VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 March 9, 1999 United States Nuclear Regulatory Commission Serial No.: 99-147 Attention: Document Control Desk NLOS/MM RO Washington, D.C. ~0555-0001 Docket Nos.: 50-280/281 License Nos.: DPR-32/37 Gentlemen:
VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNITS 1 AND 2 EMERGENCY RESPONSE DATA SYSTEM DATABASE UPDATES Modifications to
- six Emergency Response Data System . (EROS) points have been implemented at Surry Power Station to reflect changes in the descriptions for six auxiliary feedwater flow points that were modified to indicate their RG 1.97 status. Additionally, the liquid waste radiation monitoring point R3RM209C was deleted from the EROS database>
(This radiation monitor was removed from service under a Surry Design Change Package:)
- The changes are detailed in the Data Point Library (DPL) reference file forms provided in I/
II
, I . Attachment 2 provides the revision summary (change report) *for the affected points.
No new commitments are intended by this letter. If you have any questions concerning .1/-v2~
these results, please contact us.
Attachments
- 1. Surry Updated Data Point Library S eets
- 2. Revision Summary 9903170296 qqQ309280 PDR ADOCK osoo~DR p ... '-~* V \.]
cc:
U.S. Nuclear Regulatory Commission Region II
- Atlanta Federal Center
. 61 Forsyth St., SW Suite 23 T85 Atlanta, Georgia 30303-3415 Mr. R. A. Musser NRC Senior Resident Inspector Surry Power, Station Scientech, Inc. (Attachments 1 and 2 plus dBase diskette) 1690 International Way Idaho Falls, Idaho 83402 Attention: Mr. Tony LaRosa
ATTACHMENT 1 UPDATED DATA POINT LIBRARY SHEETS SURRY POWER STATION UNITS 1 AND 2 I
SURRY UNIT 1 UPDATED DATA POINT LIBRARY SHEETS
STATION: Surry PRINTED UNIT: 1 03/05/1999 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/05/1999 REACTOR UNIT: SUl DATA FEEDER: N/A NRC EROS PARAMETER: AX FD FL 1/A POINT ID: FlFWOOlA PLANT SPEC POINT DESC: SG A AFW FLOW (RD) <>
GENERIC/COND DESC: STM GEN A AUX FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 515" H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 400.0 ZERO POINT
REFERENCE:
N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL .REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses auxiliary feedwater flow to steam generator A.
STATION: Surry PRINTED UNIT: 1 03/05/1999 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/05/1999 REACTOR UNIT: SUl DATA FEEDER: N/A NRC EROS PARAMETER: AX FD FL 2/B POINT ID: FlFW002A PLANT SPEC POINT DESC: SG B AFW FLOW (WT) <>
GENERIC/COND DESC: STM GEN B AUX FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 515" H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 400.0 ZERO POINT
REFERENCE:
N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN B ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses auxiliary feedwater flow to steam generator B.
I r \
I STATION: Surry PRINTED UNIT: 1 03/05/1999 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/05/1999 REACTOR UNIT: SUl DATA FEEDER: N/A NRC EROS PARAMETER: AX FD FL 3/C POINT ID: FlFW003A PLANT SPEC POINT DESC: SG C AFW FLOW (BL) <>
GENERIC/COND DESC: STM GEN C AUX FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 515" H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 400.0 ZERO POINT
REFERENCE:
N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN C ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses auxiliary feedwater flow to steam generator C.
~----
--=--~--
SURRY UNIT 2 UPDATED DATA POINT LIBRARY SHEETS
STATION: Surry PRINTED UNIT: 2 03/05/1999 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/05/1999 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: AX FD FL 1/A*
POINT ID: F2FW001A PLANT SPEC POINT DESC: SG A AFW FLOW (RD) <>
e GENERIC/COND DESC: STM GEN A AUX FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 515" H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 400.0 ZERO POINT
REFERENCE:
N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: .AUX FEED PMP DISCH UPSTRM OF STM GEN A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses reactor containment sump level and provides a high level alarm. The largest valid narrow range signal is used for this point. If all signals are valid, 2 signals are considered. If both signals are invalid, this point is marked invalid.
STATION: Surry PIUNTED UNIT: 2 Ol/05/1999 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/05/1999 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: AX FD FL 2/B POINT ID: F2FW002A PLANT SPEC POINT DESC: SG B AFW FLOW (WT) <>
GEN~RIC/COND DESC: STM GEN B AUX FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 515" H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 400.0 ZERO POINT
REFERENCE:
N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN B ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses auxiliary feedwater flow to steam generator B.
STATION: Surry PRINTED UNIT: 2 01/05/1999 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/05/1999 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: AX FD FL 3/C POINT ID: F2FW003A PLANT SPEC POINT DESC: SG C AFW FLOW (BL) <>
GENERIC/COND DESC: STM GEN C AUX FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 515" H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 400.0 ZERO POINT
REFERENCE:
N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN C ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR .POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses auxiliary feedwater flow to steam generator c.
ATTACHMENT 2 REVISION
SUMMARY
SURRY POWER STATION UNITS 1 AND 2 I
\,
I I
I' Page No. STATION: Surry UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT PRINTED 03/08/1999 I I I
\
CHANGED POINT rlFWOOlA AT 10:02 ON 03/05/1999.
DATE: WAS: 03/23/1994 CHANGES WERE AS FOLLOWS:
I
- \
IS: 03/05/1999 PLANT SPEC POINT DESC: WAS: SG A AFW FLOW (RD)
I I
\
\
\
i i
\
i
.\
\
Page No. 2
\
STATION: Surry UNIT: 1 . PRINTED PWR DATA POINT LIBRARY REFERENCE FILE 03/08/l 99q CHANGE REPORT
\
CHANGED POINT FlFW002A AT 10:02 ON 03/05/1999. CHANGES WERE AS FOLLOWS:
DATE: WAS: 03/23/1994 IS: 03/05/1999 PLANT SPEC POINT DESC: WAS: SG B AFW 'FLOW (WT)
\
\I
\ I i
e
I
,, ~
I
\
Page No. 3 STATION: Surry UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE PRINTED 03/08/1999
\
CHANGE REPORT I
~
CHANGED POINT FlFW003A AT 10:03 ON 03/05/1999. CHANGES WERE AS FOLLOWS:
DATE: WAS: 03/23/1994 IS: 03/05/1999 PLANT SPEC POINT DESC: WAS: SG C AFW FLOW (BL)
\
\I I
I I
e
Page No. STATION: Surry PRINTED UNIT: 1 03/08/199'l PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT DELETED POINT R3RM209C AT 09:22 ON 03/08/1999. FIELDS WERE AS FOLLOWS:
DATE*: 05/20/1991 REACTOR UNIT: SUl DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R3RM209C PLANT SPEC POINT DESC: LW DISPOSAL (108)
GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: l.OE6 ZERO POINT
REFERENCE:
N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG 13' LVL ACROSS FROM CHRG PMPS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION
. FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the liquid waste system.
Page No. STATION: Surry PRINTED UNIT: 2 03/08/1999 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT
\
CHANGED POINT F2FW001A AT 10:04 ON 03/05/1999. CHANGES WERE AS FOLLOWS: \
\
DATE: WAS: 06/16/1994 IS: 93/05/1999 PLANT SPEC POINT DESC: WAS: SG A AFW FLOW (RD)
, \
\
\I
\
i
\
I
\
Page No. 2 STATION: Surry UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT PRINTED 03/08/1999
\\
\
\
CHANGED POINT F2FW002A AT 10:04 ON 03/05/1999. CHANGES WERE AS FOLLOWS: \
DATE:
PLANT SPEC POINT DESC:
WAS: 06/16/1994 IS: 03/05/1999 WAS: SG B AFW FLOW (WT)
IS: SG B AFW FLOW (WT) <> lI I
\
\i
\\
Page No. 3 STATION: Surry PRINTED UNIT: 2 03/08/1999 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT F2FW003A AT 10:04 ON 03/05/1999. CHANGES WERE AS FOLLOWS:
DATE: WAS: 06/16/1994 IS: 03/05/1999 I
~
PLANT SPEC POINT DESC: WAS: SG C AFW FLOW (BL)
\
\
Page No. STATION: Surry PRINTED UNIT: 2 03/08/1999 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT DELETED POINT R3RM209C AT 09:22 ON 03/08/1999. FIELDS WERE AS FOLLOWS:
DATE: 05/20/1991 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R3RM209C PLANT SPEC POlNT DESC: LW DISPOSAL (108)
GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1:0E6 ZERO POINT
REFERENCE:
N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG 13' LVL ACROSS FROM CHRG PMPS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
N/A Monitors the radiation level in the liquid waste system.
\