TXX-6684, Interim Deficiency Rept CP-87-54 Re Electrical Drawings Not Implementing FSAR Requirements for Class 1E motor-operated Valve Motor Starters.Initially Reported on 870731.Evaluation Underway.Next Rept Will Be Submitted by 871106

From kanterella
Revision as of 07:02, 2 December 2024 by StriderTol (talk | contribs) (StriderTol Bot change)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Interim Deficiency Rept CP-87-54 Re Electrical Drawings Not Implementing FSAR Requirements for Class 1E motor-operated Valve Motor Starters.Initially Reported on 870731.Evaluation Underway.Next Rept Will Be Submitted by 871106
ML20237J921
Person / Time
Site: Comanche Peak  
Issue date: 08/31/1987
From: Counsil W, Keeley G
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
CP-87-54, TXX-6684, NUDOCS 8709040127
Download: ML20237J921 (2)


Text

_ _ _ _ _ _ _ _ _

,i "llllll:' "lllllllll Log # TXX-6684 j

Fi1e # 10110 908.3 TUELECTRIC

"**'" G C"""Sil Augast 31, 1987 Executive Vice President 1

V. S. Nuclear Regulatory Commission i

Attn:

Document Control Desk Washington, D.C. 20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)

DOCKET NOS. 50-445 AND 50-446 CLASS 1E MOV MOTOR STARTERS SDAR:

CP-87-54 (INTEPIM REPORT)

Gentlemen:

On July 31, 1987, we verbally notified your Mr. H. S. Phillips of a deficiency involving electrical design drawings which do not apparently implement FSAR requirements for Class 1E motor-operated valve motor starters.

The drawings do not provide the motor starter with thermal overloads connected only to alarms or thermal magnetic breakers to trip the starter for sustained locked motor conditions.

This is an interim report of a potentially reportable item under the provisions of 10CFR50.55(e).

We are continuing our evaluation of the impact of this issue upon the safety of plant operations.

We anticipate submitting our next report by November 6, 1987.

Very truly yours, 6

W. G. Counsil

/l /

By:

./

G. S. Keelsy 6

/-

Manager, Nuclear Li sing WJll/mlh c - Mr. R. D. Martin, Region IV Resident Inspectors,'CPSES (3) 8709040127 9700 PDR ADOCK 0500 S

.w 400 North Olive Street LB 81 Dallas, Tens 73201 l p

USHRC-D$

NB1 SEP -3 A 9 21 l