1CAN018606, Advises That Projected Values of Resistor Temp for Pressurized Thermal Shock Do Not Exceed Screening Criteria Per BAW-1895 Before Expiration Date of License DPR-51.No Further Action Required Per 10CFR50.61

From kanterella
Revision as of 16:52, 11 December 2024 by StriderTol (talk | contribs) (StriderTol Bot change)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Advises That Projected Values of Resistor Temp for Pressurized Thermal Shock Do Not Exceed Screening Criteria Per BAW-1895 Before Expiration Date of License DPR-51.No Further Action Required Per 10CFR50.61
ML20140D585
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 01/22/1986
From: Enos J
ARKANSAS POWER & LIGHT CO.
To: Stolz J
Office of Nuclear Reactor Regulation
References
REF-GTECI-A-49, REF-GTECI-RV, TASK-A-49, TASK-OR 1CAN018606, 1CAN18606, NUDOCS 8602030061
Download: ML20140D585 (1)


Text

_

ARKANSAS POWER & LIGHT COMPANY POST OFFICE box 551 UTTLE ROCK ARKANSAS 72203 (501) 371-4000 January 22, 1986 1CAN018606 Mr. J. F. Stolz, Director PWR Project Directorate No. 6 Division of PWR Licensing - B U. S. Nuclear Regulatory Commission Washington, DC 20555

SUBJECT:

Arkansas Nuclear One - Unit 1 Docket No. 50-313 License No. OPR-51 Pressurized Thermal Shock Submittal Required By 10CFR50.61

Dear Mr. Stolz:

10CFR50.61 requires that projected values of RT at the expiration date of theoperatinglicensebedeterminedandsubmitt$bgfor each PWR with an operating license.

These values for all B&W reactors including Arkansas Nuclear One, Unit 1 (ANO-1), have been submitted by the B&W Owners Group Materials Committee in BAW-1895.

AP&L wishes to formally reference this document on our docket.

As stated in BAW-1895, ANO-1 does not exceed the NRC screening criteria for pressurized thermal shock before the expiration date of the operating license.

The most limiting welii, WF-112, is a circumferential weld with a current RT value of 201"F and a RT value of251"FattheoperatinglicenseexpihIkiondate.

Therefore,nofbrther action is required by 10CFR50.61.

Very truly yours, tL l

,'d (d u. Ted Enos, Manager N clear Engineering & Licensing JTE/MCS/sg PW988M Sta8La g

P l#INI

[i0 MEMBEn M'OOLE GoutH ufiLititti syntEM t

.