2L/1 E3D-G2J/2 G2J-V2L B4B-G2J B4B-G5Y B4B-G5Y/1 E3D-FN7/2 F51-FN7/2 FN7-G5Y/4 FN7-G5Y/5 310844 B4Ba B4Bd B4Be CBA-FN-32 CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-FV-4234-A FW-B4B-FU Fuse B4B CB-F-1B-A FW-CS-4234-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4214-B Selector Switch G2J CB-F-1B-A FW-SS-4214-B1 Selector Switch G5Y DG-F-2B-A FW-FN7-MSO-3 Auxiliary Relay FN7 CB-F-2C-A FW-B4B-42/0,C Motor Starters B4B CB-F-1B-A FW-B4B-49 Overload Relays B4B CB-F-1B-A FW-ZS-4234-B Valve Position Switch V2L EFP-F-1-A FW-FN7-4234BX Auxiliary Relay FN7 CB-F-2C-A FW-CS-4234-B1 Control Switch with Indication F51 CB-F-3A-A E3D-F51/2 F51-G2J/2 E3F/1a, 1e E3F/1c FW-E3D-R1,R2,R3,R4 Auxiliary Relays E3D CB-F-1B-A E3D-FL2 E3D-F51/4 E3D-FN7/4 FL2-FN7 FL2-FN7/1 FW-E3Q-62-1 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-2 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-3 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-4 Timing Relay E3Q CB-F-1B-A FW-FN7-R3B Auxiliary Relay FN7 CB-F-2C-A FW-FT-4234-4 Flow Transmitter GL4 EFP-F-1A-A FL2-GL4 MM-CP-297B "B" Train BOP -PCC FL2 CB-F-3A-A 310952 FL2a 12 FW-FV-4244A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2H FW-B3Y-52 460 V AC Circuit Breaker B3Y CB-F-1A-A B3Y-V2H B3Y-V2H/1 E3C-G2G/3 G2G-V2H B3Y-G5X B3Y-G5X/1 E3C-FN6/3 F51-FN6/3 FN6-G5X/6 FN6-G5X/7 310844 B3Ya B3Yd B3Ye CBA-FN-19 CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-FV-4244-B FW-B3Y-FU Fuse B3Y CB-F-1A-A FW-CS-4244-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4224-A Selector Switch G2G CB-F-1A-A FW-SS-4224-A1 Selector Switch G5X DG-F-2A-A FW-FN6-MSO-4 Auxiliary Relay FN6 CB-F-2B-A FW-B3Y-42/0,C Motor Starters B3Y CB-F-1A-A FW-B3Y-49 Overload Relays B3Y CB-F-1A-A FW-ZS-4244-A Valve Position Switch V2H EFP-F-1-A FW-FN6-4244AX Auxiliary Relay FN6 CB-F-2B-A FW-CS-4244-A1 Control Switch with Indication F51 CB-F-3A-A E3C-F51/3 F51-G2G/3 FW-E3C-R1,R2,R3,R4 Auxiliary Relays E3C CB-F-1A-A E3C-FK0 E3C-F56 E3C-FN6/4 FK0-FN6 FK0-FN6/1 E3E/1a, 1e E3E/1c FW-E3P-62-1 Timing Relay E3P CB-F-1A-A FW-E3P-62-2 Timing Relay E3P CB-F-1A-A FW-E3P-62-3 Timing Relay E3P CB-F-1A-A FW-E3P-62-4 Timing Relay E3P CB-F-1A-A FW-FN6-R4A Auxiliary Relay FN6 CB-F-2B-A FW-FT-4244-4 Flow Transmitter GL3 EFP-F-1A-A FK0-GL3 310952 FK0a MM-CP-279A "A" Train BOP -PCC FK0 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -10 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 FW-FV-4244B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2M FW-B4C-52 460 V AC Circuit Breaker B4C CB-F-1B-A B4C-V2M B4C-V2M/1 E3D-G2J/3 GJ2-V2M B4C-G2J B4C-G5Y B4C-G5Y/1 E3D-FN7/3 F51-FN7/3 FN7-G5Y/6 FN7-G5Y/7 310844 B4Ca B4Cd B4Ce CBA-FN-32 CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-FV-4244-A FW-B4C-FU Fuse B4C CB-F-1B-A FW-CS-4244-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4224-B Selector Switch G2J CB-F-1B-A FW-B4C-42/0,C Motor Starters B4C CB-F-1B-A FW-SS-4224-B1 Selector Switch G5Y DG-F-2B-A FW-FN7-MSO-4 Auxiliary Relay FN7 CB-F-2C-A FW-B4C-49 Overload Relays B4C CB-F-1B-A FW-ZS-4244-B Valve Position Switch V2M EFP-F-1-A FW-E3D-4244BX Auxiliary Relay E3D CB-F-1B-A FW-FN7-4244BX Control Switch with Indication FN7 CB-F-2C-A E3D-F51/3 F51-G2J/3 FW-E3D-R1,R2,R3,R4 Auxiliary Relays E3D CB-F-1B-A E3D-FL2 E3D-F51/4 E3D-FN7/4 FL2-FN7 FL2-FN7/1 E3F/1a, 1e E3F/1c FW-E3Q-62-1 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-2 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-3 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-4 Timing Relay E3Q CB-F-1B-A FW-FN7-R4B Auxiliary Relay FN7 CB-F-2C-A MM-CP-297B "B" Train BOP -PCC FL2 CB-F-3A-A FL2-GL4 F56-FL2 F88-FL2 310952 FL2a FW-FR-4224 Flow Recorder F86 CB-F-3A-A FW-FT-4244-2 Flow Transmitter GL4 EFP-F-1A-A FW-FI-4244-2 Flow Indicator F56 CB-F-3A-A 14 MS-PV-3001 Main Steam Header MS-20580 A/B 310589 MS-F-2B-Z X X X X V2N MS-E2T/8-72 125 V DC Circuit Breaker E2T CB-F-1A-A G2G-V2N F60-G2G/9 E2T-G5X G2G-C5X FN8-U0A FN8-U0B FN8-G2G/1 F60-FN8 310841 E2T/8a E2T/8e E2T/8f CBA-FN-19 CBA-FN-20 EDE-PP-113A INST AIR MS-PV-3002 or MS-PV-3004 MS-SS-3001-2 Selector Switch G5X DG-F-2A-A MS-PY-3001-1 Solenoid Valve UOA MS-F-2B-Z MS-PY-3001-2 Solenoid Valve U0A MS-F-2B-Z MS-PY-3001-3 Solenoid Valve U0B MS-F-2B-Z MS-PY-3001-4 Solenoid Valve U0B MS-F-2B-Z MS-CS-3001-1 Control Switch with Indication F60 CB-F-3A-A MS-CS-3001-2 Control Switch with Indication G2G CB-F-1A-A MS-SS-3001-3 Selector Switch FN8 ET-F-1B-A MS-SS-3001-1 Selector Switch G2G CB-F-1A-A MS-ZS-3001-A Valve Position Switch V2N MS-F-2B-Z MS-PY-3001-5 Solenoid Valve U0C MS-F-2B-Z E2U-F66 F66-U0C 310841 E2U/15 E2U/15 EDE-PP-113B MS-PY-3001-6 Solenoid Valve U0C MS-F-2B-Z MS-E2U/15-72 125 V DC Circuit Breaker E2U CB-F-1B-A MS-CS-3001-1 Control Switch F60 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -11 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 MS-PV-3003 Main Steam Header Atmospheric Relief Valve MS-20580 A/B 310586 MS-F-2A-Z X X X X V2Q MS-SS-3003-2 Selector Switch G5X DG-F-2A-A G2G-V2Q F60-G2G/B E2T-G5X/1 G2G-G5X/1 FN8-U0K FN8-U0L FN8-G2G/2 F60-FN8/1 310841 E2T/10a E2T/10e E2T/10f EDE-PP-113A CBA-FN-19 CBA-FN-20 INST AIR MS-PV-3002 or MS-PV-3004 MS-CS-3003-2 Control Switch with Indication G2G CB-F-1A-A MS-CS-3003-1 Control Switch with Indication F60 CB-F-3A-A MS-E2T/10-72 125 V DC Circuit Breaker E2T CB-F-1A-A MS-SS-3003-3 Selector Switch FN8 ET-F-1B-A MS-SS-3003-1 Selector Switch G2G CB-F-1A-A MS-ZS-3003-A Valve Position Switch V2Q MS-F-2A-Z MS-PY-3003-1 Solenoid Valve UOK MS-F-2A-Z MS-PY-3003-2 Solenoid Valve UOK MS-F-2A-Z MS-PY-3003-3 Solenoid Valve UOL MS-F-2A-Z MS-PY-3003-4 Solenoid Valve UOL MS-F-2A-Z MS-PY-3003-5 Solenoid Valve UOM MS-F-2A-Z E2U-F66/1 F66-U0M E2U/16 E2U/16 EDE-PP-113B MS-PY-3003-6 Solenoid Valve UOM MS-F-2A-Z MS-E2U/16-72 125 V DC Circuit Breaker E2U CB-F-1B-A MS-CS-3003-1 Control Switch F60 CB-F-3A-A 16 MS-PV-3002 Main Steam Header Atmospheric Relief Valve MS-20580 A/B 310586 MS-F-2A-Z X X X X V2P MS-SS-3002-1 Selector Switch G2J CB-F-1B-A G2J-V2P F66-G2J/1 E2U-G5Y G2J-G5Y FN9-U0G FN9-U0H FN9-G2J/1 F66-FN9 310841 E2U/8a E2U/8e E2U/8f CBA-FN-32 CBA-FN-33 EDE-PP-113B INST AIR MS-PV-3001 or MS-PV-3003 MS-CS-3002-2 Control Switch with Indication G2J CB-F-1B-A MS-CS-3002-1 Control Switch with Indication F60 CB-F-3A-A MS-E2U/8-72 125 V DC Circuit Breaker E2U CB-F-1B-A MS-SS-3002-3 Selector Switch FN9 ET-F-1D-A MS-SS-3002-2 Selector Switch G5Y DG-F-2B-A MS-ZS-3002-B Valve Position Switch V2P MS-F-2A-Z MS-PY-3002-1 Solenoid Valve UOG MS-F-2A-Z MS-PY-3002-2 Solenoid Valve UOG MS-F-2A-Z MS-PY-3002-3 Solenoid Valve UOH MS-F-2A-Z MS-PY-3002-4 Solenoid Valve UOH MS-F-2A-Z MS-PY-3002-5 Solenoid Valve UOJ MS-F-2A-Z E2T-F60 F60-U0J E2T/15 E2T/15 EDE-PP-113A MS-PY-3002-6 Solenoid Valve UOJ MS-F-2A-Z MS-E2T/15-72 125 V DC Circuit Breaker E2T CB-F-1A-A MS-CS-3002-1 Control Switch F60 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -12 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 17 MS-PV-3004 Main Steam Header Atmospheric Relief Valve MS-20580 A/B 310586 MS-F-2B-Z X X X X V2R MS-SS-3004-1 Selector Switch G2J CB-F-1B-A G2J-V2R G2J-G5Y/1 F66-G2J/3 E2U-G5Y/1 FN9-U0D FN9-U0E FN9-G2J/2 F66-FN9/1 310841 E2U/10a E2U/10e E2U/10f EDE-PP-113B CBA-FN-32 CBA-FN-33 INST AIR MS-PV-3001 or MS-PV-3003 MS-CS-3004-2 Control Switch with Indication G2J CB-F-1B-A MS-CS-3004-1 Control Switch with Indication F60 CB-F-3A-A MS-E2U/10-72 125 V DC Circuit Breaker E2U CB-F-1B-A MS-SS-3004-3 Selector Switch FN9 ET-F-1D-A MS-SS-3004-2 Selector Switch G5Y DG-F-2B-A MS-ZS-3004-B Valve Position Switch V2R MS-F-2B-Z MS-PY-3004-1 Solenoid Valve UOD MS-F-2B-Z MS-PY-3004-2 Solenoid Valve UOD MS-F-2B-Z MS-PY-3004-3 Solenoid Valve UOE MS-F-2B-Z MS-PY-3004-4 Solenoid Valve UOE MS-F-2B-Z MS-PY-3004-5 Solenoid Valve UOF MS-F-2B-Z E2T-F60/1 F60-U0F E2T/16 E2T/16 EDE-PP-113A MS-PY-3004-6 Solenoid Valve UOF MS-F-2B-Z MS-E2T/16-72 125 V DC Circuit Breaker E2T CB-F-1A-A MS-CS-3004-1 Control Switch F60 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -13 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 MS-V-86 Main Steam Isolation Valve MS-20583 A/B 310589 MS-F-2B-Z X X X X ZVO ZV1 ZV2 ZW1 MS-E87/14-72 125 V DC Circuit Breaker E87 CB-F-1A-A E87-GX6 GX6-ZV1 310841 E87/14a E87/14b CBA-FN-19 CBA-FN-20 EDE-PP-112A None Note 2 MS-FY-89A-1 Pilot Solenoid ZV1 MS-F-2B-Z MS-FY-10A-1 Pilot Solenoid ZV1 MS-F-2B-Z MS-FY-102A-1 Solenoid Valve ZV1 MS-F-2B-Z MS-FY-102B-1 Solenoid Valve ZV1 MS-F-2B-Z MS-GX6-K103 Output Relay GX6 MS-F-3A-Z MS-GX6-K104 Output Relay GX6 MS-F-3A-Z MS-GX6-CS-3005A Control Switch GX6 MS-F-3A-Z MS-E1S/7-52 120 V AC Circuit Breaker E1S CB-F-1A-A E1S-GX6/1 G2G-GX6/4 G2G-GX6/5 GX6-ZV0 G2G-GX6/3 F20-GX6 GX6-ZV0/1 FC1-GX6 F60-GX6/1 FB7-FC1/E F60-G2G/2 F60-GX6 FB7-GX6 E1S/7a E1S/7h E1S/7b E1S/7i E1S/7c E1S/7j E1S/7d E1S/7k CBA-FN-19 CBA-FN-20 EDE-PP-11E MS-GX6-FU-101,102 120 V AC Fuses GX6 MS-F-3A-Z MS-GX6-K101 Output Relay GX6 MS-F-3A-Z MS-GX6-K102 Output Relay GX6 MS-F-3A-Z MS-ZS-V86-1 Valve Position Switch ZV0 MS-F-2B-Z MS-ZS-V86-2 Valve Position Switch ZV0 MS-F-2B-Z MS-ZL-3005-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-184 MSIV Logic Cabinet (Train A) GX6 MS-F-3A-Z MS-FC1-K-804 Auxiliary Relay SSPS Test FC1 CB-F-3A-A MS-CS-3085-2 Control Switch F20 CB-F-3A-A MS-CS-3005 Control Switch with Indication F60 CB-F-3A-A MS-DS-8029 Isolation Indication FC1 CB-F-3A-A MS-FB7-K634A SSPS Auxiliary Relay FB7 CB-F-3A-A MS-E88/14-72 125 V DC Circuit Breaker E88 CB-F-1B-A E88-GX9 GX9-ZV2 E88/14a E88/14b CBA-FN-32 CBA-FN-33 EDE-PP-112B MS-FY-89B-1 Pilot Solenoid ZV2 MS-F-2B-Z MS-FY-10B-1 Pilot Solenoid ZV2 MS-F-2B-Z MS-FY-117A-1 Solenoid Valve ZV2 MS-F-2B-Z MS-FY-117B-1 Solenoid Valve ZV2 MS-F-2B-Z MS-GX9-K103 Output Relay GX9 CB-F-1B-A MS-GX9-K104 Output Relay GX9 CB-F-1B-A MS-GX9-CS-3005-B Control Switch GX9 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -14 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 MS-V-86 Main Steam Isolation Valve MS-E1T/7-52 120 V AC Circuit Breaker E1T CB-F-1B-A E1T-GX9/3 G2J-GX9/1 GX9-ZW1 G2J-GX9 FB0-GX9 F51-GX9 GX9-ZW1/1 FC2-GX9 FBO-FC2/E E1T/7a E1T/7f E1T/7b E1T/7g E1T/7c E1T/7h E1T/7i CBA-FN-32 CBA-FN-33 EDE-PP-11F (Continued) MS-GX9-FU-101,102 120 V AC Fuses GX9 CB-F-1B-A MS-GX9-K101 Output Relay GX9 CB-F-1B-A MS-GX9-K102 Output Relay GX9 CB-F-1B-A MS-ZS-V86B-1 Valve Position Switch ZW1 MS-F-2B-Z MS-ZS-V86B-2 Valve Position Switch ZW1 MS-F-2B-Z MS-ZL-3005-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A MS-CP-185 MSIV Logic Cabinet (Train B) GX9 CB-F-1B-A MS-FC2-K-804 Auxiliary Relay SSPS Test FC2 CB-F-3A-A MS-CS-3085-1 Control Switch F50 CB-F-3A-A MS-DS-8029 Isolation Indication FC2 CB-F-3A-A MS-FB0-K634B SSPS Auxiliary Relay FBO CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -15 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 MS-V-88 Main Steam Isolation Valve MS-20583 A/B 310586 MS-F-2A-Z X X X X ZW3 ZW4 ZW5 ZW6 MS-E2T/12-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-GX7 GX7-ZW3 310841 E2T/12a E2T/12c CBA-FN-19 DBA-FN-20 EDE-PP-113A None Note 2 MS-FY-89A-2 Pilot Solenoid ZW3 MS-F-2A-Z MS-FY-10A-2 Pilot Solenoid ZW3 MS-F-2A-Z MS-FY-102A-2 Solenoid Valve ZW3 MS-F-2A-Z MS-FY-102B-2 Solenoid Valve ZW3 MS-F-2A-Z MS-GX7-K103 Output Relay GX7 MS-F-3A-Z MS-GX7-K104 Output Relay GX7 MS-F-3A-Z MS-GX7-CS-3006-A Control Switch GX7 MS-F-3A-Z MS-E1S/9-52 120 V AC Circuit Breaker E1S CB-F-1A-A E1S-GX7/1 G2G-GX7/4 G2G-GX7/5 GX7-ZW5 G2G-GX7/3 FB7-GX7 F20-GX7 GX7-ZW5/1 FC1-GX7 F60-GX7/1 FC1-GX7/1 FB7-FC1/F F60-G2G/5 F60-GX7 E1S/9a E1S/9h E1S/9b E1S/9i E1S/9c E1S/9j E1S/9d E1S/9k CBA-FN-19 CBA-FN-20 EDE-PP-11E MS-GX7-FU-101,102 120 V AC Fuses GX7 MS-F-3A-Z MS-GX7-K101 Output Relay GX7 MS-F-3A-Z MS-GX7-K102 Output Relay GX7 MS-F-3A-Z MS-ZS-V88A-1 Valve Position Switch ZW5 MS-F-2A-Z MS-ZS-V88A-2 Valve Position Switch ZW5 MS-F-2A-Z MS-ZL-3006-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-182 MSIV Logic Cabinet (Train A) GX7 MS-F-3A-Z MS-CS-3006 Control Switch with Indication F60 CB-F-3A-A MS-FC1-K-804 Auxiliary Relay SSPS Test FC1 CB-F-3A-A MS-CS-3085-2 Control Switch F20 CB-F-3A-A MS-DS-8030 Isolation Indication FC1 CB-F-3A-A MS-FB7-K634A SSPS Auxiliary Relay FB7 CB-F-3A-A MS-E2U/12-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-GX8 GX8-ZW4 E2U/12a E2U/12c CBA-FN-32 CBA-FN-33 EDE-PP-113B MS-GX8-K103 Output Relay GX8 CB-F-1B-A MS-GX8-K104 Output Relay GX8 CB-F-1B-A MS-FY-89B-2 Pilot Solenoid ZW4 MS-F-2A-Z MS-FY-10B-2 Pilot Solenoid ZW4 MS-F-2A-Z MS-FY-117A-2 Solenoid Valve ZW4 MS-F-2A-Z MS-FY-117B-2 Solenoid Valve ZW4 MS-F-2A-Z MS-GX8-CS-3006-B Control Switch GX8 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -16 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 MS-V-88 Main Steam Isolation Valve (Continued) MS-E1T/9-52 125 V AC Circuit Breaker E1T CB-F-1B-A E1T-GX8/3 G2J-GX8 GX8-ZW6 G2J-GX8/1 FB0-GX8 F51-GX8 GX8-ZW6/1 FC2-GX8 FBO-FC2/F 310841 E1T/9a E1T/9f E1T/9b E1T/9g E1T/9c E1T/9h E1T/9i CBA-FN-32 CBA-FN-33 EDE-PP-11F MS-GX8-FU-101,102 120 V AC Fuses GX8 CB-F-1B-A MS-GX8-K101 Output Relay GX8 CB-F-1B-A MS-GX8-K102 Output Relay GX8 CB-F-1B-A MS-ZS-V88B-1 Valve Position Switch ZW6 MS-F-2A-Z MS-ZS-V88B-2 Valve Position Switch ZW6 MS-F-2A-Z MS-ZL-3006-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A MS-CP-183 MSIV Logic Cabinet (Train B) GX8 CB-F-1B-A MS-FC2-K-804 Auxiliary Relay SSPS Test FC2 CB-F-3A-A MS-CS-3085-1 Control Switch F50 CB-F-3A-A MS-DS-8030 Isolation Indication FC2 CB-F-3A-A MS-FB0-K634B SSPS Auxiliary Relay FBO CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -17 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 20 MS-V-90 Main Steam Isolation Valve MS-20583 A/B 310586 MS-F-2A-Z X X X X ZX1 ZW0 ZW8 ZW9 MS-E2T/14-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-GX7/1 GX7-ZW8 310841 E2T/14a E2T/14c CBA-FN-19 CBA-FN-20 EDE-PP-113A None Note 2 MS-FY-89A-3 Pilot Solenoid ZW8 MS-F-2A-Z MS-FY-10A-3 Pilot Solenoid ZW8 MS-F-2A-Z MS-FY-102A-3 Solenoid Valve ZW8 MS-F-2A-Z MS-FY-102B-3 Solenoid Valve ZW8 MS-F-2A-Z MS-GX7-K111 Output Relay GX7 MS-F-3A-Z MS-GX7-K112 Output Relay GX7 MS-F-3A-Z MS-GX7-CS-3007-A Control Switch GX7 MS-F-3A-Z MS-E1S/9-52 120 V AC Circuit Breaker E1S CB-F-1A-A E1S-GX7/1 G2G-GX7/3 G2G-GX7/4 G2G-GX7/5 GX7-ZW0 FB7-GX7 GX7-ZW0/1 FC1-GX7 F60-GX7/1 F20-GX7/1 FC1-GX7/1 F60-GX7 FB7-FC1/F F60-G2G/5 E1S/9a E1S/9h E1S/9b E1S/9i E1S/9c E1S/9j E1S/9d E1S/9k CBA-FN-19 CBA-FN-20 EDE-PP-11E MS-GX7-FU-103,104 120 V AC Fuses GX7 MS-F-3A-Z MS-GX7-K109 Output Relay GX7 MS-F-3A-Z MS-GX7-K110 Output Relay GX7 MS-F-3A-Z MS-ZS-V90A-1 Valve Position Switch ZWO MS-F-2A-A MS-ZS-V90A-2 Valve Position Switch ZWO MS-F-2A-A MS-ZL-3007-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-182 MSIV Logic Cabinet (Train A) GX7 MS-F-3A-Z MS-CS-3007 Control Switch with Indication F60 CB-F-3A-A MS-CS-3085-2 Control Switch F20 CB-F-3A-A MS-DS-8031 Isolation Indication FC1 CB-F-3A-A MS-FB7-K634A SSPS Auxiliary Relay FB7 CB-F-3A-A MS-FC1-K804 Auxiliary Relay SSPS Test FC1 CB-F-3A-A MS-E2U/14-72 125 V DC Circuit Breaker E2U CB-F-1A-A E2U-GX8/1 GX8-ZW9 E2U/14a E2U/14c CBA-FN-32 CBA-FN-33 EDE-PP-113B MS-GX8-K111 Output Relay GX8 CB-F-1B-A MS-GX8-K112 Output Relay GX8 CB-F-1B-A MS-FY-89B-3 Pilot Solenoid ZW9 MS-F-2A-Z MS-FY-10B-3 Pilot Solenoid ZW9 MS-F-2A-Z MS-FY-117A-3 Solenoid Valve ZW9 MS-F-2A-Z MS-FY-117B-3 Solenoid Valve ZW9 MS-F-2A-Z MS-CP-183 MSIV Logic Cabinet (Train B) GX8 CB-F-1B-A MS-GX8-CS-3007-B Control Switch GX8 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -18 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 20 MS-V-90 Main Steam Isolation Valve (Continued) MS-E1T/9-52 125 V AC Circuit Breaker E1T CB-F-1B-A E1T-GX8/3 G2J-GX8 G2J-GX8/1 GX8-ZX1 FB0-GX8 F51-GX8 FC2-GX8 GX8-ZX1/2 FBO-FC2/F 310841 E1T/9a E1T/9f E1T/9b E1T/9g E1T/9c E1T/9h E1T/9i CBA-FN-32 CBA-FN-33 EDE-PP-11F MS-GX8-FU-103,104 120 V AC Fuses GX8 CB-F-1B-A MS-GX8-K109 Output Relay GX8 CB-F-1B-A MS-GX8-K110 Output Relay GX8 CB-F-1B-A MS-ZS-V90B-1 Valve Position Switch ZX1 MS-F-2A-Z MS-ZS-V90B-1 Valve Position Switch ZX1 MS-F-2A-Z MS-ZL-3007-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-CP-183 MSIV Logic Cabinet (Train B) GX8 CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A MS-CS-3085-1 Control Switch F50 CB-F-3A-A MS-DS-8031 Isolation Indication FC2 CB-F-3A-A MS-FB0-K634B SSPS Auxiliary Relay FB0 CB-F-3A-A MS-FC2-K804 Auxiliary Relay SSPS Test FC2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -19 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 21 MS-V-92 Main Steam Isolation Valve MS-20583 A/B 310589 MS-F-2B-Z X X X X ZX3 Z1A Z1B Z1C MS-E87/18-52 125 V DC Circuit Breaker E87 CB-F-1A-A E87-GX6/1 GX6-ZX3 310841 E87/18a E87/18c CBA-FN-19 CBA-FN-20 EDE-PP-112A None Note 2 MS-GX6-K111 Output Relay GX6 MS-F-3A-Z MS-GX6-K112 Output Relay GX6 MS-F-3A-Z MS-FY-89A-4 Pilot Solenoid ZX3 MS-F-2B-Z MS-FY-10A-4 Pilot Solenoid ZX3 MS-F-2B-Z MS-FY-102A-4 Solenoid Valve ZX3 MS-F-2B-Z MS-FY-102B-4 Solenoid Valve ZX3 MS-F-2B-Z MS-CP-184 MSIV Logic Cabinet (Train A) GX6 CB-F-1A-A MS-GX6-CS-3008-A Control Switch GX6 MS-F-3A-Z MS-E1S/7-52 120 V AC Circuit Breaker E1S CB-F-1A-A E1S-GX6/1 G2G-GX6/3 G2G-GX6/4 G2G-GX6/5 GX6-Z1B FB7-GX6 GX6-Z1B/1 F20-GX6/1 FC1-GX6 F60-GX6/1 FB7-PC1/E F60-GX6 F60-G2G/2 E1S/7a E1S/7h E1S/7b E1S/7i E1S/7c E1S/7j E1S/7d E1S/7k CBA-FN-19 CBA-FN-20 EDE-PP-11E MS-GX6-FU-103,104 120 V AC Fuses GX6 MS-F-3A-Z MS-GX6-K109 Output Relay GX6 MS-F-3A-Z MS-GX6-K110 Output Relay GX6 MS-F-3A-Z MS-ZS-V92A-1 Valve Position Switch Z1B MS-F-2B-Z MS-ZS-V92A-2 Valve Position Switch Z1B MS-F-2B-Z MS-ZL-3008-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-184 MSIV Logic Cabinet (Train A) GX6 MS-F-3A-Z MS-CS-3008 Control Switch with Indication F60 CB-F-3A-A MS-CS-3085-2 Control Switch F20 CB-F-3A-A MS-DS-8032 Isolation Indication FC1 CB-F-3A-A MS-FB7-K634A SSPS Auxiliary Relay FB7 CB-F-3A-A MS-FC1-K804 Auxiliary Relay SSPS Test FC1 CB-F-3A-A MS-E88/14-72 125 V DC Circuit Breaker E88 CB-F-1B-A E88-GX9/1 GX9-Z1A E88/9a E88/9c CBA-FN-32 CBA-FN-33 EDE-PP-112B MS-GX9-K111 Output Relay GX9 CB-F-1B-A MS-GX9-K112 Output Relay GX9 CB-F-1B-A MS-FY-89B-4 Pilot Solenoid Z1A MS-F-2B-Z MS-FY-10B-4 Pilot Solenoid Z1A MS-F-2B-Z MS-FY-117A-4 Solenoid Valve Z1A MS-F-2B-Z MS-FY-117B-4 Solenoid Valve Z1A MS-F-2B-Z MS-CP-185 MSIV Logic Cabinet (Train B) GX9 CB-F-1B-A MS-GX9-3008-B Control Switch GX9 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -20 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 21 MS-V-92 Main Steam Isolation Valve (Continued) MS-E1T/7-52 125 V AC Circuit Breaker E1T CB-F-1B-A E1T-GX9/3 GX9-Z1C G2J-GX9 G2J-GX9/1 FB0-GX9 F51-GX9 GX9-Z1C/1 FB0-FC2/E FC2-GX9 310841 E1T/7a E1T/7f E1T/7b E1T/7g E1T/7c E1T/7h E1T/7i CBA-FN-32 CBA-FN-33 EDE-PP-11F MS-GX9-FU-103,104 120 V AC Fuses GX9 CB-F-1B-A MS-GX9-K109 Output Relay GX9 CB-F-1B-A MS-GX9-K110 Output Relay GX9 CB-F-1B-A MS-ZS-V92B-1 Valve Position Switch Z1C MS-F-2B-Z MS-ZS-V92B-2 Valve Position Switch Z1C MS-F-2B-Z MS-ZL-3008-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A MS-CP-185 MSIV Logic Cabinet (Train B) GX9 CB-F-1B-A MS-CS-3085-1 Control Switch F50 CB-F-3A-A MS-DS-8032 Isolation Indication FC2 CB-F-3A-A MS-FB0-K634B SSPS Auxiliary Relay FB0 CB-F-3A-A MS-FC2-K804 Auxiliary Relay SSPS Test FC2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -21 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 22 MS-V-204 Main Steam Isolation Valve Bypass Valve MS-20583 A 310589 MS-F-2B-Z X X X - VU6 MS-B1X-52 460 VAC Circuit Breaker B1X CB-F-1A-A - - - - None Note 3 23 MS-V-205 Main Steam Isolation Valve Bypass Valve MS-20583 A 310586 MS-F-2A-Z X X X - VU7 MS-B1Y-52 460 VAC Circuit Breaker B1Y CB-F-1A-A - - - - None Note 3 24 MS-V-206 Main Steam Isolation Valve Bypass Valve MS-20583 A 310586 MS-F-2A-Z X X X - VU8 MS-B1Z-52 460 VAC Circuit Breaker B1Z CB-F-1A-A - - - - None Note 3 25 MS-V-207 Main Steam Isolation Valve Bypass Valve MS-20583 A 310589 MS-F-2B-Z X X X - VU9 MS-B2A-52 460 VAC Circuit Breaker B2A CB-F-1A-A - - - - None Note 3 26 RC-E-11A Steam Generator RC-20841 A 310576 310582 310578 310580 C-F-1-Z C-F-1-Z C-F-2-Z C-F-3-Z X X - - - - - - - - - - - RC-E-11B or RC-E-11D Note 1 27 RC-E-11B Steam Generator RC-20842 B 310576 310582 310578 310580 C-F-1-Z C-F-1-Z C-F-2-Z C-F-3-Z X X - - - - - - - - - - - RC-E-11A or RC-E-11C Note 1 28 RC-E-11C Steam Generator RC-20843 A 310577 310583 310579 310581 C-F-1-Z C-F-1-Z C-F-2-Z C-F-3-Z X X - - - - - - - - - - - RC-E-11B or RC-E-11D Note 1 29 RC-E-11D Steam Generator RC-20844 B 310577 310583 310579 310581 C-F-1-Z C-F-1-Z C-F-2-Z C-F-3-Z X X - - - - - - - - - - - RC-E-11A or RC-E-11C Note 1 30 SB-V9 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM4 SB-CS-1900 Control Switch with Indication F28 CB-F-3A-A F26-U6V F26-UM4 F26-FB0/4 310901 E88/18a E88/18c E88/18d SB-V-1 Note 2 SB-FB0-K630B SSPS Output Relay FB0 CB-F-3A-A SS-FY-1900B Pilot Solenoid U6V MS-F-1B-Z SB-ZS-V9 Valve Position Switch UM4 MS-F-1B-Z 31 SB-V10 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM5 SB-CS-1901 Control Switch with Indication F28 CB-F-3A-A F26-U6W F26-UM5 F26-FB0/4 310901 E88/18a E88/18c E88/18d SB-V-3 Note 2 SB-FB0-K630B SSPS Output Relay FB0 CB-F-3A-A SS-FY-1901-B Pilot Solenoid U6W MS-F-1B-Z SB-ZS-V10 Valve Position Switch UM5 MS-F-1B-Z 32 SB-V11 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM6 SB-CS-1902 Control Switch with Indication F28 CB-F-3A-A F26-U6X F26-UM6 F26-FB0/4 310901 E88/18a E88/18c E88/18d SB-V-5 Note 2 SB-FB0-K630B SSPS Output Relay FB0 CB-F-3A-A SS-FY-1902-B Pilot Solenoid U6X MS-F-1B-Z SB-ZS-V11 Valve Position Switch UM6 MS-F-1B-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -22 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 33 SB-V12 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM7 SB-CS-1903 Control Switch with Indication F28 CB-F-3A-A F26-U6Y F26-UM7 F26-FB0/5 310901 E88/18a E88/18c E88/18d SB-V-7 Note 2 SB-FB0-K630B SSPS Output Relay FB7 CB-F-3A-A SS-FY-1903-B Pilot Solenoid U6Y MS-F-1B-Z SB-ZS-V12 Valve Position Switch UM7 MS-F-1B-Z 34 SB-V-1 RC-E-11A Inboard Blowdown Isolation Valve SB-20626 A 310578 C-F-2-Z X X X X VB7 SB-CS-1987 Control Switch with Indication F28 CB-F-3A-A F28-H36/4 F28-H36/5 H36-VB7/1 310901 E93/14a E93/14d E93/14b SB-V-9 Note 2 SB-FY-V1-20 Solenoid Valve VB7 C-F-2-Z SB-ZS-V1 Valve Position Switches VB7 C-F-2-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A 35 SB-V-3 RC-E-11B Inboard Blowdown Isolation Valve SB-20626 A 310579 C-F-2-Z X X X X VC6 SB-CS-1988 Control Switch with Indication F28 CB-F-3A-A F28-H36/4 F28-H36/5 H36-VC6/1 310901 E93/14a E93/14d E93/14b E93/14e SB-V-10 Note 2 SB-FY-V3-20 Solenoid Valve VC6 C-F-2-Z SB-ZS-V3 Valve Position Switches VC6 C-F-2-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A 36 SB-V-5 RC-E-11C Inboard Blowdown Isolation Valve SB-20626 A 310579 C-F-2-Z X X X X VC7 SB-CS-1989 Control Switch with Indication F28 CB-F-3A-A F28-H36/4 F28-H36/5 F28-H36/6 H36-VC7/1 310901 E93/14a E93/14d E93/14b E93/14e SB-V-11 Note 2 SB-FY-V5-20 Solenoid Valve VC7 C-F-2-Z SB-ZS-V5 Valve Position Switches VC7 C-F-2-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A 37 SB-V-7 RC-E-11D Inboard Blowdown Isolation Valve SB-20626 A 310579 C-F-2-Z X X X X VC8 SB-CS-1990 Control Switch with Indication F28 CB-F-3A-A F28-H36/5 F28-H36/6 H36-VC8/1 310901 E93/14a E93/14d E93/14b E93/14e SB-V-12 SB-FY-V7-20 Solenoid Valve VC8 C-F-2-Z SB-ZS-V7 Valve Position Switches VC8 C-F-2-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A Note 2 38 CO-V-142 Condensate Tank Emergency Outlet Valve CO-20426 A 310248 202319 CST-F-1-0 X X - - - - - - - - - - - - Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -1 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 RC-E-10 Reactor Coolant System Pressurizer RC-20846 A/B 310598 C-F-1-Z X X - - - - - - - - - - - None Note 1 2 RC-E-10 Pressurizer Heaters Group A RC-20846 A 310598 C-F-1-Z X X X - M26 RC-AB4-52 480 V AC Circuit Breaker AB4 CB-F-1A-A AB4-E07 AB4-E07/1 AB4-G81 AB4-G81/1 E07-H14 E07-H14/1 E07-H14/2 E07-H14/3 E07-H14/4 H14-X47 H14-X47/1 H14-X47/2 H14-X47/3 H14-X47/4 M26-X47 M26-X47/1 M26-X47/2 M26-X47/3 M26-X47/4 M26-X47/5 M26-X47/6 M26-X47/7 M26-X47/8 M26-X47/9 M26-X47/A M26-X47/B M26-X47/C M26-X47/D M26-X47/E FB1-HR2 F38-FB1 F38-G81 310882 AB4a AB4g AB4b AB4h AB4c AB4i CBA-FN-19 CBA-FN-20 EDE-US-52 Pressurizer -Heaters Group B RC-AB4-FV Fuses AB4 CB-F-1A-A RC-CS-7318-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-7318 Selector Switch G81 CB-F-1A-A EDE-AC3-94-3 Bus Undervoltage Relay AC3 CB-F-1A-A RC-AB4-52H-1 Truck Operated Contact AB4 CB-F-1A-A EDE-TBX-X47 Terminal Box X47 C-F-1-Z RC-AB4-G,R Indicating Lights AB4 CB-F-1A-A RC-AB4-CT1 Current Transformer (600/5) ØB Bus Side AB4 CB-F-1A-A RC-AB4-AM Ammeter AB4 CB-F-1A-A RC-AB4-CT2 Current Transformer (600/5) ØA, ØC Load Side AB4 CB-F-1A-A RC-AC3-WTR Watt Transducer AC3 CB-F-1A-A RC-PP-6A Distribution Panel E07 ET-F-1A-A EDE-MM-90 Electrical Penetration H14 ET-F-1A-A, C-F-2-Z RC-HR2-RMO, PR1 Emergency Power Sequence Auxiliary Relays HR2 CB-F-1A-A RC-CS-7318-1 Control Switch with Indication F31 CB-F-3A-A RC-PYY-455GX1 Low Pressure Auxiliary Relay FB1 CB-F-3A-A RC-LYY-459CX1 Low Level Auxiliary Relay FB1 CB-F-3A-A RC-LYY-460DX1 Low Level Auxiliary Relay FB1 CB-F-3A-A RC-LYY-459EX1 High Level Auxiliary Relay FB1 CB-F-3A-A EDE-AC3-94-3 Undervoltage Tripping Relay AC3 CB-F-1A-A RC-LT-459 Pressurizer Level Transmitter GN5 C-F-2-Z GN5-H45/1 FA1-H45/1 C509011 310942 C509027 FA1s FP30001 FA1w SH125 MM-CP-1 MM-CP-1 Process Protection System Cabinet No. 1 FA1 CB-F-3A-A EDE-MM-121 Electrical Penetration H45 C-F-2-Z, ET-F-1A-1 MM-CP-5 Process Control GP No. 1 Cabinet FA5 CB-F-3A-A RC-LT-460 Pressurizer Level Transmitter GN5 C-F-2-Z GN5-H55/2 FA2-H55/3 C509011 310942 C509027 FA2r FP30001 FA2w SH125 MM-CP-2 EDE-MM-131 Electrical Penetration H55 C-F-1-Z ET-F-1C-Z

.* Table notes on last page of table

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -2 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 RC-E-10 (Continued) MM-CP-2 Process Protection System Cabinet No. 2 FA2 CB-F-3A-A MM-CP-6 Process Control GP No. 2 Cabinet FA6 CB-F-3A-A 3 RC-E-10 Pressurizer Heaters Group B RC-20846 B 310598 C-F-1-Z X X X - M26 RC-AD4-52 480 V AC Circuit Breaker AD4 CB-F-1B-A AD4-E08 AD4-E08/1 AD4-GZ0 AD4-GZ0/1 E08-H20 E08-H20/1 E08-H20/2 E08-H20/3 E08-H20/4 H20-X44 H20-X44/1 H20-X44/2 H20-X44/3 H20-X44/4 M26-X44 M26-X44/1 M26-X44/2 M26-X44/3 M26-X44/4 M26-X44/5 M26-X44/6 M26-X44/7 M26-X44/8 M26-X44/9 M26-X44/A M26-X44/B M26-X44/C M26-X44/D M26-X44/E F31-FT0 F31-HR4 F31-GZ0 AE3-GZ0 310882 AD4a AD4f AD4b AD4g AD4c AD4p AD4n CBA-FN-32 CBA-FN-33 EDE-US-62 Pressurizer Heaters Group A RC-AD4-FU Fuses AD4 CB-F-1B-A RC-CS-7319-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-7319 Selector Switch GZ0 CB-F-1B-A EDE-AE3-94-3 Bus Undervoltage Relay AE3 CB-F-1B-A RC-AD4-52H-1 Truck Operated Contact AD4 CB-F-1B-A RC-AD4-G,R Indicating Lights AD4 CB-F-1B-A EDE-TBX-X44 Terminal Box X44 C-F-1-Z RC-AD4-CT1 Current Transformer (600/5) ØB Bus Side AD4 CB-F-1B-A RC-AD4-AM Ammeter AD4 CB-F-1B-A RC-AD4-CT2 Current Transformer (600/5) ØA, ØC Load Side AD4 CB-F-1B-A RC-AE3-WTR Watt Transducer AE3 CB-F-1B-A RC-PP-6B Distribution Panel E08 ET-F-1C-A EDE-MM-96 Electrical Penetration H20 ET-F-1C-A, C-F-1-Z RC-AE3-R1 Auxiliary Relay AE3 CB-F-1B-A RC-HR4-RM0,PR1 Emergency Power Sequencer Auxiliary Relays HR4 CB-F-1B-A RC-CS-7319-1 Control Switch with Indication F31 CB-F-3A-A EDE-FT0-KA2,KA3 KA4,KA5 Auxiliary Relays Isolation Cabinet FT0 CB-F-3A-A EDE-AE3-94-3 Undervoltage Tripping Relay AE3 CB-F-1B-A RC-FS9-FU Fuses FS9 CB-F-3A-A FB2-FS9/1 FB2-FS9/2 310966 EH9/15a EH9/15s EH9/15b EH9/15t EH9/15c EH9/15d EH9/15e EH9/15f EH9/15g EH9/15h EH9/15i RC-LYY-459CX2 Low Level Auxiliary Relay FB2 CB-F-3A-A RC-LYY-460DX2 Low Level Auxiliary Relay FB2 CB-F-3A-A EDE-FT0-KA3,KA5 Auxiliary Relays Isolation Cabinet FT0 CB-F-3A-A MM-CP-5 Process Control Cabinet FA5 CB-F-3A-A GN5-H45/1 FA1-H45/1 C509011 310942 C509027 FA1s FP30001 FA1w FP129 EDE-MM-121 Electrical Penetration H45 C-F-2-Z ET-F-1A-A MM-CP-1 Process Protection Cabinet No. 1 FA1 CB-F-3A-A RC-LT-459 Pressurizer Level Transmitter GN5 C-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -3 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 RC-E-10 (Continued) RC-LT-460 Pressurizer Level Transmitter GN5 C-F-2-Z GN5-H55/2 FA2-H55/3 C509011 310942 C509027 FA2r FP30001 FA2w SH129 EDE-MM-131 Electrical Penetration H55 C-F-1-Z ET-F-1C-Z MM-CP-2 Process Protection System Cabinet No. 2 FA2 CB-F-3A-A MM-CP-6 Process Control GP No. 2 Cabinet FA6 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -4 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 RC-V-122 RC-E-10 Pressurizer Relief Isolation Valve RC-20846 A 310581 C-F-3-Z X X X - V01 RC-B97-52-1,2 460 V AC Circuit Breakers B97 CB-F-1A-A B97-G81 B97-G81/1 B97-H18 B97-H35 H18-V01 H35-X56 V01-X56 ED1-F38 F38-G81/2 F38-G81/3 310882 B97a B97c B97e B97d CBA-FN-19 CBA-FN-20 EDE-MCC-521 RC-V-124 or RC-PCV-456A RC-B97-FU Fuse B97 CB-F-1A-A RC-CS-7313-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-7313 Selector Switch G81 CB-F-1A-A RC-B97-42-1/0,C Motor Starters B97 CB-F-1A-A RC-B97-42-2 Motor Starter B97 CB-F-1A-A RC-B97-49-1,2 Overload Relays B97 CB-F-1A-A EDE-TBX-X56 Terminal Box X56 C-F-3-Z RC-ZS-V122 Valve Position Switch and Valve Open/Close Torque Switches V01 C-F-3-Z EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A RC-CS-7313-1 Control Switch with Indication F31 CB-F-3A-A RC-ED1-R1 Auxiliary Relay ED1 CB-F-1A-A 5 RC-V-124 RC-E-10 Pressurizer Relief Isolation Valve RC-20846 B 310581 C-F-3-Z X X X - V02 RC-B98-52-1,2 460 V AC Circuit Breakers B98 CB-F-1B-A B98-GZ0 B98-GZ0/1 B98-H15 B98-H41 H15-V02 H41-X35 V02-X35 B98-GZ0/2 F31-FT0/1 F31-GZ0/5 F31-GZ0/6 310882 B98a B98c B98e B98d CBA-FN-32 CBA-FN-33 EDE-MCC-621 RC-V-122 or RC-PCV-456B RC-B98-FU Fuses B98 CB-F-1B-A RC-CS-7314-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-7314 Selector Switch GZ0 CB-F-1B-A RC-B98-42-1/0,C Motor Starters B98 CB-F-1B-A RC-B98-42-2 Motor Starter B98 CB-F-1B-A RC-B98-49-1,2 Overload Relays B98 CB-F-1B-A EDE-TBX-X35 Terminal Box X35 C-F-3-Z RC-ZS-V124 Valve Position Switch and Valve Open/Close Torque Switches V02 C-F-3-Z EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A RC-CS-7314-1 Control Switch with Indication F31 CB-F-3A-A RC-FT0-KA6 Auxiliary Relay FT0 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -5 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 RC-PCV-456A RC-E-10 Pressurizer Relief Control Valve RC-20846 A 310581 C-F-3-Z X X X - LD3 RC-E87/19-72 125 V DC Circuit Breaker E87 CB-F-1A-A E87-E4A/4 E4A-J3M G81-J3M G81-H35 G5X-J3M H18-J3M H18-LD3 H35-X56/2 LD3-X56 F38-G81/1 F38-FB1/2 F38-G5X 310882 E87/19a E87/19c E87/19d CBA-FN-19 CBA-FN-20 EDE-PP-112A RC-PCV-456B or RC-V-122 RC-CS-456A-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-456-A1 Selector Switch G81 CB-F-1A-A RC-SS-456-A2 Selector Switch G5X DG-F-2A-A RC-J3M-42 Auxiliary Relay J3M DG-F-2A-A RC-PCV-456A-20 Solenoid Operating Coil LD3 C-F-3-Z RC-ZS-PCV-456A Valve Position Switch LD3 C-F-3-Z RC-E4A-FU11,12 30 A Fuses E4A CB-F-1A-A EDE-TBX-X56 Terminal Box X56 C-F-3-Z EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A RC-CS-456A-1 Control Switch with Indication F31 CB-F-3A-A RC-PY-405CX Auxiliary Relay FB1 CB-F-3A-A RC-TY-413KK Auxiliary Relay FB1 CB-F-3A-A RC-PY-455EX Auxiliary Relay FB1 CB-F-3A-A RC-PY-458BX Auxiliary Relay FB1 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -6 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 RC-PCV-456B RC-E-10 Pressurizer Relief Control Valve RC-20846 B 310581 C-F-3-Z X X X - LD4 RC-E88/19-72 125 V DC Circuit Breaker E88 CB-F-1B-A E88-E4C/7 E4C-J3P GZ0-J3P GZ0-H39 G5Y-J3P H24-J3P H24-LD4 H39-X35 LD4-X35 F31-FT0/2 F31-GZ0/2 E4C-GZ0/2 F31-G5Y/1 310882 E88/19a E88/19c E88/19d CBA-FN-32 CBA-FN-33 EDE-PP-112B RC-PCV-456A or RC-V-124 RC-CS-456B-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-456-B1 Selector Switch GZ0 CB-F-1B-A RC-SS-456-B2 Selector Switch G5Y DG-F-2B-A RC-J3P-42 Auxiliary Relay J3P DG-F-2B-A RC-PCV-456B-20 Solenoid Operating Coil LD4 C-F-3-Z RC-ZS-PCV-456B Valve Position Switch LD4 C-F-3-Z RC-E4C-FU19,20 30 A Fuses E4C CB-F-1B-A EDE-TBX-X35 Terminal Box X35 C-F-3-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-CS-456B-1 Control Switch with Indication F31 CB-F-3A-A EDE-FT0-KA7 Auxiliary Relays Isolation Cabinet FT0 CB-F-3A-A RC-E4C-FU-23,24 30 A Fuses E4C CB-F-1B-A 8 RC-TK11 Pressurizer Relief Tank RC-20846 A/B 310577 C-F-1-Z X X - - - - - - - - - None Note 1 9 RC-V-323 Reactor Vessel Venting Valve RC-20485 B 310581 C-F-3-Z X X X - VB2 RC-BV9-42-1,2 Starter BV9 CB-F-1B-A BV9-F31 310882 BV9a BV9c BV9d RC-FV-2881 RC-BV9-49-1,2 Overload Relays BV9 CB-F-1B-A RC-CS-2885 Control Switch with Indication F31 CB-F-3A-A BV9-H41 F31-H41/2 H41-VB2 H41-VB2/1 RC-V-323 Valve Position and Open/Close Torque Switches VB2 C-F-3-Z EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A 10 RC-FV-2881 Reactor Vessel Venting Valve RC-20845 B 310581 C-F-3-Z X X X - U04 RC-CS-2881 Control Switch with Indication F31 CB-F-3A-A F31-GN0 F31-G5Y F31-H41/1 H41-U04 310882 E88/1g E88/1e E88/1d E88/1f RC-V-323 RC-SS-2881 Selector Switch G5Y CB-F-1B-A RC-GN0-R7 Auxiliary Relay EDE-CP-249 GN0 CB-F-1B-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A H39-U04 F26-H39 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -7 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 RC-LCV-459 Letdown Isolation Valve RC-20843 A 310577 C-F-1-Z X X X X L99 RC-SS-459 Selector Switch G5X DG-F-2A-A F40-FB1/2 F40-G5X F40-H36 GE5-H36/2 GE5-LH2/1 GE5-L99 L99-LH2 310882 E89/17a E89/17c E89/17d RC-LCV-460 CS-V-145 CS-ZS-V-145 Position Switch LH2 C-F-1-Z RC-CS-459 Control Switch with Indication F40 CB-F-3A-A RC-LY/459-CX1 Auxiliary Relay Auxiliary Rack No. 1 FB1 CB-F-3A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z ET-F-1A-A 12 RC-LCV-460 Letdown Isolation Valve RC-20843 A 310577 C-F-1-Z X X X X LF7 RC-CS-460 Control Switch with Indication F40 CB-F-3A-A F40-FB1 F40-H36/1 F40-H36/3 GE4-H36 GE4-LH2 GE4-LF7/1 310882 E89/1b E89/1d E89/1e E89/1f RC-V-459 CS-V-145 CS-ZS-V-145 Position Switch LH2 C-F-1-Z RC-LY/460-DX1 Auxiliary Relay Auxiliary Rack No. 1 FB1 CB-F-3A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -8 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 CS-P-2A Charging Pump CS-20725 A 310764 PAB-F-1C-A X X X - M17 CS-A62-52 4160 V AC Circuit Breaker A62-M17 A62-P01 A62-F41 A62-F41/2 A62-HR2 F41-FB7 F10-F41 310891 A62a A62h A62b A62c A62d CBA-FN-19 CBA-FN-20 EAH-FN-5A EDE-SWG-5 CS-P-2B CS-CS-7424-2 Control Switch A62 CB-F-1A-A CS-SS-7424 Selector Switch A62 CB-F-1A-A CS-A62-86 Lockout Relay A62 CB-F-1A-A CS-A62-52H Truck Operated Contact A62 CB-F-1A-A CS-A62-50/51 Inst./Time Over Current Relays Øa, ØC A62 CB-F-1A-A CS-PS-7467-1 Pressure Switch P01 PAB-F-1C-A CS-A62-AM Ammeter A62 CB-F-1A-A CS-A62-AS Ammeter Switch A62 CB-F-1A-A CS-A62-CT Current Transformer (100/5) A62 CB-F-1A-A CS-A62-TD1 CT Test Device A62 CB-F-1A-A CS-A62-ATR Transducer A62 CB-F-1A-A CS-A62-TD2 Lockout Relay Test Device A62 CB-F-1A-A CS-A62-TDR Timing Relay A62 CB-F-1A-A CS-A62-FU Fuses A62 CB-F-1A-A CS-A62-52Z Timing Relay A62 CB-F-1A-A CS-A62-G,R,W Indicating Lights A62 CB-F-1A-A CS-A62-51GS Ground Sensor Relay A62 CB-F-1A-A CS-CS-7424-1 Control Switch with Indication F41 CB-F-3A-A CS-FB7-K616A Auxiliary Relay SSPS 'A' CAB FB7 CB-F-3A-A CS-HR2-RM0,PR1 Emergency Power Sequencer Auxiliary Relays HR2 CB-F-1A-A CS-HR9-R2X Emergency Power Sequencer Auxiliary Relays HR9 CB-F-1A-A CS-ZL-7424-2 Indicating Light F10 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -9 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 14 CS-P-2B Charging Pump CS-20725 B 310764 PAB-F-1D-A X X X - M18 CS-A82-52 4160 V AC Circuit Breaker A82 CB-F-1B-A A82-M18 A82-P02 A82-F48/1 A82-F48/2 A82-HR4 F48-FB0 F10-F48 310891 A82a A82h A82b A82c A82d CBA-FN-32 CBA-FN-33 EAH-FN-5B EDE-SWG-6 CS-P-2A CS-CS-7425-2 Control Switch A82 CB-F-1B-A CS-SS-7425 Selector Switch A82 CB-F-1B-A CS-A82-86 Lockout Relay A82 CB-F-1B-A CS-A82-52H Truck Operated Contact A82 CB-F-1B-A CS-A82-50/51 Inst./Time Over Current Relays øA, øB A82 CB-F-1B-A CS-PS-7468-1 Pressure Switch P02 PAB-F-1D-A CS-A82-AM Ammeter A82 CB-F-1B-A CS-A82-AS Ammeter Switch A82 CB-F-1B-A CS-A82-CT Current Transformer (100/5) A82 CB-F-1B-A CS-A82-TD1 CT Test Device A82 CB-F-1B-A CS-A82-ATR Transducer A82 CB-F-1B-A CS-A82-TD2 Lockout Relay Test Device A82 CB-F-1B-A CS-A82-TDR Timing Relay A82 CB-F-1B-A CS-A82-FU Fuses A82 CB-F-1B-A CS-A82-52Z Timing Relay A82 CB-F-1B-A CS-A82-G,R,W Indicating Lights A82 CB-F-1B-A CS-A82-51GS Ground Sensor Relay A82 CB-F-1B-A CS-CS-7425-1 Control Switch with Indication F41 CB-F-3A-A CS-FB0-K616B Auxiliary Relay SSPS 'A' CAB FB0 CB-F-3A-A CS-HR4-RM0,PR1 Emergency Power Sequencer Auxiliary Relays HR4 CB-F-1B-A CS-A82-R2 Auxiliary Relay A82 CB-F-1B-A CS-HR0-R2X Emergency Power Sequencer Auxiliary Relays HR0 CB-F-1B-A CS-ZL-7425-2 Indicating Light F10 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -10 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 CS-V-142 Charging Line Isolation Valve CS-20722 A 310769 PP-F-1A-Z X X X - V12 CS-B82-52 460 V AC Circuit Breaker B82 CB-F-1A-A B82-G2G B82-G2G/1 B82-V12 B82-V12/1 F41-FB7/1 F41-G2G/4 F41-G2G/5 310891 B82a B82c B82d CBA-FN-19 CBA-FN-20 EAH-FN-5A EDE-MCC-512 CS-V-143 or CS-HCV-182 CS-CS-7410-2 Control Switch with Indication G2G CB-F-1A-A CS-SS-7410 Selector Switch G2G CB-F-1A-A CS-B82-42/0,C Motor Starters B82 CB-F-1A-A CS-B82-49 Overload Relay B82 CB-F-1A-A CS-ZS-V142 Valve Position and Open/Close Torque Switches V12 PP-F-1A-Z CS-B82-FU Fuse B82 CB-F-1A-A CS-CS-7410-1 Control Switch with Indication F41 CB-F-3A-A CS-FB7-K601A Auxiliary Relay SSPS 'A' CAB FB7 CB-F-3A-A 16 CS-V-143 Charging Line Isolation Valve CS-20722 B 310769 PP-F-1A-Z X X X - V11 CS-B87-52 460 V AC Circuit Breaker B87 CB-F-1B-A B87-G2J B87-G2J/1 B87-V11 B87-V11/1 F48-FB0/3 F48-G2J/2 F48-G2J/3 310891 B87a B87c B87d CBA-FN-32 CBA-FN-33 EAH-FN-5B EDE-MCC-612 CS-V-142 or CS-HCV-182 CS-CS-7411-2 Control Switch with Indication G2J CB-F-1B-A CS-SS-7411 Selector Switch G2J CB-F-1B-A CS-B87-42/0,C Motor Starters B87 CB-F-1B-A CS-B87-49 Overload Relay B87 CB-F-1B-A CS-ZS-V143 Valve Position and Open/Close Torque Switches V11 PP-F-1A-Z CS-B87-FU Fuse B87 CB-F-1B-A CS-CS-7411-1 Control Switch with Indication F41 CB-F-3A-A CS-FB0-K601B Auxiliary Relay SSPS 'A' CAB FB0 CB-F-3A-A 17 RC-P-1A Reactor Coolant Pump RC-20841 A 310576 310582 310578 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M01 RC-A05-52 13.8 kV Circuit Breaker A05 NES-F-1A-Z 310882 A05a A05g A05b A05h A05c A05d A05i None ED-E97-72 125 V DC Circuit Breaker E97 NES-F-1A-Z A05-F31/2 ED-SWG-1 RC-A05-FU Fuses (Trip Circuit) A05 NES-F-1A-Z RC-CS-7300 Control Switch with Indication F31 CB-F-3A-A 18 RC-P-1B Reactor Coolant Pump RC-20842 A 310576 310582 310578 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M02 RC-A20-52 13.8 kV Circuit Breaker A20 NES-F-1A-Z 310882 A20a A20g None ED-E97-72 125 V DC Circuit Breaker E97 NES-F-1A-Z A20-F31/2 ED-SWG-1 RC-A20-FU Fuses (Trip Circuit) A20 NES-F-1A-Z A20b A20K A20c A20d A20i RC-CS-7304 Control Switch with Indication F31 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -11 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 RC-P-1C Reactor Coolant Pump RC-20843 A 310577 310583 310579 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M03 RC-A09-52 13.8 kV Circuit Breaker A09 NES-F-1A-Z 31088 None ED-E91-72 125 V DC Circuit Breaker E91 TB-F-1A-Z A09-F38/2 A09a A09g ED-SWG-2 RC-A09-FU Fuses (Trip Circuit) A09 NES-F-1A-Z A09b A09h A09c A09d A09i RC-CS-7306 Control Switch with Indication F31 CB-F-3A-A 20 RC-P-1D Reactor Coolant Pump RC-20844 A 310577 310583 310579 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M04 RC-A24-52 13.8 kV Circuit Breaker A24 NES-F-1A-Z 310882 A24a A24g None ED-E91-72 125 V DC Circuit Breaker E91 TB-F-1A-Z A24-F31/2 ED-SWG-2 RC-A24-FU Fuses (Trip Circuit) A24 NES-F-1A-Z A24b A24h A24c A24d A24i RC-CS-7308 Control Switch with Indication F31 CB-F-3A-A 21 RC-V-22 RC-E-11A Hot Leg -RHR Isolation Valve RC-20841 B 310582 C-F-1-Z - X X - V27 RC-B54-52-1 460 V AC Circuit Breaker B54 CB-F-1B-A 310882 B54a B54c B54d RC-V-23 Note 4 7 and 8 22 RC-V-23 RC-E-11A Hot Leg -RHR Isolation Valve RC-20841 A 310576 C-F-1-Z - X X - V25 RC-B53-52-1 460 V AC Circuit Breaker B52 CB-F-1A-A 310882 B53a B53c B53d RC-V-22 Note 4, 7 and 8 23 RC-V-87 RC-E-11D Hot Leg -RHR Isolation Valve RC-20844 B 310582 C-F-1-Z - X X - V26 RC-B61-52-1 460 V AC Circuit Breaker B61 CB-F-1B-A 310882 B61a B61c B61d RC-V-88 Note 4, 7 and 8 24 RC-V-88 RC-E-11D Hot Leg -RHR Isolation Valve RC-20844 A 310577 C-F-1-Z - X X - V28 RC-B62-52-1 460 V AC Circuit Breaker B62 CB-F-1A-A 310882 B62a B62c B62d RC-V-87 Note 4, 7 and 8 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -12 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 25 SI-V-3 Accumulator TK -9A Outlet Isolation Valve SI-20450 A 310576 C-F-1-Z - X X - V39 SI-B35-52-1,2 460 V AC Circuit Breakers B35 CB-F-1A-A B35-G81 B35-H19 B35-H36 H19-V39 H36-V39 F20-FB7/5 F20-G81/1 310890 B35a B35c CBA-FN-19 CBA-FN-20 EDE-MCC-522 SI-FV-2475 SI-FV-2476 SI-B35-FU Fuse B35 CB-F-1A-A SI-CS-2403-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2403 Selector Switch G81 CB-F-1A-A SI-ZL-2403-4 Pilot Light G81 CB-F-1A-A SI-B35-42/0,C Motor Starters B35 CB-F-1A-A SI-B35-49 Overload Relay B35 CB-F-1A-A SI-ZS-V3 Valve Position and Open/Close Torque Switches V39 C-F-1-Z EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SI-FB7-K603A,K621A Auxiliary Relays FB7 CB-F-3A-A SI-CS-2403-1 Control Switch F20 CB-F-3A-A SI-EH9/9-52 120 V AC Circuit Breaker EH9 CB-F-1A-A G81-H35/5 G81-H36/6 H35-V41/1 H36-V39/1 E4H-EH9 E4H-G81 F20-G81 EH9/9a EH9/9b CBA-FN-19 CBA-FN-20 EDE-PP-1E SI-CS-2403-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2403 Selector Switch G81 CB-F-1A-A SI-ZS-V3 Valve Position and Open/Close Torque Switches V39 C-F-1-Z SI-E4H-FU7,8 30 A Fuses E4H CB-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SI-CS-2403-1 Control Switch with Indication F20 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -13 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 26 SI-V-17 Accumulator TK -9B Outlet Isolation Valve SI-20450 B 310576 C-F-1-Z - X X - V40 SI-B36-52-1,2 460 V AC Circuit Breakers B36 CB-F-1B-A B36-GZ0 B36-H15 B36-H41 H15-V40 H41-V40 F20-FB0/6 F20-GZ0/1 310890 B36a B36c CBA-FN-32 CBA-FN-33 EDE-MCC-622 SI-FV-2482 SI-FV-2483 SI-B36-FU Fuse B36 CB-F-1B-A SI-CS-2413-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2413 Selector Switch GZ0 CB-F-1B-A SI-ZL-2413-4 Pilot Light GZ0 CB-F-1B-A SI-B36-42/0,C Motor Starters B36 CB-F-1B-A SI-B36-49 Overload Relay B36 CB-F-1B-A SI-ZS-V17 Valve Position and Open/Close Torque Switches V40 C-F-1-Z EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A SI-FB0-K603B,K621B Auxiliary Relays FB0 CB-F-3A-A SI-CS-2413-1 Control Switch with Indication F20 CB-F-3A-A SI-EH0/9-52 120 V AC Circuit Breaker EH0 CB-F-1B-A GZ0-H39/5 GZ0-H41/4 H39-V42/1 H41-V40/1 E4J-EH0 E4J-GZ0 F20-GZ0 EH0/9a EH0/9b EH0/9c CBA-FN-32 CBA-FN-33 EDE-PP-1F SI-CS-2413-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2413 Selector Switch GZ0 CB-F-1B-A SI-ZS-V17 Valve Position and Open/Close Torque Switches V40 C-F-1-Z SI-E4J-FU7,8 30 A Fuses E4J CB-F-1B-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A SI-CS-2413-1 Control Switch with Indication F20 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -14 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 27 SI-V-32 Accumulator TK -9C Outlet Isolation Valve SI-20450 A 310577 C-F-1-Z - X X - V41 SI-B37-52-1,2 460 V AC Circuit Breakers B37 CB-F-1A-A B37-G81 B37-H18 B37-H35 H18-V41 H35-V41 F20-FB7/6 F20-G81/2 310890 B37a B37c CBA-FN-19 CBA-FN-20 EDE-MCC-522 SI-FV-2477 SI-FV-2486 SI-B37-FU Fuse B37 CB-F-1A-A SI-CS-2423-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2423 Selector Switch G81 CB-F-1A-A SI-ZL-2423-4 Pilot Light G81 CB-F-1A-A SI-B37-42/0,C Motor Starters B37 CB-F-1A-A SI-B37-49 Overload Relay B37 CB-F-1A-A EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-Z SI-ZS-V32 Valve Position and Open/Close Torque Switches V41 C-F-1-Z SI-FB7-K608A,K621A Auxiliary Relays FB7 CB-F-3A-A SI-CS-2423-1 Control Switch with Indication F20 CB-F-3A-A SI-EH9/9-52 120 V AC Circuit Breaker EH9 CB-F-1A-A G81-H35/5 G81-H36/6 H35-V41/1 H36-V39/1 E4H-EH9 E4H-G81 F20-G81 EH9/9a EH9/9b EH9/9c CBA-FN-19 CBA-FN-20 EDE-PP-1E SI-CS-2423-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2423 Selector Switch G81 CB-F-1A-A SI-ZS-V32 Valve Position and Open/Close Torque Switches V41 C-F-1-Z SI-E4H-FU7,8 30 A Fuses E4H CB-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A F20-G81 SI-CS-2423-1 Control Switch with Indication F20 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -15 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 28 SI-V-47 Accumulator TK -9D Outlet Isolation Valve SI-20450 B 310577 C-F-1-Z - X X - V42 SI-B38-52-1,2 460 V AC Circuit Breakers B38 CB-F-1B-A B38-GZ0 B38-H24 B38-H39 H24-V42 H39-V42 F20-FB0/7 F20-GZ0/2 310890 B38a B38c CBA-FN-32 CBA-FN-33 EDE-MCC-622 SI-FV-2495 SI-FV-2496 SI-B38-FU Fuse B38 CB-F-1B-A SI-CS-2433-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2433 Selector Switch GZ0 CB-F-1B-A SI-ZL-2433-4 Pilot Light GZ0 CB-F-1B-A SI-B38-42/0,C Motor Starters B38 CB-F-1B-A SI-B38-49 Overload Relay B38 CB-F-1B-A SI-ZS-V47 Valve Position and Open/Close Torque Switches V42 C-F-1-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A SI-FB0-K608B,K621B Auxiliary Relays FB0 CB-F-3A-A SI-CS-2433-1 Control Switch with Indication F20 CB-F-3A-A SI-EH0/9-52 120 V AC Circuit Breaker EH0 CB-F-1B-A GZ0-H39/5 GZ0-H41/4 H39-V42/1 H41-V40/1 E4J-EH0 E4J-GZ0 F20-GZ0 EH0/9a EH0/9b EH0/9c CBA-FN-32 CBA-FN-33 EDE-PP-1F SI-CS-2433-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2433 Selector Switch GZ0 CB-F-1B-A SI-ZS-V47 Valve Position and Open/Close Torque Switches V42 C-F-1-Z SI-E4J-FU7,8 30 A Fuses E4J CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A SI-CS-2433-1 Control Switch with Indication F20 CB-F-3A-A 29 CS-P-2A Charging Pump Lube Oil Cooler CS-20725 A 310764 805213 PAB-F-1C-A X X - - - - - - - - - - Component Cooling CS-P-2B Note 9 30 CS-P-2B Charging Pump Lube Oil Cooler CS-20725 B 310764 815214 PAB-F-1D-A X X - - - - - - - - - - Component Cooling CS-P-2A Note 9 31 CS-V-460 SI-P-6A Suction Valve CS-20725 A 310761 RHR-F-2B-Z - X X - V59 CS-B44-42/0,C Motor Starters B44 CB-F-1A-A B44-F10 B44-V59/1 B44-V59/2 310891 B44a B44c CS-V-475 CS-B44-49 Overload Relays B44 CB-F-1A-A CS-ZS-V460 Limit Switches and Open/Close Torque Switches V59 RHR-2B-Z CS-CS-2442 Control Switch with Indication F10 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -16 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 32 CS-V-461 SI-P-6A Suction Valve CS-20725 B 310761 RHR-F-2B-Z - X X - V60 CS-B45-42/0,C Motor Starters B45 CB-F-1B-A B45-F10 B45-V60/1 B45-V60/2 310891 B45a B45c None CS-B45-49 Overload Relays B45 CB-F-1B-A CS-ZS-V461 Limit Switches and Open/Close Torque Switches V60 RHR-2B-Z CS-CS-2452 Control Switch with Indication F10 CB-F-3A-A 33 CS-V-167 RC Pump Seal Water Isolation Valve CS-20726 A 310769 PP-F-5B-Z X X X - V05 CS-B73-42/0,C Motor Starters B73 CB-F-1A-A B73-F41 B73-V05/1 B73-V05/2 FB7-FC1/9 F41-FC1 310891 B73a B73c CS-V-10 CS-V-28 CS-V-44 CS-V-59 CS-V-175 CS-V-176 CS-B73-49 Overload Relays B73 CB-F-1A-A CS-ZS-V167 Limit Switches and Open/Close Torque Switches V05 PP-F-5B-Z CS-CS-7405 Control Switch with Indication F41 CB-F-3A-A CS-FC1-K802A Auxiliary Relay MM-CP-14 FC1 CB-F-3A-A CS-FB7-K631A Auxiliary Relay MM-CP-12 FB7 CB-F-3A-A 34 CS-V-168 RC Pump Seal Water Isolation Valve CS-20726 B 310577 C-F-1-Z X X X - V06 CS-B72-42-1,2 Motor Starters B72 CB-F-1B-A B72-H39 B72-F48 FB0-FC2/9 H39-V06 F48-FC2 310891 B72a B72c CS-V-10 CS-V-28 CS-V-44 CS-V-59 CS-V-175 CS-V-176 CS-B72-49-1,2 Overload Relays B72 CB-F-1B-A CS-CS-7404 Control Switch with Indication F41 CB-F-3A-A CS-ZS-V168 Limit Switches and Open/Close Torque Switches V06 C-F-1-Z CS-FC2-K802B Auxiliary Relay MM-CP-15 FC2 CB-F-3A-A CS-FB0-K631B Auxiliary Relay MM-CP-13 FB0 CB-F-3A-A CS-ED0-R1 Auxiliary Relay EDE-MCC-E612 ED0 CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A 35 CS-V-175 Excess Letdown Isolation Valve CS-20722 B 310577 C-F-1-Z X X X X L95 CS-ZS-V175 Valve Position Switch L95 C-F-1-Z F48-H39/2 GE5-H39/1 310891 E95/2a E95/2c E95/2d CS-V-176 Note 2 CS-CS-7418 Control Switch with Indication F41 CB-F-3A-A CS-FY-7418 Solenoid Valve GE5 C-F-1-Z EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A 36 CS-V-176 Excess Letdown Isolation Valve CS-20722 B 310577 C-F-1-Z X X X X LA5 CS-ZS-V176 Valve Position Switch LA5 C-F-1-Z F48-H39/1 GE5-H39/5 GE5-LA5/1 310891 E95/4a E95/4d E95/4b E95/4e E95/4f CS-V-175 Note 2 CS-FX-7417 Control Switch with Indication F41 CB-F-1A-A CS-FY-7417 Solenoid Valve GE5 C-F-1-Z EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -17 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 37 CS-V-196 Charging Pump Miniflow Isolation Valve CS-20725 A 310762 PAB-F-1J-Z X X X - V13 CS-B81-42/0,C Motor Starters B81 CB-F-1A-A B81-F41 B81-F41/1 B81-V13/1 F41-FB7/2 F41-FK0 B81-V13/2 310891 B81a B81c CS-V-197 CS-B81-49 Overload Relays B81 CB-F-1A-A CS-ZS-V196 Limit Switch and Open/Close Torque Switches V13 PAB-F-1J-Z CS-CS-7421 Control Switch with Indication F41 CB-F-3A-A CS-FYY-7325 Auxiliary Relay MM-CP-297A FK0 CB-F-3A-A CS-FB7-K603A Auxiliary Relay MM-CP-12 FB7 CB-F-3A-A 38 CS-V-197 Charging Pump Miniflow Isolation Valve CS-20725 B 310762 PAB-F-1J-Z X X X - V14 CS-B86-42/0,C Motor Starters B86 CB-F-1B-A B86-F48 B86-F48/1 B86-V14/1 B86-V14/2 F48-FB0/2 F48-FL2 310891 B86a B86c B86d CS-V-196 CS-B86-49 Overload Relays B86 CB-F-1B-A CS-ZS-V197 Limit Switch and Open/Close Torque Switches V14 PAB-F-1J-Z CS-CS-7422-1 Control Switch with Indication F41 CB-F-3A-A CS-FYY-7326 Auxiliary Relay MM-CP-297B FL2 CB-F-3A-A CS-FB0-K603B Auxiliary Relay MM-CP-13 FB0 CB-F-3A-A CS-CS-7422-2 Control Switch ED0 CB-F-1B-A CC-SS-7422 Selector Switch ED0 CB-F-1B-A 39 CS-LCV-112B Chemical and Volume Control Tank Outlet Isolation Valve CS-20725 A 310768 PAB-F-3B-Z X X X - VE4 CS-B50-52 460 V AC Circuit Breaker B50 CB-F-1A-A B50-G2G B50-G2G/1 B50-VE4 B50-VE4/1 B50-VE4/2 F40-FB7 F40-G2G F40-G2G/1 B50-VE6 B50-E3P E3P-G2G 310891 B50a B50c B50d B50f CBA-FN-19 CBA-FN-20 EDE-MCC-512 CS-LCV-112C CS-B50-FU Fuse B50 CB-F-1A-A CS-CS-112B-2 Control Switch with Indication G2G CB-F-1A-A CS-SS-112B Selector Switch G2G CB-F-1A-A CS-B50-42/0,C Motor Starters B50 CB-F-1A-A CS-B50-49 Overload Relay B50 CB-F-1A-A CS-ZS-LCV-112B Valve Position and Open/Close Torque Switches VE4 PAB-F-3B-Z CS-EC8-R1 Auxiliary Relay EC8 CB-F-1A-A CS-CS-112B-1 Control Switch with Indication F41 CB-F-3A-A CS-FB7-K701A, K602A,K706A Auxiliary Relays MM-CP-12 FB7 CB-F-3A-A CS-ZS-LCV-112D Valve Position Switch VE6 TF-F-1-0 CS-E3P-R2 Auxiliary Relay E3P CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -18 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 40 CS-LCV-112C Chemical and Volume Control Tank Outlet Isolation Valve CS-20725 B 310768 PAB-F-3B-Z X X X - VE7 CS-B83-52 460 V AC Circuit Breaker B83 CB-F-1B-A B83-G2J B83-G2J/1 B83-VE7 B83-VE7/1 B83-VE7/2 B83-VE5/1 F48-FB0/1 F48-G2J/4 F48-G2J/5 B83-E3Q E3Q-G2J 310891 B83a B83c B83d B83f CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-LCV-112B CS-B83-FU Fuses B83 CB-F-1B-A CS-CS-112C-2 Control Switch with Indication G2J CB-F-1B-A CS-SS-112C Selector Switch G2J CB-F-1B-A CS-B83-42/0,C Motor Starters B83 CB-F-1B-A CS-B83-49 Overload Relay B83 CB-F-1B-A CS-ZS-LCV-112C Valve Position and Open/Close Torque Switches VE7 PAB-F-3B-Z CS-ED0-R1 Auxiliary Relay ED0 CB-F-1B-A CS-CS-112C-1 Control Switch with Indication F41 CB-F-3A-A CS-FB0-K701B, K602B,K706B Auxiliary Relays MM-CP-13 FB0 CB-F-3A-A CS-ZS-LCV-112E Valve Position Switch VE5 TF-F-1-0 CS-E3Q-R2 Auxiliary Relay E3Q CB-F-1B-A 41 CS-LCV-112D Refueling Water Storage Tank to Charging Pump 2A Isolation Valve CBS-20233 A 301254 TF-F-1-0 X X X - VE6 CS-B78-52 460 V AC Circuit Breaker B78 CB-F-1A-A B78-G2G B78-G2G/1 B78-VE6 B78-VE6/1 B78-VE6/2 F10-FB7/4 F10-G2G/2 F10-G2G/3 B78-E3P/1 310891 B78a B78c B78d B78f CBA-FN-19 CBA-FN-20 EDE-MCC-512 CS-LCV-112E CS-CS-112D-2 Control Switch with Indication G2G CB-F-1A-A CS-SS-112D Selector Switch G2G CB-F-1A-A CS-B78-42/0,C Motor Starters B78 CB-F-1A-A CS-B78-49 Overload Relay B78 CB-F-1A-A CS-ZS-LCV-112D Valve Position and Open/Close Torque Switches VE6 TF-F-1-0 CS-EC8-R1 Auxiliary Relay EC8 CB-F-1A-A CS-B78-FU Fuse B78 CB-F-1A-A CS-FB7-K701A, K602A, K706A Auxiliary Relays MM-CP-12 FB7 CB-F-3A-A CS-CS-112D-1 Control Switch with Indication F10 CB-F-3A-A CS-SS-112D-1 Selector Switch F10 CB-F-3A-A CS-E3P-R0 Auxiliary Relay E3P CB-F-1A-A CS-ZS-112-C-1 Valve Position Switch VE7 PAB-F-3B-Z B78-E2P B78-VE6/1 VE4-VE6 VE4-VE7 (non-CASP) E3E/3a E3E/3b CS-E3P-R0 Auxiliary Relay E3P CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -19 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 42 CS-LCV-112E RWST CBS-TK-8 to Charging Pump 2B Isolation Valve CBS-20233 B 301254 TF-F-1-0 X X X - VE5 CS-B79-52 460 V AC Circuit Breaker B79 CB-F-1B-A B79-G2J B79-G2J/1 B79-VE5 B79-VE5/1 B79-VE5/2 F10-FB0/4 F10-G2J/2 F10-G2J/3 B79-E3Q/1 310891 B79a B79c B79d B79f CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-LCV-112D CS-CS-112E-2 Control Switch with Indication G2J CB-F-1B-A CS-SS-112E Selector Switch G2J CB-F-1B-A CS-B79-42/0,C Motor Starters B79 CB-F-1B-A CS-B79-49 Overload Relay B79 CB-F-1B-A CS-ZS-LCV-112E Valve Position and Open/Close Torque Switches VE5 TF-F-1-0 CS-ED0-R1 Auxiliary Relay ED0 CB-F-1B-A CS-B79-FU Fuse B79 CB-F-1B-A CS-FB0-K701B, K602B, K706B Auxiliary Relays MM-CP-13 FB0 CB-F-3A-A CS-CS-112E-1 Control Switch with Indication F10 CB-F-3A-A CS-SS-112E-1 Selector Switch F10 CB-F-3A-A CS-E3Q-R0 Auxiliary Relay E3Q CB-F-1B-A CS-ZS-112-B-1 Valve Position Switch VE4 PAB-F-3B-Z B79-E2Q B79-VE5//1 VE5-VE7 VE4-VE7/1 (non-CASP) E3F/3a E3F/3b CS-E3Q-R0 Auxiliary Relay E3Q CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -20 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 43 SI-V-138 Charging Pump To Cold Leg Isolation Valve SI-20447 A 310769 PP-F-1B-Z X X X - V31 SI-B31-52 460 V AC Circuit Breaker B31 CB-F-1A-A B31-G2G B31-G2G/2 B31-V31 B31-V31/1 B31-V31/2 F10-FB7 F10-G2G/4 F10-G2G/5 F10-FC1 F10-FN8 F10-FB7/9 B31-FN8 B31-FN8/1 310890 B31a B31c B31d CBA-FN-19 CBA-FN-20 EDE-MCC-521 SI-V-139 or CS-FCV-121 SI-CS-2437-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2437 Selector Switch G81 CB-F-1A-A SI-SS-2437-1 Selector Switch FN8 ET-F-1B-A MSO-5 Auxiliary Relay FN8 ET-F-1B-A SI-B31-42/0,C Motor Starters B31 CB-F-1A-A SI-B31-49 Overload Relay B31 CB-F-1A-A SI-ZS-V138 Valve Position and Open/Close Torque Switches V31 PP-F-1B-Z SI-B31-FU Fuse B31 CB-F-1A-A SI-FB7-K616A Auxiliary Relays MM-CP-12 FB7 CB-F-3A-A SI-CS-2437-1 Control Switch with Indication F10 CB-F-3A-A SI-FC1-K801A Auxiliary Relay MM-CP-14 FC1 CB-F-3A-A SI-FC1-W Indicating Light FC1 CB-F-3A-A SI-FC1-RES Resistor FC1 CB-F-3A-A 44 SI-V-139 Charging Pump To Cold Leg Isolation Valve SI-20447 B 310769 PP-F-1B-Z X X X - V32 SI-B32-52 460 V AC Circuit Breaker B32 CB-F-1B-A B32-G2J B32-G2J/2 B32-V32 B32-V32/1 B32-V32/2 F10-FB0 F10-G2J/4 F10-G2J/5 F10-FC2 F10-FB0/A F10-FN9 B32-FN9 B32-FN9/1 310890 B32a B32c B32d CBA-FN-32 CBA-FN-33 EDE-MCC-621 SI-V-138 or CS-FCV-121 SI-CS-2447-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2447 Selector Switch GZ0 CB-F-1B-A SI-SS-2447-1 Selector Switch FN9 ET-F-1D-A MSO-5 Auxiliary Relay FN9 ET-F-1D-A SI-B32-42/0,C Motor Starters B32 CB-F-1B-A SI-B32-49 Overload Relay B32 CB-F-1B-A SI-ZS-V139 Valve Position and Open/Close Torque Switches V32 PP-F-1B-Z SI-B32-FU Fuses B32 CB-F-1B-A SI-FB0-K616B Auxiliary Relays MM-CP-13 FB0 CB-F-3A-A SI-CS-2447-1 Control Switch with Indication F10 CB-F-3A-A SI-FC2-K801B Auxiliary Relay MM-CP-15 FC2 CB-F-3A-A SI-FC2-W Indicating Light FC2 CB-F-3A-A SI-FC2-RES Resistor FC2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -21 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 45 RC-E-10 Pressurizer Heaters Group C RC-20846 A 310598 C-F-1-Z X - X - M26 RC-AG4-52 480 V AC Circuit Breaker AG4 CB-F-1A-A F31-FB1/3 AG4-F31 310882 AG4a AG4b AG4d AG4e AG4f None RC-AG4-FU Fuses AG4 CB-F-1A-A RC-CS-7321 Control Switch with Indication F31 CB-F-3A-A RC-AG4-52H-1 Truck Operated Contact AG4 CB-F-1A-A RC-AG4-G,R Indicating Lights AG4 CB-F-1A-A RC-FB1-LYY-459 EXA High Level Auxiliary Relay FB1 CB-F-3A-A RC-FB1-LYY-459 CXA Low Level Auxiliary Relay FB1 CB-F-3A-A RC-FB1-LYY-460 DXA Low Level Auxiliary Relay FB1 CB-F-3A-A RC-FB1-PYY-455 GXA Low Pressure Auxiliary Relay FB1 CB-F-3A-A 46 RC-E-10 Pressurizer Heaters Group D RC-20846 A 310598 C-F-1-Z X - X - M26 RC-AM5-52 480 V AC Circuit Breaker AM5 CB-F-1A-A F31-FB2/2 AM5-F31 310882 AM5a AM5d AM5b AM5e AM5f None RC-AM5-FU Fuses AM5 CB-F-1A-A RC-AM5-52H-1 Truck Operated Contact AM5 CB-F-1A-A RC-AM5-G,R Indicating Lights AM5 CB-F-1A-A RC-CS-7322 Control Switch with Indication F31 CB-F-3A-A RC-FB2-PYY-455 GXB Low Pressure Auxiliary Relay FB2 CB-F-3A-A RC-FB2-LYY-459 CXB Low Level Auxiliary Relay FB2 CB-F-3A-A RC-FB2-LYY-459 EXB High Level Auxiliary Relay FB2 CB-F-3A-A RC-FB2-LYY-460 DXB Low Level Auxiliary Relay FB2 CB-F-3A-A RC-FB2-LYY-459 CXB Low Level Auxiliary Relay FB2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -22 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 47 CBS-P-9A Containment Spray Pump CBS-20233 A 310761 RHR-F-1B-Z X - X - M15 CBS-A61-52 4160 V AC Circuit Breaker A61 CB-F-1A-A A61-F20/1 A61-F20/2 A61-HR9 F20-FB7/1 HR2-HR9 310900 A61a A61b A61c A61d A61h None CBS-A61-AM Ammeter A61 CB-F-1A-A CBS-A61-AS Ammeter Switch A61 CB-F-1A-A CBS-A61-50/51 Overcurrent Relay A61 CB-F-1A-A CBS-A61-CT Current Transformer (100/5) A61 CB-F-1A-A CBS-CS-2300 Control Switch with Indication F20 CB-F-3A-A CBS-AU2-52S Circuit Breaker Operated Contact AU2 CB-F-1A-A CBS-A61-86 Lockout Relay A61 CB-F-1A-A CBS-A61-G,R,W Indicating Lights A61 CB-F-1A-A CBS-A61-52Z Timing Relay A61 CB-F-1A-A CBS-A61-R1,R2 Auxiliary Relays A61 CB-F-1A-A CBS-FB7-K644A Auxiliary Relay MM-CP-12 FB7 CB-F-3A-A CBS-HR2-RM0 Emergency Power Sequence Relay HR2 CB-F-1A-A CBS-HR9-SR3,LR8 Emergency Power Sequence Relay HR9 CB-F-1A-A CBS-A53-94-1B Bus Undervoltage Trip Relay A53 CB-F-1A-A CBS-A61-TD1 Test Device A61 CB-F-1A-A CBS-A61-TD2 Test Device A61 CB-F-1A-A CBS-A61-52H Truck Operated Contact A61 CB-F-1A-A CBS-A61-CS Control Switch A61 CB-F-1A-A CBS-A61-51GS Ground Sensor Relay A61 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -23 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 48 CBS-P-9B Containment Spray Pump CBS-20233 B 310761 RHR-F-1A-Z X - X - M16 CBS-A81-52 4160 V AC Circuit Breaker A81 CB-F-1B-A A81-F20/1 A81-F20/2 A81-HR0 F20-FB0/1 HR4-HR0 310900 A81a A81b A81c A81d A81h None CBS-A81-AM Ammeter A81 CB-F-1B-A CBS-A81-AS Ammeter Switch A81 CB-F-1B-A CBS-A81-50/51 Overcurrent Relay A81 CB-F-1B-A CBS-A81-CT1 Current Transformer (100/5) A81 CB-F-1B-A CBS-CS-2301 Control Switch with Indication F20 CB-F-3A-A CBS-HR4-RM0 Emergency Power Sequence Relay HR4 CB-F-1B-A CS-HR0-SR3,LR8 Emergency Power Sequence Relay HR0 CB-F-1B-A CBS-AU6-52S Circuit Breaker Operated Contact AU6 CB-F-1B-A CBS-A73-94-1B Bus Undervoltage Trip Relay A73 CB-F-1B-A CBS-FB0-R644B Auxiliary Relay MM-CP-13 FB0 CB-F-3A-A CBS-A81-86 Lockout Relay A81 CB-F-1B-A CBS-A81-G,R,W Indicating Lights A81 CB-F-1B-A CBS-A81-52Z Timing Relay A81 CB-F-1B-A CBS-A81-R1,R2 Auxiliary Relays A81 CB-F-1B-A CBS-A81-TD1 Test Device A81 CB-F-1B-A CBS-A81-TD2 Test Device A81 CB-F-1B-A CBS-A81-52H Truck Operated Contact A81 CB-F-1B-A CBS-A81-CS Control Switch A81 CB-F-1B-A CBS-A81-51GS Ground Sensor Relay A81 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -24 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 49 SI-P-6A Safety Injection Pump SI-20446 A 310761 RHR-F-2B-Z - X X - M09 SI-A56-52 4160 V AC Circuit Breaker A56 CB-F-1A-A A56-F10 F10-FB7/2 A56-F10/2 A56-HR9 310890 A56a A56b A56c A56d A56h None SI-A56-AM Ammeter A56 CB-F-1A-A SI-A56-AS Ammeter Switch A56 CB-F-1A-A SI-A56-50/51 Overcurrent Relay A56 CB-F-1A-A SI-A53-94-1A Bus Undervoltage Trip Relay A53 CB-F-1A-A SI-A56-CT Current Transformer (100/5) A56 CB-F-1A-A SI-CS-2449 Control Switch with Indication F10 CB-F-3A-A SI-FB7-K601A Auxiliary Relay MM-CP-12 FB7 CB-F-3A-A SI-HR9-RM0,SR1 Emergency Power Sequence Relays HR9 CB-F-1A-A SI-A56-TD1 Test Device A56 CB-F-1A-A SI-A56-TD2 Test Device A56 CB-F-1A-A SI-A56-51GS Ground Sensor Relay A56 CB-F-1A-A SI-A56-86 Lockout Relay A56 CB-F-1A-A SI-A56-G,R,W Indicating Lights A56 CB-F-1A-A SI-A56-CS Control Switch A56 CB-F-1A-A SI-A56-52Z Timing Relay A56 CB-F-1A-A SI-A56-52H Truck Operated Contact A56 CB-F-1A-A 50 SI-P-6B Safety Injection SI-20446 B 310761 RHR-F-2A-Z - X X - M10 SI-A76-52 4160 V AC Circuit Breaker A76 CB-F-1B-A A76-F10 F10-FB0/1 A76-F10/2 A76-HR0 310890 A76a A76b A76c A76d A76h None SI-A76-AM Ammeter A76 CB-F-1B-A SI-A76-AS Ammeter Switch A76 CB-F-1B-A SI-A76-50/51 Overcurrent Relay A76 CB-F-1B-A SI-A73-94-1A Bus Undervoltage Trip Relay A73 CB-F-1B-A SI-A76-CT Current Transformer (100/5) A76 CB-F-1B-A SI-CS-2459 Control Switch with Indication F10 CB-F-3A-A SI-FB0-K610B Auxiliary Relay MM-CP-13 FB0 CB-F-3A-A SI-HR0-RM0,SR1 Emergency Power Sequence Relays HR0 CB-F-1B-A SI-A76-TD1 Test Device A76 CB-F-1B-A SI-A76-TD2 Test Device A76 CB-F-1B-A SI-A76-51GS Ground Sensor Relay A76 CB-F-1B-A SI-A76-86 Lockout Relay A76 CB-F-1B-A SI-A76-G,R,W Indicating Lights A76 CB-F-1B-A SI-A76-CS Control Switch A76 CB-F-1B-A SI-A76-52Z Timing Relay A76 CB-F-1B-A SI-A76-52H Truck Operated Contact A76 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -25 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 51 SI-FV-2482 SI-FV-2483 Accumulator TK -9B Relief Valve SI-20450 SI-20450 A A 310578 310578 C-F-2-Z C-F-2-Z - - X X X X - - V3B V3C SI-E4H-FU Fuse E4H CB-F-1A-A E2T-E4H/2 E4H-G81/2 F20-G81/4 F20-G81/5 F20-G81/6 G81-H35/6 G81-H35/7 G81-H36/9 G81-H36/A H35-V3B H35-V3C H36-V3F H36-V3G 310890 E2T/7a E2T/7b E2T/7c E2T/7d E2T/7f E2T/7g E2T/7h EDE-PP-113A SI-V-17 SI-V-47 SI-FV-2495 SI-FV-2496 Accumulator TK -9D Relief Valve SI-20450 SI-20450 A A 310579 310579 C-F-2-Z C-F-2-Z - - X X X X - - V3F V3G SI-SS-2482 Selector Switch G81 CB-F-1A-A SI-CS-2482-1 Control Switch with Indication F20 CB-F-3A-A SI-CS-2482-2 Control Switch with Indication G81 CB-F-1A-A SI-CS-2483 Control Switch with Indication G81 CB-F-1A-A SI-CS-2495-1 Control Switch with Indication F20 CB-F-3A-A SI-CS-2495-2 Control Switch with Indication G81 CB-F-1A-A SI-CS-2496 Control Switch with Indication F20 CB-F-3A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SI-CS-2482-1X Auxiliary Relay F20 CB-F-3A-A SI-CS-2483-X Auxiliary Relay F20 CB-F-3A-A SI-CS-2495-1X Auxiliary Relay F20 CB-F-3A-A SI-CS-2496-X Auxiliary Relay F20 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -26 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 52 SI-FV-2475 SI-FV-2476 Accumulator TK -9A Relief Valves SI-20450 SI-20450 B B 310578 310578 C-F-2-Z C-F-2-Z - - X X X X - - V2Z V3A SI-E4C-FU Fuse E4C CB-F-1B-A E2U-E4C/3 E4C-GZ0/1 F20-GZ0/4 F20-GZ0/5 F20-GZ0/6 GZ0-H39/6 GZ0-H39/7 GZ0-H41/5 GZ0-H41/6 H39-V2Z H39-V3A H41-V3D H41-V3E 310890 E2U/7a E2U/7b E2U/7c E2U/7d E2U/7f E2U/7g E2U/7h EDE-PP-113B SI-V-3 SI-V-32 SI-FV-2477 SI-FV-2486 Accumulator TK -9C Relief Valves SI-20450 SI-20450 B B 310579 310579 C-F-2-Z C-F-2-Z - - X X X X - - V3D V3E SI-SS-2475 Selector Switch GZ0 CB-F-1B-A SI-CS-2475-1 Control Switch with Indication F20 CB-F-3A-A SI-CS-2475-2 Control Switch with Indication GZ0 CB-F-1B-A SI-CS-2476 Control Switch with Indication F20 CB-F-3A-A SI-CS-2477-1 Control Switch with Indication F20 CB-F-3A-A SI-CS-2477-2 Control Switch with Indication GZ0 CB-F-1B-A SI-CS-2486 Control Switch with Indication F20 CB-F-3A-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A SI-CS-2475-1X Auxiliary Relay F20 CB-F-3A-A SI-CS-2476-X Auxiliary Relay F20 CB-F-3A-A SI-CS-2477-1X Auxiliary Relay F20 CB-F-3A-A SI-CS-2486-X Auxiliary Relay F20 CB-F-3A-A 53 CS-V-475 SI-CS-P-6A Suction Cross Connection Valve CS-20725 B 310761 RHR-F-2B-Z - X X - V52 CS-B46-52 460 V AC Circuit Breakers B46 CB-F-1B-A B46-V52 B46-V52/1 B46-V52/2 B46-F10 B46-F10/1 310891 B46a B46c EDE-MCC-612 None CS-B46-CPT Control Power Transformer B46 CB-F-1B-A CS-B46-42/0,C Motor Starter B46 CB-F-1B-A CS-B46-49 Overload Relays B46 CB-F-1B-A CS-B46-FU Fuse B46 CB-F-1B-A CS-CS-2478 Control Switch with Indication F10 CB-F-3A-A 54 CS-FT-121 CS-FCV-121 Pressurizer Level Control - Flow CS-20725 A 310763 310762 PAB-F-1A-Z PAB-F-1J-Z X X X X X X - x S1E S82 CS-FQY-121 Power Supply FA7 CB-F-3A-A FA7-S1E FA7-S42 F41-FA7 F47-FA7 FA7-S82 310891 MM-CP-7 ED-PP-3C Inst. Air SI-V-139 CS-FI-121B Flow Indicator S42 PAB-F-1E-A CS-FY-121A Square Root Extractor FA7 CB-F-3A-A CS-FC-121 Controller FA7 CB-F-3A-A FP55321 310940 Sh. 23 FA7a Sh. 24 Sh. 25 CS-FCY-121 Driver (Auto) FA7 CB-F-3A-A CS-FCY-121A Driver (Manual) FA7 CB-F-3A-A CS-FK-121 Manual/Auto Control Station F41 CB-F-3A-A CS-FY-121C Relays FA7 CB-F-3A-A CS-FB-121A/B Comparator FA7 CB-F-3A-A CS-FI-121A Flow Indicator F41 CB-F-3A-A CS-FY-121B I/D Converter S82 PAB-F-1J-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -27 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 55 SI-V-158 Charging Pump Test Line Isolation Valve SI-20447 B 310577 C-F-1-Z - X X X L89 SI-CS-2416 Control Switch with Indication F26 CB-F-3A-A F26-H39/9 GE5-H39/7 GE5-L89 310890 E88/7f E88/7d E88/7a E88/7e E88/7b E88/7g EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A SI-ZS-V158 Valve Position Switches L89 C-F-1-Z SI-FY-2416 Solenoid Valve GE5 C-F-1-Z None 56 SI-V-159 Charging Pump Test Line Isolation Valve SI-20447 A 310577 C-F-1-Z - X X X L90 SI-CS-2406 Control Switch with Indication F26 CB-F-3A-A F26-H36/5 GE5-H36/5 GE5-L90 310890 E89/4d E89/4g E89/4a E89/4h E89/4b E89/4i E89/4c E89/4j E89/4k None EDE-MM-11 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SI-ZS-V159 Valve Position Switches L90 C-F-1-Z SI-FY-2406 Solenoid Valve GE5 C-F-1-Z 57 CS-HCV-182 Charging Line Control Valve CS-20722 A 310763 PAB-F-1A-Z X X X X - EDE-EH9-52 120 V AC Circuit Breaker EH9 CB-F-1A-A EH9-F20/2 F40-GP5 310105 EH9a EH9b 310891 F41c F41c 310940 EH9/7 EDE-PP-1E Inst. Air CS-V-143 MM-UQ-771A Power Supply F41 CB-F-3A-A CS-HC-182 Manual Controller F41 CB-F-3A-A 58 CS-V-154 RC Pump ID Seal Injection Isolation Valve CS-20726 A 310769 PP-F-5B-Z X X X - V18 CS-CS-7409-1 Control Switch with Indication F41 CB-F-3A-A B77-V18/1 B77-V18/2 B77-F41 B77-F41/1 B77-E3P 310891 B77a B77c CBA-FN-19 CBA-FN-20 EAH-FN-5A SI-V-139 CS-CS-7409-2 Control Switch with Indication B77 CB-F-1A-A CS-SS-7409 Selector Switch B77 CB-F-1A-A CS-B77-42/C Motor Starter B77 CB-F-1A-A CS-B77-49 Overload Relays B77 CB-F-1A-A CS-ZS-V154 Valve Position and Torque Switch V18 PP-F-5B-Z CS-B77-R1 Aux. Relay E3P CB-F-1A-A 59 CS-V-158 RC Pump 1C Seal Injection Isolation Valve CS-20726 A 310769 PP-F-5B-Z X X X - V17 CS-CS-7408-1 Control Switch with Indication F41 CB-F-3A-A B76-V17/1 B76-V17/2 B76-F41 B76-F41/1 B76-E3P 310891 B76a B76c CBA-FN-19 CBA-FN-20 EAH-FN-5A SI-V-139 CS-CS-7408-2 Control Switch with Indication B76 CB-F-1A-A CS-SS-7408 Selector Switch B76 CB-F-1A-A CS-B76-42/0,C Motor Starter B76 CB-F-1A-A CS-B76-49 Overload Relays B76 CB-F-1A-A CS-ZS-V158 Valve Position and Torque Switch V17 PP-F-5B-Z CS-B76-R1 Aux. Relay E3P CB-F-1A-A 60 CS-V-162 PC Pump 1B Seal Injection Isolation CS-20726 A 310769 PP-F-1A-Z X X X - V16 CS-CS-7407-1 Control Switch with Indication F41 CB-F-3A-A B75-V16/1 B75-V16/2 B75-F41 B75-F41/1 310891 B75a B75c CBA-FN-19 CBA-FN-20 EAH-FN-5A SI-V-139 CS-CS-7407-2 Control Switch with Indication B75 CB-F-1A-A CS-SS-7407 Selector Switch B75 CB-F-1A-A CS-B75-42/O,C Motor Starters B75 CB-F-1A-A CS-B75-49 Overload Relays B75 CB-F-1A-A CS-ZS-V162 Valve Position and Torque Switches V16 PP-F-1A-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -28 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 61 CS-V-166 RC Pump 1A Seal Injection Isolation Valve CS-20726 A 310769 PP-F-1A-Z X X X - V15 CS-CS-7406-1 Control Switch with Indication F41 CB-F-3A-A B74-V15/1 B74-V15/2 B74-F41 B74-F41/1 310891 B74a B74c CBA-FN-19 CBA-FN-20 EAH-FN-5A SI-V-139 CS-CS-7406-2 Control Switch with Indication B74 CB-F-1A-A CS-SS-7406 Selector Switch B74 CB-F-1A-A CS-B74-42/0,C Motor Starters B74 CB-F-1A-A CS-B74-49 Overload Relays B74 CB-F-1A-A CS-ZS-V166 Valve Position and Torque Switches V15 PP-F-1A-Z 62 CS-E-5A Seal Water Heat Exchanger CS-20726 A 310764 PAB-F-1A-Z X X - - - - - - - - - - - CS-E-5B Note 1 63 CS-E-5B Seal Water Heat Exchanger CS-20726 A 310764 PAB-F-1A-Z X X - - - - - - - - - - - CS-E-5A Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -29 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 64 CS-V-10 CS-V-28 CS-V-44 CS-V-59 Reactor Coolant Pumps Seal Leakoff Isolation CS-20726 CS-20726 CS-20726 CS-20726 A A A A 310576 310576 310583 310577 C-F-1-Z C-F-1-Z C-F-1-Z C-F-1-Z X X X X X X X X X X X X X X X X LA6 LA7 LA8 LA9 EDE-E89-72 125 V DC Circuit Breakers E89 CB-F-1A-A E89-E4F/1 E4F-F38 F31-H36/2 F38-H36 GA4-H36/4 GA4-LA6/1 GE5-H36/6 GE5-H36/7 GE4-H35/3 GA5-H35/3 F41-H36/3 F38-H35/3 F38-H35/2 GA5-LA7/1 GE4-LA8/1 GE5-LA9/1 GE5-L96/1 GE5-L98/1 310891 E89/7a E89/7e E89/7b E89/7f E89/7c E89/7g ED-PP-122B Inst. Air CS-V-167 CS-V-168 CS-E4F-FU-5,6,7,8 Fuses E4F CB-F-1A-A CS-CS-7400 Control Switch with Indication F31 CB-F-3A-A CS-CS-7400-1X Auxiliary Relay F31 CB-F-3A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A CS-FY-7400 Solenoid Valve GA4 C-F-1-Z CS-ZS-V10 Valve Position Switches LA6 C-F-1-Z CS-CS-7401 Control Switch with Indication F31 CB-F-3A-A CS-CS-7401-1X Auxiliary Relay F31 CB-F-3A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A CS-FY-7401 Solenoid Valve GA5 C-F-1-Z CS-ZS-V28 Valve Position Switches LA7 C-F-1-Z CS-CS-7402 Control Switch with Indication F31 CB-F-3A-A CS-CS-7402-1X Auxiliary Relay F31 CB-F-3A-A CS-FY-7402 Solenoid Valve GE4 C-F-1-Z CS-ZS-V44 Valve Position Switches LA8 C-F-1-Z CS-CS-7403 Control Switch with Indication F31 CB-F-3A-A CS-CS-7403-1X Auxiliary Relay F31 CB-F-3A-A CS-FY-7403 Solenoid Valve GE5 C-F-1-Z CS-ZS-V59 Valve Position Switches LA9 C-F-1-Z CS-CS-7413 Control Switch with Indication F41 CB-F-3A-A CS-FY-7413 Solenoid Valve GE5 C-F-1-Z CS-ZS-V177 Valve Position Switches L96 C-F-1-Z CS-CS-7414 Control Switch with Indication F31 CB-F-3A-A CS-FY-7414 Solenoid Valve GE5 C-F-1-Z CS-ZS-V185 Valve Position Switches L98 C-F-1-Z CS-CS-7403 Control Switch with Indication F31 CB-F-3A-A CS-CS-7403-1X Auxiliary Relay F31 CB-F-3A-A CS-FY-7403 Solenoid Valve GE5 C-F-1-Z CS-ZS-V59 Valve Position Switches LA9 C-F-1-Z CS-CS-7413 Control Switch with Indication F41 CB-F-3A-A CS-FY-7413 Solenoid Valve GE5 C-F-1-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -30 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 64 CS-V-10 CS-V-28 CS-V-44 CS-V-59 (Continued) Reactor Coolant Pumps Seal Leakoff Isolation CS-ZS-V177 Valve Position Switches L96 C-F-1-Z CS-CS-7414 Control Switch with Indication F31 CB-F-3A-A CS-FY-7414 Solenoid Valve GE5 C-F-1-Z CS-ZS-V185 Valve Position Switches L98 C-F-1-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -31 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 65 CS-V-145 Letdown Heat Exchanger E -2 to E-8 Isolation Valve CS-20722 A 310577 C-F-1-Z X X X X LH2 CS-CS-7447 Control Switch with Indication F40 CB-F-3A-A F40-FB1/1 F40-H36/2 GE4-H36/1 GE4-LF7/2 GE5-H36/8 GE5-L99/1 GE5-LH2/3 FB1-F59 310891 E97/11a E97/11g E97/11b E97/11h E97/11c E97/11i E97/11d E97/11j E98/11k RC-LCV-459 RC-LCV-460 RC-LY/459CX1 Low Level Auxiliary Relay FB1 CB-F-3A-A RC-LY/460DX1 Low Level Auxiliary Relay FB1 CB-F-3A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-ZS-LCV-460 Letdown Isolation Valve Position Switch LF7 C-F-1-Z RC-ZS-LCV-459 Letdown Isolation Valve Position Switch L99 C-F-1-Z CS-FY-7447 Solenoid Valve GE5 C-F-1-Z CS-ZS-V145 Valve Position Switches LH2 C-F-1-Z CS-F42-R1 Aux. Rly F42 CB-F-3A-A EDE-FS9-KB20 Aux. Rly FS9 CB-F-3A-A 66 RC-E-10 Pressurizer Heaters Control Group RC-20846 A 310598 C-F-1-Z X - X - M26 RC-AM4-52H Truck Operated Switch Contacts AM4 CB-F-1A-A AM4-F31 F31-FB1/4 310882 AM4b AM4d AM4e AM4f AM4g CBA-FN-19 CBA-FN-20 RC-CS-7320 Control Switch with Indication F31 CB-F-3A-A RC-LYY-459CXA Level Auxiliary Relay FB1 CB-F-3A-A RC-LYY-460DXA Level Auxiliary Relay FB1 CB-F-3A-A RC-AM4-FU 15 A Fuses AM4 CB-F-1A-A RC-AM4-52 480 V AC Circuit Breaker AM4 CB-F-1A-A 67 CS-V-210 Charging Pump 2A Discharge Valve CS-20725 A 310764 PAB-F-1C-A - X - - - - - - - - - - CS-V-220 Note 1 68 CS-V-219 Charging Pump 2B Bypass Valve CS-20725 B 310764 PAB-F-1D-A - X - - - - - - - - - - CS-V-221 Note 1 69 CS-V-220 Charging Pump 2B Discharge Valve CS-20725 B 310764 PAB-F-1D-A - X - - - - - - - - - - CS-V-210 Note 1 70 CS-V-221 Charging Pump 2A Bypass Valve CS-20725 A 310764 PAB-F-1C-A - X - - - - - - - - - - CS-V-219 Note 1 Notes: 1. The equipment is mechanical with no electrical requirement.

2. During normal operation, the valve is in its safe shutdown position.

To prevent spurious operations, this equipment will be disabled at the appropriate control location.

3. Disabling the valve at the appropriate control location will reposition it for shut shutdown.
4. Air is not needed to position or to reposition the valve for safe shutdown.
5. This valve is permanently disabled by tripping its circuit breaker at the MCC.
6. During normal operation, the valve is in its hot shutdown position.

To prevent spurious operations, this equipment will be disabled at the appropriate control location. For cold shutdown, the valve will be energized for repositioning.

7. These valves are closed with their circuit breakers locked open during 100% power operation.

This will prevent spurious operation. For cold shutdown, these valves are energized for repositioning.

8. These valves are also listed in Table MCR 3.1.3.6.
9. Electrical group conduit drawing, 9763

-F-310764, is listed only to show the fire zone corresponding to the area where the charging pump oil coolers are located (9763 -F-805213 and -F-815214). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.3 -1 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CS-TK-4A Boric Acid Storage Tank CS-20729 A/B 310766 PAB-F-2B-Z - X - - - - - - - - - - - CS-TK-4B Note 1 2 CS-TK-4B Boric Acid Storage Tank CS-20729 A/B 310766 PAB-F-2B-Z - X - - - - - - - - - - - CS-TK-4A Note 1 3 CS-V-410 Boric Acid Tank 4A Outlet Valve CS-20729 A/B 310766 805216 805229 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-416 CS-V-1207 Notes 1, 2, 3 4 CS-V-416 Boric Acid Tank 4B Outlet Valve CS-20729 A/B 310766 805216 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-410 CS-V-1207 Notes 1, 2, 3 5 CS-V-423 Boric Acid Recirculation Valve CS-20729 A 310766 805216 805230 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-431 CS-V-1207 Notes 1, 2, 3 6 CS-V-431 Boric Acid Recirculation Valve CS-20729 B 310766 805216 805230 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-423 CS-V-1207 Notes 1, 2, 3 7 CS-V-437 Boric Acid Transfer Pump's Suction Cross -Over Line Isolation Valve CS-20729 A 310766 805216 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-1207 Notes 1, 2, 3 8 CS-V-439 Charging Pump Isolation Valve CS-20729 A/B 310766 805216 805229 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-426 Notes 1, 2, 3 9 CS-V-442 Charging Pump Isolation Valve CS-20729 A/B 310766 805216 805229 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-426 Notes 1, 2, 3 10 CS-P-3A Boric Acid Transfer Pump CS-20729 A 310766 PAB-F-2B-Z - X X - M43 CS-B88-52 460 V AC Circuit Breaker B88 CB-F-1A-A B88-F41 B88-M43 B88-M43/1 310891 B88a B88c CBA-FN-19 CBA-FN-20 EDE-MCC-512 CS-P-3B CS-B88-CPT Control Transformer B88 CB-F-1A-A CS-B88-42 Motor Starter B88 CB-F-1A-A CS-B88-49 Overload Relay B88 CB-F-1A-A CS-M43-49 Overload M43 PAB-F-2B-Z CS-B88-FU Fuse B88 CB-F-1A-A CS-SS-7435 Selector Switch B88 CB-F-1A-A CS-CS-7435-2 Control Switch with Indication B88 CB-F-1A-A CS-CS-7435-1 Control Switch with Indication F41 CB-F-3A-A CS-EC8-R1 Auxiliary Relay EC8 CB-F-1A-A

.* Table notes on last page of table

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.3 -2 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 CS-P-3B Boric Acid Transfer Pump CS-20729 B 310766 PAB-F-2B-Z - X X - M44 CS-B89-52 460 V AC Circuit Breaker B89 CB-F-1B-A B89-F48 B89-M44 B89-M44/1 F48-FT0 310891 B89a B89c CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-P-3A CS-B89-CPT Control Transformer B89 CB-F-1B-A CS-B89-42 Motor Starter B89 CB-F-1B-A CS-B89-49 Overload Relay B89 CB-F-1B-A CS-M44-49 Overload M44 PAB-F-2B-Z CS-SS-7436 Selector Switch B89 CB-F-1B-A CS-CS-7436-2 Control Switch with Indication B89 CB-F-1B-A CS-CS-7436-1 Control Switch with Indication F41 CB-F-3A-A CS-FT0-KA1 Auxiliary Relay Isolation Cab FT0 CB-F-3A-A CS-B89-FU Fuse B89 CB-F-1B-A 12 CS-V-426 Boric Acid F -5 to Charging Pumps Isolation Valve CS-20729 B 310766 PAB-F-2B-Z - X X - V04 CS-B94-52 460 V Circuit Breaker B94 CB-F-1B-A B94-V04 B94-V04/1 B94-V04/2 B94-F48 B94-F48/1 310891 B94a B94c CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-V-439 CS-V-442 CS-B94-CPT Control Transformer B94 CB-F-1B-A CS-B94-42/0,C Motor Starter B94 CB-F-1B-A CS-B94-49 Overload Relay B94 CB-F-1B-A CS-B94-FU Fuse B94 CB-F-1B-A CS-SS-7437 Selector Switch B94 CB-F-1B-A CS-CS-7437-2 Control Switch with Indication B94 CB-F-1B-A CS-CS-7437-1 Control Switch F41 CB-F-3A-A CS-ZS-V426 Valve Position and Open/Close Torque Switches V04 PAB-F-2B-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.3 -3 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 CP-CP-111 Reactor Trip Switchgear Cab 1

- B 310442 CB-F-1A-A X - X - HD2 CP-CS-6611-1 Control Switch F42 CB-F-3A-A E94-HD2 F10-HD2 F48-HD2/1 F48-HD2  310944 HD2a HD2d HD2b EDE-PP-111B CP-CP-111 Train A              CP-CS-6601-1 Control Switch F42 CB-F-3A-A                CP-CS-6601-2 Control Switch F10 CB-F-3A-A                SI-CS-2471-1 Control Switch F10 CB-F-3A-A                  SI-CS-2471-2 Control Switch F50 CB-F-3A-A                  CP-ZL-6601-3 Indicator Light F42 CB-F-3A-A                  CP-ZL-6601-6 Indicator Light F42 CB-F-3A-A                  CP-ZL-6601-2 Indicator Light F10 CB-F-3A-A                  CP-HD2-52H Truck Operated Contact HD2 CB-F-1A-A                  CP-HD3-52H Truck Operated Contact HD3 CB-F-1A-A                  CP-HD2-STB Shunt Trip HD2 CB-F-1A-A                  CP-HD2-S1 Pushbutton HD2 CB-F-1A-A                  CP-HD3-X1B Auxiliary Relay HD3 CB-F-1A-A                  CP-HD2-X5B Auxiliary Relay HD2 CB-F-1A-A                  CP-HD2-FU Fuses HD2 CB-F-1A-A                  CP-HD3-X2B Auxiliary Relay HD3 CB-F-1A-A                  CP-HD3-X4B Auxiliary Relay HD3 CB-F-1A-A                  CP-HD2-X3B Auxiliary Relay HD2 CB-F-1A-A                  CP-HD2-XB Auxiliary Relay HD2 CB-F-1A-A                  CP-HD2-X6B Auxiliary Relay HD3 CB-F-1A-A                  CP-HD3-52 Circuit Breaker HD3 CB-F-1A-A                  CP-HD3-X3A Auxiliary Relay HD3 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.3

-4 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 14 CP-CP-111 Reactor Trip Switchgear Cab 2

- A 310442 CB-F-1A-A X - X - HD3 CP-CS-6611-1 Control Switch F42 CB-F-3A-A E93-HD3 F10-HD3 F42-HD3/1 F42-HD3  310944 HD3a HD3f HD3b EDE-PP-111A CP-CP-111 Train B              CP-CS-6601-1 Control Switch F42 CB-F-3A-A                CP-CS-6601-2 Control Switch F10 CB-F-3A-A                SI-CS-2471-1 Control Switch F10 CB-F-3A-A                  SI-CS-2471-2 Control Switch F50 CB-F-3A-A                  CP-ZL-6601-4 Indicator Light F10 CB-F-3A-A                  CP-ZL-6601-5 Indicator Light F42 CB-F-3A-A                  CP-ZL-6601-1 Indicator Light F42 CB-F-3A-A                  CP-HD2-S1 Pushbutton HD2 CB-F-1A-A                  CP-HD2-STA Shunt Trip HD2 CB-F-1A-A                  CP-HD2-52 Circuit Breaker HD2 CB-F-1A-A                  CP-HD2-52H Truck Operated Contact HD2 CB-F-1A-A                  CP-HD3-FU Fuses HD3 CB-F-1A-A                  CP-HD3-52H Truck Operated Contact HD3 CB-F-1A-A                  CP-HD2-X3A Auxiliary Relay HD2 CB-F-1A-A                  CP-HD2-X3B Auxiliary Relay HD2 CB-F-1A-A                  CP-HD2-XA Auxiliary Relay HD2 CB-F-1A-A                  CP-HD3-X2A Auxiliary Relay HD3 CB-F-1A-A                  CP-HD3-X4A Auxiliary Relay HD3 CB-F-1A-A                  CP-HD3-X6A Auxiliary Relay HD3 CB-F-1A-A      15 CS-V-1207 Boric Acid Transfer Pump's suction Cross

-over line isolation Valve CS-20729 B 310766 805216 PAB-F-2B-Z - X - - - - - - - - - - CS-V-437 Notes 1,2,3 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.3 -5 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 16 CS-FCV-110A CS-FCV-111A CS-FCV-110B CS-FCV-111B Boration & Dilution Flow Control Valves CS-20729 A 310766 PAB-F-2B-Z PAB-F-2B-Z PAB-F-2B-Z PAB-F-2B-Z - X X X LG2 LG1 LG4 LG5 CS-E97/11-72 125 V DC Circuit Breaker E97 NES-F-1A-Z F41-YB5 F41-YB5/1 LG2-YB5 LG4-YB5 LG5-YB5 LG1-YB5 LG2-YB5/1 GP7-YB5 LG1-YB5/1 F41-FB1/1 F41-FB1/2 F41-GP7/1 F41-GP7 310891 E97/11a,c,d E97/11g,h,k

- - -          CS-CS-110A Control Switch with Indication F41 CB-F-3A-A                CS-FB1-MUX5 Auxiliary Relay FB1 CB-F-3A-A                 CS-FY-110-A1,-A2 Pilot Solenoid LG2 PAB-F-2B-Z                 CS-ZS-110A Valve Position Switch LG2 PAB-F-2B-Z                 CS-D1,D2 Noise Suppression Diode LG2 PAB-F-2B-Z                 CS-CS-110B Control Switch with Indication F41 CB-F-3A-A                 CS-CS-110C Control Switch F41 CB-F-3A-A                  CS-FB1-MUX3,4,5,6,7 Auxiliary Relay FB1 CB-F-3A-A                  CS-FY-110F Pilot Solenoid GP7 PAB-F-2C-Z                   CS-ZS-110B Valve Position Switch LG4 PAB-F-2B-Z                  CS-D3 Noise Suppression Diode GP7 PAB-F-2C-Z                  CS-CS-111A Control Switch with Indication F41 CB-F-3A-A                  CS-FY-111A-1 Pilot Solenoid LG1 PAB-F-2B-Z                  CS-ZS-111A Valve Position Switch LG1 PAB-F-2B-Z                  CS-D4 Noise Suppression Diode LG1 PAB-F-2B-Z                  CS-CS-111B Control Switch with Indication F41 CB-F-3A-A                  CS-FY-111F Pilot Solenoid GP7 PAB-F-2C-Z                  CS-ZS-111B Valve Position Switch LG5 PAB-F-2B-Z                  CS-D5 Noise Suppression Diode GP7 PAB-F-2C-Z                  CS-CS-110D Control Switch F41 CB-F-3A-A F41-FB1/3 F41-FB1/4 FB1/1a,b  FB1/1e CS-FB1-MUX1,2,3,4, 5,5A,8A,9 Auxiliary Relay FB1 CB-F-3A-A                  CS-FB1-X Auxiliary Relay FB1 CB-F-3A-A                  CS-F41-R,G Indicator Light F41 CB-F-3A-A                  CS-CS-110C Control Switch F41 CB-F-3A-A                  CS-ITB-111Q Input/Output Module F41 CB-F-3A-A                  CS-LY-112DX Auxiliary Relay FB1 CB-F-3A-A                  CS-RC RC Noise Suppression FB1 CB-F-3A-A                  CS-FIY-110 Flow Indicating Converter S60 PAB-F-2B-Z EH5-S60 S60-S71 F47-S60 F47-LG2 EH5/1a EH5/1c                CS-FIC-110 Flow Controller F41 CB-F-3A-A                 CS-FT-110 Flow Transmitter S71 PAB-F-2B-Z                  CS-ZY-110A Positioner for CS-FCV-110A LG2 PAB-F-2B-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.3

-6 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 16 (Cont) CS-FIC-110,111 Flow Controller F41 CB-F-3A-A F47-SR5 F47-LG1 EJ9/15ca,cb,cd,ce EJ9/15cc CS-FIQ-111 Flow Indicating Controller F41 CB-F-3A-A CS-ZY-111A Positioner for CS-FCV-111A LG1 PAB-F-2B-Z CS-UQ-111 Power Supply F41 CB-F-3A-A CS-FT-111-1,2 Flow Transmitter SR5 PAB-F-2B-Z CS-ITB-110C,111C, 111Q Input/Output Module F41 CB-F-3A-A CS-CS-110C,110D Control Switch F41 CB-F-3A-A CS-FB1-MUX4 Auxiliary Relay FB1 CB-F-3A-A CS-FB1-MUX3,4,5,6,7 Auxiliary Relay FB1 CB-F-3A-A F47-FB1 FB1/2a FB1/2d CS-ITB-110C,111C Input/Output Module F41 CB-F-3A-A CS-FB1-MUX5A,8A Auxiliary Relay FB1 CB-F-3A-A FB1-FB3 FB2-FB3 FB3/2a FB3/2a CS-FB2-MUX5B,8B Auxiliary Relay FB2 CB-F-3A-A CS-LT-112 Level Transmitter GP9 PAB-F-3B-Z FA5-GP9 FA5-FB1 ILD-1-CS-L00112 310940 FA5a FA5h FA5b FA5d CS-LQY-112 Level Loop Pwr Supply FA5 CB-F-3A-A CS-LB-112C/D & I/E Converter FA5 CB-F-3A-A CS-LYY-112D Level Bistable FA5 CB-F-3A-A CS-LY/112DX Auxiliary Relay FB1 CB-F-3A-A CS-LI-112 Level Indication GP9 PAB-F-3B-Z CS-LDY-112 Isolation Resistors FA5 CB-F-3A-A CS-IRTU-1 Computer Termination Cabinet FD1 CB-F-3A-A F41-FD1/1 310181 FD1r FD1s ILD-1-CS-F00111 17 RMW-P-16A Reactor Makeup Water Pump CS-20360 A 310763 PAB-F-1A-Z - X X - M36 - - - - - - - - Note 4 18 RMW-P-16B Reactor Makeup Water Pump CS-20360 A 310763 PAB-F-1A-Z - X X - M37 - - - - - - - - Note 4 .Notes 1. Equipment is mechanical with no electrical requirement.

2. CS-V-423, 410, 416, 431, 437, 439, 442 are non

-electrically operated valves and will be manually positioned as required to provide their reactivity control function during safe shutdown.

3. Electrical conduit plan drawing, 310766, listed only to show fire zone correlation reference to Primary Auxiliary Building area covered by piping Drawings 805216, 805229, 805230, where Valves CS-V-410, 416, 423, 431, 437, 439, 442 are identified in plan and section.
4. This equipment is listed because it can spuriously start due to cable failure in the boration & dilution flow control valve control circuits. Spurious pump start by itself from failure of its cables is not of concern since CS-FCV-111A remains closed.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -1 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 NI-NE-6690 Intermediate Range Thermal Neutron Flux Monitoring Detector - A 310565 C-F-1-Z X X X - Q05 NI-E1S/13-52 120 V AC Circuit Breaker E1S CB-F-1A-1 H40-XP8 H40-KDO KDO-QC1 QCI-QI0 G2H-QC1 QO5-XP8 E1S-KDO E1S-QC1 E1S-QI0 F10-QC1 310943 E1S/13a E1S/13b E1S/13c CBA-FN-19 CBA-FN-20 EDE-PP-11E NI-NE-6691 NI-E1S/14-52 120 V AC Circuit Breaker E1S CB-F-1A-A NI-E1S/15-52 120 V AC Circuit Breaker E1S CB-F-1A-A NI-NI-6690-3&4 Excore Wide -Range Thermal Neutron Flux Indicators F10 CB-F-3A-A NI-NT-6690 Excore Wide -Range Transmitter KDO ET-F-1A-A NI-NM-6690 Excore Wide -Range Signal Processor QC1 CB-F-1A-A NI-NM-6690J Excore Wide -Range Signal Processor Expansion Box QI0 CB-F-1A-A EDE-TBX-XP8 Junction Box XP8 C-F-1-Z EDE-NM-116 Electrical Penetration H40 C-F-2-Z, ET-F-1A-A 2 NI-NE-6691 Intermediate Range Thermal Neutron Flux Monitoring Detector - B 310565 C-F-1-Z X X X - Q07 NI-E1T/13-52 120 V AC Circuit Breaker E1T CB-F-1B-A H21-XP9 H21-KD1 KD1-QDO QDO-QJ1 G2K-QD0 QO7-XP9 E1T-KD1 E1T-QD0 E1T-QJ1 F20-QD0 310943 E1T/13a E1T/13b E1T/13c CBA-FN-32 CBA-FN-33 EDE-PP-11F NI-NE-6690 NI-E1T/14-52 120 V AC Circuit Breaker E1T CB-F-1B-A NI-E1T/15-52 120 V AC Circuit Breaker E1T CB-F-1B-A NI-NI-6691-3&4 Excore Wide -Range Thermal Neutron Flux Indicators G2K CB-F-1B-A NI-NT-6691 Excore Wide -Range Transmitter KD1 ET-F-1C-A NI-NM-6691 Excore Wide -Range Signal Processor QD0 CB-F-1B-A NI-NM-6691J Excore Wide -Range Signal Processor Expansion Box QJ1 CB-F-1B-A EDE-TBX-XP9 Junction Box XP9 C-F-1-Z EDE-NM-97 Electrical Penetration H21 C-F-1-Z, ET-F-1C-A NI-NI-6691-1&2 Excore Wide -Range Thermal Neutron Flux Indicators F20 CB-F-3A-A 3 CS-LT-102 CS-TK-4A Boric Acid Tank Level CS-20729 A 310766 PAB-F-2B-Z - X X - RJ7 CS-LI-102 Level Indicator F41 CB-F-3A-A FA1-RJ7 310942 FA1a FA1d MM-CP-1 CS-LT-7464 MM-CP-1 Process Protection System Cabinet (PPC) No. 1 FA1 CB-F-3A-A F47-FA1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -2 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 RC-TE-413A RC Loop 1 Wide-Range Hot Leg Temperature RC-20841 A 310582 C-F-1-Z X X X - TB7 RC-TI-413A Temperature Indicator F41 CB-F-3A-A TB7-X40 H44-X40/1 FA1-H44/3 F47-FA1/1 310942 FA1r FA1v E01/9 MM-CP-1 IC-TE-XX RC-TR-413A Temperature Recorder F41 CB-F-3A-A MM-CP-1 PPC No. 1 FA1 CB-F-3A-A EDE-TBX-X40 Terminal Box X40 C-F-1-Z EDE-MM-120 Electrical Penetration H44 C-F-2-Z, ET-F-1A-A 5 RC-TE-443A RC Loop 4 Wide-Range Hot Leg Temperature RC-20844 A 310583 C-F-1-Z X X X - TB0 RC-TI-443A Temperature Indicator F41 CB-F-3A-A TB0-X40 H44-X40/1 FA1-H44/3 F47-FA1/2 310942 FA1r FA1v FA1y MM-CP-1 IC-TE-XX MM-CP-1 PPC No. 1 FA1 CB-F-3A-A EDE-TBX-X40 Terminal Box X40 C-F-1-Z EDE-MM-120 Electrical Penetration H44 C-F-2-Z, ET-F-1A-A 6 RC-PT-405 RC Loop 1 Wide-Range Hot Leg Pressure RC-20845 A 310694 ET-F-1C-A X X X - P78 RC-PI-405-1 Pressure Indicator F40 CB-F-3A-A FA1-P78/1 F47-FA1/3 F47-FA1/2 F10-F47 F10-F47/1 310942 FA1r FA1v FA1w FA1z MM-CP-1 RC-PT-403 RC-PR-405 Pressure Recorder F41 CB-F-3A-A MM-CP-1 PPC No. 1 FA1 CB-F-3A-A RC-PI-405A-1 Pressure Indicator F40 CB-F-3A-A RC-PI-405-2 Pressure Indicator F10 CB-F-3A-A RC-PI-405A-2 Pressure Indicator F10 CB-F-3A-A 7 RC-TE-423A RC Loop 2 Wide-Range Hot Leg Temperature RC-20842 A 310582 C-F-1-Z X X X - TB8 RC-TI-423A Temperature Indicator F41 CB-F-3A-A TB8-X48 H45-X48 FA1-H45/2 F47-FA1/1 310942 FA1r FA1s FA1y MM-CP-1 IC-TE-XX MM-CP-1 PPC No. 1 FA1 CB-F-3A-A EDE-TBX-X48 Terminal Box X48 C-F-1-Z EDE-MM-121 Electrical Penetration H45 C-F-2-Z, ET-F-1A-A 8 RC-TE-433A RC Loop 3 Wide-Range Hot Leg Temperature RC-20843 A 310583 C-F-1-Z X X X - TB9 RC-TI-433A Temperature Indicator F41 CB-F-3A-A H45-X94 TB9-X94 FA1-H45/2 F47-FA1/2 310942 FA1r FA1s FA1w FA1y MM-CP-1 IC-TE-XX RC-TR-433A Temperature Recorder F41 CB-F-3A-A MM-CP-1 PPC No. 1 FA1 CB-F-3A-A EDE-TBX-X94 Terminal Box X94 C-F-1-Z EDE-MM-121 Electrical Penetration H4 C-F-2-Z, ET-F-1A-A 9 RC-LT-459 RC-E-10 Pressurizer Level RC-20846 A 310579 C-F-2-Z X X X - GN5 RC-LI-459A Level Indicator F31 CB-F-3A-A GN5-H45/1 FA1-H45/1 F38-FA1/1 310942 FA1s FA1v FA1w MM-CP-1 RC-LT-460 RC-LR-459A Level Recorder F40 CB-F-3A-A MM-CP-1 PPC No. 1 FA1 CB-F-3A-A EDE-MM-121 Electrical Penetration H45 C-F-2-Z, ET-F-1A-A 10 CS-LT-106 CS-TK-4B Boric Acid Tank Level CS-20729 B 310766 PAB-F-2B-Z - X X - RJ0 CS-LI-106 Level Indicator F41 CB-F-3A-A FA2-RJ0 F48-FA2 310942 FA2a FA2d MM-CP-2 CS-LT-7464 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -3 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 RC-TE-423B RC Loop 2 Wide-Range Cold Leg Temperature RC-20842 B 310582 C-F-1-Z X X X - TC2 RC-TI-423B Level Indicator F41 CB-F-3A-A TC2-X52 H55-X52/1 F48-FA2/1 FA2-H55/6 310942 FA2r FA2s FA2w FA2x MM-CP-2 FW-PT-524 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A EDE-TBX-X52 Terminal Box X52 C-F-1-Z EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 12 RC-TE-413B RC Loop 1 Wide-Range Cold Leg Temperature RC-20841 B 310582 C-F-1-Z X X X - TC1 RC-TI-413B Temperature Indicator F41 CB-F-3A-A TC1-X14 H55-X14 F48-FA2/1 FA2-H55/6 310942 FA2r FA2s FA2w FA2x MM-CP-2 FW-PT-514 RC-TR-413B Temperature Recorder F41 CB-F-3A-A MM-CP-2 PPC No. 2 FA2 CB-F-3A-A EDE-TBX-X14 Terminal Box X14 C-F-1-Z EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 13 RC-TE-433B RC Loop 3 Wide-Range Cold Leg Temperature RC-20843 B 310583 C-F-1-Z X X X - TC3 RC-TI-433B Temperature Indicator F41 CB-F-3A-A TC3-X69 H55-X69 FA2-H55/7 F48-FA2/2 310942 FA2t FA2y FA2z MM-CP-2 FW-PT-514 RC-TR-433B Temperature Recorder F41 CB-F-3A-A MM-CP-2 PPC No. 2 FA2 CB-F-3A-A EDE-TBX-X69 Terminal Box X69 C-F-1-Z EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 14 RC-TE-443B RC Loop 4 Wide-Range Cold Leg Temperature RC-20844 B 310583 C-F-1-Z X X X - TC4 RC-TI-443B Temperature Indicator F41 CB-F-3A-A TC4-X86 H55-X86 FA2-H55/7 F48-FA2/2 310942 FA2r FA2t FA2y FA2z MM-CP-2 FW-PT-544 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A EDE-TBX-X86 Terminal Box X86 C-F-1-Z EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 15 RC-PT-403 RC Loop 4 Wide-Range Hot Leg Pressure RC-20845 D 310694 ET-F-1C-A X X X - P76 RC-PI-403-1 Pressure Indicator F41 CB-F-3A-A FA4-P76/1 F48-FA4/2 F48-FA4 F20-F48 310942 FA4r FA4u FA4v MM-CP-4 RC-PT-405 RC-PR-403 Pressure Recorder F41 CB-F-3A-A MM-CP-4 PPC No. 4 FA4 CB-F-3A-A RC-PI-403A-1 Pressure Indicator F41 CB-F-3A-A RC-PI-403-2 Pressure Indicator F20 CB-F-3A-A RC-PI-403A-2 Pressure Indicator F20 CB-F-3A-A 16 RC-LT-460 RC-E-10 Pressurizer Level RC-20846 B 310579 C-F-2-Z X X X - GN5 RC-LI-460A Level Indicator F31 CF-F-3A-A GN5-H55/2 FA2-H55/3 F39-FA2/1 310942 FA2r FA2w MM-CP-2 RC-LT-459 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 17 CO-LT-4096 CO-TK-25 Condenser Storage Tank Level FW-20426 A 310828 CST-F-1 X X - R53 CO-LI-4096 Level Indicator F61 CB-F-3A-A FJ7-R53 F66-FJ8 310953 FJ7g FJ7f MM-CP-153 BOP - Process Control Cabinet FJ7 CB-F-3A-A MM-CP-153 FW-LT-4252 FW-LT-4257 MM-CP-153 BOP - Process Control Cabinet FJ8 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -4 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 FW-FT-4214-2 RC-E-11A Emergency FW Header Flow FW-20688 A 310708 EFP-F-1-A X X X - GL3 FW-FI-4214-2 Flow Indicator F51 CB-F-3A-A FK0-GL3 F56-FK0 F86-FK0 310952 FK0a MM-CP-297A FW-FT-4224-2 FT-FT-4244-2 FW-LT-519 FW-FR-4214 Flow Recorder F86 CB-F-3A-A MM-CP-297A BOP - Process Control Cabinet (PCC) FK0 CB-F-3A-A 19 FW-FT-4224-2 RC-E-11B Emergency FW Header Flow FW-20688 B 310708 EFP-F-1-A X X X - GL4 FW-FI-4224-2 Flow Indicator F51 CB-F-3A-A FL2-GL4 F56-FL2 F88-FL2 310952 FL2a MM-CP-297B FW-FT-4214-2 FW-FT-4234-2 FW-LT-529 FW-FR-4224 Flow Recorder F86 CB-F-3A-A MM-CP-297B BOP - PCC FL2 CB-F-3A-A 20 FW-FT-4234-2 RC-E-11C Emergency FW Header Flow FW-20688 A 310708 EFP-F-1-A X X X - GL3 FW-FI-4234-2 Flow Indicator F51 CB-F-3A-A FK0-GL3 F56-FK0 F86-FK0 310952 FKOa FW-FT-4224-2 FW-FT-4244-2 FW-LT-537 FW-FR-4214 Flow Recorder F86 CB-F-3A-A MM-CP-297A BOP - PCC FK0 CB-F-3A-A MM-CP-297A 21 FW-FT-4244-2 RC-E-11D Emergency FW Header Flow FW-20688 B 310708 EFP-F-1-A X X X - GL4 FW-FI-4244-2 Flow Indicator F51 CB-F-3A-A FL2-GL4 F56-FL2 F88-FL2 310952 FL2a MM-CP-297B FW-FT-4214-2 FW-FT-4234-2 FW-LT-548 FW-FR-4224 Flow Recorde r F86 CB-F-3A-A MM-CP-297B BOP - PCC FL2 CB-F-3A-A 22 FW-LT-501 RC-E-11A Steam Generator Wide-Range Level FW-20686 A 310576 C-F-1-Z X X X - R1D FW-LI-501 Level Indicator F51 CB-F-3A-A FA1-H44 H44-R1D F56-FA1/3 F56/FA1 310942 FA1h FA1l FA1m MM-CP-1 FW-LT-502 FW-LT-504 FW-LT-519 MM-CP-1 PPC No. 1 FA1 CB-F-3A-A FW-XR-501 Recorder F51 CB-F-3A-A EDE-MM-120 Electrical Penetration H44 C-F-2-Z, ET-F-1A-A 23 FW-LT-502 RC-E-11B Steam Generator Wide-Range Level FW-20686 B 310576 C-F-1-Z X X X - R1E FW-LI-502 Level Indicator F51 CB-F-3A-A FA2-H55 H55-R1E F56-FA2/1 310942 FA2h FA2l FA2m MM-CP-2 FW-LT-501 FW-LT-503 FW-LT-529 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A FW-XR-502 Recorder F51 CB-F-3A-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 24 FW-LT-503 RC-E-11C Steam Generator Wide-Range Level FW-20686 C 310577 C-F-1-Z X X X - R1F FW-LI-503 Level Indicator F51 CB-F-3A-A FA3-H47/1 F56-FA3/2 H47-R1F 310942 FA3h FA3l MM-CP-3 FW-LT-502 FW-LT-504 FW-LT-537 MM-CP-3 PPC No. 3 FA3 CB-F-3A-A FW-XR-503 Recorder F51 CB-F-3A-A EDE-MM-123 Electrical Penetration H47 C-F-2-Z, ET-F-1A-A 25 FW-LT-504 RC-E-11D Steam Generator Wide-Range Level FW-20686 D 310577 C-F-1-Z X X X - R1G FW-LI-504 Level Indicator F51 CB-F-3A-A F56-FA4 FA4-H52/1 H52-R1G 310942 FA4h FA4l MM-CP-4 FW-LT-501 FW-LT-503 FW-LT-548 MM-CP-4 PPC No. 4 FA4 CB-F-3A-A FW-XR-504 Recorder F51 CB-F-3A-A EDE-MM-128 Electrical Penetration H52 C-F-1-Z, ET-F-1C-A 26 FW-PT-514 RC-E-11A Steam Generator Steam Pressure MS-20580 A 310589 MS-F-1B-Z X X X - GL6 FW-PI-514A Pressure Indicator F51 CB-F-3A-A FA1-GL6 F56-FA1 F56-FA1/4 310942 FA1h FA1l FA1m MM-CP-1 FW-PT-525 FW-PT-545 FW-PT-515 MM-CP-1 PPC No. 1 FA1 CB-F-3A-A FW-XR-501 Recorder F51 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -5 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 27 FW-PT-525 RC-E-11B Steam Generator Steam Pressure MS-20581 B 310586 MS-F-3A-Z X X X - GZ4 FW-PI-525A Pressure Indicator F51 CB-F-3A-A FA2-GZ4 F56-FA2/1 310942 FA2l FA2h FA2m MM-CP-2 FW-PT-514 FW-PT-534 FW-PT-524 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A 28 FW-PT-534 RC-E-11C Steam Generator Steam Pressure MS-20581 A 310586 MS-F-3A-Z X X X - GL5 FW-PI-534A Pressure Indicator F51 CB-F-3A-A FA1-GL5 F56-FA1 310942 FA1h FA1l FA1m MM-CP-1 FW-PT-525 FW-PT-545 FW-PT-535 MM-CP-1 PPC No. 1 FA1 CB-F-3A-A 29 FW-PT-545 RC-E-11D Steam Generator Steam Pressure MS-20580 B 310589 MS-F-1B-Z X X X - GZ6 FW-PI-545A Pressure Indicator F51 CB-F-3A-A FA2-GZ6 F56-FA2/1 310942 FA2l FA2h FA2m MM-CP-2 FW-PT-514 FW-PT-534 FW-PT-544 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A 30 FW-LT-4252 FW-P-37A CST Level CO-20426 A 310708 EFP-F-1-A - X X - P1G FW-LI-4252 Level Indicator F51 CB-F-3A-A FK0-P1G F56-FK0/1 310952 FKOa MM-CP-297A CO-LT-4096 FW-LT-4257 MM-CP-297A BOP - PCC FK0 CB-F-3A-A 31 FW-LT-4257 FW-P-37B CST Level CO-20426 B 310708 EFP-F-1-A - X X - P1F FW-LI-4257 Level Indicator F51 CB-F-3A-A FL2-P1F F56-FL2/1 310952 FL2a MM-CP-297B CO-LT-4096 FW-LT-4252 MM-CP-297B BOP - PCC FL2 CB-F-3A-A 32 IC-TE-1 Incore Temperature E -6 Core Grid Location J-8 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/M 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 33 IC-TE-4 Incore Temperature A -5 Core Grid Location H -6 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/Z 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 34 IC-TE-6 Incore Temperature Cal. Core Grid Location J -10 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/17 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 35 IC-TE-7 Incore Temperature B -5 Core Grid Location F -7 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-NH9/6 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 36 IC-TE-8 Incore Temperature B -3 Core Grid Location K -6 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/5 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 37 IC-TE-12 Incore Temperature A -8 Core Grid Location E -9 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/13 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration F97 C-F-1-Z, ET-F-1C-A 38 IC-TE-14 Incore Temperature E -3 Core Grid Location H -4 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/W 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -6 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 39 IC-TE-15 Incore Temperature F -1 Core Grid Location D -8 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/V 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 40 IC-TE-16 Incore Temperature E -4 Core Grid Location M -7 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/X 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 41 IC-TE-18 Incore Temperature D -10 Core Grid Location L -11 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/G 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 42 IC-TE-20 Incore Temperature C -10 Core Grid Location E -5 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/C 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 43 IC-TE-21 Incore Temperature B -10 Core Grid Location E -11 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/15 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 44 IC-TE-24 Incore Temperature B -9 Core Grid Location H -13 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/8 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 45 IC-TE-27 Incore Temperature B-9 Core Grid Location C -8 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/N 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 46 IC-TE-30 Incore Temperature C -9 Core Grid Location E -3 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/B 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 47 IC-TE-31 Incore Temperature A -6 Core Grid Location D -12 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/11 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 48 IC-TE-32 Incore Temperature D -4 Core Grid Location L -13 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/D 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -7 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 49 IC-TE-34 Incore Temperature F -2 Core Grid Location H -2 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/18 310965 F97g 310181 JW0n JW0t MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 50 IC-TE-37 Incore Temperature F -8 Core Grid Location P -9 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/U 310965 F97g 310181 JW0n JW0t MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 51 IC-TE-38 Incore Temperature A -2 Core Grid Location K -2 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 52 IC-TE-39 Incore Temperature A -7 Core Grid Location B -6 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B Electrical Penetration F97 CB-F-3A-A F97-H54 H54-HN9/12 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 53 IC-TE-40 Incore Temperature E -2 Core Grid Location F-14 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/H 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 54 IC-TE-41 Incore Temperature D -5 Core Grid Location N -4 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/Y 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 55 IC-TE-45 Incore Temperature E -5 Core Grid Location N -13 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/L 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 56 IC-TE-47 Incore Temperature F -7 Core Grid Location A -9 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/T 310965 F97g 310181 JW0n JW0t MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 57 IC-TE-50 Incore Temperature R -6 Core Grid Location R -6 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/14 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 58 IC-TE-52 Incore Temperature F -4 Core Grid Location L -15 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/S 310965 F97g 310181 JW0n JW0t MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -8 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 59 IC-TE-57 Incore Temperature F -3 Core Grid Location B -3 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/19 310965 F97g MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 310181 JW0n JW0t 60 IC-TE-58 Incore Temperature C -4 Core Grid Location B -13 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/16 310965 F97g MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 310181 JW0n JW0r 61 MM-CP-486B RVLIS/HELB Incore Temperature Display B 310501 CB-F-3A-A X X X - F97 RC-XX-7315-4 Plasma Display FT1 CB-F-3A-A F97-FT1 E53-FT1 310965 E53/18 E53/18 EDE-MCC-631 MM-CP-1 62 FW-LT-529 RC-E-11B Steam Generator Narrow-Range Level FW-20686 A 310578 C-F-2-Z X X X - GE9 FW-LR-529 Level Recorder F51 CB-F-3A-A GE9-H45 FA1-H45 F56-FA1 310942 FA1h MM-CP-1 FW-LT-502 FW-LI-529 Level Indicator F51 CB-F-3A-A MM-CP-1 PPC No. 1 FA1 CB-F-3A-A EDE-MM-121 Electrical Penetration H45 C-F-2-Z, ET-F-1A-A 63 FW-LT-519 RC-E-11A Steam Generator Narrow-Range Level FW-20686 B 310578 C-F-2-Z X X X - R15 FW-LI-519 Level Indicator F51 CB-F-3A-A H55-R1S FA2-H55 F56-FA2/1 310942 FA2h MM-CP-2 FW-LT-501 FW-LR-519 Level Recorder F51 CB-F-3A-A MM-CP-2 PPC No. 2 FA2 CB-F-3A-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 64 FW-LT-548 RC-E-11D Steam Generator Narrow-Range Level FW-20686 C 310579 C-F-2-Z X X X - GF8 FW-LI-548 Level Indicator F51 CB-F-3A-A GF8-H47 FA3-H47/1 F56-FA3/2 310942 FA3h MM-CP-3 FW-LT-504 MM-CP-3 PPC No. 3 FA3 CB-F-3A-A EDE-MM-123 Electrical Penetration H47 C-F-2-Z, ET-F-1A-A 65 FW-LT-537 RC-E-11C Steam Generator Narrow-Range Level FW-20686 D 310579 C-F-2-Z X X X - GN5 FW-LI-537 Level Indicator F51 CB-F-3A-A GN5-H52 FA4-H52 F56-FA4 310942 FA4h MM-CP-4 FW-LT-503 MM-CP-4 PPC No. 4 FA4 CB-F-3A-A EDE-MM-128 Electrical Penetration H52 C-F-1-Z, ET-F-1C-A 66 FW-PT-524 RC-E-11B Steam Generator Steam Pressure MS-20581 A 310586 MS-F-3A-Z X X X - GL5 FW-PI-524A Pressure Indicator F51 CB-F-3A-A FA1-GL5 F56-FA1 310942 FA1h MM-CP-1 FW-PT-525 MM-CP-1 PPC No. 1 FA1 CB-F-3A-A 67 FW-PT-544 RC-E-11D Steam Generator Steam Pressure MS-20580 A 310589 MS-F-1B-Z X X X - GL6 FW-PI-544A Pressure Indicator F51 CB-F-3A-A FA1-GL6 F56-FA1 310942 FA1h MM-CP-1 FW-PT-545 MM-CP-1 PPC No. 1 FA1 CB-F-3A-A 68 CC-TE-2171 PCCW Loop A Sup. Header Temperature CC-20205 A 310765 PAB-F-2C-Z X X X - TM0 MM-CP-297A BOP - Process Control Cabinet FK0 CB-F-3A-A FK0-TM0 F30-FK0/4 310952 FK0d FK0f MM-CP-297A CC-TE-2271 CC-TI-2171-1 Temperature Indicator F30 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -9 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 69 CC-TE-2271 PCCW Loop B Sup. Header Temperatur e CC-20211 B 310765 PAB-F-2C-Z X X X - TM8 MM-CP-152B BOP - Process Control Cabinet FJ4 CB-F-3A-A FJ4-TM8/10 F39-FJ4/4 310952 FJ4j FJ4n MM-CP-152B CC-TE-2171 CC-TI-2271-1 Temperature Indicator F30 CB-F-3A-A 70 MM-CP-153 BOP - Process Control Cabinet

- A 310499 CB-F-3A-A X - X - FJ7 - - - - EJ9-FJ7  310953 EJ9/12 EJ9/12 ED-PP-5 MM-CP-297B  71 MM-CP-153 BOP - Process Control Cabinet
- A 310499 CB-F-3A-A X - X - FJ8 - - - - EJ9-FJ7  310953 EJ9/12 EJ9/12 ED-PP-5 MM-CP-297B  72 MM-CP-297A BOP - Process Control Cabinet
- A 310499 CB-F-3A-A X X X - FK0 - - - - EH9-FK0  310952 EH9/19 EH9/19 EDE-PP-1E MM-CP-297B  73 MM-CP-297B BOP - Process Control Cabinet
- B 310499 CB-F-3A-A X X X - FL2 - - - - EH0-FL2  310952 EH0/19 EH0/19 EDE-PP-1F MM-CP-297A  74 MM-CP-152B BOP - Process Control Cabinet
- B 310499 CB-F-3A-A X X X - FJ4 - - - - EHO-FJ4  310952 EH0/1 EH0/1 EDE-PP-1F MM-CP-297A MM-CP-152A  75 FW-PT-515 RC-E-11D Steam Generator Steam Pressure MS-20580 B 310589 MS-F-1B-Z X X X - GZ6 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A FA2-GZ6 F56-FA2/1  310492 FA2l FA2h FA2m MM-CP-2 FW-PT-514 FW-PT-534 FW-PT-544             FW-PI-515A Pressure Indicator F51 CB-F-3A-A    76 FW-PT-535 RC-E-11B Steam Generator Steam Pressure MS-20581 B 310586 MS-F-3A-Z X X X - GZ4 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A FA2-GZ4 F56-FA2/1  310942 FA2l FA2h FA2m MM-CP-2 FW-PT-514 FW-PT-534 FW-PT-524             FW-PI-535 Pressure Indicator F51 CB-F-3A-A    77 MM-CP-7 Process Control System Cabinet 3
- A 310499 CB-F-3A-A X X X - FA7 - - - - EH7-FA7  310940 EH7/9 EH7/9 ED-PP-3C -  78 CS-LT-7464 Boric Acid Tank CS-TK-4B Level Transmitter CS-20729 B 310766 PAB-F-2B-Z - X X - RJ9 CS-LSY-7464 Comparator G2J CB-F-1B-A G2K-RJ9  310952 GZ0c CBA-FN-32 CS-LT-102             CS-LQY-7464 I/E Converter G2J CB-F-1B-A  CBA-FN-33 CS-LT-106              CS-LI-7464 Level Indicator G2J CB-F-1B-A   MM-UQ-5868                     MM-UQ-5869 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.5

-1 FUNCTION: SAFEGUARD ACTUATION SYSTEM PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 MM-CP-12 Solid State Protection System Cabinet - A 310501 CB-F-3A-A X X X - FB6 FB7 FF8 CBS-CS-2318-1 Control Switch Containment Spray and Isolation Phase B Actuation F10 CB-F-3A-A F10-F50 F10-F86/2 F10/F86/3 F10/FB7/7 F10-F50/1 F10-FB6/1 F10-FB6 F10-FB7/5 310949 FB6e FB6h FB6f FB6j FB6k EDE-PP-1A MM-CP-13 CBS-CS-2318-2 Control Switch Containment Spray and Isolation Phase B Actuation F10 CB-F-3A-A CBS-CS-2318-3 Control Switch Containment Spray and Isolation Phase B Actuation F50 CB-F-3A-A CBS-CS-2318-4 Control Switch Containment Spray and Isolation Phase B Actuation F50 CB-F-3A-A CBS-CS-2319 Control Switch Containment Spray Reset F10 CB-F-3A-A CS-CS-2572-1 Control Switch "T" Signal Containment Isolation Phase A Actuation F10 CB-F-3A-A CS-CS-2572-2 Control Switch "T" Signal Containment Isolation Phase A Actuation F50 CB-F-3A-A CS-CS-2573 Control Switch "T" Signal Containment Isolation Phase A Reset F10 CB-F-3A-A CBS-CS-2358 Control Switch "P" Signal Containment Isolation Phase B Reset F10 CB-F-3A-A SI-CS-2471-1 Control Switch Safety Injection Actuation F10 CB-F-3A-A SI-CS-2471-2 Control Switch Safety Injection Actuation F50 CB-F-3A-A SI-CS-2489 Control Switch Safety Injection Reset and Block F10 CB-F-3A-A PSC-E01/11-52 120 V AC Circuit Breaker E01 CB-F-1A-A MM-CP-450A Remote Disabling Control Panel G5X DG-F-2A-A E01-G5X FF8-G5X E01/2a E01/2b SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.5 -2 FUNCTION: SAFEGUARD ACTUATION SYSTEM PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 MM-CP-13 Solid State Protection System Cabinet - B 310501 CB-F-3A-A X X X - FB0 FB9 FF9 CBS-CS-2328-1 Control Switch Containment Spray and Isolation Phase B Actuation F20 CB-F-3A-A F10-F51 F10-FB9 F20-F51 F20-F51/2 F20-FB0/B F20-FB0/H F20-FB9 F20-FB9/1 F20-FB9/2 F20-FB9/3 310949 FB9e FB9h FB9f FB9j FB9k EDE-PP-1B MM-CP-12 CBS-CS-2328-2 Control Switch Containment Spray and Isolation Phase B Actuation F20 CB-F-3A-A CBS-CS-2328-3 Control Switch Containment Spray and Isolation Phase B Actuation F50 CB-F-3A-A CBS-CS-2328-4 Control Switch Containment Spray and Isolation Phase B Actuation F50 CB-F-3A-A CBS-CS-2329 Control Switch Containment Spray Reset F20 CB-F-3A-A CS-CS-2582-1 Control Switch "T" Signal Containment Isolation Phase A Actuation F20 CB-F-3A-A CS-CS-2582-2 Control Switch "T" Signal Containment Isolation Phase A Actuation F50 CB-F-3A-A CS-CS-2583 Control Switch "T" Signal Containment Isolation Phase A Reset F20 CB-F-3A-A CBS-CS-2359 Control Switch "P" Signal Containment Isolation Phase B Reset F20 CB-F-3A-A SI-CS-2471-1 Control Switch Safety Injection Actuation F10 CB-F-3A-A SI-CS-2471-2 Control Switch Safety Injection Actuation F50 CB-F-3A-A SI-CS-2499 Control Switch Safety Injection Reset and Block F20 CB-F-3A-A PSC-E02/11-52 120 V AC Circuit Breaker E02 CB-F-1B-A MM-CP-450B Remote Disabling Control Panel G5Y DG-F-2B-A E02-G5Y FF9-G5Y E02/4a E02/4b 3 MM-CP-1 Process Protection System Cabinet No. 1

- A 310501 CB-F-3A-A X X X - FA1 PSC-E01/9-52 120 V AC Circuit Breaker E01 CB-F-1A-A E01-FA1  310942 E01/9 E01/9 EDE-PP-1A MM-CP-2 MM-CP-4  4 MM-CP-2 Process Protection System Cabinet No. 2
- B 310501 CB-F-3A-A X X X - FA2 PSC-E02/9-52 120 V AC Circuit Breaker E02 CB-F-1B-A E02-FA2  310942 E02/9 E02/9 EDE-PP-1B MM-CP-1 MM-CP-3  5 MM-CP-3 Process Protection System Cabinet No. 3
- C 310501 CB-F-3A-A X X X - FA3 PSC-E03/9-52 120 V AC Circuit Breaker E03 CB-F-1A-A E03-FA3  310942 E03/9 E03/9 EDE-PP-1C MM-CP-2 MM-CP-4  6 MM-CP-4 Process Protection System Cabinet No. 4
- D 310501 CB-F-3A-A X X X - FA4 PSC-E04/9-52 120 V AC Circuit Breaker E04 CB-F-1B-A E04-FA4  310942 E04/10 E04/10 EDE-PP-1D MM-CP-1 MM-CP-3 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.5

-3 FUNCTION: SAFEGUARD ACTUATION SYSTEM PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 RC-PT-455 Protection Set I Pressurizer Pressure - Safety Injection Actuation, Clear Manual Block of Safety Injection RC-20846 A 310579 C-F-2-Z X - X - GN5 EDE-MM-121 Electrical Penetration H45 C-F-2-Z ET-F-1A-A GN5-H45/2 FA1-H45/1 FA1-FB5 FA1-FB8 9763-C-509012 9763-C-509046 9763-C-509048 310942 FA1b FA1s FA1e FA1w MM-CP-1 MM-CP-12 MM-CP MM-CP-1 Process Protection System Cabinet No. 1 FA1 CB-F-3A-A MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 8 RC-PT-456 Protection Set II Pressurizer Pressure - Safety Injection Actuation, Clear Manual Block of Safety Injection RC-20846 B 310579 C-F-2-Z X - X - GN5 EDE-MM-131 Electrical Penetration H55 C-F-1-Z ET-F-1C-A GN5-H55/5 FA2-H55/3 FA2-FB5 FA2-FB8 9763-C-509012 9763-C-509046 9763-C-509048 310942 FA2b FA2r FA2e FA2w MM-CP-2 MM-CP-12 MM-CP MM-CP-2 Process Protection System Cabinet No. 2 FA2 CB-F-3A-A MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 9 RC-PT-457 Protection Set III Pressurizer Pressure - Safety Injection Actuation, Clear Manual Block of Safety Injection RC-20846 C 310579 C-F-2-Z X - X - GN5 EDE-MM-123 Electrical Penetration H47 C-F-2-Z ET-F-1A-A GN5-H47/3 FA3-H47/3 FA3-FB5 FA3-FB8 9763-C-509012 9763-C-509046 9763-C-509048 310942 FA3b FA3r FA3e FA3v MM-CP-3 MM-CP-12 MM-CP MM-CP-3 Process Protection System Cabinet No. 3 FA3 CB-F-3A-A MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 10 RC-PT-458 Protection Set IV Pressurizer Pressure - Safety Injection Actuation RC-20846 D 310579 C-F-2-Z X - X - GN5 EDE-MM-128 Electrical Penetration H52 C-F-1-Z ET-F-1C-A GN5-H52/1 FA4-H52/2 FA4-FB5 FA4-FB8 9763-C-509012 9763-C-509046 9763-C-509048 310942 FA4b FA4r FA4e FA4u MM-CP-4 MM-CP-12 MM-CP MM-CP-4 Process Protection System Cabinet No. 4 FA4 CB-F-3A-A MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 11 SI-CS-2480 Control Switch - Steam Line Safety Injection Block Control - A 310443 CB-F-3A-A X - X - F51 MM-CP-12 Solid State Protection System Cabinet FB6 CB-F-3A-A F51-FB6 310949 FB6g FB6h FB6k MM-CP 12 SI-CS-2490 Control Switch - Steam Line Safety Injection Block Control - B 310443 CB-F-3A-A X - X - F51 MM-CP-13 Solid State Protection System Cabinet FB9 CB-F-3A-A F51-FB9 310949 FB9g FB9h FB9k MM-CP 13 SI-CS-2488 Control Switch - Pressurizer Pressure Safety Injection Block Control - A 310443 CB-F-3A-A X - X - F40 MM-CP-12 Solid State Protection System Cabinet FB6 CB-F-3A-A F40-FB6 310949 FB6g FB6h FB6k MM-CP 14 SI-CS-2498 Control Switch - Pressurizer Pressure Safety Injection Block Control - B 310443 CB-F-3A-A X - X - F41 MM-CP-13 Solid State Protection System Cabinet FB9 CB-F-3A-A F48-FB9/2 310949 FB9g FB9h FB9k MM-CP SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.5 -4 FUNCTION: SAFEGUARD ACTUATION SYSTEM PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 FW-PT-514 Protection Set I/ Steam Generator Loop 1 - Safety Injection MS-20580 A 310589 MS-F-1B-Z X - X - GL6 MM-CP-1 Process Protection Cabinet No. 1 FA1 CB-F-3A-A FA1-GL6 FA1-FB5 FA1-FB8 9763-C-509013 9763-C-509047 9763-C-509048 310942 FA1b FA1h FA1e FA1l MM-CP-1 MM-CP-12 MM-CP MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 16 FW-PT-515 Protection Set II/ Steam Generator Loop 1 - Safety Injection MS-20580 B 310589 MS-F-1B-Z X - X - GZ6 MM-CP-2 Process Protection Cabinet No. 2 FA2 CB-F-3A-A FA2-GZ6 FA2-FB5 FA2-FB8 9763-C-509015 9763-C-509047 9763-C-509048 310942 FA2b FA2h FA2e FA2l MM-CP-2 MM-CP-12 MM-CP MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 17 FW-PT-516 Protection Set IV/ Steam Generator Loop 1

- Safety Injection MS-20580 D 310589 MS-F-1B-Z X - X - PS3 MM-CP-4 Process Protection Cabinet No. 4 FA4 CB-F-3A-A FA4-PS3 FA4-FB5/1 FA4-FB8/1 9763-C-509021 9763-C-509047 9763-C-509048 310942 FA4b FA4h FA4e FA4l MM-CP-4 MM-CP-12 MM-CP MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 18 FW-PT-524 Protection Set I/ Steam Generator Loop 2 - Safety Injection MS-20581 A 310586 MS-F-3A-Z X - X - GL5 MM-CP-1 Process Protection Cabinet No. 1 FA1 CB-F-3A-A FA1-GL5 FA1-FB5 FA1-FB8 9763-C-509013 9763-C-509047 9763-C-509048 310942 FA1b FA1h FA1e FA1l MM-CP-1 MM-CP-12 MM-CP MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 19 FW-PT-525 Protection Set II/ Steam Generator Loop 2

- Safety Injection MS-20581 B 310586 MS-F-3A-Z X - X - GZ4 MM-CP-2 Process Protection Cabinet No. 2 FA2 CB-F-3A-A FA2-GZ4 FA2-FB5 FA2-FB8 9763-C-509016 9763-C-509047 9763-C-509048 310942 FA2b FA2h FA2e FA2l MM-CP-2 MM-CP-12 MM-CP MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 20 FW-PT-526 Protection Set III/ Steam Generator Loop 2

- Safety Injection MS-20581 C 310586 MS-F-3A-Z X - X - PS1 MM-CP-3 Process Protection Cabinet No. 3 FA3 CB-F-3A-A FA3-PS1 FA3-FB5/1 FA3-FB8/1 9763-C-509021 9763-C-509047 9763-C-509048 310942 FA3b FA3h FA3e FA3l FA3f MM-CP-3 MM-CP-12 MM-CP MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 21 FW-PT-534 Protection Set I/ Steam Generator Loop 3 - Safety Injection MS-20581 A 310586 MS-F-3A-Z X - X - GL5 MM-CP-1 Process Protection System Cabinet No. 1 FA1 CB-F-3A-A FA1-GL5 FA1-FB5/2 FA1-FB8/2 9763-C-509014 9763-C-509047 9763-C-509048 310942 FA1b FA1h FA1e FA1f FA1l MM-CP-1 MM-CP-12 MM-CP-13 MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.5 -5 FUNCTION: SAFEGUARD ACTUATION SYSTEM PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 22 FW-PT-535 Protection Set II/ Steam Generator Loop 3

- Safety Injection MS-20581 B 310586 MS-F-3A-Z X - X - GZ4 MM-CP-2 Process Protection System Cabinet No. 2 FA2 CB-F-3A-A FA2-GZ4 FA2-FB5/2 FA2-FB8/2 9763-C-509015 9763-C-509047 9763-C-509048 310942 FA2b FA2h FA2e FA2f FA2l MM-CP-2 MM-CP-12 MM-CP-13 MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 23 FW-PT-536 Protection Set III/ Steam Generator Loop 3 - Safety Injection MS-20581 C 310586 MS-F-3A-Z X - X - PS2 MM-CP-3 Process Protection System Cabinet No. 3 FA3 CB-F-3A-A FA3-PS2 FA3-FB5/1 FA3-FB8/1 9763-C-509021 9763-C-509047 9763-C-509048 310942 FA3b FA3h FA3e FA3f FA3l MM-CP-3 MM-CP-12 MM-CP-13 MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 24 FW-PT-544 Protection Set I/ Steam Generator Loop 4 - Safety Injection MS-20580 A 310589 MS-F-1B-Z X - X - GL6 MM-CP-1 Process Protection System Cabinet No. 1 FA1 CB-F-3A-A FA1-GL6 FA1-FB5/2 FA1-FB8/2 9763-C-509014 9763-C-509047 9763-C-509048 310942 FA1b FA1h FA1e FA1f FA1l MM-CP-1 MM-CP-12 MM-CP-13 MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 25 FW-PT-545 Protection Set II/ Steam Generator Loop 4 - Safety Injection MS-20580 B 310589 MS-F-1B-Z X - X - GZ6 MM-CP-2 Process Protection System Cabinet No. 2 FA2 CB-F-3A-A FA2-GZ6 FA2-FB5/2 FA2-FB8/2 9763-C-509016 9763-C-509047 9763-C-509048 310942 FA2b FA2h FA2e FA2f FA2l MM-CP-2 MM-CP-12 MM-CP-13 MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 26 FW-PT-546 Protection Set IV/ Steam Generator Loop 4

- Safety Injection MS-20580 D 310589 MS-F-1B-Z X - X - PS4 MM-CP-4 Process Protection System Cabinet No. 4 FA4 CB-F-3A-A FA4-PS4 FA4-FB5/1 FA4-FB8/1 9763-C-509021 9763-C-509047 9763-C-509048 310942 FA4b FA4h FA4e FA4f FA4l MM-CP-4 MM-CP-12 MM-CP-13 MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 27 SI-PT-934 Protection Set IV, Containment Pressure - P Signal Containment Isolation Phase B Actuation, Safety Injection Actuation, Containment Spray Actuation

- D 310694 ET-F-1C-A X - X - P85 MM-CP-4 Process Protection System Cabinet No. 4 FA4 CB-F-3A-A FA4-P85/1 FA4-FB5/1 FA4-FB8/1 9763-C-509022 9763-C-509048  310942  FA4a  FA4b  FA4d  FA4e MM-CP-4 MM-CP-12 MM-CP             MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A              MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A     28 SI-PT-935 Protection Set III, Containment Pressure 

- P Signal Containment Isolation Phase B Actuation, Safety Injection Actuation, Containment Spray Actuation

- C 310694 ET-F-1C-A X - X - P86 MM-CP-3 Process Protection System Cabinet No. 3 FA3 CB-F-3A-A FA3-P86/1 FA3-FB5/1 FA3-FB8/1 9763-C-509022 9763-C-509048  310942  FA3a  FA3b  FA3d  FA3e  FA3f MM-CP-3 MM-CP-12 MM-CP             MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A              MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.5

-6 FUNCTION: SAFEGUARD ACTUATION SYSTEM PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 29 SI-PT-936 Protection Set II, Containment Pressure - P Signal Containment Isolation Phase B Actuation, Safety Injection Actuation, Containment Spray Actuation

- B 310769 PP-F-4B-Z X - X - P87 MM-CP-2 Process Protection System Cabinet No. 2 FA2 CB-F-3A-A FA2-P87 FA2-FB5/2 FA2-FB8/2 9763-C-509022 9763-C-509048  310942  FA2a  FA2b  FA2d  FA2e  FA2f MM-CP-2 MM-CP-12 MM-CP             MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A              MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A     30 SI-PT-937 Protection Set I, Containment Pressure 

- P Signal Containment Isolation Phase B Actuation, Containment Spray Actuation

- A 310769 PP-F-4B-Z X - X - P88 MM-CP-1 Process Protection System Cabinet No. 1 FA1 CB-F-3A-A FA1-P88/1 FA1-FB5/2 FA1-FB8/2 9763-C-509022 9763-C-509048  310942  FA1a  FA1b  FA1d  FA1e  FA1f MM-CP-1 MM-CP-12 MM-CP             MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A              MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6

-1 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 RH-P-8A Residual Heat Removal Pump SI-20448 A 310761 RHR-F-1D-Z - X X - M11 RH-A57-52 4160 V AC Circuit Breaker A57 CB-F-1A-A A57-M11 A57-F20/1 A57-F20/2 A57-HR9 F20-FB7 310887 A57a A57g A57b A57c A57d CBA-FN-19 CBA-FN-20 EAH-FN-5A EAH-FN-31A EDE-SWG-5 RH-P-8B RH-A57-FU Fuses A57 CB-F-1A-A RH-CS-2467-2 Control Switch A57 CB-F-1A-A RH-SS-2467 Selector Switch A57 CB-F-1A-A EDE-A53-94-1A Bus Under Voltage Relay A53 CB-F-1A-A RH-A57-G,R,W Indicating Lights A57 CB-F-1A-A RH-A57-86 Lockout Relay A57 CB-F-1A-A RH-A57-52H Truck-Operated Contact A57 CB-F-1A-A RH-A57-50/51 Instrument/Time Overcurrent Relays øA, øC A57 CB-F-1A-A RH-A57-51GS Ground Sensor Relay A57 CB-F-1A-A RH-A57-AM Ammeter A57 CB-F-1A-A RH-A57-AS Ammeter Switch A57 CB-F-1A-A RH-A57-CT Current Transformers (75/5) A57 CB-F-1A-A RH-A57-TD1 CT Test Device A57 CB-F-1A-A RH-A57-ATR Transducer A57 CB-F-1A-A RH-A57-TD2 Lockout Relay Test Device A57 CB-F-1A-A RH-A57-52Z Time Delay Relay A57 CB-F-1A-A RH-CS-2467-1 Control Switch with Indication F20 CB-F-3A-A RH-HR9-PR1,RMO,SR2 Emergency Power Sequencer Relays HR9 CB-F-1A-A RH-FB7-K-601A Safety Injection Signal Actuating Relay FB7 CB-F-3A-A

.Notes:  1. This equipment is mechanical with no electrical requirements.
2. Electrical Conduit Plan Drawing 310761 is listed to show fire zone corresponding to the location of the RHR pump oil cooler which is identified in Drawing 805020.
3. Electrical Conduit Plan Drawings 310761 and 310762 are listed to show fire zone corresponding to the location of the RHR heat exchanger which is identified in Drawings 805202 and 805203.
4. Electrical Conduit Plan Drawing 310761 is listed corresponding to the location of the RHR sampling valve which is identified in Drawing 805201.
5. Air and power are not required for support as valve fails to safe shutdown position.
6. These valves are also listed in Table MCR 3.1.3.2.
7. These valves are closed with their circuit breakers locked open during 100% power operation. This will prevent spurious operation. For cold shutdown, these valves are energized for repositioning.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -2 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 RH-P-8B Residual Heat Removal Pump RH-20663 B 310761 RHR-F-1C-Z - X X - M12 RH-A77-52 4160 V AC Circuit Breaker A77 CB-F-1B-A A77-M12 A77-F20/1 A77-F20/2 A77-HR0 F20-FB0 310887 A77a A77g A77b A77c A77d CBA-FN-32 CBA-FN-33 EAH-FN-5B EAH-FN-31B EDE-SWG-6 RH-P-8A RH-A77-FU Fuses A77 CB-F-1B-A RH-CS-2468-2 Control Switch A77 CB-F-1B-A RH-SS-2468 Selector Switch A77 CB-F-1B-A EDE-A73-94-1A Bus Under Voltage Relay A73 CB-F-1B-A RH-A77-G,R,W Indicating Lights A77 CB-F-1B-A RH-A77-86 Lockout Relay A77 CB-F-1B-A RH-A77-52H Truck-Operated Contact A77 CB-F-1B-A RH-A77-50/51 Instrument/Time Overcurrent Relays øA, øC A77 CB-F-1B-A RH-A77-51GS Ground Sensor Relay A77 CB-F-1B-A RH-A77-AM Ammeter A77 CB-F-1B-A RH-A77-AS Ammeter Switch A77 CB-F-1B-A RH-A77-CT Current Transformers (75/5) A77 CB-F-1B-A RH-A77-TD1 CT Test Device A77 CB-F-1B-A RH-A77-ATR Transducer A77 CB-F-1B-A RH-A77-TD2 Lockout Relay Test Device A77 CB-F-1B-A RH-A77-52Z Time Delay Relay A77 CB-F-1B-A RH-CS-2468-1 Control Switch with Indication F20 CB-F-3A-A RH-HR0-PR1,RMO,SR2 Emergency Power Sequencer Relays HR0 CB-F-1B-A RH-FB0-K-601B Safety Injection Signal Actuating Relay FB0 CB-F-3A-A 3 RH-V-14 RH-P-8A to Cold Leg Isolation Valve RH-20662 A 310769 PP-F-1A-Z - X X - V47 RH-B57-52 460 V AC Circuit Breaker B57 CB-F-1A-A B57-V47 B57-F20 310887 B57a B57c CBA-FN-19 CBA-FN-20 RH-V-26 RH-CS-2461 Control Switch F20 CB-F-3A-A RH-ZL-2461-3 Pilot Light F20 CB-F-3A-A RH-B57-42/0,C Motor Starter B57 CB-F-1A-A RH-B57-49 Thermal Overload B57 CB-F-1A-A RH-ZS-V14 Position Switch V47 PP-F-1A-Z 4 RH-V-26 RH-P-8B to Cold Leg Isolation Valve RH-20663 B 310769 PP-F-1B-Z - X X - V48 RH-B65-52 460 V AC Circuit Breaker B65 CB-F-1B-A B65-V48 B65-F20 310887 B65a B65c CBA-FN-32 CBA-FN-33 RH-V-14 RH-CS-2462 Control Switch F20 CB-F-3A-A RH-ZL-2462-3 Pilot Light F20 CB-F-3A-A RH-B65-42/0,C Motor Starter B65 CB-F-1B-A RH-B65-49 Thermal Overload B65 CB-F-1B-A RH-ZS-V26 Position Switch V48 PP-F-1B-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -3 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 RH-V-35 RH-E-9A to Charging Pump Isolation Valve RH-20662 A 310761 RHR-F-4B-Z - X X - V53 RH-B59-52 460 V AC Circuit Breaker B59 CB-F-1A-A V49-V57 V49-V58 B59-V49 B59-F20 B59-F20/1 B59-H36 H36-V25 B59-V53/1 B59-V53/2 V25-V27 B59-Y32 310887 B59a B59c CBA-FN-19 CBA-FN-20 None RH-CS-2465 Control Switch with Indication F20 CB-F-3A-A RH-B59-42/0,C Motor Starters B59 CB-F-1A-A RH-ZS-V35 Position Switch V53 RHR-F-4B-Z SI-ZS-V89 Isolation Valve V58 RHR-F-2A-Z SI-ZS-V90 Isolation Valve V49 RHR-F-2B-Z SI-ZS-V93 Isolation Valve V57 RHR-F-2B-Z CBS-ZS-V8 Containment Sump Isolation Valve V35 PP-F-1A-Z RC-ZS-V23 RHR Letdown and Inlet Isolation Valve V25 C-F-1-Z RC-ZS-V22 RHR Letdown and Inlet Isolation Valve V27 C-F-1-Z RH-B59-49 Thermal Overload Relay B59 CB-F-1A-A EDE-TBX-X32 Terminal Box Y32 PP-F-1A-Z 6 RH-V-36 RH-E-9B to SI Pump Isolation Valve SI-20449 B 310761 RHR-F-2A-Z - X X - V54 RH-B66-52 460 V AC Circuit Breaker B66 CB-F-1B-A V49-V57/1 V57-V58 B66-V57 B66-V54/2 B66-V54/1 B66-F20 H36-V25 B66-F20/1 B66-Y35 B66-H39 H39-V26 V26-V28 310887 B66a B66c CBA-FN-32 CBA-FN-33 None RH-CS-2466 Control Switch with Indication F20 CB-F-3A-A RH-B66-42/0,C Motor Starters B66 CB-F-1B-A RH-B66-49 Thermal Overload B66 CB-F-1B-A RH-ZS-V36 Position Switch V54 RHR-F-2A-Z SI-ZS-V90 Isolation Valve V49 RHR-F-2B-Z SI-ZS-V89 Isolation Valve V58 RHR-F-2A-Z SI-ZS-V93 Isolation Valve V57 RHR-F-2B-Z CBS-ZS-V14 Containment Sump Isolation Valve V36 PP-F-1B-Z RC-ZS-V87 RHR Letdown and Inlet Isolation Valve V26 C-F-1-Z RC-ZS-V88 RHR Letdown and Inlet Isolation Valve V28 C-F-1-Z EDE-TBX-Y35 Terminal Box Y35 PP-F-1B-Z 7 RH-V-32 RHR PP to Hot Leg Isolation Valve RH-20663 B 310769 PP-F-1A-Z - X X - V51 RH-B58-52 460 V AC Circuit Breaker B58 CB-F-1B-A B58-V51 B58-F20 310887 B58a B58c CBA-FN-32 CBA-FN-33 None RH-CS-2460 Control Switch F20 CB-F-3A-A RH-ZL-2460-3 Pilot Light F20 CB-F-3A-A RH-B58-42 Motor Starter B58 CB-F-1B-A RH-B58-49 Thermal Overload B58 CB-F-1B-A RH-ZS-V32 Position Switch V51 PP-F-1A-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -4 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 8 RH-V-70 RHR to Hot Leg Isolation Valve RH-20663 A 310769 PP-F-1A-Z - X X - VB4 RH-D90-52 460 V AC Circuit Breaker D90 CB-F-1A-A D90-VB4/1 D90-F20 310887 D90a D90c CBA-FN-19 CBA-FN-20 None RH-CS-2479 Control Switch F20 CB-F-3A-A RH-ZL-2479-3 Pilot Light F20 CB-F-3A-A RH-D90-42 Motor Starter D90 CB-F-1A-A RH-D90-49 Thermal Overload D90 CB-F-1A-A RH-ZS-V70 Position Switch VB4 PP-F-1A-Z 9 RH-HCV-606 RH-FCV-618 RH-E-9A Outlet Flow control Valve and Bypass Flow Control Valve RH-20662 A 310761 RHR-F-4B-Z - X X X LG8 LH3 RC-CS-618 Control Switch F20 CB-F-3A-A F20-GK0 F20-VW3 310887 E87/2a E87/2c E87/2e E87/2d E87/2f CBA-FN-19 CBA-FN-20 RH-HCV-607 RH-FCV-619 Note 5 RC-CS-606 Control Switch F20 CB-F-3A-A RC-FY-618-1 E-9A RC Bypass Solenoid Valve VW3 RHR-F-4B-Z RC-HY-606-1 E-9A Outlet Valve GK0 RHR-F-4B-Z 10 RH-HCV-607 RH-FCV-619 RH-E-9B Outlet Flow control Valve and Bypass Flow Control Valve RH-20663 B 310761 RHR-F-4A-Z - X X X LG9 LH4 RC-CS-619 Control Switch F20 CB-F-3A-A F20-U7W F20-VW4 310887 E88/2a E88/2c E88/2e E88/2d E88/2f CBA-FN-32 CBA-FN-33 RH-HCV-606 RH-FCV-618 Note 5 RC-CS-607 Control Switch F20 CB-F-3A-A RC-FY-619-1 E-9B RC Bypass Solenoid Valve VW4 RHR-F-4A-Z RC-HY-607-1 E-9B Outlet Valve U7W RHR-F-4A-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -5 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 RC-V-22 RHR Inlet Isolation Valve RH-20841 B 310582 C-F-1-Z - X X - V27 RC-B54-52-1,2 460 V AC Circuit Breakers B54 CB-F-1B-A B54-G2J B54-G2J/1 B54-H39 B54-H24 H24-V27 H39-V27 F20-G2J F20-FF9/2 B54-V53 310882 B54a B54c B54d EDE-MCC-621 CBA-FN-32 CBA-FN-33 CAH-FN-1A CAH-FN-1B CAH-FN-1D RC-V-88 Notes 6 and 7 RC-B54-FU Fuse B54 CB-F-1B-A RC-CS-7302-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7302 Selector Switch G2J CB-F-1B-A RC-B54-42-1/0,C Motor Starters B54 CB-F-1B-A RC-B54-42-2 Motor Starter B54 CB-F-1B-A RC-B54-49-1,2 Overload Relays B54 CB-F-1B-A EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A RC-ZS-7302B Valve Position and Open/Close Torque Switches V27 C-F-1-Z RC-ZL-7302-1 Pilot Light G2J CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-CS-7302-1 Control Switch with Indication F20 CB-F-3A-A RC-ZL-7302-2 Pilot Light F20 CB-F-3A-A RH-ZS-2465B Valve Position Limit Switch and Open/Close Torque Switches V53 RHR-F-4B-Z RC-FF9-K734B PSC Actuating Auxiliary Relay FF9 CB-F-3A-A RC-EH0/16-52 120 V AC Circuit Breaker EH0 CB-F-1B-A E4J-EH0/1 E4J-G2J G2J-H39/6 H39-V26/3 GZ0-U8U ED0-GZ0/1 H39-V27/1 F20-G2J/2 F26-GZ0/4 EHO/16a EHO/16c EHO/16b EH0/16d EDE-PP-1F CBA-FN-32 CBA-FN-33 RC-CS-7310-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7310 Selection Switch G2J CB-F-1B-A RC-ZS-V87 Valve Position and Open/Close Torque Switches V26 C-F-1-Z EDE-MM-115 Electrical Penetration H39 C-F-1-Z RC-EJ4-FU9 & 10 30 Amp Fuses E4J ET-F-1C-A RC-CS-7302-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7302 Selector Switch G2J CB-F-1B-A RC-ZS-7302B Valve Position and Open/Close Torque Switches V27 C-F-1-Z RC-CS-2896-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-2896 Selector Switch GZ0 CB-F-1B-A RC-ZS-FV-2896 Valve Position Switch U8U PP-F-1B-Z RC-ED0-R1 Auxiliary Relay ED0 CB-F-1B-A RC-ED0-R2 Auxiliary Relay ED0 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -6 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS RC-V-22 (Continued) RC-CS-7302-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-7310-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-2896-1 Control Switch with Indication F29 CB-F-3A-A RC-PT-403 Wide-Range Pressure Transmitter P76 ET-F-1C-A FA4-P76/1 FA4-FB8 C-509036 310942 FA4r FA4w FA4b FA4e MM-CP-4 MM-CP-13 MM-CP-4 Process Protection System Cabinet No. 4 FA4 CB-F-3A-A MC-CP-13 Solid State Protection System Output No. 2 Cabinet FF9 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -7 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 12 RC-V-23 RHR Inlet Isolation Valve RC-20841 A 310576 C-F-1-Z X X X - V25 RC-B53-52-1,2 460 V AC Circuit Breakers B53 CB-F-1A-A B53-G2G B53-G2G/1 B53-H36 B53-H19 H36-V25/2 H19-V25 F20-G2G F20-FF8/2 B53-V53 310882 B53a B53c B53d EDE-MCC-521 CBA-FN-19 CBA-FN-20 CAH-FN-1C CAH-FN-1E CAH-FN-1F RC-V-87 Notes 6 and 7 RC-B53-FU Fuse B53 CB-F-1A-A RC-CS-7303-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7303 Selector Switch G2G CB-F-1A-A RC-ZL-7303-1 Pilot Light G2G CB-F-1A-A RC-B53-42-1/0,C Motor Starters B53 CB-F-1A-A RC-B53-42-2 Motor Starter B53 CB-F-1A-A RC-B53-49-1,2 Overload Relays B53 CF-F-1A-A EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A RC-ZS-V23 Valve Position and Open/Close Torque Switches V25 C-F-1-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-CS-7303-1 Control Switch with Indication F20 CB-F-3A-A RC-ZL-7303-2 Pilot Light F20 CB-F-3A-A RH-ZS-2465A Valve Position Switch V53 RHR-F-4B-Z RC-FF8-K-734A PSC Actuating Auxiliary Relay FF8 CB-F-3A-A RC-PT-405 Wide-Range Pressure Transmitter P78 ET-F-1C-A FA1-P78/1 FA1-FB5/2 C-509036 310942 FA1r FA1w FA1b FA1e MM-CP-1 MM-CP-12 MM-CP-1 Process Protection System Cabinet No. 1 FA1 CB-F-3A-A MM-CP-12 Solid State Protection System Output No. 2 Cabinet FF8 CB-F-3A-A RC-EH9/16-52 120 V AC Circuit Breaker EH9 CB-F-1A-A E4H-EH9/1 E4H-G2G G2G-H36/8 H36-V25/3 H36-V28/1 G81-U8T EC8-G81 F20-G2G/2 F29-G81/2 EC8-G81/1 EH9/16a EH9/16c EH9/16b EH9/16d EDE-PP-1E CBA-FN-19 CBA-FN-20 RC-CS-7303-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7303 Selection Switch G2G CB-F-1A-A RC-ZS-V23 Valve Position and Open/Close Torque Switches V25 C-F-1-Z EDE-MM-112 Electrical Penetration H36 ET-F-1A-A, C-F-2-Z RC-E4H-FU-9,10 30 Amp Fuses E4H CB-F-1A-A RC-CS-7311-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7311 Selector Switch G2G CB-F-1A-A RC-ZS-7311A Valve Position and Open/Close Torque Switches V28 C-F-1-Z RC-CS-2894-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-2894 Selector Switch G81 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -8 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS RC-V-23 (Continued) RC-ZS-FV-2894 Valve Position Switch U8T PP-F-1B-Z RC-EC8-R1 Auxiliary Relay EC8 CB-F-1A-Z RC-EC8-R2 Auxiliary Relay EC8 CB-F-1A-Z RC-CS-7311-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-7303-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-2894-1 Control Switch with Indication F29 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -9 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 RC-V-87 RHR Inlet Isolation Valve RC-20844 B 310582 C-F-1-Z X X X - V26 RC-B61-52-1,2 460 V AC Circuit Breakers B61 CB-F-1B-A B61-G2J B61-G2J/1 B61-H39 B61-H24 H39-V26/2 H24-V26 F20-G2J/1 F20-FF9/1 B61-V54 310882 B61a B61c B61d EDE-MCC-621 CBA-FN-32 CBA-FN-33 CAH-FN-1A CAH-FN-1B CAH-FN-1D RC-V-23 Notes 6 and 7 RC-B61-FU Fuse B61 CB-F-1B-A RC-CS-7310-2 Control Switch with Indicator G2J CB-F-1B-A RC-SS-7310 Selector Switch G2J CB-F-1B-A RC-ZL-7310-1 Pilot Light G2J CB-F-1B-A RC-B61-42-1/0,C Motor Starters B61 CB-F-1B-A RC-B61-42-2 Motor Starter B61 CB-F-1B-A RC-B61-49-1,2 Overload Relays B61 CB-F-1B-A RC-ZS-V87 Valve Position and Open/Close Torque Switches V26 C-F-1-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-CS-7310-1 Control Switch with Indication F20 CB-F-3A-A RC-ZL-7310-2 Pilot Light F20 CB-F-3A-A RH-ZS-2466B Valve Position Limit Switch V54 RHR-F-2A-Z RC-FF9-K734B PSC Actuating Auxiliary Relay FF9 CB-F-3A-A RC-PT-403 Wide-Range Pressure Transmitter P76 ET-F-1C-A FA4-P76/1 FA4-FB8 C-509036 310942 FA4r FA4w FA4b FA4e MM-CP-4 MM-CP-13 MM-CP-4 Process Protection System Cabinet No. 4 FA4 CB-F-3A-A MM-CP-13 Solid State Protection System Output No. 2 Cabinet FF9 CB-F-3A-A RC-EH0/16-52 120 v AC Circuit Breaker EH0 CB-F-1B-A E4J-EH0/1 E4J-GZJ G2J-H39/6 H39-V26/3 GZ0-U8U ED0-GZ0/1 H39-V27/1 F20-G2J/2 F26-GZ0/4 EH0/16a EH0/16c EH0/16b EH0/16d EDE-PP-1F CBA-FN-32 CBA-FN-33 RC-CS-7310-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7310 Selector Switch G2J CB-F-1B-A RC-ZS-V87 Valve Position and Open/Close Torque Switches V26 C-F-1-Z EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-E4J-FU-9,10 30 Amp Fuses E4J CB-F-1B-A RC-CS-7302-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7302 Selector Switch G2J CB-F-1B-A RC-ZS-7302B Valve Position and Open/Close Torque Switches V27 C-F-1-Z RC-CS-2896-2 Control Switch with Indication GZ0 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -10 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS RC-V-87 (Continued) RC-SS-2896 Selector Switch GZ0 CB-F-1B-A RC-ZS-FV-2896 Valve Position Switch U8U PP-F-1B-Z RC-ED0-R1 Auxiliary Relay ED0 CB-F-1B-A RC-ED0-R2 Auxiliary Relay ED0 CB-F-1B-A RC-CS-7302-1 Control Switch with Indication F20 CB-F-3B-A RC-CS-7310-1 Control Switch with Indication F20 CB-F-3B-A RC-CS-2896-1 Control Switch with Indication F29 CB-F-3B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -11 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 14 RC-V-88 RHR Inlet Isolation Valve RH-20662 A 310577 C-F-1-Z X X X - V28 RC-B62-52-1,2 460 V AC Circuit Breakers B62 CB-F-1A-A B62-G2G B62-G2G/1 B62-H36 B62-H19 H36-V28 H19-V28 F20-G2G/1 F20-FF8/3 B62-V54 310882 B62a B62c B62d EDE-MCC-521 CBA-FN-19 CBA-FN-20 CAH-FN-1C CAH-FN-1E CAH-FN-1F RC-V-22 Notes 6 and 7 RC-B62-FU Fuse B62 CB-F-1A-A RC-CS-7311-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7311 Selector Switch G2G CB-F-1A-A RC-ZL-7311-1 Pilot Light G2G CB-F-1A-A RC-B62-42-1/0,C Motor Starters B62 CB-F-1A-A RC-B62-42-2 Motor Starter B62 CB-F-1A-A RC-B62-49-1,2 Overload Relays B62 CB-F-1A-A RC-ZS-7311A Valve Position and Open/Close Torque Switches V28 C-F-1-Z EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-CS-7311-1 Control Switch with Indication F20 CB-F-3A-A RC-ZL-7311-2 Pilot Light F20 CB-F-3A-A RH-ZS-2466A Valve Position Limit Switch V54 RHR-F-1A-Z RC-FF8-K734A PSC Actuating Auxiliary Relay FF8 CB-F-3A-A RC-PT-405 Wide-Range Pressure Transmitter P78 ET-F-1C-A FA1-P78/1 FA1-FB5/2 C-509036 310942 FA1r FA1w FA1b FA1e MM-CP-1 MM-CP-12 MM-CP-1 Process Protection System Cabinet No. 1 FA1 CB-F-3A-A MM-CP-12 Solid State Protection System Output No. 2 Cabinet FF8 CB-F-3A-A RC-EH9/16-52 120 V AC Circuit Breaker EH9 CB-F-1A-A E4H-EH9/1 E4H-G2G G2G-H36/8 H36-V28/1 H36-V25/3 G81-U8T EC8-G81 F20-G2G/2 F29-G81/2 EC8-G81/1 EH9/16a EH9/16c EH9/16b EH9/16d EDE-PP-1E CBA-FN-19 CBA-FN-20 RC-CS-7311-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7311 Selector Switch G2G CB-F-1A-A RC-ZS-7311A Valve Position and Open/Close Torque Switches V28 C-F-1-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-E4H-FU-9,10 30 Amp Fuses E4H CB-F-1A-A RC-CS-7303-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7303 Selector Switch G2G CB-F-1A-A RC-ZS-V23 Valve Position and Open/Close Torque Switches V25 C-F-1-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -12 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS RC-V-88 (Continued) RC-CS-2894-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-2894 Selector Switch G81 CB-F-1A-A RC-ZS-FV-2894 Valve Position Switch U8T PP-F-1B-Z RC-EC8-R1 Auxiliary Relay EC8 CB-F-1A-A RC-EC8-R2 Auxiliary Relay EC8 CB-F-1A-A RC-CS-7303-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-7311-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-2894-1 Control Switch with Indication F29 CB-F-3A-A 15 RH-P-8A RHR Pump Lube Oil Cooler RH-20662 A 310761 805200 RHR-F-1D-Z - X - - - - - - - - - - Component Cooling RH-P-8B Notes 1 and 2 16 RH-P-8B RHR Pump Lube Oil Cooler RH-20663 B 310761 805200 RHR-F-1C-Z - X - - - - - - - - - - Component Cooling RH-P-8A Notes 1 and 2 17 RH-E-9A Residual Heat Removal Heat Exchanger SI-20448 A 310761 310762 805202 805203 RHR-F-3B-Z - X - - - - - - - - - - Component Cooling RH-E-9B Notes 1 and 3 18 RH-E-9B Residual Heat Removal Heat Exchanger RH-20663 B 310761 310762 805202 805203 RHR-F-3A-Z - X - - - - - - - - - - Component Cooling RH-E-9A Notes 1 and 3 19 RH-V-8 RHR Loop A Sample Valve RH-20662 A 310761 805201 RHR-F-4B-Z - X - - - - - - - - - - EAH-FN-5A EAH-FN-31A RH-V-44 Notes 1 and 4 20 RH-V-44 RHR Loop B Sample Valve RH-20663 B 310761 805201 RHR-F-4A-Z - X - - - - - - - - - - EAH-FN-5B EAH-FN-31B RH-V-8 Notes 1 and 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -1 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 SW-P-41A Service Water Loop "A" - Pump "A" SW-20794 A 301140 SW-F-1E-Z X X X - N81 SW-AQ3-52 4160 V AC Circuit Breaker AQ3 CB-F-1A-A AQ3-GN9 AQ3-VL3 AQ3-N81 AQ4-HR2 AQ4-F72/2 AQ3-F72/1 301107 AQ3a AQ3h AQ3b AQ3c AQ3d CBA-FN-19 CBA-FN-20 EDE-SWG-5 SW-P-41B or SW-P-41D SW-AQ3-FU Fuses AQ3 CB-F-1A-A SW-CS-6101-2 Control Switch AQ3 CB-F-1A-A SW-SS-6101 Selector Switch AQ3 CB-F-1A-A SW-ZS-V2 Valve Position Switch VL3 SW-F-1E-Z EDE-A53-94-2 Bus Undervoltage Relay A53 CB-F-1A-A SW-AQ3-52H Truck Operated Contact AQ3 CB-F-1A-A SW-AQ3-50/51 Inst/Time Overcurrent Relays ØA, ØC AQ3 CB-F-1A-A SW-AQ3-51GS Ground Sensor Relay AQ3 CB-F-1A-A SW-AQ3-86 Lockout Relay AQ3 CB-F-1A-A SW-AQ3-CT Current Transformers 100/5A AQ3 CB-F-1A-A SW-AQ3-TD1 Test Device AQ3 CB-F-1A-A SW-AQ3-AM Ammeter AQ3 CB-F-1A-A SW-AQ3-AS Ammeter Switch AQ3 CB-F-1A-A SW-AQ3-G,R,W Indicating Lights AQ3 CB-F-1A-A SW-AQ3-ATR Transducer AQ3 CB-F-1A-A SW-AQ3-TD2 Lockout Relay Test Device AQ3 CB-F-1A-A SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A SW-AQ3-52Z Time Delay Relay AQ3 CB-F-1A-A SW-AQ3-R1 Auxiliary Relay AQ3 CB-F-1A-A SW-CS-6102-1 Control Switch F72 CB-F-3A-A SW-CS-6101-1 Control Switch with Indication F72 CB-F-3A-A SW-HR2-PR1 EPS Permit Relay (K8 and K10) HR2 CB-F-1A-A SW-HR2-SR5 EPS Starting Relay (K80) HR2 CB-F-1A-A SW-HR2-RM0 EPS Manual Override Relay (K32) HR2 CB-F-1A-A SW-AW-4-52S Mechanical Operated Switch AQ4 CB-F-1A-A

.Notes   1. Air is not needed to position or to reposition the valve for safe shutdown.
2. Circuit shown in 301107, Sheet E2T/1a, involving Auxiliary Relay SW

-GN9-RV54 of SW -P-41A also affects SW -P-41C. 3. Circuit shown in 301107, Sheet E2U/1a, involving Auxiliary Relay SW -GN0-RV25 of SW -P-41B also affects SW -P-41D. 4. Electrical power not required for support.

5. The equipment is permanently disabled.
6. During normal operation, this equipment is in its safe shutdown position with its circuit breaker administratively controlled off to prevent its spurious operation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -2 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 SW-P-41A (Continued) SW-GN9-RTA Tower Actuation Sig. Auxiliary Relay GN9 CB-F-1A-A SW-GN9-RX1 TA Signal Relay GN9 CB-F-1A-A SW-ZS-V54 Valve Position Switch and Valve Open/Close Torque Switches VM5 CT-F-2B-A SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A GN9-VM5 E2T/1a E2T/1b CBA-FN-19 CBA-FN-20 Notes 2,4

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -3 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 SW-P-41B Service Water Loop "B" - Pump "B" SW-20794 B 301140 SW-F-1E-Z X X X - N82 SW-AR3-52 4160 V AC Circuit Breaker AR3 CB-F-1B-A AR3-GN0 AR3-VL4 AR3-N82 AR3-F71/1 AR4-F71/3 AR4-HR4 301107 AR3a AR3h AR3b AR3c AR3d CBA-FN-32 CBA-FN-33 EDE-SWG-6 SW-P-41A or SW-P-41C Cooling Towers SW-AR3-FU Fuses AR3 CB-F-1B-A SW-CS-6111-2 Control Switch AR3 CB-F-1B-A SW-SS-6111 Selector Switch AR3 CB-F-1B-A SW-ZS-V29 Valve Position Switch VL4 SW-F-1E-Z EDE-A73-94-2 Bus Undervoltage Relay A73 CB-F-1B-A SW-AR3-52H Truck Operated Contact AR3 CB-F-1B-A SW-AR3-50/51 Inst/Time Overcurrent Relays ØA, ØC AR3 CB-F-1B-A SW-AR3-51GS Ground Sensor Relay AR3 CB-F-1B-A SW-AR3-86 Lockout Relay AR3 CB-F-1B-A SW-AR3-CT Current Transformers 100/5A AR3 CB-F-1B-A SW-AR3-TD1 Test Device AR3 CB-F-1B-A SW-AR3-AM Ammeter AR3 CB-F-1B-A SW-AR3-AS Ammeter Switch AR3 CB-F-1B-A SW-AR3-G,R,W Indicating Lights AR3 CB-F-1B-A SW-AR3-ATR Transduce r AR3 CB-F-1B-A SW-AR3-TD2 Lockout Relay Test Device AR3 CB-F-1B-A SW-GN0-RV25 Auxiliary Relay GN0 CB-F-1B-A SW-AR3-52Z Time Delay Relay AR3 CB-F-1B-A SW-AR3-R1 Auxiliary Relay AR3 CB-F-1B-A SW-CS-6112-1 Control Switch F71 CB-F-3A-A SW-CS-6111-1 Control Switch with Indication F71 CB-F-3A-A SW-HR4-PR1 EPS Permit Relay (K8 and K10) HR4 CB-F-1B-A SW-HR0-SR5 EPS Starting Relay (K80) HR0 CB-F-1B-A SW-HR4-RM0 EPS Manual Override Relay (K32) HR4 CB-F-1B-A SW-AR4-52S Mechanical Operated Switch AR4 CB-F-1B-A SW-GN0-RTB Tower Actuation Sig. Auxiliary Relay GN0 CB-F-1B-A SW-GN0-RX1 TA Signal Relay GN0 CB-F-1B-A SW-ZS-V25 Valve Position Switch and Valve Open/Close Torque Switches VM8 CT-F-2B-A SW-GN0-RV25 Auxiliary Relay GN0 CB-F-1B-A GN0-VM8 E2U/1aE2U/1b CBA-FN-32 CBA-FN-33 Notes 3,4

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -4 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 SW-P-41C Service Water Loop "A" - Pump "C" SW-20794 A 301140 SW-F-1E-Z X X X - N83 SW-AQ4-52 4160 V AC Circuit Breaker AQ4 CB-F-1A-A AQ4-GN9 AQ4-VL5 AQ4-N83 AQ3-F72/2 AQ4-F72/1 AQ3-HR2 301107 AQ4a AQ4h AQ4b AQ4c AQ4d CBA-FN-19 CBA-FN-20 EDE-SWG-5 SW-P-41B or SW-P-41D Note 2 SW-AQ4-FU Fuses AQ4 CB-F-1A-A SW-CS-6102-2 Control Switch AQ4 CB-F-1A-A SW-SS-6102 Selector Switch AQ4 CB-F-1A-A SW-ZS-V22 Valve Position Switch VL5 SW-F-1E-Z EDE-A53-94-2 Bus Undervoltage Relay A53 CB-F-1A-A SW-AQ4-52H Truck Operated Contact AQ4 CB-F-1A-A SW-AQ4-50/51 Inst/Time Overcurrent Relays ØA, ØC AQ4 CB-F-1A-A SW-AQ4-51GS Ground Sensor Relay AQ4 CB-F-1A-A SW-AQ4-86 Lockout Relay AQ4 CB-F-1A-A SW-AQ4-CT Current Transformers 100/5A AQ4 CB-F-1A-A SW-AQ4-TD1 Test Device AQ4 CB-F-1A-A SW-AQ4-AM Ammeter AQ4 CB-F-1A-A SW-AQ4-AS Ammeter Switch AQ4 CB-F-1A-A SW-AQ4-G,R,W Indicating Lights AQ4 CB-F-1A-A SW-AQ4-ATR Transducer AQ4 CB-F-1A-A SW-AQ4-TD2 Lockout Relay Test Device AQ4 CB-F-1A-A SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A SW-AQ4-52Z Time Delay Relay AQ4 CB-F-1A-A SW-CS-6102-1 Control Switch F72 CB-F-3A-A SW-CS-6101-1 Control Switch with Indication F72 CB-F-3A-A SW-HR2-PR1 EPS Permit Relay (K8 and K10) HR2 CB-F-1A-A SW-HR2-SR5 EPS Starting Relay (K80) HR2 CB-F-1A-A SW-HR2-RM0 EPS Manual Override Relay (K32) HR2 CB-F-1A-A SW-AQ3-52S Mechanical Operated Switch AQ3 CB-F-1A-A SW-GN9-RTA Tower Actuation Sig. Auxiliary Relay GN9 CB-F-1A-A SW-GN9-RX1 TA Signal Relay GN9 CB-F-1A-A SW-AQ4-R1 Auxiliary Relay AR4 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -5 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 SW-P-41D Service Water Loop "B" - Pump "D" SW-20794 B 301140 SW-F-1E-Z X X X - N84 SW-AR4-52 4160 V AC Circuit Breaker AR4 CB-F-1B-A AR4-GN0 AR4-VL6 AR4-N84 AR3-F71/3 AR4-F71/1 AR3-HR4 301107 AR4a AR4h AR4b AR4c AR4d CBA-FN-32 CBA-FN-33 EDE-SWG-6 SW-P-41A SW-P-41C Cooling Towers Note 3 SW-AR4-FU Fuses AR4 CB-F-1B-A SW-CS-6112-2 Control Switch AR4 CB-F-1B-A SW-SS-6112 Selector Switch AR4 CB-F-1B-A SW-ZS-V31 Valve Position Switch VL6 SW-F-1E-Z EDE-A73-94-2 Bus Undervoltage Relay A73 CB-F-1B-A SW-AR4-52H Truck Operated Contact AR4 CB-F-1B-A SW-AR4-50/51 Inst/Time Overcurrent Relays ØA, ØC AR4 CB-F-1B-A SW-AR4-51GS Ground Sensor Relay AR4 CB-F-1B-A SW-AR4-86 Lockout Relay AR4 CB-F-1B-A SW-AR4-CT Current Transformers 100/5A AR4 CB-F-1B-A SW-AR4-TD1 Test Device AR4 CB-F-1B-A SW-AR4-AM Ammeter AR4 CB-F-1B-A SW-AR4-AS Ammeter Switch AR4 CB-F-1B-A SW-AR4-G,R,W Indicating Lights AR4 CB-F-1B-A SW-AR4-ATR Transducer AR4 CB-F-1B-A SW-AR4-TD2 Lockout Relay Test Device AR4 CB-F-1B-A SW-GN0-RV25 Auxiliary Relay GN0 CB-F-1B-A SW-AR4-52Z Time Delay Relay AR4 CB-F-1B-A SW-CS-6112-1 Control Switch F71 CB-F-3A-A SW-CS-6111-1 Control Switch with Indication F71 CB-F-3A-A SW-HR4-PR1 EPS Permit Relay (K8 and K10) HR4 CB-F-1B-A SW-HR4-SR5 EPS Starting Relay (K80) HR4 CB-F-1B-A SW-HR4-RM0 EPS Manual Override Relay (K32) HR4 CB-F-1B-A SW-AR3-52S Mechanical Operated Switch AR3 CB-F-1B-A SW-GN0-RTB Tower Actuation Sig. Auxiliary Relay GN0 CB-F-1B-A SW-GN0-RX1 TA Signal Relay GN0 CB-F-1B-A SW-AR4-R1 Auxiliary Relay AR4 CB-F-1B-A SW-AR4-R2 Auxiliary Relay AR4 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -6 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 SW-V2 Service Water Pump "A" Discharge Valve SW-20794 A 301140 SW-F-1E-Z X X X - VL3 SW-CR6-52 460 V AC Circuit Breaker CR6 SW-F-1B-A AQ3-CR6 CR6-VL3/1 CR6-VL3 301107 CR6a CR6c SWA-FN-40A EDE-MCC-514 SW-V-29 or SW-V-31 SW-AQ3-52S Mechanically Operated Contact AQ3 CB-F-1A-A SW-ZS-V2 Valve Position Switch and Valve Open/Close Torque Switches VL3 SW-F-1E-Z SW-CR6-42/0,C Motor Starters CR6 SW-F-1B-A SW-CR6-49 Overload Relay CR6 SW-F-1B-A SW-CR6-FU Fuses CR6 SW-F-1B-A SW-ECO-TDR Time Delay Relay ECO SW-F-1B-A 6 SW-V22 Service Water Pump "C" Discharge Valve SW-20794 A 301140 SW-F-1E-Z X X X - VL5 SW-CR7-52 460 V AC Circuit Breaker CR7 SW-F-1B-A AQ4-CR7 CR7-VL5/1 CR7-VL5 301107 CR7a CR7c SWA-FN-40A EDE-MCC-514 SW-V-29 or SW-V-31 SW-AQ4-52S Mechanically Operated Contact AQ4 CB-F-1A-A SW-ZS-V22 Valve Position Switch and Valve Open/Close Torque Switches VL5 SW-F-1E-Z SW-CR7-42/0,C Motor Starters CR7 SW-F-1B-A SW-CR7-49 Overload Relay CR7 SW-F-1B-A SW-CR7-FU Fuses CR7 SW-F-1B-A SW-ECO-TDR Time Delay Relay ECO SW-F-1B-A 7 SW-V29 Service Water Pump "B" Discharge Valve SW-20794 B 301140 SW-F-1E-Z X X X - VL4 SW-CS1-52 460 V AC Circuit Breaker CS1 SW-F-1C-A AR3-CS1 CS1-VL4/1 CS1-VL4 301107 CS1a CS1c SWA-FN-40B EDE-MCC-614 SW-V-2 SW-V-22 Cooling Towers SW-AR3-52S Mechanically Operated Contact AR3 CB-F-1B-A SW-ZS-V29 Valve Position Switch and Valve Open/Close Torque Switches VL4 SW-F-1E-Z SW-CS1-42/0,C Motor Starters CS1 SW-F-1C-A SW-CS1-49 Overload Relay CS1 SW-F-1C-A SW-CS1-FU Fuses CS1 SW-F-1C-A SW-EE2-TDR Time Delay Relay EE2 SW-F-1C-A 8 SW-V31 Service Water Pump "D" Discharge Valve SW-20794 B 301140 SW-F-1E-Z X X X - VL6 SW-CS2-52 460 V AC Circuit Breaker CS2 SW-F-1C-A AR4-CS2 CS2-VL6/1 CS2-VL6 301107 CS2a CS2c SWA-FN-40B EDE-MCC-614 SW-V-2 SW-V-22 Cooling Towers SW-AR4-52S Mechanically Operated Contact AR4 CB-F-1B-A SW-ZS-V31 Valve Position Switch and Valve Open/Close Torque Switches VL6 SW-F-1E-Z SW-CS2-42/0,C Motor Starters CS2 SW-F-1C-A SW-CS2-49 Overload Relay CS2 SW-F-1C-A SW-CS2-FU Fuses CS2 SW-F-1C-A SW-EE2-TDR Time Delay Relay EE2 SW-F-1C-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -7 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 SW-V4 Secondary Component Cooling Water Heat Exchanger Header Supply Valve SW-20795 A 310767 PAB-F-1K-Z X X X - VP0 SW-DA6-52 460 V AC Circuit Breaker DA6 CB-F-1A-A DA6-VP0 DA6-G2H DA6-G2H/2 DA6-G2H/1 DA6-VP0/1 F72-G2H/3 F72-G2H/5 F72-FB7 DA6-GN9 DA6-HR2 301107 DA6a DA6c DA6d CBA-FN-19 CBA-FN-20 EDE-MCC-512 SW-V5 SW-CS-6117-2 Control Switch with Indication G2H CB-F-1A-A SW-SS-6117 Selector Switch G2H CB-F-1A-A SW-DA6-42/0,C Motor Starters DA6 CB-F-1A-A SW-DA6-49 Overload Relays DA6 CB-F-1A-A SW-ZS-V4 Valve Position Switch and Valve Open/Close Torque Switches VP0 PAB-F-1K-Z SW-DA6-FU Fuse DA6 CB-F-1A-A SW-CS-6117-1 Control Switch with Indication F72 CB-F-3A-A SW-HR2-PR1 EPS Permit Auxiliary Relay (K8 and K11) HR2 CB-F-1A-A SW-FB7-K603A SI Actuating Auxiliary Relay FB7 CB-F-3A-A SW-GN9-RTA Tower Actuation Sig. Auxiliary Relay GN9 CB-F-1A-A 10 SW-V5 Secondary Component Cooling Water Heat Exchanger Header Supply Valve SW-20795 B 310767 PAB-F-1K-Z X X X - VQ1 SW-DA2-52 460 V AC Circuit Breaker DA2 CB-F-1B-A DA2-VQ1 DA2-G2K DA2-G2K/1 DA2-G2K/2 DA2-VQ1/1 F71-G2K/3 F71-G2K/5 F71-FB0 DA2-GN0 DA2-HR4 301107 DA2a DA2c DA2d CBA-FN-32 CBA-FN-33 EDE-MCC-612 SW-V4 SW-CS-6137-2 Control Switch with Indication G2K CB-F-1B-A SW-SS-6137 Selector Switch G2K CB-F-1B-A SW-DA2-42/0,C Motor Starters DA2 CB-F-1B-A SW-DA2-49 Overload Relays DA2 CB-F-1B-A SW-ZS-V5 Valve Position Switch and Valve Open/Close Torque Switches VQ1 PAB-F-1K-Z SW-DA2-FU Fuse DA2 CB-F-1B-A SW-CS-6137-1 Control Switch with Indication F71 CB-F-3A-A SW-HR4-PR1 EPS Permit Auxiliary Relay (K8 and K11) HR4 CB-F-1B-A SW-FB0-K603B SI Actuating Auxiliary Relay FB0 CB-F-3A-A SW-GN0-RTB Tower Actuation Sig. Auxiliary Relay GN0 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -8 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 SW-V15 CC-E-17A Outlet Valve SW-20795 A 310767 PAB-F-3A-Z X X X - VN1 SW-CS-6160 Control Switch with Indication F72 CB-F-3A-A DA7-VN1/1 DA7-F72 DA7-GN9 DA7-VN1/2 301107 DA7a DA7c CBA-FN-19 CBA-FN-20 SW-V17 Note 4 SW-DA7-42/0,C Motor Starter DA7 CB-F-1A-A SW-GN9-RTA Twr. Act. Sig. Auxiliary Relay GN9 CB-F-1A-A SW-ZS-V15 Position Switch VN1 PAB-F-3A-Z SW-DA7-52 460 V AC Circuit Breaker DA7 CB-F-1A-A 12 SW-V16 Diesel Generator "A" Water Jacket Heat Exchanger Solenoid-Operated Valve SW-20795 A 310767 PAB-F-3A-Z X X X X UK6 EDE-E2T/2-72 125 V DC Circuit Breaker E2T CB-F-1A-A F72-G06 F72-GN9/1 F72-GN9/5 GN9-UK6 301107 E2T/2a E2T/2c CBA-FN-19 CBA-FN-20 SW-V18 Notes 1,4 SW-CS-6182 Control Switch with Indication F72 CB-F-3A-A SW-GN9-R1 Auxiliary Relay GN9 CB-F-1A-A SW-G06-LSRX Low Speed Relay G06 DG-F-2A-A SW-ZS-V16 SW DG Water Jacket VLV-V16 Position Switch and Solenoid UK6 PAB-F-3A-Z 13 SW-V17 CC-E-17B Outlet Valve SW-20795 B 310767 PAB-F-3A-Z X X X - VN2 SW-DA3-52 460 V AC Circuit Breaker DA3 CB-F-1B-A - - CBA-FN-32 CBA-FN-33 SW-V15 Note 6 14 SW-V18 Diesel Generator "B" Water Jacket Heat Exchanger Solenoid-Operated Valve SW-20795 B 310767 PAB-F-3A-Z X X X X UK7 EDE-E2U/2-72 125 V DC Circuit Breaker E2U CB-F-1B-A F71-GN0/1 F71-GN0/5 F71-G18 GN0-UK7 301107 E2U/2a E2U/2c CBA-FN-32 CBA-FN-33 SW-V16 Notes 1,4 SW-CS-6192 Control Switch with Indication F71 CB-F-3A-A SW-GN0-R1 Auxiliary Relay GN0 CB-F-1B-A SW-G18-LSRX Low Speed Relay G18 DG-F-2B-A SW-ZS-V18 SW DG Water Jacket VLV-V18 Position Switch and Solenoid UK7 PAB-F-3A-Z 15 SW-V19 Service Water Discharge to Sea Isolation Valve SW-20795 B 310765 PAB-F-2C-Z X X X - VN3 SW-DA4-52 460 V AC Circuit Breaker DA4 CB-F-1B-A DA4-VN3/1 DA4-VN3/2 DA4-F71 DA4-GN0 DA4-E3Q 301107 DA4a DA4c CBA-FN-32 CBA-FN-33 SW-V20 Note 4 SW-CS-6172 Control Switch with Indication F71 CB-F-3A-A SW-CS-6172-1 Control Switch with Indication DA4 CB-F-1B-A SW-SS-8257 Selector Switch DA4 CB-F-1B-A SW-DA4-42/0,C Motor Starters DA4 CB-F-1B-A SW-DA4-49 Thermal Overload DA4 CB-F-1B-A SW-GN0-RTB-2 Twr. Act. Sig. Auxiliary Relay GN0 CB-F-1B-A SW-ZS-V19 Position Switch VN3 PAB-F-2C-Z SW-DA4-R1 Auxiliary Relay E3Q CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -9 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 16 SW-V20 Service Water Discharge to Sea Isolation Valve SW-20795 A 310765 PAB-F-2C-Z X X X - VN4 SW-DA8-52 460 V AC Circuit Breaker DA8 CB-F-1A-A DA8-VN4 DA8-VN4/1 DA8-VN4/2 DA8-F72 DA8-GN9 301107 DA8a DA8c CBA-FN-19 CBA-FN-20 EDE-MCC-512 SW-V19 SW-CS-6162 Control Switch with Indication F72 CB-F-3A-A SW-DA8-42/0,C Motor Starters DA8 CB-F-1A-A SW-DA8-49 Thermal Overload DA8 CB-F-1A-A SW-GN9-RTA-2 Twr. Act. Sig. Auxiliary Relay GN9 CB-F-1A-A SW-ZS-V20 Position Switch VN4 PAB-F-2C-Z 17 SW-V23 Service Water to Cooling Tower Isolation Valve SW-20795 B 310765 PAB-F-2C-Z X X X - VN5 SW-DA5-52 460 V AC Circuit Breaker DA5 CB-F-1B-A DA5-VN5/1 DA5-VN5/2 DA5-F71 DA5-F71/1 DA5-GN0 301107 DA5a DA5c CBA-FN-32 CBA-FN-33 SW-V34 Note 4 SW-CS-6171 Control Switch with Indication F71 CB-F-3A-A SW-DA5-42/0,C Motor Starters DA5 CB-F-1B-A SW-DA5-49 Thermal Overload DA5 CB-F-1B-A SW-GN0-RTB-2 Twr. Act. Sig. Auxiliary Relay GN0 CB-F-1B-A SW-ZS-V23 Position Switch VN5 PAB-F-2C-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -10 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 SW-V25 Cooling Tower Pump Discharge Valve SW-20794 B 310717 CT-F-2B-A X X X - VH8 SW-CQ7-52 460 V AC Circuit Breaker CQ7 CT-F-1C-A CQ7-G2K CQ7-VM8/1 CQ7-VM8/2 F71-G2K AU6-G2K G2K-GNO EE7-G2K G2K-GNO/3 301107 CQ7a CQ7c CBA-FN-32 CBA-FN-33 SW-V54 Note 4 SW-CS-6174-2 Control Switch with Indication G2K CB-F-1B-A SW-SS-6174 Selector Switch G2K CB-F-1B-A SW-CQ7-42/O,C Motor Starters CQ7 CT-F-1C-A SW-CQ7-49 Overload Relay CQ7 CT-F-1C-A SW-ZS-V25 Valve Position Switch and Valve Open/Close Torque Switches VM8 CT-F-2B-A SW-CS-6174-1 Control Switch with Indication F71 CB-F-3A-A SW-AU6-52S Mechanical Operated Switch AU6 CB-F-1B-A SW-GNO-RTB1 Tower Actuation Signal Auxiliary Relay GNO CB-F-1B-A SW-EE7-TDR Time Delay Relay EE7 CT-F-1C-A SW-GNO-RV25 Auxiliary Relay GNO CB-F-1B-A SW-ZS-V25 Position Switch VM8 CT-F-2B-A SW-GN0-RV25 Auxiliary Relay GN0 CB-F-1B-A GNO-VM8 E2U/1aE2U/1b Note 4 SW-CQ7-R1 Auxiliary Relay EE7 CT-F-1C-A 19 SW-V34 Service Water to Cooling Tower Outlet Valve SW-20795 A 310765 PAB-F-2C-Z X X X - VN6 SW-DA9-52 460 v AC Circuit Breaker DA9 CB-F-1A-A DA9-VN6 DA9-VN6/1 DA9-VN6/2 DA9-F72 DA9-F72/1 DA9-GN9 301107 DA9a DA9c CBA-FN-19 CBA-FN-20 EDE-MCC-512 SW-V23 SW-CS-6161 Control Switch with Indication F72 CB-F-3A-A SW-DA9-42/O,C Motor Starters DA9 CB-F-1A-A SW-DA9-49 Thermal Overload DA9 CB-F-1A-A SW-GN9-RTA-2 Tower Actuation Signal Auxiliary Relay GN9 CB-F-1A-A SW-ZS-V34 Position Switch VN6 PAB-F-2C-Z 20 SW-V44 Service Water Unit Pumps Intake Valve SW-20794 A 301037 SW-F-2-0 X X X - VM1 SW-CU5-52 460 V ac Circuit Breaker CU5 SW-F-1B-A None Note 5 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -11 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 21 SW-V54 Cooling Tower Pump Discharge Valve SW-20794 A 301717 CT-F-2B-A X X X - VM5 SW-CP8-52 460 V ac Circuit Breaker CP8 CT-F-1D-A CP8-G2H CP8-VM5 CP8-VM5/1 CP8-VM5/2 F72-G2H AU2-G2H G2H-GN9/1 G2H-GN9/5 ED6-G2H 301107 CP8a CP8c CBA-FN-19 CBA-FN-20 EDE-MCC-513 SW-V25 SW-CS-6164-2 Control Switch with Indication G2H CB-F-1A-A SW-SS-6164 Selector Switch G2H CB-F-1A-A SW-CP8-42/O,C Motor Starters CP8 CT-F-1D-A SW-CP8-49 Overload Relay CP8 CT-F-1D-A SW-ZS-V54 Valve Position Switch and Valve Open/Close Torque Switches VM5 CT-F-2B-A SW-CP8-FU Fuse CP8 CT-F-1D-A SW-CS-6164-1 Control Switch with Indication F72 CB-F-3A-A SW-AU2-52S Mechanical Operated Switch AU2 CB-F-1A-A SW-GN9-RTA-1 Tower Actuation Signal Auxiliary Relay GN9 CB-F-1A-A SW-ED6-TDR Timing Relay ED6 CB-F-1A-A SW-ZS-V54 Position Switch VM5 CT-F-2B-A SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A GN9-VM5 E2T/1a E2T/1b Note 4 22 SW-V63 Service Water Discharge Valve to Intake SW-20794 A 301037 SW-F-2-0 X X X - VQ0 SW-DZ3-52 460 V ac Circuit Breaker DZ3 SW-F-1B-A None Note 5 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -12 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 23 EDE-CP-248 Service Water Cooling Tower Actuation Logic (TA) SW-20794 A 310442 CB-F-1A-A X X X - GN9 SW-CS-6149-2 Control Switch F77 CB-F-3A-A EF4-GN9/1 F72-GN9 AQ3-GN9/1 ED4-F72 301107 E87/4a E87/4g E87/4b CBA-FN-19 CBA-FN-20 EDE-CP-249 Note 4 SW-CS-6148-1 Control Switch F72 CB-F-3A-A SW-CS-6148-2 Control Switch F72 CB-F-3A-A SW-CS-6149-1 Control Switch F77 CB-F-3A-A SW-AQ3-52S Circuit Breaker AQ3 CB-F-1A-A SW-AQ4-52S Circuit Breaker AW4 CB-F-1A-A SW-GN9-RX1 Auxiliary Relay GN9 CB-F-1A-A SW-GN9-TD1 Time Delay Relay GN9 CB-F-1A-A SW-EF4-RP1 Auxiliary Relay EF4 CB-F-1A-A SW-EF4-RP2 Auxiliary Relay EF4 CB-F-1A-A SW-EF4-RP3 Auxiliary Relay EF4 CB-F-1A-A SW-GN9-RTA Tower Actuation Relay GN9 CB-F-1A-A SW-GN9-RTA1 Tower Actuation Relay GN9 CB-F-1A-A SW-GN9-RTA2 Tower Actuation Relay GN9 CB-F-1A-A SW-ZL-6149 Pilot Light F77 CB-F-3A-A SW-GN9-TD2 Time Delay Relay GN9 CB-F-1A-A SW-CS-6101-1 Control Switch F72 CB-F-3A-A SW-CS-6102-1 Control Switch F72 CB-F-3A-A SW-CS-6167-1 Control Switch F72 CB-F-3A-A SW-ED4-94-5 Aux Relay ED4 CB-F-1A-A SW-PYY-8272-2 Auxiliary Relay FJ1 CB-F-3A-A EF4-FJ1/2 EH9/10a EH9/10b Note 4 SW-PYY-8273 Auxiliary Relay FJ1 CB-F-3A-A SW-PYY-8274-2 Auxiliary Relay FJ1 CB-F-3A-A SW-EF4-RP1 Auxiliary Relay EF4 CB-F-1A-A SW-EF4-RP2 Auxiliary Relay EF4 CB-F-1A-A SW-EF4-RP3 Auxiliary Relay EF4 CB-F-1A-A SW-PT-8272 MM-CP-152A SW-Discharge HDR PR BOP-PCC GRO FJ1 SW-F-1E-Z CB-F-3A-A FJ1-GRO 310952 FJ1c FJ1e SW-PT-8273 MM-CP-152A SW-Discharge HDR PR BOP-PCC GRO FJ1 SW-F-1E-Z CB-F-3A-A FJ1-GRO FJ1c FJ1e SW-PT-8274 MM-CP-152A SW-Discharge HDR PR BOP-PCC GRO FJ1 SW-F-1E-Z CB-F-3A-A FJ1-GRO FJ1c FJ1e SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -13 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 24 EDE-CP-249 Service Water Cooling Water Actuation Logic (TA) SW-20794 B 310442 CB-F-1B-A X X X - GNO SW-CS-6159-2 Control Switch F77 CB-F-3A-A EE3-GNO/1 F71-GNO AR3-GNO/1 EE6-F71 301107 E88/4a E88/4g E88/4b CBA-FN-32 CBA-FN-33 EDE-CP-248 Note 4 SW-CS-6158-1 Control Switch F71 CB-F-3A-A SW-CS-6158-2 Control Switch F71 CB-F-3A-A SW-CS-6159-1 Control Switch F77 CB-F-3A-A SW-AR3-52S Circuit Breaker AR3 CB-F-1B-A SW-AR4-52S Circuit Breaker AR4 CB-F-1B-A SW-GNO-RX1 Auxiliary Relay GNO CB-F-1B-A SW-GNO-TD1 Time Delay Relay GNO CB-F-1B-A SW-EE3-RP1 Auxiliary Relay EE3 CB-F-1B-A SW-EE3-RP2 Auxiliary Relay EE3 CB-F-1B-A SW-EE3-RP3 Auxiliary Relay EE3 CB-F-1B-A SW-GNO-RTA Tower Actuation Relay GNO CB-F-1B-A SW-GNO-RTA1 Tower Actuation Relay GNO CB-F-1B-A SW-GNO-RTA2 Tower Actuation Relay GNO CB-F-1B-A SW-ZL-6159 Pilot Light F77 CB-F-3A-A SW-GN9-TD2 Time Delay Relay GN0 CB-F-1B-A SW-CS-6111-1 Control Switch F71 CB-F-3A-A SW-CS-6112-1 Control Switch F71 CB-F-3A-A SW-CS-6177-1 Control Switch F71 CB-F-3A-A SW-EE6-94-6 Aux Relay EE6 CB-F-3A-A Note 4 SW-PYY-8282-2 Auxiliary Relay FJ4 CB-F-3A-A EE3-FJ4/2 EHO/10a EHO/10c SW-PYY-8283 Auxiliary Relay FJ4 CB-F-3A-A SW-PYY-8284-2 Auxiliary Relay FJ4 CB-F-3A-A SW-EE3-RP1 Auxiliary Relay EE3 CB-F-1B-A SW-EE3-RP2 Auxiliary Relay EE3 CB-F-1B-A SW-EE3-RP3 Auxiliary Relay EE3 CB-F-1B-A SW-PT-8282 MM-CP-152B SW-Discharge HDR PR BOP-PCC GRO FJ4 SW-F-1E-Z CB-F-3A-A FJ4-GRO 310952 FJ4g FJ4h SW-PT-8283 MM-CP-152B SW-Discharge HDR PR BOP-PCC GRO FJ4 SW-F-1E-Z CB-F-3A-A FJ4-GRO FJ4g FJ4h SW-PT-8284 MM-CP-152B SW-Discharge HDR PR BOP-PCC GRO FJ4 SW-F-1E-Z CB-F-3A-A FJ4-GRO FJ4g FJ4h SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -14 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 25 SW-P-110A Cooling Tower Pump SW-20794 A 301717 CT-F-2B-A X X X - NG4 SW-AU2-52 4160 Volt Circuit Breaker AU2 CB-F-1A-A AU2-F72/1 AU2-F72/2 AU2-GN9 AU2-HR9 AU2-VM5 AU2-VM5/1 VM5-VM7/1 AU2-NG4 301107 AU2a AU2h AU2b AU2i AU2c AU2d EDE-SWG-5 SW Pumphouse SW-AU2-FU Fuses AU2 CB-F-1A-A SW-CS-6167-2 Control Switch AU2 CB-F-1A-A SW-SS-6167 Selector Switch AU2 CB-F-1A-A EDE-A53-94-1B Bus Undervoltage Relay A53 CB-F-1A-A SW-AU2-52H Truck Operated Contact AU2 CB-F-1A-A SW-AU2-50/51 Inst/Time Overcurrent Relays ØA, ØC AU2 CB-F-1A-A SW-AU2-51GS Ground Sensor Relay AU2 CB-F-1A-A SW-AU2-86 Lockout Relay AU2 CB-F-1A-A SW-AU2-CT Current Transformers 150/5A AU2 CB-F-1A-A SW-AU2-TD1 Test Device AU2 CB-F-1A-A SW-AU2-AM Ammeter AU2 CB-F-1A-A SW-AU2-AS Ammeter Switch AU2 CB-F-1A-A SW-AU2-G,R,W Indicating Lights AU2 CB-F-1A-A SW-AU2-ATR Transducer Test Device AU2 CB-F-1A-A SW-AU2-52Z Time Delay Relay AU2 CB-F-1A-A SW-ZS-V54 Valve Position Switch & Valve Open/Close Torque Switches VM5 CT-F-2B-A SW-ZS-V56 Valve Position Switch & Valve Open/Close Torque Switches VM7 CT-F-2B-A SW-CS-6102-1 Control Switch F72 CB-F-3A-A SW-CS-6101-1 Control Switch F72 CB-F-3A-A SW-HR2-PR1 E.P.S. Permit Relay (K8 & K10) HR2 CB-F-1A-A SW-HR2-RMO E.P.S. Manual Override Relay (K32) HR2 CB-F-1A-A SW-GN9-RTA Tower Actuation Signal Auxiliary Relay GN9 CB-F-1A-A SW-HR9-HR8 E.P.S. Start Relay HR9 CB-F-1A-A CBS-A61-52S Mechanical Operated Switch A61 CB-F-1A-A SW-AU2-R1 Auxiliary Relay AU2 CB-F-1A-A SW-AU2-R1X Auxiliary Relay AU2 CB-F-1A-A SW-AU2-R4 Auxiliary Relay AU2 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -15 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 26 SW-FN-51A Cooling Tower Fan SW-20794 A 301717 CT-F-3-0 X X X - NG6 SW-AV4-52 4160 Volt Circuit Breaker AV4 CB-F-1A-A AV4-HR2 AV4-F72/2 AV4-F72/1 AV4-NG6 301107 AV4a AV4h AV4b AV4c AV4d EDE-SWG-5 SW Pumphouse SW-AV4-FU Fuses AV4 CB-F-1A-A SW-CS-6185-2 Control Switch AV4 CB-F-1A-A SW-SS-6185 Selector Switch AV4 CB-F-1A-A EDE-A53-94-1B Bus Undervoltage Relay A53 CB-F-1A-A SW-AV4-52H Truck Operated Contact AV4 CB-F-1A-A SW-AV4-50/51 Inst/Time Overcurrent Relays ØA, ØC AV4 CB-F-1A-A SW-AV4-51GS Ground Sensor Relay AV4 CB-F-1A-A SW-AV4-86 Lockout Rela y AV4 CB-F-1A-A SW-AV4-CT Current Transformers 5/50 AV4 CB-F-1A-A SW-AV4-TD1 Test Device AV4 CB-F-1A-A SW-AV4-AM Ammeter AV4 CB-F-1A-A SW-AV4-AS Ammeter Switch AV4 CB-F-1A-A SW-AV4-G,R,W Indicating Lights AV4 CB-F-1A-A SW-AV4-ATR Transducer AV4 CB-F-1A-A SW-AV4-TD2 Lockout Relay Test Device AV4 CB-F-1A-A SW-AV4-52Z Time Delay Relay AV4 CB-F-1A-A SW-CS-6285-1 Control Switch F72 CB-F-3A-A SW-HR2-RMO E.P.S. Manual Override Relay (K32) HR2 CB-F-1A-A 27 SW-V74 Loop A Discharge to Cooling Tower SW-20795 A 310765 PAB-F-1K-Z X X X - VM2 SW-BX8-52 460 V ac Circuit Breaker BX8 CB-F-1A-A F72-FB7/1 BX8-F72 FX8-F72/1 BX8-GN9 BX8-VM2 BX8-VM2/1 BX8-VM2/2 301107 BX8a BS8c EDE-MCC-512 SW Pumphouse SW-CS-8271 Control Switch with Indication F72 CB-F-3A-A SW-BX8-42/O,C Motor Starters BX8 CB-F-1A-A SW-GN9-RTA Tower Actuation Signal Auxiliary Relay GN9 CB-F-1A-A SW-ZS-V74 Position Switch VM2 PAB-F-1K-Z SW-FB7-K608A SI Actuating Auxiliary Relay FB7 CB-F-3A-A 28 SW-V55 Cooling Tower PP A Test/Bypass SW-20794 A 301717 CT-F-2B-A X X X - VM6 SW-CP9-52 460 V ac Circuit Breaker CP9 CT-F-1D-A SW Pumphouse Note 5 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -16 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 29 SW-V56 Cooling Tower Loop A Test Recirculation SW-20794 A 301717 CT-F-2B-A X X X - VM7 SW-CP0-52 460 V ac Circuit Breaker CP0 CT-F-1D-A CP0-F72 CP0-F72/1 AU2-F72/3 AU2-VM5/3 VM5-VM7 CP0-VM7 CP0-VM7/1 CPO-VM7/2 301107 CP0a CP0c EDE-MCC-513 SW Pumphouse SW-CS-6165 Control Switch with Indication F72 CB-F-3A-A SW-CP0-42/O,C Motor Starters CP0 CT-F-1D-A SW-ZS-V54 Position Switch VM5 CT-F-2B-A SW-ZS-V56 Position Switch VM7 CT-F-2B-A SW-AU2-52S Mechanical Operated Switch AU2 CB-F-1A-A SW-CP0-49 Thermal Overload CP0 CT-F-1D-A 30 SW-V139 Cooling Tower Spray Bypass Recirculation Valve SW-20794 A 301717 CT-F-3-0 X X X - V3Q SW-C3D-52 460 V ac Circuit Breaker C3D CT-F-1D-A C3D-V3Q C3D-V3Q/1 C3D-V3Q/3 C3D-F72 301107 C3Da C3Dc EDE-MCC-513 SW Pumphouse SW-CS-6168 Control Switch with Indication F72 CB-F-3A-A SW-C3D-42/O,C Motor Starters C3D CT-F-1D-A SW-ZS-V139 Position Switch V3Q CT-F-3-0 SW-C3D-49 Thermal Overload C3D CT-F-1D-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -1 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CC-P-11A PCCW Loop "A" Pump "A" CC-20205 A 310765 PAB-F-2C-Z X X X - H05 CC-A58-52 4160 V AC Circuit Breaker A58 CB-F-1A-A A58-M05/1 A58-F30/1 A58-F30/2 A58-F30/3 A58-HR9 A58-E3C 310895 A58a A58h A58b A58c A58d CBA-FN-19 CBA-FN-20 PAH-FN-42A EDE-SWG-5 CC-P-11B or CC-P-11D CC-CS-2140-2 Control Switch A58 CB-F-1A-A CC-SS-2140 Selector Switch A58 CB-F-1A-A EDE-A53-94-1A Bus Undervoltage Relay A53 CB-F-1A-A CC-A58-52H Truck-Operated Contact A58 CB-F-1A-A CC-A58-50/51 Instrument/Time Overcurrent Relays øA, øC A58 CB-F-1A-A CC-A58-86 Lockout Relay A58 CB-F-1A-A CC-A58-AM Ammeter A58 CB-F-1A-A CC-A58-AS Ammeter Switch A58 CB-F-1A-A CC-A58-CT Current Transformer (150/5) A58 CB-F-1A-A CC-A58-TD1 CT Test Device A58 CB-F-1A-A CC-A58-ATR Transducer A58 CB-F-1A-A CC-A58-TD2 Lockout Relay Test Device A58 CB-F-1A-A CC-A58-FU Fuses A58 CB-F-1A-A CC-A58-52Z Timing Relay A58 CB-F-1A-A CC-A58-G,R,W Indicating Lights A58 CB-F-1A-A CC-A58-51GS Ground Sensor Relay A58 CB-F-1A-A CC-CS-2140-1 Control Switch with Indication F30 CB-F-3A-A CC-CS-2141-1 Control Switch F30 CB-F-3A-A CC-A59-52S Mechanical -Operated Switch A59 CB-F-1A-A CC-HR2-PR1 EPS Permissive Relay (K7 and K10) HR2 CB-F-1A-A CC-HR2-RMO EPS Relay (K31) HR2 CB-F-1A-A CC-HR9-SR4 EPS Starting Relay (K78) HR9 CB-F-1A-A CC-A58-62 Time Delay Relay A58 CB-F-1A-A CC-E3C-TDRX Auxiliary Relay E3C CB-F-1A-A EDE-E42/12-52 120 V AC Circuit Breaker E42 CB-F-1A-A E42-E3C E3C-FK0/1 E42/12a E42/12b EDE-MCC-521 CC-TYY-2171A Auxiliary Relay FK0 CB-F-3A-A CC-TTY-2197A Auxiliary Relay FK0 CB-F-3A-A

.Notes   1. The equipment is mechanical with no electrical requirement.
2. These valves are in the open position with their circuit breakers locked open to prevent spurious operation.
3. Electrical conduit plan drawing, 310765, is listed only to show the fire zone corresponding to the location of the Heat Exchangers CC-E-17A and CC

-E-17B as identified in Drawing 805217.

4. Electrical conduit plan drawing, 310581, is listed only to show the fire zone corresponding to the location of CC

-TK-196 as identified in Drawing 805193.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -2 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CC-P-11A (Continued) CC-E3C-TDR Time Delay Relay E3C CB-F-1A-A CC-E3C-TDRX Auxiliary Relay E3C CB-F-1A-A CC-TE-2171 Temperature Element TMO PAB-F-2C-Z FK0-TMO/1 FK0-T3A 310952 FK0d FK0f MM-CP-297A CC-TE-2197 Temperature Element T3A PAB-F-2C-Z MM-CP-297A BOP-PCC FKO CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -3 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 CC-P-11B PCCW Loop "B" Pump "B" CC-20211 B 310765 PAB-F-2C-Z X X X - M06 CC-A78-52 4160 V AC Circuit Breaker A78 CB-F-1B-A A78-M06/1 A78-F31 A78-F31/1 A78-F31/2 A78-HR0 A78-E3D 310895 A78a A78h A78b A78c A78d CBA-FN-32 CBA-FN-33 PAH-FN-42B EDE-SWG-6 CC-P-11A or CC-P-11C CC-CS-2240-2 Control Switch A78 CB-F-1B-A CC-SS-2240 Selector Switch A78 CB-F-1B-A EDE-A73-94-1A Bus Undervoltage Relay A73 CB-F-1B-A CC-A78-52H Truck-Operated Contact A78 CB-F-1B-A CC-A78-50/51 Instrument/Time Overcurrent Relays øA, øC A78 CB-F-1B-A CC-A78-86 Lockout Relay A78 CB-F-1B-A CC-A78-AM Ammeter A78 CB-F-1B-A CC-A78-AS Ammeter Switch A78 CB-F-1B-A CC-A78-CT Current Transformer (150/5) A78 CB-F-1B-A CC-A78-TD1 CT Test Device A78 CB-F-1B-A CC-A78-ATR Transducer A78 CB-F-1B-A CC-A78-TD2 Lockout Relay Test Device A78 CB-F-1B-A CC-A78-FU Fuses A78 CB-F-1B-A CC-A78-52Z Timing Relay A78 CB-F-1B-A CC-A78-G,R,W Indicating Lights A78 CB-F-1B-A CC-A78-51GS Ground Sensor Relay A78 CB-F-1B-A CC-CS-2240-1 Control Switch with Indication F30 CB-F-3A-A CC-CS-2241-1 Control Switch F30 CB-F-3A-A CC-A79-52S Mechanical -Operated Switch A79 CB-F-1B-A CC-HR4-PR1 EPS Permissive Relay (K7 and K10) HR4 CB-F-1B-A CC-HR4-RMO EPS Relay (K31) HR4 CB-F-1B-A CC-HR0-SR4 EPS Starting Relay (K78) HR0 CB-F-1B-A CC-A78-62 Time Delay Relay A78 CB-F-1B-A CC-E3D-TDRX Auxiliary Relay E3D CB-F-1B-A EDE-E50/12-52 120 V AC Circuit Breaker E50 CB-F-1B-A E3D-E50 E3D-FJ4 E50/12a E50/12b EDE-MCC-621 CC-TYY-2271A Auxiliary Relay FJ4 CB-F-3A-A CC-TTY-2297A Auxiliary Relay FJ4 CB-F-3A-A CC-E3D-TDR Time Delay Relay E3D CB-F-1B-A CC-E3D-TDRX Auxiliary Relay E3D CB-F-1B-A CC-TE-2271 Temperature Element TM8 PAB-F-2C-Z FJ4-TM8/2 FJ4-T2Z 310952 FJ4j FJ4n MM-CP-152B CC-TE-2297 Temperature Element T2Z PAB-F-2C-Z MM-CP-152B BOP-PCC FJ4 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -4 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 CC-P-11C PCCW Loop "A" Pump "C" CC-20205 A 310766 PAB-F-2C-Z X X X - H07 CC-A59-52 4160 V AC Circuit Breaker A59 CB-F-1A-A A59-M07/1 A59-F30/1 A59-F30/2 A59-F30/3 A59-HR9 A59-E3C 310895 A59a A59h A59b A59c A59d CBA-FN-19 CBA-FN-20 PAH-FN-42A EDE-SWG-5 CC-P-11B or CC-P-11D CC-CS-2141-2 Control Switch A59 CB-F-1A-A CC-SS-2141 Selector Switch A59 CB-F-1A-A EDE-A53-94-1A Bus Undervoltage Relay A53 CB-F-1A-A CC-A59-52H Truck-Operated Contact A59 CB-F-1A-A CC-A59-50/51 Instrument/Time Overcurrent Relays øA, øC A59 CB-F-1A-A CC-A59-86 Lockout Relay A59 CB-F-1A-A CC-A59-AM Ammeter A59 CB-F-1A-A CC-A59-AS Ammeter Switch A59 CB-F-1A-A CC-A59-CT Current Transformer (150/5) A59 CB-F-1A-A CC-A59-TD1 CT Test Device A59 CB-F-1A-A CC-A59-ATR Transducer A59 CB-F-1A-A CC-A59-TD2 Lockout Relay Test Device A59 CB-F-1A-A CC-A59-FU Fuses A59 CB-F-1A-A CC-A59-52Z Timing Relay A59 CB-F-1A-A CC-A59-G,R,W Indicating Lights A59 CB-F-1A-A CC-A59-51GS Ground Sensor Relay A59 CB-F-1A-A CC-CS-2141-1 Control Switch with Indication F30 CB-F-3A-A CC-CS-2140-1 Control Switch F30 CB-F-3A-A CC-A58-52S Mechanical -Operated Switch A58 CB-F-1A-A CC-HR2-PR1 EPS Permissive Relay (K8 and K10) HR2 CB-F-1A-A CC-HR2-RMO EPS Relay (K31) HR2 CB-F-1A-A CC-HR9-SR4 EPS Starting Relay (K78) HR9 CB-F-1A-A CC-A59-62 Time Delay Relay A59 CB-F-1A-A CC-E3C-TDRX Auxiliary Relay E3C CB-F-1A-A EDE-E42/12-52 120 V AC Circuit Breaker E42 CB-F-1A-A E42-E3C E3C-FK0/1 E42/12a E42/12b EDE-MCC-521 CC-TYY-2171A Auxiliary Relay FK0 CB-F-3A-A CC-TTY-2197A Auxiliary Relay FK0 CB-F-3A-A CC-E3C-TDR Time Delay Relay E3C CB-F-1A-A CC-E3C-TDRX Auxiliary Relay E3C CB-F-1A-A CC-TE-2171 Temperature Element TM0 PAB-F-2C-Z FK0-TM0/1 FK0-T3A 310952 FK0d FKOf MM-CP-297A CC-TE-2197 Temperature Element T3A PAB-F-2C-Z MM-CP-297A BOP-PCC FK0 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -5 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 CC-P-11D PCCW Loop "B" Pump "D" CC-20211 B 310766 PAB-F-2C-Z X X X - M08 CC-A79-52 4160 V AC Circuit Breaker A79 CB-F-1B-A A79-M08/1 A79-F31 A79-F31/1 A79-F31/2 A79-HR0 A79-E3D 310895 A79a A79h A79b A79c A79d CBA-FN-32 CBA-FN-33 PAH-FN-42B EDE-SWG-6 CC-P-11A or CC-P-11C CC-CS-2241-2 Control Switch A79 CB-F-1B-A CC-SS-2241 Selector Switch A79 CB-F-1B-A EDE-A73-94-1A Bus Undervoltage Relay A73 CB-F-1B-A CC-A79-52H Truck-Operated Contact A79 CB-F-1B-A CC-A79-50/51 Instrument/Time Overcurrent Relays øA, øC A79 CB-F-1B-A CC-A79-86 Lockout Relay A79 CB-F-1B-A CC-A79-AM Ammeter A79 CB-F-1B-A CC-A79-AS Ammeter Switch A79 CB-F-1B-A CC-A79-CT Current Transformer (150/5) A79 CB-F-1B-A CC-A79-TD1 CT Test Device A79 CB-F-1B-A CC-A79-ATR Transducer A79 CB-F-1B-A CC-A79-TD2 Lockout Relay Test Device A79 CB-F-1B-A CC-A79-FU Fuses A79 CB-F-1B-A CC-A79-52Z Timing Relay A79 CB-F-1B-A CC-A79-G,R,W Indicating Lights A79 CB-F-1B-A CC-A79-51GS Ground Sensor Relay A79 CB-F-1B-A CC-CS-2241-1 Control Switch with Indication F30 CB-F-3A-A CC-CS-2240-1 Control Switch F30 CB-F-3A-A CC-A78-52S Mechanical -Operated Switch A78 CB-F-1B-A CC-HR4-PR1 EPS Permissive Relay (K8 and K10) HR4 CB-F-1B-A CC-HR4-RMO EPS Relay (K31) HR4 CB-F-1B-A CC-HR0-SR4 EPS Starting Relay (K78) HR0 CB-F-1B-A CC-A79-62 Time Delay Relay A79 CB-F-1B-A CC-E3D-TDRX Auxiliary Relay E3D CB-F-1B-A EDE-E50/12-52 120 V AC Circuit Breaker E50 CB-F-1B-A E3D-E50 E3D-FJ4 E50/12a E50/12b EDE-MCC-621 CC-TYY-2271A Auxiliary Relay FJ4 CB-F-3A-A CC-TYY-2297A Auxiliary Relay FJ4 CB-F-3A-A CC-E3D-TDR Time Delay Relay E3D CB-F-1B-A CC-E3D-TDRX Auxiliary Relay E3D CB-F-1B-A CC-TE-2271 Temperature Element TM8 PAB-F-2C-Z FJ4-TM8/2 FJ4-T2Z 310952 FJ4j FJ4n MM-CP-152B CC-TE-2297 Temperature Element T2Z PAB-F-2C-Z MM-CP-152B BOP-PCC FJ4 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -6 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 CC-V-57 Primary Component Cooling Water Loop "A" Header Isolation Inboard Supply Valve CC-20207 A 310578 C-F-2-Z - X X X VA8 CC-E2T/4-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-E4H E4H-G81/1 G81-H36/7 G81-H36/8 H36-VA8 H36-VB1 310895 E2T/4b E2T/4d E2T/4a E2T/4e E2T/4f CBA-FN-19 CBA-FN-20 Instrument Air EDE-PP-113A CC-V-176 CC-CS-2099-2 Control Switch with Indication G81 CB-F-1A-A CC-SS-2099 Selector Switch G81 CB-F-1A-A CC-ZS-V57 Valve Position Switch VA8 C-F-2-Z CC-E4H-FU3,4 30A Fuses E4H CB-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A CC-V57-20-1 Pilot Solenoid VA8 C-F-2-Z CC-V57-20-2 Pilot Solenoid VA8 C-F-2-Z CC-CS-2099-1 Control Switch with Indication F30 CB-F-3A-A F30-G81/B F30-G81/9 F30-FB7/5 G81-GN9/D FB7-G81 FC1-G81 FC1-G81/1 F30-G81/8 G81-GN9/B CC-FB7-K-633A Protection System Relay FB7 CB-F-3A-A CC-FB7-K-632A Protection System Relay FB7 CB-F-3A-A CC-ATR-LLA1 Isolation Signal Auxiliary Relay GN9 CB-F-1A-A CC-FC1-K803 Safeguard Test Cabinet Relay FC1 CB-F-3A-A CC-FC1-K811 Safeguard Test Cabinet Relay FC1 CB-F-3A-A 6 CC-V-121 Primary Component Cooling Water Loop "A" Header Isolation Inboard Return Valve CC-20207 A 310579 C-F-2-Z - X X X VB1 CC-E2T/4-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-E4H G81-H36/8 G81-H36/7 H36-VB1 H36-VA8 E4H-G81/1 310895 E2T/4a E2T/4d E2T/4b E2T/4e E2T/4f CBA-FN-19 CBA-FN-20 Instrument Air EDE-PP-113A CC-V-256 CC-CS-2150-2 Control Switch with Indication G81 CB-F-1A-A CC-SS-2150 Selector Switch G81 CB-F-1A-A CC-ZS-V121 Valve Position Switch VB1 C-F-2-Z CC-E4H-FU3,4 30A Fuses E4H CB-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A CC-V121-20-1 Pilot Solenoid VB1 C-F-2-Z CC-V121-20-2 Pilot Solenoid VB1 C-F-2-Z CC-CS-2150-1 Control Switch with Indication F30 CB-F-3A-A F30-G81/8 F30-G81/9 F30-FB7/5 G81-GN9/B FB7-G81 FC1-G81 FC1-G81/1 FC1-G81/B G81-GN9/D CC-FB7-K-633A Protection System Relay FB7 CB-F-3A-A CC-FB7-K-632A Protection System Relay FB7 CB-F-3A-A CC-ATR-LLA1 Isolation Signal Auxiliary Relay GN9 CB-F-1A-A CC-FC1-K803 Safeguard Test Cabinet Relay FC1 CB-F-3A-A CC-FC1-K811 Safeguard Test Cabinet Relay FC1 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -7 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 CC-V-122 Primary Component Cooling Water Loop "A" Header Isolation Outboard Return Valve CC-20207 B 310769 PP-F-4B-Z - X X X UZ1 CC-E2U/6-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-GZ0/2 GZ0-UZ1 GZ0-UZ2 310895 E2U/6a E2U/6d E2U/6b E2U/6e CBA-FN-32 CBA-FN-33 Instrument Air EDE-PP-113B EAH-FN-31B CC-V-257 CC-CS-2149-2 Control Switch with Indication GZ0 CB-F-1B-A CC-SS-2149 Selector Switch GZ0 CB-F-1B-A CC-ZS-V122 Valve Position Switch UZ1 PP-F-4B-Z CC-V122-20-1 Pilot Solenoid UZ1 PP-F-4B-Z CC-V122-20-2 Pilot Solenoid UZ1 PP-F-4B-Z CC-CS-2149-1 Control Switch with Indication F30 CB-F-3A-A F30-GZO/6 F30-GZO/7 F30-FB0/5 GN0-GZ0/6 FB0-GZ0 FC2-GZ0 FC2-GZ0/1 F30-GZ0/9 GNO-GZO/8 CC-FB0-K-633B Protection System Relay FB0 CB-F-3A-A CC-FB0-K-632B Protection System Relay FB0 CB-F-3A-A CC-BTR-LLA1 Isolation Signal Auxiliary Relay GN0 CB-F-1B-A CC-FC2-K803 Safeguard Test Cabinet Relay FC2 CB-F-3A-A CC-FC2-K811 Safeguard Test Cabinet Relay FC2 CB-F-3A-A 8 CC-V-168 Primary Component Cooling Water Loop "A" Header Isolation Outboard Supply Valve CC-20207 B 310769 PP-F-4B-Z - X X X UZ2 CC-E2U/6-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-GZ0/2 GZ0-UZ2 GZO-UZ1 310895 E2U/6b E2U/4d E2U/6a E2U/4e CBA-FN-32 CBA-FN-33 Instrument Air EDE-PP-113B EAH-FN-5B EAH-FN-31B CC-V-175 CC-CS-2151-2 Control Switch with Indication GZ0 CB-F-1B-A CC-SS-2151 Selector Switch GZ0 CB-F-1B-A CC-ZS-V168 Valve Position Switch UZ2 PP-F-4B-Z CC-V168-20-1 Pilot Solenoid UZ2 PP-F-4B-Z CC-V168-20-2 Pilot Solenoid UZ2 PP-F-4B-Z CC-CS-2151-1 Control Switch with Indication F30 CB-F-3A-A F30-GZO/7 F30-GZ0/9 F30-FB0/5 GN0-GZ0/8 FB0-GZ0 FC2-GZ0 FC2-GZ0/1 F30-GZ0/6 GN0-GZO/6 CC-FB0-K-633B Protection System Relay FB0 CB-F-3A-A CC-FB0-K-632B Protection System Relay FB0 CB-F-3A-A CC-BTR-LLA1 Isolation Signal Auxiliary Relay GN0 CB-F-1B-A CC-FC2-K803 Safeguard Test Cabinet Relay FC2 CB-F-3A-A CC-FC2-K811 Safeguard Test Cabinet Relay FC2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -8 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 CC-V-175 Primary Component Cooling Water Loop "B" Header Isolation Outboard Supply Valve CC-20213 A 310769 PP-F-4B-Z - X X X UZ4 CC-E2T/6-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-G2G G2G-UZ4 G2G-UZ3 310895 E2T/6a E2T/6d E2T/6b E2T/6e CBA-FN-19 CBA-FN-20 Instrument Air EDE-PP-113A EAH-FN-5A EAH-FN-31A CC-V-168 CC-CS-2251-2 Control Switch with Indication G2G CB-F-1A-A CC-SS-2251 Selector Switch G2G CB-F-1A-A CC-ZS-V175 Valve Position Switch UZ4 PP-F-4B-Z CC-V175-20-1 Pilot Solenoid UZ4 PP-F-4B-Z CC-V175-20-2 Pilot Solenoid UZ4 PP-F-4B-Z CC-CS-2251-1 Control Switch with Indication F30 CB-F-3A-A F30-G2G F30-G2G/1 F30-FB7/6 G2G-GN9 FB7-G2G FC1-G2G FC1-G2G/1 F30-G2G/5 G2G-GN9/3 CC-FB7-K-633A Protection System Relay FB7 CB-F-3A-A CC-FB7-K-632A Protection System Relay FB7 CB-F-3A-A CC-ATR-LLB1 Isolation Signal Auxiliary Relay GN9 CB-F-1A-A CC-FC1-K803 Safeguard Test Cabinet Relay FC1 CB-F-3A-A CC-FC1-K812 Safeguard Test Cabinet Relay FC1 CB-F-3A-A 10 CC-V-176 Primary Component Cooling Water Loop "B" Header Isolation Inboard Supply Valve CC-20213 B 310579 C-F-2-Z - X X X VA9 CC-E2U/4-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-E4C E4C-G2J G2J-H39 G2J-H39/1 H39-VA9 H39-VA0 310895 E2U/4a E2U/4d E2U/4b E2U/4e E2U/4f CBA-FN-32 CBA-FN-33 Instrument Air EDE-PP-113B CC-V-57 CC-CS-2299-2 Control Switch with Indication G2J CB-F-1B-A CC-SS-2299 Selector Switch G2J CB-F-1B-A CC-ZS-V176 Valve Position Switch VA9 C-F-2-Z CC-E4C-FU15,16 30A Fuses E4C CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A CC-V176-20-1 Pilot Solenoid VA9 C-F-2-Z CC-V176-20-2 Pilot Solenoid VA9 C-F-2-Z CC-CS-2299-1 Control Switch with Indication F30 CB-F-3A-A F30-G2J/1 F30-G2J/6 F30-FB0/4 G2J-GN0/2 FB0-G2J FC2-G2J FC2-G2J/2 F30-G2J G2J-GN0/3 CC-FB0-K-633B Protection System Relay FB0 CB-F-3A-A CC-FB0-K-632B Protection System Relay FBO CB-F-3A-A CC-BTR-LLB1 Isolation Signal Auxiliary Relay GN0 CB-F-1B-A CC-FC2-K803 Safeguard Test Cabinet Rela y FC2 CB-F-3A-A CC-FC2-K812 Safeguard Test Cabinet Relay FC2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -9 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 CC-V-256 Primary Component Cooling Water Loop "B" Header Isolation Inboard Return Valve CC-20213 B 310579 C-F-2-Z - X X X VA0 CC-E2U/4-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-E4C E4C-G2J G2J-H39 H39-VA0 H39-VA9 G2J-H39/1 310895 E2U/4a E2U/4d E2U/4b E2U/4e E2U/4f CBA-FN-32 CBA-FN-33 Instrument Air EDE-PP-113B CC-V-121 CC-CS-2250-2 Control Switch with Indication G2J CB-F-1B-A CC-SS-2250 Selector Switch G2J CB-F-1B-A CC-ZS-V256 Valve Position Switch VA0 C-F-2-Z CC-E4C-FU15,16 30A Fuses E4C CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A CC-V256-20-1 Pilot Solenoid VA0 C-F-2-Z CC-V256-20-2 Pilot Solenoid VA0 C-F-2-Z CC-V176-20-2 Pilot Solenoid VA9 C-F-2-Z CC-CS-2250-1 Control Switch with Indication F30 CB-F-3A-A F30-G2J F30-G2J/1 F30-FB0/4 G2J-GN0/3 FB0-G2J FC2-G2J FC2-G2J/2 G2J-GN0/2 F30-G2J/6 CC-FB0-K-633B Protection System Relay FB0 CB-F-3A-A CC-FB0-K-632B Protection System Relay FB0 CB-F-3A-A CC-BTR-LLB1 Isolation Signal Auxiliary Relay GN0 CB-F-1B-A CC-FC2-K803 Safeguard Test Cabinet Relay FC2 CB-F-3A-A CC-FC2-K812 Safeguard Test Cabinet Relay FC2 CB-F-3A-A 12 CC-V-257 Primary Component Cooling Water Loop "B" Header Isolation Outboard Return Valve CC-20213 A 310769 PP-F-4B-Z - X X X UZ3 CC-E2T/6-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-G2G G2G-UZ3 G2G-UZ4 310895 E2T/6a E2T/6d E2T/6b E2T/6e CBA-FN-19 CBA-FN-20 Instrument Air EDE-PP-113A EAH-FN-5A EAH-FN-31A CC-V-122 CC-CS-2249-2 Control Switch with Indication G2G CB-F-1A-A CC-SS-2249 Selector Switch G2G CB-F-1A-A CC-ZS-V257 Valve Position Switch UZ3 PP-F-4B-Z CC-V257-20-1 Pilot Solenoid UZ3 PP-F-4B-Z CC-V257-20-2 Pilot Solenoid UZ3 PP-F-4B-Z CC-CS-2249-1 Control Switch with Indication F30 CB-F-3A-A F30-G2G/1 F30-G2G/5 F30-FB7/6 G2G-GN9/3 FB7-G2G FC1-G2G FC1-G2G/1 F30-G2G G2G-GN9 CC-FB7-K-633A Protection System Relay FB7 CB-F-3A-A CC-FB7-K-632A Protection System Relay FB7 CB-F-3A-A CC-ATR-LLB1 Isolation Signal Auxiliary Relay GN9 CB-F-1A-A CC-FC1-K803 Safeguard Test Cabinet Relay FC1 CB-F-3A-A CC-FC1-K812 Safeguard Test Cabinet Relay FC1 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -10 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 CC-TV-2171-1 Primary Component Cooling Water Heat Exchanger E-17A Temperature Control Valve CC-20205 A 310765 PAB-F-2C-Z X X X X UN6 CC-E2T/3-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-G81 G81-G2M G81-UN6/1 G81-UN7/1 G81-GN9/A F30-G81/6 F30-G81/7 310895 E2T/3a E2T/3c E2T/3d CBA-FN-19 CBA-FN-20 PAH-FN-42A EDE-PP-113A Instrument Air CC-TV-2271-1 CC-SS-2171 Selector Switch G81 CB-F-1A-A CC-GN9-R1 Auxiliary Relay GN9 CB-F-1A-A CC-TY-2171-1 Pilot Solenoid G2M PAB-F-2C-Z CC-ZL-2171-5 Valve Position Indicating Lights G81 CB-F-1A-A CC-ZS-TV-2171-1 Valve Position Switch UN6 PAB-F-2C-Z CC-CS-2171 Control Switch F30 CB-F-3A-A G81-G2M/2 F30-FK0/3 FK0-G81/1 FK0-TM0 CC-GN9-R1 Auxiliary Relay GN9 CB-F-1A-A CC-ZL-2171-1 Indicating Lights F30 CB-F-3A-A CC-SS-2171 Selector Switch G81 CB-F-1A-A 310895 310952 4c FK0d FK0f FK0h CBA-FN-19 CB-FN-20 PAH-FN-42A Instrument Air MM-CP-297A CC-TY-2171-4 I/P Converter G2M PAB-F-2C-Z CC-TY-2171-5 I/P Converter G2M PAB-F-2C-Z CC-TE-2171 Temperature Element TM0 PAB-F-2C-Z CC-TYY-2171-2 PCCW Loop "A" Relay FK0 CB-F-3A-A CC-TK-2171 Manual Controller F30 CB-F-3A-A MM-CP-297A BOP-PCC FK0 CB-F-3A-A 14 CC-TV-2171-2 Primary Component Cooling Water Heat Exchanger E-17A Temperature Control Valve CC-20205 A 310765 PAB-F-2C-Z X X X X UN7 CC-E2T/3-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-G81 G81-G2M G81-UN6/1 G81-UN7/1 G81-GN9/A F30-G81/6 F30-G81/7 310895 E2T/3a E2T/3c E2T/3d CBA-FN-19 CBA-FN-20 PAH-FN-42A EDE-PP-113A Instrument Air CC-TV-2271-2 CC-SS-2171 Selector Switch G81 CB-F-1A-A CC-GN9-R1 Auxiliary Relay GN9 CB-F-1A-A CC-TY-2171-2 Pilot Solenoid G2M PAB-F-2C-Z CC-ZL-2171-6 Valve Position Indicating Lights G81 CB-F-1A-A CC-ZS-TV-2171-2 Valve Position Switch UN7 PAB-F-2C-Z CC-CS-2171 Control Switch F30 CB-F-3A-A CC-GN9-R1 Auxiliary Relay GN9 CB-F-1A-A CC-ZL-2171-2 Indicating Lights F30 CB-F-3A-A CC-SS-2171 Selector Switch G81 CB-F-1A-A G81-G2M/2 F30-FK0/3 FK0-G81/1 FK0-TM0 310895 310952 4c FK0d FK0f FK0h CBA-FN-19 CB-FN-20 PAH-FN-42A Instrument Air CC-TY-2171-4 I/P Converter G2M PAB-F-2C-Z CC-TY-2171-5 I/P Converter G2M PAB-F-2C-Z CC-TE-2171 Temperature Element TM0 PAB-F-2C-Z CC-TYY-2171-2 PCCW Loop "A" Relay FK0 CB-F-3A-A CC-TK-2171 Manual Controller F30 CB-F-3A-A MM-CP-297A BOP-PCC FK0 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -11 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 CC-TV-2271-1 Primary Component Cooling Water Heat Exchanger E-17B Temperature Control Valve CC-20211 B 310765 PAB-F-2C-Z X X X X UP9 CC-E2U/3-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-GZ0 GN0-GZ0/5 GZO-UP9/1 GZ0-UP0/1 GN0-GZ0/9 E2U-GN0/6 GZO-UI2 F31-GZ0/3 F31-GZ0/4 310895 E2U/3a E2U/3c E2U/3d CBA-FN-32 CBA-FN-33 PAH-FN-42B EDE-PP-113B Instrument Air CC-TV-2171-1 CC-SS-2271 Selector Switch GZ0 CB-F-1B-A CC-GN0-R1 Auxiliary Relay GN0 CB-F-1B-A CC-GNO-R2 Auxiliary Relay GN0 CB-F-1B-A CC-TY-2271-1 Pilot Solenoid UI2 PAB-F-2C-Z CC-ZL-2271-5 Valve Position Indicating Lights GZO CB-F-1B-A CC-ZS-TV-2271-1 Valve Position Switch UP9 PAB-F-2C-Z CC-CS-2271 Control Switch F30 CB-F-3A-A CC-ZL-2271-1 Indicating Lights F30 CB-F-3A-A CC-SS-2271 Selector Switch GZ0 CB-F-1B-A GZ0-Q60 FJ4-TM8/1 FJ4-GZ0/3 F30-FJ4/1 310895 310952 4c FJ4j FJ4l FJ4m CBA-FN-32 CB-FN-33 PAH-FN-42B Instrument Air MM-CP-152B CC-TY-2271-5 I/P Converter Q60 PAB-F-2C-Z CC-TY-2271-4 I/P Converter Q60 PAB-F-2C-Z CC-TE-2271 Temperature Element TM8 PAB-F-2C-Z CC-TYY-2271-2 PCCW Loop "B" Relay FJ4 CB-F-3A-A CC-TK-2271 Manual Controller F30 CB-F-3A-A MM-CP-152B BOP-PCC FJ4 CB-F-3A-A 16 CC-TV-2271-2 Primary Component Cooling Water Heat Exchanger E-17B Temperature Control Valve CC-20211 B 310765 PAB-F-2C-Z X X X X UP0 CC-E2U/3-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-GZ0 GN0-GZ0/5 GZO-UP9/1 GZ0-UP0/1 GN0-GZ0/9 E2U-GN0/6 GZO-UI2 F31-GZ0/3 F31-GZ0/4 310895 E2U/3a E2U/3c E2U/3d CBA-FN-32 CBA-FN-33 PAH-FN-42B EDE-PP-113B Instrument Air CC-TV-2171-2 CC-SS-2271 Selector Switch GZ0 CB-F-1B-A CC-GN0-R1 Auxiliary Relay GN0 CB-F-1B-A CC-GNO-R2 Auxiliary Relay GN0 CB-F-1B-A CC-TY-2271-2 Pilot Solenoid UI2 PAB-F-2C-Z CC-ZL-2271-6 Valve Position Indicating Lights GZO CB-F-1B-A CC-ZS-TV-2271-2 Valve Position Switch UP0 PAB-F-2C-Z CC-CS-2271 Control Switch F30 CB-F-3A-A CC-ZL-2271-2 Indicating Lights F30 CB-F-3A-A CC-SS-2271 Selector Switch GZ0 CB-F-1B-A GZ0-Q60 FJ4-TM8/1 FJ4-GZ0/3 F30-FJ4/1 310895 310952 4c FJ4j FJ4l FJ4m CBA-FN-32 CB-FN-33 PAH-FN-42B Instrument Air MM-CP-152B CC-TY-2271-5 I/P Converter Q60 PAB-F-2C-Z CC-TY-2271-4 I/P Converter Q60 PAB-F-2C-Z CC-TE-2271 Temperature Element TM8 PAB-F-2C-Z CC-TYY-2271-2 PCCW Loop "B" Relay FJ4 CB-F-3A-A CC-TK-2271 Manual Controller F30 CB-F-3A-A MM-CP-152B BOP-PCC FJ4 CB-F-3A-A 17 CC-E-17A Primary Component Cooling Water Heat Exchanger CC-20205 A 310765 805217 PAB-F-2C-Z PAB-F-3A-Z X X - - - - - - - - - - Service Water CC-E-17B Notes 1 and 3 18 CC-E-17B Primary Component Cooling Water Heat Exchanger CC-20211 B 310765 805217 PAB-F-2C-Z PAB-F-3A-Z X X - - - - - - - - - - Service Water CC-E-17A Notes 1 and 3 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -12 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 CC-V-145 RH-E-9A Return Header Isolation Valve V-145 CC-20207 A 310763 RHR-F-3B-Z - X X - V78 CC-BY2-52 460 V AC Circuit Breaker BY2 CB-F-1A-A BY2-F30 BY2-F30/1 F30-FB7/1 BY2-V78 BY2-V78/1 BY2-V78/2 310895 BY2a BY2c EAH-FN-5A EAH-FN-31A EDE-MCC-512 CC-V-272 CC-CS-2144 Control Switch with Indication F30 CB-F-3A-A CC-BY2-42 Motor Starter BY2 CB-F-1A-A CC-BY2-49 Thermal Overload BY2 CB-F-1A-A CC-V78-V145 Position Switch V78 RHR-F-3B-Z CC-FB7-K624A Containment Isolation Auxiliary Relay FB7 CB-F-3A-A 20 CC-V-272 RHR-E-9B Return Header Isolation Valve V-272 CC-20213 B 310763 RHR-F-3A-Z - X X - V72 CC-BY8-52 460 V AC Circuit Breaker BY8 CB-F-1A-A BY8-F31 BY8-F31/1 F31-FB0/3 BY8-V72 BY8-V72/1 BY8-V72/2 BY8-E3Q BY8a BY8c EAH-FN-5B EAH-FN-31B EDE-MCC-612 CC-V-145 CC-CS-2244 Control Switch with Indication F30 CB-F-3A-A CC-BY8-42 Motor Starter BY8 CB-F-1B-A CC-BY8-49 Thermal Overload BY8 CB-F-1B-A CC-V72-V272 Position Switch V72 RHR-F-3A-Z CC-FB0-K623B Containment Isolation Auxiliary Relay FB0 CB-F-3A-A CC-BY8-R1 Auxiliary Relay E3Q CB-F-1B-A 21 CC-P-322A Thermal Barrier PCCW Recirculation Pump CC-20209 A 310576 C-F-1-Z X X X - M1D CC-B4M-52-1,2 460 V AC Circuit Breakers B4M CB-F-1A-A B4M-H18 H18-M1D B4M-G81 F30-FK0/2 F30-G81/A B4Ma B4Mc B4Md CBA-FN-19 CBA-FN-20 EDE-MCC-515 CC-P-322B CC-CS-2077-2 Control Switch with Indication G2G CB-F-1A-A CC-SS-2077 Selector Switch G2G CB-F-1A-A CC-B4M-42 Motor Starter B4M CB-F-1A-A CC-B4M-49 Overload Relay B4M CB-F-1A-A EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A CC-B4M-FU Fuse B4M CB-F-1A-A CC-CS-2077-1 Control Switch with Indication F30 CB-F-3A-A CC-FYY-2175A Flow Relay FK0 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -13 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 22 CC-P-322B Thermal Barrier PCCW Recirculation Pump CC-20209 B 310577 C-F-1-Z X X X - M1E CC-B4Q-52-1,2 460 V AC Circuit Breaker B4Q CB-F-1B-A B4Q-H15 H15-M1E B4Q-GZ0 F30-FL2 F30-GZ0/8 B4Qa B4Qc B4Qd CBA-FN-32 CBA-FN-33 EDE-MCC-615 CC-P-322A CC-CS-2078-2 Control Switch with Indication G2J CB-F-1B-A CC-SS-2078 Selector Switch G2J CB-F-1B-A CC-B4Q-42 Motor Starter B4Q CB-F-1B-A CC-B4Q-49 Overload Relay B4Q CB-F-1B-A EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A CC-B4Q-FU Fuses B4Q CB-F-1B-A CC-CS-2078-1 Control Switch with Indication F30 CB-F-3A-A CC-FYY-2175B Flow Relay FL2 CB-F-3A-A 23 CC-E-153A Thermal Barrier Heat Exchanger CC-20209 A 310576 C-F-1-Z X X - - - - - - - - - - - CC-E-153B Note 1 24 CC-E-153B Thermal Barrier Heat Exchanger CC-20209 B 310577 C-F-1-Z X X - - - - - - - - - - - CC-E-153A Note 1 25 CC-V-1101 Thermal Barrier HX CC-E-153A Isolation Valve CC-20209 A 310769 PP-F-3A-Z X X X - V2S CC-B4K-52 460 V AC Circuit Breaker B4K CB-F-1A-A B4K-V2S/1 B4K-F29 B4K-F29/1 310895 B4Ka B4Kc B4Kd CBA-FN-19 CBA-FN-20 CC-V-1092 CC-CS-2073 Control Switch with Indication F29 CB-F-3A-A CC-B4K-42 Motor Starter B4K CB-F-1A-A CC-B4K-49 Thermal Overload B4K CB-F-1A-A CC-V2S-V1101 Position Switch V2S PP-F-3A-Z 26 CC-V-1109 Thermal Barrier HX CC-E-153A Isolation Valve CC-20209 A 310769 PP-F-3A-Z X X X - V2T CC-B4L-52 460 V AC Circuit Breaker B4L CB-F-1A-A B4L-V2T/1 B4L-F29 B4L-F29/1 310895 B4La B4Lc B4Ld CBA-FN-19 CBA-FN-20 CC-V-1095 CC-CS-2074 Control Switch with Indication F29 CB-F-3A-A CC-B4L-42 Motor Starter B4L CB-F-1A-A CC-B4L-49 Thermal Overload B4L CB-F-1A-A CC-V2T-V1109 Position Switch V2T PP-F-3A-Z 27 CC-V-1092 Thermal Barrier HX CC-E-153B Isolation Valve CC-20209 B 310769 PP-F-4B-Z X X X - V2V CC-B4P-52 460 V AC Circuit Breaker B4P CB-F-1B-A B4P-V2V/1 B4P-F20 B4P-F20/1 310895 B4Pa B4Pc B4Pd CBA-FN-32 CBA-FN-33 CC-V-1101 CC-CS-2075 Control Switch with Indication F29 CB-F-3A-A CC-B4P-42 Motor Starter B4P CB-F-1B-A CC-B4P-49 Thermal Overload B4P CB-F-1B-A CC-V2V-V1092 Position Switch V2V PP-F-4B-Z CC-B4P-R1 Auxiliary Relay E3Q CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -14 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 28 CC-V-1095 Thermal Barrier HX CC-E-153B Isolation Valve CC-20209 B 310769 PP-F-4B-Z X X X - V2U CC-B4N-52 460 V AC Circuit Breaker B4N CB-F-1B-A B4N-V2U/1 B4N-F20 B4N-F20/1 310895 B4Na B4Nc B4Nd CBA-FN-32 CBA-FN-33 CC-V-1109 CC-CS-2076 Control Switch with Indication F29 CB-F-3A-A CC-B4N-42 Motor Starter B4N CB-F-1B-A CC-B4N-49 Thermal Overload B4N CB-F-1B-A CC-V2U-V1095 Position Switch V2U PP-F-4B-Z CC-B4N-R1 Auxiliary Relay E3Q CB-F-1B-A 29 CC-V-428 RC-P-1A Thermal Barrier Isolation Valve CC-20209 A 310578 C-F-2-Z X X X - V74 CC-BY4-52-1 460 V AC Circuit Breaker BY4 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 2 30 CC-V-438 RC-P-1C Thermal Barrier Isolation Valve CC-20209 B 310579 C-F-2-Z X X X - V76 CC-BY6-52-1 460 V AC Circuit Breaker BY6 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 2 31 CC-V-439 RC-P-1D Thermal Barrier Isolation Valve CC-20209 A 310579 C-F-2-Z X X X - V70 CC-BY7-52-1 460 V AC Circuit Breaker BY7 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 2 32 CC-V-395 RC-P-1B Thermal Barrier Isolation Valve CC-20209 B 310578 C-F-2-Z X X X - V69 CC-BY5-52-1 460 V AC Circuit Breaker BY5 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 2 33 CC-TK-196 Thermal Barrier Loop Head Tank CC-20209 A/B 310581 805193 C-F-3-Z X X - - - - - - - - - - - None Notes 1 and 4 34 CC-TK-19A Primary Component Cooling Water Head Tank CC-20205 A 310767 PAB-F-3A-Z X X - - - - - - - - - - - CC-TK-19B Note 1 35 CC-TK-19B Primary Component Cooling Water Head Tank CC-20211 B 310767 PAB-F-3A-Z X X - - - - - - - - - - - CC-TK-19A Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -15 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 36 CC-LT-2172-1 CC-LT-2172-2 CC-LT-2172-3 Head Tank CC-TK-19A Level CC-20205 A 310767 PAB-F-3A-Z X X X - RG5 RW1 RW2 MM-CP-152A EDE-TBX-YH4 BOP-PCC Terminal Box FJ1 YH4 CB-F-3A-A PAB-F-3A-Z FJ1-YH4 RG5-YH4 RW1-YH4 RW2-YH4 310952 FJ1g FJ1j CC-LT-2272-1 CC-LT-2272-2 CC-LT-2272-3 Head Tank CC-TK-19B Level CC-20211 B 310768 PAB-F-3B-Z X X X - RG6 RW3 RW4 MM-CP-152A EDE-TBX-YH4 BOP-PCC Terminal Box FJ1 YH4 CB-F-3A-A PAB-F-3A-Z FJ1-YH4/1 RG6-YH4 RW3-YH4 RW4-YH4 CC-E42/10-52 120 V AC Circuit Breaker E42 CB-F-1A-A EF4-FJ1 EF4-FJ1/1 E4E-EF4 E4E-H36/3 H36-S4P GF8-H36 310895 E42/10a E42/10c E42/10d EDE-MCC-521 CC-LYY-2172-1, 2, 3 Level Relay FJ1 CB-F-3A-A CC-LYY-2272-1, 2, 3 Level Relay FJ1 CB-F-3A-A CC-RYY-2172-1LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2172-2LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2172-3LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2272-1LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2272-2LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2272-3LL Auxiliary Relay EF4 CB-F-1A-A MM-CP-152A BOP-PCC FJ1 CB-F-3A-A EDE-MM-582 Fuse Panel E4E ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A CC-FISHL-2147 Flow Switch S4P C-F-2-Z CC-FISHL-2248 Flow Switch GF8 C-F-2-Z MM-CP-14 Safeguards Cabinet FC1 CB-F-3A-A EF4-GN9 FC1-GN9/1 310895 E87/10a E87/10d E87/10b E87/10e E87/10f CC-RYY-2172-1LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2172-2LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2172-3LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2272-1LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2272-2LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2272-3LL Auxiliary Relay EF4 CB-F-1A-A CC-ATR-LLA1 Containment Isolation Relay GN9 CB-F-1A-A CC-ATR-LLB1 Containment Isolation Relay GN9 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -16 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 37 CC-LT-2192-1 CC-LT-2192-2 CC-LT-2192-3 Head Tank CC-TK-19A Level CC-20205 A 310767 PAB-F-3A-Z X X X - R81 RW5 RW6 MM-CP-152B EDE-TBX-YH5 BOP-PCC Terminal Box FJ4 YH5 CB-F-3A-A PAB-F-3A-Z FJ4-YH5 R81-YH5 RW5-YH5 RW6-YH5 310952 FJ4j FJ4l CC-LT-2292-1 CC-LT-2292-2 CC-LT-2292-3 Head Tank CC-TK-19B Level CC-20211 B 310768 PAB-F-3B-Z X X X - R82 RW7 RW8 MM-CP-152B EDE-TBX-YH5 BOP-PCC Terminal Box FJ4 YH5 CB-F-3A-A PAB-F-3A-Z FJ4-YH5/1 R82-YH5 RW7-YH5 RW8-YH5 CC-E50/6-52 120 V AC Circuit Breaker E50 CB-F-1B-A EE3-FJ4 E4J-ED0/1 E50-E4J/1 EE3-FJ4/1 EDO-H41 H41-S4Q GN5-H41 310895 E50/6a E50/6c E50/6b E50/6e EDE-MCC-621 CC-LYY-2192-1,2,3 Level Relay FJ4 CB-F-3A-A CC-LYY-2292-1,2,3 Level Relay FJ4 CB-F-3A-A CC-RYY-2192-1LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2192-2LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2192-3LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2292-1LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2292-2LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2292-3LL Auxiliary Relay EE3 CB-F-1B-A MM-CP-152B BOP-PCC FJ4 CB-F-3B-A EDE-MM-586 Fuse Panel E4J CB-F-1B-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A CC-FISHL-2247 Flow Switch S4Q C-F-2-Z CC-FISHL-2148 Flow Switch GN5 C-F-2-Z MM-CP-15 Safeguards Cabinet FC2 CB-F-3A-A FC2-GN0/2 EE3-GN0 310895 E88/8a E88/8d E88/8b E88/8e E88/8f BTR-LLA1 Isolation Relay GN0 CB-F-1B-A BTR-LLB1 Isolation Relay GN0 CB-F-1B-A CC-RYY-2192-1LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2192-2LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2192-3LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2292-1LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2292-2LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2292-3LL Auxiliary Relay EE3 CB-F-1B-A 38 MM-CP-152A BOP Process Control Cabinet - A 310499 CB-F-3A-A X X X - FJ1 - - - - EH9-FJ1 310952 EH9/1 EH9/1 EDE-PP-1E MM-CP-152B SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -1 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CAH-FN-1A Containment Structure Cooler AC-1A-Fan MAH-20506 B 301578 C-F-2-Z X X - M19 CAH-AC5-52 480 V AC Circuit Breaker AC5 CB-F-1B-A AC5-G2K AC5-G2K/1 AC5-GNO AC5-H13 AC5-H13/1 G2K-H41 G2K-H41/1 H13-JV7 H13-JV7/1 H41-M19/1 H41-SD1 JV7-JV8 JV7-M19 JV7-M19/1 JV8-M19 JV8-M19/1 F37-FBO/1 F37-G2K/9 F37-G2K/A F37-G2K/B G2K-HR4/2 G2K-HR4/7 310931 AC5a AC5d AC5b CBA-FN-32 CBA-FN-33 EDE-US-63 Primary Component Cooling Water CAH-FN-1C CAH-FN-1E CAH-FN-1F CAH-JV7-43 Safety Switch Speed Changer JV7 C-F-2-Z CAH-JV8-43 Safety Switch Speed Changer JV8 C-F-2-Z CAH-CS-5660-2 Control Switch with Indication G2K CB-F-1B-A CAH-SS-5660 Selector Switch G2K CB-F-1B-A EDE-AF8-94-4 Bus Undervoltage Relay AF8 CB-F-1B-A CAH-GNO-R1 Time Delay Relay GNO CB-F-1B-A CC-FISL-2122 Flow Indication Switch SD1 C-F-2-Z CAH-AC5-52H-1 Truck Operated Contact AC5 CB-F-1B-A CAH-AC5-G,R Indicating Lights AC5 CB-F-1B-A CAH-AC5-AM Ammeter AC5 CB-F-1B-A CAH-AC5-CT Current Transformer (300/5) AC5 CB-F-1B-A CAH-AC5-ATR Transducer AC5 CB-F-1B-A CAH-ZL-5660-2 Outlet Damper Position Lights G2K CB-F-1B-A CAH-DP-312 Outlet Damper Position Switch M19 C-F-2-Z EDE-MM-89 Electrical Penetration H13 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A CAH-AC5-FU 15A Fuses AC5 CB-F-1B-A CAH-CS-5660-1 Control Switch with Indication F37 CB-F-3A-A EPS-HR4-PR1, RA, RMO, SR3 Emergency Power Sequencer Relays HR4 CB-F-1B-A CAH-FBO-K610B SI Actuating Auxiliary Relay FBO CB-F-3A-A CAH-ZL-5660-1 Outlet Damper Position Lights F37 CB-F-3A-A CC-FISL-2122 Flow Indication Switch SD1 C-F-2-Z E4G-H41/1 E53-E4G/1 H41-SD1/1 E53-E4G H41-SD2/1 E4G-H39/1 H39-SD4/1 310895 E53/10a E53/10c EDE-MCC-631 CC-E4G-FU6, FU5 30A Fuse E4G ET-F-1C-A EDE-MM-117 Electrical Penetration H41 ET-F-1C-A, C-F-1-Z CAH-E53/10-52 120 V AC Circuit Breaker E53 CB-F-1B-A CC-FISL-2123 Flow Indication Switch SD2 C-F-2-Z EDE-MM-115 Electrical Penetration H39 ET-F-1C-A, C-F-1-Z CC-FISL-2222 Flow Indication Switch SD4 C-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -2 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 CAH-FN-1B Containment Structure Cooler AC-1B Fan MAH-20506 B 310579 C-F-2-Z X X - M20 CAH-AE5-52 480 V AC Circuit Breaker AE5 CB-F-1B-A AE5-G2K AE5-G2K/1 AE5-GNO G2K-H41/2 G2K-H41/3 AE5-H13 AE5-H13/1 H13-M20 H13-M20/1 H41-M20/1 H41-SD2 F37-FBO/2 F37-G2K/3 F37-G2K/4 F37-G2K/5 G2K-HR4/3 G2K-HR4/5 310931 AE5a AE5d AE5b CBA-FN-32 CBA-FN-33 EDE-US-63 Primary Component Cooling Water CAH-FN-1C CAH-FN-1E CAH-FN-1F CAH-CS-5661-2 Control Switch with Indication G2K CB-F-1B-A CAH-SS-5661 Selector Switch G2K CB-F-1B-A EDE-AF8-94-4 Bus Undervoltage Relay AF8 CB-F-1B-A CAH-GNO-R1 Time Delay Relay GNO CB-F-1B-A CC-FISL-2123 Flow Indication Switch SD2 C-F-2-Z CAH-AE5-52H-1 Truck Operated Contact AE5 CB-F-1B-A CAH-AE5-G,R Indicating Lights AE5 CB-F-1B-A CAH-AE5-AM Ammeter AE5 CB-F-1B-A CAH-AE5-CT Current Transformer (300/5) AE5 CB-F-1B-A CAH-AE5-ATR Transducer AE5 CB-F-1B-A CAH-ZL-5661-2 Outlet Damper Position Lights G2K CB-F-1B-A CAH-DP-313 Outlet Damper Position Switch M20 C-F-2-Z EDE-MM-89 Electrical Penetration H13 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A CAH-AE5-FU 15A Fuses AE5 CB-F-1B-A CAH-CS-5661-1 Control Switch with Indication F37 CB-F-3A-A EPS-HR4-PR1, RA, RMO, SR3 Emergency Power Sequencer Relays HR4 CB-F-1B-A CAH-FBO-K-610B SI Actuating Auxiliary Relay FBO CB-F-3A-A CAH-ZL-5661-1 Outlet Damper Position Lights F37 CB-F-3A-A CC-FISL-2123 Flow Indication Switch SD2 C-F-2-Z H41-SD2/1 E53-E4G/1 E4G-H41/1 E53-E4G H41-SD1/1 E4G-H39/1 H39-SD4/1 301895 E53/10a E53/10c EDE-MCC-631 CC-E4G-FU6, FU5 30A Fuse E4G ET-F-1C-A EDE-MM-117 Electrical Penetration H41 ET-F-1C-A, C-F-1-Z CAH-E53/10-52 120 V AC Circuit Breaker E53 CB-F-1B-A CC-FISL-2122 Flow Indication Switch SD1 C-F-2-Z EDE-MM-115 Electrical Penetration H39 ET-F-1C-A, C-F-1-Z CC-FISL-2222 Flow Indication Switch SD4 C-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -3 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 CAH-FN-1C Containment Structure Cooler AC-1C Fan MAH-20506 A 310579 C-F-2-Z - X X - M21 CAH-AE7-52 480 V AC Circuit Breaker AE7 CB-F-1A-A AE7-G2H AE7-G2H/1 AE7-GN9 AE7-HO8 AE7-HO8/1 G2H-H35 G2H-H35/1 HO8-JV3 HO8-JV3/1 H35-M21/1 H35-SD3/1 JV3-JV4 JV3-M21 JV3-M21/1 JV4-M21 JV4-M21/1 F36-FB7/4 F36-G2H/9 F36-G2H/A F36-G2H/B G2H-HR2/4 G2H-HR2/5 310931 AE7a AE7d AE7b CBA-FN-19 CBA-FN-20 EDE-US-53 Primary Component Cooling Water CAH-FN-1A CAH-FN-1B CAH-FN-1D CAH-JV3-43 Safety Switch Speed Changer JV3 C-F-2-Z CAH-JV4-43 Safety Switch Speed Changer JV4 C-F-2-Z CAH-CS-5662-2 Control Switch with Indication G2H CB-F-1A-A CAH-SS-5662 Selector Switch G2H CB-F-1A-A EDE-AF3-94-4 Bus Undervoltage Relay AF3 CB-F-1A-A CAH-GN9-R1 Time Delay Relay GN9 CB-F-1A-A CC-FISL-2124 Flow Indication Switch SD3 C-F-2-Z CAH-AE7-52H-1 Truck Operated Contact AE7 CB-F-1A-A CAH-AE7-G,R Indicating Lights AE7 CB-F-1A-A CAH-AE7-AM Ammeter AE7 CB-F-1A-A CAH-AE7-CT Current Transformer (300/5) AE7 CB-F-1A-A CAH-AE7-ATR Transducer AE7 CB-F-1A-A CAH-ZL-5662-2 Outlet Damper Position Lights G2H CB-F-1A-A CAH-DP-314 Outlet Damper Position Switch M21 C-F-2-Z EDE-MM-84 Electrical Penetration HO8 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A CAH-AE7-FU 15A Fuses AE7 CB-F-1A-A CAH-CS-5662-1 Control Switch with Indication F36 CB-F-3A-A EPS-HR4-PR1, RA, RMO, SR3 Emergency Power Sequencer Relays HR2 CB-F-1A-A CAH-FB7-K-610A SI Actuating Auxiliary Relay FB7 CB-F-3A-A CAH-ZL-5662-1 Outlet Damper Position Lights F36 CB-F-3A-A CC-FISL-2124 Flow Indication Switch SD3 C-F-2-Z E4H-H35 E45-E4H H35-SD3 E45-E4E E4E-H36/4 H36-SD5/1 H36-SD6/1 301895 E45/11a E45/11C EDE-MCC-531 CC-E4H-FU20 30A Fuse E4H CB-F-1A-A EDE-MM-111 Electrical Penetration H35 ET-F-1A-A, C-F-2-Z CAH-E45/11-52 120 V AC Circuit Breaker E45 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -4 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 CAH-FN-1C (Continued) Containment Structure Cooler AC-1C Fan EDE-MM-112 Electrical Penetration H36 ET-F-1A-A, C-F-2-Z CC-FISL-2223 Flow Indication Switch SD5 C-F-2-Z CC-FISL-2224 Flow Indication Switch SD6 C-F-2-Z CC-E4E-FU39 30A Fuse E4E ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -5 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 CAH-FN-1D Containment Structure Cooler AC-1D Fan MAH-20505 B 310579 C-F-2-Z X X - M22 CAH-AE6-52 480 V AC Circuit Breaker AE6 CB-F-1B-A AE6-G2K AE6-G2K/1 AE6-GNO AE6-HO9 AE6-HO9/1 G2K-H39 G2K-H39/1 HO9-M22 HO9-M22/1 H39-M22/1 H39-SD4 F37-FBO/3 F37-G2K/6 F37-G2K/7 F37-G2K/8 G2K-HR4/4 G2K-HR4/6 310931 AE6a AE6d AE6b CBA-FN-32 CBA-FN-33 EDE-US-63 Primary Component Cooling Water CAH-FN-1C CAH-FN-1E CAH-FN-1F CAH-CS-5663-2 Control Switch with Indication G2K CB-F-1B-A CAH-SS-5663 Selector Switch G2K CB-F-1B-A EDE-AF8-94-4 Bus Undervoltage Relay AF8 CB-F-1B-A CAH-GNO-R1 Time Delay Relay GNO CB-F-1B-A CC-FISL-2222 Flow Indication Switch SD4 C-F-2-Z CAH-AE6-52H-1 Truck Operated Contact AE6 CB-F-1B-A CAH-AE6-G,R Indicating Lights AE6 CB-F-1B-A CAH-AE6-AM Ammeter AE6 CB-F-1B-A CAH-AE6-CT Current Transformer (300/5) AE6 CB-F-1B-A CAH-AE6-ATR Transducer AE6 CB-F-1B-A CAH-ZL-5663-2 Outlet Damper Position Lights G2K CB-F-1B-A CAH-DP-315 Outlet Damper Position Switch M22 C-F-2-Z EDE-MM-85 Electrical Penetration HO9 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A CAH-AE6-FU 15A Fuses AE6 CB-F-1B-A CAH-CS-5663-1 Control Switch with Indication F37 CB-F-3A-A EPS-HR4-PR1, RA, RMO, SR3 Emergency Power Sequencer Relays HR4 CB-F-1B-A CAH-FBO-K610B SI Actuating Auxiliary Relay FBO CB-F-3A-A CAH-ZL-5663-1 Outlet Damper Position Lights F37 CB-F-3A-A CC-FISL-2222 Flow Indication Switch SD4 C-F-2-Z E4G-H39/1 E53-E4G H39-SD4/1 E53-E4G/1 E4G-H41/1 H41-SD1/1 H41-SD2/1 310895 E53/10a E53/10c EDE-MCC-631 CC-E4G-FU5, FU6 30A Fuse E4G ET-F-1C-A EDE-MM-115 Electrical Penetration H39 ET-F-1C-A, C-F-1-Z CAH-E53/10-52 120 V AC Circuit Breaker E53 CB-F-1B-A EDE-MM-117 Electrical Penetration M41 ET-F-1C-A, C-F-1-Z CC-FISL-2123 Flow Indication Switch SD2 C-F-2-Z CC-FISL-2122 Flow Indication Switch SD1 C-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -6 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 CAH-FN-1E Containment Structure Cooler AC-1E Fan MAH-20505 A 310579 C-F-2-Z X X - M23 CAH-AC6-52 480 V AC Circuit Breaker AC6 CB-F-1A-A AC6-G2H AC6-G2H/1 AC6-GN9 AC6-HO7 AC6-HO7/1 G2H-H36 G2H-H36/1 HO7-JV5 H07-JV5/1 H36-H23/1 H36-SD5 JV5-JV6 JV5-M23 JV5-M23/1 JV6-M23 JV6-M23/1 F36-FB7/5 F36-G2H/3 F36-G2H/4 F36-G2H/5 G2H-HR2 G2H-HR2/1 310931 AC6a AC6d AC6b CBA-FN-19 CBA-FN-20 EDE-US-53 Primary Component Cooling Water CAH-FN-1A CAH-FN-1B CAH-FN-1D CAH-JV5-43 Safety Switch Speed Changer JV5 C-F-2-Z CAH-JV6-43 Safety Switch Speed Switch JV6 C-F-2-Z CAH-AC6-G,R Indicating Lights AC6 CB-F-1A-A CAH-CS-5664-2 Control Switch with Indication G2H CB-F-1A-A CAH-SS-5664 Selector Switch G2H CB-F-1A-A EDE-AF3-94-4 Bus Undervoltage Relay AF3 CB-F-1A-A CAH-GN9-R1 Time Delay Relay GN9 CB-F-1A-A CC-FISL-2223 Flow Indication Switch SD5 C-F-2-Z CAH-AC6-52H-1 Truck Operated Contact AC6 CB-F-1A-A CAH-AC6-AM Ammeter AC6 CB-F-1A-A CAH-AC6-CT Current Transformer (300/5) AC6 CB-F-1A-A CAH-AC6-ATR Transducer AC6 CB-F-1A-A CAH-ZL-5664-2 Outlet Damper Position Lights G2H CB-F-1A-A CAH-DP-316 Outlet Damper Position Switch M23 C-F-2-Z EDE-MM-83 Electrical Penetration HO7 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A CAH-AC-FU 15A Fuses AC6 CB-F-1A-A CAH-CS-5664-1 Control Switch with Indication F36 CB-F-3A-A EPS-HR2-PR1, RA, RMO, SR3 Emergency Power Sequencer Relays HR2 CB-F-1A-A CAH-FB7-K610A SI Actuating Auxiliary Relay FB7 CB-F-3A-A CAH-ZL-5664-1 Outlet Damper Position Lights F36 CB-F-3A-A CC-FISL-2223 Flow Indication Switch SD5 C-F-2-Z E45-E4E E4E-H36/4 H36-SD5/1 H36-SD6/1 E45-E4H E4H-H35 H35-SD3 301895 E45/11a E45/11C EDE-MCC-531 CC-E4E-FU39 30A Fuse E4E ET-F-1A-A EDE-MM-112 Electrical Penetration H36 ET-F-1A-A, C-F-2-Z CAH-E45/11-52 120 V AC Circuit Breaker E45 CB-F-1A-A CC-FISL-2224 Flow Indication Switch SD6 C-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -7 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 CAH-FN-1E (Continued) Containment Structure Cooler AC-1E Fan EDE-MM-111 Electrical Penetratio n H35 ET-F-1A-A, C-F-2-Z CC-FISL-2124 Flow Indication Switch SD3 C-F-2-Z CC-E4H-FU20 30A Fuse E4H CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -8 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 CAH-FN-1F Containment Structure Cooler AC-1F Fan MAH-20505 A 310578 C-F-2-Z X X - M24 CAH-AC7-52 480 V AC Circuit Breaker AC7 CB-F-1A-A AC7-G2H AC7-G2H/1 AC7-GN9 AC7-HO7 G2H-H07/1 G2H-H36/2 G2H-H36/3 HO7-M24 HO7-M24/1 H36-M24/1 H36-SD6 F36-FB7/6 F36-G2H/6 F36-G2H/7 F36-G2H/8 G2H-HR2/2 G2H-HR2/3 310931 AC7a AC7d AC7b CBA-FN-19 CBA-FN-20 EDE-US-53 Primary Component Cooling Water CAH-FN-1A CAH-FN-1B CAH-FN-1D CAH-CS-5665-2 Control Switch with Indication G2H CB-F-1A-A CAH-SS-5665 Selector Switch G2H CB-F-1A-A EDE-AF3-94-4 Bus Undervoltage Relay AF3 CB-F-1A-A CAH-GN9-R1 Time Delay Relay GN9 CB-F-1A-A CC-FISL-2224 Flow Indication Switch SD6 C-F-2-Z CAH-AC7-52H-1 Truck Operated Contact AC7 CB-F-1A-A CAH-AC7-G,R Indicating Lights AC7 CB-F-1A-A CAH-AC7-AM Ammeter AC7 CB-F-1A-A CAH-AC7-CT Current Transformer (300/5) AC7 CB-F-1A-A CAH-AC7-ATR Transducer AC7 CB-F-1A-A CAH-ZL-5665-2 Outlet Damper Position Lights G2H CB-F-1A-A CAH-DP-317 Outlet Damper Position Switch M24 C-F-2-Z EDE-MM-83 Electrical Penetration HO7 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A CAH-AC7-FU 15A Fuses AC7 CB-F-1A-A CAH-CS-5665-1 Control Switch with Indication F36 CB-F-3A-A EPS-HR2-PR1, RA, RMO, SR3 Emergency Power Sequencer Relays HR2 CB-F-1A-A CAH-FB7-K610A SI Actuating Auxiliary Relay FB7 CB-F-3A-A CAH-ZL-5665-1 Outlet Damper Position Lights F36 CB-F-3A-A CC-FISL-2224 Flow Indication Switch SD6 C-F-2-Z H36-SD6/1 E45-E4E E4E-H36/4 H36-SD5/1 E45-E4H E4H-H35 H35-SD3 310895 E45/11a E45/11c EDE-MCC-531 CC-E4E-FU39 30A Fuse E4E ET-F-1A-A EDE-MM-112 Electrical Penetration H36 ET-F-1A-A, C-F-2-Z CAH-E45/11-52 120 V AC Circuit Breaker E45 CB-F-1A-A CC-FISL-2223 Flow Indication Switch SD5 C-F-2-Z EDE-MM-111 Electrical Penetration H35 ET-F-1A-A, C-F-2-Z CC-FISL-2124 Flow Indication Switch SD3 C-F-2-Z CC-E4H-FU20 30A Fuse E4H CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.10-1 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CBA-DP-24A CBA-20303 A 310443 CB-F-2B-A X X X X V1A CBA-FY-5550A Pilot Solenoid V1A CB-F-2B-A Instrument Air CBA-DP-24F Note 4 Mechanical Room

"A" Outside Air

Damper FP-R1 Signal Actuating Output Relay G3C TB-F-2-Z 310926 BK4a BK4c FP-CP-558 Fire Protection Control Panel G4P TB-F-2-Z G4P-V1A G4P-V1B G4P-V1C G3C-G4P/5 CBA-TIC-5571 Temperature Indicating Control

(Pneumatic) - CB-F-2B-A CBA-FY-5550B Pilot Solenoid V1B CB-F-2B-A CBA-FY-5550C Pilot Solenoid V1C CB-F-2B-A 2 CBA-DP-24B CBA-20303 A 310443 CB-F-2B-A X X X X V1B CBA-FY-5550B Pilot Solenoid V1B CB-F-2B-A BK4a BK4c Instrument Air CBA-DP-24E Note 4 Mechanical Room

"A" Recirculating

Air Damper FP-CP-558 Fire Protection Control Panel G4P TB-F-2-Z G4P-V1A G4P-V1B G4P-V1C G3C-G4P/5 FP-R1 Signal Actuating Output Relay G3C TB-F-2-Z CBA-TIC-5571 Temperature Indicatin g Controller (Pneumatic) - CB-F-2B-A CBA-FY-5550A Pilot Solenoid V1A CB-F-2B-A CBA-FY-5550C Pilot Solenoid V1C CB-F-2B-A 3 CBA-DP-24C CBA-20303 A 310443 CB-F-2B-A X X X X V1C CBA-FY-5550C Pilot Solenoid V1C CB-F-2B-A 310926 BK4a BK4c Instrument Air CB-DP-24D Note 4 Mechanical Room

"A" Return Air

Damper FP-CP-558 Fire Protection Control Panel G4P TB-F-2-Z G4P-V1A G4P-V1B G4P-V1C G3C-G4P/5 FP-R1 Signal Actuating Output Relay G3c TB-F-2-Z CBA-TIC-5571 Temperature Indicatin g Controller (Pneumatic) - CB-F-2B-A CBA-FY-5550A Pilot Solenoid V1A CB-F-2B-A CBA-FY-5550B Pilot Solenoid V1C CB-F-2B-A 4 CBA-DP-24D Mechanical Room "B" Return Air

Damper CBA-20303 B 310443 604094 CB-F-2C-A X X - X - CBA-TIC-5572 Temperature Indicating Controller

(Pneumatic) - CB-F-2C-A - - - Instrument Air CBA-DP-24C Notes 1,2,4 5 CBA-DP-24E Mechanical Room "B" Recirculating

Air CBA-20303 B 310443 604094 CB-F-2C-A X X - X - CBA-TIC-5572 Temperature Indicatin g Controller (Pneumatic) - CB-F-2C-A - - - Instrument Air CBA-DP-24B Notes 1,2,4 6 CBA-DP-24F Mechanical Room "B" Outside Air

Damper CBA-20303 B 310443 604094 CB-F-2C-A X X - X - CBA-TIC-5572 Temperature Indicatin g Controller (Pneumatic) - CB-F-2C-A - - - Instrument Air CBA-DP-24A Notes 1,2,4

.Notes 1. Equipment is mechanical with no electrical requirements. 
2. Electrical conduit Plan Drawing 310443, listed only to show fire zone correlation reference to control building area covered by HVAC Drawing 604094 where CBA Dampers 24 D, E, and F are identified in plan.
3. Air is not required for support as damper fails open.
4. Process connections showing positioning of air operated dampers, DP-24A-F, by pneumatic temperature indicating controllers, CBA-TIC-5571 and 5572, are detailed on I&C Loop Diagrams 506159 and 506160.
5. Air is not required for support as damper fails closed.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.10-2 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 CBA-FN-19 CBA-20303 A 310443 CB-F-2B-A X X X - N28 CBA-BL6-52 460 V ac Circuit Breaker BL6 CB-F-1A-A BL6-HR2/1 BL6-N28/2 BL6a BL6c EDE-MCC-515 CBA-FN Control Building

Train "A" SWGR

Supply Fan CBA-CS-5552 Control Switch with Indication BL6 CB-F-1A-A DG-HR2-HR9X EPS Step Loading Relay HR2 CB-F-1A-A DG-HR2-RMO EPS Manual Override Relay HR2 CB-F-1A-A CBA-BL6-42 Motor Starter BL6 CB-F-1A-A CBA-BL6-42X Motor Starter Auxiliary Relay BL6 CB-F-1A-A CBA-BL6-49 Overload Relays BL6 CB-F-1A-A CBA-BL6-FU Fuse BL6 CB-F-1A-A 8 CBA-FN-20 CBA-20303 A 310443 CB-F-2B-A X X X - N30 CBA-BL7-52 460 V ac Circuit Breaker BL7 CB-F-1A-A BL7-HR2 BL7-N30/2 BL7a BL7c EDE-MCC-521 CBA-FN Control Building

Train "A" SWGR

Return Fan DG-HR2-RMO EPS Manual Override Relay HR2 CB-F-1A-A CBA-BL7-42 Motor Starter BL7 CB-F-1A-A CBA-BL7-49 Overload Relays BL7 CB-F-1A-A CBA-BL7-FU Fuse BL7 CB-F-1A-A CBA-CS-5554 Control Switch with Indication BL7 CB-F-1A-A DG-HR2-HR9X EPS Step Loading Relay HR2 CB-F-1A-A CBA-BL7-42X Motor Starter Auxiliary Relay BL7 CB-F-1A-A 9 CBA-FN-21A CBA-20303 A 310443 CB-F-2B-A X X X - N32 CBA-BL8-52 460 V ac Circuit Breaker BL8 CB-F-1A-A BL8a BL8c EDE-MCC-521 CBA-FN-21B Control Building

Battery Room

Exhaust Fan "A" CBA-CS-5556 Control Switch with Indication BL8 CB-F-1A-A BL8-N32 BL8-VV5/1 BL8-VV5 CBA-ZS-DP-21A Damper Position Switch VV5 CB-F-2B-A CBA-BL8-42 Motor Starter BL8 CB-F-1A-A CBA-ZL-5556 Damper 21A Indicatin g Lights BL8 CB-F-1A-A CBA-BL8-49 Overload Relays BL8 CB-F-1A-A CBA-DP-21A-20 Pilot Solenoid VV5 CB-F-2B-A CBA-BL8-FU Fuse BL8 CB-F-1A-A 10 CBA-DP-21A Battery Room Exhaust Fan "A"

Damper CBA-20303 A 310443 CB-F-2B-A X X X X VV5 CBA-BL8-52 460 V ac Circuit Breaker BL8 CB-F-1A-A BL8-VV5 BL8-VV5/1 BL8a BL8c EDE-MCC-521 CBA-DP-21B Note 3 CBA-BL8-FU Fuse BL8 CB-F-1A-A CBA-CS-5556 Control Switch with Indication BL8 CB-F-1A-A CBA-DP-21A-20 Pilot Solenoid VV5 CB-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.10-3 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 CBA-FN-21B Control Building Battery Room

Exhaust Fan "B" CBA-20303 B 310443 CB-F-2C-A X X X - N33 CBA-BL5-52 460 V ac Circuit Breaker BL5 CB-F-1B-A BL5-N33 BL5-VV4/1 BL5-VV4 310926 BL5a BL5c EDE-MCC-621 CBA-FN-21A CBA-CS-5557 Control Switch with Indication BL5 CB-F-1B-A CBA-ZS-DP-21B Damper Position Switch VV4 CB-F-2C-A CBA-BL5-42 Motor Starter BL5 CB-F-1B-A CBA-ZL-5557 Damper 21B Indicatin g Lights BL5 CB-F-1B-A CBA-BL5-49 Overload Relays BL5 CB-F-1B-A CBA-DP-21B-20 Pilot Solenoid VV4 CB-F-2C-A CBA-BL5-FU Fuse BL5 CB-F-1B-A 12 CBA-DP-21B CBA-20303 B 310443 CB-F-2C-A X X X X VV4 CBA-BL5-52 460 V ac Circuit Breaker BL5 CB-F-1B-A BL5-VV4 BL5-VV4/1 310926 BL5a BL5c EDE-MCC-621 CBA-DP-21A Note 3 Battery Room Exhaust Fan "B"

Damper CBA-BL5-FU Fuse BL5 CB-F-1B-A CBA-CS-5557 Control Switch BL5 CB-F-1B-A CBA-DP-21B-20 Pilot Solenoid VV4 CB-F-2C-A 13 CBA-FN-32 CBA-20303 B 310443 CB-F-2C-A X X X - NH3 CBA-BL3-52 460 V ac Circuit Breaker BL3 CB-F-1B-A BL3-HR4 BL3-NH3 BL3a BL3c EDE-MCC-621 CBA-FN-19 Control Building

Train "B" SWGR

Supply Fan CBA-CS-5559 Control Switch with Indication BL3 CB-F-1B-A DG-HR4-HR9X EPS Step Loading Relay HR4 CB-F-1B-A DG-HR4-RMO EPS Manual Override Relay HR4 CB-F-1B-A CBA-BL3-42 Motor Starter BL3 CB-F-1B-A CBA-BL3-42X Motor Starter Auxiliary Relay BL3 CB-F-1B-A CBA-BL3-49 Overload Relays BL3 CB-F-1B-A CBA-BL3-FU Fuse BL3 CB-F-1B-A 14 CBA-FN-33 CBA-20303 B 310443 CB-F-2C-A X X X - NH5 CBA-BL4-52 460 V ac Circuit Breaker BL4 CB-F-1B-A BL4-HR4 BL4-NH5 BL4a BL4c EDE-MCC-621 CBA-FN-20 Control Building

Train "B" SWGR

Return Fan CBA-CS-5561 Control Switch with Indication BL4 CB-F-1B-A DG-HR4-HR9X EPS Step Loading Relay HR4 CB-F-1B-A CBA-BL4-42 Motor Starter BL4 CB-F-1B-A CBA-BL4-49 Overload Relays BL4 CB-F-1B-A CBA-BL4-FU Fuse BL4 CB-F-1B-A DG-HR4-RMO EPS Manual Override Relay HR4 CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.10-4 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 CBA-CP-177 CBA-20303 CBA-20304 A 310444 CB-F-3B-A X X X - GU1 CBA-AC4-52 460V ac Circuit Breaker AC4 CB-F-1A-A EDE-US-52 Instrument Air CBA-CP-178 Control Room A/C

Unit A Control

Panel CBA-FN-14A AC Unit Fan N21 CB-F-3B-A CBA-FN-211A Condenser Exhaust Fan NN1 DG-F-3A-Z 310926 AC4a AC4b AC4e AC4f CBA-PDS-21206A1/A2 FN-211A Diff Pressure PV1 DG-F-3A-Z X CBA-DP-26A Damper UG1 CB-F-3B-A CBA-CS-5300-1 FN-14A Control Switch F36 CB-F-3A-A AC4-GU1 AC4-HR2 GU1-N21 GU1-N21/1 GU1-NN1 GU1-NN1/1 GU1-PV1 GU1-UG1 F38-GU1 F38-GU1/1 CBA-CS-21222A FN-211A Control Switch F36 CB-F-3A-A CBA-AC4-FU Breaker Fuse AC4 CB-F-1A-A CBA-AC4-52H Breaker Truck Switch AC4 CB-F-1A-A CBA-CS-5300-3 Breaker Control

Switch AC3 CB-F-1A-A DG-HR2-RMO, PR1, LR1 Sequencer Relays HR2 CB-F-1A-A GU1-HR2 DG-HR9 - SR5 Sequencer Relay HR9 CB-F-1A-A EDE-AC3-94-3 Undervoltage Relay AC3 CB-F-1A-A CBA-E-230A Chiller HW4 DG-F-3A-Z AC4ma AC4me CBA-PDS-21202A Evaporator Diff Pressure PK8 DG-F-3A-Z CBA-ZL-21221A Chiller Indication F36 CB-F-3A-A GU1-HW4 GU1-HW4/1 GU1-HW4/2 GU1-HW4/3 GU1-HW4/4 B6B-HW4 B6C-HW4 HW4-PK8 HW4-PK9 CBA-TCV-21200A Chilled Water TCV LV1 CB-F-3B-A AC4na AC4nc CBA-TC-21200A Chilled Water Temp

Cont. T0L CB-F-3A-A GU1-LV1 LV1-T0L CBA-B6B-52 460V ac Circuit Breaker B6B CB-F-1A-A B6B-NM5 B6Ba B6Bc B6Ca B6Cc CBA-B6B-FU Fuse B6B CB-F-1A-A CBA-SS-21220A Selector Switch HW4 CB-F-1A-A CBA-6K13 Signal Relay HW4 CB-F-1A-A CBA-B6B-42 Motor Starter B6B CB-F-1A-A CBA-B6B-49 Overload Relays B6B CB-F-1A-A CBA-B6C-52 460V ac Circuit Breaker B6C CB-F-1A-A B6C-NM6 CBA-B6C-FU Fuse B6C CB-F-1A-A CBA-B6C-42 Motor Starter B6C CB-F-1A-A CBA-B6C-49 Overload Relays B6C CB-F-1A-A CBA-P-434A Chiller Circ. Water Pump NM5 DG-F-3A-Z CBA-P-435A Chiller Circ. Water Pump NM6 DG-F-3A-Z

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.10-5 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 16 CBA-CP-178 CBA-20303 CBA-20304 B 310444 CB-F-3B-A X X X - GU2 CBA-AE4-52 460V ac Circuit

Breaker AE4 CB-F-1B-A EDE-US-62 Instrument Air CBA-CP-177 Control Room A/C

Unit B Control

Panel CBA-FN-14B AC Unit Fan N22 CB-F-3B-A 310926 AE4a AE4b AE4e AE4f CBA-FN-211B Condenser Exhaust Fan NN3 DG-F-3B-Z CBA-PDS-21206B1/B2 FN-211B Diff Pressure PV0 DG-F-3B-Z X CBA-DP-26B Damper UG2 CB-F-3B-A CBA-CS-5301-1 FN-14B Control Switch F37 CB-F-3A-A AE4-GU2 AE4-HR4 GU2-N22 GU2-N22/1 GU2-NN3 GU2-NN3/1 GU2-PV0 GU2-UG2 F37-GU2 F37-GU2/1 CBA-CS-21222B FN-211B Control Switch F37 CB-F-3A-A CBA-AE4-FU Breaker Fuse AE4 CB-F-1B-A CBA-AE4-52H Breaker Truck Switch AE4 CB-F-1B-A CBA-CS-5301-3 Breaker Control

Switch AE3 CB-F-1B-A DG-HR4-RMO,PR1,LR1 Sequencer Relays HR4 CB-F-1B-A GU2-HR4 DG-HR0 - SR5 Sequencer Relay HR0 CB-F-1B-A EDE-AE3-94-3 Undervoltage Relay AE3 CB-F-1B-A CBA-E-230B Chiller HW5 DG-F-3B-Z AE4ma AE4me CBA-PDS-21202B Evaporator Diff

Pressure PL0 DG-F-3B-Z CBA-ZL-21221B Chiller Indication F37 CB-F-3A-A GU2-HW5 GU2-HW5/1 GU2-HW5/2 GU2-HW5/3 GU2-HW5/4 B6H-HW5 B6I-HW5 HW5-PL0 HW5-PL5 CBA-TCV-21200B Chilled Water TCV LV2 CB-F-3B-A GU2-LV2 LV2-T0N AE4na AE4nc CBA-TC-21200B Chilled Water Temp

Cont. T0N CB-F-3A-A CBA-B6H-52 460V ac Circuit

Breaker B6H CB-F-1B-A B6H-NM7 B6Ha B6Hc B6Ia B6Ic CBA-B6H-FU Fuse B6H CB-F-1B-A CBA-SS-21220B Selector Switch HW5 CB-F-1B-A CBA-6K13 Signal Relay HW5 CB-F-1B-A CBA-B6H-42 Motor Starter B6H CB-F-1B-A CBA-B6H-49 Overload Relays B6H CB-F-1B-A CBA-B6I-52 460V ac Circuit Breaker B6I CB-F-1B-A B6I-NM8 CBA-B6I-FU Fuse B6I CB-F-1B-A CBA-B6I-42 Motor Starter B6I CB-F-1B-A CBA-B6I-49 Overload Relays B6I CB-F-1B-A CBA-P-434B Chiller Circ. Water Pump NM7 DG-F-3B-Z CBA-P-435B Chiller Circ. Water Pump NM8 DG-F-3B-Z 17 CBA-DP-52 CBA-20304 A 310444 CB-F-3B-A X X X X UH2 CBA-CS-5302 Control Switch F36 CB-F-3A-A Note 5 Control Building

Recirculation Air

Damper CBA-PDSH-5305 Pressure Differential Switch P64 CB-F-3B-A E16/29a E16/29c E16/29e E16/29d E16/29g E16/29h CBA-PDSH-5306 Pressure Differential Switch P65 CB-F-3B-A GN8-P64 GN8-UH2 F36-GN8 GN8-P65 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.11 -1 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 DAH-FN-25A DG-1A Room Supply Air Fan DAH-20624 A 310525 DG-F-3A-Z X X X - N37 DAH-B01-52 460 V AC Circuit Breaker B01 CB-F-1A-A B01-N37/1 B01-G29 B01-J1E B01-GN9 310928 B01a B01c B01d EDE-MCC-521 EDE-PP-11E DAH-FN-25B DAH-CS-5529 Control Switch with Fan Indicating Lights B01 CB-F-1A-A DAH-FISH-5529 Flow Switch S40 DG-F-3A-Z DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DAH-ED1-R2 Auxiliary Relay ED1 CB-F-1A-A DG-G29-HSR DG-1A High Speed Relay G29 DG-F-2A-A DAH-B01-42 Motor Starter B01 CB-F-1A-A DAH-B01-42X Motor Starter Auxiliary Relay B01 CB-F-1A-A DAH-B01-49 Overload Relays B01 CB-F-1A-A DAH-B01-FU Fuse B01 CB-F-1A-A DAH-EDI-RI Control Circuit Power Monitor Auxiliary Relay EDI CB-F-1A-A DAH-GN9-RS EPS Permissive Auxiliary Relay GN9 CB-F-1A-A DAH-GN9-RD Damper Position Auxiliary Relay GN9 CB-F-1A-A DAH-E3E/7-52 120 V AC Circuit Breaker E3E CB-F-1A-A J1E-T3P (Non CASP) E3E-J1E E3E/7a E3E/7b EDE-MCC-515 EDE-PP-E3E DAH-TB-5529-1 Temperature Bistable J1E DG-F-2A-A DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DAH-TE-5529-1 Temperature Element T3P DG-F-2A-A DAH-TT-5529-1 Temperature Transmitter J1E DG-F-2A-A DAH-CP-295 DG-A Room Air Handling Fans and Damper Control Panel J1E DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.11 -2 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 DAH-DP-16A DG-1A Room Return Air Damper DAH-20624 A 310524 DG-F-2A-A X X X X UF9 DAH-ED1-R2 (B01 & B03) Auxiliary Relays ED1 CB-F-1A-A B01-UF9/1 B01-J1E/1 EIS-GN9 EDI-GN9 B03-UF9 B01-HR2 EIS/6a EIS/6c EDE-MCC-521 EDE-PP-11E DAH-DP-16B Note 1 DAH-DP-16A-20 Pilot Solenoi d UF9 DG-F-2A-A DAH-TB-5529-1 Temperature Bistable J1E DG-F-2A-A DAH-ZS-DP-16A Damper 16A Position Switch UF9 DG-F-2A-A DG-HR2-PR1 EPS Permissive Auxiliary Relay HR2 CB-F-1A-A DG-HR2-HR8 EPS Permissive Auxiliary Relay HR2 CB-F-1A-A DG-HR2-SR1 EPS Permissive Auxiliary Relay HR2 CB-F-1A-A DAH-GN9-RS EPS Permissive Auxiliary Relay GN9 CB-F-1A-A DAH-GN9-RD Damper Position Auxiliary Relay GN9 CB-F-1A-A DAH-E1S/6-52 120 V AC Circuit Breaker E1S CB-F-1A-A DAH-ZL-5529-4 Damper Position Indicating Lights B03 CB-F-1A-A DAH-E3E/7-52 120 V AC Circuit Breaker E3E CB-F-1A-A J1E-T3P (Non CASP) E3E-J1E E3E/7a E3E/7b EDE-MCC-515 EDE-PP-E3E DAH-TB-5529-1 Temperature Bistable J1E DG-F-2A-A DAH-TE-5529-1 Temperature Element T3P DG-F-2A-A DAH-TT-5529-1 Temperature Transmitter J1E DG-F-2A-A DAH-CP-295 DG-A Room Air Handling Fans And Damper Control Panel J1E DG-F-2A-A Notes: 1. Air is not required for support as damper is open

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.11 -3 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 DAH-FN-25B DG-1B Room Supply Air Fan DAH-20624 B 310525 DG-F-3B-Z X X X - N38 DAH-B02-52 460 V AC Circuit Breaker B02 CB-F-1B-A B02-N38/1 B02-G30 B02-S41 B02-J1F B02-GN0 EE3-E3D 310928 B02a B02c B02d EDE-MCC-621 EDE-PP-11F DAH-FN-25A DAH-CS-5530 Control Switch with Fan Indicating Lights B02 CB-F-1B-A DAH-FISH-5530 Flow Switch S41 DG-F-3B-Z DAH-J1F-RTB Temperature Bistable Auxiliary Relay J1F DG-F-2B-A DAH-EE3-R2 Auxiliary Relay EE3 CB-F-1B-A DAH-B02-FU Fuse B02 CB-F-1B-A DG-G30-HSR DG-1B High Speed Relay G30 DG-F-2B-A DAH-B02-42 Motor Starter B02 CB-F-1B-A DAH-B02-42X Motor Starter Auxiliary Relay B02 CB-F-1B-A DAH-B02-49 Overload Relays B02 CB-F-1B-A DAH-E3D-R1 Control Circuit Power Monitor Auxiliary Relay E3D CB-F-1B-A DAH-GN0-RS EPS Permissive Auxiliary Relay GN0 CB-F-1B-A DAH-GN0-RD Damper Position Auxiliary Relay GN0 CB-F-1B-A DAH-E3F/7-52 120 V AC Circuit Breaker E3F CB-F-1B-A J1F-T3Q (Non CASP) E3F-J1F E3F/7a E3F/7b EDE-MCC-615 EDE-PP-E3F DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A DAH-J1F-RTB Temperature Bistable Auxiliary Relay J1F DG-F-2B-A DAH-TE-5530-1 Temperature Element T3Q DG-F-2B-A DAH-TT-5530-1 Temperature Transmitter J1F DG-F-2B-A DAH-CP-296 DG-B Room Air Handling Fans and Damper Control Panel J1F DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.11 -4 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 DAH-DP-16B DG-1B Room Return Air Damper DAH-20624 B 310524 DG-F-2B-A X X X X UF0 DAH-EE3-R2 (B02 & B04) Auxiliary Relay EE3 CB-F-1B-A B02-UF0/1 ED0-J1F B02-EDO EE3-GN0/2 EIT-GN0 B01-HR4 B04-UF0 EIT/6a EIT/6c EDE-MCC-621 EDE-PP-11F DAH-DP-16A Note 1 DAH-DP-16B-20 Pilot Solenoid UF0 DG-F-2B-A DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A DAH-ZS-DP-16B Damper 16B Position Switch UF0 DG-F-2B-A DG-HR4-HRB EPS Permissive Auxiliary Relay HR4 CB-F-1B-A DG-HR4-PR1 EPS Permissive Auxiliary Relay HR4 CB-F-1B-A DG-HR4-SR1 EPS Permissive Auxiliary Relay HR4 CB-F-1B-A DAH-GN0-RS EPS Permissive Auxiliary Relay GN0 CB-F-1B-A DAH-GN0-RD Damper Position Auxiliary Relay GN0 CB-F-1B-A DAH-E1T/6-52 120 V AC Circuit Breaker E1T CB-F-1B-A DAH-ZL-5530-4 Damper Position Indicating Lights B04 CB-F-1B-A DAH-E3F/7-52 120 V AC Circuit Breaker E3F CB-F-1B-A J1F-T3Q (Non CASP) E3F-J1F E3F/7a E3F/7b EDE-MCC-615 EDE-PP-E3F DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A DAH-TE-5530-1 Temperature Element T3Q DG-F-2B-A DAH-TT-5530-1 Temperature Transmitter J1F DG-F-2B-A DAH-CP-296 DG-B Room Air Handling Fans and Damper Control Panel J1F DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.11 -5 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 DAH-FN-26A DG-1A Room Return Air Fan DAH-20624 A 310525 DG-F-2A-A X X X - N39 DAH-B03-52 460 V AC Circuit Breaker B03 CB-F-1A-A B03-N39/1 B03-J1E G29-J1E B03-GN9 310928 B03a B03c B03d EDE-MCC-521 EDE-PP-11E DAH-FN-26B DAH-B03-42 Motor Starter B03 CB-F-1A-A DAH-B03-42X Motor Starter Auxiliary Relays B03 CB-F-1A-A DAH-B03-49 Overload Relays B03 CB-F-1A-A DAH-B03-FU Fuse B03 CB-F-1A-A DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DG-G29-HSR DG-1A High Speed Relay G29 DG-F-2A-A DAH-CS-6058 Control Switch with Indicating Lights B03 CB-F-1A-A DAH-ED1-R2 Auxiliary Relay ED1 CB-F-1A-A DAH-ED1-R1 Control Circuit Power Monitor Auxiliary Relay ED1 CB-F-1A-A DAH-GN9-RS EPS Permissive Auxiliary Relay GN9 CB-F-1A-A DAH-GN9-RD Damper Position Auxiliary Relay GN9 CB-F-1A-A DAH-E3E/7-52 120 V DC Circuit Breaker E3E CB-F-1A-A J1E-T3P (Non CASP) E3E-J1E E3E/7a E3E/7b EDE-MCC-515 EDE-PP-E3E DAH-TB-5229-1 Temperature Bistable J1E DG-F-2A-A DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DAH-TE-5529-1 Temperature Element T3P DG-F-2A-A DAH-TT-5529-1 Temperature Transmitter J1E DG-F-2A-A DAH-CP-295 DG-A Room Air Handling Fans and Damper Control Panel J1E DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.11 -6 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 DAH-FN-26B DG-1B Room Return Air Fan DAH-20624 B 310525 DG-F-2B-A X X X - N40 DAH-B04-52 460 V AC Circuit Breaker B04 CB-F-1B-A B04-N40/1 B04-J1F G30-J1F B04-GN0 B04a B04c B04d EDE-MCC-621 EDE-PP-11F DAH-FN-26A DAH-B04-42 Motor Starter B04 CB-F-1B-A DAH-B04-42X Motor Starter Auxiliary Relays B04 CB-F-1B-A DAH-B04-49 Overload Relays B04 CB-F-1B-A DAH-B04-FU Fuse B04 CB-F-1B-A DAH-J1F-RTB Temperature Bistable Auxiliary Relay J1F DG-F-2B-A DG-G30-HSR DG-1B High Speed Relay G30 DG-F-2B-A DAH-CS-6059 Control Switch with Indicating Lights B04 CB-F-1B-A DAH-EE3-R2 Auxiliary Relay EE3 CB-F-1B-A DAH-EE3-R1 Control Circuit Power Monitor Auxiliary Relay EE3 CB-F-1B-A DAH-GN0-RS EPS Permissive Auxiliary Relay GN0 CB-F-1B-A DAH-GN0-RD Damper Position Auxiliary Relay GNO CB-F-1B-A DAH-E3F/7-52 120 V AC Circuit Breaker E3F CB-F-1B-A J1F-T3Q (Non CASP) E3F-J1F E3F/7a E3F/7b EDE-MCC-615 EDE-PP-E3F DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A DAH-J1F-RTB Temperature Bistable Auxiliary Relay J1F DG-F-2B-A DAH-TE-5530-1 Temperature Element T3Q DG-F-2B-A DAH-TT-5530-1 Temperature Transmitter J1F DG-F-2B-A DAH-CP-296 DG-B Room Air Handling Fans and Damper Control Panel J1F DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.12-1 FUNCTION: CONTAINMENT ENCLOSURE AIR HANDLING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EAH-FN-5A MAH-20495 A 310766 CE-F-1-Z X X X - M80 EAH-AF5-52 480 V AC Circuit Breaker AF5 CB-F-1A-A EAH-FN-5B Containment

Enclosure Cooler

AC-2A Fan EAH-AF5-G, R Indicating Lights AF5 CB-F-1A-A EAH-CS-5767-2 Control Switch with Indication G2H CB-F-1A-A 310932 AF5a AF5e AF5b AF5g AF5f EAH-FN-31A EDE-US-52 Primary Component Cooling Water EAH-SS-5767 Selector Switch G2H CB-F-1A-A EAH-ZL-5767-2 Outlet Damper Position Lights G2H CB-F-1A-A AF5-G2H AF5-G2H/1 AF5/M80 AF5-YC3 L41-YC3 F36-G2H F36-G2H/1 AF5-HR2 AF5-E3C EAH-ZS-DP-3A Damper Position Switch L41 CE-F-1-Z EAH-AF5-AM Ammeter AF5 CB-F-1A-A EAH-AF5-CT Current Transformer (200/5) AF5 CB-F-1A-A EDE-AC3-94-3 Bus Undervoltage Relay AC3 CB-F-1A-A EAH-AF5-52H-1 Truck-Operated Contact AF5 CB-F-1A-A EDE-TBX-YC3 Terminal Box YC3 CE-F-1-Z EAH-AF5-FU Fuses AF5 CB-F-1A-A EAH-CS-5767-1 Control Switch with Indication F36 CB-F-3A-A DG-HR2-SR1 EPS Permit Auxiliary Relay HR2 CB-F-1A-A DG-HR2-PR1 EPS Permit Auxiliary Relay HR2 CB-F-1A-A DG-HR2-RMO EPS Permit Auxiliary Relay Pressure Switch HR2 CB-F-1A-A EAH-ZL-5767-1 Outlet Damper Position Lights F36 CB-F-3A-A EAH-E3C-R1 Auxiliary Relay E3C CB-F-1A-A

. Notes 1. Equipment is mechanical with no electrical requirements. 
2. Air and electrical power are not required for support as damper fails closed.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.12-2 FUNCTION: CONTAINMENT ENCLOSURE AIR HANDLING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 EAH-FN-5B MAH-20495 B 310766 CE-F-1-Z X X X - M81 EAH-AF9-52 480 V AC Circuit Breaker AF9 CB-F-1B-A EAH-FN-5A Containment

Enclosure Cooler

AC-2B Fan EAH-AF9-G, R Indicating Lights AF9 CB-F-1B-A EAH-CS-5768-2 Control Switch with Indication G2K CB-F-1B-A AF9a AF9e AF9b AF9g AF9f EAH-FN-31B EDE-US-62 Primary Component Cooling Water EAH-SS-5768 Selector Switch G2K CB-F-1B-A EAH-ZL-5768-2 Outlet Damper Position Lights G2K CB-F-1B-A AF9-G2K AF9-G2K/1 AF9/M81 AF9-YB3 L42-YB3 F37-G2K F37-G2K/1 AF9-HR4 AF9-G2K/2 AF9-E3D EAH-ZS-DP-3B Damper Position Switch L42 CE-F-1-Z EAH-AF9-AM Ammeter AF9 CB-F-1B-A EAH-AF9-CT Current Transformer (200/5) AF9 CB-F-1B-A EDE-AE3-94-3 Bus Undervoltage Relay AE3 CB-F-1B-A EAH-AF9-52H-1 Truck-Operated Contact AF9 CB-F-1B-A EDE-TBX-YB3 Terminal Box YB3 CE-F-1-Z EAH-AF9-FU Fuses AF9 CB-F-1B-A EAH-CS-5768-1 Control Switch with Indication F37 CB-F-3A-A DG-HR4-SR1 EPS Permit Auxiliary Relay HR4 CB-F-1B-A DG-HR4-PR1 EPS Permit Auxiliary Relay HR4 CB-F-1B-A DG-HR4-RMO EPS Permit Auxiliary Relay Pressure Switch HR4 CB-F-1B-A EAH-ZL-5768-1 Outlet Damper Position Lights F37 CB-F-3A-A EAH-AE3-R1 Auxiliary Relay AE3 CB-F-1B-A EAH-E3D-R2 Auxiliary Relay E3D CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.12-3 FUNCTION: CONTAINMENT ENCLOSURE AIR HANDLING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 EAH-FN-31A MAH-20495 A 310765 CE-F-1-Z - X X - ND5 EAH-BB2-52 460 V Ac Circuit Breaker BB2 CB-F-1A-A EDE-MCC-512 EAH-FN-31B Containment

Enclosure Return

Fan "A" EAH-BB2-FU Fuses BB2 CB-F-1A-A 310932 BB2a BB2c EAH-CS-5769-2 Control Switch BB2 CB-F-1A-A EAH-BB2-G, R Indication Lights BB2 CB-F-1A-A BB2-ND5 BB2-VQ2 BB2-F36 BB2-F36/1 AF5-BB2 BB2-HR2 EAH-SS-5769 Selector Switch BB2 CB-F-1A-A EAH-BB2-42 Motor Starter BB2 CB-F-1A-A EAH-BB2-42X Motor Starter Auxiliary Relay BB2 CB-F-1A-A EAH-BB2-49 Overload Relays BB2 CB-F-1A-A EAH-ZS-DP-25A Damper Position Switch VQ2 CE-F-1-Z EAH-CS-5769-1 Control Switch with Indication F36 CB-F-3A-A EAH-ZL-5769-1 Inlet Damper Position Lights F36 CB-F-3A-A DG-HR2-RMO EPS Permit Auxiliary Relay HR2 CB-F-1A-A EAH-AF5-52 480 V AC Circuit Breaker Auxiliary

Switch AF5 CB-F-1A-A 4 EAH-FN-31B MAH-20495 B 310765 CE-F-1-Z - X X - NJ7 EAH-BC1-52 460 V Ac Circuit Breaker BC1 CB-F-1B-A BC1a BC1c EDE-MCC-612 EAH-FN-31A EAH-BC1-FU Fuses BC1 CB-F-1B-A Containment

Enclosure Return

Fan "B" EAH-CS-5770-2 Control Switch BC1 CB-F-1B-A EAH-BC1-G, R Indication Lights BC1 CB-F-1B-A BC1-NJ7 BC1-VQ3 BC1-F37 BC1-F37/1 AF9-BC1 BC1-HR4 EAH-SS-5770 Selector Switch BC1 CB-F-1B-A EAH-BC1-42 Motor Starter BC1 CB-F-1B-A EAH-BC1-42X Motor Starter Auxiliary Relay BC1 CB-F-1B-A EAH-BC1-49 Overload Relays BC1 CB-F-1B-A EAH-ZS-DP-25B Damper Position Switch VQ3 CE-F-1-Z EAH-CS-5770-1 Control Switch with Indication F37 CB-F-3A-A EAH-ZL-5770-1 Inlet Damper Position Lights F37 CB-F-3A-A DG-HR4-RMO EPS Permit Auxiliary Relay HR4 CB-F-1B-A EAH-AF9-52 480 V AC Circuit Breaker Auxiliary

Switch AF9 CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.12-4 FUNCTION: CONTAINMENT ENCLOSURE AIR HANDLING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 EAH-DP-3A Containment Enclosure Cooler

AC-2A Damper MAH-20495 A 310766 CE-F-1-Z X X - - L41 - - - - - - -

- EAH-DP-3B Note 1 6 EAH-DP-3B Containment Enclosure Cooler 

AC-2B Damper MAH-20495 B 310766 CE-F-1-Z X X - - L42 - - - - - - -

- EAH-DP-3A Note 1 7 EAH-FN-174A MAH-20503 A 310586 MS-F-4A-Z X X X - M4T EAH-B8C-52 460 V AC Circuit Breaker B8C CB-F-1A-A B8C-M4T B8C-S5G B8Ca B8Cc EAH-FN-174B MS & FWPC 

Analyzer Room

Supply Fan EAH-B8C-FU Fuse B8C CB-F-1A-A CBA-FN-19

CBA-FN-20 EDE-MCC-515 EAH-CS-5136 Control Switch with Indication B8C CB-F-1A-A EAH-B8C-42 Motor Starter B8C CB-F-1A-A EAH-B8C-49 Overload Relays B8C CB-F-1A-A EAH-TSH-5136 Temperature Switch S5G MS-F-4A-Z 8 EAH-FN-174B MAH-20503 B 310586 MS-F-4A-Z X X X - M4U EAH-B8E-52 460 V AC Circuit Breaker B8E CB-F-1B-A B8E-M4U B8E-S5H 310932 B8Ea B8Ec EAH-FN-174A MS & FWPC

Analyzer Room

Supply Fan EAH-B8E-FU Starter B8E CB-F-1B-A EDE-MCC-615 CBA-FN-32

CBA-FN-33 EAH-B8E-49 Overload Relays B8E CB-F-1B-A EAH-CS-5763 Control Switch with Indication B8E CB-F-1B-A EAH-TSH-5763 Temperature Switch S5H MS-F-4A-Z EAH-B8E-FU Fuse B8E CB-F-1B-A 9 MAH-20495 PAH-CS-5370 Control Switch F36 CB-F-3A-A Note 2 PAH-DP-35A

PAH-DP-36A CE Outboard

Isolation Dampers A A 310766 310765 PAB-F-2A-Z PAB-F-2C-Z X X X X X X X X VN8 VN0 PAH-ZS-DP-35A Position Switch VN8 PAB-F-2A-Z F36-VN8 F36-VN0 310930 E42/8a E42/8c E42/8d PAH-ZS-DP-36A Position Switch VN0 PAB-F-2C-Z PAH-FY-DP-35A Solenoid Valve VN8 PAB-F-2A-Z PAH-FY-DP-36A Solenoid Valve VN0 PAB-F-2C-Z 10 MAH-20495 PAH-CS-5371 PAH-CS-5371 F37 CB-F-3A-A Note 2 PAH-DP-35B

PAH-DP-36B CE Inboard

Isolation Dampers B B 310766 310765 CE-F-1-Z

CE-F-1-Z X X X X X X X X VN9 VP1 PAH-ZS-DP-35B PAH-ZS-DP-35B VN9 CE-F-1-Z F37-VP1 F37-VN9 310930 E50/8a E50/8c PAH-ZS-DP-36B PAH-ZS-DP-36B VP1 CE-F-1-Z PAH-FY-DP-35B PAH-FY-DP-35B VN9 CE-F-1-Z PAH-FY-DP-36B PAH-FY-DP-36B VP1 CE-F-1-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.13-1 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EPA-FN-47A MAH-20503 A 310708 EFP-F-1-A X X X - NL8 EPA-BB7-52 460 V ac Circuit Breaker BB7 CB-F-1A-A EPA-FN-47B Emergency

Feedwater

Pumphouse Intake

Fan EPA-BB7-FU Fuse BB7 CB-F-1A-A BB7-NL8 BB7-UH3 BB7-VV6 CBA-FN-19

CBA-FN-20 EDE-MCC-512 EPA-CS-5430-2 Control Switch BB7 CB-F-1A-A 310922 BB7a BB7c BB7d EPA-ZL-5430-4 Fan Indicating Lights BB7 CB-F-1A-A EPA-SS-5430 Selector Switch BB7 CB-F-1A-A EPA-EC8-RBB7 Damper Auxiliary Relay EC8 CB-F-1A-A EPA-ZS-DP-373 Damper Position Switch UH3 EFP-F-1-A EPA-ZS-DP-371 Damper Position Switch VV6 EFP-F-1-A EPA-ZL-5430-5 Damper DP-373 Position Lights BB7 CB-F-1A-A EPA-ZL-5430-6 Damper DP-371 Position Lights BB7 CB-F-1A-A EPA-BB7-42 Motor Starter BB7 CB-F-1A-A EPA-BB7-49 Overload Relays BB7 CB-F-1A-A EPA-ZL-5430-1 Fan Indicating Lights F36 CB-F-3A-A EPA-ZL-5430-2 Damper DP-373 Position Lights F36 CB-F-3A-A F36-TU9 BB7-F36 BB7-F36/1 BB7-F36/2 EPA-ZL-5430-3 Damper DP-371 Position Lights F36 CB-F-3A-A EPA-CS-5430-1 Control Switch F36 CB-F-3A-A EPA-TSH-5430 Temperature Switch TU9 EFP-F-1-A EPA-DP-373-20 Pilot Solenoid UH3 EFP-F-1-A 2 EPA-DP-373 MAH-20503 A 310708 EFP-F-1-A X X X X UH3 EPA-DP-373-20 Fuse EC8 CB-F-1A-A BB7-UH3 EPA-DP-374 Note 1 EPA-BB7-FU Auxiliary Relay BB7 CB-F-1A-A BB7a BB7c BB7d Emergency

Feedwater

Pumphouse Exhaust

Damper EPA-EC8-RBB7 Pilot Solenoid UH3 EFP-F-1-A CBA-FN-19

CBA-FN-20 EDE-MCC-512

Notes

1. Air is not required for support as damper fails open.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.13-2 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 EPA-FN-47B MAH-20503 B 310708 EFP-F-1-A X X X - NL9 EPA-BC7-52 460 V ac Circuit Breaker BC7 CB-F-1B-A EPA-FN-47A Emergency

Feedwater

Pumphouse Intake

Fan EPA-BC7-FU Fuses BC7 CB-F-1B-A BC7-NL9 BC7-UH4 BC7-VV7 BC7a BC7c BC7d CBA-FN-32

CBA-FN-33 EDE-MCC-612 EPA-ZL-5431-4 Fan Indicating Lights BC7 CB-F-1B-A EPA-SS-5431 Selector Switch BC7 CB-F-1B-A EPA-EDO-RBC7 Damper Auxiliary Relay EDO CB-F-1B-A EPA-ZS-DP-374 Damper Position Switch UH4 EFP-F-1-A EPA-ZS-DP-372 Damper Position Switch VV7 EFP-F-1-A EPA-BC7-42 Motor Starter BC7 CB-F-1B-A EPA-BC7-49 Overload Relays BC7 CB-F-1B-A EPA-ZL-5431-5 Damper DP-374 Position Lights BC7 CB-F-1B-A EPA-EDO-R1 Auxiliary Relay EDOCB-F-1B-A EPA-ZL-5431-6 Damper DP-372 Position Lights BC7 CB-F-1B-A EPA-CS-5431-2 Control Switch BC7 CB-F-1B-A F37-TUO BC7-F37 BC7-F37/1 BC7-F37/2 EPA-BC7-CPT Control Power Transformer BC7 CB-F-1B-A EPA-ZL-5431-1 Fan Indicating Lights F37 CB-F-3A-A EPA-ZL-5431-2 Damper DP-374 Indicating Lights F37 CB-F-3A-A EPA-ZL-5431-3 Damper DP-372 Indicating Lights F37 CB-F-3A-A EPA-CS-5431-1 Control Switch F37 CB-F-3A-A EPA-TSH-5431 Temperature Switch TUO EFP-F-1-A EPA-DP-374-20 Pilot Solenoid UH4 EFP-F-1-A 4 EPA-DP-374 MAH-20503 B 310708 EFP-F-1-A X X X X UH4 EPA-BC7-FU Fuses BC7 CB-F-1B-A BC7-UH4 EPA-DP-373 Note 1 EPA-EDO-RBC7 Auxiliary Relay EDO CB-F-1B-A BC7a BC7c BC7d CBA-FN-32

CBA-FN-33 EDE-MCC-612 Emergency

Feedwater

Pumphouse Exhaust

Damper EPA-DP-374-20 Pilot Solenoid UH4 EFP-F-1-A EPA-EDO-R1 Auxiliary Relay EDO CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 10 Table MCR 3.1.3.14-1 FUNCTION: PRIMARY AUXILIARY BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 PAH-FN-42A PAB Auxiliary Supply Fan "A" MAH-20495 A 310765 PAB-F-2C-Z X X X - M61 PAH-BF6-52 460 V ac Circuit Breaker BF6 CB-F-1A-A PAH-FN-42B PAH-CS-5391-2 Control Switch BF6 CB-F-1A-A PAH-ZL-5391-4 Fan Indicating Lights BF6 CB-F-1A-A 310930 BF6a BF6c BF6d CBA-FN-19

CBA-FN-20 EDE-MCC-512 PAH-SS-5391 Selector Switch BF6 CB-F-1A-A PAH-ED1-R1 Damper Auxiliary Relay ED1 CB-F-1A-A PAH-ZS-DP-43A-1A PAH-ZS-DP-43A-1B PAH-ZS-DP-43A-2A Damper Position

Switches UG5 PAB-F-1K-Z PAH-ZS-DP-357-1 PAH-ZS-DP-357-2 Damper Position

Switches UG7 PAB-F-2C-Z PAH-BF6-42 Motor Starter BF6 CB-F-1A-A PAH-BF6-49 Overload Relays BF6 CB-F-1A-A BF6-M61 BF6-ED1 BF6-UG5 BF6-UG7 UG5-UG7 BF6-UG5/1 BF6-F36 BF6-F36/1 BF6-TY3 PAH-DP-43A-20 Pilot Solenoid UG5 PAB-F-1K-Z PAH-DP-357-20 Pilot Solenoid UG7 PAB-F-2C-Z PAH-ZL-5391-5 Damper DP-43A Position Lights BF6 CB-F-1A-A PAH-ZL-5391-6 Damper DP-357 Position Lights BF6 CB-F-1A-A PAH-BF6-FU Fuse BF6 CB-F-1A-A PAH-CS-5391-1 Control Switch F36 CB-F-3A-A PAH-ZL-5391-1 Fan Indicating Lights F36 CB-F-3A-A PAH-TSH-5391 Temperature Switch High TY3 PAB-F-2C-Z PAH-ZL-5391-2 Damper DP-43A Position Lights F36 CB-F-3A-A PAH-ZL-5391-3 Damper DP-357 Position Lights F36 CB-F-3A-A 2 PAH-DP-43A PAB Auxiliary Fan Supply Damper MAH-20495 A 310765 PAB-F-1K-Z X X X X UG5 PAH-ED1-R1 Damper Auxiliary Relay ED1 CB-F-1A-A BF6-ED1 BF6-UG5 PAH-DP-43B Note 1 PAH-DP-43A-20 Pilot Solenoid UG5 PAB-F-1K-Z BF6-UG7 UG5-UG7 BF6-UG5/1 310930 BF6a BF6c BF6d CBA-FN-19

CBA-FN-20 3 PAH-DP-357 PAB Auxiliary Fan Exhaust Damper MAH-20495 A 310766 PAB-F-2C-Z X X X X UG7 PAH-ED1-R1 Damper Auxiliary Relay ED1 CB-F-1A-A BF6-ED1 BF6-UG5 PAH-DP-358 Note 1 PAH-DP-357-20 Pilot Solenoid UG7 PAB-F-2C-Z BF6-UG7 UG5-UG7 310930 BF6a BF6c CBA-FN-19

CBA-FN-20

Notes: 1. Air and electrical power are not required for support as damper fails open.

2. See Table RSS 3.1.3.12 for operation of dampers PAH-DP-35A, -35B, -36A & -36B.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 10 Table MCR 3.1.3.14-2 FUNCTION: PRIMARY AUXILIARY BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 PAH-FN-42B PAB Auxiliary Supply Fan "B" MAH-20495 B 310765 PAB-F-2C-Z X X X - M62 PAH-BF7-52 460 V ac Circuit Breaker BF7 CB-F-1B-A 310930 BF7a BF7c CBA-FN-32

CBA-FN-33 EDE-MCC-612 PAH-FN-42A PAH-CS-5393-2 Control Switch BF7 CB-F-1B-A PAH-ZL-5393-4 Fan Indicating Lights BF7 CB-F-1B-A PAH-SS-5393 Selector Switch BF7 CB-F-1B-A PAH-EDO-R1 Damper Auxiliary Relay EDO CB-F-1B-A PAH-ZS-DP-43B-1A PAH-ZS-DP-43B-1B PAH-ZS-DP-43B-2A Damper Position

Switches UG6 PAB-F-1K-Z BF7-M62 BF7-UG6 BF7-UG8 UG6-UG8 BF7-E3D/1 BF7-F37 BF7-F37/1 BF7-TY4 PAH-ZS-DP-358 Damper Position Switch UG8 PAB-F-2C-Z PAH-ZL-5393-5 Damper DP-43B Position Lights BF7 CB-F-1B-A PAH-DP-43B-20 Pilot Solenoid UG6 PAB-F-1K-Z PAH-E3D-R2 Auxiliary Relay E3D CB-F-1B-A PAH-ZL-5393-2 Damper DP-43B Position Lights F37 CB-F-3A-A PAH-ZL-5393-3 Damper DP-358 Position Lights F37 CB-F-3A-A PAH-DP-35B-20 Pilot Solenoid UG8 PAB-F-2C-Z PAH-BF7-42 Motor Starter BF7 CB-F-1B-A PAH-BF7-49 Overload Relays BF7 CB-F-1B-A PAH-BF7-FU Fuses BF7 CB-F-1B-A PAH-ZL-5393-6 Damper DP-358 Position Lights BF7 CB-F-1B-A PAH-CS-5393-1 Control Switch F37 CB-F-3A-A PAH-ZL-5393-1 Fan indicating Lights F37 CB-F-3A-A PAH-TSH-5393 Temperature Switch High TY4 PAB-F-2C-Z 5 PAH-DP-43B PAB Auxiliary Fan Supply Damper MAH-20495 B 310765 PAB-F-1K-Z X X X X UG6 PAH-EDO-R1 Damper Auxiliary Relay EDO CB-F-1B-A BF7-UG6 BF7-UG8 PAH-DP-43A Note 1 PAH-DP-43B-20 Pilot Solenoid UG6 PAB-F-1K-Z UG6-UG8 310930 BF7a BF7c CBA-FN-32

CBA-FN-33 6 PAH-DP-358 PAB Auxiliary Fan Exhaust Damper MAH-20495 B 310766 PAB-F-2C-Z X X X X UG8 PAH-EDO-R1 Damper Auxiliary Relay EDO CB-F-1B-A BF7-UG6 BF7-UG8 PAH-DP-357 Note 1 PAH-DP-358-20 Pilot Solenoid UG8 PAB-F-2C-Z UG6-UG8 310930 BF7a BF7c CBA-FN-32

CBA-FN-33 7 PAH-DP-35A - - - - - - - - - - - - - - - - - - Note 2 8 PAH-DP-36A - - - - - - - - - - - - - - - - - - Note 2 9 PAH-DP-35B - - - - - - - - - - - - - - - - - - Note 2 10 PAH-DP-36B - - - - - - - - - - - - - - - - - - Note 2

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.15-1 FUNCTION: SERVICE WATER AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 SWA-FN-40A SWA-20372 A 301139 SW-F-ID-A X X X - NJO SWA-CR5-52 460 V ac Circuit Breaker CR5 SW-F-1B-A 301115 CR5a CR5c EDE-MCC-514 SWA-FN-40B Service Water

Pumphouse Train

"A" Switchgear

Room Supply Fan SWA-CR5-42 Motor Starter CR5 SW-F-1B-A SWA-CR5-49 Overload Relays CR5 SW-F-1B-A CR5-NJO CR5-G2H/1 CR5-G2H F36-G2H/2 CR5-TV7 CR5-TW9 SWA-CS-5614-2 Control Switch with Indication G2H CB-F-1A-A SWA-SS-5614 Selector Switch G2H CB-F-1A-A SWA-CR5-FU Fuse CR5 SW-F-1B-A SWA-CS-5614-1 Control Switch with Indication F36 CB-F-3A-A SWA-TSH-5614-1 Temperature Switch TV7 SW-F-1B-A SWA-TSH-5614-2 Temperature Switch TW9 SW-F-1C-A 2 SWA-FN-40B SWA-20372 B 301139 SW-F-ID-A X X X - NK1 SWA-CRO-52 460 V ac Circuit Breaker CRO SW-F-1C-A CROa CROc EDE-MCC-614 Service Water

Pumphouse Train

"B" Switchgear

Room Supply Fan SWA-CRO-42 Motor Starter CRO SW-F-1C-A SWA-FN-40A SWA-FN-64 SWA-FN-71 SWA-CRO-49 Overload Relays CRO SW-F-1C-A SWA-CS-5615-2 Control Switch with Indication G2K CB-F-1B-A CRO-NK1 CRO-G2K/1 CRO-G2K F37-G2K/2 F37-G2K/C CRO-TV8 CRO-TWO CRO-G2K/2 SWA-SS-5615 Selector Switch G2K CB-F-1B-A SWA-CRO-FU Fuses CRO SW-F-1C-A SWA-CS-5615-1 Control Switch with Indication F37 CB-F-3A-A SWA-TSH-5615-1 Temperature Switch TV8 SW-F-1C-A SWA-TSH-5615-2 Temperature Switch TWO SW-F-1B-C 3 SWA-FN-64 SWA-20372 A 301717 CT-F-2B-A X X X - NW1 SWA-CQO-52 460 V ac Circuit Breaker CQO CT-F-1D-A EDE-MCC-513 SWA-FN-40B Service Water

Cooling Tower

Switchgear Room

Supply Fan SWA-CQO-42 Motor Starter CQO CT-F-1D-A SWA-CQO-49 Overload Relay CQO CT-F-1D-A 9763-M-301115 CQOa CQOc CQOd SWA-CS-5669 Control Switch F36 CB-F-3A-A CQO-NW1 CQO-NW1/2 CQO-NW1/3 CQO-F36 ED6-T5V ED6-F36/1 SWA-ZL-5669 Indicating Light F36 CB-F-3A-A SWA-CQO-FU Fuse CQO CT-F-1D-A SWA-TSH-5669 Temperature Switch T5V CT-F-1D-A SWA-FY-5669-1 Solenoid Valve NW1 CT-F-2B-A SWA-FY-5669-2 Solenoid Valve NW1 CT-F-2B-A SWA-DP-66 Position Switch NW1 CT-F-2B-A SWA-ED6-R1 Auxiliary Relay ED6 CT-F-1D-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.15-2 FUNCTION: SERVICE WATER AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 SWA-DP-66 SWA-20372 A 301717 CT-F-2B-A X X X - NW1 SWA-CQO-52 460 V ac Circuit Breaker CQO CT-F-1D-A CQOa CQOc CQOd EDE-MCC-513 Instrument Air SWA-FN-40B Service Water

Cooling Tower

Switchgear Room

Supply Damper SWA-CQO-42 Motor Starter CQO CT-F-1D-A SWA-CQO-49 Overload Relay CQO CT-F-1D-A CQO-NW1 CQO-NW1/2 CQO-NW1/3 CQO-F36 ED6-T5V ED6-F36/1 SWA-CS-5669 Control Switch F36 CB-F-3A-A SWA-ZL-5669 Indicating Lights F36 CB-F-3A-A SWA-CQO-FU Fuse CQO CT-F-1D-A SWA-TSH-5669 Temperature Switch T5V CT-F-1D-A SWA-FY-5669-1 Solenoid Valve NW1 CT-F-2B-A SWA-FY-5669-2 Solenoid Valve NW1 CT-F-2B-A SWA-DP-66 Position Switch NW1 CT-F-2B-A SWA-ED6-R1 Auxiliary Relay ED6 CT-F-1D-A 5 SWA-FN-71 SWA-20372 A 301717 CT-F-2B-A X X X - NW2 SWA-CR1-52 460 V ac Circuit Breaker CR1 CT-F-1D-A CR1a CR1c EDE-MCC-513 SWA-FN-40B Service Water

Tower Roof Exhaust Fan SWA-CR1-42 Motor Starter CR1 CT-F-1D-A CR1-NW2 CR1-F36 CR1-T5T SWA-CR1-49 Overload Relay CR1 CT-F-1D-A SWA-CS-5667 Control Switch with Indication F36 CB-F-3A-A SWA-TSH-5667 Temperature Switch T5T CT-F-2B-A SWA-CR1-FU Fuse CR1 CT-F-1D-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.16 -1 FUNCTION: SERVICE/INSTRUMENT AIR PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 SA-SKD-137A Service Air Compressor 16A SA-20650 A 310328 TB-F-1A-Z X X X - NN2 SA-AA2-52 460 V AC Circuit Breaker AA2 CB-F-1A-A AA2-ED4 AA2-HR2 AA2-NH2 310863 AA2a AA2d AA2b AA2e AA2c U5-52 CBA-FN-19 CBA-FN-20 SA-SKD-137b SA-AA2-FU Fuses AA2 CB-F-1A-A SA-CS-8501-A Control Switch with Indication AC3 CB-F-1A-A SA-AA2-52H-1 Truck Operated Switch AA2 CB-F-1A-A DG-HR2-HR9X-RMO EPS Relay HR2 CB-F-1A-A EDE-ED4-94-5 Undervoltage Relay ED4 CB-F-1A-A 2 SA-TK-23A Service Air Tank Receiver SA-20650 A 310328 TB-F-1A-Z X X - - - - - - - - - - - - 3 SA-V-92 Service Air Isolation Valve SA-20650 A 310328 TB-F-1A-Z X X X X UM9 SA-E46/8-52 120 V AC Circuit Breaker E46 TB-F-2-Z ED8-F71 ED8-GZ9/1 ED8-UM9 ED8-UM0 UM9-UM0 GZ9-UM9/ GZ9-UM0 E46/8a E46/8c E46/8d - - Note 11 SA-CS-8540 Control Switch with Indication F71 CB-F-3A-A SA-PSL-8540 Pressure Switch GZ9 TB-F-1A-Z SA-PIS-8509 Pressure Indication Switch GZ9 TB-F-1A-Z SA-UM9-20-1 Solenoid Valve UM9 TB-F-1A-Z SA-ED8-3 Interlocking Relay ED8 TB-F-2-Z SA-ZS-V92 Position Switch UM9 TB-F-1A-Z SA-PSL-8545 Pressure Switch GZ9 TB-F-1A-Z 4 SA-SKD-137B Service Air Compressor 16B SA-20650 B 310328 TB-F-1A-Z X X X - NT4 SA-AT2-52 460 V AC Circuit Breaker AT2 CB-F-1B-A AT2-HR4 AT2-NT4 310863 AT2a AT2d AT2b AT2e AT2c CBA-FN-32 CBA-FN-33 US-63 SA-SKD-137A SA-AT2-FU Fuses AT2 CB-F-1B-A SA-CS-8501-B Control Switch with Indication AF8 CB-F-1B-A SA-AT2-52H-1 Truck Operated Switch AT2 CB-F-1B-A DG-HR4-HR9X-RMO EPS Relay HR4 CB-F-1B-A EDE-EF8-94-3 Undervoltage Relay AF8 CB-F-1B-A 5 SA-TK-23B Service Air Tank Receiver SA-20650 B 310328 TB-F-1A-Z X X - - - - - - - - - - - - Notes: 1. Air and electrical power are not required for support as valve fails closed.

2. Fail open mechanical valve. 3. Manual valve.
4. Electrical operation of valve not credited so cables are not listed.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.16 -2 FUNCTION: SERVICE/INSTRUMENT AIR PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 SA-V-93 Service Air Isolation Valve SA-20650 A 310328 TB-F-1A-Z X X X X UM0 SA-E46/8-52 120 V AC Circuit Breaker E46 TB-F-2-Z ED8-F71 ED8-GZ9/1 ED8-UM9 ED8-UMO UM9-UM0 GZ9-UMO GZ9-UM9 E46/8a E46/8c E46/8d - - Notes 1 and 2 SA-CS-8540 Control Switch with Indication F71 CB-F-3A-A SA-PSL-8540 Pressure Switch G29 TB-F-1A-Z SA-PIS-8509 Pressure Indication Switch G29 TB-F-1A-Z SA-UM0-20-2 Solenoid Valve UMO TB-F-1A-Z SA-ED8-3 Interlocking Relay ED8 TB-F-2-Z SA-ZS-V93 Position Switch UMO TB-F-1A-Z SA-PSL-8545 Pressure Switch GZ9 TB-F-1A-Z 7 IA-SKD-18A Instrument Air Dryer (Skid 18A) IA-20637 A 310328 TB-F-1A-Z X X X - HF1 IA-C68-52 460 V AC Circuit Breaker C68 TB-F-2-Z C68-HF1/1 310864 C68a C68b IA-SKD-18B 8 IA-SKD-18B Instrument Air Dryer (Skid 18B) IA-20637 B 310328 TB-F-1A-Z X X X - HF2 IA-C74-52 460 V AC Circuit Breaker C74 CB-F-1B-A C74-HF2/1 310864 C74a C74b CBA-FN-32 CBA-FN-33 EDE-MCC-631 IA-SKD-18A 9 SA-C-4A Containment Air Compressor 4A (Skid 16A) with Control Panel IA-20643 A 310578 C-F-2-Z - X X - M38 SA-D93-52-1,2 460 V AC Circuit Breaker D93 CB-F-1A-A D93-F71 D93-F71/1 D93-HR2 D93-H19 D93-H36/1 D93-H36/2 G44-H36 G44-H36/1 H19-M38 310863 D93a D93c D93d EDE-MCC-531 Primary Component Cooling Water CAH-FN-1C CAH-FN-1E CAH-FN-1F CAH-FN-19 CAH-FN-20 SA-C-4B SA-D93-FU Fuse D93 CB-F-1A-A SA-CS-8531 Control Switch with Indication F71 CB-F-3A-A SA-HR2-HR9 EPS Permit Auxiliary Relay HR2 CB-F-1A-A SA-D93-42 Motor Starter D93 CB-F-1A-A SA-D93-49 Overload Relays D93 CB-F-1A-A SA-CS-4A-T Control Switch Load-Unload G44 C-F-2-Z SA-CS-4A-PB Reset Push Button G44 C-F-2-Z SA-PS-4A-1 Pressure Switch Lube Oil G44 C-F-2-Z SA-PS-4A-2 Pressure Switch Air Header G44 C-F-2-Z SA-TS-4A-1 Temperature Switch Compressor Outlet Air G44 C-F-2-Z SA-G44-R Compressor Shutdown Relay G44 C-F-2-Z SA-SV-4A Loading Solenoid G44 C-F-2-Z SA-G44-TR1 Compressor Loading Time Delay Relay G44 C-F-2-Z SA-G44-TR2 Compressor Auto Stop Time Delay Relay G44 C-F-2-Z SA-G44-TR3 Compressor Auto Restart Time Delay Relay G44 C-F-2-Z EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.16 -3 FUNCTION: SERVICE/INSTRUMENT AIR PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 10 SA-C-4B Containment Air Compressor 4B (Skid 16B) with Control Panel IA-20643 B 310578 C-F-2-Z - X X - M39 SA-D95-52-1,2 460 V AC Circuit Breaker D95 CB-F-1B-A D95-F71 D95-F71/1 D95-HR4 D95-H24 D95-H39/1 D95-H39/2 G45-H39 G45-H39/1 H24-M39 310863 D95a D95c D95d EDE-MCC-631 Primary Component Cooling Water CAH-FN-1A CAH-FN-1B CAH-FN-1D CBA-FN-32 CBA-FN-33 SA-C-4A SA-D95-FU Fuse D95 CB-F-1B-A SA-CS-8541 Control Switch with Indication F71 CB-F-3A-A SA-HR4-HR9 EPS Permit Auxiliary Relay HR4 CB-F-1B-A SA-D95-42 Motor Starter D95 CB-F-1B-A SA-D95-49 Overload Relays D95 CB-F-1B-A SA-CS-4B-T Control Switch Load-Unload G45 C-F-2-Z SA-CS-4B-PB Reset Push Button G45 C-F-2-Z SA-PS-4B-1 Pressure Switch Lube Oil G45 C-F-2-Z SA-PS-4B-2 Pressure Switch Air Header G45 C-F-2-Z SA-TS-4B-1 Temperature Switch Compressor Outlet Air G45 C-F-2-Z SA-G45-R Compressor Shutdown Relay G45 C-F-2-Z SA-SV-4B Loading Solenoid G45 C-F-2-Z SA-G45-TR1 Compressor Loading Time Delay Relay G45 C-F-2-Z SA-G45-TR2 Compressor Auto Stop Time Delay Relay G45 C-F-2-Z SA-G45-TR3 Compressor Auto Restart Time Delay Relay G45 C-F-2-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A 11 IA-D-2A Containment Instrument Air Dryer 2A IA-20643 A 310578 C-F-2-Z X X X - HF3 IA-E9L/3-52 120 V AC Circuit Breaker E9L ET-F-1A-A EM9-J97 HF3-J97 E4E-E9L/2 E4E-H19/2 H19-J97 310864 E9L/3a E9L/3b ED-PP-8J CAH-FN-1C CAH-FN-1E CAH-FN-1F IA-D-2B EDE-MM-582 Fuse Panel E4E ET-F-1A-A EDE-MM-95 Penetration H19 C-F-2-Z, ET-F-1C-A 12 IA-D-2B Containment Instrument Air Dryer 2B IA-20643 B 310578 C-F-2-Z X X X - HF4 IA-EM0/1-52 120 V AC Circuit Breaker EM0 C-F-1-Z EM0-J98 HF4-J98 EM0/1a EM0/1b ED-PP-8B CAH-FN-1A CAH-FN-1B CAH-FN-1D IA-D-2A 13 IA-V50 Instrument Air Dryers Outlet Cross Connect Isolation IA-20637 - 202206 TB-F-1A-Z - X - - - - - - - - - - - Note 3 14 IA-V530 Instrument Air to Containment Isolation ORC IA-20645 A 310589 MS-F-1B-Z - X - X - - - - - - - - - Note 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -1 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EDE-SWG-5 4160 V Bus E5 UAT Incoming Line SWGR 310007 A 310442 CB-F-1A-A X X X - A51 EDE-A51-52 4160 V Circuit Breaker A51 CB-F-1A-A A51-G07 A51-G07/2 A51-G10 A51-HR9 GA6-GB0/4 A51-G07/1 A51-G07/3 A51-GB4 GA0-GB3/4 GC4-GC6/4 A51-G5X A51-G5X/1 G07-HR9 F80-G07/H F80-G07/C F80-G07 G07-HR2 F80-G07/A A55-A5A A54-A5A/1 310102 A51a A51h A51b A51c A51d A51e CBA-FN-19 CBA-FN-20 ED-X-2A EDE-PP-111A DAH-FN-25A DAH-FN-26A EDE-SWG-6 UAT EDE-CS-9709-2 Control Switch A51 CB-F-1A-A EDE-CS-9709-3 Control Switch with Indication G07 DG-F-2A-A EDE-A51-G,R,W Indicating Lights A51 CB-F-1A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-A51-52H Truck Operated Contact A51 CB-F-1A-A EDE-A51-FU Fuses A51 CB-F-1A-A EDE-A51-CT1 Current Transformer (2000/5) A51 CB-F-1A-A EDE-A51-TD-1 CT Test Device A51 CB-F-1A-A EDE-A51-AM Ammeter A51 CB-F-1A-A EDE-A51-AS Ammeter Switch A51 CB-F-1A-A EDE-A51-ATR Transducer Current A51 CB-F-1A-A EDE-A51-CT2 Transformers (4000/5) A51 CB-F-1A-A EDE-A67-PT Potential Transformer (4200-120 V) A67 CB-F-1A-A EDE-A51-TD-3 PT Test Device A51 CB-F-1A-A EDE-A51-VM Voltmeter A51 CB-F-1A-A EDE-A51-86 Lockout Relay A51 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-A52-52S Mechanically Operated Contact A52 CB-F-1A-A DG-G10-25Y1 Auxiliary Synchronizing Check Relay G10 DG-F-2A-A EDE-A53-25U Synchronizing Check Relay A53 CB-F-1A-A EDE-SS-9709-1 Selector Switch G5X DG-F-2A-A EDE-CS-9707-3 Control Switch G07 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A52-86 Lockout Relay A52 CB-F-1A-A EDE-A69-86B Lockout Relay A69 CB-F-1A-A ED-86SB/2/1X -1 Lockout Relay GA0 TB-F-1C-Z ED-86-2/2/B3 Lockout Relay GA6 TB-F-1C-Z ED-86UB/2/1X -2A Lockout Relay GA8 TB-F-1C-Z ED-86UB/2/1X -2B Lockout Relay GA8 TB-F-1C-Z ED-86BF/2/2/52/TG1 Lockout Relay GA9 TB-F-1C-Z ED-86GT/2/TG1 Lockout Relay GA9 TB-F-1C-Z ED-86-1/2/B3 Lockout Relay GB0 TB-F-1C-Z ED-86BF-2/2H Lockout Relay GB3 TB-F-1C-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -2 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EDE-SWG-5 (Continued) ED-86BF-2/2E Lockout Relay GB4 TB-F-1C-Z ED-86UP/2/1X -2A Lockout Relay GC2 TB-F-1C-Z ED-86UP/2/1X -2B Lockout Relay GC2 TB-F-1C-Z ED-86BF-1/2/52/TG1 Lockout Relay GC3 TB-F-1C-Z ED-86SP/2/1X -1 Lockout Relay GC4 TB-F-1C-Z ED-86BF-1/2H Lockout Relay GC6 TB-F-1C-Z ED-86BF-1/2E Lockout Relay GC7 TB-F-1C-Z DG-HR9-RM0 EPS Auxiliary Relay HR9 CB-F-1A-A EDE-A51-3 Interposing Relay for SWYD Lockout Relays A51 CB-F-1A-A EDE-A51-TD-2 Lockout Relay Test Device (A51 -86) A51 CB-F-1A-A EDE-A51-TD-4 Interposing Relay Test Device (A51 -3) A51 CB-F-1A-A EDE-CS-9707-4 Control Switch F80 CB-F-3A-A ED-GA0-TD-2 Lockout Relay Test Device (86SB/2/1X -1) GA0 TB-F-1C-Z ED-GA6-TD-2 Lockout Relay Test Device (86 -2/2/B3) GA6 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2A) GA8 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2B) GA8 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86BF-2/2/52/TG1) GA9 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86GT/2/TG1) GA9 TB-F-1C-Z ED-GB0-TD-2 Lockout Relay Test Device (86 -1/2/B3) GB0 TB-F-1C-Z ED-GB3-TD-2 Lockout Relay Test Device (86BF -2/2H) GB3 TB-F-1C-Z ED-GB4-TD-2 Lockout Relay Test Device (86BF -2/2E) GB4 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2A) GC2 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2B) GC2 TB-F-1C-Z ED-GC3-TD-2 Lockout Relay Test Device (86BF-1/2/52/TG1) GC3 TB-F-1C-Z ED-GC4-TD-2 Lockout Relay Test Device (86SP/2/1X -1) GC4 TB-F-1C-Z ED-GC6-TD-2 Lockout Relay Test Device (86BF -1/2H) GC6 TB-F-1C-Z ED-GC7-TD-2 Lockout Relay Test Device (86BF -1/2E) GC7 TB-F-1C-Z EDE-A51-51 Time Overcurrent Relays øA, øB, øC A51 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -3 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EDE-SWG-5 (Continued) EDE-A51-51GS Ground Sensor Relay A51 CB-F-1A-A EDE-SNS-9736-1 Synchronizing Switch F80 CB-F-3A-A EDE-CS-9709-1 Control Switch with Indicating Light F80 CB-F-3A-A DG-HR2-RM0 EPS Auxiliary Relay HR2 CB-F-1A-A EDE-CS-9707-1 Control Switch F80 CB-F-3A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A 2 EDE-SWG-5 Grounding Transformer 310007 A 310442 CB-F-1A-A X X X - A67 EDE-A67-XFMR 3-1ø 15 KVA Transformers A67 CB-F-1A-A 310102 A67a CBA-FN-19 CBA-FN-20 EDE-SWG-5 EDE-SWG-6 GRD XFMR EDE-A67-FU 3-10A Fuses A67 CB-F-1A-A EDE-A67-52 120 V AC Circuit Breaker A67 CB-F-1A-A EDE-A67-RES Grounding Resistor A67 CB-F-1A-A EDE-A67-64 Grounding Relay A67 CB-F-1A-A EDE-A67-TD-3 VM Test Device A67 CB-F-1A-A EDE-A67-VM (3) Ground Voltmeters A67 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -4 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 EDE-SWG-5 4160 V Bus E5 RAT Incoming Line SWGR 310007 A 310442 CB-F-1A-A X X X - A52 EDE-A52-52 4160 V Circuit Breaker A52 CB-F-1A-A A52-G07/1 A52-G07/3 A52-G10 A52-HR2 GA7-GB7/4 GE6-GE7/4 A52-G5X A52-G5X/1 A52-G07/2 A52-G07/4 A52-GB7 AG2-HR9 GC1-GC0/4 F80-G07/J A52-F80 F80-G07/D F80-G07/4 A54-A5A/2 310102 A52a A52j A52b A52k A52c A52l A52d A52e CBA-FN-19 CBA-FN-20 ED-X-3A EDE-PP-111A DAH-FN-25A DAH-FN-26A EDE-SWG-6 RAT EDE-CS-9707-2 Control Switch A52 CB-F-1A-A EDE-CS-9707-3 Control Switch with Indication G07 DG-F-2A-A EDE-A52-G,R,W Indicating Lights A52 CB-F-1A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-A52-52H Truck Operated Contact A52 CB-F-1A-A EDE-A52-FU Fuses A52 CB-F-1A-A EDE-A52-27/59 Under/Over Voltage Relay A52 CB-F-1A-A EDE-A52-27/59X1,X2 Under/Over Voltage Auxiliary Relay A52 CB-F-1A-A EDE-A52-52Z Time Delay Relay A52 CB-F-1A-A EDE-SS-9707-1 Selector Switch G5X DG-F-2A-A EDE-CS-9709-3 Control Switch G07 DG-F-2A-A EDE-A52-CT-1 Current Transformer (2000/5) A52 CB-F-1A-A EDE-A52-TD-1 CT Test Device A52 CB-F-1A-A EDE-A52-AM Ammeter A52 CB-F-1A-A EDE-A52-AS Ammeter Switch A52 CB-F-1A-A EDE-A52-ATR Transducer A52 CB-F-1A-A EDE-A52-CT-2 Current Transformer (4000/5) A52 CB-F-1A-A EDE-A53-PT Potential Transformer A53 CB-F-1A-A EDE-A52-TD-3 PT Test Device A52 CB-F-1A-A EDE-A52-VM Voltmeter A52 CB-F-1A-A EDE-A52-52S Mechanically Operated Contact A52 CB-F-1A-A EDE-A69-86B Lockout Relay A69 CB-F-1A-A EDE-A52-86 Lockout Relay A52 CB-F-1A-A EDE-A51-86 Lockout Relay A51 CB-F-1A-A DG-HR2-RM0 EPS Auxiliary Relay HR2 CB-F-1A-A DG-HR9-RM0 EPS Auxiliary Relay HR9 CB-F-1A-A EDE-A51-52S Mechanically Operated Contact A51 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -5 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 EDE-SWG-5 (Continued) DG-G10-25Y1 Auxiliary Synchronizing Check Relay G10 DG-F-2A-A EDE-CS-9707-4 Control Switch F80 CB-F-3A-A EDE-A53-25RX Auxiliary Synchronizing Check Relay A53 CB-F-1A-A EDE-A53-25R Synchronizing Check Relay A53 CB-F-1A-A EDE-A52-62 Time Delay Relay A52 CB-F-1A-A EDE-A51-3 Interposing Relay for SWG Lockout Relays A51 CB-F-1A-A EDE-A52-TD-2 Lockout Relay Test Device (A52 -86) A52 CB-F-1A-A EDE-A52-TD-4 Interposing Relay Test Device (A52 -3) A52 CB-F-1A-A ED-86RB/2/1X -3A Lockout Relay GA7 TB-F-1C-Z ED-86-2/2/B2 Lockout Relay GB7 TB-F-1C-Z ED-86-1/2/B2 Lockout Relay GC0 TB-F-1C-Z ED-86RP/2/1X -3A Lockout Relay GC1 TB-F-1C-Z ED-86RP/2/1X -3B Lockout Relay GE6 TB-F-1C-Z ED-86RB/2/1X-3B Lockout Relay GE7 TB-F-1C-Z ED-GA7-TD-2 Lockout Relay Test Device (86RB/2/1X -3A) GA7 TB-F-1C-Z ED-GB7-TD-2 Lockout Relay Test Device (86 -2/2/B2) GB7 TB-F-1C-Z ED-GC0-TD-2 Lockout Relay Test Device (86 -1/2/B2) GC0 TB-F-1C-Z ED-GC1-TD-2 Lockout Relay Test Device (86RP/2/1X -3A) GC1 TB-F-1C-Z ED-GE6-TD-2 Lockout Relay Test Device (86RP/2/1X -3B) GE6 TB-F-1C-Z ED-GE7-TD-2 Lockout Relay Test Device (86RP/2/1X -3B) GE7 TB-F-1C-Z EDE-A52-51 Time Overcurrent Relays øA, øB, øC A52 CB-F-1A-A EDE-A52-51GS Ground Sensor Relay A52 CB-F-1A-A EDE-SNS-9736-1 Synchronizing Switch F80 CB-F-3A-A EDE-CS-9707-1 Control Switch with Indication Light F80 CB-F-3A-A EDE-A53-62BX Auxiliary Latch Relay A53 CB-F-1A-A EDE-A52-27RB-1 Residual Undervoltage Relay A52 CB-F-1A-A EDE-A52-27RB-2 Residual Undervoltage Relay A52 CB-F-1A-A EDE-CS-9709-1 Control Switch F80 CB-F-3A-A EDE-A52-62X Auxiliary Relay A52 CB-F-1A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -6 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 EDE-SWG-5 4160 V Bus E5 PT Compartment 310007 A 310442 CB-F-1A-A X X X - A53 EDE-A53-PT Potential Transformers A53 CB-F-1A-A A53-AC2 A53-HR2 AF2-ED4 A53-G07 AC2-AF2 A53-FB7 F80-G07/5 A54-A5A/4 A54-A5A/5 A55-A5A/1 A55-A5A/2 310102 A53a A53d A53e A53h CBA-FN-19 CBA-FN-20 EDE-SWG-5 EDE-PP-111A DAH-FN-25A DAH-FN-26A EDE-SWG-6 PT EDE-A53-VM Voltmeter A53 CB-F-1A-A EDE-A53-VS Voltmeter Switch A53 CB-F-1A-A EDE-A53-TD-3 PT Test Device A53 CB-F-1A-A EDE-A53-VTR-1 Voltage Transducer A53 CB-F-1A-A EDE-A53-VTR-2 Voltage Transducer A53 CB-F-1A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A53-25U Synchronizing Check Relay A53 CB-F-1A-A EDE-A53-25R Synchronizing Check Relay A53 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-A53-27B-1 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-27B-2 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-TS-3 Undervoltage Relays Test Switch A53 CB-F-1A-A EDE-A53-27D-1 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-27D-1-RES Resistor A53 CB-F-1A-A EDE-A53-27D-2 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-27D-2-RES Resistor A53 CB-F-1A-A EDE-A53-TS-1 Undervoltage Relays Test Switch A53 CB-F-1A-A EDE-A52-27RB-1,2 Residual Undervoltage Relay A52 CB-F-1A-A EDE-A53-62B Time Delay Relay A53 CB-F-1A-A EDE-A53-62B-RES Resistor A53 CB-F-1A-A EDE-A53-TS-4 Test Switch EDE -62B A53 CB-F-1A-A EDE-A53-62BX-1 Auxiliary Relay A53 CB-F-1A-A EDE-A53-62BX Auxiliary Latch Relay A53 CB-F-1A-A EDE-A51-52S Mechanically Operated Contact A51 CB-F-1A-A EDE-ED4-94-5 Undervoltage Tripping Relay ED4 CB-F-1A-A EDE-A52-27/59X1 Under/Over Voltage Auxiliary Relay A52 CB-F-1A-A EDE-AF3-94-4 Undervoltage Tripping Relay AF3 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -7 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 EDE-SWG-5 (Continued) DG-HR2-RM0 EPS Auxiliary Relay HR2 CB-F-1A-A EDE-A53-94-1A Undervoltage Tripping Relay A53 CB-F-1A-A EDE-A53-94-1B Undervoltage Tripping Relay A53 CB-F-1A-A EDE-A53-94-2 Undervoltage Tripping Relay A53 CB-F-1A-A EDE-AC3-94-3 Undervoltage Tripping Relay AC3 CB-F-1A-A EDE-A53-FU 120 V AC 3A Fuses A53 CB-F-1A-A EDE-A53-FU 125 V DC 10A Fuses (2) A53 CB-F-1A-A EDE-A53-62D Time Delay Relay A53 CB-F-1A-A EDE-A53-62D-RES Resistor A53 CB-F-1A-A EDE-A53-TS-2 Test Switch Relay 62D A53 CB-F-1A-A EDE-A53-62DX Auxiliary Relay A53 CB-F-1A-A EDE-SNS-9736-1 Synchronizing Switch F80 CB-F-3A-A EDE-FB7-K609A SI Sig. Act. Auxiliary Relay FB7 CB-F-3A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -8 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 EDE-SWG-5 4160 V Bus E5 DG-1A Incoming Line SWGR 310010 310007 A 310442 CB-F-1A-A X X X - A54 EDE-A54-52 4160 V Circuit Breaker A54 CB-F-1A-A A54-G06/2 A54-G06/4 A54-G07/1 A54-HN0 A54-G06/3 A54-G07 A54-G07/2 G06-G29/7 F80-G06/1 A54-F80/1 A54-HR9 A54-FB7 A54-F80 A5A-A5A/3 310102 A54a A54k A54b A54c A54d A54e A54f CBA-FN-19 CBA-FN-20 DG-DG-1A DAH-FN-25A DAH-FN-26A EDE-PP-111A EDE-SWG-6 DG-1B EDE-CS-9700-2 Control Switch A54 CB-F-1A-A EDE-CS-9700-3 Control Switch with Indication G06 DG-F-2A-A EDE-A54-G,R,W Indicating Lights A54 CB-F-1A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A54-52H Truck Operated Contact A54 CB-F-1A-A EDE-A54-FU Fuses A54 CB-F-1A-A EDE-A54-CT Current Transformers (2000/5) A54 CB-F-1A-A EDE-A54-DCT Differential Current Transformers (2000/5) A54 CB-F-1A-A DG-HNO-DCT DG-1A Neut. Diff. Current Transformers (2000/5) HN0 DG-F-2A-A DG-G06-CT Auxiliary Current Transformer (5:10) G06 DG-F-2A-A EDE-A54-AM Ammeter A54 CB-F-1A-A EDE-A54-AS-1 Ammeter Switch A54 CB-F-1A-A EDE-A54-ATR-1 Current Transducer A54 CB-F-1A-A EDE-A54-ATR-2 Current Transducer A54 CB-F-1A-A EDE-AM-9700-2 Ammeter G06 DG-F-2A-A EDE-G06-AS Ammeter Switch G06 DG-F-2A-A DG-SM-9585 Governor Control (2301A) G06 DG-F-2A-A EDE-A69-PT DG-1A Inc. Line Pot. Transformer (2) 4200 -120 V A69 CB-F-1A-A EDE-A69-VM Voltmeter A69 CB-F-1A-A EDE-A69-VS Voltmeter Switch A69 CB-F-1A-A EDE-A69-TD-3 PT Test Device A69 CB-F-1A-A EDE-A69-VTR-1 Voltage Transducer A69 CB-F-1A-A EDE-A69-VTR-2 Voltage Transducer A69 CB-F-1A-A EDE-A54-27DG Undervoltage Relay A54 CB-F-1A-A EDE-A69-FTR-1 Frequency Transducer A69 CB-F-1A-A EDE-A69-FTR-2 Frequency Transducer A69 CB-F-1A-A EDE-A69-W/WH-TR Watt/Watthour Transducer A69 CB-F-1A-A EDE-A69-W/TR Watt Transducer A69 CB-F-1A-A EDE-A69-VAR-TR Var Transducer A69 CB-F-1A-A EDE-A54-TS Test Start Switch A54 CB-F-1A-A EDE-A54-52Z Time Delay Relay A54 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -9 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 EDE-SWG-5 (Continued) EDE-A54-81-RES Resistor A54 CB-F-1A-A EDE-A54-86DP Primary Lockout Relay A54 CB-F-1A-A EDE-A54-W Indicating Light (A54-86DP) A54 CB-F-1A-A EDE-A69-86B Lockout Relay A69 CB-F-1A-A EDE-A69-86DB Back-Up Lockout Relay A69 CB-F-1A-A EDE-A69-W Indicating Light (A69-86B & A69 -86DB) A69 CB-F-1A-A EDE-A51-86 Lockout Relay A51 CB-F-1A-A EDE-A52-86 Lockout Relay A52 CB-F-1A-A EDE-A51-52S Mechanically Operated Contact A51 CB-F-1A-A EDE-A52-52S Mechanically Operated Contact A52 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-A69-RLA LOCA Seal Relay A69 CB-F-1A-A DG-G10-25Y Auxiliary Sync Check Relay G10 DG-F-2A-A EDE-A69-RS Fast Closure Relay A69 CB-F-1A-A EDE-A54-81 Frequency Relay A54 CB-F-1A-A EDE-A54-87DP Primary Differential Relay A54 CB-F-1A-A EDE-A69-51B Time Overcurrent Relays, øA, øB, øC A69 CB-F-1A-A EDE-A54-81X Auxiliary Frequency Relay A54 CB-F-1A-A EDE-A69-60 Voltage Balance Relay A69 CB-F-1A-A EDE-A69-60AX Auxiliary Voltage Balance Relay A69 CB-F-1A-A EDE-A69-60BX Auxiliary Voltage Balance Relay A69 CB-F-1A-A EDE-A69-40 Loss of Field Relays øA, øB A69 CB-F-1A-A EDE-A54-40X Auxiliary Loss of Field Relay A54 CB-F-1A-A EDE-A69-32 Power Directional Relay A69 CB-F-1A-A EDE-A69-TD-1 Lockout Relay Test Device (86B ) A69 CB-F-1A-A EDE-A69-TD-2 Lockout Relay Test Device (86DB) A69 CB-F-1A-A EDE-A54-TD-2 Lockout Relay Test Device (86DP) A54 CB-F-1A-A DG-G07-R43L5 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -10 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 EDE-SWG-5 (Continued) DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G29-5A Shutdown Relay G29 DG-F-2A-A EDE-A69-51V Time Overcurrent Voltage Restraint Relays, øA, øB, øC A69 CB-F-1A-A EDE-A69-FU 120 V AC 3A Fuses A69 CB-F-1A-A EDE-A54-87DP Reactor Primary Differential Relay Reactor Assembly A54 CB-F-1A-A EDE-A69-51GS Ground Sensor Relay A69 CB-F-1A-A EDE-A54-TD-1 Test Device A54 CB-F-1A-A EDE-CS-9700-1 Control Switch with Indicating Light F80 CB-F-3A-A DG-HR9-PRIX EPS Auxiliary Relay HR9 CB-F-1A-A EDE-SNS-9736-1 Synchronizing Switch F80 CB-F-3A-A MM-FB7-K601A SI Signal Act. Output Relay FB7 CB-F-3A-A DG-G07-ESS Emergency Start Auxiliary Relay G07 DG-F-2A-A EDE-A54-81Y Time Delay Relay A54 CB-F-1A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -11 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 DG-CP-75A Diesel Generator 1A Control Panel Cubicle 2 Synchronizing System 310010 A 310524 DG-F-2A-A X X X - G07 DG-G07-FU-17&18 125 V DC Fuses (6A) G07 DG-F-2A-A F80-G07/B F80-G07/1 310102 G07/2c G07/2g 7b 7f DAH-FN-25A DAH-FN-26A EDE-SWG-11A DG-CP-76A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-RAX Auxiliary Relay, Latch G07 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-CS-9700-3 Control Switch G06 DG-F-2A-A EDE-CS-9707-3 Control Switch G07 DG-F-2A-A EDE-CS-9709-3 Control Switch G07 DG-F-2A-A DG-G06-25DG Synchronizing Check Relay G06 DG-F-2A-A DG-G10-25Y Auxiliary Synchronizing Check Relay G10 DG-F-2A-A DG-G10-25Y1 Auxiliary Synchronizing Check Relay G10 DG-F-2A-A EDE-SNS-9763-1 Synchronizing Switch F80 CB-F-3A-A EDE-CS-9700-1 Control Switch F80 CB-F-3A-A EDE-CS-9707-1 Control Switch F80 CB-F-3A-A EDE-CS-9709-1 Control Switch F80 CB-F-3A-A EDE-A67-PT UAT X-2A Inc. Line Potential Transformer A67 CB-F-1A-A EDE-A53-PT RAT X-3A Inc. Line Potential Transformer A53 CB-F-1A-A EDE-A53-PT Bus E5 Potential Transformer A53 CB-F-1A-A EDE-A69-PT DG-1A Inc. Line Potential Transformer A69 CB-F-1A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-RAX Auxiliary Relay, Latch G07 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -12 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 DG-CP-75A (Continued) DG-G06-25DG Synchronizing Check Relay G06 DG-F-2A-A EDE-SYN-9701 Synchroscope G06 DG-F-2A-A EDE-ZL-9701 Synchronizing Lights G06 DG-F-2A-A EDE-VM-9701-1 Synchronizing Voltmeter Incoming G06 DG-F-2A-A EDE-VM-9701-2 Synchronizing Voltmeter Running G06 DG-F-2A-A EDE-SYN-9891 Synchroscope F80 CB-F-3A-A EDE-ZL-9891 Synchronizing Lights F80 CB-F-3A-A EDE-VM-9891-1 Voltmeter F80 CB-F-3A-A EDE-VM-9891-2 Voltmeter F80 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -13 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 EDE-SWG-5 4160 V Feed to 480 V Transformer EDE-X-5A for Substation Bus EDE-US-51 310007 A 310442 CB-F-1A-A X X X - A55 EDE-A55-52 4160 V Circuit Breaker A55 CB-F-1A-A A55-AB1 A55-F80/1 310102 A55a A55g A55b A55c A55d CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-SWG-5 EDE-SWG-6 EDE-X-5C EDE-US-61 EDE-A55-FU Fuses A55 CB-F-1A-A EDE-CS-9706 Control Switch A55 CB-F-1A-A EDE-A55-G,R,W Indicating Lights A55 CB-F-1A-A EDE-SS-9706 Selector Switch A55 CB-F-1A-A EDE-A55-52H Truck Operated Contact A55 CB-F-1A-A EDE-A55-86 Lockout Relay A55 CB-F-1A-A EDE-A55-TD2 Lockout Relay Test Device A55 CB-F-1A-A EDE-A55-50/51 Inst/Time Overcurrent Relays øA, øB, øC A55 CB-F-1A-A EDE-A55-CT Current Transformers (300/5) A55 CB-F-1A-A EDE-A55-AM Ammeter A55 CB-F-1A-A EDE-A55-AS Ammeter Switch A55 CB-F-1A-A EDE-A55-ATR Transducer A55 CB-F-1A-A EDE-A55-TD1 CT Test Device A55 CB-F-1A-A EDE-A55-51GS Ground Sensor Relay A55 CB-F-1A-A EDE-ZL-9706 Indicating Lights F80 CB-F-3A-A 8 EDE-SWG-5 4160 V Feed to 480 V Transformer EDE-X-5B for Substation Bus EDE-US-52 310007 A 310442 CB-F-1A-A X X X - A63 EDE-A63-52 4160 V Circuit Breaker A63 CB-F-1A-A A63-AC1 A63-F80/1 310102 A63a A63g A63b A63c A63d CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-SWG-5 EDE-SWG-6 EDE-X-5D EDE-US-62 EDE-A63-FU Fuses A63 CB-F-1A-A EDE-CS-9703 Control Switch A63 CB-F-1A-A EDE-A63-G,R,W Indicating Lights A63 CB-F-1A-A EDE-SS-9703 Selector Switch A63 CB-F-1A-A EDE-A63-52H Truck Operated Contact A63 CB-F-1A-A EDE-A63-86 Lockout Relay A63 CB-F-1A-A EDE-A63-TD2 Lockout Relay Test Device A63 CB-F-1A-A EDE-A63-50/51 Inst/Time Overcurrent Relays øA, øB, øC A63 CB-F-1A-A EDE-A63-CT Current Transformers (300/5) A63 CB-F-1A-A EDE-A63-AM Ammeter A63 CB-F-1A-A EDE-A63-AS Ammeter Switch A63 CB-F-1A-A EDE-A63-ATR Transducer A63 CB-F-1A-A EDE-A63-TD1 CT Test Device A63 CB-F-1A-A EDE-A63-51GS Ground Sensor Relay A63 CB-F-1A-A EDE-ZL-9703 Indicating Lights F80 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -14 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 EDE-SWG-5 4160 V Feed to 480 V Transformer EDE-X-5E for Substation Bus EDE-US-53 310007 A 310442 CB-F-1A-A X X X - A60 EDE-A60-52 4160 V Circuit Breaker A60 CB-F-1A-A A60-AF1 A60-F80/1 310102 A60a A60g A60b A60c A60d CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-SWG-5 EDE-SWG-6 EDE-X-5F EDE-US-63 EDE-A60-FU Fuses A60 CB-F-1A-A EDE-CS-9742 Control Switch A60 CB-F-1A-A EDE-A60-G,R,W Indicating Lights A60 CB-F-1A-A EDE-SS-9742 Selector Switch A60 CB-F-1A-A EDE-A60-52H Truck Operated Contact A60 CB-F-1A-A EDE-A60-86 Lockout Relay A60 CB-F-1A-A EDE-A60-TD2 Lockout Relay Test Device A60 CB-F-1A-A EDE-A60-50/51 Inst/Time Overcurrent Relays øA, øB, øC A60 CB-F-1A-A EDE-A60-CT Current Transformers (300/5) A60 CB-F-1A-A EDE-A60-AM Ammeter A60 CB-F-1A-A EDE-A60-AS Ammeter Switch A60 CB-F-1A-A EDE-A60-ATR Transducer A60 CB-F-1A-A EDE-A60-TD1 CT Test Device A60 CB-F-1A-A EDE-A60-51GS Ground Sensor Relay A60 CB-F-1A-A EDE-ZL-9742 Indicating Lights F80 CB-F-3A-A 10 EDE-US-51 480 V Bus 51 Unit Substation 310013 A 310442 CB-F-1A-A X X X - AB2 EDE-AB2-52 480 V AC Circuit Breaker AB2 CB-F-1A-A 310103 AB2a AB2b CBA-FN-19 CBA-FN-20 EDE-X-5A EDE-US-61 EDE-X-5A 4160-480 V Distribution Transformer AB1 CB-F-1A-A EDE-AB3-FU Fuses AB3 CB-F-1A-A EDE-AB1-LA 6 KV Lightning Arrestors (3) AB1 CB-F-1A-A EDE-AB2-CT Current Transformers (2000/5) AB2 CB-F-1A-A EDE-AB3-AM Ammeter AB3 CB-F-1A-A EDE-AB3-AS Ammeter Switch AB3 CB-F-1A-A 11 EDE-US-52 480 V Bus 52 Unit Substation 310013 A 310442 CB-F-1A-A X X X - AC2 EDE-AC2-52 480 V AC Circuit Breaker AC2 CB-F-1A-A 310103 AC2a AC2b CBA-FN-19 CBA-FN-20 EDE-X-5B EDE-US-62 EDE-X-5B 4160-480 V Distribution Transformer AC1 CB-F-1A-A EDE-AC3-FU Fuses AC3 CB-F-1A-A EDE-AC1-LA 6 KV Lightning Arrestors (3) AC1 CB-F-1A-A EDE-AC2-CT Current Transformers (2000/5) AC2 CB-F-1A-A EDE-AC3-AM Ammeter AC3 CB-F-1A-A EDE-AC3-AS Ammeter Switch AC3 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -15 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 12 EDE-US-53 480 V Bus 53 Unit Substation 310051 A 310442 CB-F-1A-A X X X - AF2 EDE-AF2-52 480 V AC Circuit Breaker AF2 CB-F-1A-A 310103 AF2a AF2c CBA-FN-19 CBA-FN-20 EDE-X-5E EDE-US-63 EDE-X-5E 4160-480 V Distribution Transformer AF1 CB-F-1A-A EDE-AF3-FU Fuses AF3 CB-F-1A-A EDE-AF1-LA 6 KV Lightning Arrestors (3) AF1 CB-F-1A-A EDE-AF2-CT Current Transformers (2000/5) AF2 CB-F-1A-A EDE-AF3-AM Ammeter AF3 CB-F-1A-A EDE-AF3-AS Ammeter Switch AF3 CB-F-1A-A 13 EDE-US-51 480 V Feed to 460 V Motor Control Center 512 310013 A 310442 CB-F-1A-A X X X - AB6 EDE-AB6-52 480 V AC Circuit Breaker AB6 CB-F-1A-A AB6-B10 AB6-B10/1 310103 AB6 AB6 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-612 14 EDE-US-51 480 V Feed to 460 V Motor Control Center 514 310013 A 310442 CB-F-1A-A X X X - A94 EDE-A94-52 480 V AC Circuit Breaker A94 CB-F-1A-A A94-C11 310103 A94 A94 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-614 15 EDE-US-51 480 V Feed to 460 V Motor Control Center 515 310013 A 310442 CB-F-1A-A X X X - AX8 EDE-AX8-52 480 V AC Circuit Breaker AX8 CB-F-1A-A AX8-B4D AX8-B4D/1 310103 AX8 AX8 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-615 16 EDE-US-52 480 V Feed to 460 V Motor Control Center 521 310013 A 310442 CB-F-1A-A X X X - AC8 EDE-AC8-52 480 V AC Circuit Breaker AC8 CB-F-1A-A AC8-B13 AC8-B13/1 310103 AC8 AC8 CBA-FN-19 CBA-FN-20 EDE-US-52 EDE-US-62 EDE-MCC-621 17 EDE-US-52 480 V Feed to 460 V Motor Control Center 522 310013 A 310442 CB-F-1A-A X X X - AW9 EDE-AW9-52 480 V AC Circuit Breaker AW9 CB-F-1A-A AW9-D12 AW9-G81/1 AW9-G81 F80-G81 310103 AW9a AW9e AW9b AW9c CBA-FN-19 CBA-FN-20 EDE-US-52 EDE-US-62 EDE-MCC-622 EDE-CS-9787-2 Control Switch with Indication G81 CB-F-1A-A EDE-SS-9787 Selector Switch G81 CB-F-1A-A EDE-AW9-52H Truck Operated Contact AW9 CB-F-1A-A EDE-AW9-FU Fuses AW9 CB-F-1A-A EDE-CS-9787-1 Control Switch with Indication F80 CB-F-3A-A EDE-AW9-G,R Indicating Lights AW9 CB-F-1A-A 18 EDE-US-52 480 V Feed to Motor Control Center 523 310013 A 310442 CB-F-1A-A X X X - AF4 EDE-AF4-52 480 V AC Circuit Breaker AF4 CB-F-1A-A AF4-C99 AF4-C99/1 310103 AF4 AF4 CBA-FN-19 CBA-FN-20 EDE-US-52 EDE-US-63 EDE-MCC-631 19 EDE-US-53 480 V Feed to Motor Control Center 531 310051 A 310442 CB-F-1A-A X X X - AB8 EDE-AB8-52 480 V AC Circuit Breaker AB8 CB-F-1A-A AB8-B12 AB8-B12/1 310103 AB8 AB8 CBA-FN-19 CBA-FN-20 EDE-US-53 EDE-US-63 EDE-MCC-631 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -16 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 20 EDE-US-51 Grounding Transformer 310012 A 310442 CB-F-1A-A X X X - AB3 EDE-AB3-XFMR 3-1ø KVA Transformers AB3 CB-F-1A-A 310103 AB3b - CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 GRD XFMR EDE-AB3-FU Fuses AB3 CB-F-1A-A EDE-AB3-RES Grounding Resistor AB3 CB-F-1A-A EDE-AB3-VM Ground Voltmeters (3) AB3 CB-F-1A-A EDE-AB3-64 Ground Relay AB3 CB-F-1A-A 21 EDE-US-52 Grounding Transformer 310013 A 310442 CB-F-1A-A X X X - AC3 EDE-AC3-XFMR 3-1ø KVA Transformers AC3 CB-F-1A-A 310103 AC3b - CBA-FN-19 CBA-FN-20 EDE-US-52 EDE-US-62 GRD XFMR EDE-AC3-FU Fuses AC3 CB-F-1A-A EDE-AC3-RES Grounding Resistor AC3 CB-F-1A-A EDE-AC3-VM Ground Voltmeters (3) AC3 CB-F-1A-A EDE-AC3-64 Ground Relay AC3 CB-F-1A-A 22 EDE-US-53 Grounding Transformer 310051 A 310442 CB-F-1A-A X X X - AF3 EDE-AF3-XFMR 3-1ø KVA Transformers AF3 CB-F-1A-A 310103 AF3b - CBA-FN-19 CBA-FN-20 EDE-US-53 EDE-US-63 GRD XFMR EDE-AF3-FU Fuses AF3 CB-F-1A-A EDE-AF3-RES Grounding Resistor AF3 CB-F-1A-A EDE-AF3-VM Ground Voltmeters (3) AF3 CB-F-1A-A EDE-AF3-64 Ground Relay AF3 CB-F-1A-A 23 EDE-I-1E Uninterruptible Power Supply 310043 A 310442 CB-F-1A-A X X X - HF5 EDE-DD3-52 460 V AC Circuit Breaker DD3 CB-F-1A-A DD3-HF5/1 DM7-HF5/1 310105 DD3a DD3b CBA-FN-19 CBA-FN-20 EDE-MCC-512 EDE-SWG-11A EDE-I-1F EDE-DM7-72 125 V DC Circuit Breaker DM7 CB-F-1A-A EDE-HF5/2-52 460 V AC Inc. Line Circuit Breaker HF5 CB-F-1A-A EDE-HF5/1-72 125 V DC Inc. Line Circuit Breaker HF5 CB-F-1A-A EDE-HF5/3-52 120 V AC Output Circuit Breaker HF5 CB-F-1A-A 23A EDE-CP-1E Static Transfer Switch 310043 A 310442 CB-F-1A-A X X X - E1Y EDE-E1Y-F1 300 A, 600 V Fuse E1Y CB-F-1A-A E1Y-HF5 E1Y-HF5/1 310105 DD3a DD3b EDE-I-1E CBA-FN-19 CBA-FN-20 EDE-CP-1F 24 EDE-PP-1E Vital Instrument Bus 310043 A 310442 CB-F-1A-A X X X - EH9 EDE-EH9/NC-52 120 V AC Circuit Breaker - Inc. Feed from EDE-CP-1E (Norm. Closed) EH9 CB-F-1A-A EH9-E1Y 310105 DD3a DD3b EH9a CBA-FN-19 CBA-FN-20 EDE-CP-1E EDE-PP-1F 25 EDE-PP-11E Vital Instrument Bus 310043 A 310442 CB-F-1A-A X X X - E1S EDE-EH9/13-52 120 V AC Circuit Breaker EH9 CB-F-1A-A E1S-EH9 310105 DD3a DD3b E1Sa CBA-FN-19 CBA-FN-20 EDE-PP-1E EDE-PP-11F SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -17 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 26 ED-X-14J 480-120/240 V Transformer 310026 A 310691 ET-F-1A-A X X X - EG4 ED-BOM-52 460 V AC Circuit Breaker BOM CB-F-1A-A BOM-EG4 310104 BOM CBA-FN-19 CBA-FN-20 EDE-MCC-531 CAH-FN-1C CAH-FN-1E CAH-FN-1F ED-X-16A 27 ED-PP-8J 120/240 V Distribution Panel 310026 A 310691 ET-F-1A-A X X X - E9L ED-X-14J Transformer EG4 ET-F-1A-A EG4-E9L 310104 BOM CAH-FN-1C CAH-FN-1E CAH-FN-1F ED-X-14J ED-PP-8B ED-E9L-52 250 V AC Circuit Breaker (Main) E9L ET-F-1A-A 310106 E9La 28 Deleted 29 EDE-BC-1A 125 V DC Battery Charger 310042 A 310442 CB-F-1A-A X X X - HR5 EDE-DB1-52 460 V AC Circuit Breaker DB1 CB-F-1A-A DB1-HR2 DB1-HR5 310107 DB1a DB1f DB1b DB1c CBA-FN-19 CBA-FN-20 EDE-MCC-512 EDE-BC-1B EDE-DB1-42 Contactor DB1 CB-F-1A-A EDE-DB1-42X Auxiliary Relay DB1 CB-F-1A-A DG-HR2-HR9(K20) EPS Relay HR2 CB-F-1A-A EDE-HR5/1-52 460 V AC Circuit Breaker - Incoming Feed HR5 CB-F-1A-A EDE-DB1-FU Fuse DB1 CB-F-1A-A 30 EDE-B-1A 125 V DC Battery 310042 A 310442 CB-F-1D-A X X X - HV4 EDE-J75-FU-1,2,3,4 1600A Fuses J75 CB-F-1A-A HV4-J75 HV4-J75/1 310107 DB1a DB1f DB1b DB1c CBA-FN-19 CBA-FN-20 CBA-FN-21A EDE-BC-1A EDE-SWG-11A EDE-B-1B EDE-J75-SH 1000A, 100 MV Shunt J75 CB-F-1A-A EDE-J75-ATR Transducer J75 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -18 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 31 EDE-SWG-11A 125 V DC Switchboard Auxiliary Buses 120 V AC and 125 V DC 310042 A 310442 CB-F-1A-A X X X - DM1 EDE-HR5/2-72 125 V DC Circuit Breaker HR5 CB-F-1A-A DM3-J75 DM3-J75/1 DM2-HR5 DM1-J75/1 G1W-J75 310107 DB1a DB1f DB1b DB1c 5a CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-B-1A EDE-BC-1A EDE-PP-1E EDE-SWG-11B EDE-DL4-72 125 V DC Circuit Breaker DL4 CB-F-1A-A EDE-DM2-72 125 V DC Circuit Breaker DM2 CB-F-1A-A EDE-DM3-72 125 V DC Circuit Breaker DM3 CB-F-1A-A EDE-DM1-FU-1&2 125 V DC 15A Fuses DM1 CB-F-1A-A EDE-DM1-27BL Undervoltage Relay DM1 CB-F-1A-A EDE-DM1-27BLL Undervoltage Relay DM1 CB-F-1A-A EDE-DM1-VM DC Voltmeter DM1 CB-F-1A-A EDE-DM1-VTR Voltage Transducer DM1 CB-F-1A-A EDE-DM1-DIO Diodes DM1 CB-F-1A-A EDE-DM1-XS Selector Switch DM1 CB-F-1A-A EDE-DM1-AMY Ammeter Relay DM1 CB-F-1A-A EDE-EH9/5-52 120 V AC Circuit Breaker EH9 CB-F-1A-A DM1-EH9 310105 EH9a EH9b EDE-DM1-62BL Timing Relay DM1 CB-F-1A-A EDE-DM1-62BLL Timing Relay DM1 CB-F-1A-A EDE-DM2-72 Breaker Operated Contact DM2 CB-F-1A-A EDE-DM2-72STC Circuit Breaker Shut Trip Coil DM2 CB-F-1A-A EDE-J75-ATR Current Transducer J75 CB-F-1A-A EDE-DM1-52 120 V AC Inc. Feed Circuit Breaker DM1 CB-F-1A-A EDE-DM1-FU 120 V AC 15A and 1A Fuses DM1 CB-F-1A-A 32 EDE-PP-111A 125 V DC Distribution Panel 310042 A 310442 CB-F-1A-A X X X - E93 EDE-DM5-72 125 V DC Circuit Breaker DM5 CB-F-1A-A DM5-E93 310107 DB1a DB1f E93a CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-PP-111B EDE-E93-72 125 V DC Circuit Breaker (Main) E93 CB-F-1A-A 33 EDE-PP-112A 125 V DC Distribution Panel 310042 A 310442 CB-F-1A-A X X X - E87 EDE-DM8-72 125 V DC Circuit Breaker DM8 CB-F-1A-A DM8-E87 310107 DB1a DB1f E87a CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-PP-112B EDE-E87-72 125 V DC Circuit Breaker (Main) E87 CB-F-1A-A 34 EDE-PP-113A 125 V DC Distribution Panel 310042 A 310442 CB-F-1A-A X X X - E2T EDE-DM0-72 125 V DC Circuit Breaker DM0 CB-F-1A-A DM0-E2T 310107 DB1a DB1f DB1b E2Ta CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-PP-113B EDE-E2T-72 125 V DC Circuit Breaker (Main) E2T CB-F-1A-A 35 EDE-SWG-5 4160 V SWGR 125 V DC Control Bus A 310442 CB-F-1A-A X X X - A53 EDE-E93/1-72 125 V DC Circuit Breaker E93 CB-F-1A-A A53-E93 310107 E93a E93b CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-SWG-6 EDE-A53-8 125 V DC Circuit Breaker (Main) A53 CB-F-1A-A 310102 5a, 5f, 5g, 5h SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -19 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 36 EDE-US-51 480 V Unit Substation 125 V DC Control Bus A 310442 CB-F-1A-A X X X - AB3 EDE-E93/2-72 125 V DC Circuit Breaker E93 CB-F-1A-A AB3-E93 310107 E93a E93b CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-US-61 EDE-AB3-8 125 V DC Circuit Breaker (Main) AB3 CB-F-1A-A 310103 5m 37 EDE-US-52 480 V Unit Substation 125 V DC Control Bus A 310442 CB-F-1A-A X X X - AC3 EDE-E93/3-72 125 V DC Circuit Breaker E93 CB-F-1A-A AC3-E93 310107 E93a E93b CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-US-62 EDE-AC3-8 125 V DC Circuit Breaker (Main) AC3 CB-F-1A-A 310103 5n 38 EDE-US-53 480 V Unit Substation 125 V DC Control Bus A 310442 CB-F-1A-A X X X - AF3 EDE-E93/4-72 125 V DC Circuit Breaker E93 CB-F-1A-A AF3-E93 310107 E93a E93b CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-US-63 EDE-AF3-8 125 V DC Circuit Breaker (Main) AF3 CB-F-1A-A 310103 5o 39 DG-CP-75A Diesel Generator 1A Control Panel Cubicle 3 125 V DC Supply 310010 310042 A 310524 DG-F-2A-A X X X - G10 EDE-DM9-72 125 V DC Circuit Breaker DM9 CB-F-1A-A DM9-G10 310102 DM9a DM9b DAH-FN-25A DAH-FN-26A EDE-SWG-11A CBA-FN-19 CBA-FN-20 DG-CP-76A DG-G10-72 125 V DC Circuit Breaker (Main) G10 DG-F-2A-A 310107 DB1a 40 ED-US-11 480 V Unit Substation 125 V DC Control Bus 310002 310011 A 310442 CB-F-1A-A X X X - AG3 EDE-E97/13-72 125 V DC Circuit Breaker (Main) E97 NES-F-1A-Z AG3-E97 310107 E97a E97b EDE-AG1-X-4A CBA-FN-19 CBA-FN-20 ED-US-23 EDE-AG3-72 125 V DC Circuit Breaker AG3 CB-F-1A-A 310103 5a 41 ED-US-23 480 V Unit Substation 125 V DC Control Bus 310002 310011 B 310442 CB-F-1A-A X X X - AM3 EDE-E97/14-72 125 V DC Circuit Breaker E97 NES-F-1A-Z AM3-E97 310107 E97a E97b EDE-AM1-X-4F CBA-FN-19 CBA-FN-20 ED-US-11 EDE-AM3-72 125 V DC Circuit Breaker AM3 CB-F-1A-A 310103 5h SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -20 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 42 EDE-SWG-6 4160 V Bus E6 UAT Incoming Line SWGR 310008 B 310442 CB-F-1B-A X X X - A71 EDE-A71-52 4160 V Circuit Breaker A71 CB-F-1B-A A71-G19 A71-G19/2 A71-G20 A71-HR0 GA6-GB0/5 A71-G19/1 A71-G19/3 A71-GB4 GA0-GB3/5 GC4-GC6/5 A71-G5Y A71-G5Y/1 G19-HR0 F81-G19/G F81-G19/C F81-G19/6 G19-HR4 F81-G19/A A75-A7A A74-A7A/1 310102 A71a A71h A71b A71i A71c A71k A71d A71e CBA-FN-32 CBA-FN-33 ED-X-2B EDE-PP-111B DAH-FN-25B DAH-FN-26B EDE-SWG-5 UAT EDE-CS-9719-2 Control Switch A71 CB-F-1B-A EDE-CS-9719-3 Control Switch with Indication G19 DG-F-2B-A EDE-A71-G,R,W Indicating Lights A71 CB-F-1B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-A71-52H Truck Operated Contact A71 CB-F-1B-A EDE-A71-FU Fuses A71 CB-F-1B-A EDE-A71-CT1 Current Transformers (2000/5) A71 CB-F-1B-A EDE-A71-TD-1 CT Test Device A71 CB-F-1B-A EDE-A71-AM Ammeter A71 CB-F-1B-A EDE-A71-AS Ammeter Switch A71 CB-F-1B-A EDE-A71-ATR Transducer A71 CB-F-1B-A EDE-A71-CT2 Current Transformers (4000/5) A71 CB-F-1B-A EDE-A87-PT Potential Transformer A87 CB-F-1B-A EDE-A71-TD-3 PT Test Device A71 CB-F-1B-A EDE-A71-VM Voltmeter A71 CB-F-1B-A EDE-A71-86 Lockout Relay A71 CB-F-1B-A EDE-A74-52S Mechanically Operated Contact A74 CB-F-1B-A EDE-A72-52S Mechanically Operated Contact A72 CB-F-1B-A DG-G20-25Y1 Auxiliary Sync Check Relay G20 DG-F-2B-A EDE-A73-25U Synchronizing Check Relay A73 CB-F-1B-A EDE-SS-9719-1 Selector Switch G5Y DG-F-2B-A EDE-CS-9717-3 Control Switch G19 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-A72-86 Lockout Relay A72 CB-F-1B-A EDE-A89-86B Lockout Relay A89 CB-F-1B-A ED-86SB/2/1X -1 Lockout Relay GA0 TB-F-1C-Z ED-86-2/2/B3 Lockout Relay GA6 TB-F-1C-Z ED-86UB/2/1X -2A Lockout Relay GA8 TB-F-1C-Z ED-86UB/2/1X -2B Lockout Relay GA8 TB-F-1C-Z ED-86BF-2/2/52/TG1 Lockout Relay GA9 TB-F-1C-Z ED-86GT/2/TG -1 Lockout Relay GA9 TB-F-1C-Z ED-86-1/2/B3 Lockout Relay GB0 TB-F-1C-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -21 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 42 EDE-SWG-6 (Continued) ED-86BF-2/2H Lockout Relay GB3 TB-F-1C-Z ED-86BF-2/2E Lockout Relay GB4 TB-F-1C-Z ED-86UP/2/1X -2A Lockout Relay GC2 TB-F-1C-Z ED-86UP/2/1X -2B Lockout Relay GC2 TB-F-1C-Z ED-86BF-1/2/52/TG1 Lockout Relay GC3 TB-F-1C-Z ED-86SP/2/1X -1 Lockout Relay GC4 TB-F-1C-Z ED-86BF-1/2H Lockout Relay GC6 TB-F-1C-Z ED-86BF-1/2E Lockout Relay GC7 TB-F-1C-Z DG-HR0-RM0 EPS Auxiliary Relay HR0 CB-F-1B-A EDE-A71-3 Interposing Relay for SWYD Lockout Relays A71 CB-F-1B-A EDE-A71-TD-2 Lockout Relay Test Device (A71 -86) A71 CB-F-1B-A EDE-A71-TD-4 Interposing Relay Test Device (A71 -3) A71 CB-F-1B-A EDE-CS-9719-4 Control Switch F81 CB-F-3A-A ED-GA0-TD-2 Lockout Relay Test Device (86SB/2/1X -1) GA0 TB-F-1C-Z ED-GA6-TD-2 Lockout Relay Test Device (86 -2/2/B3) GA6 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2A) GA8 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2B) GA8 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86BF -2/2/52/TG1) GA9 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86GT/2/TG -1) GA9 TB-F-1C-Z ED-GB0-TD-2 Lockout Relay Test Device (86 -1/2/B3) GB0 TB-F-1C-Z ED-GB3-TD-2 Lockout Relay Test Device (86BF -2/2H) GB3 TB-F-1C-Z ED-GB4-TD-2 Lockout Relay Test Device (86BF -2/2E) GB4 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2A) GC2 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2B) GC2 TB-F-1C-Z ED-GC3-TD-2 Lockout Relay Test Device (86BF -1/2/52/TG1) GC3 TB-F-1C-Z ED-GC4-TD-2 Lockout Relay Test Device (86SP/2/1X -1) GC4 TB-F-1C-Z ED-GC6-TD-2 Lockout Relay Test Device (86BF -1/2H) GC6 TB-F-1C-Z ED-GC7-TD-2 Lockout Relay Test Device (86BF -1/2E) GC7 TB-F-1C-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -22 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 42 EDE-SWG-6 (Continued) EDE-A71-51 Time Overcurrent Relays øA, øB, øC A71 CB-F-1B-A EDE-A71-51GS Ground Sensor Relay A71 CB-F-1B-A EDE-SNS-9737-1 Synchronizing Switch F81 CB-F-3A-A EDE-CS-9719-1 Control Switch with Indicating Lights F81 CB-F-3A-A DG-HR4-RM0 EPS Auxiliary Relay HR4 CB-F-1B-A EDE-CS-9717-1 Control Switch F81 CB-F-3A-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A 43 EDE-SWG-6 Grounding Transformer 310008 B 310442 CB-F-1B-A X X X - A87 EDE-A87-XFMR 3-1ø 15 KVA Transformers A87 CB-F-1B-A 310102 A87a CBA-FN-32 CBA-FN-33 EDE-SWG-6 EDE-SWG-5 GRD XFMR EDE-A87-FU 3-10A Fuses A87 CB-F-1B-A EDE-A87-52 120 V AC Circuit Breaker A87 CB-F-1B-A EDE-A87-RES Grounding Resistor A87 CB-F-1B-A EDE-A87-64 Ground Relay A87 CB-F-1B-A EDE-A87-TD-3 VM Test Device A87 CB-F-1B-A EDE-A87-VM (3) Ground Voltmeters A87 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -23 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 44 EDE-SWG-6 4160 V Bus E6 RAT Incoming Line SWGR 310008 B 310442 CB-F-1B-A X X X - A72 EDE-A72-52 4160 V Circuit Breaker A72 CB-F-1B-A A72-G19 A72-G19/2 A72-G20 A72-HR4 GA7-GB7/5 GE6-GE7/5 A72-G19/1 A72-G19/3 A72-GB7 A72-HR0 GC1-GC0/5 A72-G5Y A72-G5Y/1 F81-G19/H A72-F81 F81-G19/B F81-G19/4 A74-A7A/2 310102 A72a A72j A72b A72k A72c A72l A72d A72e CBA-FN-32 CBA-FN-33 ED-X-3B EDE-PP-111B DAH-FN-25B DAH-FN-26B EDE-SWG-5 RAT EDE-CS-9717-2 Control Switch A72 CB-F-1B-A EDE-CS-9717-3 Control Switch with Indication G19 DG-F-2B-A EDE-A72-G,R,W Indicating Lights A72 CB-F-1B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-A72-52H Truck Operated Contact A72 CB-F-1B-A EDE-A72-FU Fuses A72 CB-F-1B-A EDE-A72-27/59 Under/Over Voltage Relay A72 CB-F-1B-A EDE-A72-27/59X1,X2 Under/Over Voltage Auxiliary Relay A72 CB-F-1B-A EDE-A72-CT-1 Current Transformer (2000/5) A72 CB-F-1B-A EDE-A72-52Z Time Delay Relay A72 CB-F-1B-A EDE-SS-9717-1 Selector Switch G5Y DG-F-2B-A EDE-CS-9719-3 Control Switch G19 DG-F-2B-A EDE-A72-TD-1 CT Test Device A72 CB-F-1B-A EDE-A72-AM Ammeter A72 CB-F-1B-A EDE-A72-AS Ammeter Switch A72 CB-F-1B-A EDE-A72-ATR Transducer A72 CB-F-1B-A EDE-A72-CT-2 Current Transformer (4000/5) A72 CB-F-1B-A EDE-A73-PT Potential Transformer A73 CB-F-1B-A EDE-A72-TD-3 PT Test Device A72 CB-F-1B-A EE-A72-VM Voltmeter A72 CB-F-1B-A EDE-A72-52S Mechanically Operated Contact A72 CB-F-1B-A EDE-A89-86B Lockout Rela y A89 CB-F-1B-A EDE-A72-86 Lockout Relay A72 CB-F-1B-A EDE-A71-86 Lockout Relay A71 CB-F-1B-A DG-HR4-RM0 EPS Auxiliary Relay HR4 CB-F-1B-A DG-HR0-RM0 EPS Auxiliary Relay HR0 CB-F-1B-A EDE-A71-52S Mechanically Operated Contact A71 CB-F-1B-A EDE-A74-52S Mechanically Operated Contact A74 CB-F-1B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A DG-G20-25Y Auxiliary Synchronizing Check Relay G20 DG-F-2B-A EDE-A73-25RX Auxiliary Synchronizing Check Relay A73 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -24 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 44 EDE-SWG-6 (Continued) EDE-A73-25R Synchronizing Check Relay A73 CB-F-1B-A EDE-CS-9717-4 Control Switch F81 CB-F-3A-A EDE-CS-9719-1 Control Switch F81 CB-F-3A-A EDE-A72-62 Time Delay Relay A72 CB-F-1B-A EDE-A72-3 Interposing Relay for SWYD Lockout Relays A71 CB-F-1B-A EDE-A72-TD-2 Lockout Relay Test Device (A72 -86) A72 CB-F-1B-A EDE-A72-TD-4 Interposing Relay Test Device (A72 -3) A72 CB-F-1B-A EDE-SNS-9737-1 Synchronizing Switch F81 CB-F-3A-A EDE-CS-9717-1 Control Switch with Indicating Light F81 CB-F-3A-A EDE-A73-62BX Auxiliary Latch Relay A73 CB-F-1B-A EDE-A73-25R Synchronizing Check Relay A73 CB-F-1B-A EDE-A73-27RB-1 Residual Undervoltage Relay A73 CB-F-1B-A EDE-A73-27RB-2 Residual Undervoltage Relay A73 CB-F-1B-A EDE-A72-62X Auxiliary Relay A72 CB-F-1B-A ED-86RB/2/1X -3A Lockout Relay GA7 TB-F-1C-Z ED-86-2/2/B2 Lockout Relay GB7 TB-F-1C-Z ED-86-1/2/B2 Lockout Relay GC0 TB-F-1C-Z ED-86RP/2/1X -3A Lockout Relay GC1 TB-F-1C-Z ED-86RP/2/1X -3B Lockout Relay GE6 TB-F-1C-Z ED-86RB/2/1X -3B Lockout Relay GE7 TB-F-1C-Z ED-GA7-TD-2 Lockout Relay Test Device (86RB/2/1X -3A) GA7 TB-F-1C-Z ED-GB7-TD-2 Lockout Relay Test Device (86 -2/2/B2) GB7 TB-F-1C-Z ED-GC0-TD-2 Lockout Relay Test Device (86 -1/2/B2) GC0 TB-F-1C-Z ED-GC1-TD-2 Lockout Relay Test Device (86RP/2/1X -3A) GC1 TB-F-1C-Z ED-GE6-TD-2 Lockout Relay Test Device (86RP/2/1X -3B) GE6 TB-F-1C-Z ED-GE7-TD-2 Lockout Relay Test Device (86RB/2/1X -3B) GE7 TB-F-1C-Z EDE-A72-51 Time Overcurrent Relays øA, øB, øC A72 CB-F-1B-A EDE-A72-51GS Ground Sensor Relay A72 CB-F-1B-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -25 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 45 EDE-SWG-6 4160 V Bus E6 PT Compartment 310008 B 310442 CB-F-1B-A X X X - A73 EDE-A73-PT Potential Transformer A73 CB-F-1B-A A73-AE2 A73-G19 A73-HR4 AE2-AF7 AF7-EE6 AW2-EE6 F81-G19/5 A73-FB0 A74-A7A/4 A74-A7A/5 A75-A7A/1 A75-A7A/2 310102 A73a A73d A73e A73h CBA-FN-32 CBA-FN-33 EDE-SWG-6 EDE-PP-111B DAH-FN-25B DAH-FN-26B EDE-SWG-5 PT EDE-A73-VM Voltmeter A73 CB-F-1B-A EDE-A73-VS Voltmeter Switch A73 CB-F-1B-A EDE-A73-TD-3 PT Test Device A73 CB-F-1B-A EDE-A73-VTR-1 Voltage Transducer A73 CB-F-1B-A EDE-A73-VTR-2 Voltage Transducer A73 CB-F-1B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-A73-25U Synchronizing Check Relay A73 CB-F-1B-A EDE-A73-25R Synchronizing Check Relay A73 CB-F-1B-A EDE-A74-52S Mechanically Operated Contact A74 CB-F-1B-A EDE-A73-27B-1 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-27B-2 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-TS-3 UV Relays Test Switch A73 CB-F-1B-A EDE-A73-27D-1 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-27D-1-RES Resistor A73 CB-F-1B-A EDE-A73-27D-2 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-27D-2-RES Resistor A73 CB-F-1B-A EDE-A73-TS-1 UV Relays Test Switch A73 CB-F-1B-A EDE-A72-27RB-1,2 Residual Undervoltage Relay A72 CB-F-1B-A EDE-A73-62B Time Delay Relay A73 CB-F-1B-A EDE-A73-62B-RES Resistor A73 CB-F-1B-A EDE-A73-TS-4 Test Switch EDE -62B A73 CB-F-1B-A EDE-A73-62BX-1 Auxiliary Relay A73 CB-F-1B-A EDE-A73-62BX Auxiliary Latch Relay A73 CB-F-1B-A EDE-A71-52S Mechanically Operated Contact A71 CB-F-1B-A EDE-AW3-94-5 Undervoltage Tripping Relay AW3 CB-F-1B-A EDE-A72-27/59X1 Under/Over Voltage Auxiliary Relay A72 CB-F-1B-A EDE-AF8-94-4 Undervoltage Tripping Relay AF8 CB-F-1B-A DG-HR4-RM0 EPS Auxiliary Relay HR4 CB-F-1B-A EDE-A73-94-1A Undervoltage Tripping Relay A73 CB-F-1B-A EDE-A73-94-1B Undervoltage Tripping Relay A73 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -26 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 45 EDE-SWG-6 (Continued) EDE-A73-94-2 Undervoltage Tripping Relay A73 CB-F-1B-A EDE-AE3-94-3 Undervoltage Tripping Relay AE3 CB-F-1B-A EDE-EE6-94-6 Tripping Relay EE6 CB-F-1B-A EDE-A73-FU 10A Fuses A73 CB-F-1B-A EDE-A73-62D Time Delay Relay A73 CB-F-1B-A EDE-A73-62D-RES Resistor A73 CB-F-1B-A EDE-A73-TS-2 Test Switch Relay 62D A73 CB-F-1B-A EDE-A73-62DX Auxiliary Relay A73 CB-F-1B-A EDE-SNS-9737-1 Synchronizing Switch F81 CB-F-3A-A EDE-A73-FU 3A Fuse A73 CB-F-1B-A EDE-FB0-K609B SI Sig. Act. Auxiliary Relay FB0 CB-F-3A-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -27 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 46 EDE-SWG-6 4160 V Bus E6 DG-1B Incoming Line SWGR 310010 310008 B 310442 CB-F-1B-A X X X - A74 EDE-A74-52 4160 V Circuit Breaker A74 CB-F-1B-A A74-G18/2 A74-G18/3 A74-G18/4 A74-G19 A74-G19/1 A74-G19/2 A74-HP1 G18-G30/7 A74-G18/8 F81-G18/3 A74-F81 A74-F81/1 A74-FB0 A74-HR0 A74-A7A/3 310102 A74a A74k A74b A74n A74c A74d A74e A74f CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B EDE-PP-111B DG-DG-1B EDE-SWG-5 DG-1A EDE-CS-9710-2 Control Switch A74 CB-F-1B-A EDE-CS-9710-3 Control Switch with Indication G18 DG-F-2B-A EDE-A74-G,R,W Indicating Lights A74 CB-F-1B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-A74-52H Truck Operated Contact A74 CB-F-1B-A EDE-A74-FU Fuses A74 CB-F-1B-A EDE-A74-CT Current Transformers (2000/5) A74 CB-F-1B-A EDE-A74-DCT Differential Current Transformers (2000/5) A74 CB-F-1B-A DG-HP1-DCT DG-1B Neutral Differential Current Transformers (2000/5) HP1 DG-F-2B-A DG-G18-CT Auxiliary Current Transformer (5:10) G18 DG-F-2B-A EDE-A74-AM Ammeter A74 CB-F-1B-A EDE-A74-AS-1 Ammeter Switch A74 CB-F-1B-A EDE-A74-ATR-1 Current Transducer A74 CB-F-1B-A EDE-A74-ATR-2 Current Transducer A74 CB-F-1B-A EDE-AM-9710-2 Ammeter G18 DG-F-2B-A EDE-G18-AS Ammeter Switch G18 DG-F-2B-A DG-SM-9587 Governor Control (2301A) G18 DG-F-2B-A EDE-A89-PT DG-1B Inc. Line Pot. Transformer (2) 4200-120 V A89 CB-F-1B-A EDE-A89-VM Voltmeter A89 CB-F-1B-A EDE-A89-VS Voltmeter Switch A89 CB-F-1B-A EDE-A89-TD-3 PT Test Device A89 CB-F-1B-A EDE-A89-VTR-1 Voltage Transducer A89 CB-F-1B-A EDE-A89-VTR-2 Voltage Transducer A89 CB-F-1B-A EDE-A74-27DG Undervoltage Relay A74 CB-F-1B-A EDE-A89-FTR-1 Frequency Transducer A89 CB-F-1B-A EDE-A89-FTR-2 Frequency Transducer A89 CB-F-1B-A EDE-A89-W/WH-TR Watt/Watthour Transducer A89 CB-F-1B-A EDE-A89-W/TR Watt Transducer A89 CB-F-1B-A EDE-A89-VAR-TR Var Transducer A89 CB-F-1B-A EDE-A74-TS Test Start Switch A74 CB-F-1B-A EDE-A74-52Z Time Delay Relay A74 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -28 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 46 EDE-SWG-6 EDE-A74-81-RES Resistor A74 CB-F-1B-A EDE-A89-86B Lockout Relay A89 CB-F-1B-A EDE-A89-86DB Back-Up Lockout Relay A89 CB-F-1B-A EDE-A89-W Indicating Lights (A89-86B & A89 -86DB) A89 CB-F-1B-A EDE-A74-W Indicating Light (A74-86DP) A74 CB-F-1B-A EDE-A74-86DP Primary Lockout Relay A74 CB-F-1B-A EDE-A71-86 Lockout Relay A71 CB-F-1B-A EDE-A72-86 Lockout Relay A72 CB-F-1B-A EDE-A71-52S Mechanically Operated Contact A71 CB-F-1B-A EDE-A72-52S Mechanically Operated Contact A72 CB-F-1B-A EDE-A74-52S Mechanically Operated Contact A74 CB-F-1B-A EDE-A89-RLA LOCA Seal Relay A89 CB-F-1B-A DG-G20-25Y Auxiliary Sync Check Relay G20 DG-F-2B-A EDE-A89-RS Fast Closure Relay A89 CB-F-1B-A EDE-A74-81 Frequency Relay A74 CB-F-1B-A EDE-A74-87DP Primary Differential Relay A74 CB-F-1B-A EDE-A89-51B Time Overcurrent Relays øA, øB, øC A89 CB-F-1B-A EDE-A74-81X Auxiliary Frequency Relay A74 CB-F-1B-A EDE-A89-60 Voltage Balance Relay A89 CB-F-1B-A EDE-A89-60AX Auxiliary Voltage Balance Relay A89 CB-F-1B-A EDE-A89-60BX Auxiliary Voltage Balance Relay A89 CB-F-1B-A EDE-A89-40 Loss of Field Relays øA, øB A89 CB-F-1B-A EDE-A74-40X Auxiliary Loss of Field Relay A74 CB-F-1B-A EDE-A89-32 Power Directional Relay A89 CB-F-1B-A EDE-A89-TD-1 Lockout Relay Test Device (86B) A89 CB-F-1B-A EDE-A89-TD-2 Lockout Relay Test Device (86DB) A89 CB-F-1B-A EDE-A74-TD-2 Lockout Relay Test Device (86DP) A74 CB-F-1B-A DG-G19-R43L5 & R43L6 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -29 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 46 EDE-SWG-6 (Continued) DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G30-5A Shutdown Relay G30 DG-F-2B-A EDE-A89-51V Time Overcurrent Voltage Restraint Relays øA, øB, øC A89 CB-F-1B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A EDE-A89-51GS Ground Sensor Relay A89 CB-F-1B-A EDE-A74-TD-1 Test Device A74 CB-F-1B-A EDE-CS-9710-1 Control Switch with Indication F81 CB-F-3A-A EDE-HR0-PRIX EPS Auxiliary Relay HR0 CB-F-1B-A EDE-SNS-9737-1 Synchronizing Switch F81 CB-F-3A-A EDE-A74-81X-RES Auxiliary Frequency Relay Resistors A74 CB-F-1B-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A EDE-A74-87DP Reactor Primary Differential Relay Reactor Assembly A74 CB-F-1B-A EDE-FB0-K601B SI Signal Act. Output Relay FB0 CB-F-3A-A EDE-G19-ESS Emergency Start Auxiliary Relay G19 DG-F-2B-A EDE-A74-81Y Time Delay Relay A74 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -30 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 47 DG-CP-76A Diesel Generator 1B Control Panel Cubicle 2 Synchronizing System 310010 B 310524 DG-F-2B-A X X X - G19 EDE-SS-9710 Selector Switch G18 DG-F-2B-A F81-G19/9 F81-G19/1 310102 G19/2c G19/2g 7c 7g DAH-FN-25B DAH-FN-26B EDE-SWG-11B DG-CP-75A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A DG-G19-FU 125 V DC Fuses G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-RAX Auxiliary Relay, Latch G19 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-CS-9710-3 Control Switch G18 DG-F-2B-A EDE-CS-9717-3 Control Switch G19 DG-F-2B-A EDE-CS-9719-3 Control Switch G19 DG-F-2B-A DG-G18-25DG Synchronizing Check Relay G18 DG-F-2B-A DG-G20-25Y Auxiliary Synchronizing Check Relay G20 DG-F-2B-A DG-G20-25Y1 Auxiliary Synchronizing Check Relay G20 DG-F-2B-A EDE-SNS-9737-1 Synchronizing Switch F81 CB-F-3A-A EDE-CS-9710-1 Control Switch F81 CB-F-3A-A EDE-CS-9717-1 Control Switch F81 CB-F-3A-A EDE-CS-9719-1 Control Switch F81 CB-F-3A-A EDE-A87-PT UAT X-2B Inc. Line Potential Transformer A87 CB-F-1B-A EDE-A73-PT RAT X-3B Inc. Line Potential Transformer A73 CB-F-1B-A EDE-A73-PT Bus E6 Potential Transformer A73 CB-F-1B-A EDE-A89-PT DG-1B Inc. Line Potential Transformer A89 CB-F-1B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-RAX Auxiliary Relay, Latch G19 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -31 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 47 DG-CP-76A (Continued) DG-G18-25DG Synchronizing Check Relay G18 DG-F-2B-A EDE-SYN-9711 Synchroscope G18 DG-F-2B-A EDE-ZL-9711 Synchronizing Lights G18 DG-F-2B-A EDE-VM-9711-1 Synchronizing Voltmeter Incoming G18 DG-F-2B-A EDE-VM-9711-2 Synchronizing Voltmeter Running G18 DG-F-2B-A EDE-SYN-9746 Synchroscope F81 CB-F-3A-A EDE-ZL-9746 Synchronizing Lights F81 CB-F-3A-A EDE-VM-9746-1 Voltmeter F81 CB-F-3A-A EDE-VM-9746-2 Voltmeter F81 CB-F-3A-A 48 EDE-SWG-6 4160 V Feed to 480 V Transformer EDE-X-5C for Substation Bus EDE-US-61 310008 B 310442 CB-F-1B-A X X X - A75 EDE-A75-52 4160 V Circuit Breaker A75 CB-F-1B-A A75-AD1 A75-F81/1 310102 A75a A75g A75b A75c A75d CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-SWG-6 EDE-SWG-5 EDE-X-5A EDE-US-51 EDE-A75-FU Fuses A75 CB-F-1B-A EDE-CS-9716 Control Switch A75 CB-F-1B-A EDE-A75-G,R,W Indicating Lights A75 CB-F-1B-A EDE-SS-9716 Selector Switch A75 CB-F-1B-A EDE-A75-52H Truck Operated Contact A75 CB-F-1B-A EDE-A75-86 Lockout Relay A75 CB-F-1B-A EDE-A75-TD-2 Lockout Relay Test Device A75 CB-F-1B-A EDE-A75-50/51 Inst/Time Overcurrent Relays øA, øB, øC A75 CB-F-1B-A EDE-A75-CT Current Transformers (300/5) A75 CB-F-1B-A EDE-A75-AM Ammeter A75 CB-F-1B-A EDE-A75-AS Ammeter Switch A75 CB-F-1B-A EDE-A75-ATR Transducer A75 CB-F-1B-A EDE-A75-TD-1 CT Test Device A75 CB-F-1B-A EDE-A75-51GS Ground Sensor Relay A75 CB-F-1B-A EDE-ZL-9716 Indicating Lights F81 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -32 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 49 EDE-SWG-6 4160 V Feed to 480 V Transformer EDE-X-5D for Substation Bus EDE-US-62 310008 B 310442 CB-F-1B-A X X X - A83 EDE-A83-52 4160 V Circuit Breaker A83 CB-F-1B-A A83-AE1 A83-F81/1 310102 A83a A83g A83b A83c A83d CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-SWG-6 EDE-SWG-5 EDE-X-5B EDE-US-52 EDE-A83-FU Fuses A83 CB-F-1B-A EDE-CS-9713 Control Switch A83 CB-F-1B-A EDE-A83-G,R,W Indicating Lights A83 CB-F-1B-A EDE-SS-9713 Selector Switch A83 CB-F-1B-A EDE-A83-52H Truck Operated Contact A83 CB-F-1B-A EDE-A83-86 Lockout Relay A83 CB-F-1B-A EDE-A83-TD-2 Lockout Relay Test Device A83 CB-F-1B-A EDE-A83-50/51 Inst/Time Overcurrent Relays øA, øB, øC A83 CB-F-1B-A EDE-A83-CT Current Transformers (300/5) A83 CB-F-1B-A EDE-A83-AM Ammeter A83 CB-F-1B-A EDE-A83-AS Ammeter Switch A83 CB-F-1B-A EDE-A83-ATR Transducer A83 CB-F-1B-A EDE-A83-TD-1 CT Test Device A83 CB-F-1B-A EDE-A83-51GS Ground Sensor Relay A83 CB-F-1B-A EDE-ZL-9713 Indicating Lights F81 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -33 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 50 EDE-SWG-6 4160 V Feed to 480 V Transformer EDE-X-5F for Substation Bus EDE-US-63 310008 B 310442 CB-F-1B-A X X X - A90 EDE-A90-52 4160 V Circuit Breaker A90 CB-F-1B-A A90-AF6 A90-F81/1 310102 A90a A90g A90b A90c A90d CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-SWG-6 EDE-SWG-5 EDE-X-5E EDE-US-53 EDE-A90-FU Fuses A90 CB-F-1B-A EDE-CS-9743 Control Switch A90 CB-F-1B-A EDE-A90-G,R,W Indicating Lights A90 CB-F-1B-A EDE-SS-9743 Selector Switch A90 CB-F-1B-A EDE-A90-52H Truck Operated Contact A90 CB-F-1B-A EDE-A90-86 Lockout Relay A90 CB-F-1B-A EDE-A90-TD2 Lockout Relay Test Device A90 CB-F-1B-A EDE-A90-50/51 Inst/Time Overcurrent Relays øA, øB, øC A90 CB-F-1B-A EDE-A90-CT Current Transformers (300/5) A90 CB-F-1B-A EDE-A90-AM Ammeter A90 CB-F-1B-A EDE-A90-AS Ammeter Switch A90 CB-F-1B-A EDE-A90-ATR Transducer A90 CB-F-1B-A EDE-A90-TD1 CT Test Device A90 CB-F-1B-A EDE-A90-51GS Ground Sensor Relay A90 CB-F-1B-A EDE-ZL-9743 Indicating Lights A90 CB-F-1B-A 51 EDE-US-61 480 V Bus 61 Unit Substation 310014 B 310442 CB-F-1B-A X X X - AD2 EDE-AD2-52 480 V AC Circuit Breaker AD2 CB-F-1B-A 310103 AD2a AD2b CBA-FN-32 CBA-FN-33 EDE-X-5C EDE-US-51 EDE-X-5C 4160-480 V Distribution Transformer AD1 CB-F-1B-A EDE-AD3-FU Fuses AD3 CB-F-1B-A EDE-AD1-LA 6 KV Lightning Arrestors (3) AD1 CB-F-1B-A EDE-AD2-CT Current Transformers (2000/5) AD2 CB-F-1B-A EDE-AD3-AM Ammeter AD3 CB-F-1B-A EDE-AD3-AS Ammeter Switch AD3 CB-F-1B-A 52 EDE-US-62 480 V Bus 62 Unit Substation 310014 B 310442 CB-F-1B-A X X X - AE2 EDE-AE2-52 480 V AC Circuit Breaker AE2 CB-F-1B-A 310103 AE2a AE2b CBA-FN-32 CBA-FN-33 EDE-X-5D EDE-US-52 EDE-X-5D 4160-480 V Distribution Transformer AE1 CB-F-1B-A EDE-AE3-FU Fuses AE3 CB-F-1B-A EDE-AE1-LA 6 KV Lightning Arrestors (3) AE1 CB-F-1B-A EDE-AE2-CT Current Transformers (2000/5) AE2 CB-F-1B-A EDE-AE3-AM Ammeter AE3 CB-F-1B-A EDE-AE3-AS Ammeter Switch AE3 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -34 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 53 EDE-US-63 480 V Bus 63 Unit Substation 310052 B 310442 CB-F-1B-A X X X - AF7 EDE-AF7-52 480 V AC Circuit Breaker AF7 CB-F-1B-A 310103 AF7a AF7b CBA-FN-32 CBA-FN-33 EDE-X-5V EDE-US-53 EDE-X-5F 4160-480 V Distribution Transformer AF6 CB-F-1B-A EDE-AF8-FU Fuses AF8 CB-F-1B-A EDE-AF6-LA 6 KV Lightning Arrestors (3) AF7 CB-F-1B-A EDE-AF7-CT Current Transformers (2000/5) AF7 CB-F-1B-A EDE-AF8-AM Ammeter AF8 CB-F-1B-A EDE-AF8-AS Ammeter Switch AF8 CB-F-1B-A 54 EDE-US-61 480 V Feed to 460 V Motor Control Center 612 310014 B 310442 CB-F-1B-A X X X - AD6 EDE-AD6-52 480 V AC Circuit Breaker AD6 CB-F-1B-A AD6-B16 AD6-B16/1 310103 AD6 AD6 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-512 55 EDE-US-61 480 V Feed to 460 V Motor Control Center 614 310014 B 310442 CB-F-1B-A X X X - AA4 EDE-AA4-52 480 V AC Circuit Breaker AA4 CB-F-1B-A AA4-BF0 310103 AA4 AA4 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-514 56 EDE-US-61 480 V Feed to 460 V Motor Control Center 615 310014 B 310442 CB-F-1B-A X X X - AX9 EDE-AX9-52 480 V AC Circuit Breaker AX9 CB-F-1B-A AX9-B4E AX9-B4E/1 310103 AX9 AX9 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-515 57 EDE-US-62 480 V Feed to 460 V Motor Control Center 621 310014 B 310442 CB-F-1B-A X X X - AE8 EDE-AE8-52 480 V AC Circuit Breaker AE8 CB-F-1B-A AE8-B19 AE8-B19/1 310103 AE8 AE8 CBA-FN-32 CBA-FN-33 EDE-US-62 EDE-US-51 EDE-MCC-521 58 EDE-US-62 480 V Feed to 460 V Motor Control Center 622 310014 B 310442 CB-F-1B-A X X X - AW0 EDE-AW0-52 480 V AC Circuit Breaker AW0 CB-F-1B-A AW0-D13 AW0-GZ0 AW0-GZ0/1 F81-GZ0 310103 AWOa AWOe AWOb AWOc CBA-FN-32 CBA-FN-33 EDE-US-62 EDE-US-51 EDE-MCC-522 EDE-CS-9788-2 Control Switch with Indication GZ0 CB-F-1B-A EDE-SS-9788 Selector Switch GZ0 CB-F-1B-A EDE-AW0-52H Truck Operated Contact AW0 CB-F-1B-A EDE-AW0-FU Fuses AW0 CB-F-1B-A EDE-CS-9788-1 Control Switch with Indication F81 CB-F-3A-A EDE-AW0-R,G Indicating Lights AW0 CB-F-1B-A 59 EDE-US-63 480 V Feed to 460 V Motor Control Center 631 310052 B 310442 CB-F-1B-A X X X - AD8 EDE-AD8-52 480 V AC Circuit Breaker AD8 CB-F-1B-A AD8-D18 AD8-B18/1 310103 AD8 AD8 CBA-FN-32 CBA-FN-33 EDE-US-63 EDE-US-53 EDE-MCC-531 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -35 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 60 EDE-US-61 Grounding Transformer 310014 B 310442 CB-F-1B-A X X X - AD3 EDE-AD3-XFMR 3-1ø 1 KVA Transformers AD3 CB-F-1B-A - 310103 AD3b - CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 GRD XFMR EDE-AD3-FU Fuses AD3 CB-F-1B-A EDE-AD3-RES Grounding Resistor AD3 CB-F-1B-A EDE-AD3-VM Ground Voltmeters (3) AD3 CB-F-1B-A EDE-AD3-64 Ground Relay AD3 CB-F-1B-A 61 EDE-US-62 Grounding Transformer 310014 B 310442 CB-F-1B-A X X X - AE3 EDE-AE3-XFMR 3-1ø 1 KVA Transformers AE3 CB-F-1B-A - 310103 AE3b - CBA-FN-32 CBA-FN-33 EDE-US-62 EDE-US-52 GRD XFMR EDE-AE3-FU Fuses AE3 CB-F-1B-A EDE-AE3-RES Grounding Resistor AE3 CB-F-1B-A EDE-AE3-VM Ground Voltmeters (3) AE3 CB-F-1B-A EDE-AE3-64 Ground Relay AE3 CB-F-1B-A 61a EDE-US-61 480 V Feed to 460 V Motor Control Center 611 310014 B 310442 CB-F-1B-A X X X - AD5 EDE-AD5-52 480 V AC Circuit Breaker AD5 CB-F-1B-A AD5-B15 AD5-B15/1 310103 AD5 AD5 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-511 62 EDE-US-63 Grounding Transformer 310052 B 310442 CB-F-1B-A X X X - AF8 EDE-AF8-XFMR 3-1ø 1 KVA Transformers AF8 CB-F-1B-A - 310103 AF8b - CBA-FN-32 CBA-FN-33 EDE-US-63 EDE-US-53 GRD XFMR EDE-AF8-FU Fuses AF8 CB-F-1B-A EDE-AF8-RES Grounding Resistor AF8 CB-F-1B-A EDE-AF8-VM Ground Voltmeters (3) AF8 CB-F-1B-A EDE-AF8-64 Ground Relay AF8 CB-F-1B-A 63 EDE-I-1F Uninterruptible Power Supply 310043 B 310442 CB-F-1B-A X X X - HF6 EDE-DD5-52 460 V AC Circuit Breaker DD5 CB-F-1B-A DD5-HF6/1 DN0-HF6/1 310105 DD5a DD5b CBA-FN-32 CBA-FN-33 EDE-MCC-612 EDE-SWG-11B EDE-I-1E EDE-DN0-72 125 V DC Circuit Breaker DN0 CB-F-1B-A EDE-HF6/2-52 460 V AC Inc. Line Circuit Breaker HF6 CB-F-1B-A EDE-HF6/1-72 125 V DC Inc. Line Circuit Breaker HF6 CB-F-1B-A EDE-HF6/3-52 120 V AC Output Circuit Breaker HF6 CB-F-1B-A 63A EDE-CP-1F Static Transfer Switch 310043 B 310442 CB-F-1B-A X X X - E2B EDE-E2B-F1 300A, 600 V Fuse E2B CB-F-1B-A E2B-HF6 E2B-HF6/1 310105 DD5a DD5b EDE-I-1F CBA-FN-32 CBA-FN-33 EDE-CP-1E 64 EDE-PP-1F Vital Instrument Bus 310043 B 310442 CB-F-1B-A X X X - EH0 EDE-EH0/NC-52 120 V AC Circuit Breaker - Inc. Line from EDE-CP-1F (Norm. Closed) EH0 CB-F-1B-A EH0-E2B 310105 DD5a DD5b EH0a CBA-FN-32 CBA-FN-33 EDE-CP-1F EDE-PP-1E 65 EDE-PP-11F Vital Instrument Bus 310043 B 310442 CB-F-1B-A X X X - E1T EDE-EH0/13-52 120 V AC Circuit Breaker EH0 CB-F-1B-A E1T-EH0 310105 DD5a DD5b E1Ta CBA-FN-32 CBA-FN-33 EDE-PP-1F EDE-PP-11E SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -36 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 66 ED-X-16A 480-120/240 V Containment Lighting Transformer 310032 B 310576 C-F-1-Z X X X - EX6 EDE-D05-52-1 460 V AC Circuit Breaker DO5 CB-F-1B-A D05-H20 EX6-H20 310104 D05a D05b CBA-FN-32 CBA-FN-33 EDE-MCC-631 CAH-FN-1A CAH-FN-1B CAH-FN-1D ED-X-14J EDE-D05-52-2 460 V AC Circuit Breaker DO5 CB-F-1B-A EDE-MM-96 Electrical Penetration H20 C-F-1-Z, ET-F-1C-A 67 ED-PP-8B 120/240 V Distribution Panel 310032 B 310582 C-F-1-Z X X X - EM0 ED-X-16A Containment Lighting Transformer EX6 C-F-1-Z EM0-EX6 ER1-JX3 EX6-JX3 E4G-H41 H41-JX3 310104 DO5a D05b 310106 EM0a CAH-FN-1A CAH-FN-1B CAH-FN-1D ED-X-16A ED-PP-8J ED-EM0-52 250 V AC Circuit Breaker (Main) EM0 C-F-1-Z ED-JX3-42 Lighting Contactor JX3 C-F-2-Z ED-ER1-52 Lighting Panel 250 v AC Circuit Breaker (Main) ER1 C-F-2-Z EDE-MM-584 Fuse Panel E4G ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A 68 EDE-BC-1B 125 V DC Battery Charger 310042 B 310442 CB-F-1B-A X X X - HR6 EDE-DA1-52 460 V AC Circuit Breaker DA1 CB-F-1B-A DA1-HR4 DA1-HR6 310107 DA1a DA1f DA1b DA1c CBA-FN-32 CBA-FN-33 EDE-MCC-E612 EDE-BC-1A EDE-DA1-42 Contactor DA1 CB-F-1B-A EDE-DA1-42X Auxiliary Relay DA1 CB-F-1B-A DG-HR4-HR9(K20) EPS Relay HR4 CB-F-1B-A EDE-HR6/1-52 460 V AC Circuit Breaker - Incoming Feed HR6 CB-F-1B-A EDE-DA1-FU Fuse DA1 CB-F-1B-A 69 EDE-B-1B 125 V DC Battery 310042 B 310442 CB-F-1F-A X X X - HV5 EDE-J76-FU-1,2,3,4 1600A Fuses J76 CB-F-1B-A HV5-J76 HV5-J76/1 310107 DA1a DA1f DA1b DA1c CBA-FN-32 CBA-FN-33 CBA-FN-21B EDE-BC-1B EDE-SWG-11B EDE-B-1A EDE-J76-SH 1000A, 100 MV Shunt J76 CB-F-1B-A EDE-J76-ATR Transducer J76 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -37 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 70 EDE-SWG-11B 125 V DC Switchboard Auxiliary Buses 120 V AC and 125 V DC 310042 B 310442 CB-F-1B-A X X X - DN3 EDE-HR6/2-72 125 V DC Circuit Breaker HR6 CB-F-1B-A DN5-J76 DN5-J76/1 DN4-HR6 310107 DA1a DA1f DA1b DA1c 5b CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-1F EDE-B-1A EDE-BC-1A EDE-SWG-11A EDE-DL5-72 125 V DC Circuit Breaker DL5 CB-F-1B-A EDE-DN4-72 125 V DC Circuit Breaker DN4 CB-F-1B-A EDE-DN5-72 125 V DC Circuit Breaker DN5 CB-F-1B-A EDE-DN3-FU-1,2 125 V DC 10A Fuses DN3 CB-F-1B-A EDE-DN3-27BL Undervoltage Relay DN3 CB-F-1B-A EDE-DN3-27BLL Undervoltage Relay DN3 CB-F-1B-A EDE-DN3-VM DC Voltmeter DN3 CB-F-1B-A EDE-DN3-VTR Voltage Transducer DN3 CB-F-1B-A EDE-DN3-DIO Diodes DN3 CB-F-1B-A EDE-DN3-XS Selector Switch DN3 CB-F-1B-A EDE-DN3-AMY Ammeter Relay DN3 CB-F-1B-A EDE-EH0/5-52 120 V AC Circuit Breaker EH0 CB-F-1B-A DN3-EH0 DN3-J76/1 G1X-J76 310105 EH0a EHOb EDE-DN3-62BL Timing Relay DN3 CB-F-1B-A EDE-DN3-62BLL Timing Relay DN3 CB-F-1B-A EDE-DN4-72 Breaker Operated Contact DN4 CB-F-1B-A EDE-DN4-72STC Circuit Breaker Shut Trip Coil DN4 CB-F-1B-A EDE-J76-ATR Current Transducer J76 CB-F-1B-A EDE-DN3-FU 120 V AC 15A and 1A Fuses DN3 CB-F-1B-A EDE-DN3-52 120 V AC Incoming Feed Circuit Breaker DN3 CB-F-1B-A 71 EDE-PP-111B 125 V DC Distribution Panel 310042 B 310442 CB-F-1B-A X X X - E94 EDE-DN7-72 125 V DC Circuit Breaker DN7 CB-F-1B-A DN7-E94 310107 DA1a DA1f E94a CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-111A EDE-E94-72 125 V DC Circuit Breaker (Main) E94 CB-F-1B-A 72 EDE-PP-112B 125 V DC Distribution Panel 310042 B 310442 CB-F-1B-A X X X - E88 EDE-DN9-72 125 V DC Circuit Breaker DN9 CB-F-1B-A DN9-E88 310107 DA1a DA1f E88a CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-112A EDE-E88-72 125 V DC Circuit Breaker (Main) E88 CB-F-1B-A 73 EDE-PP-113B 125 V DC Distribution Panel 310042 B 310442 CB-F-1B-A X X X - E2U EDE-DP2-72 125 V DC Circuit Breaker DP2 CB-F-1B-A DP2-E2U 310107 DA1a DA1f DA1b E2Ua CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-113A EDE-E2U-72 125 V DC Circuit Breaker (Main) E2U CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -38 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 74 EDE-SWG-6 4160 V SWG 125 V DC Control Bus B 310442 CB-F-1B-A X X X - A73 EDE-E94/1-72 125 V DC Circuit Breaker E94 CB-F-1B-A A73-E94 310107 E94a E94b 310102 5i, 5j, 5k, 5l CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-SWG-5 EDE-A73-8 125 V DC Circuit Breaker (Main) A73 CB-F-1B-A 75 EDE-US-61 480 V Unit Substation 125 V DC Control Bus B 310442 CB-F-1B-A X X X - AD3 EDE-E94/2-72 125 V DC Circuit Breaker E94 CB-F-1B-A AD3-E94 310107 E94a E94b 310103 5q CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-US-51 EDE-AD3-8 125 V DC Circuit Breaker (Main) AD3 CB-F-1B-A 76 EDE-US-62 480 V Unit Substation 125 V DC Control Bus B 310442 CB-F-1B-A X X X - AE3 EDE-E94/3-72 125 V DC Circuit Breaker E94 CB-F-1B-A AE3-E94 310107 E94a E94b 310103 5r CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-US-52 EDE-AE3-8 125 V DC Circuit Breaker (Main) AE3 CB-F-1B-A 77 EDE-US-63 480 V Unit Substation 125 V DC Control Bus B 310442 CB-F-1B-A X X X - AF8 EDE-E94/4-72 125 V DC Circuit Breaker E94 CB-F-1B-A AF8-E94 310107 E94a E94b 310103 5s CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-US-53 EDE-AF8-8 125 V DC Circuit Breaker (Main) AF8 CB-F-1B-A 78 DG-CP-76A Diesel Generator 1B Control Panel Cubicle 3 125 V DC Supply 310010 310042 B 310524 DG-F-2B-A X X X - G20 EDE-DP1-72 125 V DC Circuit Breaker DP1 CB-F-1B-A DP1-G20 310102 DP1a DP1b 310107 DA1a DAH-FN-25B DAH-FN-26B EDE-SWG-11B CBA-FN-32 CBA-FN-33 DG-CP-75A DG-G20-72 125 V DC Circuit Breaker (Main) G20 DG-F-2B-A 79 DG-CP-80 Emergency Power Sequencer 310008 B 310442 CB-F-1B-A X X X - HR3 ED-X-2B Bus E6 UAT Transformer A71 CB-F-1B-A F81-HR3/3 FB0-HR3 A71-HR3 A72-HR3 A73-HR3 A74-HR3 310108 FP31417 E94/5a FP31418 E94/5b FP31429 DG-CP-79 ED-X-3B Bus E6 RAT Transformer A72 CB-F-1B-A EDE-SWG-6 UAT Potential Transformer A73 CB-F-1B-A EDE-SWG-6 Bus E6 DG -1B A74 CB-F-1B-A MM-CP-13 Prot. Cabinet Main Control Board FB0 F81 CB-F-3A-A CB-F-3A-A 80 DG-CP-79 Emergency Power Sequencer 310007 A 310442 CB-F-1A-A X X X - HR1 ED-X-2A Bus E5 UAT Transformer A51 CB-F-1A-A F80-HR1 FB7-HR1 A51-HR1 A52-HR1 A53-HR1 A54-HR1 310108 FP31417 E93/5a FP31418 E93/5b FP31429 DG-CP-80 ED-X-3A Bus E5 RAT Transformer A52 CB-F-1A-A EDE-SWG-5 UAT Potential Transformer A53 CB-F-1A-A EDE-SWG-5 Bus E5 DG -1A A54 CB-F-1A-A MM-CP-12 Prot. Cabinet Main Control Board FB7 F80 CB-F-3A-A CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -39 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 81 EDE-I-1A Uninterruptible Power Supply 310043 A 310435 CB-F-1A-A X X X - HE1 EDE-D27-52 460 V AC Circuit Breaker D27 CB-F-1A-A D27-HE1 DM6-HE1 310105 D27a D27b FP50513 to FP50517 CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-I-1B EDE-DM6-72 125 V DC Circuit Breaker DM6 CB-F-1A-A EDE-HE1/2-52 460 V AC Inc. Line Circuit Breaker HE1 CB-F-1A-A EDE-HE1/1-72 125 V DC Inc. Line Circuit Breaker HE1 CB-F-1A-A EDE-HE1/3-52 120 V AC Output Circuit Breaker HE1 CB-F-1A-A 82 EDE-PP-1A Vital Instrument Bus 310043 A 310435 CB-F-1A-A X X X - E01 EDE-E01-52 120 V AC Circuit Breaker E01 CB-F-1A-A E01-HE1 310105 D27a D27b E01a CBA-FN-19 CBA-FN-20 EDE-I-1A EDE-PP-1B 83 EDE-I-1B Uninterruptible Power Supply 310043 B 310435 CB-F-1B-A X X X - HE2 EDE-D26-52 460 V AC Circuit Breaker D26 CB-F-1B-A D26-HE2 DN8-HE2 310105 D26a D26b FP50513 to FP50517 CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-I-1A EDE-DN8-72 125 V DC Circuit Breaker DN8 CB-F-1B-A EDE-HE2/2-52 460 V AC Inc. Line Circuit Breaker HE2 CB-F-1B-A EDE-HE2/1-72 125 V DC Inc. Line Circuit Breaker HE2 CB-F-1B-A EDE-HE2/3-52 120 V AC Output Circuit Breaker HE2 CB-F-1B-A 84 EDE-PP-1B Vital Instrument Bus 310043 B 310435 CB-F-1B-A X X X - E02 EDE-E02-52 120 V AC Circuit Breaker E02 CB-F-1B-A E02-HE2 310105 D26a D26b E02a CBA-FN-32 CBA-FN-33 EDE-I-1B EDE-PP-1A 85 EDE-I-1C Uninterruptible Power Supply 310043 A 310442 CB-F-1A-A X X X HE3 EDE-D30-52 460 V AC Circuit Breaker D30 CB-F-1A-A D30-HE3 DP9-HE3 310105 D30a D30b FP50513 to FP50517 CBA-FN-19 CBA-FN-20 EDE-SWG-11C EDE-I-1D EDE-DP9-72 125 V DC Circuit Breaker DP9 CB-F-1A-A EDE-HE3/2-52 460 V AC Inc. Line Circuit Breaker HE3 CB-F-1A-A EDE-HE3/1-72 125 V DC Inc. Line Circuit Breaker HE3 CB-F-1A-A EDE-HE3/3-52 120 V AC Output Circuit Breaker HE3 CB-F-1A-A 86 EDE-PP-1C Vital Instrument Bus 310043 C 310442 CB-F-1A-A X X X E03 EDE-E03-52 120 V AC Circuit Breaker E03 CB-F-1A-A E03-HE3 310105 D30a D30b E03a CBA-FN-19 CBA-FN-20 EDE-I-1C EDE-PP-1D SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -40 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 87 EDE-I-1D Uninterruptible Power Supply 310043 B 310435 CB-F-1B-A X X X HE4 EDE-D23-52 460 V AC Circuit Breaker D23 CB-F-1B-A D23-HE4 DR1-HE4 310105 D23a D23b FP50513 to FP50517 CBA-FN-32 CBA-FN-33 EDE-SWG-11D EDE-I-1C EDE-DR1-72 125 V DC Circuit Breaker DR1 CB-F-1B-A EDE-HE4/2-52 460 V AC Inc. Line Circuit Breaker HE4 CB-F-1B-A EDE-HE4/1-72 125 V DC Inc. Line Circuit Breaker HE4 CB-F-1B-A EDE-HE4/3-52 120 V AC Output Circuit Breaker HE4 CB-F-1B-A 88 EDE-PP-1D Vital Instrument Bus 310043 D 310435 CB-F-1B-A X X X E04 EDE-E04-52 120 V AC Circuit Breaker E04 CB-F-1B-A E04-HE4 310105 D23a D23b E04a CBA-FN-32 CBA-FN-33 EDE-I-1D EDE-PP-1C SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -41 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 89 EDE-SWG-11C 125 V DC Switchboard Auxiliary Buses 120 V AC and 125 V DC 310042 A 310442 CB-F-1A-A X X X - DP5 EDE-HR7/2-72 125 V DC Circuit Breaker HR7 CB-F-1A-A DP7-J77 DP7-J77/1 DP6-HR7 G1Y-J77 DP5-J77/1 DP5-EH9 310107 D88a D88f D88c 5c 310105 EH9a EH9b CBA-FN-19 CBA-FN-20 EDE-BC-1C EDE-B-1C EDE-SWG-11D EDE-DL6-72 125 V DC Circuit Breaker DL6 CB-F-1A-A EDE-DP6-72 125 V DC Circuit Breaker DP6 CB-F-1A-A EDE-DP7-72 125 V DC Circuit Breaker DP7 CB-F-1A-A EDE-DP8-72 125 V DC Circuit Breaker DP8 CB-F-1A-A EDE-DP5-FU-1,2 Fuses DP5 CB-F-1A-A EDE-DP5-27BL Undervoltage Relay DP5 CB-F-1A-A EDE-DP5-VM DC Voltmeter DP5 CB-F-1A-A EDE-DP5-VTR Voltage Transducer DP5 CB-F-1A-A EDE-DP5-DIO Diodes DP5 CB-F-1A-A EDE-DP5-XS Selector Switch DP5 CB-F-1A-A EDE-DP5-AMY Ammeter Relay DP5 CB-F-1A-A EDE-EH9/6-52 120 V AC Circuit Breaker EH9 CB-F-1A-A EDE-DP5-27BLL Undervoltage Relay DP5 CB-F-1A-A EDE-DP5-62BL Timing Relay DP5 CB-F-1A-A EDE-DP5-62BLL Timing Relay DP5 CB-F-1A-A EDE-DP6-72 Breaker Operated Contact DP6 CB-F-1A-A EDE-DP6-72STC Circuit Breaker Shunt Trip Coil DP6 CB-F-1A-A EDE-J77-ATR Current Transducer J77 CB-F-1A-A EDE-DP5-52 120 V AC Inc. Feed Circuit Breaker DP5 CB-F-1A-A EDE-DP5-FU 120 V AC 15A and 1A Fuses DP5 CB-F-1A-A 90 EDE-BC-1C 125 V DC Battery Charger 310042 A 310442 CB-F-1A-A X X X - HR7 EDE-D88-52 460 V AC Circuit Breaker D88 CB-F-1A-A D88-HR7 D88-HR2 310107 D88a D88f D88b CBA-FN-19 CBA-FN-20 EDE-MCC-E521 EDE-BC-1D EDE-D88-42 Contactor D88 CB-F-1A-A EDE-D88-42X Auxiliary Relay D88 CB-F-1A-A DG-HR2-HR9 EPS Relay HR2 CB-F-1A-A EDE-HR7/1-52 460 V AC Circuit Breaker - Incoming Feed HR7 CB-F-1A-A EDE-D88-FU Fuse D88 CB-F-1A-A 91 EDE-B-1C 125 V DC Battery 310042 A 310442 CB-F-1E-A X X X - HV6 EDE-J77-FU-1,2,3,4 1600A Fuses J77 CB-F-1A-A HV6-J77 HV6-J77/1 310107 D88a D88f CBA-FN-19 CBA-FN-20 EDE-B-1C EDE-J77-SH 1000A, 100 MW Shunt J77 CB-F-1A-A EDE-J77-ATR Transducer J77 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -42 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 92 EDE-SWG-11D 125 V DC Switchboard Auxiliary Buses 120 V DC and 125 V DC 310042 B 310442 CB-F-1B-A X X X - DQ7 EDE-HR8/2-72 125 V DC Circuit Breaker HR8 CB-F-1B-A DQ7-J78/1 DQ9-J78 DQ9-J78/1 DQ8-HR8 D1Z-J78 310107 DB2a DB2f DB2b DB2c 5d CBA-FN-32 CBA-FN-33 EDE-BC-1D EDE-B-1D EDE-SWG-11C EDE-DL7-72 125 V DC Circuit Breaker DL7 CB-F-1B-A EDE-DQ8-72 125 V DC Circuit Breaker DQ8 CB-F-1B-A EDE-DQ9-72 125 V DC Circuit Breaker DQ9 CB-F-1B-A EDE-DQ0-72 125 V DC Circuit Breaker DQ0 CB-F-1B-A DQ7-EH0 310105 EH0a EHOb EDE-DQ7-FU-1,2 Fuses DQ7 CB-F-1B-A EDE-DQ7-27BL Undervoltage Relay DQ7 CB-F-1B-A EDE-DQ7-VM DC Voltmeter DQ7 CB-F-1B-A EDE-DQ7-VTR Voltage Transducer DQ7 CB-F-1B-A EDE-DQ7-DIO Diodes DQ7 CB-F-1B-A EDE-DQ7-XS Selector Switch DQ7 CB-F-1B-A EDE-DQ7-AMY Ammeter Relay DQ7 CB-F-1B-A EDE-DQ7-27BLL Undervoltage Relay DQ7 CB-F-1B-A EDE-EH0/6-52 120 V AC Circuit Breaker EH0 CB-F-1B-A EDE-DQ7-62BL Timing Relay DQ7 CB-F-1B-A EDE-DQ7-62BLL Timing Relay DQ7 CB-F-1B-A EDE-DQ8-72 Breaker Operated Contact DQ8 CB-F-1B-A EDE-DQ8-72STC Circuit Breaker Shunt Trip Coil DQ8 CB-F-1B-A EDE-J77-ATR Current Transducer J77 CB-F-1B-A EDE-DQ7-52 120 V AC Inc. Feed Circuit Breaker DQ7 CB-F-1B-A EDE-DQ7-FU 120 V AC 15A and 1A Fuses DQ7 CB-F-1B-A 93 EDE-BC-1D 125 V DC Battery Charger 310042 B 310442 CB-F-1B-A X X X - HR8 EDE-DB2-52 460 V AC Circuit Breaker DB2 CB-F-1B-A DB2-HR8 DB2-HR4 310107 DB2a DB2f DB2b CBA-FN-19 CBA-FN-20 EDE-MCC-E621 EDE-BC-1C EDE-DB2-42 Contactor DB2 CB-F-1B-A EDE-DB2-42X Auxiliary Relay DB2 CB-F-1B-A DG-HR4-HR9 EPS Relay HR4 CB-F-1B-A EDE-HR8/1-52 460 V AC Circuit Breaker - Incoming Feed HR8 CB-F-1B-A EDE-DB2-FU Fuse DB2 CB-F-1B-A 94 EDE-B-1D 125 V DC Battery 310042 B 310442 CB-F-1G-A X X X - HV7 EDE-J78-FU-1,2,3,4 1600A Fuses J78 CB-F-1B-A HV7-J78 HV7-J78/1 310107 DB2a DB2f DB2a DB2f CBA-FN-32 CBA-FN-33 EDE-B-1C EDE-J78-SH 1000A, 100 MW Shunt J78 CB-F-1B-A EDE-J78-ATR Transducer J78 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -43 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 95 ED-I-4 Uninterruptible Power Supply 310054 A 310292 NES-F-1A-Z X X X - HS7 EDE-BR3-52 460 V AC Circuit Breaker BR3 DG-F-2A-A BR3-HR2 BR3-HS7 DR2-HS7 310105 BR3a BR3c BR3b ED-SWG-12B ED-DR2-72 125 V DC Circuit Breaker DR2 TB-F-1A-Z ED-HS7-52 460 V AC Inc. Line Breaker HS7 NES-F-1A-Z ED-HS7-72 125 V DC Inc. Line Breaker HS7 NES-F-1A-Z ED-HS7-52 120 V AC Output Breaker HS7 NES-F-1A-Z EDE-BR3-42 Contactor BR3 DG-F-2A-A EDE-BR3-42X Auxiliary Relay BR3 DG-F-2A-A EDE-BR3-FU 2A Fuse BR3 DG-F-2A-A DG-HR2-HR9 EPS Relay HR2 CB-F-1A-A 96 ED-PP-5 Non-Vital Instrument Bus 310054 A 310292 NES-F-1A-Z X X X - EJ9 ED-EJ9-52 120 V AC Inc. Line Breaker Non -Automatic EJ9 NES-F-1A-Z EJ9-JB9 EJ9-JB9/1 310105 BR3a BR3c ED-I-4 ED-CP-532 96A ED-CP-532 Transfer Switch for ED-PP-5 310054 A 310292 NES-F-1A-Z X X X - JB9 - - HS7 EJ9 NES-F-1A-Z NES-F-1A-Z HS7-JB9 HS7-JB9/1 EJ9-JB9 EJ9-JB9/1 310105 BR3a BR3c ED-I-4 ED-PP-5 97 ED-BC-2B 125 V DC Battery Charger 310059 A 310328 TB-F-1A-Z X X X - HS4 ED-CW3-52 460 V AC Circuit Breaker CW3 TB-F-2-Z CW3-HS4 CW3-HR2 310107 CW3a CW3f CW3b ED-MCC-E523 ED-CW3-42 Contactor CW3 TB-F-2-Z ED-CW3-42X Auxiliary Relay CW3 TB-F-2-Z DG-HR2-HR9 EPS Relay HR2 CB-F-1A-A ED-HS4-52 460 V AC Circuit Breaker - Inc. Feed HS4 TB-F-1A-Z ED-CW3-FU Fuse CW3 TB-F-2-Z 98 ED-B-2B 125 V DC Battery 310059 A 310328 TB-F-1B-A X X X - HS5 ED-DS8-SH 1500A, 100 mV Shunt DS8 TB-F-1A-Z DS8-HS5 DS8-HS5/1 310107 CW3a CW3f ED-DS6-ATR Transducer DS6 TB-F-1A-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -44 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 99 ED-SWG-12B 125 V DC Switchgear Auxiliary Buses 120 V AC and 125 V DC 310059 A 310328 TB-F-1A-Z X X X - DS6 ED-HS4-72 125 V DC Circuit Breaker HS4 TB-F-1A-Z DS7-HS4 310107 CW3a CW3f ED-BC-2B ED-B-2B ED-DL9-72 125 V DC Circuit Breaker DL9 TB-F-1A-Z ED-DS7-72 125 V DC Circuit Breaker DS7 TB-F-1A-Z ED-DS8-72 125 V DC Circuit Breaker DS8 TB-F-1A-Z ED-DS6-FU-1,2 15A Fuses DS6 TB-F-1A-Z ED-DS6-27BL Undervoltage Relay DS6 TB-F-1A-Z ED-DS6-27BLL Undervoltage Relay DS6 TB-F-1A-Z ED-DS6-VM DC Voltmeter DS6 TB-F-1A-Z ED-DS6-VTR Voltage Transducer DS6 TB-F-1A-Z ED-DS6-DIO Diodes DS6 TB-F-1A-Z ED-DS6-XS Selector Switch DS6 TB-F-1A-Z ED-DS6-AMY Ammeter Relay DS6 TB-F-1A-Z ED-E20/8-52 120 V AC Circuit Breaker E20 TB-F-1A-Z DS6-E20 310106 E20a E20c ED-DS6-62BL Timing Relay DS6 TB-F-1A-Z ED-DS6-62BLL Timing Relay DS6 TB-F-1A-Z ED-DS7-72STC Circuit Breaker Shunt Trip Coil DS7 TB-F-1A-Z ED-DS7-72 Breaker Operated Contact DS7 TB-F-1A-Z ED-DS6-ATR Current Transducer DS6 TB-F-1A-Z 100 ED-PP-121B 125 V DC Distribution Panel 310059 A 310292 NES-F-1A-Z X X X - E97 ED-DQ1-72 125 V DC Circuit Breaker DQ1 TB-F-1A-Z DQ1-E97 A03-E97 A18-E97 310107 CW3a CW3f E97a ED-SWG-12B ED-E97-72 125 V DC Circuit Breaker E97 NES-F-1A-Z 101 ED-PP-122B 125 V DC Distribution Panel 310059 A 310431 CB-F-1A-A X X X - E89 ED-DQ3-72 125 V DC Circuit Breaker DQ3 TB-F-1A-Z DQ3-E89 310107 CW3a CW3f E89a ED-SWG-12B ED-E89-72 125 V DC Circuit Breaker E89 CB-F-1A-A 102 EDE-US-51 480 V Feed to 460 V Motor Control Center 511 310023 A 310442 CB-F-1A-A X X X - AB5 EDE-AB5-52 480 V AC Circuit Breaker AB5 CB-F-1A-A AB5-B09 AB5-B09/1 310103 AB5 AB5 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-611 103 EDE-US-51 480 V Feed to 460 V Motor Control Center 513 310023 A 310442 CB-F-1A-A X X X - AV6 EDE-AV6-52 480 V AC Circuit Breaker AV6 CB-F-1A-A AV6-C14 310103 AV6 AV6 CBA-FN-19 CBA-FN-20 EDE-US-51 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -45 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 104 ED-BC-2A 125 V DC Battery Charger 310059 A 310328 TB-F-1A-Z X X X - HS2 ED-CN3-52 460 V AC Circuit Breaker CN3 TB-F-2-Z CN3-HS2 CN3-HR2 310107 CN3a CN3f CN3b ED-MCC-E523 ED-CN3-42 Contactor CN3 TB-F-2-Z ED-CN3-42X Auxiliary Relay CN3 TB-F-2-Z DG-HR2-HR9 EPS Relay HR2 CB-F-1A-A ED-HS2-52 460 V AC Circuit Breaker - Inc. Feed HS2 TB-F-1A-Z ED-CN3-FU Fuse CN3 TB-F-2-Z 105 ED-B-2A 125 V DC Battery 310059 A 310328 TB-F-1B-A X X X - HS3 ED-DR8-SH 1500A, 100 mV Shunt DR8 TB-F-1A-Z DR8-HS3 310107 CN3a CN3f ED-DR6-ATR Transducer DR6 TB-F-1A-Z DR8-HS3/1 106 ED-SWG-12A 125 V DC Switchgear Auxiliary Buses 120 V AC and 125 V DC 310059 A 310328 TB-F-1A-Z X X X - DR6 ED-HS2-72 125 V DC circuit Breaker HS2 TB-F-1A-Z DR7-HS2 310107 CN3a CN3f ED-BC-2A ED-B-2A ED-DL8-72 125 V DC circuit Breaker DL8 TB-F-1A-Z ED-DR7-72 125 V DC circuit Breaker DR7 TB-F-1A-Z ED-DR8-72 125 V DC circuit Breaker DR8 TB-F-1A-Z ED-DR6-FU-1,2 15A Fuses DR6 TB-F-1A-Z ED-DR6-27BL Undervoltage Relay DR6 TB-F-1A-Z ED-DR6-27BLL Undervoltage Relay DR6 TB-F-1A-Z ED-DR6-VM DC Voltmeter DR6 TB-F-1A-Z ED-DR6-VTR Voltage Transducer DR6 TB-F-1A-Z ED-DR6-DIO Diodes DR6 TB-F-1A-Z ED-DR6-XS Selector Switch DR6 TB-F-1A-Z ED-DR6-AMY Ammeter Relay DR6 TB-F-1A-Z ED-E20/17-52 120 V DC Circuit Breaker E20 TB-F-1A-Z DR6-E20 310106 E20a E20c ED-DR6-62BL Timing Relay DR6 TB-F-1A-Z ED-DR6-62BLL Timing Relay DR6 TB-F-1A-Z ED-DR7-72STC Circuit Breaker Shunt Trip Coil DR7 TB-F-1A-Z ED-DR7-72 Breaker Operated Contact DR7 TB-F-1A-Z ED-DR6-ATR Current Transducer DR6 TB-F-1A-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -46 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 107 ED-PP-122A 125 V DC Distribution Panel 310059 A 310328 TB-F-1A-A X X X - E91 ED-DS4-72 125 V DC Circuit Breaker DS4 TB-F-1A-Z DS4-E91 DS4-E91/1 A16-E91 310107 CN3a CN3f E91a E91b ED-SWG-12A ED-E91-72 125 V DC Circuit Breaker E91 TB-F-1A-A 108 ED-PP-3C Non-Vital Instrument Bus 310043 A 310442 CB-F-1A-A X X X - EH7 ED-EH7-52 120 V AC Circuit Breaker EH7 CB-F-1A-A E03-EH7 310105 D30a D30b EH7a CBA-FN-19 CBA-FN-20 EDE-I-1C EDE-PP-1C SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -1 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 DG-DG-1A Diesel Generator 1A DG-20462 A 310524 DG-F-2A-A X X X X HA1 DG-CS-9510-2 Control Switch (Push Button) G07 DG-F-2A-A A54-G06/5 A54-G29 G06-G29 G06-G29/1 G06-HR2 G06-G29/2 G07-G29 E93-G29/1 F80-FB7 F80-G06/8 F80-G06/9 F80-G07/9 F80-G07/F F80-G07/G 310857 E93/8a E93/8n E93/8b E93/8p E93/8c E93/8d E93/8e E93/8f E93/8g E93/8r CBA-FN-19 CBA-FN-20 DAH-FN-25A DAH-FN-26A EDE-PP-111A D/G Starting Air DG-DG-1B DG-CS-9511 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9512-3 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9512-4 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9517-2 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9518-2 Control Switch (Push Button) G07 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A DG-G29-OP2 Oil Pressure Relay G29 DG-F-2A-A DG-G29-CR1 Ready for Auto Start Relay G29 DG-F-2A-A DG-G29-4A Start Relay G29 DG-F-2A-A DG-G29-T2A Cranking Time Control Time Delay Relay G29 DG-F-2A-A DG-ZL-9580-9 Start Ckt No 1 Signal Indicating Light G07 DG-F-2A-A DG-G29-ES1 Emergency Start Relay G29 DG-F-2A-A DG-G10-TSR1 Test Start Relay G10 DG-F-2A-A DG-G10-TSR2 Test Start Relay G10 DG-F-2A-A DG-G10-TSR3 Test Start Relay G10 DG-F-2A-A DG-G10-RDT Ramp Down Time Relay G10 DG-F-2A-A DG-G07-IOT Idle Operate Time Relay G07 DG-F-2A-A DG-G06-LSRX Low Speed Aux Relay G06 DG-F-2A-A DG-FY-AS1 Air Start Solenoid Valve G29 DG-F-2A-A DG-G29-OP3 Oil Pressure Relay G29 DG-F-2A-A DG-G29-CR2 Ready for Auto Start Relay G29 DG-F-2A-A DG-G29-4B Start Relay G29 DG-F-2A-A DG-G29-T2B Cranking Time Control Time Delay Relay G29 DG-F-2A-A

.* Table notes on last page of table.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -2 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-ZL-9580-10 Start Ckt No 2 Signal Indicating Light G07 DG-F-2A-A DG-G29-ES2 Emergency Start Rela y G29 DG-F-2A-A DG-FY-AS2 Air Start Solenoid Valve G29 DG-F-2A-A DG-G29-OP4 Oil Pressure Relay G29 DG-F-2A-A DG-G29-5E Emergency Stop Relay G29 DG-F-2A-A DG-G29-5 Normal Stop Relay G29 DG-F-2A-A DG-G29-5A Shutdown Relay G29 DG-F-2A-A DG-FY-SDS Shutdown Solenoid Valve G29 DG-F-2A-A DG-FY-CSV-A Jacket Coolant Auxiliary Valves Solenoid G29 DG-F-2A-A DG-G29-T3A Alarm Set Time Delay Relay G29 DG-F-2A-A DG-G29-TR Engine Velocity Transmitter G29 DG-F-2A-A DG-FY-ISV-A Intercooler Auxiliary Valves Solenoid G29 DG-F-2A-A DG-G29-SG Signal Generator G29 DG-F-2A-A DG-G29-HSR High-Speed Relay G29 DG-F-2A-A DG-G29-LSR Low-Speed Relay G29 DG-F-2A-A DG-G29-ASR Starting Air Shutoff Relay G29 DG-F-2A-A DG-G29-IPC Coolant Pump Control Relay G29 DG-F-2A-A DG-G29-BDR Barring Device Relay G29 DG-F-2A-A DG-G29-ASA Air Start Relay G29 DG-F-2A-A DG-G29-ASB Air Start Relay G29 DG-F-2A-A DG-FB7-K603A Protection System Relay FB7 CB-F-3A-A EDE-CS-9518-1 Control Switch F80 CB-F-3A-A EDE-CS-9517-1 Control Switch F80 CB-F-3A-A EDE-CS-9510-1 Control Switch F80 CB-F-3A-A DG-FB7-K608A Protection System Output Relay FB7 CB-F-3A-A EDE-CS-9512-1 Control Switch F80 CB-F-3A-A EDE-CS-9512-2 Control Switch F80 CB-F-3A-A EDE-ZL-9574 Monitoring Circuit Indication Light G07 DG-F-2A-A DG-G29-TACH Tachometer G29 DG-F-2A-A DG-G29-SFR Start Failure Relay G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -3 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) EDE-ZL-9574-1 Monitoring Circuit Indicating Light G29 DG-F-2A-A DG-G29-SDR Engine Trouble Shutdown Relay G29 DG-F-2A-A DG-G29-EOR Engine Overspeed Relay G29 DG-F-2A-A EDE-A69-RLA SI Signal Lockout Relay A69 CB-F-1A-A DG-G29-OTH High Oil Temperature Relay G29 DG-F-2A-A DG-G29-CTH High Coolant Temperature Relay G29 DG-F-2A-A EDE-A54-TD2 Test Device A54 CB-F-1A-A EDE-A69-TD2 Test Device A69 CB-F-1A-A DG-G29-EST Emergency Start Time Delay Relay G29 DG-F-2A-A DG-G29-ESX Emergency Start Auxiliary Relay G29 DG-F-2A-A DG-G29-RA1 Air Pressure Auxiliary Relay G29 DG-F-2A-A DG-G29-RA2 Air Pressure Auxiliary Relay G29 DG-F-2A-A DG-G29-CF3 Power Available Relay G29 DG-F-2A-A DG-G29-CF1 Power Available Relay G29 DG-F-2A-A DG-G29-CF2 Power Available Relay G29 DG-F-2A-A DG-G29-CF5 Power Available Relay G29 DG-F-2A-A DG-G29-OP1 Oil Pressure Relay G29 DG-F-2A-A DG-G29-FPL Fuel Pressure Relay G29 DG-F-2A-A DG-G29-CPL Jacket Coolant Pressure Relay G29 DG-F-2A-A DG-G29-IPL Intercooler Pressure Relay G29 DG-F-2A-A DG-PS-OPL1 Oil Low Pressure Switch G29 DG-F-2A-A DG-PS-FPLA Fuel Low Pressure Switch G29 DG-F-2A-A DG-PS-CPLA Jacket Coolant Low Pressure Switch G29 DG-F-2A-A DG-PS-IPLA Intercooler Low Pressure Switch G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -4 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-G29-OPC Oil Pump Control Relay G29 DG-F-2A-A DG-G29-FPC Auxiliary Fuel Oil Pump Control Relay G29 DG-F-2A-A DG-G29-CPC Coolant Pump Control Relay G29 DG-F-2A-A DG-G29-CF4 Power Available Relay G29 DG-F-2A-A DG-G07-R43L1 Selector Switch Auxiliary Latch Relay (Local) G07 DG-F-2A-A DG-G07-R43L2 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G07 DG-F-2A-A DG-G07-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G07 DG-F-2A-A DG-G07-R43R2 Selector Switch Auxiliary Latch Relay (Remote) G07 DG-F-2A-A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-HR2-PR1 EPS Auxiliary Relay HR2 CB-F-1A-A DG-HR2-PR1X EPS Auxiliary Relay HR2 CB-F-1A-A DG-G29-D1 P-N Junction Diode G29 DG-F-2A-A DG-SS-E0S Engine Overspeed Switch G29 DG-F-2A-A DG-PS-APL1 Air Pressure Low Switch G29 DG-F-2A-A DG-PS-APL2 Air Pressure Low Switch G29 DG-F-2A-A DG-PS-CPS Coolant Pressure Switch G29 DG-F-2A-A DG-PS-OPL2 Oil Low Pressure Switch G29 DG-F-2A-A DG-PS-OPL3 Oil Low Pressure Switch G29 DG-F-2A-A DG-PS-OPL4 Oil Low Pressure Switch G29 DG-F-2A-A DG-G29-CTH-1 Coolant High Temperature Auxiliary Relay G29 DG-F-2A-A DG-G29-OTH-1 Oil High Temperature Auxiliary Relay G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -5 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-ZS-BD1 Barring Device Position Switch G29 DG-F-2A-A DG-ZS-BD2 Barring Device Position Switch G29 DG-F-2A-A DG-G29-FU 10 Amp Fuses (10) G29 DG-F-2A-A EDE-A54-86DP DG Primary Protection Lockout Relay A54 CB-F-1A-A EDE-A69-86DB DG Backup Protection Lockout Relay A69 CB-F-1A-A DG-G29-TRP TR Control Power Relay G29 DG-F-2A-A DG-G29-5B Shutdown Auxiliary Relay G29 DG-F-2A-A EDE-A54-TS Test Start Control Switch A54 CB-F-1A-A EDE-G07-FU-17,18 6 Amp Fuses (2) G07 DG-F-2A-A DM9-G10 F80-G07/8 310102 G07/2a G07/2g G07/2b G07/2c DM9a DM9b DAH-FN-25A DAH-FN-25B DG-CP-75A EDE-SWG-11A EDE-SS-9700 Selector Switch G06 DG-F-2A-A DG-G07-CF6 Auxiliary Relay G07 DG-F-2A-A DG-G07-R43L1 Selector Switch Auxiliary Latch Relay (Local) G07 DG-F-2A-A DG-G07-R43L2 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L3 Selector Switch

Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L5 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R2 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G07 DG-F-2A-A DG-G07-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G07 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -6 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) EDE-SNS-9763-1 Selector Switch F80 CB-F-3A-A EDE-CS-9707-1 Control Switch F80 CB-F-3A-A EDE-SNS-9763-2 Selector Switch G06 DG-F-2A-A EDE-CS-9707-3 Control Switch G07 DG-F-2A-A EDE-G06-FU-9,10 50 Amp Fuses G06 DG-F-2A-A A69-G06 G06-HF7 A69-HN0 DM9-G10 310102 HA1a HA1c HA1b HA1d DM9a DM9b DAH-FN-25A DAH-FN-26A CBA-FN-19 CBA-FN-29 EDE-SWG-11A DG-A69,XFMR Grounding Transformer A69 CB-F-1A-A DG-HF7-XF DG Field HF7 DG-F-2A-A DG-G07-SEVR-PC Static Exciter Voltage Regulator Power Chassis G06 DG-F-2A-A DG-SM-9585 Governor Control (2301A) G06 DG-F-2A-A DG-GT3-PT1 Potential Transformer GT3 DG-F-2A-A DG-GT3-PT2 Potential Transformer GT3 DB-F-2A-A DG-GT3-PPT4 Power Transformer GT3 DB-F-2A-A DG-HNO-NCB DG Neutral Connection Box HN0 DG-F-2A-A DG-GT3-CCT Current Transformer 2000/5 GT3 DG-F-2A-A DG-G06-K2 Field Flashing Contractor G06 DB-F-2A-A DG-G10-IDR1 Isochronous Droop Relay G10 DG-F-2A-A EDE-A69-60 Voltage Balance Relays A69 CB-F-1A-A DG-G06-64F Generator Field Failure Relay G06 DG-F-2A-A DG-G10-SEVR-CC Static Exciter Voltage Regulator Control Chassis G10 DG-F-2A-A DG-GT3-XCT1,2,3 Generator Current Transformers (2000/5) GT3 DG-F-2A-A DG-VM-9702-2 Field Voltmeter G10 DG-F-2A-A DG-G10-DCT Field Voltage Transducer G10 DG-F-2A-A DG-G06-SH 50 MV Field Shunt G06 DG-F-2A-A DG-AM-9702-2 DC Field Ammeter G10 DG-F-2A-A DG-G10-ATR Current Transducer G10 DG-F-2A-A DG-G10-CF10 Loss of Power Relay G10 DG-F-2A-A DG-A69-64 Ground Fault Sensing Relay A69 CB-F-1A-A DG-G10-FU-22,23 1 Amp Fuses G10 DG-F-2A-A DG-G07-IL10 Diode Failure Light G07 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -7 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) EDE-G06-FU-1,2 10 Amp Fuses (2) G06 DG-F-2A-A G06-G29/5 DM9-G10 F80-G06/3 F80-G06/4 F80-G06/5 F80-G10/1 310102 G06/1a G06/1f G06/1b G06/1c G06/1d DM9a DM9b DAH-FN-25A DAH-FN-26A DG-CP-75A EDE-SWG-11A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A EDE-CS-9820-2 Control Switch (Push Button) G10 DG-F-2A-A DG-G29-HSR High Speed Relay G29 DG-F-2A-A DG-G29-LSR Low Speed Relay G29 DG-F-2A-A DG-G29-ES1 Emergency Start Relay G29 DG-F-2A-A DG-G29-ES2 Emergency Start Relay G29 DG-F-2A-A DG-SS-9585 Selector Switch G07 DG-F-2A-A DG-ZL-9580-11 Field Flash Signal Indicating Light G10 DG-F-2A-A DG-G07-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G07 DG-F-2A-A DG-G29-5A DG - Shutdown Relay G29 DG-F-2A-A DG-G06-LSRX Low Speed Auxiliary Relay G06 DG-F-2A-A DG-G06-LSRXX Time Delay Relay G06 DG-F-2A-A EDE-CS-9801-1 Push Button G10 DG-F-2A-A EDE-CS-9801-2 Push Button G10 DG-F-2A-A DG-G06-SERV-PC Static Exciter Voltage Regulatory Power Chassis G06 DG-F-2A-A DG-G10-NM Null Meter G10 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-CS-9821-2 Control Switch G10 DG-F-2A-A EDE-CS-9822-2 Control Switch G10 DG-F-2A-A DG-G10-RR Regulator Relay G10 DG-F-2A-A DG-G10-SERV-CC Static Exciter Voltage Regulator Control Chassis G10 DG-F-2A-A DG-G10-CF-8 Loss of Power Relay G10 DG-F-2A-A EDE-CS-9820-1 Push Button Switch F80 CB-F-3A-A EDE-CS-9822-1 Control Switch F80 CB-F-3A-A EDE-CS-9821-1 Control Switch F80 CB-F-3A-A EDE-VM-9782 Null Voltmeter F80 CB-F-3A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -8 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) EDE-G06-FU-3,4 6 Amp Fuses (2) G06 DG-F-2A-A G06-G29/8 G06-G29/9 G06-G29/6 F80-G06/6 EC7-G10 EC7-G07 EC7-HR2 DM9-G10 310102 G06/2a G06/2d G06/2b G06/2e DM9a DM9b DAH-FN-25A DAH-FN-26A DG-CP-75A EDE-SWG-11A DG-G10-IDR2 Isochronous Droop Relay G10 DG-F-2A-A DG-SZ-9585 Governor Actuator G29 DG-F-2A-A DG-SC-9585 Digital Reference Unit (DRU) G06 DG-F-2A-A DG-SM-9585 2301A Governor Controller G06 DG-F-2A-A DG-ST-9585 Magnetic Pickup (MPU-1) G29 DG-F-2A-A DG-SS-9585 Selector Switch G07 DG-F-2A-A DG-G10-TSR1 Test Start Relay G10 DG-F-2A-A DG-G10-TSR2 Test Start Relay G10 DG-F-2A-A DG-G10-TSR3 Test Start Relay G10 DG-F-2A-A DG-G10-R21 Speed Adjust Auxiliary Relay G10 DG-F-2A-A DG-G10-RDT Ramp Down Time Relay G10 DG-F-2A-A DG-G07-IOT Idle Operate Time Relay G07 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-CS-9823-2 Control Switch G06 DG-F-2A-A DG-G06-LSRX Low Speed Auxiliary G06 DG-F-2A-A DG-G29-ES1 Emergency Start Auxiliary Relay G29 DG-F-2A-A DG-G29-ES2 Emergency Start Auxiliary Relay G29 DG-F-2A-A DG-G07-ESS Emergency Start Auxiliary Relay G07 DG-F-2A-A DG-G10-CF-9 Loss of Power Relay G10 DG-F-2A-A EDE-CS-9823-1 Control Switch F80 CB-F-3A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-HR2-PR1 EPS Auxiliary Relay HR2 CB-F-1A-A DG-HR2-HR8 EPS Auxiliary Relay HR2 CB-F-1A-A DG-EC7-R1 Auxiliary Relay EC7 DG-F-2A-A DG-G10-IDR4 Isochronous Droop Relay G10 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -9 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) EDE-G10-FU-7,8 10 Amp Fuses (2) G10 DG-F-2A-A A54-G10/1 A69-G10 G10-G29 DM9-G10 G06-G29/4 F80-G07/8 A54-G07/4 F80-G06/7 F80-G07/7 G10a G10e G10b G10c DM9a DM9b DAH-FN-25A DAH-FN-26A CBA-FN-19 CBA-FN-20 DG-CP-75A EDE-SWG-11A DG-G29-CR1 Auto Start Ready Relay G29 DG-F-2A-A DG-G29-CR2 Auto Start Ready Relay G29 DG-F-2A-A DG-G29-RA1 Air Pressure Auxiliary Relay G29 DG-F-2A-A DG-G29-RA2 Air Pressure Auxiliary Relay G29 DG-F-2A-A DG-G07-R43L3 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-ESS Emergency Start Auxiliary Relay G07 DG-F-2A-A DG-G10-RR Regulator Relay G10 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L5 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-64F Generator Field Ground Relay G06 DG-F-2A-A DG-G10-64FX Generator Field Ground Auxiliary Relay G10 DG-F-2A-A DG-G07-64FXA Generator Field Ground Auxiliary Relay G07 DG-F-2A-A EDE-CS-9824-2 Control Switch G10 DG-F-2A-A DG-G10-23 Thermostat G10 DG-F-2A-A DG-G07-R-DNA Diesel Not Available Auxiliary Relay G07 DG-F-2A-A DG-G07-R-B/I SW CT Bypass/MOP Auxiliary Relay G07 DG-F-2A-A DG-G10-23X Thermostat Auxiliary Relay G10 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -10 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-ZL-9580-12 Indicating Light F80 CB-F-3A-A DG-G29-ESX Emergency Start Aux Relay G29 DG-F-2A-A EDE-ZL-9580-8 Indicating Light F80 CB-F-3A-A EDE-ZL-9518-1 Indicating Light F80 CG-F-3A-A EDE-CS-9824-1 Indicating Light F80 CB-F-3A-A EDE-ZL-9824-1 Indicating Light F80 CB-F-3A-A EDE-SNS-9763-1 Synchronizing Switch F80 CB-F-3A-A EDE-ZL-9802-1 Indicating Light F80 CB-F-3A-A EDE-CS-9824-1 Control Switch F80 CB-F-3A-A DG-A69-RLA LOCA Seal Relay A69 CB-F-1A-A EDE-ZL-9580-6 Indicating Light F80 CB-F-3A-A DG-G10-IDR1 Isochronous Droop Relay G10 DG-F-2A-A DG-G10-IDR2 Isochronous Droop Relay G10 DG-F-2A-A DG-G10-IDR3 Isochronous Droop Relay G10 DG-F-2A-A EDE-ZL-9802-2 Indicating Light G07 DG-F-2A-A DG-G07-IDR4 Isochronous Droop Relay G10 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDS-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A51-52S Circuit Breaker Operated Contact A51 CB-F-1A-A EDE-A52-52S Circuit Breaker Operated Contact A52 CB-F-1A-A EDE-A54-52S Circuit Breaker Operated Contact A54 CB-F-1A-A EDE-A69-60AX Voltage Balance Auxiliary Relay A69 CB-F-1A-A DG-ZL-9580-3 Indicating Light G07 DG-F-2A-A DG-ZL-9518-2 Indicating Light G07 DG-F-2A-A EDE-ZL-9824-1 Indicating Light G10 DG-F-2A-A EDE-ZL-9824-2 Indicating Light G10 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -11 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-ZL-9580-2 Indicating Light G07 DG-F-2A-A DG-ZL-9580-4 Indicating Light G07 DG-F-2A-A DG-ZL-9580-5 Indicating Light G07 DG-F-2A-A MM-CS-6651 Test Push Button with Indicating Light F80 CB-F-3A-A DG-G10-CF8 Loss of Control Power Relay G10 DG-F-2A-A DG-G10-CF9 Loss of Control Power Relay G10 DG-F-2A-A DG-G10-CF10 Loss of Control Power Relay G10 DG-F-2A-A DG-G10-CR45 Annunciator Auxiliary Relay G10 DG-F-2A-A DG-G10-CR42 Annunciator Auxiliary Relay G10 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -12 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 DG-TK-45A Starting Air Compressor Skid Air Receiver Tank DG-20460 A 310524 DG-F-2A-A X X - - HM2 - - - - - - - - DG-TK-45C Notes 1 and 5 3 DG-TK-45B Starting Air Compressor Skid Air Receiver tank DG-20460 A 310524 DG-F-2A-A X X - - HM2 - - - - - - - - DG-TK-45D Notes 1 and 5 4 DG-MM-8A Exhaust Silencer DG-20462 A 310525 DG-F-3E-A X X - - - - - - - - - - - DG-MM-8B Note 1 5 DG-F-36A Air Intake Filter DG-20462 A 310525 DG-F-3E-A X X - - - - - - - - - - - DF-F-36B Note 1 6 DG-TK-26A Fuel Oil Storage Tank DG-20459 A 310525 202264 DG-F-1A-A X X - - - - - - - - - - - DG-TK-26B Notes 1 and 2 7 DG-TK-78A Fuel Oil Day Tank DG-20459 A 310525 DG-F-3C-A X X - - - - - - - - - - - DG-TK-78B Note 1 8 DG-P-38A Fuel Oil Transfer Pump DG-20459 A 310524 202265 DG-F-1A-A X X X - N75 DG-BM7-52 460 V AC Circuit Breaker BM7 CB-F-1A-A BE4-BM7 BM7-RT8 BM7-N75 310857 BM7a BM7c CBA-FN-19 CBA-FN-20 DAH-FN-25A DAH-FN-26A EDE-MCC-521 DG-P-38B DG-CS-9503 Control Switch with Indication BE4 DG-F-2A-A DG-LS-FLC Fuel Low Level Switch RT8 DG-F-3C-A DG-BM7-42 Motor Starter BM7 CB-F-1A-A DG-BM7-49 Thermal Overload Relay BM7 CB-F-1A-A DG-BM7-FU Fuse BM7 CB-F-1A-A 9 DG-P-119A Engine-Driven Fuel Oil Pump DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-119B Notes 1 and 4 10 DG-P-115A Engine-Driven Lube Oil Pump DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-115B Notes 1 and 4 11 DG-TK-102A Lube Oil Reservoir DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-TK-102B Notes 1 and 4 12 DG-P-228A Engine-Driven Rocker Arm Lube Pump DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-228B Notes 1 and 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -13 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 DG-E-41A Lube Oil Heat Exchanger DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-E-41B Notes 1 and 4 14 DG-TK-46A Diesel Generator 1A Component Cooling Water Expansion Tank DG-20461 A 310525 DG-F-3C-A X X - - - - - - - - - - - DG-TK-46B Notes 1 and 4 15 DG-E-42A Diesel Generator 1A Component Cooling Water Heat Exchanger DG-20461 A 310767 805217 PAB-F-3A-Z X X - - - - - - - - - - Service Water DG-E-42B Notes 1 and 3 16 DG-P-121A Engine-Driven Jacket Coolant Pump DG-20461 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-121B Notes 1 and 4 17 DG-P-231A Engine-Driven Air Coolant Pump DG-20461 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-231B Notes 1 and 4 17a DG-C-2A DG Starting Air Compressor DG-20460 A 310524 DG-F-2A-A X X X - NC3 DG-BM3-52 460 v AC Circuit Breaker BM3 DG-F-2A-A BM3-NC3 BM3-HM2 BM3-HR2 310857 BM3a BM3c DAH-FN-25A DAH-FN-26A EDE-MCC-511 DG-C-2-B Note 5 DG-CS-9559 Control Switch BM3 DG-F-2A-A DGA-PS-APCI Pressure Switch HM2 DG-F-2A-A DG-PS-APCZ Pressure Switch HM2 DG-F-2A-A DG-HR2-HR9 EPS Relay HR2 CB-F-1A-A DG-BM3-42 Motor Starter BM3 CB-F-1A-A DG-BM3-49 Thermal O. L. BM3 CB-F-1A-A DG-BM3-FU Fuse BM3 CB-F-1A-A 17b DG-SKD-17A Diesel Generator 1A Starting Air Compressor Skid DG-20460 A 310524 DG-F-2A-A X X X - HM2 DG-E39/4-52 120 v AC Circuit Breaker E39 DG-F-2A-A E39-HM2 BM3-HM2 310857 E39/4a E39/4b DAH-FN-25A DAH-FN-26A EDE-MCC-E511 120 v AC Dist. Panel DG-SKD-17B Note 5 DG-HM2-52 120 v AC Circuit Breaker HM2 DG-F-2A-A DG-HM2-ATM Auto Drain Timer HM2 DG-F-2A-A DG-V-253A Auto Drain Solenoid Vlv. HM2 DG-F-2A-A DG-HM2-ICT Motor Synchronous Timer HM2 DG-F-2A-A DG-V-279A Left Chamber Inlet Sol. Vlv. HM2 DG-F-2A-A DG-V-280A Right Chamber Inlet Sol. Vlv. HM2 DG-F-2A-A DG-V-285A Repressurizing Sol. Vlv. HM2 DG-F-2A-A DG-V-288A Left Chamber Exhaust Sol. Vlv. HM2 DG-F-2A-A DG-V-289A Right Chamber Exhaust Sol. Vlv. HM2 DG-F-2A-A DG-V-HM2-KR Aux. Relay HM2 DG-F-2A-A DG-BM3-42 Motor Starter BM3 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -14 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 17c DG-C-18A DG Backup Operating Air Compressor DG-20460 A 310524 DG-F-2A-A X X X - ML7 DG-BS3-52 DG-BS3-42 DG-BS3-49 DG-BS3-FU DG-CS-9526 DGA-PS-APC3 DG-PS-APC4 DG-V-325A 460 v AC Ckt Bkr. Motor Starter Thermal O. L. Fuse Control Switch Pressure Switch Pressure Switch Unloader Sol. Vlv. BS3 BS3 BS3 BS3 BS3 HM2 HM2 UBO DG-F-2A-A DG-F-2A-A DG-F-2A-A DG-F-2A-A DG-F-2A-A DG-F-2A-A DG-F-2A-A DG-F-2A-A BS3-ML7 BS3-HM2

BS3-UB0 310857 BS3a BS3c DAH-FN-25A DAH-FN-26A EDE-MCC-511 DG-C-18B Note 5 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -15 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 DG-DG-1B Diesel Generator 1B DG-20467 B 310524 DG-F-2B-A X X X X HA2 DG-CS-9520-2 Control Switch (Push Button) G19 DG-F-2B-A A74-G18/7 A74-G30/6 E94-G30/1 G18-G30 G18-G30/1 G18-G30/2 G18-HR4 G19-G30 G19-G30/6 G18-G30/8 F81-FB0 F81-G18 F81-G18/1 F81-G19 F81-G19/E F81-G19/F 310857 E94/8a E94/8n E94/8b E94/8p E94/8c E94/8r E94/8d E94/8e E94/8f E94/8g E94/8s DBA-FN-32 DBA-FN-33 DAH-FN-25B DAH-FN-26B EDE-PP-111B D/G Starting Air DG-DG-1A DC-CS-9521 Control Switch (Push Button) G19 DG-F-2B-A DG-CS-9522-3 Control Switch (Push Button) G19 DG-F-2B-A DG-CS-9522-4 Control Switch (Push Button) G19 DG-F-2B-A DG-CS-9527-2 Control Switch (Push Button) G19 DG-F-2B-A DG-CS-9528-2 Control Switch (Push Button) G19 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A DG-G30-OP2 Oil Pressure Relay G30 DG-F-2B-A DG-G30-CR1 Ready for Auto Start Relay G30 DG-F-2B-A DG-G30-4A Start Relay G30 DG-F-2B-A DG-G30-T2A Cranking Time Control Time Delay Relay G30 DG-F-2B-A DG-ZL-9590-9 Start Ckt No 1 Signal Indicating Light G19 DG-F-2B-A DG-G30-ES1 Emergency Start Relay G30 DG-F-2B-A DG-G20-TSR1 Test Start Relay G20 DG-F-2B-A DG-G20-TSR2 Test Start Relay G20 DG-F-2B-A DG-G20-TSR3 Test Start Relay G20 DG-F-2B-A DG-G20-RDT Ramp Down Time Rela y G20 DG-F-2B-A DG-G19-IOT Idle Operate Time Relay G19 DG-F-2B-A DG-G18-LSRX Low Speed Auxiliary Relay G18 DG-F-2B-A DG-FY-AS1 Air Start Solenoid Valve G30 DG-F-2B-A DG-G30-OP3 Oil Pressure Relay G30 DG-F-2B-A DG-G30-CR2 Ready for Auto Start Relay G30 DG-F-2B-A DG-G30-TACH Tachometer G30 DG-F-2B-A DG-G30-4B Start Relay G30 DG-F-2B-A DG-G30-T2B Cranking Time Control Time Delay Relay G30 DG-F-2B-A DG-ZL-9590-10 Start Ckt No 2 Signal Indicating Light G19 DG-F-2B-A DG-G30-ES2 Emergency Start Relay G30 DG-F-2B-A DG-FY-AS2 Air Start Solenoid Valve G30 DG-F-2B-A DG-G30-OP4 Oil Pressure Relay G30 DG-F-2B-A DG-G30-5E Emergency Stop Relay G30 DG-F-2B-A DG-G30-5 Normal Stop Relay G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -16 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G30-5A Shutdown Relay G30 DG-F-2B-A DG-G30-5B Shutdown Relay G30 DG-F-2B-A DG-FY-SDS Shutdown Solenoid Valve G30 DG-F-2B-A DG-G30-T3A Alarm Set Time Delay Relay G30 DG-F-2B-A DG-G30-ASA Air Start Relay G30 DG-F-2B-A DG-G30-ASB Air Start Relay G30 DG-F-2B-A DG-G30-TR Engine Velocity Transmitter G30 DG-F-2B-A DG-G30-SG Signal Generator G30 DG-F-2B-A DG-G30-HSR High Speed Relay G30 DG-F-2B-A DG-G30-LSR Low Speed Relay G30 DG-F-2B-A DG-G30-ASR Starting Air Shutoff Relay G30 DG-F-2B-A DG-G30-BDR Barring Device Relay G30 DG-F-2B-A DG-G30-SFR Start Failure Relay G30 DG-F-2B-A SG-G30-SDR Engine Trouble Shutdown Relay G30 DG-F-2B-A DG-G30-EOR Engine Overspeed Relay G30 DG-F-2B-A EDE-A89-RLA SI Signal Lockout Relay A89 CB-F-1B-A DG-G30-OTH High Oil Temperature Relay G30 DG-F-2B-A DG-G30-CTH High Coolant Temperature Relay G30 DG-F-2B-A EDE-A74-TD2 Test Device A74 CB-F-1B-A EDE-A89-TD2 Test Device A89 CB-F-1B-A DG-G30-EST Emergency Start Time Delay Relay G30 DG-F-2B-A DG-G30-ESX Emergency Start Auxiliary Relay G30 DG-F-2B-A DG-G30-RA1 Air Pressure Auxiliary Relay G30 DG-F-2B-A DG-G30-RA2 Air Pressure Auxiliary Relay G30 DG-F-2B-A DG-G30-CF3 Power Available Relay G30 DG-F-2B-A DG-G30-CF4 Power Available Relay G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -17 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G19-R43L1 Selector Switch Auxiliary Latch Relay (Local) G19 DG-F-2B-A DG-G19-R43L2 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G19 DG-F-2B-A DG-G30-FU 10 Amp Fuses (10) G30 DG-F-2B-A DG-G19-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G19 DG-F-2B-A DG-G19-R43R2 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-HR4-PR1 EPS Auxiliary Relay HR4 CB-F-1B-A DG-HR4-PRIX EPS Auxiliary Relay HR4 CB-F-1B-A DG-SS-EOS Engine Overspeed Switch G30 DG-F-2B-A DG-PS-APL1 Air Pressure Low Switch G30 DG-F-2B-A DG-PS-APL2 Air Pressure Low Switch G30 DG-F-2B-A DG-G19-FU 10 Amp Fuses (20) G19 DG-F-2B-A DG-G19-R43L5 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-PS-CPS Coolant Pressure Switch G30 DG-F-2B-A DG-PS-OPL2 Oil Low Pressure Switch G30 DG-F-2B-A DG-PS-OPL3 Oil Low Pressure Switch G30 DG-F-2B-A DG-PS-OPL4 Oil Low Pressure Switch G30 DG-F-2B-A DG-G30-CTH-1 Coolant High Temperature Auxiliary Relay G30 DG-F-2B-A DG-G30-OTH-1 Oil High Temperature Auxiliary Relay G30 DG-F-2B-A DG-ZS-BD1 Barring Device Position Switch G30 DG-F-2B-A DG-G30-D1 P-N Junction Diode G30 DG-F-2B-A DG-ZS-BD2 Barring Device Position Switch G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -18 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) EDE-A74-86DP DG Primary Protection Lockout Relay A74 CB-F-1B-A EDE-A89-86DB DG Backup Protection Lockout Relay A89 CB-F-1B-A EDE-A74-TS Test Start Control Switch A74 CB-F-1B-A DG-G30-CF1 Power Available Relay G30 DG-F-2B-A DG-G30-CF2 Power Available Relay G30 DG-F-2B-A EDE-ZL-9594 Monitoring Circuit Indicating Light G19 DG-F-2B-A EDE-ZL-9594-1 Monitoring Circuit Indicating Light G30 DG-F-2B-A DG-PS-OPL1 Oil Low Pressure Switch G30 DG-F-2B-A DG-G30-OP1 Oil Pressure Relay G30 DG-F-2B-A DG-PS-FPLA Fuel Low Pressure Switch G30 DG-F-2B-A DG-G30-FPL Fuel Pressure Relay G30 DG-F-2B-A DG-PS-CPLA Jacket Coolant Low Pressure Switch G30 DG-F-2B-A DG-G30-CPL Jacket Coolant Pressure Relay G30 DG-F-2B-A DG-PS-IPLA Intercooler Low Pressure Switch G30 DG-F-2B-A DG-G30-IPL Intercoolant Pressure Relay G30 DG-F-2B-A DG-G30-CF5 Power Available Relay G30 DG-F-2B-A DG-G30-OPC Oil Pump Control Relay G30 DG-F-2B-A DG-G30-5B Shutdown Auxiliary Relay G30 DG-F-2B-A DG-G30-TRP TR Control Power Relay G30 DG-F-2B-A DG-G30-FPC Auxiliary Fuel Oil Pump Control Relay G30 DG-F-2B-A DG-G30-CPC Coolant Pump Control Relay G30 DG-F-2B-A DG-FY-CSV-B Jacket Coolant Auxiliary Valves Solenoid G30 DG-F-2B-A DG-G30-IPC Coolant Pump Control Relay G30 DG-F-2B-A DG-FY-ISV-B Intercooler Auxiliary Valves Solenoid G30 DG-F-2B-A DG-FB0-K603B Protection System Output Relay FB0 CB-F-3A-A EDE-CS-9528-1 Control Switch F81 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -19 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) EDE-CS-9527-1 Control Switch F81 CB-F-3A-A EDE-CS-9520-1 Control Switch F81 CB-F-3A-A DG-FB0-K-608B Protection System Output Relay FB0 CB-F-3A-A EDE-CS-9522-1 Control Switch F81 CB-F-3A-A EDE-CS-9522-2 Control Switch F81 CB-F-3A-A EDE-G19-FU-17,18 6 Amp Fuses (2) G19 DG-F-2B-A DP1-G20 F81-G19/9 310102 G19/2a G19/2g G19/2b G19/2c DP1a DP1b DAH-FN-25B DAH-FN-26B DC-CP-75B EDE-SWG-11B EDE-SS-9710 Selector Switch G18 DG-F-2B-A DG-G19-CF6 Auxiliary Relay G19 DG-F-2B-A DG-G19-R43L1 Selector Switch Auxiliary Latch Relay (Local) G19 DG-F-2B-A DG-G19-R43L2 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L3 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L5, R43L6 Selector Switch

Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G19 DG-F-2B-A DG-G19-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G19 DG-F-2B-A DG-G19-R43R2 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A EDE-SNS-9737-1 Selector Switch F81 CP-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -20 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) EDE-CS-9717-1 Control Switch F81 DG-F-2B-A EDE-CS-9719-1 Control Switch F81 DG-F-2B-A EDE-CS-9710-1 Control Switch F81 DG-F-2B-A EDE-SNS-9737-2 Selector Switch G18 DG-F-2B-A EDE-CS-9717-3 Control Switch G19 DG-F-2B-A EDE-CS-9719-3 Control Switch G19 DG-F-2B-A EDE-CS-9710-3 Control Switch G19 DG-F-2B-A DG-G19-FU17B, 18B 6 Amp Fuses G19 DG-F-2B-A EDE-G18-FU-9,10 50 Amp Fuses G18 DG-F-2B-A 310102 HA2a HA2c HA2b HA2d DP1a DP1b DAH-FN-25B DAH-FN-26B CBA-FN-32 CBA-FN-33 EDE-SWG-11B DG-A89-XFMR Grounding Transformer A89 CB-F-1B-A A89-G18 G18-HF8 A89-HP1 DP1-G20 DG-HF8-XF DG Field HF8 DG-F-2B-A DG-G18-SEVR-PC Static Exciter Voltage Regulator Power Chassis G18 DG-F-2B-A DG-SM-9587 Governor Control (2301A) G18 DG-F-2B-A DG-G20-SEVR-CC Voltage Regulator Control Chassis G20 DG-F-2B-A DG-GT4-PT1 Potential Transformer GT4 DG-F-2B-A DG-GT4-PT2 Potential Transformer GT4 DG-F-2B-A DG-GTR-PPT4 Power Transformer GT4 DG-F-2B-A DG-GTR-CCT Current Transformer 2000/5 GT4 DG-F-2B-A DG-G20-IDR1 Isochronous Droop Relay G20 DG-F-2B-A EDE-A89-60 Voltage Balance Relays A89 CB-F-1B-A DG-G20-64F Generator Field Failure Relay G20 DG-F-2B-A DG-HP1-NCB DG Neutral Connection Box HP1 DG-F-2B-A DG-GT4-XCT1,2,3 Generator Current Transformers (2000/5) øA,øB, øC GT4 DG-F-2B-A DG-VM-9712-2 Field Voltmeter G20 DG-F-2B-A DG-G20-DCT Field Voltage Transducer G20 DG-F-2B-A DG-G18-SH 50 MV Field Shunt G18 DG-F-2B-A DG-AM-9712-2 DC Field Ammeter G20 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -21 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G20-ATR Current Transducer G20 DG-F-2B-A DG-G20-CF10 Loss of Power Relay G20 DG-F-2B-A DG-A89-64 Ground Fault Sensing Relay A89 CB-F-1B-A DG-G20-FU-22,23 1 Amp Fuses G20 DG-F-2B-A DG-G19-IL10 Diode Failure Light G19 DG-F-2B-A DG-G20-K2 Field Flashing Contactor G20 DG-F-2B-A EDE-G18-FU-1,2 1B,2B 10 Amp Fuses (4) G18 DG-F-2B-A G18-G30/5 DP1-G20 F81-G18/4 F81-G18/5 F81-G18/6 F81-G20/1 310102 G18/1a G18/1f G18/1b G18/1c G18/1d DP1a DP1b DAH-FN-25B DAH-FN-26B DG-CP-75B EDE-SWG-11B DG-G19-R43R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A EDE-CS-9825-2 Control Switch (Push Button) G20 DG-F-2B-A DG-G30-HSR High Speed Relay G30 DG-F-2B-A DG-G30-LSR Low Speed Relay G30 DG-F-2B-A DG-G30-ES1 Emergency Start Relay G30 DG-F-2B-A DG-G30-ES2 Emergency Start Relay G30 DG-F-2B-A DG-SS-9587 Selector Switch G19 DG-F-2B-A DG-ZL-9590-11 Field Flash Signal Indicating Light G20 DG-F-2B-A DG-G19-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G19 DG-F-2B-A DG-G30-5A DG Shutdown Relay G30 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G18-LSRX Low Speed Auxiliary Relay G18 DG-F-2B-A DG-G18-LSRXX Time Delay Relay G18 DG-F-2B-A EDE-CS-9811-1 Push Button G20 DG-F-2B-A EDE-CS-9811-2 Push Button G20 DG-F-2B-A DG-G18-SEVR-PC Static Exciter Voltage Regulator Power Chassis G18 DG-F-2B-A EDE-G20-NM Null Meter G20 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-CS-9826-2 Control Switch G20 DG-F-2B-A EDE-CS-9827-2 Control Switch G20 DG-F-2B-A DG-G20-RR Regulator Relay G20 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -22 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G20-SEVR-CC Static Exciter Voltage Regulator Control Chassis G20 DG-F-2B-A DG-G20-CF8 Loss of Power Relay G20 DG-F-2B-A EDE-CS-9825-1 Push Button Switch F81 CB-F-3A-A EDE-CS-9827-1 Control Switch F81 CB-F-3A-A EDE-CS-9826-1 Control Switch F81 CB-F-3A-A EDE-VM-9783 Null Voltmeter F81 CB-F-3A-A EDE-G18-FU-3,4 3B, 4B 6 Amp Fuses (4) G18 DG-F-2B-A G18-G30/6 G18-G30/9 G18-G30/A G18/2a G18/2d G18/2b G18/2e DAH-FN-25B DAH-FN-26B DG-CP-75B EDE-SWG-11B DG-G20-IDR1 Isochronous Droop Relay G20 DG-F-2B-A DG-G20-IDR2 Isochronous Droop Relay G20 DG-F-2B-A F81-G18/8 ED9-G19 ED9-G20 ED9-HR4 DP1-G20

DP1a DP1b DG-SZ-9587 Governor Actuator G30 DG-F-2B-A DG-SC-9587 Digital Reference Unit (DRU) G18 DG-F-2B-A DG-SM-9587 2301A Governor Controller G18 DG-F-2B-A DG-ST-9587 Magnetic Pickup (MPU-1) G30 DG-F-2B-A DG-SS-9587 Selector Switch G19 DG-F-2B-A DG-G20-TSR1 Test Start Relay G20 DG-F-2B-A DG-G20-TSR2 Test Start Relay G20 DG-F-2B-A DG-G20-TSR3 Test Start Relay G20 DG-F-2B-A DG-G20-R21 Speed Adjust Auxiliary Relay G20 DG-F-2B-A DG-G20-RDT Ramp Down Time Relay G20 DG-F-2B-A DG-G19-IOT Idle Operate Time Relay G19 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-CS-9828-2 Control Switch G18 DG-F-2B-A DG-G18-LSRX Auxiliary Relay G18 DG-F-2B-A DG-G30-ES1 Emergency Start Auxiliary Relay G30 DG-F-2B-A DG-G19-ESS Emergency Start Auxiliary Relay G19 DG-F-2B-A DG-G30-ES2 Emergency Start Auxiliary Relay G30 DG-F-2B-A DG-G20-CF-9 Loss of Power Relay G20 DG-F-2B-A EDE-CS-9828-1 Control Switch F81 CB-F-3A-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -23 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-HR4-PR1 EPS Auxiliary Relay HR4 CF-F-1B-A DG-HR4-HR8 EPS Auxiliary Relay HR4 CB-F-1B-A DG-ED9-R1 Auxiliary Relay ED9 DG-F-2B-A DG-G20-IDR4 Isochronous Droop Relay G20 DG-F-2B-A EDE-G20-FU-7,8 7B, 8B 10 Amp Fuses (4) G20 DG-F-2B-A A74-G20/1 G20-G30 A89-G20 DP1-G20 F81-G19/8 A74-G19/4 F81-G18/7 F81-G19/7 G18-G30/4 G20a G20e G20b G20c DP1a DP1b DAH-FN-25B DAH-FN-26B CBA-FN-32 CBA-FN-33 DG-CP-75B EDE-SWG-11B DG-G30-CR1 Auto Start Ready Relay G30 DG-F-2B-A DG-G30-CR2 Auto Start Ready Relay G30 DG-F-2B-A DG-G30-RA1 Air Pressure Auxiliary Relay G30 DG-F-2B-A DG-G30-RA2 Air Pressure Auxiliary Relay G30 DG-F-2B-A DG-G19-R43L3 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-ESS Emergency Start Auxiliary Relay G19 DG-F-2B-A DG-G20-RR Regulator Relay G20 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L6 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L5 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R-DNA Diesel Not Available Auxiliary Relay G19 DG-F-2B-A DG-G19-R-B/I Switch Circuit Bypass/Inoperable Auxiliary Relay G19 DG-F-2B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -24 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G18-64F Generator Field Ground Relay G18 DG-F-2B-A DG-G20-64FX Generator Field Ground Auxiliary Relay G20 DG-F-2B-A DG-G19-64FXA Generator Field Ground Auxiliary Relay G19 DG-F-2B-A EDE-CS-9829-2 Control Switch G20 DG-F-2B-A DG-G20-23 Thermostat G20 DG-F-2B-A DG-G20-23X Thermostat Auxiliary Relay G20 DG-F-2B-A DG-G20-IDR1 Isochronous Droop Relay G20 DG-F-2B-A DG-G20-IDR2 Isochronous Droop Relay G20 DG-F-2B-A DG-G20-IDR3 Isochronous Droop Relay G20 DG-F-2B-A DG-G20-IDR4 Isochronous Droop Relay G20 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-A71-52S Circuit Breaker Operated Contact A71 CB-F-1B-A EDE-A72-52S Circuit Breaker Operated Contact A72 CB-F-1B-A EDE-A74-52S Circuit Breaker Operated Contact A74 CB-F-1B-A EDE-A89-60AX Voltage Balance Auxiliary Relay A89 CB-F-1B-A DG-ZL-9590-2 Indicating Light G19 DG-F-2B-A DG-ZL-9590-3 Indicating Light G19 DG-F-2B-A DG-ZL-9528-2 Indicating Light G19 DG-F-2B-A EDE-ZL-9829-1 Indicating Light G20 DG-F-2B-A EDE-ZL-9812-2 Indicating Light G19 DG-F-2B-A EDE-ZL-9829-2 Indicating Light G20 DG-F-2B-A DG-G20-CF8 Loss of Control Power Relay G20 DG-F-2B-A DG-G20-CF9 Loss of Control Power Relay G20 DG-F-2B-A DG-G20-CF10 Loss of Control Power Relay G20 DG-F-2B-A DG-G20-CR45 Annunciator Auxiliary Relay G20 DG-F-2B-A DG-C20-CR42 Annunciator Auxiliary Relay G20 DG-F-2B-A DG-ZL-9590-12 Indicating Light F81 CB-F-3A-A DG-G30-ESX Emergency Start Aux Relay G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -25 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-ZL-9590-4 Indicating Light G19 DG-F-2B-A DG-ZL-9590-5 Indicating Light G19 DG-F-2B-A DG-ZL-9590-8 Indicating Light F81 CB-F-3A-A DG-ZL-9528-1 Indicating Light F81 CB-F-3A-A EDE-ZL-9829-4 Indicating Light F81 CB-F-3A-A EDE-CS-9829-1 Indicating Light F81 CB-F-3A-A EDE-SNS-9737-1 Synchronizing Switch F81 CB-F-3A-A EDE-CS-9829-1 Control Switch F81 CB-F-3A-A DG-A89-RLA LOCA Seal Relay A89 CB-F-1B-A DG-ZL-9590-6 Indicating Light F81 CB-F-3A-A MM-CS-6653 Test Push Button and Indicating Light F81 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -26 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 DG-TK-45C Starting Air Compressor Skid Air Receiver Tank DG-20465 B 310524 DG-F-2B-A X X - - HM3 - - - - - - - - DG-TK-45A Notes 1 and 7 20 DG-TK-45D Starting Air Compressor Skid Air Receiver Tank DG-20465 B 310524 DG-F-2B-A X X - - HM3 - - - - - - - - DG-TK-45B Notes 1 and 7 21 DG-MM-8B Exhaust Silencer DG-20467 B 310525 DG-F-3F-A X X - - - - - - - - - - - DG-MM-8A Note 1 22 DG-F-36B Air Intake Filter DG-20467 B 310525 DG-F-3F-A X X - - - - - - - - - - - DG-F-36A Note 1 23 DG-TK-26B Fuel Oil Storage Tank DG-20464 B 310524 202264 DG-F-1B-A X X - - - - - - - - - - - DG-TK-26A Notes 1 and 2 24 DG-TK-78B Fuel Oil Day Tank DG-20459 B 310525 DG-F-3D-A X X - - - - - - - - - - - DG-TK-78A Note 1 25 DG-P-38B Fuel Oil Transfer Pump DG-20464 B 310524 202264 DG-F-1B-A X X X - N76 DG-BP7-52 460 V AC Circuit Breaker BP7 CB-F-1B-A BE5-BP7 BP7-RU1 BP7-N76 310857 BP7a BP7c CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B EDE-MCC-621 DG-P-38A - DG-CS-9506 Control Switch with Indication BE5 DG-F-2B-A DG-LS-FLC Fuel Low Level Control Switch RU1 DG-F-3D-A DG-BP7-42 Motor Starter BP7 CB-F-1B-A DG-BP7-49 Thermal Overload Relay BP7 CB-F-1B-A DG-BP7-FU Fuse BP7 CB-F-1B-A 26 DG-P-119B Engine-Driven Fuel Oil Pump DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-119A Notes 1 and 6 27 DG-P-115B Engine-Drive Lube Oil Pump DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-115A Notes 1 and 6 28 DG-TK-102B Lube Oil Reservoir DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-102A Notes 1 and 6 29 DG-P-228B Engine-Driven Rocker Arm Lube Pump DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-228A Notes 1 and 6 30 DG-E-41B Lube Oil Heat Exchanger DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-E-41A Notes 1 and 6 31 DG-TK-46B Diesel Generator 1B Component Cooling Water Expansion Tank DG-20466 B 310525 DG-F-3D-A X X - - - - - - - - - - - DG-TK-46A Note 1 32 DG-E-42B Diesel Generator 1B Component Cooling Water Heat Exchanger DG-20466 B 310767 805217 PAB-F-3A-Z X X - - - - - - - - - - Service Water DG-E-42A Notes 1 and 3 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -27 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 33 DG-P-121B Engine-Driven Jacket Coolant Pump DG-20466 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-121A Notes 1 and 4 34 DG-P-231B Engine-Driven Air Coolant Pump DG-20466 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-231A Notes 1 and 6 35 DG-PV-7A-2 Lube Oil Cooler Differential Pressure Control Valve DG-20461 A 310524 DG-F-2A-A X X - X HA1 DG-PT-7A-3 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-PV-7B-2 Note 8 HA1 DG-PT-7A-4 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A HA1 DG-PDT-7A-2 Differential Pressure Transmitter G29 DG-F-2A-A HA1 DG-PDC-7A-2 Differential Pressure Controller G29 DG-F-2A-A 36 DG-TCV-7A-2 Jacket Coolant Temperature Control Valve DG-20461 A 310524 DG-F-2A-A X X X X HA1 DG-CP-907A Air Cooler Coolant and Jacket Coolant Temp. Control Panel G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-TCV-7B-2 Note 8 37 DG-PV-7A-1 Jacket Coolant Differential Pressure Control Valve DG-20461 A 310524 DG-F-2A-A X X - X HA1 DG-PT-7A-1 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-PV-7B-1 Note 9 DG-PT-7A-2 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A DG-PDT-7A-1 Differential Pressure Transmitter G29 DG-F-2A-A DG-PDC-7A-1 Differential Pressure Controller G29 DG-F-2A-A 38 DG-TCV-7A-1 Jacket Coolant Temperature Control Valve DG-20461 A 310524 DG-F-2A-A X X X X HA1 DG-CP-907A Air Cooler Coolant and Jacket Coolant Temp. Control Panel G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-TCV-7B-1 Note 9 39 DG-F-64A Lube Oil Filter DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-F-64B Notes 1 and 4 40 DG-F-23A Lube Oil Duplex Filter DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-F-23B Notes 1 and 4 41 DG-S-4A Lube Oil Strainer DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-S-4B Notes 1 and 4 42 DG-S-85A Lube Oil Sump Suction Strainer DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-S-85B Notes 1 and 4 43 DG-S-5A Fuel Oil Storage Tank Duplex Strainer DG-20459 A 310524 202264 DG-F-1A-A X X - - - - - - - - - - - DG-S-5B Notes 1 and 2 44 DG-S-6A Fuel Oil Day Tank Duplex Strainer DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-S-6B Notes 1 and 4 45 DG-F-65A Fuel Oil Duplex Filter DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-F-65B Notes 1 and 4 46 DG-TK-110A Fuel Oil Accumulator Tank DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-TK-110B Notes 1 and 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -28 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 47 DG-PV-7B-2 Lube Oil Cooler Differential Pressure Control Valve DG-20466 B 310524 DG-F-2B-A X X - X HA2 DG-PT-7B-3 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DC-PV-7A-2 Note 10 DG-PT-7B-4 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A DG-PDT-7B-2 Differential Pressure Transmitter G30 DG-F-2B-A DG-PDC-7B-2 Differential Pressure Controller G30 DG-F-2B-A 48 DG-TCV-7B-2 Air Cooler Coolant Temperature Control Valve DG-20466 B 310524 DG-F-2B-A X X X X HA2 DG-CP-907B Air Cooler Coolant and Jacket Coolant Temp. Control Panel G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DG-TCV-7A-2 Note 10 49 DG-PV-7B-1 Jacket Coolant Differential Pressure Control Valve DG-20466 B 310524 DG-F-2B-A X X - X HA2 DG-PT-7B-1 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DG-PV-7A-1 Note 11 DG-PT-7B-2 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A DG-PDT-7B-1 Differential Pressure Transmitter G30 DG-F-2B-A DG-PDC-7B-1 Differential Pressure Controller G30 DG-F-2B-A 50 DG-TCV-7B-1 Jacket Coolant Temperature Control Valve DG-20466 B 310524 DG-F-2B-A X X X X HA2 DG-CP-907B Air Cooler Coolant and Jacket Coolant Temp. Control Panel G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DG-TCV-7A-1 Note 11 - - - 51 DG-F-64B Lube Oil Filter DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-64A Notes 1 and 6 52 DG-F-23B Lube Oil Duplex Filter DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-23A Notes 1 and 6 53 DG-S-4B Lube Oil Strainer DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-S-4A Notes 1 and 6 54 DG-S-85B Lube Oil Sump Suction Strainer DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-S-85A Notes 1 and 6 55 DG-S-5B Fuel Oil Storage Tank Duplex Strainer DG-20464 B 310524 202264 DG-F-1B-A X X - - - - - - - - - - - DG-S-5A Notes 1 and 2 56 DG-S-6B Fuel Oil Day Tank Duplex Strainer DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-S-6A Notes 1 and 6 57 DG-F-65B Fuel Oil Duplex Filter DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-65A Notes 1 and 6 58 DG-TK-110B Fuel Oil Accumulator Tank DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-TK-110A Notes 1 and 6 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -29 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 59 DG-C-2B DG Starting Air Compressor DG-220465 B 310524 DG-F-2B-A X X X - NC4 DG-BP3-52 460 v AC Circuit Breaker BP3 DG-F-2B-A BP3-NC4 BP3-HM3 BP3-HR4 310857 BP3a BP3c DAH-FN-25B DAH-FN-26B EDE-MCC-611 DG-C-2A Note 7 DG-CS-9569 Control Switch BP3 DG-F-2B-A DGB-PS-APCI Pressure Switch HM3 DG-F-2B-A DGB-PS-APCZ Pressure Switch HM3 DG-F-2B-A DG-HR4-HR9 EPS Relay HR3 CB-F-1B-A DG-BP3-42 Motor Starter BP3 CB-F-1B-A DG-BP3-49 Thermal O. L. BP3 CB-F-1B-A DG-BP3-FU Fuse BP3 CB-F-1B-A 59a DG-C-18B DG Backup Operating Air Compressor DG-20465 B 310524 DG-F-2B-A X X X - ML8 DG-BS5-52 460 v AC Ckt Bkr. BS5 DG-F-2B-A BS5-ML8 BS5-HM3 310857 BS5a BS5c DAH-FN-25B DAH-FN-26B EDE-MCC-611 DG-C-18A Note 7 DG-BS5-42 Motor Starter BS5 DG-F-2B-A DG-BS5-49 Thermal O. L. BS5 DG-F-2B-A DG-BS5-FU Fuse BS5 DG-F-2B-A DG-CS-9536 Control Switch BS5 DG-F-2B-A DGB-PS-APC3 Pressure Switch HM3 DG-F-2B-A DGB-PS-APC4 Pressure Switch HM3 DG-F-2B-A DG-V-325B Unloader Sol. Vlv. UB1 DG-F-2B-A BS5-UB1 60 DG-SKD-17B Diesel Generator 1B Starting Air Compressor Skid DG-20465 B 310524 DG-F-2B-A X X X - HM3 DG-E47/4-52 120 v AC Circuit Breaker E47 DG-F-2B-A E47-HM3 BP3-HM3/1 310857 E47/4a E47/4b DAH-FN-25B DAH-FN-26B EDE-MCC-E611 120 v AC Dist. Panel DG-SKD-17A Note 7 DG-HM3-52 120 v AC Circuit Breaker HM3 DG-F-2B-A DG-HM3-ATM Auto Drain Timer HM3 DG-F-2B-A DG-V-253B Auto Drain Solenoid Vlv. HM3 DG-F-2B-A DG-HM3-ICT Motor Synchronous Timer HM3 DG-F-2B-A DG-V-279B Left Chamber inlet Sol. Vlv. HM3 DG-F-2B-A DG-V-280B Right Chamber inlet Sol. Vlv. HM3 DG-F-2B-A DG-V-285B Repressurizing Sol. Vlv. HM3 DG-F-2B-A DG-V-288B Left Chamber Exhaust Sol. Vlv. HM3 DG-F-2B-A DG-V-289B Right Chamber Exhaust Sol. Vlv. HM3 DG-F-2B-A DG-V-HM3-KR Aux. Relay HM3 DG-F-2B-A DG-BP3-42 Motor Starter BP3 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -30 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 61 DG-CP-907A Diesel Generator 1A Air Cooler Coolant & Jacket Coolant Temp. Control Panel DG-20461 A 310524 DG-F-2A-A X X X X G29 DG-EH9/17-52 120 v AC Circuit Breaker EH9 CB-F-1A-A EH9-G29 310857 EH9/17a EH9/17c CBA-FN-19 CBA-FN-20 DAH-FN-25A DAH-FN-26A EDE-PP-1E DG-CP-907B Notes 8 & 9 DGA-TIC-9602 Jacket Coolant Temp. Indi. Controller G29 DG-F-2A-A DGA-TT-9602-1 & 2 Jacket Coolant Temp. Transmitters G29 DG-F-2A-A DGA-TE-9602-1 & 2 Jacket Coolant Temp. Elements G29 DG-F-2A-A DGA-ZC-9602 Jacket Coolant Temp . Dig. Vlv. Controller (I/P) G29 DG-F-2A-A DGA-ZY-9602 Jacket Coolant Temp. Cont. Vlv. Pos. Sensor G29 DG-F-2A-A DGA-TIC-9612 Air Cooler Coolant Temp. Indi. Controller G29 DG-F-2A-A DGA-TT-9612-1 & 2 Air Cooler Coolant Temp. Transmitters G29 DG-F-2A-A DGA-TE-9612-1 & 2 Air Cooler Coolant Temp. Elements G29 DG-F-2A-A DGA-ZC-9612 Air Cooler Coolant Temp. Dig. Vlv. Controller (I/P) G29 DG-F-2A-A DGA-ZY-9612 Air Cooler Coolant Temp. Vlv. Pos. Sensor G29 DG-F-2A-A DG-G29-TIC-RX Auxiliary Relay G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -31 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 62 DG-CP-907B Diesel Generator 1B Air Cooler Coolant & Jacket Coolant Temp. Control Panel DG-20466 B 310524 DG-F-2B-A X X X X G30 DG-EH0/17-52 120 v AC Circuit Breaker EH0 CB-F-1B-A EH0-G30 310857 EH0/17a EH0/17c CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B EDE-PP-1F DG-CP-907A Notes 10 & 11 DGB-TIC-9602 Jacket Coolant Temp. Indi. Controller G30 DG-F-2B-A DGB-TT-9602-1 & 2 Jacket Coolant Temp. Transmitters G30 DG-F-2B-A DGB-TE-9602-1 & 2 Jacket Coolant Temp. Elements G30 DG-F-2B-A DGB-ZC-9602 Jacket Coolant Temp . Dig. Vlv. Controller (I/P) G30 DG-F-2B-A DGB-TIC-9612 Air Cooler Coolant Temp. Indi. Controller G30 DG-F-2B-A DGB-TT-9612-1 & 2 Air Cooler Coolant Temp. Transmitters G30 DG-F-2B-A DGB-TE-9612-1 & 2 Air Cooler Coolant Temp. Elements G30 DG-F-2B-A DGB-ZC-9612 Air Cooler Coolant Temp. Dig. Vlv. Controller (I/P) G30 DG-F-2B-A DGB-ZY-9612 Air Cooler Coolant Temp. Vlv. Pos. Sensor G30 DG-F-2B-A DG-G30-TIC-RX Auxiliary Relay G30 DG-F-2B-A . NOTES 1. The equipment is mechanical with no electrical requirement.

2. Electrical conduit plan drawing, 310524, is listed only to show the fire zone corresponding to the location of this equipment in the Diesel Generator Building as identified in 202263.
3. Electrical conduit plan drawing, 310767, is listed only to show fire zone corresponding to the location of this equipment in the Primary Auxiliary Building as identified in 805217.
4. This equipment is located in the Diesel Generator Skid DG

-SKD-7A. 5. This equipment is located in the Diesel Generator Skid DG -SKD-17A. 6. This equipment is located in the Diesel Generator Skid DG -SKD-7B. 7. This equipment is located in the Diesel Generator Skid DG -SKD-17B. 8. The pneumatic control diagram of this equipment is shown in the DG air cooler water control loop diagram, 506403.

9. The pneumatic control diagram of this equipment is shown in the diesel engine jacket cooling water control loop diagram, 506404.
10. The pneumatic control diagram of this equipment is shown in the DG air cooler water control loop diagram, 506405.
11. The pneumatic control diagram of this equipment is shown in the DG diesel engine jacket cooling water loop diagram, 506406.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-1 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CO-TK-25 Condensate Storage Tank CO-20426 A/B 310248 CST-F-1-0 X X - - - - - - - - - -

- - Note 1 2 FW-P-37B Emergency Feed Pump FW-20688 B 310708 EFP-F-1-A X X X - N14 FW-A80-52 416 V AC Circuit Breaker A80 CB-F-1B-A A80-N14 None              FW-A80-FU Fuses A80 CB-F-1B-A CBA-FN-32 

CBA-FN-33 EPA-FN-47B EDE-SWG-6

FW-A80-R Auxiliary Relay A80 CB-F-1B-A FW-CS-4255-2 Control Switch A80 CB-F-1B-A 310844 A80a A80h A80b A80c A80d FW-SS-4255 Selector Switch A80 CB-F-1B-A EDE-A73-94-1B Bus Under Voltage Relay A73 CB-F-1B-A FW-A80-86 Lockout Relay A80 CB-F-1B-A FW-A80-52H Truck-Operated Contact A80 CB-F-1B-A FW-A80-50/51 Instrument/Time Overcurrent Relays

øA, øC A80 CB-F-1B-A FW-A80-AM Ammeter A80 CB-F-1B-A FW-A80-AS Ammeter Switch A80 CB-F-1B-A FW-A80-CT Current Transformers (200/5) A80 CB-F-1B-A FW-A80-TD1 CT Test Device A80 CB-F-1B-A FW-A80-ATR Transducer A80 CB-F-1B-A FW-A80-TD2 Lockout Relay Test Device A80 CB-F-1B-A FW-A80-G,R,W Indicating Lights A80 CB-F-1B-A FW-A80-52Z Time Delay Relay A80 CB-F-1B-A FW-A80-51GS Ground Sensor Relay A80 CB-F-1B-A 2A FW-V347 FW-20688 B 310708 EFP-F-1-A X X X - V4P FW-C3T-52 460 V AC Circuit Breaker C3T CB-F-1B-A None Emergency

Feedwater

Recirculating

Valve FW-C3T-FU Fuses C3T CB-F-1B-A C3T-V4P C3T-V4P/1

C3T-G2J 310844 C3Ta C3Tc EDE-MCC-615 CBA-FN-32

CBA-FN-33 EPA-FN-47B FW-CS-4369-2 Control Switch with Indication G2J CB-F-1B-A MS-SS-3064 Selector Switch G2J CB-F-1B-A FW-C3T-42/0,C Motor Starters C3T CB-F-1B-A FW-C3T-49 Overload Relays C3T CB-F-1B-A FW-ZS-V347 Valve Position Switch V4P EFP-F-1-A

.Notes  1. The equipment is mechanical with no electrical requirement. 
2. During normal operation, this equipment is in its safe shutdown position (locked closed). To prevent spurious operation, its circuit breaker is administratively controlled locked open (off).
3. Disabling the valve at the appropriate control location will reposition it for safe shutdown.
4. Air is not needed to position or to reposition the valve for safe shutdown.
5. The review of this valve was conducted with the assumption that it will be closed from the Control Room prior to evacuation and that a fire will not reset its logic before the operator could man the remote shutdown station and throw the "Remote-Local" switches to "Local". Its cables and supporting controls were listed to analyze the possibility of the valve reopening after the isolation switch has been positioned to "Local". 6. Circuit breaker tripped to disable the redundant controls.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-2 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 FW-FV-4214A FW-20688 A 310708 EFP-F-1-A X X X - V2E FW-B3V-52 460 V AC Circuit Breaker B3V CB-F-1A-A FW-FV-4214-B Emergency

Feedwater Header

Flow Valve FW-B3V-FU Fuse B3V CB-F-1A-A FW-CS-4214-A2 Control Switch with Indication G2G CB-F-1A-A B3V-V2E B3V-V2E/1

E3C-G2G G2G-V2E B3V-G5X B3V-G5X/1 310844 B3Va B3Vd B3Ve CBA-FN-19

CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-SS-4214-A Selector Switch G2G CB-F-1A-A FW-SS-4214-A1 Selector Switch G5X DG-F-2A-A FW-B3V-42/0,C Motor Starters B3V CB-F-1A-A FW-B3V-49 Overload Relays B3V CB-F-1A-A FW-ZS-4214-A Valve Position Switch V2E EFP-F-1-A 4 FW-FV-4214B FW-20688 B 310708 EFP-F-1-A X X X - V2J FW-B3Z-52 460 V AC Circuit Breaker B3Z CB-F-1B-A FW-FV-4214-A Emergency

Feedwater Header

Flow Valve FW-B3Z-FU Fuse B3Z CB-F-1B-A FW-CS-4214-B2 Control Switch with Indication G2J CB-F-1B-A B3Z-V2J B3Z-V2J/1 E3D-G2J G2J-V2J B3Z-G2J B3Z-G5Y B3Z-G5Y/1 310844 B3Za B3Zd B3Ze CBA-FN-32

CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-SS-4214-B Selector Switch G2J CB-F-1B-A FW-SS-4214-B1 Selector Switch G5Y DG-F-2B-A FW-B3Z-42/0,C Motor Starters B3Z CB-F-1B-A FW-B3Z-49 Overload Relays B3Z CB-F-1B-A FW-ZS-4214-B Valve Position Switch V2J EFP-F-1-A 5 FW-FV-4224A FW-20688 A 310708 EFP-F-1-A X X X - V2F FW-B3W-52 460 V AC Circuit Breaker B3W CB-F-1A-A FW-FV-4224-B Emergency

Feedwater Header

Flow Valve FW-B3W-FU Fuse B3W CB-F-1A-A FW-CS-4244-A2 Control Switch with Indication G2G CB-F-1A-A B3W-V2F B3W-V2F/1 E3C-G2G/1 G2G-V2F B3W-G5X B3W-G5X/1 310844 B3WA B3WD B3WE CBA-FN-19

CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-SS-4224-A Selector Switch G2G CB-F-1A-A FW-SS-4224-A1 Selector Switch G5X DG-F-2A-A FW-B3W-42/0,C Motor Starters B3W CB-F-1A-A FW-B3W-49 Overload Relays B3W CB-F-1A-A FW-ZS-4224-A Valve Position Switch V2F EFP-F-1-A 6 FW-FV-4224B FW-20688 B 310708 EFP-F-1-A X X X - V2K FW-B4A-52 460 V AC Circuit Breaker B4A CB-F-1B-A FW-FV-4224-A Emergency

Feedwater Header

Flow Valve FW-B3W-FU Fuse B4A CB-F-1B-A FW-CS-4224-B2 Control Switch with Indication G2J CB-F-1B-A B4A-V2K B4A-V2K/1 E3D-G2J/1 G2J-V2K B4A-G2J B4A-G5Y B4A-G5Y/1 310844 B4Aa B4Ad B4Ae CBA-FN-32

CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-SS-4224-B Selector Switch G2J CB-F-1B-A FW-SS-4224-B1 Selector Switch G5Y DG-F-2B-A FW-B4A-42/0,C Motor Starters B4A CB-F-1B-A FW-B4A-49 Overload Relays B4A CB-F-1B-A FW-ZS-4224-B Valve Position Switch V2K EFP-F-1-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-3 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 FW-FV-4234A FW-20688 A 310708 EFP-F-1-A X X X - V2G FW-B3X-52 460 V AC Circuit Breaker B3X CB-F-1A-A FW-FV-4234-B Emergency

Feedwater Header

Flow Valve FW-B3X-FU Fuse B3X CB-F-1A-A 310844 B3Xa B3Xd B3Xe FW-CS-4234-A2 Control Switch with Indication G2G CB-F-1A-A B3X-V2G B3X-V2G/1 G2G-V2G E3C-G2G/2 B3X-G5X B3X-G5X/1 CBA-FN-19

CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-SS-4214-A Selector Switch G2G CB-F-1A-A FW-SS-4214-A1 Selector Switch G5X DG-F-2A-A FW-B3X-42/0,C Motor Starters B3X CB-F-1A-A FW-B3X-49 Overload Relays B3X CB-F-1A-A FW-ZS-4234-A Valve Position Switch V2G EFP-F-1-A 8 FW-FV-4234B FW-20688 B 310708 EPF-F-1-A X X X - V2L FW-B4B-52 460 V AC Circuit Breaker B4B CB-F-1B-A FW-FV-4234-A Emergency

Feedwater Header

Flow Valve FW-B4B-FU Fuse B4B CB-F-1B-A FW-CS-4234-B2 Control Switch with Indication G2J CB-F-1B-A 310844 B4Ba B4Bd B4Be CBA-FN-32 CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-SS-4214-B Selector Switch G2J CB-F-1B-A B4B-V2L B4B-V2L/1 E3D-G2J/2 G2J-V2L B4B-G2J B4B-G5Y B4B-G5Y/1 FW-SS-4214-B1 Selector Switch G5Y DG-F-2B-A FW-B4B-42/0,C Motor Starters B4B CB-F-1B-A FW-B4B-49 Overload Relays B4B CB-F-1B-A FW-ZS-4234-B Valve Position Switch V2L EFP-F-1-A 9 FW-FV-4244A FW-20688 A 310708 EFP-F-1-A X X X - V2H FW-B3Y-52 460 V AC Circuit Breaker B3Y CB-F-1A-A FW-FV-4244-B Emergency

Feedwater Header

Flow Valve FW-B3Y-FU Fuse B3Y CB-F-1A-A FW-CS-4244-A2 Control Switch with Indication G2G CB-F-1A-A B3Y-V2H B3Y-V2H/1 E3C-G2G/3 G2G-V2H B3Y-G5X B3Y-G5X/1 310844 B3Ya B3Yd B3Ye CBA-FN-19

CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-SS-4224-A Selector Switch G2G CB-F-1A-A FW-SS-4224-A1 Selector Switch G5X DG-F-2A-A FW-B3Y-42/0,C Motor Starters B3Y CB-F-1A-A FW-B3Y-49 Overload Relays B3Y CB-F-1A-A FW-ZS-4244-A Valve Position Switch V2H EFP-F-1-A 10 FW-FV-4244B FW-20688 B 310708 EFP-F-1-A X X X - V2M FW-B4C-52 460 V AC Circuit Breaker B4C CB-F-1B-A FW-FV-4244-A Emergency

Feedwater Header

Flow Valve FW-B4C-FU Fuse B4C CB-F-1B-A FW-CS-4244-B2 Control Switch with Indication G2J CB-F-1B-A 310844 B4Ca B4Cd B4Ce CBA-FN-32

CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-SS-4224-B Selector Switch G2J CB-F-1B-A B4C-V2M B4C-V2M/1 E3D-G2J/3 GJ2-V2M B4C-G2J B4C-G5Y B4C-G5Y/1 FW-SS-4224-B1 Selector Switch G5Y DG-F-2B-A FW-B4C-42/0,C Motor Starters B4C CB-F-1B-A FW-B4C-49 Overload Relays B4C CB-F-1B-A FW-ZS-4244-B Valve Position Switch V2M EFP-F-1-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-4 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 MS-PV-3001 MS-20580 A/B 310589 MS-F-2B-Z X X X X V2N MS-HIC-3001 Auto/Manual Controller with

Indicator G2G CB-F-1A-A MS-PV-3002 or MS-PV-3004 Main Steam Header

Atmospheric

Relief Valve MS-HQY-3001 Mixing Amplifier G2H CB-F-1A-A MS-HY-3001 Signal Converter G2H CB-F-1A-A 310841 310953 G2Ga FJ71 310841 E2T/8a E2T/8e E2T/8f MS-SS-3001-1 Selector Switch G2G CB-F-1A-A G2G-GL6 G2G-V2N E2T-G5X G2G-G5X FN8-U0A FN8-U0B FN8-G2G/1 MS-CS-3001-2 Control Switch with Indication G2G CB-F-1A-A CBA-FN-19

CBA-FN-20 MM-UQ-5868

MM-UQ-5869 Instrument Air EDE-PP-113A CBA-FN-19

CBA-FN-20 Instrument Air MS-PY-3001 I/P Converter GL6 MS-F-1B-Z MS-E2T/8-72 125 V DC Circuit Breaker E2T CB-F-1A-A MS-CS-3001-2 Control Switch with Indication G2G CB-F-1A-A MS-SS-3001-1 Selector Switch G2G CB-F-1A-A MS-ZS-3001-A Valve Position Switch V2N MS-F-2B-Z MS-PY-3001-1 Solenoid Valve UOA MS-F-2B-Z MS-SS-3001-3 Selector Switch FN8 ET-F-1B-A MS-PY-3001-2 Solenoid Valve UOA MS-F-2B-Z MS-PY-3001-3 Solenoid Valve UOB MS-F-2B-Z MS-PY-3001-4 Solenoid Valve UOB MS-F-2B-Z MS-SS-3001-2 Selector Switch G5X DG-F-2A-A UOC MS-PY-3001-5 + 6 Solenoid Valve E2U CB-F-1B-A - - - - Note 6 12 MS-PV-3003 Main Steam Header Atmospheric

Relief Valve MS-20580 A/B 310586 MS-F-2A-Z X X X X V2Q MS-HIC-3003 Auto/Manual Controller with

Indicator G2G CB-F-1A-A MS-PV-3002 or MS-PV-3004 MS-HQY-3003 Mixing Amplifier G2H CB-F-1A-A MS-HY-3003 Signal Converter G2H CB-F-1A-A G2G-GL5 G2G-V2Q E2T-G5X/1 G2G-G5X/1 FN8-U0K FN8-U0L FN8-G2G/2 310841 310953 G2Ga FJ71 310841 E2T/10a E2T/10e E2T/10f MS-SS-3003-1 Selector Switch G2G CB-F-1A-A MS-CS-3003-2 Control Switch with Indication G2G CB-F-1A-A CBA-FN-19

CBA-FN-20 MM-UQ-5868

MM-UQ-5869 Instrument Air EDE-PP-113A CBA-FN-19

CBA-FN-20 Instrument Air MS-PY-3003 I/P Converter GL5 MS-F-3A-Z MS-E2T/10-72 125 V DC Circuit Breaker E2T CB-F-1A-A MS-CS-3003-2 Control Switch with Indication G2G CB-F-1A-A MS-SS-3003-1 Selector Switch G2G CB-F-1A-A MS-ZS-3003-A Valve Position Switch V2Q MS-F-2A-Z MS-SS-3003-3 Selector Switch FN8 ET-F-1B-A MS-PY-3003-1 Solenoid Valve UOK MS-F-2A-Z MS-PY-3003-2 Solenoid Valve UOK MS-F-2A-Z MS-PY-3003-3 Solenoid Valve UOL MS-F-2A-Z MS-PY-3003-4 Solenoid Valve UOL MS-F-2A-Z MS-SS-3003-2 Selector Switch G5X DG-F-2A-A UOM MS-PY-3003-5 + 6 Solenoid Valve E2U CB-F-1B-A - - - - Note 6 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-5 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 MS-PV-3002 MS-20580 A/B 310586 MS-F-2A-Z X X X X V2P MS-HIC-3002 Auto/Manual Controller with

Indicator G2J CB-F-1B-A MS-PV-3001 or MS-PV-3003 Main Steam Header

Atmospheric

Relief Valve MS-HQY-3002 Mixing Amplifier GZO CB-F-1B-A MS-HY-3002 Signal Converter GZ0 CB-F-1B-A G2J-GZ4 G2J-V2P E2U-G5Y G2J-G5Y FN9-U0G FN9-U0H FN9-G2J/1 310841 G2Ja FJ4d E2U/8a E2U/8e E2U/8f MS-SS-3002-1 Selector Switch G2J CB-F-1B-A CBA-FN-32 CBA-FN-33 MM-UQ-5866

MM-UQ-5867 Instrument Air EDE-PP-113B CBA-FN-32

CBA-FN-33 Instrument Air MS-CS-3002-2 Control Switch with Indication G2J CB-F-1B-A MS-PY-3002 I/P Converter GZ4 MS-F-3A-Z MS-E2U/8-72 125 V DC Circuit Breaker E2U CB-F-1B-A MS-CS-3002-2 Control Switch with Indication G2J CB-F-1B-A MS-SS-3002-3 Selector Switch FN9 ET-F-1D-A MS-SS-3002-1 Selector Switch G2J CB-F-1B-A MS-ZS-3002-B Valve Position Switch V2P MS-F-2A-Z MS-PY-3002-1 Solenoid Valve UOG MS-F-2A-Z MS-PY-3002-2 Solenoid Valve UOG MS-F-2A-Z MS-PY-3002-3 Solenoid Valve UOH MS-F-2A-Z MS-PY-3002-4 Solenoid Valve UOH MS-F-2A-Z MS-SS-3002-2 Selector Switch G5Y DG-F-2B-A UOJ MS-PY-3002-5 + 6 Solenoid Valve E2T CB-F-1A-A - - - - Note 6 14 MS-PV-3004 Main Steam Header Atmospheric

Relief Valve MS-20580 A/B 310589 MS-F-2B-Z X X X X V2R MS-HIC-3004 Auto/Manual Controller with

Indicator G2J CB-F-1B-A MS-PV-3001 or MS-PV-3003 MS-HQY-3004 Mixing Amplifier GZO CB-F-1B-A MS-HY-3004 Signal Converter GZ0 CB-F-1B-A MS-SS-3004 Selector Switch G2J CB-F-1B-A G2J-GZ6 G2J-V2R E2U-G5Y/1 G2J-G5Y/1 FN9-U0D FN9-U0E FN9-G2J/2 310841 G2Ja FJ4d E2U/10a E2U/10e E2U/10f CBA-FN-32 CBA-FN-33 MM-UQ-5866

MM-UQ-5867 Instrument Air EDE-PP-113B CBA-FN-32

CBA-FN-33 Instrument Air MS-CS-3004-2 Control Switch with Indication G2J CB-F-1B-A MS-PY-3004 I/P Converter GZ6 MS-F-1B-Z MS-E2U/10-72 125 V DC Circuit Breaker E2U CB-F-1B-A MS-SS-3004-3 Selector Switch FN9 ET-F-1D-A MS-CS-3004-2 Control Switch with Indication G2J CB-F-1B-A MS-SS-3004-1 Selector Switch G2J CB-F-1B-A MS-ZS-3004-B Valve Position Switch V2R MS-F-2B-Z MS-PY-3004-1 Solenoid Valve UOD MS-F-2B-Z MS-PY-3004-2 Solenoid Valve UOD MS-F-2B-Z MS-PY-3004-3 Solenoid Valve UOE MS-F-2B-Z MS-PY-3004-4 Solenoid Valve UOE MS-F-2B-Z MS-SS-3004-2 Selector Switch G5Y DG-F-2B-A UOF MS-PY-3004-5 + 6 Solenoid Valve E2T CB-F-1A-A - - - - Note 6 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-6 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 MS-V-86 Main Steam Isolation Valve MS-20583 A/B 310589 MS-F-2B-Z X X X X MS-E87/14-72 125 V DC Circuit Breaker E87 CB-F-1A-A None Notes 4 and 5 ZVO ZV1 ZV2 ZW1 MS-FY-89A-1 Pilot Solenoid ZV1 MS-F-2B-Z MS-FY-10A-1 Pilot Solenoid ZV1 MS-F-2B-Z MS-FY-102A-1 Solenoid Valve ZV1 MS-F-2B-Z MS-FY-102B-1 Solenoid Valve ZV1 MS-F-2B-Z 310841 E87/14a E87/14b MS-GX6-K103 Output Relay GX6 MS-F-3A-Z E87-GX6 GX6-ZV1 CBA-FN-19

CBA-FN-20 EDE-PP-112A MS-GX6-K104 Output Relay GX6 MS-F-3A-Z MS-GX6-CS-3005-A Control Switch GX6 MS-F-3A-Z MS-E1S/7-52 120 V AC Circuit Breaker E1S CB-F-1A-A MS-GX6-FU-101&102 120 V AC Fuses GX6 MS-F-3A-Z CBA-FN-19

CBA-FN-20 EDE-PP-11E MS-GX6-K101 Output Relay GX6 MS-F-3A-Z E1S-GX6/1 G2G-GX6/4 G2G-GX6/5 GX6-ZV0 G2G-GX6/3 E1S/7a E1S/7h E1S/7b E1S/7i E1S/7c E1S/7j E1S/7d E1S/7k MS-GX6-K102 Output Relay GX6 MS-F-3A-Z MS-ZS-V86A-1 Valve Position Switch ZV0 MS-F-2B-Z MS-ZS-V86A-2 Valve Position Switch ZV0 MS-F-2B-Z MS-ZL-3005-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-184 MSIV Logic Cabinet (Train A) GX6 MS-F-3A-Z MS-E88/14-72 125 V DC Circuit Breaker E88 CB-F-1B-A E88-GX9 GX9-ZV2 E88/14a E88/14b MS-FY-89B-1 Pilot Solenoid ZV2 MS-F-2B-Z CBA-FN-32

CBA-FN-33 EDE-PP-112B MS-FY-10B-1 Pilot Solenoid ZV2 MS-F-2B-Z MS-FY-117A-1 Solenoid Valve ZV2 MS-F-2B-Z MS-FY-117B-1 Solenoid Valve ZV2 MS-F-2B-Z MS-GX9-K103 Output Relay GX9 CB-F-1B-A MS-GX9-K104 Output Relay GX9 CB-F-1B-A MS-GX9-CS-3005-B Control Switch GX9 CB-F-1B-A MS-E1T/7-52 120 V AC Circuit Breaker E1T CB-F-1B-A MS-GX9-FU-101&102 120 V AC Fuses GX9 CB-F-1B-A E1T/7a E1T/7f E1T/7b E1T/7c CBA-FN-32

CBA-FN-33 EDE-PP-11F MS-GX9-K101 Output Relay GX9 CB-F-1B-A E1T-GX9/3 G2J-GX9/1 G2J-GX9 GX9-Z1C MS-GX9-K102 Output Relay GX9 CB-F-1B-A MS-ZS-V86B-1 Valve Position Switch ZW1 MS-F-2B-Z MS-ZS-V86B-2 Valve Position Switch ZW1 MS-F-2B-Z MS-ZL-3005-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-CP-185 MSIV Logic Cabinet (Train B) GX9 CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-7 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 16 MS-V-88 Main Steam Isolation Valve MS-20583 A/B 310586 MS-F-2A-Z X X X X MS-E2T/12-72 125 V DC Circuit Breaker E2T CB-F-1A-A None Notes 4 and 5 MS-FY-89A-2 Pilot Solenoid ZW3 MS-F-2A-Z ZW3 ZW4 ZW5 ZW6 MS-FY-10A-2 Pilot Solenoid ZW3 MS-F-2A-Z MS-FY-102A-2 Solenoid Valve ZW3 MS-F-2A-Z MS-FY-102B-2 Solenoid Valve ZW3 MS-F-2A-Z MS-GX7-K103 Output Relay GX7 MS-F-3A-Z MS-GX7-K104 Output Relay GX7 MS-F-3A-Z MS-GX7-CS-3006-A Control Switch GX7 MS-F-3A-Z E2T-GX7 GX7-ZW3 310841 E2T/12a E3T/12c CBA-FN-19

CBA-FN-20 EDE-PP-113A MS-E1S/9-52 120 V AC Circuit Breaker E1S CB-F-1A-A MS-GX7-FU-101&102 120 V AC Fuses GX7 MS-F-3A-Z CBA-FN-19

CBA-FN-20 EDE-PP-11E MS-GX7-K101 Output Relay GX7 MS-F-3A-Z E1S-GX7/1 G2G-GX7/4 G2G-GX7/5 GX7-ZW5 G2G-GX7/3 E1S/9a E1S/9h E1S/9b E1S/9i E1S/9c E1S/9j E1S/9D E1S/9k MS-GX7-K102 Output Relay GX7 MS-F-3A-Z MS-ZS-V88A-1 Valve Position Switch ZW5 MS-F-2A-Z MS-ZS-V88A-2 Valve Position Switch ZW5 MS-F-2A-Z MS-ZL-3006-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-182 MSIV Logic Cabinet (Train A) GX7 MS-F-3A-Z MS-E2U/12-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-GX8 GX8-ZW4 E2U/12a E2U/12c MS-GX8-K103 Output Relay GX8 CB-F-1B-A CBA-FN-32

CBA-FN-33 EDE-PP-113B MS-GX8-K104 Output Relay GX8 CB-F-1B-A MS-FY-89B-2 Pilot Solenoid ZW4 MS-F-2A-Z MS-FY-10B-2 Pilot Solenoid ZW4 MS-F-2A-Z MS-FY-117A-2 Solenoid Valve ZW4 MS-F-2A-Z MS-FY-117B-2 Solenoid Valve ZW4 MS-F-2A-Z MS-GX8-CS-3006B Control Switch GX8 CB-F-1B-A MS-E1T/9-52 120 V AC Circuit Breaker E1T CB-F-1B-A MS-GX8-FU-101&102 120 V AC Fuses GX8 CB-F-1B-A CBA-FN-32

CBA-FN-33 EDE-PP-11F MS-GX8-K101 Output Relay GX8 CB-F-1B-A E1T-GX8/3 G2J-GX8 GX8-ZW6 G2J-GX8/1 E1T/9a E1T/9f E1T/9b E1T/9g E1T/9c E1T/9h E1T/9i MS-GX8-K102 Output Relay GX8 CB-F-1B-A MS-ZS-V88B-1 Valve Position Switch ZW6 MS-F-2A-Z MS-ZS-V88B-2 Valve Position Switch ZW6 MS-F-2A-Z MS-ZL-3006-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A MS-CP-183 MSIV Logic Cabinet (Train B) GX8 CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-8 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 17 MS-V-90 Main Steam Isolation Valve MS-20583 A/B 310586 MS-F-2A-Z X X X X MS-E2T/14-72 125 V DC Circuit Breaker E2T CB-F-1A-A None Notes 4 and 5 MS-FY-89A-3 Pilot Solenoid ZW8 MS-F-2A-Z ZX1 ZWO ZW8 ZW9 MS-FY-10A-3 Pilot Solenoid ZW8 MS-F-2A-Z MS-FY-102A-3 Solenoid Valve ZW8 MS-F-2A-Z MS-FY-102B-3 Solenoid Valve ZW8 MS-F-2A-Z MS-GX7-K111 Output Relay GX7 MS-F-3A-Z MS-GX7-K112 Output Relay GX7 MS-F-3A-Z MS-GX7-3007-A Control Switch Gx7 MS-F-3A-Z E2T-GX7/1 GX7-ZW8 310841 E2T/14a E2T/14c CBA-FN-19

CBA-FN-20 EDE-PP-113A MS-E1S/9-52 120 V AC Circuit Breaker E1S CB-F-1A-A MS-GX7-FU-103&104 120 V AC Fuses GX7 MS-F-3A-Z CBA-FN-19

CBA-FN-20 EDE-PP-11E MS-GX7-K109 Output Relay GX7 MS-F-3A-Z E1S-GX7/1 G2G-GX7/3 G2G-GX7/4 G2G-GX7/5 GX7-ZWO E1S/9a E1S/9h E1S/9b E1S/9i E1S/9c E1S/9j E1S/9d E1S/9k MS-GX7-K110 Output Relay GX7 MS-F-3A-Z MS-ZS-V90A-1 Valve Position Switch ZWO MS-F-2A-Z MS-ZS-V90A-2 Valve Position Switch ZWO MS-F-2A-Z MS-ZL-3007-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-182 MSIV Logic Cabinet (Train A) GX7 MS-F-3A-Z MS-E2U/14-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-GX8/1 GX8-ZW9 E2U/14aE2U/14c MS-GX8-K111 Output Relay GX8 CB-F-1B-A CBA-FN-32

CBA-FN-33 EDE-PP-113B MS-GX8-K112 Output Relay GX8 CB-F-1B-A MS-FY-89B-3 Pilot Solenoid ZW9 MS-F-2A-Z MS-FY-10B-3 Pilot Solenoid ZW9 MS-F-2A-Z MS-FY-117A-3 Solenoid Valve ZW9 MS-F-2A-Z MS-FY-117B-3 Solenoid Valve ZW9 MS-F-2A-Z MS-GX8-CS-3007-B Control Switch GX8 CB-F-1B-A MS-E1T/9-52 120 V AC Circuit Breaker E1T CB-F-1B-A MS-GX8-FU-103&104 120 V AC Fuses GX8 CB-F-1B-A CBA-FN-32

CBA-FN-33 EDE-PP-11F MS-GX8-K109 Output Relay GX8 CB-F-1B-A E1T-GX8/3 G2J-GX8 G2J-GX8/1 GX8-ZX1 E1T/9a E1T/9f E1T/9b E1T/9g E1T/9c E1T/9h E1T/9i MS-GX8-K110 Output Relay GX8 CB-F-1B-A MS-ZS-V90B-1 Valve Position Switch ZX1 MS-F-2A-Z MS-ZS-V90B-2 Valve Position Switch ZX1 MS-F-2A-Z MS-ZL-3007-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-CP-183 MSIV Logic Cabinet (Train B) GX8 CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-9 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 MS-V-92 Main Steam Isolation Valve MS-20583 A/B 310589 MS-F-2B-Z X X X X MS-E87/18-52 125 V DC Circuit Breaker E87 CB-F-1A-A None Notes 4 and 5 MS-GX6-K111 Output Relay GX6 MS-F-3A-Z ZX3 Z1A Z1B Z1C MS-GX6-K112 Output Relay GX6 MS-F-3A-Z MS-FY-89A-4 Pilot Solenoid ZX3 MS-F-2B-Z MS-FY-10A-4 Pilot Solenoid ZX3 MS-F-2B-Z MS-FY-102A-4 Solenoid Valve ZX3 MS-F-2B-Z MS-FY-102B-4 Solenoid Valve ZX3 MS-F-2B-Z MS-GX6-CS-3008-A Control Switch GX-6 MS-F-3A-Z E87-GX6/1 GX6-ZX3 310841 E87/18a E87/18b CBA-FN-19

CBA-FN-20 EDE-PP-112A MS-E1S/7-52 120 V AC Circuit Breaker E1S CB-F-1A-A MS-GX6-FU-103&104 120 V AC Fuses GX6 MS-F-3A-Z CBA-FN-19

CBA-FN-20 EDE-PP-11E MS-GX6-K109 Output Relay GX6 MS-F-3A-Z E1S-GX6/1 G2G-GX6/3 G2G-GX6/4 G2G-GX6/5 GX6-Z1B E1S/7a E1S/7h E1S/7b E1S/7i E1S/7c E1S/7j E1S/7d E1S/7k MS-GX6-K110 Output Relay GX6 MS-F-3A-Z MS-ZS-V92A-1 Valve Position Switch Z1B MS-F-2B-Z MS-ZS-V92A-2 Valve Position Switch Z1B MS-F-2B-Z MS-ZL-3008-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-184 MSIV Logic Cabinet (Train A) GX6 MS-F-3A-Z MS-E88/9-72 125 V DC Circuit Breaker E88 CB-F-1B-A E88-GX9/1 GX9-Z1A E88/9aE88/9b MS-GX9-K111 Output Relay GX9 CB-F-1B-A CBA-FN-32

CBA-FN-33 EDE-PP-112B MS-GX9-K112 Output Relay GX9 CB-F-1B-A MS-FY-89B-4 Pilot Solenoid Z1A MS-F-2B-Z MS-FY-10B-4 Pilot Solenoid Z1A MS-F-2B-Z MS-FY-117A-4 Solenoid Valve Z1A MS-F-2B-Z MS-FY-117B-4 Solenoid Valve Z1A MS-F-2B-Z MS-GX9-CS-3008-B Control Switch GX9 CB-F-1B-A MS-E1T/7-52 125 V AC Circuit Breaker E1T CB-F-1B-A MS-GX9-FU-103&104 120 V AC Fuses GX9 CB-F-1B-A CBA-FN-32

CBA-FN-33 EDE-PP-11F MS-GX9-K109 Output Relay GX9 CB-F-1B-A E1T-GX9/3 GX9-Z1C G2J-GX9 G2J-GX9/1 E1T/7a E1T/7f E1T/7b E1T/7g E1T/7c E1T/7h E1T/7i MS-GX9-K110 Output Relay GX9 CB-F-1B-A MS-ZS-V92B-1 Valve Position Switch Z1C MS-F-2B-Z MS-ZS-V92B-2 Valve Position Switch Z1C MS-F-2B-Z MS-ZL-3008-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A MS-CP-185 MSIV Logic Cabinet (Train B) GX9 CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-10 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 MS-V-204 Main Steam Isolation Valve

Bypass Valve MS-20583 A 310589 MS-F-2B-Z X X X - VU6 MS-B1X-52 460 V AC Circuit Breaker B1X CB-F-1A-A - - - - None Note 2 20 MS-V-205 Main Steam Isolation Valve

Bypass Valve MS-20583 A 310589 MS-F-2A-Z X X X - VU7 MS-B1Y-52 460 V AC Circuit Breaker B1Y CB-F-1A-A - - - - None Note 2 21 MS-V-206 Main Steam Isolation Valve

Bypass Valve MS-20583 A 310589 MS-F-2A-Z X X X - VU8 MS-B1Z-52 460 V AC Circuit Breaker B1Z CB-F-1A-A - - - - None Note 2 22 MS-V-207 Main Steam Isolation Valve

Bypass Valve MS-20583 A 310589 MS-F-2B-Z X X X - VU9 MS-B2A-52 460 V AC Circuit Breaker B2A CB-F-1A-A - - - - None Note 2 23 RC-E-11A Steam Generator RC-20841 A 310576 310582 310578 C-F-1-Z C-F-1-Z C-F-2-Z X X - - - - - - - - - -

- RC-E-11B or RC-E-11D Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-11 FUNCTION:  DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER  SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO.

TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 24 RC-E-11B Steam Generator RC-20842 B 310576 310582 310578 C-F-1-Z C-F-1-Z C-F-2-Z X X - - - - - - - - - -

- RC-E-11A or RC-E-11C Note 1 25 RC-E-11C Steam Generator RC-20843 A 310577 310583 310579 C-F-1-Z C-F-1-Z C-F-2-Z X X - - - - - - - - - -
- RC-E-11B or RC-E-11D Note 1 26 RC-E-11D Steam Generator RC-20844 B 310577 310583 310579 C-F-1-Z C-F-1-Z C-F-2-Z X X - - - - - - - - - -
- RC-E-11A or RC-E-11C Note 1 27 SB-V9 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM4 SB-E88/18-72 125 V DC Circuit Breaker E88 CB-F-1B-A - - -
- SB-V-1 Notes 3 and 4 28 SB-V10 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM5 SB-E88/18-72 125 V DC Circuit Breaker E88 CB-F-1B-A - - -
- SB-V-3 Notes 3 and 4 29 SB-V11 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM6 SB-E88/18-72 125 V DC Circuit Breaker E88 CB-F-1B-A - - -
- SB-V-5 Notes 3 and 4 30 SB-V12 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM7 SB-E88/18-72 125 V DC Circuit Breaker E88 CB-F-1B-A - - -
- SB-V-7 Notes 3 and 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2

-1 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 RC-E-10 Reactor Coolant System Pressurizer RC-20846 A/B 310598 C-F-1-Z X X - - - - - - - - - - None Note 1 2 RC-E-10 Pressurizer Heaters Group A RC-20846 A 310598 C-F-1-Z X X X - M26 RC-AB4-52 480 V AC Circuit Breaker AB4 CB-F-1A-A AB4-E07 AB4-E07/1 AB4-G81 AB4-G81/1 E07-H14 E07-H14/1 E07-H14/2 E07-H14/3 E07-H14/4 H14-X47 H14-X47/1 H14-X47/2 H14-X47/3 H14-X47/4 M26-X47 M26-X47/1 M26-X47/2 M26-X47/3 M26-X47/4 M26-X47/5 M26-X47/6 M26-X47/7 M26-X47/8 M26-X47/9 M26-X47/A M26-X47/B M26-X47/C M26-X47/D M26-X47/E 310882 AB4a AB4g AB4b AB4c CBA-FN-19 CBA-FN-20 EDE-US-52 Pressurizer Heaters Group B RC-AB4-FU Fuses AB4 CB-F-1A-A RC-CS-7318-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-7318 Selector Switch G81 CB-F-1A-A EDE-AC3-94-3 Bus Undervoltage Relay AC3 CB-F-1A-A RC-AB4-52H-1 Truck Operated Contact AB4 CB-F-1A-A EDE-TBX-X47 Terminal Box X47 C-F-1-Z RC-AB4-G,R Indicating Lights AB4 CB-F-1A-A RC-AB4-CT1 Current Transformer (600/5) øB Bus Side AB4 CB-F-1A-A RC-AB4-AM Ammeter AB4 CB-F-1A-A RC-AB4-CT2 Current Transformer (600/5) øA, øC Load Side AB4 CB-F-1A-A RC-AC3-WTR Watt Transducer AC3 CB-F-1A-A RC-PP-6A Distribution Panel E07 ET-F-1A-A EDE-MM-90 Electrical Penetration H14 ET-F-1A-A, C-F-2-Z

.Notes   1. The equipment is mechanical with no electrical requirement.
2. During normal operation, the valve is in its safe shutdown position. To prevent spurious operations, this equipment will be disabled at the appropriate control location.
3. Disabling the valve at the appropriate control location will reposition it for safe shutdown.
4. Air is not needed to position or to reposition the valve for safe shutdown.
5. These valves are closed with their circuit breakers locked open during 100% power operation. This will prevent spurious operation. For cold shutdown, these valves are energized for repositioning.
6. Not Used.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -2 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 RC-E-10 Pressurizer Heaters Group B RC-20846 B 310598 C-F-1-Z X X X - M26 RC-AD4-52 480 V AC Circuit Breaker AD4 CB-F-1B-A AD4-E08 AD4-E08/1 AD4-GZ0 AD4-GZ0/1 AE3-GZ0 E08-H20 E08-H20/1 E08-H20/2 E08-H20/3 E08-H20/4 H20-X44 H20-X44/1 H20-X44/2 H20-X44/3 H20-X44/4 M26-X44 M26-X44/1 M26-X44/2 M26-X44/3 M26-X44/4 M26-X44/5 M26-X44/6 M26-X44/7 M26-X44/8 M26-X44/9 M26-X44/A M26-X44/B M26-X44/C M26-X44/D M26-X44/E 310882 AD4a AD4f AD4b AD4c CBA-FN-32 CBA-FN-33 EDE-US-62 Pressurizer Heaters Group A RC-AD4-FU Fuses AD4 CB-F-1B-A RC-CS-7319-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-7319 Selector Switch GZ0 CB-F-1B-A EDE-AE3-94-3 Bus Undervoltage Relay AE3 CB-F-1B-A RC-AD4-52H-1 Truck Operated Contact AD4 CB-F-1B-A RC-AD4-G,R Indicating Lights AD4 CB-F-1B-A EDE-TBX-X44 Terminal Box X44 C-F-1-Z RC-AD4-CT1 Current Transformer (600/5) øB Bus Side AD4 CB-F-1B-A RC-AD4-AM Ammeter AD4 CB-F-1B-A RC-AD4-CT2 Current Transformer (600/5) øA, øC Load Side AD4 CB-F-1B-A RC-AE3-WTR Watt Transducer AE3 CB-F-1B-A RC-PP-6B Distribution Panel E08 ET-F-1C-A EDE-MM-96 Electrical Penetration H20 ET-F-1C-A, C-F-1-Z RC-AE3-R1 Auxiliary Relay AE3 CB-F-1B-A 4 RC-V-122 RC-E-10 Pressurizer Relief Isolation Valve RC-20846 A 310581 C-F-3-Z X X X - V01 RC-B97-52-1,2 460 V AC Circuit Breakers B97 CB-F-1A-A B97-G81 B97-G81/1 B97-H18 B97-H35 H18-V01 H35-X56 V01-X56 310882 B97a B97c B97e CBA-FN-19 CBA-FN-20 EDE-MCC-521 RC-V-124 RC-PCV-456A RC-B97-FU Fuse B97 CB-F-1A-A RC-CS-7313-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-7313 Selector Switch G81 CB-F-1A-A RC-B97-42-1/0,C Motor Starters B97 CB-F-1A-A RC-B97-42-2 Motor Starter B97 CB-F-1A-A RC-B97-49-1,2 Overload Relays B97 CB-F-1A-A EDE-TBX-X56 Terminal Box X56 C-F-3-Z RC-ZS-V122 Valve Position Switch and Valve Open/Close Torque Switches V01 C-F-3-Z EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A

Notes 7. These valves are also listed in Table RSS 3.1.3.6.

8. This group of pressurizer heaters will be disabled at the appropriate control location to prevent spurious operation.
9. Electrical conduit plan drawing, 9763

-F-310764, is listed only to show the fire zone corresponding to the area where the charging pump oil coolers are located (9763 -F-805213 and -F815214).

10. Reactor Coolant Pumps will be tripped prior to main control room evacuation or they can be tripped in Non

-Essential Switchgear Room, if required.

11. This equipment will be disabled by tripping and racking

-out its circuit breaker at the switchgear.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -3 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 RC-V-124 RC-E-10 Pressurizer Relief Isolation Valve RC-20846 B 310581 C-F-3-Z X X X - V02 RC-B98-52-1,2 460 V AC Circuit Breakers B98 CB-F-1B-A B98-GZ0 B98-GZ0/1 B98-GZ0/2 B98-H15 B98-H41 H15-V02 H41-X35 V02-X35 310882 B98a B98c B98e CBA-FN-32 CBA-FN-33 EDE-MCC-621 RC-V-122 RC-PCV-456B RC-B98-FU Fuse B98 CB-F-1B-A FC-CS-7314-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-7314 Selector Switch GZ0 CB-F-1B-A RC-B98-42-1/0,C Motor Starters B98 CB-F-1B-A RC-B98-42-2 Motor Starter B98 CB-F-1B-A RC-B98-49-1,2 Overload Relays B98 CB-F-1B-A EDE-TBX-X35 Terminal Box X35 C-F-3-Z RC-ZS-V124 Valve Position Switch and Valve Open/Close Torque Switches V02 C-F-3-Z EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A 6 RC-PCV-456A RC-E-10 Pressurizer Relief Control Valve RC-20846 A 310581 C-F-3-Z X X X LD3 RC-E87/19-72 125 V DC Circuit Breaker E87 CB-F-1A-A E87-E4A/4 E4A-J3M G81-J3M G81-H35 G5X-J3M H18-J3M H18-LD3 H35-X56/2 LD3-X56 310882 E87/19a E87/19c CBA-FN-19 CBA-FN-20 EDE-PP-112A RC-PCV-456B RC-V-122 RC-CS-456A-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-456-A1 Selector Switch G81 CB-F-1A-A RC-SS-456-A2 Selector Switch G5X DG-F-2A-A RC-J3M-42 Auxiliary Relay J3M DG-F-2A-A RC-PCV-456A-20 Solenoid Operating Coil LD3 C-F-3-Z RC-ZS-PCV-456A Valve Position Switch LD3 C-F-3-Z RC-E4A-FU11,12 30 A Fuses E4A CB-F-1A-A EDE-TBX-X56 Terminal Box X56 C-F-3-Z EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -4 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 RC-PCV-456B RC-E-10 Pressurizer Relief Control Valve RC-20846 B 310581 C-F-3-Z X X X LD4 RC-E88/19-72 125 V DC Circuit Breaker E88 CB-F-1B-A E88-E4C/7 E4C-GZO/2 E4C-J3P GZ0-J3P GZO-H39 G5Y-J3P H24-J3P H24-LD4 H39-X35 LD4-X35 310882 E88/19a E88/19c CBA-FN-32 CBA-FN-33 EDE-PP-112B RC-PCV-456A or RC-V-124 RC-CS-456B-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-456-B1 Selector Switch GZ0 CB-F-1B-A RC-SS-456-B2 Selector Switch G5Y DG-F-2B-A RC-J3P-42 Auxiliary Relay J3P DG-F-2B-A RC-PCV-456B-20 Solenoid Operating Coil LD4 C-F-3-Z RC-ZS-PCV-456B Valve Position Switch LD4 C-F-3-Z RC-E4C-FU19 & 20 30 A Fuses E4C CB-F-1B-A EDE-TBX-X35 Terminal Box X35 C-F-3-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-E4C-FU-23,24 30 A Fuses E4C CB-F-1B-A 8 RC-TK11 Pressurizer Relief Tank RC-20846 A/B 310577 C-F-1-Z X X - - - - - - - - - - - None Note 1 9 RC-V-323 Reactor Vessel Venting Valve RC-20845 B 310581 C-F-3-Z X X X - VB2 RC-BV9-52-1 460 V AC Circuit Breaker BV9 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 RC-FV-2881 Note 2 10 RC-FV-2881 Reactor Vessel Venting Valve RC-20845 B 310581 C-F-3-Z X X X UO4 RC-E88/1-72 125 V DC Circuit Breaker E88 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B RC-V-323 Note 2 RC-SS-2881 Selector Switch G5Y DG-F-2B-A 11 RC-LCV-459 Letdown Isolation Valve RC-20843 A 310577 C-F-1-Z X X X X L99 RC-E89/17-72 125 V DC Circuit Breaker E89 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 DAH-FN-25A DAH-FN-26A RC-LCV-460 Note 3, 4 RC-SS-459 Selector Switch G5X DG-F-2A-A 12 RC-LCV-460 Letdown Isolation Valve RC-20843 A 310577 C-F-1-Z X X X X LF7 RC-E89/1-72 125 V DC Circuit Breaker E89 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 RC-LCV-459 Note 3, 4

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -5 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 CS-P-2A Charging Pump CS-20725 A 310764 PAB-F-1C-A X X X - M17 CS-A62-52 4160 V AC Circuit Breaker A62 CB-F-1A-A A62-M17 A62-P01 310891 A62a A62h A62b A62c A62d CBA-FN-19 CBA-FN-20 EAH-FN-5A EDE-SWG-5 CS-P-2B CS-CS-7424-2 Control Switch A62 CB-F-1A-A CS-SS-7424 Selector Switch A62 CB-F-1A-A CS-A62-86 Lockout Relay A62 CB-F-1A-A CS-A62-52H Truck Operated Contact A62 CB-F-1A-A CS-A62-50/51 Inst./Time Over Current Relays øA, øC A62 CB-F-1A-A CS-PS-7467-1 Pressure Switch P01 PAB-F-1C-A CS-A62-AM Ammeter A62 CB-F-1A-A CS-A62-AS Ammeter Switch A62 CB-F-1A-A CS-A62-CT Current Transformer (100/5) A62 CB-F-1A-A CS-A62-TD1 CT Test Device A62 CB-F-1A-A CS-A62-ATR Transducer A62 CB-F-1A-A CS-A62-TD2 Lockout Relay Test Device A62 CB-F-1A-A CS-A62-TDR Timing Relay A62 CB-F-1A-A CS-A62-FU Fuses A62 CB-F-1A-A CS-A62-52Z Timing Relay A62 CB-F-1A-A CS-A62-G,R,W Indicating Lights A62 CB-F-1A-A CS-A62-51GS Ground Sensor Relay A62 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -6 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 14 CS-P-2B Charging Pump CS-20725 B 310764 PAB-F-1D-A X X X - M18 CS-A82-52 4160 V AC Circuit Breaker A82 CB-F-1B-A A82-M18 A82-P02 310891 A82a A82h A82b A82c A82d CBA-FN-32 CBA-FN-33 EAH-FN-5B EDE-SWG-6 CS-P-2A CS-CS-7425-2 Control Switch A82 CB-F-1B-A CS-SS-7425 Selector Switch A82 CB-F-1B-A CS-A82-86 Lockout Relay A82 CB-F-1B-A CS-A82-52H Truck Operated Contact A82 CB-F-1B-A CS-A82-50/51 Inst./Time Over Current Relays øA, øB A82 CB-F-1B-A CS-PS-7468-1 Pressure Switch P02 PAB-F-1D-A CS-A82-AM Ammeter A82 CB-F-1B-A CS-A82-AS Ammeter Switch A82 CB-F-1B-A CS-A82-CT Current Transformer (100/5) A82 CB-F-1B-A CS-A82-TD1 CT Test Device A82 CB-F-1B-A CS-A82-ATR Transducer A82 CB-F-1B-A CS-A82-TD2 Lockout Relay Test Device A82 CB-F-1B-A CS-A82-TDR Timing Relay A82 CB-F-1B-A CS-A82-FU Fuses A82 CB-F-1B-A CS-A82-52Z Timing Relay A82 CB-F-1B-A CS-A82-G,R,W Indicating Lights A82 CB-F-1B-A CS-A82-51GS Ground Sensor Relay A82 CB-F-1B-A CS-A82-R2 Auxiliary Relay A82 CB-F-1B-A 15 RC-P-1A Reactor Coolant Pump RC-20841 A 310576 310582 310578 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M01 RC-A05-52 13.8 kV AC Circuit Breaker A05 NES-F-1A-Z - - - - None Note 10 16 RC-P-1B Reactor Coolant Pump RC-20842 A 310576 310582 310578 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M02 RC-A20-52 13.8 kV AC Circuit Breaker A20 NES-F-1A-Z - - - - None Note 10 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -7 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 17 RC-P-1C Reactor Coolant Pump RC-20843 A 310577 310583 310579 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M03 RC-A09-52 13.8 kV AC Circuit Breaker A09 NES-F-1A-Z - - - - None Note 10 18 RC-P-1D Reactor Coolant Pump RC-20844 A 310577 310583 310579 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M04 RC-A24-52 13.8 kV AC Circuit Breaker A24 NES-F-1A-Z - - - - None Note 10 19 RC-V-22 RC-E-11A Hot Leg -RHR Isolation Valve RC-20841 B 310582 C-F-1-Z - X X - V27 RC-B54-52-1 460 V AC Circuit Breaker B54 CB-F-1B-A - - - - RC-V-23 Notes 5 and 7 20 RC-V-23 RC-E-11A Hot Leg -RHR Isolation Valve RC-20841 A 310576 C-F-1-Z - X X - V25 RC-B53-52-1 460 V AC Circuit Breaker B53 CB-F-1A-A - - - - RC-V-22 Notes 5 and 7 21 RC-V-87 RC-E-11D Hot Leg -RHR Isolation Valve RC-20844 B 310582 C-F-1-Z - X X - V26 RC-B61-52-1 460 V AC Circuit Breaker B61 CB-F-1B-A - - - - RC-V-87 Notes 5 and 7 22 RC-V-88 RC-E-11D Hot Leg -RHR Isolation Valve RC-20844 A 310577 C-F-1-Z - X X - V28 RC-B62-52-1 460 V AC Circuit Breaker B62 CB-F-1A-A - - - - RC-V-88 Notes 5 and 7 23 SI-V-3 Accumulator TK -9A Outlet Isolation Valve SI-20450 A 310576 C-F-1-Z - X X - V39 SI-B35-5-1,2 460 V AC Circuit Breakers B35 CB-F-1A-A B35-G81 B35-H19 B35-H36 H19-V39 H36-V39 310890 B35a B35c CBA-FN-19 CBA-FN-20 EDE-MCC-522 SI-FV-2475 SI-FV-2476 SI-B35-FU Fuse B35 CB-F-1A-A SI-CS-2403-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2403 Selector Switch G81 CB-F-1A-A SI-ZL-2403-4 Pilot Light G81 CB-F-1A-A SI-B35-42/0,C Motor Starters B35 CB-F-1A-A SI-B35-49 Overload Relay B35 CB-F-1A-A SI-ZS-V3 Valve Position and Open/Close Torque Switches V39 C-F-1-Z EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SI-EH9/9-52 120 V AC Circuit Breaker EH9 CB-F-1A-A G81-H35/5 G81-H36/6 H35-V41/1 H36-V39/1 E4H-EH9 E4H-G81 EH9/9a EH9/9b CBA-FN-19 CBA-FN-20 EDE-PP-1E SI-CS-2403-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2403 Selector Switch G81 CB-F-1A-A SI-ZS-V3 Valve Position and Open/Close Torque Switches V39 C-F-1-Z SI-E4H-FU7,8 30 A Fuses E4H CB-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -8 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 24 SI-V-17 Accumulator TK -9B Outlet Isolation Valve SI-20450 B 310576 C-F-1-Z - X X - V40 SI-B36-52-1,2 460 V AC Circuit Breakers B36 CB-F-1B-A B36-GZ0 B36-H15 B36-H41 H15-V40 H41-V40 310890 B36a B36c CBA-FN-32 CBA-FN-33 EDE-MCC-622 SI-FV-2482 SI-FV-2483 SI-B36-FU Fuse B36 CB-F-1B-A SI-CS-2413-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2413 Selector Switch GZ0 CB-F-1B-A SI-ZL-2413-4 Pilot Light GZ0 CB-F-1B-A SI-B36-42/0,C Motor Starters B36 CB-F-1B-A SI-B36-49 Overload Relay B36 CB-F-1B-A SI-ZS-V17 Valve Position and Open/Close Torque Switches V40 C-F-1-Z EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A SI-EH0/9-52 120 V AC Circuit Breaker EH0 CB-F-1B-A GZ0-H39/5 GZ0-H41/4 H39-V42/1 H41-V40/1 E4J-EH0 E4J-GZ0 EH0/9a EH0/9b CBA-FN-32 CBA-FN-33 EDE-PP-1F SI-CS-2413-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2413 Selector Switch GZ0 CB-F-1B-A SI-ZS-V17 Valve Position and Open/Close Torque Switches V40 C-F-1-Z SI-E4J-FU7,8 30 A Fuses E4J CB-F-1B-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -9 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 25 SI-V-32 Accumulator TK -9C Outlet Isolation Valve SI-20450 A 310577 C-F-1-Z - X X - V41 SI-B37-52-1,2 460 V AC Circuit Breakers B37 CB-F-1A-A B37-G81 B37-H18 B37-H35 H18-V41 H35-V41 B37a B37c CBA-FN-19 CBA-FN-20 EDE-MCC-522 SI-FV-2477 SI-FV-2486 SI-B37-FU Fuse B37 CB-F-1A-A SI-CS-2423-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2423 Selector Switch G81 CB-F-1A-A SI-ZL-2423-4 Pilot Light G81 CB-F-1A-A SI-B37-42/0,C Motor Starter s B37 CB-F-1A-A SI-B37-49 Overload Relay B37 CB-F-1A-A EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A SI-ZS-V32 Valve Position and Open/Close Torque Switches V41 C-F-1-Z SI-EH9/9-52 120 V AC Circuit Breakers EH9 CB-F-1A-A G81-H35/5 G81-H36/6 H35-V41/1 H36-V39/1 E4H-EH9 E4H-G81 EH9/9a EH9/9b CBA-FN-19 CBA-FN-20 EDE-PP-1E SI-CS-2423-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2423 Selector Switch G81 CB-F-1A-A SI-ZS-V32 Valve Position and Open/Close Torque Switches V41 C-F-1-Z SI-E4H-FU7,8 30 A Fuses E4H CB-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -10 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 26 SI-V-47 Accumulator TK -9D Outlet Isolation Valve SI-20450 B 310577 C-F-1-Z - X X - V42 SI-B38-52-1,2 460 V AC Circuit Breakers B38 CB-F-1B-A B38-GZ0 B38-H24 B38-H39 H24-V42 H39-V42 310890 B38a B38c CBA-FN-32 CBA-FN-33 EDE-MCC-622 SI-FV-2495 SI-FV-2496 SI-B38-FU Fuse B38 CB-F-1B-A SI-CS-2433-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2433 Selector Switch GZ0 CB-F-1B-A SI-ZL-2433-4 Pilot Light GZ0 CB-F-1B-A SI-B38-42/0,C Motor Starters B38 CB-F-1B-A SI-B38-49 Overload Relay B38 CB-F-1B-A SI-ZS-V47 Valve Position and Open/Close Torque Switches V42 C-F-1-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A SI-EH0/9-52 120 V AC Circuit Breaker EH0 CB-F-1B-A GZ0-H39/5 GZ0-H41/4 H39-V42/1 H41-V40/1 E4J-EH0 E4J-GZ0 EH0/9a EH0/9b CBA-FN-32 CBA-FN-33 EDE-PP-1F SI-CS-2433-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2433 Selector Switch GZ0 CB-F-1B-A SI-ZS-V47 Valve Position and Open/Close Torque Switches V42 C-F-1-Z SI-E4J-FU7,8 30 A Fuses E4J CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A 27 CS-P-2A Charging Pump Lube Oil Cooler CS-20725 A 310764 805213 PAB-F-1C-A X X - - - - - - - - - - Component Cooling CS-P-2B Note 9 28 CS-P-2B Charging Pump Lube Oil Cooler CS-20725 B 310764 815214 PAB-F-1D-A X X - - - - - - - - - - Component Cooling CS-P-2A Note 9 29 CS-V-460 SI-P-6A Suction Valve CS-20725 A 310761 RHR-F-2B-Z - X X - V59 CS-B44-52 460 V AC Circuit Breaker B44 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 2 30 CS-V-461 SI-P-6A Suction Valve CS-20725 B 310761 RHR-F-2B-Z - X X - V60 VS-B45-52 460 V AC Circuit Breaker B45 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 2 31 CS-V-167 RC Pump Seal Water Isolation Valve CS-20726 A 310769 PP-F-5B-Z X X X - V05 CS-B73-52 460 V AC Circuit Breaker B73 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 2 32 CS-V-168 RC Pump Seal Water Isolation Valve CS-20726 B 310577 C-F-1-Z X X X - V06 CS-B72-52-1 450 V AC Circuit Breaker B72 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 2 33 CS-V-175 Excess Letdown Isolation Valve CS-20722 B 310577 C-F-1-Z X X X X L95 CS-E95/2-72 125 V DC Circuit Breaker E95 C-F-1B-A CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B CS-V-176 Notes 2 and 4 CS-SS-7418 Selector Switch G5Y DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -11 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 34 CS-V-176 Excess Letdown Isolation Valve CS-20722 B 310577 C-F-1-Z X X X X LA5 CS-E95/4-72 125 V DC Circuit Breaker E95 CB-F-1B-A CBA-FN-32 CBA-FN-33 CS-V-175 Notes 2 and 4 35 CS-V-196 Charging Pump Miniflow Isolation Valve CS-20725 A 310762 PAB-F-1J-Z X X X - V13 CS-B81-52 460 V AC Circuit Breaker B81 CB-F-1A-A CBA-FN-19 CBA-FN-20 CS-V-197 Note 2 36 CS-V-197 Charging Pump Miniflow Isolation Valve CS-20725 B 310762 PAB-F-1J-Z X X X - V14 CS-B86-52 460 V AC Circuit Breaker B86 CB-F-1B-A CBA-FN-32 CBA-FN-33 CS-V-196 Note 2 37 CS-LCV-112B Chemical and Volume Control Tank Outlet Isolation Valve CS-20725 A 310768 PAB-F-3B-Z X X X - VE4 CS-B50-52 460 V AC Circuit Breaker B50 CB-F-1A-A B50-G2G B50-G2G/1 B50-VE4 B50-VE4/1 B50-VE4/2 E3P-G2G B50-E3P 310891 B50a B50c B50d CBA-FN-19 CBA-FN-20 EDE-MCC-512 CS-LCV-112C CS-B50-FU Fuse B50 CB-F-1A-A CS-CS-112B-2 Control Switch with Indication G2G CB-F-1A-A CS-SS-112B Selector Switch G2G CB-F-1A-A CS-B50-42/0,C Motor Starters B50 CB-F-1A-A CS-B50-49 Overload Relay B50 CB-F-1A-A CS-ZS-LCV-112B Valve Position and Open/Close Torque Switches VE4 PAB-F-3B-Z CS-EC8-R1 Auxiliary Relay EC8 CB-F-1A-A CS-E3P-R2 Auxiliary Relay E3P CB-F-1A-A 38 CS-LCV-112C Chemical and Volume Control Tank Outlet Isolation Valve CS-20725 B 310768 PAB-F-3B-Z X X X - VE7 CS-B83-52 460 V AC Circuit Breaker B83 CB-F-1B-A B83-G2J B83-G2J/1 B83-VE7 B83-VE7/1 B83-VE7/2 E3Q-G2J B83-E3Q 310891 B83a B83c B83d CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-LCV-112B CS-B83-FU Fuse B83 CB-F-1B-A CS-CS-112C-2 Control Switch with Indication G2J CB-F-1B-A CS-SS-112C Selector Switch G2J CB-F-1B-A CS-B83-42/0,C Motor Starters B83 CB-F-1B-A CS-B83-49 Overload Relay B83 CB-F-1B-A CS-ZS-LCV-112C Valve Position and Open/Close Torque Switches VE7 PAB-F-3B-Z CS-ED0-R1 Auxiliary Relay ED0 CB-F-1B-A CS-E3Q-R2 Auxiliary Relay E3Q CB-F-1B-A 39 CS-LCV-112D Refueling Water Storage Tank to Charging Pump 2A Isolation Valve CBS-20233 A 301254 TF-F-1-0 X X X - VE6 CS-B78-52 460 V AC Circuit Breaker B78 CB-F-1A-A B78-G2G B78-G2G/1 B78-VE6 B78-VE6/1 B78-VE6/2 310891 B78a B78c B78d CBA-FN-19 CBA-FN-20 EDE-MCC-512 CS-LCV-112E CS-CS-122D-2 Control Switch with Indication G2G CB-F-1A-A CS-SS-112D Selector Switch G2G CB-F-1A-A CS-B78-42/0,C Motor Starters B78 CB-F-1A-A CS-B78-49 Overload Relay B78 CB-F-1A-A CS-ZS-LCV-112D Valve Position and Open/Close Torque Switches VE6 TF-F-1-0 CS-EC8-R1 Auxiliary Relay EC8 CB-F-1A-A CS-B78-FU Fuse B78 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -12 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 40 CS-LCV-112E RWST CBS-TK-8 to Charging Pump 2B Isolation Valve CBS-20233 B 301254 TF-F-1-0 X X X - VE5 CS-B79-52 460 V AC Circuit Breaker B79 CB-F-1B-A B79-G2J B79-G2J/1 B79-VE5 B79-VE5/1 B79-VE5/2 310891 B79a B79c B79d CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-LCV-112D CS-CS-122E-2 Control Switch with Indication G2J CB-F-1B-A CS-SS-112E Selector Switch G2J CB-F-1B-A CS-B79-42/0,C Motor Starters B79 CB-F-1B-A CS-B79-49 Overload Relay B79 CB-F-1B-A CS-ZS-LCV-112E Valve Position and Open/Close Torque Switches VE5 TF-F-1-0 CS-ED0-R1 Auxiliary Relay ED0 CB-F-1B-A CS-B79-FU Fuse B79 CB-F-1B-A 41 SI-V-138 Charging Pump To Cold Leg Isolation Valve SI-20447 A 310769 PP-F-1B-Z X X X - V31 SI-B31-52 460 V AC Circuit Breaker B31 CB-F-1A-A B31-G2G B31-G2G/2 B31-V31 B31-V31/1 B31-V31/2 B31-FN8 B31-FN8/1 310890 B31a B31c B31d CBA-FN-19 CBA-FN-20 EDE-MCC-521 SI-V-139 SI-CS-2437-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2437 Selector Switch G81 CB-F-1A-A SI-SS-2437-1 Selector Switch FN8 ET-F-1B-A SI-B31-42/0,C Motor Starters B31 CB-F-1A-A SI-B31-49 Overload Relay B31 CB-F-1A-A SI-ZS-V138 Valve Position and Open/Close Torque Switches V31 PP-F-1B-Z SI-B31-FU Fuse B31 CB-F-1A-A 42 SI-V-139 Charging Pump To Cold Leg Isolation Valve SI-20447 B 310769 PP-F-1B-Z X X X - V32 SI-B32-52 460 V AC Circuit Breaker B32 CB-F-1B-A B32-G2J B32-G2J/2 B32-V32 B32-V32/1 B32-V32/2 B32-FN9 B32-FN9/1 310890 B32a B32c B32d CBA-FN-32 CBA-FN-33 EDE-MCC-621 SI-V-138 SI-CS-2447-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2447 Selector Switch GZ0 CB-F-1B-A SI-SS-2447-1 Selector Switch FN9 ET-F-1D-A SI-B32-42/0,C Motor Starters B32 CB-F-1B-A SI-B32-49 Overload Relay B32 CB-F-1B-A SI-ZS-V139 Valve Position and Open/Close Torque Switches V32 PP-F-1B-Z SI-B32-FU Fuses B32 CB-F-1B-A 43 RC-E-10 Pressurizer Heaters Group C RC-20846 A 310598 C-F-1-Z X - X - M26 RC-AG4-52 480 V AC Circuit Breaker AG4 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 8 44 RC-E-10 Pressurizer Heaters Group D RC-20846 A 310598 C-F-1-Z X - X - M26 RC-AM5-52 480 V AC Circuit Breaker AM5 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 8 45 CBS-P-9A Containment Spray Pump CSB-20233 A 310761 RHR-F-1B-Z X - X - M15 CBS-A61-52 4160 V AC Circuit Breaker A61 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 11 46 CBS-P-9B Containment Spray Pump CBS-20233 B 310761 RHR-F-1A-Z X - X - M16 CBS-A81-52 4160 V AC Circuit Breaker A81 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 11 47 SI-P-6A Safety Injection Pump SI-20446 A 310761 RHR-F-2B-Z - X X - M09 SI-A56-52 4160 V AC Circuit Breaker A56 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 11 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -13 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 48 SI-P-6B Safety Injection Pump SI-20446 B 310761 RHR-F-2A-Z - X X - M10 SI-A76-52 4160 V AC Circuit Breaker A76 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 11 49 SI-V-158 Charging Pump Test Line Isolation Valve SI-20447 B 310577 C-F-1-Z - X X X L89 RC-E88/7-72 125 V DC Circuit Breaker E88 CB-F-1B-A - - - - - Note 2, 4 50 SI-V-159 Charging Pump Test Line Isolation Valve SI-20447 A 310577 C-F-1-Z - X X X L90 RC-E89/4-72 125 V DC Circuit Breaker E89 CB-F-1A-A - - - - - Note 2, 4 51 SI-FV-2475 Accumulator TK -9A Relief Valve SI-20450 B 310578 C-F-2-Z - X X - V2Z SI-E2U/7-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-E4C/3 E4C-GZ0/1 GZ0-H39/6 H39-V2Z 310890 E2U/7a E2U/7f E2U/7g E2U/7h EDE-PP-113B SI-E4C-FU Fuses E4C CB-F-1B-A SI-SS-2475 Selector Switch GZ0 CB-F-1B-A SI-CS-2475-2 Control Switch with Indication GZ0 CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A SI-20-FV-2475 Solenoid Valve V2Z C-F-2-Z SI-ZS-FV-2475 Valve Position Switch V2Z C-F-2-Z 52 SI-FV-2476 Accumulator TK -9A Relief Valve SI-20450 B 310578 C-F-2-Z - X X - V3A SI-E2U/7-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-E4C/3 E4C-GZ0/1 GZ0-H39/6 GZO-H39/7 H39-V3A E2U/7b E2U/7f E2U/7g E2U/7h EDE-PP-113B SI-E4C-FU Fuses E4C CB-F-1B-A SI-SS-2475 Selector Switch GZ0 CB-F-1B-A SI-CS-2475-2 Control Switch with Indication GZ0 CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A SI-20-FV-2476 Solenoid Valve V3A C-F-2-Z SI-ZS-FV-2476 Valve Position Switch V3A C-F-2-Z 53 SI-FV-2477 Accumulator T K-9C Relief Valve SI-20450 B 310578 C-F-2-Z - X X - V3D SI-E2U/7-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-E4C/3 E4C-GZ0/1 GZ0-H41/5 H41-V3D E2U/7c E2U/7f E2U/7g E2U/7h EDE-PP-113B SI-E4C-FU Fuses E4C CB-F-1B-A SI-SS-2475 Selector Switch GZ0 CB-F-1B-A SI-CS-2477-2 Control Switch with Indication GZ0 CB-F-1B-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A SI-20-FV-2477 Solenoid Valve V3D C-F-2-Z SI-ZS-FV-2477 Valve Position Switch V3D C-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -14 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 54 SI-FV-2486 Accumulator TK -9C Relief Valve SI-20450 B 310578 C-F-2-Z - X X - V3E SI-E2U/7-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-E4C/3 E4C-GZ0/1 GZ0-H41/5 GZ0-H41/6 H41-V3E E2U/7d E2U/7f E2U/7g E2U/7h EDE-PP-113B SI-E4C-FU Fuses E4C CB-F-1B-A SI-SS-2475 Selector Switch GZ0 CB-F-1B-A SI-CS-2477-2 Control Switch with Indication GZ0 CB-F-1B-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A SI-20-FV-2486 Solenoid Valve V3E C-F-2-Z SI-ZS-FV-2486 Valve Position Switch V3E C-F-2-Z 55 SI-FV-2482 Accumulator TK -9B Relief Valve SI-20450 A 310578 C-F-2-Z - X X - V3B SI-E2T/7-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-E4H/2 E4H-G81/2 G81-H35/6 H35-V3B 310890 E2T/7a E2T/7f E2T/7g E2T/7h EDE-PP-113A SI-E4H-FU Fuses E4H CB-F-1A-A SI-SS-2482 Selector Switch G81 CB-F-1A-A SI-CS-2482-2 Control Switch with Indication G81 CB-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A SI-20-FV-2482 Solenoid Valve V3B C-F-2-Z SI-ZS-FV-2482 Valve Position Switch V3B C-F-2-Z 56 SI-FV-2483 Accumulator TK -9B Relief Valve SI-20450 A 310578 C-F-2-Z - X X - V3C SI-E2T/7-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-E4H/2 E4H-G81/2 G81-H35/6 G81-H35/7 H35-V3C E2T/7b E2T/7f E2T/7g E2T/7h EDE-PP-113A SI-E4H-FU Fuses E4H CB-F-1A-A SI-SS-2482 Selector Switch G81 CB-F-1A-A SI-CS-2482-2 Control Switch with Indication G81 CB-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A SI-20-FV-2483 Solenoid Valve V3C C-F-2-Z SI-ZS-FV-2483 Valve Position Switch V3C C-F-2-Z 57 SI-FV-2495 Accumulator TK -9D Relief Valve SI-20450 A 310579 C-F-2-Z - X X - V3F SI-E2T/7-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-E4H/2 E4H-G81/2 G81-H36/9 H36-V3F E2T/7c E2T/7f E2T/7g E2T/7h EDE-PP-113A SI-E4H-FU Fuses E4H CB-F-1A-A SI-SS-2482 Selector Switch G81 CB-F-1A-A SI-CS-2495-2 Control Switch with Indication G81 CB-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SI-20-FV-2495 Solenoid Valve V3F C-F-2-Z SI-ZS-FV-2495 Valve Position Switch V3F C-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -15 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 58 SI-FV-2496 Accumulator TK -9D Relief Valve SI-20450 A 310579 C-F-2-Z - X X - V3G SI-E2T/7-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-E4H/2 E4H-G81/2 G81-H36/9 G81-H36/A H36-V3G E2T/7d E2T/7f E2T/7g EDE-PP-113A SI-E4H-FU Fuses E4H CB-F-1A-A SI-SS-2482 Selector Switch G81 CB-F-1A-A SI-CS-2495-2 Control Switch with Indication G81 CB-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SI-20-FV-2496 Solenoid Valve V3G C-F-2-Z SI-ZS-FV-2496 Valve Position Switch V3G C-F-2-Z 59 CS-E-5A Seal Water Heat Exchanger CS-20726 A 310764 PAB-F-1B-Z X X - - - - - - - - - - - - Note 1 60 CS-E-5B Seal Water Heat Exchanger CS-20726 B 310764 PAB-F-1B-Z X X - - - - - - - - - - - - Note 1 61 RC-E-10 Pressurizer Heaters Control Group RC-20846 A 310598 C-F-1-Z X - X - M26 RC-AM4-52 480 V AC Circuit Breaker AM4 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 8 62 CS-V-142 Charging Line Isolation Valve CS-20722 A 310769 PP-F-1A-Z X X X - V12 CS-B82-52 460 V AC Circuit Breaker B82 CB-F-1A-A B82-G2G B82-G2G/1 B82-V12 310891 B82a B82c B82d CBA-FN-19 CBA-FN-20 EAH-FN-5A EDE-MCC-512 CS-V-143 CS-CS-7410-2 Control Switch with Indication G2G CB-F-1A-A CS-SS-7410 Selector Switch G2G CB-F-1A-A CS-B82-42/0,C Motor Starters B82 CB-F-1A-A CS-B82-49 Overload Relay B82 CB-F-1A-A CS-ZS-V142 Valve Position and Open/Close Torque Switches V12 PP-F-1A-Z CS-B82-FU Fuse B82 CB-F-1A-A 63 CS-V-143 Charging Line Isolation Valve CS-20722 B 310769 PP-F-1A-Z X X X - V11 CS-B87-52 460 V AC Circuit Breaker B87 CB-F-1B-A B87-G2J B87-G2J/1 B87-V11 B87-V11/1 B87a B87c B87d CBA-FN-32 CBA-FN-33 EAH-FN-5B EDE-MCC-612 CS-V-142 CS-CS-7411-2 control Switch with Indication G2J CB-F-1B-A CS-SS-7411 Selector Switch G2J CB-F-1B-A CS-B87-42/0,C Motor Starters B87 CB-F-1B-A CS-B87-49 Overload Relay B87 CB-F-1B-A CS-ZS-V143 Valve Position and Open/Close Torque Switches V11 PP-F-1A-Z CS-B87-FU Fuses B87 CB-F-1B-A 64 CS-V-210 Charging Pump 2A Discharge Valve CS-20725 A 310764 PAB-F-1C-A - X - - - - - - - - - - - CS-V-220 Note 1 65 CS-V-219 Charging Pump 2B Bypass Valve CS-20725 B 310764 PAB-F-1D-A - X - - - - - - - - - - - CS-V-221 Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -16 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 66 CS-V-220 Charging Pump 2B Discharge Valve CS-20725 B 310764 PAB-F-1D-A - X - - - - - - - - - - - CS-V-210 Note 1 67 CS-V-221 Charging Pump 2A Bypass Valve CS-20725 A 310764 PAB-F-1C-A - X - - - - - - - - - - - CS-V-219 Note 1 68 CS-V-154 RCP-1D Seal Injection Isolation Valve CS-20726 A 310769 PP-F-5B-Z X X - - - - 480 V AC Circuit Breaker B77 CB-F-1A-A - - - - None Note 2 69 CS-V-158 RCP-1C Seal Injection Isolation Valve CS-20726 A 310769 PP-F-5B-Z X X - - - - 480 V AC Circuit Breaker B76 CB-F-1A-A - - - - None Note 2 70 CS-V-162 RCP-1B Seal Injection Isolation Valve CS-20726 A 310769 PP-F-1A-Z X X - - - - 480 V AC Circuit Breaker B75 CB-F-1A-A - - - - None Note 2 71 CS-V-166 RCP-1A Seal Injection Isolation Valve CS-20726 A 310769 PP-F-1A-Z X X - - - - 480 V AC Circuit Breaker B74 CB-F-1A-A - - - - None Note 2 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3 .3-1 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CS-TK-4A Boric Acid Storage Tank CS-20729 A/B 310766 PAB-F-2B-Z - X - - - - - - - - - - - CS-TK-4B Note 1 2 CS-TK-4B Boric Acid Storage Tank CS-20729 A/B 310766 PAB-F-2B-Z - X - - - - - - - - - - - CS-TK-4A Note 1 3 CS-V-410 Boric Acid Tank 4A Outlet Valve CS-20729 A/B 310766 805216 805229 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-416 CS-V-1207 Notes 1, 2 and 3 4 CS-V-416 Boric Acid Tank 4B Outlet Valve CS-20729 A/B 310766 805216 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-410 CS-V-1207 Notes 1, 2 and 3 5 CS-V-423 Boric Acid Recirculation Valve CS-20729 A 310766 805216 805230 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-431 CS-V-1207 Notes 1, 2 and 3 6 CS-V-431 Boric Acid Recirculation Valve CS-20729 B 310766 805216 805230 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-423 CS-V-1207 Notes 1, 2 and 3 7 CS-V-437 Boric Acid Transfer Pump's Suction Cross -Over Line Isolation Valve CS-20729 A 310766 805216 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-1207 Notes 1, 2 and 3 8 CS-V-439 Charging Pump Isolation Valve CS-20729 A/B 310766 805216 805229 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-426 Notes 1, 2 and 3 9 CS-V-442 Charging Pump Isolation Valve CS-20729 A/B 310766 805216 805229 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-426 Notes 1, 2 and 3 10 CS-P-3A Boric Acid Transfer Pump CS-20729 A 310766 805216 805230 PAB-F-2B-Z - X X - M43 CS-B88-52 460 V AC Circuit Breaker B88 CB-F-1A-A B88-M43 B88-M43/1 310891 B88a B88c CBA-FN-19 CBA-FN-20 EDE-MCC-512 CS-P-3B CS-B88-FU Fuse B88 CB-F-1A-A CS-CS-7435-2 Control Switch B88 CB-F-1A-A CS-SS-7435 Selector Switch B88 CB-F-1A-A CS-B88-42 Motor Starter B88 CB-F-1A-A CS-M43-49 Overload Relay M43 PAB-F-2B-Z CS-B88-49 Overload Relay B88 CB-F-1A-A

.Notes  1. Equipment is mechanical with no electrical requirement.
2. CS-V-423, 410, 416, 431, 437, 439, 442 are non

-electrically operated valves and will be manually positioned as required to provide their reactivity control function during safe shutdown.

3. Electrical conduit plan drawing, 310766, listed only to show fire zone correlation reference to Primary Auxiliary Building area covered by piping Drawings 805216, 805229, 805230, where Valves CS

-V-410, 416, 423, 431, 437, 439, 442 are identified in plan and section.

4. This equipment is listed because it can spuriously start due to cable failure in the boration and dilution flow control valve control circuits. Spurious pump start by itself from failure of its cable is not of concern since CS

-FCV-111A remains closed so the pump cables are not listed.

5. Disabling the valves at the appropriate control location will reposition CS

-FCV-110B and C S-FCV-111B for safe shutdown. Air is not needed to position or to reposition the valve for safe shutdown.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3 .3-2 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 CS-P-3B Boric Acid Transfer Pump CS-20729 B 310766 805216 805230 PAB-F-2B-Z - X X - M44 CS-B89-52 460 V AC Circuit Breaker B89 CB-F-1B-A B89-M44 B89-M44/1 310891 B89a B89c CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-P-3A CS-B89-FU Fuse B89 CB-F-1B-A CS-CS-7436-2 Control Switch B89 CB-F-1B-A CS-SS-7436 Selector Switch B89 CB-F-1B-A CS-B89-42 Motor Starter B89 CF-F-1B-A CS-M44-49 Overload Relay M44 PAB-F-2B-Z CS-B89-49 Overload Rela y B89 CB-F-1B-A 12 CS-V-426 Boric Acid F -5 to Charging Pumps Isolation Valve CS-20729 B 310766 PAB-F-2B-Z - X X V04 CS-B94-52 460 V Circuit Breaker B94 CB-F-1B-A B94-V04 B94-V04/1 B94-V04/2 310891 B94a B94c CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-V-439 CS-V-442 CS-CS-7437-2 Control Switch with Indicator B94 CB-F-1B-A CS-SS-7437 Selector Switch B94 CB-F-1B-A CS-B94-42/0,C Motor Starter B94 CB-F-1B-A CS-B94-49 Overload Relay B94 CB-F-1B-A CS-ZS-V426 Valve Position and Open/Close Torque Switches V04 PAB-F-2B-Z CS-B94-FU Fuse B94 CB-F-1B-A 13 CP-CP-111 Reactor Trip Switchgear Cab

- A/B 310442 CB-F-1A-A X - X  HD2/ HD3 - - - - - - - -   14 CS-V-1207 Boric Acid Transfer Pump's Suction Cross-Over Line Isolation Valve CS-20729 B 310766 805216 PAB-F-2B-Z - X - - - - - - - - - - - Notes 1, 2 and 3 15 CS-FCV-110A CS-FCV-111A CS-FCV-110B CS-FCV-111B Boration and Dilution Flow Control Valves CS-20729 A 310766 PAB-F-2B-Z PAB-F-2B-Z PAB-F-2B-Z PAB-F-2B-Z X X X - LG2 LG1 LG4 LG5 CS-E97/11-72 125 V DC Circuit Breaker E97 NES-F-1A-Z - - - - Note 5 16 RMW-P-16A Reactor Makeup Water Pump CS-20360 A 310763 PAB-F-1A-Z X X X - M36 - - - - - - - - Note 4 17 RMW-P-16B Reactor Makeup Water Pump CS-20360 A 310763 PAB-F-1A-Z X X X - M37 - - - - - - - - Note 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 4 Table RSS 3.1.3.4

-1 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CC-TE-2297 Primary Component Cooling Water Loop "B" Supply Header Temperature Element CC-20211 B 310763 PAB-F-2C-Z X X X - T2Z CC-TY-2297 I/E Converter GZ0 CB-F-1B-A CZ0-T2Z FP 71336 M-310952 4 GZ0c CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 CC-TE-2197 CC-TI-2297 Temp. Indicator GZ0 CB-F-1B-A 2 FW-FT-4224-5 RC-E-11B Steam Generator Emergency Feedwater Header Flow Transmitter FW-20688 B 310708 EFP-F-1-A X X X - GL4 FW-FQY-4224-5 I/E Converter GZ0 CB-F-1B-A GL4-GZ0/1 6 GZ0a CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 EPA-FN-47B FW-FT-4214-5 FW-FT-4234-5 FW-FY-4224-5 Square Root Extractor GZ0 CB-F-1B-A FW-FI-4224-5 Flow Indicator G2J CB-F-1B-A 3 FW-FT-4244-5 RC-E-11D Steam Generator Emergency Feedwater Header Flow Transmitter FW-20688 B 310708 EFP-F-1-A X X X - GL4 FW-FQY-4244-5 I/E Converter GZ0 CB-F-1B-A GL4-GZ0/1 6 GZ0a CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 EPA-FN-47B FW-FT-4214-5 FW-FT-4234-5 FW-FY-4244-5 Square Root Extractor GX0 CB-F-1B-A FW-FI-4244-5 Flow Indicator G2J CB-F-1B-A 4 FW-LT-4320 RC-E-11B Steam Generator Wide Range Level Transmitter FW-20686 B 310576 C-F-1-Z X X X - R1N FW-LQY-4320 I/E Converter GZ0 CB-F-1B-A H55-R1N GZ0-H55 E1T-G2K 7 GZ0a E1T/4 EH0/2 CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 EDE-PP-11F FW-LT-4310 FW-LT-4330 FW-LI-4320 Level Indicator G2J CB-F-1B-A FW-LR-4320 Level Recorder G2J CB-F-1B-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 5 FW-LT-4340 RC-E-11D Steam Generator Wide Range Level Transmitter FW-20686 B 310577 C-F-1-Z X X X - R1Q FW-LQY-4340 I/E Converter GZ0 CB-F-1B-A H55-R1Q GZ0-H55 E1T-G2K 7 GZ0a E1T/4 EH0/2 CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 EDE-PP-11F FW-LT-4310 FW-LT-4330 FW-LI-4340 Level Indicator G2J CB-F-1B-A FW-LR-4320 Level Recorder G2J CB-F-1B-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 6 MS-PT-3174 RC-E-11B Steam Generator Header Pressure Transmitter MS-20581 B 310586 MS-F-1A-Z X X X - GZ4 MS-PQY-3174 I/E Converter GZ0 CB-F-1B-A GZ0-GZ4 10 GZ0c CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 MS-PT-3173 MS-PT-3178 MS-PI-3174 Press. Indicator G2J CB-F-1B-A 7 MS-PT-3179 RC-E-11D Steam Generator Header Pressure Transmitter MS-20581 B 310589 MS-F-1B-A X X X - GZ6 MS-PQY-3179 I/E Converter GZ0 CB-F-1B-A GZ0-GZ6 10 GZ0c CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 MS-PT-3173 MS-PT-3178 MS-PI-3179 Press. Indicator G2J CB-F-1B-A 8 RC-LT-7333 RC-E-10 Pressurizer Level Transmitter RC-20846 B 310579 C-F-2-Z X X X - GN5 RC-LQY-7333 I/E Converter GZ0 CB-F-1B-A H55-PR8/1 GZ0-H55/1 E1T-G2K 11 GZ0a E1T/4 EH0/2 CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 EDE-PP-11F RC-LT-7334 RC-LI-7333 Level Indicator GZ0 CB-F-1B-A RC-LR-7333 Level Recorder GZ0 CB-F-1B-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A

.Notes   1. Underground duct Plan Drawing 310248 is listed only to show the fire zone corresponding to the locations of the condensate storage tank level Indicator CO

-LISL-4052 which is identified in Drawing 509066.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 4 Table RSS 3.1.3.4 -2 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 RC-PT-7335 RC-E-10 Pressurizer Pressure Transmitter RC-20846 B 310579 C-F-2-Z X X X - PR8 RC-PQY-7335 I/E Converter GZ0 CB-F-1B-A H55-PR8 GZ0-H55/1 FP 71336 310952 12 GZ0a CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 RC-PT-7336 RC-PI-7335 Press. Indicator GZ0 CB-F-1B-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 10 RC-TE-9407 Reactor Coolant Loop 4 Wide Range Hot Leg Temperature Element RC-20844 B 310583 C-F-1-Z X X X - TS7 RC-TY-9407 R/E Converter GZ0 CB-F-1B-A H55-TS7 GZ0-H55/2 E1T-G2K 13 GZ0a E1T/4 EH0/2 CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 EDE-PP-11F RC-TE-9406 RC-TI-9407 Temp. Indicator GZ0 CB-F-1B-A RC-TR-9407 Temp. Recorder GZ0 CB-F-1B-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 11 RC-TE-9411 Reactor Coolant Loop 4 Wide Range Cold Leg Temperature Element RC-20844 B 310583 C-F-1-Z X X X - T3E RC-TY-9411 R/E Converter GZ0 CB-F-1B-A H55-T3E GZ0-H55/2 E1T-G2K 13 GZ0a E1T/4 EH0/2 CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 EDE-PP-11F RC-TE-9410 RC-TI-9411 Temp. Indicator GZ0 CB-F-1B-A RC-TR-9407 Temp. Recorder GZ0 CB-F-1B-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 12 CS-LT-7464 Boric Acid Tank CS-TK-4B Level Transmitter CS-20729 B 310766 PAB-F-2B-Z - X X - RJ9 CS-LSY-7464 Comparator G2J CB-F-1B-A G2K-RJ9 GZ0c CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 CS-LT-7446 CS-LQY-7464 I/E Converter G2J CB-F-1B-A CS-LI-7464 Level Indicator G2J CB-F-1B-A 13 MM-UQ-5868 Remote Shutdown Panel MM-CP-108B Power Supply

- B 310442 CB-F-1B-A X X X - G2J VI-G2J-FU9 20A Fuse G2J CB-F-1B-A EH0-G2J  M-310952 EH0/2 EH0/2 CBA-FN-32 CBA-FN-33 EDE-PP-1F MM-UQ-5866             VI-G2J-FU10 20A Fuse G2J CB-F-1B-A    14 MM-UQ-5869 Remote Shutdown Panel MM-CP-108B Power Supply
- B 310442 CB-F-1B-A X X X - G2J VI-G2J-FU11 20A Fuse G2J CB-F-1B-A EH0-G2J EH0/2 EH0/2 CBA-FN-32 CBA-FN-33 EDE-PP-1F MM-UQ-5867             VI-G2J-FU12 20A Fuse G2J CB-F-1B-A     15 NOT USED                    16 CC-TE-2197 Primary Component Cooling Water Loop "A" Supply Header Temperature Element CC-20205 A 310763 PAB-F-2C-Z X X X - T3A CC-TY-2197 I/E Converter G2H CB-F-1A-A G2H-T3A FP 71337 M-310952 11 G81d CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 CC-TE-2297             CC-TI-2197 Temp. Indicator G81 CB-F-1A-A    17 FW-FT-4214-5 RC-E-11A Steam Generator Emergency Feedwater Header Flow Transmitter FW-20688 A 310708 EFP-F-1-A X X X - GL3 FW-FQY-4214-5 I/E Converter G81 CB-F-1A-A G81-GL3 4 G81a CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 EPA-FN-47A FW-FT-4224-5 FW-FT-4244-5             FW-FY-4214-5 Square Root Extractor G81 CB-F-1A-A               FW-FI-4214-5 Flow Indicator G2G CB-F-1A-A     18 FW-FT-4234-5 RC-E-11C Steam Generator Emergency Feedwater Header Flow Transmitter FW-20688 A 310708 EFP-F-1-A X X X - GL3 FW-FQY-4234-5 I/E Converter G81 CB-F-1A-A G81-GL3 FP 71337 310952 4 G81a CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 EPA-FN-47A FW-FT-4224-5 FW-FT-4244-5             FW-FY-4234-5 Square Root Extracto r G81 CB-F-1A-A               FW-FI-4234-5 Flow Indicator G2G CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 4 Table RSS 3.1.3.4

-3 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 FW-LT-4310 RC-E-11A Steam Generator Wide Range Level Transmitter FW-20686 A 310576 C-F-1-Z X X X - R1M FW-LQY-4310 I/E Converter G2H CB-F-1A-A H44-R1M G2H-H44 E1S-G2H 17 G81d E1S/4 EH9/2 CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 EDE-PP-11E FW-LT-4320 FW-LT-4340 FW-LI-4310 Level Indicator G2G CB-F-1A-A FW-LR-4310 Level Recorder G2G CB-F-1A-A EDE-MM-120 Electrical

Penetration H44 C-F-2-Z, ET-F-1A-A 20 FW-LT-4330 RC-E-11C Steam Generator Wide Range Level Transmitter FW-20686 A 310577 C-F-1-Z X X X - R1P FW-LQY-4330 I/E Converter G2H CB-F-1A-A H45-R1P G2H-H45 E1S-G2H 17 G81d E1S/4 EH9/2 CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 EDE-PP-11E FW-LT-4320 FW-LT-4340 FW-LI-4330 Level Indicator G2G CB-F-1A-A FW-LR-4310 Level Recorder G2G CB-F-1A-A EDE-MM-121 Electrical Penetration H45 C-F-2-Z, ET-F-1A-A 21 MS-PT-3173 RC-E-11A Steam Generator Header Pressure Transmitter MS-20580 A 310589 MS-F-1B-Z X X X - GL6 MS-PQY-3173 I/E Converter G2H CB-F-1A-A G2H-GL6 13 G81d CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 MS-PT-3174 MS-PT-3179 MS-PI-3173 Press. Indicator G2G CB-F-1A-A 22 MS-PT-3178 RC-E-11C Steam Generator Header Pressure Transmitter MS-20581 A 310586 MS-F-1A-Z X X X - GL5 MS-PQY-3178 I/E Converter G2H CB-F-1A-A G2H-GL5/1 13 G81d CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 MS-PT-3174 MS-PT-3179 MS-PI-3178 Press. Indicator G2G CB-F-1A-A 23 RC-LT-7334 RC-E-10 Pressurizer Level Transmitter RC-20846 A 310579 C-F-2-Z X X X - GK5 RC-LQY-7334 I/E Converter G81 CB-F-1A-A H45-PR9 G81-H45 E1S-G2H 6 G81a E1S/4 EH9/2 CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 EDE-PP-11E RC-LT-7333 RC-LI-7334 Level Indicator G81 CB-F-1A-A RC-LR-7334 Level Recorder G81 CB-F-1A-A EDE-MM-121 Electrical Penetration H45 C-F-2-Z, ET-F-1A-A 24 RC-PT-7336 RC-E-10 Pressurizer Pressure Transmitter RC-20846 A 310579 C-F-2-Z X X X - GK5 RC-PQY-7336 I/E Converter G2H CB-F-1A-A H45-PR9/1 G2H-H45/1 12 G81d CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 RC-PT-7335 RC-PI-7336 Press. Indicator G81 CB-F-1A-A EDE-MM-121 Electrical Penetration H45 C-F-2-Z, ET-F-1A-A 25 RC-TE-9406 Reactor Coolant Loop 1 Wide Range Hot Leg Temperature Element RC-20841 A 310582 C-F-1-Z X X X - TS6 RC-TY-9406 R/E Converter G81 CB-F-1A-A H44-TS6 G81-H44 E1S-G2H FP 71336 310952 3 G81a E1S/4 EH9/2 CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 EDE-PP-11E RC-TE-9407 RC-TI-9406 Temp. Indicator G81 CB-F-1A-A RC-TR-9406 Temp. Recorder G81 CB-F-1A-A EDE-MM-120 Electrical Penetration H44 C-F-2-Z, ET-F-1A-A 26 RC-TE-9410 Reactor Coolant Loop 1 Wide Range Cold Leg Temperature Element RC-20841 A 310582 C-F-1-Z X X X - T3D RC-TY-9410 R/E Converter G81 CB-F-1A-A H44-T3D G81-H44/1 E1S-G2H 3 G81a E1S/4 EH9/2 CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 EDE-PP-11E RC-TE-9411 RC-TI-9410 Temp. Indicator G81 CB-F-1A-A RC-TR-9406 Temp. Recorder G81 CB-F-1A-A EDE-MM-120 Electrical Penetration H44 C-F-2-Z, ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 4 Table RSS 3.1.3.4 -4 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 27 CS-LT-7446 Boric Acid Tank CS-TK-4A Level Transmitter CS-20729 A 310766 PAB-F-2B-Z - X X - RJ8 CS-LSY-7446 Comparator G2H CB-F-1A-A G2H-RJ8 G81d CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 CS-LT-7464 CS-LQY-7446 I/E Converter G2H CB-F-1A-A CS-LI-7446 Level Indicator G2H CB-F-1A-A 28 MM-UQ-5866 Remote Shutdown Panel MM-CP-108A Power Supply

- A 310442 CB-F-1A-A X X X - G2G VI-G2G-FU9 20A Fuse G2G CB-F-1A-A EH9-G2G M-310952 EH9/2 EH9/2 CBA-FN-19 CBA-FN-20 EDE-PP-1E MM-UQ-5868             VI-G2G-FU10 20A Fuse G2G CB-F-1A-A    29 MM-UQ-5867 Remote Shutdown Panel MM-CP-108A Power Supply
- A 310442 CB-F-1A-A X X X - G2G VI-G2G-FU11 20A Fuse G2G CB-F-1A-A EH9-G2G EH9/2 EH9/2 CBA-FN-19 CBA-FN-20 EDE-PP-1E MM-UQ-5869             VI-G2G-FU12 20A Fuse G2G CB-F-1A-A     30 NOT USED                    31 NI-NE-6690 Intermediate Range Thermal Neutron Flux Monitoring Detector - A 310565 C-F-1-Z X X X - QO5 NI-E1S/13-52 120 V ac Circuit Breaker E1S CB-F-1A-A H40-XP8 H40-KDO KDO-QC1 QC1-QI0 G2H-QC1 QO5-XP8 E1S-KDO E1S-QC1 E1S-QI0 310943 E1S/13a E1S/13b CBA-FN-19 CBA-FN-20 EDE-PP-11E NI-NE-6691             NI-E1S/14-52 120 V ac Circuit Breaker E1S CB-F-1A-A              NI-E1S/15-52 120 V ac Circuit Breaker E1S CB-F-1A-A                 NI-NI-6690-3&4 Excore Wide Range Thermal Neutron Flux Indicators G2H CB-F-1A-A                 NI-NT-6690 Excore Wide Range Transmitters KDO ET-F-1A-A                  NI-NM-6690 Excore Wide Range Signal Processor QC1 CB-F-1A-A                  NI-NM-6690J Excore Wide Range Signal Processor Expansion Box QI0 CB-F-1A-A                  EDE-TBX-XP8 Junction Box XP8 C-F-1-Z                  EDE-MM-116 Electrical Penetration H40 C-F-2-Z, ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 4 Table RSS 3.1.3.4

-5 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 32 NI-NE-6691 Intermediate Range Thermal Neutron Flux Monitoring Detector - B 310565 C-F-1-Z X X X - QO7 NI-EIT/13-52 120 V ac Circuit Breaker E1T CB-F-1B-A H21-XP9 H21-KD1 KD1-QDO QDO-QJ1 G2K-QDO QO7-XP9 E1T-KD1 E1T-QDO E1T-QJ1 310943 E1T/13a E1T/13b CBA-FN-32 CBA-FN-33 EDE-PP-11F NI-NE-6690 NI-E1T/14-52 120 V ac Circuit Breaker E1T CB-F-1B-A NI-E1T/15-52 120 V ac Circuit Breaker E1T CB-F-1B-A NI-NI-6691-3&4 Excore Wide Range Thermal Neutron Flux Indicators G2K CB-F-1B-A NI-NT-6691 Excore Wide Range Transmitters KD1 ET-F-1C-A NI-NM-6691 Excore Wide Range Signal Processor QDO CB-F-1B-A NI-NM-6691J Excore Wide Range Signal Processor Expansion Box QJ1 CB-F-1B-A EDE-TBX-XP9 Junction Box XP9 C-F-1-Z EDE-MM-97 Electrical Penetration H21 C-F-1-Z, ET-F-1C-A 33 CO-LISL-4052 Condensate Storage Tank Level Indicator C0-20426 A/B 310248 509066 CST-F-1 X - - R10 - - - - - - - - - Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.5-1 FUNCTION: SAFGEGUARDS ACTUATION PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 MM-CP-12 - A 310501 CB-F-3A-A X X X - FF8 PSC-E01/11-52 120 V ac Circuit Breaker E01 CB-F-1A-A - - - None Note 1 Solid State

Protection System

Cabinet (Train A

Load Group) MM-SS-5807 Selector Switch G5X DG-F-2A-A CBA-FN-19

CBA-FN-20 DAH-FN-25A

DAH-FN-26A 2 MM-CP-13 - B 310501 CB-F-3A-A X X X - FF9 PSC-E02/11-52 120 V ac Circuit Breaker E02 CB-F-1B-A - - - None Note 1 Solid State

Protection System

Cabinet (Train B

Load Group) MM-SS-5808 Selector Switch G5Y DG-F-2B-A CBA-FN-32

CBA-FN-33 DAH-FN-25B

DAH-FN-26B

.Notes   1. The Solid State Protection Cabinet will be disabled at the appropriate location to prevent the output from initiating spurious operation of various valves and pumps. 

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -1 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 RH-P-8A Residual Heat Removal Pump SI-20448 A 310761 RHR-F-1D-Z - X X - M11 RH-A57-52 4160 V ac Circuit Breaker A57 CB-F-1A-A A57-M11 310887 A57a A57g A57b A57c A57d CBA-FN-19 CBA-FN-20 EAH-FN-5A EAH-FN-31A EDE-SWG-5 RH-P-8B RHR-A57-FU Fuses A57 CB-F-1A-A RH-CS-2467-2 Control Switch A57 CB-F-1A-A RH-SS-2467 Selector Switch A57 CB-F-1A-A EDE-A53-94-1A Bus Under Voltage Relay A53 CB-F-1A-A RH-A57-G,R,W Indicating Lights A57 CB-F-1A-A RH-A57-86 Lockout Relay A57 CB-F-1A-A RH-A57-52H Truck Operated Contact A57 CB-F-1A-A RH-A57-50/51 Inst/Time Overcurrent Relays øA, øC A57 CB-F-1A-A RH-A57-51GS Ground Sensor Relay A57 CB-F-1A-A RH-A57-AM Ammeter A57 CB-F-1A-A RH-A57-AS Ammeter Switch A57 CB-F-1A-A RH-A57-CT Current Transformers (75/5) A57 CB-F-1A-A RH-A57-TD1 CT Test Device A57 CB-F-1A-A RH-A57-ATR Transducer A57 CB-F-1A-A RH-A57-TD2 Lockout Relay Test Device A57 CB-F-1A-A RH-A57-52Z Time Delay Relay A57 CB-F-1A-A

.Notes   1. This equipment is mechanical with no electrical requirements.
2. During normal operation, the valve is in its safe shutdown position.

To prevent spurious operation, this equipment will be disabled at the appropriate control location. 3. Not used.

4. Air is not needed to position or to reposition the valve for safe shutdown.
5. The valve will be operated manually utilizing handwheels.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -2 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 RH-P-8B Residual Heat Removal Pump RH-20663 B 310761 RHR-F-1C-Z - X X - M12 RH-A77-52 4160 V ac Circuit Breaker A77 CB-F-1B-A A77-M12 A77a A77g A77b A77c A77d CBA-FN-32 CBA-FN-33 EAH-FN-5B EAH-FN-31B EDE-SWG-6 RH-P-8A RHR-A77-FU Fuses A77 CB-F-1B-A RH-CS-2468-2 Control Switch A77 CB-F-1B-A RH-SS-2468 Selector Switch A77 CB-F-1B-A EDE-A73-94-1A Bus Under Voltage Relay A73 CB-F-1B-A RH-A77-G,R,W Indicating Lights A77 CB-F-1B-A RH-A77-86 Lockout Relay A77 CB-F-1B-A RH-A77-52H Truck Operated Contact A77 CB-F-1B-A RH-A77-50/51 Inst/Time Overcurrent Relays øA, øC A77 CB-F-1B-A RH-A77-51GS Ground Sensor Relay A77 CB-F-1B-A RH-A77-AM Ammeter A77 CB-F-1B-A RH-A77-AS Ammeter Switch A77 CB-F-1B-A RH-A77-CT Current Transformers (75/5) A77 CB-F-1B-A RH-A77-TD1 CT Test Device A77 CB-F-1B-A RH-A77-ATR Transducer A77 CB-F-1B-A RH-A77-TD2 Lockout Relay Test Device A77 CB-F-1B-A RH-A77-52Z Time Delay Relay A77 CB-F-1B-A 3 RH-V-14 RH-P-8A to Cold Leg Isolation Valve RH-20662 A 310769 PP-F-1A-Z - X X - V47 RH-B57-52 460 V ac Circuit Breaker B57 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 RH-V-26 Note 2 4 RH-V-26 RH-P-8B to Cold Leg Isolation Valve RH-20663 B 310769 PP-F-1B-Z - X X - V48 RH-B65-52 460 V ac Circuit Breaker B65 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 RH-V-14 Note 2 5 RH-V-35 RH-E-9A to Charging Pump Isolation Valve RH-20662 A 310761 RHR-F-4B-Z - X X - V53 RH-B59-52 460 V ac Circuit Breaker B59 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 2 6 RH-V-36 RH-E-9B to SI Pump Isolation Valve SI-20449 B 310761 RHR-F-2A-Z - X X - V54 RH-B66-52 460 V ac Circuit Breaker B66 CBA-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 2 7 RH-V-32 RHR PP to Hot Leg Isolation Valve RH-20663 B 310769 PP-F-1A-Z - X X - V51 RH-B58-52 460 V ac Circuit Breaker B58 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 2 8 RH-V-70 RHR to Hot Leg Isolation Valve RH-20663 A 310769 PP-F-1A-Z - X X - VB4 RH-D90-52 460 V ac Circuit Breaker D90 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 2 9 RH-HCV-606 RH-E-9A Outlet Flow Control Valve RH-20662 A 310761 RHR-F-4B-Z - X X X LG8 EDE-E87/2-72 125 V dc Circuit E87 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 RH-HCV-607 Notes 2 and 4 10 RH-HCV-607 RH-E-9B Outlet Flow Control Valve RH-20663 B 310761 RHR-F-4A-Z - X X X LG9 EDE-E88/2-72 125 V dc Circuit Breaker E88 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 RH-HCV-606 Notes 2 and 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -3 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 RH-FCV-618 RH-E-9A Outlet Bypass Flow Control Valve RH-20662 A 310761 RHR-F-4B-Z - X X X LH3 EDE-E87/2-72 125 V dc Circuit Breaker E87 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 RH-FCV-619 Notes 2 and 4 12 RH-FCV-619 RH-E-9B Outlet Bypass Flow Control Valve RH-20663 B 310761 RHR-F-4A-Z - X X X LH4 EDE-E88/2-72 125 V dc Circuit Breaker E88 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 RH-FCV-618 Notes 2 and 4 13 RH-V-8 RHR Loop A Sample Valve RH-20662 A 310761 805201 RHR-F-4B-Z - X - - - - - - - - - - EAH-FN-5A EAH-FN-31A RH-V-44 Notes 1 and 9 14 RH-V-44 RHR Loop B Sample Valve RH-20663 B 310761 805201 RHR-F-4A-Z - X - - - - - - - - - - EAH-FN-5B EAH-FN-31B RH-V-8 Notes 1 and 9 Notes 6. Electrical conduit plan drawing 9763 -F-310761 is listed to show fire zone corresponding to the location of the RHR pump oil cooler which is identified in drawing 9763-F-805020. 7. Electrical conduit plan drawings 9763 -F-310761 and 9763 -F-310762 are listed to show fire zone corresponding to the location of the RHR heat exchanger which is identified in drawings 9763 -F-805202 and 9763 -F-805203. 8. During normal operation, the valve is in its hot shutdown position. To prevent spurious operation, this equipment will be disabled at the appropriate control location. For cold shutdown, the valve will be energized for positioning.

9. Electrical conduit plan drawing 9763

-F-310761 is listed corresponding to the location of the RHR sampling valve which is identified in drawing 9763 -F-805201. 10. These valves are also listed in Table RSS 3.1.3.2.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -4 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 RC-V-22 RHR Inlet Isolation Valve RC-20841 B 310582 C-F-1-Z - X X - V27 RC-B54-52-1,2 460 V ac Circuit Breakers B54 CB-F-1B-A B54-G2J B54-G2J/1 B54-H39 B54-H24 H24-V27 H39-V27 310882 B54a B54c EDE-MCC-621 CBA-FN-32 CBA-FN-33 RC-V-88 Notes 8 and 10 RC-B54-FU Fuse B54 CB-F-1B-A RC-CS-7302-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7302 Selector Switch G2J CB-F-1B-A RC-B54-42-1/0,C Motor Starters B54 CB-F-1B-A RC-B54-42-2 Motor Starter B54 CB-F-1B-A RC-B54-49-1,2 Overload Relays B54 CB-F-1B-A EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A RC-ZS-7302B Valve Position and Open/Close Torque Switches V27 C-F-1-Z RC-ZL-7302-1 Pilot Light G2J CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-EHO/16-52 120 V ac Circuit Breaker EHO CB-F-1B-A E4J-EH0/1 E4J-G2J GJ2-H39/6 H39-V27/1 H39-V26/3 GZ0-U8U ED0-GZ0/1 EHO/16a EHO/16c EHO/16b EHO/16d EDE-PP-1F CBA-FN-32 CBA-FN-33 RC-CS-7302-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7302 Selector Switch G2J CB-F-1B-A RC-ZS-7302B Valve Position and Open/Close Torque Switches V27 C-F-1-Z RC-E4J-FU-9 and 10 30 Amp Fuses E4J CB-F-1B-A EDE-MM-115 Electrical Penetration H39 ET-F-1C-A, C-F-1-Z RC-CS-7310-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7310 Selector Switch G2J CB-F-1B-A RC-ZS-V87 Valve Position and Open/Close Torque Switches V26 C-F-1-Z RC-CS-2896-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-2896 Selector Switch GZ0 CB-F-1B-A RC-ZS-FV-2896 Valve Position Switch U8U PP-F-1B-Z RC-EDO-R1, R2 Auxiliary Relay ED0 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -5 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 16 RC-V-23 RHR Inlet Isolation Valve RC-20841 A 310576 C-F-1-Z - X X - V25 RC-B53-52-1,2 460 V ac Circuit Breakers B53 CB-F-1A-A B53-G2G B53-G2G/1 B53-H36 B53-H19 H36-V25/2 H19-V25 B53a B53c EDE-MCC-521 CBA-FN-19 CBA-FN-20 RC-V-87 Notes 8 and 10 RC-B53-FU Fuse B53 CB-F-1A-A RC-CS-7303-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7303 Selector Switch G2G CB-F-1A-A RC-ZL-7303-1 Pilot Light G2G CB-F-1A-A RC-B53-42-1/0,C Motor Starters B53 CB-F-1A-A RC-B53-42-2 Motor Starter B53 CB-F-1A-A RC-B53-49-1,2 Overload Relays B53 CB-F-1A-A EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A RC-ZS-V23 Valve Position and Open/Close Torque Switches V25 C-F-1-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-EH9/16-52 120 V ac Circuit Breaker EH9 CB-F-1A-A E4H-EH9/1 E4H-G2G G2G-H36/8 H36-V25/3 H36-V28/1 G81-U8T EC8-G81 EC8-G81/1 310882 EH9/16a EH9/16c EH9/16b EH9/16d EDE-PP-1E CBA-FN-19 CBA-FN-20 RC-CS-7303-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7303 Selector Switch G2G CB-F-1A-A RC-ZS-V23 Valve Position and Open/Close Torque Switches V25 C-F-1-Z EDE-MM-112 Electrical Penetration H36 ET-F-1A-A and C-F-2-Z RC-E4H-FU-9 and 10 30 Amp Fuses E4H CB-F-1A-A RC-CS-7311-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7311 Selector Switch G2G CB-F-1A-A RC-ZS-7311A Valve Position and Open/Close Torque Switches V28 C-F-1-Z RC-CS-2894-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-2894 Selector Switch G81 CB-F-1A-A RC-ZS-FV-2894 Valve Position Switch U8T PP-F-1B-Z RC-EC8-R1, R2 Auxiliary Relay EC8 CB-F-1A-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -6 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 17 RC-V-87 RHR Inlet Isolation Valve RC-20844 B 310582 C-F-1-Z - X X - V26 RC-B61-52-1,2 460 V ac Circuit Breaker B61 CB-F-1B-A B61-G2J B61-G2J/1 B61-H39 B61-H24 H39-V26/2 H24-V26 B61a B61c EDE-MCC-621 CBA-FN-32 CBA-FN-33 RC-V-23 Notes 8 and 10 RC-B61-FU Fuse B61 CB-F-1B-A RC-CS-7310-2 Control Switch with Indicator G2J CB-F-1B-A RC-SS-7310 Selector Switch G2J CB-F-1B-A RC-ZL-7310-1 Pilot Light G2J CB-F-1B-A RC-B61-42-1/0,C Motor Starters B61 CB-F-1B-A RC-B61-42-2 Motor Starter B61 CB-F-1B-A RC-B61-49-1,2 Overload Relays B61 CB-F-1B-A RC-ZS-V87 Valve Position and Open/Close Torque Switches V26 C-F-1Z-A EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-EH0/16-52 120 V ac Circuit Breaker EHO CB-F-1B-A E4J-EH0/1 E4J-G2J G2J-H39/6 H39-V26/3 GZ0-U8U EDO-GZ0/1 H39-V27/1 EHO/16a EHO/16c EHO/16b EHO/16d EDE-PP-1F CBA-FN-32 CBA-FN-33 RC-CS-7310-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7310 Selector Switch G2J CB-F-1B-A RC-ZS-V87 Valve Position and Open/Close Torque Switches V26 C-F-1-Z EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-E4J-FU-9 and 10 30 Amp Fuses E4J CB-F-1B-A RC-CS-7302-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7302 Selector Switch G2J CB-F-1B-A RC-ZS-7302B Valve Position and Open/Close Torque Switches V27 C-F-1-Z RC-CS-2896-2 Control Switch with Indication GZO CB-F-1B-A RC-SS-2896 Selector Switch GZO CB-F-1B-A RC-ZS-FV-2896 Valve Position Switch U8U PP-F-1B-Z RC-ED0-R1, R2 Auxiliary Relay ED0 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -7 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 RC-V-88 RHR Inlet Isolation Valve RH-20662 A 310577 C-F-1-Z - X X - V28 RC-B62-52-1,2 460 V ac Circuit Breaker B62 CB-F-1A-A B62-G2G B62-G2G/1 B62-H36 B62-H19 H36-V28 H19-V28 310882 B62a B62c EDE-MCC-521 CBA-FN-19 CBA-FN-20 RC-V-22 Notes 8 and 10 RC-B62-FU Fuse B62 CB-F-1A-A RC-CS-7311-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7311 Selector Switch G2G CB-F-1A-A RC-ZL-7311-1 Pilot Light G2G CB-F-1A-A RC-B62-42-1/0,C Motor Starters B62 CB-F-1A-A RC-B62-42-2 Motor Starter B62 CB-F-1A-A RC-B62-49-1,2 Overload Relays B62 CB-F-1A-A RC-ZS-7311A Valve Position and Open/Close Torque Switches V28 C-F-1-Z EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-EH9/16-52 120 V ac Circuit Breaker EH9 CB-F-1A-A E4H-EH9/1 E4H-G2G G2G-H36/8 H36-V28/1 H36-V25/3 G81-U8T EC8-G81 EC8-G81/1 EH9/16a EH9/16c EH9/16b EH9/16d EDE-PP-1E CBA-FN-19 CBA-FN-20 RC-CS-7311-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7311 Selector Switch G2G CB-F-1A-A RC-ZS-7311A Valve Position and Open/Close Torque Switches V28 C-F-1-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-E4H-FU-9 and 10 30 Amp Fuse s E4H CB-F-1A-A RC-CS-7303-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7303 Selector Switch G2G CB-F-1A-A RC-ZS-V23 Valve Position and Open/Close Torque Switches V25 C-F-1-Z RC-CS-2894-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-2894 Selector Switch G81 CB-F-1A-A RC-ZS-FV-2894 Valve Position Switch U8T PP-F-1B-Z RC-EC8-R1, R2 Auxiliary Relay EC8 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -8 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 RH-P-8A RHR Pump Lube Oil Cooler RH-20662 A 310761 805200 RHR-F-1D-Z - X - - - - - - - - - - Component Cooling RH-P-8B Notes 1 and 6 20 RH-P-8B RHR Pump Lube Oil Cooler RH-20663 B 310761 805200 RHR-F-1C-Z - X - - - - - - - - - - Component Cooling RH-P-8A Notes 1 and 6 21 RH-E-9A Residual Heat Removal Heat Exchanger SI-20448 A 310761 310762 805202 805203 RHR-F-3B-Z - X - - - - - - - - - - Component Cooling RH-E-9B Notes 1 and 7 22 RH-E-9B Residual Heat Removal Heat Exchanger RH-20663 B 310761 310762 805202 805203 RHR-F-3A-Z - X - - - - - - - - - - Component Cooling RH-E-9A Notes 1 and 7 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.7-1 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 SW-P-41A SW-20794 A 301140 SW-F-1E-Z X X X - N81 SW-AQ3-52 4160 V AC Circuit Breaker AQ3 CB-F-1A-A Service Water

Loop "A" -

Pump "A" SW-AQ3-FU Fuses AQ3 CB-F-1A-A SW-CS-6101-2 Control Switch AQ3 CB-F-1A-A CBA-FN-19

CBA-FN-20

EDE-SWG-5 SW-P-41B or SW-P-41D SW-SS-6101 Selector Switch AQ3 CB-F-1A-A AQ3-GN9 AQ3-VL3 AQ3-N81 301107 AQ3a AQ3h AQ3b AQ3c AQ3d SW-ZS-V2 Valve Position Switch VL3 SW-F-1E-Z EDE-A53-94-2 Bus Undervoltage Relay A53 CB-F-1A-A SW-AQ3-52H Truck Operated Contact AQ3 CB-F-1A-A SW-AQ3-50/51 Inst/Time Overcurrent Relays øA, øC AQ3 CB-F-1A-A SW-AQ3-51GS Ground Sensor Relay AQ3 CB-F-1A-A SW-AQ3-86 Lockout Relay AQ3 CB-F-1A-A SW-AQ3-CT Current Transformers 100/5A AQ3 CB-F-1A-A SW-AQ3-TD1 Test Device AQ3 CB-F-1A-A SW-AQ3-AM Ammeter AQ3 CB-F-1A-A SW-AQ3-AS Ammeter Switch AQ3 CB-F-1A-A SW-AQ3-G,R,W Indicating Lights AQ3 CB-F-1A-A SW-AQ3-ATR Transducer AQ3 CB-F-1A-A SW-AQ3-TD2 Lockout Relay Test Device AQ3 CB-F-1A-A SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A SW-AQ3-52Z Time Delay Relay AQ3 CB-F-1A-A SW-AQ3-R1 Auxiliary Relay AQ3 CB-F-1A-A SW-ZS-V54 Valve Position Switch and Valve Open/Close

Torque Switches VM5 CT-F-2B-A GN9-VM5 E2T/1a E2T/1b CBA-FN-19

CBA-FN-20 Notes 4 and 5 SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A

.Notes  1. During normal operation, this equipment is in its safe shutdown position. To prevent spurious operation, this equipment will be disabled or isolated at the appropriate control locations. 
2. Air is not needed to position or to reposition the valve for safe shutdown.
3. This valve will be de-energized to cause it to fail to its safe shutdown position.
4. Circuit shown in 301107, Sheet E2T/1a, involving Auxiliary Relay SW-GN9-RV54 of SW-P-41A also affects SW-P-41C.
5. Circuit shown in 301107, Sheet E2U/1a, involving Auxiliary Relay SW-GN0-RV25 of SW-P-41B also affects SW-P-41D.
6. Electrical power not required for support.
7. The equipment is permanently disabled.
8. During normal operation, this equipment is in its safe shutdown position with its circuit breaker administratively controlled off to prevent its spurious operation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.7-2 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 SW-P-41B SW-20794 B 301140 SW-F-1E-Z X X X - N82 SW-AR3-52 4160 V AC Circuit Breaker AR3 CB-F-1B-A Service Water

Loop "B" -

Pump "B" SW-AR3-FU Fuses AR3 CB-F-1B-A SW-P-41A or SW-P-41C SW-CS-6111-2 Control Switch AR3 CB-F-1B-A AR3-GN0 AR3-VL4 AR3-N82 301107 AR3a AR3h AR3b AR3c AR3d CBA-FN-32

CBA-FN-33

EDE-SWG-6 SW-SS-6111 Selector Switch AR3 CB-F-1B-A SW-ZS-V29 Valve Position Switch VL4 SW-F-1E-Z EDE-A73-94-2 Bus Undervoltage Relay A73 CB-F-1B-A SW-AR3-52H Truck Operated Contact AR3 CB-F-1B-A SW-AR3-50/51 Inst/Time Overcurrent Relays øA, øC AR3 CB-F-1B-A SW-AR3-51GS Ground Sensor Relay AR3 CB-F-1B-A SW-AR3-86 Lockout Relay AR3 CB-F-1B-A SW-AR3-CT Current Transformers 100/5A AR3 CB-F-1B-A SW-AR3-TD1 Test Device AR3 CB-F-1B-A SW-AR3-AM Ammeter AR3 CB-F-1B-A SW-AR3-AS Ammeter Switch AR3 CB-F-1B-A SW-AR3-G,R,W Indicating Lights AR3 CB-F-1B-A SW-AR3-ATR Transducer AR3 CB-F-1B-A SW-AR3-TD2 Lockout Relay Test Device AR3 CB-F-1B-A SW-GN0-RV25 Auxiliary Relay GN0 CB-F-1B-A SW-AR3-52Z Time Delay Relay AR3 CB-F-1B-A SW-AR3-R1 Auxiliary Relay AR3 CB-F-1B-A SW-ZS-V25 Valve Position Switch and Valve Open/Close

Torque Switches VM8 CT-F-2B-A GN0-VM8 E2U/1a E2U/1b CBA-FN-32

CBA-FN-33 Notes 5 and 6 SW-GN0-RV25 Auxiliary Relay GN0 CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.7-3 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 SW-P-41C SW-20794 A 301140 SW-F-1E-Z X X X - N83 SW-AQ4-52 4160 V AC Circuit Breaker AQ4 CB-F-1A-A Note 4 Service Water

Loop "A" -

Pump "C" SW-AQ4-FU Fuses AQ4 CB-F-1A-A AQ4-GN9 AQ4-VL5 AQ4-N83 SW-P-41B or SW-P-41D SW-CS-6102-2 Control Switch AQ4 CB-F-1A-A CBA-FN-19

CBA-FN-20

EDE-SWG-5 SW-SS-6102 Selector Switch AQ4 CB-F-1A-A 301107 AQ4a AQ4h AQ4b AQ4c AQ4d SW-ZS-V22 Valve Position Switch VL5 SW-F-1E-Z EDE-A53-94-2 Bus Undervoltage Relay A53 CB-F-1A-A SW-AQ4-52H Truck Operated Contact AQ4 CB-F-1A-A SW-AQ4-50/51 Inst/Time Overcurrent Relays øA, øC AQ4 CB-F-1A-A SW-AQ4-51GS Ground Sensor Relay AQ4 CB-F-1A-A SW-AQ4-86 Lockout Relay AQ4 CB-F-1A-A SW-AQ4-CT Current Transformers 100/5A AQ4 CB-F-1A-A SW-AQ4-TD1 Test Device AQ4 CB-F-1A-A SW-AQ4-AM Ammeter AQ4 CB-F-1A-A SW-AQ4-AS Ammeter Switch AQ4 CB-F-1A-A SW-AQ4-G,R,W Indicating Lights AQ4 CB-F-1A-A SW-AQ4-ATR Transducer AQ4 CB-F-1A-A SW-AQ4-TD2 Lockout Relay Test Device AQ4 CB-F-1A-A SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A SW-AQ4-52Z Time Delay Relay AQ4 CB-F-1A-A SW-AQ4-R1 Auxiliary Relay AQ4 CB-F-1A-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.7-4 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 SW-P-41D SW-20794 B 301140 SW-F-1E-Z X X X - N84 SW-AR4-52 4160 V AC Circuit Breaker AR4 CB-F-1B-A Note 5 Service Water

Loop "B" -

Pump "D" SW-AR4-FU Fuses AR4 CB-F-1B-A AR4-GN0 AR4-VL6 AR4-N84 CBA-FN-32

CBA-FN-33

EDE-SWG-6 SW-P-41A or SW-P-41C SW-CS-6112-2 Control Switch AR4 CB-F-1B-A SW-SS-6112 Selector Switch AR4 CB-F-1B-A 301107 AR4a AR4h AR4b AR4c AR4d SW-ZS-V31 Valve Position Switch VL6 SW-F-1E-Z EDE-A73-94-2 Bus Undervoltage Relay A73 CB-F-1B-A SW-AR4-52H Truck Operated Contact AR4 CB-F-1B-A SW-AR4-50/51 Inst/Time Overcurrent Relays øA, øC AR4 CB-F-1B-A SW-AR4-51GS Ground Sensor Relay AR4 CB-F-1B-A SW-AR4-86 Lockout Relay AR4 CB-F-1B-A SW-AR4-CT Current Transformer 100/5A AR4 CB-F-1B-A SW-AR4-TD1 Test Device AR4 CB-F-1B-A SW-AR4-AM Ammeter AR4 CB-F-1B-A SW-AR4-AS Ammeter Switch AR4 CB-F-1B-A SW-AR4-G,R,W Indicating Lights AR4 CB-F-1B-A SW-AR4-ATR Transducer AR4 CB-F-1B-A SW-AR4-TD2 Lockout Relay Test Device AR4 CB-F-1B-A SW-GN0-RV25 Auxiliary Relay GN0 CB-F-1B-A SW-AR4-52Z Time Delay Relay AR4 CB-F-1B-A SW-AR4-R1 Auxiliary Relay AR4 CB-F-1B-A SW-AR4-R2 Auxiliary Relay AR4 CB-F-1B-A 5 SW-V2 SW-20794 A 301140 SW-F-1E-Z X X X - VL3 SW-CR6-52 460 V AC Circuit Breaker CR6 SW-F-1B-A 301107 CR6a CR6c SWA-FN-40A EDE-MCC-514 Service Water

Pump "A"

Discharge Valve SW-AQ3-52S Mechanically Operated Contact AQ3 CB-F-1A-A AQ3-CR6 CR6-VL3/1 CR6-VL3 SW-V-29 or SW-V-31 SW-ZS-V2 Valve Position Switch and Valve Open/Close

Torque Switches VL3 SW-F-1E-Z SW-CR6-42/0,C Motor Starters CR6 SW-F-1B-A SW-CR6-49 Overload Relay CR6 SW-F-1B-A SW-CR6-FU Fuses CR6 SW-F-1B-A SW-ECO-TDR Time Delay Relay ECO SW-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.7-5 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 SW-V22 SW-20794 A 301140 SW-F-1E-Z X X X - VL5 SW-CR7-52 460 V AC Circuit Breaker CR7 SW-F-1B-A 301107 CR7a CR7c SWA-FN-40A EDE-MCC-514 Service Water

Pump "C"

Discharge Valve SW-AQ4-52S Mechanically Operated Contact AQ4 CB-F-1A-A AQ4-CR7 CR7-VL5/1 CR7-VL5 SW-V-29 or SW-V-31 SW-ZS-V22 Valve Position Switch and Valve Open/Close

Torque Switches VL5 SW-F-1E-Z SW-CR7-42/0,C Motor Starters CR7 SW-F-1B-A SW-CR7-49 Overload Relay CR7 SW-F-1B-A SW-CR7-FU Fuses CR7 SW-F-1B-A SW-ECO-TDR Time Delay Relay ECO SW-F-1B-A 7 SW-V29 SW-20794 B 301140 SW-F-1E-Z X X X - VL4 SW-CS1-52 460 V AC Circuit Breaker CS1 SW-F-1C-A 301107 CS1a CS1c SWA-FN-40B EDE-MCC-614 Service Water

Pump "B"

Discharge Valve SW-AR3-52S Mechanically Operated Contact AR3 CB-F-1B-A AR3-CS1 CS1-VL4/1 CS1-VL4 SW-V-2 or SW-V-22 SW-ZS-V29 Valve Position Switch and Valve Open/Close

Torque Switches VL4 SW-F-1E-Z SW-CS1-42/0,C Motor Starters CS1 SW-F-1C-A SW-CS1-49 Overload Relay CS1 SW-F-1C-A SW-CS1-FU Fuses CS1 SW-F-1C-A SW-EE2-TDR Time Delay Relay EE2 SW-F-1C-A 8 SW-V31 SW-20794 B 301140 SW-F-1E-Z X X X - VL6 SW-CS2-52 460 V AC Circuit Breaker CS2 SW-F-1C-A 301107 CS2a CS2c SWA-FN-40B EDE-MCC-614 Service Water

Pump "D"

Discharge Valve SW-AR4-52S Mechanically Operated Contact AR4 CB-F-1B-A AR4-CS2 CS2-VL6/1 CS2-VL6 SW-V-2 or SW-V-22 SW-ZS-V31 Valve Position Switch and Valve Open/Close

Torque Switches VL6 SW-F-1E-Z SW-CS2-42/0,C Motor Starters CS2 SW-F-1C-A SW-CS2-49 Overload Relay CS2 SW-F-1C-A SW-CS2-FU Fuses CS2 SW-F-1C-A SW-EE2-TDR Time Delay Relay EE2 SW-F-1C-A 9 SW-V4 SW-20795 A 310767 PAB-F-1K-Z X X X - VP0 SW-DA6-52 460 V AC Circuit Breaker DA6 CB-F-1A-A SW-V5 SW-CS-6117-2 Control Switch with Indication G2H CB-F-1A-A 301107 DA6a DA6c DA6d CBA-FN-19

CBA-FN-20 EDE-MCC-512 Secondary

Component Cooling

Water Heat

Exchanger Header

Supply Valve SW-SS-6117 Selector Switch G2H CB-F-1A-A SW-DA6-42/0,C Motor Starters DA6 CB-F-1A-A DA6-VP0 DA6-G2H DA6-G2H/2 DA6-G2H/1 DA6-VP0/1 SW-DA6-49 Overload Relays DA6 CB-F-1A-A SW-ZS-V4 Valve Position Switch and Valve Open/Close

Torque Switches VP0 PAB-F-1K-Z SW-DA6-FU Fuse DA6 CB-F-1A-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.7-6 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 10 SW-V5 SW-20795 B 310767 PAB-F-1K-Z X X X - VQ1 SW-DA2-52 460 V AC Circuit Breaker DA2 CB-F-1B-A SW-V4 SW-CS-6137-2 Control Switch with Indication G2K CB-F-1B-A 301107 DA2a DA2c DA2d CBA-FN-32

CBA-FN-33 EDE-MCC-612 Secondary

Component Cooling

Water Heat

Exchanger Header

Supply Valve SW-SS-6137 Selector Switch G2K CB-F-1B-A SW-DA2-42/0,C Motor Starters DA2 CB-F-1B-A DA2-VQ1 DA2-G2K DA2-G2K/1 DA2-G2K/2 DA2-VQ1/1 SW-DA2-49 Overload Relays DA2 CB-F-1B-A SW-ZS-V5 Valve Position Switch and Valve Open/Close

Torque Switches VQ1 PAB-F-1K-Z SW-DA2-FU Fuse DA2 CB-F-1B-A 11 SW-V15 CC-E-17A Outlet Valve SW-20795 A 310767 PAB-F-3A-Z X X X - VN1 SW-DA7-52 460 V AC Circuit Breaker DA7 CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 SW-V17 Note 1 12 SW-V16 Diesel Generator "A" Water Jacket

Heat Exchanger

Solenoid-Operated

Valve SW-20795 A 310767 PAB-F-3A-Z X X X X UK6 EDE-E2T/2-72 125 V DC Circuit Breaker E2T CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 SW-V18 Notes 2 and 3 13 SW-V17 CC-E-17B Outlet Valve SW-20795 B 310767 PAB-F-3A-Z X X X - VN2 SW-DA3-52 460 V AC Circuit Breaker DA3 CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 SW-V15 Note 1 14 SW-V18 Diesel Generator "B" Water Jacket

Heat Exchanger

Solenoid-Operated

Valve SW-20795 B 310767 PAB-F-3A-Z X X X X UK7 EDE-E2U/2-72 125 V DC Circuit Breaker E2U CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 SW-V16 Notes 2 and 3 15 SW-V19 SW-20795 B 310765 PAB-F-2C-Z X X X - VN3 SW-DA4-52 460 V AC Circuit Breaker DA4 CB-F-1B-A SW-V20 Service Water

Discharge to Sea

Isolation Valve SW-CS-6172-1 Control Switch with Indication DA4 CB-F-1B-A DA4-VN3 DA4-VN3/1 DA4-VN3/2 DA4-GN0 DA4-E3Q 301107 DA4a DA4c CBA-FN-32

CBA-FN-33 EDE-MCC-612 SW-SS-8257 Selector Switch DA4 CB-F-1B-A SW-DA4-42/0,C Motor Starters DA4 CB-F-1B-A SW-DA4-49 Overload Relays DA4 CB-F-1B-A SW-ZS-V19 Valve Position Switch and Valve Open/Close

Torque Switches VN3 PAB-F-2C-Z SW-DA4-FU2/FU Fuse DA4 CB-F-1B-A SW-GN0-RTB-2 Auxiliary Relay GN0 CB-F-1B-A SW-DA4-R1 Auxiliary Relay E3Q CB-F-1B-A 16 SW-V20 Service Water Discharge to Sea

Isolation Valve SW-20795 A 310765 PAB-F-2C-Z X X X - VN4 SW-DA8-52 460 V AC Circuit Breaker DA8 CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 SW-V19 Note 1 17 SW-V23 Service Water to Cooling Tower

Isolation Valve SW-20795 B 310765 PAB-F-2C-Z X X X - VN5 SW-DA5-52 460 V AC Circuit Breaker DA5 CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 SW-V34 Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.7-7 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 SW-V25 SW-20794 B 310717 CT-F-2B-A X X X - VM8 SW-CQ7-52 460 V AC Circuit Breaker CQ7 CT-F-1C-A SW-V54 Notes 1 and 6 Cooling Tower

Pump Discharge

Valve SW-CS-6174-2 Control Switch with Indication G2K CB-F-1B-A 301107 CQ7a CQ7c CBA-FN-32

CBA-FN-33 SW-SS-6174 Selector Switch G2K CB-F-1B-A CQ7-G2K CQ7-VM8/1 CQ7-VM8/2 G2K-GNO/3 SW-CQ7-42/O,C Motor Starters CQ7 CT-F-1C-A SW-CQ7-49 Overload Relay CQ7 CT-F-1C-A SW-ZS-V25 Valve Position Switch and Valve Open/Close

Torque Switches VM8 CT-F-2B-A SW-GNO-RV25 Auxiliary Relay GNO CB-F-1B-A GNO-VM8 E2U/1a E2U/1b Note 6 SW-VM8-V25 Position Switch VM8 CT-F-2B-A CBA-FN-32

CBA-FN-33 SW-CQ7-R1 Auxiliary Relay EE7 CT-F-1C-A 19 SW-V34 Service Water to Cooling Tower

Outlet Valve SW-20795 A 310765 PAB-F-2C-Z X X X - VN6 SW-DA9-52 460 V ac Circuit Breaker DA9 CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 SW-V23 Note 1 20 SW-V44 Service Water Unit Pumps Intake

Valve SW-20794 A 301037 SW-F-2-0 X X X - VM1 SW-CU5-52 460 V ac Circuit Breaker CU5 SW-F-1B-A - - - None Note 7 21 SW-V54 SW-20794 A 301717 CT-F-2B-A X X X - VM5 SW-CP8-52 460 V ac Circuit Breaker CP8 CT-F-1D-A 310107 CP8a CP8c CBA-FN-19

CBA-FN-20 SW-V25 Notes 1 and 6 Cooling Tower

Pump Discharge

Valve SW-CS-6164-2 Control Switch with Indication G2H CB-F-1A-A CP8-G2H CP8-VM5 CP8-VM5/1 CP8-VM5/2 G2H-GN9/5 SW-SS-6164 Selector Switch G2H CB-F-1A-A SW-CP8-42/O,C Motor Starters CP8 CT-F-1D-A SW-CP8-49 Overload Relay CP8 CT-F-1D-A SW-ZS-V54 Valve Position Switch and Valve Open/Close

Torque Switches VM5 CT-F-2B-A SW-CP8-FU Fuse CP8 CT-F-1D-A SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A E2T/1a E2T/1b Note 6 SW-ZS-V54 Position Switch VM5 CT-F-2B-A GN9-VM5 CBA-FN-19

CBA-FN-20 22 SW-V63 Service Water Discharge Valve

to Intake SW-20794 A 301037 SW-F-2-0 X X X - VQ0 SW-DZ3-52 460 V AC Circuit Breaker DZ3 SW-F-1B-A - - - None Note 7 23 EDE-CP-248 Service Water Cooling Tower

Actuation Logic

(TA) - A 310442 CB-F-1A-A X X X - GN9 SW-E87/4-72 125 V DC Circuit Breaker E87 CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 EDE-CP-249 Note 1 24 EDE-CP-249 Service Water Cooling Water

Actuation Logic

(TA) - B 310442 CB-F-1B-A X X X - GNO SW-E88/4-72 125 V DC Circuit Breaker E88 CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 EDE-CP-248 Note 1

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-1 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CC-P-11A PCCW Loop "A" Pump "A" CC-20205 A 310765 PAB-F-2C-Z X X X - M05 CC-A58-52 4160 V AC Circuit Breaker A58 CB-F-1A-A A58-M05/1 CC-CS-2140-2 Control Switch A58 CB-F-1A-A CC-P-11B or CC-P-11D CC-SS-2140 Selector Switch A58 CB-F-1A-A 310895 A58a A58h A58b A58c A58d CBA-FN-19

CBA-FN-20 PAH-FN-42A EDE-SWG-5 EDE-A53-94-1A Bus Undervoltage Relay A53 CB-F-1A-A CC-A58-52H Truck-Operated Contact A58 CB-F-1A-A CC-A58-50/51 Instrument/Time Overcurrent Relays

øA, øC A58 CB-F-1A-A CC-A58-86 Lockout Relay A58 CB-F-1A-A CC-A58-AM Ammeter A58 CB-F-1A-A CC-A58-AS Ammeter Switch A58 CB-F-1A-A CC-A58-CT Current Transformer (150/5) A58 CB-F-1A-A CC-A58-TD1 CT Test Device A58 CB-F-1A-A CC-A58-ATR Transducer A58 CB-F-1A-A CC-A58-TD2 Lockout Relay Test Device A58 CB-F-1A-A CC-A58-FU Fuses A58 CB-F-1A-A CC-A58-52Z Timing Relay A58 CB-F-1A-A CC-A58-G,R,W Indicating Lights A58 CB-F-1A-A CC-A58-51GS Ground Sensor Relay A58 CB-F-1A-A CC-A59-52S Mechanical Operated Switch A59 CB-F-1A-A CC-A58-62 Time Delay Relay A58 CB-F-1A-A

.Notes  1. The equipment is mechanical with no electrical requirement. 
2. During normal operation, the valve is in its safe shutdown position. To prevent spurious operation, this equipment will be disabled at the appropriate control location.
3. Electrical Conduit Plan Drawing 310765 is listed only to show the fire zone corresponding to the location of the Heat Exchangers CC-E-17A and CC-E-17B as identified in Drawing 805217.
4. The valve will be operated locally using the handwheel when establishing RHR flow for the second phase of cooldown.
5. Electrical Conduit Plan Drawings 310581 is listed only to show the fire zone corresponding to the location of CC-TK-196 as identified in Drawing 805193.
6. Refer to Table 3.1.3-4 for MM-UQ-5866, MM-UQ-5867, MM-UQ-5868, and MM-UQ-5869.
7. These valves are in the open position with their circuit breakers locked open to prevent spurious operation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-2 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 CC-P-11B PCCW Loop "B" Pump "B" CC-20211 B 310765 PAB-F-2C-Z X X X - M06 CC-A78-52 4160 V AC Circuit Breaker A78 CB-F-1B-A A78-M06/1 CC-CS-2240-2 Control Switch A78 CB-F-1B-A CC-P-11A or CC-P-11C CC-SS-2240 Selector Switch A78 CB-F-1B-A 310895 A78a A78h A78b A78c A78d CBA-FN-32

CBA-FN-33 PAH-FN-42B EDE-SWG-6 EDE-A73-94-1A Bus Undervoltage Relay A73 CB-F-1B-A CC-A78-52H Truck-Operated Contact A78 CB-F-1B-A CC-A78-50/51 Instrument/Time Overcurrent Relays

øA, øC A78 CB-F-1B-A CC-A78-86 Lockout Relay A78 CB-F-1B-A CC-A78-AM Ammeter A78 CB-F-1B-A CC-A78-AS Ammeter Switch A78 CB-F-1B-A CC-A78-CT Current Transformer (150/5) A78 CB-F-1B-A CC-A78-TD1 CT Test Device A78 CB-F-1B-A CC-A78-ATR Transducer A78 CB-F-1B-A CC-A78-TD2 Lockout Relay Test Device A78 CB-F-1B-A CC-A78-FU Fuses A78 CB-F-1B-A CC-A78-52Z Timing Relay A78 CB-F-1B-A CC-A78-G,R,W Indicating Lights A78 CB-F-1B-A CC-A78-51GS Ground Sensor Relay A78 CB-F-1B-A CC-A79-52S Mechanical-Operated Switch A79 CB-F-1B-A CC-A78-62 Time Delay Relay A78 CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-3 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 CC-P-11C PCCW Loop "A" Pump "C" CC-20205 A 310766 PAB-F-2C-Z X X X - M07 CC-A59-52 4160 V AC Circuit Breaker A59 CB-F-1A-A A59-M07/1 CC-CS-2141-2 Control Switch A59 CB-F-1A-A CC-P-11B or CC-P-11D CC-SS-2141 Selector Switch A59 CB-F-1A-A 310895 A59a A59h A59b A59c A59d CBA-FN-19

CBA-FN-20 PAH-FN-42A EDE-SWG-5 EDE-A53-94-1A Bus Undervoltage Relay A53 CB-F-1A-A CC-A59-52H Truck-Operated Contact A59 CB-F-1A-A CC-A59-50/51 Instrument/Time Overcurrent Relays

øA, øC A59 CB-F-1A-A CC-A59-86 Lockout Relay A59 CB-F-1A-A CC-A59-AM Ammeter A59 CB-F-1A-A CC-A59-AS Ammeter Switch A59 CB-F-1A-A CC-A59-CT Current Transformer (150/5) A59 CB-F-1A-A CC-A59-TD1 CT Test Device A59 CB-F-1A-A CC-A59-ATR Transducer A59 CB-F-1A-A CC-A59-TD2 Lockout Relay Test Device A59 CB-F-1A-A CC-A59-FU Fuses A59 CB-F-1A-A CC-A59-52Z Timing Relay A59 CB-F-1A-A CC-A59-G,R,W Indicating Lights A59 CB-F-1A-A CC-A59-51GS Ground Sensor Relay A59 CB-F-1A-A CC-A58-52S Mechanical-Operated Switch A58 CB-F-1A-A CC-A59-62 Time Delay Relay A59 CB-F-1A-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-4 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 CC-P-11D PCCW Loop "B" Pump "D" CC-20211 B 310766 PAB-F-2C-Z X X X - M08 CC-A79-52 4160 V AC Circuit Breaker A79 CB-F-1B-A A79-M08/1 CC-CS-2241-2 Control Switch A79 CB-F-1B-A CC-SS-2241 Selector Switch A79 CB-F-1B-A 310895 A79a A79h A79b A79c A79d CBA-FN-32

CBA-FN-33 PAH-FN-42B EDE-SWG-6 CC-P-11A or CC-P-11C EDE-A73-94-1A Bus Undervoltage Relay A73 CB-F-1B-A CC-A79-52H Truck-Operated Contact A79 CB-F-1B-A CC-A79-50/51 Instrument/Time Overcurrent Relays

øA, øC A79 CB-F-1B-A CC-A79-86 Lockout Relay A79 CB-F-1B-A CC-A79-AM Ammeter A79 CB-F-1B-A CC-A79-AS Ammeter Switch A79 CB-F-1B-A CC-A79-CT Current Transformer (150/5) A79 CB-F-1B-A CC-A79-TD1 CT Test Device A79 CB-F-1B-A CC-A79-ATR Transducer A79 CB-F-1B-A CC-A79-TD2 Lockout Relay Test Device A79 CB-F-1B-A CC-A79-FU Fuses A79 CB-F-1B-A CC-A79-52Z Timing Relay A79 CB-F-1B-A CC-A79-G,R,W Indicating Lights A79 CB-F-1B-A CC-A79-51GS Ground Sensor Relay A79 CB-F-1B-A CC-A78-52S Mechanical-Operated Switch A78 CB-F-1B-A CC-A79-62 Time Delay Relay A79 CB-F-1B-A 5 CC-TV-2171-1 CC-20205 A 310765 PAB-F-2C-Z X X X X UN6 CC-E2T/3-72 125 V DC Circuit Breaker E2T CB-F-1A-A CC-TV-2271-1 Note 6 CC-SS-2171 Selector Switch G81 CB-F-1A-A Primary Component

Cooling Water

Heat Exchanger

E-17A Temperature

Control Valve CC-GN9-R1 Auxiliary Relay GN9 CB-F-1A-A E2T-G81 G81-G2M G81-UN6/1 G81-UN7/1 G81-GN9/A 310895 E2T/3a E2T/3c E2T/3d CBA-FN-19

CBA-FN-20 PAH-FN-42A EDE-PP-113A Instrument Air CC-TY-2171-1 Pilot Solenoid G2M PAB-F-2C-Z CC-ZL-2171-5 Valve Position Indicating Lights G81 CB-F-1A-A CC-ZS-TV-2171-1 Valve Position Switch UN6 PAB-F-2C-Z CC-SS-2171 Selector Switch G81 CB-F-1A-A G81-G2M/2 CC-HIC-2171 Auto/Manual Controller with

Indicator G81 CB-F-1A-A 310895 310952 4c FK0d FK0f FP 71337

16 CC-HQY-2171 E/E Converter G2H CB-F-1A-A CBA-FN-19

CBA-FN-20 PAH-FN-42A

MM-UQ-5866

NM-UQ-5867 Instrument Air CC-HY-2171 E/I Converter G2H CB-F-1A-A CC-TY-2171-4 I/P Converter G2M PAB-F-2C-Z CC-TY-2171-5 I/P Converter G2M PAB-F-2C-Z

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-5 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 CC-TV-2171-2 CC-20205 A 310765 PAB-F-2C-E X X X X UN7 CC-E2T/3-72 125 V DC Circuit Breaker E2T CB-F-1A-A CC-TV-2271-2 Note 6 CC-SS-2171 Selector Switch G81 CB-F-1A-A Primary Component

Cooling Water

Heat Exchanger

E-17A Temperature

Control Valve CC-GN9-R1 Auxiliary Relay GN9 CB-F-1A-A 310895 E2T/3a E2T/3c E2T/3d CC-TY-2171-2 Pilot Solenoid G2M PAB-F-2C-Z CBA-FN-19

CBA-FN-20 PAH-FN-42A EDE-PP-113A Instrument Air CC-ZL-2171-6 Valve Position Indicating Lights G81 CB-F-1A-A E2T-G81 G81-G2M G81-UN6/1 G81-UN7/1 G81-GN9/A CC-ZS-TV-2171-2 Valve Position Switch UN7 PAB-F-2C-Z CC-SS-2171 Selector Switch G81 CB-F-1A-A G81-G2M/2 CC-HIC-2171 Auto/Manual Controller with

Indicator G81 CB-F-1A-A 310895 310952 4c FK0d FK0f FP 71337

16 CC-HQY-2171 E/E Converter G2H CB-F-1A-A CBA-FN-19

CBA-FN-20 PAH-FN-42A

MM-UQ-5866

MM-UQ-5867 Instrument Air CC-HY-2171 E/I Converter G2H CB-F-1A-A CC-TY-2171-4 I/P Converter G2M PAB-F-2C-Z CC-TY-2171-5 I/P Converter G2M PAB-F-2C-Z 7 CC-TV-2271-1 CC-20211 B 310765 PAB-F-2C-Z X X X X UP9 CC-E2U/3-72 125 V DC Circuit Breaker E2U CB-F-1B-A CC-TV-2171-1 Note 6 CC-SS-2271 Selector Switch GZ0 CB-F-1B-A Primary Component

Cooling Water

Heat Exchanger

E-17B Temperature

Control Valve CC-GN0-R1 Auxiliary Relay GN0 CB-F-1B-A 310895 E2U/3a E2U/3c E2U/3d CBA-FN-32 CBA-FN-33 PAH-FN-42B EDE-PP-113B Instrument Air CC-TY-2271-1 Pilot Solenoid UI2 PAB-F-2C-Z E2U-GN0/6 E2U-GZ0 GN0-GZ0/5 GN0-GZ0/9 GZ0-UP9/1 GZ0-UP0/1 GZ0-UI2 CC-ZL-2271-5 Valve Position Indicating Lights GZ0 CB-F-1B-A CC-ZS-TV-2271-1 Valve Position Switch UP9 PAB-F-2C-Z CC-GN0-R2 Auxiliary Relay GN0 CB-F-1B-A CC-SS-2271 Selector Switch GZ0 CB-F-1B-A GZ0-Q60 CC-HIC-2271 Auto/Manual Controller with

Indicator GZ0 CB-F-1B-A CC-HQY-2271 E/E Converter GZ0 CB-F-1B-A 310895 3108952 4c FJ4j FJ4n FP 71336

3 CBA-FN-32

CBA-FN-33 PAH-FN-42B

MM-UQ-5868

MM-UQ-5869 Instrument Air CC-HY-2271 E/I Converter GZ0 CB-F-1B-A CC-TY-2271-4 I/P Converter Q60 PAB-F-2C-Z CC-TY-2271-5 I/P Converter Q60 PAB-F-2C-Z

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-6 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 8 CC-TV-2271-2 CC-20211 B 310765 PAB-F-2C-Z X X X X UP0 CC-E2U/3-72 125 V DC Circuit Breaker E2U CB-F-1B-A CC-TV-2171-2 Note 6 CC-SS-2271 Selector Switch GZ0 CB-F-1B-A 310895 E2U/3a E2U/3c E2U/3d Primary Component

Cooling Water

Heat Exchanger

E-17B Temperature

Control Valve CC-GN0-R1 Auxiliary Relay GN0 CB-F-1B-A E2U-GN0/6 E2U-GZ0 GN0-GZ0/5 GN0-GZ0/9 GZ0-UP9/1 GZ0-UP0/1 GZ0-UI2 CBA-FN-32

CBA-FN-33 PAH-FN-42B EDE-PP-113B Instrument Air CC-TY-2271-2 Pilot Solenoid UI2 PAB-F-2C-Z CC-ZL-2271-6 Valve Position Indicating Lights GZ0 CB-F-1B-A CC-ZS-TV-2271-2 Valve Position Switch UP0 PAB-F-2C-Z CC-GN0-R2 Auxiliary Relay GN0 CB-F-1B-A CC-SS-2271 Selector Switch GZ0 CB-F-1B-A GZ0-Q60 CC-HIC-2271 Auto/Manual Controller with

Indicator GZ0 CB-F-1B-A CC-HQY-2271 E/E Converter GZ0 CB-F-1B-A 310895 3108952 4c FJ4j FJ4n FP 71336

3 CBA-FN-32

CBA-FN-33 PAH-FN-42B

MM-UQ-5868

MM-UQ-5869 Instrument Air CC-HY-2271 E/I Converter GZ0 CB-F-1B-A CC-TY-2271-4 I/P Converter Q60 PAB-F-2C-Z CC-TY-2271-5 I/P Converter Q60 PAB-F-2C-Z 9 CC-E-17A Primary Component Cooling Water

Heater Exchanger CC-20205 A 310765 805217 PAB-F-2C-Z PAB-F-3A-Z X X - - - - - - - - - - Service Water CC-E-17B Notes 1,3 10 CC-E-17B Primary Component Cooling Water

Heater Exchanger CC-20211 B 310765 805217 PAB-F-2C-Z PAB-F-3A-Z X X - - - - - - - - - - Service Water CC-E-17A Notes 1,3 11 CC-V-145 RH-E-9A Return Header Isolation

Valve CC-20207 A 310763 RHR-F-3B-Z - X X - V78 CC-BY2-52 460 V AC Circuit Breaker BY2 CB-F-1A-A - - - EAH-FN-5A EAH-FN-31A CC-V-272 Note 4 12 CC-V-272 RH-E-9B Return Header Isolation

Valve CC-20213 B 310763 RHR-F-3A-Z - X X - V72 CC-BY8-52 460 V AC Circuit Breaker BY8 CB-F-1B-A - - - EAH-FN-5B EAH-FN-31B CC-V-145 Note 4 13 CC-P-322A Thermal Barrier PCCW Recirc Pump CC-20209 A 310576 C-F-1-Z X X X - M1D CC-B4M-52-1,2 460 V AC Circuit Breakers B4M CB-F-1A-A 310895 B4Ma B4Mc CC-P-322B CC-CS-2077-2 Control Switch with Indication G2G CB-F-1A-A B4M-H18 H18-M1D B4M-G81 CBA-FN-19

CBA-FN-20 EDE-MCC-515 CC-SS-2077 Selector Switch G2G CB-F-1A-A CC-B4M-42 Motor Starter B4M CB-F-1A-A CC-B4M-49 Overload Relay B4M CB-F-1A-A EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A CC-B4M-FU Fuse B4M CB-F-1A-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-7 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 14 CC-P-322B Thermal Barrier PCCW Recirc Pump CC-20209 B 310577 C-F-1-Z X X X - M1E CC-B4Q-52-1,2 460 V AC Circuit Breaker B4Q CB-F-1B-A 310895 B4Qa B4Qc CC-P-322A CC-CS-2078-2 Control Switch with Indication G2J CB-F-1B-A B4Q-H15 H15-M1E B4Q-GZ0 CBA-FN-32

CBA-FN-33 EDE-MCC-615 CC-SS-2078 Selector Switch G2J CB-F-1B-A CC-B4Q-42 Motor Starter B4Q CB-F-1B-A CC-B4Q-49 Overload Relay B4Q CB-F-1B-A EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A CC-B4Q-FU Fuse B4Q CB-F-1B-A 15 CC-E-153A Thermal Barrier Heat Exchanger CC-20209 A 310576 C-F-1-Z X X - - - - - - - - - -

- CC-E-153B Note 1 16 CC-E-153B Thermal Barrier Heat Exchanger CC-20209 B 310577 C-F-1-Z X X - - -  -  - - - - - -
- CC-E-153A Note 1 17 CC-V-1101 Thermal Barrier HX CC-E-153A 

Isolation Valve CC-20209 A 310769 PP-F-3A-Z X X X - V2S CC-B4K-52 460 V AC Circuit Breaker B4K CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 CC-V-1092 Note 2 18 CC-V-1109 Thermal Barrier HX CC-E-153A

Isolation Valve CC-20209 A 310769 PP-F-3A-Z X X X - V2T CC-B4L-52 460 V AC Circuit Breaker B4L CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 CC-V-1095 Note 2 19 CC-V-1092 Thermal Barrier HX CC-E-153B

Isolation Valve CC-20209 B 310769 PP-F-4B-Z X X X - V2V CC-B4P-52 460 V AC Circuit Breaker B4P CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 CC-V-1101 Note 2 20 CC-V-1095 Thermal Barrier HX CC-E-153B

Isolation Valve CC-20209 B 310769 PP-F-4B-Z X X X - V2U CC-B4N-52 460 V AC Circuit Breaker B4N CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 CC-V-1109 Note 2 21 CC-V-428 RC-P-1A Thermal Barrier Isolation

Valve CC-20209 A 310578 C-F-2-Z X X X - V74 CC-BY4-52-1 460 V AC Circuit Breaker BY4 CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 None Note 7 22 CC-V-438 RC-P-1C Thermal Barrier Isolation

Valve CC-20209 B 310579 C-F-2-Z X X X - V76 CC-BY6-52-1 460 V AC Circuit Breaker BY6 CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 None Note 7 23 CC-V-439 RC-P-1D Thermal Barrier Isolation

Valve CC-20209 A 310579 C-F-2-Z X X X - V70 CC-BY7-52-1 460 V AC Circuit Breaker BY7 CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 None Note 7 24 CC-V-395 RC-P-1B Thermal Barrier Isolation

Valve CC-20209 B 310578 C-F-2-Z X X X - V69 CC-BY5-52-1 460 V AC Circuit Breaker BY5 CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 None Note 7 25 CC-TK-196 Thermal Barrier Loop Head Tank CC-20209 A/B 310581 805193 C-F-3-Z X X - - - - - - - - - -

- None Notes 1,5 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-8 FUNCTION:  PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER  SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO.

TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 26 CC-TK-19A Primary Component Cooling Water

Head Tank CC-20205 A 310767 PAB-F-3A-Z X X - - - - - - - - - -

- CC-TK-19B Note 1 27 CC-TK-19B Primary Component Cooling Water 

Head Tank CC-20211 B 310767 PAB-F-3A-Z X X - - - - - - - - - -

- CC-TK-19A Note 1

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 4 Table RSS 3.1.3.9-1 Table RSS 3.1.3.9 Deleted SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.10-1 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CBA-DP-24A CBA-20303 A 310443 CB-F-2B-A X X X X V1A CBA-FY-5550A Pilot Solenoid V1A CB-F-2B-A 310926 BK4a BK4c Instrument Air CBA-DP-24F Note 3,4 Mechanical Room

"A" Outside Air

Damper FP-R1 Signal Actuating

Output Relay GP4 TB-F-2-Z CBA-TIC-5571 Temperature Indicating Control

(Pneumatic) G3C CB-F-2B-A G4P-V1A G4P-V1B G4P-V1C G3C-G4P/5 CBA-FY-5550B Pilot Solenoid V1B CB-F-2B-A CBA-FY-5550C Pilot Solenoid V1C CB-F-2B-A 2 CBA-DP-24B CBA-20303 A 310443 CB-F-2B-A X X X X V1B CBA-FY-5550B Pilot Solenoid V1B CB-F-2B-A BK4a BK4c Instrument Air CBA-DP-24E Note 3,4 Mechanical Room

"A" Recirculating

Air Damper FP-R1 Signal Actuating

Output Relay G4P TB-F-2-Z G4P-V1A G4P-V1B G4P-V1C G3C-G4P/5 CBA-TIC-5571 Temperature Indicatin g Controller (Pneumatic) G3C CB-F-2B-A CBA-FY-5550A Pilot Solenoid V1A CB-F-2B-A CBA-FY-5550C Pilot Solenoid V1C CB-F-2B-A 3 CBA-DP-24C CBA-20303 A 310443 CB-F-2B-A X X X X V1C CBA-FY-5550C Pilot Solenoid V1C CB-F-2B-A BK4a BK4c Instrument Air CB-DP-24D Note 3,4 Mechanical Room

"A" Return Air

Damper FP-R1 Signal Actuating

Output Relay G4P TB-F-2-Z CBA-TIC-5571 Temperature Indicating Controller (Pneumatic) G3C CB-F-2B-A G4P-V1A G4P-V1B G4P-V1C G3C-G4P/5 CBA-FY-5550A Pilot Solenoid V1A CB-F-2B-A CBA-FY-5550B Pilot Solenoid V1B CB-F-2B-A 4 CBA-DP-24D Mechanical Room "B" Return Air

Damper CBA-20303 B 310443 604094 CB-F-2C-A X X - X - CBA-TIC-5572 Temperature Indicatin g Controller (Pneumatic) - CB-F-2C-A - - - Instrument Air CBA-DP-24C Notes 1,2,3,4 5 CBA-DP-24E Mechanical Room "B" Recirculating

Air CBA-20303 B 310443 604094 CB-F-2C-A X X - X - CBA-TIC-5572 Temperature Indicating Controller (Pneumatic) - CB-F-2C-A - - - Instrument Air CBA-DP-24B Notes 1,2,3,4 6 CBA-DP-24F Mechanical Room "B" Outside Air

Damper CBA-20303 B 310443 604094 CB-F-2C-A X X - X - CBA-TIC-5572 Temperature Indicatin g Controller (Pneumatic) - CB-F-2C-A - - - Instrument Air CBA-DP-24A Notes 1,2,3,4

.Notes  1. Equipment is mechanical with no electrical requirements. 
2. Electrical conduit Plan Drawing 310443, listed only to show fire zone correlation reference to control building area covered by HVAC Drawing 604094 where CBA Dampers 24 D, E, and F are identified in plan.
3. Process connections showing positioning of air operated dampers, DP-24A-F, by pneumatic temperature indicating controllers, CBA-TIC-5571 and 5572, are detailed on I&C Loop Diagrams 510159 and 510160.
4. Instrument air is required for normal positioning of dampers for area temperature control. Should IA fail, dampers 24A, 24B, 24E and 24F will fail "as is" and 24C and 24D fail open. The operators can start and stop fans to maintain switchgear room habitability.
5. Dampers fail open on loss of instrument air, which is the safe shutdown position.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.10-2 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 CBA-FN-19 CBA-20303 A 310443 CB-F-2B-A X X X - N28 CBA-BL6-52 460 V ac Circuit Breaker BL6 CB-F-1A-A BL6-HR2/1 BL6-N28/2 310926 BL6a BL6c EDE-MCC-515 CBA-FN-32 Control Building

Train "A" SWGR

Supply Fan CBA-CS-5552 Control Switch with Indication BL6 CB-F-1A-A DG-HR2-HR9X EPS Step Loading Relay HR2 CB-F-1A-A DG-HR2-RMO EPS Manual Override Relay HR2 CB-F-1A-A CBA-BL6-42 Motor Starter BL6 CB-F-1A-A CBA-BL6-42X Motor Starter Auxiliary Relay BL6 CB-F-1A-A CBA-BL6-49 Overload Relays BL6 CB-F-1A-A CBA-BL6-FU Fuse BL6 CB-F-1A-A 8 CBA-FN-20 CBA-20303 A 310443 CB-F-2B-A X X X - N30 CBA-BL7-52 460 V ac Circuit Breaker BL7 CB-F-1A-A BL7-HR2 BL7-N30/2 BL7a BL7c EDE-MCC-521 CBA-FN Control Building

Train "A" SWGR

Return Fan DG-HR2-RMO EPS Manual Override Relay HR2 CB-F-1A-A CBA-BL7-42 Motor Starter BL7 CB-F-1A-A CBA-BL7-49 Overload Relays BL7 CB-F-1A-A CBA-BL7-FU Fuse BL7 CB-F-1A-A CBA-CS-5554 Control Switch with Indication BL7 CB-F-1A-A DG-HR2-HR9X EPS Step Loading Relay HR2 CB-F-1A-A CBA-BL7-42X Motor Starter Auxiliary Relay BL7 CB-F-1A-A 9 CBA-FN-21A CBA-20303 A 310443 CB-F-2B-A X X X - N32 CBA-BL8-52 460 V ac Circuit Breaker BL8 CB-F-1A-A BL8a BL8c EDE-MCC-521 CBA-FN-21B Control Building

Battery Room

Exhaust Fan "A" CBA-CS-5556 Control Switch with Indication BL8 CB-F-1A-A BL8-N32 BL8-VV5/1 BL8-VV5 CBA-ZS-DP-21A Damper Position Switch VV5 CB-F-2B-A CBA-BL8-42 Motor Starter BL8 CB-F-1A-A CBA-ZL-5556 Damper 21A Indicatin g Lights BL8 CB-F-1A-A CBA-BL8-49 Overload Relays BL8 CB-F-1A-A CBA-DP-21A-20 Pilot Solenoid VV5 CB-F-2B-A CBA-BL8-FU Fuse BL8 CB-F-1A-A 10 CBA-DP-21A CBA-20303 A 310443 CB-F-2B-A X X X X VV5 CBA-BL8-52 460 V ac Circuit Breaker BL8 CB-F-1A-A BL8-VV5 BL8-VV5/1 BL8a BL8c EDE-MCC-521 CBA-DP-21B Note 5 Battery Room

Exhaust Fan "A"

Damper CBA-BL8-FU Fuse BL8 CB-F-1A-A CBA-CS-5556 Control Switch with Indication BL8 CB-F-1A-A CBA-DP-21A-20 Pilot Solenoid VV5 CB-F-2B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.10-3 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 CBA-FN-21B CBA-20303 B 310443 CB-F-2C-A X X X - N33 CBA-BL5-52 460 V ac Circuit Breaker BL5 CB-F-1B-A 310926 BL5a BL5c EDE-MCC-621 CBA-FN-21A Control Building

Battery Room

Exhaust Fan "B" CBA-CS-5557 Control Switch with Indication BL5 CB-F-1B-A BL5-N33 BL5-VV4/1 BL5-VV4 CBA-ZS-DP-21B Damper Position Switch VV4 CB-F-2C-A CBA-BL5-42 Motor Starter BL5 CB-F-1B-A CBA-ZL-5557 Damper 21B Indicatin g Lights BL5 CB-F-1B-A CBA-BL5-49 Overload Relays BL5 CB-F-1B-A CBA-DP-21B-20 Pilot Solenoid VV4 CB-F-2C-A CBA-BL5-FU Fuse BL5 CB-F-1B-A 12 CBA-DP-21B CBA-20303 B 310443 CB-F-2C-A X X X X VV4 CBA-BL5-52 460 V ac Circuit Breaker BL5 CB-F-1B-A BL5-VV4 BL5-VV4/1 BL5a BL5c EDE-MCC-621 CBA-DP-21A Note 5 Battery Room

Exhaust Fan "B"

Damper CBA-BL5-FU Fuse BL5 CB-F-1B-A CBA-CS-5557 Control Switch BL5 CB-F-1B-A CBA-DP-21B-20 Pilot Solenoid VV4 CB-F-2C-A 13 CBA-FN-32 CBA-20303 B 310443 CB-F-2C-A X X X - NH3 CBA-BL3-52 460 V ac Circuit Breaker BL3 CB-F-1B-A BL3-HR4 BL3-NH3 BL3a BL3c EDE-MCC-621 CBA-FN-19 Control Building

Train "B" SWGR

Supply Fan CBA-CS-5559 Control Switch with Indication BL3 CB-F-1B-A DG-HR4-HR9X EPS Step Loading Relay HR4 CB-F-1B-A DG-HR4-RMO EPS Manual Override Relay HR4 CB-F-1B-A CBA-BL3-42 Motor Starter BL3 CB-F-1B-A CBA-BL3-42X Motor Starter Auxiliary Relay BL3 CB-F-1B-A CBA-BL3-49 Overload Relays BL3 CB-F-1B-A CBA-BL3-FU Fuse BL3 CB-F-1B-A 14 CBA-FN-33 CBA-20303 B 310443 CB-F-2C-A X X X - NH5 CBA-BL4-52 460 V ac Circuit Breaker BL4 CB-F-1B-A BL4-NR4 BL4-NH5 BL4a BL4c EDE-MCC-621 CBA-FN-20 Control Building

Train "B" SWGR

Return Fan CBA-CS-5561 Control Switch with Indication BL4 CB-F-1B-A DG-HR4-HR9X EPS Step Loading Relay HR4 CB-F-1B-A CBA-BL4-42 Motor Starter BL4 CB-F-1B-A CBA-BL4-49 Overload Relays BL4 CB-F-1B-A CBA-BL4-FU Fuse BL4 CB-F-1B-A DG-HR4-RMO EPS Manual Override

Relay HR4 CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 11 Table RSS 3.1.3.11-1 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 DAH-FN-25A DG-1A Room Supply Air Fan DAH-20624 A 310525 DG-F-3A-Z X X X - N37 DAH-B01-52 460 V AC Circuit Breaker B01 CB-F-1A-A EDE-MCC-521 EDE-PP-11E DAH-FN-25B DAH-CS-5529 Control Switch with Fan Indicating Lights B01 CB-F-1A-A B01-N37/1 B01-J1E B01-T3P B01-GN9 310928 B01a B01c B01d DAH-FISH-5529 Flow Switch S40 DG-F-3A-Z DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DAH-ED1-R2 Auxiliary Relay ED1 CB-F-1A-A DG-G29-HSR DG-1A High Speed Relay G29 DG-F-2A-A DAH-B01-42 Motor Starter B01 CB-F-1A-A DAH-B01-42X Motor Starter Auxiliary Relay B01 CB-F-1A-A DAH-B01-49 Overload Relays B01 CB-F-1A-A DAH-B01-FU Fuse B01 CB-F-1A-A DAH-ED1-R1 Control Circuit Power Monitor Auxiliary

Relay E01 CB-F-1A-A DAH-GN9-RS EPS Permissive Auxiliary Relay GN9 CB-F-1A-A DAH-GN9-RD Damper Position Auxiliary Relay GN9 CB-F-1A-A DAH-E3E/7-52 120 V AC Circuit Breaker E3E CB-F-1A-A E3E/7a E3E/7b EDE-MCC-515 EDE-PP-E3E DAH-TB-5529-1 Temperature Bistable J1E DG-F-2A-A J1E-T3P (Non CASP) E3E-J1E DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DAH-TE-5529-1 Temperature Element T3P DG-F-2A-A DAH-TT-5529-1 Temperature Transmitter J1E DG-F-2A-A DAH-CP-295 DG-A Room Air Handling Fans and Damper Control Panel J1E DG-F-2A-A

.Notes   1. Air is not required for support as damper fails open. 

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 11 Table RSS 3.1.3.11-2 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 DAH-DP-16A DG-1A Room Return Air Damper DAH-20624 A 310524 DG-F-2A-A X X X X UF9 DAH-ED1-R2 (B01 & B03) Auxiliary Relays ED1 CB-F-1A-A E1S/6a E1S/6c EDE-MCC-521 EDE-PP-11E DAH-DP-16B Note 1 DAH-DP-16A-20 Pilot Solenoid UF9 DG-F-2A-A DAH-TB-5529-1 Temperature Bistable J1E DG-F-2A-A DAH-ZS-DP-16A Damper TBA Position Switch UF9 DG-F-2A-A DG-HR2-PR1 EPS Permissive Auxiliary Relay HR2 CB-F-1A-A DG-HR2-HR8 EPS Permissive Auxiliary Relay HR2 CB-F-1A-A DG-HR2-SR1 EPS Permissive Auxiliary Relay HR2 CB-F-1A-A DAH-GN9-RS EPS Permissive Auxiliary Relay GN9 CB-F-1A-A B01-UF9/1 B01-J1E/1 EIS-GN9 EDI-GN9 B03-UF9 B01-HR2 DAH-GN9-RD Damper Position Auxiliary Relay GN9 CB-F-1A-A DAH-E1S/6-52 120 V AC Circuit

Breaker EIS CB-F-1A-A DAH-ZL-5529-4 Damper Position Indicating Lights B03 CB-F-1A-A DAH-E3E/7-52 120 V AC Circuit Breaker E3E CB-F-1A-A E3E/7a E3E/7b EDE-MCC-515 EDE-PP-E3E DAH-TB-5529-1 Temperature Bistable J1E DG-F-2A-A J1E-T3P (Non CASP) E3E-J1E DAH-TE-5529-1 Temperature Element T3P DG-F-2A-A DAH-TT-5529-1 Temperature Transmitter J1E DG-F-2A-A DAH-CP-295 DG-A Room Air Handling Fans and

Damper Control Panel J1E DG-F-2A-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 11 Table RSS 3.1.3.11-3 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 DAH-FN-25B DG-1B Room Supply Air Fan DAH-20624 B 310525 DG-F-3B-Z X X X - N38 DAH-B02-52 460 V AC Circuit Breaker B02 CB-F-1B-A EDE-MCC-621 EDE-PP-11F DAH-FN-25A DAH-CS-5530 Control Switch with Fan Indicating Lights B02 CB-F-1B-A 310928 B02a B02c B02d DAH-FISH-5530 Flow Switch S41 DG-F-3B-Z B02-N38/1 B02-G30 B02-S41 B02-J1F B02-GN0 EE3-E3D DAH-J1F-RTB Temperature Bistable Auxiliary Relay J1F DG-F-2B-A DAH-EE3-R2 Auxiliary Relay EE3 CB-F-1B-A DAH-B02-FU Fuse B02 CB-F-1B-A DG-G30-HSR DG-1B High Speed Relay G30 DG-F-2B-A DAH-B02-42 Motor Starter B02 CB-F-1B-A DAH-B02-42X Motor Starter Auxiliary Relay B02 CB-F-1B-A DAH-B02-49 Overload Relays B02 CB-F-1B-A DAH-E3D-R1 Control Circuit Power Monitor Auxiliary

Relay E3D CB-F-1B-A DAH-GN0-RS EPS Permissive Auxiliary Relay GN0 CB-F-1B-A DAH-GN0-RD Damper Position Auxiliary Relay GN0 CB-F-1B-A DAH-E3F/7-52 120 V AC Circuit Breaker E3F CB-F-1B-A E3F/7a E3F/7b EDE-MCC-615 EDE-PP-E3F DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A J1F-T3Q (Non-CASP) E3F-J1F DAH-J1F-RTB Temperature Bistable Auxiliary Relay J1F DG-F-2B-A DAH-TE-5330-1 Temperature Element T3Q DG-F-2B-A DAH-TT-5530-1 Temperature Transmitter J1F DG-F-2B-A DAH-CP-296 DG-B Room Air Handling Fans and Damper Control Panel J1F DG-F-2B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 11 Table RSS 3.1.3.11-4 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 DAH-DP-16B DG-1B Room Return Air Damper DAH-20624 B 310524 DG-F-2B-A X X X X UF0 DAH-EE3-R2 (B02 & B04) Auxiliary Relay EE3 CB-F-1B-A E1T/6a E1T/6c EDE-MCC-621 EDE-PP-11F DAH-DP-16A Note 1 DAH-DP-16B-20 Pilot Solenoid UF0 DG-F-2B-A DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A DAH-ZS-DP-16B Damper 16B Position Switch UF0 DG-F-2B-A B02-UF0/1 ED0-J1F B02-EDO EE3-GN0/2 EIT-GN0 B01-HR4 B04-UF0 DG-HR4-HRB EPS Permissive Auxiliary Relay HR4 CB-F-1B-A DH-HR4-PR1 EPS Permissive Auxiliary Relay HR4 CB-F-1B-A DG-HR4-SR1 EPS Permissive Auxiliary Relay HR4 CB-F-1B-A DAH-GN0-RS EPS Permissive Auxiliary Relay GN0 CB-F-1B-A DAH-GN0-RD Damper Position Auxiliary Relay GN0 CB-F-1B-A DAH-E1T/6-52 120 V AC Circuit

Breaker E1T CB-F-1B-A DAH-ZL-5530-4 Damper Position Indicating Lights B04 CB-F-1B-A DAH-E3F/7-52 120 V AC Circuit Breaker E3F CB-F-1B-A E3F/7a E3F/7b EDE-MCC-615 EDE-PP-E3F DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A J1F-T3Q (Non-CASP) E3F-J1F DAH-TE-5530-1 Temperature Element T3Q DG-F-2B-A DAH-TT-5530-1 Temperature Transmitter J1F DG-F-2B-A DAH-CP-296 DG-B Room Air Handling Fans and Damper Control Panel J1F DG-F-2B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 11 Table RSS 3.1.3.11-5 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 DAH-FN-26A DG-1A Room Return Air Fan DAH-20624 A 310525 DG-F-2A-A X X X - N39 DAH-B03-52 460 V AC Circuit Breaker B03 CB-F-1A-A EDE-MCC-521 EDE-PP-11E DAH-FN-26B DAH-B03-42 Motor Starter B03 CB-F-1A-A 310928 B03a B03c B03d DAH-B03-42X Motor Starter Auxiliary Relays B03 CB-F-1A-A B03-N39/1 B03-J1E G29-J1E B03-GN9 DAH-B03-49 Overload Relays B03 CB-F-1A-A DAH-B03-FU Fuse B03 CB-F-1A-A DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DG-G29-HSR DG-1A High Speed Relay G29 DG-F-2A-A DAH-CS-6058 Control Switch with Indicating Lights B03 CB-F-1A-A DAH-ED1-R2 Auxiliary Relay ED1 CB-F-1A-A DAH-ED1-R1 Control Circuit Power Monitor Auxiliary

Relay ED1 CB-F-1A-A DAH-GN9-RS EPS Permissive Auxiliary Relay GN9 CB-F-1A-A DAH-GN9-RD Damper Position Auxiliary Relay GN9 CB-F-1A-A DAH-E3E/7-52 120 V AC Circuit Breaker E3E CB-F-1A-A E3E/7a E3E/7b EDE-MCC-515 EDE-PP-E3E DAH-TB-5529-1 Temperature Bistable J1E DG-F-2A-A J1E-T3P (Non CASP) E3E-J1E DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DAH-TE-5529-1 Temperature Element T3P DG-F-2A-A DAH-TT-5529-1 Temperature Transmitter J1E DG-F-2A-A DAH-CP-295 DG-A Room Air Handling Fans and Damper Control Panel J1E DG-F-2A-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 11 Table RSS 3.1.3.11-6 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 DAH-FN-26B DG-1B Room Return Air Fan DAH-20624 B 310525 DG-F-2B-A X X X - N40 DAH-B04-52 460 V AC Circuit Breaker B04 CB-F-1B-A B04a B04c B04d EDE-MCC-621 EDE-PP-11F DAH-FN-26A DAH-B04-42 Motor Starter B04 CB-F-1B-A DAH-B04-42X Motor Starter Auxiliary Relays B04 CB-F-1B-A B04-N40/1 B04-J1F G30-J1F B04-GN DAH-B04-49 Overload Relays B04 CB-F-1B-A DAH-B04-FU Fuse B04 CB-F-1B-A DAH-J1F-RTB Temperature Bistable Auxiliary Relay J1F DG-F-2B-A DG-G30-HSR DG-1B High Speed Relay G30 DG-F-2B-A DAH-CS-6059 Control Switch with Indicating Lights B04 CB-F-1B-A DAH-EE3-R2 Auxiliary Relay EE3 CB-F-1B-A DAH-EE3-R1 Control Circuit Power Monitor Auxiliary

Relay EE3 CB-F-1B-A DAH-GN0-RS EPS Permissive Auxiliary Relay GN0 CB-F-1B-A DAH-GN0-RD Damper Position

Auxiliary Relay GN0 CB-F-1B-A DAH-E3F/7-52 120 V AC Circuit

Breaker E3F CB-F-1B-A E3F/7a E3F/7b EDE-MCC-615 EDE-PP-E3F DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A J1F-T3Q (Non CASP) E3F-J1F DAH-J1F-RTB Temperature Bistable

Auxiliary Relay J1F DG-F-2B-A DAH-TE-5530-1 Temperature Element T3Q DG-F-2B-A DAH-TT-5530-1 Temperature

Transmitter J1F DG-F-2B-A DAH-CP-296 DG-B Room Air

Handling Fans and

Damper Control Panel J1F DG-F-2B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.12-1 FUNCTION: CONTAINMENT ENCLOSURE AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EAH-FN-5A MAH-20495 A 310766 CE-F-1-Z X X X - M80 EAH-AF5-52 480 V ac Circuit Breaker AF5 CB-F-1A-A EAH-FN-5B Containment

Enclosure Cooler

AC-2A Fan EAH-AF5-G, R Indicating Lights AF5 CB-F-1A-A EAH-CS-5767-2 Control Switch with Indication G2H CB-F-1A-A AF5-G2H AF5-G2H/1 AF5/M80 AF5-YC3 L41-YC3 310932 AF5a AF5e AF5b AF5g AF5f EAH-FN-31A EDE-US-52 Primary Component Cooling Water EAH-SS-5767 Selector Switch G2H CB-F-1A-A EAH-ZL-5767-2 Outlet Damper Position Lights G2H CB-F-1A-A EAH-ZS-DP-3A Damper Position Switch L41 CE-F-1-Z EAH-AF5-AM Ammeter AF5 CB-F-1A-A EAH-AF5-CT Current Transformer (200/5) AF5 CB-F-1A-A EDE-AC3-94-3 Bus Undervoltage Relay AC3 CB-F-1A-A EAH-AF5-52H-1 Truck-Operated Contact AF5 CB-F-1A-A EDE-TBX-YC3 Terminal Box YC3 CE-F-1-Z EAH-AF5-FU Fuses AF5 CB-F-1A-A 2 EAH-FN-5B MAH-20495 B 310766 CE-F-1-Z X X X - M81 EAH-AF9-52 480 V ac Circuit Breaker AF9 CB-F-1B-A EAH-FN-5A Containment

Enclosure Cooler

AC-2B Fan EAH-AF9-G, R Indicating Lights AF9 CB-F-1B-A EAH-CS-5768-2 Control Switch with Indication G2K CB-F-1B-A AF9-G2K AF9-G2K/1 AF9-G2K/2 AF9/M81 AF9-YB3 L42-YB3 AF9a AF9e AF9b AF9g AF9f EAH-FN-31B EDE-US-62 Primary Component Cooling Water EAH-SS-5768 Selector Switch G2K CB-F-1B-A EAH-ZL-5768-2 Outlet Damper Position Lights G2K CB-F-1B-A EAH-ZS-DP-3B Damper Position Switch L42 CE-F-1-Z EAH-AF9-AM Ammeter AF9 CB-F-1B-A EAH-AF9-CT Current Transformer (200/5) AF9 CB-F-1B-A EDE-AE3-94-3 Bus Undervoltage Relay AE3 CB-F-1B-A EAH-AF9-52H-1 Truck-Operated Contact AF9 CB-F-1B-A EDE-TBX-YB3 Terminal Box YB3 CE-F-1-Z EAH-AF9-FU Fuses AF9 CB-F-1B-A EAH-AE3-R1 Auxiliary Relay AE3CB-F-1B-A

.Notes   1. Equipment is mechanical with no electrical requirements. 
2. Air and electrical power are not required for support as damper fails closed.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.12-2 FUNCTION: CONTAINMENT ENCLOSURE AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 EAH-FN-31A MAH-20495 A 310765 CE-F-1-Z - X X - ND5 EAH-BB2-52 460 V ac Circuit Breaker BB2 CB-F-1A-A BB2-ND5 BB2-VQ2 310932 BB2a BB2c EDE-MCC-512 EAH-FN-31B Containment

Enclosure Return

Fan "A" EAH-BB2-FU Fuse BB2 CB-F-1A-A EAH-CS-5769-2 Control Switch BB2 CB-F-1A-A EAH-BB2-G, R Indicating Lights BB2 CB-F-1A-A EAH-SS-5769 Selector Switch BB2 CB-F-1A-A EAH-BB2-42 Motor Starter BB2 CB-F-1A-A EAH-BB2-42X Motor Starter Auxiliary Relay BB2 CB-F-1A-A EAH-BB2-49 Overload Relays BB2 CB-F-1A-A EAH-ZS-DP-25A Damper Position Switch VQ2 CE-F-1-Z 4 EAH-FN-31B MAH-20495 B 310765 CE-F-1-Z - X X - NJ7 EAH-BC1-52 460 V ac Circuit Breaker BC1 CB-F-1B-A BC1-NJ7 BC1-VQ3 310932 BC1a BC1c EDE-MCC-612 EAH-FN-31A Containment

Enclosure Return

Fan "B" EAH-BC1-FU Fuse BC1 CB-F-1B-A EAH-CS-5770-2 Control Switch BC1 CB-F-1B-A EAH-BC1-G, R Indicating Lights BC1 CB-F-1B-A EAH-SS-5770 Selector Switch BC1 CB-F-1B-A EAH-BC1-42 Motor Starter BC1 CB-F-1B-A EAH-BC1-42X Motor Starter Auxiliary Relay BC1 CB-F-1B-A EAH-BC1-49 Overload Relays BC1 CB-F-1B-A EAH-ZS-DP-25B Damper Position Switch VQ3CE-F-1-Z 5 EAH-DP-3A Containment Encl. Cooler AC-2A

Damper MAH-20495 A 310766 CE-F-1-Z X X - - L41 - - - - - - -

- EAH-DP-3B Note 1 6 EAH-DP-3B Containment Encl.

Cooler AC-2B

Damper MAH-20495 B 310766 CE-F-1-Z X X - - L42 - - - - - - -

- EAH-DP-3A Note 1 7 EAH-FN-174A MAH-20503 A 310586 MS-F-4A-Z X X X - M4T EAH-B8C-52 460 V ac Circuit Breaker B8C CB-F-1A-A B8C-M4T B8C-S5G B8Ca B8Cc EAH-FN-174B MS & FWPC 

Analyzer Room

Supply Fan EAH-B8C-FU Fuse B8C CB-F-1A-A CBA-FN-19

CBA-FN-20 EDE-MCC-515 EAH-CS-5136 Control Switch with Indication B8C CB-F-1A-A EAH-B8C-42 Motor Starter B8C CB-F-1A-A EAH-B8C-49 Overload Relays B8C CB-F-1A-A EAH-TSH-5136 Temperature Switch S5GMS-F-4A-Z

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.12-3 FUNCTION: CONTAINMENT ENCLOSURE AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 8 EAH-FN-174B MAH-20503 B 310586 MS-F-4A-Z X X X - M4U EAH-B8E-52 460 V ac Circuit Breaker B8E CB-F-1B-A B8E-M4U B8E-S5H 310932 B8Ea B8Ec EAH-FN-174A MS & FWPC

Analyzer Room

Supply Fan EAH-B8E-FU Fuse B8E CB-F-1B-A CBA-FN-32

CBA-FN-33 EDE-MCC-615 EAH-CS-5763 Control Switch with Indication B8E CB-F-1B-A EAH-B8E-42 Motor Starter B8E CB-F-1B-A EAH-B8E-49 Overload Relays B8E CB-F-1B-A EAH-TSH-5736 Temp. Switch S5H MS-F-4A-Z 9 PAH-DP-35A PAH-DP-36A CE Outboard

Isolation Dampers MAH-20495 A A 310766 310765 PAB-F-2A-Z PAB-F-2C-Z X X X X X X X X VN8 VN0 PAH-CS-5370 Control Switch F36 CB-F-3A-A F36-VN8 F36-VN0 310930 E42/8a E42/8c E42/8d Note 2 PAH-ZS-DP-35A Position Switch VN8 PAB-F-2A-Z PAH-ZS-DP-36A Position Switch VN0 PAB-F-2C-Z PAH-FY-DP-35A Solenoid Valve VN8 PAB-F-2A-Z PAH-FY-DP-36A Solenoid Valve VN0 PAB-F-2C-Z 10 PAH-DP-35B PAH-DP-36B CE Inboard

Isolation Dampers MAH-20495 B B 310766 310765 CE-F-1-Z CE-F-1-Z X X X X X X X X VN9 VP1 PAH-CS-5371 Control Switch F37 CB-F-3A-A F37-VP1 F37-VN9 310930 E50/8a E50/8c Note 2 PAH-ZS-DP-35B Position Switch VN9 CE-F-1-Z PAH-ZS-DP-36B Position Switch VP1 CE-F-1-Z PAH-FY-DP-35B Solenoid Valve VN9 CE-F-1-Z PAH-FY-DP-36B Solenoid Valve VP1 CE-F-1-Z

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.13-1 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EPA-FN-47A MAH-20503 A 310708 EFP-F-1-A X X X - NL8 EPA-BB7-52 460 V ac Circuit Breaker BB7 CB-F-1A-A EPA-FN-47B EPA-BB7-FU Fuse BB7 CB-F-1A-A BB7-NL8 BB7-UH3 BB7-VV6 310922 BB7a BB7c BB7d CBA-FN-19

CBA-FN-20 EDE-MCC-512 Emergency

Feedwater

Pumphouse Intake

Fan EPA-CS-5430-2 Control Switch BB7 CB-F-1A-A EPA-ZL-5430-4 Fan Indicating Lights BB7 CB-F-1A-A EPA-SS-5430 Selector Switch BB7 CB-F-1A-A EPA-EC8-RBB7 Damper Auxiliary Relay EC8 CB-F-1A-A EPA-ZS-DP-373 Damper Position Switch UH3 EFP-F-1-A EPA-ZS-DP-371 Damper Position Switch VV6 EFP-F-1-A EPA-ZL-5430-5 Damper DP-373 Position Lights BB7 CB-F-1A-A EPA-ZL-5430-6 Damper DP-371 Position Lights BB7 CB-F-1A-A EPA-BB7-42 Motor Starter BB7 CB-F-1A-A EPA-BB7-49 Overload Relays BB7 CB-F-1A-A 2 EPA-DP-373 MAH-20503 A 310708 EFP-F-1-A X X X X UH3 EPA-BB7-FU Fuse BB7 CB-F-1A-A BB7-UH3 EPA-DP-374 Note 1 EPA-EC8-RBB7 Auxiliary Relay EC8 CB-F-1A-A BB7a BB7c BB7d Emergency

Feedwater

Pumphouse Exhaust

Damper EPA-DP-373-20 Pilot Solenoid UH3 EFP-F-1-A CBA-FN-19

CBA-FN-20 EDE-MCC-512 3 EPA-FN-47B MAH-20503 B 310708 EFP-F-1-A X X X - NL9 EPA-BC7-52 460 V ac Circuit Breaker BC7 CB-F-1B-A BC7a BC7c BC7d EPA-FN-47A EPA-BC7-FU Fuses BC7 CB-F-1B-A BC7-NL9 BC7-UH4 BC7-VV7 CBA-FN-32

CBA-FN-33 EDE-MCC-612 Emergency

Feedwater

Pumphouse Intake

Fan EPA-ZL-5431-4 Fan Indicating Lights BC7 CB-F-1B-A EPA-SS-5431 Selector Switch BC7 CB-F-1B-A EPA-EDO-RBC7 Damper Auxiliary Relay EDO CB-F-1B-A EPA-ZS-DP-374 Damper Position Switch UH4 EFP-F-1-A EPA-ZS-DP-372 Damper Position Switch VV7 EFP-F-1-A EPA-BC7-42 Motor Starter BC7 CB-F-1B-A EPA-BC7-49 Overload Relays BC7 CB-F-1B-A EPA-ZL-5431-5 Damper DP-374 Position Lights BC7 CB-F-1B-A EPA-ZL-5431-6 Damper DP-372 Position Lights BC7 CB-F-1B-A EPA-CS-5431-2 Control Switch BC7 CB-F-1B-A EPA-EDO-R1 Auxiliary Relay EDO CB-F-1B-A

.Notes  1. Air is not required for support as damper fails open. 

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.13-2 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 EPA-DP-374 MAH-20503 B 310708 EFP-F-1-A X X X X UH4 EPA-BC7-FU Fuses BC7 CB-F-1B-A BC7-UH4 EPA-DP-373 Note 1 EPA-EDO-RBC7 Auxiliary Relay EDO CB-F-1B-A 310922 BC7a BC7c BC7d Emergency

Feedwater

Pumphouse Exhaust

Damper EPA-DP-374-20 Pilot Solenoid UH4 EFP-F-1-A CBA-FN-32

CBA-FN-33 EDE-MCC-612 EPA-EDO-R1 Auxiliary Relay EDO CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.14 -1 FUNCTION: PRIMARY AUXILIARY BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 PAH-FN-42A PAB Auxiliary Supply Fan "A" MAH-20495 A 310765 PAB-F-2C-Z X X X - M61 PAH-BF6-52 460 V ac Circuit Breaker BF6 CB-F-1A-A BF6-M61 BF6-ED1 BF6-UG5 BF6-UG7 UG5-UG7 BF6-UG5/1 310930 BF6a BF6c BF6d CBA-FN-19 CBA-FN-20 EDE-MCC-512 PAH-FN-42B PAH-CS-5391-2 Control Switch BF6 CB-F-1A-A PAH-ZL-5391-4 Fan Indicating Lights BF6 CB-F-1A-A PAH-SS-5391 Selector Switch BF6 CB-F-1A-A PAH-ED1-R1 Damper Auxiliary Relay ED1 CB-F-1A-A PAH-ZS-DP-43A-1A PAH-ZS-DP-43A-1B PAH-ZS-DP-43A-2A Damper Position Switch UG5 PAB-F-1K-Z PAH-ZS-DP-357 Damper Position Switch UG7 PAB-F-2C-Z PAH-BF6-42 Motor Starter BF6 CB-F-1A-A PAH-BF6-49 Overload Relays BF6 CB-F-1A-A PAH-DP-43A-20 Pilot Solenoid UG5 PAB-F-1K-Z PAH-DP-357-20 Pilot Solenoid UG7 PAB-F-2C-Z PAH-ZL-5391-5 Damper DP -43A Position Lights BF6 CB-F-1A-A PAH-ZL-5391-6 Damper DP -357 Position Lights BF6 CB-F-1A-A PAH-BF6-FU Fuse BF6 CB-F-1A-A 2 PAH-DP-43A PAB Auxiliary Fan Supply Damper MAH-20495 A 310765 PAB-F-1K-Z X X X X UG5 PAH-ED1-R1 Damper Auxiliary Relay ED1 CB-F-1A-A BF6-ED1 BF6-UG5 BF6-UG7 UG5-UG7 BF6-UG5/1 310930 BF6a BF6c BF6d CBA-FN-19 CBA-FN-20 PAH-DP-43B Note 1 PAH-DP-43A-20 Pilot Solenoid UG5 PAB-F-1K-Z 3 PAH-DP-357 PAB Auxiliary Fan Exhaust Damper MAH-20495 A 310766 PAB-F-2C-Z X X X X UG7 PAH-ED1-R1 Damper Auxiliary Relay ED1 CB-F-1A-A BF6-ED1 BF6-UG5 310930 BF6a BF6c CBA-FN-19 CBA-FN-20 PAH-DP-358 Note 1 PAH-DP-357-20 Pilot Solenoid UG7 PAB-F-2C-Z BF6-UG7 UG5-UG7

.Notes  1. Air and electrical power are not required for support as damper fails open.
2. See Table RSS 3.1.3.12 for operation of dampers PAH

-DP-35A, -35B, -36A & -36B. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.14 -2 FUNCTION: PRIMARY AUXILIARY BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 PAH-FN-42B PAB Auxiliary Supply Fan "B" MAH-20495 B 310765 PAB-F-2C-Z X X X - M62 PAH-BF7-52 460 V ac Circuit Breaker BF7 CB-F-1B-A BF7-E3D/1 BF7-M62 BF7-UG6 BF7-UG8 UG6-UG8 310930 BF7a BF7c CBA-FN-32 CBA-FN-33 EDE-MCC-612 PAH-FN-42A PAH-CS-5393-2 Control Switch BF7 CB-F-1B-A PAH-ZL-5393-4 Fan Indicating Lights BF7 CB-F-1B-A PAH-SS-5393 Selector Switch BF7 CB-F-1B-A PAH-EDO-R1 Damper Auxiliary Relay EDO CB-F-1B-A PAH-ZS-DP-43B-1A PAH-ZS-DP-43B-1B PAH-ZS-DP-43B-2A Damper Position Switch UG6 PAB-F-1K-Z PAH-ZS-DP-358 Damper Position Switch UG8 PAB-F-2C-Z PAH-ZL-5393-5 Damper DP -43B Position Lights BF7 CB-F-1B-A PAH-DP-43B-20 Pilot Solenoid UG6 PAB-F-1K-Z PAH-DP-358-20 Pilot Solenoid UG8 PAB-F-2C-Z PAH-BF7-42 Motor Starter BF7 CB-F-1B-A PAH-BF7-49 Overload Relays BF7 CB-F-1B-A PAH-BF7-FU Fuses BF7 CB-F-1B-A PAH-ZL-5393-6 Damper DP -358 Position Lights BF7 CB-F-1B-A PAH-E3D-R2 Auxiliary Relay E3D CB-F-1B-A 5 PAH-DP-43B PAB Auxiliary Fan Supply Damper MAH-20495 B 310765 PAB-F-1K-Z X X X X UG6 PAH-EDO-R1 Damper Auxiliary Relay EDO CB-F-1B-A BF7-UG6 BF7-UG8 UG6-UG8 310930 BF7a BF7c CBA-FN-32 CBA-FN-33 PAH-DP-43A Note 1 PAH-DP-43B-20 Pilot Solenoid UG6 PAB-F-1K-Z 6 PAH-DP-358 PAB Auxiliary Fan Exhaust Damper MAH-20495 B 310766 PAB-F-2C-Z X X X X UG8 PAH-EDO-R1 Damper Auxiliary Relay EDO CB-F-1B-A BF7-UG6 BF7-UG8 UG6-UG8 310930 BF7a BF7c CBA-FN-32 CBA-FN-33 PAH-DP-357 Note 1 PAH-DP-358-20 Pilot Solenoid UG8 PAB-F-2C-Z 7 PAH-DP-35A - - - - - - - - - - - - - - - - - - Note 2 8 PAH-DP-35B - - - - - - - - - - - - - - - - - - Note 2 9 PAH-DP-36A - - - - - - - - - - - - - - - - - - Note 2 10 PAH-DP-36B - - - - - - - - - - - - - - - - - - Note 2 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.15-1 FUNCTION: SERVICE WATER AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 SWA-FN-40A SWA-20372 A 301139 SW-F-ID-A X X X - NJO SWA-CR5-52 460 V ac Circuit Breaker CR5 SW-F-1B-A 301115 CR5a CR5c EDE-MCC-514 SWA-FN-40B SWA-CR5-42 Motor Starter CR5 SW-F-1B-A CR5-NJO CR5-G2H/1 CR5-G2H Service Water

Pumphouse Train

"A" Switchgear

Room Supply Fan SWA-CR5-49 Overload Relays CR5 SW-F-1B-A SWA-CS-5614-2 Control Switch with Indication G2H CB-F-1A-A SWA-SS-5614 Selector Switch G2H CB-F-1A-A SWA-CR5-FU Fuse CR5 SW-F-1B-A 2 SWA-FN-40B SWA-20372 B 301139 SW-F-ID-A X X X - NK1 SWA-CRO-52 460 V ac Circuit Breaker CRO SW-F-1C-A CROa CROc EDE-MCC-614 SWA-FN-40A SWA-CRO-42 Motor Starter CRO SW-F-1C-A Service Water

Pumphouse Train

"B" Switchgear

Room Supply Fan SWA-CRO-49 Overload Relays CRO SW-F-1C-A CRO-NK1 CRO-G2K/1 CRO-G2K F37-G2K/2 CRO-G2K/2 SWA-CS-5615-2 Control Switch with Indication G2K CB-F-1B-A SWA-SS-5615 Selector Switch G2K CB-F-1B-A SWA-CRO-FU Fuses CRO SW-F-1C-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -1 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EDE-SWG-5 4160 V Bus E5 UAT Incoming Line SWGR 310007 A 310442 CB-F-1A-A X X X - A51 EDE-A51-52 4160 V Circuit Breaker A51 CB-F-1A-A A51-G07 A51-G07/2 A51-G10 A51-HR9 GA6-GB0/4 A51-G07/1 A51-G07/3 A51-GB4 GA0-GB3/4 GC4-GC6/4 A51-G5X A51-G5X/1 A55-A5A A54-A5A/1 310102 A51a A51h A51b A51c A51d A51e CBA-FN-19 CBA-FN-20 ED-X-2A EDE-PP-111A DAH-FN-25A DAH-FN-26A EDE-SWG-6 UAT EDE-CS-9709-2 Control Switch A51 CB-F-1A-A EDE-CS-9709-3 Control Switch with Indication G07 DG-F-2A-A EDE-A51-G,R,W Indicating Lights A51 CB-F-1A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-A51-52H Truck Operated Contact A51 CB-F-1A-A EDE-A51-FU Fuses A51 CB-F-1A-A EDE-A51-CT1 Current Transformer (2000/5) A51 CB-F-1A-A EDE-A51-TD-1 CT Test Device A51 CB-F-1A-A EDE-A51-AM Ammeter A51 CB-F-1A-A EDE-A51-AS Ammeter Switch A51 CB-F-1A-A EDE-A51-ATR Current Transducer A51 CB-F-1A-A EDE-A51-CT2 Current Transformers (4000/5) A51 CB-F-1A-A EDE-A67-PT Potential Transformer (4200-120 V) A67 CB-F-1A-A EDE-A51-TD-3 PT Test Device A51 CB-F-1A-A EDE-A51-VM Voltmeter A51 CB-F-1A-A EDE-A51-86 Lockout Relay A51 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-A52-52S Mechanically Operated Contact A52 CB-F-1A-A DG-G10-25Y1 Auxiliary Synchronizing Check Relay G10 DG-F-2A-A EDE-A53-25U Synchronizing Check Relay A53 CB-F-1A-A EDE-SS-9709-1 Selector Switch G5X DG-F-2A-A EDE-CS-9707-3 Control Switch G07 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A52-86 Lockout Relay A52 CB-F-1A-A EDE-A69-86B Lockout Relay A69 CB-F-1A-A ED-86SB/2/1X -1 Lockout Relay GA0 TB-F-1C-2 ED-86-2/2/B3 Lockout Relay GA6 TB-F-1C-Z ED-86UB/2/1X -2A Lockout Relay GA8 TB-F-1C-Z ED-86UB/2/1X -2B Lockout Relay GA8 TB-F-1C-Z ED-86BF/2/2/52/TG1 Lockout Relay GA9 TB-F-1C-Z ED-86GT/2/TG1 Lockout Relay GA9 TB-F-1C-Z ED-86-1/2/B3 Lockout Relay GB0 TB-F-1C-Z ED-86BF-2/2H Lockout Relay GB3 TB-F-1C-Z ED-86BF-2/2K Lockout Relay GB4 TB-F-1C-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -2 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-5 (Continued) ED-86UP/2/1X -2A Lockout Relay GC2 TB-F-1C-Z ED-86UP/2/1X -2B Lockout Relay GC2 TB-F-1C-Z ED-86BF-1/2/52/TG1 Lockout Relay GC3 TB-F-1C-Z ED-86SP/2/1X -1 Lockout Relay GC4 TB-F-1C-Z ED-86BF-1/2H Lockout Relay CG6 TB-F-1C-Z ED-86BF-1/2E Lockout Relay CG7 TB-F-1C-Z DG-HR9-RM0 EPS Auxiliary Relay HR9 CB-F-1A-A EDE-A51-3 Interposing Relay for SWYD Lockout Relays A51 CB-F-1A-A EDE-A51-TD-2 Lockout Relay Test Device (A51 -86) A51 CB-F-1A-A EDE-A51-TD-4 Interposing Relay Test Device (A51/3) A51 CB-F-1A-A ED-GA0-TD-2 Lockout Relay Test Device (86SB/2/1X -1) GA0 TB-F-1C-Z ED-GA6-TD-2 Lockout Relay Test Device (86 -2/2/B3) GA6 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2A) GA8 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2B) GA8 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86BF-2/2/52/TG1) GA9 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86GT/2/TG1) GA9 TB-F-1C-Z ED-GB0-TD-2 Lockout Relay Test Device (86 -1/2/B3) GB0 TB-F-1C-Z ED-GB3-TD-2 Lockout Relay Test Device (86BF -2/2H) GB3 TB-F-1C-Z ED-GB4-TD-2 Lockout Relay Test Device (86BF -2/2E) GB4 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2A) GC2 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2B) GC2 TB-F-1C-Z ED-GC3-TD-2 Lockout Relay Test Device (86BF-1/2/52/TG1) GC3 TB-F-1C-Z ED-GC4-TD-2 Lockout Relay Test Device (86SP/2/1X -1) GC4 TB-F-1C-Z ED-GC6-TD-2 Lockout Relay Test Device (86BF -1/2H) GC6 TB-F-1C-Z ED-GC7-TD-2 Lockout Relay Test Device (86BF -1/2E) GC7 TB-F-1C-Z EDE-A51-51 Time Overcurrent Relays øA, øB, øC A51 CB-F-1A-A EDE-A51-51GS Ground Sensor Relay A51 CB-F-1A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -3 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 EDE-SWG-5 Grounding Transformer 310007 A 310442 CB-F-1A-A X X X - A67 EDE-A67-XFMR 3-1ø 15 kVA Transformers A67 CB-F-1A-A 310102 A67a CBA-FN-19 CBA-FN-20 EDE-SWG-5 EDE-SWG-6 GRD XFMR EDE-A67-FU 3-10A Fuses A67 CB-F-1A-A EDE-A67-52 120 V AC Circuit Breaker A67 CB-F-1A-A EDE-A67-RES Grounding Resistor A67 CB-F-1A-A EDE-A67-64 Grounding Rela y A67 CB-F-1A-A EDE-A67-TD-3 VM Test Device A67 CB-F-1A-A EDE-A67-VM (3) Ground Voltmeters A67 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -4 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 EDE-SWG-5 4160 V Bus E5 RAT Incoming Line SWGR 310007 A 310442 CB-F-1A-A X X X - A52 EDE-A52-52 4160 V Circuit Breaker A52 CB-F-1A-A A52-G07/1 A52-G07/3 A52-G10 A52-HR2 GA7-GB7/4 GE6-GE7/4 A52-G5X A52-G5X/1 A52-G07/2 A52-G07/4 A52-GB7 AG2-HR9 GC1-GC0/4 A54-A5A/2 310102 A52a A52J A52b A52c A52d A52e CBA-FN-19 CBA-FN-20 ED-X-3A EDE-PP-111A DAH-FN-25A DAH-FN-26A EDE-SWG-6 RAT EDE-CS-9707-2 Control Switch A52 CB-F-1A-A EDE-CS-9707-3 Control Switch with Indication G07 DG-F-2A-A EDE-A52-G,R,W Indicating Lights A52 CB-F-1A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-A52-52H Truck Operated Contact A52 CB-F-1A-A EDE-A52-FU Fuses A52 CB-F-1A-A EDE-A52-27/59 Under/Over Voltage Relay A52 CB-F-1A-A EDE-A52-27/59X1,X2 Under/Over Voltage Auxiliary Relay A52 CB-F-1A-A EDE-A52-52Z Time Delay Relay A52 CB-F-1A-A EDE-SS-9707-1 Selector Switch G5X DG-F-2A-A EDE-CS-9709-3 Control Switch G07 DG-F-2A-A EDE-A52-CT-1 Current Transformer (2000/5) A52 CB-F-1A-A EDE-A52-TD-1 CT Test Device A52 CB-F-1A-A EDE-A52-AM Ammeter A52 CB-F-1A-A EDE-A52-AS Ammeter Switch A52 CB-F-1A-A EDE-A52-ATR Current Transducer A52 CB-F-1A-A EDE-A52-CT-2 Current Transformer (4000/5) A52 CB-F-1A-A EDE-A53-PT Potential Transformer A53 CB-F-1A-A EDE-A52-TD-3 PT Test Device A52 CB-F-1A-A EE-A52-VM Voltmeter A52 CB-F-1A-A EDE-A52-52S Mechanically Operated Contact A52 CB-F-1A-A EDE-A69-86B Lockout Relay A69 CB-F-1A-A EDE-A52-86 Lockout Relay A52 CB-F-1A-A EDE-A51-86 Lockout Relay A51 CB-F-1A-A DG-HR2-RM0 EPS Auxiliary Relay HR2 CB-F-1A-A DG-HR9-RM0 EPS Auxiliary Relay HR9 CB-F-1A-A EDE-A51-52S Mechanically Operated Contact A51 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A DG-G10-25Y1 Auxiliary Synchronizing Check Relay G10 DG-F-2A-A EDE-A53-25RX Auxiliary Synchronizing Check Relay A53 CB-F-1A-A EDE-A53-25R Synchronizing Check Relay A53 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -5 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-5 (Continued) EDE-A52-62 & 62X Time Delay Relay A52 CB-F-1A-A EDE-A51-3 Interposing Relay for SWD Lockout Relays A51 CB-F-1A-A EDE-A52-TD-2 Lockout Relay Test Device (A52 -86) A52 CB-F-1A-A EDE-A52-TD-4 Interposing Relay Test Device (A52 -3) A52 CB-F-1A-A ED-86RB/2/1X -3A Lockout Relay GA7 TB-F-1C-Z ED-86-2/2/B2 Lockout Relay GB7 TB-F-1C-Z ED-86-1/2/B2 Lockout Relay GC0 TB-F-1C-Z ED-86RP/2/1X -3A Lockout Relay GC1 TB-F-1C-Z ED-86RP/2/1X -3B Lockout Relay GE6 TB-F-1C-Z ED-86RB/2/1X -3B Lockout Relay GE7 TB-F-1C-Z ED-GA7-TD-2 Lockout Relay Test Device (86RB/2/1X -3A) GA7 TB-F-1C-Z ED-GB7-TD-2 Lockout Relay Test Device (86 -1/2/B2) GB7 TB-F-1C-Z ED-GC0-TD-2 Lockout Relay Test Device (86 -1/2/B2) GC0 TB-F-1C-Z ED-GC1-TD-2 Lockout Relay Test Device (86RP/2/1X -3A) GC1 TB-F-1C-Z ED-GE6-TD-2 Lockout Relay Test Device (86RB/2/1X -3B) GE6 TB-F-1C-Z ED-G37-TD-2 Lockout Relay Test Device (86RP/2/1X -3B) GE7 TB-F-1C-Z EDE-A52-51 Time Overcurrent Relays øA, øB, øC A52 CB-F-1A-A EDE-A52-51GS Ground Sensor Relay A52 CB-F-1A-A EDE-A52-27RB-1 Residual Undervoltage Relay A52 CB-F-1A-A EDE-A52-27RB-2 Residual Undervoltage Relay A52 CB-F-1A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -6 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 EDE-SWG-5 4160 V Bus E5 PT Compartment 310007 A 310442 CB-F-1A-A X X X - A53 EDE-A53-PT Potential Transformers A53 CB-F-1A-A A53-AC2 A53-HR2 AF2-ED4 A53-G07 AC2-AF2 A54-A5A/4 A54-A5A/5 A55-A5A/1 A55-A5A/2 310102 A53a A53d A53e A53h CBA-FN-19 CBA-FN-20 EDE-SWG-5 EDE-PP-111A DAH-FN-25A DAH-FN-26A EDE-SWG-6 PT EDE-A53-VM Voltmeter A53 CB-F-1A-A EDE-A53-VS Voltmeter Switch A53 CB-F-1A-A EDE-A53-TD-3 PT Test Device A53 CB-F-1A-A EDE-A53-VTR-1 Voltage Transducer A53 CB-F-1A-A EDE-A53-VTR-2 Voltage Transducer A53 CB-F-1A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A53-25U Synchronizing Check Relay A53 CB-F-1A-A EDE-A53-25R Synchronizing Check Relay A53 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-A53-27B-1 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-27B-2 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-TS-3 Undervoltage Relay Test Switch A53 CB-F-1A-A EDE-A53-27D-1 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-27-D-1-RES Resistor A53 CB-F-1A-A EDE-A53-27D-2 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-27D-2-RES Resistor A53 CB-F-1A-A EDE-A53-TS-1 Undervoltage Relays Test Switch A53 CB-F-1A-A EDE-A52-27RB-1,2 Residual Undervoltage Relay A52 CB-F-1A-A EDE-A53-62B Time Delay Relay A53 CB-F-1A-A EDE-A53-62B-RES Resistor A53 CB-F-1A-A EDE-A53-TS-4 Test Switch EDE -62B A53 CB-F-1A-A EDE-A53-62BX-1 Auxiliary Relay A53 CB-F-1A-A EDE-A53-62BX Auxiliary Latch Relay A53 CB-F-1A-A EDE-A51-52S Mechanically Operated Contact A51 CB-F-1A-A EDE-ED4-94-5 Undervoltage Tripping Relay ED4 CB-F-1A-A EDE-A52-27/59X1 Under/Over Voltage Auxiliary Relay A52 CB-F-1A-A EDE-AF3-94-4 Undervoltage Tripping Relay AF3 CB-F-1A-A DG-HR2-RM0 EPS Auxiliary Relay HR2 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -7 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-5 (Continued) EDE-A53-94-1A Undervoltage Tripping Relay A53 CB-F-1A-A EDE-A53-94-1B Undervoltage Tripping Relay A53 CB-F-1A-A EDE-A53-94-2 Undervoltage Tripping Relay A53 CB-F-1A-A EDE-AC3-94-3 Undervoltage Tripping Relay AC3 CB-F-1A-A EDE-A53-FU 125 V DC 10A Fuses (2) A53 CB-F-1A-A EDE-A53-62D Time Delay Relay A53 CB-F-1A-A EDE-A53-62D-RES Resistor A53 CB-F-1A-A EDE-A53-TS-2 Test Switch Relay 62D A53 CB-F-1A-A EDE-A53-62DX Auxiliary Relay A53 CB-F-1A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -8 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 EDE-SWG-5 4160 V Bus E5 DG-1A Incoming Line SWGR 310010 310007 A 310442 CB-F-1A-A X X X - A54 EDE-A54-52 4160 V Circuit Breaker A54 CB-F-1A-A A54-G06/2 A54-G06/4 A54-G07/1 A54-HN0 A54-G06/3 A54-G07 A54-G07/2 G06-G29/7 A54-A5A/3 310102 A54a A54k A54b A54c A54d A54e A54f CBA-FN-19 CBA-FN-20 DG-DG-1A DAH-FN-25A DAH-FN-26A EDE-PP-111A EDE-SWG-6 DG-1B EDE-CS-9700-2 Control Switch A54 CB-F-1A-A EDE-CS-9700-3 Control Switch with Indication G06 DG-F-2A-A EDE-A54-G,R,W Indicating Lights A54 CB-F-1A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A54-52H Truck Operated Contact A54 CB-F-1A-A EDE-A54-FU Fuses A54 CB-F-1A-A EDE-A54-CT Current Transformers (2000/5) A54 CB-F-1A-A EDE-A54-DCT Differential Current Transformers (2000/5 ) A54 CB-F-1A-A DG-HNO-DCT DG-1A Neut. Diff. Current Transformers (2000/5) HN0 DG-F-2A-A DG-G06-CT Auxiliary Current Transformers (5:10) G06 DG-F-2A-A EDE-A54-AM Ammeter A54 CB-F-1A-A EDE-A54-AS-1 Ammeter Switch A54 CB-F-1A-A EDE-A54-ATR-1 Current Transducer A54 CB-F-1A-A EDE-A54-ATR-2 Current Transducer A54 CB-F-1A-A EDE-AM-9700-2 Ammeter G06 DG-F-2A-A EDE-G06-AS Ammeter Switch G06 DG-F-2A-A DG-SM-9585 Governor Control (2301A) G06 DG-F-2A-A EDE-A69-PT DG-1A Inc. Line Pot. Transformer (2) 4200-120 V A69 CB-F-1A-A EDE-A69-VM Voltmeter A69 CB-F-1A-A EDE-A69-VS Voltmeter Switch A69 CB-F-1A-A EDE-A69-TD-3 PT Test Device A69 CB-F-1A-A EDE-A69-VTR-1 Voltage Transducer A69 CB-F-1A-A EDE-A69-VTR-2 Voltage Transducer A69 CB-F-1A-A EDE-A54-27DG Undervoltage Relay A54 CB-F-1A-A EDE-A69-FTR-1 Frequency Transducer A69 CB-F-1A-A EDE-A69-FTR-2 Frequency Transducer A69 CB-F-1A-A EDE-A69-W/WH-TR Watt/Watthour Transducer A69 CB-F-1A-A EDE-A69-W/TR Watt Transducer A69 CB-F-1A-A EDE-A69-VAR-TR Var Transducer A69 CB-F-1A-A EDE-A54-TS Test Start Switch A54 CB-F-1A-A EDE-A54-52Z Time Delay Relay A54 CB-F-1A-A EDE-A54-81-RES Resistor A54 CB-F-1A-A EDE-A54-86DP Primary Lockout Relay A54 CB-F-1A-A EDE-A54-W Indicating Light (A54-86DP) A54 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -9 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-5 (Continued) EDE-A69-86B Lockout Relay A69 CB-F-1A-A EDE-A69-86DB Back-Up Lockout Relay A69 CB-F-1A-A EDE-A69-W Indicating Light (A69-86B & A69 -86DB) A69 CB-F-1A-A EDE-A51-86 Lockout Relay A51 CB-F-1A-A EDE-A52-86 Lockout Relay A52 CB-F-1A-A EDE-A51-52S Mechanically Operated Contact A51 CB-F-1A-A EDE-A52-52S Mechanically Operated Contact A52 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-A69-RLA LOCA Seal Relay A69 CB-F-1A-A DG-G10-25Y Auxiliary Sync Check Relay G10 DG-F-2A-A EDE-A69-RS Fast Closure Relay A69 CB-F-1A-A EDE-A54-81 Frequency Relay A54 CB-F-1A-A EDE-A54-87DP Primary Differential Relay A54 CB-F-1A-A EDE-A69-51B Time Overcurrent Relays, øA, øB, øC A69 CB-F-1A-A EDE-A54-81X Auxiliary Frequency Relay A54 CB-F-1A-A EDE-A69-60 Voltage Balance Relay A69 CB-F-1A-A EDE-A69-60AX Auxiliary Voltage Balance Relay A69 CB-F-1A-A EDE-A69-60BX Auxiliary Voltage Balance Relay A69 CB-F-1A-A EDE-A69-40 Loss of Field Relays øA, øB A69 CB-F-1A-A EDE-A54-40X Auxiliary Loss of Field Relay A54 CB-F-1A-A EDE-A69-32 Power Directional Relay A69 CB-F-1A-A EDE-A69-TD-1 Lockout Relay Test Device (86B) A69 CB-F-1A-A EDE-A69-TD-2 Lockout Relay Test Device (86DB) A69 CB-F-1A-A EDE-A54-TD-2 Lockout Relay Test Device (86DP) A54 CB-F-1A-A DG-G07-R43L5 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -10 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-5 (Continued) DG-G29-5A Shutdown Relay G29 DG-F-2A-A EDE-A69-51V Time Overcurrent Voltage Restraint Relays, øA, øB, øC A69 CB-F-1A-A EDE-A69-51GS Ground Sensor Relay A69 CB-F-1A-A EDE-A54-TD-1 Test Device A54 CB-F-1A-A EDE-A69-TD-3 Voltage Test Device A69 CB-F-1A-A EDE-A54-87DP Reactor Primary Differential Relay Reactor Assembly A54 CB-F-1A-A EDE-A54-81Y Time Delay Relay A54 CB-F-1A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -11 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 DG-CP-75A Diesel Generator 1A Control Panel Cubicle 2 Synchronizing System 310010 A 310524 DG-F-2A-A X X X - G07 DG-G07-FU-17&18 125 V DC Fuses (6A) G07 DG-F-2A-A 310102 G07/2c G07/2g DAH-FN-25A DAH-FN-26A EDE-SWG-11A DG-CP-76A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-RAX Auxiliary Relay, Latch G07 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-CS-9700-3 Control Switch G06 DG-F-2A-A EDE-CS-9707-3 Control Switch G07 DG-F-2A-A EDE-CS-9709-3 Control Switch G07 DG-F-2A-A DG-G06-25DG Synchronizing Check Relay G06 DG-F-2A-A DG-G10-25Y Auxiliary Synchronizing Check Relay G10 DG-F-2A-A DG-G10-25Y1 Auxiliary Synchronizing Check Relay G10 DG-F-2A-A EDE-A67-PT UAT X-2A Inc. Line Potential Transforme r A67 CB-F-1A-A 7b 7f EDE-A53-PT RAT X-3A Inc. Line Potential Transformer A53 CB-F-1A-A EDE-A53-PT Bus E5 Potential Transformer A53 CB-F-1A-A EDE-A69-PT DG-1A Inc. Line Potential Transformer A69 CB-F-1A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-RAX Auxiliary Relay Latch G07 DG-F-2A-A DG-G06-25DG Synchronizing Check Relay G06 DG-F-2A-A EDE-SYN-9701 Synchroscope G06 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -12 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-CP-75A (Continued) EDE-ZL-9701 Synchronizing Lights G06 DG-F-2A-A EDE-VM-9701-1 Synchronizing Voltmeter Incoming G06 DG-F-2A-A EDE-VM-9701-2 Synchronizing Voltmeter Running G06 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -13 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 EDE-SWG-5 4160 V Feed to 480 V Transformer EDE-X-5A for Substation Bus EDE-US-51 310007 A 310442 CB-F-1A-A X X X - A55 EDE-A55-52 4160 V Circuit Breaker A55 CB-F-1A-A A55-AB1 310102 A55a A55g A55b A55c A55d CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-SWG-5 EDE-SWG-6 EDE-X-5C EDE-US-61 EDE-A55-FU Fuses A55 CB-F-1A-A EDE-CS-9706 Control Switch A55 CB-F-1A-A EDE-A55-G,R,W Indicating Lights A55 CB-F-1A-A EDE-SS-9706 Selector Switch A55 CB-F-1A-A EDE-A55-52H Truck Operated Contact A55 CB-F-1A-A EDE-A55-86 Lockout Relay A55 CB-F-1A-A EDE-A55-TD2 Lockout Relay Test Device A55 CB-F-1A-A EDE-A55-50/51 Inst/Time Overcurrent Relays øA, øB, øC A55 CB-F-1A-A EDE-A55-CT Current Transformers (300/5) A55 CB-F-1A-A EDE-A55-AM Ammeter A55 CB-F-1A-A EDE-A55-AS Ammeter Switch A55 CB-F-1A-A EDE-A55-ATR Current Transducer A55 CB-F-1A-A EDE-A55-TD1 CT Test Device A55 CB-F-1A-A EDE-A55-51GS Ground Sensor Relay A55 CB-F-1A-A 8 EDE-SWG-5 4160 V Feed to 480 V Transformer EDE-X-5B for Substation Bus EDE-US-52 310007 A 310442 CB-F-1A-A X X X - A63 EDE-A63-52 4160 V Circuit Breaker A63 CB-F-1A-A A63-AC1 310102 A63a A63g A63b A63c A63d CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-SWG-5 EDE-SWG-6 EDE-X-5D EDE-US-62 EDE-A63-FU Fuses A63 CB-F-1A-A EDE-CS-9703 Control Switch A63 CB-F-1A-A EDE-A63-G,R,W Indicating Lights A63 CB-F-1A-A EDE-SS-9703 Selector Switch A63 CB-F-1A-A EDE-A63-52H Truck Operated Contact A63 CB-F-1A-A EDE-A63-86 Lockout Relay A63 CB-F-1A-A EDE-A63-TD2 Lockout Relay Test Device A63 CB-F-1A-A EDE-A63-50/51 Inst/Time Overcurrent Relays øA, øB, øC A63 CB-F-1A-A EDE-A63-CT Current Transformers (300/51) A63 CB-F-1A-A EDE-A63-AM Ammeter A63 CB-F-1A-A EDE-A63-AS Ammeter Switch A63 CB-F-1A-A EDE-A63-ATR Current Transducer A63 CB-F-1A-A EDE-A63-TD1 CT Test Device A63 CB-F-1A-A EDE-A63-51GS Ground Sensor Relay A63 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -14 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 EDE-US-51 480 V Bus 51 Unit Substation 310013 A 310442 CB-F-1A-A X X X - AB2 EDE-AB2-52 480 V ac Circuit Breaker AB2 CB-F-1A-A 310103 AB2a AB2b CBA-FN-19 CBA-FN-20 EDE-X-5A EDE-US-61 EDE-X-5A 4160-480 V Distribution Transformer AB1 CB-F-1A-A EDE-AB3-FU Fuses AB3 CB-F-1A-A EDE-AB1-LA 6 kV Lightning Arrestors (3) AB1 CB-F-1A-A EDE-AB2-CT Current Transformers (2000/5) AB2 CB-F-1A-A EDE-AB3-AM Ammeter AB3 CB-F-1A-A EDE-AB3-AS Ammeter Switch AB3 CB-F-1A-A 10 EDE-US-52 480 V Bus 51 Unit Substation 310013 A 310442 CB-F-1A-A X X X - AC2 EDE-AC2-52 480 V AC Circuit Breaker AC2 CB-F-1A-A 310103 AC2a AC2b CBA-FN-19 CBA-FN-20 EDE-X-5B EDE-US-62 EDE-X-5B 4160-480 V Distribution Transformer AC1 CB-F-1A-A EDE-AC3-FU Fuses AC3 CB-F-1A-A EDE-AC1-LA 6 kV Lightning Arrestors (3) AC1 CB-F-1A-A EDE-AC2-CT Current Transformers (2000/5) AC2 CB-F-1A-A EDE-AC3-AM Ammeter AC3 CB-F-1A-A EDE-AC3-AS Ammeter Switch AC3 CB-F-1A-A 11 EDE-US-51 480 V Feed to 460 V Motor Control Center 512 310013 A 310442 CB-F-1A-A X X X - AB6 EDE-AB6-52 480 V AC Circuit Breaker AB6 CB-F-1A-A AB6-B10 AB6-B10/1 310103 AB6 AB6 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-612 12 EDE-US-51 480 V Feed to 460V Motor Control Center 514 310013 A 310442 CB-F-1A-A X X X - A94 EDE-A94-52 480 V AC Circuit Breaker A94 CB-F-1A-A A94-C11 310103 A94 A94 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-614 13 EDE-US-51 480 V Feed to 460 V Motor Control Center 515 310013 A 310442 CB-F-1A-A X X X - AX8 EDE-AX8-52 480 V AC Circuit Breaker AX8 CB-F-1A-A AB6-B4D AB6-B4D/1 310103 AX8 AX8 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-615 14 EDE-US-52 480 V Feed to 460 V Motor Control Center 521 310013 A 310442 CB-F-1A-A X X X - AC8 EDE-AC8-52 480 V AC Circuit Breaker AC8 CB-F-1A-A AC8-B13 AC8-B13/1 310103 AC8 AC8 CBA-FN-19 CBA-FN-20 EDE-US-52 EDE-US-62 EDE-MCC-622 15 EDE-US-52 480 V Feed to 460 V Motor Control Center 522 310013 A 310442 CB-F-1A-A X X X - AW9 EDE-AW9-52 480 V AC Circuit Breaker AW9 CB-F-1A-A AW9-D12 AW9-G81/1 AW9-G81 310103 AW9a AW9c AW9b AW9c CBA-FN-19 CBA-FN-20 EDE-US-52 EDE-US-62 EDE-MCC-622 EDE-CS-9787-2 Control Switch with Indication G81 CB-F-1A-A EDE-SS-9787 Selector Switch G81 CB-F-1A-A EDE-AW9-52H Truck Operated Contact AW9 CB-F-1A-A EDE-AW9-FU Fuses AW9 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -15 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15a EDE-US-51 480 V Feed to 460 V Motor Control Center 511 310013 A 310442 CB-F-1A-A X X X - AB5 EDE-AB5-52 480 V AC Circuit Breaker AB5 CB-F-1A-A AB5-B09 AB5-B09/1 310103 AB5 AB5 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-611 16 EDE-US-51 Grounding Transformer 310012 A 310442 CB-F-1A-A X X X - AB3 EDE-AB3-XFMR 3-1ø 1 k VA Transformers AB3 CB-F-1A-A 310103 AB3b CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 Ground Transformer EDE-AB3-FU Fuses AB3 CB-F-1A-A EDE-AB3-RES Grounding Resistor AB3 CB-F-1A-A EDE-AB3-VM Ground Voltmeters (3) AB3 CB-F-1A-A EDE-AB3-64 Ground Relay AB3 CB-F-1A-A 17 EDE-US-52 Grounding Transformer 310013 A 310442 CB-F-1A-A X X X - AC3 EDE-AC3-XFMR 3-1ø 1 k VA Transformers AC3 CB-F-1A-A 310103 AC3b CBA-FN-19 CBA-FN-20 EDE-US-52 EDE-US-62 Ground Transformer EDE-AC3-FU Fuses AC3 CB-F-1A-A EDE-AC3-RES Grounding Resistor AC3 CB-F-1A-A EDE-AC3-VM Ground Voltmeters (3) AC3 CB-F-1A-A EDE-AC3-64 Ground Relay AC3 CB-F-1A-A 18 EDE-I-1E Uniterruptible Power Supply 310043 A 310442 CB-F-1A-A X X X - HF5 EDE-DD3-52 480 V AC Circuit Breaker DD3 CB-F-1A-A DD3-HF5/1 DM7-HF5/1 310105 DD3a DD3b CBA-FN-19 CBA-FN-20 EDE-MCC-512 EDE-SWG-11A EDE-I-1F EDE-DM7-72 125 V dc Circuit Breaker DM7 CB-F-1A-A EDE-HF5/2-52 460 V ac Inc. Line Circuit Breaker HF5 CB-F-1A-A EDE-HF5/1-72 125 V dc Inc. Line Circuit Breaker HF5 CB-F-1A-A EDE-HF5/3-52 120 V ac Output Circuit Breaker HF5 CB-F-1A-A 18A EDE-CP-1E Static Transfer Switch 310043 A 310442 CB-F-1A-A X X X - E1Y EDE-E1Y-F1 300A, 600 V Fuse E1Y CB-F-1A-A E1Y-HF5 E1Y-HF5/1 310105 DD3a DD3b CBA-FN-19 CBA-FN-20 EDE-I-1E EDE-CP-1F 19 EDE-PP-1E Vital Instrument Bus 310043 A 310442 CB-F-1A-A X X X - EH9 EDE-EH9/NC-52 120 V ac Circuit Breaker-Inc. Feed from EDE-CP-1E (Norm. Closed) EH9 CB-F-1A-A EH9-E1Y 310105 DD3a DD3b EH9a CBA-FN-19 CBA-FN-20 EDE-CP-1E EDE-PP-1F EDE-EH9/NO-52 120 V ac Circuit Breaker-Inc. Feed from ED-X-31E (Norm. Open) EH9 CB-F-1A-A 20 EDE-PP-11E Vital Instrument Bus 310043 A 310442 CB-F-1A-A X X X - E1S EDE-EH9/13-52 120 V ac Circuit Breaker EH9 CB-F-1A-A E1S-EH9 310105 DD3a DD3b E1Sa CBA-FN-19 CBA-FN-20 EDE-PP-1E EDE-PP-11F SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -16 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 21 EDE-BC-1A 125 V dc Battery Charger 310042 A 310442 CB-F-1A-A X X X - HR5 EDE-DB1-52 460 V ac Circuit Breaker DB1 CB-F-1A-A DB1-HR2 DB1-HR5 310107 DB1a DB1f DB1b DB1c CBA-FN-19 CBA-FN-20 EDE-MCC-512 EDE-BC-1B EDE-DB1-42 Contactor DB1 CB-F-1A-A EDE-DB1-42X Auxiliary Relay DB1 CB-F-1A-A DG-HR2-HR9 (K20) EPS Relay HR2 CB-F-1A-A EDE-HR5/1-52 460 V ac Circuit Breaker-Incoming Feed HR5 CB-F-1A-A EDE-DB1-FU Fuse DB1 CB-F-1A-A 22 EDE-B-1A 125 V dc Battery 310042 A 310442 CB-F-1D-A X X X - HV4 EDE-J75-FU-1,2,3,4 1600 A Fuses J75 CB-F-1A-A HV4-J75 HV4-J75/1 310107 DB1a DB1f DB1b DB1c CBA-FN-19 CBA-FN-20 CBA-FN-21A EDE-BC-1A EDE-SWG-11A EDE-B-1B EDE-J75-SH 1000A, 100MV Shunt J75 CB-F-1A-A EDE-J75-ATR Shunt Amplifier J75 CB-F-1A-A 23 EDE-SWG-11A 125 V dc Switchboard Auxiliary Buses 120 V ac and 125 V dc 310042 A 310442 CB-F-1A-A X X X - DM1 EDE-HR5/2-72 125 V dc Circuit Breaker HR5 CB-F-1A-A DM3-J75 DM3-J75/1 DM2-HR5 310107 DB1a DB1f DB1b DB1c CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-B-1A EDE-BC-1A EDE-PP-1E EDE-SWG-11B EDE-DL4-72 125 V dc Circuit Breaker DL4 CB-F-1A-A EDE-DM2-72 125 V dc Circuit Breaker DM2 CB-F-1A-A EDE-DM3-72 125 V dc Circuit Breaker DM3 CB-F-1A-A EDE-DM4-72 125 V dc Circuit Breaker DM4 CB-F-1A-A EDE-DM1-FU-1,2 15 amp Fuses DM1 CB-F-1A-A EDE-DM1-27BL Undervoltage Relay DM1 CB-F-1A-A EDE-DM1-27BLL Undervoltage Relay DM1 CB-F-1A-A EDE-DM1-VM DC Voltmeter DM1 CB-F-1A-A EDE-DM1-VTR Voltage Transducer DM1 CB-F-1A-A EDE-DM1-D10 Diodes DM1 CB-F-1A-A EDE-DM1-XS Selector Switch DM1 CB-F-1A-A EDE-DM1-AMY Ammeter Relay DM1 CB-F-1A-A EDE-EH9/5-52 120 V ac Circuit Breaker EH9 CB-F-1A-A DM1-EH9 DM1-J75/1 310105 EH9a EH9b 310107 DB1a DB1f DB1c 5a EDE-DM1-27BL Undervoltage Relay DM1 CB-F-1A-A EDE-DM1-62BL Timing Relay DM1 CB-F-1A-A EDE-DM1-27BLL Undervoltage Relay DM1 CB-F-1A-A EDE-DM1-62BLL Timing Relay DM1 CB-F-1A-A EDE-DM2-72 Breaker Operated Contact DM2 CB-F-1A-A EDE-DM2-72STC Circuit Breaker Shut Trip Coil DM2 CB-F-1A-A EDE-DM1-VTR Voltage Transducer DM1 CB-F-1A-A EDE-J75-ATR Current Transducer J75 CB-F-1A-A EDE-DM1-AMY Ammeter Relay DM1 CB-F-1A-A EDE-DM1-52 120 V ac Inc. Feed Circuit Breaker DM1 CB-F-1A-A EDE-DM1-FU 120 V AC 15A and 1A Fuses DM1 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -17 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 24 EDE-PP-111A 125 V dc Distribution Panel 310042 A 310442 CB-F-1A-A X X X - E93 EDE-DM5-72 125 V dc Circuit Breaker DM5 CB-F-1A-A DM5-E93 310107 DB1a DB1f E93a CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-PP-111B EDE-E93-72 125 V dc Circuit Breaker (Main) E93 CB-F-1A-A 25 EDE-PP-112A 125 V dc Distribution Panel 310042 A 310442 CB-F-1A-A X X X - E87 EDE-DM8-72 125 V ac Circuit Breaker DM8 CB-F-1A-A DM8-E87 310107 DB1a DB1f E87a CBA-FN-19 CVA-FN-20 EDE-SWG-11A EDE-PP-112B EDE-E87-72 125 V ac Circuit Breaker (Main) E87 CB-F-1A-A 26 EDE-PP-113A 125 V dc Distribution Panel 310042 A 310442 CB-F-1A-A X X X - E2T EDE-DM0-72 125 V dc Circuit Breaker DM0 CB-F-1A-A DM0-E2T 310107 DB1a DB1f DB1b E2Ta CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-PP-113B EDE-E2T-72 125 V dc Circuit Breaker (Main) E2T CB-F-1A-A 27 EDE-SWG-5 4160 V SWGR 125 V dc Control Bus A 310442 CB-F-1A-A X X X - A53 EDE-E93/1-72 125 V dc Circuit Breaker E93 CB-F-1A-A A53-E93 310107 E93a E93b 310102 5e 5f 5g 5h CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-SWG-6 EDE-A53-8 125 V dc Circuit Breaker (Main) A53 CB-F-1A-A 28 EDE-US-51 480 V Unit Substation 125 V dc Control Bus A 310442 CB-F-1A-A X X X - AB3 EDE-E93/2-72 125 V dc Circuit Breaker E93 CB-F-1A-A AB3-E93 310107 E93a E93b 310103 5m CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-US-61 EDE-AB3-8 125 V dc Circuit Breaker (Main) AB3 CB-F-1A-A 29 EDE-US-52 480 V Unit Substation 125 V dc Control Bus A 310442 CB-F-1A-A X X X - AC3 EDE-E93/3-72 125 V AC Circuit Breaker E93 CB-F-1A-A AC3-E93 310107 E93a E93b 310103 5n CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-US-62 EDE-AC3-8 125 V AC Circuit Breaker (Main) AC3 CB-F-1A-A 30 DG-CP-75A Diesel Generator 1A Control Panel Cubicle 3 125 V dc Supply 310010 310042 A 310524 DG-F-2A-A X X X - G10 EDE-DM9-72 125 V dc Circuit Breaker DM9 CB-F-1A-A DM9-G10 310102 DM9a DM9b 310107 DB1a DAH-FN-25A DAH-FN-26A EDE-SWG-11A CBA-FN-19 CBA-FN-20 DG-CP-76A DG-G10-72 125 V dc Circuit Breaker (Main) G10 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -18 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 31 EDE-SWG-6 4160 V Bus E6 UAT Incoming Line Swgr. 310008 B 310442 CB-F-1B-A X X X - A71 EDE-A71-52 4160 V Circuit Breaker A71 CB-F-1B-A A71-G19 A71-G19/2 A71-G20 A71-HRO GA6-GB0/5 A71-G19/1 A71-G19/3 A71-GB4 GAO-CB3/5 GC4-GC6/5 A71-G5Y A71-G5Y/1 A75-A7A A74-A7A/1 DM1-EH9 310102 A71a A71h A71b A71c A71d A71e CBA-FN-32 CBA-FN-33 ED-X-2B EDE-PP-111B DAH-FN-25B DAH-FN-26B EDE-SWG-5 UAT EDE-CS-9719-2 Control Switc h A71 CB-F-1B-A EDE-CS-9719-3 Control Switch with Indication G19 DG-F-2B-A EDE-A71-G,R,W Indicating Lights A71 CB-F-1B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-A71-52H Truck Operated Contact A71 CB-F-1B-A EDE-A71-FU Fuses A71 CB-F-1B-A EDE-A71-CT1 Current Transformers (2000/5) A71 CB-F-1B-A EDE-A71-TD-1 CT Test Device A71 CB-F-1B-A EDE-A71-AM Ammeter A71 CB-F-1B-A EDE-A71-AS Ammeter Switch A71 CB-F-1B-A EDE-A71-ATR Current Transducer A71 CB-F-1B-A EDE-A71-CT2 Current Transformers (4000/5) A71 CB-F-1B-A EDE-A87-PT Potential Transformer A87 CB-F-1B-A EDE-A71-TD-3 PT Test Device A71 CB-F-1B-A EDE-A71-VM Voltmeter A71 CB-F-1B-A EDE-A71-86 Lockout Relay A71 CB-F-1B-A EDE-A74-52S Mech. Operated Contact A74 CB-F-1B-A EDE-A72-52S Mech. Operated Contact A72 CB-F-1B-A DG-G20-25Y1 Auxiliary Sync. Check Relay G20 DG-F-2B-A EDE-A73-25U Synchronizing Check Relay A73 CB-F-1B-A EDE-SS-9719-1 Selector Switch G5Y DG-F-2B-A EDE-CS-9717-3 Control Switch G19 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-A72-86 Lockout Relay A72 CB-F-1B-A EDE-A89-86B Lockout Relay A89 CB-F-1B-A ED-86SB/2/1X -1 Lockout Relay GAO TB-F-1C-Z ED-86-2/2/B3 Lockout Relay GA6 TB-F-1C-Z ED-86UB/2/1X -2A Lockout Relay GA8 TB-F-1C-Z ED-86UB/2/1X -2B Lockout Relay GA8 TB-F-1C-Z ED-86BF-2/S/52/TG1 Lockout Relay GA9 TB-F-1C-Z ED-86GT/2/TG -1 Lockout Relay GA9 TB-F-1C-Z ED-86-1/2/B3 Lockout Relay GBO TB-F-1C-Z ED-86BF-2/2H Lockout Relay GB3 TB-F-1C-Z ED-86BF-2/2E Lockout Relay GB4 TB-F-1C-Z ED-86UP/2/1X -2A Lockout Relay GC2 TB-F-1C-Z ED-86UP/2/1X -2B Lockout Relay GC2 TB-F-1C-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -19 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-6 (Continued) ED-86BF-1/2/52/TG1 Lockout Relay GC3 TB-F-1C-Z ED-86SP/2/1X -1 Lockout Relay GC4 TB-F-1C-Z ED-86BF-1/2H Lockout Relay GC6 TB-F-1C-Z ED-86BF-1/2E Lockout Relay GC7 TB-F-1C-Z DG-HRO-RMO EPS Auxiliary Relay HRO CB-F-1B-A EDE-A71-3 Interposing Relay for SWYD Lockout Relays A71 CB-F-1B-A EDE-A71-TD-2 Lockout Relay Test Device (A71 -86) A71 CB-F-1B-A EDE-A71-TD-4 Interposing Relay Test Device (A71-3) A71 CB-F-1B-A ED-GA0-TD-2 Lockout Relay Test Device (86SB/2/1X -1) GA0 TB-F-1C-Z ED-GA6-TD-2 Lockout Relay Test Device (86 -2/2/B3) GA6 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2A) GA8 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2B) GA8 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86BF -2/2/52/TG1) GA9 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86GT/2/TG -1) GA9 TB-F-1C-Z ED-GB0-TD-2 Lockout Relay Test Device (86 -1/2/B3) GB0 TB-F-1C-Z ED-GB3-TD-2 Lockout Relay Test Device (86BF -2/2H) GB3 TB-F-1C-Z ED-GB4-TD-2 Lockout Relay Test Device (86BF -2/2E) GB4 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2A) GC2 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2B) GC2 TB-F-1C-Z ED-GC3-TD-2 Lockout Relay Test Device (86BF -1/2/52/TG1) GC3 TB-F-1C-Z ED-GC4-TD-2 Lockout Relay Test Device (86SP/2/1X -1) GC4 TB-F-1C-Z ED-GC6-TD-2 Lockout Relay Test Device (86BF -1/2H) GC6 TB-F-1C-Z ED-GC7-TD-2 Lockout Relay Test Device (86BF -1/2E) GC7 TB-F-1C-Z EDE-A71-51 Time Overcurrent Relays øA, øB, øC A71 CB-F-1B-A EDE-A71-51GS Ground Sensor Relay A71 CB-F-1B-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -20 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 32 EDE-SWG-6 Grounding Transforme r 310008 B 310442 CB-F-1B-A X X X - A87 EDE-A87-XFMR 3-1ø 15 k VA Transformers A87 CB-F-1B-A 310102 A87a CBA-FN-32 CBA-FN-33 EDE-SWG-6 EDE-SWG-5 Ground Transformer EDE-A87-FU 3-10A Fuses A87 CB-F-1B-A EDE-A87-52 120 V ac Circuit Breaker A87 CB-F-1B-A EDE-A87-RES Grounding Resistor A87 CB-F-1B-A EDE-A87-64 Ground Relay A87 CB-F-1B-A EDE-A87-TD-3 VM Test Device A87 CB-F-1B-A EDE-A87-VM (3) Ground Voltmeter s A87 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -21 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 33 EDE-SWG-6 4160 V Bus E6 RAT Incoming Line SWGR 310008 B 310442 CB-F-1A-A X X X - A72 EDE-A72-52 4160 V Circuit Breaker A72 CB-F-1B-A A72-G19 A72-G19/2 A72-G20 A72-HR4 GA7-GB7/5 GE6-GE7/5 A72-G19/1 A72-G19/3 A72-GB7 A72-HR0 GC1-GC0/5 A72-G5Y A72-G5Y/1 A74-A7A/2 310102 A72a A72j A72b A72c A72d A72e CBA-FN-32 CBA-FN-33 ED-X-3B EDE-PP-111B DAH-FN-25B DAH-FN-26B EDE-SWG-5 RAT EDE-CS-9717-2 Control Switch A72 CB-F-1B-A EDE-CS-9717-3 Control Switch with Indication G19 DG-F-2B-A EDE-A72-G,R,W Indicating Lights A72 CB-F-1B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-A72-52H Truck Operated Contact A72 CB-F-1B-A EDE-A72-FU Fuses A72 CB-F-1B-A EDE-A72-27/59 Under/Over Voltage Relay A72 CB-F-1B-A EDE-A72-27/59X1,X2 Under/Over Voltage Auxiliary Relay A72 CB-F-1B-A EDE-A72-CT1 Current Transformers (2000/5) A72 CB-F-1B-A EDE-A72-52Z Time Delay Relay A72 CB-F-1B-A EDE-SS-9717-1 Selector Switch G5Y DG-F-2B-A EDE-CS-9719-3 Control Switch G19 DG-F-2B-A EDE-A72-TD-1 CT Test Device A72 CB-F-1B-A EDE-A72-AM Ammeter A72 CB-F-1B-A EDE-A72-AS Ammeter Switch A72 CB-F-1B-A EDE-A72-ATR Current Transducer A72 CB-F-1B-A EDE-A72-CT2 Current Transformers (4000/5) A72 CB-F-1B-A EDE-A73-PT Potential Transformer A73 CB-F-1B-A EDE-A72-TD-3 PT Test Device A72 CB-F-1B-A EDE-A72-VM Voltmeter A72 CB-F-1B-A EDE-A72-52S Mechanically Operated Contact A72 CB-F-1B-A EDE-A72-86B Lockout Relay A89 CB-F-1B-A EDE-A72-86 Lockout Relay A72 CB-F-1B-A EDE-A72-86 Lockout Relay A71 CB-F-1B-A DG-HR4-RMO EPS Auxiliary Relay HR4 CB-F-1B-A DG-HRO-RMO EPS Auxiliary Relay HRO CB-F-1B-A EDE-A71-52S Mechanically Operated Contact A71 CB-F-1B-A EDE-A74-52S Mechanically Operated Contact A74 CB-F-1B-A EDE-SNS-9737-2 Synchronizing Switc h G18 DG-F-2B-A DG-G20-25Y1 Auxiliary Sync Check Relay G20 DG-F-2B-A EDE-A73-25RX Auxiliary Sync. Check Relay A73 CB-F-1B-A EDE-A73-25R Synchronizing Check Relay A73 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -22 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-6 (Continued) EDE-A72-62 & 62X Time Delay Relay A72 CB-F-1B-A EDE-A71-3 Interposing Relay for SWYD Lockout Relays A71 CB-F-1B-A EDE-A72-TD-2 Lockout Relay Test Device (A72 -86) A72 CB-F-1B-A EDE-TD-4 Interposing Relay Test Device (A72 -3) A72 CB-F-1B-A EDE-A72-27RB-1 Residual Undervoltage Relay A72 CB-F-1B-A EDE-A72-27RB-2 Residual Undervoltage Relay A72 CB-F-1B-A EDE-86RB/2/1X -3A Lockout Relay GA7 TB-F-1C-Z ED-86-2/2/B2 Lockout Relay GB7 TB-F-1C-Z ED-86-1/2/B2 Lockout Relay GCO TB-F-1C-Z ED-86RP/2/1X -3A Lockout Relay CG1 TB-F-1C-Z ED-86RP/2/1X -3B Lockout Relay GE6 TB-F-1C-Z ED-86RB/2/1X -3B Lockout Relay GE7 TB-F-1C-Z ED-GA7-TD-2 Lockout Relay Test Device (86RB/2/1x -3A) GA7 TB-F-1C-Z ED-GB7-TD-2 Lockout Relay Test Device (86 -2/2/B2) GB7 TB-F-1C-Z ED-GCO-TD-2 Lockout Relay Test Device (86 -1/2/B2) GCO TB-F-1C-Z ED-GC1-TD-2 Lockout Relay Test Device (86RP/2/1x -3A) GC1 TB-F-1C-Z ED-GE6-TD-2 Lockout Relay Test Device (86RP/2/1x -3B) GE6 TB-F-1C-Z ED-GE7-TD-2 Lockout Relay Test Device (86RB/2/1x -3B) GE7 TB-F-1C-Z EDE-A72-51 Time Overcurrent Relays øA, øB, øC A72 CB-F-1B-A EDE-A72-51GS Ground Sensor Relay A72 CB-F-1B-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -23 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 34 EDE-SWG-6 4160 V Bus E6 PT Compartment 310008 B 310442 CB-F-1B-A X X X - A73 EDE-A73-PT Potential Transformer A73 CB-F-1B-A A73-AE2 A73-G19 A73-HR4 AE2-AF7 AF7-EE6 AW2-EE6 A74-A7A/4 A74-A7A/5 A75-A7A/1 A75-A7A/1 310102 A73A A73d A73e A73h CBA-FN-32 CBA-FN-33 EDE-SWG-6 EDE-PP-111B DAH-FN-25B DAH-FN-26B EDE-SWG-5 PT EDE-A73-VM Voltmeter A73 CB-F-1B-A EDE-A73-VS Voltmeter Switch A73 CB-F-1B-A EDE-A73-TD-3 PT Test Device A73 CB-F-1B-A EDE-A73-VTR-1 Voltage Transducer A73 CB-F-1B-A EDE-A73-VTR-2 Voltage Transducer A73 CB-F-1B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-A73-25U Synchronizing Check Relay A73 CB-F-1B-A EDE-A73-25R Synchronizing Check Relay A73 CB-F-1B-A EDE-A74-52S Mechanically Operated Contact A74 CB-F-1B-A EDE-A73-27B-1 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-27B-2 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-TS-3 UV Relays Test Switch A73 CB-F-1B-A EDE-A73-27D-1 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-27D-1-RES Resistor A73 CB-F-1B-A EDE-A73-27D-2 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-27D-2-RES Resistor A73 CB-F-1B-A EDE-A73-TS-1 UV Relays Test Switch A73 CB-F-1B-A EDE-A72-27RB-1,2 Residual Undervoltage Relay A72 CB-F-1B-A EDE-A73-62B Time Delay Relay A73 CB-F-1B-A EDE-A73-62B-RES Resistor A73 CB-F-1B-A EDE-A73-TS-4 Test Switch EDE -62B A73 CB-F-1B-A EDE-A73-62BX-1 Auxiliary Relay A73 CB-F-1B-A EDE-A73-62BX Auxiliary Latch Relay A73 CB-F-1B-A EDE-A71-52S Mechanically Operated Contact A71 CB-F-1B-A EDE-AW3-94-5 Undervoltage Tripping Relay AW3 CB-F-1B-A EDE-A72-27/59X1 Under/Over Voltage Auxiliary Relay A72 CB-F-1B-A EDE-AF8-94-4 Undervoltage Tripping Relay AF8 CB-F-1B-A DG-HR4-RM0 EPS Auxiliary Relay HR4 CB-F-1B-A EDE-A73-94-1A Undervoltage Tripping Relay A73 CB-F-1B-A EDE-A73-94-1B Undervoltage Tripping Relay A73 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -24 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-6 (Continued) EDE-A73-94-2 Undervoltage Tripping Relay A73 CB-F-1B-A EDE-AE3-94-3 Undervoltage Tripping Relay AE3 CB-F-1B-A EDE-EE6-94-6 Tripping Relay EE6 CB-F-1B-A EDE-A73-FU 10A Fuses A73 CB-F-1B-A EDE-A73-62D Time Delay Relay A73 CB-F-1B-A EDE-A73-62D-RES Resistor A73 CB-F-1B-A EDE-A73-TS-2 Test Switch Relay 62D A73 CB-F-1B-A EDE-A73-62DX Auxiliary Relay A73 CB-F-1B-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -25 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 35 EDE-SWG-6 4160 V Bus E6 DG-1B Incoming Line SWGR 310010 310008 B 310442 CB-F-1B-A X X X - A74 EDE-A74-52 4160 V Circuit Breaker A74 CB-F-1B-A A74-G18/2 A74-G18/3 A74-G18/4 A74-G18/8 A74-G19 A74-G19/1 A74-G19/2 A74-HP1 G18-G30/7 A74-A7A/3 310102 A74a A74k A74b A74n A74c A74d A74e A74f CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B EDE-PP-111B DG-DG-1B EDE-SWG-5 DG-1A EDE-CS-9710-2 Control Switch A74 CB-F-1B-A EDE-CS-9710-3 Control Switch with Indication G18 DG-F-2B-A EDE-A74-G,R,W Indicating Lights A74 CB-F-1B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-A74-52H Truck Operated Contact A74 CB-F-1B-A EDE-A74-FU Fuses A74 CB-F-1B-A EDE-A74-CT Current Transformers (2000/5) A74 CB-F-1B-A EDE-A74-DCT Differential Current Transformers (2000/5) A74 CB-F-1B-A DG-HP1-DCT DG-1B Neutral Differential Current Transformers (2000/5) HP1 DG-F-2B-A DG-G18-CT Auxiliary Current Transformer (5:10) G18 DG-F-2B-A EDE-A74-AM Ammeter A74 CB-F-1B-A EDE-A74-AS-1 Ammeter Switch A74 CB-F-1B-A EDE-A74-ATR-1 Current Transducer A74 CB-F-1B-A EDE-A74-ATR-2 Current Transducer A74 CB-F-1B-A EDE-AM-9710-2 Ammeter G18 DG-F-2B-A EDE-G18-AS Ammeter Switch G18 DG-F-2B-A DG-SM-9587 Governor Control (2301A) G18 DG-F-2B-A EDE-A89-PT DG-1B Inc. Line Pot. Transformer (2) 4200-120 V A89 CB-F-1B-A EDE-A89-VM Voltmeter A89 CB-F-1B-A EDE-A89-VS Voltmeter Switch A89 CB-F-1B-A EDE-A89-TD-3 PT Test Device A89 CB-F-1B-A EDE-A89-VTR-1 Voltage Transducer A89 CB-F-1B-A EDE-A89-VTR-2 Voltage Transducer A89 CB-F-1B-A EDE-A74-27DG Undervoltage Relay A74 CB-F-1B-A EDE-A89-FTR-1 Frequency Transducer A89 CB-F-1B-A EDE-A89-FTR-2 Frequency Transducer A89 CB-F-1B-A EDE-A89-W/WH-TR Watt/Watthour Transducer A89 CB-F-1B-A EDE-A89-W/TR Watt Transducer A89 CB-F-1B-A EDE-A89-VAR-TR Var Transducer A89 CB-F-1B-A EDE-A74-TS Test Start Switch A74 CB-F-1B-A EDE-A74-52Z Time Delay Relay A74 CB-F-1B-A EDE-A74-81-RES Resistor A74 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -26 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-6 (Continued) EDE-A89-86B Lockout Relay A89 CB-F-1B-A EDE-A89-86DB Back-Up Lockout Relay A89 CB-F-1B-A EDE-A89-W Indicating Lights (A89-86B & A89 -86DB) A89 CB-F-1B-A EDE-A74-W Indicating Light (A74-86DP) A74 CB-F-1B-A EDE-A74-86DP Primary Lockout Relay A74 CB-F-1B-A EDE-A71-86 Lockout Relay A71 CB-F-1B-A EDE-A72-86 Lockout Relay A72 CB-F-1B-A EDE-A71-52S Mechanically Operated Contact A71 CB-F-1B-A EDE-A72-52S Mechanically Operated Contact A72 CB-F-1B-A EDE-A74-52S Mechanically Operated Contact A74 CB-F-1B-A EDE-A89-RLA LOCA Seal Relay A89 CB-F-1B-A DG-G20-25Y Auxiliary Sync Check Relay G20 DG-F-2B-A EDE-A89-RS Fast Closure Relay A89 CB-F-1B-A EDE-A74-81 Frequency Relay A74 CB-F-1B-A EDE-A74-87DP Primary Differential Relay A74 CB-F-1B-A EDE-A89-51B Time Overcurrent Relays øA, øB, øC A89 CB-F-1B-A EDE-A74-81X Auxiliary Frequency Relay A74 CB-F-1B-A EDE-A89-60 Voltage Balance Relay A89 CB-F-1B-A EDE-A89-60AX Auxiliary Voltage Balance Relay A89 CB-F-1B-A EDE-A89-60BX Auxiliary Voltage Balance Relay A89 CB-F-1B-A EDE-A89-40 Loss of Field Relays øA, øB A89 CB-F-1B-A EDE-A74-40X Auxiliary Loss of Field Relay A74 CB-F-1B-A EDE-A89-32 Power Directional Relay A89 CB-F-1B-A EDE-A89-TD-1 Lockout Relay Test Device (86B) A89 CB-F-1B-A EDE-A89-TD-2 Lockout Relay Test Device (86DB) A89 CB-F-1B-A EDE-A74-TD-2 Lockout Relay Test Device (86DP) A74 CB-F-1B-A DG-G19-R43L5 & R43L6 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -27 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-6 (Continued) DG-G30-5A Shutdown Relay G30 DG-F-2B-A EDE-A89-51V Time Overcurrent Voltage Restraint Relays øA, øB, øC A89 CB-F-1B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A EDE-A89-51GS Ground Sensor Relay A89 CB-F-1B-A EDE-A74-TD-1 Test Device A74 CB-F-1B-A EDE-A74-87DP Reactor Primary Differential Relay Reactor Assembly A74 CB-F-1B-A EDE-A74-81Y Time Delay Relay A74 CB-F-1B-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -28 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 36 DG-CP-76A Diesel Generator 1B Control Panel Cubicle 2 Synchronizing System 310010 B 310524 DG-F-2B-A X X X - G19 EDE-SS-9710 Selector Switch G18 DG-F-2B-A 310102 G19/2c G19/2g DAH-FN-25B DAH-FN-26B EDE-SWG-11B DG-CP-75A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A DG-G19-FU 125 V DC Fuses G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-RAX Auxiliary Relay, Latch G19 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-CS-9710-3 Control Switch G18 DG-F-2B-A EDE-CS-9717-3 Control Switch G19 DG-F-2B-A EDE-CS-9719-3 Control Switch G19 DG-F-2B-A DG-G18-25DG Synchronizing Check Relay G18 DG-F-2B-A DG-G20-25Y Auxiliary Synchronizing Check Relay G20 DG-F-2B-A DG-G20-25Y1 Auxiliary Synchronizing Check Relay G20 DG-F-2B-A EDE-A87-PT UAT X-2B Inc. Line Potential Transformer A87 CB-F-1B-A 7e 7g EDE-A73-PT RAT X-3B Inc. Line Potential Transformer A73 CB-F-1B-A EDE-A73-PT Bus E6 Potential Transformer A73 CB-F-1B-A EDE-A89-PT DG-1B Inc. Line Potential Transformer A89 CB-F-1B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-RAX Auxiliary Relay, Latch G19 DG-F-2B-A DG-G18-25DG Synchronizing Check Relay G18 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -29 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-CP-76A (Continued) EDE-SYN-9711 Synchroscope G18 DG-F-2B-A EDE-ZL-9711 Synchronizing Lights G18 DG-F-2B-A EDE-VM-9711-1 Synchronizing Voltmeter Incoming G18 DG-F-2B-A EDE-VM-9711-2 Synchronizing Voltmeter Running G18 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -30 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 37 EDE-SWG-6 4160 V Feed to 480 V Transformer EDE-X-5C for Substation Bus EDE-US-61 310008 B 310442 CB-F-1B-A X X X - A75 EDE-A75-52 4160 V Circuit Breaker A75 CB-F-1B-A A75-AD1 310102 A75a A75g A75b A75c A75d CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-SWG-6 EDE-SWG-5 EDE-X-5A EDE-US-51 EDE-A75-FU Fuses A75 CB-F-1B-A EDE-CS-9716 Control Switch A75 CB-F-1B-A EDE-A75-G,R,W Indicating Lights A75 CB-F-1B-A EDE-SS-9716 Selector Switch A75 CB-F-1B-A EDE-A75-52H Truck Operated Contact A75 CB-F-1B-A EDE-A75-86 Lockout Relay A75 CB-F-1B-A EDE-A75-TD-2 Lockout Relay Test Device A75 CB-F-1B-A EDE-A75-50/51 Inst/Time Overcurrent Relays øA, øB, øC A75 CB-F-1B-A EDE-A75-CT Current Transformers (300/5) A75 CB-F-1B-A EDE-A75-AM Ammeter A75 CB-F-1B-A EDE-A75-AS Ammeter Switch A75 CB-F-1B-A EDE-A75-ATR Current Transducer A75 CB-F-1B-A EDE-A75-TD-1 CT Test Device A75 CB-F-1B-A EDE-A75-51GS Ground Sensor Relay A75 CB-F-1B-A 38 EDE-SWG-6 4160 V Feed to 480 V Transformer EDE-X-5D for Substation Bus EDE-US-62 310008 B 310442 CB-F-1B-A X X X - A83 EDE-A83-52 4160 V Circuit Breaker A83 CB-F-1B-A A83-AE1 310102 A83a A83g A83b A83c A83d CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-SWG-6 EDE-SWG-5 EDE-X-5B EDE-US-52 EDE-A83-FU Fuses A83 CB-F-1B-A EDE-CS-9713 Control Switch A83 CB-F-1B-A EDE-A83-G,R,W Indicating Lights A83 CB-F-1B-A EDE-SS-9713 Selector Switch A83 CB-F-1B-A EDE-A83-52H Truck Operated Contact A83 CB-F-1B-A EDE-A83-86 Lockout Relay A83 CB-F-1B-A EDE-A83-TD-2 Lockout Relay Test Device A83 CB-F-1B-A EDE-A83-50/51 Inst/Time Overcurrent Relays øA, øB, øC A83 CB-F-1B-A EDE-A83-CT Current Transformers (300/5) A83 CB-F-1B-A EDE-A83-AM Ammeter A83 CB-F-1B-A EDE-A83-AS Ammeter Switch A83 CB-F-1B-A EDE-A83-ATR Current Transducer A83 CB-F-1B-A EDE-A83-TD-1 CT Test Device A83 CB-F-1B-A EDE-A83-51GS Ground Sensor Relay A83 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -31 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 39 EDE-US-61 480 V Bus 61 Unit Substation 310014 B 310442 CB-F-1B-A X X X - AD2 EDE-AD2-52 480 V AC Circuit Breaker AD2 CB-F-1B-A 310103 AD2a AD2b CBA-FN-32 CBA-FN-33 EDE-X-5C EDE-US-51 EDE-X-5C 4160-480 V Distribution Transformer AD1 CB-F-1B-A EDE-AD3-FU Fuses AD3 CB-F-1B-A EDE-AD1-LA 6 kV Lightning Arrestors (3) AD1 CB-F-1B-A EDE-AD2-CT Current Transformers (2000/5) AD2 CB-F-1B-A EDE-AD3-AM Ammeter AD3 CB-F-1B-A EDE-AD3-AS Ammeter Switch AD3 CB-F-1B-A 40 EDE-US-62 480 V Bus 62 Unit Substation 310014 B 310442 CB-F-1B-A X X X - AE2 EDE-AE2-52 480 V AC Circuit Breaker AE2 CB-F-1B-A 310103 AE2a AE2b CBA-FN-32 CBA-FN-33 EDE-X-5D EDE-US-52 EDE-X-5D 4160-480 V Distribution Transformer AE1 CB-F-1B-A EDE-AE3-FU Fuses AE3 CB-F-1B-A EDE-AE1-LA 6 kV Lightning Arrestors (3) AE1 CB-F-1B-A EDE-AE2-CT Current Transformers (2000/5) AE2 CB-F-1B-A EDE-AE3-AM Ammeter AE3 CB-F-1B-A EDE-AE3-AS Ammeter Switch AE3 CB-F-1B-A 41 EDE-US-61 480 V Feed to 460 V Motor Control 612 310014 B 310442 CB-F-1B-A X X X - AD6 EDE-AD6-52 480 V AC Circuit Breaker AD6 CB-F-1B-A AD6-B16 AD6-B16/1 310103 AD6 AD6 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-512 42 EDE-US-61 480 V Feed to 460 V Motor Control 614 310014 B 310442 CB-F-1B-A X X X - AA4 EDE-AA4-52 480 V AC Circuit Breaker AA4 CB-F-1B-A AA4-BF0 310103 AA4 AA4 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-514 43 EDE-US-61 480 V Feed to 460 V Motor Control 615 310014 B 310442 CB-F-1B-A X X X - AX9 EDE-AX9-52 480 V AC Circuit Breaker AX9 CB-F-1B-A AX9-B4E AX9-B4E/1 310103 AX9 AX9 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-515 44 EDE-US-62 480 V Feed to 460 V Motor Control 621 310014 B 310442 CB-F-1B-A X X X - AE8 EDE-AE8-52 480 V AC Circuit Breaker AE8 CB-F-1B-A AE8-B19 AE8-B19/1 310103 AE8 AE8 CBA-FN-32 CBA-FN-33 EDE-US-62 EDE-US-52 EDE-MCC-521 45 EDE-US-62 480 V Feed to 460 V Motor Control 622 310014 B 310442 CB-F-1B-A X X X - AW0 EDE-AW0-52 480 V AC Circuit Breaker AW0 CB-F-1B-A AW0-D13 AW0-GZ0 AW0-GZ0/1 310103 AWOa AWOe AWOb AWOc CBA-FN-32 CBA-FN-33 EDE-US-62 EDE-US-52 EDE-MCC-522 EDE-CS-9788-2 Control Switch with Indication GZ0 CB-F-1B-A EDE-SS-9788 Selector Switc h GZ0 CB-F-1B-A EDE-AW0-52H Truck Operated Contact AW0 CB-F-1B-A EDE-AW0-FU Fuses AW0 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -32 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 46 EDE-US-61 Grounding Transformer 310014 B 310442 CB-F-1B-A X X X - AD3 EDE-AD3-XFMR 3-1ø 1 kVA Transformers AD3 CB-F-1B-A - 310103 AE3b - CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 GRD XFMR EDE-AD3-FU Fuses AD3 CB-F-1B-A EDE-AD3-RES Grounding Resistor AD3 CB-F-1B-A EDE-AD3-VM Ground Voltmeters (3) AD3 CB-F-1B-A EDE-AD3-64 Ground Relay AD3 CB-F-1B-A 46a EDE-US-61 480 V Feed to 460 V Motor Control Center 611 310014 B 310442 CB-F-1B-A X X X - AD5 EDE-AD5-52 480 V AC Circuit Breaker AD5 CB-F-1B-A AD5-B15 AD5-B15/1 310103 AD5 AD5 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-511 47 EDE-US-62 Grounding Transformer 310014 B 310442 CB-F-1B-A X X X - AE3 EDE-AE3-XFMR 3-1ø 1 kVA Transformers AE3 CB-F-1B-A - 310103 AE3b - CBA-FN-32 CBA-FN-33 EDE-US-62 EDE-US-52 GRD XFMR EDE-AE3-FU Fuses AE3 CB-F-1B-A EDE-AE3-RES Grounding Resistor AE3 CB-F-1B-A EDE-AE3-VM Ground Voltmeters (3) AE3 CB-F-1B-A EDE-AE3-64 Ground Relay AE3 CB-F-1B-A 48 EDE-I-1F Uninterruptible Power Supply 310043 B 310442 CB-F-1B-A X X X - HF6 EDE-DD5-52 460 V AC Circuit Breaker DD5 CB-F-1B-A DD5-HF6/1 DN0-HF6/1 310105 DD5a DD5b CBA-FN-32 CBA-FN-33 EDE-MCC-612 EDE-SWG-11B EDE-I-1E EDE-DN0-72 125 V DC Circuit Breaker DN0 CB-F-1B-A EDE-HF6/2-52 460 V AC Inc. Line Circuit Breaker HF6 CB-F-1B-A EDE-HF6/1-72 125 V DC Inc. Line Circuit Breaker HF6 CB-F-1B-A EDE-HF6/3-52 120 V AC Output Circuit Breaker HF6 CB-F-1B-A 48A EDE-CP-1F Static Transfer Switch 310043 B 310442 CB-F-1B-A X X X - E2B EDE-E2B-F1 300A, 600 V Fuse E2B CB-F-1B-A E2B-HF6 E2B-HF6/1 310105 DD5a DD5b CBA-FN-32 CBA-FN-33 EDE-I-1F EDE-CP-1E 49 EDE-PP-1F Vital Instrument Bus 310043 B 310442 CB-F-1B-A X X X - EH0 EDE-EH0/NC-52 120 V AC Circuit Breaker - Inc. Line from EDE-CP-1F (Norm. Closed) EH0 CB-F-1B-A EH0-E2B 310105 DD5a DD5b EH0a CBA-FN-32 CBA-FN-33 EDE-CP-1F EDE-PP-1E EDE-EHO/NO-52 120 V AC Circuit Breaker - Inc. Line from ED-X-31F (Norm. Open) EHO CB-F-1B-A 50 EDE-PP-11F Vital Instrument Bus 310043 B 310442 CB-F-1B-A X X X - E1T EDE-EH0/13-52 120 V AC Circuit Breaker EH0 CB-F-1B-A E1T-EHO 310105 DD5a DD5b E1Ta CBA-FN-32 CBA-FN-33 EDE-PP-1F EDE-PP-11E SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -33 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 51 EDE-BC-1B 125 V DC Battery Charger 310042 B 310442 CB-F-1B-A X X X - HR6 EDE-DA1-52 460 V AC Circuit Breaker DA1 CB-F-1B-A DA1-HR4 DA1-HR6 310107 DA1a DA1f DA1b DA1c CBA-FN-32 CBA-FN-33 EDE-MCC-E612 EDE-BC-1A EDE-DA1-42 Contactor DA1 CB-F-1B-A EDE-DA1-42X Auxiliary Relay DA1 CB-F-1B-A DG-HR4-HR9(K20) EPS Relay HR4 CB-F-1B-A EDE-HR6/1-52 460 V AC Circuit Breaker - Incoming Feed HR6 CB-F-1B-A EDE-DA1-FU Fuse DA1 CB-F-1B-A 52 EDE-B-1B 125 V DC Battery 310042 B 310442 CB-F-1F-A X X X - HV5 EDE-J76-FU-1,2,3,4 1600A Fuses J76 CB-F-1B-A HV5-J76 NV5-J76/1 310107 DA1a DA1f DA1b DA1c CBA-FN-32 CBA-FN-33 CBA-FN-21B EDE-BC-1B EDE-SWG-11B EDE-B-1A EDE-J76-SH 1000A, 100 MV Shunt J76 CB-F-1B-A EDE-J76-ATR Shunt Amplifier J76 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -34 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 53 EDE-SWG-11B 125 V DC Switchboard Auxiliary Buses 120 V AC and 125 V DC 310042 B 310442 CB-F-1B-A X X X - DN3 EDE-HR6/2-72 125 V DC Circuit Breaker HR6 CB-F-1B-A DN5-J76 DN5-J76/1 DN4-HR6 310107 DA1a DA1f DA1b DA1c CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-1F EDE-B-1A EDE-BC-1A EDE-SWG-11A EDE-DL5-72 125 V DC Circuit Breaker DL5 CB-F-1B-A EDE-DN4-72 125 V DC Circuit Breaker DN4 CB-F-1B-A EDE-DN5-72 125 V DC Circuit Breaker DN5 CB-F-1B-A EDE-DN5-72 125 V DC Circuit Breaker DN6 CB-F-1B-A EDE-DN3-FU-1,2 10A Fuses DN3 CB-F-1B-A EDE-DN3-27BL Undervoltage Relay DN3 CB-F-1B-A EDE-DN3-27BLL Undervoltage Relay DN3 CB-F-1B-A EDE-DN3-VM DC Voltmeter DN3 CB-F-1B-A EDE-DN3-VTR Voltage Transducer DN3 CB-F-1B-A EDE-DN3-DIO Diodes DN3 CB-F-1B-A EDE-DN3-XS Selector Switch DN3 CB-F-1B-A EDE-DN3-AMY Ammeter Relay DN3 CB-F-1B-A EDE-EH0/5-52 120 V AC Circuit Breaker EH0 CB-F-1B-A DN3-EH0 DN3-J76/1 310105 EH0a EHOb 310107 DA1a DA1f DA1c 5b EDE-DN3-27BL Undervoltage Relay DN3 CB-F-1B-A EDE-DN3-62BL Timing Relay DN3 CB-F-1B-A EDE-DN3-27BLL Undervoltage Relay DN3 CB-F-1B-A EDE-DN3-62BLL Timing Relay DN3 CB-F-1B-A EDE-DN4-72 Breaker Operated Contact DN4 CB-F-1B-A EDE-DN4-72STC Circuit Breaker Shut Trip Coil DN4 CB-F-1B-A EDE-DN3-VTR Voltage Transducer DN3 CB-F-1B-A EDE-J76-ATR Current Transducer J76 CB-F-1B-A EDE-DN3-AMY Ammeter Relay DN3 CB-F-1B-A EDE-DN3-FU 120 V AC 15A and 1A Fuses DN3 CB-F-1B-A EDE-DN3-52 120 V AC Incoming Feed Circuit Breaker DN3 CB-F-1B-A 54 EDE-PP-111B 125 V DC Distribution Panel 310042 B 310442 CB-F-1B-A X X X - E94 EDE-DN7-72 125 V DC Circuit Breaker DN7 CB-F-1B-A DN7-E94 310107 DA1a DA1f E94a CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-111A EDE-E94-72 125 V DC Circuit Breaker (Main) E94 CB-F-1B-A 55 EDE-PP-112B 125 V DC Distribution Panel 310042 B 310442 CB-F-1B-A X X X - E88 EDE-DN9-72 125 V DC Circuit Breaker DN9 CB-F-1B-A DN9-E88 310107 DA1a DA1f E88a CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-112A EDE-E88-72 125 V DC Circuit Breaker (Main) E88 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -35 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 56 EDE-PP-113B 125 V DC Distribution Panel 310042 B 310442 CB-F-1B-A X X X - E2U EDE-DP2-72 125 V DC Circuit Breaker DP2 CB-F-1B-A DP2-E2U 310107 DA1a DA1f DA1b E2Ua CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-113A EDE-E2U-72 125 V DC Circuit Breaker (Main) E2U CB-F-1B-A 57 EDE-SWG-6 4160 V SWG 125 V DC Control Bus B 310442 CB-F-1B-A X X X - A73 EDE-E94/1-72 125 V DC Circuit Breaker E94 CB-F-1B-A A73-E94 310107 E94a E94b 310102 5i, 5j, 5k, 5l CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-SWG-5 EDE-A73-8 125 V DC Circuit Breaker (Main) A73 CB-F-1B-A 58 EDE-US-61 480 V Unit Substation 125 V DC Control Bus B 310442 CB-F-1B-A X X X - AD3 EDE-E94/2-72 125 V DC Circuit Breaker E94 CB-F-1B-A AD3-E94 310107 E94a E94b 310103 5q CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-US-51 EDE-AD3-8 125 V DC Circuit Breaker (Main) AD3 CB-F-1B-A 59 EDE-US-62 480 V Unit Substation 125 V DC Control Bus B 310442 CB-F-1B-A X X X - AE3 EDE-E94/3-72 125 V DC Circuit Breaker E94 CB-F-1B-A AE3-E94 310107 E94a E94b 310103 5r CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-US-52 EDE-AE3-8 125 V DC Circuit Breaker (Main) AE3 CB-F-1B-A 60 DG-CP-76A Diesel Generator 1B Control Panel Cubicle 3 125 V DC Supply 310010 310042 B 310524 DG-F-2B-A X X X - G20 EDE-DP1-72 125 V DC Circuit Breaker DP1 CB-F-1B-A DP1-G20 310102 DP1a DP1b 310107 DA1a DAH-FN-25B DAH-FN-26B EDE-SWG-11B CBA-FN-32 CBA-FN-33 DG-CP-75A DG-G20-72 125 V DC Circuit Breaker (Main) G20 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -1 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 DG-DG-1A Diesel Generator 1A DG-20462 A 310524 DG-F-2A-A X X X X HA1 DG-CS-9510-2 Control Switch (Push Button) G07 DG-F-2A-A A54-G06/5 E93-G29/1 A54-G29 G06-G29 G06-G29/1 G06-HR2 C06-G29/2 G07-G29 310857 E93/8a E93/8n E93/8b E93/8p E93/8c E93/8d E93/8e E93/8f E93/8g E93/8r CBA-FN-19 CBA-FN-20 DAH-FN-25A DAH-FN-26A EDE-PP-111A D/G Starting Air DG-DG-1B DG-CS-9511 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9512-3 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9512-4 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9517-2 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9518-2 Control Switch (Push Button) G07 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A DG-G29-OP2 Oil Pressure Relay G29 DG-F-2A-A DG-G29-CR1 Ready for Auto Start Relay G29 DG-F-2A-A DG-G29-4A Start Relay G29 DG-F-2A-A DG-G29-T2A Cranking Time Control Time Delay Relay G29 DG-F-2A-A DG-ZL-9580-9 Start Ckt No 1 Signal Indicating Light G07 DG-F-2A-A DG-G29-ES1 Emergency Start Relay G29 DG-F-2A-A DG-G10-TSR1 Test Start Relay G10 DG-F-2A-A DG-G10-TSR2 Test Start Relay G10 DG-F-2A-A DG-G10-TSR3 Test Start Relay G10 DG-F-2A-A DG-G10-RDT Ramp Down Time Relay G10 DG-F-2A-A DG-G07-IOT Idle Operate Time Relay G07 DG-F-2A-A DG-G06-LSRX Low Speed Auxiliary Relay G06 DG-F-2A-A DG-FY-AS1 Air Start Solenoid Valve G29 DG-F-2A-A DG-G29-OP3 Oil Pressure Relay G29 DG-F-2A-A DG-G29-CR2 Ready for Auto Start Relay G29 DG-F-2A-A DG-G29-4B Start Relay G29 DG-F-2A-A DG-G29-T2B Cranking Time Control Time Delay Relay G29 DG-F-2A-A DG-ZL-9580-10 Start Ckt No 2 Signal Indicating Light G07 DG-F-2A-A DG-G29-ES2 Emergency Start Relay G29 DG-F-2A-A DG-FY-AS2 Air Start Solenoid Valve G29 DG-F-2A-A DG-G29-OP4 Oil Pressure Relay G29 DG-F-2A-A DG-G29-5E Emergency Stop Relay G29 DG-F-2A-A DG-G29-5 Normal Stop Relay G29 DG-F-2A-A

.* Table notes on last page of table

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -2 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-G29-5A Shutdown Relay G29 DG-F-2A-A DG-FY-SDS Shutdown Solenoid Valve G29 DG-F-2A-A DG-FY-CSV-A Jacket Coolant Auxiliary Valves Solenoid G29 DG-F-2A-A DG-G29-T3A Alarm Set Time Delay Relay G29 DG-F-2A-A DG-G29-TR Engine Velocity Transmitter G29 DG-F-2A-A DG-FY-ISV-A Intercooler Auxiliary Valves Solenoid G29 DG-F-2A-A DG-G29-SG Signal Generator G29 DG-F-2A-A DG-G29-HSR High-Speed Relay G29 DG-F-2A-A DG-G29-LSR Low-Speed Relay G29 DG-F-2A-A DG-G29-ASR Starting Air Shutoff Relay G29 DG-F-2A-A DG-G29-IPC Coolant Pump Control Relay G29 DG-F-2A-A DG-G29-BDR Barring Device Relay G29 DG-F-2A-A DG-G29-ASA Air Start Relay G29 DG-F-2A-A DG-G29-ASB Air Start Relay G29 DG-F-2A-A EDE-ZL-9574 Monitoring Circuit Indicator Light G07 DG-F-2A-A DG-G29-TACH Tachometer G29 DG-F-2A-A DG-G29-SFR Start Failure Relay G29 DG-F-2A-A EDE-ZL-9574-1 Monitoring Circuit Indicating Light G29 DG-F-2A-A DG-G29-SDR Engine Trouble Shutdown Relay G29 DG-F-2A-A DG-G29-EOR Engine Overspeed Relay G29 DG-F-2A-A EDE-A69-RLA SI Signal Lockout Relay A69 CB-F-1A-A DG-G29-OTH High Oil Temperature Relay G29 DG-F-2A-A DG-G29-CTH High Coolant Temperature Relay G29 DG-F-2A-A DG-G29-ESX Emergency Start Auxiliary Relay G29 DG-F-2A-A EDE-A54-TD2 Test Device A54 CB-F-1A-A EDE-A69-TD2 Test Device A69 CB-F-1A-A DG-G29-EST Emergency Start Time Delay Relay G29 DG-F-2A-A DG-G29-RA1 Air Pressure Auxiliary Relay G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -3 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-G29-RA2 Air Pressure Auxiliary Relay G29 DG-F-2A-A DG-G29-CF3 Power Available Relay G29 DG-F-2A-A DG-G29-CF1 Power Available Relay G29 DG-F-2A-A DG-G29-CF2 Power Available Relay G29 DG-F-2A-A DG-G29-CF5 Power Available Relay G29 DG-F-2A-A DG-G29-OP1 Oil Pressure Relay G29 DG-F-2A-A DG-G29-FPL Fuel Pressure Relay G29 DG-F-2A-A DG-G29-CPL Jacket Coolant Pressure Relay G29 DG-F-2A-A DG-G29-IPL Intercooler Pressure Relay G29 DG-F-2A-A DG-PS-OPL1 Oil Low Pressure Switch G29 DG-F-2A-A DG-PS-PPLA Fuel Low Pressure Switch G29 DG-F-2A-A DG-PS-CPLA Jacket Coolant Low Pressure Switch G29 DG-F-2A-A DG-PS-IPLA Intercooler Low Pressure Switch G29 DG-F-2A-A DG-G29-OPC Oil Pump Control Relay G29 DG-F-2A-A DG-G29-FPC Auxiliary Fuel Oil Pump Control Relay G29 DG-F-2A-A DG-G29-CPC Coolant Pump Control Relay G29 DG-F-2A-A DG-G29-CF4 Power Available Relay G29 DG-F-2A-A DG-G07-R43L1 Selector Switch Auxiliary Latch Relay (Local) G07 DG-F-2A-A DG-G07-R43L2 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G07 DG-F-2A-A DG-G07-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G07 DG-F-2A-A DG-G07-R43R2 Selector Switch Auxiliary Latch Relay (Remote) G07 DG-F-2A-A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-HR2-PR1 ESP Auxiliary Relay HR2 CB-F-1A-A DG-HR2-PRIX EPS Auxiliary Relay HR2 CB-F-1A-A DG-G29-D1 P-H Junction Diode G29 DG-F-2A-A DG-SS-EOS Engine Overspeed Switch G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -4 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-PS-APL1 Air Pressure Low Switch G29 DG-F-2A-A DG-PS-APL2 Air Pressure Low Switch G29 DG-F-2A-A DG-PS-CPS Coolant Pressure Switch G29 DG-F-2A-A DG-PS-OPL2 Oil Low Pressure Switch G29 DG-F-2A-A DG-PS-OPL3 Oil Low Pressure Switch G29 DG-F-2A-A DG-PS-OPL4 Oil Low Pressure Switch G29 DG-F-2A-A DG-G29-CTH-1 Coolant High Temperature Auxiliary Relay G29 DG-F-2A-A DG-G29-OTH-1 Oil High Temperature Auxiliary Relay G29 DG-F-2A-A DG-ZS-BD1 Barring Device Position Switch G29 DG-F-2A-A DG-ZS-BD2 Barring Device Position Switch G29 DG-F-2A-A EDE-A54-86DP DG Primary Protection Lockout Relay A54 CB-F-1A-A EDE-A69-86DB DG Backup Protection Lockout Relay A69 CB-F-1A-A EDE-A54-TS Test Start Control Switch A54 CB-F-1A-A DG-G29-FU 10 Amp Fuses (10) G29 DG-F-2A-A DG-G29-TRP TR Control Power Relay G29 DG-F-2A-A DG-G29-5B Shutdown Auxiliary Relay G29 DG-F-2A-A EDE-G07-FU-17, 18 6 Amp Fuses (2) G07 DG-F-2A-A DM9-G10 310102 G07/2a G07/2g G07/2b G07/2c DM9a DM9b EDE-SS-9700 Selector Switch G06 DG-F-2A-A DAH-FN-25A DAH-FN-25B DG-CP-75A EDE-SWG-11A DG-G07-CF6 Auxiliary Relay G07 DG-F-2A-A DG-G07-R43L1 Selector Switch Auxiliary Latch Relay (Local) G07 DG-F-2A-A DG-G07-R43L3 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L5 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R2 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -5 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G07 DG-F-2A-A DG-G07-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G07 DG-F-2A-A EDE-G06-FU-9, 10 50 Amp Fuses G06 DG-F-2A-A A69-G06 G06-HF7 A69-HN0 DH9-G10 310102 HA1a HA1c HA1b HA1d DM9a DM9b DAH-FN-25A DAH-FN-26A CBA-FN-19 EDE-SWG-11A DG-A69, XFMR Grounding Transformer A69 CB-F-1A-A DG-HF7-XF DG Field HF7 DG-F-2A-A DG-G07-SERV-PC Static Exciter Voltage Regulator Power Chassis G06 DG-F-2A-A DG-SM-9585 Governor Control (2301A) G06 DG-F-2A-A DG-GT3-PT1 Potential Transformer GT3 DG-F-2A-A DG-GT3-PT2 Potential Transformer GT3 DG-F-2A-A DG-GT3-PPT4 Power Transformer GT3 DG-F-2A-A DG-HNO-NCB DG Neutral Connection Box HNO DG-F-2A-A DG-GT3-CCT Current Transformer 2000/5 GT3 DG-F-2A-A DG-G10-IDR1 Isochronous Droop Relay G10 DG-F-2A-A EDE-A69-60 Voltage Balance Relays A69 CB-F-1A-A DG-G06-K2 Field Flashing Contractor G06 DG-F-2A-A DG-G06-64F Generator Field Failure Relay G06 DG-F-2A-A DG-G10-SEVR-CC Static Exciter Voltage Regulator Control Chassis G10 DG-F-2A-A DG-GT3-XCT1, 2, 3 Generator Current Transformers (2000/5) GT3 DG-F-2A-A DG-VM-9702-2 Field Voltmeter G10 DG-F-2A-A DG-G10-DCT Field Voltage Transducer G10 DG-F-2A-A DG-G06-SH 50 mV Field Shunt G06 DG-F-2A-A DG-AM-9702-2 DC Field Ammeter G10 DG-F-2A-A DG-G10-ATR Current Transducer G10 DG-F-2A-A DG-G10-CF10 Loss of Power Relay G10 DG-F-2A-A DG-A69-64 Ground Fault Sensing Relay A69 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -6 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-G10-FU-22, 23 1 Amp Fuses G10 DG-F-2A-A DG-G07-IL10 Diode Failure Light G07 DG-F-2A-A EDE-G06-FU-1, 2 10 Amp Fuses (2) G06 DG-F-2A-A G06-G29/5 DM9-G10 310102 G06/1a G06/1f G06/1b G06/1c G06/1d DM9a DM9b DAH-FN-25A DAH-FN-26A DG-CP-75A EDE-SWG-11A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A EDE-CS-9820-2 Control Switch (Push Button) G10 DG-F-2A-A DG-G29-HSR High Speed Relay G29 DG-F-2A-A DG-G29-LSR Low Speed Relay G29 DG-F-2A-A DG-G29-ES1 Emergency Start Relay G29 DG-F-2A-A DG-G29-ES2 Emergency Start Relay G29 DG-F-2A-A DG-SS-9585 Selector Switch G07 DG-F-2A-A DG-ZL-9580-11 Field Flash Signal Indicating Light G10 DG-F-2A-A DG-G07-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G07 DG-F-2A-A DG-G29-5A DG - Shutdown Relay G29 DG-F-2A-A DG-G06-LSRX Low Speed Auxiliary Relay G06 DG-F-2A-A DG-G06-LSRXX Time Delay Relay G06 DG-F-2A-A EDE-CS-9801-1 Push Button G10 DG-F-2A-A EDE-CS-9801-2 Push Button G10 DG-F-2A-A DG-G06-SERV-PC Static Exciter Voltage Regulator Power Chassis G06 DG-F-2A-A DG-G10-NM Null Meter G10 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-CS-9821-2 Control Switch G10 DG-F-2A-A EDE-CS-9822-2 Control Switch G10 DG-F-2A-A DG-G10-RR Regulator Relay G10 DG-F-2A-A DG-G10-SERV-CC Static Exciter Voltage Regulatory Control Chassis DG-G10-CF-8 Loss of Power Relay G10 DG-F-2A-A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G10 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -7 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) EDE-G06-FU-3, 4 6 Amp Fuses (2) G06 DG-F-2A-A G06-G29/6 G06-G29/8 G06-G29/9 EC7-G10 EC7-G07 EC7-HR2 DM9-G10 310102 G06/2a G06/2d G06/2b G06/2e DM9a DM9b DAH-FN-25A DAH-FN-26A DG-CP-75A EDE-SWG-11A DG-C10-IDR1 Isochronous Droop Relay G10 DG-F-2A-A DG-G10-IDR2 Isochronous Droop Relay G10 DG-F-2A-A DG-SZ-9585 Governor Actuator G29 DG-F-2A-A DG-SC-9585 Digital Reference Unit (DRU) G06 DG-F-2A-A DG-SM-9585 2301A Governor Controller G06 DG-F-2A-A DG-ST-9585 Magnetic Pickup (MPU-1) G29 DG-F-2A-A DG-SS-9585 Selector Switch G07 DG-F-2A-A DG-G10-TSR1 Test Start Relay G10 DG-F-2A-A DG-G10-TSR2 Test Start Relay G10 DG-F-2A-A DG-G10-TSR3 Test Start Relay G10 DG-F-2A-A DG-G10-R21 Speed Adjust Auxiliary Relay G10 DG-F-2A-A DG-G10-RDT Ramp Down Time Relay G10 DG-F-2A-A DG-G07-IOT Idle Operate Time Relay G07 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-CS-9823-2 Control Switch G06 DG-F-2A-A DG-G06-LSRX Low Speed Auxiliary G06 DG-F-2A-A DG-G29-ES1 Emergency Start Auxiliary Relay G29 DG-F-2A-A DG-G29-ES2 Emergency Start Auxiliary Relay G29 DG-F-2A-A DG-G07-ESS Emergency Start Auxiliary Relay G07 DG-F-2A-A DG-G10-CF-9 Loss of Power Relay G10 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-HR2-PR1 EPS Auxiliary Relay HR2 CB-F-1A-A DG-HR2-HR8 EPS Auxiliary Relay HR2 CB-F-1A-A DG-EC7-R1 Auxiliary Relay EC7 DG-F-2A-A DG-G10-IDR4 Isochronous Droop Relay G10 DG-F-2A-A EDE-G10-FU-7, 8 10 Amp Fuses (2) G10 DG-F-2A-A A54-G10/1 A69-G10 G10-G29 DM9-G10 G10a G10e G10b G10c DM9a DM9b DAH-FN-25A DAH-FN-26A CBA-FN-19 CBA-FN-20 DG-CP-75A EDE-SWG-11A DG-G29-CR1 Auto Start Ready Relay G29 DG-F-2A-A DG-G29-CR2 Auto Start Ready Relay G29 DG-F-2A-A DG-G29-RA1 Air Pressure Auxiliary Relay G29 DG-F-2A-A DG-G29-RA2 Air Pressure Auxiliary Relay G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -8 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-G07-R43L3 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-ESS Emergency Start Auxiliary Relay G07 DG-F-2A-A DG-G10-RR Regulator Relay G10 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L5 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G06-64F Generator Field Ground Relay G06 DG-F-2A-A DG-G10-64FX Generator Field Ground Auxiliary Relay G10 DG-F-2A-A DG-G07-64FXA Generator Field Ground Auxiliary Relay G07 DG-F-2A-A EDE-CS-9824-2 Control Switch G10 DG-F-2A-A DG-G10-23 Thermostat G10 DG-F-2A-A DG-G10-23X Thermostat Auxiliary Relay G10 DG-F-2A-A DG-G07-R-DNA Diesel Motor Available Auxiliary Relay G07 DG-F-2A-A DG-G07-R-B/I S.W.C.T Bypass/INOP Auxiliary Relay G07 DG-F-2A-A DG-G10-IDR1 Isochronous Droop Relay G10 DG-F-2A-A DG-G10-IDR2 Isochronous Droop Relay G10 DG-F-2A-A DG-G10-IDR3 Isochronous Droop Relay G10 DG-F-2A-A EDE-ZL-9802-2 Indicating Light G07 DG-F-2A-A DG-G10-IDR4 Isochronous Droop Relay G10 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A51-52S Circuit Breaker Operated Contact A51 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -9 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) EDE-A52-52S Circuit Breaker Operated Contac t A52 CB-F-1A-A EDE-A54-52S Circuit Breaker Operated Contact A54 CB-F-1A-A EDE-A69-60AX Voltage Balance Auxiliary Relay A69 CB-F-1A-A DG-ZL-9580-3 Indicating Light G07 DG-F-2A-A DG-ZL-9518-2 Indicating Light G07 DG-F-2A-A EDE-ZL-9824-1 Indicating Light G10 DG-F-2A-A EDE-ZL-9824-2 Indicating Light G10 DG-F-2A-A DG-ZL-9580-2 Indicating Light G07 DG-F-2A-A DG-ZL-9580-4 Indicating Light G07 DG-F-2A-A DG-ZL-9580-5 Indicating Light G07 DG-F-2A-A DG-G10-CF8 Loss of Control Power Relay G10 DG-F-2A-A DG-G10-CF9 Loss of Control Power Relay G10 DG-F-2A-A DG-G10-CF10 Loss of Control Power Relay G10 DG-F-2A-A DG-G10-CR45 Annunciator Auxiliary Relay G10 DG-F-2A-A DG-G10-CR42 Annunciator Auxiliary Relay G10 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -10 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 DG-TK-45A Starting Air Compressor Skid Air Receiver Tank DG-20460 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-TK-45C Notes 1 and 5 3 DG-TK-45B Starting Air Compressor Skid Air Receiver Tank DG-20460 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-TK-45D Notes 1 and 5 4 DG-MM-8A Exhaust Silencer DG-20462 A 310525 DG-F-3E-A X X - - - - - - - - - - - DG-MM-8B Note 1 5 DG-F-36A Air Intake Filter DG-20462 A 310525 DG-F-3E-A X X - - - - - - - - - - - DG-F-36B Note 1 6 DG-TK-26A Fuel Oil Storage Tank DG-20459 A 310525 202264 DG-F-1A-A X X - - - - - - - - - - - DG-TK-26B Notes 1 and 2 7 DG-TK-78A Fuel Oil Day Tank DG-20459 A 310525 DG-F-3C-A X X - - - - - - - - - - - DG-TK-78B Note 1 8 DG-P-38A Fuel Oil Transfer Pump DG-20459 A 310524 202265 DG-F-1A-A X X X - H75 DG-BM-52 460 V AC Circuit Breaker BM7 CB-F-1A-A BE4-BM7 BM7-RT8 BM7-N75 310857 BM7a 8M7c CBA-FN-19 CBA-FN-20 DAH-FN-25A DAH-FN-26A EDE-MCC-521 DG-P-38B DG-CS-9503 Control Switch with Indication BE4 DG-F-2A-A DG-LS-FLC Fuel Low Level Switch RT8 DG-F-3C-A DG-BM7-42 Motor Starter BM7 CB-F-1A-A DG-BM7-49 Thermal Overload Relay BM7 CB-F-1A-A DG-BM7-FU Fuse BM7 CB-F-1A-A 9 DG-P-119A Engine-Driven Fuel Oil Pump DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-119B Notes 1 and 4 10 DG-P-115A Engine-Drive Fuel Oil Pump DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-115B Notes 1 and 4 11 DG-TK-102A Lube Oil Reservoir DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-TK-102B Notes 1 and 4 12 DG-P-228A Engine-Driver Rocker Arm Lube Pump DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-228B Notes 1 and 4 13 DG-E-41A Lube Oil Heat Exchanger DG-2045B A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-E-41B Notes 1 and 4 14 DG-TK-46A Diesel Generator 1A Component Cooling Water Expansion Tank DG-20461 A 310525 DG-F-3C-A X X - - - - - - - - - - - DG-TK-46B Notes 1 and 4 15 DG-E-42A Diesel Generator 1A Component Cooling Water Heat Exchanger DG-20461 A 310767 805217 PAB-F-3A-Z X X - - - - - - - - - - Service Water DG-E-42B Notes 1 and 3 16 DG-P-121A Engine-Driven Jacket Coolant Pump DG-20461 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-121B Notes 1 and 4 17 DG-P-231A Engine-Driven Air Coolant Pump DG-20461 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-231B Notes 1 and 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -11 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 17a DG-C-2A DG Starting Air Compressor DG-20460 A 310524 DG-F-2A-A X X X - NC3 DG-BM3-52 460 v AC Circuit Breaker BM3 DG-F-2A-A BM3-NC3 BM3-HM2 BM3-HR2 310857 BM3a BM3c DAH-FN-25A DAH-FN-26A EDE-MCC-511 DG-C-2-B Note 5 DG-CS-9559 Control Switch BM3 DG-F-2A-A DGA-PS-APCI Pressure Switch HM2 DG-F-2A-A DG-PS-APCZ Pressure Switch HM2 DG-F-2A-A DG-HR2-HR9 EPS Relay HR2 CB-F-1A-A DG-BM3-42 Motor Starter BM3 CB-F-1A-A DG-BM3-49 Thermal O. L. BM3 CB-F-1A-A DG-BM3-FU Fuse BM3 CB-F-1A-A 17b DG-SKD-17A Diesel Generator 1A Starting Air Compressor Skid DG-20460 A 310524 DG-F-2A-A X X X - HM2 DG-E39/4-52 120 v AC Circuit Breaker E39 DG-F-2A-A E39-HM2 BM3-HM2 310857 E39/4a E39/4b DAH-FN-25A DAH-FN-26A EDE-MCC-E511 120v AC Dist. Panel DG-SKD-17B Note 5 DG-HM2-52 120v AC Circuit Breaker HM2 DG-F-2A-A DG-HM2-ATM Auto Drain Timer HM2 DG-F-2A-A DG-V-253A Auto Drain Solenoid Vlv. HM2 DG-F-2A-A DG-HM2-ICT Motor Synchronous Timer HM2 DG-F-2A-A DG-V-279A Left Chamber Inlet Sol. Vlv. HM2 DG-F-2A-A DG-V-280A Right Chamber Inlet Sol. Vlv. HM2 DG-F-2A-A DG-V-285A Repressurizing Sol. Vlv HM2 DG-F-2A-A DG-V-288A Left Chamber Exhaust Sol. Vlv. HM2 DG-F-2A-A DG-V-289A Right Chamber Exhaust Sol. Vlv. HM2 DG-F-2A-A DG-V-HM2-KR Aux. Relay HM2 DG-F-2A-A DG-BM3-42 Motor Starter BM3 CB-F-1A-A 17c DG-C-18A DG Backup Operating Air Compressor DG-20460 A 310524 DG-F-2A-A X X X - ML7 DG-BS3-52 460 v AC Ckt Bkr. BS3 DG-F-2A-A BS3-ML7 BS3-HM2 310857 BS3a BS3c DAH-FN-25A DAH-FN-26A EDE-MCC-511 DG-C-18B Note 5 DG-BS3-42 Motor Starter BS3 DG-F-2A-A DG-BS3-49 Thermal O. L. BS3 DG-F-2A-A DG-BS3-FU Fuse BS3 DG-F-2A-A DG-CS-9526 Control Switch BS3 DG-F-2A-A DGA-PS-APC3 Pressure Switch HM2 DG-F-2A-A DG-PS-APC4 Pressure Switch HM2 DG-F-2A-A DG-V-325A Unloader Sol. Vlv. UB0 DG-F-2A-A B53-UB0 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -12 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 DG-DG-1B Diesel Generator 1B DG-20467 B 310524 DG-F-2B-A X X X X HA2 DG-CS-9520-2 Control Switch (Push Button) G19 DG-F-2B-A A74-G18/7 A74-G30/6 310857 E94/8a E94/8n CBA-FN-32 CBA-FN-33 DG-DG-1A DG-CS-9521 Control Switch (Push Button) G19 DG-F-2B-A E94-G30/1 G18-G30 E94/8b E94/8p E94/8c E94/8r DAH-FN-25B DAH-FN-26B DG-CS-9522-3 Control Switch (Push Button) G19 DG-F-2B-A G18-G30/1 G18-G30/2 E94/8d E94/8e EDE-PP-11B D/G Starting Air DG-CS-9522-4 Control Switch (Push Button) G19 DG-F-2B-A G18-HR4 G19-G30 E94/8f E94/8g DG-CS-9527-2 Control Switch (Push Button) G19 DG-F-2B-A G19-G30/6 G18-G30/8 E94/8s DG-CS-9528-2 Control Switch (Push Button) G19 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A DG-G30-OP2 Oil Pressure Relay G30 DG-F-2B-A DG-G30-CR1 Ready for Auto Start Relay G30 DG-F-2B-A DG-G30-4A Start Relay G30 DG-F-2B-A DG-G30-T2A Cranking Time Control Time Delay Relay G30 DG-F-2B-A DG-ZL-9590-9 Start Ckt No 1 Signal Indicating Light G19 DG-F-2B-A DG-G30-ES1 Emergency Start Relay G30 DG-F-2B-A DG-G20-TSR1 Test Start Relay G30 DG-F-2B-A DG-G20-TSR2 Test Start Relay G20 DG-F-2B-A DG-G20-TSR3 Test Start Relay G20 DG-F-2B-A DG-G20-RDT Ramp Down Time Relay G20 DG-F-2B-A DG-G19-IOT Idle Operate Time Relay G19 DG-F-2B-A DG-G18-LSRX Low Speed Auxiliary Relay G18 DG-F-2B-A DG-FY-AS1 Air Start Solenoid Valve G30 DG-F-2B-A DG-G30-OP3 Oil Pressure Relay G30 DG-F-2B-A DG-G30-CR2 Ready for Auto Start Relay G30 DG-F-2B-A DG-G30-TACH Tachometer G30 DG-F-2B-A DG-G30-4B Start Relay G30 DG-F-2B-A DG-G30-T2B Cranking Time Control Time Delay Relay G30 DG-F-2B-A DG-ZL-9590-10 Start Ckt No 2 Signal Indicating Light G19 DG-F-2B-A DG-G30-ES2 Emergency Start Relay G30 DG-F-2B-A DG-FY-AS2 Air Start Solenoid Valve G30 DG-F-2B-A DG-G30-OP4 Oil Pressure Relay G30 DG-F-2B-A DG-G30-5E Emergency Stop Relay G30 DG-F-2B-A DG-G30-5 Normal Stop Relay G30 DG-F-2B-A DG-G30-5A Shutdown Relay G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -13 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-FY-SDS Shutdown Solenoid Valve G30 DG-F-2B-A DG-G30-T3A Alarm Set Time Delay Relay G30 DG-F-2B-A DG-G30-TR Engine Velocity Transmitter G30 DG-F-28-A DG-G30-SG Signal Generator G30 DG-F-2B-A DG-G30-HSR High Speed Relay G30 DG-F-2B-A DG-G30-LSR Low Speed Relay G30 DG-F-2B-A DG-G30-ASR Starting Air Shutoff Relay G30 DG-F-2B-A DG-G30-ASA Air Start Relay G30 DG-F-2B-A DG-G30-ASB Air Start Relay G30 DG-F-2B-A DG-G30-BDR Barring Device Relay G30 DG-F-2B-A DG-G30-SFR Start Failure Relay G30 DG-F-2B-A DG-G30-SDR Engine Trouble Shutdown Relay G30 DG-F-2B-A DG-G30-EOR Engine Overspeed Relay G30 DG-F-2B-A EDE-A89-RLA SI Signal Lockout Relay A89 CB-F-1B-A DG-G30-OTH High Oil Temperature Relay G30 DG-F-2B-A DG-G30-CTH High Coolant Temperature Relay G30 DG-F-2B-A EDE-A74-TD2 Test Device A74 CB-F-1B-A EDE-A89-TD2 Test Device A89 CB-F-1B-A DG-G30-EST Emergency Start Time Delay Relay G30 DG-F-2B-A DG-G30-ESX Emergency Start Auxiliary Relay G30 DG-F-2B-A DG-G30-RA1 Air Pressure Auxiliary Relay G30 DG-F-2B-A DG-G30-RA2 Air Pressure Auxiliary Relay G30 DG-F-2B-A DG-G30-CF3 Power Available Relay G30 DG-F-2B-A DG-G30-CF4 Power Available Relay G30 DG-F-2B-A DG-G19-R43L1 Selector Switch Auxiliary Latch Relay (Local) G19 DG-F-2B-A DG-G19-R43L2 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G19 DG-F-2B-A DG-G30-FU 10 Amp Fuses (10) G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -14 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G19-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G19 DG-F-2B-A DG-G19-R43R2 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-HR4-PR1 EPS Auxiliary Relay HR4 CB-F-1B-A DG-HR4-PRIX EPS Auxiliary Relay HR4 CB-F-1B-A DG-SS-EOS Engine Overspeed Switch G30 DG-F-2B-A DG-PS-APL1 Air Pressure Low Switch G30 DG-F-2B-A DG-PS-APL2 Air Pressure Low Switch G30 DG-F-2B-A DG-PS-CPS Coolant Pressure Switch G30 DG-F-2B-A DG-PS-OPL2 Oil Low Pressure Switch G30 DG-F-2B-A DG-PS-OPL3 Oil Low Pressure Switch G30 DG-F-2B-A DG-G19-FU 10 Amp Fuses (20) G19 DG-F-2B-A DG-G19-R43L5 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-PS-OPL4 Oil Low Pressure Switch G30 DG-F-2B-A DG-G30-CTH-1 Coolant High Temperature Auxiliary Relay G30 DG-F-2B-A DG-G30-OTH-1 Oil High Temperature Auxiliary Relay G30 DG-F-2B-A DG-ZS-BD1 Barring Device Position Switch G30 DG-F-2B-A DG-G30-D1 P-N Junction Diode G30 DG-F-2B-A DG-ZS-BD2 Barring Device Position Switc h G30 DG-F-2B-A EDE-A74-86DP DG Primary Protection Lockout Relay A74 CB-F-1B-A EDE-A89-86DB DG Backup Protection Lockout Relay A89 CB-F-1B-A EDE-A74-TS Test Start Control Switch A74 CB-F-1B-A DG-G30-CF1 Power Available Relay G30 DG-F-2B-A DG-G30-CF2 Power Available Relay G30 DG-F-2B-A EDE-ZL-9594 Monitoring Circuit Indicating Light G19 DG-F-2B-A EDE-ZL-9594-1 Monitoring Circuit Indicating Light G30 DG-F-2B-A DG-PS-OPL1 Oil Low Pressure Switch G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -15 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G30-OP1 Oil Pressure Relay G30 DG-F-2B-A DG-PS-FPLA Fuel Low Pressure Switch G30 DG-F-2B-A DG-G30-FPL Fuel Pressure Relay G30 DG-F-2B-A DG-PS-CPLA Jacket Coolant Low Pressure Switch G30 DG-F-2B-A DG-G30-CPL Jacket Coolant Pressure Relay G30 DG-F-28-A DG-PS-IPLA Intercooler Low Pressure Switch G30 DG-F-2B-A DG-G30-IPL Intercoolant Pressure Relay G30 DG-F-2B-A DG-G30-CF5 Power Available Relay G30 DG-F-2B-A DG-G30-OPC Oil Pump Control Relay G30 DG-F-2B-A DG-G30-FPC Auxiliary Fuel Oil Pump Control Relay G30 DG-F-2B-A DG-G30-CPC Coolant Pump Control Relay G30 DG-F-2B-A DG-G30-5B Shutdown Auxiliary Relay G30 DG-F-2B-A DG-G30-TRP TR Control Power Relay G30 DG-F-2B-A DG-FY-CSV-B Jacket Coolant Auxiliary Valves Solenoid G30 DG-F-2B-A DG-G30-IPC Coolant Pump Control Relay G30 DG-F-2B-A DG-FY-ISV-B Intercoolant Auxiliary Valves Solenoid G30 DG-F-2B-A EDE-G19-FU-17, 18 6 Amp Fuses (2) G19 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A DG-G19-CF6 Auxiliary Relay G19 DG-F-2B-A DPI-G20 310102 DG-G19-R43L1 Selector Switch Auxiliary Latch Relay (Local) G19 DG-F-2B-A G19/2a G19/2g G19/2b G19/2c DP1A DP1b DAH-FN-25B DAH-FN-26B DG-CP-75B DG-G19-R43L2 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A EDE-SWG-11B DG-G19-R43L3 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L5 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G19 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -16 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G19-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G19 DG-F-2B-A DG-G19-R43R2 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43L6 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-FU17B, 18B 6 Amp Fuses (2) G19 DG-F-2B-A EDE-G18-FU-9, 10 50 Amp Fuses G18 DG-F-2B-A DG-A89-XFMR Grounding Transformer A89 CB-F-1B-A A89-G18 G18-HF8 A89-HP1 DP1-G20 310102 HA2a HA2c HA2b HA2d DP1a DP1b DAH-FN-25B DAH-FN-26B CBA-FN-32 CBA-FN-33 EDE-SWG-11B DG-HF8-XF D-F Field HF8 DG-F-2B-A DG-G18-SEVR-PC Static Exciter Voltage Regulator Power Chassis G18 DG-F-2B-A DG-SM-9587 Governor Control (2301A) G18 DG-F-2B-A DG-G20-SEVR-CC Voltage Regulator Control Chassis G20 DG-F-2B-A DG-GT4-PT1 Potential Transformer GT4 DG-F-2B-A DG-GT4-PT2 Potential Transformer GT4 DG-F-2B-A DG-GT4-PPT4 Power Transformer GT4 DG-F-2B-A DG-GT4-CCT Current Transformer 2000/5 GT4 DG-F-2B-A DG-G20-IDR1 Isochronous Droop Relay G20 DG-F-2B-A EDE-A89-60 Voltage Balance Relays A89 CB-F-1B-A DG-G20-64F Generator Field Failure Relay G20 DG-F-2B-A DG-HP1-NCB DG Neutral Connection Box HP1 DG-F-2B-A DG-GT4-XCT1, 2, 3 Generator Current Transformers (2000/5) A, B, C GT4 DG-F-2B-A DG-VM-9712-2 Field Voltmeter G20 DG-F-2B-A DG-G20-DCT Field Voltage Transducer G20 DG-F-2B-A DG-G18-SH 50 mV Field Shunt G18 DG-F-2B-A DG-AM-9712-2 DG Field Ammeter G20 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -17 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G20-ATR Current Transducer G20 DG-F-2B-A DG-G20-CF10 Loss of Power Relay G20 DG-F-2B-A DG-A89-64 Ground Fault Sensing Relay A89 CB-F-1B-A DG-G20-FU-22, 23 1 Amp Fuses G20 DG-F-2B-A DG-G19-IL10 Diode Failure Light G19 DG-F-2B-A DG-G20-K2 Field Flashing Contactor G20 DG-F-2B-A EDE-G18-FU-1, 2, 1B, 2B 10 Amp Fuses (4) G18 DG-F-2B-A G18-G30/5 DP1-G20 310102 G18/1a G18/1f DAH-FN-25B DAH-FN-26B DG-G19-R34R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A G18/1b G18/1c G18/1d DC-CP-75B EDE-SWG-11B EDE-CS-9825-2 Control Switch (Push Button) G20 DG-F-2B-A DP1a DP1b DG-G30-HSR High Speed Relay G30 DG-F-2B-A DG-G30-LSR Low Speed Relay G30 DG-F-2B-A DG-G30-ES1 Emergency Start Relay G30 DG-F-2B-A DG-G30-ES2 Emergency Start Relay G30 DG-F-2B-A DG-SS-9587 Selector Switch G19 DG-F-2B-A DG-ZL-9590-11 Field Flash Signal Indicating Light G20 DG-F-2B-A DG-G19-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G19 DG-G30-5A DG Shutdown Relay G30 DG-F-2B-A DG-G18-LSRX Low Speed Auxiliary Relay G30 DG-F-2B-A DG-G18-LSRXX Time Delay Relay G18 DG-F-2B-A EDE-CS-9811-1 Push Button EDE-CS-9811-2 Push Button G18 DG-F-2B-A DG-G18-SEVR-PC Static Exciter Voltage Regulator Power Chassis G20 DG-F-2B-A EDE-G20-NM Null Meter G20 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-CS-9826-2 Control Switch G20 DG-F-2B-A EDE-CS-9827-2 Control Switch G20 DG-F-2B-A DG-G20-RR Regulator Relay G20 DG-F-2B-A DG-G20-SEVR-CC Static Exciter Voltage Regulator Control Chassis G20 DG-F-2B-A DG-G20-CF8 Loss of Power Relay G20 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A EDE-G18-FU-3, 4, 3B, 4B 6 Amp Fuses (4) G18 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -18 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G20-IDR1 Isochronous Droop Relay G20 DG-F-2B-A G18-G30/6 G18-G30/9 G18/2a G18/2d G18/2b DAH-FN-25B DAH-FN-26B DG-G20-IDR2 Isochronous Droop Relay G20 DG-F-2B-A G18-G30/A ED9-G20 ED9-G19 ED9-HR4 G18/2e DG-CP-75B EDE-SWG-75B DG-SZ-9587 Governor Actuator G30 DG-F-2B-A DP1-G20 DP1a DP1b DG-SC-9587 Digital Reference Unit (DRU) G18 DG-F-2B-A DG-SM-9587 2301A Governor Controller G18 DG-F-2B-A DG-ST-9587 Magnetic Pickup (MPU-1) G30 DG-F-2B-A DG-SS-9587 Selector Switch G19 DG-F-2B-A DG-G20-TSR1 Test Start Relay G20 DG-F-2B-A DG-G20-TSR2 Test Start Relay G20 DG-F-2B-A DG-G20-TSR3 Test Start Relay G20 DG-F-2B-A DG-G20-R21 Speed Adjust Auxiliary Relay G20 DG-F-2B-A DG-G20-RDT Ramp Down Time Relay G20 DG-F-2B-A DG-G19-IOT Idle Operate Time Relay G19 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-CS-9828-2 Control Switch G18 DG-F-2B-A DG-G18-LSRX Auxiliary Relay G18 DG-F-2B-A DG-G30-ES1 Emergency Start Auxiliary Relay G30 DG-F-2B-A DG-G19-ESS Emergency Start Auxiliary Relay G19 DG-F-2B-A DG-G30-ES2 Emergency Start Auxiliary Relay G30 DG-F-2B-A DG-G20-CF-9 Loss of Power Relay G20 DG-F-2B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-HR4-PR1 EPS Auxiliary Relay HR4 CB-F-1B-A DG-HR4-HR8 EPS Auxiliary Relay HR4 CF-F-1B-A DG-ED9-R1 Auxiliary Relay ED9 CB-F-1B-A DG-G20-IDR4 Isochronous Droop Relay G20 DG-F-2B-A EDE-G20-FU-7, 8, 7B, 8B 10 Amp Fuses (4) G20 DG-F-2B-A A74-G20/1 G20-G30 G20a G20e G20b DAH-FN-25B DAH-FN-26B DG-G30-CR1 Auto Start Ready Relay G30 DG-F-2B-A A89-G20 DP1-G20 G20c DP1a DP1b CBA-FN-32 CBA-FN-33 DG-G30-CR2 Auto Start Ready Relay G30 DG-F-2B-A DG-CP-75B EDE-SWG-11B DG-G30-RA1 Air Pressure Auxiliary Relay G30 DG-F-2B-A DG-G30-RA2 Air Pressure Auxiliary Relay G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -19 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G19-R43L6 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R-DNA Diesel Not Available Auxiliary Relay G19 DG-F-2B-A DG-G19-R-B/I S.W.C.T Bypass/Inoperable Auxiliary Relay G19 DG-F-2B-A DG-G19-R43L3 Selector Switch Auxiliary Relay G19 DG-F-2B-A DG-G19-ESS Emergency Start Auxiliary Relay G19 DG-F-2B-A DG-G20-RR Regulator Relay G20 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L5 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G18-64F Generator Field Ground Relay G18 DG-F-2B-A DG-G20-64FX Generator Field Ground Auxiliary Relay G20 DG-F-2B-A DG-G19-64FXA Generator Field Ground Auxiliary Relay G19 DG-F-2B-A EDE-CS-9829-2 Control Switch G20 DG-F-2B-A DG-G19-23 Thermostat G19 DG-F-2B-A DG-G20-23X Thermostat Auxiliary Relay G20 DG-F-2B-A DG-G20-IDR1 Isochronous Droop Relay G20 DG-F-2B-A DG-G20-IDR2 Isochronous Droop Relay G20 DG-F-2B-A DG-G20-IDR3 Isochronous Droop Relay G20 DG-F-2B-A DG-G20-IDR4 Isochronous Droop Relay G20 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -20 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) EDE-A71-52S Circuit Breaker Operated Contact A71 CB-F-1B-A EDE-A72-52S Circuit Breaker Operated Contact A72 CB-F-1B-A EDE-A74-52S Circuit Breaker Operated Contact A74 CB-F-1B-A EDE-A89-60AX Voltage Balance Auxiliary Relay A89 CG-F-1B-A DG-ZL-9590-2 Indicating Light G19 DG-F-2B-A DG-ZL-9590-3 Indicating Light G19 DG-F-2B-A DG-ZL-9528-2 Indicating Light G20 DG-F-2B-A EDE-ZL-9829-1 Indicating Light G19 DG-F-2B-A EDE-ZL-9812-2 Indicating Light G19 DG-F-2B-A EDE-ZL-9829-2 Indicating Light G20 DG-F-2B-A DG-ZL-9590-4 Indicating Light G19 DG-F-2B-A DG-ZL-9590-5 Indicating Light G19 DG-F-2B-A DG-G20-CF8 Loss of Control Power Relay G20 DG-F-2B-A DG-G20-CF9 Loss of Control Power Relay G20 DG-F-2B-A DG-G20-CF10 Loss of Control Power Relay G20 DG-F-2B-A DG-G20-CR45 Annunciator Auxiliary Relay G20 DG-F-2B-A DG-C20-CR42 Annunciator Auxiliary Relay G20 DG-F-2B-A 19 DG-TK-45C Starting Air Compressor Skid Air Receiver Tank DG-20465 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-TK-45A Notes 1 and 7 20 DG-TK-45D Starting Air Compressor Skid Air Receiver Tank DG-20465 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-TK-45B Notes 1 and 7 21 DG-MM-8B Exhaust Silencer DG-20467 B 310525 DG-F-3F-A X X - - - - - - - - - - - DG-MM-8A Note 1 22 DG-F-36B Air Intake Filter DG-20467 B 310525 DG-F-3F-A X X - - - - - - - - - - - DG-F-36A Note 1 23 DG-TK-26B Fuel Oil Storage Tank DG-20464 B 310524 202264 DG-F-1B-A X X - - - - - - - - - - - DG-TK-26A Notes 1 and 2 24 DG-TK-78B Fuel Oil Day Tank DG-20459 B 310525 DG-F-3D-A X X - - - - - - - - - - - DG-TK-78A Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -21 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 25 DG-P-38B Fuel Oil Transfer Pump DG-20464 B 310524 202264 DG-F-1B-A X X X - N76 DG-BP7-52 460 V AC Circuit Breaker BP7 CB-F-1B-A BE5-BP7 BP7-RU1 BP7-N76 310857 BP7a BP7c CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B DG-F-38A - DG-CS-9506 Control Switch with Indication BE5 DG-F-2B-A DG-LS-FLC Fuel Low Level Control Switch RU1 DG-F-3D-A DG-BP7-42 Motor Starter BP7 CB-F-1B-A DG-BP7-49 Thermal Overload Relay BP7 CB-F-18-A DG-BP7-FU Fuse BP7 CB-F-1B-A 26 DG-P-119B Engine-Driven Fuel Oil Pump DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - DG-P-119A Notes 1 and 6 27 DG-P-115B Engine Driven Lube Oil Pump DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-115A Notes 1 and 6 28 DG-TK-102B Lube Oil Reservoir DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-TK-102A Notes 1 and 6 29 DG-P-228B Engine-Driven Rocker Arm Lube Pump DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-228A Notes 1 and 6 30 DG-E-41B Lube Oil Heat Exchanger DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-E-41A Notes 1 and 6 31 DG-TK-46B Diesel Generator 1B Component Cooling Water Expansion Tank DG-20466 B 310525 DG-F-3D-A X X - - - - - - - - - - - DG-TK-46A Note 1 32 DG-E-42B Diesel Generator 1B Component Cooling Water Heat Exchanger DG-20466 B 310767 805217 PAB-F-3A-Z X X - - - - - - - - - - Service Water DG-E-42A Notes 1 and 3 33 DG-P-121B Engine-Driven Jacket Coolant Pump DG-20466 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-121A Notes 1 and 4 34 DG-P-231B Engine-Driven Air Coolant Pump DG-20466 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-231A Notes 1 and 6 35 DG-PV-7A-2 Lube Oil Cooler Differential Pressure Control Valve DG-20461 A 310524 DG-F-2A-A X X - X HA1 DG-PT-7A-3 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-PV-7B-2 Note 8 DG-PT-7A-4 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A DG-PDT-7A-2 Differential Pressure Transmitter G29 DG-F-2A-A DG-PDC-7A-2 Differential Pressure Controller G29 DG-F-2A-A 36 DG-TCV-7A-2 Air Cooler Coolant Temperature Control Valve DG-20461 A 310524 DG-F-2A-A X X X X HA1 DG-CP-907A Air Cooler Coolant and Jacket Coolant Temp. Control Panel G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-TCV-7B-2 Note 8 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -22 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 37 DG-PV-7A-1 Jacket Coolant Differential Pressure Control Valve DG-20461 A 310524 DG-F-2A-A X X - X HA1 DG-PT-7A-1 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-PV-7B-1 Note 9 DG-PT-7A-2 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A DG-PDT-7A-1 Differential Pressure Transmitter G29 DG-F-2A-A DG-PDC-7A-1 Differential Pressure Controller G29 DG-F-2A-A 38 DG-TCV-7A-1 Air Cooler Coolant Temperature Control Valve DG-20461 A 310524 DG-F-2A-A X X X X HA1 DG-CP-907A Air Cooler Coolant and Jacket Coolant Temp. Control Panel G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-TCV-7B-1 Note 9 39 DG-F-64A Lube Oil Filter DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-F-64B Notes 1 and 4 40 DG-F-23A Lube Oil Duplex Filter DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-F-23B Notes 1 and 4 41 DG-S-4A Lube Oil Strainer DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-S-4B Notes 1 and 4 42 DG-S-85A Lube Oil Sump Suction Strainer DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-S-85B Notes 1 and 4 43 DG-S-5A Fuel Oil Storage Tank Duplex Strainer DG-20459 A 310524 202264 DG-F-1A-A X X - - - - - - - - - - - DG-S-5B Notes 1 and 2 44 DG-S-6A Fuel Oil Day Tank Duplex Strainer DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-S-6B Notes 1 and 4 45 DG-F-65A Fuel Oil Duplex Filter DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-F-65B Notes 1 and 4 46 DG-TK-110A Fuel Oil Accumulator Tank DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-TK-110B Notes 1 and 4 47 DG-PV-7B-2 Lube Oil Cooler Differential Pressure Control Valve DG-20466 B 310524 DG-F-2B-A X X - X HA2 DG-PT-7B-3 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DC-PV-7A-2 Note 10 DG-PT-7B-4 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A DG-PDT-7B-2 Differential Pressure Transmitter G30 DG-F-2B-A DG-PDC-7B-2 Differential Pressure Controller G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -23 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 48 DG-TCV-7B-2 Air Cooler Coolant Temperature Control Valve DG-20466 B 310524 DG-F-2B-A X X X X HA2 DG-CP-907B Air Cooler Coolant and Jacket Coolant Temp. Control Panel G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DG-TCV-7A-2 Note 10 49 DG-PV-7B-1 Jacket Coolant Differential Pressure Control Valve DG-20466 B 310524 DG-F-2B-A X X - X HA2 DG-PT-7B-1 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DG-PV-7A-1 Note 11 DG-PT-7B-2 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A DG-PDT-7B-1 Differential Pressure Transmitte r G30 DG-F-2B-A DG-PDC-7B-1 Differential Pressure Controller G30 DG-F-2B-A 50 DG-TCV-7B-1 Jacket Coolant Temperature Control Valve DG-20466 B 310524 DG-F-2B-A X X X X HA2 DG-CP-907B Air Cooler Coolant and Jacket Coolant Temp. Control Panel G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DG-TCV-7A-1 Note 11 51 DG-F-64B Lube Oil Filter DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-64A Notes 1 and 6 52 DG-F-23B Lube Oil Duplex Filter DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-23A Notes 1 and 6 53 DG-S-4B Lube Oil Strainer DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-S-4A Notes 1 and 6 54 DG-S-85B Lube Oil Sump Suction Strainer DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-S-85A Notes 1 and 6 55 DG-S-5B Fuel Oil Storage Tank Duplex Strainer DG-20464 B 310524 202264 DG-F-1B-A X X - - - - - - - - - - - DG-S-5A Notes 1 and 2 56 DG-S-6B Fuel Oil Day Tank Duplex Strainer DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-S-6A Notes 1 and 6 57 DG-F-65B Fuel Oil Duplex Filter DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-65A Notes 1 and 6 58 DG-TK-110B Fuel Oil Accumulator Tank DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-TK-110A Notes 1 and 6 59 DG-C-2B DG Starting Air Compressor DG-20465 B 310524 DG-F-2B-A X X X - NC4 DG-BP3-52 DG-CS-9569 DGB-PS-APCI DGB-PS-APCZ DG-HR4-HR9 DG-BP3-42 DG-BP3-49 DG-BP3-FU 460 v AC Circuit Breaker Control Switch Pressure Switch Pressure Switch EPS Relay Motor Starter Thermal O. L. Fuse BP3 BP3 HM3 HM3 HR3 BP3 BP3 BP3 DG-F-2B-A DG-F-2B-A DG-F-2B-A DG-F-2B-A CB-F-1B-A CB-F-1B-A CB-F-1B-A CB-F-1B-A BP3-NC4 BP3-HM3 BP3-HR4 310857 BP3a BP3c DAH-FN-25B DAH-FN-26B EDE-MCC-611 DG-C-2A Note 7 59a DG-C-18B DG Backup Operating Air Compressor DG-20465 B 310524 DG-F-2B-A X X X - ML8 DG-BS5-52 DG-BS5-42 DG-BS5-49 DG-BS5-FU DG-CS-9536 DGB-PS-APC3 DGB-PS-APC4 DG-V-325B 460 v AC Ckt Bkr. Motor Starter Thermal O. L. Fuse Control Switch Pressure Switch Pressure Switch Unloader Sol. Vlv. BS5 BS5 BS5 BS5 BS5 HM3 HM3 UB1 DG-F-2B-A DG-F-2B-A DG-F-2B-A DG-F-2B-A DG-F-2B-A DG-F-2B-A DG-F-2B-A DG-F-2B-A BS5-ML8 BS5-HM3 BS5-UB1 310857 BS5a BS5c DAH-FN-25B DAH-FN-26B EDE-MCC-611 DG-C-18A Note 7 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -24 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 60 DG-SKD-17B Diesel Generator 1B Starting Air Compressor Skid DG-20465 B 310524 DG-F-2B-A X X X - HM3 DG-E47/4-52 120 v AC Circuit Breaker E47 DG-F-2B-A E47-HM3 BP3-HM3/1 310857 E47/4a E47/4b DAH-FN-25B DAH-FN-26B EDE-MCC-E611 120 v AC Dist. Panel DG-SKD-17A Note 7 DG-HM3-52 120 v AC Circuit Breaker HM3 DG-F-2B-A DG-HM3-ATM Auto Drain Timer HM3 DG-F-2B-A DG-V-253B Auto Drain Solenoid Vlv. HM3 DG-F-2B-A DG-HM3-ICT Motor Synchronous Timer HM3 DG-F-2B-A DG-V-279B Left Chamber inlet Sol. Vlv. HM3 DG-F-2B-A DG-V-280B Right Chamber inlet Sol. Vlv. HM3 DG-F-2B-A DG-V-285B Repressurizing Sol. Vlv. HM3 DG-F-2B-A DG-V-288B Left Chamber Exhaust Sol. Vlv. HM3 DG-F-2B-A DG-V-289B Right Chamber Exhaust Sol. Vlv. HM3 DG-F-2B-A DG-V-HM3-KR Aux. Relay HM3 DG-F-2B-A DG-BP3-42 Motor Starter BP3 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -25 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 61 DG-CP-907A Diesel Generator 1A Air Cooler Coolant & Jacket Coolant Temp. Control Panel DG-20461 A 310524 DG-F-2A-A X X X X G29 DG-EH9/17-52 120 v AC Circuit Breaker EH9 CB-F-1A-A EH9-G29 310857 EH9/17a EH9/17c CBA-FN-19 CBA-FN-20 DAH-FN-25A DAH-FN-26A EDE-PP-1E DG-CP-907B Notes 8 & 9 DGA-TIC-9602 Jacket Coolant Temp. Indi. Controller G29 DG-F-2A-A DGA-TT-9602-1 & 2 Jacket Coolant Temp. Transmitters G29 DG-F-2A-A DGA-TE-9602-1 & 2 Jacket Coolant Temp. Elements G29 DG-F-2A-A DGA-ZC-9602 Jacket Coolant Temp . Dig. Vlv. Controller (I/P) G29 DG-F-2A-A DGA-ZY-9602 Jacket Coolant Temp. Cont. Vlv. Pos. Sensor G29 DG-F-2A-A DGA-TIC-9612 Air Cooler Coolant Temp. Indi. Controller G29 DG-F-2A-A DGA-TT-9612-1 & 2 Air Cooler Coolant Temp. Transmitters G29 DG-F-2A-A DGA-TE-9612-1 & 2 Air Cooler Coolant Temp. Elements G29 DG-F-2A-A DGA-ZC-9612 Air Cooler Coolant Temp. Dig. Vlv. Controller (I/P) G29 DG-F-2A-A DGA-ZY-9612 Air Cooler Coolant Temp. Vlv. Pos. Sensor G29 DG-F-2A-A DG-G29-TIC-RX Auxiliary Relay G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -26 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 62 DG-CP-907B Diesel Generator 1B Air Cooler Coolant & Jacket Coolant Temp. Control Panel DG-20466 B 310524 DG-F-2B-A X X X X G30 DG-EH0/17-52 120 v AC Circuit Breaker EH0 CB-F-1B-A EH0-G30 310857 EH0/17a EH0/17c CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B EDE-PP-1F DG-CP-907A Notes 10 & 11 DGB-TIC-9602 Jacket Coolant Temp. Indi. Controller G30 DG-F-2B-A DGB-TT-9602-1 & 2 Jacket Coolant Temp. Transmitters G30 DG-F-2B-A DGB-TE-9602-1 & 2 Jacket Coolant Temp. Elements G30 DG-F-2B-A DGB-ZC-9602 Jacket Coolant Temp . Dig. Vlv. Controller (I/P) G30 DG-F-2B-A DGB-ZY-9602 Jacket Coolant Temp. Cont. Vlv. Pos. Sensor G30 DG-F-2B-A DGB-TIC-9612 Air Cooler Coolant Temp. Indi. Controller G30 DG-F-2B-A DGB-TT-9612-1 & 2 Air Cooler Coolant Temp. Transmitters G30 DG-F-2B-A DGB-TE-9612-1 & 2 Air Cooler Coolant Temp. Elements G30 DG-F-2B-A DGB-ZC-9612 Air Cooler Coolant Temp. Dig. Vlv. Controller (I/P) G30 DG-F-2B-A DGB-ZY-9612 Air Cooler Coolant Temp. Vlv. Pos. Sensor G30 DG-F-2B-A DG-G30-TIC-RX Auxiliary Relay G30 DG-F-2B-A . NOTES 1. The equipment is mechanical with no electrical requirement.

2. Electrical conduit plan drawing, 310524, is listed only to show the fire zone corresponding to the location of this equipment in the Diesel Generator Building as identified in 202263.
3. Electrical conduit plan drawing, 310767, is listed only to show fire zone corresponding to the location of this equipment in the Primary Auxiliary Building as identified in 805217. 4. This equipment is located in the Diesel Generator Skid DG

-SKD-7A. 5. This equipment is located in the Diesel Generator Skid DG-SKD-17A. 6. This equipment is located in the Diesel Generator Skid DG -SKD-7B. 7. This equipment is located in the Diesel Generator Skid DG -SKD-17B. 8. The pneumatic control diagram of this equipment is shown in the DG air cooler water control loop diagram, 506403.

9. The pneumatic control diagram of this equipment is shown in the diesel engine jacket cooling water control loop diagram, 506404. 10. The pneumatic control diagram of this equipment is shown in the DG air cooler water control loop diagram, 506405. 11. The pneumatic control diagram of this equipment is shown in the DG diesel engine jacket cooling water loop diagram, 506406.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 10 Table RSS 3.1.3.19-1 FUNCTION: COMMUNICATION PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 SPC-RSS 1-NHY-311868 A X X X - G07 SPC-J-1 SPC JACK G07 DG-F-2A-A G06-G5Y - - CB-F-1A-A G19 SPC-J-2 G19 DG-F-2B-A G06-G81 311868 RSS RSSa, b 310816 301820 301841 CB-F-1B-A G2G SPC-J-3 G2G CB-F-1A-A G19-G5X Remote Safe

Shutdown Sound

Powered Telephone

Loop DG-F-2A-A G2J SPC-J-4 G2J CB-F-1B-A G19-XM9 DG-F-2B-A GK0 SPC-J-5 GK0 RHR-F-4B-Z G2J-GKO RHR-F-4A-Z GQ1 SPC-J-6 GQ1 RHR-F-4A-Z G2J-XM9 RHR-F-4B-Z G5X SPC-J-7 G5X DG-F-2A-A G81-G2J G5Y SPC-J-8 G5Y DG-F-2B-A GKO-GQ1

.* Table notes on last page of table SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Raceway Arrangement Drawings (Typical)

Rev. 5 Appendix IV Page IV-1 Raceway Arrangement Drawings (Typical) This section originally contained photographs of marked raceway arrangement drawings for several fire areas/zones of the plant containing redundant Safe Shutdown equipment and cables. The typical drawings included in this section were provided to only show the methodology used for the original report preparation. These typica l drawings were not intended to be updated for report revisions. These original drawings were typical of the raceway arrangement drawings which were marked for each fire area/zone containing safe shutdown equipment and cables. The latest design documents, not these typical dr awings, should be used to evaluate the Safe Shutdown Capability.

SEABROOK STATION Fire Protection of Safe Shutdown Capability (10CFR50, Appendix R) Revision 1 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Introduction Rev. 5Section 1 Page 1-1 INTRODUCTION General Design Criterion 3, "Fire Protection," of Appendix A, "General Design Criteria for Nuclear Power Plants," to 10 CF R Part 50" Licensing of Producti on and Utilizatio n Facilities" requires that structures, systems and components important to safety shall be designed and located to minimize, consistent with other safety requirements, the probability and effects of fires. Appendix R, "Fire Protection Program for Nuclear Power Facilities Opera ting Prior to January 1, 1979" to 10 CFR Part 50 was issued on Novemb er 19, 1980 (45 FR 76602). Paragraph III.G, "Fire Protection of Safe Shutdow n Capability," requires that fire damage be limited so that: a. One train of systems necessary to achieve and maintain hot shutdown conditions from either the control room or emergenc y control station(s) is free of fire damage; and b. Systems necessary to achieve and maintain cold shutdown from either the control room or emergency control station(s) can be repaired within 72 hours. This requires each licensee to assess those areas of the plant"....where cables or equipment, including associated non-safety circuits that could prevent operation or cause maloperation due to hot shorts, open circuits, or shorts to ground of redundant trains of systems necessary to achieve and maintain hot shutdown conditions are located in the same fire area..." The regulation establishes separation requirements for areas outside of primary containment and inside noninerted containment. Appendix R, paragraph III.L, "Alternative and Dedicated Shutdown Capability," establishes the following performance goals for the shutdown functions: a. The reactivity control function shall be capable of achieving and maintaining cold shutdown reactivity conditions. b. The reactor coolant makeup function shall be capable of maintaining the reactor coolant level within level i ndication in the pressurizer. c. The reactor heat removal function shall be capable of achieving and maintaining decay heat removal. d. The process monitoring function shall be capable of providing di rect readings of the process variables necessary to perform and control the above functions. e. The supporting functions shall be cap able of providing process cooling, lubrication, etc., necessary to permit operation of the equipment used for Safe Shutdown functions. Branch Technical Position CMEB 9.5-1 "Guidelines for Fire Protection for Nuclear Power Plants," Rev. 2, July 1981 reiterates the above requirements in Section C.5.b and C.5.c. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Introduction Rev. 5Section 1 Page 1-2 By letters dated March 16, 1981 (from R.L. Tedesco to W.C. Tallman) and September 30, 1981 (from D.G. Eisenhut to W.C. Tallman) the Nuclear Regulatory Commission (NRC) transmitted "Request for Additional Information, Seabrook Station, Units 1 & 2, Fire Protection Program, Power System." This document requested New Hampshire Yankee (NHY) to provide information relative to the equipment and cabling required to achieve and maintain hot and/or cold shutdown. By letter dated July 27, 1982 (from F.J. Miraglia to W.C. Tallman) the NRC transmitted Auxiliary System Branch RAI's. By letter of May 15, 1981 (SBN-160), NHY committed itself to undertaking a comprehensive program to address the concerns identified in the NRC letters. This report and appendix detail the program a nd the analyses and evaluations emanating from it. The "Report" is comprised of the following: 1. An "Introduction" section.

2. A "Report Preparation/Maintenance" section which summarizes the program utilized to perform the Safe Shutdown Capability review and to maintain the safe shutdown capability as plant modifications are implemented. 3. Safe Shutdown Capability 3.1 The "Discussion of Bases and Positi ons" section provide s a discussion of the bases and positions established fo r the review of the safe shutdown performance goals. 3.2 The "Main Control Room Safe Shut down" Section provides a discussion of the Shutdown Locations, Functions/Systems which satisfy the performance goals; a Safe Shutdown Equipment List; and an analysis and evaluation of each fire area. 3.3 The "Alternative Safe Shutdown Using Remote Safe Shutdown Facilities" discusses the bases and positions established for the review; a review of the Alternative Safe Shutdown capabilities; an Alternative Safe Shutdown Equipment List; and an an alysis and evaluation. 3.4 The "Alternative Safe Shutdown - Emergency Feedwater Pumphouse Fire" section discusses the location and shutdown capabilities, and an analysis and evaluation of this fire area. 3.5 The "High-Low Pressure Interfaces" s ection provides a general discussion, a list of interfaces, a High Low Pressure Interface Safe Shutdown Equipment List and an analysis and evaluation. 3.6 The "Associated Circuits" section provides a definition of associated circuits of concern and a discussion of the me thodology used to address the various types of associated circuits.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Introduction Rev. 5Section 1 Page 1-3 3.7 The "Deviations from 1OCFR50 Appendix R" section lists all deviations resulting from the shutdown analysis. The "Appendix" is comprised of the follo wing sections which support the report: I. A "P&I Diagrams (Typical)" section which contains photographs of typical marked P&I Diagrams utilized in the review. II. A "Schematic Diagrams & Cable Diagrams (Typical)" section which contains copies of typical drawings utilized in the review. III. An "Equipment Lists (Tables)" section which contains the tables that list all equipment required for performance of the Safe Shutdown functions. IV. A "Raceway Arrangement Drawings (Typical)" section which contains photographs of typical marked raceway drawings utilized in the review.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Report Preparation Rev. 13 Section 2 Page 2-1 REPORT PREPARATION/MAINTENANCE To establish a methodical course of action and provide guidance to the various organizations required to support the initial development of the Safe Shutdown Capability program, UE&C procedure TP -2 (NHY Procedure 38160) titled "Procedure for Review and Report Preparation for 10 CFR Part 50 Appendix R, Fire Protection of Safe Shutdown Capability " was prepared. The salient points of this procedure are as described in Sections 2.1 to 2.8. As modifications are implemented to the plant, the effect of these modifications to this report must be evaluated. The evaluation process is as described in Section 2.9. 2.1 DETERMINATION OF FIRE AREAS/ZONES The fire areas/zones are as delineated in "Fire Protection Program Evaluation and Comparison to Branch Technical Position APCSB 9.5 -1, Appendix A " or as determined by the Responsible Engineer. 2.2 DETERMINATION OF SAFE SHUTDOWN SYSTEMS The Safe Shutdown systems were determined by considering the minimum performance goals established in Appendix R, Paragraph III.L.2, and utilizing the following sources for guidance: 2.2.1 Final Safety Analysis Report - Seabrook Station 2.2.2 Fire Protection Program Evaluation and Comparison to Branch Technical Position APCSB 9.5 -1, Appendix A 2.2.3 Station Operating Procedure No. OS1200.01 "Safe Shutdown and Cooldown from the Main Control Room " 2.2.4 Station Operating Procedure No. OS1200.02 "Safe Shutdown and Cooldown from the Remote Safe Shutdown Facilities " 2.2.5 United Engineers & Constructors Inc. Engineering 2.2.6 Yankee Atomic Electric Co. Engineering 2.2.7 New Hampshire Yankee Engineering

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Report Preparation Rev. 13 Section 2 Page 2-2 2.3 DETERMINATION OF SAFE SHUTDOWN EQUIPMENT The minimum equipment necessary to perform the Safe Shutdown function was determined by utilizing the following sources: 2.3.1 Final Safety Analysis Report - Seabrook Station 2.3.2 Fire Protection Program Evaluation and Comparison to Branch Technical Position APCSB 9.5 -1, Appendix A 2.3.3 Station Operating Procedure No. OS1200.01 "Safe Shutdown and Cooldown from the Main Control Room " 2.3.4 Station Operating Procedure No. OS1200.02 "Safe Shutdown from the Remote Safe Shutdown Facilities " 2.3.5 Piping and Instrumentation (P&I) Diagrams 2.3.6 United Engineers & Constructors Inc. Engineering 2.3.7 Yankee Atomic Electric Co. Engineering 2.3.8 New Hampshire Yankee Engineering Sets of P&I Diagrams and One -Line Diagrams were marked to indicate hot standby equipment and cold shutdown equipment for main control room shutdown and remote safe shutdown. Train A equipment was marked in red, and Train B equipment was marked in green. Photographs of typical marked P&I Diagrams are contained in Appendix Section I. 2.4 DETERMINATION OF SAFE SHUTDOWN CABLES Considering the equipment defined and utilizing their related electrical schematic diagrams and cable schematics, the cables required for Safe Shutdown were determined. The raceways through which these cables were routed were determined; and then their associated fire area/zone(s) were determined. To document the review, the "10 CFR 50 - Appendix R, Safe Shutdown Equipment List" was prepared from data gathered in this review. Copies of typical schematic diagrams and cable schematics are contained in Appendix Section II. Copies of the safe shutdown equipment lists are contained in Appendix Section III.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Report Preparation Rev. 13 Section 2 Page 2-3 The equipment required for fire safe shutdown can be divided into supporting equipment and supported equipment. For example, CC -TE-2197 is supporting equipment for CC pump trip and CC-P-11A/C are the corresponding supported equipment. Supported equipment tag numbers are typically listed in the Appendix III Equipment Tables - "Equipment Id No. " column and represent the major components used to perform each safe shutdown function. Supporting equipment tag numbers are typically not listed in the "Equipment Id No. " column but should be listed in the "Supporting Control and Instrumentation Equipment " columns. The following guidance should be used for lisiting supported and supporting equipment tag numbers in the Appendix R Report Section 3 Tabulations and for assigning the descriptions for CASP cables. The tag number for supporting equipment should be listed in the tabulation for the fire zone/area in which the equipment is located with an "X" in the equipment column and an "X" in the cable column. For other fire zones/areas which contain just the cable for the supporting equipment, the cable should be accounted for with an "X" in the cable column using the tag number of the supported equipment. The safe shutdown analysis for each fire zone/area should discuss the impact of fire damage to the supporting equipment cables and equipment in terms of the impact on operation of the supported equipment. The cable "description " in CASP for supporting equipment cables should be the support ed equipment tag number. Note that this specific guidance was added to the Report in 2013 to address future Report changes but was typically applied in the past. 2.5 COMPUTER INPUT AND REPORTS The following data were input to UE&C 's "NRC Emergency Shutdown Program NRCESP " Program No. EL -130: a. Listing of Raceways and their Associated Fire Zones

b. Listing of Cables (from Safe Shutdown Equipment Lists)

The following output reports were generated using the NRC Emergency Shutdown Programs:

c. Listing of Fire Areas/Zones
d. Safe Shutdown Cables using CASP A Format
e. Safe Shutdown Raceways and Associated Cables by Fire Zone
f. Safe Shutdown Raceways and Cables
g. Cables with Associated Fire Zones Copies of the input data and output reports were contained in Appendix Section V.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Report Preparation Rev. 13 Section 2 Page 2-4 2.6 DETERMINATION OF SAFE SHUTDOWN RACEWAYS Utilizing the "Safe Shutdown Raceways and Associated Cables by Fire Zone " computer report, a set of raceway arrangement drawings was marked as follows: 2.6.1 Train A raceways, boxes, and termination equipment were marked in red. 2.6.2 Train B raceways, boxes, and terminating equipment were marked in green. 2.6.3 Equipment which is manually operated or disabled was marked in orange. A "D" was placed beside equipment to be disabled. An "M" was placed beside equipment needed to be manually operated. 2.6.4 Rated fire walls and barriers were marked in black. Photographs of typical marked raceway arrangement drawings are contained in Appendix Section IV. 2.7 ANALYSIS OF RACEWAYS AND EQUIPMENT TO SATISFY APPENDIX R REQUIREMENTS 2.7.1 Each fire area/zone that contained Safe Shutdown equipment or cables was reviewed to determine if Appendix R, Paragraph III.G.2 separation requirements were satisfied. 2.7.2 If the Appendix R requirements were not satisfied, further analysis was performed to determine the effects of a hot short circuit, short circuit, open circuit, ground or other equipment failure. 2.7.3 If the Safe Shutdown function was affected by a hot short circuit, short circuit, open circuit, ground or other equipment failure, then the following analysis to satisfy the Appendix R requirements was provided: 2.7.3.1 Analysis which documented that the in situ and transient combustibles were insufficient to cause a fire which affected the redundant trains of equipment and cables. 2.7.3.2 A three-hour fire barrier or a one-hour barrier and sprinklers between the redundant equipment or cables. 2.7.3.3 Rerouted the redundant cable out of the fire area/zones, or provided twenty feet of separation and sprinklers in the area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Report Preparation Rev. 13 Section 2 Page 2-5 2.7.3.4 Provided an alternative or dedicated safe shutdown equipment or system (See Section 3.3 and 3.4). 2.7.3.5 Requested a deviation from the 10 CFR 50, Appendix R requirements based on the combustibles in the fire area/zone, the spatial separation and the protective measures provided.

(See Section 3.7). 2.8 HIGH-LOW PRESSURE INTERFACES A list was prepared of the high

-low pressure interfaces and the lines with two or more electrically operated valves which could open and potentially cause a LOCA. A review was performed in the same manner as discussed in Section 2.4 and 2.5 utilizing this list. An analysis and evaluation were then performed.

(See Section 3.5) 2.9 MODIFICATION EVALUATION As plant modifications are implemented, their effect on the analysis contained in this report must be evaluated to ensure that the safe shutdown capability in the event of a fire is maintained. This evaluation will consider the UFSAR, this Appendix R Report, Supporting Documentation and the latest issue of design documents. If necessary, appropriate markups of documents will be included in the design change package to reflect any change in the Appendix R safe shutdown analysis.

The UE&C computer programs described in Section 2.5 are no longer available. New computer programs were written to produce the following reports to support the analysis contained in this report and evaluation of modifications:

a. List of Areas/Zones
b. List of Raceways and Associated Fire Zones
c. List of Cables w/Event Indicators
d. Safe Shutdown Raceways and Associated Cables by Fire Zone
e. Safe Shutdown Raceways and Cables
f. Cables with Associated Fire Zones Copies of these reports are contained in Appendix R supporting documentation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-1 SAFE SHUTDOWN CAPABILITY 3.1 DISCUSSION OF BASES AND POSITIONS 3.1.1 General 10 CFR Part 50 Appendix R, Paragraph III.G.1 requires that fire damage be limited so that:

a. One train of systems necessary to achieve and maintain hot standby condition from either the control room or emergency control station(s) is free of fire damage; and
b. Systems necessary to achieve and maintain cold shutdown from either the control room or emergency control station(s) can be repaired within 72 hours. Based on requiremen t "a" above, the design basis of Seabrook Station is that one train of systems necessary to achieve and maintain hot standby from the control room or the emergency control stations (hereafter designated the remote safe shutdown facilities) is free of fire damage. Under this basis, Appendix R, Paragraph III.G.2 and III.G.3 will apply to the safe shutdown paths controlled from the main control room or the remote safe shutdown facilities. Any deviations from the III.G.2 and III.G.3 criteria will be with respect to the main control room or the remote safe shutdown facilities and is addressed in Sections 3.2.7, 3.3.9, 3.4.3 and in the List of Deviations Section 3.7 of this report. For fires in some areas of plant, alternative shutdown capabilities are provided as discussed in Sections 3.3 and 3.4.

This Section defines the bases and positions utilized in determining and reviewing the shutdown capabilities that will satisfy the requirements of Paragraph III.G. These capabilities can be utilized to safely shut down the reactor in the event of a fire in any area/zone of the plant. 3.1.2 Safe Shutdown "Safe Shutdown " for purposes of the review is defined as a capability to bring the reactor from a 100 percent power operating condition to a "cold shutdown " condition. Included in this are conditions "hot standby, " "hot shutdown, " "cold shutdown, " and maintenance of "cold shutdown. " SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-2 The design basis event for safe shutdown is a postulated fire in a specific fire area/zone with or without the loss of offsite power (LOOP). This design basis was used for the original Appendix R Report preparation. The LOOP was assumed to occur whether the specific fire being analyzed caused it or not. The diesel generators (DGs) were analyzed to both automatically start and load, and not automatically start and load. An engineering evaluation prepared in 2007, documented that this was a conservative design basis since Appendix R does not require an arbitrary LOOP for non-alternate shutdown fire areas/zones (i.e., for shutdown control from the main control room). For future safe shutdown analyses, offsite power can be credited to remain available for

non-alternate shutdown fire areas/zones if the cables required to support offsite power are not damaged by the fire (i.e., an arbitrary LOOP need not be assumed). This approach provides greater analysis flexibility. No other design basis event (e.g. seismic or LOCA) is considered to occur coincident with the fire event. The safe shutdown functions shall assure the following:

a. No fuel clad damage. b. No rupture of any primary coolant boundary.
c. No rupture of containment boundary.
d. Reactor coolant system process variables shall be within those predicted for a loss of normal AC power.
e. Achievement of cold shutdown conditions within 72 hours and maintenance of cold shutdown conditions thereafter.

3.1.3 Redundancy

To assure a safe shutdown capability pre -fire, two redundant trains (Train A and Train B) of equipment are provided for each safe shutdown function. Each train contains a complete complement of the equipment, cabling, instrumentation and controls necessary to perform the safe shutdown functions. In several instances a single mechanical equipment is common to both trains (i.e., condensate storage tank, mechanical manual valves, piping, HVAC ducts, etc.). Single failure is not assumed to occur except to equipment that is damaged by the fire.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-3 3.1.4 Determination of Safe Shutdown Functions The safe shutdown functions are determined by considering the performance goals established in Appendix R, Paragraph III.L.2. The systems or portions of systems necessary to satisfy safe shutdown are subsequently determined. 3.1.5 Determination of Safe Shutdown Equipment Safe shutdown systems are the systems required to achieve the performance goals listed in Section 1. The equipment for these systems can be divided by function as Hot Standby (Reactor tripped and T -Avg above 350F) and Cold Shutdown (Reactor tripped/and cool down of the Reactor Coolant System T -Avg equal to or below 200F). The following criteria are used to determine the equipment required for safe shutdown:

a. The equipment is required to operate to permit a safe shutdown system to perform its safe shutdown function.
b. The equipment

's maloperation can prevent a safe shutdown system from performing the safe shutdown function.

c. The equipment is a process or electrical boundary for a safe shutdown system.

3.1.6 Safe Shutdown System Boundaries The safe shutdown system process boundaries are established by the following devices:

a. Normally closed manual valve
b. Check valve
c. Electrically operated safe shutdown valve
d. Root valve on small instrument lines to non

-safe shutdown instruments

e. Relief valve
f. Redundant valves on high

-low pressure boundaries

g. Boundary valve between a safe shutdown process line and a non

-Safe Shutdown process line which if it is an incorrect position will not affect the operation of the Safe Shutdown system.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-4 The safe shutdown electrical system boundaries are established by the following devices:

h. Isolation device (i.e., coordinated circuit breaker, fuse, transducer, etc.)
i. "Remote Local

" selector switch Cables isolated by "Remote-Local" selector switches or other isolation devices are not included in the review. 3.1.7 Manual Operator Actions Manual operator actions must satisfy the following considerations:

a. Sufficient manpower and time is available to perform all required manual actions.
b. There is accessibility to the equipment to perform the manual action either during or after the fire.

3.1.8 Spurious Operation The evaluation of the effects of spurious equipment operation on safe shutdown functions considers the effects of hot short circuits, short circuits, open circuits and grounds. The effects of hot short circuits are considered on the following:

a. Energized 120V ac grounded circuits
b. De-energized 120V ac grounded circuits
c. Energized 120V ac ungrounded circuits
d. Energized 125V dc ungrounded circuits Hot short circuits are not considered for disabled (tripped power supply) 3

-phase 480 Volt ac circuits, ungrounded 1 -phase 120 Volt ac circuits and ungrounded 125 Volt dc circuits as these would require multiple hot shorts in the correct sequence to cause a device to function. These are considered incredible events. The effects of short circuits, open circuits and grounds are considered for all circuits evaluated for spurious operation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-5 The above discussion does not provide all of the criteria used for evaluating spurious component operations during the original Appendix R Report preparation. An engineering evaluation prepared in 2007 reviewed various Seabrook, NRC, and industry documents to re -create the circuit analysis methodology bases used for the fire safe shutdown analyses that was not included in the above discussion. The following documents the added methodology criteria. The analyses shall consider fire induced damage to any and all unprotected cables in the fire area/zone being analyzed. Each cable failure shall be considered individually, one -at-a-time, and the effects of any spurious operation(s) evaluated. If the effect is unacceptable (ex. loss of inventory), then operator actions, or other corrective actions (see Section 2.7), are specified to mitigate the effects of the spurious operation. If the effect is acceptable, then additional sequential cable failures and resultant spurious operations of same function components must also be considered (ex. spurious opening of other normally closed series valves in a potential diversion flow path). If their effects are unacceptable, then appropriate preventative/disabling operator actions (ex. open a circuit breaker) are specified to prevent the unacceptable condition. Mitigating and preventative/disabling actions that rely on electrical power, ex. MOV operation, can not credit components with unprotected cables in the fire area/zone being analyzed. The basis described in the previous paragraph is typically referred to in the industry as any-and-all, one-at-a-time. In addition, it will be assumed that the loss of function from fire damage to unprotected cables within a fire area cable will prevent the effected components from operating to support safe shutdown but any resulting state changes will be evaluated as spurious operations following the above criteria of one -at-a-time. Also, a protective device state change from a short circuit (open a fuse or trip a circuit breaker) will be considered a spurious operation and will be evaluated following the above criteria of one -at-a-time including any end component state changes, ex., loss of control power to a normally energized solenoid operated valve (SOV) would cause the SOV to change state as a spurious operation. For Seabrook, failure of an individual cable typically only causes spurious operation of one component although there are exceptions where one cable failure can cause spurious operation of multiple components.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-6 The complete circuit for each equipment tag typically consists of multiple cables routed through many fire zones. It is expected that applying the failure modes to some cables in a circuit may not actually result in a spurious operation of the corresponding equipment. However, it appears that the original safe shutdown analyses conservatively assumed that every cable failure would cause spurious operation of the supported component(s) since there was no evidence found in the original analyses of credit being taken for analyzing specific conductor interactions as the basis for concluding that there was no resulting spurious operation. For future safe shutdown analyses, it is acceptable to use circuit analysis to demonstrate that a fire -induced cable failure can not cause a spurious operation. These circuit analyses should be included in appropriate engineering documents. Operator actions to mitigate spurious component operation must meet the criteria provided in Section 3.1.7 on manpower, timing and accessibility considering the system effect of the corresponding spurious operation. Preventative/disabling operator actions should be documented in a procedure and be able to be completed in a reasonable time consistent with completion of time critical mitigating actions. Automatic signals can be credited if their circuits are included in the analysis to ensure that their cables are free of fire damage for the fire areas which credit the signals. Automatic signals with unprotected cables in a fire zone must be analyzed to fail to operate or spuriously operate because of fire-induced cable damage. The automatic signals must also be analyzed to operate as designed if the system conditions caused by the fire (ex. low level, high flow, loss of power, etc.) would initiate the automatic function to ensure that the automatic actuation is not detrimental to safe shutdown. The review assumes that all conductors within multi -conductor cables would short, open or ground due to a fire. Cable to cable interactions are not considered credible events because of the

thermoset cable insulation used at Seabrook Station. 3.1.9 Disabled (tripped power supply) Equipment To prevent spurious operations of valves and other equipment which are normally aligned in their safe shutdown position, the operators will trip the power supplies to these devices upon reaching the RSS facilities.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-7 3.1.10 Fire Areas The "Fire Protection Program Evaluation and Comparison to Branch Technical Position APCSB 9.5-1, Appendix A" report establishes fire areas and zones for purposes of fire detection and protection. Although these zones are satisfactory for fire detection and protection, they do not in all cases satisfy Appendix R requirements. To assure that the Appendix R separation requirements are satisfied, zones containing redundant equipment which do not satisfy the requirements are grouped and analyzed to provide assurance that safe shutdown can be achieved. An example of this is containment which has three zones: C -F-l-Z, C-F-2-Z and C-F-3-Z. As there is no 3 -hour rated barrier between zones, they have been considered as one fire area. The delineation of the fire areas and zones which have been combined into a fire area is in Section 3.2.7. 3.1.11 Emergency Lighting Emergency lighting units per Appendix R, Paragraph III J are provided with at least an 8 -hour battery powered supply or diesel generator backed essential lighting (See letter SBN -932, dated January 27, 1986, Deviation No. 10) in all areas needed for operation of safe shutdown equipment and in access and egress routes. In areas where actions are required after eight hours and actions are needed during a cooldown, 8 -hour battery powered supplied lights are not provided. Repairs per Appendix R III G.l.b, will be implemented to provide required illumination for required cooldown actions. 3.1.12 Repairs for Cold Shutdown For cold shutdown, the following equipment will require replacement of control fuses which will be available in the Train B switchgear room.

a. EAH-FN-31B b. RC-V87 c. RC-V88 d. RH-P-8B e. SI-V17 f. SI-V47 In the event that emergency bus EDE

-SWG-5 is not available, a temporary power connection will be provided from EDE -MCC-621 to the RC -V88 MCC cubicle.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 10 Section 3.1 Page 3.1-8 In the event that PCCW cooling is lost to containment due to loss of containment instrument air causing inboard PCCW isolation valve closure, IA -V530 will be manually opened via a pneumatic jumper to supply outside containment instrument air to containment instrument air to reopen the inboard PCCW isolation valves to reestablish PCCW cooling flow to support containment habitability.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-1 3.2 MAIN CONTROL ROOM SAFE SHUTDOWN 3.2.1 Main Control Room Safe Shutdown Locations Safe shutdown will be accomplished with control from the main control room (MCR), utilizing the safe shutdown equipment and depending on the location of the fire, a combination of the following locations:

a. Train A Switchgear Room
b. Train B Switchgear Room
c. Diesel Generator Room A
d. Diesel Generator Room B
e. Primary Auxiliary Building El. 25

'-0" Boric Acid Storage Tank Area

f. Primary Auxiliary Building El. 7

'-0" Charging Pump Rooms

g. Containment
h. Equipment Train A Vault (Vault #1)
i. Equipment Train B Vault (Vault #2)
j. Mechanical Penetration Area
k. Emergency Feedwater Pump Building
l. Condensate Storage Tank
m. Control Room HVAC Equipment and Duct Area
n. Non-Essential Switchgear Room
o. Turbine Building Actions from the various areas would be of the following types: manual valve actuations, manual damper actuations, tripping of power supplies, opening of doors to provide air flow for cooling, realign power supplies, and/or manipulation of control switches.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-2 The term "prompt action " refers to an action taken after receipt of a valid fire alarm in the main control room. The term "expeditious action" or "expeditiously " refers to an action taken quickly upon entry into the applicable safe shutdown procedure. These type actions are considered to be completed prior to a spurious operation of the equipment operated by the prompt and expeditious

actions. Therefore, no associated timing calculation is required for these actions. 3.2.2 Safe Shutdown Functions for Hot Standby The following are PWR equipment necessary for hot standby: 3.2.2.1 Reactor Coolant (RC) Inventory and Pressure Control To compensate for miscellaneous RC system leakage, RC pump seal leakage and cooldown volume shrink, portions of the chemical and volume control (CS) system including centrifugal charging pumps, boric acid transfer pumps, and a borated water supply, either the refueling water storage tank (RWST) or the boric acid tanks (BAT) are used. The injection path to the RC system will be either through the seal injection flow path or the high head injection flow path. The preferred seal injection path requires that a flow control valve (CS -FCV-121) and that a minimum of two of the four seal injection valves (CS -V154, CS-V158, CS-V162 or CS -V166) be operable. Additionally, the normal charging flow path to the RC system is isolated. This can be accomplished by use of any one of three functionally redundant valves (CS -V142, CS-V143 or CS-HCV-182). Should the seal injection path not be operable, e.g., due to spurious closure of a flow path valve (CS -FCV-121) the high head injection flow path (SI -V138 or SI -V139) can be utilized initially to maintain hot standby by batch charging from the RWST to maintain pressurizer level. Should SI -V-138 or SI -V-139 spuriously open, the charging pump may have to be stopped to prevent overfill of the pressurizer. During cooldown as RC system pressure decreases, it is necessary to provide a flow restricted path to prevent charging pump cavitation. This is due to the limited flow capability from the BAT. If the high head injection path cannot be isolated at this time and/or if the flow controlled path through CS -FCV-121 is not operable, a capability is provided to manually align and throttle the charging pumps to the seal injection flow paths. The necessary operator actions and valve alignments are unique for each fire area where these flow paths are affected and are described in the analysis for each area. RC pump seal cooling is provided by a redundant thermal barrier cooling system. Should the redundant thermal barrier system not be available, the seals will be cooled by the seal injection capability. On a long term basis, seal injection will be restored. The reactor coolant pumps (RCPs) are stopped from the main control board. Circuit analysis shows that the RCPs can not spuriously restart due to fire -induced cable damage.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-3 The RC system pressure is controlled by use of a portion of the RC system which includes the pressurizer heaters (Group A and B) to increase pressure and the pressurizer power operated relief valves (PORV) which depressurize the RC system by discharging reactor coolant fluid to the pressurizer relief tank (PRT). Considering worst case scenarios for spurious actuation of affected equipment, the required times for operator actions regarding RC inventory and pressure control for safe shutdown from the main control room are provided below: Action Time Close PORV block valve Prompt Isolate letdown 15 minutes Swap charging pump suction from VCT to RWST 15.4 minutes. Should SI -V138, SI-V139, or CS -HCV-182 spuriously open, this action must be completed no later than 5.0 minutes following letdown line isolation. Trip RCPs 10 minutes Open a PORV to reduce pressurizer pressure in the event of spurious pressurizer heater operation or trip

pressurizer heaters 23 minutes Start a charging pump, or open a high head safety injection valve SI -V-138 or SI -V-139 if normal charging pump path is not available 31.1 minutes Isolate charging flow, except for seal injection 35.4 minutes Trip spuriously operating containment building spray pumps 46 minutes Trip spuriously operating SI pump < 4 hours, prior to commencement of plant cooldown Isolate the potential diversion path from the BAT to the RWST, or align BAT for gravity feed.

<4 hours, prior to commencement of plant cooldown

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-4 Action Time Align BAT for makeup source

<4 hours, prior to commencement of plant cooldown 3.2.2.2 Reactivity Control Reactivity for hot standby at normal operating temperature (not) is provided by insertion of the control rods. Reactivity conditions required for cooldown and maintaining cold shutdown are provided by a portion of the chemical and volume control (CS) system which includes a centrifugal charging pump taking suction from the BAT

's either utilizing the gravity flow path or the boric acid transfer pumps. During cooldown, the borated water source must be the BAT volume until exp ended to at least the point that the volume injected or a boron sample demonstrates that sufficient shutdown margin for cold shutdown has been achieved, at which time the RWST would be aligned. If gravity feed from the BAT is used, the RWST must be isolated. Considering worst case scenarios for spurious actuation of affected equipment, the required times for operator actions regarding reactivity control for safe shutdown from the main control room are provided below: Action Time Trip the Reactor Expeditiously Provide borated water from the BATs, via boric acid transfer pump or gravity feed

<4 hours, prior to commencement of plant cooldown Isolate boric acid flow diversion path
<4 hours, prior to commencement of plant cooldown

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-5 3.2.2.3 Decay Heat Removal The reactor coolant (RC) system temperature is controlled by use of portions of the feedwater (FW) system and the main steam (MS) system. The main steam safety/relief valves will maintain a heat dump capability. The steam generator water inventory is controlled by operating the motor driven emergency feedwater pump, the start -up feedwater pump, and associated valves. Inventory for the emergency feedwater is from the condensate storage tank. Long term water capability exists using a temporary connection between the suction of the turbine driven emergency feed pump and the fire protection system but is not required to meet Appendix R requirement. This temporary connection back feeds to the CST which supplies water to the startup feedwater pump and the motor driven emergency feedwater pump. To assure main steam system integrity the MSIV 's and MSIV bypass valves are maintained closed. The MSIV bypass valves are normally locked closed and depowered with breakers locked open to preclude spurious opening. Decay heat transfer is made possible by natural convection flow in the RC system. Considering worst case scenarios for spurious actuation of affected equipment, the required times for operator actions regarding decay heat removal for safe shutdown from the main control room are provided below: Action Time Isolate the MSIVs Expeditiously following a reactor trip Place the mode selector switches for the ASDVs to the closed position Prompt Gain Control of excessive Emergency Feedwater Flow 20 minutes Start motor driven EFW pump or startup feedwater pump to preclude steam generator dry out - normal power operation 39 minutes Start motor driven EFW pump or startup feedwater pump to preclude steam generator dry out - low power operation 75 minutes Time to bypass the startup feed pump low suction trip 4 hours SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-6 Action Time Time allotted for operator actions to preclude emptying CO tank to accommodate RHR Cut -in, and ultimately achieve cold safe shutdown within 72 hours 9 hours; 4 hours at hot standby plus

5 hours cooldown to RHR Cut -in 3.2.2.4 Process Monitoring Instrumentation is provided at the main control room for monitoring the following process variables:

a. Steam generator emergency feedwater flow
b. Reactor coolant loop hot and cold leg temperatures
c. Steam generator wide

-range level

d. Steam generator pressure
e. Pressurizer level
f. Pressurizer pressure
g. Wide-range neutron monitoring (excore)
h. Primary component cooling water temperature
i. Boric acid tank level
j. Condensate storage tank level 3.2.2.5 Service Water The service water system will supply cooling water to the primary component cooling water system, diesel generators, and if required, fire protection system. Service water supply will be from the service water pumps taking suction from the tunnels to the ocean. If necessary, transfer to the cooling towers utilizing the cooling tower fans, cooling tower pumps and associated motor-operated transfer valves can be accomplished automatically on low service water pump discharge header pressure or manually from the main control room. If a manual transfer to the cooling tower is in effect and a loss of offsite power occurs, cooling tower operation automatically resumes upon restoration of electrical power.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-7 3.2.2.6 Primary Component Cooling Water (CC) The CC system is utilized to maintain cooling water to the charging pumps, RHR pumps, RHR heat exchangers, containment structure cooling units, containment enclosure cooling units and reactor coolant pumps (RCP) thermal barrier heat exchanger. The PCCW pumps, temperature control valves, RCP thermal barrier cooling pumps, and inboard and outboard containment isolation valves are necessary for system operations. 3.2.2.7 Sampling Sampling of the reactor coolant system is not required at hot standby and cold shutdown conditions since make -up during cool -down will only be provided to the RCS from the boric acid tanks (two) which are maintained at 4 wt% boric acid. During all phases of cooldown, the core will be maintained to the shutdown margin greater than or equal to the limit specified in the Core Operating Limits Report (COLR). 3.2.2.8 Diesel-Generator Building Air Handling (DAH) The DAH system is utilized to maintain long -term habitability and equipment protection for the diesel-generator rooms. The DAH system includes the fans and dampers for air handling in these areas. 3.2.2.9 Containment Enclosure Air Handling (EAH) The EAH system is utilized to maintain long -term habitability of the mechanical penetration area, and provides equipment cooling in the charging pump rooms, and the hydrogen analyzer and electrical room. The EAH system includes the coolers, fans, and dampers required for air handling in these areas. 3.2.2.10 Emergency Feedwater Pumphouse Air Handling (EPA) The EPA system is utilized to maintain long -term habitability and equipment protection in the emergency feedwater pump building. The EPA system includes the fans and dampers required for air handling in this area. 3.2.2.11 Primary Auxiliary Building Air Handling (PAH) Portions of the PAH system are utilized to maintain long -term habitability and equipment protection in the PCCW area of the primary auxiliary building. The PAH system includes the fans and dampers required for ventilation in this area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-8 3.2.2.12 Service Water Air Handling (SWA) Portions of the SWA system are utilized for equipment protection in the SW pump house electrical control rooms. The SWA system includes the fans and dampers required for air handling in these areas. 3.2.2.13 Electrical Distribution Emergency (EDE) Portions of the EDE system are required to power the various pumps, fans, valves, etc. required for Safe Shutdown. Included in the EDE system are the 4160 Volt ac emergency switchgear, 460 Volt ac emergency unit substations and motor control centers, the uninterruptible power supplies, the static transfer switches, 120 Volt ac vital distribution panels, 125 Volt dc batteries, battery chargers, and 125 Volt dc distribution panels. 3.2.2.14 Diesel-Generators (DG) The diesel -generators provide power to the emergency electrical distribution system upon loss of off-site power. The DG system includes the diesels, generators, control panels, engine -driven auxiliaries fuel oil transfer pumps, starting air compressors and backup operating air compressors. 3.2.2.15 Safeguard Actuation System The safeguard actuation system could be actuated, depending on the fire area. A portion of this system is used to deactivate the system for recovery. 3.2.2.16 Service Air (SA) and Instrument Air (IA) Portions of the SA and IA systems are required for air operated valves and dampers necessary for safe shutdown. 3.2.2.17 Control Building Air Handling (CBA) The CBA system is used to maintain Control Building habitability and equipment protection. The CBA system is comprised of a non -safety related chilled water system that can be aligned to either safety related air handling unit and two redundant safety related chilled water systems, which are aligned to their corresponding safety related air handling units. Each chilled water system includes its own packages chiller and circulating pumps. The air handling units include cooling coils (safety related and non -safety related), fans, dampers. Fires that could disable either safety related train of Control Room cooling are discussed in applicable fire area analysis.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-9 3.2.2.18 Communication The Gaitronics or radio systems are used to announce the fire event and dispatch the fire brigade. The Gaitronics system is also used to provide a fire alarm. For shutdown from the main control room (MCR), most of the operator actions are actually performed in the MCR where face -to-face communication would be used. When field actions are required, an operator would: a) be dispatched to take the required action, b) go to the field and take the action, and c) then return to the MCR and report the action completed. No other communication methods are credited for shutdown controlled from the main control room. Radios and Gaitronics are not credited but would be used as additional means of communication, if not damaged by the fire. 3.2.3 Safe Shutdown Function for Cooldown The following equipment in addition to that which is listed in Section 3.2.2 is necessary for cooldown. 3.2.3.1 Decay Heat Removal In addition to equipment discussed in Section 3.2.2.3, the steam generator atmospheric relief valves will be used for cooldown until the residual heat removal (RH) system can be used. The residual heat removal system will be the long term heat sink at the end of cooldown. An RH pump will be operated along with various control, manual and motor operated valves. Also, the startup feedpump low suction pressure trip must also be bypassed prior to commencing cooldown. 3.2.3.2 Containment Building Air Handling (CAH) The CAH system is utilized to maintain habitability of containment for manual operation of the RHR and SI isolation valves. The CAH system includes six containment cooling units and their associated fans. 3.2.3.3 Sample System For cold shutdown, the operator will draw a manual sample from RH system to verify boron concentration before line -up to RCS. The operator will use manual valves in RH system.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-10 3.2.4 Manual Operator Actions The following equipment may require manual operation outside the MCR.

a. Control Building dampers CBA

-DP-24A, CBA-DP-24B, CBA-DP-24C, CBA-DP-24D, CBA-DP-24E, CBA-DP-24F, CBA-DP-52, CBA-DP-26A, CBA-DP-26B. b. Switchgear room fans CBA -FN-19, CBA-FN-20, CBA-FN-32 and CBA -FN-33. c. Component cooling water valves CC -V122, CC-V168, CC-V175, CC-V257 and CC-V272 d. CVC tank isolation valves CS -LCV-112B and CS -LCV-112C (RSS Panels).

e. RWST suction to charging pump valves CS

-LCV-112D and CS -LCV-112E (RSS panel) f. Charging pumps discharge and bypass valves CS -V210, CS-V219, CS-V220 and CS-V221. g. Boric acid tank level CS -LT-7464 (RSS panel)

h. Boric acid tank valves CS

-V410, CS-V416, CS-V423, CS-V426, CS-V431, CS-V437, CS-V439, CS-V442 and CS -V1207 i. Diesel generators DG -DG-1A and DG -DG-1B (DG panels)

j. RHR inlet isolation valves RC

-V22, RC-V23, RC-V87 and RC -V88 k. RHR sampling valves RH -V8 and RH -V44 l. RH heat exchanger to CS/SI pump isolation valves RH -V35 and RH -V36 m. Instrument air cross connect valves IA -V50 and IA -V530. n. Safety injection accumulator isolation valves SI -V3, SI-V32 o. PAB fans PAH-FN-42A and PAH -FN-42B (RSS panels)

p. Control building doors C119, C300, C310, C311 and C312.
q. Start-up feedpump low suction pressure trip bypass switch (FW

-CS-4233). r. Realign the suction of the start -up feedpump (CO -V-142). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-11 s. Realign the power supply of the start -up feedpump from Bus ED -SWG-4 to Bus EDE-SWG-5 (if not already aligned to Bus EDE-SWG-5). t. Not used Equipment CBA -DP-24D, CBA-DP-24E, CBA-DP-24F, CS-V210, CS-V219, CS-V220, CS-V221, CS-V410, CS-V416, CS-V423, CS-V431, CS-V437, CS-V439, CS-V442, CS-V1207, CO-V142, IA-V50, RH-V8 and RH -V44 are not electrically operated; hence, they have no cables. Electrical operation of IA -V530 is not credited so its cables are not analyzed. 3.2.5 Disabled (tripped power supply) Equipment The following equipment may require disabling:

a. Primary component cooling valves CC

-V1092, CC -V1095, CC -V1101 and CC-V1109 b. Chemical and volume control valves CS -FCV-110A, -111A, -110B, -111B CS-V154, CS-V158, CS-V162, CS-V166, CS-V175, CS-V176, CS-V196 and CS-V197 c. Not used.

d. Emergency buses EDE

-SWG-5 and EDE -SWG-6 (control power)

e. Emergency Feedwater Control Valves FW

-FV-4214A,B; FW -FV-4224A,B, FW-FV-4234A,B and FW -FV-4244A,B f. Atmospheric relief valves MS -PV-3001, MS-PV-3002, MS-PV-3003 and MS-PV-3004 g. Not used.

h. Reactor coolant valves RC

-V122, RC-V124, RC-V323, RC-FV-2881, RC-LCV-459*, RC-LCV-460*, RC-PCV-456A and RC -PCV-456B i. Pressurizer heaters Group C, Group D and Control Group

j. Reactor coolant pumps RC

-P-1A, RC-P-1B, RC-P-1C, RC-P-1D k. Residual heat removal valves RH -V14, RH-V26, RH-V32, RH-V35, RH-V36, RH-V70, RH-HCV-607* and RH -FCV-619* l. Safety injection valves SI -V158 and SI -V159 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-12 m. Service water valves SW -V15, SW-V16*, SW-V18*, SW-V19, SW-V20, SW-V23, SW-V25, SW-V34 and SW -V54 n. Engineered safety features actuation system logic cabinets

o. Service water pump permissive logics Those valves noted with an asterisk (*) fail to their safe shutdown position upon de

-energization. 3.2.6 Safe Shutdown Equipment List Tables that list all equipment, including instrumentation and vital support systems equipment, required to achieve hot standby or cold shutdown from the main control room are provided in Appendix III. However, analysis can be also provided to justify not listing components and cables in Appendix III. The tables provide the following information for each equipment listed:

a. A column which notes whether the equipment is required for hot standby or cold shutdown.
b. A column which defines each equipment

's location by fire zone/area.

c. A column which defines each equipment

's redundant counterpart.

d. A column which lists each equipment

's essential cabling. For each cable 's routing by fire zone/area see computer report, "Cables with Associated Fire Zones " (Main Control Room Safe Shut -down). e. The table also delineates the following additional information:

1) P & I Diagram Drawing No.
2) Physical Location Drawing No.
3) Power Supply
4) Electrical Node Number
5) Supporting Control and Instrumentation Equipment
6) Electrical Schematic Drawing No.
7) Electrical Cable Schematic Drawing No.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-13 8) Supporting Systems

9) Remarks Separate tables are furnished for each of the safe shutdown functions. In several instances a safe shutdown function requires components from several systems to perform its safe shutdown function.

In order to simplify the tabulation, the following are not listed: manual valves in the process flow path; mechanical check valves which provide a safe shutdown system boundary; normally closed manual valves which provide a safe shutdown system boundary; mechanical relief valves; and root valves on small instrument lines. The review of these valves is documented by the marked P & I Diagrams. Tables are provided for the following functions which satisfy the performance goals stated in Appendix R, Paragraph III.L.2. Function Table No. Decay Heat Removal 3.1.3.1 Reactor Coolant Inventory and Pressure Control 3.1.3.2 Reactivity Control 3.1.3.3 Process Monitoring 3.1.3.4 Safeguard Actuation System 3.1.3.5 Cold Shutdown 3.1.3.6 Service Water 3.1.3.7 Primary Component Cooling Water 3.1.3.8 Containment Building Air Handling 3.1.3.9 Control Building Air Handling 3.1.3.10 Diesel Generator Building Air Handling 3.1.3.11 Containment Enclosure Air Handling 3.1.3.12 Emergency Feedwater Pumphouse Air Handling 3.1.3.13 Primary Auxiliary Building Air Handling 3.1.3.14 Service Water Air Handling 3.1.3.15 Service/Instrument Air 3.1.3.16 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-14 Function Table No. Electrical Distribution Emergency 3.1.3.17 Diesel Generators 3.1.3.18 3.2.7 Analysis and Evaluation of Fire Areas Provided on the following pages is a tabulation of the safe shutdown equipment and safe shutdown cabling contained in a fire area. The Train A and Train B redundant equipment are depicted, and an "X" is shown in the tabulation if equipment and/or cables are located in the fire area. If redundant trains of equipment are affected by a fire in the area, an analysis is provided on an area, equipment or system basis for the effects of a fire in this area. An evaluation is provided as to whether the Appendix R requirements or safe shutdown requirements are satisfied. If a deviation from Appendix R requirements exists, this deviation is justified by analysis. The following fire areas and associated fire zones have been considered in this review: Building Fire Area Fire Zones Tabulation Containment C-F-1-Z, C-F-2-Z, C-F-3-Z 3.2.7.1 Control Building -El. 21'-6" CB-F-1A-A - 3.2.7.2 Control Building -El. 21'-6" CB-F-1B-A - 3.2.7.3 Control Building -El. 21'-6" CB-F-1D-A - 3.2.7.4 Control Building -El. 21'-6" CB-F-1E-A - 3.2.7.5 Control Building -El. 21'-6" CB-F-1F-A - 3.2.7.6 Control Building -El. 21'-6" CB-F-1G-A - 3.2.7.7 Control Building -El. 50'-0" CB-F-2A-A - 3.2.7.8 Control Building -El. 50'-0" CB-F-2B-A - 3.2.7.9 Control Building -El. 50'-0" CB-F-2C-A - 3.2.7.10 Control Building -El. 75'-0" CB-F-3A-A - 3.2.7.11 Control Building -El. 75'-0" CB-F-3B-A - 3.2.7.12 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-15 Building Fire Area Fire Zones Tabulation Control Building -El. 75'-0" CB-F-3C-A - 3.2.7.13 Intentionally left blank 3.2.7.14 Control Building -Stairwell CB-F-S1 3.2.7.15 Control Building -Stairwell CB-F-S2 3.2.7.16 Containment Fan Encl. Area and Containment Annulus/ CE-F-l-Z, PP-F-1A-Z, PP-F-2A-Z, PP-F-3A-Z, 3.2.7.17 Mechanical Penetration Area PP-F-1B-Z, PP-F-2B-Z, PP-F-3B-Z, PP-F-4B-Z PP-F-5B-Z Condensate Storage Area CST-F-1-0 3.2.7.18 Intentionally left blank 3.2.7.19 Intentionally left blank 3.2.7.20 Cooling Tower -El. 22'-0" CT-F-1C-A 3.2.7.21 Cooling Tower -El. 22'-0" CT-F-1D-A 3.2.7.22 Intentionally left blank 3.2.7.23 Cooling Tower -El. 46'-0" CT-F-2B-A 3.2.7.24 Cooling Tower, Fans CT-F-3-0 3.2.7.25 Duct Bank -ET to SW DCT-F-1A 3.2.7.26 Duct Bank -ET to SW DCT-F-1B 3.2.7.27 Duct Bank -PAB to CT DCT-F-2A 3.2.7.28 Duct Bank -PAB to CT DCT-F-2B 3.2.7.29 Duct Bank -CB to PAB DCT-F-3B 3.2.7.30 Duct Bank -East MUA DCT-F-4A 3.2.7.31 Duct Bank -East MUA DCT-F-4B 3.2.7.32 Duct Bank -West MUA DCT-F-5A 3.2.7.33 Duct Bank -West MUA DCT-F-5B 3.2.7.34 Duct Bank -SWPH to CW DCT-F-6 3.2.7.35 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-16 Building Fire Area Fire Zones Tabulation Duct Bank -TB to CST DCT-F-7 3.2.7.36 Diesel Gen. Bldg. -El(-)16'-0" DG-F-1A-A - 3.2.7.37 Diesel Gen. Bldg. -El (-)16'-0" DG-F-1B-A - 3.2.7.38 Diesel Gen. Bldg. -El 21'-6" DG-F-2A-A - 3.2.7.39 Diesel Gen. Bldg. -El 21'-6" DG-F-2B-A - 3.2.7.40 Diesel Gen. Bldg. -El 51'-6" - DG-F-3A-Z DG-F-3B-Z 3.2.7.41 Diesel Gen. Bldg. -El 51'-6" DG-F-3C-A - 3.2.7.42 Diesel Gen. Bldg. -El 51'-6" DG-F-3D-A - 3.2.7.43 Diesel Gen. Bldg. -El 51'-6" DG-F-3E-A - 3.2.7.44 Diesel Gen. Bldg. -El 51'-6" DG-F-3F-A - 3.2.7.45 Diesel Gen. Bldg. -Stairwell DG-F-S1 3.2.7.46 Diesel Gen. Bldg. -Stairwell DG-F-S2 3.2.7.47 Emer. Feedwater Pump Bldg. EFP-F-1-A - 3.2.7.48 Electrical Tunnel ET-F-1A-A - 3.2.7.49 Electrical Tunnel ET-F-1B-A - 3.2.7.50 Electrical Tunnel ET-F-1C-A - 3.2.7.51 Electrical Tunnel ET-F-1D-A - 3.2.7.52 Electrical Tunnel Stairwell ET-F-S1 3.2.7.53 Fire Pump House FPH-F-1A-A - 3.2.7.54 Fire Pump House FPH-F-1B-A - 3.2.7.55 Fire Pump House FPH-F-1C-A - 3.2.7.56 Fuel Storage Bldg. -El 51'-6" FSB-F-1-A - 3.2.7.57 East Mainsteam & Feedwater Pipe Chase - MS-F-1A-Z MS-F-2A-Z MS-F-3A-Z MS-F-4A-Z MS-F-5A-Z 3.2.7.58 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-17 Building Fire Area Fire Zones Tabulation West Mainsteam & Feedwater Pipe Chase - MS-F-1B-Z MS-F-2B-Z MS-F-3B-Z 3.2.7.59 East Air Make -Up Pit MUA-F-1 3.2.7.60 Intentionally left blank

- - 3.2.7.61 Non-Essential Swgr. Room
- NES-F-1A-Z 3.2.7.62 Primary Auxiliary Building 

- El. 7'-0" - PAB-F-1A-Z PAB-F-1B-Z 3.2.7.63*

3.2.7.64* Primary Auxiliary Building - El. 7'-0" - PAB-F-1F-Z 3.2.7.65* Primary Auxiliary Building - El. 7'-0" - PAB-F-1J-Z 3.2.7.66* Primary Auxiliary Building - El. 7'-0" - PAB-F-1K-Z 3.2.7.67* Primary Auxiliary Building - El. 25'-0" - PAB-F-2A-Z 3.2.7.68* Primary Auxiliary Building - El. 25'-0" - PAB-F-2B-Z 3.2.7.69* Primary Auxiliary Building - El. 25'-0" - PAB-F-2C-Z 3.2.7.70* Primary Auxiliary Building - El. 53'-0" - PAB-F-3A-Z 3.2.7.71* Primary Auxiliary Building - El. 53'-0" - PAB-F-3B-Z 3.2.7.72* Primary Auxiliary Building - El. 81'-0" - PAB-F-4-Z 3.2.7.73* Primary Auxiliary Building - El. 7'-0" PAB-F-1C-A - 3.2.7.74 Primary Auxiliary Building - El. 7'-0" PAB-F-1D-A - 3.2.7.75 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-18 Building Fire Area Fire Zones Tabulation Primary Auxiliary Building - El. 7'-0" PAB-F-1E-A - 3.2.7.76 Primary Auxiliary Building - Electrical Chase PAB-F-1G-A - 3.2.7.77 Primary Auxiliary Building - Stairwell PAB-F-S1 3.2.7.78 Primary Auxiliary Building - Stairwell PAB-F-S2 3.2.7.79 Equipment Vault -Train B (Vault 2)

- RHR-F-1A-Z RHR-F-1C-Z RHR-F-2A-Z RHR-F-3A-Z RHR-F-4A-Z 3.2.7.80 Equipment Vault

-Train A (Vault 1)

- RHR-F-1B-Z RHR-F-1D-Z RHR-F-2B-Z RHR-F-3B-Z RHR-F-4B-Z 3.2.7.81 Circulating Water Pump House SW-F-1A-Z 3.2.7.82 Service Water Pump House SW-F-1B-A  3.2.7.83 Service Water Pump House SW-F-1C-A  3.2.7.84 Service Water Pump House SW-F-1D-A  3.2.7.85 Service Water Pump House SW-F-1E-Z 3.2.7.86 Intake & Discharge Structure SW-F-2-0  3.2.7.87 Turbine Building TB-F-1A-Z TB-F-1C-Z TB-F-2-Z TB-F-3-Z 3.2.7.88 Turbine Building TB-F-1B-A  3.2.7.89 Tank Farm TF-F-1-0 3.2.7.90 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-19   Building Fire Area Fire Zones Tabulation Waste Process Building W-F-1A-Z W-F-1B-Z W-F-1K-Z W-F-2A-Z W-F-2B-Z W-F-2C-Z W-F-2D-Z W-F-2E-Z 3.2.7.91
  • All primary auxiliary building fire zones containing safe shutdown equipment and/or cables have been combined into one fire area for analysis purposes.

Tabulation 3.2.7.1 Containment Fire Area: C-F-1-Z, C-F-2-Z, C-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CAH-AC-1C x CAH-AC-1A x CAH-FN-1C x x CAH-FN-1A x x CAH-AC-1E x CAH-AC-1B x CAH-FN-1E x x CAH-FN-1B x x CAH-AC-1F x CAH-AC-1D x CAH-FN-1F x x CAH-FN-1D x x CAH-JV3-43 x x CAH-JV7-43 x x CAH-JV4-43 x x CAH-JV8-43 x x CAH-JV5-43 x x CAH-JV6-43 x x CC-FISL-2124 x x CC-FISL-2122 x x CC-FISL-2223 x x CC-FISL-2123 x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-20 Containment Fire Area: C-F-1-Z, C-F-2-Z, C-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-FISL-2224 x x CC-FISL-2222 x x CC-LT-2172-1 x CC-LT-2192-1 x CC-LT-2172-2 x CC-LT-2192-2 x CC-LT-2172-3 x CC-LT-2192-3 x CC-LT-2272-1 x CC-LT-2292-1 x CC-LT-2272-2 x CC-LT-2292-2 x CC-LT-2272-3 x CC-LT-2292-3 x CC-E-153A x CC-E-153B x CC-P-322A x x CC-P-322B x x CC-V57 x x CC-V176 x x CC-V121 x x CC-V256 x x CC-FISHL-2147 x x CC-FISHL-2247 x x CC-FISHL-2248 x x CC-FISHL-2148 x x CC-V428 x CC-V439 x CC-V395 x CC-V438 x CC-TK-196 x CC-TK-196 x ED-JX2-42 x x ED-JX3-42 x x ED-MM-163H x x ED-MM-163E x x ED-PP-8B x x ED-X-16A x x IA-D-2A x x IA-D-2B x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-21 Containment Fire Area: C-F-1-Z, C-F-2-Z, C-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable IA-J97-42 x x IA-J98-42 x x SA-C-4A x x SA-C-4B x x SA-CP-134A x x SA-CP-134B x x CS-V10 x x CS-V168 x x CS-V28 x x CS-V44 x x CS-V59 x x CS-V177 x x CS-V185 x x CS-V175 x x CS-V176 x x CS-V145 x x RC-LCV-459 x x RC-LCV-460 x x RC-FV-2881 x x RC-V323 x x RC-E-10 x x RC-E-10 x x EDE-TBX-X47 x x EDE-TBX-X44 x x RC-E-11A x RC-E-11B x RC-E-11C x RC-E-11D x RC-P-1A x RC-P-1B x RC-P-1C x RC-P-1D x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-22 Containment Fire Area: C-F-1-Z, C-F-2-Z, C-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RC-PCV-456A x x RC-PCV-456B x x RC-V122 x x RC-V124 x x EDE-TBX-X56 x x EDE-TBX-X35 x x RC-TK-11 x RC-TK-11 x RC-V23 x x RC-V22 x x RC-V88 x x RC-V87 x x SI-V3 x x SI-FV-2475 x x SI-FV-2476 x x SI-V32 x x SI-FV-2477 x x SI-FV-2486 x x SI-FV-2482 x x SI-V17 x x SI-FV-2483 x x SI-FV-2495 x x SI-V47 x x SI-FV-2496 x x SI-V158 x x SI-V159 x x RH-V35 x RH-V36 x SB-V1 x x SB-V3 x x SB-V5 x x SB-V7 x x FW-LT-501 x x FW-LT-519 x x FW-LT-503 x x FW-LT-537 x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-23 Containment Fire Area: C-F-1-Z, C-F-2-Z, C-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-LT-529 x x FW-LT-502 x x FW-LT-548 x x FW-LT-504 x x NI-NE-6690 x x NI-NE-6691 x x EDE-TBX-XP8 x x EDE-TBX-XP9 x x RC-LT-459 x x RC-LT-460 x x RC-PT-455 x x RC-PT-456 x x RC-PT-457 x x RC-PT-458 x x RC-TE-413A x x IC-TE-XX x x RC-TE-423A x x RC-TE-433A x x RC-TE-443A x x IC-MM-173 x x EDE-TBX-X40 x x EDE-TBX-X48 x x EDE-TBX-X94 x x RC-TE-413B x x RC-TE-423B x x RC-TE-433B x x RC-TE-443B x x EDE-TBX-X14 x x EDE-TBX-X86 x x EDE-TBX-X52 x x EDE-TBX-X69 x x Electrical x x Electrical x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-24 Containment Fire Area: C-F-1-Z, C-F-2-Z, C-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable Penetrations Penetrations MM-IR-1 x x MM-IR-2 x x MM-IR-3 x x MM-IR-4 x x MM-IR-4 x x MM-IR-6 x x MM-IR-8 x x MM-IR-7A x x MM-IR-7A x x B. Analysis 1. General Area Analysis The following protective measures are inherent in the existing containment design:

a. The significant in situ combustibles are limited to the reactor coolant pump lubricating oil, hydraulic snubbers, cables in trays, and EPDM rubber (debris interceptor trim).
b. An oil collection system is provided for the reactor coolant pumps.
c. Each hydraulic snubber contains 3.5 gallons of a high flash point, high auto ignition point silicon

-based hydraulic fluid. The snubbers are designed to withstand an SSE without failure. Even if leaks were to develop, studies performed at Factory Mutual Research Corporation have shown that a heat flux of 16 kW/M2 is necessary to ignite a high flash point hydraulic fluid similar to the silicon based fluid. It would require the introduction of a transient combustible to containment to provide this heat flux.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-25 d. Containment is inaccessible during normal operation with the exception of operator tours. Because of this, transient combustibles are not considered as a fire hazard. This absence of transient combustibles removes the ignition source for the cables, the hydraulic fluid, and the EPDM rubber.

e. Prior to plant start

-up administrative controls will assure the removal of transient combustibles which could be brought into containment during plant shutdowns.

f. Charcoal filter CAH

-F-8 has an early fire detection system internal to the filter.

2. System Analysis
a. Containment Structure Cooling Units CAH

-AC-1A through 1F (Fans CAH-FN-1A through 1F, Speed Changers CAH -JV3-43 through CAH -JV8-43 and CC Flow Switches CC -FISL 2122 through CC -FISL-2224) Cables for the redundant cooling unit fans, speed changers and flow switches are routed through trays and conduits from the penetration where they enter containment to the cooling units. The trays are separated by concrete floors except between Columns 2 and 4, Columns 5 and 6, Columns 7 and 8, Columns 12 and 13, Columns 14 and 15, and Columns 17 and 18 where there is grating. Between Columns 2 and 4, the Train B trays are a minimum of 12 ' above floor elevation ( -) 26'-0" and a maximum of 19 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 11 ' above the grating elevation 0 '-0". There is a minimum of 18 ' of vertical separation between the redundant trays. Even if the redundant trays are affected by a fire, only two Train B and one Train A cooling unit could be affected, the other three cooling units would continue to be operable. Between Columns 5 and 6, the Train B trays are a minimum of 14' above floor elevation ( -) 26'-0" and a maximum of 19 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 18 ' above the grating elevation 0 '-0". There is a minimum of 24 ' of vertical separation between the redundant trays. Even if the redundant trays were affected by a fire, only one Train A and one Train B cooling units could be affected; the other four cooling units would continue to be operable. Between Columns 7 and 8, only one Train A cooling units ' cables are routed. There are no Train B cooling units ' cables at this location.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-26 Between Columns 12 and 13, only one Train A and one Train B cooling units ' cables are routed. The other four cooling units would continue to be operable. Between Columns 14 and 15, the Train B trays are a minimum of 19 ' above floor elevation ( -) 26'-0" and a maximum of 21 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 17 ' above the grating elevation 0 '-0". There is a minimum of 22 ' of vertical separation between the redundant trays. Even if the redundant trays were affected by a fire, the only two Train A and one Train B cooling unit could be affected. The other three cooling units would continue to be operable. Between Columns 17 and 18, the Train B trays are a minimum of 12 ' above floor elevation ( -) 26'-0" and a maximum of 19 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 11 ' above the grating elevation 0 '-0". There is a minimum of 18 ' of vertical separation between the redundant trays. Even if the redundant trays were affected by a fire, only two Train A and one Train B cooling units could be affected; the other three cooling units would continue to be operable. A maximum of three containment structure cooling units (CAH) are needed to maintain habitability of the containment. This can be any combination of Train A and B units. At all points discussed above where Train A and B cables are run near each other without concrete floor separation, there is a minimum of 18 ' of vertical separation, with the Train B cables a minimum of 12 ' off the floor. This vertical separation, the height of the cable from the floor and the lack of combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. Additionally, a fire at any of these points would affect a maximum of three out of six units, leaving three to cool containment.

b. Thermal Barrier Pumps CC

-P-322A and CC -P-322B Cables for the redundant thermal barrier pumps are routed through trays and conduits from the penetration where they enter containment to the pumps at elevation ( -) 26'-0". The trays are separated by concrete floors except between Columns 17 and 18 where there is a grating. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-27 Between Columns 17 and 18, the Train B trays are a minimum of 12 ' above floor elevation ( -) 26'-0" and a maximum of 19 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 11 ' above the grating elevation 0 '-0". There is a minimum of 18 ' of vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in trays. The conduit to the Train A pump is routed such that there is a minimum of 6 ' horizontal separation from the Train B tray that contains the redundant cable. The conduit is run approximately 22 ' above elevation ( -) 26'-0" to the point that it drops down to the Train A pump. The pump is located 6 ' above elevation (-) 26'-0" between Columns 17 and 18. The Train A pump is separated from the tray containing the cable to the Train B pump by a horizontal distance of 6 ' and a vertical distance of 9 '. In addition there are two totally enclosed instrument trays below the Train B tray. Should the thermal barrier cooling be unavailable, the redundant seal injection cooling capability located in other plant fire areas will satisfy the safe shutdown requirements. The separation height of cable from the floor and lack of in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. The redundant seal cooling satisfies the safe shutdown requirements.

c. Component Cooling Isolation Valves CC

-V57, CC-121, CC-V176, CC-V256 Cables for the redundant valves are routed through trays and conduits from the penetration where they enter containment to the valves on the west side of containment at elevation 4 '-0". The trays are separated by a concrete floor, except between Columns 17 and 18 and between Columns 14 and 15 where there is grating. Between Columns 17 and 18, the Train B trays are a minimum of 12 ' above floor elevation ( -) 26'-0" and a maximum of 19 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 11 ' above the grating elevation 0 '-0". There is a minimum of 18 ' of vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the trays.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-28 Between Columns 14 and 15, the Train B trays are a minimum of 19 ' above floor elevation ( -) 26'-0" and a maximum of 21 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 17 ' above the grating elevation 0 '-0". There is a minimum of 22 ' of vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the trays. The Train A valves CC -V57 and CC -V121 are located between Columns 14 and 15 approximately 4 ' above the grating elevation 0 '-0". The cables for the Train B valves CC -V176 and CC -V256 are routed in trays which are a minimum of 19 ' above floor elevation ( -) 26'-0". There is a minimum of 8 ' vertical separation between the Train B trays and the Train A valves. The only in situ combustibles at this location are the cables in the trays. The Train B valves CC -V176 and CC -V256 are located between Columns 12 and 13 approximately 4 ' above the grating elevation 0 '-0". Although the cables for the redundant Train A valves are not in this location, the power cables for Train A containment structure cooling unit CAH -AC-1E are routed in this area such that a fire could impact four of the six cooling units. However, the cables are routed in tray 19' above the grating elevation 0 '-0" and then in conduit to the cooling unit. There is a vertical separation of approximately 15 ' between valves CC -V176 and CC-V256 and the Train A trays. The only in situ combustibles at this location are the cables in the tray. One set of redundant valves is needed to provide component cooling water to one train of containment structure cooling units. Between Columns 17 and 18, the vertical separation is 18 ' with the lower cables 12' off the floor. The separation and height of cable from the floor provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. Between Columns 14 and 15, there is a vertical separation of 27 ', with the lower cables 19 ' off the floor. There is a minimum separation of 8 ' between the Train A valves and the Train B cables, with the Train B cables 19 ' off the floor. The separation, height of cable from the floor and lack of in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-29 Between Columns 12 and 13, there is a vertical separation of 15 ' between the Train B valves and the Train A cable. The valves are 30 ' off the floor (Elevation (-) 26'-0"). The separation, height of the valves off the floor and lack of in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. d. Component Cooling Head Tank Level Transmitters CC -LT-2172-1, 2, 3, CC-LT-2272-1, 2, 3, CC -LT-2192-1, 2, 3, CC -LT-2292-1, 2, 3 and Associated Flow Switches CC -FISHL-2147, CC-FISHL-2248, CC-FISHL-2247, CC-FISHL-2148 Cables associated with CC heat tank level transmitters which affect the Loop B outboard isolation valves CC -V175 and CC -V257 are routed in the same trays as the Loop A inboard isolation valves CC -V57 and CC -V121. Failures in these cables could cause total loss of PCCW to containment by initiation of a spurious

lo-lo head tank level signal. Loop B PCCW can be re -established by transferring control of valves CC -V175 and CC-V257 to local control at the RSS panel in fire area CB-F-1A-A. This removes the lo -lo head tank level isolation function and allows operators to re -open the valves. Cables associated with CC head tank level transmitters which affect the Loop A

outboard isolation valves CC -V122 and CC -V168 are routed in proximity to trays containing cables for the Loop B inboard isolation valves CC -V176 and CC-V256. Failures in these cables could cause total loss of PCCW to containment by initiation of a spurious l o-lo head tank level signal. Loop A PCCW can be re -established by transferring control of valves CC -V122 and CC-V168 to local control at the RSS panel in fire area CB -F-1B-A. This removes the lo-lo head tank level isolation function and allows operators to re-open the valves. The provision of a capability to isolate the affected portion of the circuit and

re-position the valves from another fire area satisfies the safe shutdown requirements.

e. Thermal Barrier Isolation Valves CC

-V395, CC-V428, CC-V438, CC-V439 Valves CC -V395, CC-V428, CC-V438 and CC -V439 are normally open valves which must remain open for safe shutdown. The valves are permanently disabled in the open position. The disabling of the above valves satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-30 f. Air Compressors and Dryers SA -C-4A, SA-C-4B, IA-D-2A, IA-D-2B and Associated Distribution Panels, Control Panels and Contactors The air compressors and their associated dryers located at elevation 0 '-0" are required only for instrument air to the primary component cooling water containment isolation valves. These valves are required to remain operable only for containment entry when manual operation of the safety injection accumulator isolation valves SI -V3, SI-V17, SI-V32, and SI -V47 and RHR inlet isolation valves RC -V22, RC-V23, RC-V87 and RC -V88 is required. The redundant air compressors and dryers are within 4 ' of one another. The Train B cables are routed in conduit from the compressors through the floor to the Train B trays. The Train B cable is routed in conduit from the air dryer to the power panel. The only in situ combustibles at this location are the cables in trays. A cross connection to the plant instrument air system is provided to back up the containment instrument air system in the event of a compressor failure. Containment isolation is provided by an air operated, fail closed valve (outboard) and a check valve (inboard). The outboard valve is operable from the Main Control Board. The cross connection is not relied upon to achieve hot/cold shutdown for containment fires and is only described here due to its potential use as a backup. The cable and control circuits are not considered Appendix R equipment and are, therefore, not listed in the respective tables. The Train A cables to valves SI -V3 and RC -V88 are routed in power and control trays a minimum of 17 ' above floor elevation 0 '-0" in the vicinity of the Train B air compressor and dryer. The trays are effectively shielded from the compressor and dryer by a 5 ' wide by 3 ' high steel ventilation duct located 8 ' above the floor between the compressor/dryer and the trays. Should the cables to valve SI-V3 fail, the accumulator can be vented by use of Train B valves SI -FV-2475 and SI-FV-2476. Further discussion of the separation between these cables is provided in Paragraph "n". Failure of the cables to RC -V88 will not prevent safe shutdown as functionally redundant valve RC -V23 will still be operable. The Train A cables to valve RC -V23 are routed in tray and conduit a minimum of 20' horizontal from the Train B air compressors and dryers and are separated by a concrete floor when they are in proximity to the equipment. The Train B cables to valves SI -V47, RC-V22 and RC -V87 are routed in trays which are separated from the Train A air compressor and dryer by a concrete floor. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-31 The cables to Train A Valve SI -V32 and Train B valve SI -V17 are routed on the opposite side of containment from the air compressors. The separation distance, radiant shielding provided by ventilation duct and lack of in situ combustibles between the air compressors/dryers and the cabling for the valves that must remain operable should the redundant compressors/dryers be damaged due to a fire provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. g. RC Pump Seal Water Isolation Valves CS -V10, CS-V28, CS-V44, CS-V59, CS-V168, and CS - Charging to RC Isolation Valves CS -V177, CS-V185 Valve CS-V168 is a normally open valve which should remain open for safe shutdown. Spurious isolation of the Train B valve CS -V168 could result in loss of RC inventory through the upstream relief valve, if CS -V10, CS-V28, CS-V44 and CS-V59 cannot be closed. This inventory is directed to the PRT and is therefore, non -recoverable. However, the postulated flow rate (12 gpm) coupled with the RCS volume shrink over the cooldown period to 350F (approximately 5 hours) is within the capabilities of the boric acid tanks. Cooldown below 350F to cold shutdown can be accomplished using the RWST. Shutdown margin is assured in all phases of this cooldown. The safe shutdown requirements are satisfied.

h. Letdown Isolation Valves CS

-V175, CS-V176, CS-V145, RC-LCV-459, RC-LCV-460 1) Excess Letdown Line Functionally redundant Train B series valves CS -V175 and CS -V176 are normally closed and remain closed for safe shutdown. The spurious opening of one valve will not prevent safe shutdown. The operators will prevent further spurious operation by tripping the power supply breakers for CS -V175 and CS -V176 at the Train B switchgear room (Fire Area: CB -F-1B-A). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-32 2) Normal Letdown Line Functionally redundant Train A series valves CS -V145, RC-LCV-459 and RC-LCV-460 are normally open and are required to close for safe shutdown. CS -V145 can be closed from the main control room. Should this valve not close due to spurious operation, the operators can close either RC -LCV-459 or RC -LCV-460 by tripping their power supply breakers at the Train A switchgear room (Fire Area: CB -F-1A-A). This will prevent further spurious operation. The capability to isolate the letdown flow paths and mitigate spurious operations from outside the fire area satisfies the safe shutdown requirements.

i. Charging Pump Test Line Isolation Valves SI

-158, SI-159 On spurious operation of either of the normally closed, fail closed valves SI -V158 (Train B) or SI-V159 (Train A), the operators will isolate the high head injection path by closing SI -V138 and SI -V139. Charging will then be accomplished utilizing the seal injection path through valves CS -V154, CS-V158, CS-V162 and CS-V166 located in Fire Zones PP -F-1A-Z and PP-F-5B-Z. The operators can close SI-V158 and SI -V159 by tripping their power supply breakers in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The capability to provide charging to the RC System through a minimum of one flow path satisfies the safe shutdown requirements.

j. Head Vent Valves RC

-FV-2881 and RC -V323 Functionally redundant Train B series valves RC -FV-2881 and RC -V323 are normally closed and remain closed for safe shutdown. The spurious opening of one valve will not prevent safe shutdown. The operators will prevent further spurious operation by tripping the power supply breakers for RC -FV-2881 and RC-V323 at the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-33 k. Pressurizer Heaters RC -E-10 and Terminal Boxes EDE -TBX-X44, EDE-TBX-X47 Cables for the redundant pressurizer heaters are routed through trays from the penetration where they enter containment to the heaters at the pressurizer. The trays are separated by concrete floors and walls from the penetration to a point 20 ' from the pressurizer except between Columns 2 and 3 where there is grating. Between Columns 2 and 3, the Train B cables are routed in trays which are a minimum of 10 ' above floor elevation ( -) 26'-0". The Train A cables are routed in trays a minimum of 18 ' above the grating elevation 0 '-0". There is a minimum of 25' vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the trays. In the area near the entrance to the pressurizer cubicle, the Train B trays are 12 ' above floor Elevation ( -) 26'-0. There is a spatial separation of approximately 6 ' between the redundant trays. The only in situ combustibles at this location are the cables in the trays. The Train A trays are 8 '-4" above the floor and the Train B trays are 18 '-6" above the floor at the entrance of the pressurizer cubicle. This is a vertical separation between redundant trays of over 8 '. Inside the cubicle, the cables are routed in enclosed wireways up to the point where they are routed to the individual pressurizer heater connections. The heaters are located over 20 ' above the floor. There are no in situ combustibles in the pressurizer heater cubicle. The containment is a controlled entry area and the fire loading is very low. The use of transient combustibles is strictly controlled. Where the grating exists, the cables of interest are separated vertically by 25 ' minimum. The lower set of cables are at least 10, off the floor. This separation and the height of the cable from the floor provide acceptable fire protection and provide protection equivalent to the technical requirement of Appendix R. At the area near the entrance to the pressurizer cubicle, there is a spatial separation of 6' between the cables of interest. There are no in situ combustibles. Access to this area is extremely limited during power operation. The separation, lack of combustibles and limited access provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-34 At the entrance to the pressurizer and inside, the case is the same, with the additional factor being the routing of the cables in enclosed wireways up to the point where they are routed to the individual pressurizer heater conditions. The separation, lack of combustibles, limited access and routing of the cables in wireways provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. l. Pressurizer Relief Valves, RC-PCV-456A, RC-PCV-456B, RC-V122 and RC-V124 Cables for the pressurizer relief valves are routed in trays and conduits from the penetration where they enter containment to the valves on the top of the pressurizer. The trays are separated by a concrete floor except between Columns 2 and 4; between Columns 5 and 6; and between Columns 7 and 8 where there is grating. Between Columns 2 and 4, the Train B cables are routed in trays which are a minimum of 10 ' above floor Elevation ( -) 26'-0". Other trays containing Train B cables are located up to 16 ' above floor Elevation ( -) 26'-0". The Train A cables are routed in trays a minimum of 18 ' above the grating Elevation 0 '-0". There is a minimum of 25 ' vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the trays. Between Columns 5 and 6, the Train B trays are a minimum of 14 ' above floor Elevation ( -) 26'-0" and a maximum of 19 ' above floor Elevation ( -) 26'-0". The Train A trays are a minimum of 18 ' above the grating Elevation 0 '-0". There is a minimum of 24 ' vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in trays; three pints of oil in 15 HP RC drain tank pump motor contributing 56,250 Btu fire load; and five pounds of grease in 3 HP containment sump pump motors contributing 90,000 Btu fire load. Between Columns 7 and 8, the Train B trays are a minimum of 13 ' above floor Elevation ( -) 26'-0" and a maximum of 19 ' above floor Elevation (-) 26'-0". The Train A trays are a minimum of 16 ' above the grating Elevation 0 '-0". There is a minimum of 23 ' of vertical separation between the redundant trays. The only situ combustibles at this location are the cables in trays.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-35 At the pressurizer, the cables are routed in conduit on opposite outside walls of the pressurizer enclosure with a minimum horizontal separation of approximately

15'. The Train A cables are routed in the area of reactor coolant pump C. Near the top of the pressurizer, the conduits enter the pressurizer cubicle and are routed on opposite sides of the cubicle over to the valves. The redundant valves are separated by 2 ' on the top of the pressurizer. There are no in situ combustibles at the top of the pressurizer. Between Columns 2 and 4 and 7 and 8, there is a minimum vertical separation of 23' between Train A and B cables. The Train B cables area minimum of 10 ' off the floor. The separation, height off the floor and lack of in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. Between Columns 5 and 6, there is a vertical separation of 25 ' with the lower cables 14 ' off the floor. The combustibles are in two motors. The separation, height off the floor, and the enclosure of combustibles in the motors provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. At the pressurizer, the cables are routed in conduit on opposite sides of the pressurizer cubicle. At the top of the pressurizer where the valves are located, there is no access during operation and there are no in situ combustibles. Adequate fire protection is provided and provides protection equivalent to the technical requirements of Appendix R. RC-PCV-456A is a normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an over -cooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an

unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V122. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV and the block valve by tripping their power supplies in the Train A switchgear room (Fire Area:

CB-F-1A-A). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-36 RC-PCV-456B is normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an over -cooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V124. For all fires, that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under this condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV and the block valve by tripping their power supplies in the Train B switchgear room (Fire area:

CB-F-1B-A). m. RHR Isolation Valves RC -V22, RC-V23, RC-V87, RC-V88 RHR isolation valves are permanently disabled in the closed position. Redundant valves RC -V23 and RC -V88 are separated by 25 ' with no intervening combustibles other than cables in trays. Redundant valves RC -V22 and RC -V87 are separated by 3 '. These valves are not needed until 9 hours into the event and are only required to be opened for cold shutdown. This can be accomplished manually, if required. Therefore, no fire protection other than the existing separation is needed. Protection equivalent to the technical requirements of Appendix R is provided.

n. Accumulator Tank Outlet Isolation Valve SI

-V3 and Vent Valves SI -FV-2475, SI-FV-2476 Cables for the redundant valves are routed through trays and conduits from the penetration where they enter containment to the valves. The trays are separated by concrete floor except between Columns 17 and 18 where there is grating. The Train A valve SI -V3 is located near column 17 at Elevation ( -) 26'-0" and the Train B, valves SI -FV-2475 and SI -FV-2476 are located near column 16 at Elevation 0'-0". The accumulator isolation valve is separated from its redundant vent valves by approximately 20 ' horizontal with an intervening concrete floor.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-37 At Elevation ( -) 26'-0" the cables to the redundant valves are in proximity such that a fire could affect operation of both trains of equipment. However, the same fire will not prevent the operation of the Train A equipment necessary for containment habitability. These valves are not required to reach or maintain hot standby. They are required to be closed before going to cold shutdown. These valves will be manually closed, if required, prior to decreasing reactor pressure below 600 psig. Prior to this time the accumulators are prevented from injection by reactor pressure acting against a check valve. Manual operation of the isolation valve is only necessary if both the valve circuit and the redundant vent valves are rendered inoperable by the fire. This manual operation can be delayed as much as 9 hours into the event. At Elevation 0 '-0" the cables to the redundant valves are in proximity such that a fire could affect operation of both trains of equipment. Additionally, the redundant air compressors/dryers necessary for containment habitability are in the same area. As discussed above, the valves are not required for 9 hours. To assure that one train of valves can be operated from the MCR or locally, a radiant energy shield is provided around the Train B vent valves and their related cables in the area of the air compressors. The horizontal separation distance between the redundant valves provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. The provision of a capability to manually operate the accumulator isolation valve satisfies the safe shutdown requirements.

o. Accumulator Tank Outlet Isolation Valve SI

-V32 and Vent Valves SI -FV-2477, SI-FV-2486 Cables for redundant valves are routed through trays and conduits from the penetration where they enter containment to the valves. The trays are separated by concrete floors except between Columns 2 and 4; between Columns 5 and 6 and between Columns 7 and 8 where there is grating. Between Columns 2 and 4, the Train B cables are routed in trays which are a minimum of 10 ' above floor Elevation ( -) 26'-0". Other trays containing Train B cables are located up to 16 ' above floor Elevation ( -) 26'-0". The Train A cables are routed in trays a minimum of 18 ' above the grating Elevation 0 '-0". There is a minimum of 25 ' vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the trays.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-38 Between Columns 5 and 6, the Train B trays are a minimum of 14 ' above floor Elevation ( -) 26'-0" and a maximum of 19 ' above floor Elevation ( -) 26'-0". The Train A trays are a minimum of 18 ' above the grating Elevation 0 '-0". There is a minimum of 24 ' of vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in trays; three pints of oil in 15 HP RC drain tank pump motor contributing 56, 250 Btu fire load; and five pounds of grease in 3 HP containment sump pump motors contributing 90,000 Btu fire load. Between Columns 7 and 8, the Train B trays are a minimum of 13 ' above floor Elevation ( -) 26'-0" and a maximum of 19 ' above floor Elevation ( -) 26'-0". The Train A trays are a minimum of 16 ' above the grating Elevation 0 '-0". There is a minimum of 23 ' of vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in trays. The Train A Valve SI -V32 is located near column 8 at Elevation ( -) 26'-0" and the Train B valves SI -FV-2477 and SI -FV-2486 are located near column 7 at Elevation 0 '-0". The accumulator isolation valve is separated from its redundant vent valves by approximately 20 ' horizontal with an intervening concrete floor. Between Columns 7 and 8 at Elevation ( -) 26'-0" the cables are in proximity such that a fire could affect operation of both trains of equipment. However, the same fire will not prevent operation of the Train A or Train B equipment necessary for containment habitability. These valves are not required to reach or maintain hot standby. They are required to be closed before going to cold shutdown. These valves will be manually closed, if required, prior to decreasing reactor pressure below 600 psig. Prior to this time the accumulators are prevented from injection by reactor pressure acting against a check valve. Manual operation of the isolation valve is only necessary if both the valve circuit and the redundant vent valves are rendered inoperable by the fire. This manual operation can be delayed as much as 9 hours into the event. Between Columns 2 and 4 and 7 and 8, there is a minimum vertical separation of 23' between Train A and B cables. The Train B cables are a minimum of 10 ' off the floor. The separation, height off the floor and lack of in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-39 Between Columns 5 and 6, there is a vertical separation of 25 ' with the lower cables 14 ' off the floor. The combustibles are in two motors. The separation, height off the floor, and the enclosure of combustibles in the motors provide acceptable fire protection and provides protection equivalent to the technical requirements of Appendix R. At the valves, the horizontal separation between the redundant valves provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. The provision of a capability to manually operate the accumulator isolation valve satisfies the safe shutdown requirements.

p. Accumulator Tank Outlet Isolation Valve SI

-V17 and Vent Valves SI -FV-2482, SI-FV-2483 Cables for the redundant valves are routed through trays and conduits from the penetration where they enter containment to the valves. The trays are separated by concrete floors except between Columns 2 and 4. Between Columns 2 and 4, the Train B cables are routed in trays which are a minimum of 10 ' above floor Elevation ( -) 26'-0. Other trays containing Train B cables are located up to 16 ' above floor Elevation ( -) 26'-0". The Train A cables are routed in trays a minimum of 18 ' above the grating Elevati on 0'-0". There is a minimum of 25 ' vertical separation between the redundant trays. The only in situ combustible at this location are the cables in the trays. The Train B valve SI -V17 is located near column 3 at Elevation ( -) 26'-0" and the Train A valves SI-FV-2482 and SI -FV-2483 are located near column 4 at Elevation 0 '-0". The accumulator isolation valve is separated from its redundant vent valves by approximately 20 ' horizontal separation with an intervening concrete floor. Between Columns 2 and 4 there is a minimum vertical separation of 25 ' between Train A and B cables. The Train B cables are a minimum of 10 ' off the floor. The separation, height off the floor and lack of in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. At the valves, the horizontal separation between the redundant valves and the intervening concrete floor provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-40 q. Accumulator Tank Outlet Isolation Valve SI -V47 and Vent Valves SI -FV-2495 and SI-FV-2496 Cables for the redundant valves are routed through trays and conduits from the penetrations where they enter containment to the valves. The trays are separated by concrete floor except between Columns 17, and 18, between Columns 14 and 15 and between Columns 12 and 13. Between Columns 17 and 18, the Train B trays are a minimum of 12 ' above floor elevation ( -) 26'-0" and a maximum of 19 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 11 ' above the grating elevation 0 '-0". There is a minimum of 18 ' of vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the tray

s. Between Columns 14 and 15, the Train B trays are a minimum of 19

' above floor elevation ( -) 26'-0" and a maximum of 21 ' above floor elevation ( -) 26'-0". The Train A trays are a minimum of 17 ' above the grating elevation 0 '-0". There is a minimum of 22' of vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the trays. Between Columns 12 and 13, the Train B cables are routed in trays which are a minimum of 20 ' above floor Elevation ( -) 26'-0". The Train A cables are routed in tray and conduit a minimum of 19 ' above the grating Elevation 0 '-0". There is a minimum of 20 ' vertical separation between the redundant cables. The only in situ combustible at this location are the cables in the trays. The Train B valve SI -V47 is located near column 12 at Elevation ( -) 26'-0" and the Train A valves SI -FV-2495 and SI -FV-2496 are located near column 13 at Elevation 0 '-0". The accumulator isolation valve is separated from its redundant vent valves by approximately 20 ' horizontal separation with an intervening concrete floor. Between Columns 17 and 18, the vertical separation is 18 ' with the lower cables 12' off the floor. The separation and height of cable from the floor provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-41 Between Columns 14 and 15, there is a vertical separation of 27 ', with the lower cables 19 ' off the floor. There is a minimum separation of 8 ' between the Train A valves and the Train B cables, with the Train B cables 19 ' off the floor. The separation, height of cable from the floor and lack of in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. Between column 12 and 13, there is a vertical separation of 20 ' with the lower cables 20 ' off the floor. The separation and height of cable from the floor provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. At the valves, the horizontal separation between the redundant valves and the intervening concrete floor provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. r. RH Heat Exchanger to CS/SI Pump Isolation Valves RH -V35, RH-V36 Cables for the redundant valves RH -V35 and RH -V36 are routed in proximity to one another in the area of the valves RC -V22, RC-V23, RV-V87 and RV -V88. Valves RH -V35 and RH -V36 are normally closed and their position is in consequential during all modes of plant operation with the exception of cooldown below 350F when the RH system is placed in operation. At that time it is necessary to assure that the valves remain closed. Should one of the valves open spuriously, the operators can disable its power supply in either the Train A or Train B switchgear room (Fire Areas: CB -F-1A-A or CB-F-1B-A) and manually reposition the valves located in the equipment vaults (Fire Zone: RHR -F-4B-Z or RHR-F-2A-Z). Manual operation of the valves can be delayed as much as 9 hours into the event. Therefore, no fire protection other than the existing separation is needed. The provision of a capability to mitigate the spurious operation of the valves outside the fire area satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-42 s. Steam Generator Blowdown Isolation Valves SB -V1, SB-V3, SB-V5, SB-V7 One Train (Train A) of the SG Blowdown isolation valves and their related cables are located in containment. The redundant train (Train B) valves SB -V9, SB-V10, SB-V11 and SB -V12 are located in the main steam and feedwater pipe chase (Fire Zone: MS -F-1B-Z). The Appendix R separation requirements are satisfied.

t. Steam Generator Level Transmitters FW

-LT-501, FW-LT-502, FW-LT-503, FW-LT-504, FW-LT-519, FW-LT-529, FW-LT-537, FW-LT-548 Cables for redundant steam generator level transmitters are routed through enclosed trays and conduits from the penetration where they enter containment to the level transmitters. As only two steam generators are required for safe shutdown, any combinations of two transmitters will satisfy the safe shutdown requirements. At the penetrations in containment the four Train A transmitter cables are separated from the four Train B transmitter cables by a concrete floor. From the penetrations the cables separate such that two Train A and two Train B transmitter cables are routed on each side of the containment up to the transmitters. The transmitters are located approximately 75 ' apart with intervening walls. The separation between redundant transmitters and their cables provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. u. Excore Nuclear Instrumentation NI -NE-6690 and NI -NE-6691 and Terminal Boxes EDE -TBX-XP8, EDE-TBX-XP9 Cables for the redundant nuclear instrumentation are routed through conduit from the penetration where they enter containment to the instruments in the reactor pit. The conduits are separated by concrete floors and walls or by a minimum of 20 ' from the penetration to the reactor pit. The only intervening combustibles between the redundant conduits are cables in trays. The conduits enter the pit approximately 3 ' apart and again separate to turn to their respective instruments, which are 16 ' apart. Because of high radiation, the pit is inaccessible during normal operation. Other than the cable in conduit, the fire loading in this area is zero. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-43 The containment is a controlled entry area and the fire loading is very low. The use of transient combustibles is strictly controlled. The minimum of 20 ' separation and the routing of cables in conduit provide acceptable fire protection in the general containment area. At the entrance to the pit and inside it, the separation, routing of cables in conduit and inaccessibility of the pit due to high radiation, provide acceptable protection and provide protection equivalent to the technical requirements of Appendix R. v. Pressurizer Level Transmitters RC -LT-459, RC-LT-460 Cables for redundant level transmitters are routed in enclosed tray and conduit from the penetration where they enter containment to the level transmitters at Elevation 0 '-0". The trays are separated by concrete floor except between Columns 2 and 4, Columns 5 and 6 and Columns 7 and 8 where there is grating. Between Columns 2 and 4, the Train B trays are a minimum of 8 ' above floor Elevation ( -) 26'-0" and the Train A trays are a minimum of 12 ' above grating Elevation 0 '-0". There is a minimum of 23 ' vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in the trays. Between Columns 5 and 6, the Train B trays are a minimum of 14 ' above floor Elevation ( -) 26'-0" and the Train A trays are a minimum of 18 ' above grating Elevation 0 '-0". There is a minimum of 29 ' vertical separation between the redundant trays. The only in situ combustibles at this location are the cables in trays: three pints of oil in 15 HP RC drain tank pump motor contributing 56,250 Btu fire load; and five pounds of grease in 3 HP containment sump pump motors contributing 90,000 Btu fire load. Between Columns 7 and 8, the Train B trays and conduit are a minimum of 14 ' above floor Elevation ( -) 26'-0" and the Train A trays are a minimum of 14 ' above grating Elevation 0 '-0". There is a minimum of 20 ' of vertical separation between the redundant raceways. The only in situ combustibles at this location are the cables in the trays.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-44 The redundant level transmitters are located 6 ' above the floor at Elevation 0 '-0". They are separated by approximately 1 '-0" horizontally. The Train B transmitter is enclosed in a non -combustible radiant energy shield. The cable to the Train A transmitter is routed in conduit from the enclosed instrumentation tray located 14 ' above the grating Elevation 0 '-0" to the transmitter. The cable to the Train B transmitter is routed in conduit from the enclosed instrumentation tray located 15 ' above floor Elevation ( -) 26'-0" to the level transmitter. The conduit is protected by a radiant energy shield above Elevation 0 '-0" until it enters the enclosure formed by the non -combustible radiant energy shield for RC -LT-460. The combustibles in the area are limited to cables in one stack of open trays (3 trays high) between elevations ( -) 12'-8" and (-) 7'-4" approximately 13 ' above floor Elevation ( -) 26'-0" and one stack of open trays (4 trays high) between elevations 16'-8" and 20'-8" approximately 16 ' above grating Elevation 0 '-0". The separation, height of the tray off of the floor, enclosure of combustibles in the motors and provision of a radiant energy shield provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. w. Pressurizer Pressure Transmitters RC -PT-455, RC-PT-456, RC-PT-457, and RC-PT-458 Redundant channels ' of pressurizer pressure instruments and cables are located in proximity. Spurious operation of two channels will initiate safety injection and containment isolation phase A signals. The operators will have the capability to terminate SI after 1 minute by use of the manual reset and block switch and terminate containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B Switchgear Rooms (Fire Areas: CB-F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-45 x. Reactor Coolant Hot Leg Temperature Elements, RC -TE-413A through RC-TE-443B, IC-TE-1 through IC -TE-58, IC-MM-173 and Terminal Boxes EDE-TBX-X40, EDE-TBX-X48, EDE-TBX-X94 Cables for redundant RC hot leg temperature elements are routed through enclosed trays and conduits from the penetration where they enter containment to the temperature elements. As only one hot leg temperature is required for safe shutdown, any of the TE 's can satisfy the safe shutdown requirements. As the TE's are at various locations around the containment, there is a minimum of 20 ' of separation except for the penetration area. At the Train A penetration area, all hot leg TE cables could fail. This function can also be performed by the Train B incore thermocouples IC -TE-1 through IC -TE-58 which are separated from the Train A penetration area by concrete walls and floors. The separation between redundant temperature monitoring capabilities and their associated cables provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. y. Reactor Coolant Cold Leg Temperature Elements RC -TE-413B through RC-TE-443B and Terminal Boxes EDE -TBX-X14 through EDE -TBX-X69 Cables for redundant RC cold leg temperature elements are routed through enclosed trays and conduits from the penetration where they enter containment to the temperature elements. As only one cold leg temperature is required for safe shutdown any one of the TE's can satisfy the safe shutdown requirements except for the penetration area. At the Train B penetration area, all cold leg TE cables could fail. This function can also be performed by the steam generator pressure instruments because cold leg temperature approximates the saturation temperature corresponding to secondary pressure. These pressure transmitters FW -PT-514, FW-PT-525, FW-PT-534 and FW -PT-545 are located in Fire Zones MS -F-3A-Z and MS-F-1B-Z. The provision of a capability to permit RC temperature monitoring outside the fire area satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-46 C. Evaluation Deviations from the Appendix R, Paragraph III.G.2 separation requirements exist in containment and have been described above and analyzed in detail. These deviations are justified based on the analyses and our assertion that additional modifications would not enhance fire protection safety which has been insured by the protective measures listed in the "General Area Analysis " and the "System Analysis ". Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CAH-FN-1C x CAH-FN-1E x CAH-FN-1F x CBA-DP-21A x CBA-DP-24A x CBA-DP-24B x CBA-DP-24C x CBA-DP-26A x CBA-E-230A x CBA-FN-14A x CBA-FN-19 x CBA-FN-20 x CBA-FN-21A x CBA-P-434A x CBA-P-435A x CBS-P-9A x CC-LT-2172-1 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-47 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-LT-2172-2 x CC-LT-2172-3 x CC-LT-2272-1 x CC-LT-2272-2 x CC-LT-2272-3 x CC-P-11A x CC-P-11C x CC-P-322A x CC-TE-2171 x CC-TV-2171-1 x CC-TV-2171-2 x CC-V57 x CC-V121 x CC-V175 x CC-V257 x CC-V145 x CC-V1101 x CC-V1109 x CO-LT-4096 x CP-CP-111 x x CP-CP-111 x x CS-FT-121 x CS-FCV-110A x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-48 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-FCV-111A x CS-FCV-110B x CS-FCV-111B x CS-FCV-121 x CS-HCV-182 x CS-LCV-112B x CS-LCV-112D x CS-LT-102 x CS-P-2A x CS-P-2B (1) (1) CS-P-3A x CS-V10 x CS-V28 x CS-V44 x CS-V59 x CS-V142 x CS-V154 x CS-V158 x CS-V162 x CS-V166 x CS-V167 x CS-V196 x CS-V460 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-49 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable (1) CS-P-2B and its cables are not actually located in this fire area. However, CS -P-2B is listed because it is potentially affected via a systems interaction. See Analysis Section B.13. DAH-DP-16A x DAH-FN-25A x DAH-FN-26A x DAH-CP-295 x DG-CP-75A x DG-CP-79 x x DG-CP-907A x DG-DG-1A x DG-P-38A x DG-C-2A x EAH-FN-5A x EAH-FN-31A x EAH-FN-174A x ED-X-14J x ED-BC-2A x ED-BC-2B x ED-I-4 x ED-PP-122B x x ED-PP-3C x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-50 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable ED-US-11 x x ED-US-23 x x EDE-B-1A x EDE-B-1C x EDE-BC-1A x x EDE-BC-1C x x EDE-CP-1E x x EDE-CP-227 x x EDE-CP-229 x x EDE-CP-248 x x EDE-I-1A x x EDE-I-1C x x EDE-I-1E x x EDE-MCC-511 x EDE-MCC-512 x x EDE-MCC-513 x EDE-MCC-514 x EDE-MCC-515 x x EDE-MCC-521 x x EDE-MCC-522 x x EDE-MCC-523 x EDE-MCC-531 x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-51 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-MM-578 x x EDE-MM-583 x x EDE-MM-585 x x EDE-PP-1A x x EDE-PP-1C x x EDE-PP-1E x x EDE-PP-11E x x EDE-PP-111A x x EDE-PP-112A x x EDE-PP-113A x x EDE-SWG-5 x x EDE-SWG-11A x x EDE-SWG-11C x x EDE-US-51 x x EDE-US-52 x x EDE-US-53 x x EPA-DP-371 x EPA-DP-373 x EPA-FN-47A x FW-FV-4214A x FW-FV-4224A x FW-FV-4234A x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-52 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-FV-4244A x FW-P-113 x FW-P-161 x FW-V156 x FW-V163 x MS-PV-3001 x MS-PV-3002 x MS-PV-3003 x MS-PV-3004 x MS-V86 x MS-V88 x MS-V90 x MS-V92 x MM-CP-1 x MM-CP-3 x MM-CP-7 x MM-CP-12 x MM-CP-108A x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-53 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MM-CP-152A x MM-CP-153 x MM-CP-297A x NI-NE-6690 x NI-NM-6690 x x NI-MM-6690J x x PAH-DP-35A x PAH-DP-36A x PAH-DP-43A x PAH-DP-357 x PAH-FN-42A x RC-E-10 (Group A) x RC-P-1A x RC-P-1B x RC-P-1C x RC-P-1D x RC-PCV-456A x RC-V23 x RC-V88 x RC-V122 x RC-E-10 (Group C,D Control) x RH-FCV-618 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-54 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RH-HCV-606 x RH-P-8A x RH-V14 x RH-V35 x RH-V70 x SA-SKD-137A x SA-C-4A x SI-FV-2482 x SI-FV-2483 x SI-FV-2495 x SI-FV-2496 x SI-P-6A x SI-V3 x SI-V32 x SI-V138 x SI-PT-937 x SW-FN-51A x SW-P-41A x SW-P-41C x SW-P-110A x SW-V2 x SW-V4 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-55 Tabulation 3.2.7.2 Control Building - El. 21' -6" Fire Area: CB -F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-V15 x SW-V16 x SW-V20 x SW-V22 x SW-V34 x SW-V54 x SW-V56 x SW-V74 x SW-V139 x SWA-DP-66 x SWA-FN-71 x SWA-FN-40A x B. Analysis 1. General Systems/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown equipment and cables. The redundant Train B safe shutdown equipment and cables are located in fire area CB -F-1B-A. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-56 2. Containment Spray Pump CBS -P-9A This pump is not required for safe shutdown, however; a fire could cause a spurious start. The operators will terminate operation of the CBS pump either by tripping and locking out the motor 's circuit breaker from the MCR or by removing all power from the 4160V emergency bus E5. The safe shutdown requirements are satisfied.

3. Component Cooling Water Containment Isolation Valves CC

-V57, CC-V121, CC-V175, CC-V257 and Head Tank Level Transmitters CC -LT-2172-1, 2, 3, CC-LT-2272-1, 2, 3 A fire could cause loss of all PCCW to containment by spurious closure of the PCCW Loop B outboard isolation valves CC -V175 and CC -V257. One train of PCCW is required to maintain containment habitable for manual valve operations. PCCW is also required for cooling air compressor SA -C-4B. Should all PCCW be isolated, the operators will immediately trip the Train B air compressor SA-C-4B to preclude operating the compressor without cooling. As the containment instrument air pressure decays without SA -C-4B operating, the PCCW Loop B inboard isolation valves will close. The operators will manually reopen the PCCW Loop B outboard isolation valves CC-V175 and CC -V257 in the mechanical penetration fire area (Fire Zone: PP-F-4B-Z). The operators will then manually open IA -V530 to connect the outside containment Loop B instrument air to the inside containment instrument air system. Once containment instrument air is restored, the PCCW Loop B inboard isolation valves will reopen to reestablish PCCW cooling to the air compressor and to the Train B containment structure coolers. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-57 4. Reactor Trip Switchgear CP -CP-111 Redundant trains of cables and equipment are located in proximity. These breakers are tripped from the MCR as an initial operator action; however, a fire in the area of the reactor trip switchgear could prevent operation of both trains of tripping capability. Should this occur the operators can remove power from the reactor trip MG sets by tripping the switching station breakers that supply power to the UAT and RAT causing a loss of offsite power to the station. This trip can be initiated from the MCR as the switching station breaker control circuits are not routed through this fire area. The removal of power from the MG sets will, after a short time delay to allow for coastdown, result in de -energizing the reactor trip solenoids and; hence, insertion of the control rods. The safe shutdown requirements are satisfied.

5. Charging Pump Flow Control Valve CS

-FCV-121 and Flow Transmitter CS-FT-121 Under normal conditions, charging is accomplished by utilizing the control valve

CS-FCV-121 and its associated transmitter. Spurious closure of this valve could isolate the seal injection path. In this event the operators will utilize the high head injection path for hot standby charging flow by opening the Train B valve SI-V139. The cables, controls and equipment required for operation of SI -V139 are not contained in the fire area. For cooldown, the operators will manually align the Train B charging pump discharge and bypass valves (CS -V219 and CS -V220) to the seal injection flow path and throttle the bypass valve as required. This operator action can be delayed for up to four (4) hours. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-58 6. RC Pump Seal Water Isolation Valves CS -V10, CS-V28, CS-V44, CS-V59 and CS-V167 Valve CS-V167 is a normally open valve which should remain open for safe shutdown. Spurious isolation of the Train A valve CS -V167 could result in loss of RC inventory through the upstream relief valve. This inventory is directed to the PRT and is therefore, non -recoverable. Additionally, cables for the functionally redundant Train A valves CS -V10, CS-V28, CS-V44 and CS -V59 are routed in proximity. However, the postulated flow rate (12 GPM) coupled with the RCS volume shrink over the cooldown period to 350F (approximately 5 hours) is within the capabilities of the boric acid tanks. Cooldown below 350F to cold shutdown can be accomplished using the RWST. Shutdown margin is assured in all phases of this cooldown. The safe shutdown requirements are satisfied.

7. RC Pump Seal Injection Isolation Valves CS

-V154, CS-V158, CS-V162 and CS-V166 Under normal conditions, these valves are utilized for the seal injection flow path. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by removing power from the 4160V emergency bus E5. MCC E512, which powers these valves, is fed from emergency bus E5. These valves provide a redundant RC pump seal cooling capability to the safety grade thermal barrier seal cooling. Cables, controls and equipment required for the Train B thermal barrier seal cooling capability are not contained in this fire area. The Appendix R separation requirements are satisfied.

8. SI-CS Suction Cross Connection Valve CS

-V460 Valve CS-V460 is a normally closed Train A valve which is required to remain closed for cooldown. Should this valve open spuriously, the functionally redundant Train B valve CS -V475 can be closed from the MCR. Cables and controls for valve CS -V475 are not located in this fire area. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-59 9. Tower Actuation Logic EDE -CP-248 Failures in TA logic cables or equipment could initiate a spurious tower actuation signal which would transfer Train A service water cooling capability from the pumphouse to the cooling towers. The transfer will not interrupt Train A service water nor will it have any impact on Train B service water. This failure does not prevent safe shutdown. The safe shutdown requirements are satisfied.

10. 4160V Switchgear EDE

-SWG-5 Although this equipment is not required for safe shutdown for fire in this area, there are many loads powered from it whose spurious operation could affect safe shutdown should they remain powered. For any fire in the Train A switchgear room that has a potential to impact safe shutdown, the operators will trip and lockout all ac power supplies (UAT, RAT, DG) to the bus from the MCR. To assure that breakers cannot spuriously reclose, the UAT and RAT breaker dc control power will be disabled at the disabling panel and the DG breaker control power will be disabled at the DG control panel both in the Train A diesel generator room (Fire Area DG -F-2A-A). Should the capability to trip the power supplies not be available due to prior loss of the dc control power, the operators can remove power by tripping the switching station breakers that supply power to the UAT and RAT causing a loss of offsite power to the station. This trip can be initiated from the MCR as the switching station breaker control circuits are not routed through this fire area. Subsequent to this loss of offsite power, the 4160V emergency switchgear bus E6 and Train B power will be supplied by the Train B diesel generator. The safe shutdown requirements are satisfied.

11. Emergency Feedwater Pump Control Valves FW

-FV-4214A, FW -FV-4224A, FW-FV-4234A and FW -FV-4244A These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by removing power from the 4160V emergency bus E5. MCC E515, which powers these valves, is fed from emergency bus E5. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-60 12. Atmospheric Relief Valves MS -PV-3001, MS-PV-3002, MS-PV-3003, MS-PV-3004 Valves MS -PV-3001, MS-PV-3002, MS-PV-3003 and MS -PV-3004 are normally closed valves. A fire would prevent operation of the Train A capabilities provided for opening and closing these valves. However, the fire would not affect the Train B capabilities and the valves will be operable for safe shutdown. Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire

that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affected air solenoids will be de -energized from the disabling panel located in Train A diesel generator room (Fire Area: DG -F-2A-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

13. Volume Control Tank Isolation Valve CS

-LCV-112B and CS-LCV-112D, and Charging Pump CS -P-2A & CS-P-2B Volume control tank (VCT) isolation valves CS -LCV-112B & -112C are normally open to provide a suction path from the VCT to the normally operating charging pump (CS -P-2A or -2B). These valves must stay open until RWST valve CS-LCV-112D or -112E is manually opened to provide a charging pump suction path from the RWST, or the boric acid tanks are manually aligned as a charging pump suction source. Spurious closure of a VCT isolation valve caused by a hot short would interrupt suction flow to the operating charging pump causing it to be damaged. If the standby charging pump has cables in the same area then its operation can also be degraded. The result would be no charging system flow. Since this fire area contains cables for CS -LCV-112B and CS -P-2A, this condition is potentially applicable for the system alignment with CS -P-2A the standby pump and CS -P-2B the operating pump.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-61 There is an electrical interlock that automatically opens opposite train RWST valve 1-CS-LCV-112E if VCT valve 1 -CS-LCV-112B is not full open (i.e., spuriously closes). The cables, controls and equipment required for automatically opening RWST valve 1 -CS-LCV-112E are not contained in this fire area. The open RWST valve provides a suction path so operating charging pump CS -P-2B will not be damaged. Since charging flow is available, the safe shutdown requirements are satisfied.

14. Not Used. 15. Reactor Coolant Pumps RC

-P-1A, RC-P-1B, RC-P-1C and RC -P-1D Cables required for trip of the RC pumps are routed through this fire area. These breakers are tripped from the MCR as an initial operator action; however, fire in this area could prevent this trip. Should this occur the operators will either trip the RC pump circuit breakers locally (Fire Area: NES -F-1A-Z) or by removing power from the RC pump motors by tripping the switching station breakers which supply power to the UAT and RAT, thus causing a loss of offsite power to the station. This trip can be initiated from the MCR as the switching station breaker control circuits are not routed through this fire area. The safe shutdown requirements are satisfied.

16. Pressurizer Relief Valves RC-PCV-456A, RC-V122 RC-PCV-456A is a normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC

-V122. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV by placing the PORV main control board control switch to the closed position. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-62 17. RHR Isolation Valves RC -V23, RC-V88 RHR isolation valves are permanently disabled in the closed position. For entry into RHR shutdown cooling valve RC -V88 must be opened. This can be accomplished manually by entry into containment, if required. This manual

operation can be delayed as much as 9 hours into the event. The safe shutdown requirements are satisfied.

18. Safety Injection Pump SI

-P-6A This pump is not required for safe shutdown; however, a fire could cause a spurious start. The operators will terminate operation of the SI pump either by tripping and locking out the motor 's circuit breaker from the MCR or by removing all power from the 4160V emergency bus E5. The safe shutdown requirements are satisfied.

19. Cooling Tower Fan SW

-F-51A, Pump SW -P-110A, Valves SW -V54, SW-V56, SW-V139, Fans SWA -FN-69 and Dampers SWA -DP-66 and SWA -FN-71 During normal plant operation, the service water pumphouse is utilized for plant cooling. The cooling towers are considered a redundant capability which may be utilized for a limited period of time during the year (e.g., tunnel heat treating). Should a fire occur during this time period the operators can utilize the Train B service water pumphouse capability. The cables, controls and equipment required for the Train B service water pumphouse capability are not contained in this fire area. The Appendix R separation requirements are satisfied.

20. Pressurizer Heaters Group C, Group D, Control Group This equipment is not required for safe shutdown; however, a fire could cause spurious operations. The operators will terminate operation of the pressurizer heaters, or mitigate the condition by tripping the heaters

' circuit breaker, by tripping off -site power from the control room, or by reducing pressure by opening a PORV. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-63 21. Containment Pressure Transmitter SI -PT-937 A cable for one channel of containment pressure instrumentation is routed through this fire area. This channel inputs to 2 out of 3 and 2 out of 4 logics which initiate protective actions. A spurious signal from one channel is not sufficient to initiate the logic and perform the protective action; hence, a failure in this cable will not prevent safe shutdown. The safe shutdown requirements are satisfied.

22. Containment Enclosure Isolation Damper, PAH

-DP-35A, PAH-DP-36A Cables for dampers PAH -DP-35A and PAH -DP-36A are routed through this area. Under normal operation both dampers are open. If both dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in the recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. Independent operation of either damper (one open and one closed) could cause an air flow problem in EAH system. This

assumes that both redundant dampers (PAH -DP-35B and PAH -DP-36B) are in their normal open position since they would not be affected by a fire in this area. Both dampers are powered from a single Train A power supply. The circuit design is such that a spurious signal will cause both dampers to operate together either both open (normal mode) or both closed (recirculation mode). The safe shutdown requirements are satisfied.

23. Control Room Air Conditioning The non-safety related chilled water system, which is powered from a non

-safety related power supply, is normally running and aligned to either the A Train or the B Train Control Building Air Conditioning System fan unit. During normal plant operation, with the non -safety subsystem aligned for Control Room cooling on the A Train fan unit, the control switch on the MCB for the safety related train will be aligned for AUTO operation. On a loss of offsite power, the non -safety chilled water subsystem will be shut down and an automatic start sequence will be

initiated via the emergency diesel generator load sequencer to restart the AC unit and start the A Train safety chiller.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-64 In the event the A Train of the CBA fails to start, operator actions, prompted by high Control Room temperature, are assumed to secure the failed chiller and associated equipment and start the B Train. All controls for the recovery are in the Control Room. The safe shutdown requirements are satisfied.

24. Boration/Dilution Flow Control Valves, CS

-FCV-110A, -111A, -110B, -111B This area contains cables for CS -FCV-110A, -111A, -110B, -111B. Spurious opening of these valves in conjunction with spurious start of a boric acid transfer pump or reactor makeup water pump may divert boric acid from the reactor coolant system affecting cold shutdown reactivity control, or result in an unplanned dilution affecting hot standby and cold shutdown reactivity control. The operators isolate the diversion flow by closing CS -FCV-110B and -111B using the main control board control switches. The operators isolate the dilution flow by closing CS -LCV-112C using the main control board control switch. The safe shutdown requirements are satisfied.

25. Charging Pump CS

-P-2A and High Head Injection Valve SI -V-138 Either charging pump CS -P-2A or CS-P-2B is normally operating. High head injection valve SI -V-138 is normally closed. If SI-V-138 spuriously opens, CS-P-2A and CS -P-2B need to be stopped to isolate charging flow to prevent pressurizer overfill. If CS-P-2A can not be stopped from the main control room because its cables are routed through this fire area, then power will be removed from Emergency Bus E5 to stop the pump (see Item 10 analysis). A fire in this area does not affect the capability to trip CS -P-2B from the main control room. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-65 Tabulation 3.2.7.3 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CAH-FN-1A x CAH-FN-1B x CAH-FN-1D x CBA-DP-21B x CBA-DP-26B x CBA-E-230B x CBA-FN-14B x CBA-FN-21B x CBA-FN-32 x CBA-FN-33 x CBA-P-434B x CBA-P-435B x CBS-P-9B x CC-LT-2192-1 x CC-LT-2192-2 x CC-LT-2192-3 x CC-LT-2292-1 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-66 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-LT-2292-2 x CC-LT-2292-3 x CC-P-11B x CC-P-11D x CC-P-322B x CC-TE-2271 x CC-TV-2271-1 x CC-TV-2271-2 x CC-V122 x CC-V168 x CC-V176 x CC-V256 x CC-V272 x CC-V1092 x CC-V1095 x CP-CP-111 x CS-LCV-112C x CS-LCV-112E x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-67 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-LT-7464 x CS-P-2A (1) (1) CS-P-2B x CS-P-3B x CS-V143 x CS-V168 x CS-V175 x CS-V176 x CS-V197 x CS-V426 x CS-V461 x CS-V475 x DAH-DP-16B x DAH-FN-25B x DAH-FN-26B x DAH-CP-296 x (1) CS-P-2A and its cables are not actually located in this fire area. However, CS -P-2A is listed because it is potentially affected via a systems interaction. See Analysis Section B.19. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-68 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable DG-CP-76A x DG-CP-80 x x DG-CP-907B x DG-DG-1B x DG-P-38B x DG-C-2B x EAH-FN-5B x EAH-FN-31B x EAH-FN-174B x ED-X-16A x EDE-B-1B x EDE-B-1D x EDE-BC-1B x x EDE-BC-1D x x EDE-CP-1F x x EDE-CP-228 x x EDE-CP-230 x x EDE-CP-249 x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-69 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-I-1B x x EDE-I-1D x x EDE-I-1F x x EDE-MCC-612 x x EDE-MCC-614 x EDE-MCC-611 x EDE-MCC-615 x x EDE-MCC-621 x x EDE-MCC-622 x x EDE-MCC-631 x x EDE-MM-580 x x EDE-PP-1B x x EDE-PP-1D x x EDE-PP-1F x x EDE-PP-11F x x EDE-PP-111B x x EDE-PP-112B x x EDE-PP-113B x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-70 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-SWG-6 x x EDE-SWG-11B x x EDE-SWG-11D x x EDE-US-61 x x EDE-US-62 x x EDE-US-63 x x EPA-DP-372 x EPA-DP-374 x EPA-FN-47B x FW-FV-4214B x FW-FV-4224B x FW-FV-4234B x FW-FV-4244B x FW-P-37B x FW-V347 x IA-SKD-18B x MM-CP-2 x MM-CP-4 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-71 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MM-CP-13 x MM-CP-108B x x MM-CP-152B x MM-CP-486B x MM-CP-297B x MS-CP-183 x x MS-CP-185 x x MS-PV-3001 x MS-PV-3002 x MS-PV-3003 x MS-PV-3004 x MS-V86 x MS-V88 x Ms-V90 x MS-V92 x NI-NE-6691 x NI-NM-6691 x x NI-NM-6691J x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-72 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable PAH-DP-35B x PAH-DP-36B x PAH-DP-43B x PAH-DP-358 x PAH-FN-42B x RC-E-10 (Group B) x RC-FV-2881 x RC-PCV-456B x RC-V22 x RC-V87 x RC-V124 x RC-V323 x RH-FCV-619 x RH-HCV-607 x RH-P-8B x RH-V26 x RH-V32 x RH-V36 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-73 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SA-SKD-137B x SA-C-4B x SI-FV-2475 x SI-FV-2476 x SI-FV-2477 x SI-FV-2486 x SI-P-6B x SI-V17 x SI-V47 x SI-V139 x SI-V158 x SW-P-41B x SW-P-41D x SW-V5 x SW-V18 x SW-V19 x SW-V23 x SW-V25 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-74 Control Building - El. 21' -6" Fire Area - CB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-V29 x SW-V31 x SWA-FN-40B x B. ANALYSIS 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A safe shutdown equipment and cables are located in fire area CB -F-1A-A. The Appendix R separation requirements are satisfied.

2. Containment Spray Pump CBS

-P-9B This pump is not required for safe shutdown, however, a fire could cause a spurious start. The operators will terminate operation of the CBS pump either by tripping and locking out the motor 's circuit breaker from MCR or by removing all power from the 4160V emergency Bus E6. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-75 3. Component Cooling Water Containment Isolation Valves CC -V122, CC-V168, CC-V176, CC-V256 and Head Tank Level Transmitters CC -LT-2192-1, 2, 3, CC-LT-2292-1, 2, 3 A fire could cause loss of all PCCW to containment by spurious closure of the PCCW Loop B outboard isolation valves CC -V122 and CC -V168. One train of PCCW is required to maintain containment habitable for manual valve operations. PCCW is also required for cooling the air compressor SA -C-4A. Should all PCCW be isolated, the operators will immediately trip the Train A air compressor SA-C-4A to preclude operating the compressor without cooling. As the containment instrument air pressure decays without SA -C-4A operating, the PCCW Loop B inboard isolation valves will close. The operators will manually reopen the PCCW Loop A outboard isolation valves CC-V-122 and CC -V-168 in the mechanical penetration fire area (Fire Zone: PP-F-4B-Z). The operators will then manually open IA -V50 to connect the outside containment Loop A instrument air to the outside containment Loop B instrument air. The operators will then manually open IA -V530 to connect the outside containment Loop B instrument air to the inside containment instrument air system. Once containment instrument air is restored, the PCCW Loop A inboard isolation valves will reopen to reestablish cooling to the air compressor and to the Train A containment structure coolers. The safe shutdown requirements are satisfied.

4. RC Pump Seal Water Isolation Valve CS

-V168 Valve CS-V168 is a normally open valve which should remain open for safe shutdown. Spurious isolation of the Train B valve could result in RC inventory loss through the upstream relief valves. This inventory is directed to the PRT and is therefore, non -recoverable. To preclude this loss of inventory, redundant isolation capability is provided for the RC pump seal return lines by means of Train A valves CS -V10, CS-V28, CS-V44 and CS -V59. The cables, controls and equipment required for the operation of CS -V10, CS-V28, CS-V44 and CS -V59 are not contained in this fire area. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-76 5. Excess Letdown Isolation Valves CS -V175 and CS -V176 Cables for functionally redundant fail closed valves CS -V175 and CS -V176 are routed in proximity. These valves are normally closed and remain closed for safe shutdown. Should either valve spuriously open, the operators will mitigate the spurious operation by disabling the power supply to CS -V175 at the disabling panel in the Train B diesel generator room (Fire Area: DG -F-2B-A). The safe shutdown requirements are satisfied.

6. Charging Pump Test Line Isolation Valve SI

-V158 On spurious operation of the normally closed, fail closed valves SI -V158 (Train B), the operators will maintain the normally closed high head injection path valves SI -V138 and SI -V139 closed. Charging will be accomplished utilizing the seal injection flow path through valves CS -FCV-121, CS-V154, CS-V158, CS-V162 and CS -V166. The cables controls and equipment required for operation of these valves are not contained in the fire area. The capability to provide charging to the RC System through a minimum of one flow path satisfies the safe shutdown requirements.

7. BAT to Charging Pump Isolation Valve CS

-V426 Valve CS-V426 is a normally closed valve which is opened to provide a path from the boric acid tanks to the charging pump suction. This path is required to begin cooldown. In the event that this valve is inoperable, the operators can provide a redundant path by manually positioning valves in the boric acid tank room (Fire Zone: PAB -F-2B-Z). The operators can maintain the plant in hot standby for the time required to perform this manual action. The safe shutdown requirements are satisfied.

8. SI-CS Suction Cross Connection Valves CS

-V461, CS-V475 Cables for valves CS -V461 and CS -V475 are located in proximity. Prior to beginning cooldown, the normally closed valve CS -V461 valve should remain closed or the functionally redundant valve CS -V475 should be closed. The isolation of this path will prevent the potential loss of boric acid tank inventory to the RWST during cooldown. In the event of a spurious valve operation which renders this flow path open, the plant can be maintained in hot standby for as long as 4 hours.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-77 Should this area be inaccessible due to the fire or should the operators desire to initiate the cooldown sooner than 4 hours, a gravity feed can be established from the boric acid tanks to the charging pumps. As the BAT head is lower than that required to return inventory to the RWST, there would be no loss of BAT inventory through this path and the position of these valves would be inconsequential. The safe shutdown requirements are satisfied.

9. Tower Actuation Logic EDE

-CP-249 Failures in TA logic cables or equipment could initiate a spurious tower actuation signal which would transfer Train B service water cooling capability from the pumphouse to the cooling towers. The transfer will not interrupt Train B service water nor will it have any impact on Train A service water. This failure does not prevent safe shutdown. The safe shutdown requirements are satisfied.

10. 4160V Switchgear EDE

-SWG-6 Although this equipment is not required for safe shutdown for fire in this area, there are many loads powered from it whose spurious operation could affect safe shutdown should they remain powered. For any fire in the Train B switchgear room that has a potential to impact safe shutdown, the operators will trip and lockout all ac power supplies (UAT, RAT, DG) to the bus from the MCR. To assure that breakers cannot spuriously reclose, the UAT and RAT breaker dc control power will be disabled at the disabling panel and the DG breaker control power will be disabled at the DG control panel, both in the Train B diesel generator room (Fire Area: DG -F-2B-A). Should the capability to trip the power supplies not be available due to prior loss of the dc control power, the operators can remove power by tripping the switching station breakers that supply power to the UAT and RAT causing a loss of offsite power to the station. This trip can be initiated from the MCR as the switching station breaker control circuits are not routed through this fire area. Subsequent to this loss of offsite power, the 4160V emergency switchgear bus E5 and Train A power will be supplied by the Train A diesel generator. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-78 11. Emergency Feedwater Pump Control Valves FW -FV-4214B, FW -FV-4224B, FW-FV-4234B and FW -FV-4244B These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by removing power from the 4160V emergency bus E6. MCC E615, which powers these valves, is fed from emergency bus E6. The safe shutdown requirements are satisfied.

12. Atmospheric Relief Valves MS

-PV-3001, MS-PV-3002, MS-PV-3003, MS-PV-3004 Valves MS -PV-3001, MS-PV-3002, MS-PV-3003 and MS -PV-3004 are normally closed valves. A fire would prevent operation of the Train B capabilities provided for opening and closing these valves. However, the fire would not affect the Train A capabilities and the valves will be operable for safe shutdown. Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affecte d air solenoids will be de -energized from the disabling panel located in Train B diesel generator room (Fire Area: DG -F-2B-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-79 13. Reactor Vent Valves RC -FV-2881, RC-V323 Functionally redundant series valves RC -FV-2881 (fail closed) and RC -V-323 are normally closed and remain closed for safe shutdown. The spurious opening of one valve will not prevent safe shutdown. The operators will prevent spurious opening of this path by disabling the power supply to valve RC -FV-2881 at the disabling panel in the Train B diesel generator room (Fire Area: DG -F-2B-A). The safe shutdown requirements are satisfied.

14. Pressurizer Relief Valves RC

-PCV-456B, RC-V124 RC-PCV-456B is normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V124. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV by placing the PORV main control board control switch to the closed position. The safe shutdown requirements are satisfied.

15. RHR Isolation Valves RC

-V22, RC-V87 RHR isolation valves are permanently disabled in the closed position. For entry into RHR shutdown cooling valve RC -V22 must be opened. This can be accomplished by entry into containment, if required. This manual operation can be delayed as much as 9 hours into the event. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-80 16. Safety Injection Pump SI -P-6B This pump is not required for safe shutdown; however, a fire could cause a spurious start. The operators will terminate operation of SI pump either by tripping and locking out the motor 's circuit breaker from the MCR or by removing all power from the 4160V emergency bus E6. The safe shutdown requirements are satisfied. 17. Containment Enclosure Isolation Damper, PAH -DP-35B, PAH-DP-36B Cables for dampers PAH -DP-35B and PAH -DP-36B are routed through this area. Under normal operation both dampers are open. If both dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in the recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. Independent operation of either damper (one open and one closed) could cause an air flow problem in EAH system. This assumes that both redundant dampers (PAH -DP-35A and PAH -DP-36A) are in their normal open position since they would not be affected by a fire in this area. Both dampers are powered from a single Train B power supply. The circuit design is such that a spurious signal will cause both dampers to operate together, either both open (normal mode) or both closed (recirculation mode). The safe shutdown requirements are satisfied.

18. Control Room Air Conditioning The non-safety related chilled water system, which is powered from a non

-safety related power supply, is normally running and aligned to either the A Train or the B Train Control Building Air Conditioning System fan unit. During normal plant operation, with the non -safety subsystem aligned for Control Room cooling on the B Train fan unit, the control switch on the MCB for the safety related train will be aligned for AUTO operation. On a loss of offsite power, the non -safety chilled water subsystem will be shut down and an automatic start sequence will be initiated via the emergency diesel generator load sequencer to restart the AC unit and start the B Train safety chiller. In the event the B Train of the CBA fails to start, operator actions, prompted by high Control Room temperature, are assumed to secure the failed chiller and associated equipment and start the A Train. All controls for the recovery are in the Control Room. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-81 19. Volume Control Tank Isolation Valve CS -LCV-112C and CS-LCV-112E, and Charging Pump CS -P-2A & CS-P-2B Volume control tank (VCT) isolation valves CS -LCV-112B & -112C are normally open to provide a suction path from the VCT to the normally operating charging pump (CS -P-2A or -2B). These valves must stay open until RWST valve CS-LCV-112D or -112E is manually opened to provide a charging pump suction path from the RWST, or the boric acid tanks are manually aligned as a charging pump suction source. Spurious closure of a VCT isolation valve caused by a hot short would interrupt suction flow to the operating charging pump causing it to be damaged. If the standby charging pump has cables in the same area then its operation can also be degraded. The result would be no charging system flow. Since this fire area contains cables for CS -LCV-112C and CS -P-2B, this condition is applicable for the system alignment with CS -P-2B the standby pump and the CS -P-2A the operating pump. There is an electrical interlock that automatically opens opposite train RWST valve 1-CS-LCV-112D if VCT valve 1 -CS-LCV-112C is not full open (i.e., spuriously closes). The cables, controls and equipment required for automatically opening RWST valve 1 -CS-LCV-112D are not contained in this fire area. The open RWST valve provides a suction path so operating charging pump CS -P-2A will not be damaged. Since charging flow is available, the safe shutdown requirements are satisfied.

20. Charging Pump CS

-P-2B and High head Injection Valve SI -V-139 Either charging pump CS -P-2A or CS-P-2B is normally operating. High head injection valve SI -V-139 is normally closed. If SI -V-139 spuriously opens, CS-P-2A and CS -P-2B need to be stopped to isolate charging flow to prevent pressurizer overfill. If CS -P-2B can not be stopped from the main control room because its cables are routed through this fire area, then power will be removed from Emergency Bus E6 to stop the pump (see Item 10 analysis). A fire in this area does not affect the capability to trip CS -P-2A from the main control room. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-82 Tabulation 3.2.7.4 Control Building - El. 21' -6" Fire Area - CB-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-B-1A x x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area CB -F-1F-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-83 Tabulation 3.2.7.5 Control Building - El. 21' -6" Fire Area - CB-F-1E-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-B-1C x x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area CB -F-1G-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-84 Tabulation 3.2.7.6 Control Building - El. 21' -6" Fire Area - CB-F-1F-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-B-1B x x B. Analysis All equipment and cables are Train B. The redundant Train A equipment and cables are in Fire Area CB -F-1D-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-85 Tabulation 3.2.7.7 Control Building - El. 21' -6" Fire Area - CB-F-1G-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-B-1D x x B. Analysis All equipment and cables are Train B. The redundant Train A equipment and cables are in Fire Area CB -F-1E-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-86 Tabulation 3.2.7.8 Control Building - El. 50' -0" Fire Area - CB-F-2A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable Cables for all systems required for Train A Safe Shutdown. Cables for all systems required for Train B Safe Shutdown. B. Analysis This area contains cables for redundant equipment required for safe shutdown. For a fire in this area, the operators will proceed with a controlled evacuation of the MCR and establishment of control from the RSS facilities. Details of the systems and equipment required for the alternative safe shutdown utilizing the RSS facilities are contained in Section 3.3. C. Evaluation The use of the RSS facilities satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-87 Tabulation 3.2.7.9 Control Building - El. 50' -0" Fire Area - CB-F-2B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CBA-DP-21A x x CBA-DP-24A x x CBA-DP-24B x x CBA-DP-24C x x CBA-DP-26A x CBA-DP-52 x CBA-E-230A x CBA-FN-14A x CBA-FN-19 x x CBA-FN-20 x x CBA-FN-21A x x CBA-FN-211A x CBA-PDS-21206 A1/A2 x CBA-TIC-5571 x DG-CP-79 x FW-FV-4214A x FW-FV-4224A x FW-FV-4234A x FW-FV-4244A x MM-CP-152A x MM-CP-153 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-88 Control Building - El. 50' -0" Fire Area - CB-F-2B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MM-CP-297A x RC-LCV-459 x RC-PCV-456A x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown equipment and cables. The redundant Train B equipment and cables are located in fire area CB -F-2C-A. The Appendix R separation requirements are satisfied.

2. Recirculation Damper CBA

-DP-52 Cables for damper CBA -DP-52 are routed through this area. This damper is normally closed and is required to remain closed for safe shutdown if only one main control room ventilation fan is operating. In the event of a spurious opening of the damper, the operators will isolate and bleed the air line to the dampers air operator and manually re -close the damper by means of a handwheel. The damper and its air supplies are located in the main control room HVAC equipment and duct area (Fire Area: CB -F-3B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-89 3. Process Control Cabinets MM -CP-153, MM-CP-297A Power cables for PCC cabinets MM -CP-153 and MM-CP-297A are routed through this fire area. The loss of power to these cabinets will result in loss of CST level transmitter CO -LT-4096 and FW -LT-4252 and emergency feedwater flow transmitters FW -FT-4214-2 and FW-FT-4234-2. The Train B CST level transmitter FW -LT-4257 is not affected by a fire in this area. Additionally, the emergency feedwater flow to two steam generators will be available along with steam generator level for all four steam generators. The Appendix R separation requirements are satisfied.

4. Normal Letdown Isolation Valve RC

-LCV-459 Cables for valve RC -LCV-459 are routed in this fire area. The cables, controls and equipment for functionally redundant valve CS -V145 are not contained in this area and; hence, will be available for safe shutdown. The Appendix R separation requirements are satisfied.

5. Control Room Air Conditioning The non-safety related chilled water system, which is powered from a non

-safety related power supply, is normally running and aligned to either the A Train or the B Train Control Building Air Conditioning System fan unit. During normal plant operation, with the non -safety subsystem aligned for Control Room cooling on the A Train fan unit, the control switch on the MCB for the safety related train will be aligned for AUTO operation. On a loss of offsite power, the non -safety chilled water subsystem will be shut down and an automatic start sequence will be initiated via the emergency diesel generator load sequencer to restart the AC unit and start the A Train safety chiller. In the event the A Train of the CBA fails to start, operator actions, prompted by high Control Room temperature, are assumed to secure the failed chiller and associated equipment and start the B Train. All controls for the recovery are in the Control Room. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-90 6. Emergency Feedwater Pump Control Valves FW -FV-4214A, FW -FV-4224A, FW-FV-4234A, FW -FV-4244A These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train A switchgear room (Fire Area: CB -F-1A-A). The safe shutdown requirements are satisfied.

7. Pressurizer Power Operated Relief Valve (PORV) RC

-PCV-456A A cable for RC -PCV-456A is routed in this area. Failure of this cable cannot cause the PORV to spuriously open, so the RCS pressure boundary is maintained. The safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-91 Tabulation 3.2.7.10 Control Building - El. 50' -0" Fire Area - CB-F-2C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CBA-DP-21B x x CBA-DP-24D x CBA-DP-24E x CBA-DP-24F x CBA-DP-26B x CBA-E-230B x CBA-FN-14B x CBA-FN-21B x x CBA-FN-32 x x CBA-FN-33 x x CBA-FN-211B x CBA-PDS-21206 B1/B2 x CBA-TIC-5572 x DG-CP-76A x DG-DG-1B x DG-CP-80 x EDE-SWG-6 x FW-FV-4214B x FW-FV-4224B x FW-FV-4234B x FW-FV-4244B x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-92 Control Building - El. 50' -0" Fire Area - CB-F-2C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MM-CP-13 x MM-CP-297B x RC-FV-2881 x RC-PCV-456B x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A equipment and cables are located in fire areas CB -F-2B-A and other fire areas. The Appendix R separation requirements are satisfied.

2. Main Control Room Cooling Equipment CBA

-E-230A, CBA -E-230B, CBA-DP-26A, CBA-DP-26B, CBA-FN-14A, CBA-FN-14B, CBA-FN-211A, CBA-FN-211B, CBA -PDS-21206A1/A2, CBA -PDS-21206B1/B2, CBA-TCV-21200A, CBA -TCV-21200B The control building Train B mechanical room - south is a Class 1 area which for safe shutdown has a primary function of providing protection for the Train B air handling equipment for the Train B switchgear rooms and battery rooms. The area is approximately 26 ft. long by 43 ft. wide by 23 ft. high with floor area of 1120 sq. ft. and volume of 25,800 cu. ft. The in situ combustibles consist of cables in trays.

There are a total of three cable trays which run horizontally through the area. When stacked, the trays run three high with the bottom tray being an enclosed instrument tray. There is approximately 200 ft. of uncovered cable tray containing a total of approximately 50 cables. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-93 Detectors are provided throughout the area. The cable for the Train A cooling equipment is routed in a conduit and box with a one-hour, fire -rated barrier. The only exception is at an interference with two HVAC duct hangers where the one -hour wrap is butted up to the hangers and pyrocrete is installed for heat transfer protection. The conduit and box are approximately 20 ft. above the floor. There are a total of eight cables in tray within 20 ft. horizontal of the barriered conduit. The redundant Train B cables are routed in tray a minimum of 25 ft. from the barriered conduit. The spatial separation, the height above the floor, the routing of one train of cables in conduit with a one -hour, fire -rated barrier and considering the limited in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III.G.2.c "in addition to 1 hour fire barrier, and automatic fire suppression system shall be installed", has been approved. 2a. Control Room Air Conditioning The non-safety related chilled water system, which is powered from a non -safety related power supply, is normally running and aligned to either the A Train or the B Train Control Building Air Conditioning System fan unit. During normal plant operation, with the non -safety subsystem aligned for Control Room cooling on the B Train fan unit, the control switch on the MCB for the safety related train will be aligned for AUTO operation. On a loss of offsite power, the non -safety chilled water subsystem will be shut down and an automatic start sequence will be initiated via the emergency diesel generator load sequencer to restart the AC unit and start the B Train safety chiller. In the event the B Train of the CBA fails to start, operator actions, prompted by high Control Room temperature, are assumed to secure the failed chiller and associated equipment and start the A Train. All controls for the recovery are in the Control Room. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-94 3. Process Protection Cabinet MM -CP-13 The power cable for the PPC cabinet MM -CP-13 is routed through this fire area. The loss of power to this cabinet will prevent opening of valves RC -V22 and RC-V87. These valves are required to be opened for cooldown below 350F when the RH System is placed in operation. Should the cable damage be such that valves cannot be operated from the MCR, the affected portion of the circuit can be isolated at the RSS panel in the Train B switchgear room (Fire Area: CB-F-1B-A) and the valves repositioned for safe shutdown. The safe shutdown requirements are satisfied.

4. Process Control Cabinet MM

-CP-297B The power cable for PCC cabinet MM -CP-297B is routed through this fire area. The loss of power to this cabinet will result in loss of CST level transmitter FW-LT-4257 and emergency feedwater flow transmitters FW -FT-4224-2 and FW-FT-4244-2. The Train A CST level transmitter FW -LT-4252 is not affected by a fire in this area. Additionally, the emergency feedwater flow to two steam generators will be available along with steam generator level for all four steam generators. The Appendix R separation requirements are satisfied.

5. Reactor Vent Valve RC

-FV-2881 A cable for the normally closed, fail closed valve RC -FV-2881 is routed through this fire area. The spurious opening of this valve will not prevent safe shutdown as functionally redundant valve RC -V323 is normally closed and has no cables, controls, or equipment in this fire area so it cannot spuriously open. The Appendix R separation requirements are satisfied.

6. Emergency Feedwater Pump Control Valves FW

-FV-4214B, FW -FV-4224B, FW-FV-4234B, FW -FV-4244B These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-95 7. Pressurizer Power Operated Relief Valve (PORV) RC -PCV-456B A cable for RC -PCV-456B is routed in this area. Failure of this cable cannot cause the PORV to spuriously open, so the RCS pressure boundary is maintained. The safe shutdown requirements are satisfied. C. Evaluation Deviations from Appendix R, Paragraph III.G.2, separation requirements exist in the Control Building El. 50 '-0" for the CBA System and have been discussed and analyzed above. A deviation from Appendix R, Paragraph III.G.2.c, "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", is requested. These deviations are justified based on the analysis and our assertion that additional modifications would not enhance fire protection safety. For the remainder of the systems affected in this analysis, the safe shutdown requirements and the Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-96 Tabulation 3.2.7.11 Control Building - El. 75' -0" Fire Area - CB-F-3A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable Cables for all systems required for Train A Safe Shutdown. Cables for all systems required for Train B Safe Shutdown. B. Analysis This area contains cables for redundant equipment required for safe shutdown. For a fire in this area, the operators will proceed with a controlled evacuation of the MCR and establishment of control from the RSS facilities. Details of the systems and equipment required for the alternative safe shutdown utilizing the RSS facilities are contained in Section 3.3. C. Evaluation The use of the RSS facilities satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-97 Tabulation 3.2.7.12 Control Building - El. 75' -0" Fire Area - CB-F-3B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CBA-CP-177 x x CBA-CP-178 x x CBA-DP-26A x x CBA-DP-26B x x CBA-E-230A x CBA-E-230B x CBA-FN-14A x x CBA-FN-14B x x CBA-FN-211A x CBA-FN-211B x CBA-DP-52 x x CBA-PDS-21206 A1/A2 x CBA-PDS-21206 B1/B2 x CBA-PDSH-5305 x x CBA-TCV-21200B x x CBA-PDSH-5306 x x CBA-TC-21200B x CBA-TCV-21200A x x CBA-TC-21200A x DG-CP-79 x DG-CP-80 x MM-CP-152A x MM-CP-153 x MM-CP-297A x MM-CP-297B x B. Analysis This area contains cables for redundant equipment required for safe shutdown. For a fire in this area, the operators will proceed with a controlled evacuation of the MCR and establishment of control from the RSS facilities. The main control room may also become uninhabitable because of smoke from a fire in this area. Details of the systems and equipment required for the alternative safe shutdown utilizing the RSS facilities are contained in Section 3.3. C. Evaluation The use of the RSS facilities satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-98 Tabulation 3.2.7.13 Control Building - El. 75' -0" Computer Room Fire Area - CB-F-3C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-99 Tabulation 3.2.7.14 This page intentionally left blank.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-100 Tabulation 3.2.7.15 Control Building - Stairwell Fire Area - CB-F-S1-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-101 Tabulation 3.2.7.16 Control Building - Stairwell Fire Area - CB-F-S2-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-102 Tabulation 3.2.7.17 Containment Enclosure Fan Area And Containment Annulus / Mechanical Penetration Area Fire Area - CE-F-l-Z, PP-F-1A-Z, PP-F-1B-Z, PP-F-2A-Z, PP-F-2B-Z, PP-F-3A-Z, PP-F-3B-Z, PP-F-4B-Z, PP-F-5B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-V175 x x CC-V122 x x CC-V257 x x CC-V168 x x CC-V1101 x x CC-V1092 x x CC-V1109 x x CC-V1095 x x CS-V142 x x CS-V143 x x CS-V154 x x CS-V158 x x CS-V162 x x CS-V166 x x CS-V167 x x EAH-AC-2A x EAH-AC-2B x EAH-FN-5A x x EAH-FN-5B x x EAH-FN-31A x x EAH-FN-31B x x EAH-DP-3A x x EAH-DP-3B x x EAH-DP-25A x x EAH-DP-25B x x EDE-TBX-YC3 x x EDE-TBX-YB3 x x PAH-DP-35B x x PAH-DP-36B x x RC-FV-2894 x x RC-FV-2896 x x RC-V23 x RC-V22 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-103 Containment Enclosure Fan Area And Containment Annulus / Mechanical Penetration Area Fire Area - CE-F-l-Z, PP-F-1A-Z, PP-F-1B-Z, PP-F-2A-Z, PP-F-2B-Z, PP-F-3A-Z, PP-F-3B-Z, PP-F-4B-Z, PP-F-5B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RC-V88 x RC-V87 x RH-V14 x x RH-V26 x x RH-V70 x x RH-V32 x x RH-V35 x RH-V36 x EDE-TBX-Y32 x x EDE-TBX-Y35 x x CBS-V8 x x CBS-V14 x x SI-V138 x x SI-V139 x x SI-PT-937 x x SI-PT-936 x x B. Analysis 1. General Area Analysis

a. Mechanical Penetration Area (PP

-F-XX-Z) The mechanical penetration area is a Class 1 concrete structure which for safe shutdown has a primary purpose of protecting the containment isolation valves for component cooling, charging pumps and RHR. The area is sectioned into compartments, separated by concrete walls, with small openings for access. This configuration would most probably limit a fire caused by transient combustibles to one zone in the area. The area contains no in situ combustibles with the exception of cable in trays. Only Train A safe shutdown cables are routed in trays. All Train B safe shutdown cables are in conduits. Personnel access to the radioactive areas will be limited to operator tours. Detectors are provided throughout the area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-104 b. Containment Fan Enclosure Area and Containment Annulus (CE -F-l-Z) The containment fan enclosure area is a Class 1 concrete structure which for safe shutdown has a primary function of providing protection for the redundant cooling and air handling equipment for the RHR, CBS, SI equipment vaults; the charging pump rooms; and the mechanical penetration area. The area is approximately 112 feet long by 21 feet wide by 29'-6" high with a floor area of 3000 sq. ft. and volume of 90,000 cu. ft. The in situ combustibles consist of cables in trays and charcoal in filters and fiberglass ladders. There are a total of seven cable trays which are stacked four high for the Train A trays and three high for the Train B trays. The bottom tray in each stack is an enclosed instrumentation cable tray. The trays are a minimum of 13'-6" above the floor. There is approximately 275 lineal ft. of uncovered cable tray containing a total of 80 cables. With the exception of three cables, the Train B cables for the fans are routed in one -hour, fire-rated barriered conduits from the point where they enter the area to the equipment. The charcoal filters which contain 1050 lbs. of charcoal each are not required for safe shutdown nor are they within 30 ft. of the cooling units. The units have an early fire detection system internal to the units. Detectors are provided throughout the area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-105 2. System/Equipment Analysis

a. Component Cooling Isolation Valves CC

-V175, CC-V257, CC-V122, CC-V168 The redundant component cooling containment isolation valves CC -V175, CC-V257, CC-V122 and CC -V168 are located in proximity. These valves are normally open and remain open for safe shutdown. The valves are provided with dual coil solenoids that must be energized to close the valves. The operators can prevent spurious operation by tripping the power supply breakers at the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). It should be noted, however, that these valves are required to remain operable only for containment entry when manual operation of the safety injection isolation valves SI -V3, SI-V17, SI-V32 and SI -V47 and the reactor coolant - RHR isolation valves RC-V22, RC-V23, RC-V87 and RC -V88 is required. Cables for these valves are not routed through this fire area; hence the valves would be operable from the main control room or the RSS control panels and containment entry would not be required. The safe shutdown requirements are satisfied.

b. Thermal Barrier Containment Isolation Valves CC

-V1101, CC -V1109, CC-V1092, CC -V1095 The redundant thermal barrier containment isolation valves CC -V1101, CC-V1109, CC -V1092, CC -V1095 are located in the same fire area. The redundant valves are in separate fire zones separated by a concrete wall. These valves are normally open and remain open for safe shutdown. The operators will prevent spurious operation of more than one valve by tripping the power supply breakers for these valves at the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-106 c. Charging Line Isolation Valves CS -V142, CS-V143 The redundant charging line isolation valves CS -V142 and CS -V143 are located in the same fire area. These valves are normally open and at least one valve is required to be closed for safe shutdown. The functionally redundant valve CS -HCV-182 is not located in this fire area; hence, it can be closed to isolate the normal charging line. The Appendix R separation requirements are satisfied.

d. Seal Injection Isolation Valves: CS

-V154, CS-V158, CS-V162, CS-V166 and High Head Injection Valves SI -V138, SI-V139 Under normal conditions, the seal injection isolation valves CS -V154, CS-V158, CS-V162 and CS -V166 are utilized for the seal injection flow path. Spurious closure of one of these valves will not prevent safe shutdown. The operators will prevent further spurious operations by tripping the power supply breakers in the Train A switchgear room (Fire Area: CB-F-1A-A). The high head injection valves SI -V138 and SI -V139 are normally closed valves which may be opened to provide a redundant hot standby charging path. If the seal injection path is available, the position of these valves during hot standby is inconsequential. On cooldown, the operators will either close or maintain closed the high head injection path. If the high head injection path cannot be isolated, a capability is provided to manually align and throttle the charging pumps to the seal injection flow paths. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-107 e. RC Pump Seal Water Isolation Valve CS -V167 Valve CS-V167 is a normally open valve that should remain open for safe shutdown. Spurious isolation of the Train A valve could result in loss of inventory through the upstream relief valve. This inventory is directed to the PRT and is, therefore, non -recoverable. To preclude this loss of inventory, functionally redundant isolation capability is provided by the RC pump seal return lines by means of Train A valves CS -V10, CS-V28, CS-V44 and CS -V59 and the excess letdown line by means of normally closed, fail closed valves CS -V175 or CS -V176. The cables, controls and equipment required for operation of valves CS -V10, CS-V28, CS-V44, CS-V59, CS-V175 and CS -V176 are not contained in this fire area. The Appendix R separation requirements are satisfied.

f. Containment Enclosure Cooling Units EAH

-AC-2A, EAH-AC-2B; Fans EAH-FN-5A, EAH-FN-5B; Dampers EAH -DP-3A, EAH-DP-3B and Terminal Boxes EDE -TBX-YC3, EDE-TBX-YB3 The redundant cooling units EAH -AC-2A and EAH -AC-2B are totally enclosed fiberglass insulated steel units which house the motor, fan and cooling coils. The units are separated by 8 ft. of clear space and the fan motors EAH -FN-5A and EAH -FN-5B are approximately 25 ft. apart. During normal operation only one cooling unit is required to operate. An analysis has shown that a worst case fire caused by burning five (5) gallons of heptane between the cooling units can affect potentially one cooling unit. All Train B cables required for operation of the cooling unit EAH -AC-2B are routed in one -hour, fire -rated barriered conduits from the rated fire wall where they enter the fire area to the equipment. The spatial separation, the routing of one train of cables in a conduit with a one-hour, fire -rated barrier, the limited in situ combustibles provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-108 g. Containment Enclosure Return Fans EAH -FN-31A, EAH-FN-31B and Dampers EAH -DP-25A and EAH -DP-25B. The redundant return fans EAH -FN-31A and EAH -FN-31B are located 20 ft. above the floor and are an integral part of the HVAC ducts (one in each duct). These fans are required to maintain the equipment vaults habitable for entry if manual operations are required to place RHR into operation for cold shutdown. A fire in the containment enclosure fire zone CE -F-1-Z will not prevent operation from the MCR of any equipment necessary for RHR operation; hence, habitability of the equipment vaults is not required. Analysis and field testing has confirmed that the containment enclosure supply fan EAH -FN-5A or EAH -FN-5B is sufficient to maintain the equipment vaults below the equipment 's qualified temperatures. The safe shutdown requirements are satisfied.

h. Containment Enclosure Isolation Damper, PAH

-DP-35B, PAH-DP-36B Cables for dampers PAH -DP-35B and PAH -DP-36B are routed through this area. Under normal operation both dampers are open. If both dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in the recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. Independent operation of either damper (one open and one closed) could cause an air flow problem in EAH system. This assumes that both redundant dampers (PAH -DP-35A and PAH -DP-36A) are in their normal open position since they would not be affected by a fire in this area. Both dampers are powered from a single Train B power supply. The circuit design is such that a spurious signal will cause both dampers to operate together, either both open (normal mode) or both closed (recirculation mode). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-109 i. RHR Isolation Valves RC -V22, RC-V23, RC-V87, RC-V88 and Sample Valves RC -FV-2894, RC-FV-2896 Redundant cables associated with the position indicating lights for the RHR isolation valves are contained in this area. Failure of these circuits will not prevent the operators from opening the valves for entry into cold shutdown. Although this indication is desirable, other means are available to confirm RH system operability (e.g. RH Pump Flow). The safe shutdown requirements are satisfied.

j. H Pump to Cold Leg Isolation Valves RH

-V14, RH-V26 Valves RH -V14 and RH -V26 are normally open valves which are required to remain open for RH systems operation (cold shutdown). These valves and their related cables are in proximity. If either valve spuriously closes, the operators will prevent further spurious operation of the redundant valve by tripping the power supply breakers in either the Train A or Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

k. RH Pump to Hot Leg Isolation Valves RH

-V70, RH-V32 Valves RH -V70 and RH -V32 are normally closed valves which are required to remain closed for RH system operation (cold shutdown). These valves and their related cables are in proximity. If either valve spuriously opens, the operators will prevent further spurious operation of the redundant valve by tripping the power supply breakers in either the Train A or Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-110 l. RH Heat Exchanger to CS/SI Pump Isolation Valves RH-V35, RH-V36, Containment Sump Isolation Valves CBS -V8, CBS-V14 and Terminal Boxes EDE -TBX-Y32, EDE-TBX-Y35 Cables for the redundant valves RH -V35 and RH -V36 are routed in proximity to one another. Valves RH -V35 and RH -V36 are normally closed and their position is inconsequential during all modes of plant operation with the exception of cooldown below 350F when the RH system is placed in operation. At that time it is necessary to assure that the valves remain closed. Should one of the valves open spuriously the operators can disable its power supply in either the Train A or Train B switchgear rooms (Fire Areas: CB -F-1A-A or CB-F-1B-A) and manually reposition the valves located in the equipment vaults (Fire Zone RHR-F-4B-Z or RHR-F-2-A-Z). Manual operation of the valves can be delayed as much as 9 hours into the event. Therefore, no fire protection other than the existing separation is needed. The provision of a capability to mitigate the spurious operation of the valves outside the fire area satisfies the safe shutdown requirements.

m. Containment Pressure Transmitters SI

-PT-936, SI-PT-937 Redundant channels of containment pressure instruments and cables are located in proximity. Spurious operation of these channels will initiate containment spray and containment isolation Phase B. The operators will have the capability to terminate these protective actions by use of manual reset switches. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -1F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-111 C. Evaluation Deviations from the Appendix R, Paragraph III.G.2 separation requirements exist in the containment fan enclosure area and the mechanical penetration area, and have been discussed and analyzed above. A deviation for Appendix R, Paragraph III G.2c, "in addition to a 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved. These deviations are justified based on the analysis and our assertion that additional modifications would not enhance fire protection safety.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-112 Tabulation 3.2.7.18 Condensate Storage Tank Fire Area - CST-F-1-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CO-LT-4096 x x CO-TK-25 x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area EFW -F-l-A. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-113 Tabulation 3.2.7.19 This page intentionally left blank.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-114 Tabulation 3.2.7.20 This page intentionally left blank.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-115 Tabulation 3.2.7.21 Cooling Tower - El. 22'-0" Fire Area - CT-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-MCC-641 x x EDE-SWG-6 x SW-P-41B x SW-P-41D x SW-V25 x B. Analysis All equipment and cables are Train B. Thus Train B service water supplied either by the service water pumps or cooling tower pumps are not available due to a fire in this area. The redundant Train A equipment and cables are in Fire Area CT -F-1D-A, separated from this area by a 3 -hour fire wall. Train A service water, normally supplied by Train A service water pump is available. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-116 Tabulation 3.2.7.22 Cooling Tower - El. 22'-0" Fire Area - CT-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-MCC-513 x x SW-FN-51A x SW-P-41A x SW-P-41C x SW-P-110A x SW-V54 x SW-V56 x SW-V139 x SWA-DP-64B x SWA-DP-66 x SWA-FN-64 x SWA-FN-71 x SWA-L-28 x SWA-TSH-5669 x x B. Analysis All equipment and cables are Train A. Thus Train A service water supplied either by the service water pumps or cooling tower pump are not available due to a fire in this area. The redundant Train B equipment and cables are in Fire Area CT -F-1C-A, separated from this area by a 3 -hour fire wall. Train B service water, normally supplied by Train B service water pump is available. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-117 Tabulation 3.2.7.23 This page intentionally left blank

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-118 Tabulation 3.2.7.24 Cooling Tower - El. 46'-0" Fire Area - CT-F-2B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-FN-51A x SW-P-41A x SW-P-41B x SW-P-41C x SW-P-41D x SW-P-110A x x SW-V54 x x SW-V25 x x SW-V55 x SW-V56 x x SW-V139 x SWA-DP-66 x x SWA-FN-64 x x SWA-FN-71 x x SWA-TSH-5667 x x B. Analysis Redundant equipment and cables are located in the same fire area. The plant will normally be operating on service water pumps SW -P-41A, B, C, and D. These pumps are located in the service water pump house which is a separate area (Fire Area: SW -F-1E-Z). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-119 This area contains valves SW -V25 and SW -V54 which are normally closed. The spurious opening of SW -V25 would divert B Train service water flow to the cooling tower thus reducing cooling flow to the diesel generator and PCCW heat exchangers. Spurious opening of SW -V54 would result in the same condition for the A Train service water system. The operators will prevent further spurious operation of the redundant valve by tripping the power supply breakers for EDE -MCC-513 at the 480 Volt Unit Substation E51 (Fire Area: CB -F-1A-A) for SW -V54 and the EDE -US-64 supply breaker at 4160 Switchgear E6 (Fire Area: CB -F-1B-A) for valve SW -V25. Thus, one train of service water capability is assured. Permissive logic for redundant SW pumps could prevent the redundant SW pumps from being started (Note: one pump of each Train is normally running). The operators will prevent spurious operation of the permissive logic by tripping the power supply breakers at the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). This area contains cooling tower fan SW -F-51A, pump SW -P110A, valves SW -V54, SW-V55, SW-V56, SW-V139, fans SWA -FN-64, SWA-FN-71, damper SWA -DP-66 and switch SWA -TSH-5667. The cooling towers are considered a redundant capability which may be utilized for a limited period of time during the year (e.g., tunnel heat treating). Should a fire occur during this time period the operators can utilize the Train B service water pumphouse capability. The cables, controls and equipment required for the Train B service water pumphouse capability are not contained in this fire area. C. Evaluation The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-120 Tabulation 3.2.7.25 Cooling Tower - Fans Fire Area - CT-F-3-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-FN-51A x x SW-V139 x x B. Analysis All equipment and cables are Train A. However, the fire in this area does not affect the Train A or Train B service water pumps and associated equipment (located in Fire Area SW-F-1E-Z) which will normally be operating. Safe shutdown is not affected. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-121 Tabulation 3.2.7.26 Duct Bank - ET To SW-0" Fire Area - DCT-F-1A-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-CP-248 x EDE-MCC-514 x SW-P-41A x SW-P-41C x SW-PT-8272 x SW-PT-8273 x SW-PT-8274 x SW-V2 x SW-V22 x SWA-FN-40A x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area DCT -F-1B-0. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-122 Tabulation 3.2.7.27 Duct Bank - ET To SW Fire Area - DCT-F-1B-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-CP-249 x EDE-MCC-614 x SW-P-41B x SW-P-41D x SW-PT-8282 x SW-PT-8283 x SW-PT-8284 x SW-V29 x SW-V31 x SWA-FN-40B x B. Analysis All equipment and cables are Train B. The redundant Train A equipment and cables are in Fire Area DCT -F-1A-0. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-123 Tabulation 3.2.7.28 Duct Bank - PAB To CT Fire Area - DCT-F-2A-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-MCC-513 x SW-FN-51A x SW-P-41A x SW-P-41C x SW-P-110A x SW-V54 x SW-V56 x SW-V139 x SWA-DP-66 x SWA-FN-64 x SWA-FN-71 x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area DCT -F-2B-0 and other plant fire areas. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-124 Tabulation 3.2.7.29 Duct Bank - PAB To CT Fire Area - DCT-F-2B-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-SWG-6 x SW-P-41B x SW-P-41D x SW-V25 x B. Analysis All equipment and cables are Train B. The redundant Train A equipment and cables are in Fire Area DCT -F-2A-0. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-125 Tabulation 3.2.7.30 Duct Bank - CB to PAB Fire Area - DCT-F-3B-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-P-11B x CC-P-11D x CC-TE-2271 x CC-TV-2271-1 x CC-TV-2271-2 x CC-V122 x CC-V168 x CC-V1092 x CC-V1095 x CS-LCV-112C x CS-LCV-112E x CS-LT-7464 x CS-P-2A (1) (1) CS-P-2B x CS-P-3B x CS-V143 x CS-V197 x EAH-FN-5B x EAH-FN-31B x EDE-SWG-6 x PAH-DP-43B x (1) CS-P-2A and its cables are not actually located in this fire area. However, CS -P-2A is listed because it is potentially affected via a systems interaction. See Analysis Section B.4.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-126 Duct Bank - CB to PAB Fire Area - DCT-F-3B-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable PAH-DP-358 x PAH-FN-42B x RC-V22 x RC-V87 x SI-V139 x SW-P-41B x SW-P-41D x SW-V5 x SW-V18 x SW-V19 x SW-V23 x SW-V25 x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown cables. The redundant Train A safe shutdown cables are located in Fire Area PAB -F-1G-A. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-127 2. Component Cooling Water Pumps CC -P-11B, CC-P-11D and Component Cooling Water Containment Isolation Valves CC -V122, CC-V168 A fire could cause loss of all PCCW to Containment. It should be noted, however, that these valves are required to remain operable only for containment entry when manual operation of the safety injection isolation valves SI -V3, SI-V17, SI-V32 and SI -V47 and the reactor coolant - RHR isolation valves RC-V22, RC-V23, RC-V87 and RC -V88 are required. Cables for these valves are not routed through this fire area; hence, the valves would be operable from the main control room or the RSS control panels and containment entry would not be required. The safe shutdown requirements are satisfied.

3. RHR Isolation Valves RC

-V22, RC-V87 Redundant cables associated with the position indicating lights for the RH R isolation valves are contained in this area. Failure of these circuits will not prevent the operators from opening the valves for entry into cold shutdown. Although this indication is desirable, other means are available to confirm RH System operability (e.g. RH Pump Flow). The safe shutdown requirements are satisfied.

4. Volume Control Tank Isolation Valve CS

-LCV-112C and Charging Pump CS-P-2A & CS-P-2B Volume control tank (VCT) isolation valves CS -LCV-112B & -112C are normally open to provide a suction path from the VCT to the normally operating charging pump (CS -P-2A or -2B). These valves must stay open until RWST valve CS-LCV-112D or -112E is manually opened to provide a charging pump suction path from the RWST, or the boric acid tanks are manually aligned as a charging pump suction source. Spurious closure of a VCT isolation valve caused by a hot short would interrupt suction flow to the operating charging pump causing it to be damaged. If the standby charging pump has cables in the same area then its operation can also be prevented. The result would be no charging system flow. Since this fire area contains cables for CS -LCV-112C and CS -P-2B, this condition is potentially applicable for the system alignment with CS -P-2B the standby pump and CS -P-2A the operating pump.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-128 The CS-LCV-112C circuit design prevents spurious valve closure from hot shorts as follows. The field cable conductors for the motor control center (MCC) contactor close coil circuit are in different cables than the 120 V "hot" circuit conductors eliminating the hot short failure mode within the cables. Cable-to-cable hot shorts need not be postulated for thermoset cable insulation as used at Seabrook. Since CS -LCV-112C will not spuriously close, CS -P-2A as the operating charging pump will not be damaged. Also, the CS -LCV-112C and CS-P-2B cables are routed in separate concrete encased conduits within the duct bank so that one fire can not damage both the valve and the standby pump cables. Since charging flow is available, the safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-129 Tabulation 3.2.7.31 East MUA Fire Area - DCT-F-4A-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-130 Tabulation 3.2.7.32 East MUA Fire Area - DCT-F-4B-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-131 Tabulation 3.2.7.33 East MUA Fire Area - DCT-F-5A-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-132 Tabulation 3.2.7.34 East MUA Fire Area - DCT-F-5B-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-133 Tabulation 3.2.7.35 Duct Bank - SWPH To CW Fire Area - DCT-F-6-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-134 Tabulation 3.2.7.36 Duct Bank - TB To CST Fire Area - DCT-F-7-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CO-LT-4096 x B. Analysis Train A cable is located in this area. The redundant cable and equipment is located in fire area EFW-F-1-A. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-135 Tabulation 3.2.7.37 Diesel Generator Building - El. (-) 16'-0" Fire Area - DG-F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable DG-P-38A x x DG-S-5A x DG-TK-26A x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area DG -F-1B-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-136 Tabulation 3.2.7.38 Diesel Generator Building - El. (-) 16'-0" Fire Area - DG-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable DG-P-38B x x DG-S-5B x DG-TK-26B x B. Analysis All equipment and cables are Train B. The redundant Train A equipment and cables are in Fire Area DG -F-1A-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-137 Tabulation 3.2.7.39 Diesel Generator Building - El. 21'-6" Fire Area - DG-F-2A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CBA-E-230A x CBA-P-434A x CBA-P-435A x DAH-DP-16A x x DAH-FN-25A x DAH-FN-26A x x DAH-TB-5529-1 x x DAH-TE-5529-1 x x DAH-TT-5529-1 x x DAH-CP-295 x x DG-C-2A x x DG-C-18A x x DG-CP-36 x x DG-CP-75A x x DG-CP-75B x x DG-CP-907A x x DG-DG-1A x x DG-P-38A x DG-SKD-17A x x DG-TBX-HF7 x x DG-TK-45A x DG-TK-45B x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-138 Diesel Generator Building - El. 21'-6" Fire Area - DG-F-2A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable ED-I-4 x EDE-MCC-511 x x EDE-SWG-5 x FW-FV-4214A x FW-FV-4224A x FW-FV-4234A x FW-FV-4244A x MM-CP-12 x MM-CP-297A x MM-CP-450A x x MS-PV-3001 x MS-PV-3003 x RC-LCV-459 x RC-PCV-456A x SW-V16 x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown equipment and cables. The redundant Train B equipment and cables are located in fire area DG -F-2B-A. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-139 2. Process Protection Cabinet MM -CP-12 The power cables for the PPC cabinet MM -CP-12 is routed through this fire area. The loss of power to this cabinet will prevent opening of valves RC -V23 and RC-V88. Valve RC -V88 is required to be opened for cooldown below 350F when the RH system is placed in operation. Should the cable damage be such that valves cannot be operated from the MCR, the affected portion of the circuit can be isolated at the RSS panel in the Train A switchgear room (Fire Area: CB -F-1A-A) and the valves repositioned for safe shutdown. The safe shutdown requirements are satisfied.

3. Process Control Cabinet MM

-CP-297A The power cable for PCC cabinet MM -CP-297A is routed through this fire area. The loss of power to this cabinet will result in loss of CST level transmitter FW-LT-4252 and emergency feedwater flow transmitters FW -FT-4214-2 and, FW-FT-4234-2. The Train B CST level transmitter FW -LT-4257 is not affected by a fire in this area. Additionally, the emergency feedwater flow to two steam generators will be available along with steam generator level for all four steam generators. The Appendix R separation requirements are satisfied.

4. Normal Letdown Isolation Valve RC

-LCV-459 Cables for valve RC -LC-459 are routed in this fire area. The cables, controls, and equipment for functionally redundant valve CS -V145 are not contained in this area and; hence, will be available for safe shutdown. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-140 5. Pressurizer Power Operated Relief Valve RC -PCV-456A RC-PCV-456A is a normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V122. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV by tripping its power supply in the Train A switchgear room (Fire Area: CB -F-1A-A). The safe shutdown requirements are satisfied.

6. Control Room Air Conditioning The non-safety related chilled water system, which is powered from a non

-safety related power supply, is normally running and aligned to either the A Train or the B Train Control Building Air Conditioning System fan unit. During normal plant operation, with the non-safety subsystem aligned for Control Room cooling on the A Train fan unit, the control switch on the MCB for the safety related train will be aligned for AUTO operation. On a loss of offsite power, the non -safety chilled water subsystem will be shut down and an automatic start sequence will be initiated via the emergency diesel generator load sequencer to restart the AC unit and start the A Train safety chiller. In the event the A Train of the CBA fails to start, operator actions, prompted by high Control Room temperature, are assumed to secure the failed chiller and associated equipment and start the B Train. All controls for the recovery are in the Control Room. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-141 7. Emergency Feedwater Pump Control Valves FW-FV-4214A, FW -FV-4224A, FW-FV-4234A, FW -FV-4244A These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train A switchgear room (Fire Area: CB -F-1A-A). The safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-142 Tabulation 3.2.7.40 Diesel Generator Building - El. 21'-6" Fire Area - DG-F-2B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CBA-P-434B x CBA-P-435B x DAH-DP-16B x x DAH-FN-25B x DAH-FN-26B x x DAH-TB-5530-1 x x DAH-TE-5530-1 x x DAH-TT-5530-1 x x DAH-CP-296 x x DG-C-2B x x DG-C-18B x x DG-CP-37 x x DG-CP-76A x x DG-CP-76B x x DG-CP-907B x x DG-DG-1B x x DG-P-38B x DG-SKD-17B x x DG-TBX-HF8 x x DG-TK-45C x DG-TK-45D x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-143 Diesel Generator Building - El. 21'-6" Fire Area - DG-F-2B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-MCC-611 x x EDE-SWG-6 x FW-FV-4214B x FW-FV-4224B x FW-FV-4234B x FW-FV-4244B x MM-CP-13 x MM-CP-450B x x MS-PV-3002 x MS-PV-3004 x RC-FV-2881 x RC-PCV-456B x SW-V18 x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A equipment and cables are located in fire area DG -F-2A-A and other fire areas. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-144 2. Process Protection Cabinet MM -CP-13 The power cables for the PPC cabinet MM -CP-13 are routed through this fire area. The loss of power to this cabinet will prevent opening of valves RC -V22 and RC-V87. Valve RC -V22 is required to be opened for cooldown below 350F when the RH System is placed in operation. Should the cable damage be such that the valves cannot be operated from the MCR, the affected portion of the circuit can be isolated at the RSS panel in the Train B switchgear room (Fire Area: CB-F-1B-A) and the valves repositioned for safe shutdown. The safe shutdown requirements are satisfied.

3. Reactor Vent Valve RC

-FV-2881 A cable for the normally closed, fail closed valve RC -FV-2881 is routed through this fire area. The spurious opening of this valve will not prevent safe shutdown as functionally redundant valve RC -V323 is normally closed and has no cables, controls, or equipment in this fire area so it cannot spuriously open. The Appendix R separation requirements are satisfied.

4. Pressurizer Power Operated Relief Valve RC

-PCV-456B RC-PCV-456B is a normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V124. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under this condition, the initial short will not cause depressurization. To prevent subsequent

spurious operations, the operators will de -energize the PORV by tripping its power supply in the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-145 5. Control Room Air Conditioning The non-safety related chilled water system, which is powered from a non -safety related power supply, is normally running and aligned to either the A Train or the B Train Control Building Air Conditioning System fan unit. During normal plant operation, with the non -safety subsystem aligned for Control Room cooling on the B Train fan unit, the control switch on the MCB for the safety related train will be aligned for AUTO operation. On a loss of offsite power, the non -safety chilled water subsystem will be shut down and an automatic start sequence will be initiated via the emergency diesel generator load sequencer to restart the AC unit and start the B Train safety chiller. In the event the B Train of the CBA fails to start, operator actions, prompted by high Control Room temperature, are assumed to secure the failed chiller and associated equipment and start the A Train. All controls for the recovery are in the Control Room. The safe shutdown requirements are satisfied.

6. Emergency Feedwater Pump Control Valve s FW-FV-4214B, FW

-FV-4224B, FW-FV-4234B, FW -FV-4244B These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-146 Tabulation 3.2.7.41 Diesel Generator Building - El. 51'-6" Fire Area - DG-F-3A-Z, DG-F-3B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CBA-E-230A x x CBA-E-230B x x CBA-FN-211A x x CBA-FN-211B x x CBA-P-434A x x CBA-P-434B x x CBA-P-435A x x CBA-P-435B x x CBA-PDS-21202A x x CBA-PDS-21202B x x CBA-PDS-21206 A1/A2 x x CBA-PDS-21206 B1/B2 x x DAH-FN-25A x x DAH-FN-25B x x DAH-FISH-5529 x x DAH-FISH-5530 x x DG-CP-76A x DG-DG-1B x EDE-SWG-6 x MM-CP-13 x RC-LCV-459 x RC-FV-2881 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-147 B. Analysis 1. General Area Analysis The diesel generator mechanical equipment room is a Class 1 area which for safe shutdown has a primary function of providing protection for the redundant air handling equipment for the diesel generator rooms. The area is approximately 86 ft long by 37 ft. wide by 26 ft. high with a floor area of 3200 sq. ft. and volume of 83,000 cu. ft. The in situ combustibles consist of cables in trays, 7 gallons of oil in equipment, and fiberglass ladders. There are a total of six cable trays which run horizontally and vertically through the area. When stacked the trays are run three high with the bottom tray being an enclosed instrumentation cable tray. There is approximately 375 ft. of uncovered cable tray containing a total of approximately 80 cables. Detectors are provided throughout the area. An analysis has shown that a worst case fire caused by burning 3.5 gallons of oil will not affect the operation of the Safe Shutdown equipment.

2. System/Equipment Analysis
a. Main Control Room Cooling CBA

-E-230A, CBA -E-230B, CBA-FN-211A, CBA -FN-211B, CBA -P-434A, CBA -P-435A, CBA-P-434B, CBA -P-435B, CBA -PDS-21202A, CBA -PDS-21202B, CBA-PDS-21206A1/A2, CBA -PDS-21206B1/B2 The redundant control room cooling equipment and cables are located in the same fire area. A fire in this area can cause total loss of this cooling capability. Should this occur, the operators will utilize the evaporator fans CBA-FN-14A, 14B to supply outside air into the control room. These fans and their cables are not in this fire area. An air inlet and exhaust path, utilizing these fans, can be established by opening certain doors in the control room complex which will allow air to enter into the fan intake plenum from the south stairwell and exhaust the control room via the double doors to the turbine building. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-148 b. Diesel Generator Room Cooling DAH-FN-25A, DAH-FN-25B, DAH-FISH-5529, DAH -FISH-5530 The Safe Shutdown cables for the fans and flow switches are routed in barriered conduit from the floor where they enter the area to the equipment (a distance of approximately 20 feet or less). The one -hour, fire -rated barrier is reduced at two locations or stops approximately two feet from the equipment because of access or potential interference. The redundant fans and dampers are separated by approximately 28 feet with the only intervening combustible being approximately 44 cables in three vertical/horizontal Train B trays and approximately 33 cables in two horizontal Train A trays. The Train A and Train B trays are separated by 8 ft. The redundant flow switches and associated conduits are separated by 45 ft. with the above trays containing the only intervening combustibles. The spatial separation, the routing of both trains of cables in separate conduits with a one -hour, fire -rated barrier and the limited in situ combustibles provide acceptable fire protection equivalent to the technical requirements of Appendix R. Note: A deviation was requested and granted for not installing suppression in this location. Since that deviation was granted the following conservative changes have been made, the electrically operated supply dampers have been changed to back draft dampers and the supply fan flow switch interlock with the exhaust fan has been removed. Cables for the flow switch are still routed in barriered conduit because their failure could effect the control circuit for the supply fan. These changes do not adversely effect the basis of the deviation.

c. Diesel Generator Control DG

-CP-76A, DG-DG-1B, EDE-SWG-6 The cables for control panels DG -CP-76A and DG -DG-1B are located in this area. Failure of these cables will render the Train B diesel inoperable from the main control room. The operators can re -establish Train B diesel operability by transferring control to the RSS panel located in the Train B diesel room (Fire Area: DG -F-2B-A). Operation of the diesel from the RSS panel will also allow re -establishing emergency power to EDE-SWG-6 by isolation of the faulted main control room cables. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-149 d. Process Protection Cabinet MM -CP-13 The power cable for the PPC cabinet MM -CP-13 is routed through this fire area. The loss of power to this cabinet will prevent opening of valves RC-V22 and RC -V87. These valves are required to be opened for cooldown below 350F when the RH system is placed in operation. Should the cable damage be such that valves cannot be operated from the MCR, the affected portion of the circuit can be isolated at the RSS panel in the Train B switchgear room (Fire Area: CB -F-1B-A) and the valves repositioned for safe shutdown. The safe shutdown requirements are satisfied.

e. Normal Letdown Isolation Valve RC

-LCV-459 Cables for valve RC -LCV-459 are routed in this fire area. The cables, controls and equipment for functionally redundant valve CS -V145 are not contained in this area and; hence, will be available for safe shutdow

n. The Appendix R separation requirements are satisfied.
f. Reactor Vent Valve RC

-FV-2881 A cable for the normally closed, fail closed valve RC -FV-2881 is routed through this fire area. The spurious opening of this valve will not prevent safe shutdown as functionally redundant valve RC -V323 is normally closed and has no cables, controls, or equipment in this fire area so it cannot spuriously open. The Appendix R separation requirements are satisfied. C. Evaluation Deviations from the Appendix R, Paragraph III.G.2 separation requirements exist in the diesel generator building El. 51 '-6" for the DAH system and have been discussed and analyzed above. A deviation from Appendix R, Paragraph III G.2c, "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved. These deviations are justified based on the analysis and our assertion that additional modifications would not enhance fire protection safety. For the remainder of the systems affected in this analysis, the safe shutdown requirements and the Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-150 Tabulation 3.2.7.42 Diesel Generator Building - El. 51'-6" Fire Area -DG-F-3C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable DG-LS-FLC x x DG-P-38A x DG-TK-46A x DG-TK-78A x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area DG -F-3D-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-151 Tabulation 3.2.7.43 Diesel Generator Building - El. 51'-6" Fire Area -DG-F-3D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable DG-LS-FLC x x DG-P-38B x DG-TK-46B x DG-TK-78B x B. Analysis All equipment and cables are Train B. The redundant Train A equipment and cables are in Fire Area DG -F-3C-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-152 Tabulation 3.2.7.44 Diesel Generator Building - El. 51'-6" Fire Area -DG-F-3E-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable DG-F-36A x DG-MM-8A x B. Analysis There are no safe shutdown cables in this fire area. Only mechanical equipment for DG-A is contained in this fire area. The redundant equipment is contained in fire area DG-F-3F-A. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-153 Tabulation 3.2.7.45 Diesel Generator Building - El. 51'-6" Fire Area -DG-F-3F-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable DG-F-36B x DG-MM-8B x B. Analysis There are no safe shutdown cables in this fire area. Only mechanical equipment for DG-B is contained in this fire area. The redundant equipment is contained in fire area DG-F-3E-A. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-154 Tabulation 3.2.7.46 Diesel Generator Building - Stairwell (N) Fire Area -DG-F-S1-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-155 Tabulation 3.2.7.47 Diesel Generator Building

- Stairwell (S)

Fire Area -DG-F-S2-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-156 Tabulation 3.2.7.48 Emergency Feedwater Pump Building Fire Area - EFP-F-1-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EPA-TSH-5430 x x EPA-TSH-5431 x x EPA-FN-47A x x EPA-FN-47B x x EPA-DP-371 x x EPA-DP-372 x x EPA-DP-373 x x EPA-DP-374 x x MM-IR-49 x x MM-IR-50 x x FW-FT-4214-2 x x FW-FT-4224-2 x x FW-FT-4224-4 x x FW-FT-4214-4 x x FW-FT-4234-2 x x FW-FT-4244-2 x x FW-FT-4244-4 x x FW-FT-4234-4 x x FW-FV-4214A x x FW-FV-4214B x x FW-FV-4224A x x FW-FV-4224B x x FW-FV-4234A x x FW-FV-4234B x x FW-FV-4244A x x FW-FV-4244B x x FW-P-37B x x FW-LT-4252 x x FW-LT-4257 x x FW-V347 x x B. Analysis The emergency feedwater pump building is a Class 1 concrete structure which for Safe Shutdown has a primary function of providing protection for the motor driven feedwater pump and valves. The area is approximately 79 ft. long by 28 ft. wide by 18 ft. high with a floor area of 2400 sq. ft. and a volume of 43,000 cu. ft.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-157 The in situ combustibles consist of six gallons of oil in the turbine drive of emergency feedwater pump FW -P-37A and 27 pounds of plastic in a 10 ft. step and 24 ft. extension ladder. An analysis of the Design basis Fire for this combustible is contained in the "Fire Protection Program Evaluation and Comparison to Branch Technical Position APCSB-9.5-1 Appendix A. All cables are routed in conduit. Detectors are provided throughout the area.

See Section 3.4 for a discussion of the operator response for a fire in this area.

The eight emergency feed pump control valves are separated such that valves FW-FV-4214A, B and FW-FV-4244A, B are separated by 60 feet from valves FW-FV-4224A, B and FW -FV-4234A, B. See Section 3.4 for more discussion of these valves. The redundant fans and dampers are in separate steel enclosures located 11 ft. above the floor, and separated b y 1'-6". The temperature switches are separated by over 20 '. The redundant CST Level transmitters FW -LT-4252 and FW -LT-4257 are separated by 16'. The motor driven emergency feedwater pump and recirculation valve FW -V347 are located in this fire area. For a fire in this area, the start -up feedwater pump FW -P-113 (SUFP) and start -up to EFW valves FW -V156 and FW -V163 will be utilized to satisfy the safe shutdown requirements. The SUFP low suction pressure trip must also be bypassed prior to commencing cooldown. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-158 During no -load and low load plant operations, the SUFP is aligned to non -emergency Bus 4 to provide its startup and shutdown functions. After the SUFP completes its startup function, its power supply will be transferred to emergency Bus E5 as plant power is increased. The SUFP will remain aligned to Bus E5 during 100% power operation. As power is decreased in preparation for a plant shutdown, the SUFP power supply will be transferred back to Bus

4. If the SUFP is required to perform its EFW contingency function in response to a fire that disables the Train B emergency feedwater pump, while aligned to Bus 4 coincident with a loss of offsite power, it will have to be manually transferred to Bus E5 and manually started. SUFP operation will be controlled by operating procedures including selection of the appropriate power supply and verification of adequate power supply capacity prior to starting the SUFP on the emergency diesel generator.

The main control room would not have to be evacuated for a fire in this area; hence, the operators would have the capability to control and monitor all the equipment which is powered from the electrical distribution emergency system and would be required for a safe shutdown. Additional details on the alternative safe shutdown capability are contained in Section 3.4. C. Evaluation A deviation from the requirements of Appendix R, Paragraph III.G.3 requiring the installation of fixed suppression in an area for which alternative safe shutdown capability has been developed exists in the emergency feedwater pump building. This deviation is justified based on our assertion that additional modifications would not enhance plant safety which has been insured by the alternative shutdown capability discussed in Section 3.4 and Tabulation 3.4.3.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-159 Tabulation 3.2.7.49 Electrical Tunnel Fire Area - ET-F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CAH-FN-1C x CAH-FN-1E x CAH-FN-1F x CC-LT-2172-1 x CC-LT-2172-2 x CC-LT-2172-3 x CC-LT-2272-1 x CC-LT-2272-2 x CC-LT-2272-3 x CC-P-322A x CC-V57 x CC-V121 x EDE-MM-582 x x ED-X-14J x x ED-PP-8J x x SA-C-4A x CS-V10 x CS-V28 x CS-V44 x CS-V59 x CS-V145 x RC-LCV-459 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-160 Electrical Tunnel Fire Area - ET-F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RC-LCV-460 x RC-E-10 x RC-PP-6A x x RC-PCV-456A x RC-V122 x RC-V23 x RC-V88 x SI-V159 x SI-V3 x SI-V32 x SI-FV-2482 x SI-FV-2483 x SI-FV-2495 x SI-FV-2496 x RH-V35 x FW-FV-4214A x FW-FV-4224A x FW-FV-4234A x FW-FV-4244A x MS-V86 x MS-V88 x MS-V90 x MS-V92 x MS-PV-3002 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-161 Electrical Tunnel Fire Area - ET-F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MS-PV-3003 x SB-V1 x SB-V3 x SB-V5 x SB-V7 x EAH-FN-174A x EDE-CP-248 x EDE-MCC-514 x EPA-FN-47A x EPA-DP-371 x EPA-DP-373 x SW-P-41A x SW-P-41C x SW-V2 x SW-V22 x SW-PT-8272 x SW-PT-8273 x SW-PT-8274 x SWA-FN-40A x FW-LT-501 x FW-LT-503 x FW-LT-529 x FW-LT-548 x FW-PT-524 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-162 Electrical Tunnel Fire Area - ET-F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-PT-526 x FW-PT-534 x FW-PT-536 x FW-LT-4252 x FW-FT-4214-2 x FW-FT-4224-4 x FW-FT-4234-2 x FW-FT-4244-4 x NI-NE-6690 x NI-NT-6690 x x RC-LT-459 x RC-PT-405 x RC-PT-455 x RC-PT-457 x RC-TE-413A x RC-TE-423A x RC-TE-433A x RC-TE-443A x SI-PT-935 x Electrical Penetrations x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-163 B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown equipment and cables. The redundant Train B safe shutdown equipment and cables are located in fire area ET -F-1C-A. The Appendix R safe shutdown requirements are satisfied.

2. Component Cooling Water Isolation Valves CC

-V57, CC-V121, and Head Tank Level Transmitters CC -LT-2172-1, 2, 3, CC -LT-2272-1, 2, 3 Cables associated with head tank level transmitters which affect the Loop B outboard isolation valves CC -V175 and CC -V257 are routed in the same trays as the Loop A inboard isolation valves CC -V57 and CC -V121. Failures in these cables could cause total loss of PCCW to containment by initiation of a spurious

lo-lo head tank level signal. Loop B PCCW can be re -established by transferring control of valves CC -V175 and CC -V257 to local control at the RSS panel in fire area CB-F-1A-A. This removes the lo -lo head tank level isolation function and allows operators to re -open the valves. The safe shutdown requirements are satisfied.

3. RC Pump Seal Water Isolation Valves CS

-V10, CS-V28, CS-V44, CS-V59 The safe shutdown function of these valves is to isolate seal return in the event that valve CS -V168 spuriously closes due to a fire. As cabling for CS-V168 is not routed through this area, the position of these valves is inconsequential and will not prevent safe shutdown. The safe shutdown requirements are satisfied.

4. Letdown Isolation Valves CS

-V145, RC-LCV-459, RC-LCV-460 Functionally redundant Train A series valves CS -V145, RC-LCV-459 and RC-LCV-460 are normally open and are required to close for safe shutdown. CS-V145 can be closed from the main control room. Should this valve not close due to spurious operation, the operators can close either RC-LCV-459 or RC-LCV-460 by tripping their power supply breakers at the Train A switchgear room (Fire Area: CB -F-1A-A). This will prevent further spurious operation. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-164 5. Charging Pump Test Line Isolation Valve SI-V159 On spurious operation of the normally closed, fail closed valve SI -V159 (Train A), the operators will maintain the normally closed high head injection path valves SI -V138 and SI -V139 closed. Charging will be accomplished utilizing the seal injection flow path through valves CS -FCV-121, CS-V154, CS-V158, CS-V162 and CS -V166. The cables, controls and equipment required for operation of these valves are not contained in the fire area. The capability to provide charging to the RC System through a minimum of one flow path satisfies the safe shutdown requirements.

6. RHR Isolation Valves RC

-V23, RC-V88 RHR isolation valves are permanently disabled in the closed position. For entry into RHR shutdown cooling, valve RC -V88 must be opened. These valves are not required until 9 hours into the event. This can be accomplished manually by entry into containment, if required. The safe shutdown requirements are satisfied.

7. Emergency Feedwater Pump Control Valves FW

-FV-4214A, FW -FV-4224A, FW-FV-4234A, FW-FV-4244A These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train A switchgear room (Fire Area: CB -F-1A-A). The safe shutdown requirements are satisfied.

8. Main Steam Isolation Valves MS

-V86, MS-V88, MS-V90, MS-V92 Failure of the Train A cables will not prevent safe shutdown as the redundant Train B cables required for MSIV closure are routed in Fire Area ET -F-1C-A. The Appendix R separation requirements are satisfied.

9. Not used SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-165 10. Atmospheric Relief Valves MS

-PV-3002, MS-PV-3003 and Associated Solenoids Valves MS -PV-3002 and MS -PV-3003 are normally closed valves. A fire would prevent operation of the Train A capabilities provided for opening and closing these valves. However, the fire would not affect the Train B capabilities and the valves will be operable for safe shutdown. Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affected air solenoids will be de -energized from the distribution panels located in Train A switchgear room (Fire Area: CB -F-1A-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

11. Tower Actuation Logic Pressure Transmitters SW

-PT-8272, SW-PT-8273, SW-PT-8274 Failure in this cable could initiate a spurious tower actuation signal which would transfer Train A service water cooling capability from the pumphouse to the cooling towers. This transfer will not significantly interrupt Train A service Water cooling nor will it have any impact on Train B service water. This failure does not prevent safe shutdown. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-166 12. Main Steam Pressure Transmitters FW -PT-524, FW-PT-526, FW-PT-534, FW-PT-536 Redundant channels of main steam pressure cables are located in proximity. Spurious operation of the channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after 1 minute by use of the manual reset block switch and terminate the containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CS -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

13. Steam Generator Level Transmitters FW

-LT-501, FW-LT-503, FW-LT-529, FW-LT-548 Cables for transmitters FW -LT-501, FW-LT-503, FW-LT-529, FW-LT-548 are located in the same fire area. A Fire could cause loss of indication for all four steam generators. However, the same fire would not affect the redundant level transmitters FW -LT-502, FW-LT-504, FW-LT-519 and FW -LT-537. The Appendix R separation requirements are satisfied.

14. Emergency Feedwater Flow Transmitters FW

-FT-4214-2, FW-FT-4224-4, FW-FT-4234-2, FW-FT-4244-4 Failure in this cable could cause spurious closure of one emergency feedwater line. The logic will prevent isolation of additional lines. This leaves three steam generators available for heat removal; hence, safe shutdown is not affected. Although, failure in this cable could also cause loss of flow indication on two emergency feedwater lines, steam generator operability can be monitored by use of SG level indication. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-167 15. Condensate Storage Tank Level FW-LT-4252 All cables are Train A. The Train B level transmitter FW -LT-4257 will be available. In addition, the cables for CST level transmitter CO -LT-4096 are not routed through this area. The safe shutdown requirements are satisfied.

16. Pressurizer Pressure Transmitters RC

-PT-455, RC-PT-457 Redundant channels of pressurizer pressure cables are located in proximity. Spurious operation of two channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after 1 minute by use of the manual reset and block switch and terminate the containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B Switchgear Rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

17. Reactor Coolant Temperature Elements RC

-TE-413A, RC-TE-423A, RC-TE-433A, RC-TE-443A All hot leg RC temperature element cables are routed through this area; however,

this function can also be performed by the Train B incore thermocouples IC-TE-XX. The cables for these thermocouples are routed through the Train B electrical tunnel (Fire Area: ET -F-1C-A). The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-168 18. Pressurizer Relief Valves RC -PCV-456A, RC-V122 RC-PCV-456A is a normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V122. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV and the block valve by tripping their power supplies in the Train A switchgear room (Fire Area:

CB-F-1A-A). The safe shutdown requirements are required.

19. Containment Pressure Transmitter SI

-PT-935 A cable for one channel of containment pressure instrumentation is routed through this fire area. This channel inputs to 2 out of 3 and 2 out of 4 logics which initiate protective actions. A spurious signal from one channel is not sufficient to initiate the logic and perform the protective action; hence, a failure in this cable will not prevent safe shutdown. The safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-169 Tabulation 3.2.7.50 Electrical Tunnel Fire Area - ET-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CAH-FN-1C x CAH-FN-1E x CAH-FN-1F x CC-LT-2172-1 x CC-LT-2172-2 x CC-LT-2172-3 x CC-LT-2272-1 x CC-LT-2272-2 x CC-LT-2272-3 x CC-P-322A x CC-V57 x CC-V121 x ED-X-14J x SA-C-4A x CS-V10 x CS-V28 x CS-V44 x CS-V59 x CS-V145 x RC-LCV-459 x RC-LCV-460 x RC-E-10 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-170 Electrical Tunnel Fire Area - ET-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RC-PCV-456A x RC-V122 x RC-V23 x RC-V88 x SI-V138 x SI-V159 x SI-V3 x SI-V32 x SI-FV-2482 x SI-FV-2483 x SI-FV-2495 x SI-FV-2496 x RH-V35 x FW-FV-4214A x FW-FV-4224A x FW-FV-4234A x FW-FV-4244A x FW-V156 x MS-V86 x MS-V88 x MS-V90 x MS-V92 x MS-PV-3001 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-171 Electrical Tunnel Fire Area - ET-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MS-PV-3002 x MS-PV-3003 x MS-PV-3004 x SB-V1 x SB-V3 x SB-V5 x SB-V7 x EAH-FN-174A x EDE-CP-248 x EDE-MCC-514 x EPA-FN-47A x EPA-DP-371 x EPA-DP-373 x SW-P-41A x SW-P-41C x SW-V2 x SW-V22 x SW-PT-8272 x SW-PT-8273 x SW-PT-8274 x SWA-FN-40A x FW-LT-501 x FW-LT-503 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-172 Electrical Tunnel Fire Area - ET-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-LT-529 x FW-LT-548 x FW-PT-514 x FW-PT-524 x FW-PT-526 x FW-PT-534 x FW-PT-536 x FW-PT-544 x FW-LT-4252 x FW-FT-4214-2 x FW-FT-4224-4 x FW-FT-4234-2 x FW-FT-4244-4 x NI-NE-6690 x RC-LT-459 x RC-PT-405 x RC-PT-455 x RC-PT-457 x RC-TE-413A x RC-TE-423A x RC-TE-433A x RC-TE-443A x SI-PT-935 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-173 B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown equipment and cables. The redundant Train B safe shutdown equipment and cables are located in fire area ET -F-1C-A. The Appendix R safe shutdown requirements are satisfied.

2. Component Cooling Water Isolation Valves CC

-V57, CC-V121 and Head Tank Level Transmitters CC -LT-2172-1, 2, 3, CC -LT-2272-1, 2, 3 Cables associated with head tank level transmitters which affect the Loop B outboard isolation valves CC -V175 and CC -V257 are routed in the same trays as the Loop A inboard isolation valves CC -V57 and CC -V121. Failures in these cables could cause total loss of PCCW to containment by initiation of a spurious lo-lo head tank level signal. Loop B PCCW can be re -established by transferring control of valves CC -V175 and CC -V257 to local control at the RSS panel in fire area CB-F-1A-A. This removes the lo -lo head tank level isolation function and allows operators to re -open the valves. The safe shutdown requirements are satisfied.

3. RC Pump Seal Water Isolation Valves CS

-V10, CS-V28, CS-V44, CS-V59 The safe shutdown function of these valves is to isolate seal return in the event that valve CS-V168 spuriously closes due to a fire. As cabling for CS -V168 is not routed through this area, the position to these valves is inconsequential. The safe shutdown requirements are satisfied.

4. Letdown Isolation Valves CS

-V145, RC-LCV-459, RC-LCV-460 Functionally redundant Train A series valves CS -V145, RC-LCV-459 and RC-LCV-460 are normally open and are required to close for safe shutdown. CS-V145 can be closed from the main control room. Should this valve not close due to spurious operation, the operators can close either RC -LCV-459 or RC-LCV-460 by tripping their power supply breakers at the Train A switchgear room (Fire Area: CB -F-1A-A). This will prevent further spurious operation. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-174 5. Charging Pump Test Line Isolation Valve SI -V159 On spurious operation of the normally closed, fail closed valve SI -V159 (Train A), the operators will maintain the normally closed high head injection path valves SI -V138 and SI -V139 closed. Charging will then be accomplished utilizing the seal injection path through valves CS -FCV-121, CS-V154, CS-V158, CS-V162 and CS -V166. The cables, controls and equipment required for operation of these valves are not contained in the fire area. The capability to provide charging to the RC system through a minimum of one flow path satisfies the safe shutdown requirements.

6. RHR Isolation Valves RC

-V23, RC-V88 RHR isolation valves are permanently disabled in the closed position. For entry into RHR shutdown cooling, valve RC -V88 must be opened. These valves are not required until 9 hours into the event. This can be accomplished manually by entry into containment, if required. The safe shutdown requirements are satisfied.

7. Emergency Feedwater Pump Control Valves FW

-FV-4214A, FW-FV-4224A, FW-FV-4234A, FW -FV-4244A These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train A switchgear room (Fire Area CB -F-1A-A). The safe shutdown requirements are satisfied.

8. Not used 9. Main Steam Isolation Valves MS

-V86, MS-V88, MS-V90, MS-V92 Failure of the Train A cables will not prevent safe shutdown as the redundant Train B cables required for MSIV closure are routed in Fire Area ET -F-1C-A. The Appendix R separation requirements are satisfied.

10. Not used SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-175 11. Atmospheric Relief Valves MS

-PV-3001, MS-PV-3002, MS-PV-3003, MS-PV-3004 Valves MS -PV-3001, MS-PV-3002, MS-PV-3003 and MS -PV-3004 are normally closed valves. A fire would prevent operation of the Train A capabilities provided for opening and closing these valves. However, the fire would not affect the Train B capabilities and the valves will be operable for safe shutdown. Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affected air solenoids will be de -energized from the distribution panel located in Train A switchgear room (Fire Area: CB -F-1A-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

12. Tower Actuation Logic Pressure Transmitters SW

-PT-8272, SW-PT-8273, SW-PT-8274 Failure in this cable could initiate a spurious tower actuation signal which would transfer Train A service water cooling capability from the pumphouse to the cooling towers. This transfer will not significantly interrupt Train A service water cooling nor will it have any impact on Train B service water. This failure does not prevent safe shutdown. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-176 13. Main Steam Pressure Transmitters FW -PT-514, FW-PT-524, FW-PT-526, FW-PT-534, FW-PT-536, FW-PT-544 Redundant channels of main steam pressure cables are located in proximity. Spurious operation of the channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after one (1) minute by use of the manual reset and block switch and terminate the containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear room (Fire Areas: CB -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

14. Steam Generator Level Transmitters FW

-LT-501, FW-LT-503, FW-LT-529, FW-LT-548 Cables for transmitters FW -LT-501, FW-LT-503, FW-LT-529 and FW -LT-548 are located in the same fire area. A fire could cause loss of indication for all four steam generators. However, the same fire would not affect the redundant level transmitters FW -LT-502, FW-LT-504, FW-LT-519 and FW -LT-537. The Appendix R separation requirements are satisfied. 15. Emergency Feedwater Flow Transmitter FW -FT-4214-2, FW-FT-4234-2 Failure in this cable could cause spurious closure of one emergency feedwater line. The logic will prevent isolation of additional lines. This leaves three steam generators available for heat removal; hence, safe shutdown is not affected. Although failure in this cable could also cause loss of flow indication on two emergency feedwater lines, steam generator operability can be monitored by use of SG level indication. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-177 16. Condensate Storage Tank Level FW -LT-4252 All cables are Train A. The Train B level transmitter FW -LT-4257 will be available. In addition, the cables for CST level transmitter CO -LT-4096 are not routed through this area . The Appendix R separation requirements are satisfied.

17. Pressurizer Pressure Transmitters RC

-PT-455, RC-PT-457 Redundant channels of pressurizer pressure cables are located in proximity. Spurious operation of two channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after 1 minute by use of the manual reset and block switch and terminate the containment isolation by use to the manual reset switch. All ESF equipment

which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

18. Reactor Coolant Temperature Elements RC

-TE-413A, RC-TE-423A, RC-TE-433A, RC-TE-443A All hot leg RC temperature element cables are routed through this area; however, this function can also be performed by the Train B incore thermocouples

IC-TE-XX. The cables for these thermocouples are routed through the Train B electrical tunnel (Fire Area: ET -F-1C-A). The Appendix R separation requirements are satisfied.

19. Containment Pressure Transmitter SI

-PT-935 A cable for one channel of containment pressure instrumentation is routed through this fire area. This channel inputs to 2 out of 3 and 2 out of 4 logics which initiate protective actions. A spurious signal from one channel is not sufficient to initiate the logic and perform the protective action; hence, a failure in this cable will not prevent safe shutdown. The safe shutdown requirements are satisfied. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-178 20. Pressurizer Relief Valves RC -PCV-456A, RC-V122 RC-PCV-456A is normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V122. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV and the block valve by tripping their power supplies in the Train A switchgear room (Fire Area:

CB-F-1A-A). The safe shutdown requirements are satisfied.

21. High Head Safety Injection Valve SI

-V-138 SI-V-138 is a normally closed valve which may be opened to provide a redundant hot standby charging path. The functionally redundant Train B valve SI -V-139 is available to perform this function. Should SI -V-138 spuriously open, the charging pump may have to be stopped to prevent overfill of the pressurizer. The safe shutdown requirements are satisfied. C. EVALUATION The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-179 Tabulation 3.2.7.51 Electrical Tunnel Fire Area - ET-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CAH-FN-1A x CAH-FN-1B x CAH-FN-1D x CC-LT-2192-1 x CC-LT-2192-2 x CC-LT-2192-3 x CC-LT-2292-1 x CC-LT-2292-2 x CC-LT-2292-3 x CC-P-322B x CC-V122 x CC-V256 x EDE-MM-584 x x ED-PP-8B x ED-X-16A x SA-C-4B x CS-V168 x CS-V175 x CS-V176 x RC-FV-2881 x RC-V323 x RC-E-10 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-180 Electrical Tunnel Fire Area - ET-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RC-PP-6B x x RC-PCV-456B x RC-V124 x RC-V23 x RC-V22 x RC-V88 x RC-V87 x SI-V158 x SI-V17 x SI-V47 x SI-FV-2475 x SI-FV-2476 x SI-FV-2477 x SI-FV-2486 x RH-V36 x FW-FV-4214B x FW-FV-4224B x FW-FV-4234B x FW-FV-4244B x FW-P-37B x FW-V347 x MS-V88 x MS-V90 x MS-PV-3002 x MS-PV-3003 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-181 Electrical Tunnel Fire Area - ET-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EAH-FN-174B x EDE-CP-249 x EDE-MCC-614 x EPA-FN-47B x EPA-DP-372 x EPA-DP-374 x SW-P-41B x SW-P-41D x SW-V29 x SW-V31 x SW-PT-8282 x SW-PT-8283 x SW-PT-8284 x SWA-FN-40B x FW-LT-502 x FW-LT-504 x FW-LT-519 x FW-LT-537 x FW-PT-525 x FW-PT-535 x FW-LT-4257 x FW-FT-4214-4 x FW-FT-4224-2 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-182 Electrical Tunnel Fire Area - ET-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-FT-4234-4 x FW-FT-4244-2 x NI-NE-6691 x NI-NT-6691 x x RC-LT-460 x RC-PT-405 x x RC-PT-403 x x RC-PT-456 x RC-PT-458 x IC-TE-XX x MM-CP-486B x RC-TE-413B x RC-TE-423B x RC-TE-433B x RC-TE-443B x SI-PT-935 x x SI-PT-934 x x Electrical Penetrations x x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A safe shutdown equipment and cables are located in fire area ET -F-1A-A. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-183 2. Component Cooling Water Isolation Valves CC -V176, CC-V256 and Head Tank Level Transmitters CC -LT-2192-1, 2, 3, CC -LT-2292-1, 2, 3 Cables associated with head tank level transmitters which affect the Loop A outboard isolation valves CC -V122 and CC -V168 are routed in the same trays as the Loop B inboard isolation valves CC -V176 and CC -V256. Failures in these cables could cause total loss of PCCW to containment by initiation of a spurious lo-lo heat tank level signal. Loop A PCCW can be re -established by transferring control of valves CC -V122 and CC -V168 to local control at the RSS panel in fire area CB-F-1B-A. This removes the lo -lo head tank level isolation function and allows operators to re -open the valves. The safe shutdown requirements are satisfied.

3. RC Pump Seal Water Isolation Valve CS

-V168 Valve CS-V168 is a normally open valve which should remain open for safe shutdown. Spurious isolation of the Train B valve could result in RC inventory loss through the upstream relief valves. This inventory is directed to the PRT and is therefore, non -recoverable. To preclude this loss of inventory, redundant isolation capability is provided for the RC pump seal return lines by means of Train A valves CS -V10, CS-V28, CS-V44 and CS -V59. The cables, controls and equipment required for the operation of CS -V10, CS-V28, CS-V44 and CS -V59 are not contained in this fire area. The safe shutdown requirements are satisfied.

4. Letdown Isolation Valves CS

-V175, CS-V176 Functionally redundant Train B series valves CS -V175 and CS -V176 are normally closed and remain closed for safe shutdown. The spurious opening of one valve will not prevent safe shutdown. The operators will prevent further spurious operation by tripping the power supply breakers for CS -V175 and CS -V176 at the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-184 5. Charging Pump Test Line Isolation Valve SI -V158 On spurious operation of the normally closed, fail closed valve SI -V158 (Train B), the operators will maintain the normally closed high head injection path valves SI-V138 and SI -V139 closed. Charging will be accomplished utilizing the seal injection path through valves CS -FCV-121, CS-V154, CS-V158, CS-V162 and CS-V166. The cables, controls and equipment required for operation of their valves are not contained in the fire area. The capability to provide charging to the RC system through a minimum of one flow path satisfies the safe shutdown requirements.

6. Head Vent Valves RC-FV-2881 and RC

-V323 Functionally redundant Train B series valves RC -FV-2881 and RC -V323 are normally closed and remain closed for safe shutdown. The spurious opening of one valve will not prevent safe shutdown. The operators will prevent further spurious operation by tripping the power supply breakers for RC -FV-2881 and RC-V323 at the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

7. RHR Isolation Valves RC

-V22, RC-V23, RC-V87, RC-V88 RHR isolation valves are permanently disabled in the closed position. For entry into RHR shutdown cooling, valves RC -V22 and RC -V23 must be opened. This can be accomplished manually by entry into containment, if required. This manual operation can be delayed as much as 9 hours into the event. The safe shutdown requirements are satisfied.

8. Emergency Feedwater Pump Control Valves FW

-FV-4214B, FW -FV-4224B, FW-FV-4234B, FW -FV-4244B These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-185 9. Main Steam Isolation Valves MS -V88, MS-V90 Failure of the Train B cables will not prevent safe shutdown as the redundant Train A cables required for MSIV closure are routed in Fire Area ET -F-1A-A. The Appendix R separation requirements are satisfied.

10. Atmospheric Relief Valves MS

-PV-3002, MS-PV-3003 Valves MS -PV-3002 and MS -PV-3003 are normally closed valves. A fire would prevent operation of the Train B capabilities provided for opening and closing these valves. However, the fire would not affect the Train A capabilities and the valves will be operable for safe shutdown. Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affected air solenoids will be de -energized from the distribution panel located in Train B switchgear room (Fire Area: CB -F-1B-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

11. Tower Activation Logic Pressure Transmitters SW

-PT-8282, SW-PT-8283, SW-PT-8284 Failure in this cable could initiate a spurious tower actuation signal which would transfer one train of service water cooling capability from the pumphouse to the cooling towers. This transfer will not significantly interrupt Train B service water cooling nor will it have any impact on Train A service water. This failure does not prevent safe shutdown. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-186 12. Main Steam Pressure Transmitters FW -PT-525, FW-PT-535 A cable for one channel of main steam pressure instrumentation is routed through this fire area. This channel inputs to 2 out of 3 logics which initiate protective actions. A spurious signal from the one channel is not sufficient to initiate the logic. Hence, a failure in this cable will not prevent safe shutdown. The safe shutdown requirements are satisfied.

13. Steam Generator Level Transmitters FW

-LT-502, FW-LT-504, FW-LT-519, FW-LT-537 Cables for transmitters FW -LT-502, FW-LT-504, FW-LT-519, FW-LT-537 are located in the same fire area. A fire could cause loss of indication for all four steam generators. However, the same fire would not affect the redundant level transmitters FW -LT-501, FW-LT-503, FW-LT-529 and FW -LT-548. The Appendix R separation requirements are satisfied.

14. Emergency Feedwater Flow Transmitter FW

-FT-4214-4, FW-FT-4224-2, FW-FT-4234-4, FW-FT-4244-2 Failure in this cable could cause spurious closure of one emergency feedwater line. The logic will prevent isolation of additional lines. This leaves three steam generators available for heat removal; hence, safe shutdown is not affected. Although, failure in this cable could also cause loss of flow indication on two emergency feedwater lines, steam generator operability can be monitored by use of SG level indication. The safe shutdown requirements are satisfied.

15. Condensate Storage Tank Level FW

-LT-4257 All cables are Train B. The Train A level transmitter FW -LT-4252 will be available. In addition, the cables for CST level transmitter CO -LT-4096 are not routed through this area.

The Appendix R separation requirements are satisfied. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-187 16. Reactor Pressure RC -PT-403, RC-PT-405 Redundant reactor pressure instruments and cables are contained in this area. This function can also be performed by functionally redundant pressurizer pressure transmitters RC -PT-455 or RC -PT-457 routed through Fire Area ET-F-1A-A. The Appendix R separation requirements are satisfied.

17. Pressurizer Pressure Transmitters RC

-PT-456, RC-PT-458 Redundant channels of pressurizer pressure cables are located in proximity. Spurious operation of two channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after 1 minute by use of the manual reset and block switch and terminate the containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

18. Reactor Coolant Temperature RC

-TE-413B, RC-TE-423B, RC-TE-433B, RC-TE-443B All cold leg RC temperature element cables are routed through this area; however, this function can also be performed by the Train A steam generator pressure transmitters FW -PT-514, FW-PT-524, FW-PT-534, FW-PT-544 because cold leg temperature approximated the saturation temperature corresponding to secondary pressure. The cables for these PT 's are routed through fire area ET -F-1A-A. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-188 19. Pressurizer Relief Valves RC -PCV-456B, RC-V124 RC-PCV-456B is normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC -V124. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de -energize the PORV and the block valve by tripping their power supplies in Train B switchgear room (Fire Area:

CB-F-1A-A). The safe shutdown requirements are satisfied.

20. Containment Pressure Transmitters SI

-PT-934, SI-PT-935 Redundant channels of containment pressure instruments and cables are located in proximity. Spurious operation of these channels will initiate safety injection, containment spray and containment isolation Phase A and Phase B. The operators will have the capability to terminate the SI after 1 minute by use of manual reset and block switches and terminate the containment spray and containment isolation by use of manual reset switches. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -1F-1A-A and CB-F-1B-A). Provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-189 Tabulation 3.2.7.52 Electrical Tunnel Fire Area - ET-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CAH-FN-1A x CAH-FN-1B x CAH-FN-1D x CC-LT-2192-1 x CC-LT-2192-2 x CC-LT-2192-3 x CC-LT-2292-1 x CC-LT-2292-2 x CC-LT-2292-3 x CC-P-322B x CC-V176 x CC-V256 x ED-X-16A x SA-C-4B x CS-V168 x CS-V175 x CS-V176 x PAH-DP-35B x PAH-DP-36B x RC-FV-2881 x RC-V323 x RC-E-10 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-190 Electrical Tunnel Fire Area - ET-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RC-PCV-456B x RC-V124 x RC-V22 x RC-V87 x SI-V139 x SI-V158 x SI-V17 x SI-V47 x SI-FV-2475 x SI-FV-2476 x SI-FV-2477 x SI-FV-2486 x RH-V36 x FW-FV-4214B x FW-FV-4224B x FW-FV-4234B x FW-FV-4244B x FW-P-37B x FW-V-347 x MS-V86 x MS-V88 x MS-V90 x MS-V92 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-191 Electrical Tunnel Fire Area - ET-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MS-PV-3001 x MS-PV-3002 x MS-PV-3003 x MS-PV-3004 x SB-V9 x SB-V10 x SB-V11 x SB-V12 x EAH-FN-174B x EDE-CP-249 x EDE-MCC-614 x EPA-FN-47B x EPA-DP-372 x EPA-DP-374 x SW-P-41B x SW-P-41D x SW-V29 x SW-V31 x SW-PT-8282 x SW-PT-8283 x SW-PT-8284 x SWA-FN-40B x CS-LT-106 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-192 Electrical Tunnel Fire Area - ET-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-LT-502 x FW-LT-504 x FW-LT-519 x FW-LT-537 x FW-PT-515 x FW-PT-516 x FW-PT-525 x FW-PT-535 x FW-PT-545 x FW-PT-546 x FW-LT-4257 x FW-FT-4214-4 x FW-FT-4224-2 x FW-FT-4234-4 x FW-FT-4244-2 x NI-NE-6691 x RC-LT-460 x RC-PT-403 x RC-PT-456 x RC-PT-458 x IC-TE-XX x MM-CP-486B x RC-TE-413B x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-193 Electrical Tunnel Fire Area - ET-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable RC-TE-423B x RC-TE-433B x RC-TE-443B x SI-PT-934 x SI-PT-936 x MM-CP-2 x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A safe shutdown equipment and cables are located in fire area ET -F-1A-A. The Appendix R separation requirements are satisfied.

2. Component Cooling Water Isolation Valves CC

-V176, CC-V256 and Head Tank level Transmitters CC -LT-2192-1, 2, 3 and CC -LT-2292-1, 2, 3 Cables associated with head tank level transmitters which affect the Loop A outboard isolation valves CC -V122 and CC -V168 are routed in the same trays as the Loop B inboard isolation valves CC -V176 and CC -V256. Failures in these cables could cause total loss of PCCW to containment by initiation of a spurious lo-lo heat tank level signal. Loop A PCCW can be re -established by transferring control of valves CC -V122 and CC -V168 to local control at the RSS panel in fire area CB-F-1B-A. This removes the lo -lo head tank level isolation function and allows operators to re -open the valves. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-194 3. RC Pump Seal Water Isolation Valve CS -V168 Valve CS-V168 is a normally open valve which should remain open for safe shutdown. Spurious isolation of the Train B valve could result in RC inventory loss through the upstream relief valves. This inventory is directed to the PRT and is therefore, non -recoverable. To preclude this loss of inventory, redundant isolation capability is provided for the RC pump seal return lines by means of Train A valves CS -V10, CS-V28, CS-V44 and CS -V59 and the excess letdown line by means of either normally closed, fail closed valves CS -V175 or CS -V176. The cables, controls and equipment required for the operation of CS-V10, CS-V28, CS-V44 and CS -V59 are not contained in this fire area. The cables for valves CS -V175 and CS -V176 are routed in the same trays as the cables for CS-V168. To prevent the spurious closure of CS -V168 or the spurious opening of CS-V175 or CS-V176, the operators will trip their power supply breakers in the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

4. Letdown Isolation Valves CS

-V175, CS-V176 Functionally redundant Train B series valves CS -V175 and CS -V176 are normally closed and remain closed for safe shutdown. The spurious opening of one valve will not prevent safe shutdown. The operators will prevent further spurious operation by tripping the power supply breakers for CS -V175 and CS -V176 at the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

5. Charging Pump Test Line Isolation Valve SI

-V158 On spurious operation of the normally closed, fail closed valve SI -V158 (Train B), the operators will maintain the normally closed high head injection path valves SI-V138 and SI -V139 closed. Charging will be accomplished utilizing the seal injection path through valves CS -FCV-121, CS-V154, CS-V158, CS-V162 and CS-V166. The cables, controls and equipment required for operation of these valves are not contained in the fire area. The capability to provide charging to the RC System through a minimum of one flow path satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-195 6. Head Vent Valves RC -FV-2881 and RC -V323 Functionally redundant Train B series valves RC -FV-2881 and RC -V323 are normally closed and remain closed for safe shutdown. The spurious opening of one valve will not prevent safe shutdown. The operators will prevent further spurious operation by tripping the power supply breakers for RC -FV-2881 and RC-V323 at the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

7. RHR Isolation Valves RC

-V-22, RC-V87 RHR isolation valves are permanently disabled in the closed position. For entry into RHR shutdown cooling, valve RC -V22 must be opened. This can be accomplished manually by entry into containment, if required. This manual operation can be delayed as much as 9 hours into the event. The safe shutdown requirements are satisfied. 8. Emergency Feedwater Pump Control Valves FW -FV-4214B, FW -FV-4224B, FW-FV-4234B, FW -FV-4244B These valves are normally open and at least two valves must remain open for safe shutdown. Spurious closure of one valve will not prevent safe shutdown. The operators will prevent further spurious operations by disabling the power supplies to the unaffected valves in the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

9. Main Steam Isolation Valves MS

-V86, MS-V88, MS-V90, MS-V92 Failure of the Train B cables will not prevent safe shutdown as the redundant Train A cables required for MSIV closure are routed in Fire Area ET -F-1A-A. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-196 10. Atmospheric Relief Valves MS -PV-3001, MS-PV-3002, MS-PV-3003, MS-PV-3004 Valves MS -PV-3001, MS-PV-3002, MS-PV-3003, and MS -PV-3004 are normally closed valves. A fire would prevent operation of the Train B capabilities provided for opening and closing these valves. However, the fire would not affect the Train A capabilities and the valves will be operable for safe shutdown. Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affected air solenoids will be de -energized from the distribution panel located in Train B switchgear room (Fire Area: CB -F-1B-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

11. Tower Activation Logic Pressure Transmitters SW

-PT-8282, SW-PT-8283, SW-PT-8284 Failure in this cable could initiate a spurious tower actuation signal which would transfer one train of service water cooling capability form the pumphouse to the cooling towers. This transfer will not significantly interrupt Train B service water cooling nor will it have any impact on Train A service water. This failure does not prevent safe shutdown. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-197 12. Steam Generator Level Transmitters FW -LT-502, FW-LT-504, FW-LT-519, FW-LT-537 Cables for transmitters FW -LT-502, FW-LT-504, FW-LT-519, FW-LT-537 are located in the same fire area. A Fire could cause loss of indication for all four steam generators. However, the same fire would not affect the redundant level transmitters FW-LT-501, FW-LT-503, FW-LT-529 and FW -LT-548. The Appendix R separation requirements are satisfied.

13. Main Steam Pressure Transmitters FW

-PT-515, FW-PT-516, FW-PT-525, FW-PT-535, FW-PT-545, FW-PT-546 Redundant channels of main steam pressure cables are located in proximity. Spurious operation of the channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after 1 minute by use of the manual reset and block switch and terminate the containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

14. Emergency Feedwater Flow Transmitters FW

-FT-4214-4, FW-FT-4224-2, FW-FT-4234-4, FW-FT-4244-2 Failure in this cable could cause spurious closure of one emergency feedwater line. The logic will prevent isolation of additional lines. This leaves three steam generators available for heat removal; hence, safe shutdown is not affected. Although failure in this cable could also cause loss of flow indication on two emergency feedwater lines, steam generator perability can be monitored by use of SG level indication. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-198 15. Condensate Storage Tank Level FW -LT-4257 All cables are Train B. The Train A level transmitter FW -LT-4252 will be available. In addition, the cables for CST level transmitter CO -LT-4096 are not routed through this area. The Appendix R separation requirements are satisfied.

16. Pressurizer Pressure Transmitters RC

-PT-456, RC-PT-458 Redundant channels of pressurizer pressure cables are located in proximity. Spurious operation of two channels will initiate a safety injection signal. The operators will have the capability to terminate SI after 1 minute by use of the manual reset and block switch. All SI equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

17. Reactor Coolant Temperature RC

-TE-413B, RC-TE-423B, RC-TE-433B, RC-TE-443B All cold leg RC temperature element cables are routed through this area; however, this function can also be performed by the Train A steam generator pressure transmitters FW -PT-514, FW-PT-524, FW-PT-534, FW-PT-544 because cold leg temperature approximates the saturation temperature corresponding to secondary pressure. The cables for these PT 's are routed through fire area ET -F-1A-A. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-199 18. Containment Pressure Transmitters SI -PT-934, SI-PT-936 Redundant channels of containment pressure instruments and cables are located in proximity. Spurious operation of these channels will initiate safety injection, containment spray and containment isolation Phase A and Phase B. The operators will have the capability to terminate the SI after 1 minute by use of manual reset a nd block switches and terminate the containment spray and containment isolation by use of manual reset switches. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

19. Process Protection System Cabinet MM

-CP-2 Failure of cable will cause loss of power supply to Channel II process protection system cabinet and related instrumentation. The power supplies to redundant channel PPC are routed through other fire areas and; hence, the PPC 's will perform their safe shutdown function. The Appendix R separation requirements are satisfied.

20. Pressurizer Relief Valves RC

-PCV-456B, RC-V124 RC-PCV-456B is a normally closed, fail closed valve whose cables are in this fire area. The spurious opening of a PORV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. The PORV is supplemented with a normally open, series block valve RC-V122. For all fires that have the potential to cause spurious opening of the PORV, the operators will close the block valve by procedure. This will be the first step in the procedure and can readily be accomplished from the main control room. The promptness of this action is justification for the ability to isolate the block valve prior to any spurious valve operations. Under the condition, the initial short will not cause depressurization. To prevent subsequent spurious operations, the operators will de-energize the PORV and the block valve by tripping their power supply in the Train B switchgear room (Fire Area: CB -F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-200 21. Containment Enclosure Isolation Damper, PAH -DP-35B, PAH-DP-36B Cables for dampers PAH -DP-35B and PAH -DP-36B are routed through this area. Under normal operation both dampers are open. If both dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in the recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. Independent operation of either damper (one open and one closed) could cause an air flow problem in EAH system. This assumes that redundant dampers (PAH -DP-35A and PAH -DP-36A) are in their normal open position since they would not be affected by a fire in this area. Both dampers are powered from a single Train B power supply. The circuit design is such that a spurious signal will cause both dampers to operate together, either both open (normal mode) or both closed (recirculation mode).

The safe shutdown requirements are satisfied.

22. High Head Safety Injection Valve SI

-V-139 SI-V-139 is a normally closed valve which may be opened to provide a redundant hot standby charging path. The functionally redundant Train A valve SI -V-138 is available to perform this function. Should SI -V-139 spuriously open, the charging pump may have to be stopped to prevent overfill of the pressurizer. The safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-201 Tabulation 3.2.7.53 Electrical Tunnel - Stairwell Fire Area - ET-F-S1-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-202 Tabulation 3.2.7.54 Fire Pump House Fire Area - FPH-F-1A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-203 Tabulation 3.2.7.55 Fire Pump House Fire Area - FPH-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-204 Tabulation 3.2.7.56 Fire Pump House Fire Area - FPH-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-205 Tabulation 3.2.7.57 Fuel Storage Building Fire Area - FSB-F-l-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-206 Tabulation 3.2.7.58 East Main Steam and Feedwater Pipe Chase Fire Area - MS-F-1A-Z, MS-F-2A-Z, MS-F-3A-Z, MS-F-4A-Z, MS-F-5A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EAH-FN-174A x x EAH-FN-174B x x EAH-TSH-5136 x x EAH-TSH-5763 x x EDE-MCC-514 x FW-PT-524 x x FW-PT-535 x x FW-PT-526 x x FW-PT-534 x x FW-PT-525 x x FW-PT-536 x x MM-IR-51A x x MM-IR-51B x x MS-PY-3002-1,2 x x MS-PY-3002-5,6 x x MS-PY-3002-3,4 x x MS-PV-3002 x x MS-PV-3002 x x MS-PY-3003-1,2 x x MS-PY-3003-3,4 x x MS-PY-3003-5,6 x x MS-PV-3003 x x MS-PV-3003 x x MS-V86 x MS-V92 x MS-V88 x x MS-V88 x x MS-V90 x x MS-V90 x x MS-CP-182 x x MS-CP-184 x x EDE-CP-248 x SW-P-41A x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-207 East Main Steam and Feedwater Pipe Chase Fire Area - MS-F-1A-Z, MS-F-2A-Z, MS-F-3A-Z, MS-F-4A-Z, MS-F-5A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-P-41C x SW-V2 x SW-V22 x SW-PT-8272 x SW-PT-8273 x SW-PT-8274 x SWA-FN-40A x B. ANALYSIS 1. General Area Analysis The east MS & FW pipe chase is a concrete structure 74 '-9" long by 16 '-3" wide by 57' high with a floor area of 1220 sq. ft. and a volume of 69,540 cu. ft. The area contains no in situ combustibles other than cables in trays and fiberglass ladders. There is one stack of three cable trays. The bottom tray is an enclosed instrument level tray located approximately 1 '-6" above the floor. The other trays are open ladder type trays which are located approximately 10 ' above the floor. The zone contains approximately 140 lineal ft. of ladder type tray. Detectors are provided throughout the area. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-208 2. System Analysis

a. Containment Enclosure Ventilation Fans EAH

-FN-174A, EAH -FN-174B and Temperature Switches, EAH -TSH-5136, EAH -TSH-5763. Redundant ventilation fans and related cables are located in proximity. The purpose of these fans is to provide cooling for the Train A MSIV logic cabinets and the main steam pressure instrumentation. The failure of these fans will not prevent safe shutdown as the Train B logic cabinets and the main steam pressure transmitters FW -PT-514 and FW -PT-545 are not in the same fire area. The Train B logic cabinets are in the Train B switchgear room (Fire Area CB -F-1B-A) and the main steam pressure transmitters FW-PT-514 and FW -PT-545 are located in the west main steam and feedwater pipe chase (Fire Zone MS -F-1B-Z). These logic cabinets and pressure transmitters will perform their safe shutdown function. The Appendix R separation requirements are satisfied.

b. 460 Volt Motor Control Center EDE

-MCC-514 All cables are Train A. The redundant Train B cables are in Fire Area DCT-F-1B-0. The Appendix R separation requirements are satisfied.

c. Main Steam Pressure Transmitters FW

-PT-524, FW-PT-525, FW-PT-526, FW-PT-534, FW-PT-535, FW-PT-536 and Instrument Racks, MM-IR-51A, MM-IR-51B. Redundant channels of main steam pressure instruments and cables are located in proximity. Spurious operation of the channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after one (1) minute by use of the manual reset and block switch and terminate the containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B Switchgear Rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-209 Additionally main steam line pressure transmitters FW -PT-525 and FW-PT-534 utilized for process monitoring are located in the same fire areas. A fire could cause loss of indication from both main steam line pressure transmitters. However, the same fire would not affect pressure transmitters FW -PT-514 and FW -PT-545 which are functionally redundant and are located in the west main steam and feedwater pipe chase. (Fire Area: MS-F-1B-Z). These pressure transmitters and their associated atmospheric relief valves MS -PV-3001 and MS -PV-3004 will perform their safe shutdown function. The Appendix R separation requirements are satisfied.

d. Atmospheric Relief Valves MS

-PV-3002, MS-PV-3003 and Associated Solenoids. Valves MS -PV-3002 and MS -PV-3003 are normally closed valves. A fire could prevent operation of these valves. However, the same fire would not prevent the operation of valves MS -PV-3001 and MS -PV-3004 which are in the west main steam and feedwater pipe chase (Fire Area: MS -F-1B-Z, MS-F-2B-Z). Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affected air solenoids will be de -energized from the distribution panels located in Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-210 e. Main Steam Isolation Valves (MSIV) MS -V88 and MS -V90 and Logic Cabinet MS -CP-182, MS-CP-184. The valves MS -V88 and MS -V90 have no redundant counterpart, but they are supplied with redundant control capabilities. The Train A cables are routed in tray and conduit to the MSIV 's and their respective Train A logic cabinets. The Train B cables are routed in conduit on the opposite side of the MS & FW pipe chase. Their is a minimum horizontal separation of 10 ' up to the point that the conduits must run to the valves. The Train B conduits are routed approximately 15 ' above the floor. The MSIV 'S, connection boxes and electrical equipment are located approximately 25 ' above the floor. The Train B conduits are a minimum of 20 ' above the floor at the point they are in proximity to the Train A conduits. The Train A and Train B controls are on opposite sides of the MSIV approximately 2 ' apart. These valves are closed as an initial operator action. Should an MSIV reopen due to spurious operation (loss of power to both trains), the operators will isolate all feedwater to its respective steam generator and allow the SG to dry out. In the worst case this condition could occur to both MSIV 'S. The two steam generators and their associated MSIV 's in the west main steam and feedwater pipe chase (Fire Area: MS -F-1B-Z, MS-F-2B-Z) will be available for safe shutdown. The safe shutdown requirements are satisfied.

f. Main Steam Isolation Valves (MSIV) MS

-V86 and MS -V92 Valves MS -V86 and MS -V92 receive logic signals from both the Train A and the Train B MSIV logic cabinets. The cables and equipment in this Fire Area are associated with the Train A logic. The Train B logic cables and equipment are not routed through this fire area; hence, they will perform their safety function (MSIV trip). The Appendix R separation requirements are satisfied.

g. Not used.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-211 h. Service Water Pumps SW -P-41A and SW -P-41C All cables are Train A. The redundant Train B cables are in Fire Area DCT-F-1B-0. The Appendix R separation requirements are satisfied.

i. Service Water Valves SW

-V2 and SW -V22 All cables are Train A. The redundant Train B cables are in Fire Area DCT-F-1B-0. The Appendix R separation requirements are satisfied.

j. Tower Activation Logic Pressure Transmitters SW

-PT-8272, SW-PT-8273, SW-PT-8274 and Tower Actuation Panel EDE -CP-248 Failure in this cable could initiate a spurious tower actuation signal which would transfer one train of service water cooling capability from the pumphouse to the cooling towers. This transfer will not significantly interrupt Train A service water cooling nor will it have any impact on Train B service water. This failure does not prevent safe shutdown. The safe shutdown requirements are satisfied.

k. Service Water Air Handling Fan SWA

-FN-40A All cables are Train A. The redundant Train B cables are in Fire Area DCT-F-1B-0. The Appendix R separation requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-212 Tabulation 3.2.7.59 West Main Steam and Feedwater Pipe Chase Fire Area - MS-F-1B-Z, MS-F-2B-Z, MS-F-3B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-PT-514 x x FW-PT-545 x x FW-PT-544 x x FW-PT-515 x x FW-V156 x x FW-PT-516 x x FW-PT-546 x x MM-IR-52A x x MM-IR-52B x x MS-PY-3001-1, 2 x x MS-PY-3001-3, 4 x x MS-PY-3001-5, 6 x x MS-PV-3001 x x MS-PV-3001 x x MS-PY-3004-1, 2 x x MS-PY-3004-5, 6 x x MS-PY-3004-3, 4 x x MS-PV-3004 x x MS-PV-3004 x x MS-V86 x x MS-V86 x x MS-V92 x x MS-V92 x x SB-V9 x x SB-V10 x x SB-V11 x x SB-V12 x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-213 B. Analysis 1. General Area Analysis The west MS & FW pipe chase is a concrete structure 66 '-9" long by 14 ' wide by 57 ' high with a floor area of 935 sq. ft. and a volume of 64,700 cu. ft. The only in situ combustibles contained in the area consist of one gallon of oil in the steam recirculation pump for a fire loading of 150,000 Btu 's and fiberglass ladders for a fire loading of 1,586,000 Btu 's. There are no cables in trays. Detectors are provided throughout the area.

2. System/Equipment Analysis
a. Main Steam Pressure Transmitters FW

-PT-514, FW-PT-515, FW-PT-516, FW-PT-544, FW-PT-545, FW-PT-546 and Instrument Racks, MM-IR-52A, MM-IR-52B. Redundant channels of main steam pressure instruments and cables are located in proximity. Spurious operation of the channels will initiate safety injection and containment isolation Phase A signals. The operators will have the capability to terminate SI after 1 minute by use of the manual reset and block switch and terminate containment isolation by use of the manual reset switch. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). Additionally main steam line pressure transmitters FW -PT-514 and FW-PT-545 utilized for process monitoring are located in the same fire areas. A fire could cause loss of indication from both main steam line pressure transmitters. However, the same fire would not affect pressure transmitters FW -PT-525 and FW -PT-534 which are functionally redundant and are located in the east main steam and feedwater pipe chase. (Fire Area:

MS-F-3A-Z). These pressure transmitters and their associated atmospheric relief valves MS -PV-3002 and MS -PV-3003 will perform their safe shutdown function. The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-214 b. Atmospheric Relief Valves MS -PV-3001, MS-PV-3004 and Associated Solenoids. Valves MS -PV-3001 and MS -PV-3004 are normally closed valves. A fire could prevent operation of these valves. However, the same fire would not prevent the operation of valves MS -PV-3002 and MS -PV-3003 which are in the west main steam and feedwater pipe chase (Fire Areas: MS -F-1A-Z, MS-F-2A-Z). Spurious opening of even one ARV can result in an overcooling condition in the RCS. This coupled with the potential unavailability of SI constitutes an unanalyzed condition. Since the ARV 's are air operated valves, their spurious operation will be prevented by assuring that these valves are placed in a state such that the initial spurious operation in the air supply will not cause the valve to open. This will be accomplished by procedure as one of the first steps for any fire that can affect the integral ARV air system cables. This action is justifiable since it can be accomplished from the main control room. To prevent a subsequent short that could override the initial action and cause the ARV to open, the affected air solenoids will be de -energized from the distribution panels located in Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). This will isolate the faulted air supply but will not preclude operation of the ARV since the redundant air solenoids will still be operational. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-215 c. Main Steam Isolation Valves (MSIV) MS -V86 and MS -V92 The valves MS -V86 and MS -V92 have no redundant counterpart, but they are supplied with redundant control capabilities. The Train A and Train B conduits are on opposite sides of the west MS & FW pipe chase with a minimum horizontal separation of 10 ' up to the point that the conduits must run to the valves. The MSIV connection boxes and electrical equipment are located approximately 25 ' above the floor. The Train B conduits are a minimum of 20 ' above the floor at the point they are in proximity to the Train A conduits. The Train A and Train B controls are on opposite sides of the MSIV approximately 2 ' apart. These valves are closed as an initial operator action. Should an MSIV reopen due to spurious operation (loss of power to both trains), the operators will isolate all feedwater to its respective steam generator and allow the SG to dry out. In the worst case this condition could occur to both MSIV 'S. The two steam generators and their associated MSIV 's in the east main steam and feedwater pipe chase (Fire Areas: MS -F-1A-Z and MS-F-2A-Z) will be available for safe shutdown. The safe shutdown requirements are satisfied.

d. Not used.

C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-216 Tabulation 3.2.7.60 East Air Make -Up Pit Fire Area - MUA-F-1-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-217 Tabulation 3.2.7.61 This page intentionally left blank.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-218 Tabulation 3.2.7.62 Non-Essential Switchgear Room Fire Area - NES-F-1A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable ED-CP-532 x x ED-I-4 x x ED-PP-5 x x ED-PP-121B x x ED-PP-122A x ED-SWG-l x x ED-SWG-2 x x ED-US-11 x ED-US-23 x EDE-SWG-5 x FW-P-113 x FW-P-161 x MM-CP-153 x RC-P-1A x RC-P-1B x RC-P-1C x RC-P-1D x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-219 B. Analysis Loss of ED -I-4, ED-PP-5, ED-CP-532, MM-CP-153 will cause loss of CST level instrumentation CO -LT-4096. Redundant equipment is located in fire area EFP -F-1-A. RC pump switchgear control power (ED -SWG-l and ED-SWG-2) is lost. The RC pump switchgear is located in the fire area. The operator will trip the pumps by tripping offsite power from the control room. Pressurizer heaters C, D and control group control power (ED -US-11 and ED -US-23) will be lost due to this fire. If the heaters require tripping, an operator will do so manually in the Train A switchgear room (Fire Area: CB -F-1A-A). Alternatively, the operator can reduce pressure by opening a PORV. Redundant heaters are available with control power from the emergency DC bus. Cables from EDE -SWG-5 are located in this fire area. Loss of one cable could cause loss of offsite power which is acceptable since both diesel generators are available. C. Evaluation The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-220 Tabulation 3.2.7.63 Primary Auxiliary Building Fire Area - PAB-F-1A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-P-11B x CC-P-11D x CC-TE-2271 x CC-TV-2271-1 x CC-TV-2271-2 x CC-V122 x CC-V168 x CC-V1092 x CC-V1095 x CS-E-5A x CS-E-5B x CS-FCV-121 x SI-V139 x CS-FT-121 x x CS-HCV-182 x x MM-IR-17 x x CS-LCV-112C x CS-LCV-112E x CS-LT-7464 x CS-P-2A x CS-P-2B x CS-P-3B x CS-V143 x CS-V196 x CS-V197 x EAH-FN-5B x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-221 Primary Auxiliary Building Fire Area - PAB-F-1A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EAH-FN-31B x EDE-SWG-6 x EDE-MCC-513 x PAH-DP-43B x PAH-DP-358 x PAH-FN-42B x RC-V22 x RC-V87 x SW-FN-51A x SW-P-41A x SW-P-41B x SW-P-41C x SW-P-41D x SW-P-110A x SW-V5 x SW-V18 x SW-V19 x SW-V23 x SW-V54 x SW-V25 x SW-V56 x SW-V139 x SWA-DP-66 x SWA-FN-64 x SWA-FN-71 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-222 B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-223 Tabulation 3.2.7.64 Primary Auxiliary Building Fire Area - PAB-F-1B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-224 Tabulation 3.2.7.65 Primary Auxiliary Building Fire Area - PAB-F-1F-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-225 Tabulation 3.2.7.66 Primary Auxiliary Building Fire Area - PAB-F-lJ-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-V175 x CC-V257 x CS-FCV-121 x x CS-FY-121B x x CS-V158 x CS-V196 x x CS-V197 x x RC-V23 x RC-V88 x SI-PT-937 x SI-PT-936 x SI-V138 x B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-226 Tabulation 3.2.7.67 Primary Auxiliary Building Fire Area - PAB-F-lK-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-LCV-112B x CS-LCV-112C x CS-LCV-112D x CS-LCV-112E x PAH-DP-43A x x PAH-DP-43B x x PAH-DP-357 x PAH-DP-358 x PAH-FN-42A x PAH-FN-42B x SW-V4 x x SW-V5 x x SW-V74 x x B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-227 Tabulation 3.2.7.68 Primary Auxiliary Building Fire Area - PAB-F-2A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-FCV-110A x CS-FCV-111A x CS-FCV-110B x CS-FCV-111B x CS-LT-102 x CS-LT-106 x CS-P-3A x CS-V426 x EAH-FN-5B x EDE-MCC-513 x PAH-DP-35A x x PAH-DP-35B x PAH-DP-36A x PAH-DP-36B x PAH-DP-43A x PAH-DP-357 x PAH-FN-42A x SW-FN-51A x SW-P-41A x SW-P-41C x SW-P-110A x SW-V54 x SW-V56 x SW-V139 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-228 Primary Auxiliary Building Fire Area - PAB-F-2A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SWA-DP-66 x SWA-FN-64 x SWA-FN-71 x B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-229 Tabulation 3.2.7.69 Primary Auxiliary Building Fire Area - PAB-F-2B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-FCV-110A x x CS-FCV-111A x x CS-FCV-110B x x CS-FCV-111B x x CS-LT-102 x x CS-LT-106 x x CS-LT-7464 x x CS-P-3A x x CS-P-3B x x CS-V426 x x CS-V410 x CS-V410 x CS-V416 x CS-V416 x CS-V431 x CS-V423 x CS-V437 x CS-V1207 x CS-V439 x CS-V439 x CS-V442 x CS-V442 x CS-TK-4A x CS-TK-4B x PAH-DP-43A x PAH-DP-357 x PAH-FN-42A x B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-230 Tabulation 3.2.7.70 Primary Auxiliary Building Fire Area - PAB-F-2C-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-LT-2172-1 x CC-LT-2192-1 x CC-LT-2172-2 x CC-LT-2192-2 x CC-LT-2172-3 x CC-LT-2192-3 x CC-LT-2272-1 x CC-LT-2292-1 x CC-LT-2272-2 x CC-LT-2292-2 x CC-LT-2272-3 x CC-LT-2292-3 x CC-P-11A x x CC-P-11B x x CC-P-11C x x CC-P-11D x x CC-TE-2171 x x CC-TE-2271 x x CC-TE-2197 x x CC-TE-2297 x x CC-TV-2171-1 x x CC-TV-2271-1 x x CC-TV-2171-2 x x CC-TV-2271-2 x x CC-TY-2171 x x CC-TY-2271 x x MM-IR-93 x x CC-E-17A x CC-E-17B x CS-FT-121 x CS-FCV-110A x CS-FCV-111A x CS-FCV-110B x CS-FCV-111B x CS-FCV-121 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-231 Primary Auxiliary Building Fire Area - PAB-F-2C-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-HCV-182 x CS-LT-102 x CS-LT-106 x CS-LT-7464 x CS-LCV-112B x CS-LCV-112C x CS-LCV-112D x CS-LCV-112E x CS-P-2A x CS-P-3A x CS-P-3B x CS-V196 x CS-V426 x EDE-MCC-513 x EAH-FN-5A x EAH-FN-5B x EAH-FN-31A x EAH-FN-31B x PAH-DP-35A x PAH-DP-35B x PAH-DP-36A x x PAH-DP-36B x PAH-DP-43A x PAH-DP-43B x PAH-DP-357 x x PAH-DP-358 x x PAH-FN-42A x x PAH-FN-42B x x PAH-TSH-5391 x x PAH-TSH-5393 x x SW-FN-51A x SW-P-41A x SW-P-41C x SW-P-110A x SW-V4 x SW-V5 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-232 Primary Auxiliary Building Fire Area - PAB-F-2C-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-V15 x SW-V16 x SW-V18 x SW-V20 x x SW-V19 x x SW-V34 x x SW-V23 x x SW-V54 x SW-V56 x SW-V74 x SW-V139 x SWA-DP-66 x SWA-FN-64 x SWA-FN-71 x B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-233 Tabulation 3.2.7.71 Primary Auxiliary Building Fire Area - PAB-F-3A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-LT-2172-1 x x CC-LT-2192-1 x x CC-LT-2172-2 x x CC-LT-2192-2 x x CC-LT-2172-3 x x CC-LT-2192-3 x x CC-LT-2272-1 x CC-LT-2292-1 x CC-LT-2272-2 x CC-LT-2292-2 x CC-LT-2272-3 x CC-LT-2292-3 x EDE-TBX-YH4 x x EDE-TBX-YH5 x x CC-TK-19A x CC-TK-19B x CS-FCV-110A x CS-FCV-111A x CS-FCV-110B x CS-FCV-111B x CS-LCV-112B x CS-LCV-112D x DG-E-42A x DG-E-42B x SW-V4 x SW-V5 x SW-V15 x x SW-V17 x SW-V16 x x SW-V18 x x B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-234 Tabulation 3.2.7.72 Primary Auxiliary Building Fire Area - PAB-F-3B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-LT-2272-1 x x CC-LT-2292-1 x x CC-LT-2272-2 x x CC-LT-2292-2 x x CC-LT-2272-3 x x CC-LT-2292-3 x x CS-FCV-110A x CS-FCV-111A x CS-FCV-110B x CS-FCV-111B x CS-LCV-112B x x CS-LCV-112C x x CS-LCV-112D x CS-LCV-112E x B. Analysis For Analysis, see Primary Auxiliary Building Zone Analysis and Evaluation. C. Evaluation For Evaluation, see Primary Auxiliary Building Zone Analysis and Evaluation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-235 Tabulation 3.2.7.73 Primary Auxiliary Building Fire Area - PAB-F-4-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire zone. C. Evaluation The Appendix R separation requirements do not apply to this zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-236 PAB Zone Primary Auxiliary Building Zone Analysis And Evaluation B. Analysis 1. General Area Analysis

a. The PAB is a Class 1 concrete structure which contains the above listed equipment and cable required for safe shutdown. The PAB has been divided into several zones for fire protection analysis, with intervening walls, floors and ceilings of poured concrete.
b. The significant in situ combustibles consist of 0.2 gallon of oil in each of the two boron injection pumps; 1.0 gallon of oil in the monorail crane hoists; 1.0 gallon of oil in each of the two chiller pumps; 0.25 gallon of oil in each of the two reactor makeup water pumps; 1.0 pound of grease in each of the two boric acid transfer pumps; 1.0 gallon of oil in each of the four primary component cooling pumps; 0.5 gallon of oil in each of the two flash tank distillate pumps; 32,500 lbs. of charcoal within filters PAH-F-16 and CAP

-F-40 and 19,000 pounds of insulation for cables in trays. The analysis of the in situ fire load provided by the cable in trays is contained in the "Zone Analyses ". An analysis of the Design Basis Fires for the remaining combustibles is contained in the "Fire Protection Program Evaluation of Comparison to Branch Technical Position APCSB

9.5-1, Appendix A" and is summarized as follows:

1) Elevation 7'-0" and Below a) Fire Zone PAB

-F-1A-Z Total fire loading for 6.0 gallons of oil is 900,000 Btu (chiller pumps CS -P-7A, and CS -P-7B and reactor makeup water pumps RMW -P-16A and RMW -P-16B), and the fire loading for fiberglass ladders is (28 pounds plastic) 364,000 Btu. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-237 b) Fire Zone PAB -F-1J-Z Limited in situ combustibles in pumps. c) Fire Zone PAB -F-1K-Z No combustibles

2) Elevation 25

'-0" a) Fire Zone PAB -F-2A-Z Total fire load for fiberglass ladders is (71 pounds plastic) 923,000 Btu . b) Fire Zone PAB-F-2B-Z Total fire loading for 2.0 pounds of grease is 36,000 Btu (boric acid transfer pumps CS -P-3A and CS -P-3B). c) Fire Zone PAB -F-2C-Z Total fire loading for 5.25 gallons of oil is 787,500 Btu (PCCW pumps CC -P-11A, 11B, 11C and 11D; 31/2 ton monorail crane hoist CS -CR-13; 41/2 ton monorail crane hoist CS-CR-5; boron injection pumps SI -P-4A and SI -P-4B). 3) Elevation 53 '-0" a) Fire Zone PAB -F-3A-Z Total fire loading for 1.0 gallon of oil is 150,000 Btu (flash tank distillate pumps SB -P-171A and SB -P-171B). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-238 b) Fire Zone PAB -F-3B-Z Total fire loading for 0.5 gallon of oil is 75,000 Btu (41/2 ton monorail crane hoist CS -CR-6) and for 50 pounds of Class A material is 400,000 Btu and for fiberglass ladders is (71 pounds plastic) 923,000 Btu. See "Fire Protection Program Evaluation and Comparison to Branch Technical Position APCSB 9.5 -1 Appendix A" for analysis of 6600 lbs. of charcoal in CAP -F-40. c. The Train A safe shutdown cables are routed in trays. The Train B safe shutdown cables are routed in conduits with a one -hour, fire -rated barrier from the fire area boundary where they enter the PAB to the fire area boundary where they exit or the equipment at which they terminate, except as discussed in the zone analyses.

d. Detectors are provided in all zones of the PAB with the exception of Fire Zones PAB

-F-1B-Z, PAB-F-1F-Z and PAB -F-1K-Z. e. Suppression is provided in Fire Zone PAB -F-2C-Z. Details are provided in the zone analysis.

f. Early fire detection by use of carbon monoxide detectors within the

charcoal filter CAP -F-40 is provided.

g. Volume control tank (VCT) isolation valves CS

-LCV-112B & -112C are normally open to provide a suction path from the VCT to the normally operating charging pump (CS -P-2A or -2B). These valves must stay open until RWST valve CS -LCV-112D or -112E is manually opened to provide a charging pump suction path from the RWST, or the boric acid tanks are manually aligned as a charging pump suction source. Spurious closure of a VCT isolation valve caused by a hot short would interrupt suction flow to the operating charging pump causing it to be damaged. If the standby charging pump has cables in the same area then its operation can also be degraded. The result would be no charging system flow. The following PAB fire zones have been combined into one fire area for analysis purposes: PAB-F-1A-Z, PAS-F-1J-Z, PAB-F-1K-Z, PAB-F-2A-Z, PAB-F-2B-Z, PAB-F-2C-Z, PAB-F-3A-Z, and PAB -F-3B-Z. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-239 Since this combined fire area contains cables for CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B, this condition is potentially applicable for the system alignment with either combination of CS -P-2A and CS-P-2B as the standby pump and operating pump. The CS-LCV-112B and CS -LCV-112C circuit design prevents spurious valve closure from hot shorts as follows. The field cable conductors for the motor control center (MCC) contactor close coil circuit are in different cables than the 120 V "hot" circuit conductors eliminating the hot short failure mode within the cables. Cable -to-cable hot shorts need not be postulated for thermoset cable insulation as used at Seabrook. Also, the barriered conduit for CS -LCV-112C prevents Train B cable damage. Since CS-LCV-112B and CS -LCV-112C will not spuriously close, CS-P-2A or -2B as the operating charging pump will not be damaged.

2. Zone Analyses
a. Fire Zone PAB

-F-1A-Z (Tabulation 3.2.7.63)

1) Specific Zone Analysis This zone at Elevation 7

'-0" and (-) 2'-0" of the PAB is bounded by concrete floors, ceilings and walls with penetrations to other zones. The zone is approximately 140 ' long by 75 ' wide by 16 ' high with a floor area of 5200 sq. ft. and a volume of 81,600 cu ft. All Train B Safe Shutdown cables are routed in conduit with a one -hour, fire-rated barrier. Combustibles are limited to 6.0 gallons of oil for a fire loading of 900,000 Btu and 28 pounds of plastic (fiberglass ladders) for a fire loading of 364,000 Btu with a total fire loading of 248 Btu per sq. ft. of floor area. Detectors are provided throughout the zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-240 2) System Analyses a) Primary Component Cooling Water (CC) System This zone contains cable routed in barriered conduits for temperature element CC -TE-2271; pumps CC -P-11B and CC-P-11D; and valves CC -TV-2271-1, CC-TV-2272-2, CC-V122, CC-V168, CC-V1092 and CC -V1095. This equipment is all Train B. There is no redundant Train A CC system equipment or cables in this fire zone. b) Chemical and Volume Control (CS) System This zone contains cables routed in barriered conduits for pumps CS-P-2B and CS -P-3B; and valves CS -LCV-112C, CS-LCV-112E, CS-V143 and CS -V197. Cables for the Train A pump CS-P-2A which is redundant to pump CS -P-2B are routed in tray and conduit that is 10 ' above floor Elevation 7 '-0" in the area that the pump cables are in proximity. See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g. Cables for the Train A Valve CS -FCV-121 and transmitter CS-FT-121 which provide a redundant charging flow path to valve SI -V139 are routed in tray and conduit in proximity to the barriered conduit containing the cables for SI-V139. Cables for the Train A valve CS -V196 are routed in tray and conduit in proximity to the barriered conduits containing the cables for the Train B Valve CS -V197. c) Containment Enclosure Air Handling (EAH) System This zone contains cables routed in barriered conduits for fans EAH-FN-5B and EAH -FN-31B. This equipment is all Train B. There is no redundant Train A EAH system equipment or cables in this fire zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-241 d) Electrical Distribution - Emergency (EDE) System This zone contains Train B cables routed in barriered conduits for the 4160V switchgear EDE -SWG-6. There are no functionally redundant cables in this area. The Train A EDE-MCC-513 cable has functionally redundant cables located in other fire areas. e) PAB Handling (PAH) System This zone contains cables routed in barriered conduits for dampers PAH -DP-43B, PAH-DP-358 and fan PAH-FN-42B. This equipment is Train B. There is no redundant Train A PAH system equipment or cables in this fire zone. f) Reactor Coolant (RC) System This zone contains cables routed in barriered conduits for valves RC -V22 and RC -V87. The cables are part of the position indicating light circuit for valves that have been permanently disabled. Failures in this circuit will not prevent opening of the valves for cold shutdown. g) Safety Injection (SI) System This zone contains cables routed in barriered conduits for valve SI-V139. This equipment is Train B. The redundant cables and equipment are as discussed in b) above.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-242 h) Service Water (SW) System This zone contains cables routed in barriered conduits for Train B pumps SW -P-41B and SW -P-41D and valves SW-V5, SW-V18, SW-V19, SW-V23 and SW -V25. The only exception is at an interference with an HVAC duct support where the one -hour wrap is reduced and pyrocrete is installed for heat transfer protection. Cables for Train A pumps SW-P-41A and SW -P-41C and valve SW -54, which are redundant to pumps SW -P-41B and SW -P-41D and valve SW-V25 are routed in tray that is 9 ' above the floor Elevation 7 '-0" except at the entrance to the duct bank to the cooling towers where it is 3 '-6" above floor Elevation 7'-0". There is approximately 8 ' of horizontal separation between the Train B barriered conduit and the Train A tray. For the other Train A cables routed in this zone, the

redundant cables and equipment are contained in other fire areas. i) Service Water Air Handling (SWA) System All cables are Train A, the redundant cables are located in other fire areas.

3) Summary For CC, EAH, and PAH systems above, the routing of the Trai n B cables in conduit with a one

-hour, fire -rated barrier; the absence of Train A equipment and cables; and considering the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation for Appendix R, Paragraph III G.2c. "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed, " has been approved.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-243 For CS and SI systems above, the routing of the Train B cables in conduit with a one -hour, fire -rated barrier; the 10 ' height of the tray and conduit above the floor; and considering the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements and

Appendix R. A deviation for Appendix R, Paragraph III G.2c "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed, " is requested. For SW system above, the routing of the Train B cables in conduit with a one -hour, fire -rated barrier; the 8 ' of separation between the Train A tray and the Train B conduit; and considering the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation for Appendix R, Paragraph III G.2c "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed, " is requested. For RC system above, the safe shutdown requirements are satisfied. For EDE and SWA systems above the Appendix R separation requirements are satisfied.

b. Fire Zone PAB

-F-1J-Z (Tabulation 3.2.7.66)

1) Specific Zone Analysis This zone at Elevation (

-) 6'-0" and (-) 26'-0" of the PAB is bounded by concrete floors, ceiling and walls with penetrations to other zones. The zone is approximately 96 ' long by 75 ' wide by 11 ' to 18' high with floor area of 1980 sq. ft. and a volume of 23,782 cu. ft. All Train B safe shutdown cables are routed in conduit with a one-hour, fire -rated barrier. Combustibles are limited to cables in open trays with a total fire loading of 500 Btu per sq. ft. and limited in situ combustibles in pumps. Detectors are provided throughout the zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-244 2) System Analyses a) Primary Component Cooling Water (CC) System This zone contains cables routed in tray for the Train A valves CC -V175 and CC -V257. The tray is minimum of 10' above floor elevation ( -) 26'-0". Only 6 linear feet of the tray is in the zone. The redundant Train B cables are routed in barriered conduit above floor elevation ( -) 8'-0" in Fire Zone PAB -F-1Z-Z, which is approximately 18 ' horizontally above the Train A cables with an intervening concrete floor. b) Chemical and Volume Control (CS) Syst em This zone contains equipment and cables in conduit required for operation of Train A Valve CS -FCV-121 which provides a redundant charging flow path to Train B Valve SI-V139. The redundant Train B cables are routed in barriered conduit in Fire Zone PAB -F-1A-Z and are separated from the Train A cables by concrete floors and walls. Valve CS-V158 provides redundant seal cooling capabilities to the safety grade thermal barrier cooling. Cables, controls and equipment for the Train A thermal barrier cooling capability are not contained in the PAB fire area and will be available for safe shutdown. Redundant valves CS -V196 and CS -V197 are located in the same fire zone and are separated by approximately 3 ' horizontal separation. These valves are normally open

valves that remain open for Safe Shutdown. The spurious closure for one valve will not prevent shutdown. The operators will prevent further spurious operation by tripping the power supply breakers at the Train A or Train B switchgear rooms (Fire Areas: CB -F-1A-A or CB-F-1B-A). See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-245 c) Reactor Coolant (RC) System This zone contains cables routed in tray for the Train A valves RC -V23 and RC-V88. The cables are part of the position indicating light circuit for valves that have been permanently disabled. Failures in this circuit will not prevent the opening of the valves for cold shutdown. d) Safety Injection (SI) System This zone contains cables routed in tray for the Train B valve SI-V139. The tray is a minimum of 10 ' above floor Elevation ( -) 26'-0". Only six lineal feet of the tray is in the zone. The redundant Train B cables are routed in barriered conduit above floor Elevation (-) 8'-0" in Fire Zone PAB-F-1A-Z, which is approximately 18 ' horizontally above the Train A cables with an intervening concrete floor. Redundant channels of containment pressure (SI -PT-936 and SI-PT-937) cables are located in proximity. Spurious operation of these channels will initiate containment spray and containment isolation Phase B. The operators will have the capability to terminate these protective actions by use of manual reset switches. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB-F-1A-A and CB-F-1B-A). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-246 3) Summary For CC and SI systems above, the routing of the Train B cables in conduit with a one -hour, fire -rated barrier; the height of the Train A an B raceways, the provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area; and considering the low combustibles loading in the zone provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III G.2.c "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved. For CS system above, the routing of the Train B cables in conduit with a one -hour, fire -rated barrier; and the low combustibles loading in the zone provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III G.2.c in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved. For RC system above, the safe shutdown requirements are satisfied.

c. Fire Zone PAB

-F-1K-Z (Tabulation 3.2.7.67)

1) Specific Zone Analysis This zone between Elevation (

-) 6'-0" and roof Elevation 81 '-0" of the PAB is bounded by concrete floors, ceilings and walls with penetrations to other zones. The zone is approximately 68 ' long by 9' wide by 75 ' high with a floor area of 4,620 sq. ft. and a volume of 75,370 cu. ft. There is no tray in the zone and all cables are routed in conduit. All Train B safe shutdown cables are routed in conduit with a one-hour, fire -rated barrier. There are no in situ combustibles in the zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-247 2) System Analyses a) Chemical and Volume Control (CS) System This zone contains cables routed in conduit for Train A valves CS -LCV-112B and CS -LCV-112D. The Train B cables for their redundant counterpart valves CS-LCV-112C and CS -LCV-112E are routed in barriered conduit in the zone. There is 13 ' horizontal separation between the conduits containing the redundant cables. See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g. b) PAB Air Handling (PAH System) This zone contains cables routed in conduit to Train A damper PAH -DP-43A. The Train B cables to redundant damper PAH -DP-43B are routed in barriered conduit in the zone. The only exception to the barrier is a short length of flexible conduit whose wrapping would interfere with the damper operator. The dampers are located approximately 15' above the floor. The area containing the dampers is a concrete and steel enclosed air plenum with limited access and no combustibles. These dampers and the fans which they control are not needed unless the main ventilation system is lost due to loss of off-site power or unless the temperature in the PCCW area exceeds 40C (104F). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-248 c) Service Water (SW) System This zone contains cables routed in conduit for Train A valve SW-V4. The Train B cables for its redundant counterpart valve SW-V5 are routed in barriered conduit in the zone. The only exception to the barrier is one cable which runs in flexible conduit between a limit switch on valve SW-V5 to its motor operator. There is 8 ' horizontal separation between the barriered conduit for valve SW -V5 and valve SW -V4. There is 16 ' horizontal separation between the redundant valves. The valves are located approximately 15 ' above floor Elevation 53 '-0" and 3' above platform Elevation 65 '-0. This zone also contains cables routed in conduit for Train A valve SW-V74. The position of this valve is only important when the Train A cooling tower capabilities are in use at which time the valve should be closed and should remain closed. In the event this valve opens spuriously, the operators can either transfer the Train A service water to the pumphouse or utilize the Train B service water system. This satisfies the safe shutdown requirements.

3) Summary For the CS system above, the routing of the Train B cables in conduit with a one

-hour, fire-rated barrier; the spatial separation between the Train A and Train B conduits; and considering the absence of in situ combustibles in the zone provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III G.2.c "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-249 For the PAH system above, the routing of the Train B cables in conduit with a one -hour, fire-rated barrier; the height of the dampers above the floor; the absence of in situ combustibles in the zone and the fact that a fire in the area could not cause loss of off-site power, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III.G.2 has been approved. For the SW system above, the routing of the Train B cables in conduit with a one -hour, fire -rated barrier; the horizontal separation of 8 ' between conduit and valve and 16 ' between the valves themselves; the height of the valves from the floor; and considering the absence of in situ combustibles in the zone provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III G.2.c "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved.

d. Fire Zone PAB

-F-2A-Z (Tabulation 3.2.7.68)

1) Specific Zone Analysis This zone at Elevation 25

'-0" of the PAB is bounded by concrete floor, ceiling and walls (South and East) and is contiguous to fire zones PAB -F-2B-Z and PAB -F-2C-Z. The northern boundary consists of partial height concrete walls and an 11 ' wide access passage. The western boundary consists of full height concrete walls and metal partitions. There are penetrations for tray, ducts, and pipes to other fire zones. The zone is approximately 44 ' long by 39' wide by 26 ' high with a floor area of 1550 sq. ft and a volume of 40,000 cu ft. No safe shutdown equipment is contained in the zone, only safe shutdown cables. Combustibles are 71 pounds of plastic (fiberglass ladders) for a total fire loading of 596 Btu per sq. ft. of floor area and limited in situ combustibles. This is classed as a low fire load. Detectors are provided throughout the zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-250 2) System Analyses a) Chemical and Volume Control (CS) System This zone contains cables routed in tray for the redundant boric acid tank level transmitters CS -LT-102 and CS-LT-106. These tank levels are only required once cooldown has been initiated. Should both transmitter cables be damaged by a fire, the operators can utilize the Train B level transmitter CS -LT-7464. This transmitter and its associated cable are not contained in this fire zone. The indicator for this transmitter is located at the RSS panel in the Train B switchgear room (Fire Area: CB -F-1B-A). This zone contains cables routed in tray and conduit for the boric acid pump CS -P-3A and for the boric acid to charging pumps isolation valve CS -V426. Cables for the redundant Train B boric acid pump CS -P-3B are routed in barriered conduits in Fire Zones PAB -F-2B-Z and PAB -F-2C-Z. Valve CS-V426 has no electrically operated redundant counterpart. Should the valve be damaged by a fire, the operator will establish a gravity path from the BAT 's to the charging pump suction by the repositioning to manual valves in the boric acid pump room (Fire Zone PAB-F-2B-Z). These valves are not required to be operated until boric acid is required for shutdown reactivity. This would be up to four hours into the event. See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-251 This zone contains cables for CS-FCV-110A, -111A, -110B, -111B. Spurious opening of these valves in conjunction with spurious start of a boric acid transfer pump or reactor makeup water pump may divert boric acid from the reactor coolant system affecting cold shutdown reactivity control, or result in an unplanned dilution affecting hot standby and cold shutdown reactivity control. The operators isolate the diversion flow by closing

CS-FCV-110B & -111B using the main control board control switches. The operators isolate the dilution flow by closing CS -LCV-112B or CS -LCV-112C using the main control board control switch. b) Containment Enclosure Air Handling (EAH) System This zone contains cable routed in barriered conduit for the Train B fan EAH -FN-5B. The cables for the redundant Train A fan EAH -FN-5A are routed in trays in fire zone PAB-F-2C-Z. There is approximately 16 ' horizontal separation between the barriered conduit and the redundant tray. c) Electrical Distribution Emergency (EDE) System All cables are Train A. The functionally redundant cables are located in other fire areas.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-252 d) PAB Air Handling (PAH) System Cables and equipment for outboard isolation dampers PAH-DP-35A and PAH -DP-36A and inboard isolation dampers PAH -DP-35B and PAH -DP-36B are routed in trays and conduits in proximity to one another. Under normal operation both outboard and both inboard dampers are open. If both outboard or both inboard dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. If the outboard dampers and the inboard dampers operate independently such that either the supply or the exhaust path but not both are isolated, there could be an air flow problem in EAH system. Outboard dampers are powered from a single Train A power supply. Inboard dampers are powered from a single Train B power supply. The circuit design for the outboard and inboard dampers is such that a spurious signal in either or both circuits will cause both outboard and inboard dampers to operate together, either both open (normal mode) or both closed (recirculation mode). This zone contains cables routed in tray for the Train A fan PAH-FN-42A and damper PAH -DP-357. The cables for the redundant Train B fan PAH -FN-42B and damper PAH-DP-358 are routed in barriered conduit in fire zone PAB-F-2C-Z. There is greater than 50 ' of horizontal separation between the tray and the redundant barriered conduit. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-253 e) Service Water (SW) System This zone contains cable routed in tray for the Train A pumps SW-P-41A and SW -P-41C and valve SW -V54. The cables for the redundant Train B pumps SW -P-41B and SW-P-41D and valve SW -V25 are routed in barriered conduits in fire zone PAB -F-1A-Z. There is approximately 25' of horizontal separation between the tray and the redundant barriered conduits. For the other Train A cables routed in this zone, the redundant cables and equipment are contained in other fire areas. f) Service Water Air Handling (SWA) System All cable are Train A, the redundant cables are located in other fire areas.

3) Summary For the CS system above, the provision of a manual valve alignment capability that is not required for up to four hours into the event satisfies the safe shutdown requirements. Also, the capability to isolate the boric acid diversion flow and the dilution flow using the main control board control switches satisfies the safe shutdown requirements.

For the EAH, PAH and SW systems above, the routing of the Train B cables in a one -hour, fire -rated barrier; the horizontal separation of 16 ', 25' and 50' respectively; and the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III.G.2.c, "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved. For the EDE and SWA systems above, the Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-254 e. Fire Zone PAB -F-2B-Z (Tabulation 3.2.7.69)

1) Specific Zone Analysis This zone at Elevation 25

'-0" of the PAB is bounded by concrete floor, ceiling and walls (South and West) and is contiguous to fire zones PAB -F-2A-Z and PAB -F-2C-Z. The northern and eastern boundaries consists of full height concrete walls and metal partitions. There are penetrations for tray, ducts and pipes to other fire zones. The zone is approximately 28 ' long by 37 ' wide by 16 ' high with a floor area of 1300 sq. ft. and a volume of 33,800 sq. ft. Combustibles are limited to 2.0 pounds of grease for a fire loading of 36,000 Btu and cables in open trays for a total fire loading of 6000 Btu per sq. ft. of floor area. Detectors are provided throughout the zone.

2) System Analyses a) Chemical and Volume Control (CS) System The redundant boric acid tank level transmitters CS

-LT-102 and CS-LT-106 are located in the same fire zone. Should both transmitters be unavailable due to fire damage, the operators can utilize the Train B level transmitter CS-LT-7464. This transmitter and its associated cable are contained in this fire zone. The indicator for this transmitter is located on the RSS panel in the Train B switchgear room (Fire Area: CB -F-1B-A). Should all level transmitters be unavailable, the operators will open the cross-connect valve s CS-V437 and CS -V1207 and boric acid tank isolation valves CS -V410 and CS -V416 allowing charging pump suction from both boric acid tanks. The combined inventory of the two tanks is sufficient to complete the cooldown thus eliminating the need for tank level monitoring.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-255 Redundant boric acid pumps CS -P-3A and CS -P-3B and the valve CS -V426 are located in the same fire zone. Should both pumps or the valve be damaged by the fire, th e operators will establish a gravity flow path from the BAT 's to the charging pump suction by repositioning of manual valves in the fire zone. Valves CS -V410, CS-V416, CS-V437, CS-V1207, CS-V439 and CS -V442 are manual valves required for gravity feed from the boric acid tanks to the charging pumps or cross-connecting the boric acid tanks in response to a loss of level indication. These valves are not required to be operated until boric acid is required for shutdown reactivity. This would be upon commencement of cooldown, up to four hours into the event, and the valves would then be accessible for manual operation. During this time the plant would be maintained in hot standby with RC inventory makeup provided by the RWST. See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g.

This zone contains cables for CS-FCV-110A, -111A, -110B, -111B and the valves. Spurious opening of these valves in conjunction with spurious start of a boric acid transfer pump or reactor makeup water pump may divert boric acid from the reactor coolant system affecting cold shutdown reactivity control, or result in an unplanned dilution affecting hot standby and cold shutdown reactivity control. The operators isolate the diversion flow by closing CS -FCV-110B & -111B using the main control board control switches. The operators isolate the dilution flow by closing CS -LCV-112B or CS-LCV-112C using the main control board control switch.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-256 b) PAB Air Handling (PAH) System This zone contains cables routed in tray and conduit for the Train A fan PAH -FN-42A and dampers PAH -DP-43A and PAH-DP-357. The cables for the redundant Train B fan PAH-FN-42B and dampers PAH -DP-43B and PAH-DP-358 are routed in barriered conduit in fire zone PAB-F-2C-Z. There is 4 ' horizontal separation between the Train A raceways and the Train B equipment and barriered conduit. The Train A trays are a minimum of 8 ' above floor Elevation 25 '-0". A total of 3 trays exist in the stack with the bottom tray an enclosed instrument level tray containing no Safe Shutdown cables. The Train B damper PAH-DP-358 is located approximately 18 ' above floor Elevation 25 '-0". 3) Summary For the CS system above, the provision of a manual valve alignment capability that is not required for up to four hours into the event satisfies the safe shutdown requirements. Also, the capability to isolate the boric acid diversion flow and the dilution flow using the main control board control switches satisfies the safe shutdown requirements. For the PAH system above, the routing of the Train B cables in conduit with a one -hour, fire -rated barrier in another zone of the PAB; the 4 ' horizontal between the Train A and Train B equipment; the 8 ' height of the tray above the floor; and considering the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III G.2.c. "in addition to 1 hour fire barrier, automatic fire suppression system shall be installed ", has been approved.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-257 f. Fire Zone PAB -F-2C-Z (Tabulation 3.2.7.70)

1) Specific Zone Analysis This zone at Elevation 25

'-0" of the PAB is bounded by concrete floors, ceilings and walls (North, East and West) and is contiguous to fire zones PAB -F-2A-Z and PAB -F-2B-Z to the South. The southern boundary consists of full height partitions, full and partial height concrete walls and an 11' wide access passage. There are penetrations for tray, ducts and pipes to other fire zones. The zone is approximately 100 ' long by 75 ' wide by 26 ' high with a floor area of 7,200 sq. ft. and a volume of 187,000 cu. ft. The trays installed at Elevation 25 '-0" are in stacks five and six high by four wide, as a worst case, with a minimum of 4 ' between the Train A and Train B stacks. There are several areas where the trays have vertical drops through the floor. With a limited number of exceptions, the trays are a minimum of 10 ' above the floor. Metal covers are provided around the vertical trays near column lines 2 and C. The in situ combustibles are limited to cables in open trays which provide a fire load of 16,000 Btu per square foot of floor area; the boron injection pumps which contain 0.25 gallons of oil are a fire loading of 37,500 Btu; the primary component cooling water pumps CC-P-11A, 11B, 11C and 11D containing a total of four gallons of oil for a fire loading of 600,000 Btu; 41/2 ton monorail crane hoist CS -CR-5 containing 0.5 gallons of oil for a fire loading of 75,000 Btu; and 31/2 ton monorail crane hoist CS -CR-13 containing 0.5 gallons of oil for a fire loading of 75,000 Btu. The concentrated fire load in this zone is 30,000 Btu per squar e foot of tray. Because of the concentrated fire load, we have installed sprinklers to control transient fires in the area of the trays. To protect the PCCW pumps against a fire from a transient combustible, we have installed a pre -action system, using high temperature heads over the pumps and the surrounding area. Spray shields will be installed over the PCCW pump motors. Detectors are provided throughout the zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-258 2) System Analyses a) Primary Component Cooling Water (CC) System The redundant Primary Component Cooling Water (PCCW) pumps are located in the same fire area. The CC System is configured such that there are two 100% capacity PCCW pumps in each train either of which can be utilized for safe shutdown. The spatial separation between Train A pump CC-P-11A and Train B pump CC -P-11D is in excess of 20' with a metal partition between them. The spatial separation between Train A pump CC -P-11C and Train B pump CC-P-11B is in excess of 20 ' with a metal partition between them. The cables to the Train B pumps are routed in barriered conduit from the point they enter the PAB to the pump motors. The conduits are barriered in the vicinity of the Train B pumps. The Train B pumps have a spatial separation of 25 ' from the Train A trays and 15 ' from the Train B trays. The redundant PCCW heat exchanger valves CC-TV-2171-1, 2 and CC -TV-2271-1, 2 and their associated controls and instrument rack MM -IR-93 are located in the same fire area. The cables for the Train B valves CC -TV-2271-1 and CC-TV-2271-2 and the Train B controllers are routed in barriered conduits. The only exception is a reduction in the barriers at the controllers and valves due to interference with instrument lines. The redundant valves are mounted approximately 20 ' above the floor with a minimum separation of 2 '. The controllers are wall and instrument rack mounted and are separated by approximately 20 '. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-259 The redundant temperature elements CC -TE-2171, CC-TE-2197 and CC -TE-2271, CC-TE-2297 are located in the same fire area. The cable for one of the redundant Train B temperature elements is routed in a barriered conduit. The trip logic is a 2 out of 2 logic. The redundant temperature elements have a horizontal separation of approximately 8 ' and are mounted on 24 " component cooling water pipes approximately 20 ' above the floor. Cables for the redundant head tank level transmitters are in proximity. Failures in these cables could initiate a spurious

lo-lo-head tank level isolation signal. This in turn would result in closure of the PCCW containment isolation valves. These valves are only required when it is necessary to maintain containment habitable for containment entry to manually operate the RHR isolation valves and the SI accumulator isolation valves. The circuitry for these valves is not affected by a fire in this area; hence, they would be operable from the MCR. Therefore, the spurious operation of these transmitters will not prevent safe shutdown. b) Chemical and Volume Control (CS) System This zone contains cables in tray required for operation of Train A valve CS -FCV-121, which provides one of the required hot standby charging flow paths. The redundant Train B valve SI -V139 cables are routed in barriered conduit in Fire Zone PAB -F-1A-Z and are separated from the Train A cables by concrete floors. For cooldown, the operators will manually align the Train B charging pump discharge and bypass valves (CS-V219 and CS -V220) to the seal injection flow path and throttle the bypass valve as required. This operator action can be delayed for up to of 4 hours into the event. This zone contains cables in barriered conduit for the charging to RCS isolation valve CS -V143. The cables for the redundant valve CS -V142 are not contained in this fire area. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-260 This zone contains cables routed in tray for the redundant boric acid tank level transmitters CS -LT-102 and CS-LT-106. These tank levels are only required once cooldown has been initiated. Should both transmitter cables be damaged by a fire, the operators can utilize the Train B level transmitter CS -LT-7464. This transmitter 's cable is contained in this fire zone. The indicator for this transmitter is located at the RSS panel in the Train B switchgear room (Fire Area: CB -F-1B-A). Should all level transmitters be unavailable, the operators will open th e cross-connect valve CS -V437 allowing charging pump suction from both boric acid tanks. The combined inventory of the two tanks is sufficient to complete the cooldown thus eliminating the need for tank level monitoring. This zone contains cables routed in tray and conduit for the redundant boric acid pumps CS -P-3A and CS -P-3B and for the valve CS -V426. Should both pumps or the valves be damaged by a fire, the operator will establish a gravity path from the BAT 's to the charging pump suction by the repositioning of manual valves in the boric acid pump room (Fire Zone PAB -F-2B-Z). Some of these valves are also required to cross -connect the boric acid tanks in response to a loss of level indication (see above discussion). These valves are not required to be operated until boric acid is required for shutdown reactivity. This would not be required for up to four hours into the event. This zone contains cables routed in tray and conduit for the Train A charging pump CS-P-2A. The cable for the redundant Train B pump CS -P-2B are routed in a barriered conduit in Fire Zone PAB -F-1A-Z. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-261 The zone contains cables routed in tray and conduit for the redundant valves CS -LCV-112B, CS-LCV-112D, CS-LCV-112C and CS -LCV-112E. The cables for valves CS-LCV-112C and CS -LCV-112E are routed in barriered conduits. The only exception is at an interference with fire detectors where the one -hour wrap is reduced to allow air flow to the detector. At the point of the reduced one -hour wrap, there is a minimum of 20 ' of horizontal separation to functionally redundant cables. See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g.

This zone contains cables for CS-FCV-110A, -111A, -110B, -111B. Spurious opening of these valves may divert boric acid from the reactor coolant system affecting cold shutdown reactivity control, or result in an unplanned dilution affecting hot standby and cold shutdown reactivity control. The operators isolate the diversion flow by tripping the control circuit power supply breaker to close CS -FCV-110B & -111B (valves fail closed). The operators isolate the dilution flow by closing

CS-LCV-112C using the main control board control switch. This zone contains cables routed in trays for valve CS-V196. The cables for the redundant Train B valve CS-V197 are routed in a barrier conduit in Fire Zone PAB-F-1A-Z. c) Containment Enclosure Air Handling (EAH) System The cables for the redundant fans EAH -FN-5A and EAH-FN-5B, are routed in tray and conduits in the same area. All the Train B fan cables are routed in barriered conduits, which are separated from the Train A cables by a minimum of 18 '. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-262 Cables for redundant equipment vault return fans EAH-FN-31A and EAH -FN-31B are routed in trays and conduits in proximity to one another. These fans are required to maintain the equipment vaults habitable for entry if manual operations are required to place RHR into operation for cold shutdown. A fire in the PAB fire area will not prevent operation from the MCR of any equipment necessary for RHR operation; hence, habitability of the equipment vaults is not required. Analysis and field testing has confirmed that the containment enclosure supply fans EAH-FN-5A and EAH-FN-5B are sufficient to maintain the equipment vaults below the equipment 's qualified temperatures. d) Electrical Distribution Emergency (EDE) System All cables are Train A. The functionally redundant cables are located in other fire areas. e) PAB Air Handling (PAH) System Cables and equipment for outboard isolation dampers (PAH-DP-35A and PAH -DP-36A and inboard isolation dampers PAH -DP-35B and PAH -DP-36B are routed in trays and conduits in proximity to one another. Under normal operation both outboard and both inboard dampers are open. If both outboard or both inboard dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in recirculation mode. The normal and recirculation modes for EAH system operation both satisfy

the safe shutdown function. If the outboard dampers and the inboard dampers operate independently such that either the supply or the exhaust path but not both are isolated, there could be an air flow problem in EAH system.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-263 Outboard dampers are powered from a single Train A power supply. Inboard dampers are powered from a single Train B power supply. The circuit design for the outboard and inboard dampers is such that a spurious signal in either or both circuits will cause both outboard and inboard dampers to operate together, either both open (normal mode) or both closed (recirculation mode). The redundant PAH fans (PAH -FN-42A and PAH-FN-42B) and dampers (PAH -DP-43A, PAH-DP-357, PAH-DP-43B and PAH -DP-358) are in proximity. The fans and dampers are inside separate metal enclosures located approximately 15 ' above the floor. The Train B fan and damper cables are routed in barriered conduits. The only exception to the barrier is short lengths of flexible conduit whose wrapping would interfere with damper

operator PAH -DP-358. There are no cable trays in the vicinity of the fans and dampers. The only in situ combustibles in the vicinity are in the PCCW pumps which are separated from the fans and dampers by greater than 20 ' horizontally and the monorail crane hoist. These fans are not needed unless the main ventilation system is lost due to the loss of off -site power or unless the temperature in the immediate area exceeds 40C (104F). The redundant temperature switches PAH -TSH-5391 and PAH-TSH-5393 and conduits containing their cables are located in proximity. Failure of these switches or their cables could prevent operation of fans PAH -FN-42A and PAH-FN-42B. Should the switches or cables fail, the operators can isolate the affected portion of the circuit at the RSS facilities in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A) and restart the fans.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-264 f) Service Water (SW) System This zone contains cables routed in tray for the Train A pumps SW-P-11A and SW -P-11C and valve SW -V54. The redundant Train B pumps and valve cables are routed in a barriered conduit in Fire Zone PAB -F-1A-Z which is separated from this zone by an intervening concrete floor. The cables for redundant valves SW -V4, SW-V16, SW-V5 and SW-V18, are located in the same fire zone. These valves may be required to reposition to isolate secondary component cooling water or for DG cooling. The Train B valves SW -V5 and SW -V18 cables are routed in barriered conduits and are separated from the Train A cables by greater than 30' horizontally. There are no cable trays or other in situ combustibles in the vicinity of Train B conduits. The cables for redundant valves SW -V-15 and SW -V17 are located in the same fire zone. These valves are normally in their safe shutdown position to provide cooling to the PCCW heat exchangers. In addition, the circuit breaker for

SW-V17 is administratively controlled off so the valve cannot spuriously close. If SW -V15 spuriously closes, SW-V17 is still open to provide the Train B PCCW heat exchanger cooling function. Redundant valves SW -V20, SW-V34 and SW -V19, SW-V23 are located in the same fire zone. Operators for valves SW -V34 and SW -V23 are approximately 5 ' above floor Elevation 25 '-0" and operators for valves SW -V20 and SW-V19 are approximately 10' above floor Elevation 25'-0". The redundant valves are separated by approximately 16 ' horizontally. There are no cable trays in the vicinity of the valves. The only in situ combustibles in the vicinity are the PCCW pumps which are separated from the Train A valves by greater than 16 ' horizontally. The valves are in Safe Shutdown position. The operators will prevent spurious operation by tripping the power supply breakers at the Train A and Train B Switchgear Rooms (Fire Area: CB -F-1A-A and CB-F-1B-A). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-265 For the other Train A cables routed in this zone, the redundant cables and equipment are contained in other fire areas. g) Service Water Air Handling (SWA) System All cables are Train A. The redundant functionally cables are located in other fire areas. 3) Summary For the CC system above, the routing of the Train B cables in conduit with a one -hour, fire -rated barrier; the spatial separation; and the provision of the sprinkler system, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. For the CS system charging pumps and the related CS and SI valves above, the routing of the Train B cables in conduit with a

one-hour, fire -rated barrier and the provision of suppression in the area of the trays and the PCCW pumps, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. For the CS system transmitters, boric acid pumps and related valve above, the provision of a manual valve alignment capability that is not required for up to four hours into the event satisfies the safe shutdown requirements. Also, the capability to isolate the boric acid diversion flow by tripping the control circuit power supply breaker and isolate the dilution flow using the main control board control switches satisfies the safe shutdown requirements. For the EAH system supply fans above, the routing of Train B cables in conduit with a one -hour, fire -rated barrier and the provision of suppression in the area of the trays and the PCCW pumps, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. For the EAH system return fans above, the safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-266 For the PAH dampers above, the safe shutdown requirements are satisfied. For the PAH fans and related dampers above, the routing of the Train B cables in conduits with a one -hour, fire -rated barrier; the height of the fans off the floor; the lack of combustibles in the area of the fans and the fact that a fire in the area could not cause loss of offsite power, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. For the PAH temperature switches above, the safe shutdown requirements are satisfied. For the SW system above, the routing of the Train B cables in a conduit with a one -hour, fire -rated barrier; the spatial separation and the provision of the sprinkler system, provide acceptable fire protection and provide protection equivalent to the technical requirement of Appendix R. For the EDE and SWA systems above, the Appendix R separation requirements are satisfied.

g. Fire Zone PAB

-F-3A-Z (Tabulation 3.2.7.71)

1) Specific Zone Analysis This zone at Elevation 53

'-0" of the PAB is bounded by concrete floor, ceiling and walls (North, East and West) and is contiguous to fire zone PAB -F-3B-Z to the South. The southern boundary consists of a full height partition wall. There are penetrations for tray, ducts and pipes to other fire zones. The zone is approximately 53 ' long by 75 ' wide by 26 ' high with a floor area of 4000 sq. ft. and a volume of 103,400 cu. ft. Combustibles are limited to 1.0 gallon of oil for a fire loading of 150,000 Btu and cables in open trays for a total fire loading of 3000 Btu per sq. ft. of floor area. Detectors are provided throughout the zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-267 2) System Analyses a) Primary Component Cooling Water (CC) System Redundant transmitters and cables for head tank level logic are in proximity. Failures in these transmitters or cables could initiate a spurious lo -lo head tank level isolation signal. This in turn, would result in closure of the PCCW containment isolation valves. These valves are only required when it is necessary to maintain containment habitable for containment entry to manually operate the RHR isolation valves and the SI accumulator isolation valves. The circuitry for these valves is not affected by a fire in this area; hence they would be operable from the MCR. Therefore, the spurious operation of these transmitters will not prevent safe shutdown. b) Chemical and Volume Control (CS) System This zone contains cables routed in tray for the Train A valves CS-LCV-112B and CS-LCV-112D. The Train B cables are routed in barriered conduits in fire zone PAB-F-3B-Z. See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g. This zone contains cables for CS-FCV-110A, -111A, -110B, -111B. Spurious opening of these valves in conjunction with spurious start of boric acid transfer pump or reactor makeup water pump may divert boric acid from the reactor coolant system affecting cold shutdown reactivity control, or result in an unplanned dilution affecting hot standby and cold shutdown reactivity control. The operators isolate the diversion flow by closing

CS-FCV-110B & -111B using the main control board control switches. The operators isolate the dilution flow by closing CS -LCV-112C using the main control board control switch. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-268 c) Service Water (SW) System This zone contains Train A valves SW -V15 and SW -V16 and cables for Train A valve SW -V4. Also contained in this zone are the redundant Train B valves SW -V17 and SW-V18 and cables for valve SW -V5. Redundant valves SW -V15 and SW -V17 are in the Safe Shutdown position. In addition, the circuit breaker for SW-V17 is administratively controlled off so the valve cannot spuriously close. If SW -V15 spuriously closes, SW-V17 is still open to provide the Train B PCCW heat exchanger cooling function. For conservatism, the operators will prevent further spurious operation by tripping the SW -V15 power supply breaker in the Train A switchgear room (Fire Area: CB -F-1A-A). Redundant diesel generator jacket water heat exchanger valves SW -V16 and SW-V18 are normally closed and are required to open for operation of the diesel generators.

De-energizing the solenoids will open the valves. If SW-V16 or SW -V18 spuriously closes, SW to the respective train DG would be isolated. The other train DG

would still be available. Also, a fire in this area does not cause a loss -of-offsite power. To prevent further spurious operation, the operators will trip the valves ' power supply breakers in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The Train A cables for valve SW -V4 are routed in trays and conduit. The trays and conduit are a minimum of 10 ' above floor Elevation 53 '-0". The Train B cables for valve SW-V5 are routed in barriered conduits. The Train A and Train B raceways are separated by greater than 25 '. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-269 3) Summary For the CC system above, the safe shutdown requirements are satisfied. For the CS system above, the routing of the Train B cables in conduit with a one -hour, fire rated barrier in another fire zone and considering the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III G.2.c, "in addition to one (1) hour fire barrier, an automatic fire suppression system shall be installed ", has been approved. Also, the capability to isolate the boric acid diversion flow and the dilution flow using the main control board control switches satisfies the safe shutdown requirements. For the SW system above, the routing of the Train B cables in a conduit with a one -hour, fire -rated barrier; the spatial separation; the disabling capabilities in another fire area; and considering the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R, Paragraph III G.2.c, "in addition to one (1) hour fire barrier, an automatic fire suppression system shall be installed ", has bee n approved.

h. Fire Zone PAB

-F-3B-Z (Tabulation 3.2.7.72)

1) Specific Zone Analysis This zone at Elevation 53

'-0" of the PAB is bounded by concrete floor, ceiling and walls (South, East and West) and is contiguous to fire zone PAB -F-3A-Z to the North. The northern boundary consists of a full height partition wall. There are penetrations for ducts and pipes to other fire zones. The zone is approximately 88 ' long by 75 ' wide by 26 ' high with a floor area of 6500 sq. ft. and a volume of 168,200 cu. ft.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-270 Combustibles are limited to 71 pounds of plastic (fiberglass ladders) for a fire loading of 923,000 Btu, 0.5 gallon of oil for a fire loading of 75,000 Btu, 50 pounds of Class A material for a fire loading of 400,000 Btu for a total fire loading of 1602 Btu per sq. ft. of floor area. See "Fire Protection Program Evaluation and Comparison to Branch Technical Position APCSB 9.5 -1 Appendix A" for the analysis of 6600 lbs. of charcoal in CAP-F-40. Detectors are provided throughout the zone.

2) System Analysis a) Primary Component Cooling Water (CC) System Redundant transmitters and cables for head tank level logic are in proximity. Failures in these transmitters or cables could initiate a spurious lo

-lo head tank level isolation signal. This in turn would result in closure of the PCCW containment isolation valves. These valves are only required when it is necessary to maintain containment habitable for containment entry to manually operate the RHR isolation valves and the SI accumulator isolation valves. The circuitry for these valves is not affected by a fire in this area; hence, they would be operable from the MCR. Therefore, the spurious operation of these transmitters will not prevent safe shutdown. b) Chemical and Volume Control (CS) System The redundant volume control tank isolation valves

CS-LCV-112B and CS -LCV-112C are located in the same fire area. The valves are in separate concrete cells with concrete walls and a solid controlled access door between them. There are no in situ combustibles or cables in trays in the cells. The cables for the Train B valve CS-LCV-112C are routed in barriered conduits. See additional CS system discussion on CS -LCV-112B, CS-LCV-112C, CS-P-2A and CS -P-2B in the General Area Analysis, Section B.1.g.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-271 This zone contains cables for the redundant RWST suction valves CS -LCV-112D and CS -LCV-112E. These cables are part of a circuit that will automatically open the opposite train RWST valve if a VCT valve is not full open (i.e., spuriously closes). Since the VCT valves do not spuriously close for a fi re in this zone, the automatic open circuit is not required. The automatic open circuit is supplied from a separate circuit, i.e., not the RWST MOV control circuit, so failure of these cables does not affect the ability to manually open the RWST valves as part of transferring charging pump suction from the VCT to the RWST. This zone contains cables for

CS-FCV-110A, -111A, -110B, -111B. Spurious opening of these valves in conjunction with spurious start of a boric acid transfer pump or reactor makeup water pump may divert boric acid from the reactor coolant system affecting cold shutdown reactivity control, or result in an unplanned dilution affecting hot standby and cold shutdown reactivity control. The operators isolate the diversion flow by closing CS-FCV-110B & -111B using the main control board control switches. The operators isolate the dilution flow by closing CS -LCV-112C using their main control board control switch.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-272 3) Summary For the CC system above, the safe shutdown requirements are satisfied. For the CS system above, the routing of the Train B cables in a one-hour, fire -rated barrier; the separation between the valves; the absence of in situ combustibles in the cells; and considering the low combustibles loading in the zone, provide acceptable fire protection and provide protection equivalent to the technical requirements of Appendix R. A deviation from Appendix R Paragraph III G.2.c, "in addition to 1 hour fire barrier, an automatic fire suppression system shall be installed ", has been approved. Also, the capability to isolate the boric acid diversion flow and the dilution flow using the main control board control switches satisfies the safe shutdown requirements. C. Evaluation Deviations from the Appendix R, Paragraph III.G.2 separation requirements exist in the Primary Auxiliary Building fire zones PAB -F-1A-Z, PAB-F-1J-Z, PAB-F-1K-Z, PAB-F-2A-Z, PAB-F-2B-Z, PAB-F-2C-Z, PAB-F-3A-Z and PAB-F-3B-Z. These deviations are justified based on the above analyses and our assertion that additional modifications would not enhance fire protection safety.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-273 Tabulation 3.2.7.74 Primary Auxiliary Building Fire Area - PAB-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-P-2A x x CS-PS-7467-1 x x CS-V210 x CS-V221 x B. Analysis All equipment and cables are Train A. The redundant Train B equipment and cables are in Fire Area PAB -F-1D-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-274 Tabulation 3.2.7.75 Primary Auxiliary Building Fire Area - PAB-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-P-2B x x CS-PS-7468-1 x x CS-V219 x CS-V220 x B. Analysis All equipment and cables are Train B. The redundant Train A equipment and cables are in Fire Area PAB -F-1C-A, separated from this area by a 3 -hour fire wall. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-275 Tabulation 3.2.7.76 Primary Auxiliary Building Fire Area - PAB-F-1E-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-FCV-121 x CS-FI-121B x x CS-FT-121 x B. Analysis Cables and equipment necessary for operation of valve CS -FCV-121 are contained in this fire area. This valve is part of the seal injection flow path. The cables and equipment for valves SI -V-138 and SI -V-139 which are part of the functionally redundant high head injection path are not contained in this fire area; hence they will be available for hot standby. For cooldown, the operators will manually align the charging pump discharge and bypass valves (CS -V210, CS-V221 or CS -V219, CS-V220) to the seal injection flow path and throttle the bypass valves as required. C. Evaluation The safe shutdown requirements and the Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-276 Tabulation 3.2.7.77 Primary Auxiliary Building Fire Area - PAB-F-1G-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-LT-2172-1 x CC-LT-2192-1 x CC-LT-2172-2 x CC-LT-2192-2 x CC-LT-2172-3 x CC-LT-2192-3 x CC-LT-2272-1 x CC-LT-2292-1 x CC-LT-2272-2 x CC-LT-2292-2 x CC-LT-2272-3 x CC-LT-2292-3 x CC-P-11A x CC-P-11C x CC-TE-2171 x CC-TV-2171-1 x CC-TV-2171-2 x CC-V145 x CC-V272 x CC-V175 x CC-V257 x CC-V1101 x CC-V1109 x CS-FT-121 x CS-FCV-110A x CS-FCV-111A x CS-FCV-110B x CS-FCV-111B x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-277 Primary Auxiliary Building Fire Area - PAB-F-1G-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-FCV-121 x CS-HCV-182 x CS-LCV-112B x CS-LCV-112D x CS-LT-102 x CS-LT-106 x CS-P-2A x CS-P-2B (1) (1) CS-P-3A x CS-V142 x CS-V154 x CS-V158 x CS-V162 x CS-V166 x CS-V167 x CS-V196 x CS-V426 x CS-V460 x CS-V475 x CS-V461 x EAH-FN-5A x EAH-FN-31A x EDE-MCC-513 x PAH-DP-35A x PAH-DP-35B x PAH-DP-36A x PAH-DP-36B x PAH-DP-43A x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-278 Primary Auxiliary Building Fire Area - PAB-F-1G-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable PAH-DP-357 x PAH-FN-42A x (1) CS-P-2B and its cables are not actually located in this fire area. However, CS -P-2B is listed because it is potentially affected via a systems interaction. See Analysis Section B.18. RC-V23 x RC-V22 x RC-V88 x RC-V87 x RH-FCV-618 x RH-FCV-619 x RH-HCV-606 x RH-HCV-607 x RH-V14 x RH-V26 x RH-V35 x RH-V36 x RH-V70 x RH-V32 x SI-PT-937 x SI-PT-936 x SI-V138 x SW-FN-51A x SW-P-41A x SW-P-41C x SW-P-110A x SW-V4 x SW-V15 x SW-V16 x SW-V20 x SW-V34 x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-279 Primary Auxiliary Building Fire Area - PAB-F-1G-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-V54 x SW-V56 x SW-V74 x SW-V139 x SWA-DP-66 x SWA-FN-64 x SWA-FN-71 x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown cables. The redundant Train B safe shutdown cables are located in fire area DCT -F-3B-0 and other fire areas. The Appendix R separation requirements are satisfied.

2. PCCW Head Tank level Transmitters CC

-LT-2172-1, 2, 3; CC -LT-2272-1, 2, 3; CC-LT-2192-1, 2, 3, CC -LT-2292-1, 2, 3 Cables for the redundant head tank level transmitters are in proximity. Failures in these cables could initiate a spurious lo -lo-head tank level isolation signal. This in turn would result in closure of the PCCW containment isolation valves. These valves are only required when it is necessary to maintain containment habitable for containment entry to manually operate the RHR isolation valves and the SI accumulator isolation valves. The circuitry for these valves is not affected by a fire in this area; hence, they would be operable from the MCR. Therefore, the spurious operation of these transmitters will not prevent safe shutdown. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-280 3. Component Cooling Water Pumps CC -P-11A, CC-P-11C and Component Cooling Water Containment Isolation Valves CC -V175, CC-V257 A fire could cause loss of all PCCW to containment. It should be noted, however, that these valves are required to remain operable only for containment entry when manual operation of the safety injection isolation valves SI -V3, SI-V17, SI-V32 and SI-V47 and the reactor coolant - RHR isolation valves RC -V22, RC-V23, RC-V87 and RC -V88 are required. Cables for these valves are not routed through this fire area; hence, the valves would be operable from the main control room or the RSS control panels and containment entry would not be required. The safe shutdown requirements are satisfied.

4. RHR Heat Exchanger Outlet Valves CC

-V145, CC-V272 Cables for redundant valves CC -V145 and CC -V272 are routed in proximity to one another. The valves are normally open to their shutdown cooling position and their position is inconsequential until the plant is cooled down to 350F and the RH system is placed in operation. At that time, it is necessary to assure that the valve supplying PCCW to the operational RH train is opened. This can be accomplished manually if required in the appropriate equipment vault. Manual operation can be delayed as much as 9 hours into the event. Therefore, no fire protection other than the existing separation is needed. The provision of a capability to position the valve outside the fire area satisfies the safe shutdown requirements.

5. Charging Pump Discharge Valve CS

-FCV-121 This zone contains cables in tray required for operation of Train A valves

CS-FCV-121, which provides one of the required hot standby charging flow paths. The redundant Train B SI-V139 cables are located in Fire Area DCT-F-3B-0. For cooldown, the operators will manually align the Train B charging pump discharge and bypass valves (CS -V219 and CS -V220) to the seal injection flow path and throttle the bypass valve as required. This operator action can be delayed for up to of 4 hours. The Appendix R separation and safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-281 6. Boric Acid Tank Level Transmitter CS -LT-102, CS-LT-106 This zone contains cables routed in tray for the redundant boric acid tank level transmitters CS -LT-102 and CS -LT-106. These tank levels are only required once cooldown has been initiated. Should both transmitter cables be damaged by a fire, the operators can utilize the Train B level transmitter CS -LT-7464 whose cable is not routed through this fire area. The indicator for this transmitter is located at the RSS panel in the Train B switchgear room (Fire Area: CB -F-1B-A). The provision of a redundant transmitter with its cable routed in another fire area satisfies the safe shutdown requirements.

7. Seal Injection Isolation Valves CS

-V154, CS-V158, CS-V162 and CS -V166 Under normal conditions, the seal injection isolation valves CS -V154, CS-V158, CS-V162 and CS -V166 are utilized for the seal injection flow path. Spurious closure of one of these valves will not prevent safe shutdown. The operators will prevent further spurious operations by tripping the power supply breakers in the Train A switchgear room (Fire Area: CB -F-1A-A). The safe shutdown requirements are satisfied.

8. RC Pump Seal Water Isolation Valve CS

-V167 Valve CS-V167 is a normally open valve which should remain open for safe shutdown. Spurious isolation of this Train A valve could result in loss of RC inventory through the upstream relief valve. This inventory is directed to the PRT and is therefore, non -recoverable. To preclude this loss of inventory, functionally redundant isolation capability is provided by the RC pump seal return lines by means of Train A valves CS -V10, CS-V28, CS-V44, and CS -V59. The cables, controls and equipment required for operation of valves CS -V10, CS-V28, CS-V44, and CS -V59, are not contained in this fire area. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-282 9. BAT to Charging Pump Isolation Valve CS -V426 Valve CS-V426 is a normally closed valve which is opened to provide a path from the boric acid tanks to the charging pump suction. This path is required to begin cooldown. In the event that this valve is inoperable, the operators can provide a redundant path by manually positioning valves in the boric acid tank room (Fire Area: PAB -F-2B-Z). The operators can maintain the plant in hot standby for the time required to perform this manual action. The safe shutdown requirements are satisfied.

10. SI-CS Suction Cross Connection Valves CS

-V460, CS-V461, CS-V475 Valves CS -V460, CS-V461 and CS -V475 are located in proximity. Prior to beginning cooldown the normally closed CS -V460 and CS -V461 valves should remain closed or the functionally redundant valve CS -V475 should be closed. The isolation of this path will prevent loss of boric acid tank inventory to the RWST during cooldown. In the event of a spurious valve operation which renders this flow path open, the plant can be maintained in hot standby for as long as 4 hours. Should the operators desire to initiate the cooldown sooner than 4 hours, a gravity feed can be established from the boric acid tanks to the charging pumps. As the BAT head is lower than that required to return inventory to the RWST, there would be no loss of BAT inventory through this path and the position of these valves would be inconsequential. The safe shutdown requirements are satisfied.

11. Containment Enclosure Isolation Damper, PAH

-DP-35A, PAH-DP-36A, PAH-DP-35B, PAH-DP-36B Cables for outboard isolation dampers PAH -DP-35A and PAH -DP-36A and inboard isolation dampers PAH -DP-35B and PAH -DP-36B are routed in trays and conduits in proximity to one another. Under normal operation both outboard and both inboard dampers are open. If both outboard or both inboard dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. If the outboard dampers and the inboard dampers operate independently such that either the supply or the exhaust path but not both are isolated, there could be an air flow problem in EAH system. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-283 Outboard dampers are powered from a single Train A power supply. Inboard dampers are powered from a single Train B power supply. The circuit design for the outboard and inboard dampers is such that a spurious signal in either or both circuits will cause both outboard and inboard dampers to operate together, either both open (normal mode) or both closed (recirculation mode). The safe shutdown requirements are satisfied.

12. RHR Isolation Valves RC

-V22, RC-V23, RC-V87, RC-V88 Cables for redundant valves are located in proximity. As the RHR isolation valves are permanently disabled in the closed position, failures in the cables cannot cause a spurious operation. Valves RC -V87 and RC -V88 are required to be opened for cooldown below 350F when the RH system is placed in operation. Should the cable damage be such that the valves cannot be operated from the MCR, the affected portion of the circuit can be isolated at the RSS panels in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A) and the valves repositioned for safe shutdown. The safe shutdown requirements are satisfied.

13. RHR Heat Exchanger Outlet Flow Control and Bypass Flow Control Valves RH-FCV-618, RH-HCV-606, RH-FCV-619, RH-HCV-607 Cables for the redundant flow control valves are routed in proximity. The RH-HCV-606 and RH

-HCV-607 valves are normally closed and are required to open whereas the RH -FCV-618 and RH -FCV-619 are normally open and are required to close. These valves are only required to operate when the RH system is placed in operation (cold shutdown). The valves have air operators controlled by dc solenoids. These solenoids when deenergized vent the air from the operators and cause the valves to fail to their safe shutdown position. In the event this positioning cannot be performed in the MCR, the operators will position these valves by tripping the power supply breakers in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-284 14. RH Pump to Cold Leg Isolation Valves RH -V14, RH-V26 Cables for redundant valves RH -V14 and RH -V26 are routed in proximity. These valves are normally open valves which are required to remain open for RH systems operation (cold shutdown). If one of the valves spuriously closes, the operators will prevent further spurious operation of these valves by tripping the power supply breakers in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

15. RH Pump to Hot Leg Isolation Valves RH

-V70, RH-V32 Cables for redundant valves RH -V70 and RH -V32 are routed in proximity. These valves are normally closed valves which are required to remain closed for RH system operation (cold shutdown). If one of the valves spuriously opens, the operators will prevent further spurious operation of these valves by tripping the power supply breakers in the Train A and Train B switchgear rooms (Fire Areas: CB-F-1A-A and CB-F-1B-A). The safe shutdown requirements are satisfied.

16. RH Heat Exchanger to CS/SI Pump Isolation Valves RH-V35, RH-V36 Cables for the redundant valves RH

-V35 and RH -V36 are routed in proximity. Valves RH -V35 and RH -V36 are normally closed and their position is inconsequential until the plant is cooled down to 350F and the RH system is placed in operation. At that time it is necessary to assure that the valves remain closed. Should one of the valves open spuriously the operators can disable its power supply in either the Train A or Train B switchgear rooms (Fire Areas: CB-F-1A-A or CB-F-1B-A) and manually reposition the valves located in the equipment vaults (Fire Zone RHR -F-4B-Z or RHR-F-2A-Z). Manual operation of the valves can be delayed as much as 9 hours into the event. Therefore, no fire protection other than the existing separation is needed. The provision of a capability to mitigate the spurious operation of the valves outside the fire area satisfies the safe shutdown requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-285 17. Containment Pressure Transmitters SI -PT-936, SI-PT-937 Redundant channels of containment pressure cables are located in proximity. Spurious operation of these channels will initiate containment spray and containment isolation Phase B. The operators will have the capability to terminate these protective actions by use of manual reset switches. All ESF equipment which has been started will be tripped and locked out. To preclude further spurious operations, the operators will disable the engineered safety features logic cabinets in the Train A and Train B switchgear rooms (Fire Areas: CB-F-1A-A and CB-F-1B-A). The provision of a capability to mitigate the spurious operation of the pressure transmitters outside the fire area satisfies the safe shutdown requirements.

18. Volume Control Tank Isolation Valve CS

-LCV-112B and Charging Pump CS-P-2A & CS-P-2B Volume control tank (VCT) isolation valves CS -LCV-112B & -112C are normally open to provide a suction path from the VCT to the normally operating charging pump (CS -P-2A or -2B). These valves must stay open until RWST valve CS-LCV-112D or -112E is manually opened to provide a charging pump suction path from the RWST, or the boric acid tanks are manually aligned as a charging pump suction source. Spurious closure of a VCT isolation valve caused by a hot short would interrupt suction flow to the operating charging pump

causing it to be damaged. If the standby charging pump has cables in the same area then its operation can also be degraded. The result would be no charging system flow. Since this fire area contains cables for CS -LCV-112B and CS -P-2A, this condition is potentially applicable for the system alignment with CS -P-2A the standby pump and CS -P-2B the operating pump. The CS-LCV-112B circuit design prevents spurious valve closure from hot shorts as follows. The field cable conductors for the motor control center (MCC) contactor close coil circuit are in different cables than the 120 V "hot" circuit conductors eliminating the hot short failure mode within the cables. Cable-to-cable hot shorts need not be postulated for thermoset cable insulation as used at Seabrook. Since CS -LCV-112B will not spuriously close, CS -P-2B as the operating charging pump will not be damaged. Since charging flow is available, the safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-286 19. Boration/Dilution Flow Control Valves, CS -FCV-110A, -111A, -110B, -111B This area contains cables for CS -FCV-110A, -111A, -110B, -111B. Spurious opening of these valves in conjunction with spurious start of a boric acid transfer pump or reactor makeup water pump may divert boric acid from the reactor coolant system affecting cold shutdown reacivity control, or result in an unplanned dilution affecting hot standby and cold shutdown reactivity control. The operators isolate the diversion flow by closing CS -FCV-110B and -111B using the main control board control switches. The operators isolate the dilution flow by closing CS -LCV-112C using the main control broad switch. The safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-287 Tabulation 3.2.7.78 Primary Auxiliary Building - Stairwell (N) Fire Area - PAB-F-S1-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-288 Tabulation 3.2.7.79 Primary Auxiliary Building - Stairwell (S) Fire Area - PAB-F-S2-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-289 Tabulation 3.2.7.80 Equipment Vault - Train B (Vault #2) Fire Area - RHR-F-1A-Z, RHR-F-1C-Z, RHR-F-2A-Z, RHR-F-3A-Z, RHR-F-4A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-V272 x x CS-V461 x CS-V475 x RC-V22 x RC-V88 x RC-V87 x RH-E-9B x RH-HCV-607 x x RH-FCV-619 x x RH-P-8B x x RH-V26 x RH-V32 x RH-V35 x RH-V36 x x RH-V44 x SI-V89 x x SI-V89 x x B. Analysis 1. General Systems/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A safe shutdown equipment and cables are located in Train A Vault (Vault #1) (Fire Areas: RHR -F-1B-Z, RHR-F-1D-Z, RHR-F-2B-Z, RHR-F-3B-Z, RHR-F-4B-Z) or other fire areas. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-290 2. SI-CS Suction Cross Connection Valves CS -V461, CS-V475 Valves CS -V461 and CS-V475 are located in proximity. Prior to beginning cool down the normally closed valve CS -V461 should remain closed or the functionally redundant valve CS -V475 should be closed. The isolation of this path will prevent loss of boric acid tank inventory to the RWST during cooldown. In the event of a spurious valve operation, which renders this flow path open, the plant can be maintained in hot standby for as long as 4 hours. Should this area be inaccessible due to the fire or should the operators desire to initiate the cooldown sooner than 4 hours, a gravity feed can be established from the boric acid tanks to the charging pumps. As the BAT head is lower than that required to return inventory to the RWST, there would be no loss of BAT inventory through this path and the position of these valves would be inconsequential. The safe shutdown requirements are satisfied.

3. RHR Isolation Valves RC

-V22, RC-V87, RC-V88 Cables, for functionally redundant valves are located in proximity. As the RHR isolation valves are permanently disabled in the closed position, failures in the cables cannot cause a spurious operation. Valve RC -V22 is required to be opened for cool down below 350F when the RH System is placed in operation. Should the cable damage be such that the valve cannot be operated from the MCR, the affected portion of the circuit can be isolated at the RSS panel in the Train B switchgear room (Fire Area: CB -F-1B-A) and the valve repositioned for safe shutdown. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-291 4. RH Heat Exchanger to CS/SI Pump Isolation Valves RH -V35 and RH -V36 and SI Isolation Valve SI -V89 Cables for the redundant valves RH -V35 and RH -V36 are routed in proximity to one another. Valves RH -V35 and RH -V36 are normally closed and their position is inconsequential during all modes of plant operation with the exception of cooldown below 350F when the RH System is placed in operation. At that time, it is necessary to insure that the valves remain closed. Should valve RH -V35 open spuriously, the operators can disable its power supply in the Train A switchgear room (Fire Area: CB -F-1A-A) and manually reposition the valves located in the Equipment Vault - Train A (Vault #1) (Fire Zone: RHR -F-4B-Z). Manual operation of the valve can be delayed as much as 9 hours into the event. Therefore, no fire protection other than the existing separation is needed. The provision of a capability to mitigate the spurious operation of the valve outside the fire area satisfies the safe shutdown requirements. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-292 Tabulation 3.2.7.81 Equipment Vault - Train A (Vault #1) Fire Area - RHR-F-1B-Z, RHR-F-1D-Z, RHR-F-2B-Z, RHR-F-3B-Z, RHR-F-4B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CC-V145 x x CC-V1101 x CC-V1109 x CS-V142 x CS-V154 x CS-V162 x CS-V166 x CS-V167 x CS-V460 x x CS-V475 x x CS-V461 x x RC-V23 x RC-V22 x RC-V88 x RH-E-9A x RH-HCV-606 x x RH-FCV-618 x x RH-P-8A x x RH-V8 x RH-V14 x RH-V35 x x RH-V36 x RH-V70 x SI-V90 x x SI-V90 x x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-293 Equipment Vault - Train A (Vault #1) Fire Area - RHR-F-1B-Z, RHR-F-1D-Z, RHR-F-2B-Z, RHR-F-3B-Z, RHR-F-4B-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SI-V93 x x SI-V93 x x SI-V138 x MM-IR-14 x x B. ANALYSIS 1. General Systems/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown equipment and cables. The redundant Train B safe shutdown equipment and cables are located in equipment Vault Train B (Vault #2) (Fire Areas: RHR -F-1A-Z, RHR-F-1C-Z, RHR-F-2A-Z, RHR-F-3A-Z, RHR-F-4A-Z) or other fire areas. The Appendix R separation requirements are satisfied.

2. `Seal Injection Isolation Valves CS

-V154, CS-V162 and C S-V166 Under normal conditions, the seal injection isolation valves CS -V154, CS-V158, CS-V162 and CS -V166 are utilized for the seal injection flow path, spurious closure of one of these valves will not prevent safe shutdown. The operators will prevent further spurious operations by tripping the power supply breakers in the Train A switchgear room (Fire Area: CB -F-1A-A). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-294 3. RC Pump Seal Water Isolation Valve CS -V167 Valve CS-V167 is a normally open valve which should remain open for safe shutdown. Spurious isolation of this Train A valve could result in loss of RC inventory through the upstream relief valve. This inventory is directed to the PRT and is therefore, non -recoverable. To preclude this loss of inventory, functionally redundant isolation capability is provided by the RC pump seal return lines by means of Train A valves CS -V10, CS-V28, CS-V44, and CS -V59 and the excess letdown line by means of normally closed, fail closed valves CS -V175 or CS-V176. The cables, controls and equipment required for operation of valves CS-V10, CS-V28, CS-V44, CS-V59, CS-V175 and CS -V176 are not contained in this fire area. The Appendix R separation requirements are satisfied.

4. SI-CS Suction Cross Connection Valves CS

-V460, CS-V461, CS-V475 Valves CS -V460, CS-V461 and CS -V475 are located in proximity. Prior to beginning cooldown the normally closed CS -V460 and CS -V461 valves should remain closed or the functionally redundant valve CS -V475 should be closed. The isolation of this path will prevent loss of boric acid tank inventory to the RWST during cooldown. In the event of a spurious valve operation which renders this flow path open, the plant can be maintained in hot standby for as long as 4 hours. Should this area be inaccessible due to the fire or should the operators desire to initiate the cooldown sooner than 4 hours, a gravity feed can be established from the boric acid tanks to the charging pumps. As the BAT head is lower than that required to return inventory to the RWST, there would be no loss of BAT inventory through this path and the position of these valves would be inconsequential. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-295 5. RHR Isolation Valves RC -V22, RC-V23, RC-V88 Cables for redundant valves are located in proximity. As the RHR isolation valves are permanently disabled in the closed position, failures in the cables cannot cause a spurious operation. Valve RC -V88 is required to be opened for cooldown below 350F when the RH system is placed in operation. Should the cable damage be such that the valve cannot be operated from the MCR, the affected portion of the circuit can be isolated at the RSS panel in the Train A switchgear room (Fire Area: CB -F-1A-A) and the valve repositioned for safe shutdown. The safe shutdown requirements are satisfied.

6. RH Heat Exchanger to CS/SI Pump Isolation Valves RH

-V35, RH-V36 and SI Isolation Valves SI -V90, SI-V93 Cables for the redundant valves RH -V35 and RH -V36 are routed in proximity to one another. Valves RH -V35 and RH-V36 are normally closed and their position is inconsequential during all modes of plant operation with the exception of cooldown below 350F when the RH System is placed in operation. At that time, it is necessary to assure that valve RH -V36 remains closed. Should valve RH-V36 open spuriously, the operators can disable its power supply in the Train B switchgear room (Fire Area: CB -F-1B-A) and manually reposition the valve located in the equipment Vault Train B (Vault #2) (Fire Zone: RHR-F-2A-Z). Manual operation of the valve can be delayed as much as 9 hours into the event. Therefore, no fire protection other than the existing separation is needed. The provision of a capability to mitigate the spurious operation of the valves outside the fire area satisfies the safe shutdown requirements. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-296 Tabulation 3.2.7.82 Circulating Water Pump House Fire Area - SW-F-1A-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-297 Tabulation 3.2.7.83 Service Water Pump House Fire Area - SW-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-CP-248 x EDE-MCC-514 x x SW-P-41A x SW-P-41C x SW-PT-8272 x SW-PT-8273 x SW-PT-8274 x SW-V2 x SW-V22 x SWA-FN-40A x SWA-FN-40B x SWA-TSH-5614-1 x x SWA-TSH-5615-2 x x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train A safe shutdown equipment and cables. The redundant Train B equipment and cables are located in fire area SW -F-1C-A separated from this area by a 3 -hour fire wall.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-298 2. Service Water Pump House Electrical Room Fans SWA -FN-40A, SWA-FN-40B and Temperature Switches SWA -TSH-5614-1, SWA-TSH-5615-2 This area contains the electrical rooms ' supply fans SW -FN-40A and SW -FN-40B temperature switches whose failure could cause increase in temperature in the electrical rooms. This could result in the loss of electrical distribution equipment necessary for operation of both Train A and Train B service water equipment. In the event this occurs, the cooling towers will be utilized. This transfer can be initiated from the MCR manually or automatically with Train B tower actuation. The cables, controls and equipment required for operation of the cooling towers are not contained in the fire area. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-299 Tabulation 3.2.7.84 Service Water Pump House Fire Area - SW-F-1C-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-CP-249 x EDE-MCC-614 x x SW-P-41B x SW-P-41D x SW-PT-8282 x SW-PT-8283 x SW-PT-8284 x SW-V29 x SW-V31 x SWA-FN-40A x SWA-FN-40B x SWA-TSH-5614-2 x x SWA-TSH-5615-1 x x B. Analysis 1. General System/Equipment Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A equipment and cables are located in fire area SW -F-1B-A separated from this area by a 3 -hour fire wall.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-300 2. Service Water Pump House Electrical Room Fans SWA -FN-40A, SWA-FN-40B and Temperature Switches SWA -TSH-5614-2, SWA-TSH-5615-1 This area contains the electrical rooms ' supply fans SW -FN-40A and SW -FN-40B temperature switches whose failure could cause increase in temperature in the electrical rooms. This could result in the loss of electrical distribution equipment necessary for operation of both Train A and Train B service water equipment. In the event this occurs, the cooling towers will be utilized. This transfer can be initiated from the MCR manually or automatically with Train B tower actuation. The cables, controls and equipment required for operation of the cooling towers are not contained in the fire area. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-301 Tabulation 3.2.7.85 Service Water Pump House Fire Area - SW-F-1D-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SWA-FN-40A x x SWA-FN-40B x x B. Analysis Service water pump house electrical rooms ' fans SWA-FN-40A and SWA -FN-40B are in this fire area. They cool the SW electrical control rooms Train A and B. Loss of cooling would cause a heat up in these rooms which may damage electrical distribution equipment for both trains of the Service Water pumps. Loss of the normally operating service water pumps would cause a "TA" actuation signal to transfer the system to the cooling towers which are not affected by the fire. The transfer is not affected by the fire or by the loss o f cooling due to the fire. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-302 Tabulation 3.2.7.86 Service Water Pump House Fire Area - SW-F-1E-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable EDE-CP-248 x EDE-CP-249 x MM-IR-73 x x MM-IR-73 x x SW-P-41A x x SW-P-41B x x SW-P-41C x x SW-P-41D x x SW-PT-8272 x x SW-PT-8282 x x SW-PT-8273 x x SW-PT-8283 x x SW-PT-8274 x x SW-PT-8284 x x SW-V2 x x SW-V29 x x SW-V22 x x SW-V31 x x B. Analysis A fire in this zone could affect all four service water pumps and their associated discharge valves. Two of the four pumps would normally be operating. A fire in this area will not affect the operability of the cooling tower and its associated fans, pumps and valves for utilization in satisfying safe shutdown. Transfer to the cooling towers will be either automatic by a "TA" actuation generated by low discharge service water pump pressure or by manual actuation from the Main Control Room. Automatic transfer is actuated by SW-PT-8272, 8273, 8274, 8282, 8283, 8284 which are in this fire zone. Loss of the pressure transmitters or their associated instrument racks due to fire will also cause transfer. C. Evaluation The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-303 Tabulation 3.2.7.87 Intake And Discharge Structure Fire Area - SW-F-2-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable SW-V44 x SW-V63 x B. Analysis Valves SW -V44, SW-V63 are normally open valves which should remain open for safe shutdown. The valves are permanently disabled in the open position. C. Evaluation The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-304 Tabulation 3.2.7.88 Turbine Building Fire Area - TB-F-1A-Z, TB-F-1C-Z, TB-F-2-Z, TB-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CBA-DP-24A x CBA-DP-24B x CBA-DP-24C x CO-LT-4096 x ED-B-2A x ED-B-2B x ED-BC-2A x x ED-BC-2B x x ED-I-4 x ED-PP-121B x ED-PP-122A x x ED-PP-122B x ED-SWG-12A x x ED-SWG-12B x x EDE-MCC-523 x x EDE-SWG-5 x EDE-SWG-6 x FP-CP-558 x x FW-P-113 x x FW-P-161 x x FW-V163 x x IA-SKD-18A x IA-SKD-18B x SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-305 Turbine Building Fire Area - TB-F-1A-Z, TB-F-1C-Z, TB-F-2-Z, TB-F-3-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable MM-IR-33A x x SA-V92 x x SA-V93 x x SA-TK-23A x SA-TK-23B x SA-SKD-137A x x SA-SKD-137B x x SY-CP-84 x x SY-CP-84 x x SY-CP-85 x x SY-CP-85 x x SY-CP-86 x x SY-CP-86 x x SCC-FV-7050 x x SCC-FV-7050 x x SY-CP-87 x x SY-CP-87 x x SCC-FV-7050A-1 x x SCC-FV-7050A-1 x x SCC-FV-7050A-2 x x SCC-FV-7050A-2 x x SCC-PCV-7035 x B. Analysis 1. Control Building Air Handling (CBA) System Dampers CBA -DP-24A, B, C and Fire Protection Panel FP -CP-558 All equipment and cables are Train A, the redundant Train B equipment are located in fire area CB -F-2B-A, separated from this area by a 3 -hour fire wall. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-306 2. Condensate Storage Tank (CST) Level Transmitter CO -LT-4096 Cables for CO -LT-4096 and its instrument bus (ED -I-4) are located in this fire area. Redundant cable and equipment is located in the EFW Pump House (fire area EFW-F-l-A). The Appendix R separation requirements are satisfied.

3. Battery Chargers ED

-BC-2A & ED-BC-2B, Batteries ED -B-2A & ED-B-2B, Switchgear ED -SWG-12A & ED-SWG-12B, and Power Panels ED -PP-121B & ED-PP-122A Loss of these buses could cause loss of RC Pump Control Power. The operator will manually trip the switchgear in the non -essential switchgear room (Fire Area: NES-F-1A-Z). Pressurizer heaters C, D and control group control power could be lost. If the heaters require tripping, an operator will manually trip them in the Train A switchgear room (Fire Area: CB -F-1A-A). Alternatively, the operator can reduce pressure by operating a PORV. Redundant heaters are available with control power from the emergency DC buses. The safe shutdown requirements are satisfied.

4. Electrical Distribution Emergency (EDE) System (4160 Swgr. E5, E6; Control Panels SY

-CP-84, 85, 86, 87, and 460V MCC E523) Redundant equipment and cables for the 4160 switchgear are located in the same fire area. A short circuit in this equipment or cables can cause a trip of the 4160V emergency switchgear E5 and E6 incoming line breakers from the UAT and RAT, resulting in loss of the offsite power supply. Loss of the offsite power supply will require starting of the diesel generators. The emergency buses will be powered from the diesel generators. This is the design base for safe shutdown. The safe shutdown requirements are satisfied. For the 460V MCC 's all equipment and cables are Train A, the functionally redundant Train B cables and equipment are located in fire area CB -F-1B-A, separated from this area by a 3 -hour fire wall. The Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-307 5. Instrument Air (IA) System Redundant equipment and cables for instrument air dryers are located in the same fire area. Dryers IA -SKD-18A and IA -SKD-18B provide instrument air for the primary component cooling water system containment isolation valves, Train A and Train B switchgear room dampers CBA -DP-24A, B, C, D, E, F, and MCR dampers CBA-DP-26A and CBA-DP-26B. Component cooling water to containment is required to maintain containment habitability. For a fire in this area, containment entry is not required as operators have the capability to operate safety injection accumulator isolation valves SI -V3, SI-V17, SI-V32 and SI -V47 and RHR isolation valves RC -V22, RC-V23, RC-V87 and RC -V88 from the main control room (Fire Area: CB-F-3A-A) or the RSS control panels (Fire Areas: CB -F-1A-A and CB-F-1B-A), separated from this area by a 3 -hour fire wall. The operators have the capability to manually position the Main Control Room air conditioning condenser units face and bypass dampers in the Diesel Generator Building HVAC equipment area (Fire Areas DG -F-3A-Z & DG-F-3B-Z). As these dampers fail "as is", this action would only be required to maintain long term habitability required by 9 hours into the event. Therefore, the air dryers are not required for safe shutdown for a fire in this area. The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-308 6. Service Air (SA) System Redundant equipment and cables for the service air system and secondary component cooling system with its tie -in to the fire protection system are located in the same fire area. Compressor skids SA -SKD-137A and SA -SKD-137B and their associated equipment provide instrument air for the primary component cooling water system containment isolation valves, and MCR dampers CBA -DP-26A and CBA-DP-26B. Component cooling water to containment is required to maintain containment habitability. For a fire in this area, containment entry is not required as operators have the capability to operate safety injection accumulator isolation valves

SI-V3, SI-V17, SI-V32 and SI -V47 and RHR isolation valves RC -V22, RC-V23, RC-V87 and RC -V88 from the main control room (Fire Areas: CB -F-3A-A) or the RSS control panels (Fire Areas: CB -F-1A-A and CB-F-1B-A), separated from this area by a 3 -hour fire wall. The operators have the capability to manually position the MCR dampers in the Control Room HVAC Room (Fire Area: CB -F-3B-A), separated from this area by a 3 -hour fire wall. The operators have the capability to manually position the switchgear room dampers in the control building mechanical equipment rooms (Fire Areas: CB -F-2B-A and CB-F-2C-A). As the Train A and Train B switchgear room intake and recirculation dampers fail "as is" and the exhaust damper fails open, this action would only be required to maintain long term habitability required by 9 hours into the event. Therefore, the SA system is not required for safe shutdown for a fire in this area. The safe shutdown requirements are satisfied. C. Evaluation The safe shutdown requirements and Appendix R separation requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-309 Tabulation 3.2.7.89 Turbine Building Fire Area - TB-F-1B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable ED-B-2A x x ED-B-2B x x B. Analysis Fire in this area will cause loss of DC power Bus ED -SWG-12B. Loss of this bus will cause loss of CST level instrumentation CO -LT-4096. Redundant equipment is located in fire area EFW -F-1A. Also RC pump switchgear control power is lost. When the RCP 's are required to be tripped (during cooldown) the operator will manually trip them in the non -essential switchgear room (Fire Area: NES -F-1A-Z). Pressurizer Heaters C, D, and control group control power will be lost. An operator, if the heaters require tripping, will do so in the Train A switchgear room (Fire Area: CB -F-1A-A). Alternatively, the operator can reduce pressure by operating a PORV. Redundant heaters are available with control power from the emergency DC bus. C. Evaluation The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-310 Tabulation 3.2.7.90 Tank Farm Fire Area - T-F-1-0 A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable CS-LCV-112B x CS-LCV-112C x CS-LCV-112D x x CS-LCV-112E x x B. Analysis Redundant valves CS -LCV-112D and CS -LCV-112E are located in the same fire area. The cables for VCT isolation valves CS -LCV-112B and CS -LCV-112C, are also located in this fire area. These are normally open valves. A fire in this area will prevent opening the normally closed RWST to charging pump isolation valves from the control room. The normally open VCT isolation valves may experience a loss of control power but can not spuriously close as described below. A fire in this area does not affect the normal charging, letdown, and boric acid makeup functions so safe shutdown can be achieved and maintained using a charging pump aligned to the VCT through CS -LCV-112 B & -112C. The RWST is not needed for this normal shutdown so the inability to open CS -LCV-112D & -112E does not affect safe shutdown. If there was a need to use the RWST, the RWST valves could be manually opened, and the VCT isolation valves could be closed from the RSS panels or manually closed. Volume control tank (VCT) isolation valves CS -LCV-112B & -112C are normally open to provide a suction path from the VCT to the normally operating charging pump (CS-P-2A or -2B). These valves must stay open to provide a charging pump suction path from the VCT. Spurious closure of a VCT isolation valve caused by a hot short would interrupt suction flow to the operating charging pump causing it to be damaged. If the standby charging pump has cables in the same area then its operation can also be degraded. The result would be no charging system flow. Since this fire area does not contain cables for CS -P-2A or CS-P-2B, this condition is not applicable to this fire zone.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-311 Furthermore, the CS -LCV-112B and -112C circuit design prevents spurious valve closure from hot shorts as follows. The field cable conductors for the motor control center (MCC) contactor close coil circuit are in different cables from the 120 V "hot" circuit conductors eliminating the hot short failure mode within the cables. Cable -to-cable hot shorts need not be postulated for thermoset cable insulation as used at Seabrook. Since

CS-LCV-112B and -112C will not spuriously close, CS-P-2A or -2B as the operating charging pump will not be damaged. C. Evaluation The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 13 Section 3.2 Page 3.2-312 Tabulation 3.2.7.91 Waste Building Fire Area - W-F-1A-Z, W-F-1B-Z, W-F-1K-Z, W-F-2A-Z, W-F-2B-Z, W-F-2C-Z, W-F-2D-Z, W-F-2E-Z A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis There are no safe shutdown cables or equipment in this fire area. C. Evaluation The Appendix R separation requirements do not apply to this fire area.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-1 3.3 ALTERNATIVE SAFE SHUTDOWN USING REMOTE SAFE SHUTDOWN FACILITIES 3.3.1 General Remote safe shutdown (RSS) is a design feature which allows plant shutdown from locations other than the main control room in the event of a fire or other condition which requires evacuation of the main control room. The fire areas of concern are the main control room, control room HVAC room, and the cable spreading room. Remote safe shutdown contains the necessary complement of systems and equipment required to satisfy the performance goals delineated in Appendix R, Paragraph III.L.2. Technical Specification (T/S) 3/4.3.3.5 requires surveillance testing of selected equipment used for safe shutdown from outside the Control Room at Remote Safe Shutdown (RSS) locations. The required equipment is listed in Table 3.3 -9. The selection criteria for the Transfer Switch/Control Circuit portion of the table is the primary equipment which has remote/local selector switches and is required to perform the reactor coolant system inventory and pressure control, reactivity control, and decay heat removal functions to achieve and maintain hot standby. For Appendix R shutdown, only one train of equipment (safety or non -safety related) is required; redundancy is not a requirement. Seabrook is a hot standby safe shutdown design basis plant (see UFSAR Section 5.4.7.2.i). Support equipment, and equipment required only to achieve and maintain cold shutdown, are not required to be included in the T/S table. Process monitoring instruments also have surveillance requirements. 3.3.2 Safe Shutdown Control Locations Normally safe shutdown will be accomplished from the main control room, utilizing the safe shutdown equipment along with other equipment which may be available to the operators. Upon detection of a fire, the fire brigade will be dispatched to the affected area and a determination will be made as to the severity of the fire. If it is determined that the fire has a potential for impacting safe shutdown from the main control room, the operators will proceed with a planned evacuation of the main control room and manning of the Train B remote safe shutdown control panel (MM-CP-108B) and man the following remote safe shutdown (RSS) facilities as necessary:

a. Train B Switchgear Room (Switchgear E6, and various Unit Substations, Motor Control Centers (MCC) and Distribution Panels) and RSS Aux Panel in Electrical Tunnel B. b. Train A Switchgear Room (MM

-CP-108A, Switchgear E5, and various Unit Substations, Motor Control Centers (MCC), and Distribution Panels) and RSS Aux Panel in Electrical Tunnel A . SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-2 c. Diesel Generator Room A

d. Diesel Generator Room B
e. Primary Auxiliary Building El. 53

'-0" Primary Component Coolant Water Heat Exchanger Area

f. Primary Auxiliary Building El. 25

'-0" Boric Acid Tank Area

g. Primary Auxiliary Building El. 7

'-0" Train B Charging Pump Room

h. Control Building Mechanical Equipment Rooms

- El. 50'-0" i. Equipment Vault - Train B (Vault #2)

j. Condensate Storage Tank
k. Non-Essential Switchgear Room The term "prompt action

" refers to an action taken after receipt of a valid fire alarm in the main control room. The term "expeditious action " or "expeditiously " refers to an action taken quickly upon entry into the applicable safe shutdown procedure. These type actions are considered to be completed prior to a spurious operation of the equipment operated by the prompt and expeditious actions. Therefore, no associated timing calculation is required for these actions. 3.3.3 Safe Shutdown Functions for Hot Standby The following are equipment necessary for Hot Standby:

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-3 3.3.3.1 Reactor Coolant (RC) Inventory and Pressure Control To compensate for miscellaneous RC system leakage, RC pump seal leakage and cooldown volume shrink, portions of the chemical and volume control (CS) system including centrifugal charging pumps, boric acid transfer pumps, and a borated water supply, either the refueling water storage tank (RWST) or the boric acid tanks (BAT) are used. The injection path to the RC system will be either through the seal injection flow path or the high head injection flow path. The preferred seal injection path requires that a flow control valve (CS -FCV-121) and that a minimum of two of the four seal injection valves (CS -V154, CS-V158, CS-V162 or CS -V166) be operable. Additionally, the normal charging flow to the RC system is isolated. This can be accomplished by temporarily stopping a charging pump to prevent overfill of the pressurizer. It can also be accomplished by use of any one of two functionally redundant but non -credited valves (CS -V142 or CS -V143). Should the seal injection path not be operable e.g., due to spurious closure of a flowpath valve (CS-FCV-121), the high head injection flow path (SI -V138 or SI -V139) can be utilized initially to maintain hot standby by batch charging from the RWST to maintain pressurizer level. During cooldown as RC system pressure decreases, it is necessary to provide a flow restricted path to prevent charging pump cavitation. This is due to the limited flow capability from the BAT. If the high head injection path cannot be isolated at this time and/or if the flow controlled path through CS -FCV-121 is not operable, a capability is provided to manually align and throttle the charging pumps to the seal injection flow paths. The necessary operator actions and valve alignments are unique for each fire area where these flow paths are affected and are described in the analysis for each area. RC pump seal cooling is provided by a redundant thermal barrier cooling system. Should the redundant thermal barrier system not be available, the seals will be cooled by the seal injection capability. A control room or cable spreading room fire can result in a temporary loss of all cooling to the RCP seals. The operator action to accomplish restoration of cooling to the seals is to restore power to an emergency bus, restart of a thermal barrier cooling pump and a CC water pump. Then, a charging pump and SW pump are started for long term seal cooling via seal cooling, as well as inventory control. The operator action to restore RCP seal cooling is accomplished prior to the time that there would be potential damage to the seals. The reactor coolant pumps (RCPs) are stopped from the main control board prior to evacuating the main control room. Circuit analysis shows that the RCPs can not spuriously restart due to fire -induced cable damage. The RC system pressure is controlled by use of a portion of the RC system which includes the pressurizer heaters (Group A and B) to increase pressure and the pressurizer power operated relief

valves (PORV) which depressurize the RC system by discharging reactor coolant fluid to the pressurizer relief tank (PRT).

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-4 Considering worst case scenarios for spurious actuation of affected equipment, the required times for operator actions regarding RC inventory and pressure control for safe shutdown from the remote safe shutdown facilities are provided below: Action Time Close PORV block valve Prompt Open the RWST outlet valves Prompt Place the standby charging pump in pull -to-lock Prompt Restore RCP seal cooling 9.9 to 19.8 minutes, depending on the highest RCP seal rate Trip RCPs 10 minutes Restore cooling to charging pump oil cooler

9.6 minutes

Isolate letdown 15 minutes Swap charging pump suction from VCT to RWST 15.4 minutes. Should SI -V138, SI-V139, or CS -HCV-182 spuriously open, this action must be completed no later than 5.0 minutes following letdown line isolation. Restore SW to emergency diesel generators 17.6 minutes Open a PORV to reduce pressurizer pressure in the event of spurious pressurizer heater operation or trip pressurizer heaters 23 minutes Start a charging pump, or open a high head safety injection valve SI -V-138 or SI -V-139 if normal charging pump path is not available 31.1 minutes Isolate charging flow, except for seal injection 35.4 minutes Trip spuriously operating containment building spray pumps 46 minutes Trip spuriously operating SI pump

<4 hours, prior to commencement of plant cooldown

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-5 Action Time Isolate the potential diversion path from the BAT to the RWST or align BAT for gravity feed.

<4 hours, prior to commencement of plant cooldown Align BAT for makeup source
<4 hours, prior to commencement of plant cooldown 3.3.3.2  Reactivity Control Reactivity for hot standby at normal operating temperature (NOT) is provided by insertion of the control rods. Reactivity conditions required for cooldown and maintaining cold shutdown are provided by a portion of the chemical and volume control (CS) system which includes a centrifugal charging pump taking suction from the BAT

's. During cooldown, the borated source must be the BAT volume until expended to at least the point that the volume injected or a boron sample demonstrates that sufficient shutdown margin for cold shutdown has been achieved, at which time the RWST would be aligned. The credited path for boration is gravity feed with the RWSP isolated. The boric acid transfer pumps can be used if available. Considering worst case scenarios for spurious actuation of affected equipment, the required times for operator actions regarding reactivity control for safe shutdown from the remote safe shutdown facilities are provided below: Action Time Trip the Reactor Expeditiously Provide borated water from the BATs, via boric acid transfer pump or gravity feed.

<4 hours, prior to commencement of plant cooldown Isolate boric acid flow diversion path.
<4 hours, prior to commencement of plant cooldown

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-6 3.3.3.3 Decay Heat Removal The reactor coolant (RC) system temperature is controlled by use of portions of the feedwater (FW) system and the main steam (MS) system. The main steam safety/relief valves will maintain a heat dump capability. The steam generator water inventory is controlled by operating the motor driven emergency feedwater pump and associated emergency feedwater control valves. Inventory for the emergency feedwater is from the condensate storage tank. Long term water capability exists using a temporary connection between the suction of the emergency feed pumps and the fire protection system but is not required to meet Appendix R requirements. To assure main steam system integrity the MSIV 's and MSIV bypass are maintained closed. The MSIV bypass valves are normally locked closed and depowered with breakers locked open to preclude spurious opening. Decay heat transfer is made possible by natural convection flow in the RC System. Considering worst case scenarios for spurious actuation of affected equipment, the required times for operator actions regarding decay heat removal for safe shutdown from the remote safe shutdown facilities are provided below: Action Time Isolate MSIVs Expeditiously following a reactor trip Place the mode selector switches for the ASDVs to the closed position Prompt Gain Control of excessive Emergency Feedwater Flow 20 minutes Start motor driven EFW pump to preclude steam generator dry out 39 minutes Time allotted for operator actions to preclude emptying CO tank to accommodate RHR Cut -in, and ultimately achieve cold safe shutdown within 72 hours 9 hours; 4 hours at hot standby plus

5 hours cooldown to RHR Cut -in 3.3.3.4 Process Monitoring Instrumentation is provided at the Train B remote safe shutdown control panel for monitoring the following process variables:

a. Steam generator emergency feedwater flow
b. Reactor coolant loop hot and cold leg temperatures

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-7 c. Steam generator wide -range level

d. Steam generator pressure
e. Pressurizer level
f. Pressurizer pressure
g. Wide-range neutron monitoring (excore)
h. Primary component cooling water temperature
i. Boric acid tank level
j. Condensate storage tank level (local)

Instrumentation is also provided at the Train A remote safe shutdown control panel for monitoring the following process variables:

a. Steam generator emergency feedwater flow
b. Steam generator wide-range level Note that other instrumentation is provided at the Train A remote safe shutdown control panel but is not credited for Appendix R fire safe shutdown.

3.3.3.5 Service Water The service water system will supply cooling water to the primary component cooling water system, diesel generators, and if required, fire protection system. Service water supply will be from the service water pumps taking suction from the tunnels to the ocean. Section 3.3.3.1 provides the required times for operator actions, based on worst case scenarios for spurious actuation. 3.3.3.6 Primary Component Cooling Water (CC) The CC system is utilized to maintain cooling water to the charging pumps, RH pumps, RH heat exchangers, and reactor coolant pumps (RCP) thermal barrier heat exchanger. The PCCW pumps, temperature control valves, and RCP thermal barrier cooling pumps are necessary for system operations. Section 3.3.3.1 provides the required times for operator actions, based on worst case scenarios for spurious actuation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-8 3.3.3.7 Sampling Sampling of the reactor coolant system is not required at hot standby and cold shutdown conditions since make -up during cool -down will only be provided to the RCS from the boric acid tanks (two) which are maintained at 4 wt% boric acid. During all phases of cool -down, the core will be maintained to the shutdown margin greater than or equal to the limit specified in the Core Operating Limits Report (COLR). 3.3.3.8 Diesel-Generator Building Air Handling (DAH) The DAH system is utilized to maintain long -term habitability and equipment protection for the diesel-generator rooms. The DAH system includes the fans and dampers for air handling in these areas. 3.3.3.9 Containment Enclosure Air Handling (EAH) The EAH system is utilized to maintain long-term habitability of the mechanical penetration area, and provide equipment cooling in the charging pump rooms, and the hydrogen analyzer and electrical room. The EAH system includes the coolers, fans, and dampers required for air handling in these areas. 3.3.3.10 Emergency Feedwater Pumphouse Air Handling (EPA) The EPA system is utilized to maintain long -term habitability and equipment protection in the emergency feedwater pump building. The EPA system includes the fans and dampers required for air handling in this area. 3.3.3.11 Primary Auxiliary Building Air Handling (PAH) Portions of the PAH system are utilized to maintain long -term habitability and equipment protection in the PCCW area of the primary auxiliary building. The PAH system includes the fans and dampers required for ventilation in this area. 3.3.3.12 Service Water Air Handling (SWA) Portions of the SWA system are utilized for equipment protection in the SW pump house electrical control rooms. The SWA system includes the fans and dampers required for air handling in these areas. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-9 3.3.3.13 Electrical Distribution Emergency (EDE) Portions of the EDE system are required to power the various pumps, fans, valves, etc. required for safe shutdown. Included in the EDE system are the 4160 Volt ac emergency switchgear, 460 Volt ac emergency unit substations and motor control centers, the uninterruptible power supplies, 120 Volt ac vital distribution panels, 125 Volt dc batteries, battery chargers, and 125 Volt dc distribution panels. 3.3.3.14 Diesel-Generators (DG) The diesel -generators provide power to the electrical distribution emergency system upon loss of off-site power. The DG system includes the diesel, generators, control panels, engine -driven auxiliaries, fuel oil transfer pumps, starting air compressors and backup operating air compressors. 3.3.3.15 Safeguard Actuation System The safeguard actuation system could be actuated. A portion of this system is used to deactivate the system for recovery. 3.3.3.16 Communication The Gaitronics or radio systems are used to announce the fire event, dispatch the fire brigade, and to dispatch an NSO to perform local actions in the emergency diesel generator rooms. The Gaitronics system is also used to provide a fire alarm. Face -to-face communications is used to dispatch a control room operator (CRO) to the Train B switchgear room to perform local actions. A sound powered telephone loop (SPC) is provided for the CRO and NSO to communicate between the switchgear and the diesel generator rooms. Headsets or handsets are stored at these RSS locations for operator use. All actions required to achieve and maintain hot standby are taken in these areas. When field actions are required to commence cooldown, and achieve and maintain cold shutdown, an operator would: a) be dispatched to take the required action, b) go to the field and take the action, and c) then return and report the action completed. The RSS SPC loop also includes two SPC jacks in the RHR equipment vaults. Radios and Gaitronics are not credited but would be used as additional means of communications, if not damaged by the fire. 3.3.4 Safe Shutdown Functions for Cooldown The following equipment in addition to that which is listed in Section 3.3.3 are necessary for cooldown.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-10 3.3.4.1 Decay Heat Removal In addition to equipment discussed in Section 3.3.3.3, the steam generator atmospheric relief valves will be used for cooldown until the residual heat removal (RH) system can be used. The residual heat removal system will be the long term heat sink at the end of cooldown. An RH pump will be operated along with various control, manual and motor operated valves. 3.3.4.2 Sample System For cold shutdown, the operators will draw a manual sample from RH system to verify boron concentration before li ne-up to RCS. The operator will use manual valves in RH system. 3.3.5 Initial Operator Actions Remote safe shutdown procedures will require that prior to main control room evacuation the reactor, the main steam isolation valves, and the reactor coolant pumps be tripped, thus establishing a hot standby condition. Closure of the pressurizer PORV 's block valves, placing the switches for the ASDVs to the closed position, placing the standby centrifugal charging pump in pull -to-lock, and opening the RWST outlet valves to the charging pump suction will be accomplished from the main control board after alarm confirmation (promptly) to prevent over cooling situations from either the primary or secondary side of the plant and ensuring proper RCS inventory control. Additionally, capabilities to trip the four MSIV 'S, the four RCP 's and the pressurizer PORV 's and atmospheric relief valves exist outside the main control room. After a confirmed fire alarm for a main control room or cable spreading room fire, a control room operator (CRO) and nuclear systems operator (NSO) are dispatched to the Train B switchgear and emergency diesel generator rooms to take actions as directed by procedure. In the time interval required for the operators to evacuate the main control room and man the RSS facilities, decay heat removal is accomplished automatically by the steam generator safety valves. No other function is required initially to maintain a decay heat sink for the reactor. Upon arrival at the RSS facilities, the operators will transfer control capability to the RSS facility by means of "Remote-Local" selector switches at the RSS locations and take the actions necessary to maintain control of the RCS inventory and pressure, and decay heat removal functions within the time frames described in sections 3.3.3.1 and 3.3.3.3. Control of the Train B Diesel Generator will be taken and if a Loss of Offsite Power (LOOP) occurs, clear and load EDE -SWG-6 to support safe shutdown. The operators will also trip the power supplies for engineered safety features actuation system (ESFAS) logic and cooling tower actuation logic to prevent inadvertent activation of these functions. The operators will then disable (trip power supply breakers) all equipment which is properly positioned in its safe shutdown position. Any additional recovery actions needed to maintain hot standby or to start a cooldown will be completed if inadvertent safeguard operation, tower actuation or "HOT SHORT " actuation occurs.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-11 3.3.6 Manual Operator Actions The following equipment may require manual operation:

1. Mechanical room dampers CBA

-DP-24A, CBA-DP-24B, CBA-DP-24C, CBA-DP-24D, CBA-DP-24E and CBA -DP-24F. 2. Component cooling water valves CC -V145 and CC -V272. 3. Charging pump discharge and bypass valves CS -V210, CS-V219, CS-V220 and CS-V221. 4. RHR sampling valves RH -V8 and RH -V44. 5. Boric acid tank gravity feed valves CS -V410, CS-V416, CS-V437, CS-V439, CS-V442, and CS -V1207. The cables for valves CC -V145 and CC -V272 are not included in the review. Equipment CBA-DP-24D, CBA-DP-24E, CBA-DP-24F, CS-V210, CS-V219, CS-V220, CS-V221, CS-V410, CS-V416, CS-V437, CS-V439, CS-V442, CS-V1207, RH -V8, and RH -V44, are not electrically operated; hence, they have no cables. 3.3.7 Disabled (tripped power supply) Equipment The following equipment will be disabled:

a. Containment spray pumps CBS

-P-9A and CBS -P-9B b. Primary component cooling valves CC -V1092, CC -V1095, CC -V1101 and CC-V1109. c. Chemical and volume control valves CS -V154, CS-V158, CS-V162, CS-V166, CS-V167, CS-V168, CS-V175, CS-V176, CS-V196, CS-V197, CS-V460, CS-V461, CS-FCV-110A, -111A, -110B, -111B. d. Not used.

e. Main steam atmospheric relief valves MS

-PV-3001, MS-PV-3003 (Train B power supply) and MS -PV-3002, MS-PV-3004 (Train A power supply).

f. Not Used.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-12 g. Reactor coolant valves RC -V323, RC-FV-2881, RC-LCV-459* and RC-LCV-460* h. Pressurizer heaters Group C, Group D and Control Group

i. Residual heat removal valves RH

-V14, RH-V26, RH-V32, RH-V35, RH-V36, RH-V70, RH-HCV-606, RH-HCV-607, RH-FCV-618, and RH -FCV-619 j. Steam generator blowdown valves SB -V9*, SB-V10*, SB-V11* and SB -V12* k. Safety injection valves SI -V158 and SI -V159 l. Safety injection pumps SI -P-6A and SI -P-6B m. Service water valves SW -V15, SW-V16*, SW-V18*, SW-V20, SW-V23, and SW-V34. n. Engineered safety features -actuation system logic cabinets

o. Tower actuation logics The valves noted with an asterisk (*) fail to their safe shutdown position upon de

-energization. 3.3.8 Safe Shutdown Equipment List Tables that list all equipment, including instrumentation and vital support systems equipment required to achieve hot standby or cold shutdown using the RSS facilities are provided in Appendix III. However, analysis can be also provided to justify not listing components and cables in Appendix III. The tables provide the following requested information for each equipment listed: a) A column which notes whether the equipment is required for hot standby or cold shutdown. b) A column which defines each equipment 's location by fire zone/area. c) A column which defines each equipment 's redundant counterpart. d) A column which lists each equipment 's essential cabling. e) The table also delineates the following additional information:

1) P & I Diagram Drawing No.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-13 2) Physical Location Drawing No.

3) Power Supply 4) Electrical Node Number
5) Supporting Control and Instrumentation Equipment
6) Electrical Schematic Drawing No.
7) Electrical Cable Schematic Drawing No.
8) Supporting Systems
9) Remarks Separate tables are furnished for each of the safe shutdown functions. In several instances a safe shutdown function requires components from several systems to perform its safe shutdown function.

Appendix R Section III.L requires that only one train of equipment necessary to achieve and maintain hot standby must be available from alternate or dedicated RSS shutdown facilities. Redundancy is not required. Equipment required to achieve and maintain cold shutdown can be repaired within 72 hours. For Seabrook, the preferred RSS shutdown equipment is Train B. The

Train B RSS equipment with R/L selector and control switches have redundant control circuit fuses. This ensures that the local control circuit will still be operable in case the MCR control circuit blows the circuit fuse before control is transferred to local. For conservatism, redundant Train A equipment is typically listed in the RSS equipment lists in Appendix III, for example, both the Train A and the Train B charging pumps are listed whereas only one (Train B) is required to provide the safe shutdown function. This Train A equipment is desired, but not required, for safe shutdown. In some cases the Train A equipment is not listed just for conservative redundancy but is actually required for safe shutdown, for example, the SI accumulator isolation valves where there are two Train A and two Train B required valves. In order to simplify the tabulation, the following are not listed: manual valves in the process flow path; mechanical check valves which provide a Safe Shutdown system boundary; normally closed manual valves which provide a Safe Shutdown system boundary; mechanical relief valves; and root valves on small instrument lines. The review of these valves is documented by the marked P & I Diagrams. Tables are provided for the following functions which satisfy the performance goals stated in Appendix R, Paragraph III.L.2 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-14 Function Table No. Decay Heat Removal 3.1.3.1 Reactor Coolant Inventory and Pressure Control 3.1.3.2 Reactivity Control 3.1.3.3 Process Monitoring 3.1.3.4 Safeguard Actuation System 3.1.3.5 Cold Shutdown 3.1.3.6 Service Water 3.1.3.7 Primary Component Cooling Water 3.1.3.8 (Deleted) 3.1.3.9 Control Building Air Handling 3.1.3.10 Diesel Generator Building Air Handling 3.1.3.11 Containment Enclosure Air Handling 3.1.3.12 Emergency Feedwater Pumphouse Air Handling 3.1.3.13 Primary Auxiliary Building Air Handling 3.1.3.14 Service Water Air Handling 3.1.3.15 (Deleted) 3.1.3.16 Electrical Distribution Emergency 3.1.3.17 Diesel Generators 3.1.3.18 Communication 3.1.3.19 3.3.9 Analysis and Evaluation of Fire Areas An evaluation is provided as to whether the Appendix R requirements or safe shutdown requirement are satisfied. If a deviation from Appendix R requirements exists, this deviation is justified by Analysis. The following fire areas are considered: Building Fire Area Tabulation Control Bldg. - El. 50'-0" Cable Spreading Room CB-F-2A-A 3.3.9.1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-15 Building Fire Area Tabulation Control Bldg. - El. 75'-0" Main Control Room CB-F-3A-A 3.3.9.2 Control Bldg. - El. 75'-0" HVAC Equipment & Duct Area CB-F-3B-A 3.3.9.3 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-16 Tabulation 3.3.9.1 Control Building - El. 50'-0" Cable Spreading Room Fire Area: CB-F-2A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable PAH-DP-35A X PAH-DP-35B X PAH-DP-36A X PAH-DP-36B X B. Analysis The cable spreading room fire area CB -F-2A-A does not contain any cables or equipment which are required for safe shutdown from the RSS facilities except for the equipment listed. 1. Containment Enclosure Isolation Damper, PAH -DP-35A, PAH-DP-36A, PAH-DP-35B, PAH-DP-36B Cables for outboard isolation dampers PAH -DP-35A and PAH -DP-36A and inboard isolation dampers PAH -DP-35B and PAH -DP-36B are routed in trays and conduits in proximity to one another. Under normal operation both outboard and both inboard dampers are open. If both outboard or both inboard dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. If the outboard dampers and the inboard dampers operate independently such that either the supply or the exhaust path but not both are isolated, there could be an air flow problem in EAH system. Outboard dampers are powered from a single Train A power supply. Inboard dampers are powered from a single Train B power supply. The circuit design for the outboard and inboard dampers is such that a spurious signal in either or both circuits will cause both outboard and inboard dampers to operate together, either both open (normal mode) or both closed (recirculation mode). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-17 A fixed fire suppression system in accordance with Appendix R, Paragraph III.G.3 has been provided. Detectors are provided throughout the area. C. Evaluation The Appendix R Paragraphs III.G.3 and III.L. alternative shutdown capability requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-18 Tabulation 3.3.9.2 Control Building - El. 75'-0" Main Control Room Fire Area: CB-F-3A-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable PAH-DP-35A X PAH-DP-35B X PAH-DP-36A X PAH-DP-36B X B. Analysis The Main Control Room fire area CB -F-3A-A does not contain any cables or equipment which are required for safe shutdown from the RSS facilities except for the equipment listed. 1. Containment Enclosure Isolation Damper, PAH -DP-35A, PAH-DP-36A, PAH-DP-35B, PAH-DP-36B Cables for outboard isolation dampers PAH -DP-35A and PAH-DP-36A and inboard isolation dampers PAH -DP-35B and PAH -DP-36B are routed in trays and conduits in proximity to one another. Under normal operation both outboard and both inboard dampers are open. If both outboard or both inboard dampers go closed, the Containment Enclosure Air Handling (EAH) system operates in recirculation mode. The normal and recirculation modes for EAH system operation both satisfy the safe shutdown function. If the outboard dampers and the inboard dampers operate independently such that either the supply or the exhaust path but not both are isolated, there could be an air flow problem in EAH system. Outboard dampers are powered from a single Train A power supply. Inboard dampers are powered from a single Train B power supply. The circuit design for the outboard and inboard dampers is such that a spurious signal in either or both circuits will cause both outboard and inboard dampers to operate together, either both open (normal mode) or both closed (recirculation mode). The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-19 A fixed fire suppression system in accordance with Appendix R Paragraph III.G.3 has not been provided in this continually manned area. Detectors are provided throughout the area. C. Evaluation The Appendix R Paragraph s III.L alternative shutdown capability requirements are satisfied. Deviations from Appendix R, Paragraph III.G.3, fixed fire suppression requirement, exist in the main control room. This deviation is justified based on the analysis and our assertion that additional modification would not enhance fire protection safety.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 14 Section 3.3 Page 3.3-20 Tabulation 3.3.9.3 Control Building - El. 75'-0" HVAC Equipment & Duct Area Fire Area: CB-F-3B-A A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable None None B. Analysis The HVAC Equipment and Duct Area CB -F-3B-A does not contain any cables or equipment which are required for safe shutdown from the RSS facilities. A fixed fire suppression system in accordance with Appendix R Paragraph III.G.3 has not been provided in this area which contains equipment required for the main control room ventilation system. Detectors are provided throughout the area. Carbon monoxide detectors are provided in CBA -F-38 and CBA -F-8038 for early charcoal fire detection. C. Evaluation The Appendix R Paragraphs III.L alternative shutdown capability requirements are satisfied. Deviations from Appendix R, Paragraph III.G.3, fixed fire suppression requirement, exist in the HVAC equipment and duct area. This deviation is justified based on the analysis and our assertion that additional modification would not enhance protection safety.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.4 Page 3.4-1 3.4 ALTERNATIVE SAFE SHUTDOWN - EMERGENCY FEEDWATER PUMPHOUSE FIRE A fire in this area disables both emergency feedwater (EFW) pumps, associated EFW flow control valves, and related instrumentation. An immediate plant trip in response to this fire event is not desirable since this would place a demand on the EFW system which may not be available. Instead, plant operation will be maintained stable at 100% power conditions using the normal feedwater system while the fire event is assessed and appropriate mitigating actions are determined. The plant will not be perturbed by any action, including a power change, that might result in a plant trip and demand on the EFW system. If it is determined that plant shutdown is warranted, th en normal procedures will be used eliminating an EFW system demand. This approach is consistent with the Technical Specification 3/4.7.1.2 Bases. Plant shutdown using normal procedures does not require use of the EFW system so the time critical operator action response times related to the EFW system do not apply (see Section 3.2.2.3) for this fire area. If an immediate plant shutdown was required, then the startup feedwater pump (SUFP) would be used to provide the EFW function. Since both EFW trains are disabled by a fire in this area, this is considered an alternate shutdown capability area. Safe shutdown would be controlled from the main control room. Since this is not the preferred response, immediate plant shutdown is considered a beyond design basis condition analyzed for defense in depth. If the EFW flow control valves are disabled, then the EFW pumps may have to be tripped to control excessive EFW flow. The SUFP and its valves can provide throttled flow to prevent overfill/over cooling conditions. Since this is a beyond design basis, defense in depth, response, the time critical operator action response times related to the EFW system do not apply for this fire area. The following analysis evaluates the beyond design bases response of shutdown controlled from the main control room with an immediate plant trip using the SUFP to provide the EFW function. Plant shutdown using normal procedures does not require use of equipment in this fire area so no further analysis of normal shutdown is required. 3.4.1 Main Control Room Safe Shutdown Safe shutdown will be accomplished with control from the main control room, utilizing the safe shutdown equipment in the following locations:

a. Non-Essential Switchgear Area
b. Condensate Storage Tank Valve Room (CST)
c. Train A Switchgear Room
d. Train B Switchgear Room
e. Turbine Building SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.4 Page 3.4-2 Actions required in the additional areas would be to realign the suction of the startup feedpump; realign the power supply of the startup feedpump from Bus ED

-SWG-4 to Bus EDE -SWG-5 (if offsite power is not available and not already aligned to Bus EDE-SWG-5); bypass the startup feedpump low suction pressure trip (prior to commencing cooldown) and trip the power supply breakers for the feedwater flow control valves. Safe shutdown will then be performed from the main control room. 3.4.2 Safe Shutdown Equipment List Tables that list all equipment, including instrumentation and vital support systems equipment, required to achieve hot standby and cold shutdown are provided in Appendix III. The tables provide the following requested information for each equipment listed.

a. A column which notes whether the equipment is required for hot standby and cold shutdown.
b. A column which defines each equipment

's location by fire zone/area.

c. A column which defines each equipment

's redundant counterpart.

d. A column which lists each equipment

's essential cabling.

e. The table also delineates the following additional information:
1) P & I Diagram Drawing No.
2) Physical Location Drawing No.
3) Power Supply
4) Electrical Node Number
5) Supporting Control and Instrumentation Equipment
6) Electrical Schematic Drawing No.
7) Electrical Cable Schematic Drawing No.
8) Supporting Systems
9) Remarks SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.4 Page 3.4-3 Separate tables are furnished for each of the safe shutdown functions. In several instances a safe shutdown function requires components from several systems to perform its safe shutdown function.

In order to simplify the tabulation, the following are not listed: manual valves in the process flow path; mechanical check valves which provide a Safe Shutdown system boundary; normally closed manual valves which provide a Safe Shutdown system boundary; mechanical relief valves; and root valves on small instrument lines. The review of these valves is documented by the marked P

& I Diagrams.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.4 Page 3.4-4 3.4.3 Analysis and Evaluation of Fire Area EFP -F-l-A, Emergency Feedwater Pump Bldg. A. Equipment And Cables Located In The Fire Area Train A Train B Description Equip. Cable Description Equip. Cable FW-FT-4214-2 x x FW-FT-4214-4 x x FW-FT-4224-4 x x FW-FT-4224-2 x x FW-FT-4234-2 x x FW-FT-4234-4 x x FW-FT-4244-4 x x FW-FT-4244-2 x x FW-FV-4214A x x FW-FV-4214B x x FW-FV-4224A x x FW-FV-4224B x x FW-FV-4234A x x FW-FV-4234B x x FW-FV-4244A x x FW-FV-4244B x x B. Analysis With the exception of the systems/equipment discussed below, a fire in this area will only affect the Train B safe shutdown equipment and cables. The redundant Train A safe shutdown equipment and cables are located in other fire areas. Additional details on the fire protection measures and physical separation for this fire area are contained in Tabulation 3.2.7.48. Redundant emergency feedwater flow control valves and associated flow transmitters which are part of the alternative shutdown capability are located in the fire area. These valves are normally open valves and remain open for the initial phases of safe shutdown. Only two steam generators are required to satisfy the safe shutdown requirements: hence, only two valves on each of two lines need to be disabled (e.g., FW -FV-4214A, FW-FV-4214B, FW -FV-4224A and FW -FV-4224B). The operators will prevent additional spurious operations by tripping the power supply breakers for these valves in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). C. Evaluation A deviation from the Appendix R, Paragraph III.L.3 requirements exists in the emergency feedwater pump building. This deviation is justified based on the analysis and our assertion that additional modifications would not enhance fire protection safety.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.5 Page 3.5-1 3.5 HIGH LOW PRESSURE INTERFACES 3.5.1 List of Interfaces The following is a list of the high -low pressure interfaces connected to the reactor coolant system (RCS). 3.5.1.1 Chemical and Volume Control System (CS)

a. Excess letdown line
b. Normal letdown line
c. Reactor coolant pumps seal bleedoff lines 3.5.1.2 Residual Heat Removal (RH) System 3.5.1.3 Pressurizer Power Operated Relief Valves (PORV) 3.5.1.4 Reactor Vessel Head Vent 3.5.2 High-Low Pressure Interface Safe Shutdown Equipment List A list of all high

-low pressure interface valves is provided in Appendix, Section III. The table provides the following requested information for each equipment listed:

a. A column which notes whether the equipment is required for hot and/or cold shutdown.
b. A column which defines each equipment

's location by fire zones/area.

c. A column which defines each equipment

's redundant counterpart.

d. A column which lists each equipment

's essential cabling. For each cable 's routing by fire zone/area, see computer report "Cables with Associated Fire Zones " in the Appendix, Section V.G (High -Low Pressure Interface Reports).

e. The table also delineates the following additional information:
1) P & I Diagram Drawing No.
2) Physical Location Drawing No.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.5 Page 3.5-2 3) Power Supply

4) Electrical Node Number
5) Supporting Control and Instrumentation Equipment
6) Electrical Schematic Drawing No.
7) Electrical Cable Schematic Drawing No.
8) Supporting Systems
9) Remarks 3.5.3 Review and Analysis A review of each of the lines listed in subsection 3.5.1 is provided to identify lines which could open and cause a LOCA.

The flow through each high -low interface path will be evaluated. If the flow is less then the capacity of one charging pump, then the open path is not considered a LOCA and no further circuit analysis is required. The effect of the flow on system operation would still need to be evaluated. If the flow exceeds the capacity of one charging pump, then further circuit analysis is required per the criteria in Section 3.1.8 to demonstrate that spurious valve operation can not result in an open path. A specific flow value may not be documented for cases where it is obviously unacceptable (ex. RHR/RCS isolation valves). Alternatively, a circuit analysis per the criteria in Section 3.1.8 can be used to demonstrate that spurious valve operation cannot result in an open high -low interface path so no flow analysis is needed. 3.5.3.1 Chemical and Volume Control System

a. Excess letdown line The high-low pressure interface is downstream of control valve CS

-HCV-123. This is a normally closed, fail close diaphragm valve. Upstream of CS -HCV-123 are two normally closed, fail close diaphragm valves, CS -V175 and CS -V176. Spurious opening of one valve will not open the path and prevent safe shutdown. The operators will prevent further spurious openings by tripping the 125 Volt dc power supply breaker for valves CS -V175 and CS -V176 in the Train B switchgear room. An additional disabling capability exists at the disabling panel for CS -V-175 in the Train B diesel generator room (Fire Area: DG -F-2B-A) should the primary capability be inaccessible due to a fire in the switchgear room.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.5 Page 3.5-3 b. Normal letdown line The high-low pressure interface is downstream of parallel valves CS -HCV-189 and CS-HCV-190 (letdown flow control valves). These valves are motor operated drag valves. Upstream of CS -HCV-189 and CS -HCV-190 are fail close diaphragm valves CS -V145, RC-LCV-459, and RC-LCV-460. CS-HCV-189 or 190 failing full open results in a maximum flow rate that exceeds the charging pump capability . To isolate this path, the operator will close CS -V-145, RC-LCV-459 or RC-LCV-460. RC-LCV-459 and RC -LCV-460 can also be closed by tripping a circuit breaker at the 125 Volt distribution panels in the A Train switchgear room (Fire Area: CB -F-1A-A). An additional disabling capability exists in the Train A diesel generator room (Fire Area: DG -F-2A-A) for RC-LCV-459. c. Reactor coolant pumps seal bleedoff lines The high-low pressure interface is downstream of valves CS -V44 (Loop 3), CS -V59 (Loop 4), CS -V10 (Loop 1), CS -V28 (Loop 2). These valves are fail open diaphragm valves. However, these valves are not used for pressure reduction. The RCP seals are the pressure reduction device. If the bleedoff line is isolated downstream of the high/low interface, the pressure would equalize across the seals and pressurize the bleed lines. The low pressure portion of the bleedoff line is protected with relief valves CS -V173, CS-V794, and CS -V250. Bleedoff from the RCP seals will equal a maximum of 12 GPM either discharging to the reactor drain tank (RDT) if containment isolation valves CS -V168 or CS-V167 (normally open motor operated valves) close or to the charging pump suction. RCS fluid to the RDT is not recoverable but will be made up by flow to the charging suction from BAT or RWST. 3.5.3.2 Residual Heat Removal System The high-low pressure interface is downstream of motor operated valves (MOV) RV -V23 (Loop 1) and RC-V88 (Loop 4). Upstream of each MOV is MOV RC -V22 and RC -V87. All four valves are normally closed when the RCS is above RHR design pressure of 600 psig and interlocked to prevent opening when RCS pressure is above 365 psig. During normal operation these normally closed MOV 's will also be deenergized at their respective motor control center, thus there is no possibility of a short circuit, or hot short circuit opening the valves. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.5 Page 3.5-4 3.5.3.3 Pressurizer Power Operated Relief Valves The high-low pressure interface is downstream of paralleled valves RC -PCV-456A and RCV-PCV-456B. These valves are normally closed, fail closed solenoid operated valves. Upstream of each of these valves are the PORV block valves RC-V122 and RC -V124. These MOV's are normally open. Since the PORV block valves are normally open MOVs and will be closed for all fires which could cause spurious PORV operation, a hot short to the control logic or power to the PORV or block valves will not cause PORV blowdown. The operators will prevent the opening of the solenoid operated valves RC -PCV-456A and RC-PCV-456B by tripping their respective power supply breakers in the Train A and Train B switchgear rooms (Fire Areas: CB -F-1A-A and CB-F-1B-A). An additional disabling capability exists in the Train A and Train B diesel generator rooms (Fire Areas: DG -F-2A-A and DG-F-2B-A) respectively should the primary capability be inaccessible due to a fire in the switchgear room. 3.5.3.4 Reactor Vessel Head Vent The high-low pressure interface is downstream of valve, RC -V323. This is a normally closed MOV. Upstream of RC -V323 is a normally closed, solenoid valve, RC -FV-2881. Spurious opening of one valve will not open the path. The operators will prevent further spurious openings by disabling the normally closed MOV RC -V323 and solenoid RC -FV-2881 at the motor control center and 125 volt dc distribution panel, respectively, in the B Train switchgear room (Fire Area: CB-F-1B-A). An additional disabling capability exists for RC-FV-2881 in the Train B diesel generator room (Fire Area: DG -F-2B-A) should the primary capability be inaccessible due to a fire in the switchgear room.

3.5.4 Evaluation

3.5.4.1 Chemical and Volume Control System

a. Excess letdown line The safe shutdown requirements are satisfied.
b. Normal letdown line The safe shutdown requirements are satisfied
c. Reactor coolant pumps seal bleedoff lines The safe shutdown requirements are satisfied

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.5 Page 3.5-5 3.5.4.2 Residual Heat Removal System The safe shutdown requirements are satisfied. 3.5.4.3 Pressurizer Power Operated Relief Valves The safe shutdown requirements are satisfied. 3.5.4.4 Reactor Vessel Head Vent The safe shutdown requirements are satisfied.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.6 Page 3.6-1 3.6 ASSOCIATED CIRCUITS 3.6.1 Definition of Associated Circuits of Concern Circuits other than those directly required for the safe shutdown functions which have the potential to affect or prevent post -fire safe shutdown are considered associated circuits of concern. Associated circuits of concern are defined as those cables (Class 1E and non -Class 1E) that: a. Have a physical separation less than that required by Section III.G.2 of Appendix R, and b. Have one of the following:

1) a common power source with the safe shutdown equipment (redundant or alternative) and the power source is not electrically protected from the circuit of concern by coordinated breakers, fuses or similar devices, or
2) a connection to circuits of equipment whose spurious operation would adversely affect the safe shutdown capability (e.g., RHR/RCS isolation valves, PORVS, steam atmospheric dump valves, etc.), or
3) a common enclosure (e.g., panel) with the shutdown cables (redundant or alternative) and a) are not electrically protected by circuit breakers, fuses or similar devices, or b) will allow propagation of fire into the common enclosure.

3.6.2 Discussion of Methodology Sections 3.6.2.1, 3.6.2.2 and 3.6.2.3 in conjunction with Figure 3.6-1 describes the methodology utilized to address the following types of associated circuits:

a. Common power source
b. Spurious operation
c. Common enclosure

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.6 Page 3.6-2 3.6.2.1 Common Power Source As stated in FSAR Section 8.3.1.4, all non -Class 1E circuits are associated relative to electrical separation with either Train A or Train B in accordance with the provisions of FSAR Appendix 8A Section 4.5a. Based on these design consideration s, associated circuits can be powered from the Class 1E electrical distribution emergency (EDE) system or from the

non-Class 1E electrical distribution (ED) system and further may be routed in the same raceways and terminate in the same enclosure as Class 1E circuits. Although all safe shutdown circuits are powered from the EDE system, not all safe shutdown circuits are considered to be Class 1E. There are no Safe shutdown circuits, which require electrical power to operate, powered from the ED system. Associated circuits that are powered from the EDE system, and are associated with the safe shutdown circuits by a common power supply, are protected by a coordinated circuit breaker and; hence, are not considered to be associated circuits of concern. The above design considerations eliminates as associated circuits of concern all circuits which have no deleterious impact on safe shutdown. 3.6.2.2 Spurious Operation The review of each system required to satisfy the safe shutdown functions included all valves necessary to operate the system or maintain the system process boundaries. This assures that the safe shutdown system will operate as designed. If valves or other equipment from one train (i.e., Train A) are required for operation or could prevent operation of the other train (i.e., Train B), then additional reviews are performed to determine the failure modes and provide manual actions or operations of other equipment that would prevent the spurious operation from affecting safe shutdown. An example of this is the primary component cooling water containment isolation function which requires that both Train A and Train B valves remain open. The inboard containment isolation valve is the same train as the pumps which supply primary component cooling water while the outboard valve is of the opposite train but could be operated manually upon loss of power or damage to electrical circuit. To prevent the spurious operation of various safety injection system valves, containment isolation valves and service water valves, the engineered safety features actuation system logic and the tower actuation logic are disabled by tripping their power supplies after a control room evacuation. In several instances (e.g., RHR/RCS isolation valves), the power supplies are permanently disabled (breaker tripped and locked out) to prevent spurious operation. The spurious operation of valves protecting high -low pressure interfaces is discussed in Section 3.5. See Section 3.1.8 for criteria to evaluate components for spurious operation . SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 9 Section 3.6 Page 3.6-3 3.6.2.3 Common Enclosures The deleterious effects of fire on associated circuits in common enclosures is eliminated by the following three design considerations:

a. Coordinated circuit breakers, fuses or similar devices will assure that the associated circuit failure does not prevent the redundant train from performing its safe shutdown function. b. The cables are qualified to IEEE Standard 383; hence, the propagation of the fire from one train to the redundant train in another fire area/zone is very unlikely.
c. Train and channel separation for cable routing is assured by a computerized cable routing program which does not allow cables with different circuit code assignments to be routed in the same raceways.

Based on the above design considerations, associated circuits in common enclosures are not considered associated circuits of concern. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 5 Section 3.7 Page 3.7-1 3.7 DEVIATIONS FROM 10CFR50 APPENDIX R Fire Area Section Located In Report Equipment/System Type Of Deviation From Appendix C-F-1-Z/C-F-2-Z/ 3.2.7.1 B.2.c CC-V-57, 121, 176, 256 III.G.2.d C-F-3-Z 3.2.7.1 B.2.k Pressurizer Heaters III.G.2.d 3.2.7.1 B.2.l RC-PCV-456A, B III.G.2.d 3.2.7.1 B.2.n SI-V3, SI-FV-2475, 2476 III.G.2.d 3.2.7.1 B.2.o SI-V32, SI-FV-2477, 2486 III.G.2.d 3.2.7.1 B.2.p SI-V-17, SI-FV-2482, 2483 III.G.2.d 3.2.7.1 B.2.q SI-V-47, SI-FV-2495, 2496 III.G.2.d 3.2.7.1 B.2.u NI-NE-6690, 6691 III.G.2.d 3.2.7.1 B.2.v RC-LT-459, 460 III.G.2.d 3.2.7.1 B.2.x RC Hot Leg Temp. III.G.2.d CB-F-2C-A 3.2.7.10.B.2 CBA III.G.2.c Auto Fire Suppression CB-F-3A-A 3.3.9.2 Control Room/RSS III.G.3 - Fixed Fire Suppression CB-F-3B-A 3.3.9.3 HVAC Equipment & Duct Area - Control Room III.G.3 - Fixed Fire Suppression CE-F-1A-Z/ 3.2.7.17 B.f EAH-AC-2A, -2B, EAH-FN-5A, III.G.2.b - Separation 20 ' PP-F-XX-Z -5B, EAH-DP-3A, -3B III.G.2.c - Auto Fire Suppression DG-F-3A-Z/ 3.2.7.41 B.2.b DAH-FN-25A, -25B III.G.2.b - Separation 20 ' DG-F-3B-Z III.G.2.c - Auto Fire Suppression

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Rev. 5 Section 3.7 Page 3.7-2 Fire Area Section Located In Report Equipment/System Type Of Deviation From Appendix EFP-F-1-A 3.2.7.48 EFW Room III.G.3 - Fixed Fire Suppression 3.4.3 EFW Room III.L.3 - Independence PAB-F-1A-Z* 3.2.7.63 CC, CS, EAH, PAH, SI, SW III.G.2.c - Auto Fire Suppression PAB-F-1J-Z* 3.2.7.66 CC, SI, CS III.G.2.c - Auto Fire Suppression PAB-F-1K-Z* 3.2.7.67 CS, SW, PAH III.G.2.b - Separation 20 ' III.G.2.c - Auto Fire Suppression PAB-F-2A-Z* 3.2.7.68 EAH, PAH, SW III.G.2.c - Auto Fire Suppression PAB-F-2B-Z* 3.2.7.69 PAH III.G.2.c - Auto Fire Suppression PAB-F-2C-Z* 3.2.7.70 PAH III.G.2.b - Separation 20 ' PAB-F-3A-Z* 3.2.7.71 CS, SW III.G.2.c - Auto Fire Suppression PAB-F-3B-Z* 3.2.7.72 CS III.G.2.c - Auto Fire Suppression

  • Denotes Group of Fire Zones which form one Fire Area in PAB. In addition to the deviations requested, a general deviation to the requirements at III.G.2.a is requested for this area.

ASSOCIATED CIRCUITS OF CONCERN APPENDIX R Figure 3.6-1

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -1 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 FW-P-113 Start-up Feedwater Pump CO-20426 A 310326 TB-F-1A-Z X X X - M12 FW-A93-52 4160 V AC Circuit Breaker A93 CB-F-1A-A A47-A93 A47-A93/1 A47-A93/2 A47-A93/3 A47-N12 A47-P82 310844 A93a A93g A93b A93h A93c A93d A47a A47g EDE-SWG-5 CBA-FN-19 CBA-FN-20 FW-P-37B FW-A93-FU Fuses A93 CB-F-1A-A FW-CS-4268-1 Control Switch with Indication F60 CB-F-3A-A FW-SS-4268 Selector Switch A47 NES-F-1A-Z FW-A93-CS Test Control Switch A93 CB-F-1A-A FW-A93-G,R,W Indicating Lights A93 CB-F-1A-A A93-F60/1 A93-F60/2 A93-F60/3 A93-F60/4 A93-ED7 A93-G8L A93-HR2 G8L-P2V (Non-CASP) EDE-A53-94-2 Bus Undervoltage A53 CB-F-1A-A FW-A93-R1 Auxiliary Relay A93 CB-F-1A-A FW-PSLH-PS5 Lube Oil Pressure Switch P82 TB-F-1A-Z FW-A93-PS5X Pressure Switch Auxiliary Relay A93 CB-F-1A-A FW-A93-52S Mechanically Operated Contact A93 CB-F-1A-A FW-A93-52H Truck Operated Contact A93 CB-F-1A-A FW-A93-62 P85 Starting Blocking Time Delay Relay A93 CB-F-1A-A FW-ED7-2 Pre-Lube Pump Starting Auxiliary Time Delay Relay ED7 TB-F-2A-Z FW-A93-86 Lockout Relay A93 CB-F-1A-A FW-A93-TD2 Lockout Relay Test Device A93 CB-F-1A-A FW-A93-CT Current Transformers 300/5A A93 CB-F-1A-A FW-A93-TD1 CT Test Device A93 CB-F-1A-A FW-A93-50/51 Inst./Time Overcurrent Relays ØA, ØC A93 CB-F-1A-A FW-A93-AM Ammeter A93 CB-F-1A-A FW-A93-AS Ammeter Switch A93 CB-F-1A-A FW-A93-ATR Transducer A93 CB-F-1A-A FW-AM-4268-1 Ammeter F60 CB-F-3A-A FW-A47-52 4160 V AC Circuit Breaker A47 NES-F-1A-Z FW-A93-51GS Ground Sensor Relay A93 CB-F-1A-A FW-PSL-4233-2 Pressure Switch Low Suction P2V TB-F-1A-Z FW-A93-R2 Auxiliary Relay A93 CB-F-1A-A FW-HR2-RMO EPS Manual Override Relay (K27 ) HR2 CB-F-1A-A FW-CS-4233 Suction Pressure Bypass Switch G8L TB-F-1A-Z

. 1. This equipment is mechanical with no electrical requirements.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -2 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 FW-P-161 Start-up Feedwater Pump FW-P-113 Prelube Pump CO-20426 A 310326 TB-F-1A-Z X X X - NU0 FW-CN1-52 460 V AC Circuit Breaker CN1 TB-F-2-Z CNA-NU0 CN1-F60 CN1-F81 A47-F60/4 EA1-F60 F60-FB7/5 310844 CN1a CN1c EDE-MCC-523 None FW-CN1-FU Fuse CN1 TB-F-2-Z FW-CS-4268 Control Switch with Indication F60 CB-F-3A-A FW-SS-4268 Selector Switch A47 NES-F-1A-Z FW-CS-4268-1 Control Switch with Indication F60 CB-F-3A-A FW-CS-4278 Control Switch F60 CB-F-3A-A FW-ED7-2 Pump Starting Time Delay Relay ED7 TB-F-2-Z FW-PSLH-PS4 Lube Oil Pressure Switch P81 TB-F-1A-Z FW-CN1-42 Motor Starter CN1 TB-F-2-Z FW-CN1-49 Overload Relays CN1 TB-F-2-Z FW-FB7-K620A SSPS Output Relay FB7 CB-F-3A-A FW-ED7-3 Time Delay Relay ED7 TB-F-2-2 FW-J8K-K5R, S, T GE MK Vle TMR Relay J8K TB-F-2-Z EA1-J9M/1 J8M-J9M FW-J9K-K5R, S, T GE MK Vle TMR Relay J9K TB-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -3 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 FW-FV-4214A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2E FW-B3V-52 460 V AC Circuit Breaker B3V CB-F-1A-A B3V-V2E B3V-V2E/1 E3C-G2G G2G-V2E E3C-F51 F51-G2G B3V-G5X B3V-G5X/1 E3C-FN6 F51-FN6 FN6-G5X FN6-G5X/1 310844 B3Va B3Vd B3ve CBA-FN-19 CBA-FN-20 EDE-MCC-515 FW-FV-4214B FW-B3V-FU Fuse B3V CB-F-1A-A FW-CS-4214-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4214-A Selector Switch G2G CB-F-1A-A FW-SS-4214-A1 Selector Switch G5X DG-F-2A-A FW-CS-4214-A1 Control Switch with Indication F51 CB-F-3A-A FW-B3V-42/O,C Motor Starters B3V CB-F-1A-A FW-B3V-49 Overload Relays B3V CB-F-1A-A FW-ZS-4214-A Valve Position Switch V2E EFP-F-1-A FW-FN6-4214AX Auxiliary Relay FN6 CB-F-2B-A FW-FN6-MSO-1 Auxiliary Relay FN6 CB-F-2B-A FW-FN6-R1A Auxiliary Relay FN6 CB-F-2B-A FW-E3P-62-1 Timing Relay E3P CB-F-1A-A FW-E3C-R1 Auxiliary Relay (FYY-4214-2) E3C CB-F-1A-A FW-E3P-62-2 Timing Relay E3P CB-F-1A-A FW-E3C-R2 Auxiliary Relay (FYY-4224-4) E3C CB-F-1A-A FW-E3P-62-3 Timing Relay E3P CB-F-1A-A FW-E3C-R3 Auxiliary Relay (FYY-4234-2) E3C CB-F-1A-A FW-E3P-62-4 Timing Relay E3P CB-F-1A-A FW-E3C-R4 Auxiliary Relay (FYY-4244-4) E3C CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -4 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 FW-FV-4214B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2J FW-B3Z-52 460 V AC Circuit Breaker B3Z CB-F-1B-A B3Z-V2J B3Z-V2J/1 E3D-G2J G2J-V2J E3D-F51 F51-G2J B3Z-G2J B3Z-G5Y B3Z-G5Y/1 E3D-FN7 F51-FN7 FN7-G5Y FN7-G5Y/1 310844 B3Za B3Zd B3Ze CBA-FN-32 CBA-FN-33 EDE-MCC-615 FW-FV-4214A FW-B3Z-FU Fuse B3Z CB-F-1B-A FW-CS-4214-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4214-B Selector Switch G2J CB-F-1B-A FW-SS-4214-B1 Selector Switch G5Y DG-F-2B-A FW-CS-4214-B1 Control Switch with Indication F51 CB-F-3A-A FW-B3Z-42/O,C Motor Starters B3Z CB-F-1B-A FW-B3Z-49 Overload Relays B3Z CB-F-1B-A FW-ZS-4214-B Valve Position Switch V2J EFP-F-1-A FW-FN7-4214BX Auxiliary Relay FN7 CB-F-2C-A FW-FN7-MSO-1 Auxiliary Relay FN7 CB-F-2C-A FW-FN7-R1B Auxiliary Relay FN7 CB-F-2C-A FW-E3Q-62-1 Timing Relay E3Q CB-F-1B-A FW-E3D-R1 Auxiliary Relay (FYY-4214-4) E3D CB-F-1B-A FW-E3Q-62-2 Timing Relay E3Q CB-F-1B-A FW-E3D-R2 Auxiliary Relay (FYY-4224-2) E3D CB-F-1B-A FW-E3Q-62-3 Timing Relay E3Q CB-F-1B-A FW-E3D-R3 Auxiliary Relay (FYY-4234-4) E3D CB-F-1B-A FW-E3Q-62-4 Timing Relay E3Q CB-F-1B-A FW-E3D-R4 Auxiliary Relay (FYY-4244-2) E3D CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -5 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 FW-FV-4224A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2F FW-B3W-52 460 V AC Circuit Breaker B3W CB-F-1A-A B3W-V2F B3W-V2F/1 E3C-G2G/1 G2G-V2F E3C-F51/1 F51-G2G/1 B3W-G5X B3W-G5X/1 E3C-FN6/1 F51-FN6/1 FN6-G5X/2 FN6-G5X/3 310844 B3Wa B3Wd B3We CBA-FN-19 CBA-FN-20 EDE-MCC-515 FW-FV-4224B FW-B3W-FU Fuse B3W CB-F-1A-A FW-CS-4224-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4224-A Selector Switch G2G CB-F-1A-A FW-SS-4224-A1 Selector Switch G5X DG-F-2A-A FW-CS-4224-A1 Control Switch with Indication F51 CB-F-3A-A FW-B3W-42/O,C Motor Starters B3W CB-F-1A-A FW-B3W-49 Overload Relays B3W CB-F-1A-A FW-ZS-4224-A Valve Position Switch V2F EFP-F-1-A FW-FN6-4224AX Auxiliary Relay FN6 CB-F-2B-A FW-FN6-MSO-2 Auxiliary Relay FN6 CB-F-2B-A FW-FN6-R2A Auxiliary Relay FN6 CB-F-2B-A FW-E3C-R1 Auxiliary Relay (FYY-4214-2) E3C CB-F-1A-A FW-E3C-R2 Auxiliary Relay (FYY-4224-4) E3C CB-F-1A-A FW-E3C-R3 Auxiliary Relay (FYY-4234-2) E3C CB-F-1A-A FW-E3C-R4 Auxiliary Relay (FYY-4244-4) E3C CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -6 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 FW-FV-4224B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2K FW-B4A-52 460 V AC Circuit Breaker B4A CB-F-1B-A B4A-V2K B4A-V2K/1 E3D/G2J/1 G2J-V2K E3D-F51/1 F51-G2J/1 B4A-G2J B4A-G5Y B4A-G5Y/1 E3D-FN7/1 F51-FN7/1 FN7-G5Y/2 FN7-G5Y/3 310844 B4Aa B4Ad B4Ae CBA-FN-32 CBA-FN-33 EDE-MCC-615 FW-FV-4224A FW-B3W-FU Fuse B4A CB-F-1B-A FW-CS-4224-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4224-B Selector Switch G2J CB-F-1B-A FW-SS-4224-B1 Selector Switch G5Y DG-F-2B-A FW-CS-4224-B1 Control Switch with Indication F51 CB-F-3A-A FW-B4A-42/O,C Motor Starters B4A CB-F-1B-A FW-B4A-49 Overload Relays B4A CB-F-1B-A FW-ZS-4224-B Valve Position Switch V2K EFP-F-1-A FW-FN7-4224BX Auxiliary Relay FN7 CB-F-2C-A FW-FN7-MSO-2 Auxiliary Relay FN7 CB-F-2C-A FW-FN7-R2B Auxiliary Relay FN7 CB-F-2C-A FW-E3D-R1 Auxiliary Relay (FYY-4214-4) E3D CB-F-1B-A FW-E3Q-62-1 Timing Relay E3Q CB-F-1B-A FW-E3D-R2 Auxiliary Relay (FYY-4224-2) E3D CB-F-1B-A FW-E3Q-62-2 Timing Relay E3Q CB-F-1B-A FW-E3D-R3 Auxiliary Relay (FYY-4234-4) E3D CB-F-1B-A FW-E3Q-62-3 Timing Relay E3Q CB-F-1B-A FW-E3D-R4 Auxiliary Relay (FYY-4244-2) E3D CB-F-1B-A FW-E3Q-62-4 Timing Relay E3Q CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -7 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 FW-FV-4234A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2G FW-B3X-52 460 V AC Circuit Breaker B3X CB-F-1A-A B3X-V2G B3X-V2G/1 G2G-V2G E3C-G2G/2 E3C-F51/2 F51-G2G/2 B3X-G5X B3X-G5X/1 E3C-FN6/2 F51-FN6/2 FN6-G5X/4 FN6-G5X/5 310844 B3Xa B3Xd B3Xe CBA-FN-19 CBA-FN-20 EDE-MCC-515 FW-FV-4234B FW-B3X-FU Fuse B3X CB-F-1A-A FW-CS-4234-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4214-A Selector Switch G2G CB-F-1A-A FW-SS-4214-A1 Selector Switch G5X DG-F-2A-A FW-CS-4234-A1 Control Switch with Indication F51 CB-F-3A-A FW-B3X-42/O,C Motor Starters B3X CB-F-1A-A FW-B3X-49 Overload Relays B3X CB-F-1A-A FW-ZS-4234-A Valve Position Switch V2G EFP-F-1-A FW-FN6-4234AX Auxiliary Relay FN6 CB-F-2B-A FW-FN6-MSO-3 Auxiliary Relay FN6 CB-F-2B-A FW-FN6-R3A Auxiliary Relay FN6 CB-F-2B-A FW-E3C-R1 Auxiliary Relay (FYY-4214-2) E3C CB-F-1A-A FW-E3P-62-1 Timing Relay E3Q CB-F-1A-A FW-E3C-R2 Auxiliary Relay (FYY-4224-4) E3C CB-F-1A-A FW-E3P-62-2 Timing Relay E3Q CB-F-1A-A FW-E3C-R3 Auxiliary Relay (FYY-4234-2) E3C CB-F-1A-A FW-E3P-62-3 Timing Relay E3Q CB-F-1A-A FW-E3C-R4 Auxiliary Relay (FYY-4244-4) E3C CB-F-1A-A FW-E3P-62-4 Timing Relay E3Q CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -8 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 8 FW-FV-4234B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2L FW-B4B-52 460 V AC Circuit Breaker B4B CB-F-1B-A B4B-V2L B4B-V2L/1 E3D/G2J/2 G2J-V2L E3D-F51/2 F51-G2J/2 B4B-G2J B4B-G5Y B4B-G5Y/1 E3D-FN7/2 F51-FN7/2 FN7-G5Y/4 FN7-G5Y/5 310844 B4Ba B4Bd B4Be CBA-FN-32 CBA-FN-33 EDE-MCC-615 FW-FV-4234A FW-B4B-FU Fuse B4B CB-F-1B-A FW-CS-4234-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4214-B Selector Switch G2J CB-F-1B-A FW-SS-4214-B1 Selector Switch G5Y DG-F-2B-A FW-CS-4234-B1 Control Switch with Indication F51 CB-F-3A-A FW-B4B-42/O,C Motor Starters B4B CB-F-1B-A FW-B4B-49 Overload Relays B4B CB-F-1B-A FW-ZS-4234-B Valve Position Switch V2L EFP-F-1-A FW-FN7-4234BX Auxiliary Relay FN7 CB-F-2C-A FW-FN7-MSO-3 Auxiliary Relay FN7 CB-F-2C-A FW-FN7-R3B Auxiliary Relay FN7 CB-F-2C-A FW-E3D-R1 Auxiliary Relay (FYY-4214-4) E3D CB-F-1B-A FW-E3D-R2 Auxiliary Relay (FYY-4224-2) E3D CB-F-1B-A FW-E3D-R3 Auxiliary Relay (FYY-4234-4) E3D CB-F-1B-A FW-E3D-R4 Auxiliary Relay (FYY-4244-2) E3D CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -9 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 FW-FV-4244A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2H FW-B3Y-52 460 V AC Circuit Breaker B3Y CB-F-1A-A B3Y-V2H B3Y-V2H/1 E3C-G2G/3 G2G-V2H E3C-F51/3 F51-G2G/3 B3Y-G5X B3Y-G5X/1 E3C-FN6/3 F51-FN6/3 FN6-G5X/6 FN6-G5X/7 310844 B3Ya B3Yd B3Ye CBA-FN-19 CBA-FN-20 EDE-MCC-515 FW-FV-4244B FW-B3Y-FU Fuse B3Y CB-F-1A-A FW-CS-4244-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4224-A Selector Switch G2G CB-F-1A-A FW-SS-4224-A1 Selector Switch G5X DG-F-2A-A FW-CS-4244-A1 Control Switch with Indication F51 CB-F-3A-A FW-B3Y-42/O,C Motor Starters B3Y CB-F-1A-A FW-B3Y-49 Overload Relays B3Y CB-F-1A-A FW-ZS-4244-A Valve Position Switch V2H EFP-F-1-A FW-FN6-4244AX Auxiliary Relay FN6 CB-F-2B-A FW-FN6-MSO-4 Auxiliary Relay FN6 CB-F-2B-A FW-FN6-R4A Auxiliary Relay FN6 CB-F-2B-A FW-E3C-R1 Auxiliary Relay (FYY-4214-2) E3C CB-F-1A-A FW-E3P-62-1 Timing Relay E3P CB-F-1A-A FW-E3C-R2 Auxiliary Relay (FYY-4224-4) E3C CB-F-1A-A FW-E3P-62-2 Timing Relay E3P CB-F-1A-A FW-E3C-R3 Auxiliary Relay (FYY-4234-2) E3C CB-F-1A-A FW-E3P-62-3 Timing Relay E3P CB-F-1A-A FW-E3C-R4 Auxiliary Relay (FYY-4244-4) E3C CB-F-1A-A FW-E3P-62-4 Timing Relay E3P CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -10 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 10 FW-FV-4244B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2M FW-B4C-52 460 V AC Circuit Breaker B4C CB-F-1B-A B4C-V2M B4C-V2M/1 E3D/G2J/3 GJ2-V2M E3D-F51/3 F51-G2J/3 B4C-G2J B4C-G5Y B4C-G5Y/1 E3D-FN7/3 F51-FN7/3 FN7-G5Y/6 FN7-G5Y/7 310844 B4Ca B4Cd B4Ce CBA-FN-32 CBA-FN-33 EDE-MCC-615 FW-FV-4244A FW-B4C-FU Fuse B4C CB-F-1B-A FW-CS-4244-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4224-B Selector Switch G2J CB-F-1B-A FW-SS-4224-B1 Selector Switch G5Y DG-F-2B-A FW-CS-4244-B1 Control Switch with Indication F51 CB-F-3A-A FW-B4C-42/O,C Motor Starters B4C CB-F-1B-A FW-B4C-49 Overload Relays B4C CB-F-1B-A FW-ZS-4244-B Valve Position Switch V2M EFP-F-1-A FW-FN7-4244BX Auxiliary Relay FN7 CB-F-2C-A FW-FN7-MSO-4 Auxiliary Relay FN7 CB-F-2C-A FW-FN7-R4B Auxiliary Relay FN7 CB-F-2C-A FW-E3D-R1 Auxiliary Relay (FYY-4214-4) E3D CB-F-1B-A FW-E3Q-62-1 Timing Relay E3Q CB-F-1B-A FW-E3D-R2 Auxiliary Relay (FYY-4224-2) E3D CB-F-1B-A FW-E3Q-62-2 Timing Relay E3Q CB-F-1B-A FW-E3D-R3 Auxiliary Relay (FYY-4234-4) E3D CB-F-1B-A FW-E3Q-62-3 Timing Relay E3Q CB-F-1B-A FW-E3D-R4 Auxiliary Relay (FYY-4244-2) E3D CB-F-1B-A FW-E3Q-62-4 Timing Relay E3Q CB-F-1B-A 11 FW-V-156 Start-up Feed Pump to EFW Header Valve FW-20688 A 310589 MS-F-1B-Z X X X - V3L FW-B4S-52 460 V AC Circuit Breaker B4S CB-F-1A-A B4S-V3L B4S-V3L/1 B4S-F60 B4S-F60/1 310844 B4Sa B4Sc CBA-FN-19 CBA-FN-20 EDE-MCC-531 None FW-F4S-FU Fuse B4S CB-F-1A-A FW-CS-4261 Control Switch with Indication F60 CB-F-3A-A FW-B4S-42/O,C Motor Starters B4S CB-F-1A-A FW-B4S-49 Overload Relays B4S CB-F-1A-A FW-ZS-V156 Valve Position and Open/Close Torque Switches V3L MS-F-1B-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -11 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 12 FW-V-163 Start-up Feed Pump Bypass to EFW Pump Valve FW-20687 A 310326 TB-F-1A-Z X X X - V3M FW-C2R-52 460 V AC Circuit Breaker C2R TB-F-2A-Z C2R-V3M C2R-V3M/1 C2R-F60 310844 C2Ra C2Rc EDE-MCC-523 None FW-C2R-FU Fuse C2R TB-F-2A-Z FW-CS-4262 Control Switch with Indication F60 CB-F-3A-A FW-C2R-42/O,C Motor Starter C2R TB-F-2A-Z FW-C2R-49 Overload Relays C2R TB-F-2A-Z FW-ZS-V163 Valve Position and Open/Close Torque Switches V3M TB-F-1A-Z 13 FW-E3C Emergency Feedwater Valves Train "A" Vital Controls Relay Compt. (MCC -515) - A 310442 CB-F-1A-A X X X - E3C FW-E3E-52 120 V AC Circuit Breaker E3E CB-F-1A-A E3C-FK0 E3C-F56 E3C-FN6/4 FK0-FN6 FK0-FN6/1 310844 E3E/1a, 1e E3E/1c CBA-FN-19 CBA-FN-20 EDE-MCC-515 120 V AC Distribution Panel None FW-E3C-R1 Auxiliary Relay (FYY-4214-2) E3C CB-F-1A-A FW-E3C-R2 Auxiliary Relay (FYY-4224-4) E3C CB-F-1A-A FW-E3C-R3 Auxiliary Relay (FYY-4234-2) E3C CB-F-1A-A FW-E3C-R4 Auxiliary Relay (FYY-4244-4) E3C CB-F-1A-A FW-CS-4241-A1 Control Switch F51 CB-F-3A-A FW-CS-4224-A1 Control Switch F51 CB-F-3A-A FW-CS-4234-A1 Control Switch F51 CB-F-3A-A FW-CS-4244-A1 Control Switch F51 CB-F-3A-A MM-CP-279 "A" Train BOP -PCC FK0 CB-F-3A-A 14 FW-E3D Emergency Feedwater Valves Train "B" Vital Controls Relay Compt. (MCC -615) - B 310442 CB-F-1B-A X X X - E3D FW-E3F-52 120 V AC Circuit Breaker E3F CB-F-1B-A E3D-FL2 E3D-F51/4 E3D-FN7/4 FL2-FN7 FL2-FN7/1 310844 E3F/1a, 1e E3F/1c CBA-FN-32 CBA-FN-33 EDE-MCC-615 120 V AC Distribution Panel None FW-E3D-R1 Auxiliary Relay (FYY-4214-4) E3D CB-F-1B-A FW-E3D-R2 Auxiliary Relay (FYY-4224-2) E3D CB-F-1B-A FW-E3D-R3 Auxiliary Relay (FYY-4234-4) E3D CB-F-1B-A FW-E3D-R4 Auxiliary Relay (FYY-4244-2) E3D CB-F-1B-A FW-CS-4241-B1 Control Switch F51 CB-F-3A-A FW-CS-4224-B1 Control Switch F51 CB-F-3A-A FW-CS-4234-B1 Control Switch F51 CB-F-3A-A FW-CS-4234-B1 Control Switch F51 CB-F-3A-A MM-CP-279B "B" Train BOP-PCC FL2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -12 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 FW-FT-4214-2 RC-E-11A Emergency Feedwater Header Flow Transmitter FW-20688 A 310708 EFP-F-1-A X X X - GL3 MM-CP-297A "A" Train BOP Process Control Panel FK0 CB-F-3A-A FK0-GL3 310844 FP 72179 FK0a MM-CP-297A FW-LT-501 16 FW-FT-4214-4 RC-E-11A Emergency Feedwater Header Flow Transmitter FW-20688 B 310708 EFP-F-1A-A X X X - GL4 MM-CP-297B Train "B" BOP Process Control Panel FL2 CB-F-3A-A FL2-GL4 310844 FP 72181 FL2a 17 FW-FT-4224-4 RC-E-11B Emergency Feedwater Header Flow Transmitter FW-20688 A 310708 EFP-F-1A-A X X X - GL3 MM-CP-297A Train "A" BOP Process Control Panel FK0 CB-F-3A-A FK0-GL3 310844 FP 72179 FK0a 18 FW-FT-4224-2 RC-E-11B Emergency Feedwater Header Flow Transmitter FW-20688 B 310708 EFP-F-1A-A X X X - GL4 MM-CP-297B Train "B" BOP Process Control Panel FL2 CB-F-3A-A FL2-GL4 310844 FP 72181 FL2a MM-CP-297B FW-LT-502 19 FW-FT-4234-2 RC-E-11C Emergency Feedwater Header Flow Transmitter FW-20688 A 310708 EFP-F-1A-A X X X - GL3 MM-CP-297A Train "A" BOP Process Control Panel FK0 CB-F-3A-A FK0-GL3 310844 FP 72179 FK0a MM-CP-297A FW-LT-503 20 FW-FT-4234-4 RC-E-11C Emergency Feedwater Header Flow Transmitter FW-20688 B 310708 EFP-F-1A-A X X X - GL4 MM-CP-297B Train "B" BOP Process Control Panel FL2 CB-F-3A-A FL2-GL4 310844 FP 72181 FL2a 21 FW-FT-4244-4 RC-E-11D Emergency Feedwater Header Flow Transmitter FW-20688 A 310708 EFP-F-1A-A X X X - GL3 MM-CP-297A Train "A" BOP Process Control Panel FK0 CB-F-3A-A FK0-GL3 310844 FP 72179 FK0a 22 FW-FT-4244-2 RC-E-11D Emergency Feedwater Header Flow Transmitter FW-20688 B 310708 EFP-F-1A-A X X X - GL4 MM-CP-297B Train "B" BOP Process Control Panel FL2 CB-F-3A-A FL2-GL4 310844 FP 72181 FL2a MM-CP-297B FW-LT-504 23 FW-LT-501 RC-E-11A SG Wide Range Level Transmitter FW-20686 A 310576 C-F-1-Z X X X - R1D FW-LQY-501 Signal Converter FA1 CB-F-3A-A FA1-H44 H44-R1D F56-FA1 310942 FP 55315 FA1h Sh. 13 MM-CP-1 FW-LI-501 Level Indicator F51 CB-F-3A-A EDE-MM-120 Electrical Penetration H44 C-F-2-Z, ET-F-1A-A MM-CP-1 PPC #1 FA1 CB-F-3A-A 24 FW-LT-502 RC-E-11B SG Wide Range Level Transmitter FW-20686 B 310576 C-F-1-Z X X X - R1E FW-LQY-502 Signal Converter FA2 CB-F-3A-A FA2-H55 H55-R1E F56-FA2/1 310942 FP 55316 FA2h Sh. 13 MM-CP-2 FW-LI-502 Level Indicator F51 CB-F-3A-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A MM-CP-2 PPC #2 FA2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 3 Table 3.2.3 -13 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE BUILDING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 25 FW-LT-503 RC-E-11C SG Wide Range Level Transmitter FW-20686 A 310577 C-F-1-Z X X X - R1F FW-LQY-503 Signal Converter FA3 CB-F-3A-A FA3-H47/1 H47-R1F F56-FA3/2 310942 FP 55317 FA3h Sh. 13 MM-CP-3 FW-LI-503 Level Indicator F51 CB-F-3A-A EDE-MM-123 Electrical Penetration H47 C-F-2-Z, ET-F-1A-A MM-CP-3 PPC #3 FA3 CB-F-3A-A 26 FW-LT-504 RC-E-11D SG Wide Range Level Transmitter FW-20686 B 310577 C-F-1-Z X X X - R1G FW-LQY-504 Signal Converter FA4 CB-F-3A-A FA4-H52/1 H52-R1G F56-FA4 310942 FP 55318 FA4h Sh. 13 MM-CP-4 FW-LI-504 Level Indicator F51 CB-F-3A-A EDE-MM-128 Electrical Penetration H52 C-F-1-Z, ET-F-1C-A MM-CP-4 PPC #4 FA4 CB-F-3A-A - 27 CO-V-142 Condensate Tank Emergency Outlet Valve CO-20426 A 310248 202319 CST-F-1-0 X X - - - - - - - - - - - Note 1 28 CO-LT-4096 CO-TK-25 Condenser Storage Tank Level CO-20426 A 310828 CST-F-1 X X - R53 CO-LI-4096 Level Indicator F61 CB-F-3A-A FJ7-R53 F66-FJ8 310953 FJ7f FJ7g MM-CP-153 MM-CP-153 BOP-PCC FJ7 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-1 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CS-V-175 CS-20722 B 310577 C-F-1-Z X X X X L95 CS-E95/2-72 125 V DC Circuit Breaker E95 CB-F-1B-A CBA-FN-32 CBA-FN-33 CS-V176 Note 1 Excess Letdown

Line Isolation

Valve CS-CS-7418 Control Switch with Indication F41 CB-F-3A-A 310891 E95/2a E95/2c E95/2d CS-E4D-FU Fuses E4D CB-F-1B-A CS-SS-7418 Selector Switch G5Y DG-F-2B-A E95-E4D F48-G5Y F48-H39/3 GE5-H39/1 GE5-L95/1 E4D-F48 F48-H39/2 CS-FY-7418 Pilot Solenoid GE5 C-F-1-Z CS-ZS-V175 Valve Position Switch L95 C-F-1-Z EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A 2 CS-V-176 CS-20722 B 310577 C-F-1-Z X X X X LA5 CS-E95/4-72 125 V DC Circuit Breaker E95 CB-F-1B-A CBA-FN-32 CBA-FN-33 CS-V175 Note 1 Excess Letdown

Line Isolation

Valve CS-CS-7417 Control Switch with Indication F41 CB-F-3A-A CS-FY-7417 Pilot Solenoid GE5 C-F-1-Z 310891 E95/4a E95/4d E95/4b E95/4e E95/4f CS-ZS-V176 Valve Position Switch LA5 C-F-1-Z F48-H39/1 GE5-H39/5 E95-E4D/1 E4D-F26 F48-H39 GE5-H39/4 GE5-LA5/1 CS-E4D-FU Fuses E4D CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A 3 RC-LCV-459 RC-20843 A 310577 C-F-1-Z X X X X L99 RC-E89/17-72 125 V DC Circuit Breaker E89 CB-F-1A-A CBA-FN-19 CBA-FN-20 RC-LCV-460 Note 1 RC-CS-459 Control Switch with Indication F40 CB-F-3A-A 310882 E89/17a E89/17c E89/17d RC-LY-459B Pilot Solenoid GE5 C-F-1-Z Regen. Heat

Exchanger Letdown

Isolation Valve

(Outside Missile

Barrier) RC-ZS-LCV-459 Valve Position Switch L99 C-F-1-Z CS-ZS-V145 Valve Position Switch LH2 C-F-1-Z F40-H36 GE5-L99 GE5-H36/2 GE5-LH2/1 L99-LH2 F40-FB1/2 F40-G5X E4F-G5X E89-34F/8 RC-LY/459-CX1 Level Auxiliary Relay FB1 CB-F-3A-A RC-E4F-FU Fuses E4F CB-F-1A-A RC-SS-459 Selector Switch G5X DG-F-2A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A 4 RC-LCV-460 RC-20843 A 310577 C-F-1-Z X X X X LF7 RC-E89/1-72 125 V DC Circuit Breaker E89 CB-F-1A-A CBA-FN-19 CBA-FN-20 RC-LCV-459 Note 1 RC-CS-460 Control Switch with Indication F40 CB-F-3A-A Regen. Heat

Exchanger Letdown

Isolation Valve

(Inside Missile

Barrier) RC-LY-460E Pilot Solenoid GE4 C-F-1-Z 310882 E89/1b E89/1d E89/1e E89/1f RC-ZS-LCV-460 Valve Position Switch LF7 C-F-1-Z GE4-H36 GE4-LF7/1 E89-E4F E4F-F40 F40-FB1 F40-H36/1 F40-H36/3 GE4-LH2 RC-LY/460-DX1 Level Auxiliary Relay FB1 CB-F-3A-A FC-E4F-FU Fuses E4F CB-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A CS-ZS-V145 Valve Position Switch LH2 C-F-1-Z

.1. Electrical power and air are not required for support since the valve fails closed. 2. During normal operation, the valve is in its hot shutdown position. To prevent spurious operation, this equipment is permanently disabled (circuit breaker tripped). 
3. These valves are fail open diaphragm valves. See Section 3.5.3.1.c for analysis.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-2 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 RC-FV-2881 RC-20845 B 310581 C-F-3-Z X X X X U04 RC-E88/1-72 125 V Circuit Breaker E88 CB-F-1B-A RC-V323 Note 1 Reactor Head

Vent. Sol. Valve RC-CS-2881 Control Switch with Indication F31 CB-F-3A-A CBA-FN-32

CBA-FN-33

RC-FV-2881 Solenoid Valve U04 C-F-3-Z 310882 E88/1g E88/1d E88/1e E88/1f RC-GNO-R7 Auxiliary Relay GN0 CB-F-1B-A E88-E4C/4 E4C-GN0/5 F31-GN0 F31-G5Y F31-H41/1 H41/UO4 RC-ZS-FV-2881 Valve Position Switch UO4 C-F-3-Z RC-E4C-FU Fuses E4C CB-F-1B-A RC-SS-2881 Selector Switch G5Y DG-F-2B-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A H39-U04 F26-H39 6 RC-V-323 Reactor Head Venting Valve RC-20845 B 310581 C-F-3-Z X X X - VB2 RC-BV9-52-1 460 V AC Circuit Breaker BV9 CB-F-1B-A CBA-FN-32 CBA-FN-33 RC-FV-2881 RC-BV9-52-2 460 V AC Circuit Breaker BV9 CB-F-1B-A 310882 BV9a BV9c BV9d RC-CS-2885 Control Switch with Indication F31 CB-F-3A-A RC-BV9-42-1(0) Motor Starter (Open) BV9 CB-F-1B-A BV9-F31 BV9-H41 BV9-H15 F31-H41/2 H41-VB2 H41-VB2/1 H15-VB2 RC-BV9-42-1(C) Motor Starter (Close) BV9 CB-F-1B-A RC-BV9-42-2 Motor Starter BV9 CB-F-1B-A RC-BV9-49-1 Overload Relay BV9 CB-F-1B-A RC-BV9-49-2 Overload Relay BV9 CB-F-1B-A RC-ZS-V323 Valve Position Switch and Valve Open/Close

Torque Switches VB2 C-F-3-Z EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A RC-BV9-FU Fuse BV9 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-3 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 RC-V-22 RHR Inlet Isolation Valve RC-20841 B 310582 C-F-1-Z D D X - V27 RC-B54-52-1 460 V AC Circuit Breaker B54 CB-F-1B-A RC-V-23 Note 2 RC-B54-52-2 460 V AC Circuit Breaker B54 CB-F-1B-A 310882 B54a B54c B54d RC-CS-7302-1 Control Switch With Indication F20 CB-F-3A-A RC-CS-7302-2 Control Switch With Indication G2J CB-F-1B-A RC-SS-7302 Selector Switch G2J CB-F-1B-A RC-B54-42-1(0) Motor Starter (Open) B54 CB-F-1B-A B54-G2J B54-G2J/1 B54-H24 B54-H39 B54-V53 F20-G2J H24-V27 H39-V27 F20-FF9/2 RC-B54-42-1(C) Motor Starter (Close) B54 CB-F-1B-A RC-B54-42-2 Motor Starter B54 CB-F-1B-A RC-B54-49-1 Overload Relay B54 CB-F-1B-A RC-B54-49-2 Overload Relay B54 CB-F-1B-A RC-FF9-K-734B SSPC Output Relay FF9 CB-F-3A-A RC-ZS-7302B Valve Position Switch and Valve Open/Close

Torque Switches V27 C-F-1-Z RH-ZS-2465B RH-V35 Position Switch V53 RHR-F-4B-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-ZL-7302-1 Pilot Light G2J CB-F-1B-A RC-ZL-7302-2 Pilot Light F20 CB-F-3A-A RC-B54-FU Fuse B54 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-4 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 8 RC-V-23 RHR Inlet Isolation Valve RC-20841 A 310576 C-F-1-Z D D X - V25 RC-B53-52-1 460 V AC Circuit Breaker B53 CB-F-1A-A RC-V-22 Note 2 RC-B53-52-2 460 V AC Circuit Breaker B53 CB-F-1A-A 310882 B53a B53c B53d RC-CS-7303-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-7303-2 Control Switch with Indication G2G CB-F-1A-A B53-G2G B53-G2G/1 B53-H19 B53-H36 B53-V53 F20-G2G F20-FF8/2 H19-V25 H36-V25/2 RC-SS-7303 Selector Switch G2G CB-F-1A-A RC-ZL-7303-1 Pilot Light G2G CB-F-1A-A RC-ZL-7303-2 Pilot Light F20 CB-F-3A-A RC-B53-42-1(O) Motor Starter (Open) B53 CB-F-1A-A RC-B53-42-1(C) Motor Starter (Close) B53 CB-F-1A-A RC-B53-42-2 Motor Starter B53 CB-F-1A-A RC-B53-49-1 Overload Relay B53 CB-F-1A-A RC-B53-49-2 Overload Relay B53 CB-F-1A-A RC-FF8-K-734A SSPS Output Relay FF8 CB-F-3A-A RC-ZS-V23 Valve Position Switch and Valve Open/Close

Torque Switches V25 C-F-1-Z RH-ZS-2465A RH-V35 Position Switch V53 RHR-F-4B-Z EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-B53-FU Fuse B54 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-5 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 RC-V-87 RHR Inlet Isolation Valve RC-20844 B 310582 C-F-1-Z D D X - V26 RC-B61-52-1 460 V AC Circuit Breaker B61 CB-F-1B-A RC-V-88 Note 2 RC-B61-52-2 460 V AC Circuit Breaker B61 CB-F-1B-A 310882 B61a B61c B61d RC-CS-7310-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-7310-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7310 Selector Switch G2J CB-F-1B-A B61-G2J B61-G2J/1 B61-H24 B61-H39 B61-V54 F20-G2J/1 F20-FF9/1 H24-V26 H39-V26/2 RC-ZL-7310-1 Pilot Light G2J CB-F-1B-A RC-ZL-7310-2 Pilot Light F20 CB-F-3A-A RC-B61-42-1(0) Motor Starter (Open) B61 CB-F-1B-A RC-B61-42-1(C) Motor Starter (Close) B61 CB-F-1B-A RC-B61-42-2 Motor Starter B61 CB-F-1B-A RC-B61-49-1 Overload Relay B61 CB-F-1B-A RC-B61-49-2 Overload Relay B61 CB-F-1B-A RC-FF9-K-734B SSPS Output Relay FF9 CB-F-3A-A RC-ZS-V87 Valve Position Switch and Valve Open/Close

Torque Switches V26 C-F-1-Z RH-ZS-2466B RH-E-9B to SI Pump Isolation Valve

RH-V36 Position

Switch V54 RHR-F-2A-Z EDE-MM-100 Electrical Penetration H24 C-F-2-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-2-Z, ET-F-1C-A RC-B61-FU Fuse B61 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-6 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 10 RC-V-88 RHR Inlet Isolation Valve RC-20844 A 310577 C-F-1-Z D D X - V28 RC-B62-52-1 460 V AC Circuit Breaker B62 CB-F-1A-A RC-V-87 Note 2 RC-B62-52-2 460 V AC Circuit Breaker B62 CB-F-1A-A 310882 B62a B62c B62d RC-CS-7311-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-7311-2 Control Switch with Indication G2G CB-F-1A-A B62-G2G B62-G2G/1 B62-H19 B62-H36 B62-V54 F20-G2G/1 F20-FF8/3 H19-V28 H36-V28 RC-SS-7311 Selector Switch G2G CB-F-1A-A RC-ZL-7311-1 Pilot Light G2G CB-F-1A-A RC-ZL-7311-2 Pilot Light F20 CB-F-3A-A RC-B62-42-1(O) Motor Starter (Open) B62 CB-F-1A-A RC-B62-42-1(C) Motor Starter (Close) B62 CB-F-1A-A RC-B62-42-2 Motor Starter B62 CB-F-1A-A RC-B62-49-1 Overload Relay B62 CB-F-1A-A RC-B62-49-2 Overload Relay B62 CB-F-1A-A RC-FF9-K-734A SSPS Output Relay FF8 CB-F-3A-A RC-ZS-7311A Valve Position Switch and Valve Open/Close

Torque Switches V28 C-F-1-Z RH-ZS-2466A RH-E-9B to SI Pump Isolation Valve

RH-V36 Position

Switch V54 RHR-F-2A-Z EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-B62-FU Fuse B62 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-7 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 RC-PCV-456A RC-20846 A 310581 C-F-3-Z X X X X LD3 RC-E87/19-72 125 V DC Circuit Breaker E87 CB-F-1A-A RC-V122 Note 1 RC-E-10 Pressurizer

Relief Control

Valve RC-CS-456A-1 Control Switch with Indication F31 CB-F-3A-A 310882 E87/19a E87/19c E87/19d CBA-FN-19

CBA-FN-20 DAH-FN-25A

DAH-FN-26A RC-CS-456A-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-456A-1 Selector Switch G81 CB-F-1A-A RC-PCV-456A-20 Solenoid Operated Valve LD3 C-F-3-Z RC-ZS-PCV-456A Valve Position Switch LD3 C-F-3-Z F38-FB1/2 F38-G81/1 G81-H35 H35-X56/2 LD3-X56 E87-E4A/4 E4A-J3M G5X-J3M H18-J3M H18-LD3 G81-J3M F38-G5X RC-PY-405CX Auxiliary Relay FB1 CB-F-3A-A RC-PY-455EX Auxiliary Relay FB1 CB-F-3A-A RC-PY-458BX Auxiliary Relay FB1 CB-F-3A-A RC-TY-413KX Auxiliary Relay FB1 CB-F-3A-A RC-SS-456A-2 Selector Switch G5X DG-F-2A-A RC-J3M-42 125 V DC Contactor J3M DG-F-2A-A RC-E4A-FU Fuses E4A CB-F-1A-A EDE-TBX-X56 Terminal Box X56 C-F-3-Z EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-8 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 12 RC-PCV-456B RC-20846 B 310581 C-F-3-Z X X X X LD4 RC-E88/19-72 125 V DC Circuit Breaker E88 CB-F-1B-A RC-V124 Note 1 RC-E-10 Pressurizer

Relief Control

Valve RC-CS-456B-1 Control Switch with Indication F31 CB-F-3A-A 310882 E88/19a E88/19c E88/19d RC-CS-456B-2 Control Switch with Indication GZ0 CB-F-1B-A CBA-FN-32

CBA-FN-33 DAH-FN-25B

DAH-FN-26B RC-SS-456B-1 Selector Switch GZ0 CB-F-1B-A RC-PCV-456B-20 Solenoid Operated Valve LD4 C-F-3-Z RC-ZS-PCV-456B Valve Position Switch LD4 C-F-3-Z RC-FT0-KA7 Isolation Relay FT0 CB-F-3A-A F31-FT0/2 F31-GZ0/2 GZ0-H39 H39-X35 LD4-X35 GZ0-J3P E88-E4C/7 E4C-J3P G5Y-J3P H24-J3P H24-LD4 E4C-GZ0/2 F31-G5Y/1 RC-SS-456B-1 Selector Switch G5Y DG-F-2B-A RC-J3P-42 125 V DC Contactor J3P DG-F-2B-A RC-E4C-FU Fuses E4C CB-F-1B-A EDE-TBX-X35 Terminal Box X35 C-F-3-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A 13 RC-V-122 RC-20846 A 310581 C-F-3-Z X X X - V01 RC-B97-52-1 460 V AC Circuit Breaker B97 CB-F-1A-A RC-PCV-456A RC-E-10 Pressurizer

Relief Isolation

Valve RC-B97-52-2 460 V AC Circuit Breaker B97 CB-F-1A-A 310882 B97a B97c B97e B97d EDE-MCC-521 CBA-FN-19

CBA-FN-20 RC-CS-7313-1 Control Switch with Indication F31 CB-F-3A-A RC-CS-7313-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-7313 Selector Switch G81 CB-F-1A-A B97-H18 B97-H35 ED1-F38 H18-V01 H35-X56 V01-X56 F38-G81/2 F38-G81/3 B97-G81 B97-G81/1 RC-B97-FU Fuse B97 CB-F-1A-A RC-B97-42-1(O) Motor Starter (Open) B97 CB-F-1A-A RC-B97-42-1(C) Motor Starter (Close) B97 CB-F-1A-A RC-B97-42-2 Motor Starter B97 CB-F-1A-A RC-B97-49-1 Overload Relay B97 CB-F-1A-A RC-B97-49-2 Overload Relay B97 CB-F-1A-A RC-ZS-V122 Valve Position Switch and Valve Open/Close

Torque Switches V01 C-F-3-Z RC-ED1-R1 Auxiliary Relay ED1 CB-F-1A-A EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A EDE-TBX-X56 Terminal Box X56 C-F-3-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table 3.3.2-9 FUNCTION: HIGH-LOW PRESSURE BOUNDARIES . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 14 RC-V-124 RC-20846 B 310581 C-F-3-Z X X X - V02 RC-B98-52-1 460 V AC Circuit Breaker B98 CB-F-1B-A RC-PCV-456B RC-E-10 Pressurizer

Relief Control

Valve RC-B98-52-2 460 V AC Circuit Breaker B98 CB-F-1B-A RC-CS-7314-1 Control Switch with Indication F31 CB-F-3A-A 310882 B98a B98c B98e B98d EDE-MCC-621 CBA-FN-32

CBA-FN-33 RC-CS-7314-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-7314 Selector Switch GZ0 CB-F-1B-A RC-B98-42-1(O) Motor Starter (Open) B98 CB-F-1B-A B98-H15 B98-H41 F31-FT0/1 H15-V02 H41-X35 V02-X35 B98-GZ0 B98-GZ0/1 F31-GZ0/5 F31-GZ0/6 B98/GZ0/2 RC-B98-42-1(C) Motor Starter (Close) B98 CB-F-1B-A C-B98-42-2 Motor Starter B98 CB-F-1B-A RC-B98-49-1 Overload Relay B98 CB-F-1B-A RC-B98-49-2 Overload Relay B98 CB-F-1B-A RC-ZS-V124 Valve Position Switch and Valve Open/Close

Torque Switches V02 C-F-3-Z RC-FT0-KA6 Isolation Relay FT0 CB-F-3A-A EDE-MM-91 Electrical Penetration H15 C-F-2-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A EDE-TBX-X35 Terminal Box X35 C-F-3-Z RC-B98-FU Fuses B98 CB-F-1B-A 15 CS-V-10 Reactor Coolant Pump Seal Leakoff

Isolation Valve CS-20726 A 310576 C-F-1-Z X X X X LA6 Note 3 16 CS-V-28 Reactor Coolant Pump Seal Leakoff

Isolation Valve CS-20726 A 310576 C-F-1-Z X X X X LA7 Note 3 17 CS-V-44 Reactor Coolant Pump Seal Leakoff

Isolation Valve CS-20726 A 310583 C-F-1-Z X X X X LA8 Note 3 18 CS-V-59 Reactor Coolant Pump Seal Leakoff

Isolation Valve CS-20726 A 310577 C-F-1-Z X X X X LA9 Note 3

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50. Appendix R P & I Diagrams (Typical) Rev 5 Appendix I Page I-1 P & I DIAGRAMS (TYPICAL) This section originally contained photographs of the marked P & I Diagrams for the decay heat removal safe shutdown function. These drawings were typical of the P & I Diagrams which were marked for each safe shutdown function and not all inclusive, thus they have been removed from this appendicies. The typical diagrams included in this section were only to show the methodology used for the original report preparation and were not in tended to be updated for report revisions. The latest design documents, not these typical drawings, should be used to evaluate the Safe Shutdown Capability. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50. Appendix R Schematic Diagrams & Cable Schematics (Typical) Rev 5 Appendix II Page II-1 Schematic Diagrams & Cable Schematics (Typical) This section originally contained drawings that were typical of those which were marked for each safe shutdown function. The typical drawings in cluded in this section were only to show the methodology used for the original report preparation. These typical drawings were not intended to be updated for report revision. The original drawings were provided to show marked-up electrical schematic diagrams, cable schematics, and cable tables for the Train A decay heat removal safe shutdown function. The drawings were marked by shading and by cross-hatching. The equipment and cables which were shaded were isolated by a "Local Remote" selector switch or other isolation device and were not considered for further review. The equipment and cables which have been cross-hatched were analyzed, and it was determined that there was no effect on safe shutdown capability. These equipment and cables were not considered for further review. The latest design documents, not these typical drawings, should be used to evaluate the Safe Shutdown Capability. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Equipment Lists (Tables) Rev. 10 Appendix III Page III-1 Equipment Lists (Tables) This section contains the following tables which list all equipment required for performance of the safe shutdown function. Main Control Room Function Table Number Decay Heat Removal MCR 3.1.3.1 Reactor Coolant Inventory and Pressure Control MCR 3.1.3.2 Reactivity Control MCR 3.1.3.3 Process Monitoring MCR 3.1.3.4 Safeguard Actuation System MCR 3.1.3.5 Cold Shutdown MCR 3.1.3.6 Service Water MCR 3.1.3.7 Primary Component Cooling Water MCR 3.1.3.8 Containment Building Air Handling MCR 3.1.3.9 Control Building Air Handling MCR 3.1.3.10 Diesel Generator Building Air Handling MCR 3.1.3.11 Containment Enclosure Air Handling MCR 3.1.3.12 Emergency Feedwater Pumphouse Air Handling MCR 3.1.3.13 Primary Auxiliary Building Air Handling MCR 3.1.3.14 Service Water Air Handling MCR 3.1.3.15 Service/Instrument Air MCR 3.1.3.16 Electrical Distribution Emergency MCR 3.1.3.17 Diesel Generators MCR 3.1.3.18

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Equipment Lists (Tables) Rev. 10 Appendix III Page III-2 Alternative Safe Shutdown Function Table Number Decay Heat Removal RSS 3.1.3.1 Reactor Coolant Inventory and Pressure Control RSS 3.1.3.2 Reactivity Control RSS 3.1.3.3 Process Monitoring RSS 3.1.3.4 Safeguards Actuation RSS 3.1.3.5 Cold Shutdown RSS 3.1.3.6 Service Water RSS 3.1.3.7 Primary Component Cooling Water RSS 3.1.3.8 Deleted RSS 3.1.3.9 Control Building Air Handling RSS 3.1.3.10 Diesel Generator Building Air Handling RSS 3.1.3.11 Containment Enclosure Air Handling RSS 3.1.3.12 Emergency Feedwater Pumphouse Air Handling RSS 3.1.3.13 Primary Auxiliary Building Air Handling RSS 3.1.3.14 Service Water Air Handling RSS 3.1.3.15 Deleted RSS 3.1.3.16 Electrical Distribution Emergency RSS 3.1.3.17 Diesel Generators RSS 3.1.3.18 Communication RSS 3.1.3.19 Emergency Feedwater Pumphouse Building 3.2.3 High-Low Pressure Boundaries 3.3.2 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -1 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CO-TK-25 Condensate Storage Tank CO-20426 A/B 310248 CST-F-1-0 X X - - - - - - - - - - - - Note 1 2 FW-P-113 Start-Up Feedwater Pump CO-20426 A 310326 TB-F-1A-Z X X X - N12 FW-A93-52 4160 V AC Circuit Breaker A93 CB-F-1A-1 A47-A93 A47-A93/1 A47-A93/2 A47-A93/3 A47-N12 A47-P82 A93-F60/1 A93-F60/2 A93-F60/3 A93-F50/4 A93-ED7 A93-G8L A93-HR2 G8L-P2V (Non-CASP) 310844 A93a A93g A93b A93h A93c A93d A47a A47g EDE-SWG-5 CBA-FN-19 CBA-FN-20 FW-P-37B FW-A93-FU Fuses A93 CB-F-1A-A FW-CS-4268-1 Control Switch with Indication F60 CB-F-3A-A FW-SS-4268 Selector Switch A47 NES-F-1A-Z FW-A93-CS Test Control Switch A93 CB-F-1A-A FW-A93-G, R, W Indicating Lights A93 CB-F-1A-A EDE-A53-94-2 Bus Undervoltage A53 CB-F-1A-A FW-A93-R1 Auxiliary Relay A93 CB-F-1A-A FW-PSLH-PS5 Lube Oil Pressure Switch P82 TB-F-1A-Z FW-A93-PS5X Pressure Switch Auxiliary Relay A93 CB-F-1A-A FW-A93-52S Mechanically Operated Contact A93 CB-F-1A-A FW-A93-52H Truck-Operated Contact A93 CB-F-1A-A FW-A93-62 PS5 Starting Blocking Time Delay Relay A93 CB-F-1A-A FW-ED7-2 Prelube Pump Starting Auxiliary Time Delay Relay ED7 TB-F-2-Z FW-A93-R2 Auxiliary Relay A93 CB-F-1A-A FW-A93-86 Lockout Relay A93 CB-F-1A-A FW-A93-TD2 Lockout Relay Test Device A93 CB-F-1A-A FW-A93-CT Current Transformers 300/5A A93 CB-F-1A-A FW-A93-TD1 CT Test Device A93 CB-F-1A-A FW-A93-50/51 Inst/Time Overcurrent Relays øA, øC A93 CB-F-1A-A FW-A93-AM Ammeter A93 CB-F-1A-A FW-A93-AS Ammeter Switch A93 CB-F-1A-A FW-A93-ATR Transducer A93 CB-F-1A-A FW-AM-4268-1 Ammeter F60 CB-F-3A-A

. NOTES 1. The equipment is mechanical with no electrical requirement.
2. Air is not needed to position or to reposition the valve for safe shutdown.
3. During normal operation, this equipment is in its safe shutdown position (locked closed) with its circuit breaker administratively controlled locked open (off) to prevent its spurious operation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -2 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 FW-P-113 Start-Up Feedwater Pump FW-A47-52 4160 V AC Circuit Breaker A47 NES-F-1A-Z (Continued) FW-A93-S1GS Ground Sensor Relay A93 CB-F-1A-A FW-PSL-4233-2 Pressure Switch Low Suction P2V TB-F-1A-Z FW-CS-4233 Suction Pressure Bypass Switch G8L TB-F-1A-Z FW-HR2-RMO EPS Manual Override Relay (K27) HR2 CB-F-1A-A 3 FW-P-161 Start-Up Feedwater Pump FW-P-113 Prelube Pump CO-20426 A 310326 TB-F-1A-Z X X X - NU0 FW-CN1-52 460 V AC Circuit Breaker CN1 TB-F-2-Z CN1-NUO CN1-F60 CN1-P81 A47-F60/4 EA1-F60 F60-FB7/5 310884 CN1a CN1c EDE-MCC-523 None FW-CN1-FU Fuse CN1 TB-F-2-Z FW-CS-4268 Control Switch with Indication F60 CB-F-3A-A FW-SS-4268 Selector Switch A47 NES-F-1A-Z FW-CS-4268-1 Control Switch with Indication F60 CB-F-3A-A FW-CS-4278 Control Switch F60 CB-F-3A-A FW-ED7-2 Pump Starting Time Delay Relay ED7 TB-F-2-Z FW-PSLH-PS4 Lube Oil Pressure Switch P81 TB-F-1A-Z FW-CN1-42 Motor Starter CN1 TB-F-2-Z FW-CN1-49 Overload Relays CN1 TB-F-2-Z FW-FB7-K620A SSPS Output Relay FB7 CB-F-3A-A FW-ED7-3 Time Delay Relay ED7 TB-F-2-2 FW-J8K-K5R, S, T GE MK Vle TMR Relay J8K TB-F-2-Z EA1-J9M/1 J8M-J9M FW-J9K-K5R, S, T GE MK Vle TMR Relay J9K TB-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -3 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 FW-V-156 Start-Up Feed Pump to EFW Header Valve FW-20688 A 310589 MS-F-1B-Z X X X - V3L FW-B4S-52 460 V AC Circuit Breaker B4S CB-F-1A-A B4S-V3L B4S-V3L/1 B4S-F60 B4S-F60/1 310844 B4Sa B4Sc CBA-FN-19 CBA-FN-20 EDE-MCC-531 None FW-B4S-FU Fuse B4S CB-F-1A-A FW-CS-4261 Control Switch with Indication F60 CB-F-3A-A FW-B4S-42/0,C Motor Starters B4S CB-F-1A-A FW-B4S-49 Overload Relays B4S CB-F-1A-A FW-ZS-V156 Valve Position and Open/Close Torque Switches V3L MS-F-1B-Z 4A FW-V-163 Start-Up Feed Pump Bypass to EFW Pump Valve FW-20687 A 310326 TB-F-1A-Z X X X - V3M FW-C2R-52 460 V AC Circuit Breaker C2R TB-F-2-Z C2R-V3M C2R-V3M/1 C2R-F60 310884 CN1a CN1c EDE-MCC-523 None FW-C2R-FU Fuse C2R TB-F-2-Z FW-CS-4262 Control Switch with Indication F60 CB-F-3A-A FW-C2R-42/0,C Motor Starter C2R TB-F-2-Z FW-C2R-49 Overload Relays C2R TB-F-2-Z FW-ZS-V163 Valve Position and Open/Close Torque Switches V3M TB-F-1A-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -4 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 FW-P-37B Emergency Feed Pump FW-20688 B 310708 EFP-F-1-A X X X - N14 FW-A80-52 4160 V AC Circuit Breaker A80 CB-F-1B-A A80-N14 A80-F66/1 A80-F66/2 A80-HR4 FBO-HR4 FBO-FT0/1 310844 A80a A80h A80b A80c A80d CBA-FN-32 CBA-FN-33 EPA-FN-47B EDE-SWG-6 FW-P-113 FW-A80-FU Fuses A80 CB-F-1B-A FW-A80-R Auxiliary Relay A80 CB-F-1B-A FW-CS-4255-2 Control Switch A80 CB-F-1B-A FW-SS-4255 Selector Switch A80 CB-F-1B-A EDE-A73-94-1B Bus Under Voltage Relay A73 CB-F-1B-A FW-A80-86 Lockout Relay A80 CB-F-1B-A FW-A80-52H Truck-Operated Contact A80 CB-F-1B-A FW-A80-50/51 Instrument/Time Overcurrent Relays øA, øC A80 CB-F-1B-A FW-A80-AM Ammeter A80 CB-F-1B-A FW-A80-AS Ammeter Switch A80 CB-F-1B-A FW-A80-CT Current Transformers (200/5) A80 CB-F-1B-A FW-A80-TD1 CT Test Device A80 CB-F-1B-A FW-A80-ATR Transducer A80 CB-F-1B-A FW-A80-TD2 Lockout Relay Test Device A80 CB-F-1B-A FW-A80-G,R,W,A Indicating Lights A80 CB-F-1B-A FW-A80-52Z Time Delay Relay A80 CB-F-1B-A FW-A80-51GS Ground Sensor Relay A80 CB-F-1B-A FW-CS-4255-1 Control Switch F60 CB-F-3A-A FW-EPS-SR6 Emergency Power Sequencer HR0 CB-F-1B-A FW-EPS-PR1,RMO Emergency Power Sequencer HR4 CB-F-1B-A FW-FB0-K615B,K640B Auxiliary Relays FB0 CB-F-3A-A EDE-FT0-KA24 Isolation Relay FT0 CB-F-3A-A 5A FW-V347 Emergency Feedwater Recirculating Valve FW-20688 B 310708 EFP-F-1-A X X X - V4P FW-C3T-52 460 V AC Circuit Breaker C3T CB-F-1B-A C3T-V4P C3T-V4P/1 C3T-G2J F66-G2J/6 310884 CN1a CN1c EDE-MCC-523 None FW-C3T-FU Fuses C3T CB-F-1B-A FW-CS-4369-2 Control Switch with Indication G2J CB-F-1B-A MS-SS-3064 Selector Switch G2J CB-F-1B-A FW-C3T-42/0,C Motor Starters C3T CB-F-1B-A FW-C3T-49 Overload Relays C3T CB-F-1B-A FW-ZS-V347 Valve Position Switch V4P EFP-F-1-A FW-CS-4369-1 Control Switch with Indication F60 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -5 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 FW-FV-4214A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2E FW-B3V-52 460 V AC Circuit Breaker B3V CB-F-1A-A B3V-V2E B3V-V2E/1 E3C-G2G G2G-V2E B3V-G5X B3V-G5X/1 E3C-FN6 F51-FN6 FN6-G5X FN6-G5X/1 310844 B3Va B3Vd B3Ve CBA-FN-19 CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-FV-4214-B FW-B3V-FU Fuse B3V CB-F-1A-A FW-CS-4214-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4214-A Selector Switch G2G CB-F-1A-A FW-SS-4214-A1 Selector Switch G5X DG-F-2A-A FW-FN6-MSO-1 Auxiliary Relay FN6 CB-F-2B-A FW-B3V-42/0,C Motor Starters B3V CB-F-1A-A FW-B3V-49 Overload Relays B3V CB-F-1A-A FW-ZS-4214-A Valve Position Switch V2E EFP-F-1-A FW-FN6-4214AX Auxiliary Relay FN6 CB-F-2B-A FW-CS-4214-A1 Control Switch with Indication F51 CB-F-3A-A E3C-F51 F51-G2G FW-E3C-R1,R2,R3,R4 Auxiliary Relays E3C CB-F-1A-A E3C-FK0 E3C-FN6/4 FK0-FN6 FK0-FN6/1 E3E/1a, 1e E3E/1c FW-E3P-62-1 Timing Relay E3P CB-F-1A-A FW-E3P-62-2 Timing Relay E3P CB-F-1A-A FW-E3P-62-3 Timing Relay E3P CB-F-1A-A FW-E3P-62-4 Timing Relay E3P CB-F-1A-A FW-FN6-R1A Auxiliary Relay FN6 CB-F-2B-A MM-CP-297A "A" Train BOP -PCC FKO CB-F-3A-A E3C-F56 F56-FK0 F86-FK0 FK0-GL3 310952 FK0a FW-FR-4214 Flow Recorder F86 CB-F-3A-A FW-FT-4214-2 Flow Transmitter GL3 EFP-F-1A-A FW-FI-4214-2 Flow Indicators F56 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -6 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 FW-FV-4214B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2J FW-B3Z-52 460 V AC Circuit Breaker B3Z CB-F-1B-A B3Z-V2J B3Z-V2J/1 E3D-G2J G2J-V2J B3Z-G2J B3Z-G5Y B3Z-G5Y/1 E3D-FN7 F51-FN7 FN7-G5Y FN7-G5Y/1 310844 B3Za B3Zd B3Ze CBA-FN-32 CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-FV-4214-A FW-B3Z-FU Fuse B3Z CB-F-1B-A FW-CS-4214-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4214-B Selector Switch G2J CB-F-1B-A FW-SS-4214-B1 Selector Switch G5Y DG-F-2B-A FW-FN7-MSO-1 Auxiliary Relay FN7 CB-F-2C-A FW-B3Z-42/0,C Motor Starters B3Z CB-F-1B-A FW-B3Z-49 Overload Relays B3Z CB-F-1B-A FW-ZS-4214-B Valve Position Switch V2J EFP-F-1-A FW-FN7-4214BX Auxiliary Relay FN7 CB-F-2C-A FW-CS-4214-B1 Control Switch with Indication F51 CB-F-3A-A E3D-F51 F51-G2J FW-E3D-R1,R2,R3,R4 Auxiliary Relays E3D CB-F-1B-A E3D-FL2 E3D-FN7/4 FL2-FN7 FL2-FN7/1 E3F/1a, 1e E3F/1c FW-E3Q-62-1 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-2 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-3 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-4 Timing Relay E3Q CB-F-1B-A FW-FN7-R1B Auxiliary Relay FN7 CB-F-2C-A FW-FT-4214-4 Flow Transmitter GL4 EFP-F-1A-A E3D-F51/4 310952 FL2a MM-CP-297B "B" Train BOP -PCC FL2 CB-F-3A-A FL2-GL4 8 FW-FV-4224A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2F FW-B3W-52 460 V AC Circuit Breaker B3W CB-F-1A-A B3W-V2F B3W-V2F/1 E3C-G2G/1 G2G-V2F B3W-G5X B3W-G5X/1 E3C-FN6/1 F51-FN6/1 FN6-G5X/2 FN6-G5X/3 310844 B3Wa B3Wd B3We CBA-FN-19 CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-FV-4224-B FW-B3W-FU Fuse B3W CB-F-1A-A FW-CS-4224-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4224-A Selector Switch G2G CB-F-1A-A FW-SS-4224-A1 Selector Switch G5X DG-F-2A-A FW-FN6-MSO-2 Auxiliary Relay FN6 CB-F-2B-A FW-B3W-42/0,C Motor Starters B3W CB-F-1A-A FW-B3W-49 Overload Relays B3W CB-F-1A-A FW-ZS-4224-A Valve Position Switch V2F EFP-F-1-A FW-FN6-4224AX Auxiliary Relay FN6 CB-F-2B-A FW-CS-4224-A1 Control Switch with Indication F51 CB-F-3A-A E3C-F51/1 F51-G2G/1 FW-E3C-R1,R2,R3,R4 Auxiliary Relays E3C CB-F-1A-A E3C-FK0 E3C-F56 E3C-FN6/4 FK0-FN6 FK0-FN6/1 E3E/1a, 1e E3E/1c FW-E3P-62-1 Timing Relay E3P CB-F-1A-A FW-E3P-62-2 Timing Relay E3P CB-F-1A-A FW-E3P-62-3 Timing Relay E3P CB-F-1A-A FW-E3P-62-4 Timing Relay E3P CB-F-1A-A FW-FN6-R2A Auxiliary Relay FN6 CB-F-2B-A FW-FT-4224-4 Flow Transmitter GL3 EFP-F-1A-A 310952 FK0a MM-CP-297A "A" Train BOP -PCC FK0 CB-F-3A-A FK0-GL3 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -7 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 FW-FV-4224B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2K FW-B4A-52 460 V AC Circuit Breaker B4A CB-F-1B-A B4A-V2K B4A-V2K/1 E3D-G2J/1 G2G-V2K B4A-G2J B4A-G5Y B4A-G5Y/1 E3D-FN7/1 F51-FN7/1 FN7-G5Y/2 FN7-G5Y/3 310844 B4Aa B4Ad B4Ae CBA-FN-32 CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-FV-4224-A FW-B4A-FU Fuse B4A CB-F-1B-A FW-CS-4224-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4224-B Selector Switch G2J CB-F-1B-A FW-SS-4224-B1 Selector Switch G5Y DG-F-2B-A FW-FN7-MSO-2 Auxiliary Relay FN7 CB-F-2C-A FW-B4A-42/0,C Motor Starters B4A CB-F-1B-A FW-B4A-49 Overload Relays B4A CB-F-1B-A FW-ZS-4224-B Valve Position Switch V2K EFP-F-1-A FW-FN7-4224BX Auxiliary Relay FN7 CB-F-2C-A FW-CS-4224-B1 Control Switch with Indication F51 CB-F-3A-A E3D-F51/1 F51-G2J/1 FW-E3D-R1,R2,R3,R4 Auxiliary Relays E3Q CB-F-1B-A E3D-FL2 E3D-F51/4 E3D-FN7/4 FL2-FN7 FL2-FN7/1 E3F/1a, 1e E3F/1c FW-E3Q-62-1 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-2 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-3 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-4 Timing Relay E3Q CB-F-1B-A FW-FN7-R2B Auxiliary Relay FN7 CB-F-2C-A MM-CP-297B "B" Train BOP -PCC FL2 CB-F-3A-A 310952 FL2a FW-FR-4224 Flow Recorder F86 CB-F-3A-A F56-FL2 F88-FL2 FL2-GL4 FW-FT-4224-2 Flow Transmitter GL4 EFP-F-1A-A FW-FI-4224-2 Flow Indicator F56 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -8 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 10 FW-FV-4234A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2G FW-B3X-52 460 V AC Circuit Breaker B3X CB-F-1A-A B3X-V2G B3X-V2G/1 G2G-V2G E3C-G2G/2 B3X-G5X B3X-G5X/1 E3C-FN6/2 F51-FN6/2 FN6-G5X/4 FN6-G5X/5 310844 B3Xa B3Xd B3Xe CBA-FN-19 CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-FV-4234-B FW-B3X-FU Fuse B3X CB-F-1A-A FW-CS-4234-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4214-A Selector Switch G2G CB-F-1A-A FW-SS-4214-A1 Selector Switch G5X DG-F-2A-A FW-FN6-MSO-3 Auxiliary Relay FN6 CB-F-2B-A FW-B3X-42/0,C Motor Starters B3X CB-F-1A-A FW-B3X-49 Overload Relays B3X CB-F-1A-A FW-ZS-4234-A Valve Position Switch V2G EFP-F-1-A FW-FN6-4234AX Auxiliary Relay FN6 CB-F-2B-A FW-CS-4234-A1 Control Switch with Indication F51 CB-F-3A-A E3C-F51/2 F51-G2G/2 FW-E3C-R1,R2,R3,R4 Auxiliary Relays E3C CB-F-1A-A E3C-FK0 E3C-FN6/4 FK0-FN6 FK0-FN6/1 E3E/1a, 1e E3E/1c FW-E3P-62-1 Timing Relay E3P CB-F-1A-A FW-E3P-62-2 Timing Relay E3P CB-F-1A-A FW-E3P-62-3 Timing Relay E3P CB-F-1A-A FW-E3P-62-4 Timing Relay E3P CB-F-1A-A FW-FN6-R3A Auxiliary Relay FN6 CB-F-2B-A MM-CP-297A "A" Train BOP-PCC FK0 CB-F-3A-A E3C-F56 FK0-GL3 F56-FK0 F86-KF0 310952 FK0a FW-FR-4214 Flow Recorder F86 CB-F-3A-A FW-FT-4234-2 Flow Transmitter GL3 EFP-F-1A-A FW-FI-4234-2 Flow Indicator F56 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -9 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 FW-FV-4234B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2L FW-B4B-52 460 V AC Circuit Breaker B4B CB-F-1B-A B4B-V2L B4B-V2L/1 E3D-G2J/2 G2J-V2L B4B-G2J B4B-G5Y B4B-G5Y/1 E3D-FN7/2 F51-FN7/2 FN7-G5Y/4 FN7-G5Y/5 310844 B4Ba B4Bd B4Be CBA-FN-32 CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-FV-4234-A FW-B4B-FU Fuse B4B CB-F-1B-A FW-CS-4234-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4214-B Selector Switch G2J CB-F-1B-A FW-SS-4214-B1 Selector Switch G5Y DG-F-2B-A FW-FN7-MSO-3 Auxiliary Relay FN7 CB-F-2C-A FW-B4B-42/0,C Motor Starters B4B CB-F-1B-A FW-B4B-49 Overload Relays B4B CB-F-1B-A FW-ZS-4234-B Valve Position Switch V2L EFP-F-1-A FW-FN7-4234BX Auxiliary Relay FN7 CB-F-2C-A FW-CS-4234-B1 Control Switch with Indication F51 CB-F-3A-A E3D-F51/2 F51-G2J/2 E3F/1a, 1e E3F/1c FW-E3D-R1,R2,R3,R4 Auxiliary Relays E3D CB-F-1B-A E3D-FL2 E3D-F51/4 E3D-FN7/4 FL2-FN7 FL2-FN7/1 FW-E3Q-62-1 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-2 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-3 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-4 Timing Relay E3Q CB-F-1B-A FW-FN7-R3B Auxiliary Relay FN7 CB-F-2C-A FW-FT-4234-4 Flow Transmitter GL4 EFP-F-1A-A FL2-GL4 MM-CP-297B "B" Train BOP -PCC FL2 CB-F-3A-A 310952 FL2a 12 FW-FV-4244A Emergency Feedwater Header Flow Valve FW-20688 A 310708 EFP-F-1-A X X X - V2H FW-B3Y-52 460 V AC Circuit Breaker B3Y CB-F-1A-A B3Y-V2H B3Y-V2H/1 E3C-G2G/3 G2G-V2H B3Y-G5X B3Y-G5X/1 E3C-FN6/3 F51-FN6/3 FN6-G5X/6 FN6-G5X/7 310844 B3Ya B3Yd B3Ye CBA-FN-19 CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-FV-4244-B FW-B3Y-FU Fuse B3Y CB-F-1A-A FW-CS-4244-A2 Control Switch with Indication G2G CB-F-1A-A FW-SS-4224-A Selector Switch G2G CB-F-1A-A FW-SS-4224-A1 Selector Switch G5X DG-F-2A-A FW-FN6-MSO-4 Auxiliary Relay FN6 CB-F-2B-A FW-B3Y-42/0,C Motor Starters B3Y CB-F-1A-A FW-B3Y-49 Overload Relays B3Y CB-F-1A-A FW-ZS-4244-A Valve Position Switch V2H EFP-F-1-A FW-FN6-4244AX Auxiliary Relay FN6 CB-F-2B-A FW-CS-4244-A1 Control Switch with Indication F51 CB-F-3A-A E3C-F51/3 F51-G2G/3 FW-E3C-R1,R2,R3,R4 Auxiliary Relays E3C CB-F-1A-A E3C-FK0 E3C-F56 E3C-FN6/4 FK0-FN6 FK0-FN6/1 E3E/1a, 1e E3E/1c FW-E3P-62-1 Timing Relay E3P CB-F-1A-A FW-E3P-62-2 Timing Relay E3P CB-F-1A-A FW-E3P-62-3 Timing Relay E3P CB-F-1A-A FW-E3P-62-4 Timing Relay E3P CB-F-1A-A FW-FN6-R4A Auxiliary Relay FN6 CB-F-2B-A FW-FT-4244-4 Flow Transmitter GL3 EFP-F-1A-A FK0-GL3 310952 FK0a MM-CP-279A "A" Train BOP -PCC FK0 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -10 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 FW-FV-4244B Emergency Feedwater Header Flow Valve FW-20688 B 310708 EFP-F-1-A X X X - V2M FW-B4C-52 460 V AC Circuit Breaker B4C CB-F-1B-A B4C-V2M B4C-V2M/1 E3D-G2J/3 GJ2-V2M B4C-G2J B4C-G5Y B4C-G5Y/1 E3D-FN7/3 F51-FN7/3 FN7-G5Y/6 FN7-G5Y/7 310844 B4Ca B4Cd B4Ce CBA-FN-32 CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-FV-4244-A FW-B4C-FU Fuse B4C CB-F-1B-A FW-CS-4244-B2 Control Switch with Indication G2J CB-F-1B-A FW-SS-4224-B Selector Switch G2J CB-F-1B-A FW-B4C-42/0,C Motor Starters B4C CB-F-1B-A FW-SS-4224-B1 Selector Switch G5Y DG-F-2B-A FW-FN7-MSO-4 Auxiliary Relay FN7 CB-F-2C-A FW-B4C-49 Overload Relays B4C CB-F-1B-A FW-ZS-4244-B Valve Position Switch V2M EFP-F-1-A FW-E3D-4244BX Auxiliary Relay E3D CB-F-1B-A FW-FN7-4244BX Control Switch with Indication FN7 CB-F-2C-A E3D-F51/3 F51-G2J/3 FW-E3D-R1,R2,R3,R4 Auxiliary Relays E3D CB-F-1B-A E3D-FL2 E3D-F51/4 E3D-FN7/4 FL2-FN7 FL2-FN7/1 E3F/1a, 1e E3F/1c FW-E3Q-62-1 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-2 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-3 Timing Relay E3Q CB-F-1B-A FW-E3Q-62-4 Timing Relay E3Q CB-F-1B-A FW-FN7-R4B Auxiliary Relay FN7 CB-F-2C-A MM-CP-297B "B" Train BOP -PCC FL2 CB-F-3A-A FL2-GL4 F56-FL2 F88-FL2 310952 FL2a FW-FR-4224 Flow Recorder F86 CB-F-3A-A FW-FT-4244-2 Flow Transmitter GL4 EFP-F-1A-A FW-FI-4244-2 Flow Indicator F56 CB-F-3A-A 14 MS-PV-3001 Main Steam Header MS-20580 A/B 310589 MS-F-2B-Z X X X X V2N MS-E2T/8-72 125 V DC Circuit Breaker E2T CB-F-1A-A G2G-V2N F60-G2G/9 E2T-G5X G2G-C5X FN8-U0A FN8-U0B FN8-G2G/1 F60-FN8 310841 E2T/8a E2T/8e E2T/8f CBA-FN-19 CBA-FN-20 EDE-PP-113A INST AIR MS-PV-3002 or MS-PV-3004 MS-SS-3001-2 Selector Switch G5X DG-F-2A-A MS-PY-3001-1 Solenoid Valve UOA MS-F-2B-Z MS-PY-3001-2 Solenoid Valve U0A MS-F-2B-Z MS-PY-3001-3 Solenoid Valve U0B MS-F-2B-Z MS-PY-3001-4 Solenoid Valve U0B MS-F-2B-Z MS-CS-3001-1 Control Switch with Indication F60 CB-F-3A-A MS-CS-3001-2 Control Switch with Indication G2G CB-F-1A-A MS-SS-3001-3 Selector Switch FN8 ET-F-1B-A MS-SS-3001-1 Selector Switch G2G CB-F-1A-A MS-ZS-3001-A Valve Position Switch V2N MS-F-2B-Z MS-PY-3001-5 Solenoid Valve U0C MS-F-2B-Z E2U-F66 F66-U0C 310841 E2U/15 E2U/15 EDE-PP-113B MS-PY-3001-6 Solenoid Valve U0C MS-F-2B-Z MS-E2U/15-72 125 V DC Circuit Breaker E2U CB-F-1B-A MS-CS-3001-1 Control Switch F60 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -11 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 MS-PV-3003 Main Steam Header Atmospheric Relief Valve MS-20580 A/B 310586 MS-F-2A-Z X X X X V2Q MS-SS-3003-2 Selector Switch G5X DG-F-2A-A G2G-V2Q F60-G2G/B E2T-G5X/1 G2G-G5X/1 FN8-U0K FN8-U0L FN8-G2G/2 F60-FN8/1 310841 E2T/10a E2T/10e E2T/10f EDE-PP-113A CBA-FN-19 CBA-FN-20 INST AIR MS-PV-3002 or MS-PV-3004 MS-CS-3003-2 Control Switch with Indication G2G CB-F-1A-A MS-CS-3003-1 Control Switch with Indication F60 CB-F-3A-A MS-E2T/10-72 125 V DC Circuit Breaker E2T CB-F-1A-A MS-SS-3003-3 Selector Switch FN8 ET-F-1B-A MS-SS-3003-1 Selector Switch G2G CB-F-1A-A MS-ZS-3003-A Valve Position Switch V2Q MS-F-2A-Z MS-PY-3003-1 Solenoid Valve UOK MS-F-2A-Z MS-PY-3003-2 Solenoid Valve UOK MS-F-2A-Z MS-PY-3003-3 Solenoid Valve UOL MS-F-2A-Z MS-PY-3003-4 Solenoid Valve UOL MS-F-2A-Z MS-PY-3003-5 Solenoid Valve UOM MS-F-2A-Z E2U-F66/1 F66-U0M E2U/16 E2U/16 EDE-PP-113B MS-PY-3003-6 Solenoid Valve UOM MS-F-2A-Z MS-E2U/16-72 125 V DC Circuit Breaker E2U CB-F-1B-A MS-CS-3003-1 Control Switch F60 CB-F-3A-A 16 MS-PV-3002 Main Steam Header Atmospheric Relief Valve MS-20580 A/B 310586 MS-F-2A-Z X X X X V2P MS-SS-3002-1 Selector Switch G2J CB-F-1B-A G2J-V2P F66-G2J/1 E2U-G5Y G2J-G5Y FN9-U0G FN9-U0H FN9-G2J/1 F66-FN9 310841 E2U/8a E2U/8e E2U/8f CBA-FN-32 CBA-FN-33 EDE-PP-113B INST AIR MS-PV-3001 or MS-PV-3003 MS-CS-3002-2 Control Switch with Indication G2J CB-F-1B-A MS-CS-3002-1 Control Switch with Indication F60 CB-F-3A-A MS-E2U/8-72 125 V DC Circuit Breaker E2U CB-F-1B-A MS-SS-3002-3 Selector Switch FN9 ET-F-1D-A MS-SS-3002-2 Selector Switch G5Y DG-F-2B-A MS-ZS-3002-B Valve Position Switch V2P MS-F-2A-Z MS-PY-3002-1 Solenoid Valve UOG MS-F-2A-Z MS-PY-3002-2 Solenoid Valve UOG MS-F-2A-Z MS-PY-3002-3 Solenoid Valve UOH MS-F-2A-Z MS-PY-3002-4 Solenoid Valve UOH MS-F-2A-Z MS-PY-3002-5 Solenoid Valve UOJ MS-F-2A-Z E2T-F60 F60-U0J E2T/15 E2T/15 EDE-PP-113A MS-PY-3002-6 Solenoid Valve UOJ MS-F-2A-Z MS-E2T/15-72 125 V DC Circuit Breaker E2T CB-F-1A-A MS-CS-3002-1 Control Switch F60 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -12 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 17 MS-PV-3004 Main Steam Header Atmospheric Relief Valve MS-20580 A/B 310586 MS-F-2B-Z X X X X V2R MS-SS-3004-1 Selector Switch G2J CB-F-1B-A G2J-V2R G2J-G5Y/1 F66-G2J/3 E2U-G5Y/1 FN9-U0D FN9-U0E FN9-G2J/2 F66-FN9/1 310841 E2U/10a E2U/10e E2U/10f EDE-PP-113B CBA-FN-32 CBA-FN-33 INST AIR MS-PV-3001 or MS-PV-3003 MS-CS-3004-2 Control Switch with Indication G2J CB-F-1B-A MS-CS-3004-1 Control Switch with Indication F60 CB-F-3A-A MS-E2U/10-72 125 V DC Circuit Breaker E2U CB-F-1B-A MS-SS-3004-3 Selector Switch FN9 ET-F-1D-A MS-SS-3004-2 Selector Switch G5Y DG-F-2B-A MS-ZS-3004-B Valve Position Switch V2R MS-F-2B-Z MS-PY-3004-1 Solenoid Valve UOD MS-F-2B-Z MS-PY-3004-2 Solenoid Valve UOD MS-F-2B-Z MS-PY-3004-3 Solenoid Valve UOE MS-F-2B-Z MS-PY-3004-4 Solenoid Valve UOE MS-F-2B-Z MS-PY-3004-5 Solenoid Valve UOF MS-F-2B-Z E2T-F60/1 F60-U0F E2T/16 E2T/16 EDE-PP-113A MS-PY-3004-6 Solenoid Valve UOF MS-F-2B-Z MS-E2T/16-72 125 V DC Circuit Breaker E2T CB-F-1A-A MS-CS-3004-1 Control Switch F60 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -13 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 MS-V-86 Main Steam Isolation Valve MS-20583 A/B 310589 MS-F-2B-Z X X X X ZVO ZV1 ZV2 ZW1 MS-E87/14-72 125 V DC Circuit Breaker E87 CB-F-1A-A E87-GX6 GX6-ZV1 310841 E87/14a E87/14b CBA-FN-19 CBA-FN-20 EDE-PP-112A None Note 2 MS-FY-89A-1 Pilot Solenoid ZV1 MS-F-2B-Z MS-FY-10A-1 Pilot Solenoid ZV1 MS-F-2B-Z MS-FY-102A-1 Solenoid Valve ZV1 MS-F-2B-Z MS-FY-102B-1 Solenoid Valve ZV1 MS-F-2B-Z MS-GX6-K103 Output Relay GX6 MS-F-3A-Z MS-GX6-K104 Output Relay GX6 MS-F-3A-Z MS-GX6-CS-3005A Control Switch GX6 MS-F-3A-Z MS-E1S/7-52 120 V AC Circuit Breaker E1S CB-F-1A-A E1S-GX6/1 G2G-GX6/4 G2G-GX6/5 GX6-ZV0 G2G-GX6/3 F20-GX6 GX6-ZV0/1 FC1-GX6 F60-GX6/1 FB7-FC1/E F60-G2G/2 F60-GX6 FB7-GX6 E1S/7a E1S/7h E1S/7b E1S/7i E1S/7c E1S/7j E1S/7d E1S/7k CBA-FN-19 CBA-FN-20 EDE-PP-11E MS-GX6-FU-101,102 120 V AC Fuses GX6 MS-F-3A-Z MS-GX6-K101 Output Relay GX6 MS-F-3A-Z MS-GX6-K102 Output Relay GX6 MS-F-3A-Z MS-ZS-V86-1 Valve Position Switch ZV0 MS-F-2B-Z MS-ZS-V86-2 Valve Position Switch ZV0 MS-F-2B-Z MS-ZL-3005-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-184 MSIV Logic Cabinet (Train A) GX6 MS-F-3A-Z MS-FC1-K-804 Auxiliary Relay SSPS Test FC1 CB-F-3A-A MS-CS-3085-2 Control Switch F20 CB-F-3A-A MS-CS-3005 Control Switch with Indication F60 CB-F-3A-A MS-DS-8029 Isolation Indication FC1 CB-F-3A-A MS-FB7-K634A SSPS Auxiliary Relay FB7 CB-F-3A-A MS-E88/14-72 125 V DC Circuit Breaker E88 CB-F-1B-A E88-GX9 GX9-ZV2 E88/14a E88/14b CBA-FN-32 CBA-FN-33 EDE-PP-112B MS-FY-89B-1 Pilot Solenoid ZV2 MS-F-2B-Z MS-FY-10B-1 Pilot Solenoid ZV2 MS-F-2B-Z MS-FY-117A-1 Solenoid Valve ZV2 MS-F-2B-Z MS-FY-117B-1 Solenoid Valve ZV2 MS-F-2B-Z MS-GX9-K103 Output Relay GX9 CB-F-1B-A MS-GX9-K104 Output Relay GX9 CB-F-1B-A MS-GX9-CS-3005-B Control Switch GX9 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -14 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 MS-V-86 Main Steam Isolation Valve MS-E1T/7-52 120 V AC Circuit Breaker E1T CB-F-1B-A E1T-GX9/3 G2J-GX9/1 GX9-ZW1 G2J-GX9 FB0-GX9 F51-GX9 GX9-ZW1/1 FC2-GX9 FBO-FC2/E E1T/7a E1T/7f E1T/7b E1T/7g E1T/7c E1T/7h E1T/7i CBA-FN-32 CBA-FN-33 EDE-PP-11F (Continued) MS-GX9-FU-101,102 120 V AC Fuses GX9 CB-F-1B-A MS-GX9-K101 Output Relay GX9 CB-F-1B-A MS-GX9-K102 Output Relay GX9 CB-F-1B-A MS-ZS-V86B-1 Valve Position Switch ZW1 MS-F-2B-Z MS-ZS-V86B-2 Valve Position Switch ZW1 MS-F-2B-Z MS-ZL-3005-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A MS-CP-185 MSIV Logic Cabinet (Train B) GX9 CB-F-1B-A MS-FC2-K-804 Auxiliary Relay SSPS Test FC2 CB-F-3A-A MS-CS-3085-1 Control Switch F50 CB-F-3A-A MS-DS-8029 Isolation Indication FC2 CB-F-3A-A MS-FB0-K634B SSPS Auxiliary Relay FBO CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -15 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 MS-V-88 Main Steam Isolation Valve MS-20583 A/B 310586 MS-F-2A-Z X X X X ZW3 ZW4 ZW5 ZW6 MS-E2T/12-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-GX7 GX7-ZW3 310841 E2T/12a E2T/12c CBA-FN-19 DBA-FN-20 EDE-PP-113A None Note 2 MS-FY-89A-2 Pilot Solenoid ZW3 MS-F-2A-Z MS-FY-10A-2 Pilot Solenoid ZW3 MS-F-2A-Z MS-FY-102A-2 Solenoid Valve ZW3 MS-F-2A-Z MS-FY-102B-2 Solenoid Valve ZW3 MS-F-2A-Z MS-GX7-K103 Output Relay GX7 MS-F-3A-Z MS-GX7-K104 Output Relay GX7 MS-F-3A-Z MS-GX7-CS-3006-A Control Switch GX7 MS-F-3A-Z MS-E1S/9-52 120 V AC Circuit Breaker E1S CB-F-1A-A E1S-GX7/1 G2G-GX7/4 G2G-GX7/5 GX7-ZW5 G2G-GX7/3 FB7-GX7 F20-GX7 GX7-ZW5/1 FC1-GX7 F60-GX7/1 FC1-GX7/1 FB7-FC1/F F60-G2G/5 F60-GX7 E1S/9a E1S/9h E1S/9b E1S/9i E1S/9c E1S/9j E1S/9d E1S/9k CBA-FN-19 CBA-FN-20 EDE-PP-11E MS-GX7-FU-101,102 120 V AC Fuses GX7 MS-F-3A-Z MS-GX7-K101 Output Relay GX7 MS-F-3A-Z MS-GX7-K102 Output Relay GX7 MS-F-3A-Z MS-ZS-V88A-1 Valve Position Switch ZW5 MS-F-2A-Z MS-ZS-V88A-2 Valve Position Switch ZW5 MS-F-2A-Z MS-ZL-3006-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-182 MSIV Logic Cabinet (Train A) GX7 MS-F-3A-Z MS-CS-3006 Control Switch with Indication F60 CB-F-3A-A MS-FC1-K-804 Auxiliary Relay SSPS Test FC1 CB-F-3A-A MS-CS-3085-2 Control Switch F20 CB-F-3A-A MS-DS-8030 Isolation Indication FC1 CB-F-3A-A MS-FB7-K634A SSPS Auxiliary Relay FB7 CB-F-3A-A MS-E2U/12-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-GX8 GX8-ZW4 E2U/12a E2U/12c CBA-FN-32 CBA-FN-33 EDE-PP-113B MS-GX8-K103 Output Relay GX8 CB-F-1B-A MS-GX8-K104 Output Relay GX8 CB-F-1B-A MS-FY-89B-2 Pilot Solenoid ZW4 MS-F-2A-Z MS-FY-10B-2 Pilot Solenoid ZW4 MS-F-2A-Z MS-FY-117A-2 Solenoid Valve ZW4 MS-F-2A-Z MS-FY-117B-2 Solenoid Valve ZW4 MS-F-2A-Z MS-GX8-CS-3006-B Control Switch GX8 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -16 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 MS-V-88 Main Steam Isolation Valve (Continued) MS-E1T/9-52 125 V AC Circuit Breaker E1T CB-F-1B-A E1T-GX8/3 G2J-GX8 GX8-ZW6 G2J-GX8/1 FB0-GX8 F51-GX8 GX8-ZW6/1 FC2-GX8 FBO-FC2/F 310841 E1T/9a E1T/9f E1T/9b E1T/9g E1T/9c E1T/9h E1T/9i CBA-FN-32 CBA-FN-33 EDE-PP-11F MS-GX8-FU-101,102 120 V AC Fuses GX8 CB-F-1B-A MS-GX8-K101 Output Relay GX8 CB-F-1B-A MS-GX8-K102 Output Relay GX8 CB-F-1B-A MS-ZS-V88B-1 Valve Position Switch ZW6 MS-F-2A-Z MS-ZS-V88B-2 Valve Position Switch ZW6 MS-F-2A-Z MS-ZL-3006-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A MS-CP-183 MSIV Logic Cabinet (Train B) GX8 CB-F-1B-A MS-FC2-K-804 Auxiliary Relay SSPS Test FC2 CB-F-3A-A MS-CS-3085-1 Control Switch F50 CB-F-3A-A MS-DS-8030 Isolation Indication FC2 CB-F-3A-A MS-FB0-K634B SSPS Auxiliary Relay FBO CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -17 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 20 MS-V-90 Main Steam Isolation Valve MS-20583 A/B 310586 MS-F-2A-Z X X X X ZX1 ZW0 ZW8 ZW9 MS-E2T/14-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-GX7/1 GX7-ZW8 310841 E2T/14a E2T/14c CBA-FN-19 CBA-FN-20 EDE-PP-113A None Note 2 MS-FY-89A-3 Pilot Solenoid ZW8 MS-F-2A-Z MS-FY-10A-3 Pilot Solenoid ZW8 MS-F-2A-Z MS-FY-102A-3 Solenoid Valve ZW8 MS-F-2A-Z MS-FY-102B-3 Solenoid Valve ZW8 MS-F-2A-Z MS-GX7-K111 Output Relay GX7 MS-F-3A-Z MS-GX7-K112 Output Relay GX7 MS-F-3A-Z MS-GX7-CS-3007-A Control Switch GX7 MS-F-3A-Z MS-E1S/9-52 120 V AC Circuit Breaker E1S CB-F-1A-A E1S-GX7/1 G2G-GX7/3 G2G-GX7/4 G2G-GX7/5 GX7-ZW0 FB7-GX7 GX7-ZW0/1 FC1-GX7 F60-GX7/1 F20-GX7/1 FC1-GX7/1 F60-GX7 FB7-FC1/F F60-G2G/5 E1S/9a E1S/9h E1S/9b E1S/9i E1S/9c E1S/9j E1S/9d E1S/9k CBA-FN-19 CBA-FN-20 EDE-PP-11E MS-GX7-FU-103,104 120 V AC Fuses GX7 MS-F-3A-Z MS-GX7-K109 Output Relay GX7 MS-F-3A-Z MS-GX7-K110 Output Relay GX7 MS-F-3A-Z MS-ZS-V90A-1 Valve Position Switch ZWO MS-F-2A-A MS-ZS-V90A-2 Valve Position Switch ZWO MS-F-2A-A MS-ZL-3007-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-182 MSIV Logic Cabinet (Train A) GX7 MS-F-3A-Z MS-CS-3007 Control Switch with Indication F60 CB-F-3A-A MS-CS-3085-2 Control Switch F20 CB-F-3A-A MS-DS-8031 Isolation Indication FC1 CB-F-3A-A MS-FB7-K634A SSPS Auxiliary Relay FB7 CB-F-3A-A MS-FC1-K804 Auxiliary Relay SSPS Test FC1 CB-F-3A-A MS-E2U/14-72 125 V DC Circuit Breaker E2U CB-F-1A-A E2U-GX8/1 GX8-ZW9 E2U/14a E2U/14c CBA-FN-32 CBA-FN-33 EDE-PP-113B MS-GX8-K111 Output Relay GX8 CB-F-1B-A MS-GX8-K112 Output Relay GX8 CB-F-1B-A MS-FY-89B-3 Pilot Solenoid ZW9 MS-F-2A-Z MS-FY-10B-3 Pilot Solenoid ZW9 MS-F-2A-Z MS-FY-117A-3 Solenoid Valve ZW9 MS-F-2A-Z MS-FY-117B-3 Solenoid Valve ZW9 MS-F-2A-Z MS-CP-183 MSIV Logic Cabinet (Train B) GX8 CB-F-1B-A MS-GX8-CS-3007-B Control Switch GX8 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -18 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 20 MS-V-90 Main Steam Isolation Valve (Continued) MS-E1T/9-52 125 V AC Circuit Breaker E1T CB-F-1B-A E1T-GX8/3 G2J-GX8 G2J-GX8/1 GX8-ZX1 FB0-GX8 F51-GX8 FC2-GX8 GX8-ZX1/2 FBO-FC2/F 310841 E1T/9a E1T/9f E1T/9b E1T/9g E1T/9c E1T/9h E1T/9i CBA-FN-32 CBA-FN-33 EDE-PP-11F MS-GX8-FU-103,104 120 V AC Fuses GX8 CB-F-1B-A MS-GX8-K109 Output Relay GX8 CB-F-1B-A MS-GX8-K110 Output Relay GX8 CB-F-1B-A MS-ZS-V90B-1 Valve Position Switch ZX1 MS-F-2A-Z MS-ZS-V90B-1 Valve Position Switch ZX1 MS-F-2A-Z MS-ZL-3007-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-CP-183 MSIV Logic Cabinet (Train B) GX8 CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A MS-CS-3085-1 Control Switch F50 CB-F-3A-A MS-DS-8031 Isolation Indication FC2 CB-F-3A-A MS-FB0-K634B SSPS Auxiliary Relay FB0 CB-F-3A-A MS-FC2-K804 Auxiliary Relay SSPS Test FC2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -19 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 21 MS-V-92 Main Steam Isolation Valve MS-20583 A/B 310589 MS-F-2B-Z X X X X ZX3 Z1A Z1B Z1C MS-E87/18-52 125 V DC Circuit Breaker E87 CB-F-1A-A E87-GX6/1 GX6-ZX3 310841 E87/18a E87/18c CBA-FN-19 CBA-FN-20 EDE-PP-112A None Note 2 MS-GX6-K111 Output Relay GX6 MS-F-3A-Z MS-GX6-K112 Output Relay GX6 MS-F-3A-Z MS-FY-89A-4 Pilot Solenoid ZX3 MS-F-2B-Z MS-FY-10A-4 Pilot Solenoid ZX3 MS-F-2B-Z MS-FY-102A-4 Solenoid Valve ZX3 MS-F-2B-Z MS-FY-102B-4 Solenoid Valve ZX3 MS-F-2B-Z MS-CP-184 MSIV Logic Cabinet (Train A) GX6 CB-F-1A-A MS-GX6-CS-3008-A Control Switch GX6 MS-F-3A-Z MS-E1S/7-52 120 V AC Circuit Breaker E1S CB-F-1A-A E1S-GX6/1 G2G-GX6/3 G2G-GX6/4 G2G-GX6/5 GX6-Z1B FB7-GX6 GX6-Z1B/1 F20-GX6/1 FC1-GX6 F60-GX6/1 FB7-PC1/E F60-GX6 F60-G2G/2 E1S/7a E1S/7h E1S/7b E1S/7i E1S/7c E1S/7j E1S/7d E1S/7k CBA-FN-19 CBA-FN-20 EDE-PP-11E MS-GX6-FU-103,104 120 V AC Fuses GX6 MS-F-3A-Z MS-GX6-K109 Output Relay GX6 MS-F-3A-Z MS-GX6-K110 Output Relay GX6 MS-F-3A-Z MS-ZS-V92A-1 Valve Position Switch Z1B MS-F-2B-Z MS-ZS-V92A-2 Valve Position Switch Z1B MS-F-2B-Z MS-ZL-3008-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-184 MSIV Logic Cabinet (Train A) GX6 MS-F-3A-Z MS-CS-3008 Control Switch with Indication F60 CB-F-3A-A MS-CS-3085-2 Control Switch F20 CB-F-3A-A MS-DS-8032 Isolation Indication FC1 CB-F-3A-A MS-FB7-K634A SSPS Auxiliary Relay FB7 CB-F-3A-A MS-FC1-K804 Auxiliary Relay SSPS Test FC1 CB-F-3A-A MS-E88/14-72 125 V DC Circuit Breaker E88 CB-F-1B-A E88-GX9/1 GX9-Z1A E88/9a E88/9c CBA-FN-32 CBA-FN-33 EDE-PP-112B MS-GX9-K111 Output Relay GX9 CB-F-1B-A MS-GX9-K112 Output Relay GX9 CB-F-1B-A MS-FY-89B-4 Pilot Solenoid Z1A MS-F-2B-Z MS-FY-10B-4 Pilot Solenoid Z1A MS-F-2B-Z MS-FY-117A-4 Solenoid Valve Z1A MS-F-2B-Z MS-FY-117B-4 Solenoid Valve Z1A MS-F-2B-Z MS-CP-185 MSIV Logic Cabinet (Train B) GX9 CB-F-1B-A MS-GX9-3008-B Control Switch GX9 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -20 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 21 MS-V-92 Main Steam Isolation Valve (Continued) MS-E1T/7-52 125 V AC Circuit Breaker E1T CB-F-1B-A E1T-GX9/3 GX9-Z1C G2J-GX9 G2J-GX9/1 FB0-GX9 F51-GX9 GX9-Z1C/1 FB0-FC2/E FC2-GX9 310841 E1T/7a E1T/7f E1T/7b E1T/7g E1T/7c E1T/7h E1T/7i CBA-FN-32 CBA-FN-33 EDE-PP-11F MS-GX9-FU-103,104 120 V AC Fuses GX9 CB-F-1B-A MS-GX9-K109 Output Relay GX9 CB-F-1B-A MS-GX9-K110 Output Relay GX9 CB-F-1B-A MS-ZS-V92B-1 Valve Position Switch Z1C MS-F-2B-Z MS-ZS-V92B-2 Valve Position Switch Z1C MS-F-2B-Z MS-ZL-3008-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A MS-CP-185 MSIV Logic Cabinet (Train B) GX9 CB-F-1B-A MS-CS-3085-1 Control Switch F50 CB-F-3A-A MS-DS-8032 Isolation Indication FC2 CB-F-3A-A MS-FB0-K634B SSPS Auxiliary Relay FB0 CB-F-3A-A MS-FC2-K804 Auxiliary Relay SSPS Test FC2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -21 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 22 MS-V-204 Main Steam Isolation Valve Bypass Valve MS-20583 A 310589 MS-F-2B-Z X X X - VU6 MS-B1X-52 460 VAC Circuit Breaker B1X CB-F-1A-A - - - - None Note 3 23 MS-V-205 Main Steam Isolation Valve Bypass Valve MS-20583 A 310586 MS-F-2A-Z X X X - VU7 MS-B1Y-52 460 VAC Circuit Breaker B1Y CB-F-1A-A - - - - None Note 3 24 MS-V-206 Main Steam Isolation Valve Bypass Valve MS-20583 A 310586 MS-F-2A-Z X X X - VU8 MS-B1Z-52 460 VAC Circuit Breaker B1Z CB-F-1A-A - - - - None Note 3 25 MS-V-207 Main Steam Isolation Valve Bypass Valve MS-20583 A 310589 MS-F-2B-Z X X X - VU9 MS-B2A-52 460 VAC Circuit Breaker B2A CB-F-1A-A - - - - None Note 3 26 RC-E-11A Steam Generator RC-20841 A 310576 310582 310578 310580 C-F-1-Z C-F-1-Z C-F-2-Z C-F-3-Z X X - - - - - - - - - - - RC-E-11B or RC-E-11D Note 1 27 RC-E-11B Steam Generator RC-20842 B 310576 310582 310578 310580 C-F-1-Z C-F-1-Z C-F-2-Z C-F-3-Z X X - - - - - - - - - - - RC-E-11A or RC-E-11C Note 1 28 RC-E-11C Steam Generator RC-20843 A 310577 310583 310579 310581 C-F-1-Z C-F-1-Z C-F-2-Z C-F-3-Z X X - - - - - - - - - - - RC-E-11B or RC-E-11D Note 1 29 RC-E-11D Steam Generator RC-20844 B 310577 310583 310579 310581 C-F-1-Z C-F-1-Z C-F-2-Z C-F-3-Z X X - - - - - - - - - - - RC-E-11A or RC-E-11C Note 1 30 SB-V9 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM4 SB-CS-1900 Control Switch with Indication F28 CB-F-3A-A F26-U6V F26-UM4 F26-FB0/4 310901 E88/18a E88/18c E88/18d SB-V-1 Note 2 SB-FB0-K630B SSPS Output Relay FB0 CB-F-3A-A SS-FY-1900B Pilot Solenoid U6V MS-F-1B-Z SB-ZS-V9 Valve Position Switch UM4 MS-F-1B-Z 31 SB-V10 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM5 SB-CS-1901 Control Switch with Indication F28 CB-F-3A-A F26-U6W F26-UM5 F26-FB0/4 310901 E88/18a E88/18c E88/18d SB-V-3 Note 2 SB-FB0-K630B SSPS Output Relay FB0 CB-F-3A-A SS-FY-1901-B Pilot Solenoid U6W MS-F-1B-Z SB-ZS-V10 Valve Position Switch UM5 MS-F-1B-Z 32 SB-V11 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM6 SB-CS-1902 Control Switch with Indication F28 CB-F-3A-A F26-U6X F26-UM6 F26-FB0/4 310901 E88/18a E88/18c E88/18d SB-V-5 Note 2 SB-FB0-K630B SSPS Output Relay FB0 CB-F-3A-A SS-FY-1902-B Pilot Solenoid U6X MS-F-1B-Z SB-ZS-V11 Valve Position Switch UM6 MS-F-1B-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.1 -22 FUNCTION: DECAY HEAT REMOVAL . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 33 SB-V12 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM7 SB-CS-1903 Control Switch with Indication F28 CB-F-3A-A F26-U6Y F26-UM7 F26-FB0/5 310901 E88/18a E88/18c E88/18d SB-V-7 Note 2 SB-FB0-K630B SSPS Output Relay FB7 CB-F-3A-A SS-FY-1903-B Pilot Solenoid U6Y MS-F-1B-Z SB-ZS-V12 Valve Position Switch UM7 MS-F-1B-Z 34 SB-V-1 RC-E-11A Inboard Blowdown Isolation Valve SB-20626 A 310578 C-F-2-Z X X X X VB7 SB-CS-1987 Control Switch with Indication F28 CB-F-3A-A F28-H36/4 F28-H36/5 H36-VB7/1 310901 E93/14a E93/14d E93/14b SB-V-9 Note 2 SB-FY-V1-20 Solenoid Valve VB7 C-F-2-Z SB-ZS-V1 Valve Position Switches VB7 C-F-2-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A 35 SB-V-3 RC-E-11B Inboard Blowdown Isolation Valve SB-20626 A 310579 C-F-2-Z X X X X VC6 SB-CS-1988 Control Switch with Indication F28 CB-F-3A-A F28-H36/4 F28-H36/5 H36-VC6/1 310901 E93/14a E93/14d E93/14b E93/14e SB-V-10 Note 2 SB-FY-V3-20 Solenoid Valve VC6 C-F-2-Z SB-ZS-V3 Valve Position Switches VC6 C-F-2-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A 36 SB-V-5 RC-E-11C Inboard Blowdown Isolation Valve SB-20626 A 310579 C-F-2-Z X X X X VC7 SB-CS-1989 Control Switch with Indication F28 CB-F-3A-A F28-H36/4 F28-H36/5 F28-H36/6 H36-VC7/1 310901 E93/14a E93/14d E93/14b E93/14e SB-V-11 Note 2 SB-FY-V5-20 Solenoid Valve VC7 C-F-2-Z SB-ZS-V5 Valve Position Switches VC7 C-F-2-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A 37 SB-V-7 RC-E-11D Inboard Blowdown Isolation Valve SB-20626 A 310579 C-F-2-Z X X X X VC8 SB-CS-1990 Control Switch with Indication F28 CB-F-3A-A F28-H36/5 F28-H36/6 H36-VC8/1 310901 E93/14a E93/14d E93/14b E93/14e SB-V-12 SB-FY-V7-20 Solenoid Valve VC8 C-F-2-Z SB-ZS-V7 Valve Position Switches VC8 C-F-2-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A Note 2 38 CO-V-142 Condensate Tank Emergency Outlet Valve CO-20426 A 310248 202319 CST-F-1-0 X X - - - - - - - - - - - - Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -1 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 RC-E-10 Reactor Coolant System Pressurizer RC-20846 A/B 310598 C-F-1-Z X X - - - - - - - - - - - None Note 1 2 RC-E-10 Pressurizer Heaters Group A RC-20846 A 310598 C-F-1-Z X X X - M26 RC-AB4-52 480 V AC Circuit Breaker AB4 CB-F-1A-A AB4-E07 AB4-E07/1 AB4-G81 AB4-G81/1 E07-H14 E07-H14/1 E07-H14/2 E07-H14/3 E07-H14/4 H14-X47 H14-X47/1 H14-X47/2 H14-X47/3 H14-X47/4 M26-X47 M26-X47/1 M26-X47/2 M26-X47/3 M26-X47/4 M26-X47/5 M26-X47/6 M26-X47/7 M26-X47/8 M26-X47/9 M26-X47/A M26-X47/B M26-X47/C M26-X47/D M26-X47/E FB1-HR2 F38-FB1 F38-G81 310882 AB4a AB4g AB4b AB4h AB4c AB4i CBA-FN-19 CBA-FN-20 EDE-US-52 Pressurizer -Heaters Group B RC-AB4-FV Fuses AB4 CB-F-1A-A RC-CS-7318-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-7318 Selector Switch G81 CB-F-1A-A EDE-AC3-94-3 Bus Undervoltage Relay AC3 CB-F-1A-A RC-AB4-52H-1 Truck Operated Contact AB4 CB-F-1A-A EDE-TBX-X47 Terminal Box X47 C-F-1-Z RC-AB4-G,R Indicating Lights AB4 CB-F-1A-A RC-AB4-CT1 Current Transformer (600/5) ØB Bus Side AB4 CB-F-1A-A RC-AB4-AM Ammeter AB4 CB-F-1A-A RC-AB4-CT2 Current Transformer (600/5) ØA, ØC Load Side AB4 CB-F-1A-A RC-AC3-WTR Watt Transducer AC3 CB-F-1A-A RC-PP-6A Distribution Panel E07 ET-F-1A-A EDE-MM-90 Electrical Penetration H14 ET-F-1A-A, C-F-2-Z RC-HR2-RMO, PR1 Emergency Power Sequence Auxiliary Relays HR2 CB-F-1A-A RC-CS-7318-1 Control Switch with Indication F31 CB-F-3A-A RC-PYY-455GX1 Low Pressure Auxiliary Relay FB1 CB-F-3A-A RC-LYY-459CX1 Low Level Auxiliary Relay FB1 CB-F-3A-A RC-LYY-460DX1 Low Level Auxiliary Relay FB1 CB-F-3A-A RC-LYY-459EX1 High Level Auxiliary Relay FB1 CB-F-3A-A EDE-AC3-94-3 Undervoltage Tripping Relay AC3 CB-F-1A-A RC-LT-459 Pressurizer Level Transmitter GN5 C-F-2-Z GN5-H45/1 FA1-H45/1 C509011 310942 C509027 FA1s FP30001 FA1w SH125 MM-CP-1 MM-CP-1 Process Protection System Cabinet No. 1 FA1 CB-F-3A-A EDE-MM-121 Electrical Penetration H45 C-F-2-Z, ET-F-1A-1 MM-CP-5 Process Control GP No. 1 Cabinet FA5 CB-F-3A-A RC-LT-460 Pressurizer Level Transmitter GN5 C-F-2-Z GN5-H55/2 FA2-H55/3 C509011 310942 C509027 FA2r FP30001 FA2w SH125 MM-CP-2 EDE-MM-131 Electrical Penetration H55 C-F-1-Z ET-F-1C-Z

.* Table notes on last page of table

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -2 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 RC-E-10 (Continued) MM-CP-2 Process Protection System Cabinet No. 2 FA2 CB-F-3A-A MM-CP-6 Process Control GP No. 2 Cabinet FA6 CB-F-3A-A 3 RC-E-10 Pressurizer Heaters Group B RC-20846 B 310598 C-F-1-Z X X X - M26 RC-AD4-52 480 V AC Circuit Breaker AD4 CB-F-1B-A AD4-E08 AD4-E08/1 AD4-GZ0 AD4-GZ0/1 E08-H20 E08-H20/1 E08-H20/2 E08-H20/3 E08-H20/4 H20-X44 H20-X44/1 H20-X44/2 H20-X44/3 H20-X44/4 M26-X44 M26-X44/1 M26-X44/2 M26-X44/3 M26-X44/4 M26-X44/5 M26-X44/6 M26-X44/7 M26-X44/8 M26-X44/9 M26-X44/A M26-X44/B M26-X44/C M26-X44/D M26-X44/E F31-FT0 F31-HR4 F31-GZ0 AE3-GZ0 310882 AD4a AD4f AD4b AD4g AD4c AD4p AD4n CBA-FN-32 CBA-FN-33 EDE-US-62 Pressurizer Heaters Group A RC-AD4-FU Fuses AD4 CB-F-1B-A RC-CS-7319-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-7319 Selector Switch GZ0 CB-F-1B-A EDE-AE3-94-3 Bus Undervoltage Relay AE3 CB-F-1B-A RC-AD4-52H-1 Truck Operated Contact AD4 CB-F-1B-A RC-AD4-G,R Indicating Lights AD4 CB-F-1B-A EDE-TBX-X44 Terminal Box X44 C-F-1-Z RC-AD4-CT1 Current Transformer (600/5) ØB Bus Side AD4 CB-F-1B-A RC-AD4-AM Ammeter AD4 CB-F-1B-A RC-AD4-CT2 Current Transformer (600/5) ØA, ØC Load Side AD4 CB-F-1B-A RC-AE3-WTR Watt Transducer AE3 CB-F-1B-A RC-PP-6B Distribution Panel E08 ET-F-1C-A EDE-MM-96 Electrical Penetration H20 ET-F-1C-A, C-F-1-Z RC-AE3-R1 Auxiliary Relay AE3 CB-F-1B-A RC-HR4-RM0,PR1 Emergency Power Sequencer Auxiliary Relays HR4 CB-F-1B-A RC-CS-7319-1 Control Switch with Indication F31 CB-F-3A-A EDE-FT0-KA2,KA3 KA4,KA5 Auxiliary Relays Isolation Cabinet FT0 CB-F-3A-A EDE-AE3-94-3 Undervoltage Tripping Relay AE3 CB-F-1B-A RC-FS9-FU Fuses FS9 CB-F-3A-A FB2-FS9/1 FB2-FS9/2 310966 EH9/15a EH9/15s EH9/15b EH9/15t EH9/15c EH9/15d EH9/15e EH9/15f EH9/15g EH9/15h EH9/15i RC-LYY-459CX2 Low Level Auxiliary Relay FB2 CB-F-3A-A RC-LYY-460DX2 Low Level Auxiliary Relay FB2 CB-F-3A-A EDE-FT0-KA3,KA5 Auxiliary Relays Isolation Cabinet FT0 CB-F-3A-A MM-CP-5 Process Control Cabinet FA5 CB-F-3A-A GN5-H45/1 FA1-H45/1 C509011 310942 C509027 FA1s FP30001 FA1w FP129 EDE-MM-121 Electrical Penetration H45 C-F-2-Z ET-F-1A-A MM-CP-1 Process Protection Cabinet No. 1 FA1 CB-F-3A-A RC-LT-459 Pressurizer Level Transmitter GN5 C-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -3 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 RC-E-10 (Continued) RC-LT-460 Pressurizer Level Transmitter GN5 C-F-2-Z GN5-H55/2 FA2-H55/3 C509011 310942 C509027 FA2r FP30001 FA2w SH129 EDE-MM-131 Electrical Penetration H55 C-F-1-Z ET-F-1C-Z MM-CP-2 Process Protection System Cabinet No. 2 FA2 CB-F-3A-A MM-CP-6 Process Control GP No. 2 Cabinet FA6 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -4 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 RC-V-122 RC-E-10 Pressurizer Relief Isolation Valve RC-20846 A 310581 C-F-3-Z X X X - V01 RC-B97-52-1,2 460 V AC Circuit Breakers B97 CB-F-1A-A B97-G81 B97-G81/1 B97-H18 B97-H35 H18-V01 H35-X56 V01-X56 ED1-F38 F38-G81/2 F38-G81/3 310882 B97a B97c B97e B97d CBA-FN-19 CBA-FN-20 EDE-MCC-521 RC-V-124 or RC-PCV-456A RC-B97-FU Fuse B97 CB-F-1A-A RC-CS-7313-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-7313 Selector Switch G81 CB-F-1A-A RC-B97-42-1/0,C Motor Starters B97 CB-F-1A-A RC-B97-42-2 Motor Starter B97 CB-F-1A-A RC-B97-49-1,2 Overload Relays B97 CB-F-1A-A EDE-TBX-X56 Terminal Box X56 C-F-3-Z RC-ZS-V122 Valve Position Switch and Valve Open/Close Torque Switches V01 C-F-3-Z EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A RC-CS-7313-1 Control Switch with Indication F31 CB-F-3A-A RC-ED1-R1 Auxiliary Relay ED1 CB-F-1A-A 5 RC-V-124 RC-E-10 Pressurizer Relief Isolation Valve RC-20846 B 310581 C-F-3-Z X X X - V02 RC-B98-52-1,2 460 V AC Circuit Breakers B98 CB-F-1B-A B98-GZ0 B98-GZ0/1 B98-H15 B98-H41 H15-V02 H41-X35 V02-X35 B98-GZ0/2 F31-FT0/1 F31-GZ0/5 F31-GZ0/6 310882 B98a B98c B98e B98d CBA-FN-32 CBA-FN-33 EDE-MCC-621 RC-V-122 or RC-PCV-456B RC-B98-FU Fuses B98 CB-F-1B-A RC-CS-7314-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-7314 Selector Switch GZ0 CB-F-1B-A RC-B98-42-1/0,C Motor Starters B98 CB-F-1B-A RC-B98-42-2 Motor Starter B98 CB-F-1B-A RC-B98-49-1,2 Overload Relays B98 CB-F-1B-A EDE-TBX-X35 Terminal Box X35 C-F-3-Z RC-ZS-V124 Valve Position Switch and Valve Open/Close Torque Switches V02 C-F-3-Z EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A RC-CS-7314-1 Control Switch with Indication F31 CB-F-3A-A RC-FT0-KA6 Auxiliary Relay FT0 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -5 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 RC-PCV-456A RC-E-10 Pressurizer Relief Control Valve RC-20846 A 310581 C-F-3-Z X X X - LD3 RC-E87/19-72 125 V DC Circuit Breaker E87 CB-F-1A-A E87-E4A/4 E4A-J3M G81-J3M G81-H35 G5X-J3M H18-J3M H18-LD3 H35-X56/2 LD3-X56 F38-G81/1 F38-FB1/2 F38-G5X 310882 E87/19a E87/19c E87/19d CBA-FN-19 CBA-FN-20 EDE-PP-112A RC-PCV-456B or RC-V-122 RC-CS-456A-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-456-A1 Selector Switch G81 CB-F-1A-A RC-SS-456-A2 Selector Switch G5X DG-F-2A-A RC-J3M-42 Auxiliary Relay J3M DG-F-2A-A RC-PCV-456A-20 Solenoid Operating Coil LD3 C-F-3-Z RC-ZS-PCV-456A Valve Position Switch LD3 C-F-3-Z RC-E4A-FU11,12 30 A Fuses E4A CB-F-1A-A EDE-TBX-X56 Terminal Box X56 C-F-3-Z EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A RC-CS-456A-1 Control Switch with Indication F31 CB-F-3A-A RC-PY-405CX Auxiliary Relay FB1 CB-F-3A-A RC-TY-413KK Auxiliary Relay FB1 CB-F-3A-A RC-PY-455EX Auxiliary Relay FB1 CB-F-3A-A RC-PY-458BX Auxiliary Relay FB1 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -6 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 RC-PCV-456B RC-E-10 Pressurizer Relief Control Valve RC-20846 B 310581 C-F-3-Z X X X - LD4 RC-E88/19-72 125 V DC Circuit Breaker E88 CB-F-1B-A E88-E4C/7 E4C-J3P GZ0-J3P GZ0-H39 G5Y-J3P H24-J3P H24-LD4 H39-X35 LD4-X35 F31-FT0/2 F31-GZ0/2 E4C-GZ0/2 F31-G5Y/1 310882 E88/19a E88/19c E88/19d CBA-FN-32 CBA-FN-33 EDE-PP-112B RC-PCV-456A or RC-V-124 RC-CS-456B-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-456-B1 Selector Switch GZ0 CB-F-1B-A RC-SS-456-B2 Selector Switch G5Y DG-F-2B-A RC-J3P-42 Auxiliary Relay J3P DG-F-2B-A RC-PCV-456B-20 Solenoid Operating Coil LD4 C-F-3-Z RC-ZS-PCV-456B Valve Position Switch LD4 C-F-3-Z RC-E4C-FU19,20 30 A Fuses E4C CB-F-1B-A EDE-TBX-X35 Terminal Box X35 C-F-3-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-CS-456B-1 Control Switch with Indication F31 CB-F-3A-A EDE-FT0-KA7 Auxiliary Relays Isolation Cabinet FT0 CB-F-3A-A RC-E4C-FU-23,24 30 A Fuses E4C CB-F-1B-A 8 RC-TK11 Pressurizer Relief Tank RC-20846 A/B 310577 C-F-1-Z X X - - - - - - - - - None Note 1 9 RC-V-323 Reactor Vessel Venting Valve RC-20485 B 310581 C-F-3-Z X X X - VB2 RC-BV9-42-1,2 Starter BV9 CB-F-1B-A BV9-F31 310882 BV9a BV9c BV9d RC-FV-2881 RC-BV9-49-1,2 Overload Relays BV9 CB-F-1B-A RC-CS-2885 Control Switch with Indication F31 CB-F-3A-A BV9-H41 F31-H41/2 H41-VB2 H41-VB2/1 RC-V-323 Valve Position and Open/Close Torque Switches VB2 C-F-3-Z EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A 10 RC-FV-2881 Reactor Vessel Venting Valve RC-20845 B 310581 C-F-3-Z X X X - U04 RC-CS-2881 Control Switch with Indication F31 CB-F-3A-A F31-GN0 F31-G5Y F31-H41/1 H41-U04 310882 E88/1g E88/1e E88/1d E88/1f RC-V-323 RC-SS-2881 Selector Switch G5Y CB-F-1B-A RC-GN0-R7 Auxiliary Relay EDE-CP-249 GN0 CB-F-1B-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A H39-U04 F26-H39 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -7 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 RC-LCV-459 Letdown Isolation Valve RC-20843 A 310577 C-F-1-Z X X X X L99 RC-SS-459 Selector Switch G5X DG-F-2A-A F40-FB1/2 F40-G5X F40-H36 GE5-H36/2 GE5-LH2/1 GE5-L99 L99-LH2 310882 E89/17a E89/17c E89/17d RC-LCV-460 CS-V-145 CS-ZS-V-145 Position Switch LH2 C-F-1-Z RC-CS-459 Control Switch with Indication F40 CB-F-3A-A RC-LY/459-CX1 Auxiliary Relay Auxiliary Rack No. 1 FB1 CB-F-3A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z ET-F-1A-A 12 RC-LCV-460 Letdown Isolation Valve RC-20843 A 310577 C-F-1-Z X X X X LF7 RC-CS-460 Control Switch with Indication F40 CB-F-3A-A F40-FB1 F40-H36/1 F40-H36/3 GE4-H36 GE4-LH2 GE4-LF7/1 310882 E89/1b E89/1d E89/1e E89/1f RC-V-459 CS-V-145 CS-ZS-V-145 Position Switch LH2 C-F-1-Z RC-LY/460-DX1 Auxiliary Relay Auxiliary Rack No. 1 FB1 CB-F-3A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -8 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 CS-P-2A Charging Pump CS-20725 A 310764 PAB-F-1C-A X X X - M17 CS-A62-52 4160 V AC Circuit Breaker A62-M17 A62-P01 A62-F41 A62-F41/2 A62-HR2 F41-FB7 F10-F41 310891 A62a A62h A62b A62c A62d CBA-FN-19 CBA-FN-20 EAH-FN-5A EDE-SWG-5 CS-P-2B CS-CS-7424-2 Control Switch A62 CB-F-1A-A CS-SS-7424 Selector Switch A62 CB-F-1A-A CS-A62-86 Lockout Relay A62 CB-F-1A-A CS-A62-52H Truck Operated Contact A62 CB-F-1A-A CS-A62-50/51 Inst./Time Over Current Relays Øa, ØC A62 CB-F-1A-A CS-PS-7467-1 Pressure Switch P01 PAB-F-1C-A CS-A62-AM Ammeter A62 CB-F-1A-A CS-A62-AS Ammeter Switch A62 CB-F-1A-A CS-A62-CT Current Transformer (100/5) A62 CB-F-1A-A CS-A62-TD1 CT Test Device A62 CB-F-1A-A CS-A62-ATR Transducer A62 CB-F-1A-A CS-A62-TD2 Lockout Relay Test Device A62 CB-F-1A-A CS-A62-TDR Timing Relay A62 CB-F-1A-A CS-A62-FU Fuses A62 CB-F-1A-A CS-A62-52Z Timing Relay A62 CB-F-1A-A CS-A62-G,R,W Indicating Lights A62 CB-F-1A-A CS-A62-51GS Ground Sensor Relay A62 CB-F-1A-A CS-CS-7424-1 Control Switch with Indication F41 CB-F-3A-A CS-FB7-K616A Auxiliary Relay SSPS 'A' CAB FB7 CB-F-3A-A CS-HR2-RM0,PR1 Emergency Power Sequencer Auxiliary Relays HR2 CB-F-1A-A CS-HR9-R2X Emergency Power Sequencer Auxiliary Relays HR9 CB-F-1A-A CS-ZL-7424-2 Indicating Light F10 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -9 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 14 CS-P-2B Charging Pump CS-20725 B 310764 PAB-F-1D-A X X X - M18 CS-A82-52 4160 V AC Circuit Breaker A82 CB-F-1B-A A82-M18 A82-P02 A82-F48/1 A82-F48/2 A82-HR4 F48-FB0 F10-F48 310891 A82a A82h A82b A82c A82d CBA-FN-32 CBA-FN-33 EAH-FN-5B EDE-SWG-6 CS-P-2A CS-CS-7425-2 Control Switch A82 CB-F-1B-A CS-SS-7425 Selector Switch A82 CB-F-1B-A CS-A82-86 Lockout Relay A82 CB-F-1B-A CS-A82-52H Truck Operated Contact A82 CB-F-1B-A CS-A82-50/51 Inst./Time Over Current Relays øA, øB A82 CB-F-1B-A CS-PS-7468-1 Pressure Switch P02 PAB-F-1D-A CS-A82-AM Ammeter A82 CB-F-1B-A CS-A82-AS Ammeter Switch A82 CB-F-1B-A CS-A82-CT Current Transformer (100/5) A82 CB-F-1B-A CS-A82-TD1 CT Test Device A82 CB-F-1B-A CS-A82-ATR Transducer A82 CB-F-1B-A CS-A82-TD2 Lockout Relay Test Device A82 CB-F-1B-A CS-A82-TDR Timing Relay A82 CB-F-1B-A CS-A82-FU Fuses A82 CB-F-1B-A CS-A82-52Z Timing Relay A82 CB-F-1B-A CS-A82-G,R,W Indicating Lights A82 CB-F-1B-A CS-A82-51GS Ground Sensor Relay A82 CB-F-1B-A CS-CS-7425-1 Control Switch with Indication F41 CB-F-3A-A CS-FB0-K616B Auxiliary Relay SSPS 'A' CAB FB0 CB-F-3A-A CS-HR4-RM0,PR1 Emergency Power Sequencer Auxiliary Relays HR4 CB-F-1B-A CS-A82-R2 Auxiliary Relay A82 CB-F-1B-A CS-HR0-R2X Emergency Power Sequencer Auxiliary Relays HR0 CB-F-1B-A CS-ZL-7425-2 Indicating Light F10 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -10 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 CS-V-142 Charging Line Isolation Valve CS-20722 A 310769 PP-F-1A-Z X X X - V12 CS-B82-52 460 V AC Circuit Breaker B82 CB-F-1A-A B82-G2G B82-G2G/1 B82-V12 B82-V12/1 F41-FB7/1 F41-G2G/4 F41-G2G/5 310891 B82a B82c B82d CBA-FN-19 CBA-FN-20 EAH-FN-5A EDE-MCC-512 CS-V-143 or CS-HCV-182 CS-CS-7410-2 Control Switch with Indication G2G CB-F-1A-A CS-SS-7410 Selector Switch G2G CB-F-1A-A CS-B82-42/0,C Motor Starters B82 CB-F-1A-A CS-B82-49 Overload Relay B82 CB-F-1A-A CS-ZS-V142 Valve Position and Open/Close Torque Switches V12 PP-F-1A-Z CS-B82-FU Fuse B82 CB-F-1A-A CS-CS-7410-1 Control Switch with Indication F41 CB-F-3A-A CS-FB7-K601A Auxiliary Relay SSPS 'A' CAB FB7 CB-F-3A-A 16 CS-V-143 Charging Line Isolation Valve CS-20722 B 310769 PP-F-1A-Z X X X - V11 CS-B87-52 460 V AC Circuit Breaker B87 CB-F-1B-A B87-G2J B87-G2J/1 B87-V11 B87-V11/1 F48-FB0/3 F48-G2J/2 F48-G2J/3 310891 B87a B87c B87d CBA-FN-32 CBA-FN-33 EAH-FN-5B EDE-MCC-612 CS-V-142 or CS-HCV-182 CS-CS-7411-2 Control Switch with Indication G2J CB-F-1B-A CS-SS-7411 Selector Switch G2J CB-F-1B-A CS-B87-42/0,C Motor Starters B87 CB-F-1B-A CS-B87-49 Overload Relay B87 CB-F-1B-A CS-ZS-V143 Valve Position and Open/Close Torque Switches V11 PP-F-1A-Z CS-B87-FU Fuse B87 CB-F-1B-A CS-CS-7411-1 Control Switch with Indication F41 CB-F-3A-A CS-FB0-K601B Auxiliary Relay SSPS 'A' CAB FB0 CB-F-3A-A 17 RC-P-1A Reactor Coolant Pump RC-20841 A 310576 310582 310578 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M01 RC-A05-52 13.8 kV Circuit Breaker A05 NES-F-1A-Z 310882 A05a A05g A05b A05h A05c A05d A05i None ED-E97-72 125 V DC Circuit Breaker E97 NES-F-1A-Z A05-F31/2 ED-SWG-1 RC-A05-FU Fuses (Trip Circuit) A05 NES-F-1A-Z RC-CS-7300 Control Switch with Indication F31 CB-F-3A-A 18 RC-P-1B Reactor Coolant Pump RC-20842 A 310576 310582 310578 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M02 RC-A20-52 13.8 kV Circuit Breaker A20 NES-F-1A-Z 310882 A20a A20g None ED-E97-72 125 V DC Circuit Breaker E97 NES-F-1A-Z A20-F31/2 ED-SWG-1 RC-A20-FU Fuses (Trip Circuit) A20 NES-F-1A-Z A20b A20K A20c A20d A20i RC-CS-7304 Control Switch with Indication F31 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -11 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 RC-P-1C Reactor Coolant Pump RC-20843 A 310577 310583 310579 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M03 RC-A09-52 13.8 kV Circuit Breaker A09 NES-F-1A-Z 31088 None ED-E91-72 125 V DC Circuit Breaker E91 TB-F-1A-Z A09-F38/2 A09a A09g ED-SWG-2 RC-A09-FU Fuses (Trip Circuit) A09 NES-F-1A-Z A09b A09h A09c A09d A09i RC-CS-7306 Control Switch with Indication F31 CB-F-3A-A 20 RC-P-1D Reactor Coolant Pump RC-20844 A 310577 310583 310579 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M04 RC-A24-52 13.8 kV Circuit Breaker A24 NES-F-1A-Z 310882 A24a A24g None ED-E91-72 125 V DC Circuit Breaker E91 TB-F-1A-Z A24-F31/2 ED-SWG-2 RC-A24-FU Fuses (Trip Circuit) A24 NES-F-1A-Z A24b A24h A24c A24d A24i RC-CS-7308 Control Switch with Indication F31 CB-F-3A-A 21 RC-V-22 RC-E-11A Hot Leg -RHR Isolation Valve RC-20841 B 310582 C-F-1-Z - X X - V27 RC-B54-52-1 460 V AC Circuit Breaker B54 CB-F-1B-A 310882 B54a B54c B54d RC-V-23 Note 4 7 and 8 22 RC-V-23 RC-E-11A Hot Leg -RHR Isolation Valve RC-20841 A 310576 C-F-1-Z - X X - V25 RC-B53-52-1 460 V AC Circuit Breaker B52 CB-F-1A-A 310882 B53a B53c B53d RC-V-22 Note 4, 7 and 8 23 RC-V-87 RC-E-11D Hot Leg -RHR Isolation Valve RC-20844 B 310582 C-F-1-Z - X X - V26 RC-B61-52-1 460 V AC Circuit Breaker B61 CB-F-1B-A 310882 B61a B61c B61d RC-V-88 Note 4, 7 and 8 24 RC-V-88 RC-E-11D Hot Leg -RHR Isolation Valve RC-20844 A 310577 C-F-1-Z - X X - V28 RC-B62-52-1 460 V AC Circuit Breaker B62 CB-F-1A-A 310882 B62a B62c B62d RC-V-87 Note 4, 7 and 8 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -12 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 25 SI-V-3 Accumulator TK -9A Outlet Isolation Valve SI-20450 A 310576 C-F-1-Z - X X - V39 SI-B35-52-1,2 460 V AC Circuit Breakers B35 CB-F-1A-A B35-G81 B35-H19 B35-H36 H19-V39 H36-V39 F20-FB7/5 F20-G81/1 310890 B35a B35c CBA-FN-19 CBA-FN-20 EDE-MCC-522 SI-FV-2475 SI-FV-2476 SI-B35-FU Fuse B35 CB-F-1A-A SI-CS-2403-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2403 Selector Switch G81 CB-F-1A-A SI-ZL-2403-4 Pilot Light G81 CB-F-1A-A SI-B35-42/0,C Motor Starters B35 CB-F-1A-A SI-B35-49 Overload Relay B35 CB-F-1A-A SI-ZS-V3 Valve Position and Open/Close Torque Switches V39 C-F-1-Z EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SI-FB7-K603A,K621A Auxiliary Relays FB7 CB-F-3A-A SI-CS-2403-1 Control Switch F20 CB-F-3A-A SI-EH9/9-52 120 V AC Circuit Breaker EH9 CB-F-1A-A G81-H35/5 G81-H36/6 H35-V41/1 H36-V39/1 E4H-EH9 E4H-G81 F20-G81 EH9/9a EH9/9b CBA-FN-19 CBA-FN-20 EDE-PP-1E SI-CS-2403-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2403 Selector Switch G81 CB-F-1A-A SI-ZS-V3 Valve Position and Open/Close Torque Switches V39 C-F-1-Z SI-E4H-FU7,8 30 A Fuses E4H CB-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SI-CS-2403-1 Control Switch with Indication F20 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -13 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 26 SI-V-17 Accumulator TK -9B Outlet Isolation Valve SI-20450 B 310576 C-F-1-Z - X X - V40 SI-B36-52-1,2 460 V AC Circuit Breakers B36 CB-F-1B-A B36-GZ0 B36-H15 B36-H41 H15-V40 H41-V40 F20-FB0/6 F20-GZ0/1 310890 B36a B36c CBA-FN-32 CBA-FN-33 EDE-MCC-622 SI-FV-2482 SI-FV-2483 SI-B36-FU Fuse B36 CB-F-1B-A SI-CS-2413-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2413 Selector Switch GZ0 CB-F-1B-A SI-ZL-2413-4 Pilot Light GZ0 CB-F-1B-A SI-B36-42/0,C Motor Starters B36 CB-F-1B-A SI-B36-49 Overload Relay B36 CB-F-1B-A SI-ZS-V17 Valve Position and Open/Close Torque Switches V40 C-F-1-Z EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A SI-FB0-K603B,K621B Auxiliary Relays FB0 CB-F-3A-A SI-CS-2413-1 Control Switch with Indication F20 CB-F-3A-A SI-EH0/9-52 120 V AC Circuit Breaker EH0 CB-F-1B-A GZ0-H39/5 GZ0-H41/4 H39-V42/1 H41-V40/1 E4J-EH0 E4J-GZ0 F20-GZ0 EH0/9a EH0/9b EH0/9c CBA-FN-32 CBA-FN-33 EDE-PP-1F SI-CS-2413-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2413 Selector Switch GZ0 CB-F-1B-A SI-ZS-V17 Valve Position and Open/Close Torque Switches V40 C-F-1-Z SI-E4J-FU7,8 30 A Fuses E4J CB-F-1B-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A SI-CS-2413-1 Control Switch with Indication F20 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -14 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 27 SI-V-32 Accumulator TK -9C Outlet Isolation Valve SI-20450 A 310577 C-F-1-Z - X X - V41 SI-B37-52-1,2 460 V AC Circuit Breakers B37 CB-F-1A-A B37-G81 B37-H18 B37-H35 H18-V41 H35-V41 F20-FB7/6 F20-G81/2 310890 B37a B37c CBA-FN-19 CBA-FN-20 EDE-MCC-522 SI-FV-2477 SI-FV-2486 SI-B37-FU Fuse B37 CB-F-1A-A SI-CS-2423-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2423 Selector Switch G81 CB-F-1A-A SI-ZL-2423-4 Pilot Light G81 CB-F-1A-A SI-B37-42/0,C Motor Starters B37 CB-F-1A-A SI-B37-49 Overload Relay B37 CB-F-1A-A EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-Z SI-ZS-V32 Valve Position and Open/Close Torque Switches V41 C-F-1-Z SI-FB7-K608A,K621A Auxiliary Relays FB7 CB-F-3A-A SI-CS-2423-1 Control Switch with Indication F20 CB-F-3A-A SI-EH9/9-52 120 V AC Circuit Breaker EH9 CB-F-1A-A G81-H35/5 G81-H36/6 H35-V41/1 H36-V39/1 E4H-EH9 E4H-G81 F20-G81 EH9/9a EH9/9b EH9/9c CBA-FN-19 CBA-FN-20 EDE-PP-1E SI-CS-2423-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2423 Selector Switch G81 CB-F-1A-A SI-ZS-V32 Valve Position and Open/Close Torque Switches V41 C-F-1-Z SI-E4H-FU7,8 30 A Fuses E4H CB-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A F20-G81 SI-CS-2423-1 Control Switch with Indication F20 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -15 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 28 SI-V-47 Accumulator TK -9D Outlet Isolation Valve SI-20450 B 310577 C-F-1-Z - X X - V42 SI-B38-52-1,2 460 V AC Circuit Breakers B38 CB-F-1B-A B38-GZ0 B38-H24 B38-H39 H24-V42 H39-V42 F20-FB0/7 F20-GZ0/2 310890 B38a B38c CBA-FN-32 CBA-FN-33 EDE-MCC-622 SI-FV-2495 SI-FV-2496 SI-B38-FU Fuse B38 CB-F-1B-A SI-CS-2433-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2433 Selector Switch GZ0 CB-F-1B-A SI-ZL-2433-4 Pilot Light GZ0 CB-F-1B-A SI-B38-42/0,C Motor Starters B38 CB-F-1B-A SI-B38-49 Overload Relay B38 CB-F-1B-A SI-ZS-V47 Valve Position and Open/Close Torque Switches V42 C-F-1-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A SI-FB0-K608B,K621B Auxiliary Relays FB0 CB-F-3A-A SI-CS-2433-1 Control Switch with Indication F20 CB-F-3A-A SI-EH0/9-52 120 V AC Circuit Breaker EH0 CB-F-1B-A GZ0-H39/5 GZ0-H41/4 H39-V42/1 H41-V40/1 E4J-EH0 E4J-GZ0 F20-GZ0 EH0/9a EH0/9b EH0/9c CBA-FN-32 CBA-FN-33 EDE-PP-1F SI-CS-2433-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2433 Selector Switch GZ0 CB-F-1B-A SI-ZS-V47 Valve Position and Open/Close Torque Switches V42 C-F-1-Z SI-E4J-FU7,8 30 A Fuses E4J CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A SI-CS-2433-1 Control Switch with Indication F20 CB-F-3A-A 29 CS-P-2A Charging Pump Lube Oil Cooler CS-20725 A 310764 805213 PAB-F-1C-A X X - - - - - - - - - - Component Cooling CS-P-2B Note 9 30 CS-P-2B Charging Pump Lube Oil Cooler CS-20725 B 310764 815214 PAB-F-1D-A X X - - - - - - - - - - Component Cooling CS-P-2A Note 9 31 CS-V-460 SI-P-6A Suction Valve CS-20725 A 310761 RHR-F-2B-Z - X X - V59 CS-B44-42/0,C Motor Starters B44 CB-F-1A-A B44-F10 B44-V59/1 B44-V59/2 310891 B44a B44c CS-V-475 CS-B44-49 Overload Relays B44 CB-F-1A-A CS-ZS-V460 Limit Switches and Open/Close Torque Switches V59 RHR-2B-Z CS-CS-2442 Control Switch with Indication F10 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -16 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 32 CS-V-461 SI-P-6A Suction Valve CS-20725 B 310761 RHR-F-2B-Z - X X - V60 CS-B45-42/0,C Motor Starters B45 CB-F-1B-A B45-F10 B45-V60/1 B45-V60/2 310891 B45a B45c None CS-B45-49 Overload Relays B45 CB-F-1B-A CS-ZS-V461 Limit Switches and Open/Close Torque Switches V60 RHR-2B-Z CS-CS-2452 Control Switch with Indication F10 CB-F-3A-A 33 CS-V-167 RC Pump Seal Water Isolation Valve CS-20726 A 310769 PP-F-5B-Z X X X - V05 CS-B73-42/0,C Motor Starters B73 CB-F-1A-A B73-F41 B73-V05/1 B73-V05/2 FB7-FC1/9 F41-FC1 310891 B73a B73c CS-V-10 CS-V-28 CS-V-44 CS-V-59 CS-V-175 CS-V-176 CS-B73-49 Overload Relays B73 CB-F-1A-A CS-ZS-V167 Limit Switches and Open/Close Torque Switches V05 PP-F-5B-Z CS-CS-7405 Control Switch with Indication F41 CB-F-3A-A CS-FC1-K802A Auxiliary Relay MM-CP-14 FC1 CB-F-3A-A CS-FB7-K631A Auxiliary Relay MM-CP-12 FB7 CB-F-3A-A 34 CS-V-168 RC Pump Seal Water Isolation Valve CS-20726 B 310577 C-F-1-Z X X X - V06 CS-B72-42-1,2 Motor Starters B72 CB-F-1B-A B72-H39 B72-F48 FB0-FC2/9 H39-V06 F48-FC2 310891 B72a B72c CS-V-10 CS-V-28 CS-V-44 CS-V-59 CS-V-175 CS-V-176 CS-B72-49-1,2 Overload Relays B72 CB-F-1B-A CS-CS-7404 Control Switch with Indication F41 CB-F-3A-A CS-ZS-V168 Limit Switches and Open/Close Torque Switches V06 C-F-1-Z CS-FC2-K802B Auxiliary Relay MM-CP-15 FC2 CB-F-3A-A CS-FB0-K631B Auxiliary Relay MM-CP-13 FB0 CB-F-3A-A CS-ED0-R1 Auxiliary Relay EDE-MCC-E612 ED0 CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A 35 CS-V-175 Excess Letdown Isolation Valve CS-20722 B 310577 C-F-1-Z X X X X L95 CS-ZS-V175 Valve Position Switch L95 C-F-1-Z F48-H39/2 GE5-H39/1 310891 E95/2a E95/2c E95/2d CS-V-176 Note 2 CS-CS-7418 Control Switch with Indication F41 CB-F-3A-A CS-FY-7418 Solenoid Valve GE5 C-F-1-Z EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A 36 CS-V-176 Excess Letdown Isolation Valve CS-20722 B 310577 C-F-1-Z X X X X LA5 CS-ZS-V176 Valve Position Switch LA5 C-F-1-Z F48-H39/1 GE5-H39/5 GE5-LA5/1 310891 E95/4a E95/4d E95/4b E95/4e E95/4f CS-V-175 Note 2 CS-FX-7417 Control Switch with Indication F41 CB-F-1A-A CS-FY-7417 Solenoid Valve GE5 C-F-1-Z EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -17 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 37 CS-V-196 Charging Pump Miniflow Isolation Valve CS-20725 A 310762 PAB-F-1J-Z X X X - V13 CS-B81-42/0,C Motor Starters B81 CB-F-1A-A B81-F41 B81-F41/1 B81-V13/1 F41-FB7/2 F41-FK0 B81-V13/2 310891 B81a B81c CS-V-197 CS-B81-49 Overload Relays B81 CB-F-1A-A CS-ZS-V196 Limit Switch and Open/Close Torque Switches V13 PAB-F-1J-Z CS-CS-7421 Control Switch with Indication F41 CB-F-3A-A CS-FYY-7325 Auxiliary Relay MM-CP-297A FK0 CB-F-3A-A CS-FB7-K603A Auxiliary Relay MM-CP-12 FB7 CB-F-3A-A 38 CS-V-197 Charging Pump Miniflow Isolation Valve CS-20725 B 310762 PAB-F-1J-Z X X X - V14 CS-B86-42/0,C Motor Starters B86 CB-F-1B-A B86-F48 B86-F48/1 B86-V14/1 B86-V14/2 F48-FB0/2 F48-FL2 310891 B86a B86c B86d CS-V-196 CS-B86-49 Overload Relays B86 CB-F-1B-A CS-ZS-V197 Limit Switch and Open/Close Torque Switches V14 PAB-F-1J-Z CS-CS-7422-1 Control Switch with Indication F41 CB-F-3A-A CS-FYY-7326 Auxiliary Relay MM-CP-297B FL2 CB-F-3A-A CS-FB0-K603B Auxiliary Relay MM-CP-13 FB0 CB-F-3A-A CS-CS-7422-2 Control Switch ED0 CB-F-1B-A CC-SS-7422 Selector Switch ED0 CB-F-1B-A 39 CS-LCV-112B Chemical and Volume Control Tank Outlet Isolation Valve CS-20725 A 310768 PAB-F-3B-Z X X X - VE4 CS-B50-52 460 V AC Circuit Breaker B50 CB-F-1A-A B50-G2G B50-G2G/1 B50-VE4 B50-VE4/1 B50-VE4/2 F40-FB7 F40-G2G F40-G2G/1 B50-VE6 B50-E3P E3P-G2G 310891 B50a B50c B50d B50f CBA-FN-19 CBA-FN-20 EDE-MCC-512 CS-LCV-112C CS-B50-FU Fuse B50 CB-F-1A-A CS-CS-112B-2 Control Switch with Indication G2G CB-F-1A-A CS-SS-112B Selector Switch G2G CB-F-1A-A CS-B50-42/0,C Motor Starters B50 CB-F-1A-A CS-B50-49 Overload Relay B50 CB-F-1A-A CS-ZS-LCV-112B Valve Position and Open/Close Torque Switches VE4 PAB-F-3B-Z CS-EC8-R1 Auxiliary Relay EC8 CB-F-1A-A CS-CS-112B-1 Control Switch with Indication F41 CB-F-3A-A CS-FB7-K701A, K602A,K706A Auxiliary Relays MM-CP-12 FB7 CB-F-3A-A CS-ZS-LCV-112D Valve Position Switch VE6 TF-F-1-0 CS-E3P-R2 Auxiliary Relay E3P CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -18 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 40 CS-LCV-112C Chemical and Volume Control Tank Outlet Isolation Valve CS-20725 B 310768 PAB-F-3B-Z X X X - VE7 CS-B83-52 460 V AC Circuit Breaker B83 CB-F-1B-A B83-G2J B83-G2J/1 B83-VE7 B83-VE7/1 B83-VE7/2 B83-VE5/1 F48-FB0/1 F48-G2J/4 F48-G2J/5 B83-E3Q E3Q-G2J 310891 B83a B83c B83d B83f CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-LCV-112B CS-B83-FU Fuses B83 CB-F-1B-A CS-CS-112C-2 Control Switch with Indication G2J CB-F-1B-A CS-SS-112C Selector Switch G2J CB-F-1B-A CS-B83-42/0,C Motor Starters B83 CB-F-1B-A CS-B83-49 Overload Relay B83 CB-F-1B-A CS-ZS-LCV-112C Valve Position and Open/Close Torque Switches VE7 PAB-F-3B-Z CS-ED0-R1 Auxiliary Relay ED0 CB-F-1B-A CS-CS-112C-1 Control Switch with Indication F41 CB-F-3A-A CS-FB0-K701B, K602B,K706B Auxiliary Relays MM-CP-13 FB0 CB-F-3A-A CS-ZS-LCV-112E Valve Position Switch VE5 TF-F-1-0 CS-E3Q-R2 Auxiliary Relay E3Q CB-F-1B-A 41 CS-LCV-112D Refueling Water Storage Tank to Charging Pump 2A Isolation Valve CBS-20233 A 301254 TF-F-1-0 X X X - VE6 CS-B78-52 460 V AC Circuit Breaker B78 CB-F-1A-A B78-G2G B78-G2G/1 B78-VE6 B78-VE6/1 B78-VE6/2 F10-FB7/4 F10-G2G/2 F10-G2G/3 B78-E3P/1 310891 B78a B78c B78d B78f CBA-FN-19 CBA-FN-20 EDE-MCC-512 CS-LCV-112E CS-CS-112D-2 Control Switch with Indication G2G CB-F-1A-A CS-SS-112D Selector Switch G2G CB-F-1A-A CS-B78-42/0,C Motor Starters B78 CB-F-1A-A CS-B78-49 Overload Relay B78 CB-F-1A-A CS-ZS-LCV-112D Valve Position and Open/Close Torque Switches VE6 TF-F-1-0 CS-EC8-R1 Auxiliary Relay EC8 CB-F-1A-A CS-B78-FU Fuse B78 CB-F-1A-A CS-FB7-K701A, K602A, K706A Auxiliary Relays MM-CP-12 FB7 CB-F-3A-A CS-CS-112D-1 Control Switch with Indication F10 CB-F-3A-A CS-SS-112D-1 Selector Switch F10 CB-F-3A-A CS-E3P-R0 Auxiliary Relay E3P CB-F-1A-A CS-ZS-112-C-1 Valve Position Switch VE7 PAB-F-3B-Z B78-E2P B78-VE6/1 VE4-VE6 VE4-VE7 (non-CASP) E3E/3a E3E/3b CS-E3P-R0 Auxiliary Relay E3P CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -19 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 42 CS-LCV-112E RWST CBS-TK-8 to Charging Pump 2B Isolation Valve CBS-20233 B 301254 TF-F-1-0 X X X - VE5 CS-B79-52 460 V AC Circuit Breaker B79 CB-F-1B-A B79-G2J B79-G2J/1 B79-VE5 B79-VE5/1 B79-VE5/2 F10-FB0/4 F10-G2J/2 F10-G2J/3 B79-E3Q/1 310891 B79a B79c B79d B79f CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-LCV-112D CS-CS-112E-2 Control Switch with Indication G2J CB-F-1B-A CS-SS-112E Selector Switch G2J CB-F-1B-A CS-B79-42/0,C Motor Starters B79 CB-F-1B-A CS-B79-49 Overload Relay B79 CB-F-1B-A CS-ZS-LCV-112E Valve Position and Open/Close Torque Switches VE5 TF-F-1-0 CS-ED0-R1 Auxiliary Relay ED0 CB-F-1B-A CS-B79-FU Fuse B79 CB-F-1B-A CS-FB0-K701B, K602B, K706B Auxiliary Relays MM-CP-13 FB0 CB-F-3A-A CS-CS-112E-1 Control Switch with Indication F10 CB-F-3A-A CS-SS-112E-1 Selector Switch F10 CB-F-3A-A CS-E3Q-R0 Auxiliary Relay E3Q CB-F-1B-A CS-ZS-112-B-1 Valve Position Switch VE4 PAB-F-3B-Z B79-E2Q B79-VE5//1 VE5-VE7 VE4-VE7/1 (non-CASP) E3F/3a E3F/3b CS-E3Q-R0 Auxiliary Relay E3Q CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -20 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 43 SI-V-138 Charging Pump To Cold Leg Isolation Valve SI-20447 A 310769 PP-F-1B-Z X X X - V31 SI-B31-52 460 V AC Circuit Breaker B31 CB-F-1A-A B31-G2G B31-G2G/2 B31-V31 B31-V31/1 B31-V31/2 F10-FB7 F10-G2G/4 F10-G2G/5 F10-FC1 F10-FN8 F10-FB7/9 B31-FN8 B31-FN8/1 310890 B31a B31c B31d CBA-FN-19 CBA-FN-20 EDE-MCC-521 SI-V-139 or CS-FCV-121 SI-CS-2437-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2437 Selector Switch G81 CB-F-1A-A SI-SS-2437-1 Selector Switch FN8 ET-F-1B-A MSO-5 Auxiliary Relay FN8 ET-F-1B-A SI-B31-42/0,C Motor Starters B31 CB-F-1A-A SI-B31-49 Overload Relay B31 CB-F-1A-A SI-ZS-V138 Valve Position and Open/Close Torque Switches V31 PP-F-1B-Z SI-B31-FU Fuse B31 CB-F-1A-A SI-FB7-K616A Auxiliary Relays MM-CP-12 FB7 CB-F-3A-A SI-CS-2437-1 Control Switch with Indication F10 CB-F-3A-A SI-FC1-K801A Auxiliary Relay MM-CP-14 FC1 CB-F-3A-A SI-FC1-W Indicating Light FC1 CB-F-3A-A SI-FC1-RES Resistor FC1 CB-F-3A-A 44 SI-V-139 Charging Pump To Cold Leg Isolation Valve SI-20447 B 310769 PP-F-1B-Z X X X - V32 SI-B32-52 460 V AC Circuit Breaker B32 CB-F-1B-A B32-G2J B32-G2J/2 B32-V32 B32-V32/1 B32-V32/2 F10-FB0 F10-G2J/4 F10-G2J/5 F10-FC2 F10-FB0/A F10-FN9 B32-FN9 B32-FN9/1 310890 B32a B32c B32d CBA-FN-32 CBA-FN-33 EDE-MCC-621 SI-V-138 or CS-FCV-121 SI-CS-2447-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2447 Selector Switch GZ0 CB-F-1B-A SI-SS-2447-1 Selector Switch FN9 ET-F-1D-A MSO-5 Auxiliary Relay FN9 ET-F-1D-A SI-B32-42/0,C Motor Starters B32 CB-F-1B-A SI-B32-49 Overload Relay B32 CB-F-1B-A SI-ZS-V139 Valve Position and Open/Close Torque Switches V32 PP-F-1B-Z SI-B32-FU Fuses B32 CB-F-1B-A SI-FB0-K616B Auxiliary Relays MM-CP-13 FB0 CB-F-3A-A SI-CS-2447-1 Control Switch with Indication F10 CB-F-3A-A SI-FC2-K801B Auxiliary Relay MM-CP-15 FC2 CB-F-3A-A SI-FC2-W Indicating Light FC2 CB-F-3A-A SI-FC2-RES Resistor FC2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -21 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 45 RC-E-10 Pressurizer Heaters Group C RC-20846 A 310598 C-F-1-Z X - X - M26 RC-AG4-52 480 V AC Circuit Breaker AG4 CB-F-1A-A F31-FB1/3 AG4-F31 310882 AG4a AG4b AG4d AG4e AG4f None RC-AG4-FU Fuses AG4 CB-F-1A-A RC-CS-7321 Control Switch with Indication F31 CB-F-3A-A RC-AG4-52H-1 Truck Operated Contact AG4 CB-F-1A-A RC-AG4-G,R Indicating Lights AG4 CB-F-1A-A RC-FB1-LYY-459 EXA High Level Auxiliary Relay FB1 CB-F-3A-A RC-FB1-LYY-459 CXA Low Level Auxiliary Relay FB1 CB-F-3A-A RC-FB1-LYY-460 DXA Low Level Auxiliary Relay FB1 CB-F-3A-A RC-FB1-PYY-455 GXA Low Pressure Auxiliary Relay FB1 CB-F-3A-A 46 RC-E-10 Pressurizer Heaters Group D RC-20846 A 310598 C-F-1-Z X - X - M26 RC-AM5-52 480 V AC Circuit Breaker AM5 CB-F-1A-A F31-FB2/2 AM5-F31 310882 AM5a AM5d AM5b AM5e AM5f None RC-AM5-FU Fuses AM5 CB-F-1A-A RC-AM5-52H-1 Truck Operated Contact AM5 CB-F-1A-A RC-AM5-G,R Indicating Lights AM5 CB-F-1A-A RC-CS-7322 Control Switch with Indication F31 CB-F-3A-A RC-FB2-PYY-455 GXB Low Pressure Auxiliary Relay FB2 CB-F-3A-A RC-FB2-LYY-459 CXB Low Level Auxiliary Relay FB2 CB-F-3A-A RC-FB2-LYY-459 EXB High Level Auxiliary Relay FB2 CB-F-3A-A RC-FB2-LYY-460 DXB Low Level Auxiliary Relay FB2 CB-F-3A-A RC-FB2-LYY-459 CXB Low Level Auxiliary Relay FB2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -22 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 47 CBS-P-9A Containment Spray Pump CBS-20233 A 310761 RHR-F-1B-Z X - X - M15 CBS-A61-52 4160 V AC Circuit Breaker A61 CB-F-1A-A A61-F20/1 A61-F20/2 A61-HR9 F20-FB7/1 HR2-HR9 310900 A61a A61b A61c A61d A61h None CBS-A61-AM Ammeter A61 CB-F-1A-A CBS-A61-AS Ammeter Switch A61 CB-F-1A-A CBS-A61-50/51 Overcurrent Relay A61 CB-F-1A-A CBS-A61-CT Current Transformer (100/5) A61 CB-F-1A-A CBS-CS-2300 Control Switch with Indication F20 CB-F-3A-A CBS-AU2-52S Circuit Breaker Operated Contact AU2 CB-F-1A-A CBS-A61-86 Lockout Relay A61 CB-F-1A-A CBS-A61-G,R,W Indicating Lights A61 CB-F-1A-A CBS-A61-52Z Timing Relay A61 CB-F-1A-A CBS-A61-R1,R2 Auxiliary Relays A61 CB-F-1A-A CBS-FB7-K644A Auxiliary Relay MM-CP-12 FB7 CB-F-3A-A CBS-HR2-RM0 Emergency Power Sequence Relay HR2 CB-F-1A-A CBS-HR9-SR3,LR8 Emergency Power Sequence Relay HR9 CB-F-1A-A CBS-A53-94-1B Bus Undervoltage Trip Relay A53 CB-F-1A-A CBS-A61-TD1 Test Device A61 CB-F-1A-A CBS-A61-TD2 Test Device A61 CB-F-1A-A CBS-A61-52H Truck Operated Contact A61 CB-F-1A-A CBS-A61-CS Control Switch A61 CB-F-1A-A CBS-A61-51GS Ground Sensor Relay A61 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -23 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 48 CBS-P-9B Containment Spray Pump CBS-20233 B 310761 RHR-F-1A-Z X - X - M16 CBS-A81-52 4160 V AC Circuit Breaker A81 CB-F-1B-A A81-F20/1 A81-F20/2 A81-HR0 F20-FB0/1 HR4-HR0 310900 A81a A81b A81c A81d A81h None CBS-A81-AM Ammeter A81 CB-F-1B-A CBS-A81-AS Ammeter Switch A81 CB-F-1B-A CBS-A81-50/51 Overcurrent Relay A81 CB-F-1B-A CBS-A81-CT1 Current Transformer (100/5) A81 CB-F-1B-A CBS-CS-2301 Control Switch with Indication F20 CB-F-3A-A CBS-HR4-RM0 Emergency Power Sequence Relay HR4 CB-F-1B-A CS-HR0-SR3,LR8 Emergency Power Sequence Relay HR0 CB-F-1B-A CBS-AU6-52S Circuit Breaker Operated Contact AU6 CB-F-1B-A CBS-A73-94-1B Bus Undervoltage Trip Relay A73 CB-F-1B-A CBS-FB0-R644B Auxiliary Relay MM-CP-13 FB0 CB-F-3A-A CBS-A81-86 Lockout Relay A81 CB-F-1B-A CBS-A81-G,R,W Indicating Lights A81 CB-F-1B-A CBS-A81-52Z Timing Relay A81 CB-F-1B-A CBS-A81-R1,R2 Auxiliary Relays A81 CB-F-1B-A CBS-A81-TD1 Test Device A81 CB-F-1B-A CBS-A81-TD2 Test Device A81 CB-F-1B-A CBS-A81-52H Truck Operated Contact A81 CB-F-1B-A CBS-A81-CS Control Switch A81 CB-F-1B-A CBS-A81-51GS Ground Sensor Relay A81 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -24 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 49 SI-P-6A Safety Injection Pump SI-20446 A 310761 RHR-F-2B-Z - X X - M09 SI-A56-52 4160 V AC Circuit Breaker A56 CB-F-1A-A A56-F10 F10-FB7/2 A56-F10/2 A56-HR9 310890 A56a A56b A56c A56d A56h None SI-A56-AM Ammeter A56 CB-F-1A-A SI-A56-AS Ammeter Switch A56 CB-F-1A-A SI-A56-50/51 Overcurrent Relay A56 CB-F-1A-A SI-A53-94-1A Bus Undervoltage Trip Relay A53 CB-F-1A-A SI-A56-CT Current Transformer (100/5) A56 CB-F-1A-A SI-CS-2449 Control Switch with Indication F10 CB-F-3A-A SI-FB7-K601A Auxiliary Relay MM-CP-12 FB7 CB-F-3A-A SI-HR9-RM0,SR1 Emergency Power Sequence Relays HR9 CB-F-1A-A SI-A56-TD1 Test Device A56 CB-F-1A-A SI-A56-TD2 Test Device A56 CB-F-1A-A SI-A56-51GS Ground Sensor Relay A56 CB-F-1A-A SI-A56-86 Lockout Relay A56 CB-F-1A-A SI-A56-G,R,W Indicating Lights A56 CB-F-1A-A SI-A56-CS Control Switch A56 CB-F-1A-A SI-A56-52Z Timing Relay A56 CB-F-1A-A SI-A56-52H Truck Operated Contact A56 CB-F-1A-A 50 SI-P-6B Safety Injection SI-20446 B 310761 RHR-F-2A-Z - X X - M10 SI-A76-52 4160 V AC Circuit Breaker A76 CB-F-1B-A A76-F10 F10-FB0/1 A76-F10/2 A76-HR0 310890 A76a A76b A76c A76d A76h None SI-A76-AM Ammeter A76 CB-F-1B-A SI-A76-AS Ammeter Switch A76 CB-F-1B-A SI-A76-50/51 Overcurrent Relay A76 CB-F-1B-A SI-A73-94-1A Bus Undervoltage Trip Relay A73 CB-F-1B-A SI-A76-CT Current Transformer (100/5) A76 CB-F-1B-A SI-CS-2459 Control Switch with Indication F10 CB-F-3A-A SI-FB0-K610B Auxiliary Relay MM-CP-13 FB0 CB-F-3A-A SI-HR0-RM0,SR1 Emergency Power Sequence Relays HR0 CB-F-1B-A SI-A76-TD1 Test Device A76 CB-F-1B-A SI-A76-TD2 Test Device A76 CB-F-1B-A SI-A76-51GS Ground Sensor Relay A76 CB-F-1B-A SI-A76-86 Lockout Relay A76 CB-F-1B-A SI-A76-G,R,W Indicating Lights A76 CB-F-1B-A SI-A76-CS Control Switch A76 CB-F-1B-A SI-A76-52Z Timing Relay A76 CB-F-1B-A SI-A76-52H Truck Operated Contact A76 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -25 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 51 SI-FV-2482 SI-FV-2483 Accumulator TK -9B Relief Valve SI-20450 SI-20450 A A 310578 310578 C-F-2-Z C-F-2-Z - - X X X X - - V3B V3C SI-E4H-FU Fuse E4H CB-F-1A-A E2T-E4H/2 E4H-G81/2 F20-G81/4 F20-G81/5 F20-G81/6 G81-H35/6 G81-H35/7 G81-H36/9 G81-H36/A H35-V3B H35-V3C H36-V3F H36-V3G 310890 E2T/7a E2T/7b E2T/7c E2T/7d E2T/7f E2T/7g E2T/7h EDE-PP-113A SI-V-17 SI-V-47 SI-FV-2495 SI-FV-2496 Accumulator TK -9D Relief Valve SI-20450 SI-20450 A A 310579 310579 C-F-2-Z C-F-2-Z - - X X X X - - V3F V3G SI-SS-2482 Selector Switch G81 CB-F-1A-A SI-CS-2482-1 Control Switch with Indication F20 CB-F-3A-A SI-CS-2482-2 Control Switch with Indication G81 CB-F-1A-A SI-CS-2483 Control Switch with Indication G81 CB-F-1A-A SI-CS-2495-1 Control Switch with Indication F20 CB-F-3A-A SI-CS-2495-2 Control Switch with Indication G81 CB-F-1A-A SI-CS-2496 Control Switch with Indication F20 CB-F-3A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SI-CS-2482-1X Auxiliary Relay F20 CB-F-3A-A SI-CS-2483-X Auxiliary Relay F20 CB-F-3A-A SI-CS-2495-1X Auxiliary Relay F20 CB-F-3A-A SI-CS-2496-X Auxiliary Relay F20 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -26 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 52 SI-FV-2475 SI-FV-2476 Accumulator TK -9A Relief Valves SI-20450 SI-20450 B B 310578 310578 C-F-2-Z C-F-2-Z - - X X X X - - V2Z V3A SI-E4C-FU Fuse E4C CB-F-1B-A E2U-E4C/3 E4C-GZ0/1 F20-GZ0/4 F20-GZ0/5 F20-GZ0/6 GZ0-H39/6 GZ0-H39/7 GZ0-H41/5 GZ0-H41/6 H39-V2Z H39-V3A H41-V3D H41-V3E 310890 E2U/7a E2U/7b E2U/7c E2U/7d E2U/7f E2U/7g E2U/7h EDE-PP-113B SI-V-3 SI-V-32 SI-FV-2477 SI-FV-2486 Accumulator TK -9C Relief Valves SI-20450 SI-20450 B B 310579 310579 C-F-2-Z C-F-2-Z - - X X X X - - V3D V3E SI-SS-2475 Selector Switch GZ0 CB-F-1B-A SI-CS-2475-1 Control Switch with Indication F20 CB-F-3A-A SI-CS-2475-2 Control Switch with Indication GZ0 CB-F-1B-A SI-CS-2476 Control Switch with Indication F20 CB-F-3A-A SI-CS-2477-1 Control Switch with Indication F20 CB-F-3A-A SI-CS-2477-2 Control Switch with Indication GZ0 CB-F-1B-A SI-CS-2486 Control Switch with Indication F20 CB-F-3A-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A SI-CS-2475-1X Auxiliary Relay F20 CB-F-3A-A SI-CS-2476-X Auxiliary Relay F20 CB-F-3A-A SI-CS-2477-1X Auxiliary Relay F20 CB-F-3A-A SI-CS-2486-X Auxiliary Relay F20 CB-F-3A-A 53 CS-V-475 SI-CS-P-6A Suction Cross Connection Valve CS-20725 B 310761 RHR-F-2B-Z - X X - V52 CS-B46-52 460 V AC Circuit Breakers B46 CB-F-1B-A B46-V52 B46-V52/1 B46-V52/2 B46-F10 B46-F10/1 310891 B46a B46c EDE-MCC-612 None CS-B46-CPT Control Power Transformer B46 CB-F-1B-A CS-B46-42/0,C Motor Starter B46 CB-F-1B-A CS-B46-49 Overload Relays B46 CB-F-1B-A CS-B46-FU Fuse B46 CB-F-1B-A CS-CS-2478 Control Switch with Indication F10 CB-F-3A-A 54 CS-FT-121 CS-FCV-121 Pressurizer Level Control - Flow CS-20725 A 310763 310762 PAB-F-1A-Z PAB-F-1J-Z X X X X X X - x S1E S82 CS-FQY-121 Power Supply FA7 CB-F-3A-A FA7-S1E FA7-S42 F41-FA7 F47-FA7 FA7-S82 310891 MM-CP-7 ED-PP-3C Inst. Air SI-V-139 CS-FI-121B Flow Indicator S42 PAB-F-1E-A CS-FY-121A Square Root Extractor FA7 CB-F-3A-A CS-FC-121 Controller FA7 CB-F-3A-A FP55321 310940 Sh. 23 FA7a Sh. 24 Sh. 25 CS-FCY-121 Driver (Auto) FA7 CB-F-3A-A CS-FCY-121A Driver (Manual) FA7 CB-F-3A-A CS-FK-121 Manual/Auto Control Station F41 CB-F-3A-A CS-FY-121C Relays FA7 CB-F-3A-A CS-FB-121A/B Comparator FA7 CB-F-3A-A CS-FI-121A Flow Indicator F41 CB-F-3A-A CS-FY-121B I/D Converter S82 PAB-F-1J-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -27 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 55 SI-V-158 Charging Pump Test Line Isolation Valve SI-20447 B 310577 C-F-1-Z - X X X L89 SI-CS-2416 Control Switch with Indication F26 CB-F-3A-A F26-H39/9 GE5-H39/7 GE5-L89 310890 E88/7f E88/7d E88/7a E88/7e E88/7b E88/7g EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A SI-ZS-V158 Valve Position Switches L89 C-F-1-Z SI-FY-2416 Solenoid Valve GE5 C-F-1-Z None 56 SI-V-159 Charging Pump Test Line Isolation Valve SI-20447 A 310577 C-F-1-Z - X X X L90 SI-CS-2406 Control Switch with Indication F26 CB-F-3A-A F26-H36/5 GE5-H36/5 GE5-L90 310890 E89/4d E89/4g E89/4a E89/4h E89/4b E89/4i E89/4c E89/4j E89/4k None EDE-MM-11 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SI-ZS-V159 Valve Position Switches L90 C-F-1-Z SI-FY-2406 Solenoid Valve GE5 C-F-1-Z 57 CS-HCV-182 Charging Line Control Valve CS-20722 A 310763 PAB-F-1A-Z X X X X - EDE-EH9-52 120 V AC Circuit Breaker EH9 CB-F-1A-A EH9-F20/2 F40-GP5 310105 EH9a EH9b 310891 F41c F41c 310940 EH9/7 EDE-PP-1E Inst. Air CS-V-143 MM-UQ-771A Power Supply F41 CB-F-3A-A CS-HC-182 Manual Controller F41 CB-F-3A-A 58 CS-V-154 RC Pump ID Seal Injection Isolation Valve CS-20726 A 310769 PP-F-5B-Z X X X - V18 CS-CS-7409-1 Control Switch with Indication F41 CB-F-3A-A B77-V18/1 B77-V18/2 B77-F41 B77-F41/1 B77-E3P 310891 B77a B77c CBA-FN-19 CBA-FN-20 EAH-FN-5A SI-V-139 CS-CS-7409-2 Control Switch with Indication B77 CB-F-1A-A CS-SS-7409 Selector Switch B77 CB-F-1A-A CS-B77-42/C Motor Starter B77 CB-F-1A-A CS-B77-49 Overload Relays B77 CB-F-1A-A CS-ZS-V154 Valve Position and Torque Switch V18 PP-F-5B-Z CS-B77-R1 Aux. Relay E3P CB-F-1A-A 59 CS-V-158 RC Pump 1C Seal Injection Isolation Valve CS-20726 A 310769 PP-F-5B-Z X X X - V17 CS-CS-7408-1 Control Switch with Indication F41 CB-F-3A-A B76-V17/1 B76-V17/2 B76-F41 B76-F41/1 B76-E3P 310891 B76a B76c CBA-FN-19 CBA-FN-20 EAH-FN-5A SI-V-139 CS-CS-7408-2 Control Switch with Indication B76 CB-F-1A-A CS-SS-7408 Selector Switch B76 CB-F-1A-A CS-B76-42/0,C Motor Starter B76 CB-F-1A-A CS-B76-49 Overload Relays B76 CB-F-1A-A CS-ZS-V158 Valve Position and Torque Switch V17 PP-F-5B-Z CS-B76-R1 Aux. Relay E3P CB-F-1A-A 60 CS-V-162 PC Pump 1B Seal Injection Isolation CS-20726 A 310769 PP-F-1A-Z X X X - V16 CS-CS-7407-1 Control Switch with Indication F41 CB-F-3A-A B75-V16/1 B75-V16/2 B75-F41 B75-F41/1 310891 B75a B75c CBA-FN-19 CBA-FN-20 EAH-FN-5A SI-V-139 CS-CS-7407-2 Control Switch with Indication B75 CB-F-1A-A CS-SS-7407 Selector Switch B75 CB-F-1A-A CS-B75-42/O,C Motor Starters B75 CB-F-1A-A CS-B75-49 Overload Relays B75 CB-F-1A-A CS-ZS-V162 Valve Position and Torque Switches V16 PP-F-1A-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -28 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 61 CS-V-166 RC Pump 1A Seal Injection Isolation Valve CS-20726 A 310769 PP-F-1A-Z X X X - V15 CS-CS-7406-1 Control Switch with Indication F41 CB-F-3A-A B74-V15/1 B74-V15/2 B74-F41 B74-F41/1 310891 B74a B74c CBA-FN-19 CBA-FN-20 EAH-FN-5A SI-V-139 CS-CS-7406-2 Control Switch with Indication B74 CB-F-1A-A CS-SS-7406 Selector Switch B74 CB-F-1A-A CS-B74-42/0,C Motor Starters B74 CB-F-1A-A CS-B74-49 Overload Relays B74 CB-F-1A-A CS-ZS-V166 Valve Position and Torque Switches V15 PP-F-1A-Z 62 CS-E-5A Seal Water Heat Exchanger CS-20726 A 310764 PAB-F-1A-Z X X - - - - - - - - - - - CS-E-5B Note 1 63 CS-E-5B Seal Water Heat Exchanger CS-20726 A 310764 PAB-F-1A-Z X X - - - - - - - - - - - CS-E-5A Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -29 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 64 CS-V-10 CS-V-28 CS-V-44 CS-V-59 Reactor Coolant Pumps Seal Leakoff Isolation CS-20726 CS-20726 CS-20726 CS-20726 A A A A 310576 310576 310583 310577 C-F-1-Z C-F-1-Z C-F-1-Z C-F-1-Z X X X X X X X X X X X X X X X X LA6 LA7 LA8 LA9 EDE-E89-72 125 V DC Circuit Breakers E89 CB-F-1A-A E89-E4F/1 E4F-F38 F31-H36/2 F38-H36 GA4-H36/4 GA4-LA6/1 GE5-H36/6 GE5-H36/7 GE4-H35/3 GA5-H35/3 F41-H36/3 F38-H35/3 F38-H35/2 GA5-LA7/1 GE4-LA8/1 GE5-LA9/1 GE5-L96/1 GE5-L98/1 310891 E89/7a E89/7e E89/7b E89/7f E89/7c E89/7g ED-PP-122B Inst. Air CS-V-167 CS-V-168 CS-E4F-FU-5,6,7,8 Fuses E4F CB-F-1A-A CS-CS-7400 Control Switch with Indication F31 CB-F-3A-A CS-CS-7400-1X Auxiliary Relay F31 CB-F-3A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A CS-FY-7400 Solenoid Valve GA4 C-F-1-Z CS-ZS-V10 Valve Position Switches LA6 C-F-1-Z CS-CS-7401 Control Switch with Indication F31 CB-F-3A-A CS-CS-7401-1X Auxiliary Relay F31 CB-F-3A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A CS-FY-7401 Solenoid Valve GA5 C-F-1-Z CS-ZS-V28 Valve Position Switches LA7 C-F-1-Z CS-CS-7402 Control Switch with Indication F31 CB-F-3A-A CS-CS-7402-1X Auxiliary Relay F31 CB-F-3A-A CS-FY-7402 Solenoid Valve GE4 C-F-1-Z CS-ZS-V44 Valve Position Switches LA8 C-F-1-Z CS-CS-7403 Control Switch with Indication F31 CB-F-3A-A CS-CS-7403-1X Auxiliary Relay F31 CB-F-3A-A CS-FY-7403 Solenoid Valve GE5 C-F-1-Z CS-ZS-V59 Valve Position Switches LA9 C-F-1-Z CS-CS-7413 Control Switch with Indication F41 CB-F-3A-A CS-FY-7413 Solenoid Valve GE5 C-F-1-Z CS-ZS-V177 Valve Position Switches L96 C-F-1-Z CS-CS-7414 Control Switch with Indication F31 CB-F-3A-A CS-FY-7414 Solenoid Valve GE5 C-F-1-Z CS-ZS-V185 Valve Position Switches L98 C-F-1-Z CS-CS-7403 Control Switch with Indication F31 CB-F-3A-A CS-CS-7403-1X Auxiliary Relay F31 CB-F-3A-A CS-FY-7403 Solenoid Valve GE5 C-F-1-Z CS-ZS-V59 Valve Position Switches LA9 C-F-1-Z CS-CS-7413 Control Switch with Indication F41 CB-F-3A-A CS-FY-7413 Solenoid Valve GE5 C-F-1-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -30 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 64 CS-V-10 CS-V-28 CS-V-44 CS-V-59 (Continued) Reactor Coolant Pumps Seal Leakoff Isolation CS-ZS-V177 Valve Position Switches L96 C-F-1-Z CS-CS-7414 Control Switch with Indication F31 CB-F-3A-A CS-FY-7414 Solenoid Valve GE5 C-F-1-Z CS-ZS-V185 Valve Position Switches L98 C-F-1-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.2 -31 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 65 CS-V-145 Letdown Heat Exchanger E -2 to E-8 Isolation Valve CS-20722 A 310577 C-F-1-Z X X X X LH2 CS-CS-7447 Control Switch with Indication F40 CB-F-3A-A F40-FB1/1 F40-H36/2 GE4-H36/1 GE4-LF7/2 GE5-H36/8 GE5-L99/1 GE5-LH2/3 FB1-F59 310891 E97/11a E97/11g E97/11b E97/11h E97/11c E97/11i E97/11d E97/11j E98/11k RC-LCV-459 RC-LCV-460 RC-LY/459CX1 Low Level Auxiliary Relay FB1 CB-F-3A-A RC-LY/460DX1 Low Level Auxiliary Relay FB1 CB-F-3A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-ZS-LCV-460 Letdown Isolation Valve Position Switch LF7 C-F-1-Z RC-ZS-LCV-459 Letdown Isolation Valve Position Switch L99 C-F-1-Z CS-FY-7447 Solenoid Valve GE5 C-F-1-Z CS-ZS-V145 Valve Position Switches LH2 C-F-1-Z CS-F42-R1 Aux. Rly F42 CB-F-3A-A EDE-FS9-KB20 Aux. Rly FS9 CB-F-3A-A 66 RC-E-10 Pressurizer Heaters Control Group RC-20846 A 310598 C-F-1-Z X - X - M26 RC-AM4-52H Truck Operated Switch Contacts AM4 CB-F-1A-A AM4-F31 F31-FB1/4 310882 AM4b AM4d AM4e AM4f AM4g CBA-FN-19 CBA-FN-20 RC-CS-7320 Control Switch with Indication F31 CB-F-3A-A RC-LYY-459CXA Level Auxiliary Relay FB1 CB-F-3A-A RC-LYY-460DXA Level Auxiliary Relay FB1 CB-F-3A-A RC-AM4-FU 15 A Fuses AM4 CB-F-1A-A RC-AM4-52 480 V AC Circuit Breaker AM4 CB-F-1A-A 67 CS-V-210 Charging Pump 2A Discharge Valve CS-20725 A 310764 PAB-F-1C-A - X - - - - - - - - - - CS-V-220 Note 1 68 CS-V-219 Charging Pump 2B Bypass Valve CS-20725 B 310764 PAB-F-1D-A - X - - - - - - - - - - CS-V-221 Note 1 69 CS-V-220 Charging Pump 2B Discharge Valve CS-20725 B 310764 PAB-F-1D-A - X - - - - - - - - - - CS-V-210 Note 1 70 CS-V-221 Charging Pump 2A Bypass Valve CS-20725 A 310764 PAB-F-1C-A - X - - - - - - - - - - CS-V-219 Note 1 Notes: 1. The equipment is mechanical with no electrical requirement.

2. During normal operation, the valve is in its safe shutdown position.

To prevent spurious operations, this equipment will be disabled at the appropriate control location.

3. Disabling the valve at the appropriate control location will reposition it for shut shutdown.
4. Air is not needed to position or to reposition the valve for safe shutdown.
5. This valve is permanently disabled by tripping its circuit breaker at the MCC.
6. During normal operation, the valve is in its hot shutdown position.

To prevent spurious operations, this equipment will be disabled at the appropriate control location. For cold shutdown, the valve will be energized for repositioning.

7. These valves are closed with their circuit breakers locked open during 100% power operation.

This will prevent spurious operation. For cold shutdown, these valves are energized for repositioning.

8. These valves are also listed in Table MCR 3.1.3.6.
9. Electrical group conduit drawing, 9763

-F-310764, is listed only to show the fire zone corresponding to the area where the charging pump oil coolers are located (9763 -F-805213 and -F-815214). SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.3 -1 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CS-TK-4A Boric Acid Storage Tank CS-20729 A/B 310766 PAB-F-2B-Z - X - - - - - - - - - - - CS-TK-4B Note 1 2 CS-TK-4B Boric Acid Storage Tank CS-20729 A/B 310766 PAB-F-2B-Z - X - - - - - - - - - - - CS-TK-4A Note 1 3 CS-V-410 Boric Acid Tank 4A Outlet Valve CS-20729 A/B 310766 805216 805229 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-416 CS-V-1207 Notes 1, 2, 3 4 CS-V-416 Boric Acid Tank 4B Outlet Valve CS-20729 A/B 310766 805216 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-410 CS-V-1207 Notes 1, 2, 3 5 CS-V-423 Boric Acid Recirculation Valve CS-20729 A 310766 805216 805230 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-431 CS-V-1207 Notes 1, 2, 3 6 CS-V-431 Boric Acid Recirculation Valve CS-20729 B 310766 805216 805230 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-423 CS-V-1207 Notes 1, 2, 3 7 CS-V-437 Boric Acid Transfer Pump's Suction Cross -Over Line Isolation Valve CS-20729 A 310766 805216 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-1207 Notes 1, 2, 3 8 CS-V-439 Charging Pump Isolation Valve CS-20729 A/B 310766 805216 805229 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-426 Notes 1, 2, 3 9 CS-V-442 Charging Pump Isolation Valve CS-20729 A/B 310766 805216 805229 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-426 Notes 1, 2, 3 10 CS-P-3A Boric Acid Transfer Pump CS-20729 A 310766 PAB-F-2B-Z - X X - M43 CS-B88-52 460 V AC Circuit Breaker B88 CB-F-1A-A B88-F41 B88-M43 B88-M43/1 310891 B88a B88c CBA-FN-19 CBA-FN-20 EDE-MCC-512 CS-P-3B CS-B88-CPT Control Transformer B88 CB-F-1A-A CS-B88-42 Motor Starter B88 CB-F-1A-A CS-B88-49 Overload Relay B88 CB-F-1A-A CS-M43-49 Overload M43 PAB-F-2B-Z CS-B88-FU Fuse B88 CB-F-1A-A CS-SS-7435 Selector Switch B88 CB-F-1A-A CS-CS-7435-2 Control Switch with Indication B88 CB-F-1A-A CS-CS-7435-1 Control Switch with Indication F41 CB-F-3A-A CS-EC8-R1 Auxiliary Relay EC8 CB-F-1A-A

.* Table notes on last page of table

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.3 -2 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 CS-P-3B Boric Acid Transfer Pump CS-20729 B 310766 PAB-F-2B-Z - X X - M44 CS-B89-52 460 V AC Circuit Breaker B89 CB-F-1B-A B89-F48 B89-M44 B89-M44/1 F48-FT0 310891 B89a B89c CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-P-3A CS-B89-CPT Control Transformer B89 CB-F-1B-A CS-B89-42 Motor Starter B89 CB-F-1B-A CS-B89-49 Overload Relay B89 CB-F-1B-A CS-M44-49 Overload M44 PAB-F-2B-Z CS-SS-7436 Selector Switch B89 CB-F-1B-A CS-CS-7436-2 Control Switch with Indication B89 CB-F-1B-A CS-CS-7436-1 Control Switch with Indication F41 CB-F-3A-A CS-FT0-KA1 Auxiliary Relay Isolation Cab FT0 CB-F-3A-A CS-B89-FU Fuse B89 CB-F-1B-A 12 CS-V-426 Boric Acid F -5 to Charging Pumps Isolation Valve CS-20729 B 310766 PAB-F-2B-Z - X X - V04 CS-B94-52 460 V Circuit Breaker B94 CB-F-1B-A B94-V04 B94-V04/1 B94-V04/2 B94-F48 B94-F48/1 310891 B94a B94c CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-V-439 CS-V-442 CS-B94-CPT Control Transformer B94 CB-F-1B-A CS-B94-42/0,C Motor Starter B94 CB-F-1B-A CS-B94-49 Overload Relay B94 CB-F-1B-A CS-B94-FU Fuse B94 CB-F-1B-A CS-SS-7437 Selector Switch B94 CB-F-1B-A CS-CS-7437-2 Control Switch with Indication B94 CB-F-1B-A CS-CS-7437-1 Control Switch F41 CB-F-3A-A CS-ZS-V426 Valve Position and Open/Close Torque Switches V04 PAB-F-2B-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.3 -3 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 CP-CP-111 Reactor Trip Switchgear Cab 1

- B 310442 CB-F-1A-A X - X - HD2 CP-CS-6611-1 Control Switch F42 CB-F-3A-A E94-HD2 F10-HD2 F48-HD2/1 F48-HD2  310944 HD2a HD2d HD2b EDE-PP-111B CP-CP-111 Train A              CP-CS-6601-1 Control Switch F42 CB-F-3A-A                CP-CS-6601-2 Control Switch F10 CB-F-3A-A                SI-CS-2471-1 Control Switch F10 CB-F-3A-A                  SI-CS-2471-2 Control Switch F50 CB-F-3A-A                  CP-ZL-6601-3 Indicator Light F42 CB-F-3A-A                  CP-ZL-6601-6 Indicator Light F42 CB-F-3A-A                  CP-ZL-6601-2 Indicator Light F10 CB-F-3A-A                  CP-HD2-52H Truck Operated Contact HD2 CB-F-1A-A                  CP-HD3-52H Truck Operated Contact HD3 CB-F-1A-A                  CP-HD2-STB Shunt Trip HD2 CB-F-1A-A                  CP-HD2-S1 Pushbutton HD2 CB-F-1A-A                  CP-HD3-X1B Auxiliary Relay HD3 CB-F-1A-A                  CP-HD2-X5B Auxiliary Relay HD2 CB-F-1A-A                  CP-HD2-FU Fuses HD2 CB-F-1A-A                  CP-HD3-X2B Auxiliary Relay HD3 CB-F-1A-A                  CP-HD3-X4B Auxiliary Relay HD3 CB-F-1A-A                  CP-HD2-X3B Auxiliary Relay HD2 CB-F-1A-A                  CP-HD2-XB Auxiliary Relay HD2 CB-F-1A-A                  CP-HD2-X6B Auxiliary Relay HD3 CB-F-1A-A                  CP-HD3-52 Circuit Breaker HD3 CB-F-1A-A                  CP-HD3-X3A Auxiliary Relay HD3 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.3

-4 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 14 CP-CP-111 Reactor Trip Switchgear Cab 2

- A 310442 CB-F-1A-A X - X - HD3 CP-CS-6611-1 Control Switch F42 CB-F-3A-A E93-HD3 F10-HD3 F42-HD3/1 F42-HD3  310944 HD3a HD3f HD3b EDE-PP-111A CP-CP-111 Train B              CP-CS-6601-1 Control Switch F42 CB-F-3A-A                CP-CS-6601-2 Control Switch F10 CB-F-3A-A                SI-CS-2471-1 Control Switch F10 CB-F-3A-A                  SI-CS-2471-2 Control Switch F50 CB-F-3A-A                  CP-ZL-6601-4 Indicator Light F10 CB-F-3A-A                  CP-ZL-6601-5 Indicator Light F42 CB-F-3A-A                  CP-ZL-6601-1 Indicator Light F42 CB-F-3A-A                  CP-HD2-S1 Pushbutton HD2 CB-F-1A-A                  CP-HD2-STA Shunt Trip HD2 CB-F-1A-A                  CP-HD2-52 Circuit Breaker HD2 CB-F-1A-A                  CP-HD2-52H Truck Operated Contact HD2 CB-F-1A-A                  CP-HD3-FU Fuses HD3 CB-F-1A-A                  CP-HD3-52H Truck Operated Contact HD3 CB-F-1A-A                  CP-HD2-X3A Auxiliary Relay HD2 CB-F-1A-A                  CP-HD2-X3B Auxiliary Relay HD2 CB-F-1A-A                  CP-HD2-XA Auxiliary Relay HD2 CB-F-1A-A                  CP-HD3-X2A Auxiliary Relay HD3 CB-F-1A-A                  CP-HD3-X4A Auxiliary Relay HD3 CB-F-1A-A                  CP-HD3-X6A Auxiliary Relay HD3 CB-F-1A-A      15 CS-V-1207 Boric Acid Transfer Pump's suction Cross

-over line isolation Valve CS-20729 B 310766 805216 PAB-F-2B-Z - X - - - - - - - - - - CS-V-437 Notes 1,2,3 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.3 -5 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 16 CS-FCV-110A CS-FCV-111A CS-FCV-110B CS-FCV-111B Boration & Dilution Flow Control Valves CS-20729 A 310766 PAB-F-2B-Z PAB-F-2B-Z PAB-F-2B-Z PAB-F-2B-Z - X X X LG2 LG1 LG4 LG5 CS-E97/11-72 125 V DC Circuit Breaker E97 NES-F-1A-Z F41-YB5 F41-YB5/1 LG2-YB5 LG4-YB5 LG5-YB5 LG1-YB5 LG2-YB5/1 GP7-YB5 LG1-YB5/1 F41-FB1/1 F41-FB1/2 F41-GP7/1 F41-GP7 310891 E97/11a,c,d E97/11g,h,k

- - -          CS-CS-110A Control Switch with Indication F41 CB-F-3A-A                CS-FB1-MUX5 Auxiliary Relay FB1 CB-F-3A-A                 CS-FY-110-A1,-A2 Pilot Solenoid LG2 PAB-F-2B-Z                 CS-ZS-110A Valve Position Switch LG2 PAB-F-2B-Z                 CS-D1,D2 Noise Suppression Diode LG2 PAB-F-2B-Z                 CS-CS-110B Control Switch with Indication F41 CB-F-3A-A                 CS-CS-110C Control Switch F41 CB-F-3A-A                  CS-FB1-MUX3,4,5,6,7 Auxiliary Relay FB1 CB-F-3A-A                  CS-FY-110F Pilot Solenoid GP7 PAB-F-2C-Z                   CS-ZS-110B Valve Position Switch LG4 PAB-F-2B-Z                  CS-D3 Noise Suppression Diode GP7 PAB-F-2C-Z                  CS-CS-111A Control Switch with Indication F41 CB-F-3A-A                  CS-FY-111A-1 Pilot Solenoid LG1 PAB-F-2B-Z                  CS-ZS-111A Valve Position Switch LG1 PAB-F-2B-Z                  CS-D4 Noise Suppression Diode LG1 PAB-F-2B-Z                  CS-CS-111B Control Switch with Indication F41 CB-F-3A-A                  CS-FY-111F Pilot Solenoid GP7 PAB-F-2C-Z                  CS-ZS-111B Valve Position Switch LG5 PAB-F-2B-Z                  CS-D5 Noise Suppression Diode GP7 PAB-F-2C-Z                  CS-CS-110D Control Switch F41 CB-F-3A-A F41-FB1/3 F41-FB1/4 FB1/1a,b  FB1/1e CS-FB1-MUX1,2,3,4, 5,5A,8A,9 Auxiliary Relay FB1 CB-F-3A-A                  CS-FB1-X Auxiliary Relay FB1 CB-F-3A-A                  CS-F41-R,G Indicator Light F41 CB-F-3A-A                  CS-CS-110C Control Switch F41 CB-F-3A-A                  CS-ITB-111Q Input/Output Module F41 CB-F-3A-A                  CS-LY-112DX Auxiliary Relay FB1 CB-F-3A-A                  CS-RC RC Noise Suppression FB1 CB-F-3A-A                  CS-FIY-110 Flow Indicating Converter S60 PAB-F-2B-Z EH5-S60 S60-S71 F47-S60 F47-LG2 EH5/1a EH5/1c                CS-FIC-110 Flow Controller F41 CB-F-3A-A                 CS-FT-110 Flow Transmitter S71 PAB-F-2B-Z                  CS-ZY-110A Positioner for CS-FCV-110A LG2 PAB-F-2B-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.3

-6 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 16 (Cont) CS-FIC-110,111 Flow Controller F41 CB-F-3A-A F47-SR5 F47-LG1 EJ9/15ca,cb,cd,ce EJ9/15cc CS-FIQ-111 Flow Indicating Controller F41 CB-F-3A-A CS-ZY-111A Positioner for CS-FCV-111A LG1 PAB-F-2B-Z CS-UQ-111 Power Supply F41 CB-F-3A-A CS-FT-111-1,2 Flow Transmitter SR5 PAB-F-2B-Z CS-ITB-110C,111C, 111Q Input/Output Module F41 CB-F-3A-A CS-CS-110C,110D Control Switch F41 CB-F-3A-A CS-FB1-MUX4 Auxiliary Relay FB1 CB-F-3A-A CS-FB1-MUX3,4,5,6,7 Auxiliary Relay FB1 CB-F-3A-A F47-FB1 FB1/2a FB1/2d CS-ITB-110C,111C Input/Output Module F41 CB-F-3A-A CS-FB1-MUX5A,8A Auxiliary Relay FB1 CB-F-3A-A FB1-FB3 FB2-FB3 FB3/2a FB3/2a CS-FB2-MUX5B,8B Auxiliary Relay FB2 CB-F-3A-A CS-LT-112 Level Transmitter GP9 PAB-F-3B-Z FA5-GP9 FA5-FB1 ILD-1-CS-L00112 310940 FA5a FA5h FA5b FA5d CS-LQY-112 Level Loop Pwr Supply FA5 CB-F-3A-A CS-LB-112C/D & I/E Converter FA5 CB-F-3A-A CS-LYY-112D Level Bistable FA5 CB-F-3A-A CS-LY/112DX Auxiliary Relay FB1 CB-F-3A-A CS-LI-112 Level Indication GP9 PAB-F-3B-Z CS-LDY-112 Isolation Resistors FA5 CB-F-3A-A CS-IRTU-1 Computer Termination Cabinet FD1 CB-F-3A-A F41-FD1/1 310181 FD1r FD1s ILD-1-CS-F00111 17 RMW-P-16A Reactor Makeup Water Pump CS-20360 A 310763 PAB-F-1A-Z - X X - M36 - - - - - - - - Note 4 18 RMW-P-16B Reactor Makeup Water Pump CS-20360 A 310763 PAB-F-1A-Z - X X - M37 - - - - - - - - Note 4 .Notes 1. Equipment is mechanical with no electrical requirement.

2. CS-V-423, 410, 416, 431, 437, 439, 442 are non

-electrically operated valves and will be manually positioned as required to provide their reactivity control function during safe shutdown.

3. Electrical conduit plan drawing, 310766, listed only to show fire zone correlation reference to Primary Auxiliary Building area covered by piping Drawings 805216, 805229, 805230, where Valves CS-V-410, 416, 423, 431, 437, 439, 442 are identified in plan and section.
4. This equipment is listed because it can spuriously start due to cable failure in the boration & dilution flow control valve control circuits. Spurious pump start by itself from failure of its cables is not of concern since CS-FCV-111A remains closed.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -1 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 NI-NE-6690 Intermediate Range Thermal Neutron Flux Monitoring Detector - A 310565 C-F-1-Z X X X - Q05 NI-E1S/13-52 120 V AC Circuit Breaker E1S CB-F-1A-1 H40-XP8 H40-KDO KDO-QC1 QCI-QI0 G2H-QC1 QO5-XP8 E1S-KDO E1S-QC1 E1S-QI0 F10-QC1 310943 E1S/13a E1S/13b E1S/13c CBA-FN-19 CBA-FN-20 EDE-PP-11E NI-NE-6691 NI-E1S/14-52 120 V AC Circuit Breaker E1S CB-F-1A-A NI-E1S/15-52 120 V AC Circuit Breaker E1S CB-F-1A-A NI-NI-6690-3&4 Excore Wide -Range Thermal Neutron Flux Indicators F10 CB-F-3A-A NI-NT-6690 Excore Wide -Range Transmitter KDO ET-F-1A-A NI-NM-6690 Excore Wide -Range Signal Processor QC1 CB-F-1A-A NI-NM-6690J Excore Wide -Range Signal Processor Expansion Box QI0 CB-F-1A-A EDE-TBX-XP8 Junction Box XP8 C-F-1-Z EDE-NM-116 Electrical Penetration H40 C-F-2-Z, ET-F-1A-A 2 NI-NE-6691 Intermediate Range Thermal Neutron Flux Monitoring Detector - B 310565 C-F-1-Z X X X - Q07 NI-E1T/13-52 120 V AC Circuit Breaker E1T CB-F-1B-A H21-XP9 H21-KD1 KD1-QDO QDO-QJ1 G2K-QD0 QO7-XP9 E1T-KD1 E1T-QD0 E1T-QJ1 F20-QD0 310943 E1T/13a E1T/13b E1T/13c CBA-FN-32 CBA-FN-33 EDE-PP-11F NI-NE-6690 NI-E1T/14-52 120 V AC Circuit Breaker E1T CB-F-1B-A NI-E1T/15-52 120 V AC Circuit Breaker E1T CB-F-1B-A NI-NI-6691-3&4 Excore Wide -Range Thermal Neutron Flux Indicators G2K CB-F-1B-A NI-NT-6691 Excore Wide -Range Transmitter KD1 ET-F-1C-A NI-NM-6691 Excore Wide -Range Signal Processor QD0 CB-F-1B-A NI-NM-6691J Excore Wide -Range Signal Processor Expansion Box QJ1 CB-F-1B-A EDE-TBX-XP9 Junction Box XP9 C-F-1-Z EDE-NM-97 Electrical Penetration H21 C-F-1-Z, ET-F-1C-A NI-NI-6691-1&2 Excore Wide -Range Thermal Neutron Flux Indicators F20 CB-F-3A-A 3 CS-LT-102 CS-TK-4A Boric Acid Tank Level CS-20729 A 310766 PAB-F-2B-Z - X X - RJ7 CS-LI-102 Level Indicator F41 CB-F-3A-A FA1-RJ7 310942 FA1a FA1d MM-CP-1 CS-LT-7464 MM-CP-1 Process Protection System Cabinet (PPC) No. 1 FA1 CB-F-3A-A F47-FA1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -2 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 RC-TE-413A RC Loop 1 Wide-Range Hot Leg Temperature RC-20841 A 310582 C-F-1-Z X X X - TB7 RC-TI-413A Temperature Indicator F41 CB-F-3A-A TB7-X40 H44-X40/1 FA1-H44/3 F47-FA1/1 310942 FA1r FA1v E01/9 MM-CP-1 IC-TE-XX RC-TR-413A Temperature Recorder F41 CB-F-3A-A MM-CP-1 PPC No. 1 FA1 CB-F-3A-A EDE-TBX-X40 Terminal Box X40 C-F-1-Z EDE-MM-120 Electrical Penetration H44 C-F-2-Z, ET-F-1A-A 5 RC-TE-443A RC Loop 4 Wide-Range Hot Leg Temperature RC-20844 A 310583 C-F-1-Z X X X - TB0 RC-TI-443A Temperature Indicator F41 CB-F-3A-A TB0-X40 H44-X40/1 FA1-H44/3 F47-FA1/2 310942 FA1r FA1v FA1y MM-CP-1 IC-TE-XX MM-CP-1 PPC No. 1 FA1 CB-F-3A-A EDE-TBX-X40 Terminal Box X40 C-F-1-Z EDE-MM-120 Electrical Penetration H44 C-F-2-Z, ET-F-1A-A 6 RC-PT-405 RC Loop 1 Wide-Range Hot Leg Pressure RC-20845 A 310694 ET-F-1C-A X X X - P78 RC-PI-405-1 Pressure Indicator F40 CB-F-3A-A FA1-P78/1 F47-FA1/3 F47-FA1/2 F10-F47 F10-F47/1 310942 FA1r FA1v FA1w FA1z MM-CP-1 RC-PT-403 RC-PR-405 Pressure Recorder F41 CB-F-3A-A MM-CP-1 PPC No. 1 FA1 CB-F-3A-A RC-PI-405A-1 Pressure Indicator F40 CB-F-3A-A RC-PI-405-2 Pressure Indicator F10 CB-F-3A-A RC-PI-405A-2 Pressure Indicator F10 CB-F-3A-A 7 RC-TE-423A RC Loop 2 Wide-Range Hot Leg Temperature RC-20842 A 310582 C-F-1-Z X X X - TB8 RC-TI-423A Temperature Indicator F41 CB-F-3A-A TB8-X48 H45-X48 FA1-H45/2 F47-FA1/1 310942 FA1r FA1s FA1y MM-CP-1 IC-TE-XX MM-CP-1 PPC No. 1 FA1 CB-F-3A-A EDE-TBX-X48 Terminal Box X48 C-F-1-Z EDE-MM-121 Electrical Penetration H45 C-F-2-Z, ET-F-1A-A 8 RC-TE-433A RC Loop 3 Wide-Range Hot Leg Temperature RC-20843 A 310583 C-F-1-Z X X X - TB9 RC-TI-433A Temperature Indicator F41 CB-F-3A-A H45-X94 TB9-X94 FA1-H45/2 F47-FA1/2 310942 FA1r FA1s FA1w FA1y MM-CP-1 IC-TE-XX RC-TR-433A Temperature Recorder F41 CB-F-3A-A MM-CP-1 PPC No. 1 FA1 CB-F-3A-A EDE-TBX-X94 Terminal Box X94 C-F-1-Z EDE-MM-121 Electrical Penetration H4 C-F-2-Z, ET-F-1A-A 9 RC-LT-459 RC-E-10 Pressurizer Level RC-20846 A 310579 C-F-2-Z X X X - GN5 RC-LI-459A Level Indicator F31 CB-F-3A-A GN5-H45/1 FA1-H45/1 F38-FA1/1 310942 FA1s FA1v FA1w MM-CP-1 RC-LT-460 RC-LR-459A Level Recorder F40 CB-F-3A-A MM-CP-1 PPC No. 1 FA1 CB-F-3A-A EDE-MM-121 Electrical Penetration H45 C-F-2-Z, ET-F-1A-A 10 CS-LT-106 CS-TK-4B Boric Acid Tank Level CS-20729 B 310766 PAB-F-2B-Z - X X - RJ0 CS-LI-106 Level Indicator F41 CB-F-3A-A FA2-RJ0 F48-FA2 310942 FA2a FA2d MM-CP-2 CS-LT-7464 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -3 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 RC-TE-423B RC Loop 2 Wide-Range Cold Leg Temperature RC-20842 B 310582 C-F-1-Z X X X - TC2 RC-TI-423B Level Indicator F41 CB-F-3A-A TC2-X52 H55-X52/1 F48-FA2/1 FA2-H55/6 310942 FA2r FA2s FA2w FA2x MM-CP-2 FW-PT-524 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A EDE-TBX-X52 Terminal Box X52 C-F-1-Z EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 12 RC-TE-413B RC Loop 1 Wide-Range Cold Leg Temperature RC-20841 B 310582 C-F-1-Z X X X - TC1 RC-TI-413B Temperature Indicator F41 CB-F-3A-A TC1-X14 H55-X14 F48-FA2/1 FA2-H55/6 310942 FA2r FA2s FA2w FA2x MM-CP-2 FW-PT-514 RC-TR-413B Temperature Recorder F41 CB-F-3A-A MM-CP-2 PPC No. 2 FA2 CB-F-3A-A EDE-TBX-X14 Terminal Box X14 C-F-1-Z EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 13 RC-TE-433B RC Loop 3 Wide-Range Cold Leg Temperature RC-20843 B 310583 C-F-1-Z X X X - TC3 RC-TI-433B Temperature Indicator F41 CB-F-3A-A TC3-X69 H55-X69 FA2-H55/7 F48-FA2/2 310942 FA2t FA2y FA2z MM-CP-2 FW-PT-514 RC-TR-433B Temperature Recorder F41 CB-F-3A-A MM-CP-2 PPC No. 2 FA2 CB-F-3A-A EDE-TBX-X69 Terminal Box X69 C-F-1-Z EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 14 RC-TE-443B RC Loop 4 Wide-Range Cold Leg Temperature RC-20844 B 310583 C-F-1-Z X X X - TC4 RC-TI-443B Temperature Indicator F41 CB-F-3A-A TC4-X86 H55-X86 FA2-H55/7 F48-FA2/2 310942 FA2r FA2t FA2y FA2z MM-CP-2 FW-PT-544 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A EDE-TBX-X86 Terminal Box X86 C-F-1-Z EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 15 RC-PT-403 RC Loop 4 Wide-Range Hot Leg Pressure RC-20845 D 310694 ET-F-1C-A X X X - P76 RC-PI-403-1 Pressure Indicator F41 CB-F-3A-A FA4-P76/1 F48-FA4/2 F48-FA4 F20-F48 310942 FA4r FA4u FA4v MM-CP-4 RC-PT-405 RC-PR-403 Pressure Recorder F41 CB-F-3A-A MM-CP-4 PPC No. 4 FA4 CB-F-3A-A RC-PI-403A-1 Pressure Indicator F41 CB-F-3A-A RC-PI-403-2 Pressure Indicator F20 CB-F-3A-A RC-PI-403A-2 Pressure Indicator F20 CB-F-3A-A 16 RC-LT-460 RC-E-10 Pressurizer Level RC-20846 B 310579 C-F-2-Z X X X - GN5 RC-LI-460A Level Indicator F31 CF-F-3A-A GN5-H55/2 FA2-H55/3 F39-FA2/1 310942 FA2r FA2w MM-CP-2 RC-LT-459 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 17 CO-LT-4096 CO-TK-25 Condenser Storage Tank Level FW-20426 A 310828 CST-F-1 X X - R53 CO-LI-4096 Level Indicator F61 CB-F-3A-A FJ7-R53 F66-FJ8 310953 FJ7g FJ7f MM-CP-153 BOP - Process Control Cabinet FJ7 CB-F-3A-A MM-CP-153 FW-LT-4252 FW-LT-4257 MM-CP-153 BOP - Process Control Cabinet FJ8 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -4 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 FW-FT-4214-2 RC-E-11A Emergency FW Header Flow FW-20688 A 310708 EFP-F-1-A X X X - GL3 FW-FI-4214-2 Flow Indicator F51 CB-F-3A-A FK0-GL3 F56-FK0 F86-FK0 310952 FK0a MM-CP-297A FW-FT-4224-2 FT-FT-4244-2 FW-LT-519 FW-FR-4214 Flow Recorder F86 CB-F-3A-A MM-CP-297A BOP - Process Control Cabinet (PCC) FK0 CB-F-3A-A 19 FW-FT-4224-2 RC-E-11B Emergency FW Header Flow FW-20688 B 310708 EFP-F-1-A X X X - GL4 FW-FI-4224-2 Flow Indicator F51 CB-F-3A-A FL2-GL4 F56-FL2 F88-FL2 310952 FL2a MM-CP-297B FW-FT-4214-2 FW-FT-4234-2 FW-LT-529 FW-FR-4224 Flow Recorder F86 CB-F-3A-A MM-CP-297B BOP - PCC FL2 CB-F-3A-A 20 FW-FT-4234-2 RC-E-11C Emergency FW Header Flow FW-20688 A 310708 EFP-F-1-A X X X - GL3 FW-FI-4234-2 Flow Indicator F51 CB-F-3A-A FK0-GL3 F56-FK0 F86-FK0 310952 FKOa FW-FT-4224-2 FW-FT-4244-2 FW-LT-537 FW-FR-4214 Flow Recorder F86 CB-F-3A-A MM-CP-297A BOP - PCC FK0 CB-F-3A-A MM-CP-297A 21 FW-FT-4244-2 RC-E-11D Emergency FW Header Flow FW-20688 B 310708 EFP-F-1-A X X X - GL4 FW-FI-4244-2 Flow Indicator F51 CB-F-3A-A FL2-GL4 F56-FL2 F88-FL2 310952 FL2a MM-CP-297B FW-FT-4214-2 FW-FT-4234-2 FW-LT-548 FW-FR-4224 Flow Recorde r F86 CB-F-3A-A MM-CP-297B BOP - PCC FL2 CB-F-3A-A 22 FW-LT-501 RC-E-11A Steam Generator Wide-Range Level FW-20686 A 310576 C-F-1-Z X X X - R1D FW-LI-501 Level Indicator F51 CB-F-3A-A FA1-H44 H44-R1D F56-FA1/3 F56/FA1 310942 FA1h FA1l FA1m MM-CP-1 FW-LT-502 FW-LT-504 FW-LT-519 MM-CP-1 PPC No. 1 FA1 CB-F-3A-A FW-XR-501 Recorder F51 CB-F-3A-A EDE-MM-120 Electrical Penetration H44 C-F-2-Z, ET-F-1A-A 23 FW-LT-502 RC-E-11B Steam Generator Wide-Range Level FW-20686 B 310576 C-F-1-Z X X X - R1E FW-LI-502 Level Indicator F51 CB-F-3A-A FA2-H55 H55-R1E F56-FA2/1 310942 FA2h FA2l FA2m MM-CP-2 FW-LT-501 FW-LT-503 FW-LT-529 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A FW-XR-502 Recorder F51 CB-F-3A-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 24 FW-LT-503 RC-E-11C Steam Generator Wide-Range Level FW-20686 C 310577 C-F-1-Z X X X - R1F FW-LI-503 Level Indicator F51 CB-F-3A-A FA3-H47/1 F56-FA3/2 H47-R1F 310942 FA3h FA3l MM-CP-3 FW-LT-502 FW-LT-504 FW-LT-537 MM-CP-3 PPC No. 3 FA3 CB-F-3A-A FW-XR-503 Recorder F51 CB-F-3A-A EDE-MM-123 Electrical Penetration H47 C-F-2-Z, ET-F-1A-A 25 FW-LT-504 RC-E-11D Steam Generator Wide-Range Level FW-20686 D 310577 C-F-1-Z X X X - R1G FW-LI-504 Level Indicator F51 CB-F-3A-A F56-FA4 FA4-H52/1 H52-R1G 310942 FA4h FA4l MM-CP-4 FW-LT-501 FW-LT-503 FW-LT-548 MM-CP-4 PPC No. 4 FA4 CB-F-3A-A FW-XR-504 Recorder F51 CB-F-3A-A EDE-MM-128 Electrical Penetration H52 C-F-1-Z, ET-F-1C-A 26 FW-PT-514 RC-E-11A Steam Generator Steam Pressure MS-20580 A 310589 MS-F-1B-Z X X X - GL6 FW-PI-514A Pressure Indicator F51 CB-F-3A-A FA1-GL6 F56-FA1 F56-FA1/4 310942 FA1h FA1l FA1m MM-CP-1 FW-PT-525 FW-PT-545 FW-PT-515 MM-CP-1 PPC No. 1 FA1 CB-F-3A-A FW-XR-501 Recorder F51 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -5 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 27 FW-PT-525 RC-E-11B Steam Generator Steam Pressure MS-20581 B 310586 MS-F-3A-Z X X X - GZ4 FW-PI-525A Pressure Indicator F51 CB-F-3A-A FA2-GZ4 F56-FA2/1 310942 FA2l FA2h FA2m MM-CP-2 FW-PT-514 FW-PT-534 FW-PT-524 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A 28 FW-PT-534 RC-E-11C Steam Generator Steam Pressure MS-20581 A 310586 MS-F-3A-Z X X X - GL5 FW-PI-534A Pressure Indicator F51 CB-F-3A-A FA1-GL5 F56-FA1 310942 FA1h FA1l FA1m MM-CP-1 FW-PT-525 FW-PT-545 FW-PT-535 MM-CP-1 PPC No. 1 FA1 CB-F-3A-A 29 FW-PT-545 RC-E-11D Steam Generator Steam Pressure MS-20580 B 310589 MS-F-1B-Z X X X - GZ6 FW-PI-545A Pressure Indicator F51 CB-F-3A-A FA2-GZ6 F56-FA2/1 310942 FA2l FA2h FA2m MM-CP-2 FW-PT-514 FW-PT-534 FW-PT-544 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A 30 FW-LT-4252 FW-P-37A CST Level CO-20426 A 310708 EFP-F-1-A - X X - P1G FW-LI-4252 Level Indicator F51 CB-F-3A-A FK0-P1G F56-FK0/1 310952 FKOa MM-CP-297A CO-LT-4096 FW-LT-4257 MM-CP-297A BOP - PCC FK0 CB-F-3A-A 31 FW-LT-4257 FW-P-37B CST Level CO-20426 B 310708 EFP-F-1-A - X X - P1F FW-LI-4257 Level Indicator F51 CB-F-3A-A FL2-P1F F56-FL2/1 310952 FL2a MM-CP-297B CO-LT-4096 FW-LT-4252 MM-CP-297B BOP - PCC FL2 CB-F-3A-A 32 IC-TE-1 Incore Temperature E -6 Core Grid Location J-8 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/M 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 33 IC-TE-4 Incore Temperature A -5 Core Grid Location H -6 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/Z 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 34 IC-TE-6 Incore Temperature Cal. Core Grid Location J -10 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/17 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 35 IC-TE-7 Incore Temperature B -5 Core Grid Location F -7 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-NH9/6 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 36 IC-TE-8 Incore Temperature B -3 Core Grid Location K -6 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/5 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 37 IC-TE-12 Incore Temperature A -8 Core Grid Location E -9 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/13 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration F97 C-F-1-Z, ET-F-1C-A 38 IC-TE-14 Incore Temperature E -3 Core Grid Location H -4 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/W 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -6 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 39 IC-TE-15 Incore Temperature F -1 Core Grid Location D -8 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/V 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 40 IC-TE-16 Incore Temperature E -4 Core Grid Location M -7 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/X 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 41 IC-TE-18 Incore Temperature D -10 Core Grid Location L -11 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/G 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 42 IC-TE-20 Incore Temperature C -10 Core Grid Location E -5 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/C 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 43 IC-TE-21 Incore Temperature B -10 Core Grid Location E -11 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/15 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 44 IC-TE-24 Incore Temperature B -9 Core Grid Location H -13 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/8 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 45 IC-TE-27 Incore Temperature B-9 Core Grid Location C -8 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/N 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 46 IC-TE-30 Incore Temperature C -9 Core Grid Location E -3 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/B 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 47 IC-TE-31 Incore Temperature A -6 Core Grid Location D -12 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/11 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 48 IC-TE-32 Incore Temperature D -4 Core Grid Location L -13 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/D 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -7 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 49 IC-TE-34 Incore Temperature F -2 Core Grid Location H -2 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/18 310965 F97g 310181 JW0n JW0t MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 50 IC-TE-37 Incore Temperature F -8 Core Grid Location P -9 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/U 310965 F97g 310181 JW0n JW0t MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 51 IC-TE-38 Incore Temperature A -2 Core Grid Location K -2 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 52 IC-TE-39 Incore Temperature A -7 Core Grid Location B -6 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B Electrical Penetration F97 CB-F-3A-A F97-H54 H54-HN9/12 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 53 IC-TE-40 Incore Temperature E -2 Core Grid Location F-14 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/H 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 54 IC-TE-41 Incore Temperature D -5 Core Grid Location N -4 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/Y 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 55 IC-TE-45 Incore Temperature E -5 Core Grid Location N -13 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/L 310965 F97g 310181 JW0n JW0s MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 56 IC-TE-47 Incore Temperature F -7 Core Grid Location A -9 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/T 310965 F97g 310181 JW0n JW0t MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 57 IC-TE-50 Incore Temperature R -6 Core Grid Location R -6 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/14 310965 F97g 310181 JW0n JW0r MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 58 IC-TE-52 Incore Temperature F -4 Core Grid Location L -15 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/S 310965 F97g 310181 JW0n JW0t MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -8 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 59 IC-TE-57 Incore Temperature F -3 Core Grid Location B -3 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/19 310965 F97g MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 310181 JW0n JW0t 60 IC-TE-58 Incore Temperature C -4 Core Grid Location B -13 B 310572 C-F-2-Z X X X - HN9 MM-CP-486B RVLIS/HELB Cabinet F97 CB-F-3A-A F97-H54 H54-HN9/16 310965 F97g MM-CP-486B RC-TE-413A RC-TE-423A RC-TE-433A RC-TE-443A EDE-MM-130 Electrical Penetration H54 C-F-1-Z, ET-F-1C-A 310181 JW0n JW0r 61 MM-CP-486B RVLIS/HELB Incore Temperature Display B 310501 CB-F-3A-A X X X - F97 RC-XX-7315-4 Plasma Display FT1 CB-F-3A-A F97-FT1 E53-FT1 310965 E53/18 E53/18 EDE-MCC-631 MM-CP-1 62 FW-LT-529 RC-E-11B Steam Generator Narrow-Range Level FW-20686 A 310578 C-F-2-Z X X X - GE9 FW-LR-529 Level Recorder F51 CB-F-3A-A GE9-H45 FA1-H45 F56-FA1 310942 FA1h MM-CP-1 FW-LT-502 FW-LI-529 Level Indicator F51 CB-F-3A-A MM-CP-1 PPC No. 1 FA1 CB-F-3A-A EDE-MM-121 Electrical Penetration H45 C-F-2-Z, ET-F-1A-A 63 FW-LT-519 RC-E-11A Steam Generator Narrow-Range Level FW-20686 B 310578 C-F-2-Z X X X - R15 FW-LI-519 Level Indicator F51 CB-F-3A-A H55-R1S FA2-H55 F56-FA2/1 310942 FA2h MM-CP-2 FW-LT-501 FW-LR-519 Level Recorder F51 CB-F-3A-A MM-CP-2 PPC No. 2 FA2 CB-F-3A-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 64 FW-LT-548 RC-E-11D Steam Generator Narrow-Range Level FW-20686 C 310579 C-F-2-Z X X X - GF8 FW-LI-548 Level Indicator F51 CB-F-3A-A GF8-H47 FA3-H47/1 F56-FA3/2 310942 FA3h MM-CP-3 FW-LT-504 MM-CP-3 PPC No. 3 FA3 CB-F-3A-A EDE-MM-123 Electrical Penetration H47 C-F-2-Z, ET-F-1A-A 65 FW-LT-537 RC-E-11C Steam Generator Narrow-Range Level FW-20686 D 310579 C-F-2-Z X X X - GN5 FW-LI-537 Level Indicator F51 CB-F-3A-A GN5-H52 FA4-H52 F56-FA4 310942 FA4h MM-CP-4 FW-LT-503 MM-CP-4 PPC No. 4 FA4 CB-F-3A-A EDE-MM-128 Electrical Penetration H52 C-F-1-Z, ET-F-1C-A 66 FW-PT-524 RC-E-11B Steam Generator Steam Pressure MS-20581 A 310586 MS-F-3A-Z X X X - GL5 FW-PI-524A Pressure Indicator F51 CB-F-3A-A FA1-GL5 F56-FA1 310942 FA1h MM-CP-1 FW-PT-525 MM-CP-1 PPC No. 1 FA1 CB-F-3A-A 67 FW-PT-544 RC-E-11D Steam Generator Steam Pressure MS-20580 A 310589 MS-F-1B-Z X X X - GL6 FW-PI-544A Pressure Indicator F51 CB-F-3A-A FA1-GL6 F56-FA1 310942 FA1h MM-CP-1 FW-PT-545 MM-CP-1 PPC No. 1 FA1 CB-F-3A-A 68 CC-TE-2171 PCCW Loop A Sup. Header Temperature CC-20205 A 310765 PAB-F-2C-Z X X X - TM0 MM-CP-297A BOP - Process Control Cabinet FK0 CB-F-3A-A FK0-TM0 F30-FK0/4 310952 FK0d FK0f MM-CP-297A CC-TE-2271 CC-TI-2171-1 Temperature Indicator F30 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 14 Table MCR 3.1.3.4 -9 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 69 CC-TE-2271 PCCW Loop B Sup. Header Temperatur e CC-20211 B 310765 PAB-F-2C-Z X X X - TM8 MM-CP-152B BOP - Process Control Cabinet FJ4 CB-F-3A-A FJ4-TM8/10 F39-FJ4/4 310952 FJ4j FJ4n MM-CP-152B CC-TE-2171 CC-TI-2271-1 Temperature Indicator F30 CB-F-3A-A 70 MM-CP-153 BOP - Process Control Cabinet

- A 310499 CB-F-3A-A X - X - FJ7 - - - - EJ9-FJ7  310953 EJ9/12 EJ9/12 ED-PP-5 MM-CP-297B  71 MM-CP-153 BOP - Process Control Cabinet
- A 310499 CB-F-3A-A X - X - FJ8 - - - - EJ9-FJ7  310953 EJ9/12 EJ9/12 ED-PP-5 MM-CP-297B  72 MM-CP-297A BOP - Process Control Cabinet
- A 310499 CB-F-3A-A X X X - FK0 - - - - EH9-FK0  310952 EH9/19 EH9/19 EDE-PP-1E MM-CP-297B  73 MM-CP-297B BOP - Process Control Cabinet
- B 310499 CB-F-3A-A X X X - FL2 - - - - EH0-FL2  310952 EH0/19 EH0/19 EDE-PP-1F MM-CP-297A  74 MM-CP-152B BOP - Process Control Cabinet
- B 310499 CB-F-3A-A X X X - FJ4 - - - - EHO-FJ4  310952 EH0/1 EH0/1 EDE-PP-1F MM-CP-297A MM-CP-152A  75 FW-PT-515 RC-E-11D Steam Generator Steam Pressure MS-20580 B 310589 MS-F-1B-Z X X X - GZ6 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A FA2-GZ6 F56-FA2/1  310492 FA2l FA2h FA2m MM-CP-2 FW-PT-514 FW-PT-534 FW-PT-544             FW-PI-515A Pressure Indicator F51 CB-F-3A-A    76 FW-PT-535 RC-E-11B Steam Generator Steam Pressure MS-20581 B 310586 MS-F-3A-Z X X X - GZ4 MM-CP-2 PPC No. 2 FA2 CB-F-3A-A FA2-GZ4 F56-FA2/1  310942 FA2l FA2h FA2m MM-CP-2 FW-PT-514 FW-PT-534 FW-PT-524             FW-PI-535 Pressure Indicator F51 CB-F-3A-A    77 MM-CP-7 Process Control System Cabinet 3
- A 310499 CB-F-3A-A X X X - FA7 - - - - EH7-FA7  310940 EH7/9 EH7/9 ED-PP-3C -  78 CS-LT-7464 Boric Acid Tank CS-TK-4B Level Transmitter CS-20729 B 310766 PAB-F-2B-Z - X X - RJ9 CS-LSY-7464 Comparator G2J CB-F-1B-A G2K-RJ9  310952 GZ0c CBA-FN-32 CS-LT-102             CS-LQY-7464 I/E Converter G2J CB-F-1B-A  CBA-FN-33 CS-LT-106              CS-LI-7464 Level Indicator G2J CB-F-1B-A   MM-UQ-5868                     MM-UQ-5869 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.5

-1 FUNCTION: SAFEGUARD ACTUATION SYSTEM PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 MM-CP-12 Solid State Protection System Cabinet - A 310501 CB-F-3A-A X X X - FB6 FB7 FF8 CBS-CS-2318-1 Control Switch Containment Spray and Isolation Phase B Actuation F10 CB-F-3A-A F10-F50 F10-F86/2 F10/F86/3 F10/FB7/7 F10-F50/1 F10-FB6/1 F10-FB6 F10-FB7/5 310949 FB6e FB6h FB6f FB6j FB6k EDE-PP-1A MM-CP-13 CBS-CS-2318-2 Control Switch Containment Spray and Isolation Phase B Actuation F10 CB-F-3A-A CBS-CS-2318-3 Control Switch Containment Spray and Isolation Phase B Actuation F50 CB-F-3A-A CBS-CS-2318-4 Control Switch Containment Spray and Isolation Phase B Actuation F50 CB-F-3A-A CBS-CS-2319 Control Switch Containment Spray Reset F10 CB-F-3A-A CS-CS-2572-1 Control Switch "T" Signal Containment Isolation Phase A Actuation F10 CB-F-3A-A CS-CS-2572-2 Control Switch "T" Signal Containment Isolation Phase A Actuation F50 CB-F-3A-A CS-CS-2573 Control Switch "T" Signal Containment Isolation Phase A Reset F10 CB-F-3A-A CBS-CS-2358 Control Switch "P" Signal Containment Isolation Phase B Reset F10 CB-F-3A-A SI-CS-2471-1 Control Switch Safety Injection Actuation F10 CB-F-3A-A SI-CS-2471-2 Control Switch Safety Injection Actuation F50 CB-F-3A-A SI-CS-2489 Control Switch Safety Injection Reset and Block F10 CB-F-3A-A PSC-E01/11-52 120 V AC Circuit Breaker E01 CB-F-1A-A MM-CP-450A Remote Disabling Control Panel G5X DG-F-2A-A E01-G5X FF8-G5X E01/2a E01/2b SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.5 -2 FUNCTION: SAFEGUARD ACTUATION SYSTEM PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 MM-CP-13 Solid State Protection System Cabinet - B 310501 CB-F-3A-A X X X - FB0 FB9 FF9 CBS-CS-2328-1 Control Switch Containment Spray and Isolation Phase B Actuation F20 CB-F-3A-A F10-F51 F10-FB9 F20-F51 F20-F51/2 F20-FB0/B F20-FB0/H F20-FB9 F20-FB9/1 F20-FB9/2 F20-FB9/3 310949 FB9e FB9h FB9f FB9j FB9k EDE-PP-1B MM-CP-12 CBS-CS-2328-2 Control Switch Containment Spray and Isolation Phase B Actuation F20 CB-F-3A-A CBS-CS-2328-3 Control Switch Containment Spray and Isolation Phase B Actuation F50 CB-F-3A-A CBS-CS-2328-4 Control Switch Containment Spray and Isolation Phase B Actuation F50 CB-F-3A-A CBS-CS-2329 Control Switch Containment Spray Reset F20 CB-F-3A-A CS-CS-2582-1 Control Switch "T" Signal Containment Isolation Phase A Actuation F20 CB-F-3A-A CS-CS-2582-2 Control Switch "T" Signal Containment Isolation Phase A Actuation F50 CB-F-3A-A CS-CS-2583 Control Switch "T" Signal Containment Isolation Phase A Reset F20 CB-F-3A-A CBS-CS-2359 Control Switch "P" Signal Containment Isolation Phase B Reset F20 CB-F-3A-A SI-CS-2471-1 Control Switch Safety Injection Actuation F10 CB-F-3A-A SI-CS-2471-2 Control Switch Safety Injection Actuation F50 CB-F-3A-A SI-CS-2499 Control Switch Safety Injection Reset and Block F20 CB-F-3A-A PSC-E02/11-52 120 V AC Circuit Breaker E02 CB-F-1B-A MM-CP-450B Remote Disabling Control Panel G5Y DG-F-2B-A E02-G5Y FF9-G5Y E02/4a E02/4b 3 MM-CP-1 Process Protection System Cabinet No. 1

- A 310501 CB-F-3A-A X X X - FA1 PSC-E01/9-52 120 V AC Circuit Breaker E01 CB-F-1A-A E01-FA1  310942 E01/9 E01/9 EDE-PP-1A MM-CP-2 MM-CP-4  4 MM-CP-2 Process Protection System Cabinet No. 2
- B 310501 CB-F-3A-A X X X - FA2 PSC-E02/9-52 120 V AC Circuit Breaker E02 CB-F-1B-A E02-FA2  310942 E02/9 E02/9 EDE-PP-1B MM-CP-1 MM-CP-3  5 MM-CP-3 Process Protection System Cabinet No. 3
- C 310501 CB-F-3A-A X X X - FA3 PSC-E03/9-52 120 V AC Circuit Breaker E03 CB-F-1A-A E03-FA3  310942 E03/9 E03/9 EDE-PP-1C MM-CP-2 MM-CP-4  6 MM-CP-4 Process Protection System Cabinet No. 4
- D 310501 CB-F-3A-A X X X - FA4 PSC-E04/9-52 120 V AC Circuit Breaker E04 CB-F-1B-A E04-FA4  310942 E04/10 E04/10 EDE-PP-1D MM-CP-1 MM-CP-3 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.5

-3 FUNCTION: SAFEGUARD ACTUATION SYSTEM PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 RC-PT-455 Protection Set I Pressurizer Pressure - Safety Injection Actuation, Clear Manual Block of Safety Injection RC-20846 A 310579 C-F-2-Z X - X - GN5 EDE-MM-121 Electrical Penetration H45 C-F-2-Z ET-F-1A-A GN5-H45/2 FA1-H45/1 FA1-FB5 FA1-FB8 9763-C-509012 9763-C-509046 9763-C-509048 310942 FA1b FA1s FA1e FA1w MM-CP-1 MM-CP-12 MM-CP MM-CP-1 Process Protection System Cabinet No. 1 FA1 CB-F-3A-A MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 8 RC-PT-456 Protection Set II Pressurizer Pressure - Safety Injection Actuation, Clear Manual Block of Safety Injection RC-20846 B 310579 C-F-2-Z X - X - GN5 EDE-MM-131 Electrical Penetration H55 C-F-1-Z ET-F-1C-A GN5-H55/5 FA2-H55/3 FA2-FB5 FA2-FB8 9763-C-509012 9763-C-509046 9763-C-509048 310942 FA2b FA2r FA2e FA2w MM-CP-2 MM-CP-12 MM-CP MM-CP-2 Process Protection System Cabinet No. 2 FA2 CB-F-3A-A MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 9 RC-PT-457 Protection Set III Pressurizer Pressure - Safety Injection Actuation, Clear Manual Block of Safety Injection RC-20846 C 310579 C-F-2-Z X - X - GN5 EDE-MM-123 Electrical Penetration H47 C-F-2-Z ET-F-1A-A GN5-H47/3 FA3-H47/3 FA3-FB5 FA3-FB8 9763-C-509012 9763-C-509046 9763-C-509048 310942 FA3b FA3r FA3e FA3v MM-CP-3 MM-CP-12 MM-CP MM-CP-3 Process Protection System Cabinet No. 3 FA3 CB-F-3A-A MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 10 RC-PT-458 Protection Set IV Pressurizer Pressure - Safety Injection Actuation RC-20846 D 310579 C-F-2-Z X - X - GN5 EDE-MM-128 Electrical Penetration H52 C-F-1-Z ET-F-1C-A GN5-H52/1 FA4-H52/2 FA4-FB5 FA4-FB8 9763-C-509012 9763-C-509046 9763-C-509048 310942 FA4b FA4r FA4e FA4u MM-CP-4 MM-CP-12 MM-CP MM-CP-4 Process Protection System Cabinet No. 4 FA4 CB-F-3A-A MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 11 SI-CS-2480 Control Switch - Steam Line Safety Injection Block Control - A 310443 CB-F-3A-A X - X - F51 MM-CP-12 Solid State Protection System Cabinet FB6 CB-F-3A-A F51-FB6 310949 FB6g FB6h FB6k MM-CP 12 SI-CS-2490 Control Switch - Steam Line Safety Injection Block Control - B 310443 CB-F-3A-A X - X - F51 MM-CP-13 Solid State Protection System Cabinet FB9 CB-F-3A-A F51-FB9 310949 FB9g FB9h FB9k MM-CP 13 SI-CS-2488 Control Switch - Pressurizer Pressure Safety Injection Block Control - A 310443 CB-F-3A-A X - X - F40 MM-CP-12 Solid State Protection System Cabinet FB6 CB-F-3A-A F40-FB6 310949 FB6g FB6h FB6k MM-CP 14 SI-CS-2498 Control Switch - Pressurizer Pressure Safety Injection Block Control - B 310443 CB-F-3A-A X - X - F41 MM-CP-13 Solid State Protection System Cabinet FB9 CB-F-3A-A F48-FB9/2 310949 FB9g FB9h FB9k MM-CP SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.5 -4 FUNCTION: SAFEGUARD ACTUATION SYSTEM PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 FW-PT-514 Protection Set I/ Steam Generator Loop 1 - Safety Injection MS-20580 A 310589 MS-F-1B-Z X - X - GL6 MM-CP-1 Process Protection Cabinet No. 1 FA1 CB-F-3A-A FA1-GL6 FA1-FB5 FA1-FB8 9763-C-509013 9763-C-509047 9763-C-509048 310942 FA1b FA1h FA1e FA1l MM-CP-1 MM-CP-12 MM-CP MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 16 FW-PT-515 Protection Set II/ Steam Generator Loop 1 - Safety Injection MS-20580 B 310589 MS-F-1B-Z X - X - GZ6 MM-CP-2 Process Protection Cabinet No. 2 FA2 CB-F-3A-A FA2-GZ6 FA2-FB5 FA2-FB8 9763-C-509015 9763-C-509047 9763-C-509048 310942 FA2b FA2h FA2e FA2l MM-CP-2 MM-CP-12 MM-CP MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 17 FW-PT-516 Protection Set IV/ Steam Generator Loop 1

- Safety Injection MS-20580 D 310589 MS-F-1B-Z X - X - PS3 MM-CP-4 Process Protection Cabinet No. 4 FA4 CB-F-3A-A FA4-PS3 FA4-FB5/1 FA4-FB8/1 9763-C-509021 9763-C-509047 9763-C-509048 310942 FA4b FA4h FA4e FA4l MM-CP-4 MM-CP-12 MM-CP MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 18 FW-PT-524 Protection Set I/ Steam Generator Loop 2 - Safety Injection MS-20581 A 310586 MS-F-3A-Z X - X - GL5 MM-CP-1 Process Protection Cabinet No. 1 FA1 CB-F-3A-A FA1-GL5 FA1-FB5 FA1-FB8 9763-C-509013 9763-C-509047 9763-C-509048 310942 FA1b FA1h FA1e FA1l MM-CP-1 MM-CP-12 MM-CP MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 19 FW-PT-525 Protection Set II/ Steam Generator Loop 2

- Safety Injection MS-20581 B 310586 MS-F-3A-Z X - X - GZ4 MM-CP-2 Process Protection Cabinet No. 2 FA2 CB-F-3A-A FA2-GZ4 FA2-FB5 FA2-FB8 9763-C-509016 9763-C-509047 9763-C-509048 310942 FA2b FA2h FA2e FA2l MM-CP-2 MM-CP-12 MM-CP MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 20 FW-PT-526 Protection Set III/ Steam Generator Loop 2

- Safety Injection MS-20581 C 310586 MS-F-3A-Z X - X - PS1 MM-CP-3 Process Protection Cabinet No. 3 FA3 CB-F-3A-A FA3-PS1 FA3-FB5/1 FA3-FB8/1 9763-C-509021 9763-C-509047 9763-C-509048 310942 FA3b FA3h FA3e FA3l FA3f MM-CP-3 MM-CP-12 MM-CP MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 21 FW-PT-534 Protection Set I/ Steam Generator Loop 3 - Safety Injection MS-20581 A 310586 MS-F-3A-Z X - X - GL5 MM-CP-1 Process Protection System Cabinet No. 1 FA1 CB-F-3A-A FA1-GL5 FA1-FB5/2 FA1-FB8/2 9763-C-509014 9763-C-509047 9763-C-509048 310942 FA1b FA1h FA1e FA1f FA1l MM-CP-1 MM-CP-12 MM-CP-13 MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.5 -5 FUNCTION: SAFEGUARD ACTUATION SYSTEM PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 22 FW-PT-535 Protection Set II/ Steam Generator Loop 3

- Safety Injection MS-20581 B 310586 MS-F-3A-Z X - X - GZ4 MM-CP-2 Process Protection System Cabinet No. 2 FA2 CB-F-3A-A FA2-GZ4 FA2-FB5/2 FA2-FB8/2 9763-C-509015 9763-C-509047 9763-C-509048 310942 FA2b FA2h FA2e FA2f FA2l MM-CP-2 MM-CP-12 MM-CP-13 MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 23 FW-PT-536 Protection Set III/ Steam Generator Loop 3 - Safety Injection MS-20581 C 310586 MS-F-3A-Z X - X - PS2 MM-CP-3 Process Protection System Cabinet No. 3 FA3 CB-F-3A-A FA3-PS2 FA3-FB5/1 FA3-FB8/1 9763-C-509021 9763-C-509047 9763-C-509048 310942 FA3b FA3h FA3e FA3f FA3l MM-CP-3 MM-CP-12 MM-CP-13 MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 24 FW-PT-544 Protection Set I/ Steam Generator Loop 4 - Safety Injection MS-20580 A 310589 MS-F-1B-Z X - X - GL6 MM-CP-1 Process Protection System Cabinet No. 1 FA1 CB-F-3A-A FA1-GL6 FA1-FB5/2 FA1-FB8/2 9763-C-509014 9763-C-509047 9763-C-509048 310942 FA1b FA1h FA1e FA1f FA1l MM-CP-1 MM-CP-12 MM-CP-13 MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 25 FW-PT-545 Protection Set II/ Steam Generator Loop 4 - Safety Injection MS-20580 B 310589 MS-F-1B-Z X - X - GZ6 MM-CP-2 Process Protection System Cabinet No. 2 FA2 CB-F-3A-A FA2-GZ6 FA2-FB5/2 FA2-FB8/2 9763-C-509016 9763-C-509047 9763-C-509048 310942 FA2b FA2h FA2e FA2f FA2l MM-CP-2 MM-CP-12 MM-CP-13 MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 26 FW-PT-546 Protection Set IV/ Steam Generator Loop 4

- Safety Injection MS-20580 D 310589 MS-F-1B-Z X - X - PS4 MM-CP-4 Process Protection System Cabinet No. 4 FA4 CB-F-3A-A FA4-PS4 FA4-FB5/1 FA4-FB8/1 9763-C-509021 9763-C-509047 9763-C-509048 310942 FA4b FA4h FA4e FA4f FA4l MM-CP-4 MM-CP-12 MM-CP-13 MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A 27 SI-PT-934 Protection Set IV, Containment Pressure - P Signal Containment Isolation Phase B Actuation, Safety Injection Actuation, Containment Spray Actuation

- D 310694 ET-F-1C-A X - X - P85 MM-CP-4 Process Protection System Cabinet No. 4 FA4 CB-F-3A-A FA4-P85/1 FA4-FB5/1 FA4-FB8/1 9763-C-509022 9763-C-509048  310942  FA4a  FA4b  FA4d  FA4e MM-CP-4 MM-CP-12 MM-CP             MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A              MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A     28 SI-PT-935 Protection Set III, Containment Pressure 

- P Signal Containment Isolation Phase B Actuation, Safety Injection Actuation, Containment Spray Actuation

- C 310694 ET-F-1C-A X - X - P86 MM-CP-3 Process Protection System Cabinet No. 3 FA3 CB-F-3A-A FA3-P86/1 FA3-FB5/1 FA3-FB8/1 9763-C-509022 9763-C-509048  310942  FA3a  FA3b  FA3d  FA3e  FA3f MM-CP-3 MM-CP-12 MM-CP             MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A              MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.5

-6 FUNCTION: SAFEGUARD ACTUATION SYSTEM PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 29 SI-PT-936 Protection Set II, Containment Pressure - P Signal Containment Isolation Phase B Actuation, Safety Injection Actuation, Containment Spray Actuation

- B 310769 PP-F-4B-Z X - X - P87 MM-CP-2 Process Protection System Cabinet No. 2 FA2 CB-F-3A-A FA2-P87 FA2-FB5/2 FA2-FB8/2 9763-C-509022 9763-C-509048  310942  FA2a  FA2b  FA2d  FA2e  FA2f MM-CP-2 MM-CP-12 MM-CP             MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A              MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A     30 SI-PT-937 Protection Set I, Containment Pressure 

- P Signal Containment Isolation Phase B Actuation, Containment Spray Actuation

- A 310769 PP-F-4B-Z X - X - P88 MM-CP-1 Process Protection System Cabinet No. 1 FA1 CB-F-3A-A FA1-P88/1 FA1-FB5/2 FA1-FB8/2 9763-C-509022 9763-C-509048  310942  FA1a  FA1b  FA1d  FA1e  FA1f MM-CP-1 MM-CP-12 MM-CP             MM-CP-12 Solid State Protection System Cabinet FB5 CB-F-3A-A              MM-CP-13 Solid State Protection System Cabinet FB8 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6

-1 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 RH-P-8A Residual Heat Removal Pump SI-20448 A 310761 RHR-F-1D-Z - X X - M11 RH-A57-52 4160 V AC Circuit Breaker A57 CB-F-1A-A A57-M11 A57-F20/1 A57-F20/2 A57-HR9 F20-FB7 310887 A57a A57g A57b A57c A57d CBA-FN-19 CBA-FN-20 EAH-FN-5A EAH-FN-31A EDE-SWG-5 RH-P-8B RH-A57-FU Fuses A57 CB-F-1A-A RH-CS-2467-2 Control Switch A57 CB-F-1A-A RH-SS-2467 Selector Switch A57 CB-F-1A-A EDE-A53-94-1A Bus Under Voltage Relay A53 CB-F-1A-A RH-A57-G,R,W Indicating Lights A57 CB-F-1A-A RH-A57-86 Lockout Relay A57 CB-F-1A-A RH-A57-52H Truck-Operated Contact A57 CB-F-1A-A RH-A57-50/51 Instrument/Time Overcurrent Relays øA, øC A57 CB-F-1A-A RH-A57-51GS Ground Sensor Relay A57 CB-F-1A-A RH-A57-AM Ammeter A57 CB-F-1A-A RH-A57-AS Ammeter Switch A57 CB-F-1A-A RH-A57-CT Current Transformers (75/5) A57 CB-F-1A-A RH-A57-TD1 CT Test Device A57 CB-F-1A-A RH-A57-ATR Transducer A57 CB-F-1A-A RH-A57-TD2 Lockout Relay Test Device A57 CB-F-1A-A RH-A57-52Z Time Delay Relay A57 CB-F-1A-A RH-CS-2467-1 Control Switch with Indication F20 CB-F-3A-A RH-HR9-PR1,RMO,SR2 Emergency Power Sequencer Relays HR9 CB-F-1A-A RH-FB7-K-601A Safety Injection Signal Actuating Relay FB7 CB-F-3A-A

.Notes:  1. This equipment is mechanical with no electrical requirements.
2. Electrical Conduit Plan Drawing 310761 is listed to show fire zone corresponding to the location of the RHR pump oil cooler which is identified in Drawing 805020.
3. Electrical Conduit Plan Drawings 310761 and 310762 are listed to show fire zone corresponding to the location of the RHR heat exchanger which is identified in Drawings 805202 and 805203.
4. Electrical Conduit Plan Drawing 310761 is listed corresponding to the location of the RHR sampling valve which is identified in Drawing 805201.
5. Air and power are not required for support as valve fails to safe shutdown position.
6. These valves are also listed in Table MCR 3.1.3.2.
7. These valves are closed with their circuit breakers locked open during 100% power operation. This will prevent spurious operation. For cold shutdown, these valves are energized for repositioning.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -2 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 RH-P-8B Residual Heat Removal Pump RH-20663 B 310761 RHR-F-1C-Z - X X - M12 RH-A77-52 4160 V AC Circuit Breaker A77 CB-F-1B-A A77-M12 A77-F20/1 A77-F20/2 A77-HR0 F20-FB0 310887 A77a A77g A77b A77c A77d CBA-FN-32 CBA-FN-33 EAH-FN-5B EAH-FN-31B EDE-SWG-6 RH-P-8A RH-A77-FU Fuses A77 CB-F-1B-A RH-CS-2468-2 Control Switch A77 CB-F-1B-A RH-SS-2468 Selector Switch A77 CB-F-1B-A EDE-A73-94-1A Bus Under Voltage Relay A73 CB-F-1B-A RH-A77-G,R,W Indicating Lights A77 CB-F-1B-A RH-A77-86 Lockout Relay A77 CB-F-1B-A RH-A77-52H Truck-Operated Contact A77 CB-F-1B-A RH-A77-50/51 Instrument/Time Overcurrent Relays øA, øC A77 CB-F-1B-A RH-A77-51GS Ground Sensor Relay A77 CB-F-1B-A RH-A77-AM Ammeter A77 CB-F-1B-A RH-A77-AS Ammeter Switch A77 CB-F-1B-A RH-A77-CT Current Transformers (75/5) A77 CB-F-1B-A RH-A77-TD1 CT Test Device A77 CB-F-1B-A RH-A77-ATR Transducer A77 CB-F-1B-A RH-A77-TD2 Lockout Relay Test Device A77 CB-F-1B-A RH-A77-52Z Time Delay Relay A77 CB-F-1B-A RH-CS-2468-1 Control Switch with Indication F20 CB-F-3A-A RH-HR0-PR1,RMO,SR2 Emergency Power Sequencer Relays HR0 CB-F-1B-A RH-FB0-K-601B Safety Injection Signal Actuating Relay FB0 CB-F-3A-A 3 RH-V-14 RH-P-8A to Cold Leg Isolation Valve RH-20662 A 310769 PP-F-1A-Z - X X - V47 RH-B57-52 460 V AC Circuit Breaker B57 CB-F-1A-A B57-V47 B57-F20 310887 B57a B57c CBA-FN-19 CBA-FN-20 RH-V-26 RH-CS-2461 Control Switch F20 CB-F-3A-A RH-ZL-2461-3 Pilot Light F20 CB-F-3A-A RH-B57-42/0,C Motor Starter B57 CB-F-1A-A RH-B57-49 Thermal Overload B57 CB-F-1A-A RH-ZS-V14 Position Switch V47 PP-F-1A-Z 4 RH-V-26 RH-P-8B to Cold Leg Isolation Valve RH-20663 B 310769 PP-F-1B-Z - X X - V48 RH-B65-52 460 V AC Circuit Breaker B65 CB-F-1B-A B65-V48 B65-F20 310887 B65a B65c CBA-FN-32 CBA-FN-33 RH-V-14 RH-CS-2462 Control Switch F20 CB-F-3A-A RH-ZL-2462-3 Pilot Light F20 CB-F-3A-A RH-B65-42/0,C Motor Starter B65 CB-F-1B-A RH-B65-49 Thermal Overload B65 CB-F-1B-A RH-ZS-V26 Position Switch V48 PP-F-1B-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -3 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 RH-V-35 RH-E-9A to Charging Pump Isolation Valve RH-20662 A 310761 RHR-F-4B-Z - X X - V53 RH-B59-52 460 V AC Circuit Breaker B59 CB-F-1A-A V49-V57 V49-V58 B59-V49 B59-F20 B59-F20/1 B59-H36 H36-V25 B59-V53/1 B59-V53/2 V25-V27 B59-Y32 310887 B59a B59c CBA-FN-19 CBA-FN-20 None RH-CS-2465 Control Switch with Indication F20 CB-F-3A-A RH-B59-42/0,C Motor Starters B59 CB-F-1A-A RH-ZS-V35 Position Switch V53 RHR-F-4B-Z SI-ZS-V89 Isolation Valve V58 RHR-F-2A-Z SI-ZS-V90 Isolation Valve V49 RHR-F-2B-Z SI-ZS-V93 Isolation Valve V57 RHR-F-2B-Z CBS-ZS-V8 Containment Sump Isolation Valve V35 PP-F-1A-Z RC-ZS-V23 RHR Letdown and Inlet Isolation Valve V25 C-F-1-Z RC-ZS-V22 RHR Letdown and Inlet Isolation Valve V27 C-F-1-Z RH-B59-49 Thermal Overload Relay B59 CB-F-1A-A EDE-TBX-X32 Terminal Box Y32 PP-F-1A-Z 6 RH-V-36 RH-E-9B to SI Pump Isolation Valve SI-20449 B 310761 RHR-F-2A-Z - X X - V54 RH-B66-52 460 V AC Circuit Breaker B66 CB-F-1B-A V49-V57/1 V57-V58 B66-V57 B66-V54/2 B66-V54/1 B66-F20 H36-V25 B66-F20/1 B66-Y35 B66-H39 H39-V26 V26-V28 310887 B66a B66c CBA-FN-32 CBA-FN-33 None RH-CS-2466 Control Switch with Indication F20 CB-F-3A-A RH-B66-42/0,C Motor Starters B66 CB-F-1B-A RH-B66-49 Thermal Overload B66 CB-F-1B-A RH-ZS-V36 Position Switch V54 RHR-F-2A-Z SI-ZS-V90 Isolation Valve V49 RHR-F-2B-Z SI-ZS-V89 Isolation Valve V58 RHR-F-2A-Z SI-ZS-V93 Isolation Valve V57 RHR-F-2B-Z CBS-ZS-V14 Containment Sump Isolation Valve V36 PP-F-1B-Z RC-ZS-V87 RHR Letdown and Inlet Isolation Valve V26 C-F-1-Z RC-ZS-V88 RHR Letdown and Inlet Isolation Valve V28 C-F-1-Z EDE-TBX-Y35 Terminal Box Y35 PP-F-1B-Z 7 RH-V-32 RHR PP to Hot Leg Isolation Valve RH-20663 B 310769 PP-F-1A-Z - X X - V51 RH-B58-52 460 V AC Circuit Breaker B58 CB-F-1B-A B58-V51 B58-F20 310887 B58a B58c CBA-FN-32 CBA-FN-33 None RH-CS-2460 Control Switch F20 CB-F-3A-A RH-ZL-2460-3 Pilot Light F20 CB-F-3A-A RH-B58-42 Motor Starter B58 CB-F-1B-A RH-B58-49 Thermal Overload B58 CB-F-1B-A RH-ZS-V32 Position Switch V51 PP-F-1A-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -4 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 8 RH-V-70 RHR to Hot Leg Isolation Valve RH-20663 A 310769 PP-F-1A-Z - X X - VB4 RH-D90-52 460 V AC Circuit Breaker D90 CB-F-1A-A D90-VB4/1 D90-F20 310887 D90a D90c CBA-FN-19 CBA-FN-20 None RH-CS-2479 Control Switch F20 CB-F-3A-A RH-ZL-2479-3 Pilot Light F20 CB-F-3A-A RH-D90-42 Motor Starter D90 CB-F-1A-A RH-D90-49 Thermal Overload D90 CB-F-1A-A RH-ZS-V70 Position Switch VB4 PP-F-1A-Z 9 RH-HCV-606 RH-FCV-618 RH-E-9A Outlet Flow control Valve and Bypass Flow Control Valve RH-20662 A 310761 RHR-F-4B-Z - X X X LG8 LH3 RC-CS-618 Control Switch F20 CB-F-3A-A F20-GK0 F20-VW3 310887 E87/2a E87/2c E87/2e E87/2d E87/2f CBA-FN-19 CBA-FN-20 RH-HCV-607 RH-FCV-619 Note 5 RC-CS-606 Control Switch F20 CB-F-3A-A RC-FY-618-1 E-9A RC Bypass Solenoid Valve VW3 RHR-F-4B-Z RC-HY-606-1 E-9A Outlet Valve GK0 RHR-F-4B-Z 10 RH-HCV-607 RH-FCV-619 RH-E-9B Outlet Flow control Valve and Bypass Flow Control Valve RH-20663 B 310761 RHR-F-4A-Z - X X X LG9 LH4 RC-CS-619 Control Switch F20 CB-F-3A-A F20-U7W F20-VW4 310887 E88/2a E88/2c E88/2e E88/2d E88/2f CBA-FN-32 CBA-FN-33 RH-HCV-606 RH-FCV-618 Note 5 RC-CS-607 Control Switch F20 CB-F-3A-A RC-FY-619-1 E-9B RC Bypass Solenoid Valve VW4 RHR-F-4A-Z RC-HY-607-1 E-9B Outlet Valve U7W RHR-F-4A-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -5 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 RC-V-22 RHR Inlet Isolation Valve RH-20841 B 310582 C-F-1-Z - X X - V27 RC-B54-52-1,2 460 V AC Circuit Breakers B54 CB-F-1B-A B54-G2J B54-G2J/1 B54-H39 B54-H24 H24-V27 H39-V27 F20-G2J F20-FF9/2 B54-V53 310882 B54a B54c B54d EDE-MCC-621 CBA-FN-32 CBA-FN-33 CAH-FN-1A CAH-FN-1B CAH-FN-1D RC-V-88 Notes 6 and 7 RC-B54-FU Fuse B54 CB-F-1B-A RC-CS-7302-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7302 Selector Switch G2J CB-F-1B-A RC-B54-42-1/0,C Motor Starters B54 CB-F-1B-A RC-B54-42-2 Motor Starter B54 CB-F-1B-A RC-B54-49-1,2 Overload Relays B54 CB-F-1B-A EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A RC-ZS-7302B Valve Position and Open/Close Torque Switches V27 C-F-1-Z RC-ZL-7302-1 Pilot Light G2J CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-CS-7302-1 Control Switch with Indication F20 CB-F-3A-A RC-ZL-7302-2 Pilot Light F20 CB-F-3A-A RH-ZS-2465B Valve Position Limit Switch and Open/Close Torque Switches V53 RHR-F-4B-Z RC-FF9-K734B PSC Actuating Auxiliary Relay FF9 CB-F-3A-A RC-EH0/16-52 120 V AC Circuit Breaker EH0 CB-F-1B-A E4J-EH0/1 E4J-G2J G2J-H39/6 H39-V26/3 GZ0-U8U ED0-GZ0/1 H39-V27/1 F20-G2J/2 F26-GZ0/4 EHO/16a EHO/16c EHO/16b EH0/16d EDE-PP-1F CBA-FN-32 CBA-FN-33 RC-CS-7310-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7310 Selection Switch G2J CB-F-1B-A RC-ZS-V87 Valve Position and Open/Close Torque Switches V26 C-F-1-Z EDE-MM-115 Electrical Penetration H39 C-F-1-Z RC-EJ4-FU9 & 10 30 Amp Fuses E4J ET-F-1C-A RC-CS-7302-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7302 Selector Switch G2J CB-F-1B-A RC-ZS-7302B Valve Position and Open/Close Torque Switches V27 C-F-1-Z RC-CS-2896-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-2896 Selector Switch GZ0 CB-F-1B-A RC-ZS-FV-2896 Valve Position Switch U8U PP-F-1B-Z RC-ED0-R1 Auxiliary Relay ED0 CB-F-1B-A RC-ED0-R2 Auxiliary Relay ED0 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -6 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS RC-V-22 (Continued) RC-CS-7302-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-7310-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-2896-1 Control Switch with Indication F29 CB-F-3A-A RC-PT-403 Wide-Range Pressure Transmitter P76 ET-F-1C-A FA4-P76/1 FA4-FB8 C-509036 310942 FA4r FA4w FA4b FA4e MM-CP-4 MM-CP-13 MM-CP-4 Process Protection System Cabinet No. 4 FA4 CB-F-3A-A MC-CP-13 Solid State Protection System Output No. 2 Cabinet FF9 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -7 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 12 RC-V-23 RHR Inlet Isolation Valve RC-20841 A 310576 C-F-1-Z X X X - V25 RC-B53-52-1,2 460 V AC Circuit Breakers B53 CB-F-1A-A B53-G2G B53-G2G/1 B53-H36 B53-H19 H36-V25/2 H19-V25 F20-G2G F20-FF8/2 B53-V53 310882 B53a B53c B53d EDE-MCC-521 CBA-FN-19 CBA-FN-20 CAH-FN-1C CAH-FN-1E CAH-FN-1F RC-V-87 Notes 6 and 7 RC-B53-FU Fuse B53 CB-F-1A-A RC-CS-7303-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7303 Selector Switch G2G CB-F-1A-A RC-ZL-7303-1 Pilot Light G2G CB-F-1A-A RC-B53-42-1/0,C Motor Starters B53 CB-F-1A-A RC-B53-42-2 Motor Starter B53 CB-F-1A-A RC-B53-49-1,2 Overload Relays B53 CF-F-1A-A EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A RC-ZS-V23 Valve Position and Open/Close Torque Switches V25 C-F-1-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-CS-7303-1 Control Switch with Indication F20 CB-F-3A-A RC-ZL-7303-2 Pilot Light F20 CB-F-3A-A RH-ZS-2465A Valve Position Switch V53 RHR-F-4B-Z RC-FF8-K-734A PSC Actuating Auxiliary Relay FF8 CB-F-3A-A RC-PT-405 Wide-Range Pressure Transmitter P78 ET-F-1C-A FA1-P78/1 FA1-FB5/2 C-509036 310942 FA1r FA1w FA1b FA1e MM-CP-1 MM-CP-12 MM-CP-1 Process Protection System Cabinet No. 1 FA1 CB-F-3A-A MM-CP-12 Solid State Protection System Output No. 2 Cabinet FF8 CB-F-3A-A RC-EH9/16-52 120 V AC Circuit Breaker EH9 CB-F-1A-A E4H-EH9/1 E4H-G2G G2G-H36/8 H36-V25/3 H36-V28/1 G81-U8T EC8-G81 F20-G2G/2 F29-G81/2 EC8-G81/1 EH9/16a EH9/16c EH9/16b EH9/16d EDE-PP-1E CBA-FN-19 CBA-FN-20 RC-CS-7303-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7303 Selection Switch G2G CB-F-1A-A RC-ZS-V23 Valve Position and Open/Close Torque Switches V25 C-F-1-Z EDE-MM-112 Electrical Penetration H36 ET-F-1A-A, C-F-2-Z RC-E4H-FU-9,10 30 Amp Fuses E4H CB-F-1A-A RC-CS-7311-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7311 Selector Switch G2G CB-F-1A-A RC-ZS-7311A Valve Position and Open/Close Torque Switches V28 C-F-1-Z RC-CS-2894-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-2894 Selector Switch G81 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -8 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS RC-V-23 (Continued) RC-ZS-FV-2894 Valve Position Switch U8T PP-F-1B-Z RC-EC8-R1 Auxiliary Relay EC8 CB-F-1A-Z RC-EC8-R2 Auxiliary Relay EC8 CB-F-1A-Z RC-CS-7311-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-7303-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-2894-1 Control Switch with Indication F29 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -9 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 RC-V-87 RHR Inlet Isolation Valve RC-20844 B 310582 C-F-1-Z X X X - V26 RC-B61-52-1,2 460 V AC Circuit Breakers B61 CB-F-1B-A B61-G2J B61-G2J/1 B61-H39 B61-H24 H39-V26/2 H24-V26 F20-G2J/1 F20-FF9/1 B61-V54 310882 B61a B61c B61d EDE-MCC-621 CBA-FN-32 CBA-FN-33 CAH-FN-1A CAH-FN-1B CAH-FN-1D RC-V-23 Notes 6 and 7 RC-B61-FU Fuse B61 CB-F-1B-A RC-CS-7310-2 Control Switch with Indicator G2J CB-F-1B-A RC-SS-7310 Selector Switch G2J CB-F-1B-A RC-ZL-7310-1 Pilot Light G2J CB-F-1B-A RC-B61-42-1/0,C Motor Starters B61 CB-F-1B-A RC-B61-42-2 Motor Starter B61 CB-F-1B-A RC-B61-49-1,2 Overload Relays B61 CB-F-1B-A RC-ZS-V87 Valve Position and Open/Close Torque Switches V26 C-F-1-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-CS-7310-1 Control Switch with Indication F20 CB-F-3A-A RC-ZL-7310-2 Pilot Light F20 CB-F-3A-A RH-ZS-2466B Valve Position Limit Switch V54 RHR-F-2A-Z RC-FF9-K734B PSC Actuating Auxiliary Relay FF9 CB-F-3A-A RC-PT-403 Wide-Range Pressure Transmitter P76 ET-F-1C-A FA4-P76/1 FA4-FB8 C-509036 310942 FA4r FA4w FA4b FA4e MM-CP-4 MM-CP-13 MM-CP-4 Process Protection System Cabinet No. 4 FA4 CB-F-3A-A MM-CP-13 Solid State Protection System Output No. 2 Cabinet FF9 CB-F-3A-A RC-EH0/16-52 120 v AC Circuit Breaker EH0 CB-F-1B-A E4J-EH0/1 E4J-GZJ G2J-H39/6 H39-V26/3 GZ0-U8U ED0-GZ0/1 H39-V27/1 F20-G2J/2 F26-GZ0/4 EH0/16a EH0/16c EH0/16b EH0/16d EDE-PP-1F CBA-FN-32 CBA-FN-33 RC-CS-7310-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7310 Selector Switch G2J CB-F-1B-A RC-ZS-V87 Valve Position and Open/Close Torque Switches V26 C-F-1-Z EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-E4J-FU-9,10 30 Amp Fuses E4J CB-F-1B-A RC-CS-7302-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7302 Selector Switch G2J CB-F-1B-A RC-ZS-7302B Valve Position and Open/Close Torque Switches V27 C-F-1-Z RC-CS-2896-2 Control Switch with Indication GZ0 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -10 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS RC-V-87 (Continued) RC-SS-2896 Selector Switch GZ0 CB-F-1B-A RC-ZS-FV-2896 Valve Position Switch U8U PP-F-1B-Z RC-ED0-R1 Auxiliary Relay ED0 CB-F-1B-A RC-ED0-R2 Auxiliary Relay ED0 CB-F-1B-A RC-CS-7302-1 Control Switch with Indication F20 CB-F-3B-A RC-CS-7310-1 Control Switch with Indication F20 CB-F-3B-A RC-CS-2896-1 Control Switch with Indication F29 CB-F-3B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -11 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 14 RC-V-88 RHR Inlet Isolation Valve RH-20662 A 310577 C-F-1-Z X X X - V28 RC-B62-52-1,2 460 V AC Circuit Breakers B62 CB-F-1A-A B62-G2G B62-G2G/1 B62-H36 B62-H19 H36-V28 H19-V28 F20-G2G/1 F20-FF8/3 B62-V54 310882 B62a B62c B62d EDE-MCC-521 CBA-FN-19 CBA-FN-20 CAH-FN-1C CAH-FN-1E CAH-FN-1F RC-V-22 Notes 6 and 7 RC-B62-FU Fuse B62 CB-F-1A-A RC-CS-7311-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7311 Selector Switch G2G CB-F-1A-A RC-ZL-7311-1 Pilot Light G2G CB-F-1A-A RC-B62-42-1/0,C Motor Starters B62 CB-F-1A-A RC-B62-42-2 Motor Starter B62 CB-F-1A-A RC-B62-49-1,2 Overload Relays B62 CB-F-1A-A RC-ZS-7311A Valve Position and Open/Close Torque Switches V28 C-F-1-Z EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-CS-7311-1 Control Switch with Indication F20 CB-F-3A-A RC-ZL-7311-2 Pilot Light F20 CB-F-3A-A RH-ZS-2466A Valve Position Limit Switch V54 RHR-F-1A-Z RC-FF8-K734A PSC Actuating Auxiliary Relay FF8 CB-F-3A-A RC-PT-405 Wide-Range Pressure Transmitter P78 ET-F-1C-A FA1-P78/1 FA1-FB5/2 C-509036 310942 FA1r FA1w FA1b FA1e MM-CP-1 MM-CP-12 MM-CP-1 Process Protection System Cabinet No. 1 FA1 CB-F-3A-A MM-CP-12 Solid State Protection System Output No. 2 Cabinet FF8 CB-F-3A-A RC-EH9/16-52 120 V AC Circuit Breaker EH9 CB-F-1A-A E4H-EH9/1 E4H-G2G G2G-H36/8 H36-V28/1 H36-V25/3 G81-U8T EC8-G81 F20-G2G/2 F29-G81/2 EC8-G81/1 EH9/16a EH9/16c EH9/16b EH9/16d EDE-PP-1E CBA-FN-19 CBA-FN-20 RC-CS-7311-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7311 Selector Switch G2G CB-F-1A-A RC-ZS-7311A Valve Position and Open/Close Torque Switches V28 C-F-1-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-E4H-FU-9,10 30 Amp Fuses E4H CB-F-1A-A RC-CS-7303-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7303 Selector Switch G2G CB-F-1A-A RC-ZS-V23 Valve Position and Open/Close Torque Switches V25 C-F-1-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.6 -12 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STANDBY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS RC-V-88 (Continued) RC-CS-2894-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-2894 Selector Switch G81 CB-F-1A-A RC-ZS-FV-2894 Valve Position Switch U8T PP-F-1B-Z RC-EC8-R1 Auxiliary Relay EC8 CB-F-1A-A RC-EC8-R2 Auxiliary Relay EC8 CB-F-1A-A RC-CS-7303-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-7311-1 Control Switch with Indication F20 CB-F-3A-A RC-CS-2894-1 Control Switch with Indication F29 CB-F-3A-A 15 RH-P-8A RHR Pump Lube Oil Cooler RH-20662 A 310761 805200 RHR-F-1D-Z - X - - - - - - - - - - Component Cooling RH-P-8B Notes 1 and 2 16 RH-P-8B RHR Pump Lube Oil Cooler RH-20663 B 310761 805200 RHR-F-1C-Z - X - - - - - - - - - - Component Cooling RH-P-8A Notes 1 and 2 17 RH-E-9A Residual Heat Removal Heat Exchanger SI-20448 A 310761 310762 805202 805203 RHR-F-3B-Z - X - - - - - - - - - - Component Cooling RH-E-9B Notes 1 and 3 18 RH-E-9B Residual Heat Removal Heat Exchanger RH-20663 B 310761 310762 805202 805203 RHR-F-3A-Z - X - - - - - - - - - - Component Cooling RH-E-9A Notes 1 and 3 19 RH-V-8 RHR Loop A Sample Valve RH-20662 A 310761 805201 RHR-F-4B-Z - X - - - - - - - - - - EAH-FN-5A EAH-FN-31A RH-V-44 Notes 1 and 4 20 RH-V-44 RHR Loop B Sample Valve RH-20663 B 310761 805201 RHR-F-4A-Z - X - - - - - - - - - - EAH-FN-5B EAH-FN-31B RH-V-8 Notes 1 and 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -1 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 SW-P-41A Service Water Loop "A" - Pump "A" SW-20794 A 301140 SW-F-1E-Z X X X - N81 SW-AQ3-52 4160 V AC Circuit Breaker AQ3 CB-F-1A-A AQ3-GN9 AQ3-VL3 AQ3-N81 AQ4-HR2 AQ4-F72/2 AQ3-F72/1 301107 AQ3a AQ3h AQ3b AQ3c AQ3d CBA-FN-19 CBA-FN-20 EDE-SWG-5 SW-P-41B or SW-P-41D SW-AQ3-FU Fuses AQ3 CB-F-1A-A SW-CS-6101-2 Control Switch AQ3 CB-F-1A-A SW-SS-6101 Selector Switch AQ3 CB-F-1A-A SW-ZS-V2 Valve Position Switch VL3 SW-F-1E-Z EDE-A53-94-2 Bus Undervoltage Relay A53 CB-F-1A-A SW-AQ3-52H Truck Operated Contact AQ3 CB-F-1A-A SW-AQ3-50/51 Inst/Time Overcurrent Relays ØA, ØC AQ3 CB-F-1A-A SW-AQ3-51GS Ground Sensor Relay AQ3 CB-F-1A-A SW-AQ3-86 Lockout Relay AQ3 CB-F-1A-A SW-AQ3-CT Current Transformers 100/5A AQ3 CB-F-1A-A SW-AQ3-TD1 Test Device AQ3 CB-F-1A-A SW-AQ3-AM Ammeter AQ3 CB-F-1A-A SW-AQ3-AS Ammeter Switch AQ3 CB-F-1A-A SW-AQ3-G,R,W Indicating Lights AQ3 CB-F-1A-A SW-AQ3-ATR Transducer AQ3 CB-F-1A-A SW-AQ3-TD2 Lockout Relay Test Device AQ3 CB-F-1A-A SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A SW-AQ3-52Z Time Delay Relay AQ3 CB-F-1A-A SW-AQ3-R1 Auxiliary Relay AQ3 CB-F-1A-A SW-CS-6102-1 Control Switch F72 CB-F-3A-A SW-CS-6101-1 Control Switch with Indication F72 CB-F-3A-A SW-HR2-PR1 EPS Permit Relay (K8 and K10) HR2 CB-F-1A-A SW-HR2-SR5 EPS Starting Relay (K80) HR2 CB-F-1A-A SW-HR2-RM0 EPS Manual Override Relay (K32) HR2 CB-F-1A-A SW-AW-4-52S Mechanical Operated Switch AQ4 CB-F-1A-A

.Notes   1. Air is not needed to position or to reposition the valve for safe shutdown.
2. Circuit shown in 301107, Sheet E2T/1a, involving Auxiliary Relay SW

-GN9-RV54 of SW -P-41A also affects SW -P-41C. 3. Circuit shown in 301107, Sheet E2U/1a, involving Auxiliary Relay SW -GN0-RV25 of SW -P-41B also affects SW -P-41D. 4. Electrical power not required for support.

5. The equipment is permanently disabled.
6. During normal operation, this equipment is in its safe shutdown position with its circuit breaker administratively controlled off to prevent its spurious operation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -2 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 SW-P-41A (Continued) SW-GN9-RTA Tower Actuation Sig. Auxiliary Relay GN9 CB-F-1A-A SW-GN9-RX1 TA Signal Relay GN9 CB-F-1A-A SW-ZS-V54 Valve Position Switch and Valve Open/Close Torque Switches VM5 CT-F-2B-A SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A GN9-VM5 E2T/1a E2T/1b CBA-FN-19 CBA-FN-20 Notes 2,4

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -3 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 SW-P-41B Service Water Loop "B" - Pump "B" SW-20794 B 301140 SW-F-1E-Z X X X - N82 SW-AR3-52 4160 V AC Circuit Breaker AR3 CB-F-1B-A AR3-GN0 AR3-VL4 AR3-N82 AR3-F71/1 AR4-F71/3 AR4-HR4 301107 AR3a AR3h AR3b AR3c AR3d CBA-FN-32 CBA-FN-33 EDE-SWG-6 SW-P-41A or SW-P-41C Cooling Towers SW-AR3-FU Fuses AR3 CB-F-1B-A SW-CS-6111-2 Control Switch AR3 CB-F-1B-A SW-SS-6111 Selector Switch AR3 CB-F-1B-A SW-ZS-V29 Valve Position Switch VL4 SW-F-1E-Z EDE-A73-94-2 Bus Undervoltage Relay A73 CB-F-1B-A SW-AR3-52H Truck Operated Contact AR3 CB-F-1B-A SW-AR3-50/51 Inst/Time Overcurrent Relays ØA, ØC AR3 CB-F-1B-A SW-AR3-51GS Ground Sensor Relay AR3 CB-F-1B-A SW-AR3-86 Lockout Relay AR3 CB-F-1B-A SW-AR3-CT Current Transformers 100/5A AR3 CB-F-1B-A SW-AR3-TD1 Test Device AR3 CB-F-1B-A SW-AR3-AM Ammeter AR3 CB-F-1B-A SW-AR3-AS Ammeter Switch AR3 CB-F-1B-A SW-AR3-G,R,W Indicating Lights AR3 CB-F-1B-A SW-AR3-ATR Transduce r AR3 CB-F-1B-A SW-AR3-TD2 Lockout Relay Test Device AR3 CB-F-1B-A SW-GN0-RV25 Auxiliary Relay GN0 CB-F-1B-A SW-AR3-52Z Time Delay Relay AR3 CB-F-1B-A SW-AR3-R1 Auxiliary Relay AR3 CB-F-1B-A SW-CS-6112-1 Control Switch F71 CB-F-3A-A SW-CS-6111-1 Control Switch with Indication F71 CB-F-3A-A SW-HR4-PR1 EPS Permit Relay (K8 and K10) HR4 CB-F-1B-A SW-HR0-SR5 EPS Starting Relay (K80) HR0 CB-F-1B-A SW-HR4-RM0 EPS Manual Override Relay (K32) HR4 CB-F-1B-A SW-AR4-52S Mechanical Operated Switch AR4 CB-F-1B-A SW-GN0-RTB Tower Actuation Sig. Auxiliary Relay GN0 CB-F-1B-A SW-GN0-RX1 TA Signal Relay GN0 CB-F-1B-A SW-ZS-V25 Valve Position Switch and Valve Open/Close Torque Switches VM8 CT-F-2B-A SW-GN0-RV25 Auxiliary Relay GN0 CB-F-1B-A GN0-VM8 E2U/1aE2U/1b CBA-FN-32 CBA-FN-33 Notes 3,4

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -4 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 SW-P-41C Service Water Loop "A" - Pump "C" SW-20794 A 301140 SW-F-1E-Z X X X - N83 SW-AQ4-52 4160 V AC Circuit Breaker AQ4 CB-F-1A-A AQ4-GN9 AQ4-VL5 AQ4-N83 AQ3-F72/2 AQ4-F72/1 AQ3-HR2 301107 AQ4a AQ4h AQ4b AQ4c AQ4d CBA-FN-19 CBA-FN-20 EDE-SWG-5 SW-P-41B or SW-P-41D Note 2 SW-AQ4-FU Fuses AQ4 CB-F-1A-A SW-CS-6102-2 Control Switch AQ4 CB-F-1A-A SW-SS-6102 Selector Switch AQ4 CB-F-1A-A SW-ZS-V22 Valve Position Switch VL5 SW-F-1E-Z EDE-A53-94-2 Bus Undervoltage Relay A53 CB-F-1A-A SW-AQ4-52H Truck Operated Contact AQ4 CB-F-1A-A SW-AQ4-50/51 Inst/Time Overcurrent Relays ØA, ØC AQ4 CB-F-1A-A SW-AQ4-51GS Ground Sensor Relay AQ4 CB-F-1A-A SW-AQ4-86 Lockout Relay AQ4 CB-F-1A-A SW-AQ4-CT Current Transformers 100/5A AQ4 CB-F-1A-A SW-AQ4-TD1 Test Device AQ4 CB-F-1A-A SW-AQ4-AM Ammeter AQ4 CB-F-1A-A SW-AQ4-AS Ammeter Switch AQ4 CB-F-1A-A SW-AQ4-G,R,W Indicating Lights AQ4 CB-F-1A-A SW-AQ4-ATR Transducer AQ4 CB-F-1A-A SW-AQ4-TD2 Lockout Relay Test Device AQ4 CB-F-1A-A SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A SW-AQ4-52Z Time Delay Relay AQ4 CB-F-1A-A SW-CS-6102-1 Control Switch F72 CB-F-3A-A SW-CS-6101-1 Control Switch with Indication F72 CB-F-3A-A SW-HR2-PR1 EPS Permit Relay (K8 and K10) HR2 CB-F-1A-A SW-HR2-SR5 EPS Starting Relay (K80) HR2 CB-F-1A-A SW-HR2-RM0 EPS Manual Override Relay (K32) HR2 CB-F-1A-A SW-AQ3-52S Mechanical Operated Switch AQ3 CB-F-1A-A SW-GN9-RTA Tower Actuation Sig. Auxiliary Relay GN9 CB-F-1A-A SW-GN9-RX1 TA Signal Relay GN9 CB-F-1A-A SW-AQ4-R1 Auxiliary Relay AR4 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -5 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 SW-P-41D Service Water Loop "B" - Pump "D" SW-20794 B 301140 SW-F-1E-Z X X X - N84 SW-AR4-52 4160 V AC Circuit Breaker AR4 CB-F-1B-A AR4-GN0 AR4-VL6 AR4-N84 AR3-F71/3 AR4-F71/1 AR3-HR4 301107 AR4a AR4h AR4b AR4c AR4d CBA-FN-32 CBA-FN-33 EDE-SWG-6 SW-P-41A SW-P-41C Cooling Towers Note 3 SW-AR4-FU Fuses AR4 CB-F-1B-A SW-CS-6112-2 Control Switch AR4 CB-F-1B-A SW-SS-6112 Selector Switch AR4 CB-F-1B-A SW-ZS-V31 Valve Position Switch VL6 SW-F-1E-Z EDE-A73-94-2 Bus Undervoltage Relay A73 CB-F-1B-A SW-AR4-52H Truck Operated Contact AR4 CB-F-1B-A SW-AR4-50/51 Inst/Time Overcurrent Relays ØA, ØC AR4 CB-F-1B-A SW-AR4-51GS Ground Sensor Relay AR4 CB-F-1B-A SW-AR4-86 Lockout Relay AR4 CB-F-1B-A SW-AR4-CT Current Transformers 100/5A AR4 CB-F-1B-A SW-AR4-TD1 Test Device AR4 CB-F-1B-A SW-AR4-AM Ammeter AR4 CB-F-1B-A SW-AR4-AS Ammeter Switch AR4 CB-F-1B-A SW-AR4-G,R,W Indicating Lights AR4 CB-F-1B-A SW-AR4-ATR Transducer AR4 CB-F-1B-A SW-AR4-TD2 Lockout Relay Test Device AR4 CB-F-1B-A SW-GN0-RV25 Auxiliary Relay GN0 CB-F-1B-A SW-AR4-52Z Time Delay Relay AR4 CB-F-1B-A SW-CS-6112-1 Control Switch F71 CB-F-3A-A SW-CS-6111-1 Control Switch with Indication F71 CB-F-3A-A SW-HR4-PR1 EPS Permit Relay (K8 and K10) HR4 CB-F-1B-A SW-HR4-SR5 EPS Starting Relay (K80) HR4 CB-F-1B-A SW-HR4-RM0 EPS Manual Override Relay (K32) HR4 CB-F-1B-A SW-AR3-52S Mechanical Operated Switch AR3 CB-F-1B-A SW-GN0-RTB Tower Actuation Sig. Auxiliary Relay GN0 CB-F-1B-A SW-GN0-RX1 TA Signal Relay GN0 CB-F-1B-A SW-AR4-R1 Auxiliary Relay AR4 CB-F-1B-A SW-AR4-R2 Auxiliary Relay AR4 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -6 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 SW-V2 Service Water Pump "A" Discharge Valve SW-20794 A 301140 SW-F-1E-Z X X X - VL3 SW-CR6-52 460 V AC Circuit Breaker CR6 SW-F-1B-A AQ3-CR6 CR6-VL3/1 CR6-VL3 301107 CR6a CR6c SWA-FN-40A EDE-MCC-514 SW-V-29 or SW-V-31 SW-AQ3-52S Mechanically Operated Contact AQ3 CB-F-1A-A SW-ZS-V2 Valve Position Switch and Valve Open/Close Torque Switches VL3 SW-F-1E-Z SW-CR6-42/0,C Motor Starters CR6 SW-F-1B-A SW-CR6-49 Overload Relay CR6 SW-F-1B-A SW-CR6-FU Fuses CR6 SW-F-1B-A SW-ECO-TDR Time Delay Relay ECO SW-F-1B-A 6 SW-V22 Service Water Pump "C" Discharge Valve SW-20794 A 301140 SW-F-1E-Z X X X - VL5 SW-CR7-52 460 V AC Circuit Breaker CR7 SW-F-1B-A AQ4-CR7 CR7-VL5/1 CR7-VL5 301107 CR7a CR7c SWA-FN-40A EDE-MCC-514 SW-V-29 or SW-V-31 SW-AQ4-52S Mechanically Operated Contact AQ4 CB-F-1A-A SW-ZS-V22 Valve Position Switch and Valve Open/Close Torque Switches VL5 SW-F-1E-Z SW-CR7-42/0,C Motor Starters CR7 SW-F-1B-A SW-CR7-49 Overload Relay CR7 SW-F-1B-A SW-CR7-FU Fuses CR7 SW-F-1B-A SW-ECO-TDR Time Delay Relay ECO SW-F-1B-A 7 SW-V29 Service Water Pump "B" Discharge Valve SW-20794 B 301140 SW-F-1E-Z X X X - VL4 SW-CS1-52 460 V AC Circuit Breaker CS1 SW-F-1C-A AR3-CS1 CS1-VL4/1 CS1-VL4 301107 CS1a CS1c SWA-FN-40B EDE-MCC-614 SW-V-2 SW-V-22 Cooling Towers SW-AR3-52S Mechanically Operated Contact AR3 CB-F-1B-A SW-ZS-V29 Valve Position Switch and Valve Open/Close Torque Switches VL4 SW-F-1E-Z SW-CS1-42/0,C Motor Starters CS1 SW-F-1C-A SW-CS1-49 Overload Relay CS1 SW-F-1C-A SW-CS1-FU Fuses CS1 SW-F-1C-A SW-EE2-TDR Time Delay Relay EE2 SW-F-1C-A 8 SW-V31 Service Water Pump "D" Discharge Valve SW-20794 B 301140 SW-F-1E-Z X X X - VL6 SW-CS2-52 460 V AC Circuit Breaker CS2 SW-F-1C-A AR4-CS2 CS2-VL6/1 CS2-VL6 301107 CS2a CS2c SWA-FN-40B EDE-MCC-614 SW-V-2 SW-V-22 Cooling Towers SW-AR4-52S Mechanically Operated Contact AR4 CB-F-1B-A SW-ZS-V31 Valve Position Switch and Valve Open/Close Torque Switches VL6 SW-F-1E-Z SW-CS2-42/0,C Motor Starters CS2 SW-F-1C-A SW-CS2-49 Overload Relay CS2 SW-F-1C-A SW-CS2-FU Fuses CS2 SW-F-1C-A SW-EE2-TDR Time Delay Relay EE2 SW-F-1C-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -7 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 SW-V4 Secondary Component Cooling Water Heat Exchanger Header Supply Valve SW-20795 A 310767 PAB-F-1K-Z X X X - VP0 SW-DA6-52 460 V AC Circuit Breaker DA6 CB-F-1A-A DA6-VP0 DA6-G2H DA6-G2H/2 DA6-G2H/1 DA6-VP0/1 F72-G2H/3 F72-G2H/5 F72-FB7 DA6-GN9 DA6-HR2 301107 DA6a DA6c DA6d CBA-FN-19 CBA-FN-20 EDE-MCC-512 SW-V5 SW-CS-6117-2 Control Switch with Indication G2H CB-F-1A-A SW-SS-6117 Selector Switch G2H CB-F-1A-A SW-DA6-42/0,C Motor Starters DA6 CB-F-1A-A SW-DA6-49 Overload Relays DA6 CB-F-1A-A SW-ZS-V4 Valve Position Switch and Valve Open/Close Torque Switches VP0 PAB-F-1K-Z SW-DA6-FU Fuse DA6 CB-F-1A-A SW-CS-6117-1 Control Switch with Indication F72 CB-F-3A-A SW-HR2-PR1 EPS Permit Auxiliary Relay (K8 and K11) HR2 CB-F-1A-A SW-FB7-K603A SI Actuating Auxiliary Relay FB7 CB-F-3A-A SW-GN9-RTA Tower Actuation Sig. Auxiliary Relay GN9 CB-F-1A-A 10 SW-V5 Secondary Component Cooling Water Heat Exchanger Header Supply Valve SW-20795 B 310767 PAB-F-1K-Z X X X - VQ1 SW-DA2-52 460 V AC Circuit Breaker DA2 CB-F-1B-A DA2-VQ1 DA2-G2K DA2-G2K/1 DA2-G2K/2 DA2-VQ1/1 F71-G2K/3 F71-G2K/5 F71-FB0 DA2-GN0 DA2-HR4 301107 DA2a DA2c DA2d CBA-FN-32 CBA-FN-33 EDE-MCC-612 SW-V4 SW-CS-6137-2 Control Switch with Indication G2K CB-F-1B-A SW-SS-6137 Selector Switch G2K CB-F-1B-A SW-DA2-42/0,C Motor Starters DA2 CB-F-1B-A SW-DA2-49 Overload Relays DA2 CB-F-1B-A SW-ZS-V5 Valve Position Switch and Valve Open/Close Torque Switches VQ1 PAB-F-1K-Z SW-DA2-FU Fuse DA2 CB-F-1B-A SW-CS-6137-1 Control Switch with Indication F71 CB-F-3A-A SW-HR4-PR1 EPS Permit Auxiliary Relay (K8 and K11) HR4 CB-F-1B-A SW-FB0-K603B SI Actuating Auxiliary Relay FB0 CB-F-3A-A SW-GN0-RTB Tower Actuation Sig. Auxiliary Relay GN0 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -8 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 SW-V15 CC-E-17A Outlet Valve SW-20795 A 310767 PAB-F-3A-Z X X X - VN1 SW-CS-6160 Control Switch with Indication F72 CB-F-3A-A DA7-VN1/1 DA7-F72 DA7-GN9 DA7-VN1/2 301107 DA7a DA7c CBA-FN-19 CBA-FN-20 SW-V17 Note 4 SW-DA7-42/0,C Motor Starter DA7 CB-F-1A-A SW-GN9-RTA Twr. Act. Sig. Auxiliary Relay GN9 CB-F-1A-A SW-ZS-V15 Position Switch VN1 PAB-F-3A-Z SW-DA7-52 460 V AC Circuit Breaker DA7 CB-F-1A-A 12 SW-V16 Diesel Generator "A" Water Jacket Heat Exchanger Solenoid-Operated Valve SW-20795 A 310767 PAB-F-3A-Z X X X X UK6 EDE-E2T/2-72 125 V DC Circuit Breaker E2T CB-F-1A-A F72-G06 F72-GN9/1 F72-GN9/5 GN9-UK6 301107 E2T/2a E2T/2c CBA-FN-19 CBA-FN-20 SW-V18 Notes 1,4 SW-CS-6182 Control Switch with Indication F72 CB-F-3A-A SW-GN9-R1 Auxiliary Relay GN9 CB-F-1A-A SW-G06-LSRX Low Speed Relay G06 DG-F-2A-A SW-ZS-V16 SW DG Water Jacket VLV-V16 Position Switch and Solenoid UK6 PAB-F-3A-Z 13 SW-V17 CC-E-17B Outlet Valve SW-20795 B 310767 PAB-F-3A-Z X X X - VN2 SW-DA3-52 460 V AC Circuit Breaker DA3 CB-F-1B-A - - CBA-FN-32 CBA-FN-33 SW-V15 Note 6 14 SW-V18 Diesel Generator "B" Water Jacket Heat Exchanger Solenoid-Operated Valve SW-20795 B 310767 PAB-F-3A-Z X X X X UK7 EDE-E2U/2-72 125 V DC Circuit Breaker E2U CB-F-1B-A F71-GN0/1 F71-GN0/5 F71-G18 GN0-UK7 301107 E2U/2a E2U/2c CBA-FN-32 CBA-FN-33 SW-V16 Notes 1,4 SW-CS-6192 Control Switch with Indication F71 CB-F-3A-A SW-GN0-R1 Auxiliary Relay GN0 CB-F-1B-A SW-G18-LSRX Low Speed Relay G18 DG-F-2B-A SW-ZS-V18 SW DG Water Jacket VLV-V18 Position Switch and Solenoid UK7 PAB-F-3A-Z 15 SW-V19 Service Water Discharge to Sea Isolation Valve SW-20795 B 310765 PAB-F-2C-Z X X X - VN3 SW-DA4-52 460 V AC Circuit Breaker DA4 CB-F-1B-A DA4-VN3/1 DA4-VN3/2 DA4-F71 DA4-GN0 DA4-E3Q 301107 DA4a DA4c CBA-FN-32 CBA-FN-33 SW-V20 Note 4 SW-CS-6172 Control Switch with Indication F71 CB-F-3A-A SW-CS-6172-1 Control Switch with Indication DA4 CB-F-1B-A SW-SS-8257 Selector Switch DA4 CB-F-1B-A SW-DA4-42/0,C Motor Starters DA4 CB-F-1B-A SW-DA4-49 Thermal Overload DA4 CB-F-1B-A SW-GN0-RTB-2 Twr. Act. Sig. Auxiliary Relay GN0 CB-F-1B-A SW-ZS-V19 Position Switch VN3 PAB-F-2C-Z SW-DA4-R1 Auxiliary Relay E3Q CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -9 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 16 SW-V20 Service Water Discharge to Sea Isolation Valve SW-20795 A 310765 PAB-F-2C-Z X X X - VN4 SW-DA8-52 460 V AC Circuit Breaker DA8 CB-F-1A-A DA8-VN4 DA8-VN4/1 DA8-VN4/2 DA8-F72 DA8-GN9 301107 DA8a DA8c CBA-FN-19 CBA-FN-20 EDE-MCC-512 SW-V19 SW-CS-6162 Control Switch with Indication F72 CB-F-3A-A SW-DA8-42/0,C Motor Starters DA8 CB-F-1A-A SW-DA8-49 Thermal Overload DA8 CB-F-1A-A SW-GN9-RTA-2 Twr. Act. Sig. Auxiliary Relay GN9 CB-F-1A-A SW-ZS-V20 Position Switch VN4 PAB-F-2C-Z 17 SW-V23 Service Water to Cooling Tower Isolation Valve SW-20795 B 310765 PAB-F-2C-Z X X X - VN5 SW-DA5-52 460 V AC Circuit Breaker DA5 CB-F-1B-A DA5-VN5/1 DA5-VN5/2 DA5-F71 DA5-F71/1 DA5-GN0 301107 DA5a DA5c CBA-FN-32 CBA-FN-33 SW-V34 Note 4 SW-CS-6171 Control Switch with Indication F71 CB-F-3A-A SW-DA5-42/0,C Motor Starters DA5 CB-F-1B-A SW-DA5-49 Thermal Overload DA5 CB-F-1B-A SW-GN0-RTB-2 Twr. Act. Sig. Auxiliary Relay GN0 CB-F-1B-A SW-ZS-V23 Position Switch VN5 PAB-F-2C-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -10 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 SW-V25 Cooling Tower Pump Discharge Valve SW-20794 B 310717 CT-F-2B-A X X X - VH8 SW-CQ7-52 460 V AC Circuit Breaker CQ7 CT-F-1C-A CQ7-G2K CQ7-VM8/1 CQ7-VM8/2 F71-G2K AU6-G2K G2K-GNO EE7-G2K G2K-GNO/3 301107 CQ7a CQ7c CBA-FN-32 CBA-FN-33 SW-V54 Note 4 SW-CS-6174-2 Control Switch with Indication G2K CB-F-1B-A SW-SS-6174 Selector Switch G2K CB-F-1B-A SW-CQ7-42/O,C Motor Starters CQ7 CT-F-1C-A SW-CQ7-49 Overload Relay CQ7 CT-F-1C-A SW-ZS-V25 Valve Position Switch and Valve Open/Close Torque Switches VM8 CT-F-2B-A SW-CS-6174-1 Control Switch with Indication F71 CB-F-3A-A SW-AU6-52S Mechanical Operated Switch AU6 CB-F-1B-A SW-GNO-RTB1 Tower Actuation Signal Auxiliary Relay GNO CB-F-1B-A SW-EE7-TDR Time Delay Relay EE7 CT-F-1C-A SW-GNO-RV25 Auxiliary Relay GNO CB-F-1B-A SW-ZS-V25 Position Switch VM8 CT-F-2B-A SW-GN0-RV25 Auxiliary Relay GN0 CB-F-1B-A GNO-VM8 E2U/1aE2U/1b Note 4 SW-CQ7-R1 Auxiliary Relay EE7 CT-F-1C-A 19 SW-V34 Service Water to Cooling Tower Outlet Valve SW-20795 A 310765 PAB-F-2C-Z X X X - VN6 SW-DA9-52 460 v AC Circuit Breaker DA9 CB-F-1A-A DA9-VN6 DA9-VN6/1 DA9-VN6/2 DA9-F72 DA9-F72/1 DA9-GN9 301107 DA9a DA9c CBA-FN-19 CBA-FN-20 EDE-MCC-512 SW-V23 SW-CS-6161 Control Switch with Indication F72 CB-F-3A-A SW-DA9-42/O,C Motor Starters DA9 CB-F-1A-A SW-DA9-49 Thermal Overload DA9 CB-F-1A-A SW-GN9-RTA-2 Tower Actuation Signal Auxiliary Relay GN9 CB-F-1A-A SW-ZS-V34 Position Switch VN6 PAB-F-2C-Z 20 SW-V44 Service Water Unit Pumps Intake Valve SW-20794 A 301037 SW-F-2-0 X X X - VM1 SW-CU5-52 460 V ac Circuit Breaker CU5 SW-F-1B-A None Note 5 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -11 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 21 SW-V54 Cooling Tower Pump Discharge Valve SW-20794 A 301717 CT-F-2B-A X X X - VM5 SW-CP8-52 460 V ac Circuit Breaker CP8 CT-F-1D-A CP8-G2H CP8-VM5 CP8-VM5/1 CP8-VM5/2 F72-G2H AU2-G2H G2H-GN9/1 G2H-GN9/5 ED6-G2H 301107 CP8a CP8c CBA-FN-19 CBA-FN-20 EDE-MCC-513 SW-V25 SW-CS-6164-2 Control Switch with Indication G2H CB-F-1A-A SW-SS-6164 Selector Switch G2H CB-F-1A-A SW-CP8-42/O,C Motor Starters CP8 CT-F-1D-A SW-CP8-49 Overload Relay CP8 CT-F-1D-A SW-ZS-V54 Valve Position Switch and Valve Open/Close Torque Switches VM5 CT-F-2B-A SW-CP8-FU Fuse CP8 CT-F-1D-A SW-CS-6164-1 Control Switch with Indication F72 CB-F-3A-A SW-AU2-52S Mechanical Operated Switch AU2 CB-F-1A-A SW-GN9-RTA-1 Tower Actuation Signal Auxiliary Relay GN9 CB-F-1A-A SW-ED6-TDR Timing Relay ED6 CB-F-1A-A SW-ZS-V54 Position Switch VM5 CT-F-2B-A SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A GN9-VM5 E2T/1a E2T/1b Note 4 22 SW-V63 Service Water Discharge Valve to Intake SW-20794 A 301037 SW-F-2-0 X X X - VQ0 SW-DZ3-52 460 V ac Circuit Breaker DZ3 SW-F-1B-A None Note 5 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -12 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 23 EDE-CP-248 Service Water Cooling Tower Actuation Logic (TA) SW-20794 A 310442 CB-F-1A-A X X X - GN9 SW-CS-6149-2 Control Switch F77 CB-F-3A-A EF4-GN9/1 F72-GN9 AQ3-GN9/1 ED4-F72 301107 E87/4a E87/4g E87/4b CBA-FN-19 CBA-FN-20 EDE-CP-249 Note 4 SW-CS-6148-1 Control Switch F72 CB-F-3A-A SW-CS-6148-2 Control Switch F72 CB-F-3A-A SW-CS-6149-1 Control Switch F77 CB-F-3A-A SW-AQ3-52S Circuit Breaker AQ3 CB-F-1A-A SW-AQ4-52S Circuit Breaker AW4 CB-F-1A-A SW-GN9-RX1 Auxiliary Relay GN9 CB-F-1A-A SW-GN9-TD1 Time Delay Relay GN9 CB-F-1A-A SW-EF4-RP1 Auxiliary Relay EF4 CB-F-1A-A SW-EF4-RP2 Auxiliary Relay EF4 CB-F-1A-A SW-EF4-RP3 Auxiliary Relay EF4 CB-F-1A-A SW-GN9-RTA Tower Actuation Relay GN9 CB-F-1A-A SW-GN9-RTA1 Tower Actuation Relay GN9 CB-F-1A-A SW-GN9-RTA2 Tower Actuation Relay GN9 CB-F-1A-A SW-ZL-6149 Pilot Light F77 CB-F-3A-A SW-GN9-TD2 Time Delay Relay GN9 CB-F-1A-A SW-CS-6101-1 Control Switch F72 CB-F-3A-A SW-CS-6102-1 Control Switch F72 CB-F-3A-A SW-CS-6167-1 Control Switch F72 CB-F-3A-A SW-ED4-94-5 Aux Relay ED4 CB-F-1A-A SW-PYY-8272-2 Auxiliary Relay FJ1 CB-F-3A-A EF4-FJ1/2 EH9/10a EH9/10b Note 4 SW-PYY-8273 Auxiliary Relay FJ1 CB-F-3A-A SW-PYY-8274-2 Auxiliary Relay FJ1 CB-F-3A-A SW-EF4-RP1 Auxiliary Relay EF4 CB-F-1A-A SW-EF4-RP2 Auxiliary Relay EF4 CB-F-1A-A SW-EF4-RP3 Auxiliary Relay EF4 CB-F-1A-A SW-PT-8272 MM-CP-152A SW-Discharge HDR PR BOP-PCC GRO FJ1 SW-F-1E-Z CB-F-3A-A FJ1-GRO 310952 FJ1c FJ1e SW-PT-8273 MM-CP-152A SW-Discharge HDR PR BOP-PCC GRO FJ1 SW-F-1E-Z CB-F-3A-A FJ1-GRO FJ1c FJ1e SW-PT-8274 MM-CP-152A SW-Discharge HDR PR BOP-PCC GRO FJ1 SW-F-1E-Z CB-F-3A-A FJ1-GRO FJ1c FJ1e SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -13 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 24 EDE-CP-249 Service Water Cooling Water Actuation Logic (TA) SW-20794 B 310442 CB-F-1B-A X X X - GNO SW-CS-6159-2 Control Switch F77 CB-F-3A-A EE3-GNO/1 F71-GNO AR3-GNO/1 EE6-F71 301107 E88/4a E88/4g E88/4b CBA-FN-32 CBA-FN-33 EDE-CP-248 Note 4 SW-CS-6158-1 Control Switch F71 CB-F-3A-A SW-CS-6158-2 Control Switch F71 CB-F-3A-A SW-CS-6159-1 Control Switch F77 CB-F-3A-A SW-AR3-52S Circuit Breaker AR3 CB-F-1B-A SW-AR4-52S Circuit Breaker AR4 CB-F-1B-A SW-GNO-RX1 Auxiliary Relay GNO CB-F-1B-A SW-GNO-TD1 Time Delay Relay GNO CB-F-1B-A SW-EE3-RP1 Auxiliary Relay EE3 CB-F-1B-A SW-EE3-RP2 Auxiliary Relay EE3 CB-F-1B-A SW-EE3-RP3 Auxiliary Relay EE3 CB-F-1B-A SW-GNO-RTA Tower Actuation Relay GNO CB-F-1B-A SW-GNO-RTA1 Tower Actuation Relay GNO CB-F-1B-A SW-GNO-RTA2 Tower Actuation Relay GNO CB-F-1B-A SW-ZL-6159 Pilot Light F77 CB-F-3A-A SW-GN9-TD2 Time Delay Relay GN0 CB-F-1B-A SW-CS-6111-1 Control Switch F71 CB-F-3A-A SW-CS-6112-1 Control Switch F71 CB-F-3A-A SW-CS-6177-1 Control Switch F71 CB-F-3A-A SW-EE6-94-6 Aux Relay EE6 CB-F-3A-A Note 4 SW-PYY-8282-2 Auxiliary Relay FJ4 CB-F-3A-A EE3-FJ4/2 EHO/10a EHO/10c SW-PYY-8283 Auxiliary Relay FJ4 CB-F-3A-A SW-PYY-8284-2 Auxiliary Relay FJ4 CB-F-3A-A SW-EE3-RP1 Auxiliary Relay EE3 CB-F-1B-A SW-EE3-RP2 Auxiliary Relay EE3 CB-F-1B-A SW-EE3-RP3 Auxiliary Relay EE3 CB-F-1B-A SW-PT-8282 MM-CP-152B SW-Discharge HDR PR BOP-PCC GRO FJ4 SW-F-1E-Z CB-F-3A-A FJ4-GRO 310952 FJ4g FJ4h SW-PT-8283 MM-CP-152B SW-Discharge HDR PR BOP-PCC GRO FJ4 SW-F-1E-Z CB-F-3A-A FJ4-GRO FJ4g FJ4h SW-PT-8284 MM-CP-152B SW-Discharge HDR PR BOP-PCC GRO FJ4 SW-F-1E-Z CB-F-3A-A FJ4-GRO FJ4g FJ4h SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -14 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 25 SW-P-110A Cooling Tower Pump SW-20794 A 301717 CT-F-2B-A X X X - NG4 SW-AU2-52 4160 Volt Circuit Breaker AU2 CB-F-1A-A AU2-F72/1 AU2-F72/2 AU2-GN9 AU2-HR9 AU2-VM5 AU2-VM5/1 VM5-VM7/1 AU2-NG4 301107 AU2a AU2h AU2b AU2i AU2c AU2d EDE-SWG-5 SW Pumphouse SW-AU2-FU Fuses AU2 CB-F-1A-A SW-CS-6167-2 Control Switch AU2 CB-F-1A-A SW-SS-6167 Selector Switch AU2 CB-F-1A-A EDE-A53-94-1B Bus Undervoltage Relay A53 CB-F-1A-A SW-AU2-52H Truck Operated Contact AU2 CB-F-1A-A SW-AU2-50/51 Inst/Time Overcurrent Relays ØA, ØC AU2 CB-F-1A-A SW-AU2-51GS Ground Sensor Relay AU2 CB-F-1A-A SW-AU2-86 Lockout Relay AU2 CB-F-1A-A SW-AU2-CT Current Transformers 150/5A AU2 CB-F-1A-A SW-AU2-TD1 Test Device AU2 CB-F-1A-A SW-AU2-AM Ammeter AU2 CB-F-1A-A SW-AU2-AS Ammeter Switch AU2 CB-F-1A-A SW-AU2-G,R,W Indicating Lights AU2 CB-F-1A-A SW-AU2-ATR Transducer Test Device AU2 CB-F-1A-A SW-AU2-52Z Time Delay Relay AU2 CB-F-1A-A SW-ZS-V54 Valve Position Switch & Valve Open/Close Torque Switches VM5 CT-F-2B-A SW-ZS-V56 Valve Position Switch & Valve Open/Close Torque Switches VM7 CT-F-2B-A SW-CS-6102-1 Control Switch F72 CB-F-3A-A SW-CS-6101-1 Control Switch F72 CB-F-3A-A SW-HR2-PR1 E.P.S. Permit Relay (K8 & K10) HR2 CB-F-1A-A SW-HR2-RMO E.P.S. Manual Override Relay (K32) HR2 CB-F-1A-A SW-GN9-RTA Tower Actuation Signal Auxiliary Relay GN9 CB-F-1A-A SW-HR9-HR8 E.P.S. Start Relay HR9 CB-F-1A-A CBS-A61-52S Mechanical Operated Switch A61 CB-F-1A-A SW-AU2-R1 Auxiliary Relay AU2 CB-F-1A-A SW-AU2-R1X Auxiliary Relay AU2 CB-F-1A-A SW-AU2-R4 Auxiliary Relay AU2 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -15 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 26 SW-FN-51A Cooling Tower Fan SW-20794 A 301717 CT-F-3-0 X X X - NG6 SW-AV4-52 4160 Volt Circuit Breaker AV4 CB-F-1A-A AV4-HR2 AV4-F72/2 AV4-F72/1 AV4-NG6 301107 AV4a AV4h AV4b AV4c AV4d EDE-SWG-5 SW Pumphouse SW-AV4-FU Fuses AV4 CB-F-1A-A SW-CS-6185-2 Control Switch AV4 CB-F-1A-A SW-SS-6185 Selector Switch AV4 CB-F-1A-A EDE-A53-94-1B Bus Undervoltage Relay A53 CB-F-1A-A SW-AV4-52H Truck Operated Contact AV4 CB-F-1A-A SW-AV4-50/51 Inst/Time Overcurrent Relays ØA, ØC AV4 CB-F-1A-A SW-AV4-51GS Ground Sensor Relay AV4 CB-F-1A-A SW-AV4-86 Lockout Rela y AV4 CB-F-1A-A SW-AV4-CT Current Transformers 5/50 AV4 CB-F-1A-A SW-AV4-TD1 Test Device AV4 CB-F-1A-A SW-AV4-AM Ammeter AV4 CB-F-1A-A SW-AV4-AS Ammeter Switch AV4 CB-F-1A-A SW-AV4-G,R,W Indicating Lights AV4 CB-F-1A-A SW-AV4-ATR Transducer AV4 CB-F-1A-A SW-AV4-TD2 Lockout Relay Test Device AV4 CB-F-1A-A SW-AV4-52Z Time Delay Relay AV4 CB-F-1A-A SW-CS-6285-1 Control Switch F72 CB-F-3A-A SW-HR2-RMO E.P.S. Manual Override Relay (K32) HR2 CB-F-1A-A 27 SW-V74 Loop A Discharge to Cooling Tower SW-20795 A 310765 PAB-F-1K-Z X X X - VM2 SW-BX8-52 460 V ac Circuit Breaker BX8 CB-F-1A-A F72-FB7/1 BX8-F72 FX8-F72/1 BX8-GN9 BX8-VM2 BX8-VM2/1 BX8-VM2/2 301107 BX8a BS8c EDE-MCC-512 SW Pumphouse SW-CS-8271 Control Switch with Indication F72 CB-F-3A-A SW-BX8-42/O,C Motor Starters BX8 CB-F-1A-A SW-GN9-RTA Tower Actuation Signal Auxiliary Relay GN9 CB-F-1A-A SW-ZS-V74 Position Switch VM2 PAB-F-1K-Z SW-FB7-K608A SI Actuating Auxiliary Relay FB7 CB-F-3A-A 28 SW-V55 Cooling Tower PP A Test/Bypass SW-20794 A 301717 CT-F-2B-A X X X - VM6 SW-CP9-52 460 V ac Circuit Breaker CP9 CT-F-1D-A SW Pumphouse Note 5 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.7 -16 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 29 SW-V56 Cooling Tower Loop A Test Recirculation SW-20794 A 301717 CT-F-2B-A X X X - VM7 SW-CP0-52 460 V ac Circuit Breaker CP0 CT-F-1D-A CP0-F72 CP0-F72/1 AU2-F72/3 AU2-VM5/3 VM5-VM7 CP0-VM7 CP0-VM7/1 CPO-VM7/2 301107 CP0a CP0c EDE-MCC-513 SW Pumphouse SW-CS-6165 Control Switch with Indication F72 CB-F-3A-A SW-CP0-42/O,C Motor Starters CP0 CT-F-1D-A SW-ZS-V54 Position Switch VM5 CT-F-2B-A SW-ZS-V56 Position Switch VM7 CT-F-2B-A SW-AU2-52S Mechanical Operated Switch AU2 CB-F-1A-A SW-CP0-49 Thermal Overload CP0 CT-F-1D-A 30 SW-V139 Cooling Tower Spray Bypass Recirculation Valve SW-20794 A 301717 CT-F-3-0 X X X - V3Q SW-C3D-52 460 V ac Circuit Breaker C3D CT-F-1D-A C3D-V3Q C3D-V3Q/1 C3D-V3Q/3 C3D-F72 301107 C3Da C3Dc EDE-MCC-513 SW Pumphouse SW-CS-6168 Control Switch with Indication F72 CB-F-3A-A SW-C3D-42/O,C Motor Starters C3D CT-F-1D-A SW-ZS-V139 Position Switch V3Q CT-F-3-0 SW-C3D-49 Thermal Overload C3D CT-F-1D-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -1 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CC-P-11A PCCW Loop "A" Pump "A" CC-20205 A 310765 PAB-F-2C-Z X X X - H05 CC-A58-52 4160 V AC Circuit Breaker A58 CB-F-1A-A A58-M05/1 A58-F30/1 A58-F30/2 A58-F30/3 A58-HR9 A58-E3C 310895 A58a A58h A58b A58c A58d CBA-FN-19 CBA-FN-20 PAH-FN-42A EDE-SWG-5 CC-P-11B or CC-P-11D CC-CS-2140-2 Control Switch A58 CB-F-1A-A CC-SS-2140 Selector Switch A58 CB-F-1A-A EDE-A53-94-1A Bus Undervoltage Relay A53 CB-F-1A-A CC-A58-52H Truck-Operated Contact A58 CB-F-1A-A CC-A58-50/51 Instrument/Time Overcurrent Relays øA, øC A58 CB-F-1A-A CC-A58-86 Lockout Relay A58 CB-F-1A-A CC-A58-AM Ammeter A58 CB-F-1A-A CC-A58-AS Ammeter Switch A58 CB-F-1A-A CC-A58-CT Current Transformer (150/5) A58 CB-F-1A-A CC-A58-TD1 CT Test Device A58 CB-F-1A-A CC-A58-ATR Transducer A58 CB-F-1A-A CC-A58-TD2 Lockout Relay Test Device A58 CB-F-1A-A CC-A58-FU Fuses A58 CB-F-1A-A CC-A58-52Z Timing Relay A58 CB-F-1A-A CC-A58-G,R,W Indicating Lights A58 CB-F-1A-A CC-A58-51GS Ground Sensor Relay A58 CB-F-1A-A CC-CS-2140-1 Control Switch with Indication F30 CB-F-3A-A CC-CS-2141-1 Control Switch F30 CB-F-3A-A CC-A59-52S Mechanical -Operated Switch A59 CB-F-1A-A CC-HR2-PR1 EPS Permissive Relay (K7 and K10) HR2 CB-F-1A-A CC-HR2-RMO EPS Relay (K31) HR2 CB-F-1A-A CC-HR9-SR4 EPS Starting Relay (K78) HR9 CB-F-1A-A CC-A58-62 Time Delay Relay A58 CB-F-1A-A CC-E3C-TDRX Auxiliary Relay E3C CB-F-1A-A EDE-E42/12-52 120 V AC Circuit Breaker E42 CB-F-1A-A E42-E3C E3C-FK0/1 E42/12a E42/12b EDE-MCC-521 CC-TYY-2171A Auxiliary Relay FK0 CB-F-3A-A CC-TTY-2197A Auxiliary Relay FK0 CB-F-3A-A

.Notes   1. The equipment is mechanical with no electrical requirement.
2. These valves are in the open position with their circuit breakers locked open to prevent spurious operation.
3. Electrical conduit plan drawing, 310765, is listed only to show the fire zone corresponding to the location of the Heat Exchangers CC-E-17A and CC

-E-17B as identified in Drawing 805217.

4. Electrical conduit plan drawing, 310581, is listed only to show the fire zone corresponding to the location of CC

-TK-196 as identified in Drawing 805193.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -2 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CC-P-11A (Continued) CC-E3C-TDR Time Delay Relay E3C CB-F-1A-A CC-E3C-TDRX Auxiliary Relay E3C CB-F-1A-A CC-TE-2171 Temperature Element TMO PAB-F-2C-Z FK0-TMO/1 FK0-T3A 310952 FK0d FK0f MM-CP-297A CC-TE-2197 Temperature Element T3A PAB-F-2C-Z MM-CP-297A BOP-PCC FKO CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -3 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 CC-P-11B PCCW Loop "B" Pump "B" CC-20211 B 310765 PAB-F-2C-Z X X X - M06 CC-A78-52 4160 V AC Circuit Breaker A78 CB-F-1B-A A78-M06/1 A78-F31 A78-F31/1 A78-F31/2 A78-HR0 A78-E3D 310895 A78a A78h A78b A78c A78d CBA-FN-32 CBA-FN-33 PAH-FN-42B EDE-SWG-6 CC-P-11A or CC-P-11C CC-CS-2240-2 Control Switch A78 CB-F-1B-A CC-SS-2240 Selector Switch A78 CB-F-1B-A EDE-A73-94-1A Bus Undervoltage Relay A73 CB-F-1B-A CC-A78-52H Truck-Operated Contact A78 CB-F-1B-A CC-A78-50/51 Instrument/Time Overcurrent Relays øA, øC A78 CB-F-1B-A CC-A78-86 Lockout Relay A78 CB-F-1B-A CC-A78-AM Ammeter A78 CB-F-1B-A CC-A78-AS Ammeter Switch A78 CB-F-1B-A CC-A78-CT Current Transformer (150/5) A78 CB-F-1B-A CC-A78-TD1 CT Test Device A78 CB-F-1B-A CC-A78-ATR Transducer A78 CB-F-1B-A CC-A78-TD2 Lockout Relay Test Device A78 CB-F-1B-A CC-A78-FU Fuses A78 CB-F-1B-A CC-A78-52Z Timing Relay A78 CB-F-1B-A CC-A78-G,R,W Indicating Lights A78 CB-F-1B-A CC-A78-51GS Ground Sensor Relay A78 CB-F-1B-A CC-CS-2240-1 Control Switch with Indication F30 CB-F-3A-A CC-CS-2241-1 Control Switch F30 CB-F-3A-A CC-A79-52S Mechanical -Operated Switch A79 CB-F-1B-A CC-HR4-PR1 EPS Permissive Relay (K7 and K10) HR4 CB-F-1B-A CC-HR4-RMO EPS Relay (K31) HR4 CB-F-1B-A CC-HR0-SR4 EPS Starting Relay (K78) HR0 CB-F-1B-A CC-A78-62 Time Delay Relay A78 CB-F-1B-A CC-E3D-TDRX Auxiliary Relay E3D CB-F-1B-A EDE-E50/12-52 120 V AC Circuit Breaker E50 CB-F-1B-A E3D-E50 E3D-FJ4 E50/12a E50/12b EDE-MCC-621 CC-TYY-2271A Auxiliary Relay FJ4 CB-F-3A-A CC-TTY-2297A Auxiliary Relay FJ4 CB-F-3A-A CC-E3D-TDR Time Delay Relay E3D CB-F-1B-A CC-E3D-TDRX Auxiliary Relay E3D CB-F-1B-A CC-TE-2271 Temperature Element TM8 PAB-F-2C-Z FJ4-TM8/2 FJ4-T2Z 310952 FJ4j FJ4n MM-CP-152B CC-TE-2297 Temperature Element T2Z PAB-F-2C-Z MM-CP-152B BOP-PCC FJ4 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -4 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 CC-P-11C PCCW Loop "A" Pump "C" CC-20205 A 310766 PAB-F-2C-Z X X X - H07 CC-A59-52 4160 V AC Circuit Breaker A59 CB-F-1A-A A59-M07/1 A59-F30/1 A59-F30/2 A59-F30/3 A59-HR9 A59-E3C 310895 A59a A59h A59b A59c A59d CBA-FN-19 CBA-FN-20 PAH-FN-42A EDE-SWG-5 CC-P-11B or CC-P-11D CC-CS-2141-2 Control Switch A59 CB-F-1A-A CC-SS-2141 Selector Switch A59 CB-F-1A-A EDE-A53-94-1A Bus Undervoltage Relay A53 CB-F-1A-A CC-A59-52H Truck-Operated Contact A59 CB-F-1A-A CC-A59-50/51 Instrument/Time Overcurrent Relays øA, øC A59 CB-F-1A-A CC-A59-86 Lockout Relay A59 CB-F-1A-A CC-A59-AM Ammeter A59 CB-F-1A-A CC-A59-AS Ammeter Switch A59 CB-F-1A-A CC-A59-CT Current Transformer (150/5) A59 CB-F-1A-A CC-A59-TD1 CT Test Device A59 CB-F-1A-A CC-A59-ATR Transducer A59 CB-F-1A-A CC-A59-TD2 Lockout Relay Test Device A59 CB-F-1A-A CC-A59-FU Fuses A59 CB-F-1A-A CC-A59-52Z Timing Relay A59 CB-F-1A-A CC-A59-G,R,W Indicating Lights A59 CB-F-1A-A CC-A59-51GS Ground Sensor Relay A59 CB-F-1A-A CC-CS-2141-1 Control Switch with Indication F30 CB-F-3A-A CC-CS-2140-1 Control Switch F30 CB-F-3A-A CC-A58-52S Mechanical -Operated Switch A58 CB-F-1A-A CC-HR2-PR1 EPS Permissive Relay (K8 and K10) HR2 CB-F-1A-A CC-HR2-RMO EPS Relay (K31) HR2 CB-F-1A-A CC-HR9-SR4 EPS Starting Relay (K78) HR9 CB-F-1A-A CC-A59-62 Time Delay Relay A59 CB-F-1A-A CC-E3C-TDRX Auxiliary Relay E3C CB-F-1A-A EDE-E42/12-52 120 V AC Circuit Breaker E42 CB-F-1A-A E42-E3C E3C-FK0/1 E42/12a E42/12b EDE-MCC-521 CC-TYY-2171A Auxiliary Relay FK0 CB-F-3A-A CC-TTY-2197A Auxiliary Relay FK0 CB-F-3A-A CC-E3C-TDR Time Delay Relay E3C CB-F-1A-A CC-E3C-TDRX Auxiliary Relay E3C CB-F-1A-A CC-TE-2171 Temperature Element TM0 PAB-F-2C-Z FK0-TM0/1 FK0-T3A 310952 FK0d FKOf MM-CP-297A CC-TE-2197 Temperature Element T3A PAB-F-2C-Z MM-CP-297A BOP-PCC FK0 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -5 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 CC-P-11D PCCW Loop "B" Pump "D" CC-20211 B 310766 PAB-F-2C-Z X X X - M08 CC-A79-52 4160 V AC Circuit Breaker A79 CB-F-1B-A A79-M08/1 A79-F31 A79-F31/1 A79-F31/2 A79-HR0 A79-E3D 310895 A79a A79h A79b A79c A79d CBA-FN-32 CBA-FN-33 PAH-FN-42B EDE-SWG-6 CC-P-11A or CC-P-11C CC-CS-2241-2 Control Switch A79 CB-F-1B-A CC-SS-2241 Selector Switch A79 CB-F-1B-A EDE-A73-94-1A Bus Undervoltage Relay A73 CB-F-1B-A CC-A79-52H Truck-Operated Contact A79 CB-F-1B-A CC-A79-50/51 Instrument/Time Overcurrent Relays øA, øC A79 CB-F-1B-A CC-A79-86 Lockout Relay A79 CB-F-1B-A CC-A79-AM Ammeter A79 CB-F-1B-A CC-A79-AS Ammeter Switch A79 CB-F-1B-A CC-A79-CT Current Transformer (150/5) A79 CB-F-1B-A CC-A79-TD1 CT Test Device A79 CB-F-1B-A CC-A79-ATR Transducer A79 CB-F-1B-A CC-A79-TD2 Lockout Relay Test Device A79 CB-F-1B-A CC-A79-FU Fuses A79 CB-F-1B-A CC-A79-52Z Timing Relay A79 CB-F-1B-A CC-A79-G,R,W Indicating Lights A79 CB-F-1B-A CC-A79-51GS Ground Sensor Relay A79 CB-F-1B-A CC-CS-2241-1 Control Switch with Indication F30 CB-F-3A-A CC-CS-2240-1 Control Switch F30 CB-F-3A-A CC-A78-52S Mechanical -Operated Switch A78 CB-F-1B-A CC-HR4-PR1 EPS Permissive Relay (K8 and K10) HR4 CB-F-1B-A CC-HR4-RMO EPS Relay (K31) HR4 CB-F-1B-A CC-HR0-SR4 EPS Starting Relay (K78) HR0 CB-F-1B-A CC-A79-62 Time Delay Relay A79 CB-F-1B-A CC-E3D-TDRX Auxiliary Relay E3D CB-F-1B-A EDE-E50/12-52 120 V AC Circuit Breaker E50 CB-F-1B-A E3D-E50 E3D-FJ4 E50/12a E50/12b EDE-MCC-621 CC-TYY-2271A Auxiliary Relay FJ4 CB-F-3A-A CC-TYY-2297A Auxiliary Relay FJ4 CB-F-3A-A CC-E3D-TDR Time Delay Relay E3D CB-F-1B-A CC-E3D-TDRX Auxiliary Relay E3D CB-F-1B-A CC-TE-2271 Temperature Element TM8 PAB-F-2C-Z FJ4-TM8/2 FJ4-T2Z 310952 FJ4j FJ4n MM-CP-152B CC-TE-2297 Temperature Element T2Z PAB-F-2C-Z MM-CP-152B BOP-PCC FJ4 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -6 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 CC-V-57 Primary Component Cooling Water Loop "A" Header Isolation Inboard Supply Valve CC-20207 A 310578 C-F-2-Z - X X X VA8 CC-E2T/4-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-E4H E4H-G81/1 G81-H36/7 G81-H36/8 H36-VA8 H36-VB1 310895 E2T/4b E2T/4d E2T/4a E2T/4e E2T/4f CBA-FN-19 CBA-FN-20 Instrument Air EDE-PP-113A CC-V-176 CC-CS-2099-2 Control Switch with Indication G81 CB-F-1A-A CC-SS-2099 Selector Switch G81 CB-F-1A-A CC-ZS-V57 Valve Position Switch VA8 C-F-2-Z CC-E4H-FU3,4 30A Fuses E4H CB-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A CC-V57-20-1 Pilot Solenoid VA8 C-F-2-Z CC-V57-20-2 Pilot Solenoid VA8 C-F-2-Z CC-CS-2099-1 Control Switch with Indication F30 CB-F-3A-A F30-G81/B F30-G81/9 F30-FB7/5 G81-GN9/D FB7-G81 FC1-G81 FC1-G81/1 F30-G81/8 G81-GN9/B CC-FB7-K-633A Protection System Relay FB7 CB-F-3A-A CC-FB7-K-632A Protection System Relay FB7 CB-F-3A-A CC-ATR-LLA1 Isolation Signal Auxiliary Relay GN9 CB-F-1A-A CC-FC1-K803 Safeguard Test Cabinet Relay FC1 CB-F-3A-A CC-FC1-K811 Safeguard Test Cabinet Relay FC1 CB-F-3A-A 6 CC-V-121 Primary Component Cooling Water Loop "A" Header Isolation Inboard Return Valve CC-20207 A 310579 C-F-2-Z - X X X VB1 CC-E2T/4-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-E4H G81-H36/8 G81-H36/7 H36-VB1 H36-VA8 E4H-G81/1 310895 E2T/4a E2T/4d E2T/4b E2T/4e E2T/4f CBA-FN-19 CBA-FN-20 Instrument Air EDE-PP-113A CC-V-256 CC-CS-2150-2 Control Switch with Indication G81 CB-F-1A-A CC-SS-2150 Selector Switch G81 CB-F-1A-A CC-ZS-V121 Valve Position Switch VB1 C-F-2-Z CC-E4H-FU3,4 30A Fuses E4H CB-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A CC-V121-20-1 Pilot Solenoid VB1 C-F-2-Z CC-V121-20-2 Pilot Solenoid VB1 C-F-2-Z CC-CS-2150-1 Control Switch with Indication F30 CB-F-3A-A F30-G81/8 F30-G81/9 F30-FB7/5 G81-GN9/B FB7-G81 FC1-G81 FC1-G81/1 FC1-G81/B G81-GN9/D CC-FB7-K-633A Protection System Relay FB7 CB-F-3A-A CC-FB7-K-632A Protection System Relay FB7 CB-F-3A-A CC-ATR-LLA1 Isolation Signal Auxiliary Relay GN9 CB-F-1A-A CC-FC1-K803 Safeguard Test Cabinet Relay FC1 CB-F-3A-A CC-FC1-K811 Safeguard Test Cabinet Relay FC1 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -7 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 CC-V-122 Primary Component Cooling Water Loop "A" Header Isolation Outboard Return Valve CC-20207 B 310769 PP-F-4B-Z - X X X UZ1 CC-E2U/6-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-GZ0/2 GZ0-UZ1 GZ0-UZ2 310895 E2U/6a E2U/6d E2U/6b E2U/6e CBA-FN-32 CBA-FN-33 Instrument Air EDE-PP-113B EAH-FN-31B CC-V-257 CC-CS-2149-2 Control Switch with Indication GZ0 CB-F-1B-A CC-SS-2149 Selector Switch GZ0 CB-F-1B-A CC-ZS-V122 Valve Position Switch UZ1 PP-F-4B-Z CC-V122-20-1 Pilot Solenoid UZ1 PP-F-4B-Z CC-V122-20-2 Pilot Solenoid UZ1 PP-F-4B-Z CC-CS-2149-1 Control Switch with Indication F30 CB-F-3A-A F30-GZO/6 F30-GZO/7 F30-FB0/5 GN0-GZ0/6 FB0-GZ0 FC2-GZ0 FC2-GZ0/1 F30-GZ0/9 GNO-GZO/8 CC-FB0-K-633B Protection System Relay FB0 CB-F-3A-A CC-FB0-K-632B Protection System Relay FB0 CB-F-3A-A CC-BTR-LLA1 Isolation Signal Auxiliary Relay GN0 CB-F-1B-A CC-FC2-K803 Safeguard Test Cabinet Relay FC2 CB-F-3A-A CC-FC2-K811 Safeguard Test Cabinet Relay FC2 CB-F-3A-A 8 CC-V-168 Primary Component Cooling Water Loop "A" Header Isolation Outboard Supply Valve CC-20207 B 310769 PP-F-4B-Z - X X X UZ2 CC-E2U/6-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-GZ0/2 GZ0-UZ2 GZO-UZ1 310895 E2U/6b E2U/4d E2U/6a E2U/4e CBA-FN-32 CBA-FN-33 Instrument Air EDE-PP-113B EAH-FN-5B EAH-FN-31B CC-V-175 CC-CS-2151-2 Control Switch with Indication GZ0 CB-F-1B-A CC-SS-2151 Selector Switch GZ0 CB-F-1B-A CC-ZS-V168 Valve Position Switch UZ2 PP-F-4B-Z CC-V168-20-1 Pilot Solenoid UZ2 PP-F-4B-Z CC-V168-20-2 Pilot Solenoid UZ2 PP-F-4B-Z CC-CS-2151-1 Control Switch with Indication F30 CB-F-3A-A F30-GZO/7 F30-GZ0/9 F30-FB0/5 GN0-GZ0/8 FB0-GZ0 FC2-GZ0 FC2-GZ0/1 F30-GZ0/6 GN0-GZO/6 CC-FB0-K-633B Protection System Relay FB0 CB-F-3A-A CC-FB0-K-632B Protection System Relay FB0 CB-F-3A-A CC-BTR-LLA1 Isolation Signal Auxiliary Relay GN0 CB-F-1B-A CC-FC2-K803 Safeguard Test Cabinet Relay FC2 CB-F-3A-A CC-FC2-K811 Safeguard Test Cabinet Relay FC2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -8 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 CC-V-175 Primary Component Cooling Water Loop "B" Header Isolation Outboard Supply Valve CC-20213 A 310769 PP-F-4B-Z - X X X UZ4 CC-E2T/6-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-G2G G2G-UZ4 G2G-UZ3 310895 E2T/6a E2T/6d E2T/6b E2T/6e CBA-FN-19 CBA-FN-20 Instrument Air EDE-PP-113A EAH-FN-5A EAH-FN-31A CC-V-168 CC-CS-2251-2 Control Switch with Indication G2G CB-F-1A-A CC-SS-2251 Selector Switch G2G CB-F-1A-A CC-ZS-V175 Valve Position Switch UZ4 PP-F-4B-Z CC-V175-20-1 Pilot Solenoid UZ4 PP-F-4B-Z CC-V175-20-2 Pilot Solenoid UZ4 PP-F-4B-Z CC-CS-2251-1 Control Switch with Indication F30 CB-F-3A-A F30-G2G F30-G2G/1 F30-FB7/6 G2G-GN9 FB7-G2G FC1-G2G FC1-G2G/1 F30-G2G/5 G2G-GN9/3 CC-FB7-K-633A Protection System Relay FB7 CB-F-3A-A CC-FB7-K-632A Protection System Relay FB7 CB-F-3A-A CC-ATR-LLB1 Isolation Signal Auxiliary Relay GN9 CB-F-1A-A CC-FC1-K803 Safeguard Test Cabinet Relay FC1 CB-F-3A-A CC-FC1-K812 Safeguard Test Cabinet Relay FC1 CB-F-3A-A 10 CC-V-176 Primary Component Cooling Water Loop "B" Header Isolation Inboard Supply Valve CC-20213 B 310579 C-F-2-Z - X X X VA9 CC-E2U/4-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-E4C E4C-G2J G2J-H39 G2J-H39/1 H39-VA9 H39-VA0 310895 E2U/4a E2U/4d E2U/4b E2U/4e E2U/4f CBA-FN-32 CBA-FN-33 Instrument Air EDE-PP-113B CC-V-57 CC-CS-2299-2 Control Switch with Indication G2J CB-F-1B-A CC-SS-2299 Selector Switch G2J CB-F-1B-A CC-ZS-V176 Valve Position Switch VA9 C-F-2-Z CC-E4C-FU15,16 30A Fuses E4C CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A CC-V176-20-1 Pilot Solenoid VA9 C-F-2-Z CC-V176-20-2 Pilot Solenoid VA9 C-F-2-Z CC-CS-2299-1 Control Switch with Indication F30 CB-F-3A-A F30-G2J/1 F30-G2J/6 F30-FB0/4 G2J-GN0/2 FB0-G2J FC2-G2J FC2-G2J/2 F30-G2J G2J-GN0/3 CC-FB0-K-633B Protection System Relay FB0 CB-F-3A-A CC-FB0-K-632B Protection System Relay FBO CB-F-3A-A CC-BTR-LLB1 Isolation Signal Auxiliary Relay GN0 CB-F-1B-A CC-FC2-K803 Safeguard Test Cabinet Rela y FC2 CB-F-3A-A CC-FC2-K812 Safeguard Test Cabinet Relay FC2 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -9 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 CC-V-256 Primary Component Cooling Water Loop "B" Header Isolation Inboard Return Valve CC-20213 B 310579 C-F-2-Z - X X X VA0 CC-E2U/4-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-E4C E4C-G2J G2J-H39 H39-VA0 H39-VA9 G2J-H39/1 310895 E2U/4a E2U/4d E2U/4b E2U/4e E2U/4f CBA-FN-32 CBA-FN-33 Instrument Air EDE-PP-113B CC-V-121 CC-CS-2250-2 Control Switch with Indication G2J CB-F-1B-A CC-SS-2250 Selector Switch G2J CB-F-1B-A CC-ZS-V256 Valve Position Switch VA0 C-F-2-Z CC-E4C-FU15,16 30A Fuses E4C CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A CC-V256-20-1 Pilot Solenoid VA0 C-F-2-Z CC-V256-20-2 Pilot Solenoid VA0 C-F-2-Z CC-V176-20-2 Pilot Solenoid VA9 C-F-2-Z CC-CS-2250-1 Control Switch with Indication F30 CB-F-3A-A F30-G2J F30-G2J/1 F30-FB0/4 G2J-GN0/3 FB0-G2J FC2-G2J FC2-G2J/2 G2J-GN0/2 F30-G2J/6 CC-FB0-K-633B Protection System Relay FB0 CB-F-3A-A CC-FB0-K-632B Protection System Relay FB0 CB-F-3A-A CC-BTR-LLB1 Isolation Signal Auxiliary Relay GN0 CB-F-1B-A CC-FC2-K803 Safeguard Test Cabinet Relay FC2 CB-F-3A-A CC-FC2-K812 Safeguard Test Cabinet Relay FC2 CB-F-3A-A 12 CC-V-257 Primary Component Cooling Water Loop "B" Header Isolation Outboard Return Valve CC-20213 A 310769 PP-F-4B-Z - X X X UZ3 CC-E2T/6-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-G2G G2G-UZ3 G2G-UZ4 310895 E2T/6a E2T/6d E2T/6b E2T/6e CBA-FN-19 CBA-FN-20 Instrument Air EDE-PP-113A EAH-FN-5A EAH-FN-31A CC-V-122 CC-CS-2249-2 Control Switch with Indication G2G CB-F-1A-A CC-SS-2249 Selector Switch G2G CB-F-1A-A CC-ZS-V257 Valve Position Switch UZ3 PP-F-4B-Z CC-V257-20-1 Pilot Solenoid UZ3 PP-F-4B-Z CC-V257-20-2 Pilot Solenoid UZ3 PP-F-4B-Z CC-CS-2249-1 Control Switch with Indication F30 CB-F-3A-A F30-G2G/1 F30-G2G/5 F30-FB7/6 G2G-GN9/3 FB7-G2G FC1-G2G FC1-G2G/1 F30-G2G G2G-GN9 CC-FB7-K-633A Protection System Relay FB7 CB-F-3A-A CC-FB7-K-632A Protection System Relay FB7 CB-F-3A-A CC-ATR-LLB1 Isolation Signal Auxiliary Relay GN9 CB-F-1A-A CC-FC1-K803 Safeguard Test Cabinet Relay FC1 CB-F-3A-A CC-FC1-K812 Safeguard Test Cabinet Relay FC1 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -10 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 CC-TV-2171-1 Primary Component Cooling Water Heat Exchanger E-17A Temperature Control Valve CC-20205 A 310765 PAB-F-2C-Z X X X X UN6 CC-E2T/3-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-G81 G81-G2M G81-UN6/1 G81-UN7/1 G81-GN9/A F30-G81/6 F30-G81/7 310895 E2T/3a E2T/3c E2T/3d CBA-FN-19 CBA-FN-20 PAH-FN-42A EDE-PP-113A Instrument Air CC-TV-2271-1 CC-SS-2171 Selector Switch G81 CB-F-1A-A CC-GN9-R1 Auxiliary Relay GN9 CB-F-1A-A CC-TY-2171-1 Pilot Solenoid G2M PAB-F-2C-Z CC-ZL-2171-5 Valve Position Indicating Lights G81 CB-F-1A-A CC-ZS-TV-2171-1 Valve Position Switch UN6 PAB-F-2C-Z CC-CS-2171 Control Switch F30 CB-F-3A-A G81-G2M/2 F30-FK0/3 FK0-G81/1 FK0-TM0 CC-GN9-R1 Auxiliary Relay GN9 CB-F-1A-A CC-ZL-2171-1 Indicating Lights F30 CB-F-3A-A CC-SS-2171 Selector Switch G81 CB-F-1A-A 310895 310952 4c FK0d FK0f FK0h CBA-FN-19 CB-FN-20 PAH-FN-42A Instrument Air MM-CP-297A CC-TY-2171-4 I/P Converter G2M PAB-F-2C-Z CC-TY-2171-5 I/P Converter G2M PAB-F-2C-Z CC-TE-2171 Temperature Element TM0 PAB-F-2C-Z CC-TYY-2171-2 PCCW Loop "A" Relay FK0 CB-F-3A-A CC-TK-2171 Manual Controller F30 CB-F-3A-A MM-CP-297A BOP-PCC FK0 CB-F-3A-A 14 CC-TV-2171-2 Primary Component Cooling Water Heat Exchanger E-17A Temperature Control Valve CC-20205 A 310765 PAB-F-2C-Z X X X X UN7 CC-E2T/3-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-G81 G81-G2M G81-UN6/1 G81-UN7/1 G81-GN9/A F30-G81/6 F30-G81/7 310895 E2T/3a E2T/3c E2T/3d CBA-FN-19 CBA-FN-20 PAH-FN-42A EDE-PP-113A Instrument Air CC-TV-2271-2 CC-SS-2171 Selector Switch G81 CB-F-1A-A CC-GN9-R1 Auxiliary Relay GN9 CB-F-1A-A CC-TY-2171-2 Pilot Solenoid G2M PAB-F-2C-Z CC-ZL-2171-6 Valve Position Indicating Lights G81 CB-F-1A-A CC-ZS-TV-2171-2 Valve Position Switch UN7 PAB-F-2C-Z CC-CS-2171 Control Switch F30 CB-F-3A-A CC-GN9-R1 Auxiliary Relay GN9 CB-F-1A-A CC-ZL-2171-2 Indicating Lights F30 CB-F-3A-A CC-SS-2171 Selector Switch G81 CB-F-1A-A G81-G2M/2 F30-FK0/3 FK0-G81/1 FK0-TM0 310895 310952 4c FK0d FK0f FK0h CBA-FN-19 CB-FN-20 PAH-FN-42A Instrument Air CC-TY-2171-4 I/P Converter G2M PAB-F-2C-Z CC-TY-2171-5 I/P Converter G2M PAB-F-2C-Z CC-TE-2171 Temperature Element TM0 PAB-F-2C-Z CC-TYY-2171-2 PCCW Loop "A" Relay FK0 CB-F-3A-A CC-TK-2171 Manual Controller F30 CB-F-3A-A MM-CP-297A BOP-PCC FK0 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -11 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 CC-TV-2271-1 Primary Component Cooling Water Heat Exchanger E-17B Temperature Control Valve CC-20211 B 310765 PAB-F-2C-Z X X X X UP9 CC-E2U/3-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-GZ0 GN0-GZ0/5 GZO-UP9/1 GZ0-UP0/1 GN0-GZ0/9 E2U-GN0/6 GZO-UI2 F31-GZ0/3 F31-GZ0/4 310895 E2U/3a E2U/3c E2U/3d CBA-FN-32 CBA-FN-33 PAH-FN-42B EDE-PP-113B Instrument Air CC-TV-2171-1 CC-SS-2271 Selector Switch GZ0 CB-F-1B-A CC-GN0-R1 Auxiliary Relay GN0 CB-F-1B-A CC-GNO-R2 Auxiliary Relay GN0 CB-F-1B-A CC-TY-2271-1 Pilot Solenoid UI2 PAB-F-2C-Z CC-ZL-2271-5 Valve Position Indicating Lights GZO CB-F-1B-A CC-ZS-TV-2271-1 Valve Position Switch UP9 PAB-F-2C-Z CC-CS-2271 Control Switch F30 CB-F-3A-A CC-ZL-2271-1 Indicating Lights F30 CB-F-3A-A CC-SS-2271 Selector Switch GZ0 CB-F-1B-A GZ0-Q60 FJ4-TM8/1 FJ4-GZ0/3 F30-FJ4/1 310895 310952 4c FJ4j FJ4l FJ4m CBA-FN-32 CB-FN-33 PAH-FN-42B Instrument Air MM-CP-152B CC-TY-2271-5 I/P Converter Q60 PAB-F-2C-Z CC-TY-2271-4 I/P Converter Q60 PAB-F-2C-Z CC-TE-2271 Temperature Element TM8 PAB-F-2C-Z CC-TYY-2271-2 PCCW Loop "B" Relay FJ4 CB-F-3A-A CC-TK-2271 Manual Controller F30 CB-F-3A-A MM-CP-152B BOP-PCC FJ4 CB-F-3A-A 16 CC-TV-2271-2 Primary Component Cooling Water Heat Exchanger E-17B Temperature Control Valve CC-20211 B 310765 PAB-F-2C-Z X X X X UP0 CC-E2U/3-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-GZ0 GN0-GZ0/5 GZO-UP9/1 GZ0-UP0/1 GN0-GZ0/9 E2U-GN0/6 GZO-UI2 F31-GZ0/3 F31-GZ0/4 310895 E2U/3a E2U/3c E2U/3d CBA-FN-32 CBA-FN-33 PAH-FN-42B EDE-PP-113B Instrument Air CC-TV-2171-2 CC-SS-2271 Selector Switch GZ0 CB-F-1B-A CC-GN0-R1 Auxiliary Relay GN0 CB-F-1B-A CC-GNO-R2 Auxiliary Relay GN0 CB-F-1B-A CC-TY-2271-2 Pilot Solenoid UI2 PAB-F-2C-Z CC-ZL-2271-6 Valve Position Indicating Lights GZO CB-F-1B-A CC-ZS-TV-2271-2 Valve Position Switch UP0 PAB-F-2C-Z CC-CS-2271 Control Switch F30 CB-F-3A-A CC-ZL-2271-2 Indicating Lights F30 CB-F-3A-A CC-SS-2271 Selector Switch GZ0 CB-F-1B-A GZ0-Q60 FJ4-TM8/1 FJ4-GZ0/3 F30-FJ4/1 310895 310952 4c FJ4j FJ4l FJ4m CBA-FN-32 CB-FN-33 PAH-FN-42B Instrument Air MM-CP-152B CC-TY-2271-5 I/P Converter Q60 PAB-F-2C-Z CC-TY-2271-4 I/P Converter Q60 PAB-F-2C-Z CC-TE-2271 Temperature Element TM8 PAB-F-2C-Z CC-TYY-2271-2 PCCW Loop "B" Relay FJ4 CB-F-3A-A CC-TK-2271 Manual Controller F30 CB-F-3A-A MM-CP-152B BOP-PCC FJ4 CB-F-3A-A 17 CC-E-17A Primary Component Cooling Water Heat Exchanger CC-20205 A 310765 805217 PAB-F-2C-Z PAB-F-3A-Z X X - - - - - - - - - - Service Water CC-E-17B Notes 1 and 3 18 CC-E-17B Primary Component Cooling Water Heat Exchanger CC-20211 B 310765 805217 PAB-F-2C-Z PAB-F-3A-Z X X - - - - - - - - - - Service Water CC-E-17A Notes 1 and 3 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -12 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 CC-V-145 RH-E-9A Return Header Isolation Valve V-145 CC-20207 A 310763 RHR-F-3B-Z - X X - V78 CC-BY2-52 460 V AC Circuit Breaker BY2 CB-F-1A-A BY2-F30 BY2-F30/1 F30-FB7/1 BY2-V78 BY2-V78/1 BY2-V78/2 310895 BY2a BY2c EAH-FN-5A EAH-FN-31A EDE-MCC-512 CC-V-272 CC-CS-2144 Control Switch with Indication F30 CB-F-3A-A CC-BY2-42 Motor Starter BY2 CB-F-1A-A CC-BY2-49 Thermal Overload BY2 CB-F-1A-A CC-V78-V145 Position Switch V78 RHR-F-3B-Z CC-FB7-K624A Containment Isolation Auxiliary Relay FB7 CB-F-3A-A 20 CC-V-272 RHR-E-9B Return Header Isolation Valve V-272 CC-20213 B 310763 RHR-F-3A-Z - X X - V72 CC-BY8-52 460 V AC Circuit Breaker BY8 CB-F-1A-A BY8-F31 BY8-F31/1 F31-FB0/3 BY8-V72 BY8-V72/1 BY8-V72/2 BY8-E3Q BY8a BY8c EAH-FN-5B EAH-FN-31B EDE-MCC-612 CC-V-145 CC-CS-2244 Control Switch with Indication F30 CB-F-3A-A CC-BY8-42 Motor Starter BY8 CB-F-1B-A CC-BY8-49 Thermal Overload BY8 CB-F-1B-A CC-V72-V272 Position Switch V72 RHR-F-3A-Z CC-FB0-K623B Containment Isolation Auxiliary Relay FB0 CB-F-3A-A CC-BY8-R1 Auxiliary Relay E3Q CB-F-1B-A 21 CC-P-322A Thermal Barrier PCCW Recirculation Pump CC-20209 A 310576 C-F-1-Z X X X - M1D CC-B4M-52-1,2 460 V AC Circuit Breakers B4M CB-F-1A-A B4M-H18 H18-M1D B4M-G81 F30-FK0/2 F30-G81/A B4Ma B4Mc B4Md CBA-FN-19 CBA-FN-20 EDE-MCC-515 CC-P-322B CC-CS-2077-2 Control Switch with Indication G2G CB-F-1A-A CC-SS-2077 Selector Switch G2G CB-F-1A-A CC-B4M-42 Motor Starter B4M CB-F-1A-A CC-B4M-49 Overload Relay B4M CB-F-1A-A EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A CC-B4M-FU Fuse B4M CB-F-1A-A CC-CS-2077-1 Control Switch with Indication F30 CB-F-3A-A CC-FYY-2175A Flow Relay FK0 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -13 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 22 CC-P-322B Thermal Barrier PCCW Recirculation Pump CC-20209 B 310577 C-F-1-Z X X X - M1E CC-B4Q-52-1,2 460 V AC Circuit Breaker B4Q CB-F-1B-A B4Q-H15 H15-M1E B4Q-GZ0 F30-FL2 F30-GZ0/8 B4Qa B4Qc B4Qd CBA-FN-32 CBA-FN-33 EDE-MCC-615 CC-P-322A CC-CS-2078-2 Control Switch with Indication G2J CB-F-1B-A CC-SS-2078 Selector Switch G2J CB-F-1B-A CC-B4Q-42 Motor Starter B4Q CB-F-1B-A CC-B4Q-49 Overload Relay B4Q CB-F-1B-A EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A CC-B4Q-FU Fuses B4Q CB-F-1B-A CC-CS-2078-1 Control Switch with Indication F30 CB-F-3A-A CC-FYY-2175B Flow Relay FL2 CB-F-3A-A 23 CC-E-153A Thermal Barrier Heat Exchanger CC-20209 A 310576 C-F-1-Z X X - - - - - - - - - - - CC-E-153B Note 1 24 CC-E-153B Thermal Barrier Heat Exchanger CC-20209 B 310577 C-F-1-Z X X - - - - - - - - - - - CC-E-153A Note 1 25 CC-V-1101 Thermal Barrier HX CC-E-153A Isolation Valve CC-20209 A 310769 PP-F-3A-Z X X X - V2S CC-B4K-52 460 V AC Circuit Breaker B4K CB-F-1A-A B4K-V2S/1 B4K-F29 B4K-F29/1 310895 B4Ka B4Kc B4Kd CBA-FN-19 CBA-FN-20 CC-V-1092 CC-CS-2073 Control Switch with Indication F29 CB-F-3A-A CC-B4K-42 Motor Starter B4K CB-F-1A-A CC-B4K-49 Thermal Overload B4K CB-F-1A-A CC-V2S-V1101 Position Switch V2S PP-F-3A-Z 26 CC-V-1109 Thermal Barrier HX CC-E-153A Isolation Valve CC-20209 A 310769 PP-F-3A-Z X X X - V2T CC-B4L-52 460 V AC Circuit Breaker B4L CB-F-1A-A B4L-V2T/1 B4L-F29 B4L-F29/1 310895 B4La B4Lc B4Ld CBA-FN-19 CBA-FN-20 CC-V-1095 CC-CS-2074 Control Switch with Indication F29 CB-F-3A-A CC-B4L-42 Motor Starter B4L CB-F-1A-A CC-B4L-49 Thermal Overload B4L CB-F-1A-A CC-V2T-V1109 Position Switch V2T PP-F-3A-Z 27 CC-V-1092 Thermal Barrier HX CC-E-153B Isolation Valve CC-20209 B 310769 PP-F-4B-Z X X X - V2V CC-B4P-52 460 V AC Circuit Breaker B4P CB-F-1B-A B4P-V2V/1 B4P-F20 B4P-F20/1 310895 B4Pa B4Pc B4Pd CBA-FN-32 CBA-FN-33 CC-V-1101 CC-CS-2075 Control Switch with Indication F29 CB-F-3A-A CC-B4P-42 Motor Starter B4P CB-F-1B-A CC-B4P-49 Thermal Overload B4P CB-F-1B-A CC-V2V-V1092 Position Switch V2V PP-F-4B-Z CC-B4P-R1 Auxiliary Relay E3Q CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -14 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 28 CC-V-1095 Thermal Barrier HX CC-E-153B Isolation Valve CC-20209 B 310769 PP-F-4B-Z X X X - V2U CC-B4N-52 460 V AC Circuit Breaker B4N CB-F-1B-A B4N-V2U/1 B4N-F20 B4N-F20/1 310895 B4Na B4Nc B4Nd CBA-FN-32 CBA-FN-33 CC-V-1109 CC-CS-2076 Control Switch with Indication F29 CB-F-3A-A CC-B4N-42 Motor Starter B4N CB-F-1B-A CC-B4N-49 Thermal Overload B4N CB-F-1B-A CC-V2U-V1095 Position Switch V2U PP-F-4B-Z CC-B4N-R1 Auxiliary Relay E3Q CB-F-1B-A 29 CC-V-428 RC-P-1A Thermal Barrier Isolation Valve CC-20209 A 310578 C-F-2-Z X X X - V74 CC-BY4-52-1 460 V AC Circuit Breaker BY4 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 2 30 CC-V-438 RC-P-1C Thermal Barrier Isolation Valve CC-20209 B 310579 C-F-2-Z X X X - V76 CC-BY6-52-1 460 V AC Circuit Breaker BY6 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 2 31 CC-V-439 RC-P-1D Thermal Barrier Isolation Valve CC-20209 A 310579 C-F-2-Z X X X - V70 CC-BY7-52-1 460 V AC Circuit Breaker BY7 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 2 32 CC-V-395 RC-P-1B Thermal Barrier Isolation Valve CC-20209 B 310578 C-F-2-Z X X X - V69 CC-BY5-52-1 460 V AC Circuit Breaker BY5 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 2 33 CC-TK-196 Thermal Barrier Loop Head Tank CC-20209 A/B 310581 805193 C-F-3-Z X X - - - - - - - - - - - None Notes 1 and 4 34 CC-TK-19A Primary Component Cooling Water Head Tank CC-20205 A 310767 PAB-F-3A-Z X X - - - - - - - - - - - CC-TK-19B Note 1 35 CC-TK-19B Primary Component Cooling Water Head Tank CC-20211 B 310767 PAB-F-3A-Z X X - - - - - - - - - - - CC-TK-19A Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -15 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 36 CC-LT-2172-1 CC-LT-2172-2 CC-LT-2172-3 Head Tank CC-TK-19A Level CC-20205 A 310767 PAB-F-3A-Z X X X - RG5 RW1 RW2 MM-CP-152A EDE-TBX-YH4 BOP-PCC Terminal Box FJ1 YH4 CB-F-3A-A PAB-F-3A-Z FJ1-YH4 RG5-YH4 RW1-YH4 RW2-YH4 310952 FJ1g FJ1j CC-LT-2272-1 CC-LT-2272-2 CC-LT-2272-3 Head Tank CC-TK-19B Level CC-20211 B 310768 PAB-F-3B-Z X X X - RG6 RW3 RW4 MM-CP-152A EDE-TBX-YH4 BOP-PCC Terminal Box FJ1 YH4 CB-F-3A-A PAB-F-3A-Z FJ1-YH4/1 RG6-YH4 RW3-YH4 RW4-YH4 CC-E42/10-52 120 V AC Circuit Breaker E42 CB-F-1A-A EF4-FJ1 EF4-FJ1/1 E4E-EF4 E4E-H36/3 H36-S4P GF8-H36 310895 E42/10a E42/10c E42/10d EDE-MCC-521 CC-LYY-2172-1, 2, 3 Level Relay FJ1 CB-F-3A-A CC-LYY-2272-1, 2, 3 Level Relay FJ1 CB-F-3A-A CC-RYY-2172-1LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2172-2LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2172-3LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2272-1LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2272-2LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2272-3LL Auxiliary Relay EF4 CB-F-1A-A MM-CP-152A BOP-PCC FJ1 CB-F-3A-A EDE-MM-582 Fuse Panel E4E ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A CC-FISHL-2147 Flow Switch S4P C-F-2-Z CC-FISHL-2248 Flow Switch GF8 C-F-2-Z MM-CP-14 Safeguards Cabinet FC1 CB-F-3A-A EF4-GN9 FC1-GN9/1 310895 E87/10a E87/10d E87/10b E87/10e E87/10f CC-RYY-2172-1LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2172-2LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2172-3LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2272-1LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2272-2LL Auxiliary Relay EF4 CB-F-1A-A CC-RYY-2272-3LL Auxiliary Relay EF4 CB-F-1A-A CC-ATR-LLA1 Containment Isolation Relay GN9 CB-F-1A-A CC-ATR-LLB1 Containment Isolation Relay GN9 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.8 -16 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 37 CC-LT-2192-1 CC-LT-2192-2 CC-LT-2192-3 Head Tank CC-TK-19A Level CC-20205 A 310767 PAB-F-3A-Z X X X - R81 RW5 RW6 MM-CP-152B EDE-TBX-YH5 BOP-PCC Terminal Box FJ4 YH5 CB-F-3A-A PAB-F-3A-Z FJ4-YH5 R81-YH5 RW5-YH5 RW6-YH5 310952 FJ4j FJ4l CC-LT-2292-1 CC-LT-2292-2 CC-LT-2292-3 Head Tank CC-TK-19B Level CC-20211 B 310768 PAB-F-3B-Z X X X - R82 RW7 RW8 MM-CP-152B EDE-TBX-YH5 BOP-PCC Terminal Box FJ4 YH5 CB-F-3A-A PAB-F-3A-Z FJ4-YH5/1 R82-YH5 RW7-YH5 RW8-YH5 CC-E50/6-52 120 V AC Circuit Breaker E50 CB-F-1B-A EE3-FJ4 E4J-ED0/1 E50-E4J/1 EE3-FJ4/1 EDO-H41 H41-S4Q GN5-H41 310895 E50/6a E50/6c E50/6b E50/6e EDE-MCC-621 CC-LYY-2192-1,2,3 Level Relay FJ4 CB-F-3A-A CC-LYY-2292-1,2,3 Level Relay FJ4 CB-F-3A-A CC-RYY-2192-1LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2192-2LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2192-3LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2292-1LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2292-2LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2292-3LL Auxiliary Relay EE3 CB-F-1B-A MM-CP-152B BOP-PCC FJ4 CB-F-3B-A EDE-MM-586 Fuse Panel E4J CB-F-1B-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A CC-FISHL-2247 Flow Switch S4Q C-F-2-Z CC-FISHL-2148 Flow Switch GN5 C-F-2-Z MM-CP-15 Safeguards Cabinet FC2 CB-F-3A-A FC2-GN0/2 EE3-GN0 310895 E88/8a E88/8d E88/8b E88/8e E88/8f BTR-LLA1 Isolation Relay GN0 CB-F-1B-A BTR-LLB1 Isolation Relay GN0 CB-F-1B-A CC-RYY-2192-1LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2192-2LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2192-3LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2292-1LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2292-2LL Auxiliary Relay EE3 CB-F-1B-A CC-RYY-2292-3LL Auxiliary Relay EE3 CB-F-1B-A 38 MM-CP-152A BOP Process Control Cabinet - A 310499 CB-F-3A-A X X X - FJ1 - - - - EH9-FJ1 310952 EH9/1 EH9/1 EDE-PP-1E MM-CP-152B SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -1 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CAH-FN-1A Containment Structure Cooler AC-1A-Fan MAH-20506 B 301578 C-F-2-Z X X - M19 CAH-AC5-52 480 V AC Circuit Breaker AC5 CB-F-1B-A AC5-G2K AC5-G2K/1 AC5-GNO AC5-H13 AC5-H13/1 G2K-H41 G2K-H41/1 H13-JV7 H13-JV7/1 H41-M19/1 H41-SD1 JV7-JV8 JV7-M19 JV7-M19/1 JV8-M19 JV8-M19/1 F37-FBO/1 F37-G2K/9 F37-G2K/A F37-G2K/B G2K-HR4/2 G2K-HR4/7 310931 AC5a AC5d AC5b CBA-FN-32 CBA-FN-33 EDE-US-63 Primary Component Cooling Water CAH-FN-1C CAH-FN-1E CAH-FN-1F CAH-JV7-43 Safety Switch Speed Changer JV7 C-F-2-Z CAH-JV8-43 Safety Switch Speed Changer JV8 C-F-2-Z CAH-CS-5660-2 Control Switch with Indication G2K CB-F-1B-A CAH-SS-5660 Selector Switch G2K CB-F-1B-A EDE-AF8-94-4 Bus Undervoltage Relay AF8 CB-F-1B-A CAH-GNO-R1 Time Delay Relay GNO CB-F-1B-A CC-FISL-2122 Flow Indication Switch SD1 C-F-2-Z CAH-AC5-52H-1 Truck Operated Contact AC5 CB-F-1B-A CAH-AC5-G,R Indicating Lights AC5 CB-F-1B-A CAH-AC5-AM Ammeter AC5 CB-F-1B-A CAH-AC5-CT Current Transformer (300/5) AC5 CB-F-1B-A CAH-AC5-ATR Transducer AC5 CB-F-1B-A CAH-ZL-5660-2 Outlet Damper Position Lights G2K CB-F-1B-A CAH-DP-312 Outlet Damper Position Switch M19 C-F-2-Z EDE-MM-89 Electrical Penetration H13 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A CAH-AC5-FU 15A Fuses AC5 CB-F-1B-A CAH-CS-5660-1 Control Switch with Indication F37 CB-F-3A-A EPS-HR4-PR1, RA, RMO, SR3 Emergency Power Sequencer Relays HR4 CB-F-1B-A CAH-FBO-K610B SI Actuating Auxiliary Relay FBO CB-F-3A-A CAH-ZL-5660-1 Outlet Damper Position Lights F37 CB-F-3A-A CC-FISL-2122 Flow Indication Switch SD1 C-F-2-Z E4G-H41/1 E53-E4G/1 H41-SD1/1 E53-E4G H41-SD2/1 E4G-H39/1 H39-SD4/1 310895 E53/10a E53/10c EDE-MCC-631 CC-E4G-FU6, FU5 30A Fuse E4G ET-F-1C-A EDE-MM-117 Electrical Penetration H41 ET-F-1C-A, C-F-1-Z CAH-E53/10-52 120 V AC Circuit Breaker E53 CB-F-1B-A CC-FISL-2123 Flow Indication Switch SD2 C-F-2-Z EDE-MM-115 Electrical Penetration H39 ET-F-1C-A, C-F-1-Z CC-FISL-2222 Flow Indication Switch SD4 C-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -2 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 CAH-FN-1B Containment Structure Cooler AC-1B Fan MAH-20506 B 310579 C-F-2-Z X X - M20 CAH-AE5-52 480 V AC Circuit Breaker AE5 CB-F-1B-A AE5-G2K AE5-G2K/1 AE5-GNO G2K-H41/2 G2K-H41/3 AE5-H13 AE5-H13/1 H13-M20 H13-M20/1 H41-M20/1 H41-SD2 F37-FBO/2 F37-G2K/3 F37-G2K/4 F37-G2K/5 G2K-HR4/3 G2K-HR4/5 310931 AE5a AE5d AE5b CBA-FN-32 CBA-FN-33 EDE-US-63 Primary Component Cooling Water CAH-FN-1C CAH-FN-1E CAH-FN-1F CAH-CS-5661-2 Control Switch with Indication G2K CB-F-1B-A CAH-SS-5661 Selector Switch G2K CB-F-1B-A EDE-AF8-94-4 Bus Undervoltage Relay AF8 CB-F-1B-A CAH-GNO-R1 Time Delay Relay GNO CB-F-1B-A CC-FISL-2123 Flow Indication Switch SD2 C-F-2-Z CAH-AE5-52H-1 Truck Operated Contact AE5 CB-F-1B-A CAH-AE5-G,R Indicating Lights AE5 CB-F-1B-A CAH-AE5-AM Ammeter AE5 CB-F-1B-A CAH-AE5-CT Current Transformer (300/5) AE5 CB-F-1B-A CAH-AE5-ATR Transducer AE5 CB-F-1B-A CAH-ZL-5661-2 Outlet Damper Position Lights G2K CB-F-1B-A CAH-DP-313 Outlet Damper Position Switch M20 C-F-2-Z EDE-MM-89 Electrical Penetration H13 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A CAH-AE5-FU 15A Fuses AE5 CB-F-1B-A CAH-CS-5661-1 Control Switch with Indication F37 CB-F-3A-A EPS-HR4-PR1, RA, RMO, SR3 Emergency Power Sequencer Relays HR4 CB-F-1B-A CAH-FBO-K-610B SI Actuating Auxiliary Relay FBO CB-F-3A-A CAH-ZL-5661-1 Outlet Damper Position Lights F37 CB-F-3A-A CC-FISL-2123 Flow Indication Switch SD2 C-F-2-Z H41-SD2/1 E53-E4G/1 E4G-H41/1 E53-E4G H41-SD1/1 E4G-H39/1 H39-SD4/1 301895 E53/10a E53/10c EDE-MCC-631 CC-E4G-FU6, FU5 30A Fuse E4G ET-F-1C-A EDE-MM-117 Electrical Penetration H41 ET-F-1C-A, C-F-1-Z CAH-E53/10-52 120 V AC Circuit Breaker E53 CB-F-1B-A CC-FISL-2122 Flow Indication Switch SD1 C-F-2-Z EDE-MM-115 Electrical Penetration H39 ET-F-1C-A, C-F-1-Z CC-FISL-2222 Flow Indication Switch SD4 C-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -3 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 CAH-FN-1C Containment Structure Cooler AC-1C Fan MAH-20506 A 310579 C-F-2-Z - X X - M21 CAH-AE7-52 480 V AC Circuit Breaker AE7 CB-F-1A-A AE7-G2H AE7-G2H/1 AE7-GN9 AE7-HO8 AE7-HO8/1 G2H-H35 G2H-H35/1 HO8-JV3 HO8-JV3/1 H35-M21/1 H35-SD3/1 JV3-JV4 JV3-M21 JV3-M21/1 JV4-M21 JV4-M21/1 F36-FB7/4 F36-G2H/9 F36-G2H/A F36-G2H/B G2H-HR2/4 G2H-HR2/5 310931 AE7a AE7d AE7b CBA-FN-19 CBA-FN-20 EDE-US-53 Primary Component Cooling Water CAH-FN-1A CAH-FN-1B CAH-FN-1D CAH-JV3-43 Safety Switch Speed Changer JV3 C-F-2-Z CAH-JV4-43 Safety Switch Speed Changer JV4 C-F-2-Z CAH-CS-5662-2 Control Switch with Indication G2H CB-F-1A-A CAH-SS-5662 Selector Switch G2H CB-F-1A-A EDE-AF3-94-4 Bus Undervoltage Relay AF3 CB-F-1A-A CAH-GN9-R1 Time Delay Relay GN9 CB-F-1A-A CC-FISL-2124 Flow Indication Switch SD3 C-F-2-Z CAH-AE7-52H-1 Truck Operated Contact AE7 CB-F-1A-A CAH-AE7-G,R Indicating Lights AE7 CB-F-1A-A CAH-AE7-AM Ammeter AE7 CB-F-1A-A CAH-AE7-CT Current Transformer (300/5) AE7 CB-F-1A-A CAH-AE7-ATR Transducer AE7 CB-F-1A-A CAH-ZL-5662-2 Outlet Damper Position Lights G2H CB-F-1A-A CAH-DP-314 Outlet Damper Position Switch M21 C-F-2-Z EDE-MM-84 Electrical Penetration HO8 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A CAH-AE7-FU 15A Fuses AE7 CB-F-1A-A CAH-CS-5662-1 Control Switch with Indication F36 CB-F-3A-A EPS-HR4-PR1, RA, RMO, SR3 Emergency Power Sequencer Relays HR2 CB-F-1A-A CAH-FB7-K-610A SI Actuating Auxiliary Relay FB7 CB-F-3A-A CAH-ZL-5662-1 Outlet Damper Position Lights F36 CB-F-3A-A CC-FISL-2124 Flow Indication Switch SD3 C-F-2-Z E4H-H35 E45-E4H H35-SD3 E45-E4E E4E-H36/4 H36-SD5/1 H36-SD6/1 301895 E45/11a E45/11C EDE-MCC-531 CC-E4H-FU20 30A Fuse E4H CB-F-1A-A EDE-MM-111 Electrical Penetration H35 ET-F-1A-A, C-F-2-Z CAH-E45/11-52 120 V AC Circuit Breaker E45 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -4 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 CAH-FN-1C (Continued) Containment Structure Cooler AC-1C Fan EDE-MM-112 Electrical Penetration H36 ET-F-1A-A, C-F-2-Z CC-FISL-2223 Flow Indication Switch SD5 C-F-2-Z CC-FISL-2224 Flow Indication Switch SD6 C-F-2-Z CC-E4E-FU39 30A Fuse E4E ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -5 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 CAH-FN-1D Containment Structure Cooler AC-1D Fan MAH-20505 B 310579 C-F-2-Z X X - M22 CAH-AE6-52 480 V AC Circuit Breaker AE6 CB-F-1B-A AE6-G2K AE6-G2K/1 AE6-GNO AE6-HO9 AE6-HO9/1 G2K-H39 G2K-H39/1 HO9-M22 HO9-M22/1 H39-M22/1 H39-SD4 F37-FBO/3 F37-G2K/6 F37-G2K/7 F37-G2K/8 G2K-HR4/4 G2K-HR4/6 310931 AE6a AE6d AE6b CBA-FN-32 CBA-FN-33 EDE-US-63 Primary Component Cooling Water CAH-FN-1C CAH-FN-1E CAH-FN-1F CAH-CS-5663-2 Control Switch with Indication G2K CB-F-1B-A CAH-SS-5663 Selector Switch G2K CB-F-1B-A EDE-AF8-94-4 Bus Undervoltage Relay AF8 CB-F-1B-A CAH-GNO-R1 Time Delay Relay GNO CB-F-1B-A CC-FISL-2222 Flow Indication Switch SD4 C-F-2-Z CAH-AE6-52H-1 Truck Operated Contact AE6 CB-F-1B-A CAH-AE6-G,R Indicating Lights AE6 CB-F-1B-A CAH-AE6-AM Ammeter AE6 CB-F-1B-A CAH-AE6-CT Current Transformer (300/5) AE6 CB-F-1B-A CAH-AE6-ATR Transducer AE6 CB-F-1B-A CAH-ZL-5663-2 Outlet Damper Position Lights G2K CB-F-1B-A CAH-DP-315 Outlet Damper Position Switch M22 C-F-2-Z EDE-MM-85 Electrical Penetration HO9 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A CAH-AE6-FU 15A Fuses AE6 CB-F-1B-A CAH-CS-5663-1 Control Switch with Indication F37 CB-F-3A-A EPS-HR4-PR1, RA, RMO, SR3 Emergency Power Sequencer Relays HR4 CB-F-1B-A CAH-FBO-K610B SI Actuating Auxiliary Relay FBO CB-F-3A-A CAH-ZL-5663-1 Outlet Damper Position Lights F37 CB-F-3A-A CC-FISL-2222 Flow Indication Switch SD4 C-F-2-Z E4G-H39/1 E53-E4G H39-SD4/1 E53-E4G/1 E4G-H41/1 H41-SD1/1 H41-SD2/1 310895 E53/10a E53/10c EDE-MCC-631 CC-E4G-FU5, FU6 30A Fuse E4G ET-F-1C-A EDE-MM-115 Electrical Penetration H39 ET-F-1C-A, C-F-1-Z CAH-E53/10-52 120 V AC Circuit Breaker E53 CB-F-1B-A EDE-MM-117 Electrical Penetration M41 ET-F-1C-A, C-F-1-Z CC-FISL-2123 Flow Indication Switch SD2 C-F-2-Z CC-FISL-2122 Flow Indication Switch SD1 C-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -6 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 CAH-FN-1E Containment Structure Cooler AC-1E Fan MAH-20505 A 310579 C-F-2-Z X X - M23 CAH-AC6-52 480 V AC Circuit Breaker AC6 CB-F-1A-A AC6-G2H AC6-G2H/1 AC6-GN9 AC6-HO7 AC6-HO7/1 G2H-H36 G2H-H36/1 HO7-JV5 H07-JV5/1 H36-H23/1 H36-SD5 JV5-JV6 JV5-M23 JV5-M23/1 JV6-M23 JV6-M23/1 F36-FB7/5 F36-G2H/3 F36-G2H/4 F36-G2H/5 G2H-HR2 G2H-HR2/1 310931 AC6a AC6d AC6b CBA-FN-19 CBA-FN-20 EDE-US-53 Primary Component Cooling Water CAH-FN-1A CAH-FN-1B CAH-FN-1D CAH-JV5-43 Safety Switch Speed Changer JV5 C-F-2-Z CAH-JV6-43 Safety Switch Speed Switch JV6 C-F-2-Z CAH-AC6-G,R Indicating Lights AC6 CB-F-1A-A CAH-CS-5664-2 Control Switch with Indication G2H CB-F-1A-A CAH-SS-5664 Selector Switch G2H CB-F-1A-A EDE-AF3-94-4 Bus Undervoltage Relay AF3 CB-F-1A-A CAH-GN9-R1 Time Delay Relay GN9 CB-F-1A-A CC-FISL-2223 Flow Indication Switch SD5 C-F-2-Z CAH-AC6-52H-1 Truck Operated Contact AC6 CB-F-1A-A CAH-AC6-AM Ammeter AC6 CB-F-1A-A CAH-AC6-CT Current Transformer (300/5) AC6 CB-F-1A-A CAH-AC6-ATR Transducer AC6 CB-F-1A-A CAH-ZL-5664-2 Outlet Damper Position Lights G2H CB-F-1A-A CAH-DP-316 Outlet Damper Position Switch M23 C-F-2-Z EDE-MM-83 Electrical Penetration HO7 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A CAH-AC-FU 15A Fuses AC6 CB-F-1A-A CAH-CS-5664-1 Control Switch with Indication F36 CB-F-3A-A EPS-HR2-PR1, RA, RMO, SR3 Emergency Power Sequencer Relays HR2 CB-F-1A-A CAH-FB7-K610A SI Actuating Auxiliary Relay FB7 CB-F-3A-A CAH-ZL-5664-1 Outlet Damper Position Lights F36 CB-F-3A-A CC-FISL-2223 Flow Indication Switch SD5 C-F-2-Z E45-E4E E4E-H36/4 H36-SD5/1 H36-SD6/1 E45-E4H E4H-H35 H35-SD3 301895 E45/11a E45/11C EDE-MCC-531 CC-E4E-FU39 30A Fuse E4E ET-F-1A-A EDE-MM-112 Electrical Penetration H36 ET-F-1A-A, C-F-2-Z CAH-E45/11-52 120 V AC Circuit Breaker E45 CB-F-1A-A CC-FISL-2224 Flow Indication Switch SD6 C-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -7 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 CAH-FN-1E (Continued) Containment Structure Cooler AC-1E Fan EDE-MM-111 Electrical Penetratio n H35 ET-F-1A-A, C-F-2-Z CC-FISL-2124 Flow Indication Switch SD3 C-F-2-Z CC-E4H-FU20 30A Fuse E4H CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.9 -8 FUNCTION: CONTAINMENT BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 CAH-FN-1F Containment Structure Cooler AC-1F Fan MAH-20505 A 310578 C-F-2-Z X X - M24 CAH-AC7-52 480 V AC Circuit Breaker AC7 CB-F-1A-A AC7-G2H AC7-G2H/1 AC7-GN9 AC7-HO7 G2H-H07/1 G2H-H36/2 G2H-H36/3 HO7-M24 HO7-M24/1 H36-M24/1 H36-SD6 F36-FB7/6 F36-G2H/6 F36-G2H/7 F36-G2H/8 G2H-HR2/2 G2H-HR2/3 310931 AC7a AC7d AC7b CBA-FN-19 CBA-FN-20 EDE-US-53 Primary Component Cooling Water CAH-FN-1A CAH-FN-1B CAH-FN-1D CAH-CS-5665-2 Control Switch with Indication G2H CB-F-1A-A CAH-SS-5665 Selector Switch G2H CB-F-1A-A EDE-AF3-94-4 Bus Undervoltage Relay AF3 CB-F-1A-A CAH-GN9-R1 Time Delay Relay GN9 CB-F-1A-A CC-FISL-2224 Flow Indication Switch SD6 C-F-2-Z CAH-AC7-52H-1 Truck Operated Contact AC7 CB-F-1A-A CAH-AC7-G,R Indicating Lights AC7 CB-F-1A-A CAH-AC7-AM Ammeter AC7 CB-F-1A-A CAH-AC7-CT Current Transformer (300/5) AC7 CB-F-1A-A CAH-AC7-ATR Transducer AC7 CB-F-1A-A CAH-ZL-5665-2 Outlet Damper Position Lights G2H CB-F-1A-A CAH-DP-317 Outlet Damper Position Switch M24 C-F-2-Z EDE-MM-83 Electrical Penetration HO7 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A CAH-AC7-FU 15A Fuses AC7 CB-F-1A-A CAH-CS-5665-1 Control Switch with Indication F36 CB-F-3A-A EPS-HR2-PR1, RA, RMO, SR3 Emergency Power Sequencer Relays HR2 CB-F-1A-A CAH-FB7-K610A SI Actuating Auxiliary Relay FB7 CB-F-3A-A CAH-ZL-5665-1 Outlet Damper Position Lights F36 CB-F-3A-A CC-FISL-2224 Flow Indication Switch SD6 C-F-2-Z H36-SD6/1 E45-E4E E4E-H36/4 H36-SD5/1 E45-E4H E4H-H35 H35-SD3 310895 E45/11a E45/11c EDE-MCC-531 CC-E4E-FU39 30A Fuse E4E ET-F-1A-A EDE-MM-112 Electrical Penetration H36 ET-F-1A-A, C-F-2-Z CAH-E45/11-52 120 V AC Circuit Breaker E45 CB-F-1A-A CC-FISL-2223 Flow Indication Switch SD5 C-F-2-Z EDE-MM-111 Electrical Penetration H35 ET-F-1A-A, C-F-2-Z CC-FISL-2124 Flow Indication Switch SD3 C-F-2-Z CC-E4H-FU20 30A Fuse E4H CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.10-1 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CBA-DP-24A CBA-20303 A 310443 CB-F-2B-A X X X X V1A CBA-FY-5550A Pilot Solenoid V1A CB-F-2B-A Instrument Air CBA-DP-24F Note 4 Mechanical Room

"A" Outside Air

Damper FP-R1 Signal Actuating Output Relay G3C TB-F-2-Z 310926 BK4a BK4c FP-CP-558 Fire Protection Control Panel G4P TB-F-2-Z G4P-V1A G4P-V1B G4P-V1C G3C-G4P/5 CBA-TIC-5571 Temperature Indicating Control

(Pneumatic) - CB-F-2B-A CBA-FY-5550B Pilot Solenoid V1B CB-F-2B-A CBA-FY-5550C Pilot Solenoid V1C CB-F-2B-A 2 CBA-DP-24B CBA-20303 A 310443 CB-F-2B-A X X X X V1B CBA-FY-5550B Pilot Solenoid V1B CB-F-2B-A BK4a BK4c Instrument Air CBA-DP-24E Note 4 Mechanical Room

"A" Recirculating

Air Damper FP-CP-558 Fire Protection Control Panel G4P TB-F-2-Z G4P-V1A G4P-V1B G4P-V1C G3C-G4P/5 FP-R1 Signal Actuating Output Relay G3C TB-F-2-Z CBA-TIC-5571 Temperature Indicatin g Controller (Pneumatic) - CB-F-2B-A CBA-FY-5550A Pilot Solenoid V1A CB-F-2B-A CBA-FY-5550C Pilot Solenoid V1C CB-F-2B-A 3 CBA-DP-24C CBA-20303 A 310443 CB-F-2B-A X X X X V1C CBA-FY-5550C Pilot Solenoid V1C CB-F-2B-A 310926 BK4a BK4c Instrument Air CB-DP-24D Note 4 Mechanical Room

"A" Return Air

Damper FP-CP-558 Fire Protection Control Panel G4P TB-F-2-Z G4P-V1A G4P-V1B G4P-V1C G3C-G4P/5 FP-R1 Signal Actuating Output Relay G3c TB-F-2-Z CBA-TIC-5571 Temperature Indicatin g Controller (Pneumatic) - CB-F-2B-A CBA-FY-5550A Pilot Solenoid V1A CB-F-2B-A CBA-FY-5550B Pilot Solenoid V1C CB-F-2B-A 4 CBA-DP-24D Mechanical Room "B" Return Air

Damper CBA-20303 B 310443 604094 CB-F-2C-A X X - X - CBA-TIC-5572 Temperature Indicating Controller

(Pneumatic) - CB-F-2C-A - - - Instrument Air CBA-DP-24C Notes 1,2,4 5 CBA-DP-24E Mechanical Room "B" Recirculating

Air CBA-20303 B 310443 604094 CB-F-2C-A X X - X - CBA-TIC-5572 Temperature Indicatin g Controller (Pneumatic) - CB-F-2C-A - - - Instrument Air CBA-DP-24B Notes 1,2,4 6 CBA-DP-24F Mechanical Room "B" Outside Air

Damper CBA-20303 B 310443 604094 CB-F-2C-A X X - X - CBA-TIC-5572 Temperature Indicatin g Controller (Pneumatic) - CB-F-2C-A - - - Instrument Air CBA-DP-24A Notes 1,2,4

.Notes 1. Equipment is mechanical with no electrical requirements. 
2. Electrical conduit Plan Drawing 310443, listed only to show fire zone correlation reference to control building area covered by HVAC Drawing 604094 where CBA Dampers 24 D, E, and F are identified in plan.
3. Air is not required for support as damper fails open.
4. Process connections showing positioning of air operated dampers, DP-24A-F, by pneumatic temperature indicating controllers, CBA-TIC-5571 and 5572, are detailed on I&C Loop Diagrams 506159 and 506160.
5. Air is not required for support as damper fails closed.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.10-2 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 CBA-FN-19 CBA-20303 A 310443 CB-F-2B-A X X X - N28 CBA-BL6-52 460 V ac Circuit Breaker BL6 CB-F-1A-A BL6-HR2/1 BL6-N28/2 BL6a BL6c EDE-MCC-515 CBA-FN Control Building

Train "A" SWGR

Supply Fan CBA-CS-5552 Control Switch with Indication BL6 CB-F-1A-A DG-HR2-HR9X EPS Step Loading Relay HR2 CB-F-1A-A DG-HR2-RMO EPS Manual Override Relay HR2 CB-F-1A-A CBA-BL6-42 Motor Starter BL6 CB-F-1A-A CBA-BL6-42X Motor Starter Auxiliary Relay BL6 CB-F-1A-A CBA-BL6-49 Overload Relays BL6 CB-F-1A-A CBA-BL6-FU Fuse BL6 CB-F-1A-A 8 CBA-FN-20 CBA-20303 A 310443 CB-F-2B-A X X X - N30 CBA-BL7-52 460 V ac Circuit Breaker BL7 CB-F-1A-A BL7-HR2 BL7-N30/2 BL7a BL7c EDE-MCC-521 CBA-FN Control Building

Train "A" SWGR

Return Fan DG-HR2-RMO EPS Manual Override Relay HR2 CB-F-1A-A CBA-BL7-42 Motor Starter BL7 CB-F-1A-A CBA-BL7-49 Overload Relays BL7 CB-F-1A-A CBA-BL7-FU Fuse BL7 CB-F-1A-A CBA-CS-5554 Control Switch with Indication BL7 CB-F-1A-A DG-HR2-HR9X EPS Step Loading Relay HR2 CB-F-1A-A CBA-BL7-42X Motor Starter Auxiliary Relay BL7 CB-F-1A-A 9 CBA-FN-21A CBA-20303 A 310443 CB-F-2B-A X X X - N32 CBA-BL8-52 460 V ac Circuit Breaker BL8 CB-F-1A-A BL8a BL8c EDE-MCC-521 CBA-FN-21B Control Building

Battery Room

Exhaust Fan "A" CBA-CS-5556 Control Switch with Indication BL8 CB-F-1A-A BL8-N32 BL8-VV5/1 BL8-VV5 CBA-ZS-DP-21A Damper Position Switch VV5 CB-F-2B-A CBA-BL8-42 Motor Starter BL8 CB-F-1A-A CBA-ZL-5556 Damper 21A Indicatin g Lights BL8 CB-F-1A-A CBA-BL8-49 Overload Relays BL8 CB-F-1A-A CBA-DP-21A-20 Pilot Solenoid VV5 CB-F-2B-A CBA-BL8-FU Fuse BL8 CB-F-1A-A 10 CBA-DP-21A Battery Room Exhaust Fan "A"

Damper CBA-20303 A 310443 CB-F-2B-A X X X X VV5 CBA-BL8-52 460 V ac Circuit Breaker BL8 CB-F-1A-A BL8-VV5 BL8-VV5/1 BL8a BL8c EDE-MCC-521 CBA-DP-21B Note 3 CBA-BL8-FU Fuse BL8 CB-F-1A-A CBA-CS-5556 Control Switch with Indication BL8 CB-F-1A-A CBA-DP-21A-20 Pilot Solenoid VV5 CB-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.10-3 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 CBA-FN-21B Control Building Battery Room

Exhaust Fan "B" CBA-20303 B 310443 CB-F-2C-A X X X - N33 CBA-BL5-52 460 V ac Circuit Breaker BL5 CB-F-1B-A BL5-N33 BL5-VV4/1 BL5-VV4 310926 BL5a BL5c EDE-MCC-621 CBA-FN-21A CBA-CS-5557 Control Switch with Indication BL5 CB-F-1B-A CBA-ZS-DP-21B Damper Position Switch VV4 CB-F-2C-A CBA-BL5-42 Motor Starter BL5 CB-F-1B-A CBA-ZL-5557 Damper 21B Indicatin g Lights BL5 CB-F-1B-A CBA-BL5-49 Overload Relays BL5 CB-F-1B-A CBA-DP-21B-20 Pilot Solenoid VV4 CB-F-2C-A CBA-BL5-FU Fuse BL5 CB-F-1B-A 12 CBA-DP-21B CBA-20303 B 310443 CB-F-2C-A X X X X VV4 CBA-BL5-52 460 V ac Circuit Breaker BL5 CB-F-1B-A BL5-VV4 BL5-VV4/1 310926 BL5a BL5c EDE-MCC-621 CBA-DP-21A Note 3 Battery Room Exhaust Fan "B"

Damper CBA-BL5-FU Fuse BL5 CB-F-1B-A CBA-CS-5557 Control Switch BL5 CB-F-1B-A CBA-DP-21B-20 Pilot Solenoid VV4 CB-F-2C-A 13 CBA-FN-32 CBA-20303 B 310443 CB-F-2C-A X X X - NH3 CBA-BL3-52 460 V ac Circuit Breaker BL3 CB-F-1B-A BL3-HR4 BL3-NH3 BL3a BL3c EDE-MCC-621 CBA-FN-19 Control Building

Train "B" SWGR

Supply Fan CBA-CS-5559 Control Switch with Indication BL3 CB-F-1B-A DG-HR4-HR9X EPS Step Loading Relay HR4 CB-F-1B-A DG-HR4-RMO EPS Manual Override Relay HR4 CB-F-1B-A CBA-BL3-42 Motor Starter BL3 CB-F-1B-A CBA-BL3-42X Motor Starter Auxiliary Relay BL3 CB-F-1B-A CBA-BL3-49 Overload Relays BL3 CB-F-1B-A CBA-BL3-FU Fuse BL3 CB-F-1B-A 14 CBA-FN-33 CBA-20303 B 310443 CB-F-2C-A X X X - NH5 CBA-BL4-52 460 V ac Circuit Breaker BL4 CB-F-1B-A BL4-HR4 BL4-NH5 BL4a BL4c EDE-MCC-621 CBA-FN-20 Control Building

Train "B" SWGR

Return Fan CBA-CS-5561 Control Switch with Indication BL4 CB-F-1B-A DG-HR4-HR9X EPS Step Loading Relay HR4 CB-F-1B-A CBA-BL4-42 Motor Starter BL4 CB-F-1B-A CBA-BL4-49 Overload Relays BL4 CB-F-1B-A CBA-BL4-FU Fuse BL4 CB-F-1B-A DG-HR4-RMO EPS Manual Override Relay HR4 CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.10-4 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 CBA-CP-177 CBA-20303 CBA-20304 A 310444 CB-F-3B-A X X X - GU1 CBA-AC4-52 460V ac Circuit Breaker AC4 CB-F-1A-A EDE-US-52 Instrument Air CBA-CP-178 Control Room A/C

Unit A Control

Panel CBA-FN-14A AC Unit Fan N21 CB-F-3B-A CBA-FN-211A Condenser Exhaust Fan NN1 DG-F-3A-Z 310926 AC4a AC4b AC4e AC4f CBA-PDS-21206A1/A2 FN-211A Diff Pressure PV1 DG-F-3A-Z X CBA-DP-26A Damper UG1 CB-F-3B-A CBA-CS-5300-1 FN-14A Control Switch F36 CB-F-3A-A AC4-GU1 AC4-HR2 GU1-N21 GU1-N21/1 GU1-NN1 GU1-NN1/1 GU1-PV1 GU1-UG1 F38-GU1 F38-GU1/1 CBA-CS-21222A FN-211A Control Switch F36 CB-F-3A-A CBA-AC4-FU Breaker Fuse AC4 CB-F-1A-A CBA-AC4-52H Breaker Truck Switch AC4 CB-F-1A-A CBA-CS-5300-3 Breaker Control

Switch AC3 CB-F-1A-A DG-HR2-RMO, PR1, LR1 Sequencer Relays HR2 CB-F-1A-A GU1-HR2 DG-HR9 - SR5 Sequencer Relay HR9 CB-F-1A-A EDE-AC3-94-3 Undervoltage Relay AC3 CB-F-1A-A CBA-E-230A Chiller HW4 DG-F-3A-Z AC4ma AC4me CBA-PDS-21202A Evaporator Diff Pressure PK8 DG-F-3A-Z CBA-ZL-21221A Chiller Indication F36 CB-F-3A-A GU1-HW4 GU1-HW4/1 GU1-HW4/2 GU1-HW4/3 GU1-HW4/4 B6B-HW4 B6C-HW4 HW4-PK8 HW4-PK9 CBA-TCV-21200A Chilled Water TCV LV1 CB-F-3B-A AC4na AC4nc CBA-TC-21200A Chilled Water Temp

Cont. T0L CB-F-3A-A GU1-LV1 LV1-T0L CBA-B6B-52 460V ac Circuit Breaker B6B CB-F-1A-A B6B-NM5 B6Ba B6Bc B6Ca B6Cc CBA-B6B-FU Fuse B6B CB-F-1A-A CBA-SS-21220A Selector Switch HW4 CB-F-1A-A CBA-6K13 Signal Relay HW4 CB-F-1A-A CBA-B6B-42 Motor Starter B6B CB-F-1A-A CBA-B6B-49 Overload Relays B6B CB-F-1A-A CBA-B6C-52 460V ac Circuit Breaker B6C CB-F-1A-A B6C-NM6 CBA-B6C-FU Fuse B6C CB-F-1A-A CBA-B6C-42 Motor Starter B6C CB-F-1A-A CBA-B6C-49 Overload Relays B6C CB-F-1A-A CBA-P-434A Chiller Circ. Water Pump NM5 DG-F-3A-Z CBA-P-435A Chiller Circ. Water Pump NM6 DG-F-3A-Z

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.10-5 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 16 CBA-CP-178 CBA-20303 CBA-20304 B 310444 CB-F-3B-A X X X - GU2 CBA-AE4-52 460V ac Circuit

Breaker AE4 CB-F-1B-A EDE-US-62 Instrument Air CBA-CP-177 Control Room A/C

Unit B Control

Panel CBA-FN-14B AC Unit Fan N22 CB-F-3B-A 310926 AE4a AE4b AE4e AE4f CBA-FN-211B Condenser Exhaust Fan NN3 DG-F-3B-Z CBA-PDS-21206B1/B2 FN-211B Diff Pressure PV0 DG-F-3B-Z X CBA-DP-26B Damper UG2 CB-F-3B-A CBA-CS-5301-1 FN-14B Control Switch F37 CB-F-3A-A AE4-GU2 AE4-HR4 GU2-N22 GU2-N22/1 GU2-NN3 GU2-NN3/1 GU2-PV0 GU2-UG2 F37-GU2 F37-GU2/1 CBA-CS-21222B FN-211B Control Switch F37 CB-F-3A-A CBA-AE4-FU Breaker Fuse AE4 CB-F-1B-A CBA-AE4-52H Breaker Truck Switch AE4 CB-F-1B-A CBA-CS-5301-3 Breaker Control

Switch AE3 CB-F-1B-A DG-HR4-RMO,PR1,LR1 Sequencer Relays HR4 CB-F-1B-A GU2-HR4 DG-HR0 - SR5 Sequencer Relay HR0 CB-F-1B-A EDE-AE3-94-3 Undervoltage Relay AE3 CB-F-1B-A CBA-E-230B Chiller HW5 DG-F-3B-Z AE4ma AE4me CBA-PDS-21202B Evaporator Diff

Pressure PL0 DG-F-3B-Z CBA-ZL-21221B Chiller Indication F37 CB-F-3A-A GU2-HW5 GU2-HW5/1 GU2-HW5/2 GU2-HW5/3 GU2-HW5/4 B6H-HW5 B6I-HW5 HW5-PL0 HW5-PL5 CBA-TCV-21200B Chilled Water TCV LV2 CB-F-3B-A GU2-LV2 LV2-T0N AE4na AE4nc CBA-TC-21200B Chilled Water Temp

Cont. T0N CB-F-3A-A CBA-B6H-52 460V ac Circuit

Breaker B6H CB-F-1B-A B6H-NM7 B6Ha B6Hc B6Ia B6Ic CBA-B6H-FU Fuse B6H CB-F-1B-A CBA-SS-21220B Selector Switch HW5 CB-F-1B-A CBA-6K13 Signal Relay HW5 CB-F-1B-A CBA-B6H-42 Motor Starter B6H CB-F-1B-A CBA-B6H-49 Overload Relays B6H CB-F-1B-A CBA-B6I-52 460V ac Circuit Breaker B6I CB-F-1B-A B6I-NM8 CBA-B6I-FU Fuse B6I CB-F-1B-A CBA-B6I-42 Motor Starter B6I CB-F-1B-A CBA-B6I-49 Overload Relays B6I CB-F-1B-A CBA-P-434B Chiller Circ. Water Pump NM7 DG-F-3B-Z CBA-P-435B Chiller Circ. Water Pump NM8 DG-F-3B-Z 17 CBA-DP-52 CBA-20304 A 310444 CB-F-3B-A X X X X UH2 CBA-CS-5302 Control Switch F36 CB-F-3A-A Note 5 Control Building

Recirculation Air

Damper CBA-PDSH-5305 Pressure Differential Switch P64 CB-F-3B-A E16/29a E16/29c E16/29e E16/29d E16/29g E16/29h CBA-PDSH-5306 Pressure Differential Switch P65 CB-F-3B-A GN8-P64 GN8-UH2 F36-GN8 GN8-P65 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.11 -1 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 DAH-FN-25A DG-1A Room Supply Air Fan DAH-20624 A 310525 DG-F-3A-Z X X X - N37 DAH-B01-52 460 V AC Circuit Breaker B01 CB-F-1A-A B01-N37/1 B01-G29 B01-J1E B01-GN9 310928 B01a B01c B01d EDE-MCC-521 EDE-PP-11E DAH-FN-25B DAH-CS-5529 Control Switch with Fan Indicating Lights B01 CB-F-1A-A DAH-FISH-5529 Flow Switch S40 DG-F-3A-Z DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DAH-ED1-R2 Auxiliary Relay ED1 CB-F-1A-A DG-G29-HSR DG-1A High Speed Relay G29 DG-F-2A-A DAH-B01-42 Motor Starter B01 CB-F-1A-A DAH-B01-42X Motor Starter Auxiliary Relay B01 CB-F-1A-A DAH-B01-49 Overload Relays B01 CB-F-1A-A DAH-B01-FU Fuse B01 CB-F-1A-A DAH-EDI-RI Control Circuit Power Monitor Auxiliary Relay EDI CB-F-1A-A DAH-GN9-RS EPS Permissive Auxiliary Relay GN9 CB-F-1A-A DAH-GN9-RD Damper Position Auxiliary Relay GN9 CB-F-1A-A DAH-E3E/7-52 120 V AC Circuit Breaker E3E CB-F-1A-A J1E-T3P (Non CASP) E3E-J1E E3E/7a E3E/7b EDE-MCC-515 EDE-PP-E3E DAH-TB-5529-1 Temperature Bistable J1E DG-F-2A-A DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DAH-TE-5529-1 Temperature Element T3P DG-F-2A-A DAH-TT-5529-1 Temperature Transmitter J1E DG-F-2A-A DAH-CP-295 DG-A Room Air Handling Fans and Damper Control Panel J1E DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.11 -2 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 DAH-DP-16A DG-1A Room Return Air Damper DAH-20624 A 310524 DG-F-2A-A X X X X UF9 DAH-ED1-R2 (B01 & B03) Auxiliary Relays ED1 CB-F-1A-A B01-UF9/1 B01-J1E/1 EIS-GN9 EDI-GN9 B03-UF9 B01-HR2 EIS/6a EIS/6c EDE-MCC-521 EDE-PP-11E DAH-DP-16B Note 1 DAH-DP-16A-20 Pilot Solenoi d UF9 DG-F-2A-A DAH-TB-5529-1 Temperature Bistable J1E DG-F-2A-A DAH-ZS-DP-16A Damper 16A Position Switch UF9 DG-F-2A-A DG-HR2-PR1 EPS Permissive Auxiliary Relay HR2 CB-F-1A-A DG-HR2-HR8 EPS Permissive Auxiliary Relay HR2 CB-F-1A-A DG-HR2-SR1 EPS Permissive Auxiliary Relay HR2 CB-F-1A-A DAH-GN9-RS EPS Permissive Auxiliary Relay GN9 CB-F-1A-A DAH-GN9-RD Damper Position Auxiliary Relay GN9 CB-F-1A-A DAH-E1S/6-52 120 V AC Circuit Breaker E1S CB-F-1A-A DAH-ZL-5529-4 Damper Position Indicating Lights B03 CB-F-1A-A DAH-E3E/7-52 120 V AC Circuit Breaker E3E CB-F-1A-A J1E-T3P (Non CASP) E3E-J1E E3E/7a E3E/7b EDE-MCC-515 EDE-PP-E3E DAH-TB-5529-1 Temperature Bistable J1E DG-F-2A-A DAH-TE-5529-1 Temperature Element T3P DG-F-2A-A DAH-TT-5529-1 Temperature Transmitter J1E DG-F-2A-A DAH-CP-295 DG-A Room Air Handling Fans And Damper Control Panel J1E DG-F-2A-A Notes: 1. Air is not required for support as damper is open

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.11 -3 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 DAH-FN-25B DG-1B Room Supply Air Fan DAH-20624 B 310525 DG-F-3B-Z X X X - N38 DAH-B02-52 460 V AC Circuit Breaker B02 CB-F-1B-A B02-N38/1 B02-G30 B02-S41 B02-J1F B02-GN0 EE3-E3D 310928 B02a B02c B02d EDE-MCC-621 EDE-PP-11F DAH-FN-25A DAH-CS-5530 Control Switch with Fan Indicating Lights B02 CB-F-1B-A DAH-FISH-5530 Flow Switch S41 DG-F-3B-Z DAH-J1F-RTB Temperature Bistable Auxiliary Relay J1F DG-F-2B-A DAH-EE3-R2 Auxiliary Relay EE3 CB-F-1B-A DAH-B02-FU Fuse B02 CB-F-1B-A DG-G30-HSR DG-1B High Speed Relay G30 DG-F-2B-A DAH-B02-42 Motor Starter B02 CB-F-1B-A DAH-B02-42X Motor Starter Auxiliary Relay B02 CB-F-1B-A DAH-B02-49 Overload Relays B02 CB-F-1B-A DAH-E3D-R1 Control Circuit Power Monitor Auxiliary Relay E3D CB-F-1B-A DAH-GN0-RS EPS Permissive Auxiliary Relay GN0 CB-F-1B-A DAH-GN0-RD Damper Position Auxiliary Relay GN0 CB-F-1B-A DAH-E3F/7-52 120 V AC Circuit Breaker E3F CB-F-1B-A J1F-T3Q (Non CASP) E3F-J1F E3F/7a E3F/7b EDE-MCC-615 EDE-PP-E3F DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A DAH-J1F-RTB Temperature Bistable Auxiliary Relay J1F DG-F-2B-A DAH-TE-5530-1 Temperature Element T3Q DG-F-2B-A DAH-TT-5530-1 Temperature Transmitter J1F DG-F-2B-A DAH-CP-296 DG-B Room Air Handling Fans and Damper Control Panel J1F DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.11 -4 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 DAH-DP-16B DG-1B Room Return Air Damper DAH-20624 B 310524 DG-F-2B-A X X X X UF0 DAH-EE3-R2 (B02 & B04) Auxiliary Relay EE3 CB-F-1B-A B02-UF0/1 ED0-J1F B02-EDO EE3-GN0/2 EIT-GN0 B01-HR4 B04-UF0 EIT/6a EIT/6c EDE-MCC-621 EDE-PP-11F DAH-DP-16A Note 1 DAH-DP-16B-20 Pilot Solenoid UF0 DG-F-2B-A DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A DAH-ZS-DP-16B Damper 16B Position Switch UF0 DG-F-2B-A DG-HR4-HRB EPS Permissive Auxiliary Relay HR4 CB-F-1B-A DG-HR4-PR1 EPS Permissive Auxiliary Relay HR4 CB-F-1B-A DG-HR4-SR1 EPS Permissive Auxiliary Relay HR4 CB-F-1B-A DAH-GN0-RS EPS Permissive Auxiliary Relay GN0 CB-F-1B-A DAH-GN0-RD Damper Position Auxiliary Relay GN0 CB-F-1B-A DAH-E1T/6-52 120 V AC Circuit Breaker E1T CB-F-1B-A DAH-ZL-5530-4 Damper Position Indicating Lights B04 CB-F-1B-A DAH-E3F/7-52 120 V AC Circuit Breaker E3F CB-F-1B-A J1F-T3Q (Non CASP) E3F-J1F E3F/7a E3F/7b EDE-MCC-615 EDE-PP-E3F DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A DAH-TE-5530-1 Temperature Element T3Q DG-F-2B-A DAH-TT-5530-1 Temperature Transmitter J1F DG-F-2B-A DAH-CP-296 DG-B Room Air Handling Fans and Damper Control Panel J1F DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.11 -5 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 DAH-FN-26A DG-1A Room Return Air Fan DAH-20624 A 310525 DG-F-2A-A X X X - N39 DAH-B03-52 460 V AC Circuit Breaker B03 CB-F-1A-A B03-N39/1 B03-J1E G29-J1E B03-GN9 310928 B03a B03c B03d EDE-MCC-521 EDE-PP-11E DAH-FN-26B DAH-B03-42 Motor Starter B03 CB-F-1A-A DAH-B03-42X Motor Starter Auxiliary Relays B03 CB-F-1A-A DAH-B03-49 Overload Relays B03 CB-F-1A-A DAH-B03-FU Fuse B03 CB-F-1A-A DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DG-G29-HSR DG-1A High Speed Relay G29 DG-F-2A-A DAH-CS-6058 Control Switch with Indicating Lights B03 CB-F-1A-A DAH-ED1-R2 Auxiliary Relay ED1 CB-F-1A-A DAH-ED1-R1 Control Circuit Power Monitor Auxiliary Relay ED1 CB-F-1A-A DAH-GN9-RS EPS Permissive Auxiliary Relay GN9 CB-F-1A-A DAH-GN9-RD Damper Position Auxiliary Relay GN9 CB-F-1A-A DAH-E3E/7-52 120 V DC Circuit Breaker E3E CB-F-1A-A J1E-T3P (Non CASP) E3E-J1E E3E/7a E3E/7b EDE-MCC-515 EDE-PP-E3E DAH-TB-5229-1 Temperature Bistable J1E DG-F-2A-A DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DAH-TE-5529-1 Temperature Element T3P DG-F-2A-A DAH-TT-5529-1 Temperature Transmitter J1E DG-F-2A-A DAH-CP-295 DG-A Room Air Handling Fans and Damper Control Panel J1E DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.11 -6 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 DAH-FN-26B DG-1B Room Return Air Fan DAH-20624 B 310525 DG-F-2B-A X X X - N40 DAH-B04-52 460 V AC Circuit Breaker B04 CB-F-1B-A B04-N40/1 B04-J1F G30-J1F B04-GN0 B04a B04c B04d EDE-MCC-621 EDE-PP-11F DAH-FN-26A DAH-B04-42 Motor Starter B04 CB-F-1B-A DAH-B04-42X Motor Starter Auxiliary Relays B04 CB-F-1B-A DAH-B04-49 Overload Relays B04 CB-F-1B-A DAH-B04-FU Fuse B04 CB-F-1B-A DAH-J1F-RTB Temperature Bistable Auxiliary Relay J1F DG-F-2B-A DG-G30-HSR DG-1B High Speed Relay G30 DG-F-2B-A DAH-CS-6059 Control Switch with Indicating Lights B04 CB-F-1B-A DAH-EE3-R2 Auxiliary Relay EE3 CB-F-1B-A DAH-EE3-R1 Control Circuit Power Monitor Auxiliary Relay EE3 CB-F-1B-A DAH-GN0-RS EPS Permissive Auxiliary Relay GN0 CB-F-1B-A DAH-GN0-RD Damper Position Auxiliary Relay GNO CB-F-1B-A DAH-E3F/7-52 120 V AC Circuit Breaker E3F CB-F-1B-A J1F-T3Q (Non CASP) E3F-J1F E3F/7a E3F/7b EDE-MCC-615 EDE-PP-E3F DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A DAH-J1F-RTB Temperature Bistable Auxiliary Relay J1F DG-F-2B-A DAH-TE-5530-1 Temperature Element T3Q DG-F-2B-A DAH-TT-5530-1 Temperature Transmitter J1F DG-F-2B-A DAH-CP-296 DG-B Room Air Handling Fans and Damper Control Panel J1F DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.12-1 FUNCTION: CONTAINMENT ENCLOSURE AIR HANDLING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EAH-FN-5A MAH-20495 A 310766 CE-F-1-Z X X X - M80 EAH-AF5-52 480 V AC Circuit Breaker AF5 CB-F-1A-A EAH-FN-5B Containment

Enclosure Cooler

AC-2A Fan EAH-AF5-G, R Indicating Lights AF5 CB-F-1A-A EAH-CS-5767-2 Control Switch with Indication G2H CB-F-1A-A 310932 AF5a AF5e AF5b AF5g AF5f EAH-FN-31A EDE-US-52 Primary Component Cooling Water EAH-SS-5767 Selector Switch G2H CB-F-1A-A EAH-ZL-5767-2 Outlet Damper Position Lights G2H CB-F-1A-A AF5-G2H AF5-G2H/1 AF5/M80 AF5-YC3 L41-YC3 F36-G2H F36-G2H/1 AF5-HR2 AF5-E3C EAH-ZS-DP-3A Damper Position Switch L41 CE-F-1-Z EAH-AF5-AM Ammeter AF5 CB-F-1A-A EAH-AF5-CT Current Transformer (200/5) AF5 CB-F-1A-A EDE-AC3-94-3 Bus Undervoltage Relay AC3 CB-F-1A-A EAH-AF5-52H-1 Truck-Operated Contact AF5 CB-F-1A-A EDE-TBX-YC3 Terminal Box YC3 CE-F-1-Z EAH-AF5-FU Fuses AF5 CB-F-1A-A EAH-CS-5767-1 Control Switch with Indication F36 CB-F-3A-A DG-HR2-SR1 EPS Permit Auxiliary Relay HR2 CB-F-1A-A DG-HR2-PR1 EPS Permit Auxiliary Relay HR2 CB-F-1A-A DG-HR2-RMO EPS Permit Auxiliary Relay Pressure Switch HR2 CB-F-1A-A EAH-ZL-5767-1 Outlet Damper Position Lights F36 CB-F-3A-A EAH-E3C-R1 Auxiliary Relay E3C CB-F-1A-A

. Notes 1. Equipment is mechanical with no electrical requirements. 
2. Air and electrical power are not required for support as damper fails closed.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.12-2 FUNCTION: CONTAINMENT ENCLOSURE AIR HANDLING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 EAH-FN-5B MAH-20495 B 310766 CE-F-1-Z X X X - M81 EAH-AF9-52 480 V AC Circuit Breaker AF9 CB-F-1B-A EAH-FN-5A Containment

Enclosure Cooler

AC-2B Fan EAH-AF9-G, R Indicating Lights AF9 CB-F-1B-A EAH-CS-5768-2 Control Switch with Indication G2K CB-F-1B-A AF9a AF9e AF9b AF9g AF9f EAH-FN-31B EDE-US-62 Primary Component Cooling Water EAH-SS-5768 Selector Switch G2K CB-F-1B-A EAH-ZL-5768-2 Outlet Damper Position Lights G2K CB-F-1B-A AF9-G2K AF9-G2K/1 AF9/M81 AF9-YB3 L42-YB3 F37-G2K F37-G2K/1 AF9-HR4 AF9-G2K/2 AF9-E3D EAH-ZS-DP-3B Damper Position Switch L42 CE-F-1-Z EAH-AF9-AM Ammeter AF9 CB-F-1B-A EAH-AF9-CT Current Transformer (200/5) AF9 CB-F-1B-A EDE-AE3-94-3 Bus Undervoltage Relay AE3 CB-F-1B-A EAH-AF9-52H-1 Truck-Operated Contact AF9 CB-F-1B-A EDE-TBX-YB3 Terminal Box YB3 CE-F-1-Z EAH-AF9-FU Fuses AF9 CB-F-1B-A EAH-CS-5768-1 Control Switch with Indication F37 CB-F-3A-A DG-HR4-SR1 EPS Permit Auxiliary Relay HR4 CB-F-1B-A DG-HR4-PR1 EPS Permit Auxiliary Relay HR4 CB-F-1B-A DG-HR4-RMO EPS Permit Auxiliary Relay Pressure Switch HR4 CB-F-1B-A EAH-ZL-5768-1 Outlet Damper Position Lights F37 CB-F-3A-A EAH-AE3-R1 Auxiliary Relay AE3 CB-F-1B-A EAH-E3D-R2 Auxiliary Relay E3D CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.12-3 FUNCTION: CONTAINMENT ENCLOSURE AIR HANDLING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 EAH-FN-31A MAH-20495 A 310765 CE-F-1-Z - X X - ND5 EAH-BB2-52 460 V Ac Circuit Breaker BB2 CB-F-1A-A EDE-MCC-512 EAH-FN-31B Containment

Enclosure Return

Fan "A" EAH-BB2-FU Fuses BB2 CB-F-1A-A 310932 BB2a BB2c EAH-CS-5769-2 Control Switch BB2 CB-F-1A-A EAH-BB2-G, R Indication Lights BB2 CB-F-1A-A BB2-ND5 BB2-VQ2 BB2-F36 BB2-F36/1 AF5-BB2 BB2-HR2 EAH-SS-5769 Selector Switch BB2 CB-F-1A-A EAH-BB2-42 Motor Starter BB2 CB-F-1A-A EAH-BB2-42X Motor Starter Auxiliary Relay BB2 CB-F-1A-A EAH-BB2-49 Overload Relays BB2 CB-F-1A-A EAH-ZS-DP-25A Damper Position Switch VQ2 CE-F-1-Z EAH-CS-5769-1 Control Switch with Indication F36 CB-F-3A-A EAH-ZL-5769-1 Inlet Damper Position Lights F36 CB-F-3A-A DG-HR2-RMO EPS Permit Auxiliary Relay HR2 CB-F-1A-A EAH-AF5-52 480 V AC Circuit Breaker Auxiliary

Switch AF5 CB-F-1A-A 4 EAH-FN-31B MAH-20495 B 310765 CE-F-1-Z - X X - NJ7 EAH-BC1-52 460 V Ac Circuit Breaker BC1 CB-F-1B-A BC1a BC1c EDE-MCC-612 EAH-FN-31A EAH-BC1-FU Fuses BC1 CB-F-1B-A Containment

Enclosure Return

Fan "B" EAH-CS-5770-2 Control Switch BC1 CB-F-1B-A EAH-BC1-G, R Indication Lights BC1 CB-F-1B-A BC1-NJ7 BC1-VQ3 BC1-F37 BC1-F37/1 AF9-BC1 BC1-HR4 EAH-SS-5770 Selector Switch BC1 CB-F-1B-A EAH-BC1-42 Motor Starter BC1 CB-F-1B-A EAH-BC1-42X Motor Starter Auxiliary Relay BC1 CB-F-1B-A EAH-BC1-49 Overload Relays BC1 CB-F-1B-A EAH-ZS-DP-25B Damper Position Switch VQ3 CE-F-1-Z EAH-CS-5770-1 Control Switch with Indication F37 CB-F-3A-A EAH-ZL-5770-1 Inlet Damper Position Lights F37 CB-F-3A-A DG-HR4-RMO EPS Permit Auxiliary Relay HR4 CB-F-1B-A EAH-AF9-52 480 V AC Circuit Breaker Auxiliary

Switch AF9 CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.12-4 FUNCTION: CONTAINMENT ENCLOSURE AIR HANDLING . PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 EAH-DP-3A Containment Enclosure Cooler

AC-2A Damper MAH-20495 A 310766 CE-F-1-Z X X - - L41 - - - - - - -

- EAH-DP-3B Note 1 6 EAH-DP-3B Containment Enclosure Cooler 

AC-2B Damper MAH-20495 B 310766 CE-F-1-Z X X - - L42 - - - - - - -

- EAH-DP-3A Note 1 7 EAH-FN-174A MAH-20503 A 310586 MS-F-4A-Z X X X - M4T EAH-B8C-52 460 V AC Circuit Breaker B8C CB-F-1A-A B8C-M4T B8C-S5G B8Ca B8Cc EAH-FN-174B MS & FWPC 

Analyzer Room

Supply Fan EAH-B8C-FU Fuse B8C CB-F-1A-A CBA-FN-19

CBA-FN-20 EDE-MCC-515 EAH-CS-5136 Control Switch with Indication B8C CB-F-1A-A EAH-B8C-42 Motor Starter B8C CB-F-1A-A EAH-B8C-49 Overload Relays B8C CB-F-1A-A EAH-TSH-5136 Temperature Switch S5G MS-F-4A-Z 8 EAH-FN-174B MAH-20503 B 310586 MS-F-4A-Z X X X - M4U EAH-B8E-52 460 V AC Circuit Breaker B8E CB-F-1B-A B8E-M4U B8E-S5H 310932 B8Ea B8Ec EAH-FN-174A MS & FWPC

Analyzer Room

Supply Fan EAH-B8E-FU Starter B8E CB-F-1B-A EDE-MCC-615 CBA-FN-32

CBA-FN-33 EAH-B8E-49 Overload Relays B8E CB-F-1B-A EAH-CS-5763 Control Switch with Indication B8E CB-F-1B-A EAH-TSH-5763 Temperature Switch S5H MS-F-4A-Z EAH-B8E-FU Fuse B8E CB-F-1B-A 9 MAH-20495 PAH-CS-5370 Control Switch F36 CB-F-3A-A Note 2 PAH-DP-35A

PAH-DP-36A CE Outboard

Isolation Dampers A A 310766 310765 PAB-F-2A-Z PAB-F-2C-Z X X X X X X X X VN8 VN0 PAH-ZS-DP-35A Position Switch VN8 PAB-F-2A-Z F36-VN8 F36-VN0 310930 E42/8a E42/8c E42/8d PAH-ZS-DP-36A Position Switch VN0 PAB-F-2C-Z PAH-FY-DP-35A Solenoid Valve VN8 PAB-F-2A-Z PAH-FY-DP-36A Solenoid Valve VN0 PAB-F-2C-Z 10 MAH-20495 PAH-CS-5371 PAH-CS-5371 F37 CB-F-3A-A Note 2 PAH-DP-35B

PAH-DP-36B CE Inboard

Isolation Dampers B B 310766 310765 CE-F-1-Z

CE-F-1-Z X X X X X X X X VN9 VP1 PAH-ZS-DP-35B PAH-ZS-DP-35B VN9 CE-F-1-Z F37-VP1 F37-VN9 310930 E50/8a E50/8c PAH-ZS-DP-36B PAH-ZS-DP-36B VP1 CE-F-1-Z PAH-FY-DP-35B PAH-FY-DP-35B VN9 CE-F-1-Z PAH-FY-DP-36B PAH-FY-DP-36B VP1 CE-F-1-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.13-1 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EPA-FN-47A MAH-20503 A 310708 EFP-F-1-A X X X - NL8 EPA-BB7-52 460 V ac Circuit Breaker BB7 CB-F-1A-A EPA-FN-47B Emergency

Feedwater

Pumphouse Intake

Fan EPA-BB7-FU Fuse BB7 CB-F-1A-A BB7-NL8 BB7-UH3 BB7-VV6 CBA-FN-19

CBA-FN-20 EDE-MCC-512 EPA-CS-5430-2 Control Switch BB7 CB-F-1A-A 310922 BB7a BB7c BB7d EPA-ZL-5430-4 Fan Indicating Lights BB7 CB-F-1A-A EPA-SS-5430 Selector Switch BB7 CB-F-1A-A EPA-EC8-RBB7 Damper Auxiliary Relay EC8 CB-F-1A-A EPA-ZS-DP-373 Damper Position Switch UH3 EFP-F-1-A EPA-ZS-DP-371 Damper Position Switch VV6 EFP-F-1-A EPA-ZL-5430-5 Damper DP-373 Position Lights BB7 CB-F-1A-A EPA-ZL-5430-6 Damper DP-371 Position Lights BB7 CB-F-1A-A EPA-BB7-42 Motor Starter BB7 CB-F-1A-A EPA-BB7-49 Overload Relays BB7 CB-F-1A-A EPA-ZL-5430-1 Fan Indicating Lights F36 CB-F-3A-A EPA-ZL-5430-2 Damper DP-373 Position Lights F36 CB-F-3A-A F36-TU9 BB7-F36 BB7-F36/1 BB7-F36/2 EPA-ZL-5430-3 Damper DP-371 Position Lights F36 CB-F-3A-A EPA-CS-5430-1 Control Switch F36 CB-F-3A-A EPA-TSH-5430 Temperature Switch TU9 EFP-F-1-A EPA-DP-373-20 Pilot Solenoid UH3 EFP-F-1-A 2 EPA-DP-373 MAH-20503 A 310708 EFP-F-1-A X X X X UH3 EPA-DP-373-20 Fuse EC8 CB-F-1A-A BB7-UH3 EPA-DP-374 Note 1 EPA-BB7-FU Auxiliary Relay BB7 CB-F-1A-A BB7a BB7c BB7d Emergency

Feedwater

Pumphouse Exhaust

Damper EPA-EC8-RBB7 Pilot Solenoid UH3 EFP-F-1-A CBA-FN-19

CBA-FN-20 EDE-MCC-512

Notes

1. Air is not required for support as damper fails open.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.13-2 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 EPA-FN-47B MAH-20503 B 310708 EFP-F-1-A X X X - NL9 EPA-BC7-52 460 V ac Circuit Breaker BC7 CB-F-1B-A EPA-FN-47A Emergency

Feedwater

Pumphouse Intake

Fan EPA-BC7-FU Fuses BC7 CB-F-1B-A BC7-NL9 BC7-UH4 BC7-VV7 BC7a BC7c BC7d CBA-FN-32

CBA-FN-33 EDE-MCC-612 EPA-ZL-5431-4 Fan Indicating Lights BC7 CB-F-1B-A EPA-SS-5431 Selector Switch BC7 CB-F-1B-A EPA-EDO-RBC7 Damper Auxiliary Relay EDO CB-F-1B-A EPA-ZS-DP-374 Damper Position Switch UH4 EFP-F-1-A EPA-ZS-DP-372 Damper Position Switch VV7 EFP-F-1-A EPA-BC7-42 Motor Starter BC7 CB-F-1B-A EPA-BC7-49 Overload Relays BC7 CB-F-1B-A EPA-ZL-5431-5 Damper DP-374 Position Lights BC7 CB-F-1B-A EPA-EDO-R1 Auxiliary Relay EDOCB-F-1B-A EPA-ZL-5431-6 Damper DP-372 Position Lights BC7 CB-F-1B-A EPA-CS-5431-2 Control Switch BC7 CB-F-1B-A F37-TUO BC7-F37 BC7-F37/1 BC7-F37/2 EPA-BC7-CPT Control Power Transformer BC7 CB-F-1B-A EPA-ZL-5431-1 Fan Indicating Lights F37 CB-F-3A-A EPA-ZL-5431-2 Damper DP-374 Indicating Lights F37 CB-F-3A-A EPA-ZL-5431-3 Damper DP-372 Indicating Lights F37 CB-F-3A-A EPA-CS-5431-1 Control Switch F37 CB-F-3A-A EPA-TSH-5431 Temperature Switch TUO EFP-F-1-A EPA-DP-374-20 Pilot Solenoid UH4 EFP-F-1-A 4 EPA-DP-374 MAH-20503 B 310708 EFP-F-1-A X X X X UH4 EPA-BC7-FU Fuses BC7 CB-F-1B-A BC7-UH4 EPA-DP-373 Note 1 EPA-EDO-RBC7 Auxiliary Relay EDO CB-F-1B-A BC7a BC7c BC7d CBA-FN-32

CBA-FN-33 EDE-MCC-612 Emergency

Feedwater

Pumphouse Exhaust

Damper EPA-DP-374-20 Pilot Solenoid UH4 EFP-F-1-A EPA-EDO-R1 Auxiliary Relay EDO CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 10 Table MCR 3.1.3.14-1 FUNCTION: PRIMARY AUXILIARY BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 PAH-FN-42A PAB Auxiliary Supply Fan "A" MAH-20495 A 310765 PAB-F-2C-Z X X X - M61 PAH-BF6-52 460 V ac Circuit Breaker BF6 CB-F-1A-A PAH-FN-42B PAH-CS-5391-2 Control Switch BF6 CB-F-1A-A PAH-ZL-5391-4 Fan Indicating Lights BF6 CB-F-1A-A 310930 BF6a BF6c BF6d CBA-FN-19

CBA-FN-20 EDE-MCC-512 PAH-SS-5391 Selector Switch BF6 CB-F-1A-A PAH-ED1-R1 Damper Auxiliary Relay ED1 CB-F-1A-A PAH-ZS-DP-43A-1A PAH-ZS-DP-43A-1B PAH-ZS-DP-43A-2A Damper Position

Switches UG5 PAB-F-1K-Z PAH-ZS-DP-357-1 PAH-ZS-DP-357-2 Damper Position

Switches UG7 PAB-F-2C-Z PAH-BF6-42 Motor Starter BF6 CB-F-1A-A PAH-BF6-49 Overload Relays BF6 CB-F-1A-A BF6-M61 BF6-ED1 BF6-UG5 BF6-UG7 UG5-UG7 BF6-UG5/1 BF6-F36 BF6-F36/1 BF6-TY3 PAH-DP-43A-20 Pilot Solenoid UG5 PAB-F-1K-Z PAH-DP-357-20 Pilot Solenoid UG7 PAB-F-2C-Z PAH-ZL-5391-5 Damper DP-43A Position Lights BF6 CB-F-1A-A PAH-ZL-5391-6 Damper DP-357 Position Lights BF6 CB-F-1A-A PAH-BF6-FU Fuse BF6 CB-F-1A-A PAH-CS-5391-1 Control Switch F36 CB-F-3A-A PAH-ZL-5391-1 Fan Indicating Lights F36 CB-F-3A-A PAH-TSH-5391 Temperature Switch High TY3 PAB-F-2C-Z PAH-ZL-5391-2 Damper DP-43A Position Lights F36 CB-F-3A-A PAH-ZL-5391-3 Damper DP-357 Position Lights F36 CB-F-3A-A 2 PAH-DP-43A PAB Auxiliary Fan Supply Damper MAH-20495 A 310765 PAB-F-1K-Z X X X X UG5 PAH-ED1-R1 Damper Auxiliary Relay ED1 CB-F-1A-A BF6-ED1 BF6-UG5 PAH-DP-43B Note 1 PAH-DP-43A-20 Pilot Solenoid UG5 PAB-F-1K-Z BF6-UG7 UG5-UG7 BF6-UG5/1 310930 BF6a BF6c BF6d CBA-FN-19

CBA-FN-20 3 PAH-DP-357 PAB Auxiliary Fan Exhaust Damper MAH-20495 A 310766 PAB-F-2C-Z X X X X UG7 PAH-ED1-R1 Damper Auxiliary Relay ED1 CB-F-1A-A BF6-ED1 BF6-UG5 PAH-DP-358 Note 1 PAH-DP-357-20 Pilot Solenoid UG7 PAB-F-2C-Z BF6-UG7 UG5-UG7 310930 BF6a BF6c CBA-FN-19

CBA-FN-20

Notes: 1. Air and electrical power are not required for support as damper fails open.

2. See Table RSS 3.1.3.12 for operation of dampers PAH-DP-35A, -35B, -36A & -36B.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 10 Table MCR 3.1.3.14-2 FUNCTION: PRIMARY AUXILIARY BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 PAH-FN-42B PAB Auxiliary Supply Fan "B" MAH-20495 B 310765 PAB-F-2C-Z X X X - M62 PAH-BF7-52 460 V ac Circuit Breaker BF7 CB-F-1B-A 310930 BF7a BF7c CBA-FN-32

CBA-FN-33 EDE-MCC-612 PAH-FN-42A PAH-CS-5393-2 Control Switch BF7 CB-F-1B-A PAH-ZL-5393-4 Fan Indicating Lights BF7 CB-F-1B-A PAH-SS-5393 Selector Switch BF7 CB-F-1B-A PAH-EDO-R1 Damper Auxiliary Relay EDO CB-F-1B-A PAH-ZS-DP-43B-1A PAH-ZS-DP-43B-1B PAH-ZS-DP-43B-2A Damper Position

Switches UG6 PAB-F-1K-Z BF7-M62 BF7-UG6 BF7-UG8 UG6-UG8 BF7-E3D/1 BF7-F37 BF7-F37/1 BF7-TY4 PAH-ZS-DP-358 Damper Position Switch UG8 PAB-F-2C-Z PAH-ZL-5393-5 Damper DP-43B Position Lights BF7 CB-F-1B-A PAH-DP-43B-20 Pilot Solenoid UG6 PAB-F-1K-Z PAH-E3D-R2 Auxiliary Relay E3D CB-F-1B-A PAH-ZL-5393-2 Damper DP-43B Position Lights F37 CB-F-3A-A PAH-ZL-5393-3 Damper DP-358 Position Lights F37 CB-F-3A-A PAH-DP-35B-20 Pilot Solenoid UG8 PAB-F-2C-Z PAH-BF7-42 Motor Starter BF7 CB-F-1B-A PAH-BF7-49 Overload Relays BF7 CB-F-1B-A PAH-BF7-FU Fuses BF7 CB-F-1B-A PAH-ZL-5393-6 Damper DP-358 Position Lights BF7 CB-F-1B-A PAH-CS-5393-1 Control Switch F37 CB-F-3A-A PAH-ZL-5393-1 Fan indicating Lights F37 CB-F-3A-A PAH-TSH-5393 Temperature Switch High TY4 PAB-F-2C-Z 5 PAH-DP-43B PAB Auxiliary Fan Supply Damper MAH-20495 B 310765 PAB-F-1K-Z X X X X UG6 PAH-EDO-R1 Damper Auxiliary Relay EDO CB-F-1B-A BF7-UG6 BF7-UG8 PAH-DP-43A Note 1 PAH-DP-43B-20 Pilot Solenoid UG6 PAB-F-1K-Z UG6-UG8 310930 BF7a BF7c CBA-FN-32

CBA-FN-33 6 PAH-DP-358 PAB Auxiliary Fan Exhaust Damper MAH-20495 B 310766 PAB-F-2C-Z X X X X UG8 PAH-EDO-R1 Damper Auxiliary Relay EDO CB-F-1B-A BF7-UG6 BF7-UG8 PAH-DP-357 Note 1 PAH-DP-358-20 Pilot Solenoid UG8 PAB-F-2C-Z UG6-UG8 310930 BF7a BF7c CBA-FN-32

CBA-FN-33 7 PAH-DP-35A - - - - - - - - - - - - - - - - - - Note 2 8 PAH-DP-36A - - - - - - - - - - - - - - - - - - Note 2 9 PAH-DP-35B - - - - - - - - - - - - - - - - - - Note 2 10 PAH-DP-36B - - - - - - - - - - - - - - - - - - Note 2

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.15-1 FUNCTION: SERVICE WATER AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 SWA-FN-40A SWA-20372 A 301139 SW-F-ID-A X X X - NJO SWA-CR5-52 460 V ac Circuit Breaker CR5 SW-F-1B-A 301115 CR5a CR5c EDE-MCC-514 SWA-FN-40B Service Water

Pumphouse Train

"A" Switchgear

Room Supply Fan SWA-CR5-42 Motor Starter CR5 SW-F-1B-A SWA-CR5-49 Overload Relays CR5 SW-F-1B-A CR5-NJO CR5-G2H/1 CR5-G2H F36-G2H/2 CR5-TV7 CR5-TW9 SWA-CS-5614-2 Control Switch with Indication G2H CB-F-1A-A SWA-SS-5614 Selector Switch G2H CB-F-1A-A SWA-CR5-FU Fuse CR5 SW-F-1B-A SWA-CS-5614-1 Control Switch with Indication F36 CB-F-3A-A SWA-TSH-5614-1 Temperature Switch TV7 SW-F-1B-A SWA-TSH-5614-2 Temperature Switch TW9 SW-F-1C-A 2 SWA-FN-40B SWA-20372 B 301139 SW-F-ID-A X X X - NK1 SWA-CRO-52 460 V ac Circuit Breaker CRO SW-F-1C-A CROa CROc EDE-MCC-614 Service Water

Pumphouse Train

"B" Switchgear

Room Supply Fan SWA-CRO-42 Motor Starter CRO SW-F-1C-A SWA-FN-40A SWA-FN-64 SWA-FN-71 SWA-CRO-49 Overload Relays CRO SW-F-1C-A SWA-CS-5615-2 Control Switch with Indication G2K CB-F-1B-A CRO-NK1 CRO-G2K/1 CRO-G2K F37-G2K/2 F37-G2K/C CRO-TV8 CRO-TWO CRO-G2K/2 SWA-SS-5615 Selector Switch G2K CB-F-1B-A SWA-CRO-FU Fuses CRO SW-F-1C-A SWA-CS-5615-1 Control Switch with Indication F37 CB-F-3A-A SWA-TSH-5615-1 Temperature Switch TV8 SW-F-1C-A SWA-TSH-5615-2 Temperature Switch TWO SW-F-1B-C 3 SWA-FN-64 SWA-20372 A 301717 CT-F-2B-A X X X - NW1 SWA-CQO-52 460 V ac Circuit Breaker CQO CT-F-1D-A EDE-MCC-513 SWA-FN-40B Service Water

Cooling Tower

Switchgear Room

Supply Fan SWA-CQO-42 Motor Starter CQO CT-F-1D-A SWA-CQO-49 Overload Relay CQO CT-F-1D-A 9763-M-301115 CQOa CQOc CQOd SWA-CS-5669 Control Switch F36 CB-F-3A-A CQO-NW1 CQO-NW1/2 CQO-NW1/3 CQO-F36 ED6-T5V ED6-F36/1 SWA-ZL-5669 Indicating Light F36 CB-F-3A-A SWA-CQO-FU Fuse CQO CT-F-1D-A SWA-TSH-5669 Temperature Switch T5V CT-F-1D-A SWA-FY-5669-1 Solenoid Valve NW1 CT-F-2B-A SWA-FY-5669-2 Solenoid Valve NW1 CT-F-2B-A SWA-DP-66 Position Switch NW1 CT-F-2B-A SWA-ED6-R1 Auxiliary Relay ED6 CT-F-1D-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table MCR 3.1.3.15-2 FUNCTION: SERVICE WATER AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 SWA-DP-66 SWA-20372 A 301717 CT-F-2B-A X X X - NW1 SWA-CQO-52 460 V ac Circuit Breaker CQO CT-F-1D-A CQOa CQOc CQOd EDE-MCC-513 Instrument Air SWA-FN-40B Service Water

Cooling Tower

Switchgear Room

Supply Damper SWA-CQO-42 Motor Starter CQO CT-F-1D-A SWA-CQO-49 Overload Relay CQO CT-F-1D-A CQO-NW1 CQO-NW1/2 CQO-NW1/3 CQO-F36 ED6-T5V ED6-F36/1 SWA-CS-5669 Control Switch F36 CB-F-3A-A SWA-ZL-5669 Indicating Lights F36 CB-F-3A-A SWA-CQO-FU Fuse CQO CT-F-1D-A SWA-TSH-5669 Temperature Switch T5V CT-F-1D-A SWA-FY-5669-1 Solenoid Valve NW1 CT-F-2B-A SWA-FY-5669-2 Solenoid Valve NW1 CT-F-2B-A SWA-DP-66 Position Switch NW1 CT-F-2B-A SWA-ED6-R1 Auxiliary Relay ED6 CT-F-1D-A 5 SWA-FN-71 SWA-20372 A 301717 CT-F-2B-A X X X - NW2 SWA-CR1-52 460 V ac Circuit Breaker CR1 CT-F-1D-A CR1a CR1c EDE-MCC-513 SWA-FN-40B Service Water

Tower Roof Exhaust Fan SWA-CR1-42 Motor Starter CR1 CT-F-1D-A CR1-NW2 CR1-F36 CR1-T5T SWA-CR1-49 Overload Relay CR1 CT-F-1D-A SWA-CS-5667 Control Switch with Indication F36 CB-F-3A-A SWA-TSH-5667 Temperature Switch T5T CT-F-2B-A SWA-CR1-FU Fuse CR1 CT-F-1D-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.16 -1 FUNCTION: SERVICE/INSTRUMENT AIR PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 SA-SKD-137A Service Air Compressor 16A SA-20650 A 310328 TB-F-1A-Z X X X - NN2 SA-AA2-52 460 V AC Circuit Breaker AA2 CB-F-1A-A AA2-ED4 AA2-HR2 AA2-NH2 310863 AA2a AA2d AA2b AA2e AA2c U5-52 CBA-FN-19 CBA-FN-20 SA-SKD-137b SA-AA2-FU Fuses AA2 CB-F-1A-A SA-CS-8501-A Control Switch with Indication AC3 CB-F-1A-A SA-AA2-52H-1 Truck Operated Switch AA2 CB-F-1A-A DG-HR2-HR9X-RMO EPS Relay HR2 CB-F-1A-A EDE-ED4-94-5 Undervoltage Relay ED4 CB-F-1A-A 2 SA-TK-23A Service Air Tank Receiver SA-20650 A 310328 TB-F-1A-Z X X - - - - - - - - - - - - 3 SA-V-92 Service Air Isolation Valve SA-20650 A 310328 TB-F-1A-Z X X X X UM9 SA-E46/8-52 120 V AC Circuit Breaker E46 TB-F-2-Z ED8-F71 ED8-GZ9/1 ED8-UM9 ED8-UM0 UM9-UM0 GZ9-UM9/ GZ9-UM0 E46/8a E46/8c E46/8d - - Note 11 SA-CS-8540 Control Switch with Indication F71 CB-F-3A-A SA-PSL-8540 Pressure Switch GZ9 TB-F-1A-Z SA-PIS-8509 Pressure Indication Switch GZ9 TB-F-1A-Z SA-UM9-20-1 Solenoid Valve UM9 TB-F-1A-Z SA-ED8-3 Interlocking Relay ED8 TB-F-2-Z SA-ZS-V92 Position Switch UM9 TB-F-1A-Z SA-PSL-8545 Pressure Switch GZ9 TB-F-1A-Z 4 SA-SKD-137B Service Air Compressor 16B SA-20650 B 310328 TB-F-1A-Z X X X - NT4 SA-AT2-52 460 V AC Circuit Breaker AT2 CB-F-1B-A AT2-HR4 AT2-NT4 310863 AT2a AT2d AT2b AT2e AT2c CBA-FN-32 CBA-FN-33 US-63 SA-SKD-137A SA-AT2-FU Fuses AT2 CB-F-1B-A SA-CS-8501-B Control Switch with Indication AF8 CB-F-1B-A SA-AT2-52H-1 Truck Operated Switch AT2 CB-F-1B-A DG-HR4-HR9X-RMO EPS Relay HR4 CB-F-1B-A EDE-EF8-94-3 Undervoltage Relay AF8 CB-F-1B-A 5 SA-TK-23B Service Air Tank Receiver SA-20650 B 310328 TB-F-1A-Z X X - - - - - - - - - - - - Notes: 1. Air and electrical power are not required for support as valve fails closed.

2. Fail open mechanical valve. 3. Manual valve.
4. Electrical operation of valve not credited so cables are not listed.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.16 -2 FUNCTION: SERVICE/INSTRUMENT AIR PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 SA-V-93 Service Air Isolation Valve SA-20650 A 310328 TB-F-1A-Z X X X X UM0 SA-E46/8-52 120 V AC Circuit Breaker E46 TB-F-2-Z ED8-F71 ED8-GZ9/1 ED8-UM9 ED8-UMO UM9-UM0 GZ9-UMO GZ9-UM9 E46/8a E46/8c E46/8d - - Notes 1 and 2 SA-CS-8540 Control Switch with Indication F71 CB-F-3A-A SA-PSL-8540 Pressure Switch G29 TB-F-1A-Z SA-PIS-8509 Pressure Indication Switch G29 TB-F-1A-Z SA-UM0-20-2 Solenoid Valve UMO TB-F-1A-Z SA-ED8-3 Interlocking Relay ED8 TB-F-2-Z SA-ZS-V93 Position Switch UMO TB-F-1A-Z SA-PSL-8545 Pressure Switch GZ9 TB-F-1A-Z 7 IA-SKD-18A Instrument Air Dryer (Skid 18A) IA-20637 A 310328 TB-F-1A-Z X X X - HF1 IA-C68-52 460 V AC Circuit Breaker C68 TB-F-2-Z C68-HF1/1 310864 C68a C68b IA-SKD-18B 8 IA-SKD-18B Instrument Air Dryer (Skid 18B) IA-20637 B 310328 TB-F-1A-Z X X X - HF2 IA-C74-52 460 V AC Circuit Breaker C74 CB-F-1B-A C74-HF2/1 310864 C74a C74b CBA-FN-32 CBA-FN-33 EDE-MCC-631 IA-SKD-18A 9 SA-C-4A Containment Air Compressor 4A (Skid 16A) with Control Panel IA-20643 A 310578 C-F-2-Z - X X - M38 SA-D93-52-1,2 460 V AC Circuit Breaker D93 CB-F-1A-A D93-F71 D93-F71/1 D93-HR2 D93-H19 D93-H36/1 D93-H36/2 G44-H36 G44-H36/1 H19-M38 310863 D93a D93c D93d EDE-MCC-531 Primary Component Cooling Water CAH-FN-1C CAH-FN-1E CAH-FN-1F CAH-FN-19 CAH-FN-20 SA-C-4B SA-D93-FU Fuse D93 CB-F-1A-A SA-CS-8531 Control Switch with Indication F71 CB-F-3A-A SA-HR2-HR9 EPS Permit Auxiliary Relay HR2 CB-F-1A-A SA-D93-42 Motor Starter D93 CB-F-1A-A SA-D93-49 Overload Relays D93 CB-F-1A-A SA-CS-4A-T Control Switch Load-Unload G44 C-F-2-Z SA-CS-4A-PB Reset Push Button G44 C-F-2-Z SA-PS-4A-1 Pressure Switch Lube Oil G44 C-F-2-Z SA-PS-4A-2 Pressure Switch Air Header G44 C-F-2-Z SA-TS-4A-1 Temperature Switch Compressor Outlet Air G44 C-F-2-Z SA-G44-R Compressor Shutdown Relay G44 C-F-2-Z SA-SV-4A Loading Solenoid G44 C-F-2-Z SA-G44-TR1 Compressor Loading Time Delay Relay G44 C-F-2-Z SA-G44-TR2 Compressor Auto Stop Time Delay Relay G44 C-F-2-Z SA-G44-TR3 Compressor Auto Restart Time Delay Relay G44 C-F-2-Z EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.16 -3 FUNCTION: SERVICE/INSTRUMENT AIR PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 10 SA-C-4B Containment Air Compressor 4B (Skid 16B) with Control Panel IA-20643 B 310578 C-F-2-Z - X X - M39 SA-D95-52-1,2 460 V AC Circuit Breaker D95 CB-F-1B-A D95-F71 D95-F71/1 D95-HR4 D95-H24 D95-H39/1 D95-H39/2 G45-H39 G45-H39/1 H24-M39 310863 D95a D95c D95d EDE-MCC-631 Primary Component Cooling Water CAH-FN-1A CAH-FN-1B CAH-FN-1D CBA-FN-32 CBA-FN-33 SA-C-4A SA-D95-FU Fuse D95 CB-F-1B-A SA-CS-8541 Control Switch with Indication F71 CB-F-3A-A SA-HR4-HR9 EPS Permit Auxiliary Relay HR4 CB-F-1B-A SA-D95-42 Motor Starter D95 CB-F-1B-A SA-D95-49 Overload Relays D95 CB-F-1B-A SA-CS-4B-T Control Switch Load-Unload G45 C-F-2-Z SA-CS-4B-PB Reset Push Button G45 C-F-2-Z SA-PS-4B-1 Pressure Switch Lube Oil G45 C-F-2-Z SA-PS-4B-2 Pressure Switch Air Header G45 C-F-2-Z SA-TS-4B-1 Temperature Switch Compressor Outlet Air G45 C-F-2-Z SA-G45-R Compressor Shutdown Relay G45 C-F-2-Z SA-SV-4B Loading Solenoid G45 C-F-2-Z SA-G45-TR1 Compressor Loading Time Delay Relay G45 C-F-2-Z SA-G45-TR2 Compressor Auto Stop Time Delay Relay G45 C-F-2-Z SA-G45-TR3 Compressor Auto Restart Time Delay Relay G45 C-F-2-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A 11 IA-D-2A Containment Instrument Air Dryer 2A IA-20643 A 310578 C-F-2-Z X X X - HF3 IA-E9L/3-52 120 V AC Circuit Breaker E9L ET-F-1A-A EM9-J97 HF3-J97 E4E-E9L/2 E4E-H19/2 H19-J97 310864 E9L/3a E9L/3b ED-PP-8J CAH-FN-1C CAH-FN-1E CAH-FN-1F IA-D-2B EDE-MM-582 Fuse Panel E4E ET-F-1A-A EDE-MM-95 Penetration H19 C-F-2-Z, ET-F-1C-A 12 IA-D-2B Containment Instrument Air Dryer 2B IA-20643 B 310578 C-F-2-Z X X X - HF4 IA-EM0/1-52 120 V AC Circuit Breaker EM0 C-F-1-Z EM0-J98 HF4-J98 EM0/1a EM0/1b ED-PP-8B CAH-FN-1A CAH-FN-1B CAH-FN-1D IA-D-2A 13 IA-V50 Instrument Air Dryers Outlet Cross Connect Isolation IA-20637 - 202206 TB-F-1A-Z - X - - - - - - - - - - - Note 3 14 IA-V530 Instrument Air to Containment Isolation ORC IA-20645 A 310589 MS-F-1B-Z - X - X - - - - - - - - - Note 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -1 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EDE-SWG-5 4160 V Bus E5 UAT Incoming Line SWGR 310007 A 310442 CB-F-1A-A X X X - A51 EDE-A51-52 4160 V Circuit Breaker A51 CB-F-1A-A A51-G07 A51-G07/2 A51-G10 A51-HR9 GA6-GB0/4 A51-G07/1 A51-G07/3 A51-GB4 GA0-GB3/4 GC4-GC6/4 A51-G5X A51-G5X/1 G07-HR9 F80-G07/H F80-G07/C F80-G07 G07-HR2 F80-G07/A A55-A5A A54-A5A/1 310102 A51a A51h A51b A51c A51d A51e CBA-FN-19 CBA-FN-20 ED-X-2A EDE-PP-111A DAH-FN-25A DAH-FN-26A EDE-SWG-6 UAT EDE-CS-9709-2 Control Switch A51 CB-F-1A-A EDE-CS-9709-3 Control Switch with Indication G07 DG-F-2A-A EDE-A51-G,R,W Indicating Lights A51 CB-F-1A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-A51-52H Truck Operated Contact A51 CB-F-1A-A EDE-A51-FU Fuses A51 CB-F-1A-A EDE-A51-CT1 Current Transformer (2000/5) A51 CB-F-1A-A EDE-A51-TD-1 CT Test Device A51 CB-F-1A-A EDE-A51-AM Ammeter A51 CB-F-1A-A EDE-A51-AS Ammeter Switch A51 CB-F-1A-A EDE-A51-ATR Transducer Current A51 CB-F-1A-A EDE-A51-CT2 Transformers (4000/5) A51 CB-F-1A-A EDE-A67-PT Potential Transformer (4200-120 V) A67 CB-F-1A-A EDE-A51-TD-3 PT Test Device A51 CB-F-1A-A EDE-A51-VM Voltmeter A51 CB-F-1A-A EDE-A51-86 Lockout Relay A51 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-A52-52S Mechanically Operated Contact A52 CB-F-1A-A DG-G10-25Y1 Auxiliary Synchronizing Check Relay G10 DG-F-2A-A EDE-A53-25U Synchronizing Check Relay A53 CB-F-1A-A EDE-SS-9709-1 Selector Switch G5X DG-F-2A-A EDE-CS-9707-3 Control Switch G07 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A52-86 Lockout Relay A52 CB-F-1A-A EDE-A69-86B Lockout Relay A69 CB-F-1A-A ED-86SB/2/1X -1 Lockout Relay GA0 TB-F-1C-Z ED-86-2/2/B3 Lockout Relay GA6 TB-F-1C-Z ED-86UB/2/1X -2A Lockout Relay GA8 TB-F-1C-Z ED-86UB/2/1X -2B Lockout Relay GA8 TB-F-1C-Z ED-86BF/2/2/52/TG1 Lockout Relay GA9 TB-F-1C-Z ED-86GT/2/TG1 Lockout Relay GA9 TB-F-1C-Z ED-86-1/2/B3 Lockout Relay GB0 TB-F-1C-Z ED-86BF-2/2H Lockout Relay GB3 TB-F-1C-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -2 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EDE-SWG-5 (Continued) ED-86BF-2/2E Lockout Relay GB4 TB-F-1C-Z ED-86UP/2/1X -2A Lockout Relay GC2 TB-F-1C-Z ED-86UP/2/1X -2B Lockout Relay GC2 TB-F-1C-Z ED-86BF-1/2/52/TG1 Lockout Relay GC3 TB-F-1C-Z ED-86SP/2/1X -1 Lockout Relay GC4 TB-F-1C-Z ED-86BF-1/2H Lockout Relay GC6 TB-F-1C-Z ED-86BF-1/2E Lockout Relay GC7 TB-F-1C-Z DG-HR9-RM0 EPS Auxiliary Relay HR9 CB-F-1A-A EDE-A51-3 Interposing Relay for SWYD Lockout Relays A51 CB-F-1A-A EDE-A51-TD-2 Lockout Relay Test Device (A51 -86) A51 CB-F-1A-A EDE-A51-TD-4 Interposing Relay Test Device (A51 -3) A51 CB-F-1A-A EDE-CS-9707-4 Control Switch F80 CB-F-3A-A ED-GA0-TD-2 Lockout Relay Test Device (86SB/2/1X -1) GA0 TB-F-1C-Z ED-GA6-TD-2 Lockout Relay Test Device (86 -2/2/B3) GA6 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2A) GA8 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2B) GA8 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86BF-2/2/52/TG1) GA9 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86GT/2/TG1) GA9 TB-F-1C-Z ED-GB0-TD-2 Lockout Relay Test Device (86 -1/2/B3) GB0 TB-F-1C-Z ED-GB3-TD-2 Lockout Relay Test Device (86BF -2/2H) GB3 TB-F-1C-Z ED-GB4-TD-2 Lockout Relay Test Device (86BF -2/2E) GB4 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2A) GC2 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2B) GC2 TB-F-1C-Z ED-GC3-TD-2 Lockout Relay Test Device (86BF-1/2/52/TG1) GC3 TB-F-1C-Z ED-GC4-TD-2 Lockout Relay Test Device (86SP/2/1X -1) GC4 TB-F-1C-Z ED-GC6-TD-2 Lockout Relay Test Device (86BF -1/2H) GC6 TB-F-1C-Z ED-GC7-TD-2 Lockout Relay Test Device (86BF -1/2E) GC7 TB-F-1C-Z EDE-A51-51 Time Overcurrent Relays øA, øB, øC A51 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -3 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EDE-SWG-5 (Continued) EDE-A51-51GS Ground Sensor Relay A51 CB-F-1A-A EDE-SNS-9736-1 Synchronizing Switch F80 CB-F-3A-A EDE-CS-9709-1 Control Switch with Indicating Light F80 CB-F-3A-A DG-HR2-RM0 EPS Auxiliary Relay HR2 CB-F-1A-A EDE-CS-9707-1 Control Switch F80 CB-F-3A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A 2 EDE-SWG-5 Grounding Transformer 310007 A 310442 CB-F-1A-A X X X - A67 EDE-A67-XFMR 3-1ø 15 KVA Transformers A67 CB-F-1A-A 310102 A67a CBA-FN-19 CBA-FN-20 EDE-SWG-5 EDE-SWG-6 GRD XFMR EDE-A67-FU 3-10A Fuses A67 CB-F-1A-A EDE-A67-52 120 V AC Circuit Breaker A67 CB-F-1A-A EDE-A67-RES Grounding Resistor A67 CB-F-1A-A EDE-A67-64 Grounding Relay A67 CB-F-1A-A EDE-A67-TD-3 VM Test Device A67 CB-F-1A-A EDE-A67-VM (3) Ground Voltmeters A67 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -4 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 EDE-SWG-5 4160 V Bus E5 RAT Incoming Line SWGR 310007 A 310442 CB-F-1A-A X X X - A52 EDE-A52-52 4160 V Circuit Breaker A52 CB-F-1A-A A52-G07/1 A52-G07/3 A52-G10 A52-HR2 GA7-GB7/4 GE6-GE7/4 A52-G5X A52-G5X/1 A52-G07/2 A52-G07/4 A52-GB7 AG2-HR9 GC1-GC0/4 F80-G07/J A52-F80 F80-G07/D F80-G07/4 A54-A5A/2 310102 A52a A52j A52b A52k A52c A52l A52d A52e CBA-FN-19 CBA-FN-20 ED-X-3A EDE-PP-111A DAH-FN-25A DAH-FN-26A EDE-SWG-6 RAT EDE-CS-9707-2 Control Switch A52 CB-F-1A-A EDE-CS-9707-3 Control Switch with Indication G07 DG-F-2A-A EDE-A52-G,R,W Indicating Lights A52 CB-F-1A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-A52-52H Truck Operated Contact A52 CB-F-1A-A EDE-A52-FU Fuses A52 CB-F-1A-A EDE-A52-27/59 Under/Over Voltage Relay A52 CB-F-1A-A EDE-A52-27/59X1,X2 Under/Over Voltage Auxiliary Relay A52 CB-F-1A-A EDE-A52-52Z Time Delay Relay A52 CB-F-1A-A EDE-SS-9707-1 Selector Switch G5X DG-F-2A-A EDE-CS-9709-3 Control Switch G07 DG-F-2A-A EDE-A52-CT-1 Current Transformer (2000/5) A52 CB-F-1A-A EDE-A52-TD-1 CT Test Device A52 CB-F-1A-A EDE-A52-AM Ammeter A52 CB-F-1A-A EDE-A52-AS Ammeter Switch A52 CB-F-1A-A EDE-A52-ATR Transducer A52 CB-F-1A-A EDE-A52-CT-2 Current Transformer (4000/5) A52 CB-F-1A-A EDE-A53-PT Potential Transformer A53 CB-F-1A-A EDE-A52-TD-3 PT Test Device A52 CB-F-1A-A EDE-A52-VM Voltmeter A52 CB-F-1A-A EDE-A52-52S Mechanically Operated Contact A52 CB-F-1A-A EDE-A69-86B Lockout Relay A69 CB-F-1A-A EDE-A52-86 Lockout Relay A52 CB-F-1A-A EDE-A51-86 Lockout Relay A51 CB-F-1A-A DG-HR2-RM0 EPS Auxiliary Relay HR2 CB-F-1A-A DG-HR9-RM0 EPS Auxiliary Relay HR9 CB-F-1A-A EDE-A51-52S Mechanically Operated Contact A51 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -5 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 EDE-SWG-5 (Continued) DG-G10-25Y1 Auxiliary Synchronizing Check Relay G10 DG-F-2A-A EDE-CS-9707-4 Control Switch F80 CB-F-3A-A EDE-A53-25RX Auxiliary Synchronizing Check Relay A53 CB-F-1A-A EDE-A53-25R Synchronizing Check Relay A53 CB-F-1A-A EDE-A52-62 Time Delay Relay A52 CB-F-1A-A EDE-A51-3 Interposing Relay for SWG Lockout Relays A51 CB-F-1A-A EDE-A52-TD-2 Lockout Relay Test Device (A52 -86) A52 CB-F-1A-A EDE-A52-TD-4 Interposing Relay Test Device (A52 -3) A52 CB-F-1A-A ED-86RB/2/1X -3A Lockout Relay GA7 TB-F-1C-Z ED-86-2/2/B2 Lockout Relay GB7 TB-F-1C-Z ED-86-1/2/B2 Lockout Relay GC0 TB-F-1C-Z ED-86RP/2/1X -3A Lockout Relay GC1 TB-F-1C-Z ED-86RP/2/1X -3B Lockout Relay GE6 TB-F-1C-Z ED-86RB/2/1X-3B Lockout Relay GE7 TB-F-1C-Z ED-GA7-TD-2 Lockout Relay Test Device (86RB/2/1X -3A) GA7 TB-F-1C-Z ED-GB7-TD-2 Lockout Relay Test Device (86 -2/2/B2) GB7 TB-F-1C-Z ED-GC0-TD-2 Lockout Relay Test Device (86 -1/2/B2) GC0 TB-F-1C-Z ED-GC1-TD-2 Lockout Relay Test Device (86RP/2/1X -3A) GC1 TB-F-1C-Z ED-GE6-TD-2 Lockout Relay Test Device (86RP/2/1X -3B) GE6 TB-F-1C-Z ED-GE7-TD-2 Lockout Relay Test Device (86RP/2/1X -3B) GE7 TB-F-1C-Z EDE-A52-51 Time Overcurrent Relays øA, øB, øC A52 CB-F-1A-A EDE-A52-51GS Ground Sensor Relay A52 CB-F-1A-A EDE-SNS-9736-1 Synchronizing Switch F80 CB-F-3A-A EDE-CS-9707-1 Control Switch with Indication Light F80 CB-F-3A-A EDE-A53-62BX Auxiliary Latch Relay A53 CB-F-1A-A EDE-A52-27RB-1 Residual Undervoltage Relay A52 CB-F-1A-A EDE-A52-27RB-2 Residual Undervoltage Relay A52 CB-F-1A-A EDE-CS-9709-1 Control Switch F80 CB-F-3A-A EDE-A52-62X Auxiliary Relay A52 CB-F-1A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -6 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 EDE-SWG-5 4160 V Bus E5 PT Compartment 310007 A 310442 CB-F-1A-A X X X - A53 EDE-A53-PT Potential Transformers A53 CB-F-1A-A A53-AC2 A53-HR2 AF2-ED4 A53-G07 AC2-AF2 A53-FB7 F80-G07/5 A54-A5A/4 A54-A5A/5 A55-A5A/1 A55-A5A/2 310102 A53a A53d A53e A53h CBA-FN-19 CBA-FN-20 EDE-SWG-5 EDE-PP-111A DAH-FN-25A DAH-FN-26A EDE-SWG-6 PT EDE-A53-VM Voltmeter A53 CB-F-1A-A EDE-A53-VS Voltmeter Switch A53 CB-F-1A-A EDE-A53-TD-3 PT Test Device A53 CB-F-1A-A EDE-A53-VTR-1 Voltage Transducer A53 CB-F-1A-A EDE-A53-VTR-2 Voltage Transducer A53 CB-F-1A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A53-25U Synchronizing Check Relay A53 CB-F-1A-A EDE-A53-25R Synchronizing Check Relay A53 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-A53-27B-1 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-27B-2 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-TS-3 Undervoltage Relays Test Switch A53 CB-F-1A-A EDE-A53-27D-1 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-27D-1-RES Resistor A53 CB-F-1A-A EDE-A53-27D-2 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-27D-2-RES Resistor A53 CB-F-1A-A EDE-A53-TS-1 Undervoltage Relays Test Switch A53 CB-F-1A-A EDE-A52-27RB-1,2 Residual Undervoltage Relay A52 CB-F-1A-A EDE-A53-62B Time Delay Relay A53 CB-F-1A-A EDE-A53-62B-RES Resistor A53 CB-F-1A-A EDE-A53-TS-4 Test Switch EDE -62B A53 CB-F-1A-A EDE-A53-62BX-1 Auxiliary Relay A53 CB-F-1A-A EDE-A53-62BX Auxiliary Latch Relay A53 CB-F-1A-A EDE-A51-52S Mechanically Operated Contact A51 CB-F-1A-A EDE-ED4-94-5 Undervoltage Tripping Relay ED4 CB-F-1A-A EDE-A52-27/59X1 Under/Over Voltage Auxiliary Relay A52 CB-F-1A-A EDE-AF3-94-4 Undervoltage Tripping Relay AF3 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -7 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 EDE-SWG-5 (Continued) DG-HR2-RM0 EPS Auxiliary Relay HR2 CB-F-1A-A EDE-A53-94-1A Undervoltage Tripping Relay A53 CB-F-1A-A EDE-A53-94-1B Undervoltage Tripping Relay A53 CB-F-1A-A EDE-A53-94-2 Undervoltage Tripping Relay A53 CB-F-1A-A EDE-AC3-94-3 Undervoltage Tripping Relay AC3 CB-F-1A-A EDE-A53-FU 120 V AC 3A Fuses A53 CB-F-1A-A EDE-A53-FU 125 V DC 10A Fuses (2) A53 CB-F-1A-A EDE-A53-62D Time Delay Relay A53 CB-F-1A-A EDE-A53-62D-RES Resistor A53 CB-F-1A-A EDE-A53-TS-2 Test Switch Relay 62D A53 CB-F-1A-A EDE-A53-62DX Auxiliary Relay A53 CB-F-1A-A EDE-SNS-9736-1 Synchronizing Switch F80 CB-F-3A-A EDE-FB7-K609A SI Sig. Act. Auxiliary Relay FB7 CB-F-3A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -8 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 EDE-SWG-5 4160 V Bus E5 DG-1A Incoming Line SWGR 310010 310007 A 310442 CB-F-1A-A X X X - A54 EDE-A54-52 4160 V Circuit Breaker A54 CB-F-1A-A A54-G06/2 A54-G06/4 A54-G07/1 A54-HN0 A54-G06/3 A54-G07 A54-G07/2 G06-G29/7 F80-G06/1 A54-F80/1 A54-HR9 A54-FB7 A54-F80 A5A-A5A/3 310102 A54a A54k A54b A54c A54d A54e A54f CBA-FN-19 CBA-FN-20 DG-DG-1A DAH-FN-25A DAH-FN-26A EDE-PP-111A EDE-SWG-6 DG-1B EDE-CS-9700-2 Control Switch A54 CB-F-1A-A EDE-CS-9700-3 Control Switch with Indication G06 DG-F-2A-A EDE-A54-G,R,W Indicating Lights A54 CB-F-1A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A54-52H Truck Operated Contact A54 CB-F-1A-A EDE-A54-FU Fuses A54 CB-F-1A-A EDE-A54-CT Current Transformers (2000/5) A54 CB-F-1A-A EDE-A54-DCT Differential Current Transformers (2000/5) A54 CB-F-1A-A DG-HNO-DCT DG-1A Neut. Diff. Current Transformers (2000/5) HN0 DG-F-2A-A DG-G06-CT Auxiliary Current Transformer (5:10) G06 DG-F-2A-A EDE-A54-AM Ammeter A54 CB-F-1A-A EDE-A54-AS-1 Ammeter Switch A54 CB-F-1A-A EDE-A54-ATR-1 Current Transducer A54 CB-F-1A-A EDE-A54-ATR-2 Current Transducer A54 CB-F-1A-A EDE-AM-9700-2 Ammeter G06 DG-F-2A-A EDE-G06-AS Ammeter Switch G06 DG-F-2A-A DG-SM-9585 Governor Control (2301A) G06 DG-F-2A-A EDE-A69-PT DG-1A Inc. Line Pot. Transformer (2) 4200 -120 V A69 CB-F-1A-A EDE-A69-VM Voltmeter A69 CB-F-1A-A EDE-A69-VS Voltmeter Switch A69 CB-F-1A-A EDE-A69-TD-3 PT Test Device A69 CB-F-1A-A EDE-A69-VTR-1 Voltage Transducer A69 CB-F-1A-A EDE-A69-VTR-2 Voltage Transducer A69 CB-F-1A-A EDE-A54-27DG Undervoltage Relay A54 CB-F-1A-A EDE-A69-FTR-1 Frequency Transducer A69 CB-F-1A-A EDE-A69-FTR-2 Frequency Transducer A69 CB-F-1A-A EDE-A69-W/WH-TR Watt/Watthour Transducer A69 CB-F-1A-A EDE-A69-W/TR Watt Transducer A69 CB-F-1A-A EDE-A69-VAR-TR Var Transducer A69 CB-F-1A-A EDE-A54-TS Test Start Switch A54 CB-F-1A-A EDE-A54-52Z Time Delay Relay A54 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -9 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 EDE-SWG-5 (Continued) EDE-A54-81-RES Resistor A54 CB-F-1A-A EDE-A54-86DP Primary Lockout Relay A54 CB-F-1A-A EDE-A54-W Indicating Light (A54-86DP) A54 CB-F-1A-A EDE-A69-86B Lockout Relay A69 CB-F-1A-A EDE-A69-86DB Back-Up Lockout Relay A69 CB-F-1A-A EDE-A69-W Indicating Light (A69-86B & A69 -86DB) A69 CB-F-1A-A EDE-A51-86 Lockout Relay A51 CB-F-1A-A EDE-A52-86 Lockout Relay A52 CB-F-1A-A EDE-A51-52S Mechanically Operated Contact A51 CB-F-1A-A EDE-A52-52S Mechanically Operated Contact A52 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-A69-RLA LOCA Seal Relay A69 CB-F-1A-A DG-G10-25Y Auxiliary Sync Check Relay G10 DG-F-2A-A EDE-A69-RS Fast Closure Relay A69 CB-F-1A-A EDE-A54-81 Frequency Relay A54 CB-F-1A-A EDE-A54-87DP Primary Differential Relay A54 CB-F-1A-A EDE-A69-51B Time Overcurrent Relays, øA, øB, øC A69 CB-F-1A-A EDE-A54-81X Auxiliary Frequency Relay A54 CB-F-1A-A EDE-A69-60 Voltage Balance Relay A69 CB-F-1A-A EDE-A69-60AX Auxiliary Voltage Balance Relay A69 CB-F-1A-A EDE-A69-60BX Auxiliary Voltage Balance Relay A69 CB-F-1A-A EDE-A69-40 Loss of Field Relays øA, øB A69 CB-F-1A-A EDE-A54-40X Auxiliary Loss of Field Relay A54 CB-F-1A-A EDE-A69-32 Power Directional Relay A69 CB-F-1A-A EDE-A69-TD-1 Lockout Relay Test Device (86B ) A69 CB-F-1A-A EDE-A69-TD-2 Lockout Relay Test Device (86DB) A69 CB-F-1A-A EDE-A54-TD-2 Lockout Relay Test Device (86DP) A54 CB-F-1A-A DG-G07-R43L5 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -10 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 EDE-SWG-5 (Continued) DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G29-5A Shutdown Relay G29 DG-F-2A-A EDE-A69-51V Time Overcurrent Voltage Restraint Relays, øA, øB, øC A69 CB-F-1A-A EDE-A69-FU 120 V AC 3A Fuses A69 CB-F-1A-A EDE-A54-87DP Reactor Primary Differential Relay Reactor Assembly A54 CB-F-1A-A EDE-A69-51GS Ground Sensor Relay A69 CB-F-1A-A EDE-A54-TD-1 Test Device A54 CB-F-1A-A EDE-CS-9700-1 Control Switch with Indicating Light F80 CB-F-3A-A DG-HR9-PRIX EPS Auxiliary Relay HR9 CB-F-1A-A EDE-SNS-9736-1 Synchronizing Switch F80 CB-F-3A-A MM-FB7-K601A SI Signal Act. Output Relay FB7 CB-F-3A-A DG-G07-ESS Emergency Start Auxiliary Relay G07 DG-F-2A-A EDE-A54-81Y Time Delay Relay A54 CB-F-1A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -11 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 DG-CP-75A Diesel Generator 1A Control Panel Cubicle 2 Synchronizing System 310010 A 310524 DG-F-2A-A X X X - G07 DG-G07-FU-17&18 125 V DC Fuses (6A) G07 DG-F-2A-A F80-G07/B F80-G07/1 310102 G07/2c G07/2g 7b 7f DAH-FN-25A DAH-FN-26A EDE-SWG-11A DG-CP-76A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-RAX Auxiliary Relay, Latch G07 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-CS-9700-3 Control Switch G06 DG-F-2A-A EDE-CS-9707-3 Control Switch G07 DG-F-2A-A EDE-CS-9709-3 Control Switch G07 DG-F-2A-A DG-G06-25DG Synchronizing Check Relay G06 DG-F-2A-A DG-G10-25Y Auxiliary Synchronizing Check Relay G10 DG-F-2A-A DG-G10-25Y1 Auxiliary Synchronizing Check Relay G10 DG-F-2A-A EDE-SNS-9763-1 Synchronizing Switch F80 CB-F-3A-A EDE-CS-9700-1 Control Switch F80 CB-F-3A-A EDE-CS-9707-1 Control Switch F80 CB-F-3A-A EDE-CS-9709-1 Control Switch F80 CB-F-3A-A EDE-A67-PT UAT X-2A Inc. Line Potential Transformer A67 CB-F-1A-A EDE-A53-PT RAT X-3A Inc. Line Potential Transformer A53 CB-F-1A-A EDE-A53-PT Bus E5 Potential Transformer A53 CB-F-1A-A EDE-A69-PT DG-1A Inc. Line Potential Transformer A69 CB-F-1A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-RAX Auxiliary Relay, Latch G07 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -12 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 DG-CP-75A (Continued) DG-G06-25DG Synchronizing Check Relay G06 DG-F-2A-A EDE-SYN-9701 Synchroscope G06 DG-F-2A-A EDE-ZL-9701 Synchronizing Lights G06 DG-F-2A-A EDE-VM-9701-1 Synchronizing Voltmeter Incoming G06 DG-F-2A-A EDE-VM-9701-2 Synchronizing Voltmeter Running G06 DG-F-2A-A EDE-SYN-9891 Synchroscope F80 CB-F-3A-A EDE-ZL-9891 Synchronizing Lights F80 CB-F-3A-A EDE-VM-9891-1 Voltmeter F80 CB-F-3A-A EDE-VM-9891-2 Voltmeter F80 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -13 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 EDE-SWG-5 4160 V Feed to 480 V Transformer EDE-X-5A for Substation Bus EDE-US-51 310007 A 310442 CB-F-1A-A X X X - A55 EDE-A55-52 4160 V Circuit Breaker A55 CB-F-1A-A A55-AB1 A55-F80/1 310102 A55a A55g A55b A55c A55d CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-SWG-5 EDE-SWG-6 EDE-X-5C EDE-US-61 EDE-A55-FU Fuses A55 CB-F-1A-A EDE-CS-9706 Control Switch A55 CB-F-1A-A EDE-A55-G,R,W Indicating Lights A55 CB-F-1A-A EDE-SS-9706 Selector Switch A55 CB-F-1A-A EDE-A55-52H Truck Operated Contact A55 CB-F-1A-A EDE-A55-86 Lockout Relay A55 CB-F-1A-A EDE-A55-TD2 Lockout Relay Test Device A55 CB-F-1A-A EDE-A55-50/51 Inst/Time Overcurrent Relays øA, øB, øC A55 CB-F-1A-A EDE-A55-CT Current Transformers (300/5) A55 CB-F-1A-A EDE-A55-AM Ammeter A55 CB-F-1A-A EDE-A55-AS Ammeter Switch A55 CB-F-1A-A EDE-A55-ATR Transducer A55 CB-F-1A-A EDE-A55-TD1 CT Test Device A55 CB-F-1A-A EDE-A55-51GS Ground Sensor Relay A55 CB-F-1A-A EDE-ZL-9706 Indicating Lights F80 CB-F-3A-A 8 EDE-SWG-5 4160 V Feed to 480 V Transformer EDE-X-5B for Substation Bus EDE-US-52 310007 A 310442 CB-F-1A-A X X X - A63 EDE-A63-52 4160 V Circuit Breaker A63 CB-F-1A-A A63-AC1 A63-F80/1 310102 A63a A63g A63b A63c A63d CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-SWG-5 EDE-SWG-6 EDE-X-5D EDE-US-62 EDE-A63-FU Fuses A63 CB-F-1A-A EDE-CS-9703 Control Switch A63 CB-F-1A-A EDE-A63-G,R,W Indicating Lights A63 CB-F-1A-A EDE-SS-9703 Selector Switch A63 CB-F-1A-A EDE-A63-52H Truck Operated Contact A63 CB-F-1A-A EDE-A63-86 Lockout Relay A63 CB-F-1A-A EDE-A63-TD2 Lockout Relay Test Device A63 CB-F-1A-A EDE-A63-50/51 Inst/Time Overcurrent Relays øA, øB, øC A63 CB-F-1A-A EDE-A63-CT Current Transformers (300/5) A63 CB-F-1A-A EDE-A63-AM Ammeter A63 CB-F-1A-A EDE-A63-AS Ammeter Switch A63 CB-F-1A-A EDE-A63-ATR Transducer A63 CB-F-1A-A EDE-A63-TD1 CT Test Device A63 CB-F-1A-A EDE-A63-51GS Ground Sensor Relay A63 CB-F-1A-A EDE-ZL-9703 Indicating Lights F80 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -14 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 EDE-SWG-5 4160 V Feed to 480 V Transformer EDE-X-5E for Substation Bus EDE-US-53 310007 A 310442 CB-F-1A-A X X X - A60 EDE-A60-52 4160 V Circuit Breaker A60 CB-F-1A-A A60-AF1 A60-F80/1 310102 A60a A60g A60b A60c A60d CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-SWG-5 EDE-SWG-6 EDE-X-5F EDE-US-63 EDE-A60-FU Fuses A60 CB-F-1A-A EDE-CS-9742 Control Switch A60 CB-F-1A-A EDE-A60-G,R,W Indicating Lights A60 CB-F-1A-A EDE-SS-9742 Selector Switch A60 CB-F-1A-A EDE-A60-52H Truck Operated Contact A60 CB-F-1A-A EDE-A60-86 Lockout Relay A60 CB-F-1A-A EDE-A60-TD2 Lockout Relay Test Device A60 CB-F-1A-A EDE-A60-50/51 Inst/Time Overcurrent Relays øA, øB, øC A60 CB-F-1A-A EDE-A60-CT Current Transformers (300/5) A60 CB-F-1A-A EDE-A60-AM Ammeter A60 CB-F-1A-A EDE-A60-AS Ammeter Switch A60 CB-F-1A-A EDE-A60-ATR Transducer A60 CB-F-1A-A EDE-A60-TD1 CT Test Device A60 CB-F-1A-A EDE-A60-51GS Ground Sensor Relay A60 CB-F-1A-A EDE-ZL-9742 Indicating Lights F80 CB-F-3A-A 10 EDE-US-51 480 V Bus 51 Unit Substation 310013 A 310442 CB-F-1A-A X X X - AB2 EDE-AB2-52 480 V AC Circuit Breaker AB2 CB-F-1A-A 310103 AB2a AB2b CBA-FN-19 CBA-FN-20 EDE-X-5A EDE-US-61 EDE-X-5A 4160-480 V Distribution Transformer AB1 CB-F-1A-A EDE-AB3-FU Fuses AB3 CB-F-1A-A EDE-AB1-LA 6 KV Lightning Arrestors (3) AB1 CB-F-1A-A EDE-AB2-CT Current Transformers (2000/5) AB2 CB-F-1A-A EDE-AB3-AM Ammeter AB3 CB-F-1A-A EDE-AB3-AS Ammeter Switch AB3 CB-F-1A-A 11 EDE-US-52 480 V Bus 52 Unit Substation 310013 A 310442 CB-F-1A-A X X X - AC2 EDE-AC2-52 480 V AC Circuit Breaker AC2 CB-F-1A-A 310103 AC2a AC2b CBA-FN-19 CBA-FN-20 EDE-X-5B EDE-US-62 EDE-X-5B 4160-480 V Distribution Transformer AC1 CB-F-1A-A EDE-AC3-FU Fuses AC3 CB-F-1A-A EDE-AC1-LA 6 KV Lightning Arrestors (3) AC1 CB-F-1A-A EDE-AC2-CT Current Transformers (2000/5) AC2 CB-F-1A-A EDE-AC3-AM Ammeter AC3 CB-F-1A-A EDE-AC3-AS Ammeter Switch AC3 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -15 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 12 EDE-US-53 480 V Bus 53 Unit Substation 310051 A 310442 CB-F-1A-A X X X - AF2 EDE-AF2-52 480 V AC Circuit Breaker AF2 CB-F-1A-A 310103 AF2a AF2c CBA-FN-19 CBA-FN-20 EDE-X-5E EDE-US-63 EDE-X-5E 4160-480 V Distribution Transformer AF1 CB-F-1A-A EDE-AF3-FU Fuses AF3 CB-F-1A-A EDE-AF1-LA 6 KV Lightning Arrestors (3) AF1 CB-F-1A-A EDE-AF2-CT Current Transformers (2000/5) AF2 CB-F-1A-A EDE-AF3-AM Ammeter AF3 CB-F-1A-A EDE-AF3-AS Ammeter Switch AF3 CB-F-1A-A 13 EDE-US-51 480 V Feed to 460 V Motor Control Center 512 310013 A 310442 CB-F-1A-A X X X - AB6 EDE-AB6-52 480 V AC Circuit Breaker AB6 CB-F-1A-A AB6-B10 AB6-B10/1 310103 AB6 AB6 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-612 14 EDE-US-51 480 V Feed to 460 V Motor Control Center 514 310013 A 310442 CB-F-1A-A X X X - A94 EDE-A94-52 480 V AC Circuit Breaker A94 CB-F-1A-A A94-C11 310103 A94 A94 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-614 15 EDE-US-51 480 V Feed to 460 V Motor Control Center 515 310013 A 310442 CB-F-1A-A X X X - AX8 EDE-AX8-52 480 V AC Circuit Breaker AX8 CB-F-1A-A AX8-B4D AX8-B4D/1 310103 AX8 AX8 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-615 16 EDE-US-52 480 V Feed to 460 V Motor Control Center 521 310013 A 310442 CB-F-1A-A X X X - AC8 EDE-AC8-52 480 V AC Circuit Breaker AC8 CB-F-1A-A AC8-B13 AC8-B13/1 310103 AC8 AC8 CBA-FN-19 CBA-FN-20 EDE-US-52 EDE-US-62 EDE-MCC-621 17 EDE-US-52 480 V Feed to 460 V Motor Control Center 522 310013 A 310442 CB-F-1A-A X X X - AW9 EDE-AW9-52 480 V AC Circuit Breaker AW9 CB-F-1A-A AW9-D12 AW9-G81/1 AW9-G81 F80-G81 310103 AW9a AW9e AW9b AW9c CBA-FN-19 CBA-FN-20 EDE-US-52 EDE-US-62 EDE-MCC-622 EDE-CS-9787-2 Control Switch with Indication G81 CB-F-1A-A EDE-SS-9787 Selector Switch G81 CB-F-1A-A EDE-AW9-52H Truck Operated Contact AW9 CB-F-1A-A EDE-AW9-FU Fuses AW9 CB-F-1A-A EDE-CS-9787-1 Control Switch with Indication F80 CB-F-3A-A EDE-AW9-G,R Indicating Lights AW9 CB-F-1A-A 18 EDE-US-52 480 V Feed to Motor Control Center 523 310013 A 310442 CB-F-1A-A X X X - AF4 EDE-AF4-52 480 V AC Circuit Breaker AF4 CB-F-1A-A AF4-C99 AF4-C99/1 310103 AF4 AF4 CBA-FN-19 CBA-FN-20 EDE-US-52 EDE-US-63 EDE-MCC-631 19 EDE-US-53 480 V Feed to Motor Control Center 531 310051 A 310442 CB-F-1A-A X X X - AB8 EDE-AB8-52 480 V AC Circuit Breaker AB8 CB-F-1A-A AB8-B12 AB8-B12/1 310103 AB8 AB8 CBA-FN-19 CBA-FN-20 EDE-US-53 EDE-US-63 EDE-MCC-631 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -16 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 20 EDE-US-51 Grounding Transformer 310012 A 310442 CB-F-1A-A X X X - AB3 EDE-AB3-XFMR 3-1ø KVA Transformers AB3 CB-F-1A-A 310103 AB3b - CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 GRD XFMR EDE-AB3-FU Fuses AB3 CB-F-1A-A EDE-AB3-RES Grounding Resistor AB3 CB-F-1A-A EDE-AB3-VM Ground Voltmeters (3) AB3 CB-F-1A-A EDE-AB3-64 Ground Relay AB3 CB-F-1A-A 21 EDE-US-52 Grounding Transformer 310013 A 310442 CB-F-1A-A X X X - AC3 EDE-AC3-XFMR 3-1ø KVA Transformers AC3 CB-F-1A-A 310103 AC3b - CBA-FN-19 CBA-FN-20 EDE-US-52 EDE-US-62 GRD XFMR EDE-AC3-FU Fuses AC3 CB-F-1A-A EDE-AC3-RES Grounding Resistor AC3 CB-F-1A-A EDE-AC3-VM Ground Voltmeters (3) AC3 CB-F-1A-A EDE-AC3-64 Ground Relay AC3 CB-F-1A-A 22 EDE-US-53 Grounding Transformer 310051 A 310442 CB-F-1A-A X X X - AF3 EDE-AF3-XFMR 3-1ø KVA Transformers AF3 CB-F-1A-A 310103 AF3b - CBA-FN-19 CBA-FN-20 EDE-US-53 EDE-US-63 GRD XFMR EDE-AF3-FU Fuses AF3 CB-F-1A-A EDE-AF3-RES Grounding Resistor AF3 CB-F-1A-A EDE-AF3-VM Ground Voltmeters (3) AF3 CB-F-1A-A EDE-AF3-64 Ground Relay AF3 CB-F-1A-A 23 EDE-I-1E Uninterruptible Power Supply 310043 A 310442 CB-F-1A-A X X X - HF5 EDE-DD3-52 460 V AC Circuit Breaker DD3 CB-F-1A-A DD3-HF5/1 DM7-HF5/1 310105 DD3a DD3b CBA-FN-19 CBA-FN-20 EDE-MCC-512 EDE-SWG-11A EDE-I-1F EDE-DM7-72 125 V DC Circuit Breaker DM7 CB-F-1A-A EDE-HF5/2-52 460 V AC Inc. Line Circuit Breaker HF5 CB-F-1A-A EDE-HF5/1-72 125 V DC Inc. Line Circuit Breaker HF5 CB-F-1A-A EDE-HF5/3-52 120 V AC Output Circuit Breaker HF5 CB-F-1A-A 23A EDE-CP-1E Static Transfer Switch 310043 A 310442 CB-F-1A-A X X X - E1Y EDE-E1Y-F1 300 A, 600 V Fuse E1Y CB-F-1A-A E1Y-HF5 E1Y-HF5/1 310105 DD3a DD3b EDE-I-1E CBA-FN-19 CBA-FN-20 EDE-CP-1F 24 EDE-PP-1E Vital Instrument Bus 310043 A 310442 CB-F-1A-A X X X - EH9 EDE-EH9/NC-52 120 V AC Circuit Breaker - Inc. Feed from EDE-CP-1E (Norm. Closed) EH9 CB-F-1A-A EH9-E1Y 310105 DD3a DD3b EH9a CBA-FN-19 CBA-FN-20 EDE-CP-1E EDE-PP-1F 25 EDE-PP-11E Vital Instrument Bus 310043 A 310442 CB-F-1A-A X X X - E1S EDE-EH9/13-52 120 V AC Circuit Breaker EH9 CB-F-1A-A E1S-EH9 310105 DD3a DD3b E1Sa CBA-FN-19 CBA-FN-20 EDE-PP-1E EDE-PP-11F SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -17 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 26 ED-X-14J 480-120/240 V Transformer 310026 A 310691 ET-F-1A-A X X X - EG4 ED-BOM-52 460 V AC Circuit Breaker BOM CB-F-1A-A BOM-EG4 310104 BOM CBA-FN-19 CBA-FN-20 EDE-MCC-531 CAH-FN-1C CAH-FN-1E CAH-FN-1F ED-X-16A 27 ED-PP-8J 120/240 V Distribution Panel 310026 A 310691 ET-F-1A-A X X X - E9L ED-X-14J Transformer EG4 ET-F-1A-A EG4-E9L 310104 BOM CAH-FN-1C CAH-FN-1E CAH-FN-1F ED-X-14J ED-PP-8B ED-E9L-52 250 V AC Circuit Breaker (Main) E9L ET-F-1A-A 310106 E9La 28 Deleted 29 EDE-BC-1A 125 V DC Battery Charger 310042 A 310442 CB-F-1A-A X X X - HR5 EDE-DB1-52 460 V AC Circuit Breaker DB1 CB-F-1A-A DB1-HR2 DB1-HR5 310107 DB1a DB1f DB1b DB1c CBA-FN-19 CBA-FN-20 EDE-MCC-512 EDE-BC-1B EDE-DB1-42 Contactor DB1 CB-F-1A-A EDE-DB1-42X Auxiliary Relay DB1 CB-F-1A-A DG-HR2-HR9(K20) EPS Relay HR2 CB-F-1A-A EDE-HR5/1-52 460 V AC Circuit Breaker - Incoming Feed HR5 CB-F-1A-A EDE-DB1-FU Fuse DB1 CB-F-1A-A 30 EDE-B-1A 125 V DC Battery 310042 A 310442 CB-F-1D-A X X X - HV4 EDE-J75-FU-1,2,3,4 1600A Fuses J75 CB-F-1A-A HV4-J75 HV4-J75/1 310107 DB1a DB1f DB1b DB1c CBA-FN-19 CBA-FN-20 CBA-FN-21A EDE-BC-1A EDE-SWG-11A EDE-B-1B EDE-J75-SH 1000A, 100 MV Shunt J75 CB-F-1A-A EDE-J75-ATR Transducer J75 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -18 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 31 EDE-SWG-11A 125 V DC Switchboard Auxiliary Buses 120 V AC and 125 V DC 310042 A 310442 CB-F-1A-A X X X - DM1 EDE-HR5/2-72 125 V DC Circuit Breaker HR5 CB-F-1A-A DM3-J75 DM3-J75/1 DM2-HR5 DM1-J75/1 G1W-J75 310107 DB1a DB1f DB1b DB1c 5a CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-B-1A EDE-BC-1A EDE-PP-1E EDE-SWG-11B EDE-DL4-72 125 V DC Circuit Breaker DL4 CB-F-1A-A EDE-DM2-72 125 V DC Circuit Breaker DM2 CB-F-1A-A EDE-DM3-72 125 V DC Circuit Breaker DM3 CB-F-1A-A EDE-DM1-FU-1&2 125 V DC 15A Fuses DM1 CB-F-1A-A EDE-DM1-27BL Undervoltage Relay DM1 CB-F-1A-A EDE-DM1-27BLL Undervoltage Relay DM1 CB-F-1A-A EDE-DM1-VM DC Voltmeter DM1 CB-F-1A-A EDE-DM1-VTR Voltage Transducer DM1 CB-F-1A-A EDE-DM1-DIO Diodes DM1 CB-F-1A-A EDE-DM1-XS Selector Switch DM1 CB-F-1A-A EDE-DM1-AMY Ammeter Relay DM1 CB-F-1A-A EDE-EH9/5-52 120 V AC Circuit Breaker EH9 CB-F-1A-A DM1-EH9 310105 EH9a EH9b EDE-DM1-62BL Timing Relay DM1 CB-F-1A-A EDE-DM1-62BLL Timing Relay DM1 CB-F-1A-A EDE-DM2-72 Breaker Operated Contact DM2 CB-F-1A-A EDE-DM2-72STC Circuit Breaker Shut Trip Coil DM2 CB-F-1A-A EDE-J75-ATR Current Transducer J75 CB-F-1A-A EDE-DM1-52 120 V AC Inc. Feed Circuit Breaker DM1 CB-F-1A-A EDE-DM1-FU 120 V AC 15A and 1A Fuses DM1 CB-F-1A-A 32 EDE-PP-111A 125 V DC Distribution Panel 310042 A 310442 CB-F-1A-A X X X - E93 EDE-DM5-72 125 V DC Circuit Breaker DM5 CB-F-1A-A DM5-E93 310107 DB1a DB1f E93a CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-PP-111B EDE-E93-72 125 V DC Circuit Breaker (Main) E93 CB-F-1A-A 33 EDE-PP-112A 125 V DC Distribution Panel 310042 A 310442 CB-F-1A-A X X X - E87 EDE-DM8-72 125 V DC Circuit Breaker DM8 CB-F-1A-A DM8-E87 310107 DB1a DB1f E87a CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-PP-112B EDE-E87-72 125 V DC Circuit Breaker (Main) E87 CB-F-1A-A 34 EDE-PP-113A 125 V DC Distribution Panel 310042 A 310442 CB-F-1A-A X X X - E2T EDE-DM0-72 125 V DC Circuit Breaker DM0 CB-F-1A-A DM0-E2T 310107 DB1a DB1f DB1b E2Ta CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-PP-113B EDE-E2T-72 125 V DC Circuit Breaker (Main) E2T CB-F-1A-A 35 EDE-SWG-5 4160 V SWGR 125 V DC Control Bus A 310442 CB-F-1A-A X X X - A53 EDE-E93/1-72 125 V DC Circuit Breaker E93 CB-F-1A-A A53-E93 310107 E93a E93b CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-SWG-6 EDE-A53-8 125 V DC Circuit Breaker (Main) A53 CB-F-1A-A 310102 5a, 5f, 5g, 5h SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -19 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 36 EDE-US-51 480 V Unit Substation 125 V DC Control Bus A 310442 CB-F-1A-A X X X - AB3 EDE-E93/2-72 125 V DC Circuit Breaker E93 CB-F-1A-A AB3-E93 310107 E93a E93b CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-US-61 EDE-AB3-8 125 V DC Circuit Breaker (Main) AB3 CB-F-1A-A 310103 5m 37 EDE-US-52 480 V Unit Substation 125 V DC Control Bus A 310442 CB-F-1A-A X X X - AC3 EDE-E93/3-72 125 V DC Circuit Breaker E93 CB-F-1A-A AC3-E93 310107 E93a E93b CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-US-62 EDE-AC3-8 125 V DC Circuit Breaker (Main) AC3 CB-F-1A-A 310103 5n 38 EDE-US-53 480 V Unit Substation 125 V DC Control Bus A 310442 CB-F-1A-A X X X - AF3 EDE-E93/4-72 125 V DC Circuit Breaker E93 CB-F-1A-A AF3-E93 310107 E93a E93b CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-US-63 EDE-AF3-8 125 V DC Circuit Breaker (Main) AF3 CB-F-1A-A 310103 5o 39 DG-CP-75A Diesel Generator 1A Control Panel Cubicle 3 125 V DC Supply 310010 310042 A 310524 DG-F-2A-A X X X - G10 EDE-DM9-72 125 V DC Circuit Breaker DM9 CB-F-1A-A DM9-G10 310102 DM9a DM9b DAH-FN-25A DAH-FN-26A EDE-SWG-11A CBA-FN-19 CBA-FN-20 DG-CP-76A DG-G10-72 125 V DC Circuit Breaker (Main) G10 DG-F-2A-A 310107 DB1a 40 ED-US-11 480 V Unit Substation 125 V DC Control Bus 310002 310011 A 310442 CB-F-1A-A X X X - AG3 EDE-E97/13-72 125 V DC Circuit Breaker (Main) E97 NES-F-1A-Z AG3-E97 310107 E97a E97b EDE-AG1-X-4A CBA-FN-19 CBA-FN-20 ED-US-23 EDE-AG3-72 125 V DC Circuit Breaker AG3 CB-F-1A-A 310103 5a 41 ED-US-23 480 V Unit Substation 125 V DC Control Bus 310002 310011 B 310442 CB-F-1A-A X X X - AM3 EDE-E97/14-72 125 V DC Circuit Breaker E97 NES-F-1A-Z AM3-E97 310107 E97a E97b EDE-AM1-X-4F CBA-FN-19 CBA-FN-20 ED-US-11 EDE-AM3-72 125 V DC Circuit Breaker AM3 CB-F-1A-A 310103 5h SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -20 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 42 EDE-SWG-6 4160 V Bus E6 UAT Incoming Line SWGR 310008 B 310442 CB-F-1B-A X X X - A71 EDE-A71-52 4160 V Circuit Breaker A71 CB-F-1B-A A71-G19 A71-G19/2 A71-G20 A71-HR0 GA6-GB0/5 A71-G19/1 A71-G19/3 A71-GB4 GA0-GB3/5 GC4-GC6/5 A71-G5Y A71-G5Y/1 G19-HR0 F81-G19/G F81-G19/C F81-G19/6 G19-HR4 F81-G19/A A75-A7A A74-A7A/1 310102 A71a A71h A71b A71i A71c A71k A71d A71e CBA-FN-32 CBA-FN-33 ED-X-2B EDE-PP-111B DAH-FN-25B DAH-FN-26B EDE-SWG-5 UAT EDE-CS-9719-2 Control Switch A71 CB-F-1B-A EDE-CS-9719-3 Control Switch with Indication G19 DG-F-2B-A EDE-A71-G,R,W Indicating Lights A71 CB-F-1B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-A71-52H Truck Operated Contact A71 CB-F-1B-A EDE-A71-FU Fuses A71 CB-F-1B-A EDE-A71-CT1 Current Transformers (2000/5) A71 CB-F-1B-A EDE-A71-TD-1 CT Test Device A71 CB-F-1B-A EDE-A71-AM Ammeter A71 CB-F-1B-A EDE-A71-AS Ammeter Switch A71 CB-F-1B-A EDE-A71-ATR Transducer A71 CB-F-1B-A EDE-A71-CT2 Current Transformers (4000/5) A71 CB-F-1B-A EDE-A87-PT Potential Transformer A87 CB-F-1B-A EDE-A71-TD-3 PT Test Device A71 CB-F-1B-A EDE-A71-VM Voltmeter A71 CB-F-1B-A EDE-A71-86 Lockout Relay A71 CB-F-1B-A EDE-A74-52S Mechanically Operated Contact A74 CB-F-1B-A EDE-A72-52S Mechanically Operated Contact A72 CB-F-1B-A DG-G20-25Y1 Auxiliary Sync Check Relay G20 DG-F-2B-A EDE-A73-25U Synchronizing Check Relay A73 CB-F-1B-A EDE-SS-9719-1 Selector Switch G5Y DG-F-2B-A EDE-CS-9717-3 Control Switch G19 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-A72-86 Lockout Relay A72 CB-F-1B-A EDE-A89-86B Lockout Relay A89 CB-F-1B-A ED-86SB/2/1X -1 Lockout Relay GA0 TB-F-1C-Z ED-86-2/2/B3 Lockout Relay GA6 TB-F-1C-Z ED-86UB/2/1X -2A Lockout Relay GA8 TB-F-1C-Z ED-86UB/2/1X -2B Lockout Relay GA8 TB-F-1C-Z ED-86BF-2/2/52/TG1 Lockout Relay GA9 TB-F-1C-Z ED-86GT/2/TG -1 Lockout Relay GA9 TB-F-1C-Z ED-86-1/2/B3 Lockout Relay GB0 TB-F-1C-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -21 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 42 EDE-SWG-6 (Continued) ED-86BF-2/2H Lockout Relay GB3 TB-F-1C-Z ED-86BF-2/2E Lockout Relay GB4 TB-F-1C-Z ED-86UP/2/1X -2A Lockout Relay GC2 TB-F-1C-Z ED-86UP/2/1X -2B Lockout Relay GC2 TB-F-1C-Z ED-86BF-1/2/52/TG1 Lockout Relay GC3 TB-F-1C-Z ED-86SP/2/1X -1 Lockout Relay GC4 TB-F-1C-Z ED-86BF-1/2H Lockout Relay GC6 TB-F-1C-Z ED-86BF-1/2E Lockout Relay GC7 TB-F-1C-Z DG-HR0-RM0 EPS Auxiliary Relay HR0 CB-F-1B-A EDE-A71-3 Interposing Relay for SWYD Lockout Relays A71 CB-F-1B-A EDE-A71-TD-2 Lockout Relay Test Device (A71 -86) A71 CB-F-1B-A EDE-A71-TD-4 Interposing Relay Test Device (A71 -3) A71 CB-F-1B-A EDE-CS-9719-4 Control Switch F81 CB-F-3A-A ED-GA0-TD-2 Lockout Relay Test Device (86SB/2/1X -1) GA0 TB-F-1C-Z ED-GA6-TD-2 Lockout Relay Test Device (86 -2/2/B3) GA6 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2A) GA8 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2B) GA8 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86BF -2/2/52/TG1) GA9 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86GT/2/TG -1) GA9 TB-F-1C-Z ED-GB0-TD-2 Lockout Relay Test Device (86 -1/2/B3) GB0 TB-F-1C-Z ED-GB3-TD-2 Lockout Relay Test Device (86BF -2/2H) GB3 TB-F-1C-Z ED-GB4-TD-2 Lockout Relay Test Device (86BF -2/2E) GB4 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2A) GC2 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2B) GC2 TB-F-1C-Z ED-GC3-TD-2 Lockout Relay Test Device (86BF -1/2/52/TG1) GC3 TB-F-1C-Z ED-GC4-TD-2 Lockout Relay Test Device (86SP/2/1X -1) GC4 TB-F-1C-Z ED-GC6-TD-2 Lockout Relay Test Device (86BF -1/2H) GC6 TB-F-1C-Z ED-GC7-TD-2 Lockout Relay Test Device (86BF -1/2E) GC7 TB-F-1C-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -22 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 42 EDE-SWG-6 (Continued) EDE-A71-51 Time Overcurrent Relays øA, øB, øC A71 CB-F-1B-A EDE-A71-51GS Ground Sensor Relay A71 CB-F-1B-A EDE-SNS-9737-1 Synchronizing Switch F81 CB-F-3A-A EDE-CS-9719-1 Control Switch with Indicating Lights F81 CB-F-3A-A DG-HR4-RM0 EPS Auxiliary Relay HR4 CB-F-1B-A EDE-CS-9717-1 Control Switch F81 CB-F-3A-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A 43 EDE-SWG-6 Grounding Transformer 310008 B 310442 CB-F-1B-A X X X - A87 EDE-A87-XFMR 3-1ø 15 KVA Transformers A87 CB-F-1B-A 310102 A87a CBA-FN-32 CBA-FN-33 EDE-SWG-6 EDE-SWG-5 GRD XFMR EDE-A87-FU 3-10A Fuses A87 CB-F-1B-A EDE-A87-52 120 V AC Circuit Breaker A87 CB-F-1B-A EDE-A87-RES Grounding Resistor A87 CB-F-1B-A EDE-A87-64 Ground Relay A87 CB-F-1B-A EDE-A87-TD-3 VM Test Device A87 CB-F-1B-A EDE-A87-VM (3) Ground Voltmeters A87 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -23 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 44 EDE-SWG-6 4160 V Bus E6 RAT Incoming Line SWGR 310008 B 310442 CB-F-1B-A X X X - A72 EDE-A72-52 4160 V Circuit Breaker A72 CB-F-1B-A A72-G19 A72-G19/2 A72-G20 A72-HR4 GA7-GB7/5 GE6-GE7/5 A72-G19/1 A72-G19/3 A72-GB7 A72-HR0 GC1-GC0/5 A72-G5Y A72-G5Y/1 F81-G19/H A72-F81 F81-G19/B F81-G19/4 A74-A7A/2 310102 A72a A72j A72b A72k A72c A72l A72d A72e CBA-FN-32 CBA-FN-33 ED-X-3B EDE-PP-111B DAH-FN-25B DAH-FN-26B EDE-SWG-5 RAT EDE-CS-9717-2 Control Switch A72 CB-F-1B-A EDE-CS-9717-3 Control Switch with Indication G19 DG-F-2B-A EDE-A72-G,R,W Indicating Lights A72 CB-F-1B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-A72-52H Truck Operated Contact A72 CB-F-1B-A EDE-A72-FU Fuses A72 CB-F-1B-A EDE-A72-27/59 Under/Over Voltage Relay A72 CB-F-1B-A EDE-A72-27/59X1,X2 Under/Over Voltage Auxiliary Relay A72 CB-F-1B-A EDE-A72-CT-1 Current Transformer (2000/5) A72 CB-F-1B-A EDE-A72-52Z Time Delay Relay A72 CB-F-1B-A EDE-SS-9717-1 Selector Switch G5Y DG-F-2B-A EDE-CS-9719-3 Control Switch G19 DG-F-2B-A EDE-A72-TD-1 CT Test Device A72 CB-F-1B-A EDE-A72-AM Ammeter A72 CB-F-1B-A EDE-A72-AS Ammeter Switch A72 CB-F-1B-A EDE-A72-ATR Transducer A72 CB-F-1B-A EDE-A72-CT-2 Current Transformer (4000/5) A72 CB-F-1B-A EDE-A73-PT Potential Transformer A73 CB-F-1B-A EDE-A72-TD-3 PT Test Device A72 CB-F-1B-A EE-A72-VM Voltmeter A72 CB-F-1B-A EDE-A72-52S Mechanically Operated Contact A72 CB-F-1B-A EDE-A89-86B Lockout Rela y A89 CB-F-1B-A EDE-A72-86 Lockout Relay A72 CB-F-1B-A EDE-A71-86 Lockout Relay A71 CB-F-1B-A DG-HR4-RM0 EPS Auxiliary Relay HR4 CB-F-1B-A DG-HR0-RM0 EPS Auxiliary Relay HR0 CB-F-1B-A EDE-A71-52S Mechanically Operated Contact A71 CB-F-1B-A EDE-A74-52S Mechanically Operated Contact A74 CB-F-1B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A DG-G20-25Y Auxiliary Synchronizing Check Relay G20 DG-F-2B-A EDE-A73-25RX Auxiliary Synchronizing Check Relay A73 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -24 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 44 EDE-SWG-6 (Continued) EDE-A73-25R Synchronizing Check Relay A73 CB-F-1B-A EDE-CS-9717-4 Control Switch F81 CB-F-3A-A EDE-CS-9719-1 Control Switch F81 CB-F-3A-A EDE-A72-62 Time Delay Relay A72 CB-F-1B-A EDE-A72-3 Interposing Relay for SWYD Lockout Relays A71 CB-F-1B-A EDE-A72-TD-2 Lockout Relay Test Device (A72 -86) A72 CB-F-1B-A EDE-A72-TD-4 Interposing Relay Test Device (A72 -3) A72 CB-F-1B-A EDE-SNS-9737-1 Synchronizing Switch F81 CB-F-3A-A EDE-CS-9717-1 Control Switch with Indicating Light F81 CB-F-3A-A EDE-A73-62BX Auxiliary Latch Relay A73 CB-F-1B-A EDE-A73-25R Synchronizing Check Relay A73 CB-F-1B-A EDE-A73-27RB-1 Residual Undervoltage Relay A73 CB-F-1B-A EDE-A73-27RB-2 Residual Undervoltage Relay A73 CB-F-1B-A EDE-A72-62X Auxiliary Relay A72 CB-F-1B-A ED-86RB/2/1X -3A Lockout Relay GA7 TB-F-1C-Z ED-86-2/2/B2 Lockout Relay GB7 TB-F-1C-Z ED-86-1/2/B2 Lockout Relay GC0 TB-F-1C-Z ED-86RP/2/1X -3A Lockout Relay GC1 TB-F-1C-Z ED-86RP/2/1X -3B Lockout Relay GE6 TB-F-1C-Z ED-86RB/2/1X -3B Lockout Relay GE7 TB-F-1C-Z ED-GA7-TD-2 Lockout Relay Test Device (86RB/2/1X -3A) GA7 TB-F-1C-Z ED-GB7-TD-2 Lockout Relay Test Device (86 -2/2/B2) GB7 TB-F-1C-Z ED-GC0-TD-2 Lockout Relay Test Device (86 -1/2/B2) GC0 TB-F-1C-Z ED-GC1-TD-2 Lockout Relay Test Device (86RP/2/1X -3A) GC1 TB-F-1C-Z ED-GE6-TD-2 Lockout Relay Test Device (86RP/2/1X -3B) GE6 TB-F-1C-Z ED-GE7-TD-2 Lockout Relay Test Device (86RB/2/1X -3B) GE7 TB-F-1C-Z EDE-A72-51 Time Overcurrent Relays øA, øB, øC A72 CB-F-1B-A EDE-A72-51GS Ground Sensor Relay A72 CB-F-1B-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -25 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 45 EDE-SWG-6 4160 V Bus E6 PT Compartment 310008 B 310442 CB-F-1B-A X X X - A73 EDE-A73-PT Potential Transformer A73 CB-F-1B-A A73-AE2 A73-G19 A73-HR4 AE2-AF7 AF7-EE6 AW2-EE6 F81-G19/5 A73-FB0 A74-A7A/4 A74-A7A/5 A75-A7A/1 A75-A7A/2 310102 A73a A73d A73e A73h CBA-FN-32 CBA-FN-33 EDE-SWG-6 EDE-PP-111B DAH-FN-25B DAH-FN-26B EDE-SWG-5 PT EDE-A73-VM Voltmeter A73 CB-F-1B-A EDE-A73-VS Voltmeter Switch A73 CB-F-1B-A EDE-A73-TD-3 PT Test Device A73 CB-F-1B-A EDE-A73-VTR-1 Voltage Transducer A73 CB-F-1B-A EDE-A73-VTR-2 Voltage Transducer A73 CB-F-1B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-A73-25U Synchronizing Check Relay A73 CB-F-1B-A EDE-A73-25R Synchronizing Check Relay A73 CB-F-1B-A EDE-A74-52S Mechanically Operated Contact A74 CB-F-1B-A EDE-A73-27B-1 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-27B-2 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-TS-3 UV Relays Test Switch A73 CB-F-1B-A EDE-A73-27D-1 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-27D-1-RES Resistor A73 CB-F-1B-A EDE-A73-27D-2 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-27D-2-RES Resistor A73 CB-F-1B-A EDE-A73-TS-1 UV Relays Test Switch A73 CB-F-1B-A EDE-A72-27RB-1,2 Residual Undervoltage Relay A72 CB-F-1B-A EDE-A73-62B Time Delay Relay A73 CB-F-1B-A EDE-A73-62B-RES Resistor A73 CB-F-1B-A EDE-A73-TS-4 Test Switch EDE -62B A73 CB-F-1B-A EDE-A73-62BX-1 Auxiliary Relay A73 CB-F-1B-A EDE-A73-62BX Auxiliary Latch Relay A73 CB-F-1B-A EDE-A71-52S Mechanically Operated Contact A71 CB-F-1B-A EDE-AW3-94-5 Undervoltage Tripping Relay AW3 CB-F-1B-A EDE-A72-27/59X1 Under/Over Voltage Auxiliary Relay A72 CB-F-1B-A EDE-AF8-94-4 Undervoltage Tripping Relay AF8 CB-F-1B-A DG-HR4-RM0 EPS Auxiliary Relay HR4 CB-F-1B-A EDE-A73-94-1A Undervoltage Tripping Relay A73 CB-F-1B-A EDE-A73-94-1B Undervoltage Tripping Relay A73 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -26 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 45 EDE-SWG-6 (Continued) EDE-A73-94-2 Undervoltage Tripping Relay A73 CB-F-1B-A EDE-AE3-94-3 Undervoltage Tripping Relay AE3 CB-F-1B-A EDE-EE6-94-6 Tripping Relay EE6 CB-F-1B-A EDE-A73-FU 10A Fuses A73 CB-F-1B-A EDE-A73-62D Time Delay Relay A73 CB-F-1B-A EDE-A73-62D-RES Resistor A73 CB-F-1B-A EDE-A73-TS-2 Test Switch Relay 62D A73 CB-F-1B-A EDE-A73-62DX Auxiliary Relay A73 CB-F-1B-A EDE-SNS-9737-1 Synchronizing Switch F81 CB-F-3A-A EDE-A73-FU 3A Fuse A73 CB-F-1B-A EDE-FB0-K609B SI Sig. Act. Auxiliary Relay FB0 CB-F-3A-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -27 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 46 EDE-SWG-6 4160 V Bus E6 DG-1B Incoming Line SWGR 310010 310008 B 310442 CB-F-1B-A X X X - A74 EDE-A74-52 4160 V Circuit Breaker A74 CB-F-1B-A A74-G18/2 A74-G18/3 A74-G18/4 A74-G19 A74-G19/1 A74-G19/2 A74-HP1 G18-G30/7 A74-G18/8 F81-G18/3 A74-F81 A74-F81/1 A74-FB0 A74-HR0 A74-A7A/3 310102 A74a A74k A74b A74n A74c A74d A74e A74f CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B EDE-PP-111B DG-DG-1B EDE-SWG-5 DG-1A EDE-CS-9710-2 Control Switch A74 CB-F-1B-A EDE-CS-9710-3 Control Switch with Indication G18 DG-F-2B-A EDE-A74-G,R,W Indicating Lights A74 CB-F-1B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-A74-52H Truck Operated Contact A74 CB-F-1B-A EDE-A74-FU Fuses A74 CB-F-1B-A EDE-A74-CT Current Transformers (2000/5) A74 CB-F-1B-A EDE-A74-DCT Differential Current Transformers (2000/5) A74 CB-F-1B-A DG-HP1-DCT DG-1B Neutral Differential Current Transformers (2000/5) HP1 DG-F-2B-A DG-G18-CT Auxiliary Current Transformer (5:10) G18 DG-F-2B-A EDE-A74-AM Ammeter A74 CB-F-1B-A EDE-A74-AS-1 Ammeter Switch A74 CB-F-1B-A EDE-A74-ATR-1 Current Transducer A74 CB-F-1B-A EDE-A74-ATR-2 Current Transducer A74 CB-F-1B-A EDE-AM-9710-2 Ammeter G18 DG-F-2B-A EDE-G18-AS Ammeter Switch G18 DG-F-2B-A DG-SM-9587 Governor Control (2301A) G18 DG-F-2B-A EDE-A89-PT DG-1B Inc. Line Pot. Transformer (2) 4200-120 V A89 CB-F-1B-A EDE-A89-VM Voltmeter A89 CB-F-1B-A EDE-A89-VS Voltmeter Switch A89 CB-F-1B-A EDE-A89-TD-3 PT Test Device A89 CB-F-1B-A EDE-A89-VTR-1 Voltage Transducer A89 CB-F-1B-A EDE-A89-VTR-2 Voltage Transducer A89 CB-F-1B-A EDE-A74-27DG Undervoltage Relay A74 CB-F-1B-A EDE-A89-FTR-1 Frequency Transducer A89 CB-F-1B-A EDE-A89-FTR-2 Frequency Transducer A89 CB-F-1B-A EDE-A89-W/WH-TR Watt/Watthour Transducer A89 CB-F-1B-A EDE-A89-W/TR Watt Transducer A89 CB-F-1B-A EDE-A89-VAR-TR Var Transducer A89 CB-F-1B-A EDE-A74-TS Test Start Switch A74 CB-F-1B-A EDE-A74-52Z Time Delay Relay A74 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -28 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 46 EDE-SWG-6 EDE-A74-81-RES Resistor A74 CB-F-1B-A EDE-A89-86B Lockout Relay A89 CB-F-1B-A EDE-A89-86DB Back-Up Lockout Relay A89 CB-F-1B-A EDE-A89-W Indicating Lights (A89-86B & A89 -86DB) A89 CB-F-1B-A EDE-A74-W Indicating Light (A74-86DP) A74 CB-F-1B-A EDE-A74-86DP Primary Lockout Relay A74 CB-F-1B-A EDE-A71-86 Lockout Relay A71 CB-F-1B-A EDE-A72-86 Lockout Relay A72 CB-F-1B-A EDE-A71-52S Mechanically Operated Contact A71 CB-F-1B-A EDE-A72-52S Mechanically Operated Contact A72 CB-F-1B-A EDE-A74-52S Mechanically Operated Contact A74 CB-F-1B-A EDE-A89-RLA LOCA Seal Relay A89 CB-F-1B-A DG-G20-25Y Auxiliary Sync Check Relay G20 DG-F-2B-A EDE-A89-RS Fast Closure Relay A89 CB-F-1B-A EDE-A74-81 Frequency Relay A74 CB-F-1B-A EDE-A74-87DP Primary Differential Relay A74 CB-F-1B-A EDE-A89-51B Time Overcurrent Relays øA, øB, øC A89 CB-F-1B-A EDE-A74-81X Auxiliary Frequency Relay A74 CB-F-1B-A EDE-A89-60 Voltage Balance Relay A89 CB-F-1B-A EDE-A89-60AX Auxiliary Voltage Balance Relay A89 CB-F-1B-A EDE-A89-60BX Auxiliary Voltage Balance Relay A89 CB-F-1B-A EDE-A89-40 Loss of Field Relays øA, øB A89 CB-F-1B-A EDE-A74-40X Auxiliary Loss of Field Relay A74 CB-F-1B-A EDE-A89-32 Power Directional Relay A89 CB-F-1B-A EDE-A89-TD-1 Lockout Relay Test Device (86B) A89 CB-F-1B-A EDE-A89-TD-2 Lockout Relay Test Device (86DB) A89 CB-F-1B-A EDE-A74-TD-2 Lockout Relay Test Device (86DP) A74 CB-F-1B-A DG-G19-R43L5 & R43L6 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -29 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 46 EDE-SWG-6 (Continued) DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G30-5A Shutdown Relay G30 DG-F-2B-A EDE-A89-51V Time Overcurrent Voltage Restraint Relays øA, øB, øC A89 CB-F-1B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A EDE-A89-51GS Ground Sensor Relay A89 CB-F-1B-A EDE-A74-TD-1 Test Device A74 CB-F-1B-A EDE-CS-9710-1 Control Switch with Indication F81 CB-F-3A-A EDE-HR0-PRIX EPS Auxiliary Relay HR0 CB-F-1B-A EDE-SNS-9737-1 Synchronizing Switch F81 CB-F-3A-A EDE-A74-81X-RES Auxiliary Frequency Relay Resistors A74 CB-F-1B-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A EDE-A74-87DP Reactor Primary Differential Relay Reactor Assembly A74 CB-F-1B-A EDE-FB0-K601B SI Signal Act. Output Relay FB0 CB-F-3A-A EDE-G19-ESS Emergency Start Auxiliary Relay G19 DG-F-2B-A EDE-A74-81Y Time Delay Relay A74 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -30 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 47 DG-CP-76A Diesel Generator 1B Control Panel Cubicle 2 Synchronizing System 310010 B 310524 DG-F-2B-A X X X - G19 EDE-SS-9710 Selector Switch G18 DG-F-2B-A F81-G19/9 F81-G19/1 310102 G19/2c G19/2g 7c 7g DAH-FN-25B DAH-FN-26B EDE-SWG-11B DG-CP-75A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A DG-G19-FU 125 V DC Fuses G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-RAX Auxiliary Relay, Latch G19 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-CS-9710-3 Control Switch G18 DG-F-2B-A EDE-CS-9717-3 Control Switch G19 DG-F-2B-A EDE-CS-9719-3 Control Switch G19 DG-F-2B-A DG-G18-25DG Synchronizing Check Relay G18 DG-F-2B-A DG-G20-25Y Auxiliary Synchronizing Check Relay G20 DG-F-2B-A DG-G20-25Y1 Auxiliary Synchronizing Check Relay G20 DG-F-2B-A EDE-SNS-9737-1 Synchronizing Switch F81 CB-F-3A-A EDE-CS-9710-1 Control Switch F81 CB-F-3A-A EDE-CS-9717-1 Control Switch F81 CB-F-3A-A EDE-CS-9719-1 Control Switch F81 CB-F-3A-A EDE-A87-PT UAT X-2B Inc. Line Potential Transformer A87 CB-F-1B-A EDE-A73-PT RAT X-3B Inc. Line Potential Transformer A73 CB-F-1B-A EDE-A73-PT Bus E6 Potential Transformer A73 CB-F-1B-A EDE-A89-PT DG-1B Inc. Line Potential Transformer A89 CB-F-1B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-RAX Auxiliary Relay, Latch G19 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -31 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 47 DG-CP-76A (Continued) DG-G18-25DG Synchronizing Check Relay G18 DG-F-2B-A EDE-SYN-9711 Synchroscope G18 DG-F-2B-A EDE-ZL-9711 Synchronizing Lights G18 DG-F-2B-A EDE-VM-9711-1 Synchronizing Voltmeter Incoming G18 DG-F-2B-A EDE-VM-9711-2 Synchronizing Voltmeter Running G18 DG-F-2B-A EDE-SYN-9746 Synchroscope F81 CB-F-3A-A EDE-ZL-9746 Synchronizing Lights F81 CB-F-3A-A EDE-VM-9746-1 Voltmeter F81 CB-F-3A-A EDE-VM-9746-2 Voltmeter F81 CB-F-3A-A 48 EDE-SWG-6 4160 V Feed to 480 V Transformer EDE-X-5C for Substation Bus EDE-US-61 310008 B 310442 CB-F-1B-A X X X - A75 EDE-A75-52 4160 V Circuit Breaker A75 CB-F-1B-A A75-AD1 A75-F81/1 310102 A75a A75g A75b A75c A75d CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-SWG-6 EDE-SWG-5 EDE-X-5A EDE-US-51 EDE-A75-FU Fuses A75 CB-F-1B-A EDE-CS-9716 Control Switch A75 CB-F-1B-A EDE-A75-G,R,W Indicating Lights A75 CB-F-1B-A EDE-SS-9716 Selector Switch A75 CB-F-1B-A EDE-A75-52H Truck Operated Contact A75 CB-F-1B-A EDE-A75-86 Lockout Relay A75 CB-F-1B-A EDE-A75-TD-2 Lockout Relay Test Device A75 CB-F-1B-A EDE-A75-50/51 Inst/Time Overcurrent Relays øA, øB, øC A75 CB-F-1B-A EDE-A75-CT Current Transformers (300/5) A75 CB-F-1B-A EDE-A75-AM Ammeter A75 CB-F-1B-A EDE-A75-AS Ammeter Switch A75 CB-F-1B-A EDE-A75-ATR Transducer A75 CB-F-1B-A EDE-A75-TD-1 CT Test Device A75 CB-F-1B-A EDE-A75-51GS Ground Sensor Relay A75 CB-F-1B-A EDE-ZL-9716 Indicating Lights F81 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -32 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 49 EDE-SWG-6 4160 V Feed to 480 V Transformer EDE-X-5D for Substation Bus EDE-US-62 310008 B 310442 CB-F-1B-A X X X - A83 EDE-A83-52 4160 V Circuit Breaker A83 CB-F-1B-A A83-AE1 A83-F81/1 310102 A83a A83g A83b A83c A83d CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-SWG-6 EDE-SWG-5 EDE-X-5B EDE-US-52 EDE-A83-FU Fuses A83 CB-F-1B-A EDE-CS-9713 Control Switch A83 CB-F-1B-A EDE-A83-G,R,W Indicating Lights A83 CB-F-1B-A EDE-SS-9713 Selector Switch A83 CB-F-1B-A EDE-A83-52H Truck Operated Contact A83 CB-F-1B-A EDE-A83-86 Lockout Relay A83 CB-F-1B-A EDE-A83-TD-2 Lockout Relay Test Device A83 CB-F-1B-A EDE-A83-50/51 Inst/Time Overcurrent Relays øA, øB, øC A83 CB-F-1B-A EDE-A83-CT Current Transformers (300/5) A83 CB-F-1B-A EDE-A83-AM Ammeter A83 CB-F-1B-A EDE-A83-AS Ammeter Switch A83 CB-F-1B-A EDE-A83-ATR Transducer A83 CB-F-1B-A EDE-A83-TD-1 CT Test Device A83 CB-F-1B-A EDE-A83-51GS Ground Sensor Relay A83 CB-F-1B-A EDE-ZL-9713 Indicating Lights F81 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -33 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 50 EDE-SWG-6 4160 V Feed to 480 V Transformer EDE-X-5F for Substation Bus EDE-US-63 310008 B 310442 CB-F-1B-A X X X - A90 EDE-A90-52 4160 V Circuit Breaker A90 CB-F-1B-A A90-AF6 A90-F81/1 310102 A90a A90g A90b A90c A90d CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-SWG-6 EDE-SWG-5 EDE-X-5E EDE-US-53 EDE-A90-FU Fuses A90 CB-F-1B-A EDE-CS-9743 Control Switch A90 CB-F-1B-A EDE-A90-G,R,W Indicating Lights A90 CB-F-1B-A EDE-SS-9743 Selector Switch A90 CB-F-1B-A EDE-A90-52H Truck Operated Contact A90 CB-F-1B-A EDE-A90-86 Lockout Relay A90 CB-F-1B-A EDE-A90-TD2 Lockout Relay Test Device A90 CB-F-1B-A EDE-A90-50/51 Inst/Time Overcurrent Relays øA, øB, øC A90 CB-F-1B-A EDE-A90-CT Current Transformers (300/5) A90 CB-F-1B-A EDE-A90-AM Ammeter A90 CB-F-1B-A EDE-A90-AS Ammeter Switch A90 CB-F-1B-A EDE-A90-ATR Transducer A90 CB-F-1B-A EDE-A90-TD1 CT Test Device A90 CB-F-1B-A EDE-A90-51GS Ground Sensor Relay A90 CB-F-1B-A EDE-ZL-9743 Indicating Lights A90 CB-F-1B-A 51 EDE-US-61 480 V Bus 61 Unit Substation 310014 B 310442 CB-F-1B-A X X X - AD2 EDE-AD2-52 480 V AC Circuit Breaker AD2 CB-F-1B-A 310103 AD2a AD2b CBA-FN-32 CBA-FN-33 EDE-X-5C EDE-US-51 EDE-X-5C 4160-480 V Distribution Transformer AD1 CB-F-1B-A EDE-AD3-FU Fuses AD3 CB-F-1B-A EDE-AD1-LA 6 KV Lightning Arrestors (3) AD1 CB-F-1B-A EDE-AD2-CT Current Transformers (2000/5) AD2 CB-F-1B-A EDE-AD3-AM Ammeter AD3 CB-F-1B-A EDE-AD3-AS Ammeter Switch AD3 CB-F-1B-A 52 EDE-US-62 480 V Bus 62 Unit Substation 310014 B 310442 CB-F-1B-A X X X - AE2 EDE-AE2-52 480 V AC Circuit Breaker AE2 CB-F-1B-A 310103 AE2a AE2b CBA-FN-32 CBA-FN-33 EDE-X-5D EDE-US-52 EDE-X-5D 4160-480 V Distribution Transformer AE1 CB-F-1B-A EDE-AE3-FU Fuses AE3 CB-F-1B-A EDE-AE1-LA 6 KV Lightning Arrestors (3) AE1 CB-F-1B-A EDE-AE2-CT Current Transformers (2000/5) AE2 CB-F-1B-A EDE-AE3-AM Ammeter AE3 CB-F-1B-A EDE-AE3-AS Ammeter Switch AE3 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -34 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 53 EDE-US-63 480 V Bus 63 Unit Substation 310052 B 310442 CB-F-1B-A X X X - AF7 EDE-AF7-52 480 V AC Circuit Breaker AF7 CB-F-1B-A 310103 AF7a AF7b CBA-FN-32 CBA-FN-33 EDE-X-5V EDE-US-53 EDE-X-5F 4160-480 V Distribution Transformer AF6 CB-F-1B-A EDE-AF8-FU Fuses AF8 CB-F-1B-A EDE-AF6-LA 6 KV Lightning Arrestors (3) AF7 CB-F-1B-A EDE-AF7-CT Current Transformers (2000/5) AF7 CB-F-1B-A EDE-AF8-AM Ammeter AF8 CB-F-1B-A EDE-AF8-AS Ammeter Switch AF8 CB-F-1B-A 54 EDE-US-61 480 V Feed to 460 V Motor Control Center 612 310014 B 310442 CB-F-1B-A X X X - AD6 EDE-AD6-52 480 V AC Circuit Breaker AD6 CB-F-1B-A AD6-B16 AD6-B16/1 310103 AD6 AD6 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-512 55 EDE-US-61 480 V Feed to 460 V Motor Control Center 614 310014 B 310442 CB-F-1B-A X X X - AA4 EDE-AA4-52 480 V AC Circuit Breaker AA4 CB-F-1B-A AA4-BF0 310103 AA4 AA4 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-514 56 EDE-US-61 480 V Feed to 460 V Motor Control Center 615 310014 B 310442 CB-F-1B-A X X X - AX9 EDE-AX9-52 480 V AC Circuit Breaker AX9 CB-F-1B-A AX9-B4E AX9-B4E/1 310103 AX9 AX9 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-515 57 EDE-US-62 480 V Feed to 460 V Motor Control Center 621 310014 B 310442 CB-F-1B-A X X X - AE8 EDE-AE8-52 480 V AC Circuit Breaker AE8 CB-F-1B-A AE8-B19 AE8-B19/1 310103 AE8 AE8 CBA-FN-32 CBA-FN-33 EDE-US-62 EDE-US-51 EDE-MCC-521 58 EDE-US-62 480 V Feed to 460 V Motor Control Center 622 310014 B 310442 CB-F-1B-A X X X - AW0 EDE-AW0-52 480 V AC Circuit Breaker AW0 CB-F-1B-A AW0-D13 AW0-GZ0 AW0-GZ0/1 F81-GZ0 310103 AWOa AWOe AWOb AWOc CBA-FN-32 CBA-FN-33 EDE-US-62 EDE-US-51 EDE-MCC-522 EDE-CS-9788-2 Control Switch with Indication GZ0 CB-F-1B-A EDE-SS-9788 Selector Switch GZ0 CB-F-1B-A EDE-AW0-52H Truck Operated Contact AW0 CB-F-1B-A EDE-AW0-FU Fuses AW0 CB-F-1B-A EDE-CS-9788-1 Control Switch with Indication F81 CB-F-3A-A EDE-AW0-R,G Indicating Lights AW0 CB-F-1B-A 59 EDE-US-63 480 V Feed to 460 V Motor Control Center 631 310052 B 310442 CB-F-1B-A X X X - AD8 EDE-AD8-52 480 V AC Circuit Breaker AD8 CB-F-1B-A AD8-D18 AD8-B18/1 310103 AD8 AD8 CBA-FN-32 CBA-FN-33 EDE-US-63 EDE-US-53 EDE-MCC-531 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -35 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 60 EDE-US-61 Grounding Transformer 310014 B 310442 CB-F-1B-A X X X - AD3 EDE-AD3-XFMR 3-1ø 1 KVA Transformers AD3 CB-F-1B-A - 310103 AD3b - CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 GRD XFMR EDE-AD3-FU Fuses AD3 CB-F-1B-A EDE-AD3-RES Grounding Resistor AD3 CB-F-1B-A EDE-AD3-VM Ground Voltmeters (3) AD3 CB-F-1B-A EDE-AD3-64 Ground Relay AD3 CB-F-1B-A 61 EDE-US-62 Grounding Transformer 310014 B 310442 CB-F-1B-A X X X - AE3 EDE-AE3-XFMR 3-1ø 1 KVA Transformers AE3 CB-F-1B-A - 310103 AE3b - CBA-FN-32 CBA-FN-33 EDE-US-62 EDE-US-52 GRD XFMR EDE-AE3-FU Fuses AE3 CB-F-1B-A EDE-AE3-RES Grounding Resistor AE3 CB-F-1B-A EDE-AE3-VM Ground Voltmeters (3) AE3 CB-F-1B-A EDE-AE3-64 Ground Relay AE3 CB-F-1B-A 61a EDE-US-61 480 V Feed to 460 V Motor Control Center 611 310014 B 310442 CB-F-1B-A X X X - AD5 EDE-AD5-52 480 V AC Circuit Breaker AD5 CB-F-1B-A AD5-B15 AD5-B15/1 310103 AD5 AD5 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-511 62 EDE-US-63 Grounding Transformer 310052 B 310442 CB-F-1B-A X X X - AF8 EDE-AF8-XFMR 3-1ø 1 KVA Transformers AF8 CB-F-1B-A - 310103 AF8b - CBA-FN-32 CBA-FN-33 EDE-US-63 EDE-US-53 GRD XFMR EDE-AF8-FU Fuses AF8 CB-F-1B-A EDE-AF8-RES Grounding Resistor AF8 CB-F-1B-A EDE-AF8-VM Ground Voltmeters (3) AF8 CB-F-1B-A EDE-AF8-64 Ground Relay AF8 CB-F-1B-A 63 EDE-I-1F Uninterruptible Power Supply 310043 B 310442 CB-F-1B-A X X X - HF6 EDE-DD5-52 460 V AC Circuit Breaker DD5 CB-F-1B-A DD5-HF6/1 DN0-HF6/1 310105 DD5a DD5b CBA-FN-32 CBA-FN-33 EDE-MCC-612 EDE-SWG-11B EDE-I-1E EDE-DN0-72 125 V DC Circuit Breaker DN0 CB-F-1B-A EDE-HF6/2-52 460 V AC Inc. Line Circuit Breaker HF6 CB-F-1B-A EDE-HF6/1-72 125 V DC Inc. Line Circuit Breaker HF6 CB-F-1B-A EDE-HF6/3-52 120 V AC Output Circuit Breaker HF6 CB-F-1B-A 63A EDE-CP-1F Static Transfer Switch 310043 B 310442 CB-F-1B-A X X X - E2B EDE-E2B-F1 300A, 600 V Fuse E2B CB-F-1B-A E2B-HF6 E2B-HF6/1 310105 DD5a DD5b EDE-I-1F CBA-FN-32 CBA-FN-33 EDE-CP-1E 64 EDE-PP-1F Vital Instrument Bus 310043 B 310442 CB-F-1B-A X X X - EH0 EDE-EH0/NC-52 120 V AC Circuit Breaker - Inc. Line from EDE-CP-1F (Norm. Closed) EH0 CB-F-1B-A EH0-E2B 310105 DD5a DD5b EH0a CBA-FN-32 CBA-FN-33 EDE-CP-1F EDE-PP-1E 65 EDE-PP-11F Vital Instrument Bus 310043 B 310442 CB-F-1B-A X X X - E1T EDE-EH0/13-52 120 V AC Circuit Breaker EH0 CB-F-1B-A E1T-EH0 310105 DD5a DD5b E1Ta CBA-FN-32 CBA-FN-33 EDE-PP-1F EDE-PP-11E SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -36 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 66 ED-X-16A 480-120/240 V Containment Lighting Transformer 310032 B 310576 C-F-1-Z X X X - EX6 EDE-D05-52-1 460 V AC Circuit Breaker DO5 CB-F-1B-A D05-H20 EX6-H20 310104 D05a D05b CBA-FN-32 CBA-FN-33 EDE-MCC-631 CAH-FN-1A CAH-FN-1B CAH-FN-1D ED-X-14J EDE-D05-52-2 460 V AC Circuit Breaker DO5 CB-F-1B-A EDE-MM-96 Electrical Penetration H20 C-F-1-Z, ET-F-1C-A 67 ED-PP-8B 120/240 V Distribution Panel 310032 B 310582 C-F-1-Z X X X - EM0 ED-X-16A Containment Lighting Transformer EX6 C-F-1-Z EM0-EX6 ER1-JX3 EX6-JX3 E4G-H41 H41-JX3 310104 DO5a D05b 310106 EM0a CAH-FN-1A CAH-FN-1B CAH-FN-1D ED-X-16A ED-PP-8J ED-EM0-52 250 V AC Circuit Breaker (Main) EM0 C-F-1-Z ED-JX3-42 Lighting Contactor JX3 C-F-2-Z ED-ER1-52 Lighting Panel 250 v AC Circuit Breaker (Main) ER1 C-F-2-Z EDE-MM-584 Fuse Panel E4G ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A 68 EDE-BC-1B 125 V DC Battery Charger 310042 B 310442 CB-F-1B-A X X X - HR6 EDE-DA1-52 460 V AC Circuit Breaker DA1 CB-F-1B-A DA1-HR4 DA1-HR6 310107 DA1a DA1f DA1b DA1c CBA-FN-32 CBA-FN-33 EDE-MCC-E612 EDE-BC-1A EDE-DA1-42 Contactor DA1 CB-F-1B-A EDE-DA1-42X Auxiliary Relay DA1 CB-F-1B-A DG-HR4-HR9(K20) EPS Relay HR4 CB-F-1B-A EDE-HR6/1-52 460 V AC Circuit Breaker - Incoming Feed HR6 CB-F-1B-A EDE-DA1-FU Fuse DA1 CB-F-1B-A 69 EDE-B-1B 125 V DC Battery 310042 B 310442 CB-F-1F-A X X X - HV5 EDE-J76-FU-1,2,3,4 1600A Fuses J76 CB-F-1B-A HV5-J76 HV5-J76/1 310107 DA1a DA1f DA1b DA1c CBA-FN-32 CBA-FN-33 CBA-FN-21B EDE-BC-1B EDE-SWG-11B EDE-B-1A EDE-J76-SH 1000A, 100 MV Shunt J76 CB-F-1B-A EDE-J76-ATR Transducer J76 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -37 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 70 EDE-SWG-11B 125 V DC Switchboard Auxiliary Buses 120 V AC and 125 V DC 310042 B 310442 CB-F-1B-A X X X - DN3 EDE-HR6/2-72 125 V DC Circuit Breaker HR6 CB-F-1B-A DN5-J76 DN5-J76/1 DN4-HR6 310107 DA1a DA1f DA1b DA1c 5b CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-1F EDE-B-1A EDE-BC-1A EDE-SWG-11A EDE-DL5-72 125 V DC Circuit Breaker DL5 CB-F-1B-A EDE-DN4-72 125 V DC Circuit Breaker DN4 CB-F-1B-A EDE-DN5-72 125 V DC Circuit Breaker DN5 CB-F-1B-A EDE-DN3-FU-1,2 125 V DC 10A Fuses DN3 CB-F-1B-A EDE-DN3-27BL Undervoltage Relay DN3 CB-F-1B-A EDE-DN3-27BLL Undervoltage Relay DN3 CB-F-1B-A EDE-DN3-VM DC Voltmeter DN3 CB-F-1B-A EDE-DN3-VTR Voltage Transducer DN3 CB-F-1B-A EDE-DN3-DIO Diodes DN3 CB-F-1B-A EDE-DN3-XS Selector Switch DN3 CB-F-1B-A EDE-DN3-AMY Ammeter Relay DN3 CB-F-1B-A EDE-EH0/5-52 120 V AC Circuit Breaker EH0 CB-F-1B-A DN3-EH0 DN3-J76/1 G1X-J76 310105 EH0a EHOb EDE-DN3-62BL Timing Relay DN3 CB-F-1B-A EDE-DN3-62BLL Timing Relay DN3 CB-F-1B-A EDE-DN4-72 Breaker Operated Contact DN4 CB-F-1B-A EDE-DN4-72STC Circuit Breaker Shut Trip Coil DN4 CB-F-1B-A EDE-J76-ATR Current Transducer J76 CB-F-1B-A EDE-DN3-FU 120 V AC 15A and 1A Fuses DN3 CB-F-1B-A EDE-DN3-52 120 V AC Incoming Feed Circuit Breaker DN3 CB-F-1B-A 71 EDE-PP-111B 125 V DC Distribution Panel 310042 B 310442 CB-F-1B-A X X X - E94 EDE-DN7-72 125 V DC Circuit Breaker DN7 CB-F-1B-A DN7-E94 310107 DA1a DA1f E94a CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-111A EDE-E94-72 125 V DC Circuit Breaker (Main) E94 CB-F-1B-A 72 EDE-PP-112B 125 V DC Distribution Panel 310042 B 310442 CB-F-1B-A X X X - E88 EDE-DN9-72 125 V DC Circuit Breaker DN9 CB-F-1B-A DN9-E88 310107 DA1a DA1f E88a CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-112A EDE-E88-72 125 V DC Circuit Breaker (Main) E88 CB-F-1B-A 73 EDE-PP-113B 125 V DC Distribution Panel 310042 B 310442 CB-F-1B-A X X X - E2U EDE-DP2-72 125 V DC Circuit Breaker DP2 CB-F-1B-A DP2-E2U 310107 DA1a DA1f DA1b E2Ua CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-113A EDE-E2U-72 125 V DC Circuit Breaker (Main) E2U CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -38 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 74 EDE-SWG-6 4160 V SWG 125 V DC Control Bus B 310442 CB-F-1B-A X X X - A73 EDE-E94/1-72 125 V DC Circuit Breaker E94 CB-F-1B-A A73-E94 310107 E94a E94b 310102 5i, 5j, 5k, 5l CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-SWG-5 EDE-A73-8 125 V DC Circuit Breaker (Main) A73 CB-F-1B-A 75 EDE-US-61 480 V Unit Substation 125 V DC Control Bus B 310442 CB-F-1B-A X X X - AD3 EDE-E94/2-72 125 V DC Circuit Breaker E94 CB-F-1B-A AD3-E94 310107 E94a E94b 310103 5q CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-US-51 EDE-AD3-8 125 V DC Circuit Breaker (Main) AD3 CB-F-1B-A 76 EDE-US-62 480 V Unit Substation 125 V DC Control Bus B 310442 CB-F-1B-A X X X - AE3 EDE-E94/3-72 125 V DC Circuit Breaker E94 CB-F-1B-A AE3-E94 310107 E94a E94b 310103 5r CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-US-52 EDE-AE3-8 125 V DC Circuit Breaker (Main) AE3 CB-F-1B-A 77 EDE-US-63 480 V Unit Substation 125 V DC Control Bus B 310442 CB-F-1B-A X X X - AF8 EDE-E94/4-72 125 V DC Circuit Breaker E94 CB-F-1B-A AF8-E94 310107 E94a E94b 310103 5s CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-US-53 EDE-AF8-8 125 V DC Circuit Breaker (Main) AF8 CB-F-1B-A 78 DG-CP-76A Diesel Generator 1B Control Panel Cubicle 3 125 V DC Supply 310010 310042 B 310524 DG-F-2B-A X X X - G20 EDE-DP1-72 125 V DC Circuit Breaker DP1 CB-F-1B-A DP1-G20 310102 DP1a DP1b 310107 DA1a DAH-FN-25B DAH-FN-26B EDE-SWG-11B CBA-FN-32 CBA-FN-33 DG-CP-75A DG-G20-72 125 V DC Circuit Breaker (Main) G20 DG-F-2B-A 79 DG-CP-80 Emergency Power Sequencer 310008 B 310442 CB-F-1B-A X X X - HR3 ED-X-2B Bus E6 UAT Transformer A71 CB-F-1B-A F81-HR3/3 FB0-HR3 A71-HR3 A72-HR3 A73-HR3 A74-HR3 310108 FP31417 E94/5a FP31418 E94/5b FP31429 DG-CP-79 ED-X-3B Bus E6 RAT Transformer A72 CB-F-1B-A EDE-SWG-6 UAT Potential Transformer A73 CB-F-1B-A EDE-SWG-6 Bus E6 DG -1B A74 CB-F-1B-A MM-CP-13 Prot. Cabinet Main Control Board FB0 F81 CB-F-3A-A CB-F-3A-A 80 DG-CP-79 Emergency Power Sequencer 310007 A 310442 CB-F-1A-A X X X - HR1 ED-X-2A Bus E5 UAT Transformer A51 CB-F-1A-A F80-HR1 FB7-HR1 A51-HR1 A52-HR1 A53-HR1 A54-HR1 310108 FP31417 E93/5a FP31418 E93/5b FP31429 DG-CP-80 ED-X-3A Bus E5 RAT Transformer A52 CB-F-1A-A EDE-SWG-5 UAT Potential Transformer A53 CB-F-1A-A EDE-SWG-5 Bus E5 DG -1A A54 CB-F-1A-A MM-CP-12 Prot. Cabinet Main Control Board FB7 F80 CB-F-3A-A CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -39 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 81 EDE-I-1A Uninterruptible Power Supply 310043 A 310435 CB-F-1A-A X X X - HE1 EDE-D27-52 460 V AC Circuit Breaker D27 CB-F-1A-A D27-HE1 DM6-HE1 310105 D27a D27b FP50513 to FP50517 CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-I-1B EDE-DM6-72 125 V DC Circuit Breaker DM6 CB-F-1A-A EDE-HE1/2-52 460 V AC Inc. Line Circuit Breaker HE1 CB-F-1A-A EDE-HE1/1-72 125 V DC Inc. Line Circuit Breaker HE1 CB-F-1A-A EDE-HE1/3-52 120 V AC Output Circuit Breaker HE1 CB-F-1A-A 82 EDE-PP-1A Vital Instrument Bus 310043 A 310435 CB-F-1A-A X X X - E01 EDE-E01-52 120 V AC Circuit Breaker E01 CB-F-1A-A E01-HE1 310105 D27a D27b E01a CBA-FN-19 CBA-FN-20 EDE-I-1A EDE-PP-1B 83 EDE-I-1B Uninterruptible Power Supply 310043 B 310435 CB-F-1B-A X X X - HE2 EDE-D26-52 460 V AC Circuit Breaker D26 CB-F-1B-A D26-HE2 DN8-HE2 310105 D26a D26b FP50513 to FP50517 CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-I-1A EDE-DN8-72 125 V DC Circuit Breaker DN8 CB-F-1B-A EDE-HE2/2-52 460 V AC Inc. Line Circuit Breaker HE2 CB-F-1B-A EDE-HE2/1-72 125 V DC Inc. Line Circuit Breaker HE2 CB-F-1B-A EDE-HE2/3-52 120 V AC Output Circuit Breaker HE2 CB-F-1B-A 84 EDE-PP-1B Vital Instrument Bus 310043 B 310435 CB-F-1B-A X X X - E02 EDE-E02-52 120 V AC Circuit Breaker E02 CB-F-1B-A E02-HE2 310105 D26a D26b E02a CBA-FN-32 CBA-FN-33 EDE-I-1B EDE-PP-1A 85 EDE-I-1C Uninterruptible Power Supply 310043 A 310442 CB-F-1A-A X X X HE3 EDE-D30-52 460 V AC Circuit Breaker D30 CB-F-1A-A D30-HE3 DP9-HE3 310105 D30a D30b FP50513 to FP50517 CBA-FN-19 CBA-FN-20 EDE-SWG-11C EDE-I-1D EDE-DP9-72 125 V DC Circuit Breaker DP9 CB-F-1A-A EDE-HE3/2-52 460 V AC Inc. Line Circuit Breaker HE3 CB-F-1A-A EDE-HE3/1-72 125 V DC Inc. Line Circuit Breaker HE3 CB-F-1A-A EDE-HE3/3-52 120 V AC Output Circuit Breaker HE3 CB-F-1A-A 86 EDE-PP-1C Vital Instrument Bus 310043 C 310442 CB-F-1A-A X X X E03 EDE-E03-52 120 V AC Circuit Breaker E03 CB-F-1A-A E03-HE3 310105 D30a D30b E03a CBA-FN-19 CBA-FN-20 EDE-I-1C EDE-PP-1D SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -40 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 87 EDE-I-1D Uninterruptible Power Supply 310043 B 310435 CB-F-1B-A X X X HE4 EDE-D23-52 460 V AC Circuit Breaker D23 CB-F-1B-A D23-HE4 DR1-HE4 310105 D23a D23b FP50513 to FP50517 CBA-FN-32 CBA-FN-33 EDE-SWG-11D EDE-I-1C EDE-DR1-72 125 V DC Circuit Breaker DR1 CB-F-1B-A EDE-HE4/2-52 460 V AC Inc. Line Circuit Breaker HE4 CB-F-1B-A EDE-HE4/1-72 125 V DC Inc. Line Circuit Breaker HE4 CB-F-1B-A EDE-HE4/3-52 120 V AC Output Circuit Breaker HE4 CB-F-1B-A 88 EDE-PP-1D Vital Instrument Bus 310043 D 310435 CB-F-1B-A X X X E04 EDE-E04-52 120 V AC Circuit Breaker E04 CB-F-1B-A E04-HE4 310105 D23a D23b E04a CBA-FN-32 CBA-FN-33 EDE-I-1D EDE-PP-1C SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -41 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 89 EDE-SWG-11C 125 V DC Switchboard Auxiliary Buses 120 V AC and 125 V DC 310042 A 310442 CB-F-1A-A X X X - DP5 EDE-HR7/2-72 125 V DC Circuit Breaker HR7 CB-F-1A-A DP7-J77 DP7-J77/1 DP6-HR7 G1Y-J77 DP5-J77/1 DP5-EH9 310107 D88a D88f D88c 5c 310105 EH9a EH9b CBA-FN-19 CBA-FN-20 EDE-BC-1C EDE-B-1C EDE-SWG-11D EDE-DL6-72 125 V DC Circuit Breaker DL6 CB-F-1A-A EDE-DP6-72 125 V DC Circuit Breaker DP6 CB-F-1A-A EDE-DP7-72 125 V DC Circuit Breaker DP7 CB-F-1A-A EDE-DP8-72 125 V DC Circuit Breaker DP8 CB-F-1A-A EDE-DP5-FU-1,2 Fuses DP5 CB-F-1A-A EDE-DP5-27BL Undervoltage Relay DP5 CB-F-1A-A EDE-DP5-VM DC Voltmeter DP5 CB-F-1A-A EDE-DP5-VTR Voltage Transducer DP5 CB-F-1A-A EDE-DP5-DIO Diodes DP5 CB-F-1A-A EDE-DP5-XS Selector Switch DP5 CB-F-1A-A EDE-DP5-AMY Ammeter Relay DP5 CB-F-1A-A EDE-EH9/6-52 120 V AC Circuit Breaker EH9 CB-F-1A-A EDE-DP5-27BLL Undervoltage Relay DP5 CB-F-1A-A EDE-DP5-62BL Timing Relay DP5 CB-F-1A-A EDE-DP5-62BLL Timing Relay DP5 CB-F-1A-A EDE-DP6-72 Breaker Operated Contact DP6 CB-F-1A-A EDE-DP6-72STC Circuit Breaker Shunt Trip Coil DP6 CB-F-1A-A EDE-J77-ATR Current Transducer J77 CB-F-1A-A EDE-DP5-52 120 V AC Inc. Feed Circuit Breaker DP5 CB-F-1A-A EDE-DP5-FU 120 V AC 15A and 1A Fuses DP5 CB-F-1A-A 90 EDE-BC-1C 125 V DC Battery Charger 310042 A 310442 CB-F-1A-A X X X - HR7 EDE-D88-52 460 V AC Circuit Breaker D88 CB-F-1A-A D88-HR7 D88-HR2 310107 D88a D88f D88b CBA-FN-19 CBA-FN-20 EDE-MCC-E521 EDE-BC-1D EDE-D88-42 Contactor D88 CB-F-1A-A EDE-D88-42X Auxiliary Relay D88 CB-F-1A-A DG-HR2-HR9 EPS Relay HR2 CB-F-1A-A EDE-HR7/1-52 460 V AC Circuit Breaker - Incoming Feed HR7 CB-F-1A-A EDE-D88-FU Fuse D88 CB-F-1A-A 91 EDE-B-1C 125 V DC Battery 310042 A 310442 CB-F-1E-A X X X - HV6 EDE-J77-FU-1,2,3,4 1600A Fuses J77 CB-F-1A-A HV6-J77 HV6-J77/1 310107 D88a D88f CBA-FN-19 CBA-FN-20 EDE-B-1C EDE-J77-SH 1000A, 100 MW Shunt J77 CB-F-1A-A EDE-J77-ATR Transducer J77 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -42 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 92 EDE-SWG-11D 125 V DC Switchboard Auxiliary Buses 120 V DC and 125 V DC 310042 B 310442 CB-F-1B-A X X X - DQ7 EDE-HR8/2-72 125 V DC Circuit Breaker HR8 CB-F-1B-A DQ7-J78/1 DQ9-J78 DQ9-J78/1 DQ8-HR8 D1Z-J78 310107 DB2a DB2f DB2b DB2c 5d CBA-FN-32 CBA-FN-33 EDE-BC-1D EDE-B-1D EDE-SWG-11C EDE-DL7-72 125 V DC Circuit Breaker DL7 CB-F-1B-A EDE-DQ8-72 125 V DC Circuit Breaker DQ8 CB-F-1B-A EDE-DQ9-72 125 V DC Circuit Breaker DQ9 CB-F-1B-A EDE-DQ0-72 125 V DC Circuit Breaker DQ0 CB-F-1B-A DQ7-EH0 310105 EH0a EHOb EDE-DQ7-FU-1,2 Fuses DQ7 CB-F-1B-A EDE-DQ7-27BL Undervoltage Relay DQ7 CB-F-1B-A EDE-DQ7-VM DC Voltmeter DQ7 CB-F-1B-A EDE-DQ7-VTR Voltage Transducer DQ7 CB-F-1B-A EDE-DQ7-DIO Diodes DQ7 CB-F-1B-A EDE-DQ7-XS Selector Switch DQ7 CB-F-1B-A EDE-DQ7-AMY Ammeter Relay DQ7 CB-F-1B-A EDE-DQ7-27BLL Undervoltage Relay DQ7 CB-F-1B-A EDE-EH0/6-52 120 V AC Circuit Breaker EH0 CB-F-1B-A EDE-DQ7-62BL Timing Relay DQ7 CB-F-1B-A EDE-DQ7-62BLL Timing Relay DQ7 CB-F-1B-A EDE-DQ8-72 Breaker Operated Contact DQ8 CB-F-1B-A EDE-DQ8-72STC Circuit Breaker Shunt Trip Coil DQ8 CB-F-1B-A EDE-J77-ATR Current Transducer J77 CB-F-1B-A EDE-DQ7-52 120 V AC Inc. Feed Circuit Breaker DQ7 CB-F-1B-A EDE-DQ7-FU 120 V AC 15A and 1A Fuses DQ7 CB-F-1B-A 93 EDE-BC-1D 125 V DC Battery Charger 310042 B 310442 CB-F-1B-A X X X - HR8 EDE-DB2-52 460 V AC Circuit Breaker DB2 CB-F-1B-A DB2-HR8 DB2-HR4 310107 DB2a DB2f DB2b CBA-FN-19 CBA-FN-20 EDE-MCC-E621 EDE-BC-1C EDE-DB2-42 Contactor DB2 CB-F-1B-A EDE-DB2-42X Auxiliary Relay DB2 CB-F-1B-A DG-HR4-HR9 EPS Relay HR4 CB-F-1B-A EDE-HR8/1-52 460 V AC Circuit Breaker - Incoming Feed HR8 CB-F-1B-A EDE-DB2-FU Fuse DB2 CB-F-1B-A 94 EDE-B-1D 125 V DC Battery 310042 B 310442 CB-F-1G-A X X X - HV7 EDE-J78-FU-1,2,3,4 1600A Fuses J78 CB-F-1B-A HV7-J78 HV7-J78/1 310107 DB2a DB2f DB2a DB2f CBA-FN-32 CBA-FN-33 EDE-B-1C EDE-J78-SH 1000A, 100 MW Shunt J78 CB-F-1B-A EDE-J78-ATR Transducer J78 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -43 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 95 ED-I-4 Uninterruptible Power Supply 310054 A 310292 NES-F-1A-Z X X X - HS7 EDE-BR3-52 460 V AC Circuit Breaker BR3 DG-F-2A-A BR3-HR2 BR3-HS7 DR2-HS7 310105 BR3a BR3c BR3b ED-SWG-12B ED-DR2-72 125 V DC Circuit Breaker DR2 TB-F-1A-Z ED-HS7-52 460 V AC Inc. Line Breaker HS7 NES-F-1A-Z ED-HS7-72 125 V DC Inc. Line Breaker HS7 NES-F-1A-Z ED-HS7-52 120 V AC Output Breaker HS7 NES-F-1A-Z EDE-BR3-42 Contactor BR3 DG-F-2A-A EDE-BR3-42X Auxiliary Relay BR3 DG-F-2A-A EDE-BR3-FU 2A Fuse BR3 DG-F-2A-A DG-HR2-HR9 EPS Relay HR2 CB-F-1A-A 96 ED-PP-5 Non-Vital Instrument Bus 310054 A 310292 NES-F-1A-Z X X X - EJ9 ED-EJ9-52 120 V AC Inc. Line Breaker Non -Automatic EJ9 NES-F-1A-Z EJ9-JB9 EJ9-JB9/1 310105 BR3a BR3c ED-I-4 ED-CP-532 96A ED-CP-532 Transfer Switch for ED-PP-5 310054 A 310292 NES-F-1A-Z X X X - JB9 - - HS7 EJ9 NES-F-1A-Z NES-F-1A-Z HS7-JB9 HS7-JB9/1 EJ9-JB9 EJ9-JB9/1 310105 BR3a BR3c ED-I-4 ED-PP-5 97 ED-BC-2B 125 V DC Battery Charger 310059 A 310328 TB-F-1A-Z X X X - HS4 ED-CW3-52 460 V AC Circuit Breaker CW3 TB-F-2-Z CW3-HS4 CW3-HR2 310107 CW3a CW3f CW3b ED-MCC-E523 ED-CW3-42 Contactor CW3 TB-F-2-Z ED-CW3-42X Auxiliary Relay CW3 TB-F-2-Z DG-HR2-HR9 EPS Relay HR2 CB-F-1A-A ED-HS4-52 460 V AC Circuit Breaker - Inc. Feed HS4 TB-F-1A-Z ED-CW3-FU Fuse CW3 TB-F-2-Z 98 ED-B-2B 125 V DC Battery 310059 A 310328 TB-F-1B-A X X X - HS5 ED-DS8-SH 1500A, 100 mV Shunt DS8 TB-F-1A-Z DS8-HS5 DS8-HS5/1 310107 CW3a CW3f ED-DS6-ATR Transducer DS6 TB-F-1A-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -44 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 99 ED-SWG-12B 125 V DC Switchgear Auxiliary Buses 120 V AC and 125 V DC 310059 A 310328 TB-F-1A-Z X X X - DS6 ED-HS4-72 125 V DC Circuit Breaker HS4 TB-F-1A-Z DS7-HS4 310107 CW3a CW3f ED-BC-2B ED-B-2B ED-DL9-72 125 V DC Circuit Breaker DL9 TB-F-1A-Z ED-DS7-72 125 V DC Circuit Breaker DS7 TB-F-1A-Z ED-DS8-72 125 V DC Circuit Breaker DS8 TB-F-1A-Z ED-DS6-FU-1,2 15A Fuses DS6 TB-F-1A-Z ED-DS6-27BL Undervoltage Relay DS6 TB-F-1A-Z ED-DS6-27BLL Undervoltage Relay DS6 TB-F-1A-Z ED-DS6-VM DC Voltmeter DS6 TB-F-1A-Z ED-DS6-VTR Voltage Transducer DS6 TB-F-1A-Z ED-DS6-DIO Diodes DS6 TB-F-1A-Z ED-DS6-XS Selector Switch DS6 TB-F-1A-Z ED-DS6-AMY Ammeter Relay DS6 TB-F-1A-Z ED-E20/8-52 120 V AC Circuit Breaker E20 TB-F-1A-Z DS6-E20 310106 E20a E20c ED-DS6-62BL Timing Relay DS6 TB-F-1A-Z ED-DS6-62BLL Timing Relay DS6 TB-F-1A-Z ED-DS7-72STC Circuit Breaker Shunt Trip Coil DS7 TB-F-1A-Z ED-DS7-72 Breaker Operated Contact DS7 TB-F-1A-Z ED-DS6-ATR Current Transducer DS6 TB-F-1A-Z 100 ED-PP-121B 125 V DC Distribution Panel 310059 A 310292 NES-F-1A-Z X X X - E97 ED-DQ1-72 125 V DC Circuit Breaker DQ1 TB-F-1A-Z DQ1-E97 A03-E97 A18-E97 310107 CW3a CW3f E97a ED-SWG-12B ED-E97-72 125 V DC Circuit Breaker E97 NES-F-1A-Z 101 ED-PP-122B 125 V DC Distribution Panel 310059 A 310431 CB-F-1A-A X X X - E89 ED-DQ3-72 125 V DC Circuit Breaker DQ3 TB-F-1A-Z DQ3-E89 310107 CW3a CW3f E89a ED-SWG-12B ED-E89-72 125 V DC Circuit Breaker E89 CB-F-1A-A 102 EDE-US-51 480 V Feed to 460 V Motor Control Center 511 310023 A 310442 CB-F-1A-A X X X - AB5 EDE-AB5-52 480 V AC Circuit Breaker AB5 CB-F-1A-A AB5-B09 AB5-B09/1 310103 AB5 AB5 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-611 103 EDE-US-51 480 V Feed to 460 V Motor Control Center 513 310023 A 310442 CB-F-1A-A X X X - AV6 EDE-AV6-52 480 V AC Circuit Breaker AV6 CB-F-1A-A AV6-C14 310103 AV6 AV6 CBA-FN-19 CBA-FN-20 EDE-US-51 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -45 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 104 ED-BC-2A 125 V DC Battery Charger 310059 A 310328 TB-F-1A-Z X X X - HS2 ED-CN3-52 460 V AC Circuit Breaker CN3 TB-F-2-Z CN3-HS2 CN3-HR2 310107 CN3a CN3f CN3b ED-MCC-E523 ED-CN3-42 Contactor CN3 TB-F-2-Z ED-CN3-42X Auxiliary Relay CN3 TB-F-2-Z DG-HR2-HR9 EPS Relay HR2 CB-F-1A-A ED-HS2-52 460 V AC Circuit Breaker - Inc. Feed HS2 TB-F-1A-Z ED-CN3-FU Fuse CN3 TB-F-2-Z 105 ED-B-2A 125 V DC Battery 310059 A 310328 TB-F-1B-A X X X - HS3 ED-DR8-SH 1500A, 100 mV Shunt DR8 TB-F-1A-Z DR8-HS3 310107 CN3a CN3f ED-DR6-ATR Transducer DR6 TB-F-1A-Z DR8-HS3/1 106 ED-SWG-12A 125 V DC Switchgear Auxiliary Buses 120 V AC and 125 V DC 310059 A 310328 TB-F-1A-Z X X X - DR6 ED-HS2-72 125 V DC circuit Breaker HS2 TB-F-1A-Z DR7-HS2 310107 CN3a CN3f ED-BC-2A ED-B-2A ED-DL8-72 125 V DC circuit Breaker DL8 TB-F-1A-Z ED-DR7-72 125 V DC circuit Breaker DR7 TB-F-1A-Z ED-DR8-72 125 V DC circuit Breaker DR8 TB-F-1A-Z ED-DR6-FU-1,2 15A Fuses DR6 TB-F-1A-Z ED-DR6-27BL Undervoltage Relay DR6 TB-F-1A-Z ED-DR6-27BLL Undervoltage Relay DR6 TB-F-1A-Z ED-DR6-VM DC Voltmeter DR6 TB-F-1A-Z ED-DR6-VTR Voltage Transducer DR6 TB-F-1A-Z ED-DR6-DIO Diodes DR6 TB-F-1A-Z ED-DR6-XS Selector Switch DR6 TB-F-1A-Z ED-DR6-AMY Ammeter Relay DR6 TB-F-1A-Z ED-E20/17-52 120 V DC Circuit Breaker E20 TB-F-1A-Z DR6-E20 310106 E20a E20c ED-DR6-62BL Timing Relay DR6 TB-F-1A-Z ED-DR6-62BLL Timing Relay DR6 TB-F-1A-Z ED-DR7-72STC Circuit Breaker Shunt Trip Coil DR7 TB-F-1A-Z ED-DR7-72 Breaker Operated Contact DR7 TB-F-1A-Z ED-DR6-ATR Current Transducer DR6 TB-F-1A-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.17 -46 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 107 ED-PP-122A 125 V DC Distribution Panel 310059 A 310328 TB-F-1A-A X X X - E91 ED-DS4-72 125 V DC Circuit Breaker DS4 TB-F-1A-Z DS4-E91 DS4-E91/1 A16-E91 310107 CN3a CN3f E91a E91b ED-SWG-12A ED-E91-72 125 V DC Circuit Breaker E91 TB-F-1A-A 108 ED-PP-3C Non-Vital Instrument Bus 310043 A 310442 CB-F-1A-A X X X - EH7 ED-EH7-52 120 V AC Circuit Breaker EH7 CB-F-1A-A E03-EH7 310105 D30a D30b EH7a CBA-FN-19 CBA-FN-20 EDE-I-1C EDE-PP-1C SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -1 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 DG-DG-1A Diesel Generator 1A DG-20462 A 310524 DG-F-2A-A X X X X HA1 DG-CS-9510-2 Control Switch (Push Button) G07 DG-F-2A-A A54-G06/5 A54-G29 G06-G29 G06-G29/1 G06-HR2 G06-G29/2 G07-G29 E93-G29/1 F80-FB7 F80-G06/8 F80-G06/9 F80-G07/9 F80-G07/F F80-G07/G 310857 E93/8a E93/8n E93/8b E93/8p E93/8c E93/8d E93/8e E93/8f E93/8g E93/8r CBA-FN-19 CBA-FN-20 DAH-FN-25A DAH-FN-26A EDE-PP-111A D/G Starting Air DG-DG-1B DG-CS-9511 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9512-3 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9512-4 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9517-2 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9518-2 Control Switch (Push Button) G07 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A DG-G29-OP2 Oil Pressure Relay G29 DG-F-2A-A DG-G29-CR1 Ready for Auto Start Relay G29 DG-F-2A-A DG-G29-4A Start Relay G29 DG-F-2A-A DG-G29-T2A Cranking Time Control Time Delay Relay G29 DG-F-2A-A DG-ZL-9580-9 Start Ckt No 1 Signal Indicating Light G07 DG-F-2A-A DG-G29-ES1 Emergency Start Relay G29 DG-F-2A-A DG-G10-TSR1 Test Start Relay G10 DG-F-2A-A DG-G10-TSR2 Test Start Relay G10 DG-F-2A-A DG-G10-TSR3 Test Start Relay G10 DG-F-2A-A DG-G10-RDT Ramp Down Time Relay G10 DG-F-2A-A DG-G07-IOT Idle Operate Time Relay G07 DG-F-2A-A DG-G06-LSRX Low Speed Aux Relay G06 DG-F-2A-A DG-FY-AS1 Air Start Solenoid Valve G29 DG-F-2A-A DG-G29-OP3 Oil Pressure Relay G29 DG-F-2A-A DG-G29-CR2 Ready for Auto Start Relay G29 DG-F-2A-A DG-G29-4B Start Relay G29 DG-F-2A-A DG-G29-T2B Cranking Time Control Time Delay Relay G29 DG-F-2A-A

.* Table notes on last page of table.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -2 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-ZL-9580-10 Start Ckt No 2 Signal Indicating Light G07 DG-F-2A-A DG-G29-ES2 Emergency Start Rela y G29 DG-F-2A-A DG-FY-AS2 Air Start Solenoid Valve G29 DG-F-2A-A DG-G29-OP4 Oil Pressure Relay G29 DG-F-2A-A DG-G29-5E Emergency Stop Relay G29 DG-F-2A-A DG-G29-5 Normal Stop Relay G29 DG-F-2A-A DG-G29-5A Shutdown Relay G29 DG-F-2A-A DG-FY-SDS Shutdown Solenoid Valve G29 DG-F-2A-A DG-FY-CSV-A Jacket Coolant Auxiliary Valves Solenoid G29 DG-F-2A-A DG-G29-T3A Alarm Set Time Delay Relay G29 DG-F-2A-A DG-G29-TR Engine Velocity Transmitter G29 DG-F-2A-A DG-FY-ISV-A Intercooler Auxiliary Valves Solenoid G29 DG-F-2A-A DG-G29-SG Signal Generator G29 DG-F-2A-A DG-G29-HSR High-Speed Relay G29 DG-F-2A-A DG-G29-LSR Low-Speed Relay G29 DG-F-2A-A DG-G29-ASR Starting Air Shutoff Relay G29 DG-F-2A-A DG-G29-IPC Coolant Pump Control Relay G29 DG-F-2A-A DG-G29-BDR Barring Device Relay G29 DG-F-2A-A DG-G29-ASA Air Start Relay G29 DG-F-2A-A DG-G29-ASB Air Start Relay G29 DG-F-2A-A DG-FB7-K603A Protection System Relay FB7 CB-F-3A-A EDE-CS-9518-1 Control Switch F80 CB-F-3A-A EDE-CS-9517-1 Control Switch F80 CB-F-3A-A EDE-CS-9510-1 Control Switch F80 CB-F-3A-A DG-FB7-K608A Protection System Output Relay FB7 CB-F-3A-A EDE-CS-9512-1 Control Switch F80 CB-F-3A-A EDE-CS-9512-2 Control Switch F80 CB-F-3A-A EDE-ZL-9574 Monitoring Circuit Indication Light G07 DG-F-2A-A DG-G29-TACH Tachometer G29 DG-F-2A-A DG-G29-SFR Start Failure Relay G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -3 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) EDE-ZL-9574-1 Monitoring Circuit Indicating Light G29 DG-F-2A-A DG-G29-SDR Engine Trouble Shutdown Relay G29 DG-F-2A-A DG-G29-EOR Engine Overspeed Relay G29 DG-F-2A-A EDE-A69-RLA SI Signal Lockout Relay A69 CB-F-1A-A DG-G29-OTH High Oil Temperature Relay G29 DG-F-2A-A DG-G29-CTH High Coolant Temperature Relay G29 DG-F-2A-A EDE-A54-TD2 Test Device A54 CB-F-1A-A EDE-A69-TD2 Test Device A69 CB-F-1A-A DG-G29-EST Emergency Start Time Delay Relay G29 DG-F-2A-A DG-G29-ESX Emergency Start Auxiliary Relay G29 DG-F-2A-A DG-G29-RA1 Air Pressure Auxiliary Relay G29 DG-F-2A-A DG-G29-RA2 Air Pressure Auxiliary Relay G29 DG-F-2A-A DG-G29-CF3 Power Available Relay G29 DG-F-2A-A DG-G29-CF1 Power Available Relay G29 DG-F-2A-A DG-G29-CF2 Power Available Relay G29 DG-F-2A-A DG-G29-CF5 Power Available Relay G29 DG-F-2A-A DG-G29-OP1 Oil Pressure Relay G29 DG-F-2A-A DG-G29-FPL Fuel Pressure Relay G29 DG-F-2A-A DG-G29-CPL Jacket Coolant Pressure Relay G29 DG-F-2A-A DG-G29-IPL Intercooler Pressure Relay G29 DG-F-2A-A DG-PS-OPL1 Oil Low Pressure Switch G29 DG-F-2A-A DG-PS-FPLA Fuel Low Pressure Switch G29 DG-F-2A-A DG-PS-CPLA Jacket Coolant Low Pressure Switch G29 DG-F-2A-A DG-PS-IPLA Intercooler Low Pressure Switch G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -4 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-G29-OPC Oil Pump Control Relay G29 DG-F-2A-A DG-G29-FPC Auxiliary Fuel Oil Pump Control Relay G29 DG-F-2A-A DG-G29-CPC Coolant Pump Control Relay G29 DG-F-2A-A DG-G29-CF4 Power Available Relay G29 DG-F-2A-A DG-G07-R43L1 Selector Switch Auxiliary Latch Relay (Local) G07 DG-F-2A-A DG-G07-R43L2 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G07 DG-F-2A-A DG-G07-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G07 DG-F-2A-A DG-G07-R43R2 Selector Switch Auxiliary Latch Relay (Remote) G07 DG-F-2A-A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-HR2-PR1 EPS Auxiliary Relay HR2 CB-F-1A-A DG-HR2-PR1X EPS Auxiliary Relay HR2 CB-F-1A-A DG-G29-D1 P-N Junction Diode G29 DG-F-2A-A DG-SS-E0S Engine Overspeed Switch G29 DG-F-2A-A DG-PS-APL1 Air Pressure Low Switch G29 DG-F-2A-A DG-PS-APL2 Air Pressure Low Switch G29 DG-F-2A-A DG-PS-CPS Coolant Pressure Switch G29 DG-F-2A-A DG-PS-OPL2 Oil Low Pressure Switch G29 DG-F-2A-A DG-PS-OPL3 Oil Low Pressure Switch G29 DG-F-2A-A DG-PS-OPL4 Oil Low Pressure Switch G29 DG-F-2A-A DG-G29-CTH-1 Coolant High Temperature Auxiliary Relay G29 DG-F-2A-A DG-G29-OTH-1 Oil High Temperature Auxiliary Relay G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -5 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-ZS-BD1 Barring Device Position Switch G29 DG-F-2A-A DG-ZS-BD2 Barring Device Position Switch G29 DG-F-2A-A DG-G29-FU 10 Amp Fuses (10) G29 DG-F-2A-A EDE-A54-86DP DG Primary Protection Lockout Relay A54 CB-F-1A-A EDE-A69-86DB DG Backup Protection Lockout Relay A69 CB-F-1A-A DG-G29-TRP TR Control Power Relay G29 DG-F-2A-A DG-G29-5B Shutdown Auxiliary Relay G29 DG-F-2A-A EDE-A54-TS Test Start Control Switch A54 CB-F-1A-A EDE-G07-FU-17,18 6 Amp Fuses (2) G07 DG-F-2A-A DM9-G10 F80-G07/8 310102 G07/2a G07/2g G07/2b G07/2c DM9a DM9b DAH-FN-25A DAH-FN-25B DG-CP-75A EDE-SWG-11A EDE-SS-9700 Selector Switch G06 DG-F-2A-A DG-G07-CF6 Auxiliary Relay G07 DG-F-2A-A DG-G07-R43L1 Selector Switch Auxiliary Latch Relay (Local) G07 DG-F-2A-A DG-G07-R43L2 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L3 Selector Switch

Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L5 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R2 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G07 DG-F-2A-A DG-G07-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G07 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -6 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) EDE-SNS-9763-1 Selector Switch F80 CB-F-3A-A EDE-CS-9707-1 Control Switch F80 CB-F-3A-A EDE-SNS-9763-2 Selector Switch G06 DG-F-2A-A EDE-CS-9707-3 Control Switch G07 DG-F-2A-A EDE-G06-FU-9,10 50 Amp Fuses G06 DG-F-2A-A A69-G06 G06-HF7 A69-HN0 DM9-G10 310102 HA1a HA1c HA1b HA1d DM9a DM9b DAH-FN-25A DAH-FN-26A CBA-FN-19 CBA-FN-29 EDE-SWG-11A DG-A69,XFMR Grounding Transformer A69 CB-F-1A-A DG-HF7-XF DG Field HF7 DG-F-2A-A DG-G07-SEVR-PC Static Exciter Voltage Regulator Power Chassis G06 DG-F-2A-A DG-SM-9585 Governor Control (2301A) G06 DG-F-2A-A DG-GT3-PT1 Potential Transformer GT3 DG-F-2A-A DG-GT3-PT2 Potential Transformer GT3 DB-F-2A-A DG-GT3-PPT4 Power Transformer GT3 DB-F-2A-A DG-HNO-NCB DG Neutral Connection Box HN0 DG-F-2A-A DG-GT3-CCT Current Transformer 2000/5 GT3 DG-F-2A-A DG-G06-K2 Field Flashing Contractor G06 DB-F-2A-A DG-G10-IDR1 Isochronous Droop Relay G10 DG-F-2A-A EDE-A69-60 Voltage Balance Relays A69 CB-F-1A-A DG-G06-64F Generator Field Failure Relay G06 DG-F-2A-A DG-G10-SEVR-CC Static Exciter Voltage Regulator Control Chassis G10 DG-F-2A-A DG-GT3-XCT1,2,3 Generator Current Transformers (2000/5) GT3 DG-F-2A-A DG-VM-9702-2 Field Voltmeter G10 DG-F-2A-A DG-G10-DCT Field Voltage Transducer G10 DG-F-2A-A DG-G06-SH 50 MV Field Shunt G06 DG-F-2A-A DG-AM-9702-2 DC Field Ammeter G10 DG-F-2A-A DG-G10-ATR Current Transducer G10 DG-F-2A-A DG-G10-CF10 Loss of Power Relay G10 DG-F-2A-A DG-A69-64 Ground Fault Sensing Relay A69 CB-F-1A-A DG-G10-FU-22,23 1 Amp Fuses G10 DG-F-2A-A DG-G07-IL10 Diode Failure Light G07 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -7 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) EDE-G06-FU-1,2 10 Amp Fuses (2) G06 DG-F-2A-A G06-G29/5 DM9-G10 F80-G06/3 F80-G06/4 F80-G06/5 F80-G10/1 310102 G06/1a G06/1f G06/1b G06/1c G06/1d DM9a DM9b DAH-FN-25A DAH-FN-26A DG-CP-75A EDE-SWG-11A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A EDE-CS-9820-2 Control Switch (Push Button) G10 DG-F-2A-A DG-G29-HSR High Speed Relay G29 DG-F-2A-A DG-G29-LSR Low Speed Relay G29 DG-F-2A-A DG-G29-ES1 Emergency Start Relay G29 DG-F-2A-A DG-G29-ES2 Emergency Start Relay G29 DG-F-2A-A DG-SS-9585 Selector Switch G07 DG-F-2A-A DG-ZL-9580-11 Field Flash Signal Indicating Light G10 DG-F-2A-A DG-G07-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G07 DG-F-2A-A DG-G29-5A DG - Shutdown Relay G29 DG-F-2A-A DG-G06-LSRX Low Speed Auxiliary Relay G06 DG-F-2A-A DG-G06-LSRXX Time Delay Relay G06 DG-F-2A-A EDE-CS-9801-1 Push Button G10 DG-F-2A-A EDE-CS-9801-2 Push Button G10 DG-F-2A-A DG-G06-SERV-PC Static Exciter Voltage Regulatory Power Chassis G06 DG-F-2A-A DG-G10-NM Null Meter G10 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-CS-9821-2 Control Switch G10 DG-F-2A-A EDE-CS-9822-2 Control Switch G10 DG-F-2A-A DG-G10-RR Regulator Relay G10 DG-F-2A-A DG-G10-SERV-CC Static Exciter Voltage Regulator Control Chassis G10 DG-F-2A-A DG-G10-CF-8 Loss of Power Relay G10 DG-F-2A-A EDE-CS-9820-1 Push Button Switch F80 CB-F-3A-A EDE-CS-9822-1 Control Switch F80 CB-F-3A-A EDE-CS-9821-1 Control Switch F80 CB-F-3A-A EDE-VM-9782 Null Voltmeter F80 CB-F-3A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -8 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) EDE-G06-FU-3,4 6 Amp Fuses (2) G06 DG-F-2A-A G06-G29/8 G06-G29/9 G06-G29/6 F80-G06/6 EC7-G10 EC7-G07 EC7-HR2 DM9-G10 310102 G06/2a G06/2d G06/2b G06/2e DM9a DM9b DAH-FN-25A DAH-FN-26A DG-CP-75A EDE-SWG-11A DG-G10-IDR2 Isochronous Droop Relay G10 DG-F-2A-A DG-SZ-9585 Governor Actuator G29 DG-F-2A-A DG-SC-9585 Digital Reference Unit (DRU) G06 DG-F-2A-A DG-SM-9585 2301A Governor Controller G06 DG-F-2A-A DG-ST-9585 Magnetic Pickup (MPU-1) G29 DG-F-2A-A DG-SS-9585 Selector Switch G07 DG-F-2A-A DG-G10-TSR1 Test Start Relay G10 DG-F-2A-A DG-G10-TSR2 Test Start Relay G10 DG-F-2A-A DG-G10-TSR3 Test Start Relay G10 DG-F-2A-A DG-G10-R21 Speed Adjust Auxiliary Relay G10 DG-F-2A-A DG-G10-RDT Ramp Down Time Relay G10 DG-F-2A-A DG-G07-IOT Idle Operate Time Relay G07 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-CS-9823-2 Control Switch G06 DG-F-2A-A DG-G06-LSRX Low Speed Auxiliary G06 DG-F-2A-A DG-G29-ES1 Emergency Start Auxiliary Relay G29 DG-F-2A-A DG-G29-ES2 Emergency Start Auxiliary Relay G29 DG-F-2A-A DG-G07-ESS Emergency Start Auxiliary Relay G07 DG-F-2A-A DG-G10-CF-9 Loss of Power Relay G10 DG-F-2A-A EDE-CS-9823-1 Control Switch F80 CB-F-3A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-HR2-PR1 EPS Auxiliary Relay HR2 CB-F-1A-A DG-HR2-HR8 EPS Auxiliary Relay HR2 CB-F-1A-A DG-EC7-R1 Auxiliary Relay EC7 DG-F-2A-A DG-G10-IDR4 Isochronous Droop Relay G10 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -9 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) EDE-G10-FU-7,8 10 Amp Fuses (2) G10 DG-F-2A-A A54-G10/1 A69-G10 G10-G29 DM9-G10 G06-G29/4 F80-G07/8 A54-G07/4 F80-G06/7 F80-G07/7 G10a G10e G10b G10c DM9a DM9b DAH-FN-25A DAH-FN-26A CBA-FN-19 CBA-FN-20 DG-CP-75A EDE-SWG-11A DG-G29-CR1 Auto Start Ready Relay G29 DG-F-2A-A DG-G29-CR2 Auto Start Ready Relay G29 DG-F-2A-A DG-G29-RA1 Air Pressure Auxiliary Relay G29 DG-F-2A-A DG-G29-RA2 Air Pressure Auxiliary Relay G29 DG-F-2A-A DG-G07-R43L3 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-ESS Emergency Start Auxiliary Relay G07 DG-F-2A-A DG-G10-RR Regulator Relay G10 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L5 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-64F Generator Field Ground Relay G06 DG-F-2A-A DG-G10-64FX Generator Field Ground Auxiliary Relay G10 DG-F-2A-A DG-G07-64FXA Generator Field Ground Auxiliary Relay G07 DG-F-2A-A EDE-CS-9824-2 Control Switch G10 DG-F-2A-A DG-G10-23 Thermostat G10 DG-F-2A-A DG-G07-R-DNA Diesel Not Available Auxiliary Relay G07 DG-F-2A-A DG-G07-R-B/I SW CT Bypass/MOP Auxiliary Relay G07 DG-F-2A-A DG-G10-23X Thermostat Auxiliary Relay G10 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -10 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-ZL-9580-12 Indicating Light F80 CB-F-3A-A DG-G29-ESX Emergency Start Aux Relay G29 DG-F-2A-A EDE-ZL-9580-8 Indicating Light F80 CB-F-3A-A EDE-ZL-9518-1 Indicating Light F80 CG-F-3A-A EDE-CS-9824-1 Indicating Light F80 CB-F-3A-A EDE-ZL-9824-1 Indicating Light F80 CB-F-3A-A EDE-SNS-9763-1 Synchronizing Switch F80 CB-F-3A-A EDE-ZL-9802-1 Indicating Light F80 CB-F-3A-A EDE-CS-9824-1 Control Switch F80 CB-F-3A-A DG-A69-RLA LOCA Seal Relay A69 CB-F-1A-A EDE-ZL-9580-6 Indicating Light F80 CB-F-3A-A DG-G10-IDR1 Isochronous Droop Relay G10 DG-F-2A-A DG-G10-IDR2 Isochronous Droop Relay G10 DG-F-2A-A DG-G10-IDR3 Isochronous Droop Relay G10 DG-F-2A-A EDE-ZL-9802-2 Indicating Light G07 DG-F-2A-A DG-G07-IDR4 Isochronous Droop Relay G10 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDS-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A51-52S Circuit Breaker Operated Contact A51 CB-F-1A-A EDE-A52-52S Circuit Breaker Operated Contact A52 CB-F-1A-A EDE-A54-52S Circuit Breaker Operated Contact A54 CB-F-1A-A EDE-A69-60AX Voltage Balance Auxiliary Relay A69 CB-F-1A-A DG-ZL-9580-3 Indicating Light G07 DG-F-2A-A DG-ZL-9518-2 Indicating Light G07 DG-F-2A-A EDE-ZL-9824-1 Indicating Light G10 DG-F-2A-A EDE-ZL-9824-2 Indicating Light G10 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -11 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-ZL-9580-2 Indicating Light G07 DG-F-2A-A DG-ZL-9580-4 Indicating Light G07 DG-F-2A-A DG-ZL-9580-5 Indicating Light G07 DG-F-2A-A MM-CS-6651 Test Push Button with Indicating Light F80 CB-F-3A-A DG-G10-CF8 Loss of Control Power Relay G10 DG-F-2A-A DG-G10-CF9 Loss of Control Power Relay G10 DG-F-2A-A DG-G10-CF10 Loss of Control Power Relay G10 DG-F-2A-A DG-G10-CR45 Annunciator Auxiliary Relay G10 DG-F-2A-A DG-G10-CR42 Annunciator Auxiliary Relay G10 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -12 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 DG-TK-45A Starting Air Compressor Skid Air Receiver Tank DG-20460 A 310524 DG-F-2A-A X X - - HM2 - - - - - - - - DG-TK-45C Notes 1 and 5 3 DG-TK-45B Starting Air Compressor Skid Air Receiver tank DG-20460 A 310524 DG-F-2A-A X X - - HM2 - - - - - - - - DG-TK-45D Notes 1 and 5 4 DG-MM-8A Exhaust Silencer DG-20462 A 310525 DG-F-3E-A X X - - - - - - - - - - - DG-MM-8B Note 1 5 DG-F-36A Air Intake Filter DG-20462 A 310525 DG-F-3E-A X X - - - - - - - - - - - DF-F-36B Note 1 6 DG-TK-26A Fuel Oil Storage Tank DG-20459 A 310525 202264 DG-F-1A-A X X - - - - - - - - - - - DG-TK-26B Notes 1 and 2 7 DG-TK-78A Fuel Oil Day Tank DG-20459 A 310525 DG-F-3C-A X X - - - - - - - - - - - DG-TK-78B Note 1 8 DG-P-38A Fuel Oil Transfer Pump DG-20459 A 310524 202265 DG-F-1A-A X X X - N75 DG-BM7-52 460 V AC Circuit Breaker BM7 CB-F-1A-A BE4-BM7 BM7-RT8 BM7-N75 310857 BM7a BM7c CBA-FN-19 CBA-FN-20 DAH-FN-25A DAH-FN-26A EDE-MCC-521 DG-P-38B DG-CS-9503 Control Switch with Indication BE4 DG-F-2A-A DG-LS-FLC Fuel Low Level Switch RT8 DG-F-3C-A DG-BM7-42 Motor Starter BM7 CB-F-1A-A DG-BM7-49 Thermal Overload Relay BM7 CB-F-1A-A DG-BM7-FU Fuse BM7 CB-F-1A-A 9 DG-P-119A Engine-Driven Fuel Oil Pump DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-119B Notes 1 and 4 10 DG-P-115A Engine-Driven Lube Oil Pump DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-115B Notes 1 and 4 11 DG-TK-102A Lube Oil Reservoir DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-TK-102B Notes 1 and 4 12 DG-P-228A Engine-Driven Rocker Arm Lube Pump DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-228B Notes 1 and 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -13 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 DG-E-41A Lube Oil Heat Exchanger DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-E-41B Notes 1 and 4 14 DG-TK-46A Diesel Generator 1A Component Cooling Water Expansion Tank DG-20461 A 310525 DG-F-3C-A X X - - - - - - - - - - - DG-TK-46B Notes 1 and 4 15 DG-E-42A Diesel Generator 1A Component Cooling Water Heat Exchanger DG-20461 A 310767 805217 PAB-F-3A-Z X X - - - - - - - - - - Service Water DG-E-42B Notes 1 and 3 16 DG-P-121A Engine-Driven Jacket Coolant Pump DG-20461 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-121B Notes 1 and 4 17 DG-P-231A Engine-Driven Air Coolant Pump DG-20461 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-231B Notes 1 and 4 17a DG-C-2A DG Starting Air Compressor DG-20460 A 310524 DG-F-2A-A X X X - NC3 DG-BM3-52 460 v AC Circuit Breaker BM3 DG-F-2A-A BM3-NC3 BM3-HM2 BM3-HR2 310857 BM3a BM3c DAH-FN-25A DAH-FN-26A EDE-MCC-511 DG-C-2-B Note 5 DG-CS-9559 Control Switch BM3 DG-F-2A-A DGA-PS-APCI Pressure Switch HM2 DG-F-2A-A DG-PS-APCZ Pressure Switch HM2 DG-F-2A-A DG-HR2-HR9 EPS Relay HR2 CB-F-1A-A DG-BM3-42 Motor Starter BM3 CB-F-1A-A DG-BM3-49 Thermal O. L. BM3 CB-F-1A-A DG-BM3-FU Fuse BM3 CB-F-1A-A 17b DG-SKD-17A Diesel Generator 1A Starting Air Compressor Skid DG-20460 A 310524 DG-F-2A-A X X X - HM2 DG-E39/4-52 120 v AC Circuit Breaker E39 DG-F-2A-A E39-HM2 BM3-HM2 310857 E39/4a E39/4b DAH-FN-25A DAH-FN-26A EDE-MCC-E511 120 v AC Dist. Panel DG-SKD-17B Note 5 DG-HM2-52 120 v AC Circuit Breaker HM2 DG-F-2A-A DG-HM2-ATM Auto Drain Timer HM2 DG-F-2A-A DG-V-253A Auto Drain Solenoid Vlv. HM2 DG-F-2A-A DG-HM2-ICT Motor Synchronous Timer HM2 DG-F-2A-A DG-V-279A Left Chamber Inlet Sol. Vlv. HM2 DG-F-2A-A DG-V-280A Right Chamber Inlet Sol. Vlv. HM2 DG-F-2A-A DG-V-285A Repressurizing Sol. Vlv. HM2 DG-F-2A-A DG-V-288A Left Chamber Exhaust Sol. Vlv. HM2 DG-F-2A-A DG-V-289A Right Chamber Exhaust Sol. Vlv. HM2 DG-F-2A-A DG-V-HM2-KR Aux. Relay HM2 DG-F-2A-A DG-BM3-42 Motor Starter BM3 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -14 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 17c DG-C-18A DG Backup Operating Air Compressor DG-20460 A 310524 DG-F-2A-A X X X - ML7 DG-BS3-52 DG-BS3-42 DG-BS3-49 DG-BS3-FU DG-CS-9526 DGA-PS-APC3 DG-PS-APC4 DG-V-325A 460 v AC Ckt Bkr. Motor Starter Thermal O. L. Fuse Control Switch Pressure Switch Pressure Switch Unloader Sol. Vlv. BS3 BS3 BS3 BS3 BS3 HM2 HM2 UBO DG-F-2A-A DG-F-2A-A DG-F-2A-A DG-F-2A-A DG-F-2A-A DG-F-2A-A DG-F-2A-A DG-F-2A-A BS3-ML7 BS3-HM2

BS3-UB0 310857 BS3a BS3c DAH-FN-25A DAH-FN-26A EDE-MCC-511 DG-C-18B Note 5 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -15 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 DG-DG-1B Diesel Generator 1B DG-20467 B 310524 DG-F-2B-A X X X X HA2 DG-CS-9520-2 Control Switch (Push Button) G19 DG-F-2B-A A74-G18/7 A74-G30/6 E94-G30/1 G18-G30 G18-G30/1 G18-G30/2 G18-HR4 G19-G30 G19-G30/6 G18-G30/8 F81-FB0 F81-G18 F81-G18/1 F81-G19 F81-G19/E F81-G19/F 310857 E94/8a E94/8n E94/8b E94/8p E94/8c E94/8r E94/8d E94/8e E94/8f E94/8g E94/8s DBA-FN-32 DBA-FN-33 DAH-FN-25B DAH-FN-26B EDE-PP-111B D/G Starting Air DG-DG-1A DC-CS-9521 Control Switch (Push Button) G19 DG-F-2B-A DG-CS-9522-3 Control Switch (Push Button) G19 DG-F-2B-A DG-CS-9522-4 Control Switch (Push Button) G19 DG-F-2B-A DG-CS-9527-2 Control Switch (Push Button) G19 DG-F-2B-A DG-CS-9528-2 Control Switch (Push Button) G19 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A DG-G30-OP2 Oil Pressure Relay G30 DG-F-2B-A DG-G30-CR1 Ready for Auto Start Relay G30 DG-F-2B-A DG-G30-4A Start Relay G30 DG-F-2B-A DG-G30-T2A Cranking Time Control Time Delay Relay G30 DG-F-2B-A DG-ZL-9590-9 Start Ckt No 1 Signal Indicating Light G19 DG-F-2B-A DG-G30-ES1 Emergency Start Relay G30 DG-F-2B-A DG-G20-TSR1 Test Start Relay G20 DG-F-2B-A DG-G20-TSR2 Test Start Relay G20 DG-F-2B-A DG-G20-TSR3 Test Start Relay G20 DG-F-2B-A DG-G20-RDT Ramp Down Time Rela y G20 DG-F-2B-A DG-G19-IOT Idle Operate Time Relay G19 DG-F-2B-A DG-G18-LSRX Low Speed Auxiliary Relay G18 DG-F-2B-A DG-FY-AS1 Air Start Solenoid Valve G30 DG-F-2B-A DG-G30-OP3 Oil Pressure Relay G30 DG-F-2B-A DG-G30-CR2 Ready for Auto Start Relay G30 DG-F-2B-A DG-G30-TACH Tachometer G30 DG-F-2B-A DG-G30-4B Start Relay G30 DG-F-2B-A DG-G30-T2B Cranking Time Control Time Delay Relay G30 DG-F-2B-A DG-ZL-9590-10 Start Ckt No 2 Signal Indicating Light G19 DG-F-2B-A DG-G30-ES2 Emergency Start Relay G30 DG-F-2B-A DG-FY-AS2 Air Start Solenoid Valve G30 DG-F-2B-A DG-G30-OP4 Oil Pressure Relay G30 DG-F-2B-A DG-G30-5E Emergency Stop Relay G30 DG-F-2B-A DG-G30-5 Normal Stop Relay G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -16 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G30-5A Shutdown Relay G30 DG-F-2B-A DG-G30-5B Shutdown Relay G30 DG-F-2B-A DG-FY-SDS Shutdown Solenoid Valve G30 DG-F-2B-A DG-G30-T3A Alarm Set Time Delay Relay G30 DG-F-2B-A DG-G30-ASA Air Start Relay G30 DG-F-2B-A DG-G30-ASB Air Start Relay G30 DG-F-2B-A DG-G30-TR Engine Velocity Transmitter G30 DG-F-2B-A DG-G30-SG Signal Generator G30 DG-F-2B-A DG-G30-HSR High Speed Relay G30 DG-F-2B-A DG-G30-LSR Low Speed Relay G30 DG-F-2B-A DG-G30-ASR Starting Air Shutoff Relay G30 DG-F-2B-A DG-G30-BDR Barring Device Relay G30 DG-F-2B-A DG-G30-SFR Start Failure Relay G30 DG-F-2B-A SG-G30-SDR Engine Trouble Shutdown Relay G30 DG-F-2B-A DG-G30-EOR Engine Overspeed Relay G30 DG-F-2B-A EDE-A89-RLA SI Signal Lockout Relay A89 CB-F-1B-A DG-G30-OTH High Oil Temperature Relay G30 DG-F-2B-A DG-G30-CTH High Coolant Temperature Relay G30 DG-F-2B-A EDE-A74-TD2 Test Device A74 CB-F-1B-A EDE-A89-TD2 Test Device A89 CB-F-1B-A DG-G30-EST Emergency Start Time Delay Relay G30 DG-F-2B-A DG-G30-ESX Emergency Start Auxiliary Relay G30 DG-F-2B-A DG-G30-RA1 Air Pressure Auxiliary Relay G30 DG-F-2B-A DG-G30-RA2 Air Pressure Auxiliary Relay G30 DG-F-2B-A DG-G30-CF3 Power Available Relay G30 DG-F-2B-A DG-G30-CF4 Power Available Relay G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -17 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G19-R43L1 Selector Switch Auxiliary Latch Relay (Local) G19 DG-F-2B-A DG-G19-R43L2 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G19 DG-F-2B-A DG-G30-FU 10 Amp Fuses (10) G30 DG-F-2B-A DG-G19-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G19 DG-F-2B-A DG-G19-R43R2 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-HR4-PR1 EPS Auxiliary Relay HR4 CB-F-1B-A DG-HR4-PRIX EPS Auxiliary Relay HR4 CB-F-1B-A DG-SS-EOS Engine Overspeed Switch G30 DG-F-2B-A DG-PS-APL1 Air Pressure Low Switch G30 DG-F-2B-A DG-PS-APL2 Air Pressure Low Switch G30 DG-F-2B-A DG-G19-FU 10 Amp Fuses (20) G19 DG-F-2B-A DG-G19-R43L5 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-PS-CPS Coolant Pressure Switch G30 DG-F-2B-A DG-PS-OPL2 Oil Low Pressure Switch G30 DG-F-2B-A DG-PS-OPL3 Oil Low Pressure Switch G30 DG-F-2B-A DG-PS-OPL4 Oil Low Pressure Switch G30 DG-F-2B-A DG-G30-CTH-1 Coolant High Temperature Auxiliary Relay G30 DG-F-2B-A DG-G30-OTH-1 Oil High Temperature Auxiliary Relay G30 DG-F-2B-A DG-ZS-BD1 Barring Device Position Switch G30 DG-F-2B-A DG-G30-D1 P-N Junction Diode G30 DG-F-2B-A DG-ZS-BD2 Barring Device Position Switch G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -18 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) EDE-A74-86DP DG Primary Protection Lockout Relay A74 CB-F-1B-A EDE-A89-86DB DG Backup Protection Lockout Relay A89 CB-F-1B-A EDE-A74-TS Test Start Control Switch A74 CB-F-1B-A DG-G30-CF1 Power Available Relay G30 DG-F-2B-A DG-G30-CF2 Power Available Relay G30 DG-F-2B-A EDE-ZL-9594 Monitoring Circuit Indicating Light G19 DG-F-2B-A EDE-ZL-9594-1 Monitoring Circuit Indicating Light G30 DG-F-2B-A DG-PS-OPL1 Oil Low Pressure Switch G30 DG-F-2B-A DG-G30-OP1 Oil Pressure Relay G30 DG-F-2B-A DG-PS-FPLA Fuel Low Pressure Switch G30 DG-F-2B-A DG-G30-FPL Fuel Pressure Relay G30 DG-F-2B-A DG-PS-CPLA Jacket Coolant Low Pressure Switch G30 DG-F-2B-A DG-G30-CPL Jacket Coolant Pressure Relay G30 DG-F-2B-A DG-PS-IPLA Intercooler Low Pressure Switch G30 DG-F-2B-A DG-G30-IPL Intercoolant Pressure Relay G30 DG-F-2B-A DG-G30-CF5 Power Available Relay G30 DG-F-2B-A DG-G30-OPC Oil Pump Control Relay G30 DG-F-2B-A DG-G30-5B Shutdown Auxiliary Relay G30 DG-F-2B-A DG-G30-TRP TR Control Power Relay G30 DG-F-2B-A DG-G30-FPC Auxiliary Fuel Oil Pump Control Relay G30 DG-F-2B-A DG-G30-CPC Coolant Pump Control Relay G30 DG-F-2B-A DG-FY-CSV-B Jacket Coolant Auxiliary Valves Solenoid G30 DG-F-2B-A DG-G30-IPC Coolant Pump Control Relay G30 DG-F-2B-A DG-FY-ISV-B Intercooler Auxiliary Valves Solenoid G30 DG-F-2B-A DG-FB0-K603B Protection System Output Relay FB0 CB-F-3A-A EDE-CS-9528-1 Control Switch F81 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -19 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) EDE-CS-9527-1 Control Switch F81 CB-F-3A-A EDE-CS-9520-1 Control Switch F81 CB-F-3A-A DG-FB0-K-608B Protection System Output Relay FB0 CB-F-3A-A EDE-CS-9522-1 Control Switch F81 CB-F-3A-A EDE-CS-9522-2 Control Switch F81 CB-F-3A-A EDE-G19-FU-17,18 6 Amp Fuses (2) G19 DG-F-2B-A DP1-G20 F81-G19/9 310102 G19/2a G19/2g G19/2b G19/2c DP1a DP1b DAH-FN-25B DAH-FN-26B DC-CP-75B EDE-SWG-11B EDE-SS-9710 Selector Switch G18 DG-F-2B-A DG-G19-CF6 Auxiliary Relay G19 DG-F-2B-A DG-G19-R43L1 Selector Switch Auxiliary Latch Relay (Local) G19 DG-F-2B-A DG-G19-R43L2 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L3 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L5, R43L6 Selector Switch

Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G19 DG-F-2B-A DG-G19-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G19 DG-F-2B-A DG-G19-R43R2 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A EDE-SNS-9737-1 Selector Switch F81 CP-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -20 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) EDE-CS-9717-1 Control Switch F81 DG-F-2B-A EDE-CS-9719-1 Control Switch F81 DG-F-2B-A EDE-CS-9710-1 Control Switch F81 DG-F-2B-A EDE-SNS-9737-2 Selector Switch G18 DG-F-2B-A EDE-CS-9717-3 Control Switch G19 DG-F-2B-A EDE-CS-9719-3 Control Switch G19 DG-F-2B-A EDE-CS-9710-3 Control Switch G19 DG-F-2B-A DG-G19-FU17B, 18B 6 Amp Fuses G19 DG-F-2B-A EDE-G18-FU-9,10 50 Amp Fuses G18 DG-F-2B-A 310102 HA2a HA2c HA2b HA2d DP1a DP1b DAH-FN-25B DAH-FN-26B CBA-FN-32 CBA-FN-33 EDE-SWG-11B DG-A89-XFMR Grounding Transformer A89 CB-F-1B-A A89-G18 G18-HF8 A89-HP1 DP1-G20 DG-HF8-XF DG Field HF8 DG-F-2B-A DG-G18-SEVR-PC Static Exciter Voltage Regulator Power Chassis G18 DG-F-2B-A DG-SM-9587 Governor Control (2301A) G18 DG-F-2B-A DG-G20-SEVR-CC Voltage Regulator Control Chassis G20 DG-F-2B-A DG-GT4-PT1 Potential Transformer GT4 DG-F-2B-A DG-GT4-PT2 Potential Transformer GT4 DG-F-2B-A DG-GTR-PPT4 Power Transformer GT4 DG-F-2B-A DG-GTR-CCT Current Transformer 2000/5 GT4 DG-F-2B-A DG-G20-IDR1 Isochronous Droop Relay G20 DG-F-2B-A EDE-A89-60 Voltage Balance Relays A89 CB-F-1B-A DG-G20-64F Generator Field Failure Relay G20 DG-F-2B-A DG-HP1-NCB DG Neutral Connection Box HP1 DG-F-2B-A DG-GT4-XCT1,2,3 Generator Current Transformers (2000/5) øA,øB, øC GT4 DG-F-2B-A DG-VM-9712-2 Field Voltmeter G20 DG-F-2B-A DG-G20-DCT Field Voltage Transducer G20 DG-F-2B-A DG-G18-SH 50 MV Field Shunt G18 DG-F-2B-A DG-AM-9712-2 DC Field Ammeter G20 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -21 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G20-ATR Current Transducer G20 DG-F-2B-A DG-G20-CF10 Loss of Power Relay G20 DG-F-2B-A DG-A89-64 Ground Fault Sensing Relay A89 CB-F-1B-A DG-G20-FU-22,23 1 Amp Fuses G20 DG-F-2B-A DG-G19-IL10 Diode Failure Light G19 DG-F-2B-A DG-G20-K2 Field Flashing Contactor G20 DG-F-2B-A EDE-G18-FU-1,2 1B,2B 10 Amp Fuses (4) G18 DG-F-2B-A G18-G30/5 DP1-G20 F81-G18/4 F81-G18/5 F81-G18/6 F81-G20/1 310102 G18/1a G18/1f G18/1b G18/1c G18/1d DP1a DP1b DAH-FN-25B DAH-FN-26B DG-CP-75B EDE-SWG-11B DG-G19-R43R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A EDE-CS-9825-2 Control Switch (Push Button) G20 DG-F-2B-A DG-G30-HSR High Speed Relay G30 DG-F-2B-A DG-G30-LSR Low Speed Relay G30 DG-F-2B-A DG-G30-ES1 Emergency Start Relay G30 DG-F-2B-A DG-G30-ES2 Emergency Start Relay G30 DG-F-2B-A DG-SS-9587 Selector Switch G19 DG-F-2B-A DG-ZL-9590-11 Field Flash Signal Indicating Light G20 DG-F-2B-A DG-G19-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G19 DG-F-2B-A DG-G30-5A DG Shutdown Relay G30 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G18-LSRX Low Speed Auxiliary Relay G18 DG-F-2B-A DG-G18-LSRXX Time Delay Relay G18 DG-F-2B-A EDE-CS-9811-1 Push Button G20 DG-F-2B-A EDE-CS-9811-2 Push Button G20 DG-F-2B-A DG-G18-SEVR-PC Static Exciter Voltage Regulator Power Chassis G18 DG-F-2B-A EDE-G20-NM Null Meter G20 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-CS-9826-2 Control Switch G20 DG-F-2B-A EDE-CS-9827-2 Control Switch G20 DG-F-2B-A DG-G20-RR Regulator Relay G20 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -22 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G20-SEVR-CC Static Exciter Voltage Regulator Control Chassis G20 DG-F-2B-A DG-G20-CF8 Loss of Power Relay G20 DG-F-2B-A EDE-CS-9825-1 Push Button Switch F81 CB-F-3A-A EDE-CS-9827-1 Control Switch F81 CB-F-3A-A EDE-CS-9826-1 Control Switch F81 CB-F-3A-A EDE-VM-9783 Null Voltmeter F81 CB-F-3A-A EDE-G18-FU-3,4 3B, 4B 6 Amp Fuses (4) G18 DG-F-2B-A G18-G30/6 G18-G30/9 G18-G30/A G18/2a G18/2d G18/2b G18/2e DAH-FN-25B DAH-FN-26B DG-CP-75B EDE-SWG-11B DG-G20-IDR1 Isochronous Droop Relay G20 DG-F-2B-A DG-G20-IDR2 Isochronous Droop Relay G20 DG-F-2B-A F81-G18/8 ED9-G19 ED9-G20 ED9-HR4 DP1-G20

DP1a DP1b DG-SZ-9587 Governor Actuator G30 DG-F-2B-A DG-SC-9587 Digital Reference Unit (DRU) G18 DG-F-2B-A DG-SM-9587 2301A Governor Controller G18 DG-F-2B-A DG-ST-9587 Magnetic Pickup (MPU-1) G30 DG-F-2B-A DG-SS-9587 Selector Switch G19 DG-F-2B-A DG-G20-TSR1 Test Start Relay G20 DG-F-2B-A DG-G20-TSR2 Test Start Relay G20 DG-F-2B-A DG-G20-TSR3 Test Start Relay G20 DG-F-2B-A DG-G20-R21 Speed Adjust Auxiliary Relay G20 DG-F-2B-A DG-G20-RDT Ramp Down Time Relay G20 DG-F-2B-A DG-G19-IOT Idle Operate Time Relay G19 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-CS-9828-2 Control Switch G18 DG-F-2B-A DG-G18-LSRX Auxiliary Relay G18 DG-F-2B-A DG-G30-ES1 Emergency Start Auxiliary Relay G30 DG-F-2B-A DG-G19-ESS Emergency Start Auxiliary Relay G19 DG-F-2B-A DG-G30-ES2 Emergency Start Auxiliary Relay G30 DG-F-2B-A DG-G20-CF-9 Loss of Power Relay G20 DG-F-2B-A EDE-CS-9828-1 Control Switch F81 CB-F-3A-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -23 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-HR4-PR1 EPS Auxiliary Relay HR4 CF-F-1B-A DG-HR4-HR8 EPS Auxiliary Relay HR4 CB-F-1B-A DG-ED9-R1 Auxiliary Relay ED9 DG-F-2B-A DG-G20-IDR4 Isochronous Droop Relay G20 DG-F-2B-A EDE-G20-FU-7,8 7B, 8B 10 Amp Fuses (4) G20 DG-F-2B-A A74-G20/1 G20-G30 A89-G20 DP1-G20 F81-G19/8 A74-G19/4 F81-G18/7 F81-G19/7 G18-G30/4 G20a G20e G20b G20c DP1a DP1b DAH-FN-25B DAH-FN-26B CBA-FN-32 CBA-FN-33 DG-CP-75B EDE-SWG-11B DG-G30-CR1 Auto Start Ready Relay G30 DG-F-2B-A DG-G30-CR2 Auto Start Ready Relay G30 DG-F-2B-A DG-G30-RA1 Air Pressure Auxiliary Relay G30 DG-F-2B-A DG-G30-RA2 Air Pressure Auxiliary Relay G30 DG-F-2B-A DG-G19-R43L3 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-ESS Emergency Start Auxiliary Relay G19 DG-F-2B-A DG-G20-RR Regulator Relay G20 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L6 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L5 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R-DNA Diesel Not Available Auxiliary Relay G19 DG-F-2B-A DG-G19-R-B/I Switch Circuit Bypass/Inoperable Auxiliary Relay G19 DG-F-2B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -24 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G18-64F Generator Field Ground Relay G18 DG-F-2B-A DG-G20-64FX Generator Field Ground Auxiliary Relay G20 DG-F-2B-A DG-G19-64FXA Generator Field Ground Auxiliary Relay G19 DG-F-2B-A EDE-CS-9829-2 Control Switch G20 DG-F-2B-A DG-G20-23 Thermostat G20 DG-F-2B-A DG-G20-23X Thermostat Auxiliary Relay G20 DG-F-2B-A DG-G20-IDR1 Isochronous Droop Relay G20 DG-F-2B-A DG-G20-IDR2 Isochronous Droop Relay G20 DG-F-2B-A DG-G20-IDR3 Isochronous Droop Relay G20 DG-F-2B-A DG-G20-IDR4 Isochronous Droop Relay G20 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-A71-52S Circuit Breaker Operated Contact A71 CB-F-1B-A EDE-A72-52S Circuit Breaker Operated Contact A72 CB-F-1B-A EDE-A74-52S Circuit Breaker Operated Contact A74 CB-F-1B-A EDE-A89-60AX Voltage Balance Auxiliary Relay A89 CB-F-1B-A DG-ZL-9590-2 Indicating Light G19 DG-F-2B-A DG-ZL-9590-3 Indicating Light G19 DG-F-2B-A DG-ZL-9528-2 Indicating Light G19 DG-F-2B-A EDE-ZL-9829-1 Indicating Light G20 DG-F-2B-A EDE-ZL-9812-2 Indicating Light G19 DG-F-2B-A EDE-ZL-9829-2 Indicating Light G20 DG-F-2B-A DG-G20-CF8 Loss of Control Power Relay G20 DG-F-2B-A DG-G20-CF9 Loss of Control Power Relay G20 DG-F-2B-A DG-G20-CF10 Loss of Control Power Relay G20 DG-F-2B-A DG-G20-CR45 Annunciator Auxiliary Relay G20 DG-F-2B-A DG-C20-CR42 Annunciator Auxiliary Relay G20 DG-F-2B-A DG-ZL-9590-12 Indicating Light F81 CB-F-3A-A DG-G30-ESX Emergency Start Aux Relay G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -25 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-ZL-9590-4 Indicating Light G19 DG-F-2B-A DG-ZL-9590-5 Indicating Light G19 DG-F-2B-A DG-ZL-9590-8 Indicating Light F81 CB-F-3A-A DG-ZL-9528-1 Indicating Light F81 CB-F-3A-A EDE-ZL-9829-4 Indicating Light F81 CB-F-3A-A EDE-CS-9829-1 Indicating Light F81 CB-F-3A-A EDE-SNS-9737-1 Synchronizing Switch F81 CB-F-3A-A EDE-CS-9829-1 Control Switch F81 CB-F-3A-A DG-A89-RLA LOCA Seal Relay A89 CB-F-1B-A DG-ZL-9590-6 Indicating Light F81 CB-F-3A-A MM-CS-6653 Test Push Button and Indicating Light F81 CB-F-3A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -26 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 DG-TK-45C Starting Air Compressor Skid Air Receiver Tank DG-20465 B 310524 DG-F-2B-A X X - - HM3 - - - - - - - - DG-TK-45A Notes 1 and 7 20 DG-TK-45D Starting Air Compressor Skid Air Receiver Tank DG-20465 B 310524 DG-F-2B-A X X - - HM3 - - - - - - - - DG-TK-45B Notes 1 and 7 21 DG-MM-8B Exhaust Silencer DG-20467 B 310525 DG-F-3F-A X X - - - - - - - - - - - DG-MM-8A Note 1 22 DG-F-36B Air Intake Filter DG-20467 B 310525 DG-F-3F-A X X - - - - - - - - - - - DG-F-36A Note 1 23 DG-TK-26B Fuel Oil Storage Tank DG-20464 B 310524 202264 DG-F-1B-A X X - - - - - - - - - - - DG-TK-26A Notes 1 and 2 24 DG-TK-78B Fuel Oil Day Tank DG-20459 B 310525 DG-F-3D-A X X - - - - - - - - - - - DG-TK-78A Note 1 25 DG-P-38B Fuel Oil Transfer Pump DG-20464 B 310524 202264 DG-F-1B-A X X X - N76 DG-BP7-52 460 V AC Circuit Breaker BP7 CB-F-1B-A BE5-BP7 BP7-RU1 BP7-N76 310857 BP7a BP7c CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B EDE-MCC-621 DG-P-38A - DG-CS-9506 Control Switch with Indication BE5 DG-F-2B-A DG-LS-FLC Fuel Low Level Control Switch RU1 DG-F-3D-A DG-BP7-42 Motor Starter BP7 CB-F-1B-A DG-BP7-49 Thermal Overload Relay BP7 CB-F-1B-A DG-BP7-FU Fuse BP7 CB-F-1B-A 26 DG-P-119B Engine-Driven Fuel Oil Pump DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-119A Notes 1 and 6 27 DG-P-115B Engine-Drive Lube Oil Pump DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-115A Notes 1 and 6 28 DG-TK-102B Lube Oil Reservoir DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-102A Notes 1 and 6 29 DG-P-228B Engine-Driven Rocker Arm Lube Pump DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-228A Notes 1 and 6 30 DG-E-41B Lube Oil Heat Exchanger DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-E-41A Notes 1 and 6 31 DG-TK-46B Diesel Generator 1B Component Cooling Water Expansion Tank DG-20466 B 310525 DG-F-3D-A X X - - - - - - - - - - - DG-TK-46A Note 1 32 DG-E-42B Diesel Generator 1B Component Cooling Water Heat Exchanger DG-20466 B 310767 805217 PAB-F-3A-Z X X - - - - - - - - - - Service Water DG-E-42A Notes 1 and 3 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -27 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 33 DG-P-121B Engine-Driven Jacket Coolant Pump DG-20466 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-121A Notes 1 and 4 34 DG-P-231B Engine-Driven Air Coolant Pump DG-20466 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-231A Notes 1 and 6 35 DG-PV-7A-2 Lube Oil Cooler Differential Pressure Control Valve DG-20461 A 310524 DG-F-2A-A X X - X HA1 DG-PT-7A-3 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-PV-7B-2 Note 8 HA1 DG-PT-7A-4 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A HA1 DG-PDT-7A-2 Differential Pressure Transmitter G29 DG-F-2A-A HA1 DG-PDC-7A-2 Differential Pressure Controller G29 DG-F-2A-A 36 DG-TCV-7A-2 Jacket Coolant Temperature Control Valve DG-20461 A 310524 DG-F-2A-A X X X X HA1 DG-CP-907A Air Cooler Coolant and Jacket Coolant Temp. Control Panel G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-TCV-7B-2 Note 8 37 DG-PV-7A-1 Jacket Coolant Differential Pressure Control Valve DG-20461 A 310524 DG-F-2A-A X X - X HA1 DG-PT-7A-1 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-PV-7B-1 Note 9 DG-PT-7A-2 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A DG-PDT-7A-1 Differential Pressure Transmitter G29 DG-F-2A-A DG-PDC-7A-1 Differential Pressure Controller G29 DG-F-2A-A 38 DG-TCV-7A-1 Jacket Coolant Temperature Control Valve DG-20461 A 310524 DG-F-2A-A X X X X HA1 DG-CP-907A Air Cooler Coolant and Jacket Coolant Temp. Control Panel G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-TCV-7B-1 Note 9 39 DG-F-64A Lube Oil Filter DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-F-64B Notes 1 and 4 40 DG-F-23A Lube Oil Duplex Filter DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-F-23B Notes 1 and 4 41 DG-S-4A Lube Oil Strainer DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-S-4B Notes 1 and 4 42 DG-S-85A Lube Oil Sump Suction Strainer DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-S-85B Notes 1 and 4 43 DG-S-5A Fuel Oil Storage Tank Duplex Strainer DG-20459 A 310524 202264 DG-F-1A-A X X - - - - - - - - - - - DG-S-5B Notes 1 and 2 44 DG-S-6A Fuel Oil Day Tank Duplex Strainer DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-S-6B Notes 1 and 4 45 DG-F-65A Fuel Oil Duplex Filter DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-F-65B Notes 1 and 4 46 DG-TK-110A Fuel Oil Accumulator Tank DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-TK-110B Notes 1 and 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -28 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 47 DG-PV-7B-2 Lube Oil Cooler Differential Pressure Control Valve DG-20466 B 310524 DG-F-2B-A X X - X HA2 DG-PT-7B-3 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DC-PV-7A-2 Note 10 DG-PT-7B-4 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A DG-PDT-7B-2 Differential Pressure Transmitter G30 DG-F-2B-A DG-PDC-7B-2 Differential Pressure Controller G30 DG-F-2B-A 48 DG-TCV-7B-2 Air Cooler Coolant Temperature Control Valve DG-20466 B 310524 DG-F-2B-A X X X X HA2 DG-CP-907B Air Cooler Coolant and Jacket Coolant Temp. Control Panel G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DG-TCV-7A-2 Note 10 49 DG-PV-7B-1 Jacket Coolant Differential Pressure Control Valve DG-20466 B 310524 DG-F-2B-A X X - X HA2 DG-PT-7B-1 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DG-PV-7A-1 Note 11 DG-PT-7B-2 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A DG-PDT-7B-1 Differential Pressure Transmitter G30 DG-F-2B-A DG-PDC-7B-1 Differential Pressure Controller G30 DG-F-2B-A 50 DG-TCV-7B-1 Jacket Coolant Temperature Control Valve DG-20466 B 310524 DG-F-2B-A X X X X HA2 DG-CP-907B Air Cooler Coolant and Jacket Coolant Temp. Control Panel G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DG-TCV-7A-1 Note 11 - - - 51 DG-F-64B Lube Oil Filter DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-64A Notes 1 and 6 52 DG-F-23B Lube Oil Duplex Filter DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-23A Notes 1 and 6 53 DG-S-4B Lube Oil Strainer DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-S-4A Notes 1 and 6 54 DG-S-85B Lube Oil Sump Suction Strainer DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-S-85A Notes 1 and 6 55 DG-S-5B Fuel Oil Storage Tank Duplex Strainer DG-20464 B 310524 202264 DG-F-1B-A X X - - - - - - - - - - - DG-S-5A Notes 1 and 2 56 DG-S-6B Fuel Oil Day Tank Duplex Strainer DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-S-6A Notes 1 and 6 57 DG-F-65B Fuel Oil Duplex Filter DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-65A Notes 1 and 6 58 DG-TK-110B Fuel Oil Accumulator Tank DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-TK-110A Notes 1 and 6 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -29 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 59 DG-C-2B DG Starting Air Compressor DG-220465 B 310524 DG-F-2B-A X X X - NC4 DG-BP3-52 460 v AC Circuit Breaker BP3 DG-F-2B-A BP3-NC4 BP3-HM3 BP3-HR4 310857 BP3a BP3c DAH-FN-25B DAH-FN-26B EDE-MCC-611 DG-C-2A Note 7 DG-CS-9569 Control Switch BP3 DG-F-2B-A DGB-PS-APCI Pressure Switch HM3 DG-F-2B-A DGB-PS-APCZ Pressure Switch HM3 DG-F-2B-A DG-HR4-HR9 EPS Relay HR3 CB-F-1B-A DG-BP3-42 Motor Starter BP3 CB-F-1B-A DG-BP3-49 Thermal O. L. BP3 CB-F-1B-A DG-BP3-FU Fuse BP3 CB-F-1B-A 59a DG-C-18B DG Backup Operating Air Compressor DG-20465 B 310524 DG-F-2B-A X X X - ML8 DG-BS5-52 460 v AC Ckt Bkr. BS5 DG-F-2B-A BS5-ML8 BS5-HM3 310857 BS5a BS5c DAH-FN-25B DAH-FN-26B EDE-MCC-611 DG-C-18A Note 7 DG-BS5-42 Motor Starter BS5 DG-F-2B-A DG-BS5-49 Thermal O. L. BS5 DG-F-2B-A DG-BS5-FU Fuse BS5 DG-F-2B-A DG-CS-9536 Control Switch BS5 DG-F-2B-A DGB-PS-APC3 Pressure Switch HM3 DG-F-2B-A DGB-PS-APC4 Pressure Switch HM3 DG-F-2B-A DG-V-325B Unloader Sol. Vlv. UB1 DG-F-2B-A BS5-UB1 60 DG-SKD-17B Diesel Generator 1B Starting Air Compressor Skid DG-20465 B 310524 DG-F-2B-A X X X - HM3 DG-E47/4-52 120 v AC Circuit Breaker E47 DG-F-2B-A E47-HM3 BP3-HM3/1 310857 E47/4a E47/4b DAH-FN-25B DAH-FN-26B EDE-MCC-E611 120 v AC Dist. Panel DG-SKD-17A Note 7 DG-HM3-52 120 v AC Circuit Breaker HM3 DG-F-2B-A DG-HM3-ATM Auto Drain Timer HM3 DG-F-2B-A DG-V-253B Auto Drain Solenoid Vlv. HM3 DG-F-2B-A DG-HM3-ICT Motor Synchronous Timer HM3 DG-F-2B-A DG-V-279B Left Chamber inlet Sol. Vlv. HM3 DG-F-2B-A DG-V-280B Right Chamber inlet Sol. Vlv. HM3 DG-F-2B-A DG-V-285B Repressurizing Sol. Vlv. HM3 DG-F-2B-A DG-V-288B Left Chamber Exhaust Sol. Vlv. HM3 DG-F-2B-A DG-V-289B Right Chamber Exhaust Sol. Vlv. HM3 DG-F-2B-A DG-V-HM3-KR Aux. Relay HM3 DG-F-2B-A DG-BP3-42 Motor Starter BP3 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -30 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 61 DG-CP-907A Diesel Generator 1A Air Cooler Coolant & Jacket Coolant Temp. Control Panel DG-20461 A 310524 DG-F-2A-A X X X X G29 DG-EH9/17-52 120 v AC Circuit Breaker EH9 CB-F-1A-A EH9-G29 310857 EH9/17a EH9/17c CBA-FN-19 CBA-FN-20 DAH-FN-25A DAH-FN-26A EDE-PP-1E DG-CP-907B Notes 8 & 9 DGA-TIC-9602 Jacket Coolant Temp. Indi. Controller G29 DG-F-2A-A DGA-TT-9602-1 & 2 Jacket Coolant Temp. Transmitters G29 DG-F-2A-A DGA-TE-9602-1 & 2 Jacket Coolant Temp. Elements G29 DG-F-2A-A DGA-ZC-9602 Jacket Coolant Temp . Dig. Vlv. Controller (I/P) G29 DG-F-2A-A DGA-ZY-9602 Jacket Coolant Temp. Cont. Vlv. Pos. Sensor G29 DG-F-2A-A DGA-TIC-9612 Air Cooler Coolant Temp. Indi. Controller G29 DG-F-2A-A DGA-TT-9612-1 & 2 Air Cooler Coolant Temp. Transmitters G29 DG-F-2A-A DGA-TE-9612-1 & 2 Air Cooler Coolant Temp. Elements G29 DG-F-2A-A DGA-ZC-9612 Air Cooler Coolant Temp. Dig. Vlv. Controller (I/P) G29 DG-F-2A-A DGA-ZY-9612 Air Cooler Coolant Temp. Vlv. Pos. Sensor G29 DG-F-2A-A DG-G29-TIC-RX Auxiliary Relay G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table MCR 3.1.3.18 -31 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 62 DG-CP-907B Diesel Generator 1B Air Cooler Coolant & Jacket Coolant Temp. Control Panel DG-20466 B 310524 DG-F-2B-A X X X X G30 DG-EH0/17-52 120 v AC Circuit Breaker EH0 CB-F-1B-A EH0-G30 310857 EH0/17a EH0/17c CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B EDE-PP-1F DG-CP-907A Notes 10 & 11 DGB-TIC-9602 Jacket Coolant Temp. Indi. Controller G30 DG-F-2B-A DGB-TT-9602-1 & 2 Jacket Coolant Temp. Transmitters G30 DG-F-2B-A DGB-TE-9602-1 & 2 Jacket Coolant Temp. Elements G30 DG-F-2B-A DGB-ZC-9602 Jacket Coolant Temp . Dig. Vlv. Controller (I/P) G30 DG-F-2B-A DGB-TIC-9612 Air Cooler Coolant Temp. Indi. Controller G30 DG-F-2B-A DGB-TT-9612-1 & 2 Air Cooler Coolant Temp. Transmitters G30 DG-F-2B-A DGB-TE-9612-1 & 2 Air Cooler Coolant Temp. Elements G30 DG-F-2B-A DGB-ZC-9612 Air Cooler Coolant Temp. Dig. Vlv. Controller (I/P) G30 DG-F-2B-A DGB-ZY-9612 Air Cooler Coolant Temp. Vlv. Pos. Sensor G30 DG-F-2B-A DG-G30-TIC-RX Auxiliary Relay G30 DG-F-2B-A . NOTES 1. The equipment is mechanical with no electrical requirement.

2. Electrical conduit plan drawing, 310524, is listed only to show the fire zone corresponding to the location of this equipment in the Diesel Generator Building as identified in 202263.
3. Electrical conduit plan drawing, 310767, is listed only to show fire zone corresponding to the location of this equipment in the Primary Auxiliary Building as identified in 805217.
4. This equipment is located in the Diesel Generator Skid DG

-SKD-7A. 5. This equipment is located in the Diesel Generator Skid DG -SKD-17A. 6. This equipment is located in the Diesel Generator Skid DG -SKD-7B. 7. This equipment is located in the Diesel Generator Skid DG -SKD-17B. 8. The pneumatic control diagram of this equipment is shown in the DG air cooler water control loop diagram, 506403.

9. The pneumatic control diagram of this equipment is shown in the diesel engine jacket cooling water control loop diagram, 506404.
10. The pneumatic control diagram of this equipment is shown in the DG air cooler water control loop diagram, 506405.
11. The pneumatic control diagram of this equipment is shown in the DG diesel engine jacket cooling water loop diagram, 506406.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-1 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CO-TK-25 Condensate Storage Tank CO-20426 A/B 310248 CST-F-1-0 X X - - - - - - - - - -

- - Note 1 2 FW-P-37B Emergency Feed Pump FW-20688 B 310708 EFP-F-1-A X X X - N14 FW-A80-52 416 V AC Circuit Breaker A80 CB-F-1B-A A80-N14 None              FW-A80-FU Fuses A80 CB-F-1B-A CBA-FN-32 

CBA-FN-33 EPA-FN-47B EDE-SWG-6

FW-A80-R Auxiliary Relay A80 CB-F-1B-A FW-CS-4255-2 Control Switch A80 CB-F-1B-A 310844 A80a A80h A80b A80c A80d FW-SS-4255 Selector Switch A80 CB-F-1B-A EDE-A73-94-1B Bus Under Voltage Relay A73 CB-F-1B-A FW-A80-86 Lockout Relay A80 CB-F-1B-A FW-A80-52H Truck-Operated Contact A80 CB-F-1B-A FW-A80-50/51 Instrument/Time Overcurrent Relays

øA, øC A80 CB-F-1B-A FW-A80-AM Ammeter A80 CB-F-1B-A FW-A80-AS Ammeter Switch A80 CB-F-1B-A FW-A80-CT Current Transformers (200/5) A80 CB-F-1B-A FW-A80-TD1 CT Test Device A80 CB-F-1B-A FW-A80-ATR Transducer A80 CB-F-1B-A FW-A80-TD2 Lockout Relay Test Device A80 CB-F-1B-A FW-A80-G,R,W Indicating Lights A80 CB-F-1B-A FW-A80-52Z Time Delay Relay A80 CB-F-1B-A FW-A80-51GS Ground Sensor Relay A80 CB-F-1B-A 2A FW-V347 FW-20688 B 310708 EFP-F-1-A X X X - V4P FW-C3T-52 460 V AC Circuit Breaker C3T CB-F-1B-A None Emergency

Feedwater

Recirculating

Valve FW-C3T-FU Fuses C3T CB-F-1B-A C3T-V4P C3T-V4P/1

C3T-G2J 310844 C3Ta C3Tc EDE-MCC-615 CBA-FN-32

CBA-FN-33 EPA-FN-47B FW-CS-4369-2 Control Switch with Indication G2J CB-F-1B-A MS-SS-3064 Selector Switch G2J CB-F-1B-A FW-C3T-42/0,C Motor Starters C3T CB-F-1B-A FW-C3T-49 Overload Relays C3T CB-F-1B-A FW-ZS-V347 Valve Position Switch V4P EFP-F-1-A

.Notes  1. The equipment is mechanical with no electrical requirement. 
2. During normal operation, this equipment is in its safe shutdown position (locked closed). To prevent spurious operation, its circuit breaker is administratively controlled locked open (off).
3. Disabling the valve at the appropriate control location will reposition it for safe shutdown.
4. Air is not needed to position or to reposition the valve for safe shutdown.
5. The review of this valve was conducted with the assumption that it will be closed from the Control Room prior to evacuation and that a fire will not reset its logic before the operator could man the remote shutdown station and throw the "Remote-Local" switches to "Local". Its cables and supporting controls were listed to analyze the possibility of the valve reopening after the isolation switch has been positioned to "Local". 6. Circuit breaker tripped to disable the redundant controls.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-2 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 FW-FV-4214A FW-20688 A 310708 EFP-F-1-A X X X - V2E FW-B3V-52 460 V AC Circuit Breaker B3V CB-F-1A-A FW-FV-4214-B Emergency

Feedwater Header

Flow Valve FW-B3V-FU Fuse B3V CB-F-1A-A FW-CS-4214-A2 Control Switch with Indication G2G CB-F-1A-A B3V-V2E B3V-V2E/1

E3C-G2G G2G-V2E B3V-G5X B3V-G5X/1 310844 B3Va B3Vd B3Ve CBA-FN-19

CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-SS-4214-A Selector Switch G2G CB-F-1A-A FW-SS-4214-A1 Selector Switch G5X DG-F-2A-A FW-B3V-42/0,C Motor Starters B3V CB-F-1A-A FW-B3V-49 Overload Relays B3V CB-F-1A-A FW-ZS-4214-A Valve Position Switch V2E EFP-F-1-A 4 FW-FV-4214B FW-20688 B 310708 EFP-F-1-A X X X - V2J FW-B3Z-52 460 V AC Circuit Breaker B3Z CB-F-1B-A FW-FV-4214-A Emergency

Feedwater Header

Flow Valve FW-B3Z-FU Fuse B3Z CB-F-1B-A FW-CS-4214-B2 Control Switch with Indication G2J CB-F-1B-A B3Z-V2J B3Z-V2J/1 E3D-G2J G2J-V2J B3Z-G2J B3Z-G5Y B3Z-G5Y/1 310844 B3Za B3Zd B3Ze CBA-FN-32

CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-SS-4214-B Selector Switch G2J CB-F-1B-A FW-SS-4214-B1 Selector Switch G5Y DG-F-2B-A FW-B3Z-42/0,C Motor Starters B3Z CB-F-1B-A FW-B3Z-49 Overload Relays B3Z CB-F-1B-A FW-ZS-4214-B Valve Position Switch V2J EFP-F-1-A 5 FW-FV-4224A FW-20688 A 310708 EFP-F-1-A X X X - V2F FW-B3W-52 460 V AC Circuit Breaker B3W CB-F-1A-A FW-FV-4224-B Emergency

Feedwater Header

Flow Valve FW-B3W-FU Fuse B3W CB-F-1A-A FW-CS-4244-A2 Control Switch with Indication G2G CB-F-1A-A B3W-V2F B3W-V2F/1 E3C-G2G/1 G2G-V2F B3W-G5X B3W-G5X/1 310844 B3WA B3WD B3WE CBA-FN-19

CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-SS-4224-A Selector Switch G2G CB-F-1A-A FW-SS-4224-A1 Selector Switch G5X DG-F-2A-A FW-B3W-42/0,C Motor Starters B3W CB-F-1A-A FW-B3W-49 Overload Relays B3W CB-F-1A-A FW-ZS-4224-A Valve Position Switch V2F EFP-F-1-A 6 FW-FV-4224B FW-20688 B 310708 EFP-F-1-A X X X - V2K FW-B4A-52 460 V AC Circuit Breaker B4A CB-F-1B-A FW-FV-4224-A Emergency

Feedwater Header

Flow Valve FW-B3W-FU Fuse B4A CB-F-1B-A FW-CS-4224-B2 Control Switch with Indication G2J CB-F-1B-A B4A-V2K B4A-V2K/1 E3D-G2J/1 G2J-V2K B4A-G2J B4A-G5Y B4A-G5Y/1 310844 B4Aa B4Ad B4Ae CBA-FN-32

CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-SS-4224-B Selector Switch G2J CB-F-1B-A FW-SS-4224-B1 Selector Switch G5Y DG-F-2B-A FW-B4A-42/0,C Motor Starters B4A CB-F-1B-A FW-B4A-49 Overload Relays B4A CB-F-1B-A FW-ZS-4224-B Valve Position Switch V2K EFP-F-1-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-3 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 FW-FV-4234A FW-20688 A 310708 EFP-F-1-A X X X - V2G FW-B3X-52 460 V AC Circuit Breaker B3X CB-F-1A-A FW-FV-4234-B Emergency

Feedwater Header

Flow Valve FW-B3X-FU Fuse B3X CB-F-1A-A 310844 B3Xa B3Xd B3Xe FW-CS-4234-A2 Control Switch with Indication G2G CB-F-1A-A B3X-V2G B3X-V2G/1 G2G-V2G E3C-G2G/2 B3X-G5X B3X-G5X/1 CBA-FN-19

CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-SS-4214-A Selector Switch G2G CB-F-1A-A FW-SS-4214-A1 Selector Switch G5X DG-F-2A-A FW-B3X-42/0,C Motor Starters B3X CB-F-1A-A FW-B3X-49 Overload Relays B3X CB-F-1A-A FW-ZS-4234-A Valve Position Switch V2G EFP-F-1-A 8 FW-FV-4234B FW-20688 B 310708 EPF-F-1-A X X X - V2L FW-B4B-52 460 V AC Circuit Breaker B4B CB-F-1B-A FW-FV-4234-A Emergency

Feedwater Header

Flow Valve FW-B4B-FU Fuse B4B CB-F-1B-A FW-CS-4234-B2 Control Switch with Indication G2J CB-F-1B-A 310844 B4Ba B4Bd B4Be CBA-FN-32 CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-SS-4214-B Selector Switch G2J CB-F-1B-A B4B-V2L B4B-V2L/1 E3D-G2J/2 G2J-V2L B4B-G2J B4B-G5Y B4B-G5Y/1 FW-SS-4214-B1 Selector Switch G5Y DG-F-2B-A FW-B4B-42/0,C Motor Starters B4B CB-F-1B-A FW-B4B-49 Overload Relays B4B CB-F-1B-A FW-ZS-4234-B Valve Position Switch V2L EFP-F-1-A 9 FW-FV-4244A FW-20688 A 310708 EFP-F-1-A X X X - V2H FW-B3Y-52 460 V AC Circuit Breaker B3Y CB-F-1A-A FW-FV-4244-B Emergency

Feedwater Header

Flow Valve FW-B3Y-FU Fuse B3Y CB-F-1A-A FW-CS-4244-A2 Control Switch with Indication G2G CB-F-1A-A B3Y-V2H B3Y-V2H/1 E3C-G2G/3 G2G-V2H B3Y-G5X B3Y-G5X/1 310844 B3Ya B3Yd B3Ye CBA-FN-19

CBA-FN-20 EPA-FN-47A EDE-MCC-515 FW-SS-4224-A Selector Switch G2G CB-F-1A-A FW-SS-4224-A1 Selector Switch G5X DG-F-2A-A FW-B3Y-42/0,C Motor Starters B3Y CB-F-1A-A FW-B3Y-49 Overload Relays B3Y CB-F-1A-A FW-ZS-4244-A Valve Position Switch V2H EFP-F-1-A 10 FW-FV-4244B FW-20688 B 310708 EFP-F-1-A X X X - V2M FW-B4C-52 460 V AC Circuit Breaker B4C CB-F-1B-A FW-FV-4244-A Emergency

Feedwater Header

Flow Valve FW-B4C-FU Fuse B4C CB-F-1B-A FW-CS-4244-B2 Control Switch with Indication G2J CB-F-1B-A 310844 B4Ca B4Cd B4Ce CBA-FN-32

CBA-FN-33 EPA-FN-47B EDE-MCC-615 FW-SS-4224-B Selector Switch G2J CB-F-1B-A B4C-V2M B4C-V2M/1 E3D-G2J/3 GJ2-V2M B4C-G2J B4C-G5Y B4C-G5Y/1 FW-SS-4224-B1 Selector Switch G5Y DG-F-2B-A FW-B4C-42/0,C Motor Starters B4C CB-F-1B-A FW-B4C-49 Overload Relays B4C CB-F-1B-A FW-ZS-4244-B Valve Position Switch V2M EFP-F-1-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-4 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 MS-PV-3001 MS-20580 A/B 310589 MS-F-2B-Z X X X X V2N MS-HIC-3001 Auto/Manual Controller with

Indicator G2G CB-F-1A-A MS-PV-3002 or MS-PV-3004 Main Steam Header

Atmospheric

Relief Valve MS-HQY-3001 Mixing Amplifier G2H CB-F-1A-A MS-HY-3001 Signal Converter G2H CB-F-1A-A 310841 310953 G2Ga FJ71 310841 E2T/8a E2T/8e E2T/8f MS-SS-3001-1 Selector Switch G2G CB-F-1A-A G2G-GL6 G2G-V2N E2T-G5X G2G-G5X FN8-U0A FN8-U0B FN8-G2G/1 MS-CS-3001-2 Control Switch with Indication G2G CB-F-1A-A CBA-FN-19

CBA-FN-20 MM-UQ-5868

MM-UQ-5869 Instrument Air EDE-PP-113A CBA-FN-19

CBA-FN-20 Instrument Air MS-PY-3001 I/P Converter GL6 MS-F-1B-Z MS-E2T/8-72 125 V DC Circuit Breaker E2T CB-F-1A-A MS-CS-3001-2 Control Switch with Indication G2G CB-F-1A-A MS-SS-3001-1 Selector Switch G2G CB-F-1A-A MS-ZS-3001-A Valve Position Switch V2N MS-F-2B-Z MS-PY-3001-1 Solenoid Valve UOA MS-F-2B-Z MS-SS-3001-3 Selector Switch FN8 ET-F-1B-A MS-PY-3001-2 Solenoid Valve UOA MS-F-2B-Z MS-PY-3001-3 Solenoid Valve UOB MS-F-2B-Z MS-PY-3001-4 Solenoid Valve UOB MS-F-2B-Z MS-SS-3001-2 Selector Switch G5X DG-F-2A-A UOC MS-PY-3001-5 + 6 Solenoid Valve E2U CB-F-1B-A - - - - Note 6 12 MS-PV-3003 Main Steam Header Atmospheric

Relief Valve MS-20580 A/B 310586 MS-F-2A-Z X X X X V2Q MS-HIC-3003 Auto/Manual Controller with

Indicator G2G CB-F-1A-A MS-PV-3002 or MS-PV-3004 MS-HQY-3003 Mixing Amplifier G2H CB-F-1A-A MS-HY-3003 Signal Converter G2H CB-F-1A-A G2G-GL5 G2G-V2Q E2T-G5X/1 G2G-G5X/1 FN8-U0K FN8-U0L FN8-G2G/2 310841 310953 G2Ga FJ71 310841 E2T/10a E2T/10e E2T/10f MS-SS-3003-1 Selector Switch G2G CB-F-1A-A MS-CS-3003-2 Control Switch with Indication G2G CB-F-1A-A CBA-FN-19

CBA-FN-20 MM-UQ-5868

MM-UQ-5869 Instrument Air EDE-PP-113A CBA-FN-19

CBA-FN-20 Instrument Air MS-PY-3003 I/P Converter GL5 MS-F-3A-Z MS-E2T/10-72 125 V DC Circuit Breaker E2T CB-F-1A-A MS-CS-3003-2 Control Switch with Indication G2G CB-F-1A-A MS-SS-3003-1 Selector Switch G2G CB-F-1A-A MS-ZS-3003-A Valve Position Switch V2Q MS-F-2A-Z MS-SS-3003-3 Selector Switch FN8 ET-F-1B-A MS-PY-3003-1 Solenoid Valve UOK MS-F-2A-Z MS-PY-3003-2 Solenoid Valve UOK MS-F-2A-Z MS-PY-3003-3 Solenoid Valve UOL MS-F-2A-Z MS-PY-3003-4 Solenoid Valve UOL MS-F-2A-Z MS-SS-3003-2 Selector Switch G5X DG-F-2A-A UOM MS-PY-3003-5 + 6 Solenoid Valve E2U CB-F-1B-A - - - - Note 6 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-5 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 MS-PV-3002 MS-20580 A/B 310586 MS-F-2A-Z X X X X V2P MS-HIC-3002 Auto/Manual Controller with

Indicator G2J CB-F-1B-A MS-PV-3001 or MS-PV-3003 Main Steam Header

Atmospheric

Relief Valve MS-HQY-3002 Mixing Amplifier GZO CB-F-1B-A MS-HY-3002 Signal Converter GZ0 CB-F-1B-A G2J-GZ4 G2J-V2P E2U-G5Y G2J-G5Y FN9-U0G FN9-U0H FN9-G2J/1 310841 G2Ja FJ4d E2U/8a E2U/8e E2U/8f MS-SS-3002-1 Selector Switch G2J CB-F-1B-A CBA-FN-32 CBA-FN-33 MM-UQ-5866

MM-UQ-5867 Instrument Air EDE-PP-113B CBA-FN-32

CBA-FN-33 Instrument Air MS-CS-3002-2 Control Switch with Indication G2J CB-F-1B-A MS-PY-3002 I/P Converter GZ4 MS-F-3A-Z MS-E2U/8-72 125 V DC Circuit Breaker E2U CB-F-1B-A MS-CS-3002-2 Control Switch with Indication G2J CB-F-1B-A MS-SS-3002-3 Selector Switch FN9 ET-F-1D-A MS-SS-3002-1 Selector Switch G2J CB-F-1B-A MS-ZS-3002-B Valve Position Switch V2P MS-F-2A-Z MS-PY-3002-1 Solenoid Valve UOG MS-F-2A-Z MS-PY-3002-2 Solenoid Valve UOG MS-F-2A-Z MS-PY-3002-3 Solenoid Valve UOH MS-F-2A-Z MS-PY-3002-4 Solenoid Valve UOH MS-F-2A-Z MS-SS-3002-2 Selector Switch G5Y DG-F-2B-A UOJ MS-PY-3002-5 + 6 Solenoid Valve E2T CB-F-1A-A - - - - Note 6 14 MS-PV-3004 Main Steam Header Atmospheric

Relief Valve MS-20580 A/B 310589 MS-F-2B-Z X X X X V2R MS-HIC-3004 Auto/Manual Controller with

Indicator G2J CB-F-1B-A MS-PV-3001 or MS-PV-3003 MS-HQY-3004 Mixing Amplifier GZO CB-F-1B-A MS-HY-3004 Signal Converter GZ0 CB-F-1B-A MS-SS-3004 Selector Switch G2J CB-F-1B-A G2J-GZ6 G2J-V2R E2U-G5Y/1 G2J-G5Y/1 FN9-U0D FN9-U0E FN9-G2J/2 310841 G2Ja FJ4d E2U/10a E2U/10e E2U/10f CBA-FN-32 CBA-FN-33 MM-UQ-5866

MM-UQ-5867 Instrument Air EDE-PP-113B CBA-FN-32

CBA-FN-33 Instrument Air MS-CS-3004-2 Control Switch with Indication G2J CB-F-1B-A MS-PY-3004 I/P Converter GZ6 MS-F-1B-Z MS-E2U/10-72 125 V DC Circuit Breaker E2U CB-F-1B-A MS-SS-3004-3 Selector Switch FN9 ET-F-1D-A MS-CS-3004-2 Control Switch with Indication G2J CB-F-1B-A MS-SS-3004-1 Selector Switch G2J CB-F-1B-A MS-ZS-3004-B Valve Position Switch V2R MS-F-2B-Z MS-PY-3004-1 Solenoid Valve UOD MS-F-2B-Z MS-PY-3004-2 Solenoid Valve UOD MS-F-2B-Z MS-PY-3004-3 Solenoid Valve UOE MS-F-2B-Z MS-PY-3004-4 Solenoid Valve UOE MS-F-2B-Z MS-SS-3004-2 Selector Switch G5Y DG-F-2B-A UOF MS-PY-3004-5 + 6 Solenoid Valve E2T CB-F-1A-A - - - - Note 6 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-6 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 MS-V-86 Main Steam Isolation Valve MS-20583 A/B 310589 MS-F-2B-Z X X X X MS-E87/14-72 125 V DC Circuit Breaker E87 CB-F-1A-A None Notes 4 and 5 ZVO ZV1 ZV2 ZW1 MS-FY-89A-1 Pilot Solenoid ZV1 MS-F-2B-Z MS-FY-10A-1 Pilot Solenoid ZV1 MS-F-2B-Z MS-FY-102A-1 Solenoid Valve ZV1 MS-F-2B-Z MS-FY-102B-1 Solenoid Valve ZV1 MS-F-2B-Z 310841 E87/14a E87/14b MS-GX6-K103 Output Relay GX6 MS-F-3A-Z E87-GX6 GX6-ZV1 CBA-FN-19

CBA-FN-20 EDE-PP-112A MS-GX6-K104 Output Relay GX6 MS-F-3A-Z MS-GX6-CS-3005-A Control Switch GX6 MS-F-3A-Z MS-E1S/7-52 120 V AC Circuit Breaker E1S CB-F-1A-A MS-GX6-FU-101&102 120 V AC Fuses GX6 MS-F-3A-Z CBA-FN-19

CBA-FN-20 EDE-PP-11E MS-GX6-K101 Output Relay GX6 MS-F-3A-Z E1S-GX6/1 G2G-GX6/4 G2G-GX6/5 GX6-ZV0 G2G-GX6/3 E1S/7a E1S/7h E1S/7b E1S/7i E1S/7c E1S/7j E1S/7d E1S/7k MS-GX6-K102 Output Relay GX6 MS-F-3A-Z MS-ZS-V86A-1 Valve Position Switch ZV0 MS-F-2B-Z MS-ZS-V86A-2 Valve Position Switch ZV0 MS-F-2B-Z MS-ZL-3005-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-184 MSIV Logic Cabinet (Train A) GX6 MS-F-3A-Z MS-E88/14-72 125 V DC Circuit Breaker E88 CB-F-1B-A E88-GX9 GX9-ZV2 E88/14a E88/14b MS-FY-89B-1 Pilot Solenoid ZV2 MS-F-2B-Z CBA-FN-32

CBA-FN-33 EDE-PP-112B MS-FY-10B-1 Pilot Solenoid ZV2 MS-F-2B-Z MS-FY-117A-1 Solenoid Valve ZV2 MS-F-2B-Z MS-FY-117B-1 Solenoid Valve ZV2 MS-F-2B-Z MS-GX9-K103 Output Relay GX9 CB-F-1B-A MS-GX9-K104 Output Relay GX9 CB-F-1B-A MS-GX9-CS-3005-B Control Switch GX9 CB-F-1B-A MS-E1T/7-52 120 V AC Circuit Breaker E1T CB-F-1B-A MS-GX9-FU-101&102 120 V AC Fuses GX9 CB-F-1B-A E1T/7a E1T/7f E1T/7b E1T/7c CBA-FN-32

CBA-FN-33 EDE-PP-11F MS-GX9-K101 Output Relay GX9 CB-F-1B-A E1T-GX9/3 G2J-GX9/1 G2J-GX9 GX9-Z1C MS-GX9-K102 Output Relay GX9 CB-F-1B-A MS-ZS-V86B-1 Valve Position Switch ZW1 MS-F-2B-Z MS-ZS-V86B-2 Valve Position Switch ZW1 MS-F-2B-Z MS-ZL-3005-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-CP-185 MSIV Logic Cabinet (Train B) GX9 CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-7 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 16 MS-V-88 Main Steam Isolation Valve MS-20583 A/B 310586 MS-F-2A-Z X X X X MS-E2T/12-72 125 V DC Circuit Breaker E2T CB-F-1A-A None Notes 4 and 5 MS-FY-89A-2 Pilot Solenoid ZW3 MS-F-2A-Z ZW3 ZW4 ZW5 ZW6 MS-FY-10A-2 Pilot Solenoid ZW3 MS-F-2A-Z MS-FY-102A-2 Solenoid Valve ZW3 MS-F-2A-Z MS-FY-102B-2 Solenoid Valve ZW3 MS-F-2A-Z MS-GX7-K103 Output Relay GX7 MS-F-3A-Z MS-GX7-K104 Output Relay GX7 MS-F-3A-Z MS-GX7-CS-3006-A Control Switch GX7 MS-F-3A-Z E2T-GX7 GX7-ZW3 310841 E2T/12a E3T/12c CBA-FN-19

CBA-FN-20 EDE-PP-113A MS-E1S/9-52 120 V AC Circuit Breaker E1S CB-F-1A-A MS-GX7-FU-101&102 120 V AC Fuses GX7 MS-F-3A-Z CBA-FN-19

CBA-FN-20 EDE-PP-11E MS-GX7-K101 Output Relay GX7 MS-F-3A-Z E1S-GX7/1 G2G-GX7/4 G2G-GX7/5 GX7-ZW5 G2G-GX7/3 E1S/9a E1S/9h E1S/9b E1S/9i E1S/9c E1S/9j E1S/9D E1S/9k MS-GX7-K102 Output Relay GX7 MS-F-3A-Z MS-ZS-V88A-1 Valve Position Switch ZW5 MS-F-2A-Z MS-ZS-V88A-2 Valve Position Switch ZW5 MS-F-2A-Z MS-ZL-3006-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-182 MSIV Logic Cabinet (Train A) GX7 MS-F-3A-Z MS-E2U/12-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-GX8 GX8-ZW4 E2U/12a E2U/12c MS-GX8-K103 Output Relay GX8 CB-F-1B-A CBA-FN-32

CBA-FN-33 EDE-PP-113B MS-GX8-K104 Output Relay GX8 CB-F-1B-A MS-FY-89B-2 Pilot Solenoid ZW4 MS-F-2A-Z MS-FY-10B-2 Pilot Solenoid ZW4 MS-F-2A-Z MS-FY-117A-2 Solenoid Valve ZW4 MS-F-2A-Z MS-FY-117B-2 Solenoid Valve ZW4 MS-F-2A-Z MS-GX8-CS-3006B Control Switch GX8 CB-F-1B-A MS-E1T/9-52 120 V AC Circuit Breaker E1T CB-F-1B-A MS-GX8-FU-101&102 120 V AC Fuses GX8 CB-F-1B-A CBA-FN-32

CBA-FN-33 EDE-PP-11F MS-GX8-K101 Output Relay GX8 CB-F-1B-A E1T-GX8/3 G2J-GX8 GX8-ZW6 G2J-GX8/1 E1T/9a E1T/9f E1T/9b E1T/9g E1T/9c E1T/9h E1T/9i MS-GX8-K102 Output Relay GX8 CB-F-1B-A MS-ZS-V88B-1 Valve Position Switch ZW6 MS-F-2A-Z MS-ZS-V88B-2 Valve Position Switch ZW6 MS-F-2A-Z MS-ZL-3006-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A MS-CP-183 MSIV Logic Cabinet (Train B) GX8 CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-8 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 17 MS-V-90 Main Steam Isolation Valve MS-20583 A/B 310586 MS-F-2A-Z X X X X MS-E2T/14-72 125 V DC Circuit Breaker E2T CB-F-1A-A None Notes 4 and 5 MS-FY-89A-3 Pilot Solenoid ZW8 MS-F-2A-Z ZX1 ZWO ZW8 ZW9 MS-FY-10A-3 Pilot Solenoid ZW8 MS-F-2A-Z MS-FY-102A-3 Solenoid Valve ZW8 MS-F-2A-Z MS-FY-102B-3 Solenoid Valve ZW8 MS-F-2A-Z MS-GX7-K111 Output Relay GX7 MS-F-3A-Z MS-GX7-K112 Output Relay GX7 MS-F-3A-Z MS-GX7-3007-A Control Switch Gx7 MS-F-3A-Z E2T-GX7/1 GX7-ZW8 310841 E2T/14a E2T/14c CBA-FN-19

CBA-FN-20 EDE-PP-113A MS-E1S/9-52 120 V AC Circuit Breaker E1S CB-F-1A-A MS-GX7-FU-103&104 120 V AC Fuses GX7 MS-F-3A-Z CBA-FN-19

CBA-FN-20 EDE-PP-11E MS-GX7-K109 Output Relay GX7 MS-F-3A-Z E1S-GX7/1 G2G-GX7/3 G2G-GX7/4 G2G-GX7/5 GX7-ZWO E1S/9a E1S/9h E1S/9b E1S/9i E1S/9c E1S/9j E1S/9d E1S/9k MS-GX7-K110 Output Relay GX7 MS-F-3A-Z MS-ZS-V90A-1 Valve Position Switch ZWO MS-F-2A-Z MS-ZS-V90A-2 Valve Position Switch ZWO MS-F-2A-Z MS-ZL-3007-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-182 MSIV Logic Cabinet (Train A) GX7 MS-F-3A-Z MS-E2U/14-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-GX8/1 GX8-ZW9 E2U/14aE2U/14c MS-GX8-K111 Output Relay GX8 CB-F-1B-A CBA-FN-32

CBA-FN-33 EDE-PP-113B MS-GX8-K112 Output Relay GX8 CB-F-1B-A MS-FY-89B-3 Pilot Solenoid ZW9 MS-F-2A-Z MS-FY-10B-3 Pilot Solenoid ZW9 MS-F-2A-Z MS-FY-117A-3 Solenoid Valve ZW9 MS-F-2A-Z MS-FY-117B-3 Solenoid Valve ZW9 MS-F-2A-Z MS-GX8-CS-3007-B Control Switch GX8 CB-F-1B-A MS-E1T/9-52 120 V AC Circuit Breaker E1T CB-F-1B-A MS-GX8-FU-103&104 120 V AC Fuses GX8 CB-F-1B-A CBA-FN-32

CBA-FN-33 EDE-PP-11F MS-GX8-K109 Output Relay GX8 CB-F-1B-A E1T-GX8/3 G2J-GX8 G2J-GX8/1 GX8-ZX1 E1T/9a E1T/9f E1T/9b E1T/9g E1T/9c E1T/9h E1T/9i MS-GX8-K110 Output Relay GX8 CB-F-1B-A MS-ZS-V90B-1 Valve Position Switch ZX1 MS-F-2A-Z MS-ZS-V90B-2 Valve Position Switch ZX1 MS-F-2A-Z MS-ZL-3007-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-CP-183 MSIV Logic Cabinet (Train B) GX8 CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-9 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 MS-V-92 Main Steam Isolation Valve MS-20583 A/B 310589 MS-F-2B-Z X X X X MS-E87/18-52 125 V DC Circuit Breaker E87 CB-F-1A-A None Notes 4 and 5 MS-GX6-K111 Output Relay GX6 MS-F-3A-Z ZX3 Z1A Z1B Z1C MS-GX6-K112 Output Relay GX6 MS-F-3A-Z MS-FY-89A-4 Pilot Solenoid ZX3 MS-F-2B-Z MS-FY-10A-4 Pilot Solenoid ZX3 MS-F-2B-Z MS-FY-102A-4 Solenoid Valve ZX3 MS-F-2B-Z MS-FY-102B-4 Solenoid Valve ZX3 MS-F-2B-Z MS-GX6-CS-3008-A Control Switch GX-6 MS-F-3A-Z E87-GX6/1 GX6-ZX3 310841 E87/18a E87/18b CBA-FN-19

CBA-FN-20 EDE-PP-112A MS-E1S/7-52 120 V AC Circuit Breaker E1S CB-F-1A-A MS-GX6-FU-103&104 120 V AC Fuses GX6 MS-F-3A-Z CBA-FN-19

CBA-FN-20 EDE-PP-11E MS-GX6-K109 Output Relay GX6 MS-F-3A-Z E1S-GX6/1 G2G-GX6/3 G2G-GX6/4 G2G-GX6/5 GX6-Z1B E1S/7a E1S/7h E1S/7b E1S/7i E1S/7c E1S/7j E1S/7d E1S/7k MS-GX6-K110 Output Relay GX6 MS-F-3A-Z MS-ZS-V92A-1 Valve Position Switch Z1B MS-F-2B-Z MS-ZS-V92A-2 Valve Position Switch Z1B MS-F-2B-Z MS-ZL-3008-1 Valve Position Indicating Lights G2G CB-F-1A-A MS-SS-3005-1 Selector Switch G2G CB-F-1A-A MS-CP-184 MSIV Logic Cabinet (Train A) GX6 MS-F-3A-Z MS-E88/9-72 125 V DC Circuit Breaker E88 CB-F-1B-A E88-GX9/1 GX9-Z1A E88/9aE88/9b MS-GX9-K111 Output Relay GX9 CB-F-1B-A CBA-FN-32

CBA-FN-33 EDE-PP-112B MS-GX9-K112 Output Relay GX9 CB-F-1B-A MS-FY-89B-4 Pilot Solenoid Z1A MS-F-2B-Z MS-FY-10B-4 Pilot Solenoid Z1A MS-F-2B-Z MS-FY-117A-4 Solenoid Valve Z1A MS-F-2B-Z MS-FY-117B-4 Solenoid Valve Z1A MS-F-2B-Z MS-GX9-CS-3008-B Control Switch GX9 CB-F-1B-A MS-E1T/7-52 125 V AC Circuit Breaker E1T CB-F-1B-A MS-GX9-FU-103&104 120 V AC Fuses GX9 CB-F-1B-A CBA-FN-32

CBA-FN-33 EDE-PP-11F MS-GX9-K109 Output Relay GX9 CB-F-1B-A E1T-GX9/3 GX9-Z1C G2J-GX9 G2J-GX9/1 E1T/7a E1T/7f E1T/7b E1T/7g E1T/7c E1T/7h E1T/7i MS-GX9-K110 Output Relay GX9 CB-F-1B-A MS-ZS-V92B-1 Valve Position Switch Z1C MS-F-2B-Z MS-ZS-V92B-2 Valve Position Switch Z1C MS-F-2B-Z MS-ZL-3008-2 Valve Position Indicating Lights G2J CB-F-1B-A MS-SS-3005-2 Selector Switch G2J CB-F-1B-A MS-CP-185 MSIV Logic Cabinet (Train B) GX9 CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-10 FUNCTION: DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 MS-V-204 Main Steam Isolation Valve

Bypass Valve MS-20583 A 310589 MS-F-2B-Z X X X - VU6 MS-B1X-52 460 V AC Circuit Breaker B1X CB-F-1A-A - - - - None Note 2 20 MS-V-205 Main Steam Isolation Valve

Bypass Valve MS-20583 A 310589 MS-F-2A-Z X X X - VU7 MS-B1Y-52 460 V AC Circuit Breaker B1Y CB-F-1A-A - - - - None Note 2 21 MS-V-206 Main Steam Isolation Valve

Bypass Valve MS-20583 A 310589 MS-F-2A-Z X X X - VU8 MS-B1Z-52 460 V AC Circuit Breaker B1Z CB-F-1A-A - - - - None Note 2 22 MS-V-207 Main Steam Isolation Valve

Bypass Valve MS-20583 A 310589 MS-F-2B-Z X X X - VU9 MS-B2A-52 460 V AC Circuit Breaker B2A CB-F-1A-A - - - - None Note 2 23 RC-E-11A Steam Generator RC-20841 A 310576 310582 310578 C-F-1-Z C-F-1-Z C-F-2-Z X X - - - - - - - - - -

- RC-E-11B or RC-E-11D Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.1-11 FUNCTION:  DECAY HEAT REMOVAL PHYSICAL REQUIRED FOR POWER  SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO.

TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 24 RC-E-11B Steam Generator RC-20842 B 310576 310582 310578 C-F-1-Z C-F-1-Z C-F-2-Z X X - - - - - - - - - -

- RC-E-11A or RC-E-11C Note 1 25 RC-E-11C Steam Generator RC-20843 A 310577 310583 310579 C-F-1-Z C-F-1-Z C-F-2-Z X X - - - - - - - - - -
- RC-E-11B or RC-E-11D Note 1 26 RC-E-11D Steam Generator RC-20844 B 310577 310583 310579 C-F-1-Z C-F-1-Z C-F-2-Z X X - - - - - - - - - -
- RC-E-11A or RC-E-11C Note 1 27 SB-V9 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM4 SB-E88/18-72 125 V DC Circuit Breaker E88 CB-F-1B-A - - -
- SB-V-1 Notes 3 and 4 28 SB-V10 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM5 SB-E88/18-72 125 V DC Circuit Breaker E88 CB-F-1B-A - - -
- SB-V-3 Notes 3 and 4 29 SB-V11 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM6 SB-E88/18-72 125 V DC Circuit Breaker E88 CB-F-1B-A - - -
- SB-V-5 Notes 3 and 4 30 SB-V12 Outboard Blowdown Isolation Valve SB-20626 B 310589 MS-F-1B-Z X X X X UM7 SB-E88/18-72 125 V DC Circuit Breaker E88 CB-F-1B-A - - -
- SB-V-7 Notes 3 and 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2

-1 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 RC-E-10 Reactor Coolant System Pressurizer RC-20846 A/B 310598 C-F-1-Z X X - - - - - - - - - - None Note 1 2 RC-E-10 Pressurizer Heaters Group A RC-20846 A 310598 C-F-1-Z X X X - M26 RC-AB4-52 480 V AC Circuit Breaker AB4 CB-F-1A-A AB4-E07 AB4-E07/1 AB4-G81 AB4-G81/1 E07-H14 E07-H14/1 E07-H14/2 E07-H14/3 E07-H14/4 H14-X47 H14-X47/1 H14-X47/2 H14-X47/3 H14-X47/4 M26-X47 M26-X47/1 M26-X47/2 M26-X47/3 M26-X47/4 M26-X47/5 M26-X47/6 M26-X47/7 M26-X47/8 M26-X47/9 M26-X47/A M26-X47/B M26-X47/C M26-X47/D M26-X47/E 310882 AB4a AB4g AB4b AB4c CBA-FN-19 CBA-FN-20 EDE-US-52 Pressurizer Heaters Group B RC-AB4-FU Fuses AB4 CB-F-1A-A RC-CS-7318-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-7318 Selector Switch G81 CB-F-1A-A EDE-AC3-94-3 Bus Undervoltage Relay AC3 CB-F-1A-A RC-AB4-52H-1 Truck Operated Contact AB4 CB-F-1A-A EDE-TBX-X47 Terminal Box X47 C-F-1-Z RC-AB4-G,R Indicating Lights AB4 CB-F-1A-A RC-AB4-CT1 Current Transformer (600/5) øB Bus Side AB4 CB-F-1A-A RC-AB4-AM Ammeter AB4 CB-F-1A-A RC-AB4-CT2 Current Transformer (600/5) øA, øC Load Side AB4 CB-F-1A-A RC-AC3-WTR Watt Transducer AC3 CB-F-1A-A RC-PP-6A Distribution Panel E07 ET-F-1A-A EDE-MM-90 Electrical Penetration H14 ET-F-1A-A, C-F-2-Z

.Notes   1. The equipment is mechanical with no electrical requirement.
2. During normal operation, the valve is in its safe shutdown position. To prevent spurious operations, this equipment will be disabled at the appropriate control location.
3. Disabling the valve at the appropriate control location will reposition it for safe shutdown.
4. Air is not needed to position or to reposition the valve for safe shutdown.
5. These valves are closed with their circuit breakers locked open during 100% power operation. This will prevent spurious operation. For cold shutdown, these valves are energized for repositioning.
6. Not Used.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -2 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 RC-E-10 Pressurizer Heaters Group B RC-20846 B 310598 C-F-1-Z X X X - M26 RC-AD4-52 480 V AC Circuit Breaker AD4 CB-F-1B-A AD4-E08 AD4-E08/1 AD4-GZ0 AD4-GZ0/1 AE3-GZ0 E08-H20 E08-H20/1 E08-H20/2 E08-H20/3 E08-H20/4 H20-X44 H20-X44/1 H20-X44/2 H20-X44/3 H20-X44/4 M26-X44 M26-X44/1 M26-X44/2 M26-X44/3 M26-X44/4 M26-X44/5 M26-X44/6 M26-X44/7 M26-X44/8 M26-X44/9 M26-X44/A M26-X44/B M26-X44/C M26-X44/D M26-X44/E 310882 AD4a AD4f AD4b AD4c CBA-FN-32 CBA-FN-33 EDE-US-62 Pressurizer Heaters Group A RC-AD4-FU Fuses AD4 CB-F-1B-A RC-CS-7319-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-7319 Selector Switch GZ0 CB-F-1B-A EDE-AE3-94-3 Bus Undervoltage Relay AE3 CB-F-1B-A RC-AD4-52H-1 Truck Operated Contact AD4 CB-F-1B-A RC-AD4-G,R Indicating Lights AD4 CB-F-1B-A EDE-TBX-X44 Terminal Box X44 C-F-1-Z RC-AD4-CT1 Current Transformer (600/5) øB Bus Side AD4 CB-F-1B-A RC-AD4-AM Ammeter AD4 CB-F-1B-A RC-AD4-CT2 Current Transformer (600/5) øA, øC Load Side AD4 CB-F-1B-A RC-AE3-WTR Watt Transducer AE3 CB-F-1B-A RC-PP-6B Distribution Panel E08 ET-F-1C-A EDE-MM-96 Electrical Penetration H20 ET-F-1C-A, C-F-1-Z RC-AE3-R1 Auxiliary Relay AE3 CB-F-1B-A 4 RC-V-122 RC-E-10 Pressurizer Relief Isolation Valve RC-20846 A 310581 C-F-3-Z X X X - V01 RC-B97-52-1,2 460 V AC Circuit Breakers B97 CB-F-1A-A B97-G81 B97-G81/1 B97-H18 B97-H35 H18-V01 H35-X56 V01-X56 310882 B97a B97c B97e CBA-FN-19 CBA-FN-20 EDE-MCC-521 RC-V-124 RC-PCV-456A RC-B97-FU Fuse B97 CB-F-1A-A RC-CS-7313-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-7313 Selector Switch G81 CB-F-1A-A RC-B97-42-1/0,C Motor Starters B97 CB-F-1A-A RC-B97-42-2 Motor Starter B97 CB-F-1A-A RC-B97-49-1,2 Overload Relays B97 CB-F-1A-A EDE-TBX-X56 Terminal Box X56 C-F-3-Z RC-ZS-V122 Valve Position Switch and Valve Open/Close Torque Switches V01 C-F-3-Z EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A

Notes 7. These valves are also listed in Table RSS 3.1.3.6.

8. This group of pressurizer heaters will be disabled at the appropriate control location to prevent spurious operation.
9. Electrical conduit plan drawing, 9763

-F-310764, is listed only to show the fire zone corresponding to the area where the charging pump oil coolers are located (9763 -F-805213 and -F815214).

10. Reactor Coolant Pumps will be tripped prior to main control room evacuation or they can be tripped in Non

-Essential Switchgear Room, if required.

11. This equipment will be disabled by tripping and racking

-out its circuit breaker at the switchgear.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -3 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 RC-V-124 RC-E-10 Pressurizer Relief Isolation Valve RC-20846 B 310581 C-F-3-Z X X X - V02 RC-B98-52-1,2 460 V AC Circuit Breakers B98 CB-F-1B-A B98-GZ0 B98-GZ0/1 B98-GZ0/2 B98-H15 B98-H41 H15-V02 H41-X35 V02-X35 310882 B98a B98c B98e CBA-FN-32 CBA-FN-33 EDE-MCC-621 RC-V-122 RC-PCV-456B RC-B98-FU Fuse B98 CB-F-1B-A FC-CS-7314-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-7314 Selector Switch GZ0 CB-F-1B-A RC-B98-42-1/0,C Motor Starters B98 CB-F-1B-A RC-B98-42-2 Motor Starter B98 CB-F-1B-A RC-B98-49-1,2 Overload Relays B98 CB-F-1B-A EDE-TBX-X35 Terminal Box X35 C-F-3-Z RC-ZS-V124 Valve Position Switch and Valve Open/Close Torque Switches V02 C-F-3-Z EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A 6 RC-PCV-456A RC-E-10 Pressurizer Relief Control Valve RC-20846 A 310581 C-F-3-Z X X X LD3 RC-E87/19-72 125 V DC Circuit Breaker E87 CB-F-1A-A E87-E4A/4 E4A-J3M G81-J3M G81-H35 G5X-J3M H18-J3M H18-LD3 H35-X56/2 LD3-X56 310882 E87/19a E87/19c CBA-FN-19 CBA-FN-20 EDE-PP-112A RC-PCV-456B RC-V-122 RC-CS-456A-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-456-A1 Selector Switch G81 CB-F-1A-A RC-SS-456-A2 Selector Switch G5X DG-F-2A-A RC-J3M-42 Auxiliary Relay J3M DG-F-2A-A RC-PCV-456A-20 Solenoid Operating Coil LD3 C-F-3-Z RC-ZS-PCV-456A Valve Position Switch LD3 C-F-3-Z RC-E4A-FU11,12 30 A Fuses E4A CB-F-1A-A EDE-TBX-X56 Terminal Box X56 C-F-3-Z EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -4 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 RC-PCV-456B RC-E-10 Pressurizer Relief Control Valve RC-20846 B 310581 C-F-3-Z X X X LD4 RC-E88/19-72 125 V DC Circuit Breaker E88 CB-F-1B-A E88-E4C/7 E4C-GZO/2 E4C-J3P GZ0-J3P GZO-H39 G5Y-J3P H24-J3P H24-LD4 H39-X35 LD4-X35 310882 E88/19a E88/19c CBA-FN-32 CBA-FN-33 EDE-PP-112B RC-PCV-456A or RC-V-124 RC-CS-456B-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-456-B1 Selector Switch GZ0 CB-F-1B-A RC-SS-456-B2 Selector Switch G5Y DG-F-2B-A RC-J3P-42 Auxiliary Relay J3P DG-F-2B-A RC-PCV-456B-20 Solenoid Operating Coil LD4 C-F-3-Z RC-ZS-PCV-456B Valve Position Switch LD4 C-F-3-Z RC-E4C-FU19 & 20 30 A Fuses E4C CB-F-1B-A EDE-TBX-X35 Terminal Box X35 C-F-3-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-E4C-FU-23,24 30 A Fuses E4C CB-F-1B-A 8 RC-TK11 Pressurizer Relief Tank RC-20846 A/B 310577 C-F-1-Z X X - - - - - - - - - - - None Note 1 9 RC-V-323 Reactor Vessel Venting Valve RC-20845 B 310581 C-F-3-Z X X X - VB2 RC-BV9-52-1 460 V AC Circuit Breaker BV9 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 RC-FV-2881 Note 2 10 RC-FV-2881 Reactor Vessel Venting Valve RC-20845 B 310581 C-F-3-Z X X X UO4 RC-E88/1-72 125 V DC Circuit Breaker E88 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B RC-V-323 Note 2 RC-SS-2881 Selector Switch G5Y DG-F-2B-A 11 RC-LCV-459 Letdown Isolation Valve RC-20843 A 310577 C-F-1-Z X X X X L99 RC-E89/17-72 125 V DC Circuit Breaker E89 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 DAH-FN-25A DAH-FN-26A RC-LCV-460 Note 3, 4 RC-SS-459 Selector Switch G5X DG-F-2A-A 12 RC-LCV-460 Letdown Isolation Valve RC-20843 A 310577 C-F-1-Z X X X X LF7 RC-E89/1-72 125 V DC Circuit Breaker E89 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 RC-LCV-459 Note 3, 4

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -5 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 13 CS-P-2A Charging Pump CS-20725 A 310764 PAB-F-1C-A X X X - M17 CS-A62-52 4160 V AC Circuit Breaker A62 CB-F-1A-A A62-M17 A62-P01 310891 A62a A62h A62b A62c A62d CBA-FN-19 CBA-FN-20 EAH-FN-5A EDE-SWG-5 CS-P-2B CS-CS-7424-2 Control Switch A62 CB-F-1A-A CS-SS-7424 Selector Switch A62 CB-F-1A-A CS-A62-86 Lockout Relay A62 CB-F-1A-A CS-A62-52H Truck Operated Contact A62 CB-F-1A-A CS-A62-50/51 Inst./Time Over Current Relays øA, øC A62 CB-F-1A-A CS-PS-7467-1 Pressure Switch P01 PAB-F-1C-A CS-A62-AM Ammeter A62 CB-F-1A-A CS-A62-AS Ammeter Switch A62 CB-F-1A-A CS-A62-CT Current Transformer (100/5) A62 CB-F-1A-A CS-A62-TD1 CT Test Device A62 CB-F-1A-A CS-A62-ATR Transducer A62 CB-F-1A-A CS-A62-TD2 Lockout Relay Test Device A62 CB-F-1A-A CS-A62-TDR Timing Relay A62 CB-F-1A-A CS-A62-FU Fuses A62 CB-F-1A-A CS-A62-52Z Timing Relay A62 CB-F-1A-A CS-A62-G,R,W Indicating Lights A62 CB-F-1A-A CS-A62-51GS Ground Sensor Relay A62 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -6 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 14 CS-P-2B Charging Pump CS-20725 B 310764 PAB-F-1D-A X X X - M18 CS-A82-52 4160 V AC Circuit Breaker A82 CB-F-1B-A A82-M18 A82-P02 310891 A82a A82h A82b A82c A82d CBA-FN-32 CBA-FN-33 EAH-FN-5B EDE-SWG-6 CS-P-2A CS-CS-7425-2 Control Switch A82 CB-F-1B-A CS-SS-7425 Selector Switch A82 CB-F-1B-A CS-A82-86 Lockout Relay A82 CB-F-1B-A CS-A82-52H Truck Operated Contact A82 CB-F-1B-A CS-A82-50/51 Inst./Time Over Current Relays øA, øB A82 CB-F-1B-A CS-PS-7468-1 Pressure Switch P02 PAB-F-1D-A CS-A82-AM Ammeter A82 CB-F-1B-A CS-A82-AS Ammeter Switch A82 CB-F-1B-A CS-A82-CT Current Transformer (100/5) A82 CB-F-1B-A CS-A82-TD1 CT Test Device A82 CB-F-1B-A CS-A82-ATR Transducer A82 CB-F-1B-A CS-A82-TD2 Lockout Relay Test Device A82 CB-F-1B-A CS-A82-TDR Timing Relay A82 CB-F-1B-A CS-A82-FU Fuses A82 CB-F-1B-A CS-A82-52Z Timing Relay A82 CB-F-1B-A CS-A82-G,R,W Indicating Lights A82 CB-F-1B-A CS-A82-51GS Ground Sensor Relay A82 CB-F-1B-A CS-A82-R2 Auxiliary Relay A82 CB-F-1B-A 15 RC-P-1A Reactor Coolant Pump RC-20841 A 310576 310582 310578 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M01 RC-A05-52 13.8 kV AC Circuit Breaker A05 NES-F-1A-Z - - - - None Note 10 16 RC-P-1B Reactor Coolant Pump RC-20842 A 310576 310582 310578 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M02 RC-A20-52 13.8 kV AC Circuit Breaker A20 NES-F-1A-Z - - - - None Note 10 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -7 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 17 RC-P-1C Reactor Coolant Pump RC-20843 A 310577 310583 310579 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M03 RC-A09-52 13.8 kV AC Circuit Breaker A09 NES-F-1A-Z - - - - None Note 10 18 RC-P-1D Reactor Coolant Pump RC-20844 A 310577 310583 310579 C-F-1-Z C-F-1-Z C-F-2-Z X - X - M04 RC-A24-52 13.8 kV AC Circuit Breaker A24 NES-F-1A-Z - - - - None Note 10 19 RC-V-22 RC-E-11A Hot Leg -RHR Isolation Valve RC-20841 B 310582 C-F-1-Z - X X - V27 RC-B54-52-1 460 V AC Circuit Breaker B54 CB-F-1B-A - - - - RC-V-23 Notes 5 and 7 20 RC-V-23 RC-E-11A Hot Leg -RHR Isolation Valve RC-20841 A 310576 C-F-1-Z - X X - V25 RC-B53-52-1 460 V AC Circuit Breaker B53 CB-F-1A-A - - - - RC-V-22 Notes 5 and 7 21 RC-V-87 RC-E-11D Hot Leg -RHR Isolation Valve RC-20844 B 310582 C-F-1-Z - X X - V26 RC-B61-52-1 460 V AC Circuit Breaker B61 CB-F-1B-A - - - - RC-V-87 Notes 5 and 7 22 RC-V-88 RC-E-11D Hot Leg -RHR Isolation Valve RC-20844 A 310577 C-F-1-Z - X X - V28 RC-B62-52-1 460 V AC Circuit Breaker B62 CB-F-1A-A - - - - RC-V-88 Notes 5 and 7 23 SI-V-3 Accumulator TK -9A Outlet Isolation Valve SI-20450 A 310576 C-F-1-Z - X X - V39 SI-B35-5-1,2 460 V AC Circuit Breakers B35 CB-F-1A-A B35-G81 B35-H19 B35-H36 H19-V39 H36-V39 310890 B35a B35c CBA-FN-19 CBA-FN-20 EDE-MCC-522 SI-FV-2475 SI-FV-2476 SI-B35-FU Fuse B35 CB-F-1A-A SI-CS-2403-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2403 Selector Switch G81 CB-F-1A-A SI-ZL-2403-4 Pilot Light G81 CB-F-1A-A SI-B35-42/0,C Motor Starters B35 CB-F-1A-A SI-B35-49 Overload Relay B35 CB-F-1A-A SI-ZS-V3 Valve Position and Open/Close Torque Switches V39 C-F-1-Z EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SI-EH9/9-52 120 V AC Circuit Breaker EH9 CB-F-1A-A G81-H35/5 G81-H36/6 H35-V41/1 H36-V39/1 E4H-EH9 E4H-G81 EH9/9a EH9/9b CBA-FN-19 CBA-FN-20 EDE-PP-1E SI-CS-2403-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2403 Selector Switch G81 CB-F-1A-A SI-ZS-V3 Valve Position and Open/Close Torque Switches V39 C-F-1-Z SI-E4H-FU7,8 30 A Fuses E4H CB-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -8 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 24 SI-V-17 Accumulator TK -9B Outlet Isolation Valve SI-20450 B 310576 C-F-1-Z - X X - V40 SI-B36-52-1,2 460 V AC Circuit Breakers B36 CB-F-1B-A B36-GZ0 B36-H15 B36-H41 H15-V40 H41-V40 310890 B36a B36c CBA-FN-32 CBA-FN-33 EDE-MCC-622 SI-FV-2482 SI-FV-2483 SI-B36-FU Fuse B36 CB-F-1B-A SI-CS-2413-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2413 Selector Switch GZ0 CB-F-1B-A SI-ZL-2413-4 Pilot Light GZ0 CB-F-1B-A SI-B36-42/0,C Motor Starters B36 CB-F-1B-A SI-B36-49 Overload Relay B36 CB-F-1B-A SI-ZS-V17 Valve Position and Open/Close Torque Switches V40 C-F-1-Z EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A SI-EH0/9-52 120 V AC Circuit Breaker EH0 CB-F-1B-A GZ0-H39/5 GZ0-H41/4 H39-V42/1 H41-V40/1 E4J-EH0 E4J-GZ0 EH0/9a EH0/9b CBA-FN-32 CBA-FN-33 EDE-PP-1F SI-CS-2413-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2413 Selector Switch GZ0 CB-F-1B-A SI-ZS-V17 Valve Position and Open/Close Torque Switches V40 C-F-1-Z SI-E4J-FU7,8 30 A Fuses E4J CB-F-1B-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -9 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 25 SI-V-32 Accumulator TK -9C Outlet Isolation Valve SI-20450 A 310577 C-F-1-Z - X X - V41 SI-B37-52-1,2 460 V AC Circuit Breakers B37 CB-F-1A-A B37-G81 B37-H18 B37-H35 H18-V41 H35-V41 B37a B37c CBA-FN-19 CBA-FN-20 EDE-MCC-522 SI-FV-2477 SI-FV-2486 SI-B37-FU Fuse B37 CB-F-1A-A SI-CS-2423-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2423 Selector Switch G81 CB-F-1A-A SI-ZL-2423-4 Pilot Light G81 CB-F-1A-A SI-B37-42/0,C Motor Starter s B37 CB-F-1A-A SI-B37-49 Overload Relay B37 CB-F-1A-A EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A SI-ZS-V32 Valve Position and Open/Close Torque Switches V41 C-F-1-Z SI-EH9/9-52 120 V AC Circuit Breakers EH9 CB-F-1A-A G81-H35/5 G81-H36/6 H35-V41/1 H36-V39/1 E4H-EH9 E4H-G81 EH9/9a EH9/9b CBA-FN-19 CBA-FN-20 EDE-PP-1E SI-CS-2423-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2423 Selector Switch G81 CB-F-1A-A SI-ZS-V32 Valve Position and Open/Close Torque Switches V41 C-F-1-Z SI-E4H-FU7,8 30 A Fuses E4H CB-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -10 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 26 SI-V-47 Accumulator TK -9D Outlet Isolation Valve SI-20450 B 310577 C-F-1-Z - X X - V42 SI-B38-52-1,2 460 V AC Circuit Breakers B38 CB-F-1B-A B38-GZ0 B38-H24 B38-H39 H24-V42 H39-V42 310890 B38a B38c CBA-FN-32 CBA-FN-33 EDE-MCC-622 SI-FV-2495 SI-FV-2496 SI-B38-FU Fuse B38 CB-F-1B-A SI-CS-2433-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2433 Selector Switch GZ0 CB-F-1B-A SI-ZL-2433-4 Pilot Light GZ0 CB-F-1B-A SI-B38-42/0,C Motor Starters B38 CB-F-1B-A SI-B38-49 Overload Relay B38 CB-F-1B-A SI-ZS-V47 Valve Position and Open/Close Torque Switches V42 C-F-1-Z EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A SI-EH0/9-52 120 V AC Circuit Breaker EH0 CB-F-1B-A GZ0-H39/5 GZ0-H41/4 H39-V42/1 H41-V40/1 E4J-EH0 E4J-GZ0 EH0/9a EH0/9b CBA-FN-32 CBA-FN-33 EDE-PP-1F SI-CS-2433-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2433 Selector Switch GZ0 CB-F-1B-A SI-ZS-V47 Valve Position and Open/Close Torque Switches V42 C-F-1-Z SI-E4J-FU7,8 30 A Fuses E4J CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A 27 CS-P-2A Charging Pump Lube Oil Cooler CS-20725 A 310764 805213 PAB-F-1C-A X X - - - - - - - - - - Component Cooling CS-P-2B Note 9 28 CS-P-2B Charging Pump Lube Oil Cooler CS-20725 B 310764 815214 PAB-F-1D-A X X - - - - - - - - - - Component Cooling CS-P-2A Note 9 29 CS-V-460 SI-P-6A Suction Valve CS-20725 A 310761 RHR-F-2B-Z - X X - V59 CS-B44-52 460 V AC Circuit Breaker B44 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 2 30 CS-V-461 SI-P-6A Suction Valve CS-20725 B 310761 RHR-F-2B-Z - X X - V60 VS-B45-52 460 V AC Circuit Breaker B45 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 2 31 CS-V-167 RC Pump Seal Water Isolation Valve CS-20726 A 310769 PP-F-5B-Z X X X - V05 CS-B73-52 460 V AC Circuit Breaker B73 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 2 32 CS-V-168 RC Pump Seal Water Isolation Valve CS-20726 B 310577 C-F-1-Z X X X - V06 CS-B72-52-1 450 V AC Circuit Breaker B72 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 2 33 CS-V-175 Excess Letdown Isolation Valve CS-20722 B 310577 C-F-1-Z X X X X L95 CS-E95/2-72 125 V DC Circuit Breaker E95 C-F-1B-A CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B CS-V-176 Notes 2 and 4 CS-SS-7418 Selector Switch G5Y DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -11 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 34 CS-V-176 Excess Letdown Isolation Valve CS-20722 B 310577 C-F-1-Z X X X X LA5 CS-E95/4-72 125 V DC Circuit Breaker E95 CB-F-1B-A CBA-FN-32 CBA-FN-33 CS-V-175 Notes 2 and 4 35 CS-V-196 Charging Pump Miniflow Isolation Valve CS-20725 A 310762 PAB-F-1J-Z X X X - V13 CS-B81-52 460 V AC Circuit Breaker B81 CB-F-1A-A CBA-FN-19 CBA-FN-20 CS-V-197 Note 2 36 CS-V-197 Charging Pump Miniflow Isolation Valve CS-20725 B 310762 PAB-F-1J-Z X X X - V14 CS-B86-52 460 V AC Circuit Breaker B86 CB-F-1B-A CBA-FN-32 CBA-FN-33 CS-V-196 Note 2 37 CS-LCV-112B Chemical and Volume Control Tank Outlet Isolation Valve CS-20725 A 310768 PAB-F-3B-Z X X X - VE4 CS-B50-52 460 V AC Circuit Breaker B50 CB-F-1A-A B50-G2G B50-G2G/1 B50-VE4 B50-VE4/1 B50-VE4/2 E3P-G2G B50-E3P 310891 B50a B50c B50d CBA-FN-19 CBA-FN-20 EDE-MCC-512 CS-LCV-112C CS-B50-FU Fuse B50 CB-F-1A-A CS-CS-112B-2 Control Switch with Indication G2G CB-F-1A-A CS-SS-112B Selector Switch G2G CB-F-1A-A CS-B50-42/0,C Motor Starters B50 CB-F-1A-A CS-B50-49 Overload Relay B50 CB-F-1A-A CS-ZS-LCV-112B Valve Position and Open/Close Torque Switches VE4 PAB-F-3B-Z CS-EC8-R1 Auxiliary Relay EC8 CB-F-1A-A CS-E3P-R2 Auxiliary Relay E3P CB-F-1A-A 38 CS-LCV-112C Chemical and Volume Control Tank Outlet Isolation Valve CS-20725 B 310768 PAB-F-3B-Z X X X - VE7 CS-B83-52 460 V AC Circuit Breaker B83 CB-F-1B-A B83-G2J B83-G2J/1 B83-VE7 B83-VE7/1 B83-VE7/2 E3Q-G2J B83-E3Q 310891 B83a B83c B83d CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-LCV-112B CS-B83-FU Fuse B83 CB-F-1B-A CS-CS-112C-2 Control Switch with Indication G2J CB-F-1B-A CS-SS-112C Selector Switch G2J CB-F-1B-A CS-B83-42/0,C Motor Starters B83 CB-F-1B-A CS-B83-49 Overload Relay B83 CB-F-1B-A CS-ZS-LCV-112C Valve Position and Open/Close Torque Switches VE7 PAB-F-3B-Z CS-ED0-R1 Auxiliary Relay ED0 CB-F-1B-A CS-E3Q-R2 Auxiliary Relay E3Q CB-F-1B-A 39 CS-LCV-112D Refueling Water Storage Tank to Charging Pump 2A Isolation Valve CBS-20233 A 301254 TF-F-1-0 X X X - VE6 CS-B78-52 460 V AC Circuit Breaker B78 CB-F-1A-A B78-G2G B78-G2G/1 B78-VE6 B78-VE6/1 B78-VE6/2 310891 B78a B78c B78d CBA-FN-19 CBA-FN-20 EDE-MCC-512 CS-LCV-112E CS-CS-122D-2 Control Switch with Indication G2G CB-F-1A-A CS-SS-112D Selector Switch G2G CB-F-1A-A CS-B78-42/0,C Motor Starters B78 CB-F-1A-A CS-B78-49 Overload Relay B78 CB-F-1A-A CS-ZS-LCV-112D Valve Position and Open/Close Torque Switches VE6 TF-F-1-0 CS-EC8-R1 Auxiliary Relay EC8 CB-F-1A-A CS-B78-FU Fuse B78 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -12 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 40 CS-LCV-112E RWST CBS-TK-8 to Charging Pump 2B Isolation Valve CBS-20233 B 301254 TF-F-1-0 X X X - VE5 CS-B79-52 460 V AC Circuit Breaker B79 CB-F-1B-A B79-G2J B79-G2J/1 B79-VE5 B79-VE5/1 B79-VE5/2 310891 B79a B79c B79d CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-LCV-112D CS-CS-122E-2 Control Switch with Indication G2J CB-F-1B-A CS-SS-112E Selector Switch G2J CB-F-1B-A CS-B79-42/0,C Motor Starters B79 CB-F-1B-A CS-B79-49 Overload Relay B79 CB-F-1B-A CS-ZS-LCV-112E Valve Position and Open/Close Torque Switches VE5 TF-F-1-0 CS-ED0-R1 Auxiliary Relay ED0 CB-F-1B-A CS-B79-FU Fuse B79 CB-F-1B-A 41 SI-V-138 Charging Pump To Cold Leg Isolation Valve SI-20447 A 310769 PP-F-1B-Z X X X - V31 SI-B31-52 460 V AC Circuit Breaker B31 CB-F-1A-A B31-G2G B31-G2G/2 B31-V31 B31-V31/1 B31-V31/2 B31-FN8 B31-FN8/1 310890 B31a B31c B31d CBA-FN-19 CBA-FN-20 EDE-MCC-521 SI-V-139 SI-CS-2437-2 Control Switch with Indication G81 CB-F-1A-A SI-SS-2437 Selector Switch G81 CB-F-1A-A SI-SS-2437-1 Selector Switch FN8 ET-F-1B-A SI-B31-42/0,C Motor Starters B31 CB-F-1A-A SI-B31-49 Overload Relay B31 CB-F-1A-A SI-ZS-V138 Valve Position and Open/Close Torque Switches V31 PP-F-1B-Z SI-B31-FU Fuse B31 CB-F-1A-A 42 SI-V-139 Charging Pump To Cold Leg Isolation Valve SI-20447 B 310769 PP-F-1B-Z X X X - V32 SI-B32-52 460 V AC Circuit Breaker B32 CB-F-1B-A B32-G2J B32-G2J/2 B32-V32 B32-V32/1 B32-V32/2 B32-FN9 B32-FN9/1 310890 B32a B32c B32d CBA-FN-32 CBA-FN-33 EDE-MCC-621 SI-V-138 SI-CS-2447-2 Control Switch with Indication GZ0 CB-F-1B-A SI-SS-2447 Selector Switch GZ0 CB-F-1B-A SI-SS-2447-1 Selector Switch FN9 ET-F-1D-A SI-B32-42/0,C Motor Starters B32 CB-F-1B-A SI-B32-49 Overload Relay B32 CB-F-1B-A SI-ZS-V139 Valve Position and Open/Close Torque Switches V32 PP-F-1B-Z SI-B32-FU Fuses B32 CB-F-1B-A 43 RC-E-10 Pressurizer Heaters Group C RC-20846 A 310598 C-F-1-Z X - X - M26 RC-AG4-52 480 V AC Circuit Breaker AG4 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 8 44 RC-E-10 Pressurizer Heaters Group D RC-20846 A 310598 C-F-1-Z X - X - M26 RC-AM5-52 480 V AC Circuit Breaker AM5 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 8 45 CBS-P-9A Containment Spray Pump CSB-20233 A 310761 RHR-F-1B-Z X - X - M15 CBS-A61-52 4160 V AC Circuit Breaker A61 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 11 46 CBS-P-9B Containment Spray Pump CBS-20233 B 310761 RHR-F-1A-Z X - X - M16 CBS-A81-52 4160 V AC Circuit Breaker A81 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 11 47 SI-P-6A Safety Injection Pump SI-20446 A 310761 RHR-F-2B-Z - X X - M09 SI-A56-52 4160 V AC Circuit Breaker A56 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 11 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -13 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 48 SI-P-6B Safety Injection Pump SI-20446 B 310761 RHR-F-2A-Z - X X - M10 SI-A76-52 4160 V AC Circuit Breaker A76 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 11 49 SI-V-158 Charging Pump Test Line Isolation Valve SI-20447 B 310577 C-F-1-Z - X X X L89 RC-E88/7-72 125 V DC Circuit Breaker E88 CB-F-1B-A - - - - - Note 2, 4 50 SI-V-159 Charging Pump Test Line Isolation Valve SI-20447 A 310577 C-F-1-Z - X X X L90 RC-E89/4-72 125 V DC Circuit Breaker E89 CB-F-1A-A - - - - - Note 2, 4 51 SI-FV-2475 Accumulator TK -9A Relief Valve SI-20450 B 310578 C-F-2-Z - X X - V2Z SI-E2U/7-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-E4C/3 E4C-GZ0/1 GZ0-H39/6 H39-V2Z 310890 E2U/7a E2U/7f E2U/7g E2U/7h EDE-PP-113B SI-E4C-FU Fuses E4C CB-F-1B-A SI-SS-2475 Selector Switch GZ0 CB-F-1B-A SI-CS-2475-2 Control Switch with Indication GZ0 CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A SI-20-FV-2475 Solenoid Valve V2Z C-F-2-Z SI-ZS-FV-2475 Valve Position Switch V2Z C-F-2-Z 52 SI-FV-2476 Accumulator TK -9A Relief Valve SI-20450 B 310578 C-F-2-Z - X X - V3A SI-E2U/7-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-E4C/3 E4C-GZ0/1 GZ0-H39/6 GZO-H39/7 H39-V3A E2U/7b E2U/7f E2U/7g E2U/7h EDE-PP-113B SI-E4C-FU Fuses E4C CB-F-1B-A SI-SS-2475 Selector Switch GZ0 CB-F-1B-A SI-CS-2475-2 Control Switch with Indication GZ0 CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A SI-20-FV-2476 Solenoid Valve V3A C-F-2-Z SI-ZS-FV-2476 Valve Position Switch V3A C-F-2-Z 53 SI-FV-2477 Accumulator T K-9C Relief Valve SI-20450 B 310578 C-F-2-Z - X X - V3D SI-E2U/7-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-E4C/3 E4C-GZ0/1 GZ0-H41/5 H41-V3D E2U/7c E2U/7f E2U/7g E2U/7h EDE-PP-113B SI-E4C-FU Fuses E4C CB-F-1B-A SI-SS-2475 Selector Switch GZ0 CB-F-1B-A SI-CS-2477-2 Control Switch with Indication GZ0 CB-F-1B-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A SI-20-FV-2477 Solenoid Valve V3D C-F-2-Z SI-ZS-FV-2477 Valve Position Switch V3D C-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -14 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 54 SI-FV-2486 Accumulator TK -9C Relief Valve SI-20450 B 310578 C-F-2-Z - X X - V3E SI-E2U/7-72 125 V DC Circuit Breaker E2U CB-F-1B-A E2U-E4C/3 E4C-GZ0/1 GZ0-H41/5 GZ0-H41/6 H41-V3E E2U/7d E2U/7f E2U/7g E2U/7h EDE-PP-113B SI-E4C-FU Fuses E4C CB-F-1B-A SI-SS-2475 Selector Switch GZ0 CB-F-1B-A SI-CS-2477-2 Control Switch with Indication GZ0 CB-F-1B-A EDE-MM-117 Electrical Penetration H41 C-F-1-Z, ET-F-1C-A SI-20-FV-2486 Solenoid Valve V3E C-F-2-Z SI-ZS-FV-2486 Valve Position Switch V3E C-F-2-Z 55 SI-FV-2482 Accumulator TK -9B Relief Valve SI-20450 A 310578 C-F-2-Z - X X - V3B SI-E2T/7-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-E4H/2 E4H-G81/2 G81-H35/6 H35-V3B 310890 E2T/7a E2T/7f E2T/7g E2T/7h EDE-PP-113A SI-E4H-FU Fuses E4H CB-F-1A-A SI-SS-2482 Selector Switch G81 CB-F-1A-A SI-CS-2482-2 Control Switch with Indication G81 CB-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A SI-20-FV-2482 Solenoid Valve V3B C-F-2-Z SI-ZS-FV-2482 Valve Position Switch V3B C-F-2-Z 56 SI-FV-2483 Accumulator TK -9B Relief Valve SI-20450 A 310578 C-F-2-Z - X X - V3C SI-E2T/7-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-E4H/2 E4H-G81/2 G81-H35/6 G81-H35/7 H35-V3C E2T/7b E2T/7f E2T/7g E2T/7h EDE-PP-113A SI-E4H-FU Fuses E4H CB-F-1A-A SI-SS-2482 Selector Switch G81 CB-F-1A-A SI-CS-2482-2 Control Switch with Indication G81 CB-F-1A-A EDE-MM-111 Electrical Penetration H35 C-F-2-Z, ET-F-1A-A SI-20-FV-2483 Solenoid Valve V3C C-F-2-Z SI-ZS-FV-2483 Valve Position Switch V3C C-F-2-Z 57 SI-FV-2495 Accumulator TK -9D Relief Valve SI-20450 A 310579 C-F-2-Z - X X - V3F SI-E2T/7-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-E4H/2 E4H-G81/2 G81-H36/9 H36-V3F E2T/7c E2T/7f E2T/7g E2T/7h EDE-PP-113A SI-E4H-FU Fuses E4H CB-F-1A-A SI-SS-2482 Selector Switch G81 CB-F-1A-A SI-CS-2495-2 Control Switch with Indication G81 CB-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SI-20-FV-2495 Solenoid Valve V3F C-F-2-Z SI-ZS-FV-2495 Valve Position Switch V3F C-F-2-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -15 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 58 SI-FV-2496 Accumulator TK -9D Relief Valve SI-20450 A 310579 C-F-2-Z - X X - V3G SI-E2T/7-72 125 V DC Circuit Breaker E2T CB-F-1A-A E2T-E4H/2 E4H-G81/2 G81-H36/9 G81-H36/A H36-V3G E2T/7d E2T/7f E2T/7g EDE-PP-113A SI-E4H-FU Fuses E4H CB-F-1A-A SI-SS-2482 Selector Switch G81 CB-F-1A-A SI-CS-2495-2 Control Switch with Indication G81 CB-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A SI-20-FV-2496 Solenoid Valve V3G C-F-2-Z SI-ZS-FV-2496 Valve Position Switch V3G C-F-2-Z 59 CS-E-5A Seal Water Heat Exchanger CS-20726 A 310764 PAB-F-1B-Z X X - - - - - - - - - - - - Note 1 60 CS-E-5B Seal Water Heat Exchanger CS-20726 B 310764 PAB-F-1B-Z X X - - - - - - - - - - - - Note 1 61 RC-E-10 Pressurizer Heaters Control Group RC-20846 A 310598 C-F-1-Z X - X - M26 RC-AM4-52 480 V AC Circuit Breaker AM4 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 8 62 CS-V-142 Charging Line Isolation Valve CS-20722 A 310769 PP-F-1A-Z X X X - V12 CS-B82-52 460 V AC Circuit Breaker B82 CB-F-1A-A B82-G2G B82-G2G/1 B82-V12 310891 B82a B82c B82d CBA-FN-19 CBA-FN-20 EAH-FN-5A EDE-MCC-512 CS-V-143 CS-CS-7410-2 Control Switch with Indication G2G CB-F-1A-A CS-SS-7410 Selector Switch G2G CB-F-1A-A CS-B82-42/0,C Motor Starters B82 CB-F-1A-A CS-B82-49 Overload Relay B82 CB-F-1A-A CS-ZS-V142 Valve Position and Open/Close Torque Switches V12 PP-F-1A-Z CS-B82-FU Fuse B82 CB-F-1A-A 63 CS-V-143 Charging Line Isolation Valve CS-20722 B 310769 PP-F-1A-Z X X X - V11 CS-B87-52 460 V AC Circuit Breaker B87 CB-F-1B-A B87-G2J B87-G2J/1 B87-V11 B87-V11/1 B87a B87c B87d CBA-FN-32 CBA-FN-33 EAH-FN-5B EDE-MCC-612 CS-V-142 CS-CS-7411-2 control Switch with Indication G2J CB-F-1B-A CS-SS-7411 Selector Switch G2J CB-F-1B-A CS-B87-42/0,C Motor Starters B87 CB-F-1B-A CS-B87-49 Overload Relay B87 CB-F-1B-A CS-ZS-V143 Valve Position and Open/Close Torque Switches V11 PP-F-1A-Z CS-B87-FU Fuses B87 CB-F-1B-A 64 CS-V-210 Charging Pump 2A Discharge Valve CS-20725 A 310764 PAB-F-1C-A - X - - - - - - - - - - - CS-V-220 Note 1 65 CS-V-219 Charging Pump 2B Bypass Valve CS-20725 B 310764 PAB-F-1D-A - X - - - - - - - - - - - CS-V-221 Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.2 -16 FUNCTION: REACTOR COOLANT INVENTORY AND PRESSURE CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 66 CS-V-220 Charging Pump 2B Discharge Valve CS-20725 B 310764 PAB-F-1D-A - X - - - - - - - - - - - CS-V-210 Note 1 67 CS-V-221 Charging Pump 2A Bypass Valve CS-20725 A 310764 PAB-F-1C-A - X - - - - - - - - - - - CS-V-219 Note 1 68 CS-V-154 RCP-1D Seal Injection Isolation Valve CS-20726 A 310769 PP-F-5B-Z X X - - - - 480 V AC Circuit Breaker B77 CB-F-1A-A - - - - None Note 2 69 CS-V-158 RCP-1C Seal Injection Isolation Valve CS-20726 A 310769 PP-F-5B-Z X X - - - - 480 V AC Circuit Breaker B76 CB-F-1A-A - - - - None Note 2 70 CS-V-162 RCP-1B Seal Injection Isolation Valve CS-20726 A 310769 PP-F-1A-Z X X - - - - 480 V AC Circuit Breaker B75 CB-F-1A-A - - - - None Note 2 71 CS-V-166 RCP-1A Seal Injection Isolation Valve CS-20726 A 310769 PP-F-1A-Z X X - - - - 480 V AC Circuit Breaker B74 CB-F-1A-A - - - - None Note 2 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3 .3-1 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CS-TK-4A Boric Acid Storage Tank CS-20729 A/B 310766 PAB-F-2B-Z - X - - - - - - - - - - - CS-TK-4B Note 1 2 CS-TK-4B Boric Acid Storage Tank CS-20729 A/B 310766 PAB-F-2B-Z - X - - - - - - - - - - - CS-TK-4A Note 1 3 CS-V-410 Boric Acid Tank 4A Outlet Valve CS-20729 A/B 310766 805216 805229 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-416 CS-V-1207 Notes 1, 2 and 3 4 CS-V-416 Boric Acid Tank 4B Outlet Valve CS-20729 A/B 310766 805216 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-410 CS-V-1207 Notes 1, 2 and 3 5 CS-V-423 Boric Acid Recirculation Valve CS-20729 A 310766 805216 805230 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-431 CS-V-1207 Notes 1, 2 and 3 6 CS-V-431 Boric Acid Recirculation Valve CS-20729 B 310766 805216 805230 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-423 CS-V-1207 Notes 1, 2 and 3 7 CS-V-437 Boric Acid Transfer Pump's Suction Cross -Over Line Isolation Valve CS-20729 A 310766 805216 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-1207 Notes 1, 2 and 3 8 CS-V-439 Charging Pump Isolation Valve CS-20729 A/B 310766 805216 805229 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-426 Notes 1, 2 and 3 9 CS-V-442 Charging Pump Isolation Valve CS-20729 A/B 310766 805216 805229 PAB-F-2B-Z - X - - - - - - - - - - - CS-V-426 Notes 1, 2 and 3 10 CS-P-3A Boric Acid Transfer Pump CS-20729 A 310766 805216 805230 PAB-F-2B-Z - X X - M43 CS-B88-52 460 V AC Circuit Breaker B88 CB-F-1A-A B88-M43 B88-M43/1 310891 B88a B88c CBA-FN-19 CBA-FN-20 EDE-MCC-512 CS-P-3B CS-B88-FU Fuse B88 CB-F-1A-A CS-CS-7435-2 Control Switch B88 CB-F-1A-A CS-SS-7435 Selector Switch B88 CB-F-1A-A CS-B88-42 Motor Starter B88 CB-F-1A-A CS-M43-49 Overload Relay M43 PAB-F-2B-Z CS-B88-49 Overload Relay B88 CB-F-1A-A

.Notes  1. Equipment is mechanical with no electrical requirement.
2. CS-V-423, 410, 416, 431, 437, 439, 442 are non

-electrically operated valves and will be manually positioned as required to provide their reactivity control function during safe shutdown.

3. Electrical conduit plan drawing, 310766, listed only to show fire zone correlation reference to Primary Auxiliary Building area covered by piping Drawings 805216, 805229, 805230, where Valves CS

-V-410, 416, 423, 431, 437, 439, 442 are identified in plan and section.

4. This equipment is listed because it can spuriously start due to cable failure in the boration and dilution flow control valve control circuits. Spurious pump start by itself from failure of its cable is not of concern since CS

-FCV-111A remains closed so the pump cables are not listed.

5. Disabling the valves at the appropriate control location will reposition CS

-FCV-110B and C S-FCV-111B for safe shutdown. Air is not needed to position or to reposition the valve for safe shutdown.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3 .3-2 FUNCTION: REACTIVITY CONTROL PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 CS-P-3B Boric Acid Transfer Pump CS-20729 B 310766 805216 805230 PAB-F-2B-Z - X X - M44 CS-B89-52 460 V AC Circuit Breaker B89 CB-F-1B-A B89-M44 B89-M44/1 310891 B89a B89c CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-P-3A CS-B89-FU Fuse B89 CB-F-1B-A CS-CS-7436-2 Control Switch B89 CB-F-1B-A CS-SS-7436 Selector Switch B89 CB-F-1B-A CS-B89-42 Motor Starter B89 CF-F-1B-A CS-M44-49 Overload Relay M44 PAB-F-2B-Z CS-B89-49 Overload Rela y B89 CB-F-1B-A 12 CS-V-426 Boric Acid F -5 to Charging Pumps Isolation Valve CS-20729 B 310766 PAB-F-2B-Z - X X V04 CS-B94-52 460 V Circuit Breaker B94 CB-F-1B-A B94-V04 B94-V04/1 B94-V04/2 310891 B94a B94c CBA-FN-32 CBA-FN-33 EDE-MCC-612 CS-V-439 CS-V-442 CS-CS-7437-2 Control Switch with Indicator B94 CB-F-1B-A CS-SS-7437 Selector Switch B94 CB-F-1B-A CS-B94-42/0,C Motor Starter B94 CB-F-1B-A CS-B94-49 Overload Relay B94 CB-F-1B-A CS-ZS-V426 Valve Position and Open/Close Torque Switches V04 PAB-F-2B-Z CS-B94-FU Fuse B94 CB-F-1B-A 13 CP-CP-111 Reactor Trip Switchgear Cab

- A/B 310442 CB-F-1A-A X - X  HD2/ HD3 - - - - - - - -   14 CS-V-1207 Boric Acid Transfer Pump's Suction Cross-Over Line Isolation Valve CS-20729 B 310766 805216 PAB-F-2B-Z - X - - - - - - - - - - - Notes 1, 2 and 3 15 CS-FCV-110A CS-FCV-111A CS-FCV-110B CS-FCV-111B Boration and Dilution Flow Control Valves CS-20729 A 310766 PAB-F-2B-Z PAB-F-2B-Z PAB-F-2B-Z PAB-F-2B-Z X X X - LG2 LG1 LG4 LG5 CS-E97/11-72 125 V DC Circuit Breaker E97 NES-F-1A-Z - - - - Note 5 16 RMW-P-16A Reactor Makeup Water Pump CS-20360 A 310763 PAB-F-1A-Z X X X - M36 - - - - - - - - Note 4 17 RMW-P-16B Reactor Makeup Water Pump CS-20360 A 310763 PAB-F-1A-Z X X X - M37 - - - - - - - - Note 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 4 Table RSS 3.1.3.4

-1 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CC-TE-2297 Primary Component Cooling Water Loop "B" Supply Header Temperature Element CC-20211 B 310763 PAB-F-2C-Z X X X - T2Z CC-TY-2297 I/E Converter GZ0 CB-F-1B-A CZ0-T2Z FP 71336 M-310952 4 GZ0c CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 CC-TE-2197 CC-TI-2297 Temp. Indicator GZ0 CB-F-1B-A 2 FW-FT-4224-5 RC-E-11B Steam Generator Emergency Feedwater Header Flow Transmitter FW-20688 B 310708 EFP-F-1-A X X X - GL4 FW-FQY-4224-5 I/E Converter GZ0 CB-F-1B-A GL4-GZ0/1 6 GZ0a CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 EPA-FN-47B FW-FT-4214-5 FW-FT-4234-5 FW-FY-4224-5 Square Root Extractor GZ0 CB-F-1B-A FW-FI-4224-5 Flow Indicator G2J CB-F-1B-A 3 FW-FT-4244-5 RC-E-11D Steam Generator Emergency Feedwater Header Flow Transmitter FW-20688 B 310708 EFP-F-1-A X X X - GL4 FW-FQY-4244-5 I/E Converter GZ0 CB-F-1B-A GL4-GZ0/1 6 GZ0a CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 EPA-FN-47B FW-FT-4214-5 FW-FT-4234-5 FW-FY-4244-5 Square Root Extractor GX0 CB-F-1B-A FW-FI-4244-5 Flow Indicator G2J CB-F-1B-A 4 FW-LT-4320 RC-E-11B Steam Generator Wide Range Level Transmitter FW-20686 B 310576 C-F-1-Z X X X - R1N FW-LQY-4320 I/E Converter GZ0 CB-F-1B-A H55-R1N GZ0-H55 E1T-G2K 7 GZ0a E1T/4 EH0/2 CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 EDE-PP-11F FW-LT-4310 FW-LT-4330 FW-LI-4320 Level Indicator G2J CB-F-1B-A FW-LR-4320 Level Recorder G2J CB-F-1B-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 5 FW-LT-4340 RC-E-11D Steam Generator Wide Range Level Transmitter FW-20686 B 310577 C-F-1-Z X X X - R1Q FW-LQY-4340 I/E Converter GZ0 CB-F-1B-A H55-R1Q GZ0-H55 E1T-G2K 7 GZ0a E1T/4 EH0/2 CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 EDE-PP-11F FW-LT-4310 FW-LT-4330 FW-LI-4340 Level Indicator G2J CB-F-1B-A FW-LR-4320 Level Recorder G2J CB-F-1B-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 6 MS-PT-3174 RC-E-11B Steam Generator Header Pressure Transmitter MS-20581 B 310586 MS-F-1A-Z X X X - GZ4 MS-PQY-3174 I/E Converter GZ0 CB-F-1B-A GZ0-GZ4 10 GZ0c CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 MS-PT-3173 MS-PT-3178 MS-PI-3174 Press. Indicator G2J CB-F-1B-A 7 MS-PT-3179 RC-E-11D Steam Generator Header Pressure Transmitter MS-20581 B 310589 MS-F-1B-A X X X - GZ6 MS-PQY-3179 I/E Converter GZ0 CB-F-1B-A GZ0-GZ6 10 GZ0c CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 MS-PT-3173 MS-PT-3178 MS-PI-3179 Press. Indicator G2J CB-F-1B-A 8 RC-LT-7333 RC-E-10 Pressurizer Level Transmitter RC-20846 B 310579 C-F-2-Z X X X - GN5 RC-LQY-7333 I/E Converter GZ0 CB-F-1B-A H55-PR8/1 GZ0-H55/1 E1T-G2K 11 GZ0a E1T/4 EH0/2 CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 EDE-PP-11F RC-LT-7334 RC-LI-7333 Level Indicator GZ0 CB-F-1B-A RC-LR-7333 Level Recorder GZ0 CB-F-1B-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A

.Notes   1. Underground duct Plan Drawing 310248 is listed only to show the fire zone corresponding to the locations of the condensate storage tank level Indicator CO

-LISL-4052 which is identified in Drawing 509066.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 4 Table RSS 3.1.3.4 -2 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 RC-PT-7335 RC-E-10 Pressurizer Pressure Transmitter RC-20846 B 310579 C-F-2-Z X X X - PR8 RC-PQY-7335 I/E Converter GZ0 CB-F-1B-A H55-PR8 GZ0-H55/1 FP 71336 310952 12 GZ0a CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 RC-PT-7336 RC-PI-7335 Press. Indicator GZ0 CB-F-1B-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 10 RC-TE-9407 Reactor Coolant Loop 4 Wide Range Hot Leg Temperature Element RC-20844 B 310583 C-F-1-Z X X X - TS7 RC-TY-9407 R/E Converter GZ0 CB-F-1B-A H55-TS7 GZ0-H55/2 E1T-G2K 13 GZ0a E1T/4 EH0/2 CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 EDE-PP-11F RC-TE-9406 RC-TI-9407 Temp. Indicator GZ0 CB-F-1B-A RC-TR-9407 Temp. Recorder GZ0 CB-F-1B-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 11 RC-TE-9411 Reactor Coolant Loop 4 Wide Range Cold Leg Temperature Element RC-20844 B 310583 C-F-1-Z X X X - T3E RC-TY-9411 R/E Converter GZ0 CB-F-1B-A H55-T3E GZ0-H55/2 E1T-G2K 13 GZ0a E1T/4 EH0/2 CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 EDE-PP-11F RC-TE-9410 RC-TI-9411 Temp. Indicator GZ0 CB-F-1B-A RC-TR-9407 Temp. Recorder GZ0 CB-F-1B-A EDE-MM-131 Electrical Penetration H55 C-F-1-Z, ET-F-1C-A 12 CS-LT-7464 Boric Acid Tank CS-TK-4B Level Transmitter CS-20729 B 310766 PAB-F-2B-Z - X X - RJ9 CS-LSY-7464 Comparator G2J CB-F-1B-A G2K-RJ9 GZ0c CBA-FN-32 CBA-FN-33 MM-UQ-5868 MM-UQ-5869 CS-LT-7446 CS-LQY-7464 I/E Converter G2J CB-F-1B-A CS-LI-7464 Level Indicator G2J CB-F-1B-A 13 MM-UQ-5868 Remote Shutdown Panel MM-CP-108B Power Supply

- B 310442 CB-F-1B-A X X X - G2J VI-G2J-FU9 20A Fuse G2J CB-F-1B-A EH0-G2J  M-310952 EH0/2 EH0/2 CBA-FN-32 CBA-FN-33 EDE-PP-1F MM-UQ-5866             VI-G2J-FU10 20A Fuse G2J CB-F-1B-A    14 MM-UQ-5869 Remote Shutdown Panel MM-CP-108B Power Supply
- B 310442 CB-F-1B-A X X X - G2J VI-G2J-FU11 20A Fuse G2J CB-F-1B-A EH0-G2J EH0/2 EH0/2 CBA-FN-32 CBA-FN-33 EDE-PP-1F MM-UQ-5867             VI-G2J-FU12 20A Fuse G2J CB-F-1B-A     15 NOT USED                    16 CC-TE-2197 Primary Component Cooling Water Loop "A" Supply Header Temperature Element CC-20205 A 310763 PAB-F-2C-Z X X X - T3A CC-TY-2197 I/E Converter G2H CB-F-1A-A G2H-T3A FP 71337 M-310952 11 G81d CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 CC-TE-2297             CC-TI-2197 Temp. Indicator G81 CB-F-1A-A    17 FW-FT-4214-5 RC-E-11A Steam Generator Emergency Feedwater Header Flow Transmitter FW-20688 A 310708 EFP-F-1-A X X X - GL3 FW-FQY-4214-5 I/E Converter G81 CB-F-1A-A G81-GL3 4 G81a CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 EPA-FN-47A FW-FT-4224-5 FW-FT-4244-5             FW-FY-4214-5 Square Root Extractor G81 CB-F-1A-A               FW-FI-4214-5 Flow Indicator G2G CB-F-1A-A     18 FW-FT-4234-5 RC-E-11C Steam Generator Emergency Feedwater Header Flow Transmitter FW-20688 A 310708 EFP-F-1-A X X X - GL3 FW-FQY-4234-5 I/E Converter G81 CB-F-1A-A G81-GL3 FP 71337 310952 4 G81a CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 EPA-FN-47A FW-FT-4224-5 FW-FT-4244-5             FW-FY-4234-5 Square Root Extracto r G81 CB-F-1A-A               FW-FI-4234-5 Flow Indicator G2G CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 4 Table RSS 3.1.3.4

-3 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 FW-LT-4310 RC-E-11A Steam Generator Wide Range Level Transmitter FW-20686 A 310576 C-F-1-Z X X X - R1M FW-LQY-4310 I/E Converter G2H CB-F-1A-A H44-R1M G2H-H44 E1S-G2H 17 G81d E1S/4 EH9/2 CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 EDE-PP-11E FW-LT-4320 FW-LT-4340 FW-LI-4310 Level Indicator G2G CB-F-1A-A FW-LR-4310 Level Recorder G2G CB-F-1A-A EDE-MM-120 Electrical

Penetration H44 C-F-2-Z, ET-F-1A-A 20 FW-LT-4330 RC-E-11C Steam Generator Wide Range Level Transmitter FW-20686 A 310577 C-F-1-Z X X X - R1P FW-LQY-4330 I/E Converter G2H CB-F-1A-A H45-R1P G2H-H45 E1S-G2H 17 G81d E1S/4 EH9/2 CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 EDE-PP-11E FW-LT-4320 FW-LT-4340 FW-LI-4330 Level Indicator G2G CB-F-1A-A FW-LR-4310 Level Recorder G2G CB-F-1A-A EDE-MM-121 Electrical Penetration H45 C-F-2-Z, ET-F-1A-A 21 MS-PT-3173 RC-E-11A Steam Generator Header Pressure Transmitter MS-20580 A 310589 MS-F-1B-Z X X X - GL6 MS-PQY-3173 I/E Converter G2H CB-F-1A-A G2H-GL6 13 G81d CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 MS-PT-3174 MS-PT-3179 MS-PI-3173 Press. Indicator G2G CB-F-1A-A 22 MS-PT-3178 RC-E-11C Steam Generator Header Pressure Transmitter MS-20581 A 310586 MS-F-1A-Z X X X - GL5 MS-PQY-3178 I/E Converter G2H CB-F-1A-A G2H-GL5/1 13 G81d CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 MS-PT-3174 MS-PT-3179 MS-PI-3178 Press. Indicator G2G CB-F-1A-A 23 RC-LT-7334 RC-E-10 Pressurizer Level Transmitter RC-20846 A 310579 C-F-2-Z X X X - GK5 RC-LQY-7334 I/E Converter G81 CB-F-1A-A H45-PR9 G81-H45 E1S-G2H 6 G81a E1S/4 EH9/2 CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 EDE-PP-11E RC-LT-7333 RC-LI-7334 Level Indicator G81 CB-F-1A-A RC-LR-7334 Level Recorder G81 CB-F-1A-A EDE-MM-121 Electrical Penetration H45 C-F-2-Z, ET-F-1A-A 24 RC-PT-7336 RC-E-10 Pressurizer Pressure Transmitter RC-20846 A 310579 C-F-2-Z X X X - GK5 RC-PQY-7336 I/E Converter G2H CB-F-1A-A H45-PR9/1 G2H-H45/1 12 G81d CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 RC-PT-7335 RC-PI-7336 Press. Indicator G81 CB-F-1A-A EDE-MM-121 Electrical Penetration H45 C-F-2-Z, ET-F-1A-A 25 RC-TE-9406 Reactor Coolant Loop 1 Wide Range Hot Leg Temperature Element RC-20841 A 310582 C-F-1-Z X X X - TS6 RC-TY-9406 R/E Converter G81 CB-F-1A-A H44-TS6 G81-H44 E1S-G2H FP 71336 310952 3 G81a E1S/4 EH9/2 CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 EDE-PP-11E RC-TE-9407 RC-TI-9406 Temp. Indicator G81 CB-F-1A-A RC-TR-9406 Temp. Recorder G81 CB-F-1A-A EDE-MM-120 Electrical Penetration H44 C-F-2-Z, ET-F-1A-A 26 RC-TE-9410 Reactor Coolant Loop 1 Wide Range Cold Leg Temperature Element RC-20841 A 310582 C-F-1-Z X X X - T3D RC-TY-9410 R/E Converter G81 CB-F-1A-A H44-T3D G81-H44/1 E1S-G2H 3 G81a E1S/4 EH9/2 CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 EDE-PP-11E RC-TE-9411 RC-TI-9410 Temp. Indicator G81 CB-F-1A-A RC-TR-9406 Temp. Recorder G81 CB-F-1A-A EDE-MM-120 Electrical Penetration H44 C-F-2-Z, ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 4 Table RSS 3.1.3.4 -4 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 27 CS-LT-7446 Boric Acid Tank CS-TK-4A Level Transmitter CS-20729 A 310766 PAB-F-2B-Z - X X - RJ8 CS-LSY-7446 Comparator G2H CB-F-1A-A G2H-RJ8 G81d CBA-FN-19 CBA-FN-20 MM-UQ-5866 MM-UQ-5867 CS-LT-7464 CS-LQY-7446 I/E Converter G2H CB-F-1A-A CS-LI-7446 Level Indicator G2H CB-F-1A-A 28 MM-UQ-5866 Remote Shutdown Panel MM-CP-108A Power Supply

- A 310442 CB-F-1A-A X X X - G2G VI-G2G-FU9 20A Fuse G2G CB-F-1A-A EH9-G2G M-310952 EH9/2 EH9/2 CBA-FN-19 CBA-FN-20 EDE-PP-1E MM-UQ-5868             VI-G2G-FU10 20A Fuse G2G CB-F-1A-A    29 MM-UQ-5867 Remote Shutdown Panel MM-CP-108A Power Supply
- A 310442 CB-F-1A-A X X X - G2G VI-G2G-FU11 20A Fuse G2G CB-F-1A-A EH9-G2G EH9/2 EH9/2 CBA-FN-19 CBA-FN-20 EDE-PP-1E MM-UQ-5869             VI-G2G-FU12 20A Fuse G2G CB-F-1A-A     30 NOT USED                    31 NI-NE-6690 Intermediate Range Thermal Neutron Flux Monitoring Detector - A 310565 C-F-1-Z X X X - QO5 NI-E1S/13-52 120 V ac Circuit Breaker E1S CB-F-1A-A H40-XP8 H40-KDO KDO-QC1 QC1-QI0 G2H-QC1 QO5-XP8 E1S-KDO E1S-QC1 E1S-QI0 310943 E1S/13a E1S/13b CBA-FN-19 CBA-FN-20 EDE-PP-11E NI-NE-6691             NI-E1S/14-52 120 V ac Circuit Breaker E1S CB-F-1A-A              NI-E1S/15-52 120 V ac Circuit Breaker E1S CB-F-1A-A                 NI-NI-6690-3&4 Excore Wide Range Thermal Neutron Flux Indicators G2H CB-F-1A-A                 NI-NT-6690 Excore Wide Range Transmitters KDO ET-F-1A-A                  NI-NM-6690 Excore Wide Range Signal Processor QC1 CB-F-1A-A                  NI-NM-6690J Excore Wide Range Signal Processor Expansion Box QI0 CB-F-1A-A                  EDE-TBX-XP8 Junction Box XP8 C-F-1-Z                  EDE-MM-116 Electrical Penetration H40 C-F-2-Z, ET-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 1 4 Table RSS 3.1.3.4

-5 FUNCTION: PROCESS MONITORING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 32 NI-NE-6691 Intermediate Range Thermal Neutron Flux Monitoring Detector - B 310565 C-F-1-Z X X X - QO7 NI-EIT/13-52 120 V ac Circuit Breaker E1T CB-F-1B-A H21-XP9 H21-KD1 KD1-QDO QDO-QJ1 G2K-QDO QO7-XP9 E1T-KD1 E1T-QDO E1T-QJ1 310943 E1T/13a E1T/13b CBA-FN-32 CBA-FN-33 EDE-PP-11F NI-NE-6690 NI-E1T/14-52 120 V ac Circuit Breaker E1T CB-F-1B-A NI-E1T/15-52 120 V ac Circuit Breaker E1T CB-F-1B-A NI-NI-6691-3&4 Excore Wide Range Thermal Neutron Flux Indicators G2K CB-F-1B-A NI-NT-6691 Excore Wide Range Transmitters KD1 ET-F-1C-A NI-NM-6691 Excore Wide Range Signal Processor QDO CB-F-1B-A NI-NM-6691J Excore Wide Range Signal Processor Expansion Box QJ1 CB-F-1B-A EDE-TBX-XP9 Junction Box XP9 C-F-1-Z EDE-MM-97 Electrical Penetration H21 C-F-1-Z, ET-F-1C-A 33 CO-LISL-4052 Condensate Storage Tank Level Indicator C0-20426 A/B 310248 509066 CST-F-1 X - - R10 - - - - - - - - - Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.5-1 FUNCTION: SAFGEGUARDS ACTUATION PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 MM-CP-12 - A 310501 CB-F-3A-A X X X - FF8 PSC-E01/11-52 120 V ac Circuit Breaker E01 CB-F-1A-A - - - None Note 1 Solid State

Protection System

Cabinet (Train A

Load Group) MM-SS-5807 Selector Switch G5X DG-F-2A-A CBA-FN-19

CBA-FN-20 DAH-FN-25A

DAH-FN-26A 2 MM-CP-13 - B 310501 CB-F-3A-A X X X - FF9 PSC-E02/11-52 120 V ac Circuit Breaker E02 CB-F-1B-A - - - None Note 1 Solid State

Protection System

Cabinet (Train B

Load Group) MM-SS-5808 Selector Switch G5Y DG-F-2B-A CBA-FN-32

CBA-FN-33 DAH-FN-25B

DAH-FN-26B

.Notes   1. The Solid State Protection Cabinet will be disabled at the appropriate location to prevent the output from initiating spurious operation of various valves and pumps. 

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -1 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 RH-P-8A Residual Heat Removal Pump SI-20448 A 310761 RHR-F-1D-Z - X X - M11 RH-A57-52 4160 V ac Circuit Breaker A57 CB-F-1A-A A57-M11 310887 A57a A57g A57b A57c A57d CBA-FN-19 CBA-FN-20 EAH-FN-5A EAH-FN-31A EDE-SWG-5 RH-P-8B RHR-A57-FU Fuses A57 CB-F-1A-A RH-CS-2467-2 Control Switch A57 CB-F-1A-A RH-SS-2467 Selector Switch A57 CB-F-1A-A EDE-A53-94-1A Bus Under Voltage Relay A53 CB-F-1A-A RH-A57-G,R,W Indicating Lights A57 CB-F-1A-A RH-A57-86 Lockout Relay A57 CB-F-1A-A RH-A57-52H Truck Operated Contact A57 CB-F-1A-A RH-A57-50/51 Inst/Time Overcurrent Relays øA, øC A57 CB-F-1A-A RH-A57-51GS Ground Sensor Relay A57 CB-F-1A-A RH-A57-AM Ammeter A57 CB-F-1A-A RH-A57-AS Ammeter Switch A57 CB-F-1A-A RH-A57-CT Current Transformers (75/5) A57 CB-F-1A-A RH-A57-TD1 CT Test Device A57 CB-F-1A-A RH-A57-ATR Transducer A57 CB-F-1A-A RH-A57-TD2 Lockout Relay Test Device A57 CB-F-1A-A RH-A57-52Z Time Delay Relay A57 CB-F-1A-A

.Notes   1. This equipment is mechanical with no electrical requirements.
2. During normal operation, the valve is in its safe shutdown position.

To prevent spurious operation, this equipment will be disabled at the appropriate control location. 3. Not used.

4. Air is not needed to position or to reposition the valve for safe shutdown.
5. The valve will be operated manually utilizing handwheels.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -2 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 RH-P-8B Residual Heat Removal Pump RH-20663 B 310761 RHR-F-1C-Z - X X - M12 RH-A77-52 4160 V ac Circuit Breaker A77 CB-F-1B-A A77-M12 A77a A77g A77b A77c A77d CBA-FN-32 CBA-FN-33 EAH-FN-5B EAH-FN-31B EDE-SWG-6 RH-P-8A RHR-A77-FU Fuses A77 CB-F-1B-A RH-CS-2468-2 Control Switch A77 CB-F-1B-A RH-SS-2468 Selector Switch A77 CB-F-1B-A EDE-A73-94-1A Bus Under Voltage Relay A73 CB-F-1B-A RH-A77-G,R,W Indicating Lights A77 CB-F-1B-A RH-A77-86 Lockout Relay A77 CB-F-1B-A RH-A77-52H Truck Operated Contact A77 CB-F-1B-A RH-A77-50/51 Inst/Time Overcurrent Relays øA, øC A77 CB-F-1B-A RH-A77-51GS Ground Sensor Relay A77 CB-F-1B-A RH-A77-AM Ammeter A77 CB-F-1B-A RH-A77-AS Ammeter Switch A77 CB-F-1B-A RH-A77-CT Current Transformers (75/5) A77 CB-F-1B-A RH-A77-TD1 CT Test Device A77 CB-F-1B-A RH-A77-ATR Transducer A77 CB-F-1B-A RH-A77-TD2 Lockout Relay Test Device A77 CB-F-1B-A RH-A77-52Z Time Delay Relay A77 CB-F-1B-A 3 RH-V-14 RH-P-8A to Cold Leg Isolation Valve RH-20662 A 310769 PP-F-1A-Z - X X - V47 RH-B57-52 460 V ac Circuit Breaker B57 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 RH-V-26 Note 2 4 RH-V-26 RH-P-8B to Cold Leg Isolation Valve RH-20663 B 310769 PP-F-1B-Z - X X - V48 RH-B65-52 460 V ac Circuit Breaker B65 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 RH-V-14 Note 2 5 RH-V-35 RH-E-9A to Charging Pump Isolation Valve RH-20662 A 310761 RHR-F-4B-Z - X X - V53 RH-B59-52 460 V ac Circuit Breaker B59 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 2 6 RH-V-36 RH-E-9B to SI Pump Isolation Valve SI-20449 B 310761 RHR-F-2A-Z - X X - V54 RH-B66-52 460 V ac Circuit Breaker B66 CBA-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 2 7 RH-V-32 RHR PP to Hot Leg Isolation Valve RH-20663 B 310769 PP-F-1A-Z - X X - V51 RH-B58-52 460 V ac Circuit Breaker B58 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 None Note 2 8 RH-V-70 RHR to Hot Leg Isolation Valve RH-20663 A 310769 PP-F-1A-Z - X X - VB4 RH-D90-52 460 V ac Circuit Breaker D90 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 None Note 2 9 RH-HCV-606 RH-E-9A Outlet Flow Control Valve RH-20662 A 310761 RHR-F-4B-Z - X X X LG8 EDE-E87/2-72 125 V dc Circuit E87 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 RH-HCV-607 Notes 2 and 4 10 RH-HCV-607 RH-E-9B Outlet Flow Control Valve RH-20663 B 310761 RHR-F-4A-Z - X X X LG9 EDE-E88/2-72 125 V dc Circuit Breaker E88 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 RH-HCV-606 Notes 2 and 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -3 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 RH-FCV-618 RH-E-9A Outlet Bypass Flow Control Valve RH-20662 A 310761 RHR-F-4B-Z - X X X LH3 EDE-E87/2-72 125 V dc Circuit Breaker E87 CB-F-1A-A - - - CBA-FN-19 CBA-FN-20 RH-FCV-619 Notes 2 and 4 12 RH-FCV-619 RH-E-9B Outlet Bypass Flow Control Valve RH-20663 B 310761 RHR-F-4A-Z - X X X LH4 EDE-E88/2-72 125 V dc Circuit Breaker E88 CB-F-1B-A - - - CBA-FN-32 CBA-FN-33 RH-FCV-618 Notes 2 and 4 13 RH-V-8 RHR Loop A Sample Valve RH-20662 A 310761 805201 RHR-F-4B-Z - X - - - - - - - - - - EAH-FN-5A EAH-FN-31A RH-V-44 Notes 1 and 9 14 RH-V-44 RHR Loop B Sample Valve RH-20663 B 310761 805201 RHR-F-4A-Z - X - - - - - - - - - - EAH-FN-5B EAH-FN-31B RH-V-8 Notes 1 and 9 Notes 6. Electrical conduit plan drawing 9763 -F-310761 is listed to show fire zone corresponding to the location of the RHR pump oil cooler which is identified in drawing 9763-F-805020. 7. Electrical conduit plan drawings 9763 -F-310761 and 9763 -F-310762 are listed to show fire zone corresponding to the location of the RHR heat exchanger which is identified in drawings 9763 -F-805202 and 9763 -F-805203. 8. During normal operation, the valve is in its hot shutdown position. To prevent spurious operation, this equipment will be disabled at the appropriate control location. For cold shutdown, the valve will be energized for positioning.

9. Electrical conduit plan drawing 9763

-F-310761 is listed corresponding to the location of the RHR sampling valve which is identified in drawing 9763 -F-805201. 10. These valves are also listed in Table RSS 3.1.3.2.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -4 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15 RC-V-22 RHR Inlet Isolation Valve RC-20841 B 310582 C-F-1-Z - X X - V27 RC-B54-52-1,2 460 V ac Circuit Breakers B54 CB-F-1B-A B54-G2J B54-G2J/1 B54-H39 B54-H24 H24-V27 H39-V27 310882 B54a B54c EDE-MCC-621 CBA-FN-32 CBA-FN-33 RC-V-88 Notes 8 and 10 RC-B54-FU Fuse B54 CB-F-1B-A RC-CS-7302-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7302 Selector Switch G2J CB-F-1B-A RC-B54-42-1/0,C Motor Starters B54 CB-F-1B-A RC-B54-42-2 Motor Starter B54 CB-F-1B-A RC-B54-49-1,2 Overload Relays B54 CB-F-1B-A EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A RC-ZS-7302B Valve Position and Open/Close Torque Switches V27 C-F-1-Z RC-ZL-7302-1 Pilot Light G2J CB-F-1B-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-EHO/16-52 120 V ac Circuit Breaker EHO CB-F-1B-A E4J-EH0/1 E4J-G2J GJ2-H39/6 H39-V27/1 H39-V26/3 GZ0-U8U ED0-GZ0/1 EHO/16a EHO/16c EHO/16b EHO/16d EDE-PP-1F CBA-FN-32 CBA-FN-33 RC-CS-7302-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7302 Selector Switch G2J CB-F-1B-A RC-ZS-7302B Valve Position and Open/Close Torque Switches V27 C-F-1-Z RC-E4J-FU-9 and 10 30 Amp Fuses E4J CB-F-1B-A EDE-MM-115 Electrical Penetration H39 ET-F-1C-A, C-F-1-Z RC-CS-7310-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7310 Selector Switch G2J CB-F-1B-A RC-ZS-V87 Valve Position and Open/Close Torque Switches V26 C-F-1-Z RC-CS-2896-2 Control Switch with Indication GZ0 CB-F-1B-A RC-SS-2896 Selector Switch GZ0 CB-F-1B-A RC-ZS-FV-2896 Valve Position Switch U8U PP-F-1B-Z RC-EDO-R1, R2 Auxiliary Relay ED0 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -5 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 16 RC-V-23 RHR Inlet Isolation Valve RC-20841 A 310576 C-F-1-Z - X X - V25 RC-B53-52-1,2 460 V ac Circuit Breakers B53 CB-F-1A-A B53-G2G B53-G2G/1 B53-H36 B53-H19 H36-V25/2 H19-V25 B53a B53c EDE-MCC-521 CBA-FN-19 CBA-FN-20 RC-V-87 Notes 8 and 10 RC-B53-FU Fuse B53 CB-F-1A-A RC-CS-7303-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7303 Selector Switch G2G CB-F-1A-A RC-ZL-7303-1 Pilot Light G2G CB-F-1A-A RC-B53-42-1/0,C Motor Starters B53 CB-F-1A-A RC-B53-42-2 Motor Starter B53 CB-F-1A-A RC-B53-49-1,2 Overload Relays B53 CB-F-1A-A EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A RC-ZS-V23 Valve Position and Open/Close Torque Switches V25 C-F-1-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-EH9/16-52 120 V ac Circuit Breaker EH9 CB-F-1A-A E4H-EH9/1 E4H-G2G G2G-H36/8 H36-V25/3 H36-V28/1 G81-U8T EC8-G81 EC8-G81/1 310882 EH9/16a EH9/16c EH9/16b EH9/16d EDE-PP-1E CBA-FN-19 CBA-FN-20 RC-CS-7303-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7303 Selector Switch G2G CB-F-1A-A RC-ZS-V23 Valve Position and Open/Close Torque Switches V25 C-F-1-Z EDE-MM-112 Electrical Penetration H36 ET-F-1A-A and C-F-2-Z RC-E4H-FU-9 and 10 30 Amp Fuses E4H CB-F-1A-A RC-CS-7311-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7311 Selector Switch G2G CB-F-1A-A RC-ZS-7311A Valve Position and Open/Close Torque Switches V28 C-F-1-Z RC-CS-2894-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-2894 Selector Switch G81 CB-F-1A-A RC-ZS-FV-2894 Valve Position Switch U8T PP-F-1B-Z RC-EC8-R1, R2 Auxiliary Relay EC8 CB-F-1A-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -6 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 17 RC-V-87 RHR Inlet Isolation Valve RC-20844 B 310582 C-F-1-Z - X X - V26 RC-B61-52-1,2 460 V ac Circuit Breaker B61 CB-F-1B-A B61-G2J B61-G2J/1 B61-H39 B61-H24 H39-V26/2 H24-V26 B61a B61c EDE-MCC-621 CBA-FN-32 CBA-FN-33 RC-V-23 Notes 8 and 10 RC-B61-FU Fuse B61 CB-F-1B-A RC-CS-7310-2 Control Switch with Indicator G2J CB-F-1B-A RC-SS-7310 Selector Switch G2J CB-F-1B-A RC-ZL-7310-1 Pilot Light G2J CB-F-1B-A RC-B61-42-1/0,C Motor Starters B61 CB-F-1B-A RC-B61-42-2 Motor Starter B61 CB-F-1B-A RC-B61-49-1,2 Overload Relays B61 CB-F-1B-A RC-ZS-V87 Valve Position and Open/Close Torque Switches V26 C-F-1Z-A EDE-MM-100 Electrical Penetration H24 C-F-1-Z, ET-F-1C-A EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-EH0/16-52 120 V ac Circuit Breaker EHO CB-F-1B-A E4J-EH0/1 E4J-G2J G2J-H39/6 H39-V26/3 GZ0-U8U EDO-GZ0/1 H39-V27/1 EHO/16a EHO/16c EHO/16b EHO/16d EDE-PP-1F CBA-FN-32 CBA-FN-33 RC-CS-7310-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7310 Selector Switch G2J CB-F-1B-A RC-ZS-V87 Valve Position and Open/Close Torque Switches V26 C-F-1-Z EDE-MM-115 Electrical Penetration H39 C-F-1-Z, ET-F-1C-A RC-E4J-FU-9 and 10 30 Amp Fuses E4J CB-F-1B-A RC-CS-7302-2 Control Switch with Indication G2J CB-F-1B-A RC-SS-7302 Selector Switch G2J CB-F-1B-A RC-ZS-7302B Valve Position and Open/Close Torque Switches V27 C-F-1-Z RC-CS-2896-2 Control Switch with Indication GZO CB-F-1B-A RC-SS-2896 Selector Switch GZO CB-F-1B-A RC-ZS-FV-2896 Valve Position Switch U8U PP-F-1B-Z RC-ED0-R1, R2 Auxiliary Relay ED0 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -7 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 RC-V-88 RHR Inlet Isolation Valve RH-20662 A 310577 C-F-1-Z - X X - V28 RC-B62-52-1,2 460 V ac Circuit Breaker B62 CB-F-1A-A B62-G2G B62-G2G/1 B62-H36 B62-H19 H36-V28 H19-V28 310882 B62a B62c EDE-MCC-521 CBA-FN-19 CBA-FN-20 RC-V-22 Notes 8 and 10 RC-B62-FU Fuse B62 CB-F-1A-A RC-CS-7311-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7311 Selector Switch G2G CB-F-1A-A RC-ZL-7311-1 Pilot Light G2G CB-F-1A-A RC-B62-42-1/0,C Motor Starters B62 CB-F-1A-A RC-B62-42-2 Motor Starter B62 CB-F-1A-A RC-B62-49-1,2 Overload Relays B62 CB-F-1A-A RC-ZS-7311A Valve Position and Open/Close Torque Switches V28 C-F-1-Z EDE-MM-95 Electrical Penetration H19 C-F-2-Z, ET-F-1A-A EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-EH9/16-52 120 V ac Circuit Breaker EH9 CB-F-1A-A E4H-EH9/1 E4H-G2G G2G-H36/8 H36-V28/1 H36-V25/3 G81-U8T EC8-G81 EC8-G81/1 EH9/16a EH9/16c EH9/16b EH9/16d EDE-PP-1E CBA-FN-19 CBA-FN-20 RC-CS-7311-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7311 Selector Switch G2G CB-F-1A-A RC-ZS-7311A Valve Position and Open/Close Torque Switches V28 C-F-1-Z EDE-MM-112 Electrical Penetration H36 C-F-2-Z, ET-F-1A-A RC-E4H-FU-9 and 10 30 Amp Fuse s E4H CB-F-1A-A RC-CS-7303-2 Control Switch with Indication G2G CB-F-1A-A RC-SS-7303 Selector Switch G2G CB-F-1A-A RC-ZS-V23 Valve Position and Open/Close Torque Switches V25 C-F-1-Z RC-CS-2894-2 Control Switch with Indication G81 CB-F-1A-A RC-SS-2894 Selector Switch G81 CB-F-1A-A RC-ZS-FV-2894 Valve Position Switch U8T PP-F-1B-Z RC-EC8-R1, R2 Auxiliary Relay EC8 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.6 -8 FUNCTION: COLD SHUTDOWN PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P and ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 19 RH-P-8A RHR Pump Lube Oil Cooler RH-20662 A 310761 805200 RHR-F-1D-Z - X - - - - - - - - - - Component Cooling RH-P-8B Notes 1 and 6 20 RH-P-8B RHR Pump Lube Oil Cooler RH-20663 B 310761 805200 RHR-F-1C-Z - X - - - - - - - - - - Component Cooling RH-P-8A Notes 1 and 6 21 RH-E-9A Residual Heat Removal Heat Exchanger SI-20448 A 310761 310762 805202 805203 RHR-F-3B-Z - X - - - - - - - - - - Component Cooling RH-E-9B Notes 1 and 7 22 RH-E-9B Residual Heat Removal Heat Exchanger RH-20663 B 310761 310762 805202 805203 RHR-F-3A-Z - X - - - - - - - - - - Component Cooling RH-E-9A Notes 1 and 7 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.7-1 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 SW-P-41A SW-20794 A 301140 SW-F-1E-Z X X X - N81 SW-AQ3-52 4160 V AC Circuit Breaker AQ3 CB-F-1A-A Service Water

Loop "A" -

Pump "A" SW-AQ3-FU Fuses AQ3 CB-F-1A-A SW-CS-6101-2 Control Switch AQ3 CB-F-1A-A CBA-FN-19

CBA-FN-20

EDE-SWG-5 SW-P-41B or SW-P-41D SW-SS-6101 Selector Switch AQ3 CB-F-1A-A AQ3-GN9 AQ3-VL3 AQ3-N81 301107 AQ3a AQ3h AQ3b AQ3c AQ3d SW-ZS-V2 Valve Position Switch VL3 SW-F-1E-Z EDE-A53-94-2 Bus Undervoltage Relay A53 CB-F-1A-A SW-AQ3-52H Truck Operated Contact AQ3 CB-F-1A-A SW-AQ3-50/51 Inst/Time Overcurrent Relays øA, øC AQ3 CB-F-1A-A SW-AQ3-51GS Ground Sensor Relay AQ3 CB-F-1A-A SW-AQ3-86 Lockout Relay AQ3 CB-F-1A-A SW-AQ3-CT Current Transformers 100/5A AQ3 CB-F-1A-A SW-AQ3-TD1 Test Device AQ3 CB-F-1A-A SW-AQ3-AM Ammeter AQ3 CB-F-1A-A SW-AQ3-AS Ammeter Switch AQ3 CB-F-1A-A SW-AQ3-G,R,W Indicating Lights AQ3 CB-F-1A-A SW-AQ3-ATR Transducer AQ3 CB-F-1A-A SW-AQ3-TD2 Lockout Relay Test Device AQ3 CB-F-1A-A SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A SW-AQ3-52Z Time Delay Relay AQ3 CB-F-1A-A SW-AQ3-R1 Auxiliary Relay AQ3 CB-F-1A-A SW-ZS-V54 Valve Position Switch and Valve Open/Close

Torque Switches VM5 CT-F-2B-A GN9-VM5 E2T/1a E2T/1b CBA-FN-19

CBA-FN-20 Notes 4 and 5 SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A

.Notes  1. During normal operation, this equipment is in its safe shutdown position. To prevent spurious operation, this equipment will be disabled or isolated at the appropriate control locations. 
2. Air is not needed to position or to reposition the valve for safe shutdown.
3. This valve will be de-energized to cause it to fail to its safe shutdown position.
4. Circuit shown in 301107, Sheet E2T/1a, involving Auxiliary Relay SW-GN9-RV54 of SW-P-41A also affects SW-P-41C.
5. Circuit shown in 301107, Sheet E2U/1a, involving Auxiliary Relay SW-GN0-RV25 of SW-P-41B also affects SW-P-41D.
6. Electrical power not required for support.
7. The equipment is permanently disabled.
8. During normal operation, this equipment is in its safe shutdown position with its circuit breaker administratively controlled off to prevent its spurious operation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.7-2 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 SW-P-41B SW-20794 B 301140 SW-F-1E-Z X X X - N82 SW-AR3-52 4160 V AC Circuit Breaker AR3 CB-F-1B-A Service Water

Loop "B" -

Pump "B" SW-AR3-FU Fuses AR3 CB-F-1B-A SW-P-41A or SW-P-41C SW-CS-6111-2 Control Switch AR3 CB-F-1B-A AR3-GN0 AR3-VL4 AR3-N82 301107 AR3a AR3h AR3b AR3c AR3d CBA-FN-32

CBA-FN-33

EDE-SWG-6 SW-SS-6111 Selector Switch AR3 CB-F-1B-A SW-ZS-V29 Valve Position Switch VL4 SW-F-1E-Z EDE-A73-94-2 Bus Undervoltage Relay A73 CB-F-1B-A SW-AR3-52H Truck Operated Contact AR3 CB-F-1B-A SW-AR3-50/51 Inst/Time Overcurrent Relays øA, øC AR3 CB-F-1B-A SW-AR3-51GS Ground Sensor Relay AR3 CB-F-1B-A SW-AR3-86 Lockout Relay AR3 CB-F-1B-A SW-AR3-CT Current Transformers 100/5A AR3 CB-F-1B-A SW-AR3-TD1 Test Device AR3 CB-F-1B-A SW-AR3-AM Ammeter AR3 CB-F-1B-A SW-AR3-AS Ammeter Switch AR3 CB-F-1B-A SW-AR3-G,R,W Indicating Lights AR3 CB-F-1B-A SW-AR3-ATR Transducer AR3 CB-F-1B-A SW-AR3-TD2 Lockout Relay Test Device AR3 CB-F-1B-A SW-GN0-RV25 Auxiliary Relay GN0 CB-F-1B-A SW-AR3-52Z Time Delay Relay AR3 CB-F-1B-A SW-AR3-R1 Auxiliary Relay AR3 CB-F-1B-A SW-ZS-V25 Valve Position Switch and Valve Open/Close

Torque Switches VM8 CT-F-2B-A GN0-VM8 E2U/1a E2U/1b CBA-FN-32

CBA-FN-33 Notes 5 and 6 SW-GN0-RV25 Auxiliary Relay GN0 CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.7-3 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 SW-P-41C SW-20794 A 301140 SW-F-1E-Z X X X - N83 SW-AQ4-52 4160 V AC Circuit Breaker AQ4 CB-F-1A-A Note 4 Service Water

Loop "A" -

Pump "C" SW-AQ4-FU Fuses AQ4 CB-F-1A-A AQ4-GN9 AQ4-VL5 AQ4-N83 SW-P-41B or SW-P-41D SW-CS-6102-2 Control Switch AQ4 CB-F-1A-A CBA-FN-19

CBA-FN-20

EDE-SWG-5 SW-SS-6102 Selector Switch AQ4 CB-F-1A-A 301107 AQ4a AQ4h AQ4b AQ4c AQ4d SW-ZS-V22 Valve Position Switch VL5 SW-F-1E-Z EDE-A53-94-2 Bus Undervoltage Relay A53 CB-F-1A-A SW-AQ4-52H Truck Operated Contact AQ4 CB-F-1A-A SW-AQ4-50/51 Inst/Time Overcurrent Relays øA, øC AQ4 CB-F-1A-A SW-AQ4-51GS Ground Sensor Relay AQ4 CB-F-1A-A SW-AQ4-86 Lockout Relay AQ4 CB-F-1A-A SW-AQ4-CT Current Transformers 100/5A AQ4 CB-F-1A-A SW-AQ4-TD1 Test Device AQ4 CB-F-1A-A SW-AQ4-AM Ammeter AQ4 CB-F-1A-A SW-AQ4-AS Ammeter Switch AQ4 CB-F-1A-A SW-AQ4-G,R,W Indicating Lights AQ4 CB-F-1A-A SW-AQ4-ATR Transducer AQ4 CB-F-1A-A SW-AQ4-TD2 Lockout Relay Test Device AQ4 CB-F-1A-A SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A SW-AQ4-52Z Time Delay Relay AQ4 CB-F-1A-A SW-AQ4-R1 Auxiliary Relay AQ4 CB-F-1A-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.7-4 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 SW-P-41D SW-20794 B 301140 SW-F-1E-Z X X X - N84 SW-AR4-52 4160 V AC Circuit Breaker AR4 CB-F-1B-A Note 5 Service Water

Loop "B" -

Pump "D" SW-AR4-FU Fuses AR4 CB-F-1B-A AR4-GN0 AR4-VL6 AR4-N84 CBA-FN-32

CBA-FN-33

EDE-SWG-6 SW-P-41A or SW-P-41C SW-CS-6112-2 Control Switch AR4 CB-F-1B-A SW-SS-6112 Selector Switch AR4 CB-F-1B-A 301107 AR4a AR4h AR4b AR4c AR4d SW-ZS-V31 Valve Position Switch VL6 SW-F-1E-Z EDE-A73-94-2 Bus Undervoltage Relay A73 CB-F-1B-A SW-AR4-52H Truck Operated Contact AR4 CB-F-1B-A SW-AR4-50/51 Inst/Time Overcurrent Relays øA, øC AR4 CB-F-1B-A SW-AR4-51GS Ground Sensor Relay AR4 CB-F-1B-A SW-AR4-86 Lockout Relay AR4 CB-F-1B-A SW-AR4-CT Current Transformer 100/5A AR4 CB-F-1B-A SW-AR4-TD1 Test Device AR4 CB-F-1B-A SW-AR4-AM Ammeter AR4 CB-F-1B-A SW-AR4-AS Ammeter Switch AR4 CB-F-1B-A SW-AR4-G,R,W Indicating Lights AR4 CB-F-1B-A SW-AR4-ATR Transducer AR4 CB-F-1B-A SW-AR4-TD2 Lockout Relay Test Device AR4 CB-F-1B-A SW-GN0-RV25 Auxiliary Relay GN0 CB-F-1B-A SW-AR4-52Z Time Delay Relay AR4 CB-F-1B-A SW-AR4-R1 Auxiliary Relay AR4 CB-F-1B-A SW-AR4-R2 Auxiliary Relay AR4 CB-F-1B-A 5 SW-V2 SW-20794 A 301140 SW-F-1E-Z X X X - VL3 SW-CR6-52 460 V AC Circuit Breaker CR6 SW-F-1B-A 301107 CR6a CR6c SWA-FN-40A EDE-MCC-514 Service Water

Pump "A"

Discharge Valve SW-AQ3-52S Mechanically Operated Contact AQ3 CB-F-1A-A AQ3-CR6 CR6-VL3/1 CR6-VL3 SW-V-29 or SW-V-31 SW-ZS-V2 Valve Position Switch and Valve Open/Close

Torque Switches VL3 SW-F-1E-Z SW-CR6-42/0,C Motor Starters CR6 SW-F-1B-A SW-CR6-49 Overload Relay CR6 SW-F-1B-A SW-CR6-FU Fuses CR6 SW-F-1B-A SW-ECO-TDR Time Delay Relay ECO SW-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.7-5 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 SW-V22 SW-20794 A 301140 SW-F-1E-Z X X X - VL5 SW-CR7-52 460 V AC Circuit Breaker CR7 SW-F-1B-A 301107 CR7a CR7c SWA-FN-40A EDE-MCC-514 Service Water

Pump "C"

Discharge Valve SW-AQ4-52S Mechanically Operated Contact AQ4 CB-F-1A-A AQ4-CR7 CR7-VL5/1 CR7-VL5 SW-V-29 or SW-V-31 SW-ZS-V22 Valve Position Switch and Valve Open/Close

Torque Switches VL5 SW-F-1E-Z SW-CR7-42/0,C Motor Starters CR7 SW-F-1B-A SW-CR7-49 Overload Relay CR7 SW-F-1B-A SW-CR7-FU Fuses CR7 SW-F-1B-A SW-ECO-TDR Time Delay Relay ECO SW-F-1B-A 7 SW-V29 SW-20794 B 301140 SW-F-1E-Z X X X - VL4 SW-CS1-52 460 V AC Circuit Breaker CS1 SW-F-1C-A 301107 CS1a CS1c SWA-FN-40B EDE-MCC-614 Service Water

Pump "B"

Discharge Valve SW-AR3-52S Mechanically Operated Contact AR3 CB-F-1B-A AR3-CS1 CS1-VL4/1 CS1-VL4 SW-V-2 or SW-V-22 SW-ZS-V29 Valve Position Switch and Valve Open/Close

Torque Switches VL4 SW-F-1E-Z SW-CS1-42/0,C Motor Starters CS1 SW-F-1C-A SW-CS1-49 Overload Relay CS1 SW-F-1C-A SW-CS1-FU Fuses CS1 SW-F-1C-A SW-EE2-TDR Time Delay Relay EE2 SW-F-1C-A 8 SW-V31 SW-20794 B 301140 SW-F-1E-Z X X X - VL6 SW-CS2-52 460 V AC Circuit Breaker CS2 SW-F-1C-A 301107 CS2a CS2c SWA-FN-40B EDE-MCC-614 Service Water

Pump "D"

Discharge Valve SW-AR4-52S Mechanically Operated Contact AR4 CB-F-1B-A AR4-CS2 CS2-VL6/1 CS2-VL6 SW-V-2 or SW-V-22 SW-ZS-V31 Valve Position Switch and Valve Open/Close

Torque Switches VL6 SW-F-1E-Z SW-CS2-42/0,C Motor Starters CS2 SW-F-1C-A SW-CS2-49 Overload Relay CS2 SW-F-1C-A SW-CS2-FU Fuses CS2 SW-F-1C-A SW-EE2-TDR Time Delay Relay EE2 SW-F-1C-A 9 SW-V4 SW-20795 A 310767 PAB-F-1K-Z X X X - VP0 SW-DA6-52 460 V AC Circuit Breaker DA6 CB-F-1A-A SW-V5 SW-CS-6117-2 Control Switch with Indication G2H CB-F-1A-A 301107 DA6a DA6c DA6d CBA-FN-19

CBA-FN-20 EDE-MCC-512 Secondary

Component Cooling

Water Heat

Exchanger Header

Supply Valve SW-SS-6117 Selector Switch G2H CB-F-1A-A SW-DA6-42/0,C Motor Starters DA6 CB-F-1A-A DA6-VP0 DA6-G2H DA6-G2H/2 DA6-G2H/1 DA6-VP0/1 SW-DA6-49 Overload Relays DA6 CB-F-1A-A SW-ZS-V4 Valve Position Switch and Valve Open/Close

Torque Switches VP0 PAB-F-1K-Z SW-DA6-FU Fuse DA6 CB-F-1A-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.7-6 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 10 SW-V5 SW-20795 B 310767 PAB-F-1K-Z X X X - VQ1 SW-DA2-52 460 V AC Circuit Breaker DA2 CB-F-1B-A SW-V4 SW-CS-6137-2 Control Switch with Indication G2K CB-F-1B-A 301107 DA2a DA2c DA2d CBA-FN-32

CBA-FN-33 EDE-MCC-612 Secondary

Component Cooling

Water Heat

Exchanger Header

Supply Valve SW-SS-6137 Selector Switch G2K CB-F-1B-A SW-DA2-42/0,C Motor Starters DA2 CB-F-1B-A DA2-VQ1 DA2-G2K DA2-G2K/1 DA2-G2K/2 DA2-VQ1/1 SW-DA2-49 Overload Relays DA2 CB-F-1B-A SW-ZS-V5 Valve Position Switch and Valve Open/Close

Torque Switches VQ1 PAB-F-1K-Z SW-DA2-FU Fuse DA2 CB-F-1B-A 11 SW-V15 CC-E-17A Outlet Valve SW-20795 A 310767 PAB-F-3A-Z X X X - VN1 SW-DA7-52 460 V AC Circuit Breaker DA7 CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 SW-V17 Note 1 12 SW-V16 Diesel Generator "A" Water Jacket

Heat Exchanger

Solenoid-Operated

Valve SW-20795 A 310767 PAB-F-3A-Z X X X X UK6 EDE-E2T/2-72 125 V DC Circuit Breaker E2T CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 SW-V18 Notes 2 and 3 13 SW-V17 CC-E-17B Outlet Valve SW-20795 B 310767 PAB-F-3A-Z X X X - VN2 SW-DA3-52 460 V AC Circuit Breaker DA3 CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 SW-V15 Note 1 14 SW-V18 Diesel Generator "B" Water Jacket

Heat Exchanger

Solenoid-Operated

Valve SW-20795 B 310767 PAB-F-3A-Z X X X X UK7 EDE-E2U/2-72 125 V DC Circuit Breaker E2U CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 SW-V16 Notes 2 and 3 15 SW-V19 SW-20795 B 310765 PAB-F-2C-Z X X X - VN3 SW-DA4-52 460 V AC Circuit Breaker DA4 CB-F-1B-A SW-V20 Service Water

Discharge to Sea

Isolation Valve SW-CS-6172-1 Control Switch with Indication DA4 CB-F-1B-A DA4-VN3 DA4-VN3/1 DA4-VN3/2 DA4-GN0 DA4-E3Q 301107 DA4a DA4c CBA-FN-32

CBA-FN-33 EDE-MCC-612 SW-SS-8257 Selector Switch DA4 CB-F-1B-A SW-DA4-42/0,C Motor Starters DA4 CB-F-1B-A SW-DA4-49 Overload Relays DA4 CB-F-1B-A SW-ZS-V19 Valve Position Switch and Valve Open/Close

Torque Switches VN3 PAB-F-2C-Z SW-DA4-FU2/FU Fuse DA4 CB-F-1B-A SW-GN0-RTB-2 Auxiliary Relay GN0 CB-F-1B-A SW-DA4-R1 Auxiliary Relay E3Q CB-F-1B-A 16 SW-V20 Service Water Discharge to Sea

Isolation Valve SW-20795 A 310765 PAB-F-2C-Z X X X - VN4 SW-DA8-52 460 V AC Circuit Breaker DA8 CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 SW-V19 Note 1 17 SW-V23 Service Water to Cooling Tower

Isolation Valve SW-20795 B 310765 PAB-F-2C-Z X X X - VN5 SW-DA5-52 460 V AC Circuit Breaker DA5 CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 SW-V34 Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 12 Table RSS 3.1.3.7-7 FUNCTION: SERVICE WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 SW-V25 SW-20794 B 310717 CT-F-2B-A X X X - VM8 SW-CQ7-52 460 V AC Circuit Breaker CQ7 CT-F-1C-A SW-V54 Notes 1 and 6 Cooling Tower

Pump Discharge

Valve SW-CS-6174-2 Control Switch with Indication G2K CB-F-1B-A 301107 CQ7a CQ7c CBA-FN-32

CBA-FN-33 SW-SS-6174 Selector Switch G2K CB-F-1B-A CQ7-G2K CQ7-VM8/1 CQ7-VM8/2 G2K-GNO/3 SW-CQ7-42/O,C Motor Starters CQ7 CT-F-1C-A SW-CQ7-49 Overload Relay CQ7 CT-F-1C-A SW-ZS-V25 Valve Position Switch and Valve Open/Close

Torque Switches VM8 CT-F-2B-A SW-GNO-RV25 Auxiliary Relay GNO CB-F-1B-A GNO-VM8 E2U/1a E2U/1b Note 6 SW-VM8-V25 Position Switch VM8 CT-F-2B-A CBA-FN-32

CBA-FN-33 SW-CQ7-R1 Auxiliary Relay EE7 CT-F-1C-A 19 SW-V34 Service Water to Cooling Tower

Outlet Valve SW-20795 A 310765 PAB-F-2C-Z X X X - VN6 SW-DA9-52 460 V ac Circuit Breaker DA9 CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 SW-V23 Note 1 20 SW-V44 Service Water Unit Pumps Intake

Valve SW-20794 A 301037 SW-F-2-0 X X X - VM1 SW-CU5-52 460 V ac Circuit Breaker CU5 SW-F-1B-A - - - None Note 7 21 SW-V54 SW-20794 A 301717 CT-F-2B-A X X X - VM5 SW-CP8-52 460 V ac Circuit Breaker CP8 CT-F-1D-A 310107 CP8a CP8c CBA-FN-19

CBA-FN-20 SW-V25 Notes 1 and 6 Cooling Tower

Pump Discharge

Valve SW-CS-6164-2 Control Switch with Indication G2H CB-F-1A-A CP8-G2H CP8-VM5 CP8-VM5/1 CP8-VM5/2 G2H-GN9/5 SW-SS-6164 Selector Switch G2H CB-F-1A-A SW-CP8-42/O,C Motor Starters CP8 CT-F-1D-A SW-CP8-49 Overload Relay CP8 CT-F-1D-A SW-ZS-V54 Valve Position Switch and Valve Open/Close

Torque Switches VM5 CT-F-2B-A SW-CP8-FU Fuse CP8 CT-F-1D-A SW-GN9-RV54 Auxiliary Relay GN9 CB-F-1A-A E2T/1a E2T/1b Note 6 SW-ZS-V54 Position Switch VM5 CT-F-2B-A GN9-VM5 CBA-FN-19

CBA-FN-20 22 SW-V63 Service Water Discharge Valve

to Intake SW-20794 A 301037 SW-F-2-0 X X X - VQ0 SW-DZ3-52 460 V AC Circuit Breaker DZ3 SW-F-1B-A - - - None Note 7 23 EDE-CP-248 Service Water Cooling Tower

Actuation Logic

(TA) - A 310442 CB-F-1A-A X X X - GN9 SW-E87/4-72 125 V DC Circuit Breaker E87 CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 EDE-CP-249 Note 1 24 EDE-CP-249 Service Water Cooling Water

Actuation Logic

(TA) - B 310442 CB-F-1B-A X X X - GNO SW-E88/4-72 125 V DC Circuit Breaker E88 CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 EDE-CP-248 Note 1

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-1 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CC-P-11A PCCW Loop "A" Pump "A" CC-20205 A 310765 PAB-F-2C-Z X X X - M05 CC-A58-52 4160 V AC Circuit Breaker A58 CB-F-1A-A A58-M05/1 CC-CS-2140-2 Control Switch A58 CB-F-1A-A CC-P-11B or CC-P-11D CC-SS-2140 Selector Switch A58 CB-F-1A-A 310895 A58a A58h A58b A58c A58d CBA-FN-19

CBA-FN-20 PAH-FN-42A EDE-SWG-5 EDE-A53-94-1A Bus Undervoltage Relay A53 CB-F-1A-A CC-A58-52H Truck-Operated Contact A58 CB-F-1A-A CC-A58-50/51 Instrument/Time Overcurrent Relays

øA, øC A58 CB-F-1A-A CC-A58-86 Lockout Relay A58 CB-F-1A-A CC-A58-AM Ammeter A58 CB-F-1A-A CC-A58-AS Ammeter Switch A58 CB-F-1A-A CC-A58-CT Current Transformer (150/5) A58 CB-F-1A-A CC-A58-TD1 CT Test Device A58 CB-F-1A-A CC-A58-ATR Transducer A58 CB-F-1A-A CC-A58-TD2 Lockout Relay Test Device A58 CB-F-1A-A CC-A58-FU Fuses A58 CB-F-1A-A CC-A58-52Z Timing Relay A58 CB-F-1A-A CC-A58-G,R,W Indicating Lights A58 CB-F-1A-A CC-A58-51GS Ground Sensor Relay A58 CB-F-1A-A CC-A59-52S Mechanical Operated Switch A59 CB-F-1A-A CC-A58-62 Time Delay Relay A58 CB-F-1A-A

.Notes  1. The equipment is mechanical with no electrical requirement. 
2. During normal operation, the valve is in its safe shutdown position. To prevent spurious operation, this equipment will be disabled at the appropriate control location.
3. Electrical Conduit Plan Drawing 310765 is listed only to show the fire zone corresponding to the location of the Heat Exchangers CC-E-17A and CC-E-17B as identified in Drawing 805217.
4. The valve will be operated locally using the handwheel when establishing RHR flow for the second phase of cooldown.
5. Electrical Conduit Plan Drawings 310581 is listed only to show the fire zone corresponding to the location of CC-TK-196 as identified in Drawing 805193.
6. Refer to Table 3.1.3-4 for MM-UQ-5866, MM-UQ-5867, MM-UQ-5868, and MM-UQ-5869.
7. These valves are in the open position with their circuit breakers locked open to prevent spurious operation.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-2 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 CC-P-11B PCCW Loop "B" Pump "B" CC-20211 B 310765 PAB-F-2C-Z X X X - M06 CC-A78-52 4160 V AC Circuit Breaker A78 CB-F-1B-A A78-M06/1 CC-CS-2240-2 Control Switch A78 CB-F-1B-A CC-P-11A or CC-P-11C CC-SS-2240 Selector Switch A78 CB-F-1B-A 310895 A78a A78h A78b A78c A78d CBA-FN-32

CBA-FN-33 PAH-FN-42B EDE-SWG-6 EDE-A73-94-1A Bus Undervoltage Relay A73 CB-F-1B-A CC-A78-52H Truck-Operated Contact A78 CB-F-1B-A CC-A78-50/51 Instrument/Time Overcurrent Relays

øA, øC A78 CB-F-1B-A CC-A78-86 Lockout Relay A78 CB-F-1B-A CC-A78-AM Ammeter A78 CB-F-1B-A CC-A78-AS Ammeter Switch A78 CB-F-1B-A CC-A78-CT Current Transformer (150/5) A78 CB-F-1B-A CC-A78-TD1 CT Test Device A78 CB-F-1B-A CC-A78-ATR Transducer A78 CB-F-1B-A CC-A78-TD2 Lockout Relay Test Device A78 CB-F-1B-A CC-A78-FU Fuses A78 CB-F-1B-A CC-A78-52Z Timing Relay A78 CB-F-1B-A CC-A78-G,R,W Indicating Lights A78 CB-F-1B-A CC-A78-51GS Ground Sensor Relay A78 CB-F-1B-A CC-A79-52S Mechanical-Operated Switch A79 CB-F-1B-A CC-A78-62 Time Delay Relay A78 CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-3 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 CC-P-11C PCCW Loop "A" Pump "C" CC-20205 A 310766 PAB-F-2C-Z X X X - M07 CC-A59-52 4160 V AC Circuit Breaker A59 CB-F-1A-A A59-M07/1 CC-CS-2141-2 Control Switch A59 CB-F-1A-A CC-P-11B or CC-P-11D CC-SS-2141 Selector Switch A59 CB-F-1A-A 310895 A59a A59h A59b A59c A59d CBA-FN-19

CBA-FN-20 PAH-FN-42A EDE-SWG-5 EDE-A53-94-1A Bus Undervoltage Relay A53 CB-F-1A-A CC-A59-52H Truck-Operated Contact A59 CB-F-1A-A CC-A59-50/51 Instrument/Time Overcurrent Relays

øA, øC A59 CB-F-1A-A CC-A59-86 Lockout Relay A59 CB-F-1A-A CC-A59-AM Ammeter A59 CB-F-1A-A CC-A59-AS Ammeter Switch A59 CB-F-1A-A CC-A59-CT Current Transformer (150/5) A59 CB-F-1A-A CC-A59-TD1 CT Test Device A59 CB-F-1A-A CC-A59-ATR Transducer A59 CB-F-1A-A CC-A59-TD2 Lockout Relay Test Device A59 CB-F-1A-A CC-A59-FU Fuses A59 CB-F-1A-A CC-A59-52Z Timing Relay A59 CB-F-1A-A CC-A59-G,R,W Indicating Lights A59 CB-F-1A-A CC-A59-51GS Ground Sensor Relay A59 CB-F-1A-A CC-A58-52S Mechanical-Operated Switch A58 CB-F-1A-A CC-A59-62 Time Delay Relay A59 CB-F-1A-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-4 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 CC-P-11D PCCW Loop "B" Pump "D" CC-20211 B 310766 PAB-F-2C-Z X X X - M08 CC-A79-52 4160 V AC Circuit Breaker A79 CB-F-1B-A A79-M08/1 CC-CS-2241-2 Control Switch A79 CB-F-1B-A CC-SS-2241 Selector Switch A79 CB-F-1B-A 310895 A79a A79h A79b A79c A79d CBA-FN-32

CBA-FN-33 PAH-FN-42B EDE-SWG-6 CC-P-11A or CC-P-11C EDE-A73-94-1A Bus Undervoltage Relay A73 CB-F-1B-A CC-A79-52H Truck-Operated Contact A79 CB-F-1B-A CC-A79-50/51 Instrument/Time Overcurrent Relays

øA, øC A79 CB-F-1B-A CC-A79-86 Lockout Relay A79 CB-F-1B-A CC-A79-AM Ammeter A79 CB-F-1B-A CC-A79-AS Ammeter Switch A79 CB-F-1B-A CC-A79-CT Current Transformer (150/5) A79 CB-F-1B-A CC-A79-TD1 CT Test Device A79 CB-F-1B-A CC-A79-ATR Transducer A79 CB-F-1B-A CC-A79-TD2 Lockout Relay Test Device A79 CB-F-1B-A CC-A79-FU Fuses A79 CB-F-1B-A CC-A79-52Z Timing Relay A79 CB-F-1B-A CC-A79-G,R,W Indicating Lights A79 CB-F-1B-A CC-A79-51GS Ground Sensor Relay A79 CB-F-1B-A CC-A78-52S Mechanical-Operated Switch A78 CB-F-1B-A CC-A79-62 Time Delay Relay A79 CB-F-1B-A 5 CC-TV-2171-1 CC-20205 A 310765 PAB-F-2C-Z X X X X UN6 CC-E2T/3-72 125 V DC Circuit Breaker E2T CB-F-1A-A CC-TV-2271-1 Note 6 CC-SS-2171 Selector Switch G81 CB-F-1A-A Primary Component

Cooling Water

Heat Exchanger

E-17A Temperature

Control Valve CC-GN9-R1 Auxiliary Relay GN9 CB-F-1A-A E2T-G81 G81-G2M G81-UN6/1 G81-UN7/1 G81-GN9/A 310895 E2T/3a E2T/3c E2T/3d CBA-FN-19

CBA-FN-20 PAH-FN-42A EDE-PP-113A Instrument Air CC-TY-2171-1 Pilot Solenoid G2M PAB-F-2C-Z CC-ZL-2171-5 Valve Position Indicating Lights G81 CB-F-1A-A CC-ZS-TV-2171-1 Valve Position Switch UN6 PAB-F-2C-Z CC-SS-2171 Selector Switch G81 CB-F-1A-A G81-G2M/2 CC-HIC-2171 Auto/Manual Controller with

Indicator G81 CB-F-1A-A 310895 310952 4c FK0d FK0f FP 71337

16 CC-HQY-2171 E/E Converter G2H CB-F-1A-A CBA-FN-19

CBA-FN-20 PAH-FN-42A

MM-UQ-5866

NM-UQ-5867 Instrument Air CC-HY-2171 E/I Converter G2H CB-F-1A-A CC-TY-2171-4 I/P Converter G2M PAB-F-2C-Z CC-TY-2171-5 I/P Converter G2M PAB-F-2C-Z

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-5 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 CC-TV-2171-2 CC-20205 A 310765 PAB-F-2C-E X X X X UN7 CC-E2T/3-72 125 V DC Circuit Breaker E2T CB-F-1A-A CC-TV-2271-2 Note 6 CC-SS-2171 Selector Switch G81 CB-F-1A-A Primary Component

Cooling Water

Heat Exchanger

E-17A Temperature

Control Valve CC-GN9-R1 Auxiliary Relay GN9 CB-F-1A-A 310895 E2T/3a E2T/3c E2T/3d CC-TY-2171-2 Pilot Solenoid G2M PAB-F-2C-Z CBA-FN-19

CBA-FN-20 PAH-FN-42A EDE-PP-113A Instrument Air CC-ZL-2171-6 Valve Position Indicating Lights G81 CB-F-1A-A E2T-G81 G81-G2M G81-UN6/1 G81-UN7/1 G81-GN9/A CC-ZS-TV-2171-2 Valve Position Switch UN7 PAB-F-2C-Z CC-SS-2171 Selector Switch G81 CB-F-1A-A G81-G2M/2 CC-HIC-2171 Auto/Manual Controller with

Indicator G81 CB-F-1A-A 310895 310952 4c FK0d FK0f FP 71337

16 CC-HQY-2171 E/E Converter G2H CB-F-1A-A CBA-FN-19

CBA-FN-20 PAH-FN-42A

MM-UQ-5866

MM-UQ-5867 Instrument Air CC-HY-2171 E/I Converter G2H CB-F-1A-A CC-TY-2171-4 I/P Converter G2M PAB-F-2C-Z CC-TY-2171-5 I/P Converter G2M PAB-F-2C-Z 7 CC-TV-2271-1 CC-20211 B 310765 PAB-F-2C-Z X X X X UP9 CC-E2U/3-72 125 V DC Circuit Breaker E2U CB-F-1B-A CC-TV-2171-1 Note 6 CC-SS-2271 Selector Switch GZ0 CB-F-1B-A Primary Component

Cooling Water

Heat Exchanger

E-17B Temperature

Control Valve CC-GN0-R1 Auxiliary Relay GN0 CB-F-1B-A 310895 E2U/3a E2U/3c E2U/3d CBA-FN-32 CBA-FN-33 PAH-FN-42B EDE-PP-113B Instrument Air CC-TY-2271-1 Pilot Solenoid UI2 PAB-F-2C-Z E2U-GN0/6 E2U-GZ0 GN0-GZ0/5 GN0-GZ0/9 GZ0-UP9/1 GZ0-UP0/1 GZ0-UI2 CC-ZL-2271-5 Valve Position Indicating Lights GZ0 CB-F-1B-A CC-ZS-TV-2271-1 Valve Position Switch UP9 PAB-F-2C-Z CC-GN0-R2 Auxiliary Relay GN0 CB-F-1B-A CC-SS-2271 Selector Switch GZ0 CB-F-1B-A GZ0-Q60 CC-HIC-2271 Auto/Manual Controller with

Indicator GZ0 CB-F-1B-A CC-HQY-2271 E/E Converter GZ0 CB-F-1B-A 310895 3108952 4c FJ4j FJ4n FP 71336

3 CBA-FN-32

CBA-FN-33 PAH-FN-42B

MM-UQ-5868

MM-UQ-5869 Instrument Air CC-HY-2271 E/I Converter GZ0 CB-F-1B-A CC-TY-2271-4 I/P Converter Q60 PAB-F-2C-Z CC-TY-2271-5 I/P Converter Q60 PAB-F-2C-Z

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-6 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 8 CC-TV-2271-2 CC-20211 B 310765 PAB-F-2C-Z X X X X UP0 CC-E2U/3-72 125 V DC Circuit Breaker E2U CB-F-1B-A CC-TV-2171-2 Note 6 CC-SS-2271 Selector Switch GZ0 CB-F-1B-A 310895 E2U/3a E2U/3c E2U/3d Primary Component

Cooling Water

Heat Exchanger

E-17B Temperature

Control Valve CC-GN0-R1 Auxiliary Relay GN0 CB-F-1B-A E2U-GN0/6 E2U-GZ0 GN0-GZ0/5 GN0-GZ0/9 GZ0-UP9/1 GZ0-UP0/1 GZ0-UI2 CBA-FN-32

CBA-FN-33 PAH-FN-42B EDE-PP-113B Instrument Air CC-TY-2271-2 Pilot Solenoid UI2 PAB-F-2C-Z CC-ZL-2271-6 Valve Position Indicating Lights GZ0 CB-F-1B-A CC-ZS-TV-2271-2 Valve Position Switch UP0 PAB-F-2C-Z CC-GN0-R2 Auxiliary Relay GN0 CB-F-1B-A CC-SS-2271 Selector Switch GZ0 CB-F-1B-A GZ0-Q60 CC-HIC-2271 Auto/Manual Controller with

Indicator GZ0 CB-F-1B-A CC-HQY-2271 E/E Converter GZ0 CB-F-1B-A 310895 3108952 4c FJ4j FJ4n FP 71336

3 CBA-FN-32

CBA-FN-33 PAH-FN-42B

MM-UQ-5868

MM-UQ-5869 Instrument Air CC-HY-2271 E/I Converter GZ0 CB-F-1B-A CC-TY-2271-4 I/P Converter Q60 PAB-F-2C-Z CC-TY-2271-5 I/P Converter Q60 PAB-F-2C-Z 9 CC-E-17A Primary Component Cooling Water

Heater Exchanger CC-20205 A 310765 805217 PAB-F-2C-Z PAB-F-3A-Z X X - - - - - - - - - - Service Water CC-E-17B Notes 1,3 10 CC-E-17B Primary Component Cooling Water

Heater Exchanger CC-20211 B 310765 805217 PAB-F-2C-Z PAB-F-3A-Z X X - - - - - - - - - - Service Water CC-E-17A Notes 1,3 11 CC-V-145 RH-E-9A Return Header Isolation

Valve CC-20207 A 310763 RHR-F-3B-Z - X X - V78 CC-BY2-52 460 V AC Circuit Breaker BY2 CB-F-1A-A - - - EAH-FN-5A EAH-FN-31A CC-V-272 Note 4 12 CC-V-272 RH-E-9B Return Header Isolation

Valve CC-20213 B 310763 RHR-F-3A-Z - X X - V72 CC-BY8-52 460 V AC Circuit Breaker BY8 CB-F-1B-A - - - EAH-FN-5B EAH-FN-31B CC-V-145 Note 4 13 CC-P-322A Thermal Barrier PCCW Recirc Pump CC-20209 A 310576 C-F-1-Z X X X - M1D CC-B4M-52-1,2 460 V AC Circuit Breakers B4M CB-F-1A-A 310895 B4Ma B4Mc CC-P-322B CC-CS-2077-2 Control Switch with Indication G2G CB-F-1A-A B4M-H18 H18-M1D B4M-G81 CBA-FN-19

CBA-FN-20 EDE-MCC-515 CC-SS-2077 Selector Switch G2G CB-F-1A-A CC-B4M-42 Motor Starter B4M CB-F-1A-A CC-B4M-49 Overload Relay B4M CB-F-1A-A EDE-MM-94 Electrical Penetration H18 C-F-2-Z, ET-F-1A-A CC-B4M-FU Fuse B4M CB-F-1A-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-7 FUNCTION: PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 14 CC-P-322B Thermal Barrier PCCW Recirc Pump CC-20209 B 310577 C-F-1-Z X X X - M1E CC-B4Q-52-1,2 460 V AC Circuit Breaker B4Q CB-F-1B-A 310895 B4Qa B4Qc CC-P-322A CC-CS-2078-2 Control Switch with Indication G2J CB-F-1B-A B4Q-H15 H15-M1E B4Q-GZ0 CBA-FN-32

CBA-FN-33 EDE-MCC-615 CC-SS-2078 Selector Switch G2J CB-F-1B-A CC-B4Q-42 Motor Starter B4Q CB-F-1B-A CC-B4Q-49 Overload Relay B4Q CB-F-1B-A EDE-MM-91 Electrical Penetration H15 C-F-1-Z, ET-F-1C-A CC-B4Q-FU Fuse B4Q CB-F-1B-A 15 CC-E-153A Thermal Barrier Heat Exchanger CC-20209 A 310576 C-F-1-Z X X - - - - - - - - - -

- CC-E-153B Note 1 16 CC-E-153B Thermal Barrier Heat Exchanger CC-20209 B 310577 C-F-1-Z X X - - -  -  - - - - - -
- CC-E-153A Note 1 17 CC-V-1101 Thermal Barrier HX CC-E-153A 

Isolation Valve CC-20209 A 310769 PP-F-3A-Z X X X - V2S CC-B4K-52 460 V AC Circuit Breaker B4K CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 CC-V-1092 Note 2 18 CC-V-1109 Thermal Barrier HX CC-E-153A

Isolation Valve CC-20209 A 310769 PP-F-3A-Z X X X - V2T CC-B4L-52 460 V AC Circuit Breaker B4L CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 CC-V-1095 Note 2 19 CC-V-1092 Thermal Barrier HX CC-E-153B

Isolation Valve CC-20209 B 310769 PP-F-4B-Z X X X - V2V CC-B4P-52 460 V AC Circuit Breaker B4P CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 CC-V-1101 Note 2 20 CC-V-1095 Thermal Barrier HX CC-E-153B

Isolation Valve CC-20209 B 310769 PP-F-4B-Z X X X - V2U CC-B4N-52 460 V AC Circuit Breaker B4N CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 CC-V-1109 Note 2 21 CC-V-428 RC-P-1A Thermal Barrier Isolation

Valve CC-20209 A 310578 C-F-2-Z X X X - V74 CC-BY4-52-1 460 V AC Circuit Breaker BY4 CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 None Note 7 22 CC-V-438 RC-P-1C Thermal Barrier Isolation

Valve CC-20209 B 310579 C-F-2-Z X X X - V76 CC-BY6-52-1 460 V AC Circuit Breaker BY6 CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 None Note 7 23 CC-V-439 RC-P-1D Thermal Barrier Isolation

Valve CC-20209 A 310579 C-F-2-Z X X X - V70 CC-BY7-52-1 460 V AC Circuit Breaker BY7 CB-F-1A-A - - - CBA-FN-19

CBA-FN-20 None Note 7 24 CC-V-395 RC-P-1B Thermal Barrier Isolation

Valve CC-20209 B 310578 C-F-2-Z X X X - V69 CC-BY5-52-1 460 V AC Circuit Breaker BY5 CB-F-1B-A - - - CBA-FN-32

CBA-FN-33 None Note 7 25 CC-TK-196 Thermal Barrier Loop Head Tank CC-20209 A/B 310581 805193 C-F-3-Z X X - - - - - - - - - -

- None Notes 1,5 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.8-8 FUNCTION:  PRIMARY COMPONENT COOLING WATER PHYSICAL REQUIRED FOR POWER  SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO.

TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 26 CC-TK-19A Primary Component Cooling Water

Head Tank CC-20205 A 310767 PAB-F-3A-Z X X - - - - - - - - - -

- CC-TK-19B Note 1 27 CC-TK-19B Primary Component Cooling Water 

Head Tank CC-20211 B 310767 PAB-F-3A-Z X X - - - - - - - - - -

- CC-TK-19A Note 1

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 4 Table RSS 3.1.3.9-1 Table RSS 3.1.3.9 Deleted SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.10-1 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 CBA-DP-24A CBA-20303 A 310443 CB-F-2B-A X X X X V1A CBA-FY-5550A Pilot Solenoid V1A CB-F-2B-A 310926 BK4a BK4c Instrument Air CBA-DP-24F Note 3,4 Mechanical Room

"A" Outside Air

Damper FP-R1 Signal Actuating

Output Relay GP4 TB-F-2-Z CBA-TIC-5571 Temperature Indicating Control

(Pneumatic) G3C CB-F-2B-A G4P-V1A G4P-V1B G4P-V1C G3C-G4P/5 CBA-FY-5550B Pilot Solenoid V1B CB-F-2B-A CBA-FY-5550C Pilot Solenoid V1C CB-F-2B-A 2 CBA-DP-24B CBA-20303 A 310443 CB-F-2B-A X X X X V1B CBA-FY-5550B Pilot Solenoid V1B CB-F-2B-A BK4a BK4c Instrument Air CBA-DP-24E Note 3,4 Mechanical Room

"A" Recirculating

Air Damper FP-R1 Signal Actuating

Output Relay G4P TB-F-2-Z G4P-V1A G4P-V1B G4P-V1C G3C-G4P/5 CBA-TIC-5571 Temperature Indicatin g Controller (Pneumatic) G3C CB-F-2B-A CBA-FY-5550A Pilot Solenoid V1A CB-F-2B-A CBA-FY-5550C Pilot Solenoid V1C CB-F-2B-A 3 CBA-DP-24C CBA-20303 A 310443 CB-F-2B-A X X X X V1C CBA-FY-5550C Pilot Solenoid V1C CB-F-2B-A BK4a BK4c Instrument Air CB-DP-24D Note 3,4 Mechanical Room

"A" Return Air

Damper FP-R1 Signal Actuating

Output Relay G4P TB-F-2-Z CBA-TIC-5571 Temperature Indicating Controller (Pneumatic) G3C CB-F-2B-A G4P-V1A G4P-V1B G4P-V1C G3C-G4P/5 CBA-FY-5550A Pilot Solenoid V1A CB-F-2B-A CBA-FY-5550B Pilot Solenoid V1B CB-F-2B-A 4 CBA-DP-24D Mechanical Room "B" Return Air

Damper CBA-20303 B 310443 604094 CB-F-2C-A X X - X - CBA-TIC-5572 Temperature Indicatin g Controller (Pneumatic) - CB-F-2C-A - - - Instrument Air CBA-DP-24C Notes 1,2,3,4 5 CBA-DP-24E Mechanical Room "B" Recirculating

Air CBA-20303 B 310443 604094 CB-F-2C-A X X - X - CBA-TIC-5572 Temperature Indicating Controller (Pneumatic) - CB-F-2C-A - - - Instrument Air CBA-DP-24B Notes 1,2,3,4 6 CBA-DP-24F Mechanical Room "B" Outside Air

Damper CBA-20303 B 310443 604094 CB-F-2C-A X X - X - CBA-TIC-5572 Temperature Indicatin g Controller (Pneumatic) - CB-F-2C-A - - - Instrument Air CBA-DP-24A Notes 1,2,3,4

.Notes  1. Equipment is mechanical with no electrical requirements. 
2. Electrical conduit Plan Drawing 310443, listed only to show fire zone correlation reference to control building area covered by HVAC Drawing 604094 where CBA Dampers 24 D, E, and F are identified in plan.
3. Process connections showing positioning of air operated dampers, DP-24A-F, by pneumatic temperature indicating controllers, CBA-TIC-5571 and 5572, are detailed on I&C Loop Diagrams 510159 and 510160.
4. Instrument air is required for normal positioning of dampers for area temperature control. Should IA fail, dampers 24A, 24B, 24E and 24F will fail "as is" and 24C and 24D fail open. The operators can start and stop fans to maintain switchgear room habitability.
5. Dampers fail open on loss of instrument air, which is the safe shutdown position.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.10-2 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 CBA-FN-19 CBA-20303 A 310443 CB-F-2B-A X X X - N28 CBA-BL6-52 460 V ac Circuit Breaker BL6 CB-F-1A-A BL6-HR2/1 BL6-N28/2 310926 BL6a BL6c EDE-MCC-515 CBA-FN-32 Control Building

Train "A" SWGR

Supply Fan CBA-CS-5552 Control Switch with Indication BL6 CB-F-1A-A DG-HR2-HR9X EPS Step Loading Relay HR2 CB-F-1A-A DG-HR2-RMO EPS Manual Override Relay HR2 CB-F-1A-A CBA-BL6-42 Motor Starter BL6 CB-F-1A-A CBA-BL6-42X Motor Starter Auxiliary Relay BL6 CB-F-1A-A CBA-BL6-49 Overload Relays BL6 CB-F-1A-A CBA-BL6-FU Fuse BL6 CB-F-1A-A 8 CBA-FN-20 CBA-20303 A 310443 CB-F-2B-A X X X - N30 CBA-BL7-52 460 V ac Circuit Breaker BL7 CB-F-1A-A BL7-HR2 BL7-N30/2 BL7a BL7c EDE-MCC-521 CBA-FN Control Building

Train "A" SWGR

Return Fan DG-HR2-RMO EPS Manual Override Relay HR2 CB-F-1A-A CBA-BL7-42 Motor Starter BL7 CB-F-1A-A CBA-BL7-49 Overload Relays BL7 CB-F-1A-A CBA-BL7-FU Fuse BL7 CB-F-1A-A CBA-CS-5554 Control Switch with Indication BL7 CB-F-1A-A DG-HR2-HR9X EPS Step Loading Relay HR2 CB-F-1A-A CBA-BL7-42X Motor Starter Auxiliary Relay BL7 CB-F-1A-A 9 CBA-FN-21A CBA-20303 A 310443 CB-F-2B-A X X X - N32 CBA-BL8-52 460 V ac Circuit Breaker BL8 CB-F-1A-A BL8a BL8c EDE-MCC-521 CBA-FN-21B Control Building

Battery Room

Exhaust Fan "A" CBA-CS-5556 Control Switch with Indication BL8 CB-F-1A-A BL8-N32 BL8-VV5/1 BL8-VV5 CBA-ZS-DP-21A Damper Position Switch VV5 CB-F-2B-A CBA-BL8-42 Motor Starter BL8 CB-F-1A-A CBA-ZL-5556 Damper 21A Indicatin g Lights BL8 CB-F-1A-A CBA-BL8-49 Overload Relays BL8 CB-F-1A-A CBA-DP-21A-20 Pilot Solenoid VV5 CB-F-2B-A CBA-BL8-FU Fuse BL8 CB-F-1A-A 10 CBA-DP-21A CBA-20303 A 310443 CB-F-2B-A X X X X VV5 CBA-BL8-52 460 V ac Circuit Breaker BL8 CB-F-1A-A BL8-VV5 BL8-VV5/1 BL8a BL8c EDE-MCC-521 CBA-DP-21B Note 5 Battery Room

Exhaust Fan "A"

Damper CBA-BL8-FU Fuse BL8 CB-F-1A-A CBA-CS-5556 Control Switch with Indication BL8 CB-F-1A-A CBA-DP-21A-20 Pilot Solenoid VV5 CB-F-2B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.10-3 FUNCTION: CONTROL BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 11 CBA-FN-21B CBA-20303 B 310443 CB-F-2C-A X X X - N33 CBA-BL5-52 460 V ac Circuit Breaker BL5 CB-F-1B-A 310926 BL5a BL5c EDE-MCC-621 CBA-FN-21A Control Building

Battery Room

Exhaust Fan "B" CBA-CS-5557 Control Switch with Indication BL5 CB-F-1B-A BL5-N33 BL5-VV4/1 BL5-VV4 CBA-ZS-DP-21B Damper Position Switch VV4 CB-F-2C-A CBA-BL5-42 Motor Starter BL5 CB-F-1B-A CBA-ZL-5557 Damper 21B Indicatin g Lights BL5 CB-F-1B-A CBA-BL5-49 Overload Relays BL5 CB-F-1B-A CBA-DP-21B-20 Pilot Solenoid VV4 CB-F-2C-A CBA-BL5-FU Fuse BL5 CB-F-1B-A 12 CBA-DP-21B CBA-20303 B 310443 CB-F-2C-A X X X X VV4 CBA-BL5-52 460 V ac Circuit Breaker BL5 CB-F-1B-A BL5-VV4 BL5-VV4/1 BL5a BL5c EDE-MCC-621 CBA-DP-21A Note 5 Battery Room

Exhaust Fan "B"

Damper CBA-BL5-FU Fuse BL5 CB-F-1B-A CBA-CS-5557 Control Switch BL5 CB-F-1B-A CBA-DP-21B-20 Pilot Solenoid VV4 CB-F-2C-A 13 CBA-FN-32 CBA-20303 B 310443 CB-F-2C-A X X X - NH3 CBA-BL3-52 460 V ac Circuit Breaker BL3 CB-F-1B-A BL3-HR4 BL3-NH3 BL3a BL3c EDE-MCC-621 CBA-FN-19 Control Building

Train "B" SWGR

Supply Fan CBA-CS-5559 Control Switch with Indication BL3 CB-F-1B-A DG-HR4-HR9X EPS Step Loading Relay HR4 CB-F-1B-A DG-HR4-RMO EPS Manual Override Relay HR4 CB-F-1B-A CBA-BL3-42 Motor Starter BL3 CB-F-1B-A CBA-BL3-42X Motor Starter Auxiliary Relay BL3 CB-F-1B-A CBA-BL3-49 Overload Relays BL3 CB-F-1B-A CBA-BL3-FU Fuse BL3 CB-F-1B-A 14 CBA-FN-33 CBA-20303 B 310443 CB-F-2C-A X X X - NH5 CBA-BL4-52 460 V ac Circuit Breaker BL4 CB-F-1B-A BL4-NR4 BL4-NH5 BL4a BL4c EDE-MCC-621 CBA-FN-20 Control Building

Train "B" SWGR

Return Fan CBA-CS-5561 Control Switch with Indication BL4 CB-F-1B-A DG-HR4-HR9X EPS Step Loading Relay HR4 CB-F-1B-A CBA-BL4-42 Motor Starter BL4 CB-F-1B-A CBA-BL4-49 Overload Relays BL4 CB-F-1B-A CBA-BL4-FU Fuse BL4 CB-F-1B-A DG-HR4-RMO EPS Manual Override

Relay HR4 CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 11 Table RSS 3.1.3.11-1 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 DAH-FN-25A DG-1A Room Supply Air Fan DAH-20624 A 310525 DG-F-3A-Z X X X - N37 DAH-B01-52 460 V AC Circuit Breaker B01 CB-F-1A-A EDE-MCC-521 EDE-PP-11E DAH-FN-25B DAH-CS-5529 Control Switch with Fan Indicating Lights B01 CB-F-1A-A B01-N37/1 B01-J1E B01-T3P B01-GN9 310928 B01a B01c B01d DAH-FISH-5529 Flow Switch S40 DG-F-3A-Z DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DAH-ED1-R2 Auxiliary Relay ED1 CB-F-1A-A DG-G29-HSR DG-1A High Speed Relay G29 DG-F-2A-A DAH-B01-42 Motor Starter B01 CB-F-1A-A DAH-B01-42X Motor Starter Auxiliary Relay B01 CB-F-1A-A DAH-B01-49 Overload Relays B01 CB-F-1A-A DAH-B01-FU Fuse B01 CB-F-1A-A DAH-ED1-R1 Control Circuit Power Monitor Auxiliary

Relay E01 CB-F-1A-A DAH-GN9-RS EPS Permissive Auxiliary Relay GN9 CB-F-1A-A DAH-GN9-RD Damper Position Auxiliary Relay GN9 CB-F-1A-A DAH-E3E/7-52 120 V AC Circuit Breaker E3E CB-F-1A-A E3E/7a E3E/7b EDE-MCC-515 EDE-PP-E3E DAH-TB-5529-1 Temperature Bistable J1E DG-F-2A-A J1E-T3P (Non CASP) E3E-J1E DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DAH-TE-5529-1 Temperature Element T3P DG-F-2A-A DAH-TT-5529-1 Temperature Transmitter J1E DG-F-2A-A DAH-CP-295 DG-A Room Air Handling Fans and Damper Control Panel J1E DG-F-2A-A

.Notes   1. Air is not required for support as damper fails open. 

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 11 Table RSS 3.1.3.11-2 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 DAH-DP-16A DG-1A Room Return Air Damper DAH-20624 A 310524 DG-F-2A-A X X X X UF9 DAH-ED1-R2 (B01 & B03) Auxiliary Relays ED1 CB-F-1A-A E1S/6a E1S/6c EDE-MCC-521 EDE-PP-11E DAH-DP-16B Note 1 DAH-DP-16A-20 Pilot Solenoid UF9 DG-F-2A-A DAH-TB-5529-1 Temperature Bistable J1E DG-F-2A-A DAH-ZS-DP-16A Damper TBA Position Switch UF9 DG-F-2A-A DG-HR2-PR1 EPS Permissive Auxiliary Relay HR2 CB-F-1A-A DG-HR2-HR8 EPS Permissive Auxiliary Relay HR2 CB-F-1A-A DG-HR2-SR1 EPS Permissive Auxiliary Relay HR2 CB-F-1A-A DAH-GN9-RS EPS Permissive Auxiliary Relay GN9 CB-F-1A-A B01-UF9/1 B01-J1E/1 EIS-GN9 EDI-GN9 B03-UF9 B01-HR2 DAH-GN9-RD Damper Position Auxiliary Relay GN9 CB-F-1A-A DAH-E1S/6-52 120 V AC Circuit

Breaker EIS CB-F-1A-A DAH-ZL-5529-4 Damper Position Indicating Lights B03 CB-F-1A-A DAH-E3E/7-52 120 V AC Circuit Breaker E3E CB-F-1A-A E3E/7a E3E/7b EDE-MCC-515 EDE-PP-E3E DAH-TB-5529-1 Temperature Bistable J1E DG-F-2A-A J1E-T3P (Non CASP) E3E-J1E DAH-TE-5529-1 Temperature Element T3P DG-F-2A-A DAH-TT-5529-1 Temperature Transmitter J1E DG-F-2A-A DAH-CP-295 DG-A Room Air Handling Fans and

Damper Control Panel J1E DG-F-2A-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 11 Table RSS 3.1.3.11-3 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 DAH-FN-25B DG-1B Room Supply Air Fan DAH-20624 B 310525 DG-F-3B-Z X X X - N38 DAH-B02-52 460 V AC Circuit Breaker B02 CB-F-1B-A EDE-MCC-621 EDE-PP-11F DAH-FN-25A DAH-CS-5530 Control Switch with Fan Indicating Lights B02 CB-F-1B-A 310928 B02a B02c B02d DAH-FISH-5530 Flow Switch S41 DG-F-3B-Z B02-N38/1 B02-G30 B02-S41 B02-J1F B02-GN0 EE3-E3D DAH-J1F-RTB Temperature Bistable Auxiliary Relay J1F DG-F-2B-A DAH-EE3-R2 Auxiliary Relay EE3 CB-F-1B-A DAH-B02-FU Fuse B02 CB-F-1B-A DG-G30-HSR DG-1B High Speed Relay G30 DG-F-2B-A DAH-B02-42 Motor Starter B02 CB-F-1B-A DAH-B02-42X Motor Starter Auxiliary Relay B02 CB-F-1B-A DAH-B02-49 Overload Relays B02 CB-F-1B-A DAH-E3D-R1 Control Circuit Power Monitor Auxiliary

Relay E3D CB-F-1B-A DAH-GN0-RS EPS Permissive Auxiliary Relay GN0 CB-F-1B-A DAH-GN0-RD Damper Position Auxiliary Relay GN0 CB-F-1B-A DAH-E3F/7-52 120 V AC Circuit Breaker E3F CB-F-1B-A E3F/7a E3F/7b EDE-MCC-615 EDE-PP-E3F DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A J1F-T3Q (Non-CASP) E3F-J1F DAH-J1F-RTB Temperature Bistable Auxiliary Relay J1F DG-F-2B-A DAH-TE-5330-1 Temperature Element T3Q DG-F-2B-A DAH-TT-5530-1 Temperature Transmitter J1F DG-F-2B-A DAH-CP-296 DG-B Room Air Handling Fans and Damper Control Panel J1F DG-F-2B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 11 Table RSS 3.1.3.11-4 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 DAH-DP-16B DG-1B Room Return Air Damper DAH-20624 B 310524 DG-F-2B-A X X X X UF0 DAH-EE3-R2 (B02 & B04) Auxiliary Relay EE3 CB-F-1B-A E1T/6a E1T/6c EDE-MCC-621 EDE-PP-11F DAH-DP-16A Note 1 DAH-DP-16B-20 Pilot Solenoid UF0 DG-F-2B-A DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A DAH-ZS-DP-16B Damper 16B Position Switch UF0 DG-F-2B-A B02-UF0/1 ED0-J1F B02-EDO EE3-GN0/2 EIT-GN0 B01-HR4 B04-UF0 DG-HR4-HRB EPS Permissive Auxiliary Relay HR4 CB-F-1B-A DH-HR4-PR1 EPS Permissive Auxiliary Relay HR4 CB-F-1B-A DG-HR4-SR1 EPS Permissive Auxiliary Relay HR4 CB-F-1B-A DAH-GN0-RS EPS Permissive Auxiliary Relay GN0 CB-F-1B-A DAH-GN0-RD Damper Position Auxiliary Relay GN0 CB-F-1B-A DAH-E1T/6-52 120 V AC Circuit

Breaker E1T CB-F-1B-A DAH-ZL-5530-4 Damper Position Indicating Lights B04 CB-F-1B-A DAH-E3F/7-52 120 V AC Circuit Breaker E3F CB-F-1B-A E3F/7a E3F/7b EDE-MCC-615 EDE-PP-E3F DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A J1F-T3Q (Non-CASP) E3F-J1F DAH-TE-5530-1 Temperature Element T3Q DG-F-2B-A DAH-TT-5530-1 Temperature Transmitter J1F DG-F-2B-A DAH-CP-296 DG-B Room Air Handling Fans and Damper Control Panel J1F DG-F-2B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 11 Table RSS 3.1.3.11-5 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 DAH-FN-26A DG-1A Room Return Air Fan DAH-20624 A 310525 DG-F-2A-A X X X - N39 DAH-B03-52 460 V AC Circuit Breaker B03 CB-F-1A-A EDE-MCC-521 EDE-PP-11E DAH-FN-26B DAH-B03-42 Motor Starter B03 CB-F-1A-A 310928 B03a B03c B03d DAH-B03-42X Motor Starter Auxiliary Relays B03 CB-F-1A-A B03-N39/1 B03-J1E G29-J1E B03-GN9 DAH-B03-49 Overload Relays B03 CB-F-1A-A DAH-B03-FU Fuse B03 CB-F-1A-A DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DG-G29-HSR DG-1A High Speed Relay G29 DG-F-2A-A DAH-CS-6058 Control Switch with Indicating Lights B03 CB-F-1A-A DAH-ED1-R2 Auxiliary Relay ED1 CB-F-1A-A DAH-ED1-R1 Control Circuit Power Monitor Auxiliary

Relay ED1 CB-F-1A-A DAH-GN9-RS EPS Permissive Auxiliary Relay GN9 CB-F-1A-A DAH-GN9-RD Damper Position Auxiliary Relay GN9 CB-F-1A-A DAH-E3E/7-52 120 V AC Circuit Breaker E3E CB-F-1A-A E3E/7a E3E/7b EDE-MCC-515 EDE-PP-E3E DAH-TB-5529-1 Temperature Bistable J1E DG-F-2A-A J1E-T3P (Non CASP) E3E-J1E DAH-J1E-RTB Temperature Bistable Auxiliary Relay J1E DG-F-2A-A DAH-TE-5529-1 Temperature Element T3P DG-F-2A-A DAH-TT-5529-1 Temperature Transmitter J1E DG-F-2A-A DAH-CP-295 DG-A Room Air Handling Fans and Damper Control Panel J1E DG-F-2A-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 11 Table RSS 3.1.3.11-6 FUNCTION: DIESEL GENERATOR BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 DAH-FN-26B DG-1B Room Return Air Fan DAH-20624 B 310525 DG-F-2B-A X X X - N40 DAH-B04-52 460 V AC Circuit Breaker B04 CB-F-1B-A B04a B04c B04d EDE-MCC-621 EDE-PP-11F DAH-FN-26A DAH-B04-42 Motor Starter B04 CB-F-1B-A DAH-B04-42X Motor Starter Auxiliary Relays B04 CB-F-1B-A B04-N40/1 B04-J1F G30-J1F B04-GN DAH-B04-49 Overload Relays B04 CB-F-1B-A DAH-B04-FU Fuse B04 CB-F-1B-A DAH-J1F-RTB Temperature Bistable Auxiliary Relay J1F DG-F-2B-A DG-G30-HSR DG-1B High Speed Relay G30 DG-F-2B-A DAH-CS-6059 Control Switch with Indicating Lights B04 CB-F-1B-A DAH-EE3-R2 Auxiliary Relay EE3 CB-F-1B-A DAH-EE3-R1 Control Circuit Power Monitor Auxiliary

Relay EE3 CB-F-1B-A DAH-GN0-RS EPS Permissive Auxiliary Relay GN0 CB-F-1B-A DAH-GN0-RD Damper Position

Auxiliary Relay GN0 CB-F-1B-A DAH-E3F/7-52 120 V AC Circuit

Breaker E3F CB-F-1B-A E3F/7a E3F/7b EDE-MCC-615 EDE-PP-E3F DAH-TB-5530-1 Temperature Bistable J1F DG-F-2B-A J1F-T3Q (Non CASP) E3F-J1F DAH-J1F-RTB Temperature Bistable

Auxiliary Relay J1F DG-F-2B-A DAH-TE-5530-1 Temperature Element T3Q DG-F-2B-A DAH-TT-5530-1 Temperature

Transmitter J1F DG-F-2B-A DAH-CP-296 DG-B Room Air

Handling Fans and

Damper Control Panel J1F DG-F-2B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.12-1 FUNCTION: CONTAINMENT ENCLOSURE AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EAH-FN-5A MAH-20495 A 310766 CE-F-1-Z X X X - M80 EAH-AF5-52 480 V ac Circuit Breaker AF5 CB-F-1A-A EAH-FN-5B Containment

Enclosure Cooler

AC-2A Fan EAH-AF5-G, R Indicating Lights AF5 CB-F-1A-A EAH-CS-5767-2 Control Switch with Indication G2H CB-F-1A-A AF5-G2H AF5-G2H/1 AF5/M80 AF5-YC3 L41-YC3 310932 AF5a AF5e AF5b AF5g AF5f EAH-FN-31A EDE-US-52 Primary Component Cooling Water EAH-SS-5767 Selector Switch G2H CB-F-1A-A EAH-ZL-5767-2 Outlet Damper Position Lights G2H CB-F-1A-A EAH-ZS-DP-3A Damper Position Switch L41 CE-F-1-Z EAH-AF5-AM Ammeter AF5 CB-F-1A-A EAH-AF5-CT Current Transformer (200/5) AF5 CB-F-1A-A EDE-AC3-94-3 Bus Undervoltage Relay AC3 CB-F-1A-A EAH-AF5-52H-1 Truck-Operated Contact AF5 CB-F-1A-A EDE-TBX-YC3 Terminal Box YC3 CE-F-1-Z EAH-AF5-FU Fuses AF5 CB-F-1A-A 2 EAH-FN-5B MAH-20495 B 310766 CE-F-1-Z X X X - M81 EAH-AF9-52 480 V ac Circuit Breaker AF9 CB-F-1B-A EAH-FN-5A Containment

Enclosure Cooler

AC-2B Fan EAH-AF9-G, R Indicating Lights AF9 CB-F-1B-A EAH-CS-5768-2 Control Switch with Indication G2K CB-F-1B-A AF9-G2K AF9-G2K/1 AF9-G2K/2 AF9/M81 AF9-YB3 L42-YB3 AF9a AF9e AF9b AF9g AF9f EAH-FN-31B EDE-US-62 Primary Component Cooling Water EAH-SS-5768 Selector Switch G2K CB-F-1B-A EAH-ZL-5768-2 Outlet Damper Position Lights G2K CB-F-1B-A EAH-ZS-DP-3B Damper Position Switch L42 CE-F-1-Z EAH-AF9-AM Ammeter AF9 CB-F-1B-A EAH-AF9-CT Current Transformer (200/5) AF9 CB-F-1B-A EDE-AE3-94-3 Bus Undervoltage Relay AE3 CB-F-1B-A EAH-AF9-52H-1 Truck-Operated Contact AF9 CB-F-1B-A EDE-TBX-YB3 Terminal Box YB3 CE-F-1-Z EAH-AF9-FU Fuses AF9 CB-F-1B-A EAH-AE3-R1 Auxiliary Relay AE3CB-F-1B-A

.Notes   1. Equipment is mechanical with no electrical requirements. 
2. Air and electrical power are not required for support as damper fails closed.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.12-2 FUNCTION: CONTAINMENT ENCLOSURE AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 EAH-FN-31A MAH-20495 A 310765 CE-F-1-Z - X X - ND5 EAH-BB2-52 460 V ac Circuit Breaker BB2 CB-F-1A-A BB2-ND5 BB2-VQ2 310932 BB2a BB2c EDE-MCC-512 EAH-FN-31B Containment

Enclosure Return

Fan "A" EAH-BB2-FU Fuse BB2 CB-F-1A-A EAH-CS-5769-2 Control Switch BB2 CB-F-1A-A EAH-BB2-G, R Indicating Lights BB2 CB-F-1A-A EAH-SS-5769 Selector Switch BB2 CB-F-1A-A EAH-BB2-42 Motor Starter BB2 CB-F-1A-A EAH-BB2-42X Motor Starter Auxiliary Relay BB2 CB-F-1A-A EAH-BB2-49 Overload Relays BB2 CB-F-1A-A EAH-ZS-DP-25A Damper Position Switch VQ2 CE-F-1-Z 4 EAH-FN-31B MAH-20495 B 310765 CE-F-1-Z - X X - NJ7 EAH-BC1-52 460 V ac Circuit Breaker BC1 CB-F-1B-A BC1-NJ7 BC1-VQ3 310932 BC1a BC1c EDE-MCC-612 EAH-FN-31A Containment

Enclosure Return

Fan "B" EAH-BC1-FU Fuse BC1 CB-F-1B-A EAH-CS-5770-2 Control Switch BC1 CB-F-1B-A EAH-BC1-G, R Indicating Lights BC1 CB-F-1B-A EAH-SS-5770 Selector Switch BC1 CB-F-1B-A EAH-BC1-42 Motor Starter BC1 CB-F-1B-A EAH-BC1-42X Motor Starter Auxiliary Relay BC1 CB-F-1B-A EAH-BC1-49 Overload Relays BC1 CB-F-1B-A EAH-ZS-DP-25B Damper Position Switch VQ3CE-F-1-Z 5 EAH-DP-3A Containment Encl. Cooler AC-2A

Damper MAH-20495 A 310766 CE-F-1-Z X X - - L41 - - - - - - -

- EAH-DP-3B Note 1 6 EAH-DP-3B Containment Encl.

Cooler AC-2B

Damper MAH-20495 B 310766 CE-F-1-Z X X - - L42 - - - - - - -

- EAH-DP-3A Note 1 7 EAH-FN-174A MAH-20503 A 310586 MS-F-4A-Z X X X - M4T EAH-B8C-52 460 V ac Circuit Breaker B8C CB-F-1A-A B8C-M4T B8C-S5G B8Ca B8Cc EAH-FN-174B MS & FWPC 

Analyzer Room

Supply Fan EAH-B8C-FU Fuse B8C CB-F-1A-A CBA-FN-19

CBA-FN-20 EDE-MCC-515 EAH-CS-5136 Control Switch with Indication B8C CB-F-1A-A EAH-B8C-42 Motor Starter B8C CB-F-1A-A EAH-B8C-49 Overload Relays B8C CB-F-1A-A EAH-TSH-5136 Temperature Switch S5GMS-F-4A-Z

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.12-3 FUNCTION: CONTAINMENT ENCLOSURE AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 8 EAH-FN-174B MAH-20503 B 310586 MS-F-4A-Z X X X - M4U EAH-B8E-52 460 V ac Circuit Breaker B8E CB-F-1B-A B8E-M4U B8E-S5H 310932 B8Ea B8Ec EAH-FN-174A MS & FWPC

Analyzer Room

Supply Fan EAH-B8E-FU Fuse B8E CB-F-1B-A CBA-FN-32

CBA-FN-33 EDE-MCC-615 EAH-CS-5763 Control Switch with Indication B8E CB-F-1B-A EAH-B8E-42 Motor Starter B8E CB-F-1B-A EAH-B8E-49 Overload Relays B8E CB-F-1B-A EAH-TSH-5736 Temp. Switch S5H MS-F-4A-Z 9 PAH-DP-35A PAH-DP-36A CE Outboard

Isolation Dampers MAH-20495 A A 310766 310765 PAB-F-2A-Z PAB-F-2C-Z X X X X X X X X VN8 VN0 PAH-CS-5370 Control Switch F36 CB-F-3A-A F36-VN8 F36-VN0 310930 E42/8a E42/8c E42/8d Note 2 PAH-ZS-DP-35A Position Switch VN8 PAB-F-2A-Z PAH-ZS-DP-36A Position Switch VN0 PAB-F-2C-Z PAH-FY-DP-35A Solenoid Valve VN8 PAB-F-2A-Z PAH-FY-DP-36A Solenoid Valve VN0 PAB-F-2C-Z 10 PAH-DP-35B PAH-DP-36B CE Inboard

Isolation Dampers MAH-20495 B B 310766 310765 CE-F-1-Z CE-F-1-Z X X X X X X X X VN9 VP1 PAH-CS-5371 Control Switch F37 CB-F-3A-A F37-VP1 F37-VN9 310930 E50/8a E50/8c Note 2 PAH-ZS-DP-35B Position Switch VN9 CE-F-1-Z PAH-ZS-DP-36B Position Switch VP1 CE-F-1-Z PAH-FY-DP-35B Solenoid Valve VN9 CE-F-1-Z PAH-FY-DP-36B Solenoid Valve VP1 CE-F-1-Z

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.13-1 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EPA-FN-47A MAH-20503 A 310708 EFP-F-1-A X X X - NL8 EPA-BB7-52 460 V ac Circuit Breaker BB7 CB-F-1A-A EPA-FN-47B EPA-BB7-FU Fuse BB7 CB-F-1A-A BB7-NL8 BB7-UH3 BB7-VV6 310922 BB7a BB7c BB7d CBA-FN-19

CBA-FN-20 EDE-MCC-512 Emergency

Feedwater

Pumphouse Intake

Fan EPA-CS-5430-2 Control Switch BB7 CB-F-1A-A EPA-ZL-5430-4 Fan Indicating Lights BB7 CB-F-1A-A EPA-SS-5430 Selector Switch BB7 CB-F-1A-A EPA-EC8-RBB7 Damper Auxiliary Relay EC8 CB-F-1A-A EPA-ZS-DP-373 Damper Position Switch UH3 EFP-F-1-A EPA-ZS-DP-371 Damper Position Switch VV6 EFP-F-1-A EPA-ZL-5430-5 Damper DP-373 Position Lights BB7 CB-F-1A-A EPA-ZL-5430-6 Damper DP-371 Position Lights BB7 CB-F-1A-A EPA-BB7-42 Motor Starter BB7 CB-F-1A-A EPA-BB7-49 Overload Relays BB7 CB-F-1A-A 2 EPA-DP-373 MAH-20503 A 310708 EFP-F-1-A X X X X UH3 EPA-BB7-FU Fuse BB7 CB-F-1A-A BB7-UH3 EPA-DP-374 Note 1 EPA-EC8-RBB7 Auxiliary Relay EC8 CB-F-1A-A BB7a BB7c BB7d Emergency

Feedwater

Pumphouse Exhaust

Damper EPA-DP-373-20 Pilot Solenoid UH3 EFP-F-1-A CBA-FN-19

CBA-FN-20 EDE-MCC-512 3 EPA-FN-47B MAH-20503 B 310708 EFP-F-1-A X X X - NL9 EPA-BC7-52 460 V ac Circuit Breaker BC7 CB-F-1B-A BC7a BC7c BC7d EPA-FN-47A EPA-BC7-FU Fuses BC7 CB-F-1B-A BC7-NL9 BC7-UH4 BC7-VV7 CBA-FN-32

CBA-FN-33 EDE-MCC-612 Emergency

Feedwater

Pumphouse Intake

Fan EPA-ZL-5431-4 Fan Indicating Lights BC7 CB-F-1B-A EPA-SS-5431 Selector Switch BC7 CB-F-1B-A EPA-EDO-RBC7 Damper Auxiliary Relay EDO CB-F-1B-A EPA-ZS-DP-374 Damper Position Switch UH4 EFP-F-1-A EPA-ZS-DP-372 Damper Position Switch VV7 EFP-F-1-A EPA-BC7-42 Motor Starter BC7 CB-F-1B-A EPA-BC7-49 Overload Relays BC7 CB-F-1B-A EPA-ZL-5431-5 Damper DP-374 Position Lights BC7 CB-F-1B-A EPA-ZL-5431-6 Damper DP-372 Position Lights BC7 CB-F-1B-A EPA-CS-5431-2 Control Switch BC7 CB-F-1B-A EPA-EDO-R1 Auxiliary Relay EDO CB-F-1B-A

.Notes  1. Air is not required for support as damper fails open. 

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.13-2 FUNCTION: EMERGENCY FEEDWATER PUMPHOUSE AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 EPA-DP-374 MAH-20503 B 310708 EFP-F-1-A X X X X UH4 EPA-BC7-FU Fuses BC7 CB-F-1B-A BC7-UH4 EPA-DP-373 Note 1 EPA-EDO-RBC7 Auxiliary Relay EDO CB-F-1B-A 310922 BC7a BC7c BC7d Emergency

Feedwater

Pumphouse Exhaust

Damper EPA-DP-374-20 Pilot Solenoid UH4 EFP-F-1-A CBA-FN-32

CBA-FN-33 EDE-MCC-612 EPA-EDO-R1 Auxiliary Relay EDO CB-F-1B-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.14 -1 FUNCTION: PRIMARY AUXILIARY BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 PAH-FN-42A PAB Auxiliary Supply Fan "A" MAH-20495 A 310765 PAB-F-2C-Z X X X - M61 PAH-BF6-52 460 V ac Circuit Breaker BF6 CB-F-1A-A BF6-M61 BF6-ED1 BF6-UG5 BF6-UG7 UG5-UG7 BF6-UG5/1 310930 BF6a BF6c BF6d CBA-FN-19 CBA-FN-20 EDE-MCC-512 PAH-FN-42B PAH-CS-5391-2 Control Switch BF6 CB-F-1A-A PAH-ZL-5391-4 Fan Indicating Lights BF6 CB-F-1A-A PAH-SS-5391 Selector Switch BF6 CB-F-1A-A PAH-ED1-R1 Damper Auxiliary Relay ED1 CB-F-1A-A PAH-ZS-DP-43A-1A PAH-ZS-DP-43A-1B PAH-ZS-DP-43A-2A Damper Position Switch UG5 PAB-F-1K-Z PAH-ZS-DP-357 Damper Position Switch UG7 PAB-F-2C-Z PAH-BF6-42 Motor Starter BF6 CB-F-1A-A PAH-BF6-49 Overload Relays BF6 CB-F-1A-A PAH-DP-43A-20 Pilot Solenoid UG5 PAB-F-1K-Z PAH-DP-357-20 Pilot Solenoid UG7 PAB-F-2C-Z PAH-ZL-5391-5 Damper DP -43A Position Lights BF6 CB-F-1A-A PAH-ZL-5391-6 Damper DP -357 Position Lights BF6 CB-F-1A-A PAH-BF6-FU Fuse BF6 CB-F-1A-A 2 PAH-DP-43A PAB Auxiliary Fan Supply Damper MAH-20495 A 310765 PAB-F-1K-Z X X X X UG5 PAH-ED1-R1 Damper Auxiliary Relay ED1 CB-F-1A-A BF6-ED1 BF6-UG5 BF6-UG7 UG5-UG7 BF6-UG5/1 310930 BF6a BF6c BF6d CBA-FN-19 CBA-FN-20 PAH-DP-43B Note 1 PAH-DP-43A-20 Pilot Solenoid UG5 PAB-F-1K-Z 3 PAH-DP-357 PAB Auxiliary Fan Exhaust Damper MAH-20495 A 310766 PAB-F-2C-Z X X X X UG7 PAH-ED1-R1 Damper Auxiliary Relay ED1 CB-F-1A-A BF6-ED1 BF6-UG5 310930 BF6a BF6c CBA-FN-19 CBA-FN-20 PAH-DP-358 Note 1 PAH-DP-357-20 Pilot Solenoid UG7 PAB-F-2C-Z BF6-UG7 UG5-UG7

.Notes  1. Air and electrical power are not required for support as damper fails open.
2. See Table RSS 3.1.3.12 for operation of dampers PAH

-DP-35A, -35B, -36A & -36B. SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.14 -2 FUNCTION: PRIMARY AUXILIARY BUILDING AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 PAH-FN-42B PAB Auxiliary Supply Fan "B" MAH-20495 B 310765 PAB-F-2C-Z X X X - M62 PAH-BF7-52 460 V ac Circuit Breaker BF7 CB-F-1B-A BF7-E3D/1 BF7-M62 BF7-UG6 BF7-UG8 UG6-UG8 310930 BF7a BF7c CBA-FN-32 CBA-FN-33 EDE-MCC-612 PAH-FN-42A PAH-CS-5393-2 Control Switch BF7 CB-F-1B-A PAH-ZL-5393-4 Fan Indicating Lights BF7 CB-F-1B-A PAH-SS-5393 Selector Switch BF7 CB-F-1B-A PAH-EDO-R1 Damper Auxiliary Relay EDO CB-F-1B-A PAH-ZS-DP-43B-1A PAH-ZS-DP-43B-1B PAH-ZS-DP-43B-2A Damper Position Switch UG6 PAB-F-1K-Z PAH-ZS-DP-358 Damper Position Switch UG8 PAB-F-2C-Z PAH-ZL-5393-5 Damper DP -43B Position Lights BF7 CB-F-1B-A PAH-DP-43B-20 Pilot Solenoid UG6 PAB-F-1K-Z PAH-DP-358-20 Pilot Solenoid UG8 PAB-F-2C-Z PAH-BF7-42 Motor Starter BF7 CB-F-1B-A PAH-BF7-49 Overload Relays BF7 CB-F-1B-A PAH-BF7-FU Fuses BF7 CB-F-1B-A PAH-ZL-5393-6 Damper DP -358 Position Lights BF7 CB-F-1B-A PAH-E3D-R2 Auxiliary Relay E3D CB-F-1B-A 5 PAH-DP-43B PAB Auxiliary Fan Supply Damper MAH-20495 B 310765 PAB-F-1K-Z X X X X UG6 PAH-EDO-R1 Damper Auxiliary Relay EDO CB-F-1B-A BF7-UG6 BF7-UG8 UG6-UG8 310930 BF7a BF7c CBA-FN-32 CBA-FN-33 PAH-DP-43A Note 1 PAH-DP-43B-20 Pilot Solenoid UG6 PAB-F-1K-Z 6 PAH-DP-358 PAB Auxiliary Fan Exhaust Damper MAH-20495 B 310766 PAB-F-2C-Z X X X X UG8 PAH-EDO-R1 Damper Auxiliary Relay EDO CB-F-1B-A BF7-UG6 BF7-UG8 UG6-UG8 310930 BF7a BF7c CBA-FN-32 CBA-FN-33 PAH-DP-357 Note 1 PAH-DP-358-20 Pilot Solenoid UG8 PAB-F-2C-Z 7 PAH-DP-35A - - - - - - - - - - - - - - - - - - Note 2 8 PAH-DP-35B - - - - - - - - - - - - - - - - - - Note 2 9 PAH-DP-36A - - - - - - - - - - - - - - - - - - Note 2 10 PAH-DP-36B - - - - - - - - - - - - - - - - - - Note 2 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 7 Table RSS 3.1.3.15-1 FUNCTION: SERVICE WATER AIR HANDLING PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 SWA-FN-40A SWA-20372 A 301139 SW-F-ID-A X X X - NJO SWA-CR5-52 460 V ac Circuit Breaker CR5 SW-F-1B-A 301115 CR5a CR5c EDE-MCC-514 SWA-FN-40B SWA-CR5-42 Motor Starter CR5 SW-F-1B-A CR5-NJO CR5-G2H/1 CR5-G2H Service Water

Pumphouse Train

"A" Switchgear

Room Supply Fan SWA-CR5-49 Overload Relays CR5 SW-F-1B-A SWA-CS-5614-2 Control Switch with Indication G2H CB-F-1A-A SWA-SS-5614 Selector Switch G2H CB-F-1A-A SWA-CR5-FU Fuse CR5 SW-F-1B-A 2 SWA-FN-40B SWA-20372 B 301139 SW-F-ID-A X X X - NK1 SWA-CRO-52 460 V ac Circuit Breaker CRO SW-F-1C-A CROa CROc EDE-MCC-614 SWA-FN-40A SWA-CRO-42 Motor Starter CRO SW-F-1C-A Service Water

Pumphouse Train

"B" Switchgear

Room Supply Fan SWA-CRO-49 Overload Relays CRO SW-F-1C-A CRO-NK1 CRO-G2K/1 CRO-G2K F37-G2K/2 CRO-G2K/2 SWA-CS-5615-2 Control Switch with Indication G2K CB-F-1B-A SWA-SS-5615 Selector Switch G2K CB-F-1B-A SWA-CRO-FU Fuses CRO SW-F-1C-A

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -1 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 EDE-SWG-5 4160 V Bus E5 UAT Incoming Line SWGR 310007 A 310442 CB-F-1A-A X X X - A51 EDE-A51-52 4160 V Circuit Breaker A51 CB-F-1A-A A51-G07 A51-G07/2 A51-G10 A51-HR9 GA6-GB0/4 A51-G07/1 A51-G07/3 A51-GB4 GA0-GB3/4 GC4-GC6/4 A51-G5X A51-G5X/1 A55-A5A A54-A5A/1 310102 A51a A51h A51b A51c A51d A51e CBA-FN-19 CBA-FN-20 ED-X-2A EDE-PP-111A DAH-FN-25A DAH-FN-26A EDE-SWG-6 UAT EDE-CS-9709-2 Control Switch A51 CB-F-1A-A EDE-CS-9709-3 Control Switch with Indication G07 DG-F-2A-A EDE-A51-G,R,W Indicating Lights A51 CB-F-1A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-A51-52H Truck Operated Contact A51 CB-F-1A-A EDE-A51-FU Fuses A51 CB-F-1A-A EDE-A51-CT1 Current Transformer (2000/5) A51 CB-F-1A-A EDE-A51-TD-1 CT Test Device A51 CB-F-1A-A EDE-A51-AM Ammeter A51 CB-F-1A-A EDE-A51-AS Ammeter Switch A51 CB-F-1A-A EDE-A51-ATR Current Transducer A51 CB-F-1A-A EDE-A51-CT2 Current Transformers (4000/5) A51 CB-F-1A-A EDE-A67-PT Potential Transformer (4200-120 V) A67 CB-F-1A-A EDE-A51-TD-3 PT Test Device A51 CB-F-1A-A EDE-A51-VM Voltmeter A51 CB-F-1A-A EDE-A51-86 Lockout Relay A51 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-A52-52S Mechanically Operated Contact A52 CB-F-1A-A DG-G10-25Y1 Auxiliary Synchronizing Check Relay G10 DG-F-2A-A EDE-A53-25U Synchronizing Check Relay A53 CB-F-1A-A EDE-SS-9709-1 Selector Switch G5X DG-F-2A-A EDE-CS-9707-3 Control Switch G07 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A52-86 Lockout Relay A52 CB-F-1A-A EDE-A69-86B Lockout Relay A69 CB-F-1A-A ED-86SB/2/1X -1 Lockout Relay GA0 TB-F-1C-2 ED-86-2/2/B3 Lockout Relay GA6 TB-F-1C-Z ED-86UB/2/1X -2A Lockout Relay GA8 TB-F-1C-Z ED-86UB/2/1X -2B Lockout Relay GA8 TB-F-1C-Z ED-86BF/2/2/52/TG1 Lockout Relay GA9 TB-F-1C-Z ED-86GT/2/TG1 Lockout Relay GA9 TB-F-1C-Z ED-86-1/2/B3 Lockout Relay GB0 TB-F-1C-Z ED-86BF-2/2H Lockout Relay GB3 TB-F-1C-Z ED-86BF-2/2K Lockout Relay GB4 TB-F-1C-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -2 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-5 (Continued) ED-86UP/2/1X -2A Lockout Relay GC2 TB-F-1C-Z ED-86UP/2/1X -2B Lockout Relay GC2 TB-F-1C-Z ED-86BF-1/2/52/TG1 Lockout Relay GC3 TB-F-1C-Z ED-86SP/2/1X -1 Lockout Relay GC4 TB-F-1C-Z ED-86BF-1/2H Lockout Relay CG6 TB-F-1C-Z ED-86BF-1/2E Lockout Relay CG7 TB-F-1C-Z DG-HR9-RM0 EPS Auxiliary Relay HR9 CB-F-1A-A EDE-A51-3 Interposing Relay for SWYD Lockout Relays A51 CB-F-1A-A EDE-A51-TD-2 Lockout Relay Test Device (A51 -86) A51 CB-F-1A-A EDE-A51-TD-4 Interposing Relay Test Device (A51/3) A51 CB-F-1A-A ED-GA0-TD-2 Lockout Relay Test Device (86SB/2/1X -1) GA0 TB-F-1C-Z ED-GA6-TD-2 Lockout Relay Test Device (86 -2/2/B3) GA6 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2A) GA8 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2B) GA8 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86BF-2/2/52/TG1) GA9 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86GT/2/TG1) GA9 TB-F-1C-Z ED-GB0-TD-2 Lockout Relay Test Device (86 -1/2/B3) GB0 TB-F-1C-Z ED-GB3-TD-2 Lockout Relay Test Device (86BF -2/2H) GB3 TB-F-1C-Z ED-GB4-TD-2 Lockout Relay Test Device (86BF -2/2E) GB4 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2A) GC2 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2B) GC2 TB-F-1C-Z ED-GC3-TD-2 Lockout Relay Test Device (86BF-1/2/52/TG1) GC3 TB-F-1C-Z ED-GC4-TD-2 Lockout Relay Test Device (86SP/2/1X -1) GC4 TB-F-1C-Z ED-GC6-TD-2 Lockout Relay Test Device (86BF -1/2H) GC6 TB-F-1C-Z ED-GC7-TD-2 Lockout Relay Test Device (86BF -1/2E) GC7 TB-F-1C-Z EDE-A51-51 Time Overcurrent Relays øA, øB, øC A51 CB-F-1A-A EDE-A51-51GS Ground Sensor Relay A51 CB-F-1A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -3 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 EDE-SWG-5 Grounding Transformer 310007 A 310442 CB-F-1A-A X X X - A67 EDE-A67-XFMR 3-1ø 15 kVA Transformers A67 CB-F-1A-A 310102 A67a CBA-FN-19 CBA-FN-20 EDE-SWG-5 EDE-SWG-6 GRD XFMR EDE-A67-FU 3-10A Fuses A67 CB-F-1A-A EDE-A67-52 120 V AC Circuit Breaker A67 CB-F-1A-A EDE-A67-RES Grounding Resistor A67 CB-F-1A-A EDE-A67-64 Grounding Rela y A67 CB-F-1A-A EDE-A67-TD-3 VM Test Device A67 CB-F-1A-A EDE-A67-VM (3) Ground Voltmeters A67 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -4 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 3 EDE-SWG-5 4160 V Bus E5 RAT Incoming Line SWGR 310007 A 310442 CB-F-1A-A X X X - A52 EDE-A52-52 4160 V Circuit Breaker A52 CB-F-1A-A A52-G07/1 A52-G07/3 A52-G10 A52-HR2 GA7-GB7/4 GE6-GE7/4 A52-G5X A52-G5X/1 A52-G07/2 A52-G07/4 A52-GB7 AG2-HR9 GC1-GC0/4 A54-A5A/2 310102 A52a A52J A52b A52c A52d A52e CBA-FN-19 CBA-FN-20 ED-X-3A EDE-PP-111A DAH-FN-25A DAH-FN-26A EDE-SWG-6 RAT EDE-CS-9707-2 Control Switch A52 CB-F-1A-A EDE-CS-9707-3 Control Switch with Indication G07 DG-F-2A-A EDE-A52-G,R,W Indicating Lights A52 CB-F-1A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-A52-52H Truck Operated Contact A52 CB-F-1A-A EDE-A52-FU Fuses A52 CB-F-1A-A EDE-A52-27/59 Under/Over Voltage Relay A52 CB-F-1A-A EDE-A52-27/59X1,X2 Under/Over Voltage Auxiliary Relay A52 CB-F-1A-A EDE-A52-52Z Time Delay Relay A52 CB-F-1A-A EDE-SS-9707-1 Selector Switch G5X DG-F-2A-A EDE-CS-9709-3 Control Switch G07 DG-F-2A-A EDE-A52-CT-1 Current Transformer (2000/5) A52 CB-F-1A-A EDE-A52-TD-1 CT Test Device A52 CB-F-1A-A EDE-A52-AM Ammeter A52 CB-F-1A-A EDE-A52-AS Ammeter Switch A52 CB-F-1A-A EDE-A52-ATR Current Transducer A52 CB-F-1A-A EDE-A52-CT-2 Current Transformer (4000/5) A52 CB-F-1A-A EDE-A53-PT Potential Transformer A53 CB-F-1A-A EDE-A52-TD-3 PT Test Device A52 CB-F-1A-A EE-A52-VM Voltmeter A52 CB-F-1A-A EDE-A52-52S Mechanically Operated Contact A52 CB-F-1A-A EDE-A69-86B Lockout Relay A69 CB-F-1A-A EDE-A52-86 Lockout Relay A52 CB-F-1A-A EDE-A51-86 Lockout Relay A51 CB-F-1A-A DG-HR2-RM0 EPS Auxiliary Relay HR2 CB-F-1A-A DG-HR9-RM0 EPS Auxiliary Relay HR9 CB-F-1A-A EDE-A51-52S Mechanically Operated Contact A51 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A DG-G10-25Y1 Auxiliary Synchronizing Check Relay G10 DG-F-2A-A EDE-A53-25RX Auxiliary Synchronizing Check Relay A53 CB-F-1A-A EDE-A53-25R Synchronizing Check Relay A53 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -5 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-5 (Continued) EDE-A52-62 & 62X Time Delay Relay A52 CB-F-1A-A EDE-A51-3 Interposing Relay for SWD Lockout Relays A51 CB-F-1A-A EDE-A52-TD-2 Lockout Relay Test Device (A52 -86) A52 CB-F-1A-A EDE-A52-TD-4 Interposing Relay Test Device (A52 -3) A52 CB-F-1A-A ED-86RB/2/1X -3A Lockout Relay GA7 TB-F-1C-Z ED-86-2/2/B2 Lockout Relay GB7 TB-F-1C-Z ED-86-1/2/B2 Lockout Relay GC0 TB-F-1C-Z ED-86RP/2/1X -3A Lockout Relay GC1 TB-F-1C-Z ED-86RP/2/1X -3B Lockout Relay GE6 TB-F-1C-Z ED-86RB/2/1X -3B Lockout Relay GE7 TB-F-1C-Z ED-GA7-TD-2 Lockout Relay Test Device (86RB/2/1X -3A) GA7 TB-F-1C-Z ED-GB7-TD-2 Lockout Relay Test Device (86 -1/2/B2) GB7 TB-F-1C-Z ED-GC0-TD-2 Lockout Relay Test Device (86 -1/2/B2) GC0 TB-F-1C-Z ED-GC1-TD-2 Lockout Relay Test Device (86RP/2/1X -3A) GC1 TB-F-1C-Z ED-GE6-TD-2 Lockout Relay Test Device (86RB/2/1X -3B) GE6 TB-F-1C-Z ED-G37-TD-2 Lockout Relay Test Device (86RP/2/1X -3B) GE7 TB-F-1C-Z EDE-A52-51 Time Overcurrent Relays øA, øB, øC A52 CB-F-1A-A EDE-A52-51GS Ground Sensor Relay A52 CB-F-1A-A EDE-A52-27RB-1 Residual Undervoltage Relay A52 CB-F-1A-A EDE-A52-27RB-2 Residual Undervoltage Relay A52 CB-F-1A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -6 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 4 EDE-SWG-5 4160 V Bus E5 PT Compartment 310007 A 310442 CB-F-1A-A X X X - A53 EDE-A53-PT Potential Transformers A53 CB-F-1A-A A53-AC2 A53-HR2 AF2-ED4 A53-G07 AC2-AF2 A54-A5A/4 A54-A5A/5 A55-A5A/1 A55-A5A/2 310102 A53a A53d A53e A53h CBA-FN-19 CBA-FN-20 EDE-SWG-5 EDE-PP-111A DAH-FN-25A DAH-FN-26A EDE-SWG-6 PT EDE-A53-VM Voltmeter A53 CB-F-1A-A EDE-A53-VS Voltmeter Switch A53 CB-F-1A-A EDE-A53-TD-3 PT Test Device A53 CB-F-1A-A EDE-A53-VTR-1 Voltage Transducer A53 CB-F-1A-A EDE-A53-VTR-2 Voltage Transducer A53 CB-F-1A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A53-25U Synchronizing Check Relay A53 CB-F-1A-A EDE-A53-25R Synchronizing Check Relay A53 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-A53-27B-1 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-27B-2 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-TS-3 Undervoltage Relay Test Switch A53 CB-F-1A-A EDE-A53-27D-1 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-27-D-1-RES Resistor A53 CB-F-1A-A EDE-A53-27D-2 Instantaneous Undervoltage Relay A53 CB-F-1A-A EDE-A53-27D-2-RES Resistor A53 CB-F-1A-A EDE-A53-TS-1 Undervoltage Relays Test Switch A53 CB-F-1A-A EDE-A52-27RB-1,2 Residual Undervoltage Relay A52 CB-F-1A-A EDE-A53-62B Time Delay Relay A53 CB-F-1A-A EDE-A53-62B-RES Resistor A53 CB-F-1A-A EDE-A53-TS-4 Test Switch EDE -62B A53 CB-F-1A-A EDE-A53-62BX-1 Auxiliary Relay A53 CB-F-1A-A EDE-A53-62BX Auxiliary Latch Relay A53 CB-F-1A-A EDE-A51-52S Mechanically Operated Contact A51 CB-F-1A-A EDE-ED4-94-5 Undervoltage Tripping Relay ED4 CB-F-1A-A EDE-A52-27/59X1 Under/Over Voltage Auxiliary Relay A52 CB-F-1A-A EDE-AF3-94-4 Undervoltage Tripping Relay AF3 CB-F-1A-A DG-HR2-RM0 EPS Auxiliary Relay HR2 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -7 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-5 (Continued) EDE-A53-94-1A Undervoltage Tripping Relay A53 CB-F-1A-A EDE-A53-94-1B Undervoltage Tripping Relay A53 CB-F-1A-A EDE-A53-94-2 Undervoltage Tripping Relay A53 CB-F-1A-A EDE-AC3-94-3 Undervoltage Tripping Relay AC3 CB-F-1A-A EDE-A53-FU 125 V DC 10A Fuses (2) A53 CB-F-1A-A EDE-A53-62D Time Delay Relay A53 CB-F-1A-A EDE-A53-62D-RES Resistor A53 CB-F-1A-A EDE-A53-TS-2 Test Switch Relay 62D A53 CB-F-1A-A EDE-A53-62DX Auxiliary Relay A53 CB-F-1A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -8 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 5 EDE-SWG-5 4160 V Bus E5 DG-1A Incoming Line SWGR 310010 310007 A 310442 CB-F-1A-A X X X - A54 EDE-A54-52 4160 V Circuit Breaker A54 CB-F-1A-A A54-G06/2 A54-G06/4 A54-G07/1 A54-HN0 A54-G06/3 A54-G07 A54-G07/2 G06-G29/7 A54-A5A/3 310102 A54a A54k A54b A54c A54d A54e A54f CBA-FN-19 CBA-FN-20 DG-DG-1A DAH-FN-25A DAH-FN-26A EDE-PP-111A EDE-SWG-6 DG-1B EDE-CS-9700-2 Control Switch A54 CB-F-1A-A EDE-CS-9700-3 Control Switch with Indication G06 DG-F-2A-A EDE-A54-G,R,W Indicating Lights A54 CB-F-1A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A54-52H Truck Operated Contact A54 CB-F-1A-A EDE-A54-FU Fuses A54 CB-F-1A-A EDE-A54-CT Current Transformers (2000/5) A54 CB-F-1A-A EDE-A54-DCT Differential Current Transformers (2000/5 ) A54 CB-F-1A-A DG-HNO-DCT DG-1A Neut. Diff. Current Transformers (2000/5) HN0 DG-F-2A-A DG-G06-CT Auxiliary Current Transformers (5:10) G06 DG-F-2A-A EDE-A54-AM Ammeter A54 CB-F-1A-A EDE-A54-AS-1 Ammeter Switch A54 CB-F-1A-A EDE-A54-ATR-1 Current Transducer A54 CB-F-1A-A EDE-A54-ATR-2 Current Transducer A54 CB-F-1A-A EDE-AM-9700-2 Ammeter G06 DG-F-2A-A EDE-G06-AS Ammeter Switch G06 DG-F-2A-A DG-SM-9585 Governor Control (2301A) G06 DG-F-2A-A EDE-A69-PT DG-1A Inc. Line Pot. Transformer (2) 4200-120 V A69 CB-F-1A-A EDE-A69-VM Voltmeter A69 CB-F-1A-A EDE-A69-VS Voltmeter Switch A69 CB-F-1A-A EDE-A69-TD-3 PT Test Device A69 CB-F-1A-A EDE-A69-VTR-1 Voltage Transducer A69 CB-F-1A-A EDE-A69-VTR-2 Voltage Transducer A69 CB-F-1A-A EDE-A54-27DG Undervoltage Relay A54 CB-F-1A-A EDE-A69-FTR-1 Frequency Transducer A69 CB-F-1A-A EDE-A69-FTR-2 Frequency Transducer A69 CB-F-1A-A EDE-A69-W/WH-TR Watt/Watthour Transducer A69 CB-F-1A-A EDE-A69-W/TR Watt Transducer A69 CB-F-1A-A EDE-A69-VAR-TR Var Transducer A69 CB-F-1A-A EDE-A54-TS Test Start Switch A54 CB-F-1A-A EDE-A54-52Z Time Delay Relay A54 CB-F-1A-A EDE-A54-81-RES Resistor A54 CB-F-1A-A EDE-A54-86DP Primary Lockout Relay A54 CB-F-1A-A EDE-A54-W Indicating Light (A54-86DP) A54 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -9 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-5 (Continued) EDE-A69-86B Lockout Relay A69 CB-F-1A-A EDE-A69-86DB Back-Up Lockout Relay A69 CB-F-1A-A EDE-A69-W Indicating Light (A69-86B & A69 -86DB) A69 CB-F-1A-A EDE-A51-86 Lockout Relay A51 CB-F-1A-A EDE-A52-86 Lockout Relay A52 CB-F-1A-A EDE-A51-52S Mechanically Operated Contact A51 CB-F-1A-A EDE-A52-52S Mechanically Operated Contact A52 CB-F-1A-A EDE-A54-52S Mechanically Operated Contact A54 CB-F-1A-A EDE-A69-RLA LOCA Seal Relay A69 CB-F-1A-A DG-G10-25Y Auxiliary Sync Check Relay G10 DG-F-2A-A EDE-A69-RS Fast Closure Relay A69 CB-F-1A-A EDE-A54-81 Frequency Relay A54 CB-F-1A-A EDE-A54-87DP Primary Differential Relay A54 CB-F-1A-A EDE-A69-51B Time Overcurrent Relays, øA, øB, øC A69 CB-F-1A-A EDE-A54-81X Auxiliary Frequency Relay A54 CB-F-1A-A EDE-A69-60 Voltage Balance Relay A69 CB-F-1A-A EDE-A69-60AX Auxiliary Voltage Balance Relay A69 CB-F-1A-A EDE-A69-60BX Auxiliary Voltage Balance Relay A69 CB-F-1A-A EDE-A69-40 Loss of Field Relays øA, øB A69 CB-F-1A-A EDE-A54-40X Auxiliary Loss of Field Relay A54 CB-F-1A-A EDE-A69-32 Power Directional Relay A69 CB-F-1A-A EDE-A69-TD-1 Lockout Relay Test Device (86B) A69 CB-F-1A-A EDE-A69-TD-2 Lockout Relay Test Device (86DB) A69 CB-F-1A-A EDE-A54-TD-2 Lockout Relay Test Device (86DP) A54 CB-F-1A-A DG-G07-R43L5 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -10 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-5 (Continued) DG-G29-5A Shutdown Relay G29 DG-F-2A-A EDE-A69-51V Time Overcurrent Voltage Restraint Relays, øA, øB, øC A69 CB-F-1A-A EDE-A69-51GS Ground Sensor Relay A69 CB-F-1A-A EDE-A54-TD-1 Test Device A54 CB-F-1A-A EDE-A69-TD-3 Voltage Test Device A69 CB-F-1A-A EDE-A54-87DP Reactor Primary Differential Relay Reactor Assembly A54 CB-F-1A-A EDE-A54-81Y Time Delay Relay A54 CB-F-1A-A EDE-A5A-52S Mechanically Operated Contact A5A CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -11 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 6 DG-CP-75A Diesel Generator 1A Control Panel Cubicle 2 Synchronizing System 310010 A 310524 DG-F-2A-A X X X - G07 DG-G07-FU-17&18 125 V DC Fuses (6A) G07 DG-F-2A-A 310102 G07/2c G07/2g DAH-FN-25A DAH-FN-26A EDE-SWG-11A DG-CP-76A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-RAX Auxiliary Relay, Latch G07 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-CS-9700-3 Control Switch G06 DG-F-2A-A EDE-CS-9707-3 Control Switch G07 DG-F-2A-A EDE-CS-9709-3 Control Switch G07 DG-F-2A-A DG-G06-25DG Synchronizing Check Relay G06 DG-F-2A-A DG-G10-25Y Auxiliary Synchronizing Check Relay G10 DG-F-2A-A DG-G10-25Y1 Auxiliary Synchronizing Check Relay G10 DG-F-2A-A EDE-A67-PT UAT X-2A Inc. Line Potential Transforme r A67 CB-F-1A-A 7b 7f EDE-A53-PT RAT X-3A Inc. Line Potential Transformer A53 CB-F-1A-A EDE-A53-PT Bus E5 Potential Transformer A53 CB-F-1A-A EDE-A69-PT DG-1A Inc. Line Potential Transformer A69 CB-F-1A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-SS-9707 Selector Switch G07 DG-F-2A-A EDE-SS-9709 Selector Switch G07 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-RAX Auxiliary Relay Latch G07 DG-F-2A-A DG-G06-25DG Synchronizing Check Relay G06 DG-F-2A-A EDE-SYN-9701 Synchroscope G06 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -12 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-CP-75A (Continued) EDE-ZL-9701 Synchronizing Lights G06 DG-F-2A-A EDE-VM-9701-1 Synchronizing Voltmeter Incoming G06 DG-F-2A-A EDE-VM-9701-2 Synchronizing Voltmeter Running G06 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -13 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 7 EDE-SWG-5 4160 V Feed to 480 V Transformer EDE-X-5A for Substation Bus EDE-US-51 310007 A 310442 CB-F-1A-A X X X - A55 EDE-A55-52 4160 V Circuit Breaker A55 CB-F-1A-A A55-AB1 310102 A55a A55g A55b A55c A55d CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-SWG-5 EDE-SWG-6 EDE-X-5C EDE-US-61 EDE-A55-FU Fuses A55 CB-F-1A-A EDE-CS-9706 Control Switch A55 CB-F-1A-A EDE-A55-G,R,W Indicating Lights A55 CB-F-1A-A EDE-SS-9706 Selector Switch A55 CB-F-1A-A EDE-A55-52H Truck Operated Contact A55 CB-F-1A-A EDE-A55-86 Lockout Relay A55 CB-F-1A-A EDE-A55-TD2 Lockout Relay Test Device A55 CB-F-1A-A EDE-A55-50/51 Inst/Time Overcurrent Relays øA, øB, øC A55 CB-F-1A-A EDE-A55-CT Current Transformers (300/5) A55 CB-F-1A-A EDE-A55-AM Ammeter A55 CB-F-1A-A EDE-A55-AS Ammeter Switch A55 CB-F-1A-A EDE-A55-ATR Current Transducer A55 CB-F-1A-A EDE-A55-TD1 CT Test Device A55 CB-F-1A-A EDE-A55-51GS Ground Sensor Relay A55 CB-F-1A-A 8 EDE-SWG-5 4160 V Feed to 480 V Transformer EDE-X-5B for Substation Bus EDE-US-52 310007 A 310442 CB-F-1A-A X X X - A63 EDE-A63-52 4160 V Circuit Breaker A63 CB-F-1A-A A63-AC1 310102 A63a A63g A63b A63c A63d CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-SWG-5 EDE-SWG-6 EDE-X-5D EDE-US-62 EDE-A63-FU Fuses A63 CB-F-1A-A EDE-CS-9703 Control Switch A63 CB-F-1A-A EDE-A63-G,R,W Indicating Lights A63 CB-F-1A-A EDE-SS-9703 Selector Switch A63 CB-F-1A-A EDE-A63-52H Truck Operated Contact A63 CB-F-1A-A EDE-A63-86 Lockout Relay A63 CB-F-1A-A EDE-A63-TD2 Lockout Relay Test Device A63 CB-F-1A-A EDE-A63-50/51 Inst/Time Overcurrent Relays øA, øB, øC A63 CB-F-1A-A EDE-A63-CT Current Transformers (300/51) A63 CB-F-1A-A EDE-A63-AM Ammeter A63 CB-F-1A-A EDE-A63-AS Ammeter Switch A63 CB-F-1A-A EDE-A63-ATR Current Transducer A63 CB-F-1A-A EDE-A63-TD1 CT Test Device A63 CB-F-1A-A EDE-A63-51GS Ground Sensor Relay A63 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -14 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 9 EDE-US-51 480 V Bus 51 Unit Substation 310013 A 310442 CB-F-1A-A X X X - AB2 EDE-AB2-52 480 V ac Circuit Breaker AB2 CB-F-1A-A 310103 AB2a AB2b CBA-FN-19 CBA-FN-20 EDE-X-5A EDE-US-61 EDE-X-5A 4160-480 V Distribution Transformer AB1 CB-F-1A-A EDE-AB3-FU Fuses AB3 CB-F-1A-A EDE-AB1-LA 6 kV Lightning Arrestors (3) AB1 CB-F-1A-A EDE-AB2-CT Current Transformers (2000/5) AB2 CB-F-1A-A EDE-AB3-AM Ammeter AB3 CB-F-1A-A EDE-AB3-AS Ammeter Switch AB3 CB-F-1A-A 10 EDE-US-52 480 V Bus 51 Unit Substation 310013 A 310442 CB-F-1A-A X X X - AC2 EDE-AC2-52 480 V AC Circuit Breaker AC2 CB-F-1A-A 310103 AC2a AC2b CBA-FN-19 CBA-FN-20 EDE-X-5B EDE-US-62 EDE-X-5B 4160-480 V Distribution Transformer AC1 CB-F-1A-A EDE-AC3-FU Fuses AC3 CB-F-1A-A EDE-AC1-LA 6 kV Lightning Arrestors (3) AC1 CB-F-1A-A EDE-AC2-CT Current Transformers (2000/5) AC2 CB-F-1A-A EDE-AC3-AM Ammeter AC3 CB-F-1A-A EDE-AC3-AS Ammeter Switch AC3 CB-F-1A-A 11 EDE-US-51 480 V Feed to 460 V Motor Control Center 512 310013 A 310442 CB-F-1A-A X X X - AB6 EDE-AB6-52 480 V AC Circuit Breaker AB6 CB-F-1A-A AB6-B10 AB6-B10/1 310103 AB6 AB6 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-612 12 EDE-US-51 480 V Feed to 460V Motor Control Center 514 310013 A 310442 CB-F-1A-A X X X - A94 EDE-A94-52 480 V AC Circuit Breaker A94 CB-F-1A-A A94-C11 310103 A94 A94 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-614 13 EDE-US-51 480 V Feed to 460 V Motor Control Center 515 310013 A 310442 CB-F-1A-A X X X - AX8 EDE-AX8-52 480 V AC Circuit Breaker AX8 CB-F-1A-A AB6-B4D AB6-B4D/1 310103 AX8 AX8 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-615 14 EDE-US-52 480 V Feed to 460 V Motor Control Center 521 310013 A 310442 CB-F-1A-A X X X - AC8 EDE-AC8-52 480 V AC Circuit Breaker AC8 CB-F-1A-A AC8-B13 AC8-B13/1 310103 AC8 AC8 CBA-FN-19 CBA-FN-20 EDE-US-52 EDE-US-62 EDE-MCC-622 15 EDE-US-52 480 V Feed to 460 V Motor Control Center 522 310013 A 310442 CB-F-1A-A X X X - AW9 EDE-AW9-52 480 V AC Circuit Breaker AW9 CB-F-1A-A AW9-D12 AW9-G81/1 AW9-G81 310103 AW9a AW9c AW9b AW9c CBA-FN-19 CBA-FN-20 EDE-US-52 EDE-US-62 EDE-MCC-622 EDE-CS-9787-2 Control Switch with Indication G81 CB-F-1A-A EDE-SS-9787 Selector Switch G81 CB-F-1A-A EDE-AW9-52H Truck Operated Contact AW9 CB-F-1A-A EDE-AW9-FU Fuses AW9 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -15 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 15a EDE-US-51 480 V Feed to 460 V Motor Control Center 511 310013 A 310442 CB-F-1A-A X X X - AB5 EDE-AB5-52 480 V AC Circuit Breaker AB5 CB-F-1A-A AB5-B09 AB5-B09/1 310103 AB5 AB5 CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 EDE-MCC-611 16 EDE-US-51 Grounding Transformer 310012 A 310442 CB-F-1A-A X X X - AB3 EDE-AB3-XFMR 3-1ø 1 k VA Transformers AB3 CB-F-1A-A 310103 AB3b CBA-FN-19 CBA-FN-20 EDE-US-51 EDE-US-61 Ground Transformer EDE-AB3-FU Fuses AB3 CB-F-1A-A EDE-AB3-RES Grounding Resistor AB3 CB-F-1A-A EDE-AB3-VM Ground Voltmeters (3) AB3 CB-F-1A-A EDE-AB3-64 Ground Relay AB3 CB-F-1A-A 17 EDE-US-52 Grounding Transformer 310013 A 310442 CB-F-1A-A X X X - AC3 EDE-AC3-XFMR 3-1ø 1 k VA Transformers AC3 CB-F-1A-A 310103 AC3b CBA-FN-19 CBA-FN-20 EDE-US-52 EDE-US-62 Ground Transformer EDE-AC3-FU Fuses AC3 CB-F-1A-A EDE-AC3-RES Grounding Resistor AC3 CB-F-1A-A EDE-AC3-VM Ground Voltmeters (3) AC3 CB-F-1A-A EDE-AC3-64 Ground Relay AC3 CB-F-1A-A 18 EDE-I-1E Uniterruptible Power Supply 310043 A 310442 CB-F-1A-A X X X - HF5 EDE-DD3-52 480 V AC Circuit Breaker DD3 CB-F-1A-A DD3-HF5/1 DM7-HF5/1 310105 DD3a DD3b CBA-FN-19 CBA-FN-20 EDE-MCC-512 EDE-SWG-11A EDE-I-1F EDE-DM7-72 125 V dc Circuit Breaker DM7 CB-F-1A-A EDE-HF5/2-52 460 V ac Inc. Line Circuit Breaker HF5 CB-F-1A-A EDE-HF5/1-72 125 V dc Inc. Line Circuit Breaker HF5 CB-F-1A-A EDE-HF5/3-52 120 V ac Output Circuit Breaker HF5 CB-F-1A-A 18A EDE-CP-1E Static Transfer Switch 310043 A 310442 CB-F-1A-A X X X - E1Y EDE-E1Y-F1 300A, 600 V Fuse E1Y CB-F-1A-A E1Y-HF5 E1Y-HF5/1 310105 DD3a DD3b CBA-FN-19 CBA-FN-20 EDE-I-1E EDE-CP-1F 19 EDE-PP-1E Vital Instrument Bus 310043 A 310442 CB-F-1A-A X X X - EH9 EDE-EH9/NC-52 120 V ac Circuit Breaker-Inc. Feed from EDE-CP-1E (Norm. Closed) EH9 CB-F-1A-A EH9-E1Y 310105 DD3a DD3b EH9a CBA-FN-19 CBA-FN-20 EDE-CP-1E EDE-PP-1F EDE-EH9/NO-52 120 V ac Circuit Breaker-Inc. Feed from ED-X-31E (Norm. Open) EH9 CB-F-1A-A 20 EDE-PP-11E Vital Instrument Bus 310043 A 310442 CB-F-1A-A X X X - E1S EDE-EH9/13-52 120 V ac Circuit Breaker EH9 CB-F-1A-A E1S-EH9 310105 DD3a DD3b E1Sa CBA-FN-19 CBA-FN-20 EDE-PP-1E EDE-PP-11F SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -16 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 21 EDE-BC-1A 125 V dc Battery Charger 310042 A 310442 CB-F-1A-A X X X - HR5 EDE-DB1-52 460 V ac Circuit Breaker DB1 CB-F-1A-A DB1-HR2 DB1-HR5 310107 DB1a DB1f DB1b DB1c CBA-FN-19 CBA-FN-20 EDE-MCC-512 EDE-BC-1B EDE-DB1-42 Contactor DB1 CB-F-1A-A EDE-DB1-42X Auxiliary Relay DB1 CB-F-1A-A DG-HR2-HR9 (K20) EPS Relay HR2 CB-F-1A-A EDE-HR5/1-52 460 V ac Circuit Breaker-Incoming Feed HR5 CB-F-1A-A EDE-DB1-FU Fuse DB1 CB-F-1A-A 22 EDE-B-1A 125 V dc Battery 310042 A 310442 CB-F-1D-A X X X - HV4 EDE-J75-FU-1,2,3,4 1600 A Fuses J75 CB-F-1A-A HV4-J75 HV4-J75/1 310107 DB1a DB1f DB1b DB1c CBA-FN-19 CBA-FN-20 CBA-FN-21A EDE-BC-1A EDE-SWG-11A EDE-B-1B EDE-J75-SH 1000A, 100MV Shunt J75 CB-F-1A-A EDE-J75-ATR Shunt Amplifier J75 CB-F-1A-A 23 EDE-SWG-11A 125 V dc Switchboard Auxiliary Buses 120 V ac and 125 V dc 310042 A 310442 CB-F-1A-A X X X - DM1 EDE-HR5/2-72 125 V dc Circuit Breaker HR5 CB-F-1A-A DM3-J75 DM3-J75/1 DM2-HR5 310107 DB1a DB1f DB1b DB1c CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-B-1A EDE-BC-1A EDE-PP-1E EDE-SWG-11B EDE-DL4-72 125 V dc Circuit Breaker DL4 CB-F-1A-A EDE-DM2-72 125 V dc Circuit Breaker DM2 CB-F-1A-A EDE-DM3-72 125 V dc Circuit Breaker DM3 CB-F-1A-A EDE-DM4-72 125 V dc Circuit Breaker DM4 CB-F-1A-A EDE-DM1-FU-1,2 15 amp Fuses DM1 CB-F-1A-A EDE-DM1-27BL Undervoltage Relay DM1 CB-F-1A-A EDE-DM1-27BLL Undervoltage Relay DM1 CB-F-1A-A EDE-DM1-VM DC Voltmeter DM1 CB-F-1A-A EDE-DM1-VTR Voltage Transducer DM1 CB-F-1A-A EDE-DM1-D10 Diodes DM1 CB-F-1A-A EDE-DM1-XS Selector Switch DM1 CB-F-1A-A EDE-DM1-AMY Ammeter Relay DM1 CB-F-1A-A EDE-EH9/5-52 120 V ac Circuit Breaker EH9 CB-F-1A-A DM1-EH9 DM1-J75/1 310105 EH9a EH9b 310107 DB1a DB1f DB1c 5a EDE-DM1-27BL Undervoltage Relay DM1 CB-F-1A-A EDE-DM1-62BL Timing Relay DM1 CB-F-1A-A EDE-DM1-27BLL Undervoltage Relay DM1 CB-F-1A-A EDE-DM1-62BLL Timing Relay DM1 CB-F-1A-A EDE-DM2-72 Breaker Operated Contact DM2 CB-F-1A-A EDE-DM2-72STC Circuit Breaker Shut Trip Coil DM2 CB-F-1A-A EDE-DM1-VTR Voltage Transducer DM1 CB-F-1A-A EDE-J75-ATR Current Transducer J75 CB-F-1A-A EDE-DM1-AMY Ammeter Relay DM1 CB-F-1A-A EDE-DM1-52 120 V ac Inc. Feed Circuit Breaker DM1 CB-F-1A-A EDE-DM1-FU 120 V AC 15A and 1A Fuses DM1 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -17 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 24 EDE-PP-111A 125 V dc Distribution Panel 310042 A 310442 CB-F-1A-A X X X - E93 EDE-DM5-72 125 V dc Circuit Breaker DM5 CB-F-1A-A DM5-E93 310107 DB1a DB1f E93a CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-PP-111B EDE-E93-72 125 V dc Circuit Breaker (Main) E93 CB-F-1A-A 25 EDE-PP-112A 125 V dc Distribution Panel 310042 A 310442 CB-F-1A-A X X X - E87 EDE-DM8-72 125 V ac Circuit Breaker DM8 CB-F-1A-A DM8-E87 310107 DB1a DB1f E87a CBA-FN-19 CVA-FN-20 EDE-SWG-11A EDE-PP-112B EDE-E87-72 125 V ac Circuit Breaker (Main) E87 CB-F-1A-A 26 EDE-PP-113A 125 V dc Distribution Panel 310042 A 310442 CB-F-1A-A X X X - E2T EDE-DM0-72 125 V dc Circuit Breaker DM0 CB-F-1A-A DM0-E2T 310107 DB1a DB1f DB1b E2Ta CBA-FN-19 CBA-FN-20 EDE-SWG-11A EDE-PP-113B EDE-E2T-72 125 V dc Circuit Breaker (Main) E2T CB-F-1A-A 27 EDE-SWG-5 4160 V SWGR 125 V dc Control Bus A 310442 CB-F-1A-A X X X - A53 EDE-E93/1-72 125 V dc Circuit Breaker E93 CB-F-1A-A A53-E93 310107 E93a E93b 310102 5e 5f 5g 5h CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-SWG-6 EDE-A53-8 125 V dc Circuit Breaker (Main) A53 CB-F-1A-A 28 EDE-US-51 480 V Unit Substation 125 V dc Control Bus A 310442 CB-F-1A-A X X X - AB3 EDE-E93/2-72 125 V dc Circuit Breaker E93 CB-F-1A-A AB3-E93 310107 E93a E93b 310103 5m CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-US-61 EDE-AB3-8 125 V dc Circuit Breaker (Main) AB3 CB-F-1A-A 29 EDE-US-52 480 V Unit Substation 125 V dc Control Bus A 310442 CB-F-1A-A X X X - AC3 EDE-E93/3-72 125 V AC Circuit Breaker E93 CB-F-1A-A AC3-E93 310107 E93a E93b 310103 5n CBA-FN-19 CBA-FN-20 EDE-PP-111A EDE-US-62 EDE-AC3-8 125 V AC Circuit Breaker (Main) AC3 CB-F-1A-A 30 DG-CP-75A Diesel Generator 1A Control Panel Cubicle 3 125 V dc Supply 310010 310042 A 310524 DG-F-2A-A X X X - G10 EDE-DM9-72 125 V dc Circuit Breaker DM9 CB-F-1A-A DM9-G10 310102 DM9a DM9b 310107 DB1a DAH-FN-25A DAH-FN-26A EDE-SWG-11A CBA-FN-19 CBA-FN-20 DG-CP-76A DG-G10-72 125 V dc Circuit Breaker (Main) G10 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -18 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 31 EDE-SWG-6 4160 V Bus E6 UAT Incoming Line Swgr. 310008 B 310442 CB-F-1B-A X X X - A71 EDE-A71-52 4160 V Circuit Breaker A71 CB-F-1B-A A71-G19 A71-G19/2 A71-G20 A71-HRO GA6-GB0/5 A71-G19/1 A71-G19/3 A71-GB4 GAO-CB3/5 GC4-GC6/5 A71-G5Y A71-G5Y/1 A75-A7A A74-A7A/1 DM1-EH9 310102 A71a A71h A71b A71c A71d A71e CBA-FN-32 CBA-FN-33 ED-X-2B EDE-PP-111B DAH-FN-25B DAH-FN-26B EDE-SWG-5 UAT EDE-CS-9719-2 Control Switc h A71 CB-F-1B-A EDE-CS-9719-3 Control Switch with Indication G19 DG-F-2B-A EDE-A71-G,R,W Indicating Lights A71 CB-F-1B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-A71-52H Truck Operated Contact A71 CB-F-1B-A EDE-A71-FU Fuses A71 CB-F-1B-A EDE-A71-CT1 Current Transformers (2000/5) A71 CB-F-1B-A EDE-A71-TD-1 CT Test Device A71 CB-F-1B-A EDE-A71-AM Ammeter A71 CB-F-1B-A EDE-A71-AS Ammeter Switch A71 CB-F-1B-A EDE-A71-ATR Current Transducer A71 CB-F-1B-A EDE-A71-CT2 Current Transformers (4000/5) A71 CB-F-1B-A EDE-A87-PT Potential Transformer A87 CB-F-1B-A EDE-A71-TD-3 PT Test Device A71 CB-F-1B-A EDE-A71-VM Voltmeter A71 CB-F-1B-A EDE-A71-86 Lockout Relay A71 CB-F-1B-A EDE-A74-52S Mech. Operated Contact A74 CB-F-1B-A EDE-A72-52S Mech. Operated Contact A72 CB-F-1B-A DG-G20-25Y1 Auxiliary Sync. Check Relay G20 DG-F-2B-A EDE-A73-25U Synchronizing Check Relay A73 CB-F-1B-A EDE-SS-9719-1 Selector Switch G5Y DG-F-2B-A EDE-CS-9717-3 Control Switch G19 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-A72-86 Lockout Relay A72 CB-F-1B-A EDE-A89-86B Lockout Relay A89 CB-F-1B-A ED-86SB/2/1X -1 Lockout Relay GAO TB-F-1C-Z ED-86-2/2/B3 Lockout Relay GA6 TB-F-1C-Z ED-86UB/2/1X -2A Lockout Relay GA8 TB-F-1C-Z ED-86UB/2/1X -2B Lockout Relay GA8 TB-F-1C-Z ED-86BF-2/S/52/TG1 Lockout Relay GA9 TB-F-1C-Z ED-86GT/2/TG -1 Lockout Relay GA9 TB-F-1C-Z ED-86-1/2/B3 Lockout Relay GBO TB-F-1C-Z ED-86BF-2/2H Lockout Relay GB3 TB-F-1C-Z ED-86BF-2/2E Lockout Relay GB4 TB-F-1C-Z ED-86UP/2/1X -2A Lockout Relay GC2 TB-F-1C-Z ED-86UP/2/1X -2B Lockout Relay GC2 TB-F-1C-Z SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -19 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-6 (Continued) ED-86BF-1/2/52/TG1 Lockout Relay GC3 TB-F-1C-Z ED-86SP/2/1X -1 Lockout Relay GC4 TB-F-1C-Z ED-86BF-1/2H Lockout Relay GC6 TB-F-1C-Z ED-86BF-1/2E Lockout Relay GC7 TB-F-1C-Z DG-HRO-RMO EPS Auxiliary Relay HRO CB-F-1B-A EDE-A71-3 Interposing Relay for SWYD Lockout Relays A71 CB-F-1B-A EDE-A71-TD-2 Lockout Relay Test Device (A71 -86) A71 CB-F-1B-A EDE-A71-TD-4 Interposing Relay Test Device (A71-3) A71 CB-F-1B-A ED-GA0-TD-2 Lockout Relay Test Device (86SB/2/1X -1) GA0 TB-F-1C-Z ED-GA6-TD-2 Lockout Relay Test Device (86 -2/2/B3) GA6 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2A) GA8 TB-F-1C-Z ED-GA8-TD-2 Lockout Relay Test Device (86UB/2/1X -2B) GA8 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86BF -2/2/52/TG1) GA9 TB-F-1C-Z ED-GA9-TD-2 Lockout Relay Test Device (86GT/2/TG -1) GA9 TB-F-1C-Z ED-GB0-TD-2 Lockout Relay Test Device (86 -1/2/B3) GB0 TB-F-1C-Z ED-GB3-TD-2 Lockout Relay Test Device (86BF -2/2H) GB3 TB-F-1C-Z ED-GB4-TD-2 Lockout Relay Test Device (86BF -2/2E) GB4 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2A) GC2 TB-F-1C-Z ED-GC2-TD-2 Lockout Relay Test Device (86UP/2/1X -2B) GC2 TB-F-1C-Z ED-GC3-TD-2 Lockout Relay Test Device (86BF -1/2/52/TG1) GC3 TB-F-1C-Z ED-GC4-TD-2 Lockout Relay Test Device (86SP/2/1X -1) GC4 TB-F-1C-Z ED-GC6-TD-2 Lockout Relay Test Device (86BF -1/2H) GC6 TB-F-1C-Z ED-GC7-TD-2 Lockout Relay Test Device (86BF -1/2E) GC7 TB-F-1C-Z EDE-A71-51 Time Overcurrent Relays øA, øB, øC A71 CB-F-1B-A EDE-A71-51GS Ground Sensor Relay A71 CB-F-1B-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -20 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 32 EDE-SWG-6 Grounding Transforme r 310008 B 310442 CB-F-1B-A X X X - A87 EDE-A87-XFMR 3-1ø 15 k VA Transformers A87 CB-F-1B-A 310102 A87a CBA-FN-32 CBA-FN-33 EDE-SWG-6 EDE-SWG-5 Ground Transformer EDE-A87-FU 3-10A Fuses A87 CB-F-1B-A EDE-A87-52 120 V ac Circuit Breaker A87 CB-F-1B-A EDE-A87-RES Grounding Resistor A87 CB-F-1B-A EDE-A87-64 Ground Relay A87 CB-F-1B-A EDE-A87-TD-3 VM Test Device A87 CB-F-1B-A EDE-A87-VM (3) Ground Voltmeter s A87 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -21 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 33 EDE-SWG-6 4160 V Bus E6 RAT Incoming Line SWGR 310008 B 310442 CB-F-1A-A X X X - A72 EDE-A72-52 4160 V Circuit Breaker A72 CB-F-1B-A A72-G19 A72-G19/2 A72-G20 A72-HR4 GA7-GB7/5 GE6-GE7/5 A72-G19/1 A72-G19/3 A72-GB7 A72-HR0 GC1-GC0/5 A72-G5Y A72-G5Y/1 A74-A7A/2 310102 A72a A72j A72b A72c A72d A72e CBA-FN-32 CBA-FN-33 ED-X-3B EDE-PP-111B DAH-FN-25B DAH-FN-26B EDE-SWG-5 RAT EDE-CS-9717-2 Control Switch A72 CB-F-1B-A EDE-CS-9717-3 Control Switch with Indication G19 DG-F-2B-A EDE-A72-G,R,W Indicating Lights A72 CB-F-1B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-A72-52H Truck Operated Contact A72 CB-F-1B-A EDE-A72-FU Fuses A72 CB-F-1B-A EDE-A72-27/59 Under/Over Voltage Relay A72 CB-F-1B-A EDE-A72-27/59X1,X2 Under/Over Voltage Auxiliary Relay A72 CB-F-1B-A EDE-A72-CT1 Current Transformers (2000/5) A72 CB-F-1B-A EDE-A72-52Z Time Delay Relay A72 CB-F-1B-A EDE-SS-9717-1 Selector Switch G5Y DG-F-2B-A EDE-CS-9719-3 Control Switch G19 DG-F-2B-A EDE-A72-TD-1 CT Test Device A72 CB-F-1B-A EDE-A72-AM Ammeter A72 CB-F-1B-A EDE-A72-AS Ammeter Switch A72 CB-F-1B-A EDE-A72-ATR Current Transducer A72 CB-F-1B-A EDE-A72-CT2 Current Transformers (4000/5) A72 CB-F-1B-A EDE-A73-PT Potential Transformer A73 CB-F-1B-A EDE-A72-TD-3 PT Test Device A72 CB-F-1B-A EDE-A72-VM Voltmeter A72 CB-F-1B-A EDE-A72-52S Mechanically Operated Contact A72 CB-F-1B-A EDE-A72-86B Lockout Relay A89 CB-F-1B-A EDE-A72-86 Lockout Relay A72 CB-F-1B-A EDE-A72-86 Lockout Relay A71 CB-F-1B-A DG-HR4-RMO EPS Auxiliary Relay HR4 CB-F-1B-A DG-HRO-RMO EPS Auxiliary Relay HRO CB-F-1B-A EDE-A71-52S Mechanically Operated Contact A71 CB-F-1B-A EDE-A74-52S Mechanically Operated Contact A74 CB-F-1B-A EDE-SNS-9737-2 Synchronizing Switc h G18 DG-F-2B-A DG-G20-25Y1 Auxiliary Sync Check Relay G20 DG-F-2B-A EDE-A73-25RX Auxiliary Sync. Check Relay A73 CB-F-1B-A EDE-A73-25R Synchronizing Check Relay A73 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -22 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-6 (Continued) EDE-A72-62 & 62X Time Delay Relay A72 CB-F-1B-A EDE-A71-3 Interposing Relay for SWYD Lockout Relays A71 CB-F-1B-A EDE-A72-TD-2 Lockout Relay Test Device (A72 -86) A72 CB-F-1B-A EDE-TD-4 Interposing Relay Test Device (A72 -3) A72 CB-F-1B-A EDE-A72-27RB-1 Residual Undervoltage Relay A72 CB-F-1B-A EDE-A72-27RB-2 Residual Undervoltage Relay A72 CB-F-1B-A EDE-86RB/2/1X -3A Lockout Relay GA7 TB-F-1C-Z ED-86-2/2/B2 Lockout Relay GB7 TB-F-1C-Z ED-86-1/2/B2 Lockout Relay GCO TB-F-1C-Z ED-86RP/2/1X -3A Lockout Relay CG1 TB-F-1C-Z ED-86RP/2/1X -3B Lockout Relay GE6 TB-F-1C-Z ED-86RB/2/1X -3B Lockout Relay GE7 TB-F-1C-Z ED-GA7-TD-2 Lockout Relay Test Device (86RB/2/1x -3A) GA7 TB-F-1C-Z ED-GB7-TD-2 Lockout Relay Test Device (86 -2/2/B2) GB7 TB-F-1C-Z ED-GCO-TD-2 Lockout Relay Test Device (86 -1/2/B2) GCO TB-F-1C-Z ED-GC1-TD-2 Lockout Relay Test Device (86RP/2/1x -3A) GC1 TB-F-1C-Z ED-GE6-TD-2 Lockout Relay Test Device (86RP/2/1x -3B) GE6 TB-F-1C-Z ED-GE7-TD-2 Lockout Relay Test Device (86RB/2/1x -3B) GE7 TB-F-1C-Z EDE-A72-51 Time Overcurrent Relays øA, øB, øC A72 CB-F-1B-A EDE-A72-51GS Ground Sensor Relay A72 CB-F-1B-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -23 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 34 EDE-SWG-6 4160 V Bus E6 PT Compartment 310008 B 310442 CB-F-1B-A X X X - A73 EDE-A73-PT Potential Transformer A73 CB-F-1B-A A73-AE2 A73-G19 A73-HR4 AE2-AF7 AF7-EE6 AW2-EE6 A74-A7A/4 A74-A7A/5 A75-A7A/1 A75-A7A/1 310102 A73A A73d A73e A73h CBA-FN-32 CBA-FN-33 EDE-SWG-6 EDE-PP-111B DAH-FN-25B DAH-FN-26B EDE-SWG-5 PT EDE-A73-VM Voltmeter A73 CB-F-1B-A EDE-A73-VS Voltmeter Switch A73 CB-F-1B-A EDE-A73-TD-3 PT Test Device A73 CB-F-1B-A EDE-A73-VTR-1 Voltage Transducer A73 CB-F-1B-A EDE-A73-VTR-2 Voltage Transducer A73 CB-F-1B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-A73-25U Synchronizing Check Relay A73 CB-F-1B-A EDE-A73-25R Synchronizing Check Relay A73 CB-F-1B-A EDE-A74-52S Mechanically Operated Contact A74 CB-F-1B-A EDE-A73-27B-1 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-27B-2 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-TS-3 UV Relays Test Switch A73 CB-F-1B-A EDE-A73-27D-1 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-27D-1-RES Resistor A73 CB-F-1B-A EDE-A73-27D-2 Instantaneous Undervoltage Relay A73 CB-F-1B-A EDE-A73-27D-2-RES Resistor A73 CB-F-1B-A EDE-A73-TS-1 UV Relays Test Switch A73 CB-F-1B-A EDE-A72-27RB-1,2 Residual Undervoltage Relay A72 CB-F-1B-A EDE-A73-62B Time Delay Relay A73 CB-F-1B-A EDE-A73-62B-RES Resistor A73 CB-F-1B-A EDE-A73-TS-4 Test Switch EDE -62B A73 CB-F-1B-A EDE-A73-62BX-1 Auxiliary Relay A73 CB-F-1B-A EDE-A73-62BX Auxiliary Latch Relay A73 CB-F-1B-A EDE-A71-52S Mechanically Operated Contact A71 CB-F-1B-A EDE-AW3-94-5 Undervoltage Tripping Relay AW3 CB-F-1B-A EDE-A72-27/59X1 Under/Over Voltage Auxiliary Relay A72 CB-F-1B-A EDE-AF8-94-4 Undervoltage Tripping Relay AF8 CB-F-1B-A DG-HR4-RM0 EPS Auxiliary Relay HR4 CB-F-1B-A EDE-A73-94-1A Undervoltage Tripping Relay A73 CB-F-1B-A EDE-A73-94-1B Undervoltage Tripping Relay A73 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -24 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-6 (Continued) EDE-A73-94-2 Undervoltage Tripping Relay A73 CB-F-1B-A EDE-AE3-94-3 Undervoltage Tripping Relay AE3 CB-F-1B-A EDE-EE6-94-6 Tripping Relay EE6 CB-F-1B-A EDE-A73-FU 10A Fuses A73 CB-F-1B-A EDE-A73-62D Time Delay Relay A73 CB-F-1B-A EDE-A73-62D-RES Resistor A73 CB-F-1B-A EDE-A73-TS-2 Test Switch Relay 62D A73 CB-F-1B-A EDE-A73-62DX Auxiliary Relay A73 CB-F-1B-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -25 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 35 EDE-SWG-6 4160 V Bus E6 DG-1B Incoming Line SWGR 310010 310008 B 310442 CB-F-1B-A X X X - A74 EDE-A74-52 4160 V Circuit Breaker A74 CB-F-1B-A A74-G18/2 A74-G18/3 A74-G18/4 A74-G18/8 A74-G19 A74-G19/1 A74-G19/2 A74-HP1 G18-G30/7 A74-A7A/3 310102 A74a A74k A74b A74n A74c A74d A74e A74f CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B EDE-PP-111B DG-DG-1B EDE-SWG-5 DG-1A EDE-CS-9710-2 Control Switch A74 CB-F-1B-A EDE-CS-9710-3 Control Switch with Indication G18 DG-F-2B-A EDE-A74-G,R,W Indicating Lights A74 CB-F-1B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-A74-52H Truck Operated Contact A74 CB-F-1B-A EDE-A74-FU Fuses A74 CB-F-1B-A EDE-A74-CT Current Transformers (2000/5) A74 CB-F-1B-A EDE-A74-DCT Differential Current Transformers (2000/5) A74 CB-F-1B-A DG-HP1-DCT DG-1B Neutral Differential Current Transformers (2000/5) HP1 DG-F-2B-A DG-G18-CT Auxiliary Current Transformer (5:10) G18 DG-F-2B-A EDE-A74-AM Ammeter A74 CB-F-1B-A EDE-A74-AS-1 Ammeter Switch A74 CB-F-1B-A EDE-A74-ATR-1 Current Transducer A74 CB-F-1B-A EDE-A74-ATR-2 Current Transducer A74 CB-F-1B-A EDE-AM-9710-2 Ammeter G18 DG-F-2B-A EDE-G18-AS Ammeter Switch G18 DG-F-2B-A DG-SM-9587 Governor Control (2301A) G18 DG-F-2B-A EDE-A89-PT DG-1B Inc. Line Pot. Transformer (2) 4200-120 V A89 CB-F-1B-A EDE-A89-VM Voltmeter A89 CB-F-1B-A EDE-A89-VS Voltmeter Switch A89 CB-F-1B-A EDE-A89-TD-3 PT Test Device A89 CB-F-1B-A EDE-A89-VTR-1 Voltage Transducer A89 CB-F-1B-A EDE-A89-VTR-2 Voltage Transducer A89 CB-F-1B-A EDE-A74-27DG Undervoltage Relay A74 CB-F-1B-A EDE-A89-FTR-1 Frequency Transducer A89 CB-F-1B-A EDE-A89-FTR-2 Frequency Transducer A89 CB-F-1B-A EDE-A89-W/WH-TR Watt/Watthour Transducer A89 CB-F-1B-A EDE-A89-W/TR Watt Transducer A89 CB-F-1B-A EDE-A89-VAR-TR Var Transducer A89 CB-F-1B-A EDE-A74-TS Test Start Switch A74 CB-F-1B-A EDE-A74-52Z Time Delay Relay A74 CB-F-1B-A EDE-A74-81-RES Resistor A74 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -26 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-6 (Continued) EDE-A89-86B Lockout Relay A89 CB-F-1B-A EDE-A89-86DB Back-Up Lockout Relay A89 CB-F-1B-A EDE-A89-W Indicating Lights (A89-86B & A89 -86DB) A89 CB-F-1B-A EDE-A74-W Indicating Light (A74-86DP) A74 CB-F-1B-A EDE-A74-86DP Primary Lockout Relay A74 CB-F-1B-A EDE-A71-86 Lockout Relay A71 CB-F-1B-A EDE-A72-86 Lockout Relay A72 CB-F-1B-A EDE-A71-52S Mechanically Operated Contact A71 CB-F-1B-A EDE-A72-52S Mechanically Operated Contact A72 CB-F-1B-A EDE-A74-52S Mechanically Operated Contact A74 CB-F-1B-A EDE-A89-RLA LOCA Seal Relay A89 CB-F-1B-A DG-G20-25Y Auxiliary Sync Check Relay G20 DG-F-2B-A EDE-A89-RS Fast Closure Relay A89 CB-F-1B-A EDE-A74-81 Frequency Relay A74 CB-F-1B-A EDE-A74-87DP Primary Differential Relay A74 CB-F-1B-A EDE-A89-51B Time Overcurrent Relays øA, øB, øC A89 CB-F-1B-A EDE-A74-81X Auxiliary Frequency Relay A74 CB-F-1B-A EDE-A89-60 Voltage Balance Relay A89 CB-F-1B-A EDE-A89-60AX Auxiliary Voltage Balance Relay A89 CB-F-1B-A EDE-A89-60BX Auxiliary Voltage Balance Relay A89 CB-F-1B-A EDE-A89-40 Loss of Field Relays øA, øB A89 CB-F-1B-A EDE-A74-40X Auxiliary Loss of Field Relay A74 CB-F-1B-A EDE-A89-32 Power Directional Relay A89 CB-F-1B-A EDE-A89-TD-1 Lockout Relay Test Device (86B) A89 CB-F-1B-A EDE-A89-TD-2 Lockout Relay Test Device (86DB) A89 CB-F-1B-A EDE-A74-TD-2 Lockout Relay Test Device (86DP) A74 CB-F-1B-A DG-G19-R43L5 & R43L6 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -27 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS EDE-SWG-6 (Continued) DG-G30-5A Shutdown Relay G30 DG-F-2B-A EDE-A89-51V Time Overcurrent Voltage Restraint Relays øA, øB, øC A89 CB-F-1B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A EDE-A89-51GS Ground Sensor Relay A89 CB-F-1B-A EDE-A74-TD-1 Test Device A74 CB-F-1B-A EDE-A74-87DP Reactor Primary Differential Relay Reactor Assembly A74 CB-F-1B-A EDE-A74-81Y Time Delay Relay A74 CB-F-1B-A EDE-A7A-52S Mechanically Operated Contact A7A CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -28 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 36 DG-CP-76A Diesel Generator 1B Control Panel Cubicle 2 Synchronizing System 310010 B 310524 DG-F-2B-A X X X - G19 EDE-SS-9710 Selector Switch G18 DG-F-2B-A 310102 G19/2c G19/2g DAH-FN-25B DAH-FN-26B EDE-SWG-11B DG-CP-75A EDE-SS-9719 Selector Switch G19 DG-F-2B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A DG-G19-FU 125 V DC Fuses G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-RAX Auxiliary Relay, Latch G19 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-CS-9710-3 Control Switch G18 DG-F-2B-A EDE-CS-9717-3 Control Switch G19 DG-F-2B-A EDE-CS-9719-3 Control Switch G19 DG-F-2B-A DG-G18-25DG Synchronizing Check Relay G18 DG-F-2B-A DG-G20-25Y Auxiliary Synchronizing Check Relay G20 DG-F-2B-A DG-G20-25Y1 Auxiliary Synchronizing Check Relay G20 DG-F-2B-A EDE-A87-PT UAT X-2B Inc. Line Potential Transformer A87 CB-F-1B-A 7e 7g EDE-A73-PT RAT X-3B Inc. Line Potential Transformer A73 CB-F-1B-A EDE-A73-PT Bus E6 Potential Transformer A73 CB-F-1B-A EDE-A89-PT DG-1B Inc. Line Potential Transformer A89 CB-F-1B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A EDE-SS-9717 Selector Switch G19 DG-F-2B-A EDE-SS-9719 Selector Switch G19 DG-F-2B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-RAX Auxiliary Relay, Latch G19 DG-F-2B-A DG-G18-25DG Synchronizing Check Relay G18 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -29 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-CP-76A (Continued) EDE-SYN-9711 Synchroscope G18 DG-F-2B-A EDE-ZL-9711 Synchronizing Lights G18 DG-F-2B-A EDE-VM-9711-1 Synchronizing Voltmeter Incoming G18 DG-F-2B-A EDE-VM-9711-2 Synchronizing Voltmeter Running G18 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -30 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 37 EDE-SWG-6 4160 V Feed to 480 V Transformer EDE-X-5C for Substation Bus EDE-US-61 310008 B 310442 CB-F-1B-A X X X - A75 EDE-A75-52 4160 V Circuit Breaker A75 CB-F-1B-A A75-AD1 310102 A75a A75g A75b A75c A75d CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-SWG-6 EDE-SWG-5 EDE-X-5A EDE-US-51 EDE-A75-FU Fuses A75 CB-F-1B-A EDE-CS-9716 Control Switch A75 CB-F-1B-A EDE-A75-G,R,W Indicating Lights A75 CB-F-1B-A EDE-SS-9716 Selector Switch A75 CB-F-1B-A EDE-A75-52H Truck Operated Contact A75 CB-F-1B-A EDE-A75-86 Lockout Relay A75 CB-F-1B-A EDE-A75-TD-2 Lockout Relay Test Device A75 CB-F-1B-A EDE-A75-50/51 Inst/Time Overcurrent Relays øA, øB, øC A75 CB-F-1B-A EDE-A75-CT Current Transformers (300/5) A75 CB-F-1B-A EDE-A75-AM Ammeter A75 CB-F-1B-A EDE-A75-AS Ammeter Switch A75 CB-F-1B-A EDE-A75-ATR Current Transducer A75 CB-F-1B-A EDE-A75-TD-1 CT Test Device A75 CB-F-1B-A EDE-A75-51GS Ground Sensor Relay A75 CB-F-1B-A 38 EDE-SWG-6 4160 V Feed to 480 V Transformer EDE-X-5D for Substation Bus EDE-US-62 310008 B 310442 CB-F-1B-A X X X - A83 EDE-A83-52 4160 V Circuit Breaker A83 CB-F-1B-A A83-AE1 310102 A83a A83g A83b A83c A83d CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-SWG-6 EDE-SWG-5 EDE-X-5B EDE-US-52 EDE-A83-FU Fuses A83 CB-F-1B-A EDE-CS-9713 Control Switch A83 CB-F-1B-A EDE-A83-G,R,W Indicating Lights A83 CB-F-1B-A EDE-SS-9713 Selector Switch A83 CB-F-1B-A EDE-A83-52H Truck Operated Contact A83 CB-F-1B-A EDE-A83-86 Lockout Relay A83 CB-F-1B-A EDE-A83-TD-2 Lockout Relay Test Device A83 CB-F-1B-A EDE-A83-50/51 Inst/Time Overcurrent Relays øA, øB, øC A83 CB-F-1B-A EDE-A83-CT Current Transformers (300/5) A83 CB-F-1B-A EDE-A83-AM Ammeter A83 CB-F-1B-A EDE-A83-AS Ammeter Switch A83 CB-F-1B-A EDE-A83-ATR Current Transducer A83 CB-F-1B-A EDE-A83-TD-1 CT Test Device A83 CB-F-1B-A EDE-A83-51GS Ground Sensor Relay A83 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -31 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 39 EDE-US-61 480 V Bus 61 Unit Substation 310014 B 310442 CB-F-1B-A X X X - AD2 EDE-AD2-52 480 V AC Circuit Breaker AD2 CB-F-1B-A 310103 AD2a AD2b CBA-FN-32 CBA-FN-33 EDE-X-5C EDE-US-51 EDE-X-5C 4160-480 V Distribution Transformer AD1 CB-F-1B-A EDE-AD3-FU Fuses AD3 CB-F-1B-A EDE-AD1-LA 6 kV Lightning Arrestors (3) AD1 CB-F-1B-A EDE-AD2-CT Current Transformers (2000/5) AD2 CB-F-1B-A EDE-AD3-AM Ammeter AD3 CB-F-1B-A EDE-AD3-AS Ammeter Switch AD3 CB-F-1B-A 40 EDE-US-62 480 V Bus 62 Unit Substation 310014 B 310442 CB-F-1B-A X X X - AE2 EDE-AE2-52 480 V AC Circuit Breaker AE2 CB-F-1B-A 310103 AE2a AE2b CBA-FN-32 CBA-FN-33 EDE-X-5D EDE-US-52 EDE-X-5D 4160-480 V Distribution Transformer AE1 CB-F-1B-A EDE-AE3-FU Fuses AE3 CB-F-1B-A EDE-AE1-LA 6 kV Lightning Arrestors (3) AE1 CB-F-1B-A EDE-AE2-CT Current Transformers (2000/5) AE2 CB-F-1B-A EDE-AE3-AM Ammeter AE3 CB-F-1B-A EDE-AE3-AS Ammeter Switch AE3 CB-F-1B-A 41 EDE-US-61 480 V Feed to 460 V Motor Control 612 310014 B 310442 CB-F-1B-A X X X - AD6 EDE-AD6-52 480 V AC Circuit Breaker AD6 CB-F-1B-A AD6-B16 AD6-B16/1 310103 AD6 AD6 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-512 42 EDE-US-61 480 V Feed to 460 V Motor Control 614 310014 B 310442 CB-F-1B-A X X X - AA4 EDE-AA4-52 480 V AC Circuit Breaker AA4 CB-F-1B-A AA4-BF0 310103 AA4 AA4 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-514 43 EDE-US-61 480 V Feed to 460 V Motor Control 615 310014 B 310442 CB-F-1B-A X X X - AX9 EDE-AX9-52 480 V AC Circuit Breaker AX9 CB-F-1B-A AX9-B4E AX9-B4E/1 310103 AX9 AX9 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-515 44 EDE-US-62 480 V Feed to 460 V Motor Control 621 310014 B 310442 CB-F-1B-A X X X - AE8 EDE-AE8-52 480 V AC Circuit Breaker AE8 CB-F-1B-A AE8-B19 AE8-B19/1 310103 AE8 AE8 CBA-FN-32 CBA-FN-33 EDE-US-62 EDE-US-52 EDE-MCC-521 45 EDE-US-62 480 V Feed to 460 V Motor Control 622 310014 B 310442 CB-F-1B-A X X X - AW0 EDE-AW0-52 480 V AC Circuit Breaker AW0 CB-F-1B-A AW0-D13 AW0-GZ0 AW0-GZ0/1 310103 AWOa AWOe AWOb AWOc CBA-FN-32 CBA-FN-33 EDE-US-62 EDE-US-52 EDE-MCC-522 EDE-CS-9788-2 Control Switch with Indication GZ0 CB-F-1B-A EDE-SS-9788 Selector Switc h GZ0 CB-F-1B-A EDE-AW0-52H Truck Operated Contact AW0 CB-F-1B-A EDE-AW0-FU Fuses AW0 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -32 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 46 EDE-US-61 Grounding Transformer 310014 B 310442 CB-F-1B-A X X X - AD3 EDE-AD3-XFMR 3-1ø 1 kVA Transformers AD3 CB-F-1B-A - 310103 AE3b - CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 GRD XFMR EDE-AD3-FU Fuses AD3 CB-F-1B-A EDE-AD3-RES Grounding Resistor AD3 CB-F-1B-A EDE-AD3-VM Ground Voltmeters (3) AD3 CB-F-1B-A EDE-AD3-64 Ground Relay AD3 CB-F-1B-A 46a EDE-US-61 480 V Feed to 460 V Motor Control Center 611 310014 B 310442 CB-F-1B-A X X X - AD5 EDE-AD5-52 480 V AC Circuit Breaker AD5 CB-F-1B-A AD5-B15 AD5-B15/1 310103 AD5 AD5 CBA-FN-32 CBA-FN-33 EDE-US-61 EDE-US-51 EDE-MCC-511 47 EDE-US-62 Grounding Transformer 310014 B 310442 CB-F-1B-A X X X - AE3 EDE-AE3-XFMR 3-1ø 1 kVA Transformers AE3 CB-F-1B-A - 310103 AE3b - CBA-FN-32 CBA-FN-33 EDE-US-62 EDE-US-52 GRD XFMR EDE-AE3-FU Fuses AE3 CB-F-1B-A EDE-AE3-RES Grounding Resistor AE3 CB-F-1B-A EDE-AE3-VM Ground Voltmeters (3) AE3 CB-F-1B-A EDE-AE3-64 Ground Relay AE3 CB-F-1B-A 48 EDE-I-1F Uninterruptible Power Supply 310043 B 310442 CB-F-1B-A X X X - HF6 EDE-DD5-52 460 V AC Circuit Breaker DD5 CB-F-1B-A DD5-HF6/1 DN0-HF6/1 310105 DD5a DD5b CBA-FN-32 CBA-FN-33 EDE-MCC-612 EDE-SWG-11B EDE-I-1E EDE-DN0-72 125 V DC Circuit Breaker DN0 CB-F-1B-A EDE-HF6/2-52 460 V AC Inc. Line Circuit Breaker HF6 CB-F-1B-A EDE-HF6/1-72 125 V DC Inc. Line Circuit Breaker HF6 CB-F-1B-A EDE-HF6/3-52 120 V AC Output Circuit Breaker HF6 CB-F-1B-A 48A EDE-CP-1F Static Transfer Switch 310043 B 310442 CB-F-1B-A X X X - E2B EDE-E2B-F1 300A, 600 V Fuse E2B CB-F-1B-A E2B-HF6 E2B-HF6/1 310105 DD5a DD5b CBA-FN-32 CBA-FN-33 EDE-I-1F EDE-CP-1E 49 EDE-PP-1F Vital Instrument Bus 310043 B 310442 CB-F-1B-A X X X - EH0 EDE-EH0/NC-52 120 V AC Circuit Breaker - Inc. Line from EDE-CP-1F (Norm. Closed) EH0 CB-F-1B-A EH0-E2B 310105 DD5a DD5b EH0a CBA-FN-32 CBA-FN-33 EDE-CP-1F EDE-PP-1E EDE-EHO/NO-52 120 V AC Circuit Breaker - Inc. Line from ED-X-31F (Norm. Open) EHO CB-F-1B-A 50 EDE-PP-11F Vital Instrument Bus 310043 B 310442 CB-F-1B-A X X X - E1T EDE-EH0/13-52 120 V AC Circuit Breaker EH0 CB-F-1B-A E1T-EHO 310105 DD5a DD5b E1Ta CBA-FN-32 CBA-FN-33 EDE-PP-1F EDE-PP-11E SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -33 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 51 EDE-BC-1B 125 V DC Battery Charger 310042 B 310442 CB-F-1B-A X X X - HR6 EDE-DA1-52 460 V AC Circuit Breaker DA1 CB-F-1B-A DA1-HR4 DA1-HR6 310107 DA1a DA1f DA1b DA1c CBA-FN-32 CBA-FN-33 EDE-MCC-E612 EDE-BC-1A EDE-DA1-42 Contactor DA1 CB-F-1B-A EDE-DA1-42X Auxiliary Relay DA1 CB-F-1B-A DG-HR4-HR9(K20) EPS Relay HR4 CB-F-1B-A EDE-HR6/1-52 460 V AC Circuit Breaker - Incoming Feed HR6 CB-F-1B-A EDE-DA1-FU Fuse DA1 CB-F-1B-A 52 EDE-B-1B 125 V DC Battery 310042 B 310442 CB-F-1F-A X X X - HV5 EDE-J76-FU-1,2,3,4 1600A Fuses J76 CB-F-1B-A HV5-J76 NV5-J76/1 310107 DA1a DA1f DA1b DA1c CBA-FN-32 CBA-FN-33 CBA-FN-21B EDE-BC-1B EDE-SWG-11B EDE-B-1A EDE-J76-SH 1000A, 100 MV Shunt J76 CB-F-1B-A EDE-J76-ATR Shunt Amplifier J76 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -34 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 53 EDE-SWG-11B 125 V DC Switchboard Auxiliary Buses 120 V AC and 125 V DC 310042 B 310442 CB-F-1B-A X X X - DN3 EDE-HR6/2-72 125 V DC Circuit Breaker HR6 CB-F-1B-A DN5-J76 DN5-J76/1 DN4-HR6 310107 DA1a DA1f DA1b DA1c CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-1F EDE-B-1A EDE-BC-1A EDE-SWG-11A EDE-DL5-72 125 V DC Circuit Breaker DL5 CB-F-1B-A EDE-DN4-72 125 V DC Circuit Breaker DN4 CB-F-1B-A EDE-DN5-72 125 V DC Circuit Breaker DN5 CB-F-1B-A EDE-DN5-72 125 V DC Circuit Breaker DN6 CB-F-1B-A EDE-DN3-FU-1,2 10A Fuses DN3 CB-F-1B-A EDE-DN3-27BL Undervoltage Relay DN3 CB-F-1B-A EDE-DN3-27BLL Undervoltage Relay DN3 CB-F-1B-A EDE-DN3-VM DC Voltmeter DN3 CB-F-1B-A EDE-DN3-VTR Voltage Transducer DN3 CB-F-1B-A EDE-DN3-DIO Diodes DN3 CB-F-1B-A EDE-DN3-XS Selector Switch DN3 CB-F-1B-A EDE-DN3-AMY Ammeter Relay DN3 CB-F-1B-A EDE-EH0/5-52 120 V AC Circuit Breaker EH0 CB-F-1B-A DN3-EH0 DN3-J76/1 310105 EH0a EHOb 310107 DA1a DA1f DA1c 5b EDE-DN3-27BL Undervoltage Relay DN3 CB-F-1B-A EDE-DN3-62BL Timing Relay DN3 CB-F-1B-A EDE-DN3-27BLL Undervoltage Relay DN3 CB-F-1B-A EDE-DN3-62BLL Timing Relay DN3 CB-F-1B-A EDE-DN4-72 Breaker Operated Contact DN4 CB-F-1B-A EDE-DN4-72STC Circuit Breaker Shut Trip Coil DN4 CB-F-1B-A EDE-DN3-VTR Voltage Transducer DN3 CB-F-1B-A EDE-J76-ATR Current Transducer J76 CB-F-1B-A EDE-DN3-AMY Ammeter Relay DN3 CB-F-1B-A EDE-DN3-FU 120 V AC 15A and 1A Fuses DN3 CB-F-1B-A EDE-DN3-52 120 V AC Incoming Feed Circuit Breaker DN3 CB-F-1B-A 54 EDE-PP-111B 125 V DC Distribution Panel 310042 B 310442 CB-F-1B-A X X X - E94 EDE-DN7-72 125 V DC Circuit Breaker DN7 CB-F-1B-A DN7-E94 310107 DA1a DA1f E94a CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-111A EDE-E94-72 125 V DC Circuit Breaker (Main) E94 CB-F-1B-A 55 EDE-PP-112B 125 V DC Distribution Panel 310042 B 310442 CB-F-1B-A X X X - E88 EDE-DN9-72 125 V DC Circuit Breaker DN9 CB-F-1B-A DN9-E88 310107 DA1a DA1f E88a CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-112A EDE-E88-72 125 V DC Circuit Breaker (Main) E88 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 13 Table RSS 3.1.3.17 -35 FUNCTION: ELECTRICAL DISTRIBUTION EMERGENCY PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 56 EDE-PP-113B 125 V DC Distribution Panel 310042 B 310442 CB-F-1B-A X X X - E2U EDE-DP2-72 125 V DC Circuit Breaker DP2 CB-F-1B-A DP2-E2U 310107 DA1a DA1f DA1b E2Ua CBA-FN-32 CBA-FN-33 EDE-SWG-11B EDE-PP-113A EDE-E2U-72 125 V DC Circuit Breaker (Main) E2U CB-F-1B-A 57 EDE-SWG-6 4160 V SWG 125 V DC Control Bus B 310442 CB-F-1B-A X X X - A73 EDE-E94/1-72 125 V DC Circuit Breaker E94 CB-F-1B-A A73-E94 310107 E94a E94b 310102 5i, 5j, 5k, 5l CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-SWG-5 EDE-A73-8 125 V DC Circuit Breaker (Main) A73 CB-F-1B-A 58 EDE-US-61 480 V Unit Substation 125 V DC Control Bus B 310442 CB-F-1B-A X X X - AD3 EDE-E94/2-72 125 V DC Circuit Breaker E94 CB-F-1B-A AD3-E94 310107 E94a E94b 310103 5q CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-US-51 EDE-AD3-8 125 V DC Circuit Breaker (Main) AD3 CB-F-1B-A 59 EDE-US-62 480 V Unit Substation 125 V DC Control Bus B 310442 CB-F-1B-A X X X - AE3 EDE-E94/3-72 125 V DC Circuit Breaker E94 CB-F-1B-A AE3-E94 310107 E94a E94b 310103 5r CBA-FN-32 CBA-FN-33 EDE-PP-111B EDE-US-52 EDE-AE3-8 125 V DC Circuit Breaker (Main) AE3 CB-F-1B-A 60 DG-CP-76A Diesel Generator 1B Control Panel Cubicle 3 125 V DC Supply 310010 310042 B 310524 DG-F-2B-A X X X - G20 EDE-DP1-72 125 V DC Circuit Breaker DP1 CB-F-1B-A DP1-G20 310102 DP1a DP1b 310107 DA1a DAH-FN-25B DAH-FN-26B EDE-SWG-11B CBA-FN-32 CBA-FN-33 DG-CP-75A DG-G20-72 125 V DC Circuit Breaker (Main) G20 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -1 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 DG-DG-1A Diesel Generator 1A DG-20462 A 310524 DG-F-2A-A X X X X HA1 DG-CS-9510-2 Control Switch (Push Button) G07 DG-F-2A-A A54-G06/5 E93-G29/1 A54-G29 G06-G29 G06-G29/1 G06-HR2 C06-G29/2 G07-G29 310857 E93/8a E93/8n E93/8b E93/8p E93/8c E93/8d E93/8e E93/8f E93/8g E93/8r CBA-FN-19 CBA-FN-20 DAH-FN-25A DAH-FN-26A EDE-PP-111A D/G Starting Air DG-DG-1B DG-CS-9511 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9512-3 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9512-4 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9517-2 Control Switch (Push Button) G07 DG-F-2A-A DG-CS-9518-2 Control Switch (Push Button) G07 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A DG-G29-OP2 Oil Pressure Relay G29 DG-F-2A-A DG-G29-CR1 Ready for Auto Start Relay G29 DG-F-2A-A DG-G29-4A Start Relay G29 DG-F-2A-A DG-G29-T2A Cranking Time Control Time Delay Relay G29 DG-F-2A-A DG-ZL-9580-9 Start Ckt No 1 Signal Indicating Light G07 DG-F-2A-A DG-G29-ES1 Emergency Start Relay G29 DG-F-2A-A DG-G10-TSR1 Test Start Relay G10 DG-F-2A-A DG-G10-TSR2 Test Start Relay G10 DG-F-2A-A DG-G10-TSR3 Test Start Relay G10 DG-F-2A-A DG-G10-RDT Ramp Down Time Relay G10 DG-F-2A-A DG-G07-IOT Idle Operate Time Relay G07 DG-F-2A-A DG-G06-LSRX Low Speed Auxiliary Relay G06 DG-F-2A-A DG-FY-AS1 Air Start Solenoid Valve G29 DG-F-2A-A DG-G29-OP3 Oil Pressure Relay G29 DG-F-2A-A DG-G29-CR2 Ready for Auto Start Relay G29 DG-F-2A-A DG-G29-4B Start Relay G29 DG-F-2A-A DG-G29-T2B Cranking Time Control Time Delay Relay G29 DG-F-2A-A DG-ZL-9580-10 Start Ckt No 2 Signal Indicating Light G07 DG-F-2A-A DG-G29-ES2 Emergency Start Relay G29 DG-F-2A-A DG-FY-AS2 Air Start Solenoid Valve G29 DG-F-2A-A DG-G29-OP4 Oil Pressure Relay G29 DG-F-2A-A DG-G29-5E Emergency Stop Relay G29 DG-F-2A-A DG-G29-5 Normal Stop Relay G29 DG-F-2A-A

.* Table notes on last page of table

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -2 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-G29-5A Shutdown Relay G29 DG-F-2A-A DG-FY-SDS Shutdown Solenoid Valve G29 DG-F-2A-A DG-FY-CSV-A Jacket Coolant Auxiliary Valves Solenoid G29 DG-F-2A-A DG-G29-T3A Alarm Set Time Delay Relay G29 DG-F-2A-A DG-G29-TR Engine Velocity Transmitter G29 DG-F-2A-A DG-FY-ISV-A Intercooler Auxiliary Valves Solenoid G29 DG-F-2A-A DG-G29-SG Signal Generator G29 DG-F-2A-A DG-G29-HSR High-Speed Relay G29 DG-F-2A-A DG-G29-LSR Low-Speed Relay G29 DG-F-2A-A DG-G29-ASR Starting Air Shutoff Relay G29 DG-F-2A-A DG-G29-IPC Coolant Pump Control Relay G29 DG-F-2A-A DG-G29-BDR Barring Device Relay G29 DG-F-2A-A DG-G29-ASA Air Start Relay G29 DG-F-2A-A DG-G29-ASB Air Start Relay G29 DG-F-2A-A EDE-ZL-9574 Monitoring Circuit Indicator Light G07 DG-F-2A-A DG-G29-TACH Tachometer G29 DG-F-2A-A DG-G29-SFR Start Failure Relay G29 DG-F-2A-A EDE-ZL-9574-1 Monitoring Circuit Indicating Light G29 DG-F-2A-A DG-G29-SDR Engine Trouble Shutdown Relay G29 DG-F-2A-A DG-G29-EOR Engine Overspeed Relay G29 DG-F-2A-A EDE-A69-RLA SI Signal Lockout Relay A69 CB-F-1A-A DG-G29-OTH High Oil Temperature Relay G29 DG-F-2A-A DG-G29-CTH High Coolant Temperature Relay G29 DG-F-2A-A DG-G29-ESX Emergency Start Auxiliary Relay G29 DG-F-2A-A EDE-A54-TD2 Test Device A54 CB-F-1A-A EDE-A69-TD2 Test Device A69 CB-F-1A-A DG-G29-EST Emergency Start Time Delay Relay G29 DG-F-2A-A DG-G29-RA1 Air Pressure Auxiliary Relay G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -3 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-G29-RA2 Air Pressure Auxiliary Relay G29 DG-F-2A-A DG-G29-CF3 Power Available Relay G29 DG-F-2A-A DG-G29-CF1 Power Available Relay G29 DG-F-2A-A DG-G29-CF2 Power Available Relay G29 DG-F-2A-A DG-G29-CF5 Power Available Relay G29 DG-F-2A-A DG-G29-OP1 Oil Pressure Relay G29 DG-F-2A-A DG-G29-FPL Fuel Pressure Relay G29 DG-F-2A-A DG-G29-CPL Jacket Coolant Pressure Relay G29 DG-F-2A-A DG-G29-IPL Intercooler Pressure Relay G29 DG-F-2A-A DG-PS-OPL1 Oil Low Pressure Switch G29 DG-F-2A-A DG-PS-PPLA Fuel Low Pressure Switch G29 DG-F-2A-A DG-PS-CPLA Jacket Coolant Low Pressure Switch G29 DG-F-2A-A DG-PS-IPLA Intercooler Low Pressure Switch G29 DG-F-2A-A DG-G29-OPC Oil Pump Control Relay G29 DG-F-2A-A DG-G29-FPC Auxiliary Fuel Oil Pump Control Relay G29 DG-F-2A-A DG-G29-CPC Coolant Pump Control Relay G29 DG-F-2A-A DG-G29-CF4 Power Available Relay G29 DG-F-2A-A DG-G07-R43L1 Selector Switch Auxiliary Latch Relay (Local) G07 DG-F-2A-A DG-G07-R43L2 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G07 DG-F-2A-A DG-G07-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G07 DG-F-2A-A DG-G07-R43R2 Selector Switch Auxiliary Latch Relay (Remote) G07 DG-F-2A-A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-HR2-PR1 ESP Auxiliary Relay HR2 CB-F-1A-A DG-HR2-PRIX EPS Auxiliary Relay HR2 CB-F-1A-A DG-G29-D1 P-H Junction Diode G29 DG-F-2A-A DG-SS-EOS Engine Overspeed Switch G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -4 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-PS-APL1 Air Pressure Low Switch G29 DG-F-2A-A DG-PS-APL2 Air Pressure Low Switch G29 DG-F-2A-A DG-PS-CPS Coolant Pressure Switch G29 DG-F-2A-A DG-PS-OPL2 Oil Low Pressure Switch G29 DG-F-2A-A DG-PS-OPL3 Oil Low Pressure Switch G29 DG-F-2A-A DG-PS-OPL4 Oil Low Pressure Switch G29 DG-F-2A-A DG-G29-CTH-1 Coolant High Temperature Auxiliary Relay G29 DG-F-2A-A DG-G29-OTH-1 Oil High Temperature Auxiliary Relay G29 DG-F-2A-A DG-ZS-BD1 Barring Device Position Switch G29 DG-F-2A-A DG-ZS-BD2 Barring Device Position Switch G29 DG-F-2A-A EDE-A54-86DP DG Primary Protection Lockout Relay A54 CB-F-1A-A EDE-A69-86DB DG Backup Protection Lockout Relay A69 CB-F-1A-A EDE-A54-TS Test Start Control Switch A54 CB-F-1A-A DG-G29-FU 10 Amp Fuses (10) G29 DG-F-2A-A DG-G29-TRP TR Control Power Relay G29 DG-F-2A-A DG-G29-5B Shutdown Auxiliary Relay G29 DG-F-2A-A EDE-G07-FU-17, 18 6 Amp Fuses (2) G07 DG-F-2A-A DM9-G10 310102 G07/2a G07/2g G07/2b G07/2c DM9a DM9b EDE-SS-9700 Selector Switch G06 DG-F-2A-A DAH-FN-25A DAH-FN-25B DG-CP-75A EDE-SWG-11A DG-G07-CF6 Auxiliary Relay G07 DG-F-2A-A DG-G07-R43L1 Selector Switch Auxiliary Latch Relay (Local) G07 DG-F-2A-A DG-G07-R43L3 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L5 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R2 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -5 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G07 DG-F-2A-A DG-G07-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G07 DG-F-2A-A EDE-G06-FU-9, 10 50 Amp Fuses G06 DG-F-2A-A A69-G06 G06-HF7 A69-HN0 DH9-G10 310102 HA1a HA1c HA1b HA1d DM9a DM9b DAH-FN-25A DAH-FN-26A CBA-FN-19 EDE-SWG-11A DG-A69, XFMR Grounding Transformer A69 CB-F-1A-A DG-HF7-XF DG Field HF7 DG-F-2A-A DG-G07-SERV-PC Static Exciter Voltage Regulator Power Chassis G06 DG-F-2A-A DG-SM-9585 Governor Control (2301A) G06 DG-F-2A-A DG-GT3-PT1 Potential Transformer GT3 DG-F-2A-A DG-GT3-PT2 Potential Transformer GT3 DG-F-2A-A DG-GT3-PPT4 Power Transformer GT3 DG-F-2A-A DG-HNO-NCB DG Neutral Connection Box HNO DG-F-2A-A DG-GT3-CCT Current Transformer 2000/5 GT3 DG-F-2A-A DG-G10-IDR1 Isochronous Droop Relay G10 DG-F-2A-A EDE-A69-60 Voltage Balance Relays A69 CB-F-1A-A DG-G06-K2 Field Flashing Contractor G06 DG-F-2A-A DG-G06-64F Generator Field Failure Relay G06 DG-F-2A-A DG-G10-SEVR-CC Static Exciter Voltage Regulator Control Chassis G10 DG-F-2A-A DG-GT3-XCT1, 2, 3 Generator Current Transformers (2000/5) GT3 DG-F-2A-A DG-VM-9702-2 Field Voltmeter G10 DG-F-2A-A DG-G10-DCT Field Voltage Transducer G10 DG-F-2A-A DG-G06-SH 50 mV Field Shunt G06 DG-F-2A-A DG-AM-9702-2 DC Field Ammeter G10 DG-F-2A-A DG-G10-ATR Current Transducer G10 DG-F-2A-A DG-G10-CF10 Loss of Power Relay G10 DG-F-2A-A DG-A69-64 Ground Fault Sensing Relay A69 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -6 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-G10-FU-22, 23 1 Amp Fuses G10 DG-F-2A-A DG-G07-IL10 Diode Failure Light G07 DG-F-2A-A EDE-G06-FU-1, 2 10 Amp Fuses (2) G06 DG-F-2A-A G06-G29/5 DM9-G10 310102 G06/1a G06/1f G06/1b G06/1c G06/1d DM9a DM9b DAH-FN-25A DAH-FN-26A DG-CP-75A EDE-SWG-11A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A EDE-CS-9820-2 Control Switch (Push Button) G10 DG-F-2A-A DG-G29-HSR High Speed Relay G29 DG-F-2A-A DG-G29-LSR Low Speed Relay G29 DG-F-2A-A DG-G29-ES1 Emergency Start Relay G29 DG-F-2A-A DG-G29-ES2 Emergency Start Relay G29 DG-F-2A-A DG-SS-9585 Selector Switch G07 DG-F-2A-A DG-ZL-9580-11 Field Flash Signal Indicating Light G10 DG-F-2A-A DG-G07-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G07 DG-F-2A-A DG-G29-5A DG - Shutdown Relay G29 DG-F-2A-A DG-G06-LSRX Low Speed Auxiliary Relay G06 DG-F-2A-A DG-G06-LSRXX Time Delay Relay G06 DG-F-2A-A EDE-CS-9801-1 Push Button G10 DG-F-2A-A EDE-CS-9801-2 Push Button G10 DG-F-2A-A DG-G06-SERV-PC Static Exciter Voltage Regulator Power Chassis G06 DG-F-2A-A DG-G10-NM Null Meter G10 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-CS-9821-2 Control Switch G10 DG-F-2A-A EDE-CS-9822-2 Control Switch G10 DG-F-2A-A DG-G10-RR Regulator Relay G10 DG-F-2A-A DG-G10-SERV-CC Static Exciter Voltage Regulatory Control Chassis DG-G10-CF-8 Loss of Power Relay G10 DG-F-2A-A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G10 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -7 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) EDE-G06-FU-3, 4 6 Amp Fuses (2) G06 DG-F-2A-A G06-G29/6 G06-G29/8 G06-G29/9 EC7-G10 EC7-G07 EC7-HR2 DM9-G10 310102 G06/2a G06/2d G06/2b G06/2e DM9a DM9b DAH-FN-25A DAH-FN-26A DG-CP-75A EDE-SWG-11A DG-C10-IDR1 Isochronous Droop Relay G10 DG-F-2A-A DG-G10-IDR2 Isochronous Droop Relay G10 DG-F-2A-A DG-SZ-9585 Governor Actuator G29 DG-F-2A-A DG-SC-9585 Digital Reference Unit (DRU) G06 DG-F-2A-A DG-SM-9585 2301A Governor Controller G06 DG-F-2A-A DG-ST-9585 Magnetic Pickup (MPU-1) G29 DG-F-2A-A DG-SS-9585 Selector Switch G07 DG-F-2A-A DG-G10-TSR1 Test Start Relay G10 DG-F-2A-A DG-G10-TSR2 Test Start Relay G10 DG-F-2A-A DG-G10-TSR3 Test Start Relay G10 DG-F-2A-A DG-G10-R21 Speed Adjust Auxiliary Relay G10 DG-F-2A-A DG-G10-RDT Ramp Down Time Relay G10 DG-F-2A-A DG-G07-IOT Idle Operate Time Relay G07 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-CS-9823-2 Control Switch G06 DG-F-2A-A DG-G06-LSRX Low Speed Auxiliary G06 DG-F-2A-A DG-G29-ES1 Emergency Start Auxiliary Relay G29 DG-F-2A-A DG-G29-ES2 Emergency Start Auxiliary Relay G29 DG-F-2A-A DG-G07-ESS Emergency Start Auxiliary Relay G07 DG-F-2A-A DG-G10-CF-9 Loss of Power Relay G10 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-HR2-PR1 EPS Auxiliary Relay HR2 CB-F-1A-A DG-HR2-HR8 EPS Auxiliary Relay HR2 CB-F-1A-A DG-EC7-R1 Auxiliary Relay EC7 DG-F-2A-A DG-G10-IDR4 Isochronous Droop Relay G10 DG-F-2A-A EDE-G10-FU-7, 8 10 Amp Fuses (2) G10 DG-F-2A-A A54-G10/1 A69-G10 G10-G29 DM9-G10 G10a G10e G10b G10c DM9a DM9b DAH-FN-25A DAH-FN-26A CBA-FN-19 CBA-FN-20 DG-CP-75A EDE-SWG-11A DG-G29-CR1 Auto Start Ready Relay G29 DG-F-2A-A DG-G29-CR2 Auto Start Ready Relay G29 DG-F-2A-A DG-G29-RA1 Air Pressure Auxiliary Relay G29 DG-F-2A-A DG-G29-RA2 Air Pressure Auxiliary Relay G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -8 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) DG-G07-R43L3 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-ESS Emergency Start Auxiliary Relay G07 DG-F-2A-A DG-G10-RR Regulator Relay G10 DG-F-2A-A DG-G07-R43L4 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43L5 Selector Switch Auxiliary Relay (Local) G07 DG-F-2A-A DG-G07-R43R3 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R4 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R5 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G07-R43R6 Selector Switch Auxiliary Relay (Remote) G07 DG-F-2A-A DG-G06-64F Generator Field Ground Relay G06 DG-F-2A-A DG-G10-64FX Generator Field Ground Auxiliary Relay G10 DG-F-2A-A DG-G07-64FXA Generator Field Ground Auxiliary Relay G07 DG-F-2A-A EDE-CS-9824-2 Control Switch G10 DG-F-2A-A DG-G10-23 Thermostat G10 DG-F-2A-A DG-G10-23X Thermostat Auxiliary Relay G10 DG-F-2A-A DG-G07-R-DNA Diesel Motor Available Auxiliary Relay G07 DG-F-2A-A DG-G07-R-B/I S.W.C.T Bypass/INOP Auxiliary Relay G07 DG-F-2A-A DG-G10-IDR1 Isochronous Droop Relay G10 DG-F-2A-A DG-G10-IDR2 Isochronous Droop Relay G10 DG-F-2A-A DG-G10-IDR3 Isochronous Droop Relay G10 DG-F-2A-A EDE-ZL-9802-2 Indicating Light G07 DG-F-2A-A DG-G10-IDR4 Isochronous Droop Relay G10 DG-F-2A-A EDE-SS-9700 Selector Switch G06 DG-F-2A-A EDE-SNS-9736-2 Synchronizing Switch G06 DG-F-2A-A EDE-A51-52S Circuit Breaker Operated Contact A51 CB-F-1A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -9 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1A (Continued) EDE-A52-52S Circuit Breaker Operated Contac t A52 CB-F-1A-A EDE-A54-52S Circuit Breaker Operated Contact A54 CB-F-1A-A EDE-A69-60AX Voltage Balance Auxiliary Relay A69 CB-F-1A-A DG-ZL-9580-3 Indicating Light G07 DG-F-2A-A DG-ZL-9518-2 Indicating Light G07 DG-F-2A-A EDE-ZL-9824-1 Indicating Light G10 DG-F-2A-A EDE-ZL-9824-2 Indicating Light G10 DG-F-2A-A DG-ZL-9580-2 Indicating Light G07 DG-F-2A-A DG-ZL-9580-4 Indicating Light G07 DG-F-2A-A DG-ZL-9580-5 Indicating Light G07 DG-F-2A-A DG-G10-CF8 Loss of Control Power Relay G10 DG-F-2A-A DG-G10-CF9 Loss of Control Power Relay G10 DG-F-2A-A DG-G10-CF10 Loss of Control Power Relay G10 DG-F-2A-A DG-G10-CR45 Annunciator Auxiliary Relay G10 DG-F-2A-A DG-G10-CR42 Annunciator Auxiliary Relay G10 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -10 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 2 DG-TK-45A Starting Air Compressor Skid Air Receiver Tank DG-20460 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-TK-45C Notes 1 and 5 3 DG-TK-45B Starting Air Compressor Skid Air Receiver Tank DG-20460 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-TK-45D Notes 1 and 5 4 DG-MM-8A Exhaust Silencer DG-20462 A 310525 DG-F-3E-A X X - - - - - - - - - - - DG-MM-8B Note 1 5 DG-F-36A Air Intake Filter DG-20462 A 310525 DG-F-3E-A X X - - - - - - - - - - - DG-F-36B Note 1 6 DG-TK-26A Fuel Oil Storage Tank DG-20459 A 310525 202264 DG-F-1A-A X X - - - - - - - - - - - DG-TK-26B Notes 1 and 2 7 DG-TK-78A Fuel Oil Day Tank DG-20459 A 310525 DG-F-3C-A X X - - - - - - - - - - - DG-TK-78B Note 1 8 DG-P-38A Fuel Oil Transfer Pump DG-20459 A 310524 202265 DG-F-1A-A X X X - H75 DG-BM-52 460 V AC Circuit Breaker BM7 CB-F-1A-A BE4-BM7 BM7-RT8 BM7-N75 310857 BM7a 8M7c CBA-FN-19 CBA-FN-20 DAH-FN-25A DAH-FN-26A EDE-MCC-521 DG-P-38B DG-CS-9503 Control Switch with Indication BE4 DG-F-2A-A DG-LS-FLC Fuel Low Level Switch RT8 DG-F-3C-A DG-BM7-42 Motor Starter BM7 CB-F-1A-A DG-BM7-49 Thermal Overload Relay BM7 CB-F-1A-A DG-BM7-FU Fuse BM7 CB-F-1A-A 9 DG-P-119A Engine-Driven Fuel Oil Pump DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-119B Notes 1 and 4 10 DG-P-115A Engine-Drive Fuel Oil Pump DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-115B Notes 1 and 4 11 DG-TK-102A Lube Oil Reservoir DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-TK-102B Notes 1 and 4 12 DG-P-228A Engine-Driver Rocker Arm Lube Pump DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-228B Notes 1 and 4 13 DG-E-41A Lube Oil Heat Exchanger DG-2045B A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-E-41B Notes 1 and 4 14 DG-TK-46A Diesel Generator 1A Component Cooling Water Expansion Tank DG-20461 A 310525 DG-F-3C-A X X - - - - - - - - - - - DG-TK-46B Notes 1 and 4 15 DG-E-42A Diesel Generator 1A Component Cooling Water Heat Exchanger DG-20461 A 310767 805217 PAB-F-3A-Z X X - - - - - - - - - - Service Water DG-E-42B Notes 1 and 3 16 DG-P-121A Engine-Driven Jacket Coolant Pump DG-20461 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-121B Notes 1 and 4 17 DG-P-231A Engine-Driven Air Coolant Pump DG-20461 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-P-231B Notes 1 and 4 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -11 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 17a DG-C-2A DG Starting Air Compressor DG-20460 A 310524 DG-F-2A-A X X X - NC3 DG-BM3-52 460 v AC Circuit Breaker BM3 DG-F-2A-A BM3-NC3 BM3-HM2 BM3-HR2 310857 BM3a BM3c DAH-FN-25A DAH-FN-26A EDE-MCC-511 DG-C-2-B Note 5 DG-CS-9559 Control Switch BM3 DG-F-2A-A DGA-PS-APCI Pressure Switch HM2 DG-F-2A-A DG-PS-APCZ Pressure Switch HM2 DG-F-2A-A DG-HR2-HR9 EPS Relay HR2 CB-F-1A-A DG-BM3-42 Motor Starter BM3 CB-F-1A-A DG-BM3-49 Thermal O. L. BM3 CB-F-1A-A DG-BM3-FU Fuse BM3 CB-F-1A-A 17b DG-SKD-17A Diesel Generator 1A Starting Air Compressor Skid DG-20460 A 310524 DG-F-2A-A X X X - HM2 DG-E39/4-52 120 v AC Circuit Breaker E39 DG-F-2A-A E39-HM2 BM3-HM2 310857 E39/4a E39/4b DAH-FN-25A DAH-FN-26A EDE-MCC-E511 120v AC Dist. Panel DG-SKD-17B Note 5 DG-HM2-52 120v AC Circuit Breaker HM2 DG-F-2A-A DG-HM2-ATM Auto Drain Timer HM2 DG-F-2A-A DG-V-253A Auto Drain Solenoid Vlv. HM2 DG-F-2A-A DG-HM2-ICT Motor Synchronous Timer HM2 DG-F-2A-A DG-V-279A Left Chamber Inlet Sol. Vlv. HM2 DG-F-2A-A DG-V-280A Right Chamber Inlet Sol. Vlv. HM2 DG-F-2A-A DG-V-285A Repressurizing Sol. Vlv HM2 DG-F-2A-A DG-V-288A Left Chamber Exhaust Sol. Vlv. HM2 DG-F-2A-A DG-V-289A Right Chamber Exhaust Sol. Vlv. HM2 DG-F-2A-A DG-V-HM2-KR Aux. Relay HM2 DG-F-2A-A DG-BM3-42 Motor Starter BM3 CB-F-1A-A 17c DG-C-18A DG Backup Operating Air Compressor DG-20460 A 310524 DG-F-2A-A X X X - ML7 DG-BS3-52 460 v AC Ckt Bkr. BS3 DG-F-2A-A BS3-ML7 BS3-HM2 310857 BS3a BS3c DAH-FN-25A DAH-FN-26A EDE-MCC-511 DG-C-18B Note 5 DG-BS3-42 Motor Starter BS3 DG-F-2A-A DG-BS3-49 Thermal O. L. BS3 DG-F-2A-A DG-BS3-FU Fuse BS3 DG-F-2A-A DG-CS-9526 Control Switch BS3 DG-F-2A-A DGA-PS-APC3 Pressure Switch HM2 DG-F-2A-A DG-PS-APC4 Pressure Switch HM2 DG-F-2A-A DG-V-325A Unloader Sol. Vlv. UB0 DG-F-2A-A B53-UB0 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -12 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 18 DG-DG-1B Diesel Generator 1B DG-20467 B 310524 DG-F-2B-A X X X X HA2 DG-CS-9520-2 Control Switch (Push Button) G19 DG-F-2B-A A74-G18/7 A74-G30/6 310857 E94/8a E94/8n CBA-FN-32 CBA-FN-33 DG-DG-1A DG-CS-9521 Control Switch (Push Button) G19 DG-F-2B-A E94-G30/1 G18-G30 E94/8b E94/8p E94/8c E94/8r DAH-FN-25B DAH-FN-26B DG-CS-9522-3 Control Switch (Push Button) G19 DG-F-2B-A G18-G30/1 G18-G30/2 E94/8d E94/8e EDE-PP-11B D/G Starting Air DG-CS-9522-4 Control Switch (Push Button) G19 DG-F-2B-A G18-HR4 G19-G30 E94/8f E94/8g DG-CS-9527-2 Control Switch (Push Button) G19 DG-F-2B-A G19-G30/6 G18-G30/8 E94/8s DG-CS-9528-2 Control Switch (Push Button) G19 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A DG-G30-OP2 Oil Pressure Relay G30 DG-F-2B-A DG-G30-CR1 Ready for Auto Start Relay G30 DG-F-2B-A DG-G30-4A Start Relay G30 DG-F-2B-A DG-G30-T2A Cranking Time Control Time Delay Relay G30 DG-F-2B-A DG-ZL-9590-9 Start Ckt No 1 Signal Indicating Light G19 DG-F-2B-A DG-G30-ES1 Emergency Start Relay G30 DG-F-2B-A DG-G20-TSR1 Test Start Relay G30 DG-F-2B-A DG-G20-TSR2 Test Start Relay G20 DG-F-2B-A DG-G20-TSR3 Test Start Relay G20 DG-F-2B-A DG-G20-RDT Ramp Down Time Relay G20 DG-F-2B-A DG-G19-IOT Idle Operate Time Relay G19 DG-F-2B-A DG-G18-LSRX Low Speed Auxiliary Relay G18 DG-F-2B-A DG-FY-AS1 Air Start Solenoid Valve G30 DG-F-2B-A DG-G30-OP3 Oil Pressure Relay G30 DG-F-2B-A DG-G30-CR2 Ready for Auto Start Relay G30 DG-F-2B-A DG-G30-TACH Tachometer G30 DG-F-2B-A DG-G30-4B Start Relay G30 DG-F-2B-A DG-G30-T2B Cranking Time Control Time Delay Relay G30 DG-F-2B-A DG-ZL-9590-10 Start Ckt No 2 Signal Indicating Light G19 DG-F-2B-A DG-G30-ES2 Emergency Start Relay G30 DG-F-2B-A DG-FY-AS2 Air Start Solenoid Valve G30 DG-F-2B-A DG-G30-OP4 Oil Pressure Relay G30 DG-F-2B-A DG-G30-5E Emergency Stop Relay G30 DG-F-2B-A DG-G30-5 Normal Stop Relay G30 DG-F-2B-A DG-G30-5A Shutdown Relay G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -13 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-FY-SDS Shutdown Solenoid Valve G30 DG-F-2B-A DG-G30-T3A Alarm Set Time Delay Relay G30 DG-F-2B-A DG-G30-TR Engine Velocity Transmitter G30 DG-F-28-A DG-G30-SG Signal Generator G30 DG-F-2B-A DG-G30-HSR High Speed Relay G30 DG-F-2B-A DG-G30-LSR Low Speed Relay G30 DG-F-2B-A DG-G30-ASR Starting Air Shutoff Relay G30 DG-F-2B-A DG-G30-ASA Air Start Relay G30 DG-F-2B-A DG-G30-ASB Air Start Relay G30 DG-F-2B-A DG-G30-BDR Barring Device Relay G30 DG-F-2B-A DG-G30-SFR Start Failure Relay G30 DG-F-2B-A DG-G30-SDR Engine Trouble Shutdown Relay G30 DG-F-2B-A DG-G30-EOR Engine Overspeed Relay G30 DG-F-2B-A EDE-A89-RLA SI Signal Lockout Relay A89 CB-F-1B-A DG-G30-OTH High Oil Temperature Relay G30 DG-F-2B-A DG-G30-CTH High Coolant Temperature Relay G30 DG-F-2B-A EDE-A74-TD2 Test Device A74 CB-F-1B-A EDE-A89-TD2 Test Device A89 CB-F-1B-A DG-G30-EST Emergency Start Time Delay Relay G30 DG-F-2B-A DG-G30-ESX Emergency Start Auxiliary Relay G30 DG-F-2B-A DG-G30-RA1 Air Pressure Auxiliary Relay G30 DG-F-2B-A DG-G30-RA2 Air Pressure Auxiliary Relay G30 DG-F-2B-A DG-G30-CF3 Power Available Relay G30 DG-F-2B-A DG-G30-CF4 Power Available Relay G30 DG-F-2B-A DG-G19-R43L1 Selector Switch Auxiliary Latch Relay (Local) G19 DG-F-2B-A DG-G19-R43L2 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G19 DG-F-2B-A DG-G30-FU 10 Amp Fuses (10) G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -14 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G19-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G19 DG-F-2B-A DG-G19-R43R2 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-HR4-PR1 EPS Auxiliary Relay HR4 CB-F-1B-A DG-HR4-PRIX EPS Auxiliary Relay HR4 CB-F-1B-A DG-SS-EOS Engine Overspeed Switch G30 DG-F-2B-A DG-PS-APL1 Air Pressure Low Switch G30 DG-F-2B-A DG-PS-APL2 Air Pressure Low Switch G30 DG-F-2B-A DG-PS-CPS Coolant Pressure Switch G30 DG-F-2B-A DG-PS-OPL2 Oil Low Pressure Switch G30 DG-F-2B-A DG-PS-OPL3 Oil Low Pressure Switch G30 DG-F-2B-A DG-G19-FU 10 Amp Fuses (20) G19 DG-F-2B-A DG-G19-R43L5 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-PS-OPL4 Oil Low Pressure Switch G30 DG-F-2B-A DG-G30-CTH-1 Coolant High Temperature Auxiliary Relay G30 DG-F-2B-A DG-G30-OTH-1 Oil High Temperature Auxiliary Relay G30 DG-F-2B-A DG-ZS-BD1 Barring Device Position Switch G30 DG-F-2B-A DG-G30-D1 P-N Junction Diode G30 DG-F-2B-A DG-ZS-BD2 Barring Device Position Switc h G30 DG-F-2B-A EDE-A74-86DP DG Primary Protection Lockout Relay A74 CB-F-1B-A EDE-A89-86DB DG Backup Protection Lockout Relay A89 CB-F-1B-A EDE-A74-TS Test Start Control Switch A74 CB-F-1B-A DG-G30-CF1 Power Available Relay G30 DG-F-2B-A DG-G30-CF2 Power Available Relay G30 DG-F-2B-A EDE-ZL-9594 Monitoring Circuit Indicating Light G19 DG-F-2B-A EDE-ZL-9594-1 Monitoring Circuit Indicating Light G30 DG-F-2B-A DG-PS-OPL1 Oil Low Pressure Switch G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -15 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G30-OP1 Oil Pressure Relay G30 DG-F-2B-A DG-PS-FPLA Fuel Low Pressure Switch G30 DG-F-2B-A DG-G30-FPL Fuel Pressure Relay G30 DG-F-2B-A DG-PS-CPLA Jacket Coolant Low Pressure Switch G30 DG-F-2B-A DG-G30-CPL Jacket Coolant Pressure Relay G30 DG-F-28-A DG-PS-IPLA Intercooler Low Pressure Switch G30 DG-F-2B-A DG-G30-IPL Intercoolant Pressure Relay G30 DG-F-2B-A DG-G30-CF5 Power Available Relay G30 DG-F-2B-A DG-G30-OPC Oil Pump Control Relay G30 DG-F-2B-A DG-G30-FPC Auxiliary Fuel Oil Pump Control Relay G30 DG-F-2B-A DG-G30-CPC Coolant Pump Control Relay G30 DG-F-2B-A DG-G30-5B Shutdown Auxiliary Relay G30 DG-F-2B-A DG-G30-TRP TR Control Power Relay G30 DG-F-2B-A DG-FY-CSV-B Jacket Coolant Auxiliary Valves Solenoid G30 DG-F-2B-A DG-G30-IPC Coolant Pump Control Relay G30 DG-F-2B-A DG-FY-ISV-B Intercoolant Auxiliary Valves Solenoid G30 DG-F-2B-A EDE-G19-FU-17, 18 6 Amp Fuses (2) G19 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A DG-G19-CF6 Auxiliary Relay G19 DG-F-2B-A DPI-G20 310102 DG-G19-R43L1 Selector Switch Auxiliary Latch Relay (Local) G19 DG-F-2B-A G19/2a G19/2g G19/2b G19/2c DP1A DP1b DAH-FN-25B DAH-FN-26B DG-CP-75B DG-G19-R43L2 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A EDE-SWG-11B DG-G19-R43L3 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L5 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43R1 Selector Switch Auxiliary Latch Relay (Remote) G19 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -16 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G19-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G19 DG-F-2B-A DG-G19-R43R2 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43L6 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-FU17B, 18B 6 Amp Fuses (2) G19 DG-F-2B-A EDE-G18-FU-9, 10 50 Amp Fuses G18 DG-F-2B-A DG-A89-XFMR Grounding Transformer A89 CB-F-1B-A A89-G18 G18-HF8 A89-HP1 DP1-G20 310102 HA2a HA2c HA2b HA2d DP1a DP1b DAH-FN-25B DAH-FN-26B CBA-FN-32 CBA-FN-33 EDE-SWG-11B DG-HF8-XF D-F Field HF8 DG-F-2B-A DG-G18-SEVR-PC Static Exciter Voltage Regulator Power Chassis G18 DG-F-2B-A DG-SM-9587 Governor Control (2301A) G18 DG-F-2B-A DG-G20-SEVR-CC Voltage Regulator Control Chassis G20 DG-F-2B-A DG-GT4-PT1 Potential Transformer GT4 DG-F-2B-A DG-GT4-PT2 Potential Transformer GT4 DG-F-2B-A DG-GT4-PPT4 Power Transformer GT4 DG-F-2B-A DG-GT4-CCT Current Transformer 2000/5 GT4 DG-F-2B-A DG-G20-IDR1 Isochronous Droop Relay G20 DG-F-2B-A EDE-A89-60 Voltage Balance Relays A89 CB-F-1B-A DG-G20-64F Generator Field Failure Relay G20 DG-F-2B-A DG-HP1-NCB DG Neutral Connection Box HP1 DG-F-2B-A DG-GT4-XCT1, 2, 3 Generator Current Transformers (2000/5) A, B, C GT4 DG-F-2B-A DG-VM-9712-2 Field Voltmeter G20 DG-F-2B-A DG-G20-DCT Field Voltage Transducer G20 DG-F-2B-A DG-G18-SH 50 mV Field Shunt G18 DG-F-2B-A DG-AM-9712-2 DG Field Ammeter G20 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -17 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G20-ATR Current Transducer G20 DG-F-2B-A DG-G20-CF10 Loss of Power Relay G20 DG-F-2B-A DG-A89-64 Ground Fault Sensing Relay A89 CB-F-1B-A DG-G20-FU-22, 23 1 Amp Fuses G20 DG-F-2B-A DG-G19-IL10 Diode Failure Light G19 DG-F-2B-A DG-G20-K2 Field Flashing Contactor G20 DG-F-2B-A EDE-G18-FU-1, 2, 1B, 2B 10 Amp Fuses (4) G18 DG-F-2B-A G18-G30/5 DP1-G20 310102 G18/1a G18/1f DAH-FN-25B DAH-FN-26B DG-G19-R34R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A G18/1b G18/1c G18/1d DC-CP-75B EDE-SWG-11B EDE-CS-9825-2 Control Switch (Push Button) G20 DG-F-2B-A DP1a DP1b DG-G30-HSR High Speed Relay G30 DG-F-2B-A DG-G30-LSR Low Speed Relay G30 DG-F-2B-A DG-G30-ES1 Emergency Start Relay G30 DG-F-2B-A DG-G30-ES2 Emergency Start Relay G30 DG-F-2B-A DG-SS-9587 Selector Switch G19 DG-F-2B-A DG-ZL-9590-11 Field Flash Signal Indicating Light G20 DG-F-2B-A DG-G19-R43M1 Selector Switch Auxiliary Latch Relay (Maintenance) G19 DG-G30-5A DG Shutdown Relay G30 DG-F-2B-A DG-G18-LSRX Low Speed Auxiliary Relay G30 DG-F-2B-A DG-G18-LSRXX Time Delay Relay G18 DG-F-2B-A EDE-CS-9811-1 Push Button EDE-CS-9811-2 Push Button G18 DG-F-2B-A DG-G18-SEVR-PC Static Exciter Voltage Regulator Power Chassis G20 DG-F-2B-A EDE-G20-NM Null Meter G20 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-CS-9826-2 Control Switch G20 DG-F-2B-A EDE-CS-9827-2 Control Switch G20 DG-F-2B-A DG-G20-RR Regulator Relay G20 DG-F-2B-A DG-G20-SEVR-CC Static Exciter Voltage Regulator Control Chassis G20 DG-F-2B-A DG-G20-CF8 Loss of Power Relay G20 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A EDE-G18-FU-3, 4, 3B, 4B 6 Amp Fuses (4) G18 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -18 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G20-IDR1 Isochronous Droop Relay G20 DG-F-2B-A G18-G30/6 G18-G30/9 G18/2a G18/2d G18/2b DAH-FN-25B DAH-FN-26B DG-G20-IDR2 Isochronous Droop Relay G20 DG-F-2B-A G18-G30/A ED9-G20 ED9-G19 ED9-HR4 G18/2e DG-CP-75B EDE-SWG-75B DG-SZ-9587 Governor Actuator G30 DG-F-2B-A DP1-G20 DP1a DP1b DG-SC-9587 Digital Reference Unit (DRU) G18 DG-F-2B-A DG-SM-9587 2301A Governor Controller G18 DG-F-2B-A DG-ST-9587 Magnetic Pickup (MPU-1) G30 DG-F-2B-A DG-SS-9587 Selector Switch G19 DG-F-2B-A DG-G20-TSR1 Test Start Relay G20 DG-F-2B-A DG-G20-TSR2 Test Start Relay G20 DG-F-2B-A DG-G20-TSR3 Test Start Relay G20 DG-F-2B-A DG-G20-R21 Speed Adjust Auxiliary Relay G20 DG-F-2B-A DG-G20-RDT Ramp Down Time Relay G20 DG-F-2B-A DG-G19-IOT Idle Operate Time Relay G19 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-CS-9828-2 Control Switch G18 DG-F-2B-A DG-G18-LSRX Auxiliary Relay G18 DG-F-2B-A DG-G30-ES1 Emergency Start Auxiliary Relay G30 DG-F-2B-A DG-G19-ESS Emergency Start Auxiliary Relay G19 DG-F-2B-A DG-G30-ES2 Emergency Start Auxiliary Relay G30 DG-F-2B-A DG-G20-CF-9 Loss of Power Relay G20 DG-F-2B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-HR4-PR1 EPS Auxiliary Relay HR4 CB-F-1B-A DG-HR4-HR8 EPS Auxiliary Relay HR4 CF-F-1B-A DG-ED9-R1 Auxiliary Relay ED9 CB-F-1B-A DG-G20-IDR4 Isochronous Droop Relay G20 DG-F-2B-A EDE-G20-FU-7, 8, 7B, 8B 10 Amp Fuses (4) G20 DG-F-2B-A A74-G20/1 G20-G30 G20a G20e G20b DAH-FN-25B DAH-FN-26B DG-G30-CR1 Auto Start Ready Relay G30 DG-F-2B-A A89-G20 DP1-G20 G20c DP1a DP1b CBA-FN-32 CBA-FN-33 DG-G30-CR2 Auto Start Ready Relay G30 DG-F-2B-A DG-CP-75B EDE-SWG-11B DG-G30-RA1 Air Pressure Auxiliary Relay G30 DG-F-2B-A DG-G30-RA2 Air Pressure Auxiliary Relay G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -19 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) DG-G19-R43L6 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R-DNA Diesel Not Available Auxiliary Relay G19 DG-F-2B-A DG-G19-R-B/I S.W.C.T Bypass/Inoperable Auxiliary Relay G19 DG-F-2B-A DG-G19-R43L3 Selector Switch Auxiliary Relay G19 DG-F-2B-A DG-G19-ESS Emergency Start Auxiliary Relay G19 DG-F-2B-A DG-G20-RR Regulator Relay G20 DG-F-2B-A DG-G19-R43L4 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43L5 Selector Switch Auxiliary Relay (Local) G19 DG-F-2B-A DG-G19-R43R3 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R4 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R5 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G19-R43R6 Selector Switch Auxiliary Relay (Remote) G19 DG-F-2B-A DG-G18-64F Generator Field Ground Relay G18 DG-F-2B-A DG-G20-64FX Generator Field Ground Auxiliary Relay G20 DG-F-2B-A DG-G19-64FXA Generator Field Ground Auxiliary Relay G19 DG-F-2B-A EDE-CS-9829-2 Control Switch G20 DG-F-2B-A DG-G19-23 Thermostat G19 DG-F-2B-A DG-G20-23X Thermostat Auxiliary Relay G20 DG-F-2B-A DG-G20-IDR1 Isochronous Droop Relay G20 DG-F-2B-A DG-G20-IDR2 Isochronous Droop Relay G20 DG-F-2B-A DG-G20-IDR3 Isochronous Droop Relay G20 DG-F-2B-A DG-G20-IDR4 Isochronous Droop Relay G20 DG-F-2B-A EDE-SS-9710 Selector Switch G18 DG-F-2B-A EDE-SNS-9737-2 Synchronizing Switch G18 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -20 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS DG-DG-1B (Continued) EDE-A71-52S Circuit Breaker Operated Contact A71 CB-F-1B-A EDE-A72-52S Circuit Breaker Operated Contact A72 CB-F-1B-A EDE-A74-52S Circuit Breaker Operated Contact A74 CB-F-1B-A EDE-A89-60AX Voltage Balance Auxiliary Relay A89 CG-F-1B-A DG-ZL-9590-2 Indicating Light G19 DG-F-2B-A DG-ZL-9590-3 Indicating Light G19 DG-F-2B-A DG-ZL-9528-2 Indicating Light G20 DG-F-2B-A EDE-ZL-9829-1 Indicating Light G19 DG-F-2B-A EDE-ZL-9812-2 Indicating Light G19 DG-F-2B-A EDE-ZL-9829-2 Indicating Light G20 DG-F-2B-A DG-ZL-9590-4 Indicating Light G19 DG-F-2B-A DG-ZL-9590-5 Indicating Light G19 DG-F-2B-A DG-G20-CF8 Loss of Control Power Relay G20 DG-F-2B-A DG-G20-CF9 Loss of Control Power Relay G20 DG-F-2B-A DG-G20-CF10 Loss of Control Power Relay G20 DG-F-2B-A DG-G20-CR45 Annunciator Auxiliary Relay G20 DG-F-2B-A DG-C20-CR42 Annunciator Auxiliary Relay G20 DG-F-2B-A 19 DG-TK-45C Starting Air Compressor Skid Air Receiver Tank DG-20465 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-TK-45A Notes 1 and 7 20 DG-TK-45D Starting Air Compressor Skid Air Receiver Tank DG-20465 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-TK-45B Notes 1 and 7 21 DG-MM-8B Exhaust Silencer DG-20467 B 310525 DG-F-3F-A X X - - - - - - - - - - - DG-MM-8A Note 1 22 DG-F-36B Air Intake Filter DG-20467 B 310525 DG-F-3F-A X X - - - - - - - - - - - DG-F-36A Note 1 23 DG-TK-26B Fuel Oil Storage Tank DG-20464 B 310524 202264 DG-F-1B-A X X - - - - - - - - - - - DG-TK-26A Notes 1 and 2 24 DG-TK-78B Fuel Oil Day Tank DG-20459 B 310525 DG-F-3D-A X X - - - - - - - - - - - DG-TK-78A Note 1 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -21 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 25 DG-P-38B Fuel Oil Transfer Pump DG-20464 B 310524 202264 DG-F-1B-A X X X - N76 DG-BP7-52 460 V AC Circuit Breaker BP7 CB-F-1B-A BE5-BP7 BP7-RU1 BP7-N76 310857 BP7a BP7c CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B DG-F-38A - DG-CS-9506 Control Switch with Indication BE5 DG-F-2B-A DG-LS-FLC Fuel Low Level Control Switch RU1 DG-F-3D-A DG-BP7-42 Motor Starter BP7 CB-F-1B-A DG-BP7-49 Thermal Overload Relay BP7 CB-F-18-A DG-BP7-FU Fuse BP7 CB-F-1B-A 26 DG-P-119B Engine-Driven Fuel Oil Pump DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - DG-P-119A Notes 1 and 6 27 DG-P-115B Engine Driven Lube Oil Pump DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-115A Notes 1 and 6 28 DG-TK-102B Lube Oil Reservoir DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-TK-102A Notes 1 and 6 29 DG-P-228B Engine-Driven Rocker Arm Lube Pump DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-228A Notes 1 and 6 30 DG-E-41B Lube Oil Heat Exchanger DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-E-41A Notes 1 and 6 31 DG-TK-46B Diesel Generator 1B Component Cooling Water Expansion Tank DG-20466 B 310525 DG-F-3D-A X X - - - - - - - - - - - DG-TK-46A Note 1 32 DG-E-42B Diesel Generator 1B Component Cooling Water Heat Exchanger DG-20466 B 310767 805217 PAB-F-3A-Z X X - - - - - - - - - - Service Water DG-E-42A Notes 1 and 3 33 DG-P-121B Engine-Driven Jacket Coolant Pump DG-20466 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-P-121A Notes 1 and 4 34 DG-P-231B Engine-Driven Air Coolant Pump DG-20466 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-231A Notes 1 and 6 35 DG-PV-7A-2 Lube Oil Cooler Differential Pressure Control Valve DG-20461 A 310524 DG-F-2A-A X X - X HA1 DG-PT-7A-3 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-PV-7B-2 Note 8 DG-PT-7A-4 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A DG-PDT-7A-2 Differential Pressure Transmitter G29 DG-F-2A-A DG-PDC-7A-2 Differential Pressure Controller G29 DG-F-2A-A 36 DG-TCV-7A-2 Air Cooler Coolant Temperature Control Valve DG-20461 A 310524 DG-F-2A-A X X X X HA1 DG-CP-907A Air Cooler Coolant and Jacket Coolant Temp. Control Panel G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-TCV-7B-2 Note 8 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -22 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 37 DG-PV-7A-1 Jacket Coolant Differential Pressure Control Valve DG-20461 A 310524 DG-F-2A-A X X - X HA1 DG-PT-7A-1 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-PV-7B-1 Note 9 DG-PT-7A-2 Pressure Relay Pneumatic Transmitter G29 DG-F-2A-A DG-PDT-7A-1 Differential Pressure Transmitter G29 DG-F-2A-A DG-PDC-7A-1 Differential Pressure Controller G29 DG-F-2A-A 38 DG-TCV-7A-1 Air Cooler Coolant Temperature Control Valve DG-20461 A 310524 DG-F-2A-A X X X X HA1 DG-CP-907A Air Cooler Coolant and Jacket Coolant Temp. Control Panel G29 DG-F-2A-A - - - DAH-FN-25A DAH-FN-26A D/G Starting Air DG-TCV-7B-1 Note 9 39 DG-F-64A Lube Oil Filter DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-F-64B Notes 1 and 4 40 DG-F-23A Lube Oil Duplex Filter DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-F-23B Notes 1 and 4 41 DG-S-4A Lube Oil Strainer DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-S-4B Notes 1 and 4 42 DG-S-85A Lube Oil Sump Suction Strainer DG-20458 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-S-85B Notes 1 and 4 43 DG-S-5A Fuel Oil Storage Tank Duplex Strainer DG-20459 A 310524 202264 DG-F-1A-A X X - - - - - - - - - - - DG-S-5B Notes 1 and 2 44 DG-S-6A Fuel Oil Day Tank Duplex Strainer DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-S-6B Notes 1 and 4 45 DG-F-65A Fuel Oil Duplex Filter DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-F-65B Notes 1 and 4 46 DG-TK-110A Fuel Oil Accumulator Tank DG-20459 A 310524 DG-F-2A-A X X - - - - - - - - - - - DG-TK-110B Notes 1 and 4 47 DG-PV-7B-2 Lube Oil Cooler Differential Pressure Control Valve DG-20466 B 310524 DG-F-2B-A X X - X HA2 DG-PT-7B-3 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DC-PV-7A-2 Note 10 DG-PT-7B-4 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A DG-PDT-7B-2 Differential Pressure Transmitter G30 DG-F-2B-A DG-PDC-7B-2 Differential Pressure Controller G30 DG-F-2B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -23 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 48 DG-TCV-7B-2 Air Cooler Coolant Temperature Control Valve DG-20466 B 310524 DG-F-2B-A X X X X HA2 DG-CP-907B Air Cooler Coolant and Jacket Coolant Temp. Control Panel G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DG-TCV-7A-2 Note 10 49 DG-PV-7B-1 Jacket Coolant Differential Pressure Control Valve DG-20466 B 310524 DG-F-2B-A X X - X HA2 DG-PT-7B-1 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DG-PV-7A-1 Note 11 DG-PT-7B-2 Pressure Relay Pneumatic Transmitter G30 DG-F-2B-A DG-PDT-7B-1 Differential Pressure Transmitte r G30 DG-F-2B-A DG-PDC-7B-1 Differential Pressure Controller G30 DG-F-2B-A 50 DG-TCV-7B-1 Jacket Coolant Temperature Control Valve DG-20466 B 310524 DG-F-2B-A X X X X HA2 DG-CP-907B Air Cooler Coolant and Jacket Coolant Temp. Control Panel G30 DG-F-2B-A - - - DAH-FN-25B DAH-FN-26B D/G Starting Air DG-TCV-7A-1 Note 11 51 DG-F-64B Lube Oil Filter DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-64A Notes 1 and 6 52 DG-F-23B Lube Oil Duplex Filter DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-23A Notes 1 and 6 53 DG-S-4B Lube Oil Strainer DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-S-4A Notes 1 and 6 54 DG-S-85B Lube Oil Sump Suction Strainer DG-20463 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-S-85A Notes 1 and 6 55 DG-S-5B Fuel Oil Storage Tank Duplex Strainer DG-20464 B 310524 202264 DG-F-1B-A X X - - - - - - - - - - - DG-S-5A Notes 1 and 2 56 DG-S-6B Fuel Oil Day Tank Duplex Strainer DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-S-6A Notes 1 and 6 57 DG-F-65B Fuel Oil Duplex Filter DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-F-65A Notes 1 and 6 58 DG-TK-110B Fuel Oil Accumulator Tank DG-20464 B 310524 DG-F-2B-A X X - - - - - - - - - - - DG-TK-110A Notes 1 and 6 59 DG-C-2B DG Starting Air Compressor DG-20465 B 310524 DG-F-2B-A X X X - NC4 DG-BP3-52 DG-CS-9569 DGB-PS-APCI DGB-PS-APCZ DG-HR4-HR9 DG-BP3-42 DG-BP3-49 DG-BP3-FU 460 v AC Circuit Breaker Control Switch Pressure Switch Pressure Switch EPS Relay Motor Starter Thermal O. L. Fuse BP3 BP3 HM3 HM3 HR3 BP3 BP3 BP3 DG-F-2B-A DG-F-2B-A DG-F-2B-A DG-F-2B-A CB-F-1B-A CB-F-1B-A CB-F-1B-A CB-F-1B-A BP3-NC4 BP3-HM3 BP3-HR4 310857 BP3a BP3c DAH-FN-25B DAH-FN-26B EDE-MCC-611 DG-C-2A Note 7 59a DG-C-18B DG Backup Operating Air Compressor DG-20465 B 310524 DG-F-2B-A X X X - ML8 DG-BS5-52 DG-BS5-42 DG-BS5-49 DG-BS5-FU DG-CS-9536 DGB-PS-APC3 DGB-PS-APC4 DG-V-325B 460 v AC Ckt Bkr. Motor Starter Thermal O. L. Fuse Control Switch Pressure Switch Pressure Switch Unloader Sol. Vlv. BS5 BS5 BS5 BS5 BS5 HM3 HM3 UB1 DG-F-2B-A DG-F-2B-A DG-F-2B-A DG-F-2B-A DG-F-2B-A DG-F-2B-A DG-F-2B-A DG-F-2B-A BS5-ML8 BS5-HM3 BS5-UB1 310857 BS5a BS5c DAH-FN-25B DAH-FN-26B EDE-MCC-611 DG-C-18A Note 7 SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -24 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 60 DG-SKD-17B Diesel Generator 1B Starting Air Compressor Skid DG-20465 B 310524 DG-F-2B-A X X X - HM3 DG-E47/4-52 120 v AC Circuit Breaker E47 DG-F-2B-A E47-HM3 BP3-HM3/1 310857 E47/4a E47/4b DAH-FN-25B DAH-FN-26B EDE-MCC-E611 120 v AC Dist. Panel DG-SKD-17A Note 7 DG-HM3-52 120 v AC Circuit Breaker HM3 DG-F-2B-A DG-HM3-ATM Auto Drain Timer HM3 DG-F-2B-A DG-V-253B Auto Drain Solenoid Vlv. HM3 DG-F-2B-A DG-HM3-ICT Motor Synchronous Timer HM3 DG-F-2B-A DG-V-279B Left Chamber inlet Sol. Vlv. HM3 DG-F-2B-A DG-V-280B Right Chamber inlet Sol. Vlv. HM3 DG-F-2B-A DG-V-285B Repressurizing Sol. Vlv. HM3 DG-F-2B-A DG-V-288B Left Chamber Exhaust Sol. Vlv. HM3 DG-F-2B-A DG-V-289B Right Chamber Exhaust Sol. Vlv. HM3 DG-F-2B-A DG-V-HM3-KR Aux. Relay HM3 DG-F-2B-A DG-BP3-42 Motor Starter BP3 CB-F-1B-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -25 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 61 DG-CP-907A Diesel Generator 1A Air Cooler Coolant & Jacket Coolant Temp. Control Panel DG-20461 A 310524 DG-F-2A-A X X X X G29 DG-EH9/17-52 120 v AC Circuit Breaker EH9 CB-F-1A-A EH9-G29 310857 EH9/17a EH9/17c CBA-FN-19 CBA-FN-20 DAH-FN-25A DAH-FN-26A EDE-PP-1E DG-CP-907B Notes 8 & 9 DGA-TIC-9602 Jacket Coolant Temp. Indi. Controller G29 DG-F-2A-A DGA-TT-9602-1 & 2 Jacket Coolant Temp. Transmitters G29 DG-F-2A-A DGA-TE-9602-1 & 2 Jacket Coolant Temp. Elements G29 DG-F-2A-A DGA-ZC-9602 Jacket Coolant Temp . Dig. Vlv. Controller (I/P) G29 DG-F-2A-A DGA-ZY-9602 Jacket Coolant Temp. Cont. Vlv. Pos. Sensor G29 DG-F-2A-A DGA-TIC-9612 Air Cooler Coolant Temp. Indi. Controller G29 DG-F-2A-A DGA-TT-9612-1 & 2 Air Cooler Coolant Temp. Transmitters G29 DG-F-2A-A DGA-TE-9612-1 & 2 Air Cooler Coolant Temp. Elements G29 DG-F-2A-A DGA-ZC-9612 Air Cooler Coolant Temp. Dig. Vlv. Controller (I/P) G29 DG-F-2A-A DGA-ZY-9612 Air Cooler Coolant Temp. Vlv. Pos. Sensor G29 DG-F-2A-A DG-G29-TIC-RX Auxiliary Relay G29 DG-F-2A-A SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50 , Appendix R Safe Shutdown Capability Revision 1 3 Table RSS 3.1.3.18 -26 FUNCTION: DIESEL GENERATORS PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 62 DG-CP-907B Diesel Generator 1B Air Cooler Coolant & Jacket Coolant Temp. Control Panel DG-20466 B 310524 DG-F-2B-A X X X X G30 DG-EH0/17-52 120 v AC Circuit Breaker EH0 CB-F-1B-A EH0-G30 310857 EH0/17a EH0/17c CBA-FN-32 CBA-FN-33 DAH-FN-25B DAH-FN-26B EDE-PP-1F DG-CP-907A Notes 10 & 11 DGB-TIC-9602 Jacket Coolant Temp. Indi. Controller G30 DG-F-2B-A DGB-TT-9602-1 & 2 Jacket Coolant Temp. Transmitters G30 DG-F-2B-A DGB-TE-9602-1 & 2 Jacket Coolant Temp. Elements G30 DG-F-2B-A DGB-ZC-9602 Jacket Coolant Temp . Dig. Vlv. Controller (I/P) G30 DG-F-2B-A DGB-ZY-9602 Jacket Coolant Temp. Cont. Vlv. Pos. Sensor G30 DG-F-2B-A DGB-TIC-9612 Air Cooler Coolant Temp. Indi. Controller G30 DG-F-2B-A DGB-TT-9612-1 & 2 Air Cooler Coolant Temp. Transmitters G30 DG-F-2B-A DGB-TE-9612-1 & 2 Air Cooler Coolant Temp. Elements G30 DG-F-2B-A DGB-ZC-9612 Air Cooler Coolant Temp. Dig. Vlv. Controller (I/P) G30 DG-F-2B-A DGB-ZY-9612 Air Cooler Coolant Temp. Vlv. Pos. Sensor G30 DG-F-2B-A DG-G30-TIC-RX Auxiliary Relay G30 DG-F-2B-A . NOTES 1. The equipment is mechanical with no electrical requirement.

2. Electrical conduit plan drawing, 310524, is listed only to show the fire zone corresponding to the location of this equipment in the Diesel Generator Building as identified in 202263.
3. Electrical conduit plan drawing, 310767, is listed only to show fire zone corresponding to the location of this equipment in the Primary Auxiliary Building as identified in 805217. 4. This equipment is located in the Diesel Generator Skid DG

-SKD-7A. 5. This equipment is located in the Diesel Generator Skid DG-SKD-17A. 6. This equipment is located in the Diesel Generator Skid DG -SKD-7B. 7. This equipment is located in the Diesel Generator Skid DG -SKD-17B. 8. The pneumatic control diagram of this equipment is shown in the DG air cooler water control loop diagram, 506403.

9. The pneumatic control diagram of this equipment is shown in the diesel engine jacket cooling water control loop diagram, 506404. 10. The pneumatic control diagram of this equipment is shown in the DG air cooler water control loop diagram, 506405. 11. The pneumatic control diagram of this equipment is shown in the DG diesel engine jacket cooling water loop diagram, 506406.

SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Safe Shutdown Capability Revision 10 Table RSS 3.1.3.19-1 FUNCTION: COMMUNICATION PHYSICAL REQUIRED FOR POWER SUPPORTING CONTROL AND INSTRUMENTATION EQUIPMENT ELECTRICAL DRAWING NO. ITEM NO. EQUIPMENT ID NO. EQUIPMENT DESCRIPTION P&ID/1-LINE DRAWING NO. TRAIN LOCATION DRAWING NO. FIRE AREA/ZONE HOT STAND BY COLD SHUT DOWN ELEC AIR ELEC NODE EQUIPMENT ID NO. EQUIPMENT DESCRIPTION ELEC NODE FIRE AREA/ZONE CABLES SCHEM. CABLE SUPPORTING SYSTEMS REDUNDANT COUNTERPART REMARKS 1 SPC-RSS 1-NHY-311868 A X X X - G07 SPC-J-1 SPC JACK G07 DG-F-2A-A G06-G5Y - - CB-F-1A-A G19 SPC-J-2 G19 DG-F-2B-A G06-G81 311868 RSS RSSa, b 310816 301820 301841 CB-F-1B-A G2G SPC-J-3 G2G CB-F-1A-A G19-G5X Remote Safe

Shutdown Sound

Powered Telephone

Loop DG-F-2A-A G2J SPC-J-4 G2J CB-F-1B-A G19-XM9 DG-F-2B-A GK0 SPC-J-5 GK0 RHR-F-4B-Z G2J-GKO RHR-F-4A-Z GQ1 SPC-J-6 GQ1 RHR-F-4A-Z G2J-XM9 RHR-F-4B-Z G5X SPC-J-7 G5X DG-F-2A-A G81-G2J G5Y SPC-J-8 G5Y DG-F-2B-A GKO-GQ1

.* Table notes on last page of table SEABROOK STATION Fire Protection of Safe Shutdown Capability 10CFR50, Appendix R Raceway Arrangement Drawings (Typical)

Rev. 5 Appendix IV Page IV-1 Raceway Arrangement Drawings (Typical) This section originally contained photographs of marked raceway arrangement drawings for several fire areas/zones of the plant containing redundant Safe Shutdown equipment and cables. The typical drawings included in this section were provided to only show the methodology used for the original report preparation. These typica l drawings were not intended to be updated for report revisions. These original drawings were typical of the raceway arrangement drawings which were marked for each fire area/zone containing safe shutdown equipment and cables. The latest design documents, not these typical dr awings, should be used to evaluate the Safe Shutdown Capability.}}