Forwards Case Study Rept - Effects of Ambient Temp on Electronic Components in Safety-Related Instrumentation & Control Sys. W/O Encl
ML20215E671
Person / Time
Issue date: 12/05/1986
From: Heltemes C
NRC OFFICE FOR ANALYSIS & EVALUATION OF OPERATIONAL DATA (AEOD)
To: Beckjord E, Murley T, Taylor J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I), NRC OFFICE OF INSPECTION & ENFORCEMENT (IE), NRC OFFICE OF NUCLEAR REGULATORY RESEARCH (RES)
References
AEOD-C604, NUDOCS 8612230065
Download: ML20215E671 (2)


Text

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _

,N

.- December 5, 1986 MEMORANDUM FOR: James M. Taylor, Director AE0D/C604 Office of Inspection and Enforcement Eric S. Beckjord, Director Office of Nuclear Regulatory Research Thomas E. Murley, Regional Administrator, Region I J. Nelson Grace, Regional Administrator, Region II James G. Keppler, Regional Administrator, Region III Robert D. Martin, Regional Administrator, Region IV John B. Martin, Regional Administrator, Region V FROM: C. J. Heltemes, Jr., Director Office for Analysis and Evaluation of Operational Data

SUBJECT:

CASE STUDY REPORT--EFFECTS OF AMBIENT TEMPERATURE ON ELECTRONIC COMPONENTS IN SAFETY-RELATED INSTRUMENTATION AND CONTROL SYSTEMS The Office for Analysis and Evaluation of Operational Data (AE00) has finalized its case study on the effects of ambient temperature on electronic components in safety-related instrumentation and control systems. The final report addresses the peer review comments provided by NRR, IE, the Regions, INP0, i

NSAC, Westinghouse Electric Corporation and Duke Power Company. The final report also includes the analysis and evaluation of three additional operational experiences not included in the preliminary report involving failures of electronic components due to elevated temperature. We have enclosed a copy of our final report for your information and use as you may deem appropriate.

The study was initiated by an event that occurred at the McGuire Station in June 1984, during which the plant's control area ventilation system was lost for 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. Based on this event, and the resulting initial AE0D study, Information Notice 85-89 " Potential Loss of Solid-State Instrumentation Following Failure of Control Room Cooling" was issued to alert licensees of operating nuclear plants of the event and the NRC's concerns. Three other events were subsequently identified in which the root cause of failure of the instrumentation system was determined to be overheating of electronic components located in cabinets in a controlled environmental area. The enclosed report documents the review and evaluation of these four events.

i TR 25 spak c Wa

<, 7CD "7 8612230065 861205 PDR ORO NEXD PDR

a' Multiple Addressees Overheating of electronic components in safety-related instrumentation and control systems raises two concerns: (1) decreased reliability of electronic equipment due to increased failure rate of heat sensitive electronic components, and (2) the potential for common cause failure of redundant instrument channels due to extended loss of normal cooling to the cabinets in which the instruments are located. The enclosed case study report contains specific recommendations which, based on the study's findings and conclusions, address these two concerns. A separate memorandum is being sent to NRR requesting consideration of these recommendations.

If you have any questions regarding this report, please contact Matthew Chiramal of my staff. Mr. Chiramal can reached at 492-4441.

ow t,W to C.1 % s.

C. J. Heltemes, Jr., Director Office for Analysis and Evaluation of Operational Data

Enclosure:

As Stated cc w/ enclosure:

H. Dance, Region II R. Prevatte, Summer W. Orders, McGuire V. Brownlee, Region II D. Kosloff, Davis-Besse R. Zimmerman, Palo Verde cc w/o enclosure:

D/ Humenansky, OCM DISTRIBUTION:

PDR AE00 CF AE00 SF ROAB CF ROAB SR (conc.)

MChiramal SRubin WLanning KBlack MWilliams FHebdon CHeltemes

BC:ROAB  : DD:AE00  : D:  :  :  :

OFC :SC:ROAB b j ----:------------:------------:-----------


:---------C'-:------------:----hon-----:..

NAME :MChiramal:as SRubin  : FHet  : CH mes  :  :  : :

DATE :12/4 /86  : 12/4 /86  : 12/L4 /86  : 12/ /86  :  :  :

0FFICIAL RECORD COPY