LER-1981-023, /03L-0:on 810510,damaged Cable Heat Tray Detector Caused False Alarm Which Could Have Masked Other Alarms. Probable Cause of Damaged Heat Detector Attributed to Cable Pulling Crew.Heat Detector Replaced & Functionally Tested |
| Event date: |
|
|---|
| Report date: |
|
|---|
| 2591981023R03 - NRC Website |
|
text
t6 g c.uCLE AR REGULATORY COMMISSION NILC 6 OftM 31,0 17 77) s LICENSEE EVENT REPORT 0NrHOLtil00..[
l l
l l
l l
(PLEASE PRINT ok TYPE ALL REQUIRED 'NFORMATIONI I:
i [LQ] [ AIL) B l R l F l 1l@l 0 l 0 l-l 010 l 0 l 0 l 0 l-l0 l0 l@l 4l 1l 1l 1l 1l@l l
l@
/
e L ICDgE L & Of)t 14 tb LICENSE NUMMEH
/5 2G UCENSE TYPE JO SI C A f Sd covi I"!'l
!$,,$n'" l L @l 0 l 5 l 0 l 0 l 0 l 2 l 5 l 9 @l 0 l 5 l 1 10 l 8 l1 !@l 0 l 6 l 0 l 4 l 8 l 1 l@
t r.0 61 DOCKET NUMBER 68 69 EVENT D ATE 14 7S REPORT DAT5 80 LvrN r onscniPflON AND PROBAGLE CONSEQUENCES h B ] LDuring refueling, while pulling cables, a cable tray heat dete or was damaged, f
G E l causing a false alarm which could have maskdd alarms from other detectors which are
[
g g l required to be operable per T.S. 3.11.C.1.
There was no danger to the health or l
I ioj.,1 l safety of the public. There are no redundant systems. Previous similar events:
[
g [ BFR0 50-259/76010W; 296/79004, 80025.
1 l
I o I e 1 l_
l 101"I L__
tt0 1
<t 1
S'. S T E M
CAUSE
C AUSE COMP va(vg rOCE CODE SunCODE t.OMPCNENT CoOE SURCOOE SUUCODE 1 Al Bl@ l A j@ lE l@ l Il Nl Sl Tj Rl Ul@ g@ { @
to1,1 3
.o it 12 13 is 13 20 SEOuf NTI AL CCOURRENCE REFORT AEVISION i(q qq 6 VENT YE AR REPORT NO.
CODE TYPE No.
O.7.=
I 81 11 L-- J l 01 2l 31 l-l l013l l Ll
[_j l0 l
_ 21 27 2J 24
'6 27 23
.J Jo 31 32 M ANU,PON E N T COM v rt0N F elrunE EFFECT SHUTDOWN A T* ACHM E N T NPRO 4 PRIVE COMP.
ACTt,R( a I AKl N E rlON ON Pt. A NT METHOD HOURS SUB uf fT E D FORM WB.
SUPPLIER l A lgl14z ig l;5zl@
l z[@
l 01 0l 0 l
l Yl@
lN[g lLl@
l K l 1 l 2 l 0 l(
'3 36 3
4g 43 47 43 44 47 camE nescniPrioN ANO CORRECTIVE ACTIONS Il Cable pulling crev probably damaged the heat detector. Kidde heat detector, model l
l j i
[ W ] l897096, 50 feet continuous strip, was replaced and successfully tested. No recurrence [
g g gontrol required due to low frequency of occurrences.
l l
[J_LL) I l
I'lt 1l a,
T itt.
POWER O THE R S T A TUS ISCOV Y
OISCOVERY DESCR8PTION 32 NA l
lAjgl Alarm received in contror room.
l l'I l l_l}J(@) l 0l 0l Oj@l
- 2 n
44 4s m
sio
' u'Tia r v COO rea
.muNT O, AC riv,Tv @ l LOC AT,0N D, REu ASE @
nmAu,,~,,tuAu NA l
NA l
l' ic I LzJ @ Lz J@l
/
4 1
10 19 44 4$
ad PC W ANE L r gpqf,yga g y,
' 13 9tlF N TYPE O( 5(.lif f* TION >
l NA FT 1 10! OI OJ@l zl@l
. m, r ",N,, ' ?,, s n, <au,,,c N @
...,m NA l
L: 11Iolol0181
Jbh"^'"'" @
{
30 l
f il l'. il)( '
JL I (P f ION
)
NA l
ll llllllll ll l Lid j Njhl 68 09 MO 3
III GF NE/ARDI PHONE
" Tennessee Valley Authority Form BF-17 Browns Ferry Nuclear Plant BF 15.2 3/24/81 LER SUPPLEMENTAL INFORMATION BFRO 259 / 81023 Technical Specification Involved 3.11.C.1 Reported Under Technical Specification
- 6. 7.2.b (2)
Date of Occurrence 5/10/81 Time of Occurrence 1315 Unit 1
Identification and Description of Occurrence:
A heat detector cable was damaged, rendering TE 39-44C inoperable, and causing an alarm in the control room.
Conditions Prior to Occurrence:
Unit 1 refueling outage Unit 2 at 83%
Unit 3 at 97%
Action specified in the Technical Specification Surveillance Requirements met due to inoperable equipment. Describe.
Met surveillance requirements of T.S. 3.11.C.2.
i i
j
- \\pperent Cause of O_ccurrence
cable pulling crew probably damaged the heat detector.
i l
l l
Analysis of Occurrence:
There was no danger to the health or safety of the public, no release of activity, no damage to the plant or equipment and no resulting significant chain of events.
9
Corrective Action
Replaced heat detector and functionally tested.
l Failure Data:
l BFRO-50-259/76010W; 296/79004, 80025.
- Retention : Period - Lifetime; Responsibility - Document Control Supervisor
[
\\
i l
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000260/LER-1981-001, Forwards LER 81-001/01T-0 | Forwards LER 81-001/01T-0 | | | 05000260/LER-1981-001-01, /01T-0:on 810102,scram Discharge Vol Level Switch 2-LS-85-45A Found Inoperable & -C & -D Found Offscale.Caused by One Robert Shaw Switch Model SL-305-EI-X Sticking & Setpoint Drift.Stuck Switches Float Chamber Back Flushed | /01T-0:on 810102,scram Discharge Vol Level Switch 2-LS-85-45A Found Inoperable & -C & -D Found Offscale.Caused by One Robert Shaw Switch Model SL-305-EI-X Sticking & Setpoint Drift.Stuck Switches Float Chamber Back Flushed | | | 05000259/LER-1981-001, Forwards LER 81-001/03L-0 | Forwards LER 81-001/03L-0 | | | 05000296/LER-1981-001, Forwards LER 81-001/03L-0 | Forwards LER 81-001/03L-0 | | | 05000296/LER-1981-001-03, /03L-0:on 810106,both Smoke Detectors in Reactor Bldg Fixed Spray Zone Were Inoperable.Caused by Loose Screw in Terminal Block.Screw Replaced | /03L-0:on 810106,both Smoke Detectors in Reactor Bldg Fixed Spray Zone Were Inoperable.Caused by Loose Screw in Terminal Block.Screw Replaced | | | 05000259/LER-1981-001-03, /03L-0:on 810105,core Spray Sparger to Reactor Pressure Vessel D/P Switch 1-PDIS-75-28 Found Set Above Tech Spec Limit.Caused by Barton Model 288 Setpoint Drift.Switch Replaced W/New Switch on 810115 | /03L-0:on 810105,core Spray Sparger to Reactor Pressure Vessel D/P Switch 1-PDIS-75-28 Found Set Above Tech Spec Limit.Caused by Barton Model 288 Setpoint Drift.Switch Replaced W/New Switch on 810115 | | | 05000260/LER-1981-002-03, /03L-0:on 810102,scram Discharge Instrument Vol Rod Block Level Switch 2-LS-85-45E Found Set at 27 Gallons. Alarm Switch 2-LS-85-45F Found Inoperable.Caused by Drift of Robertshaw Model SL-305-EI-X.Switch Recalibr | /03L-0:on 810102,scram Discharge Instrument Vol Rod Block Level Switch 2-LS-85-45E Found Set at 27 Gallons. Alarm Switch 2-LS-85-45F Found Inoperable.Caused by Drift of Robertshaw Model SL-305-EI-X.Switch Recalibr | | | 05000296/LER-1981-002-03, /03L-0:on 810104,excess Flow Check Valves in B3 & B7 Instrument Lines to Panel 25-7 Would Not Restrict Flow Properly.Cause Not Stated.Internals Changed & SI 4.7.D.1.d Successfully Completed | /03L-0:on 810104,excess Flow Check Valves in B3 & B7 Instrument Lines to Panel 25-7 Would Not Restrict Flow Properly.Cause Not Stated.Internals Changed & SI 4.7.D.1.d Successfully Completed | | | 05000259/LER-1981-002, Forwards LER 81-002/03L-0 | Forwards LER 81-002/03L-0 | | | 05000259/LER-1981-002-03, /03L-0:on 810114,smoke Detector in Relay Room Alarmed & Would Not Clear.Caused by Detector Sensitivity Increasing Due to Normal,Natural Aging.Detector Replaced & Tested | /03L-0:on 810114,smoke Detector in Relay Room Alarmed & Would Not Clear.Caused by Detector Sensitivity Increasing Due to Normal,Natural Aging.Detector Replaced & Tested | | | 05000296/LER-1981-002, Forwards LER 81-002/03L-0 | Forwards LER 81-002/03L-0 | | | 05000260/LER-1981-002, Forwards LER 81-002/03L-0 | Forwards LER 81-002/03L-0 | | | 05000260/LER-1981-003-03, /03L-0:on 810112,core Spray Pump Discharge Pressure Switch 2-PS-75-16 Found Outside Tech Spec Limits. Caused by Setpoint Drift.Switch Recalibr & Replaced | /03L-0:on 810112,core Spray Pump Discharge Pressure Switch 2-PS-75-16 Found Outside Tech Spec Limits. Caused by Setpoint Drift.Switch Recalibr & Replaced | | | 05000259/LER-1981-003-01, /01T-0:on 810124,Div of Engineering Notified That 1-inch Vent Line on Unit 1 Scram Discharge Vol Not Seismically Qualified.Caused by Piping Configuration Not Conforming to Design Requirements | /01T-0:on 810124,Div of Engineering Notified That 1-inch Vent Line on Unit 1 Scram Discharge Vol Not Seismically Qualified.Caused by Piping Configuration Not Conforming to Design Requirements | | | 05000259/LER-1981-003, Forwards LER 81-003/01T-0 | Forwards LER 81-003/01T-0 | | | 05000260/LER-1981-003, Forwards LER 81-003/03L-0 | Forwards LER 81-003/03L-0 | | | 05000296/LER-1981-003, Forwards LER 81-003/03L-0 | Forwards LER 81-003/03L-0 | | | 05000296/LER-1981-003-03, /03L-0:on 810107,during Refueling Outage,Fuel Pool Cooling Sys Auto Isolated When Power Was Removed.Fuel Pool Sampling Not Performed on 8-h Schedule.Caused by Personnel Error.Personnel Reinstructed | /03L-0:on 810107,during Refueling Outage,Fuel Pool Cooling Sys Auto Isolated When Power Was Removed.Fuel Pool Sampling Not Performed on 8-h Schedule.Caused by Personnel Error.Personnel Reinstructed | | | 05000260/LER-1981-004-01, /01T-0:on 810119,reactor Water Level Switches LIS-3-203A Switch 1 & LIS-3-A,B,C,D Switch 2 Found Outside Tech Specs.Caused by Drift Due to Air Impact Drilling Next to Switch Panel.Switches Recalibr | /01T-0:on 810119,reactor Water Level Switches LIS-3-203A Switch 1 & LIS-3-A,B,C,D Switch 2 Found Outside Tech Specs.Caused by Drift Due to Air Impact Drilling Next to Switch Panel.Switches Recalibr | | | 05000296/LER-1981-004-03, Diesel Generator 3A & Breaker 1836 Tripped from Generator Overspeed During Testing.Caused by Vs Relay on Speed Sensing Panel Energizing at Less than 870 Rpm,Closing Breaker 1836 | Diesel Generator 3A & Breaker 1836 Tripped from Generator Overspeed During Testing.Caused by Vs Relay on Speed Sensing Panel Energizing at Less than 870 Rpm,Closing Breaker 1836 | | | 05000296/LER-1981-004, Forwards Updated LER 81-004/03X-1 | Forwards Updated LER 81-004/03X-1 | | | 05000259/LER-1981-004, Forwards Updated LER 81-004/03L-1 | Forwards Updated LER 81-004/03L-1 | | | 05000259/LER-1981-004-03, Standby Gas Treatment Sys Train C Relative Humidity Heaters Declared Inoperable.Caused by Dwyer Photohelic Pressure Switch/Gage Circuit Hh & Ite Imperial Relay Contact Block Malfunction | Standby Gas Treatment Sys Train C Relative Humidity Heaters Declared Inoperable.Caused by Dwyer Photohelic Pressure Switch/Gage Circuit Hh & Ite Imperial Relay Contact Block Malfunction | | | 05000260/LER-1981-005-03, /03L-0:on 810119,core Max Fraction of Limiting Power Density Exceeded Limit for One Node in Core.Caused by Operation Close to Limit in Conjunction W/Minor (Normal) Perturbation in Monitored Parameters.Power Reduced Slightly | /03L-0:on 810119,core Max Fraction of Limiting Power Density Exceeded Limit for One Node in Core.Caused by Operation Close to Limit in Conjunction W/Minor (Normal) Perturbation in Monitored Parameters.Power Reduced Slightly | | | 05000259/LER-1981-005-04, /04T-0:on 810131,hydrogen Ion Concentration of Reservoir Near Plant Found in Excess of Allowable Discharge Limit.Probably Caused by Upstream Source.Discharge of Spent Regenerants Stopped & Monitoring Program Established | /04T-0:on 810131,hydrogen Ion Concentration of Reservoir Near Plant Found in Excess of Allowable Discharge Limit.Probably Caused by Upstream Source.Discharge of Spent Regenerants Stopped & Monitoring Program Established | | | 05000296/LER-1981-005-03, /03L-0:on 810127,containment Atmosphere Hydrogen analyzer,3-H2M-76-94,removed from Svc.Caused by Maint on Sensing Line at 3-FIC-76-94,Model 1350,due to Water Collection.Water Removed & Lines Returned to Svc | /03L-0:on 810127,containment Atmosphere Hydrogen analyzer,3-H2M-76-94,removed from Svc.Caused by Maint on Sensing Line at 3-FIC-76-94,Model 1350,due to Water Collection.Water Removed & Lines Returned to Svc | | | 05000296/LER-1981-005, Forwards LER 81-005/03L-0 | Forwards LER 81-005/03L-0 | | | 05000260/LER-1981-005, Forwards LER 81-005/03L-0 | Forwards LER 81-005/03L-0 | | | 05000259/LER-1981-005, Forwards LER 81-005/04T-0 | Forwards LER 81-005/04T-0 | | | 05000259/LER-1981-006, Forwards LER 81-006/03L-0 | Forwards LER 81-006/03L-0 | | | 05000259/LER-1981-006-03, /03L-0:on 810211,while Performing SI 4.2.B-57,RHR Area Cooling Fan Temp Switch 1-TS-64-68 Failed to Operate. Caused by Switch T675A1540 Failure.Switch Replaced,Calibr & 4.2.B-57 Completed | /03L-0:on 810211,while Performing SI 4.2.B-57,RHR Area Cooling Fan Temp Switch 1-TS-64-68 Failed to Operate. Caused by Switch T675A1540 Failure.Switch Replaced,Calibr & 4.2.B-57 Completed | | | 05000296/LER-1981-006-03, /03L-0:on 810128,containment Atmosphere Hydrogen Analyzer Removed from Svc.Caused by Maint on Sensing Lines Due to Effect of Water Accumulation on Model 76-01A625 Timer.Water Removed & Monitor Returned to Svc | /03L-0:on 810128,containment Atmosphere Hydrogen Analyzer Removed from Svc.Caused by Maint on Sensing Lines Due to Effect of Water Accumulation on Model 76-01A625 Timer.Water Removed & Monitor Returned to Svc | | | 05000296/LER-1981-006, Forwards LER 81-006/03L-0 | Forwards LER 81-006/03L-0 | | | 05000260/LER-1981-006-03, /03L-0:on 810121,core Max Fraction of Limiting Power Density Exceeded Limit.Caused by Power Increase in Conjunction W/Inoperable Process Computer.Power Reduced & Control Rod Pattern Adjustment Made on 810123 | /03L-0:on 810121,core Max Fraction of Limiting Power Density Exceeded Limit.Caused by Power Increase in Conjunction W/Inoperable Process Computer.Power Reduced & Control Rod Pattern Adjustment Made on 810123 | | | 05000260/LER-1981-006, Forwards LER 81-006/03L-0 | Forwards LER 81-006/03L-0 | | | 05000260/LER-1981-007-03, /03L-0:on 810129,during Power Increases,Tech Spec Limit of 13.33 Kw/Ft for Linear Heat Generation Rate Exceeded in One Node.Node Reached 13.77 Kw/Ft.Caused by Xenon Transient Resulting from Increased Core Power | /03L-0:on 810129,during Power Increases,Tech Spec Limit of 13.33 Kw/Ft for Linear Heat Generation Rate Exceeded in One Node.Node Reached 13.77 Kw/Ft.Caused by Xenon Transient Resulting from Increased Core Power | | | 05000260/LER-1981-007, Forwards LER 81-007/03L-0 | Forwards LER 81-007/03L-0 | | | 05000259/LER-1981-007, Forwards LER 81-007/03L-0 | Forwards LER 81-007/03L-0 | | | 05000259/LER-1981-007-03, /03L-0:on 810210,during Fire Door Insp,Fire Door Damper (Door 472) Not Closed.Caused by Paint Buildup in Operating Mechanism.Damper Closed & Other Dampers Inspected. Procedure for Insp & Preventive Maint Will Be Written | /03L-0:on 810210,during Fire Door Insp,Fire Door Damper (Door 472) Not Closed.Caused by Paint Buildup in Operating Mechanism.Damper Closed & Other Dampers Inspected. Procedure for Insp & Preventive Maint Will Be Written | | | 05000296/LER-1981-007-03, /03L-0:on 810202,setpoint for 3-PS-1-76 Below Tech Specs Limit.Caused by B2TA12SS Setpoint Drift.Switch Recalibr & Verified.Switch to Be Replaced W/Analog Trip Sys by DCR 1398 | /03L-0:on 810202,setpoint for 3-PS-1-76 Below Tech Specs Limit.Caused by B2TA12SS Setpoint Drift.Switch Recalibr & Verified.Switch to Be Replaced W/Analog Trip Sys by DCR 1398 | | | 05000296/LER-1981-007, Forwards LER 81-007/03L-0 | Forwards LER 81-007/03L-0 | | | 05000260/LER-1981-008-03, /03L-0:on 810220,reactor Core Isolation Cooler Turbine Trip & Throttle Valve Closed & Would Not Reopen. Caused by Overload Heater Relay.Relay Replaced | /03L-0:on 810220,reactor Core Isolation Cooler Turbine Trip & Throttle Valve Closed & Would Not Reopen. Caused by Overload Heater Relay.Relay Replaced | | | 05000259/LER-1981-008-01, /01T-0:on 810226,secondary Containment Integrity Lost When Exterior Equipment Access Door 229 & Interior Personnel Door 228 Opened Simultaneously.Caused by Lack of Interlocks Between Doors.Interlocks to Be Installed | /01T-0:on 810226,secondary Containment Integrity Lost When Exterior Equipment Access Door 229 & Interior Personnel Door 228 Opened Simultaneously.Caused by Lack of Interlocks Between Doors.Interlocks to Be Installed | | | 05000296/LER-1981-008-03, /03L-0:on 810202,RHR Pump Found Inoperable.Caused by Loose Pump 3D Breaker Trip Adjustment Nut & Adjustment Change,Causing Breaker to Trip Free on Attempting to Close. Breaker Replaced.Adjustment Locknut Tightness Checks Add | /03L-0:on 810202,RHR Pump Found Inoperable.Caused by Loose Pump 3D Breaker Trip Adjustment Nut & Adjustment Change,Causing Breaker to Trip Free on Attempting to Close. Breaker Replaced.Adjustment Locknut Tightness Checks Added | | | 05000296/LER-1981-008, Forwards LER 81-008/03L-0 | Forwards LER 81-008/03L-0 | | | 05000259/LER-1981-008, Forwards LER 81-008/01T-0 | Forwards LER 81-008/01T-0 | | | 05000260/LER-1981-008, Forwards LER 81-008/03L-0 | Forwards LER 81-008/03L-0 | | | 05000296/LER-1981-009, Forwards LER 81-009/03L-0 | Forwards LER 81-009/03L-0 | | | 05000259/LER-1981-009, Forwards LER 81-009/01T-0 | Forwards LER 81-009/01T-0 | | | 05000260/LER-1981-009, Forwards LER 81-009/03L-0 | Forwards LER 81-009/03L-0 | |
|