TXX-6836, Interim Deficiency Rept CP-87-98 Re Review of Cable & Raceway Data Sys Which Indicates That Wrong Cable Diameter May Have Been Used in Calculations.Evaluation of Impact of Application of Nominal Cable Continues.Next Rept by 871120
| ML20235U860 | |
| Person / Time | |
|---|---|
| Site: | Comanche Peak |
| Issue date: | 10/09/1987 |
| From: | Counsil W TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC) |
| To: | NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM) |
| References | |
| CP-87-98, TXX-6836, NUDOCS 8710140287 | |
| Download: ML20235U860 (1) | |
Text
_ _ _ _ _ - -
e
~
'1
=M Log # TXX-6836 h
File # 10110
=
=
908.3 Ref # 10CFR50.55(e)
W# ELECTRIC wim.m c. coumu October 9, 1987 Executwe Vice nnkknt U. S. Nuclear Regulatory Commission Attn:
Document Control Desk Washington, D.C.
20555
SUBJECT:
COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)
DOCKET NOS. 50-445 AND 50-446 CABLE RACEWAY FILL CALCULATIONS: CABLE OUTSIDE DIAMETER
,SDAR:
CP-87-98 (INTERIM REPORT) i l
Gentlemen:
l
~On September 9, 1987, we verbally notified your Mr. H. S. Phillips of'a deficiency involving review of. the cable and raceway data system (CARDS) which indicates that the wrong cable diameter may have been used in calculations.
Specifically, CARDS 2323-El-1700 and 2323-E2-1700 use the nominal (versus maximum) cable dianader for calculating raceway fill.
This issue was identified during investigations initiated under the Corrective Actien Program (CAP).
This is an interim report of a potentially reportable item under the provisions of 10CFR50.55(e).
Currently, we are developing our evaluation to assess the impact of the 1
application of nominal as opposed to the maximum allowed cable outside diameter. Our next report on this issue will be submitted no later than November 20, 1987.
Very truly yours, Zb?'
W. G. Counsil WJH/mgt c - Mr. R. D. Martin, Regien IV Resident Inspectors, CPSES (3)