//g(c~ROBERTC.MECREDYVicePresident NvcfeorOperotions ROCHESTER GASANDELECTRICCORPORATION

~89EASTAVENUE ROCHESTER N.Y.Id6d9.0MI AREACODE71654'6-2700 January15,1998U.S.NuclearRegulatory Commission DocumentControlDeskAttn:GuyS.VissingProjectDirectorate I-1Washington, D.C.20555

Subject:

10CFRPart2130DayReportR.E.GinnaNuclearPowerPlantDocketNo.50-244

DearMr.Vissing:

Inaccordance with10CFRPart21,Reporting ofDefectsandNoncompliance, Section21(d)(3)(ii),whichrequires"Writtennotification totheNRC...ontheidentificatiohi ofadefectorafailuretocomply",theattached10CFR21reportisherebysubmitted.

Verytrulyyours,RobertC.Mecredxc:Mr.GuyS.Vissing(MailStop14B2)ProjectDirectorate I-1DivisionofReactorProjects-I/IIOfficeofNuclearReactorRegulation U.S.NuclearRegulatory Commission Washington, D.C.20555RegionalAdministrator, RegionIU.S.NuclearRegulatory Commission 475Allendale RoadKingofPrussia,PA194066IU.S.NRCGinnaSeniorResidentInspector

'tt80i2203b5

'sI80ii5PDRADQCK05000244SPDRIIIIIII/IIIIIIIIIlIIIIIIIIIIIIIIIIIIIII h~.

10CFR2130DAYWRITTENREPORTPage2I.'AMEANDADDRESSOFTHEINDIVIDUAL INFORMING THECOMMISSION:

NAME:RobertC.Mecredy'icePresident NuclearOperations GroupADDRESS:Rochester Gas&ElectricCorporation 89.EastAvenueRochester, NewYork14649'IDENTIFICATION OFTHEFACILITY, THEACTIVITY, ORTHEBASICCOMPONENT SUPPLIEDFORSUCHFACILITYWHICHFAILSTOCOMPLYORCONTAINSADEFECT:IThefacilityistheR.E.GinnaNuclearPowerPlant.Thebasiccomponent istheshunttripassemblyonthe"B"Emergency DieselGenerator (EDG)SupplyBreakertoBus16.ThisbreakerisaWestinghouse DB-75aircircuitbreakerandtheGinnaequipment identification numberisEIN52/EG1B1, Theshunttripassemblywasinstalled onthisbreakerinMay,1995,usingsparepartspurchased in1977.IDENTIFICATION OFTHEFIRMCONSTRUCTING THEFACILITYORSUPPLYING THEBASICCOMPONENT WHICHFAILSTOCOMPLYORCONTAINSADEFECT:Theshunttripassemblywassuppliedby:Westinghouse ElectricCorporation PowerSystemsSwitchgear Division700BraddockAvenueEastPittsburgh, PA15112NATUREOFTHEDEFECTORFAILURETOCOMPLYANDTHESAFETYHAZARDWHICHISCREATEDORCOULDBECREATEDBYSUCHDEFECTORFAILURETOCOMPLY:Theshunttripcoilplungerispartoftheshunttripandalarmswitchassembly.

Theplungeroftheshunttripassemblywasbindingintheshunttripcoil.Whenactivated, thebreaker's shunttripcoilplungerpullsthebreakertripperbartotripthebreaker.Theboundplungerwasnotreturning toitsdeenergized position.

Thebreakertripperbarwasbeingmaintained inthetripfreeposition, preventing theDB-75aircircuitbreakerfromclosing.

r't,I/

Page3Testingofthe"B"EDGSupplyBreakertoBus16wasperformed inNovember, 1997,duringthe1997outage.'Duringthistesting,thebreakerfailedtoclose.Thebreakercouldnotbeclosedelectrically ormanually, becausetheshunttripcoilplungerwasmaintaining thetripperbarinthetripfreeposition.

Thisfailurewouldpreventthe"B"EDGfromsupplying powertothesafeguards loadsonBus16.Thisisconsidered amajordegradation since,inconjunction withasinglefailureontheredundant train,requiredsafetyfunctions couldnotbeperformed.

THEDATEONWHICHTHEINFORMATION OFSUCHDEFECTORFAILURETOCOMPLYWASOBTAINED:

Theinformation wasobtainedduringtestingperformed onNovember14,1997.INTHECASEOFABASICCOMPONENT WHICHCONTAINSADEFECTORFAILSTOCOMPLY,THENUMBERANDLOCATIONOFALLSUCHCOMPONENTS INUSEAT,SUPPLIEDFOR,ORBEINGSUPPLIEDFORGINNASTATION:TherearesixWestinghouse DB-75breakerspermanently installed atGinnaStation,insafeguards buses14,and16.Oneofthesebreakersismanuallyoperatedandtheshunttripcoilisnotused.Inaddition, thereisonespareDB-75breakerinstock.Withtheexception ofthe52/EG1B1breaker,thesebreakersstillhavetheiroriginalshunttripassemblies installed.

The52/EG181breakeristheonlyDB-75breakerthathashadtheshunttripassemblyreplaced.

Thereplacement shunttripassemblythatfailedwasoneoftenpurchased in1977asspares.THECORRECTIVE ACTIONWHICHHASBEEN,ISBEING,ORWILLBETAKEN;THENAMEOFTHEINDIVIDUAL ORORGANIZATION RESPONSIBLE FORTHEACTION;ANDTHELENGTHOFTIMETHATHASBEENORWILLBETAKENTOCOMPLETETHEACTION:Corrective actioniscomplete.

Thefailedshunttripassemblywasreplacedwithasparefromstock.Theassemblywasmanuallyandelectrically bench'tested priortobeingreturnedtooperablestatus.Theremaining eightassemblies instockwereinspected.

Twoassemblies hadcoilplungersthatdidnotfullyreturntothedeenergized positionduringmanualmanipulation.

Thesewereremovedfromstock.1TheotherDB-75breakerswerevisuallyinspected.

Acceptable plungermovementisindicated byadequateplungertotripperbargapandfullretraction ofthealarmswitchattachment pushrod.Noadditional bindingconcernswerefound.

Page4TheProcurement AnalysisForm(PAF)fortheshunttripassemblywasappended.

Priortoreordering, thePAFnowrequirestheadditionofplungermovementverification totheassemblyacceptance plan.Westinghouse wascontacted.

Therehavebeennootherreportedeventsofthisnature'that Westinghouse isawareof.Acheckofindustryoperational eventsdidnotidentifysimilarbreakerfailure.ANYADVICERELATEDTOTHEDEFECTORFAILURETOCOMPLYABOUTTHEFACILITY,

ACTIVITY, ORBASICCOMPONENT THATHASBEEN,ISBEING,ORWILLBEGIVENTOPURCHASERS ORLICENSEES:

Receiptinspection couldverifyacceptable plungermovement.

DuringDB-75breakermaintenance, considerverifying thattheshunttripcoilplungermovesfreely.inthecoilbyverifying adequateplungertotripperbargapandfullretraction ofthealarmswitchattachment pushrod.

~f)JGENERALINFORMATION orOTHEREVENTNUMBER:33442LICENSEE:

ROCHESTER GASRELECTRICCORPCITY:ROCHESTER REGION:1COUNTY:STATE:NYLICENSES:

AGREEMENT:

YDOCKET:NOTIFICATXON DATE:12/22/97NOTIFICATION TIME:09:10[ET]EVENTDATE:11/14/97EVENTTIME:12:00[EST]

LASTUPDATEDATE:12/22/97NOTIFICATIONS NRCNOTIFIEDBY:JOHNST.MARTENHQOPSOFFICER:DOUGWEAVEREMERGENCY CLASS:NOTAPPLICABLE 10CFRSECTION:CCCC21.21UNSPECIFIED PARAGRAPH JAMESNOGGLEJERRYCARTERRDONRREVENTTEXTPART21-DEFECTIVE SHUNTTRIPCOXLSTHELICENSEED1SCOVERED AWESTINGHOUSE DB-75BREAKERTHATWASFAILINGTOCLOSEATTHEIRGINNAPLANT.THEPLUNGEROFTHESHUNTTRIPCOILASSEMBLYWASBXNDING,MAINTAINING THEBREAKERTRIPPERBARINTHETRIPFREEPOSITION.

THELICENSEEHASSEVENDB-75BREAKERSONSITE,ONLYONEHADTHEPROBLEMDESCRIBED.

THEBREAKERWITHTHEFAILEDSHUNTTRIPCOILISTHEONLYONETOHAVEHADTHATPARTPREVIOUSLY REPLACED.

THEREPLACEMENT SHUNTTR1PCOILTHATFAILEDWASONEOFTENPURCHASED IN1977ASSPARES.THEFAILEDSHUNTTRIPCOILWASREPLACEDWITHASPAREFROMSTOCK.THEREMAINING EIGHTASSEMBLIES INSTOCKWEREINSPECTED.

TWOASSEMBLXES HADCOILPLUNGERSTHATDIDNOTFULLYRETURNTOTHEDEENERGIZED POSITIONDURINGMANUALMANIPULATION.

THESEWEREREMOVEDFROMSTOCK.LICENSEERECOMMENDS RECEIPTINSPECTION TOVERIFYACCEPTABLE PLUNGERMOVEMENTANDALSOVERIFYING THATTHESHUNTTRIPCOILPLUNGERMOVESFREELYINTHECOILASSEMBLYDURINGBREAKERMAINTENANCE.

~(qk

~t