ML20054H527

From kanterella
Revision as of 10:29, 14 March 2020 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
LER 82-039/03L-0:on 820517,steam Flow Channel IV Flow Indicator FI-1485 for Steam Generator 1B Discovered Reading Offscale Low.Cause Not Determined.Channel Placed in Trip Condition,Transmitter Calibr & Instrument Loop Checked
ML20054H527
Person / Time
Site:  Dominion icon.png
Issue date: 06/15/1982
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20054H524 List:
References
LER-82-039-03L, NUDOCS 8206240166
Download: ML20054H527 (1)


Text

e N

' b, U.S. NUCLEAR REGULATORY COMMISSION LICENSEE EVENT REPORT CONTROL BLOCK / / / / / / / (1) (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION)

/0/1/ /V/A/N/A/S/1/ (2) /0/0/-/0/0/0/0/0/-/0/0/ (3) /4/1/1/1[1/ (4) /// (5)

LICENSEE CODE LICENSE NUMBFR LICENSE TYPE CAT

/0/1/ RE

/0/5/0/0/0/3/3/8/ /0/5/1/7/8/2/ (8) /0/6/1/5/8/2/ (9)

O [L/ (6) (7)

DOCKET NUMBER EVENT DATE REPORT DATE EVENT DESCRIPTION AND PROBABLE CONSEQUENCES (10)

[0/2/ / On May 17, 1982, with Unit I at 17% power, Steam Flow Channel IV (Flow Indicator /

/0/3/ / FI-1485 for Steam Generator IB) was removed from service for reading off scale /

/0/4[ / (Low). Since the channel was placed in trip within one hour and one redundant /

/0/5/ / channel remained available for Steam Generator IB, the public health and safety /

/0/6/ / were not affected. This event is contrary to T.S. 3.3.1.1 and 3.3.2 and it is /

/0/7/ / reportable pursuant to T.S. 6.9.1.9.b. There are no generic implications to /

/0/8/ / this event. /

SYSTEM CAUSE CAUSE COMP. VALVE CODE CODE SUBCODE COMPONENT CODE SUBCODE SUBCODE

/0/9/ /I/A/ (11) [E/ (12) [E/ (13) /I/N/S/T/R/U/ (14) [X/ (15) [Z/ (16)

SEQUENTIAL OCCURRENCE REPORT REVISION LER/R0 EVENT YEAR REPORT NO. CODE TYPE NO.

(17) REPORT NUMBER /8/2/ [-/ /0/3/9/ [_1_/ /0/3/ [L/ [-/. [0/

ACTION FUTURE EFFECT SHUTDOWN ATTACHMENT NPRD-4 PRIME COMP. COMPONENT' TAKEN ACTION ON PLANT METIl0D HOURS SUBMITTED FORM SUB. SUPPLIER MANUFACTURER-

[E/ (18) [B/ (19) [Z/ (20) /Z/ (21) /0/0/0/0/ (22) /N/ (23) [N/ (24) [A/ (25) /R/3/6/9/ (26}

CAUSE DESCRIPTION AND CORRECTIVE ACTIONS (27)

/1/0/ / The exact cause of this event is unknown. The failed channel was placed in the /

/1/1/ / trip condition and the transmitter was calibrated and found satisfactory. The /

/1/2/ / entire instrument loop was checked and found to be operating properly. The /

/1/3/ / instrument line valves will be examined for leakage and repaired prior to the /

/1/4/ / end of the refueling outage. /

l FACILITY METHOD OF STATUS  % POWER OTHER STATUS DISCOVERY DESCRIPTION (32)

/1/5/ [C/ (28) /0/1/7/ (29) / NA / (30) DISCOVERY

[A/ (31) / Operator Observation /

l ACTIVITY CONTENT l

RELEASED OF RELEASE AMOUNT OF ACTIVITY (35) LOCATION OF RELEASE (36) i /1/6/ [Z/ (33) [Z/ (34) / NA / / NA /

PERSONNEL EXPOSURES NUMBER TYPE DESCRIPTION (39)

/1/7/ /0/0/0/ (37) LZ[ (38) / NA /

l PERSONNEL INJURIES NUMBER DESCRIPTION (41)

, /1/8/ /0/0/0/ (40) / NA /

LOSS TYPE OF OR DAMAGE TO FACILITY (43)

DESCRIPTION

/1/9/ /Z/ (42) / NA /

PUBLICITY ISSUED DESCRIPTION (45) NRC USE ONLY

/2/0/ /N/ (44) / NA /////////////

NAME OF PREPARER W. R. CARTWRIGHT PHONE (703) 894-5151 0206240166 820615 PDR ADOCK 05000339 S PDR ~