05000461/LER-1998-001, :on 970929,failure of Division 2 SR Battery Charger Was Noted.Caused by Deficient Supplier Soldered Connections.Insp of Division 1,2 & 4 SR Battery Chargers Are Complete & Have Been Reworked & Repaired