Responds to NRC Bulletin 88-011, Pressurizer Surge Line Thermal Stratification. VT-3 Visual Exam of Pressurizer Surge Line & Bounding Analysis Performed W/O Considering Effects of Thermal Striping
ML20235Z007
Person / Time
Site: Rancho Seco
Issue date: 03/06/1989
From: Croley B
SACRAMENTO MUNICIPAL UTILITY DISTRICT
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20235Z010 List:
References
AGM-NTS-89-042, AGM-NTS-89-42, IEB-88-011, IEB-88-11, NUDOCS 8903150035
Download: ML20235Z007 (2)


Text

  • 1()SMUDSACRAMENTO MUNICIPAL UTIUTY DISTRICT O 6201 S Street, P.O. Box 15830, Sacramento CA 95852-1830, (916) 452-3211 AN ELECTRIC SYSTEM SERVING THE HEART OF CAllFORNIA MAR 0 61999 AGM/NTS89-042 l U. S. Nuclear Regulatory Commission Attn: Document Control Desk Hashington, DC 20555 Docket No. 50-312 Rancho Seco Nuclear Generating Station License No. DPR-54 NRC BULLETIN NO. 88-11: PRESSURIZER SURGE LINE THERMAL STRATIFICATION Attention: George Knighton

References:

D. F. Spond, Babcock and Hilcox Owners Group (B& HOG) letter to Charles E. Rossi, NRC, dated February 24, 1989.

The District, in accordance with Bulletin Requested Action 1.a performed a VT-3 visual examination of the pressurizer surge line. This examination included the piping (with insulation installed) and associated supports.

Results of the inspection were acceptable, with no signs of unanticipated expansion / movement of the pipe. For certain sections of this piping an examination of only one side was possible due to high radiation levels present in the inspection area. This inaccessibility does not reduce the District's confidence that the pressurizer surge line has not experienced gross discernible distress or structural damage.

As detailed in the referenced letter, the District, as a member of the B& HOG, is evaluating thermal stratification and striping and the effects on the pressurizer surge line. Striping, being a relatively newly discovered phenomenon, is difficult to effectively quantify. The B&WOG is initially performing the bounding analysis requested by Bulletin Requested Action 1.b without considering the effects of thermal striping. The results of this analysis will be submitted in accordance with the schedule provided in the Bulletin. The District will submit the results of a bounding analysis considering both stratification and striping on or before October 31, 1989.

l l

8903150035 890306 PDR ADOCK 05000312 gN a PDC I f I

RANCHO SECo NUCLEAR GENERATING STATION O 14440 Twin Cities Road, Herald, CA 95638-9799;(209) 333-2935

! l George Knighton - AGM/NTS89-042 Members of your staff with questions requiring additional information or clarification may contact Mr. Dave Swank at (209) 333-2935, extension 4920.

r.e:: m State of California ELIZAIhTH em bomi ,-

meuc-cau,NDY ,

SS  : l

SACRAMENTO c0UNTY l County of Sacramento l MY c0MM. EXP. NOV. _20,1992 l

1 Bob G. Croley, being first duly sworn, deposes and says: that he is Assistant General Manager, Nuclear Technical Services of Sacramento Municipal Utility District (SMUD), the licensee herein; that he has executed the foregoing document; that the statements made in this document are true and correct to the best of his knowledge, information, and belief, and that he is authorized to execute this document on behalf of said licensee.

Bob G. Croley /

Assistant General Manage'r Nuclear Technical Services Subscribed and affirmed to before me on this 0 day of ,1989.

2 beth L. Gandy~ 472d4 El No ry Public [

Attachment cc w/atch: J. B. Martin, NRC, Halnut Creek A. D'Angelo. NRC, Rancho Seco 1

i