Preliminary 10 Stage Orifice Assembly Design for Turbine and Motor Driven Aux. Feed Water Pumps (Provided to Inspector During November 2002 Inspection)
ML030630550
Person / Time
Site: Point Beach  NextEra Energy icon.png
Issue date: 02/06/2003
From:
- No Known Affiliation
To:
Office of Nuclear Reactor Regulation
References
FOIA/PA-2003-0094
Download: ML030630550 (3)


Text

a- - d'f 4

  • L 2.0" SOCKET WELD TYP BOl] INDS SMALLEST OPENING: .3125"-

0-40 00 2 4 5 6 7 8 9 10 10 STAGE ORIFICE ASSEMBLY FOR BYRON JACKSON S/N 681-S-1030/31 INLET PRESSURE 1350 PSIG OUTLET PRESSURE- 15 PSIG C- FLOW 130 GPM OPERATING TEMP. lOOF REFERENCE RFQ NUMBER 0005074, ITEM 001 CUSTOMER: NMC - POINT BEACH DRAWING #DWG005956 PRELIMINARY 61, -- yc c

S) 'w::

2.0" SOCKET WFL D IYP 00111 ENDS-SMALLEST OPENING: .234".

0 0

1 2 3 4 5 6 7 8 9 10 10 STAGE ORIFICE ASSEMBLY FOR BYRON JACKSON S/N 6B1-S-1028/29 INLET PRESSURE 1300 PSIG OUTLET PRESSURE 15 PSIG FLOW. 75 GPM OPERATING TEMP 100F REFERENCE RFO NUMBER 0005074, ITEM 002 CUSTOMER- NMC - POINT BEACH DRAWING #DWG005955 R REL IMINARY

-' .4.

IAF-15 1RO-4003 Note 5 Flow 1 FE-4049 Note I Notes:

1 - Pipe section welded to flange will be re-used.

2 - All welds are P-8 to P-8.

3 - All welds shall be oversized (2xl) per SK-MR-02-039.

4 - Add field weld flags to this weld map, based on how the piping was installed.

5 - Center Multi stage orifice betwen valve & elbow 6 - Flow is upward