Forwards LER 78-043/03L-0
Date released: 12/06/2019 Download: ML19326A191


LER 78-043/03L-0:on 780428,RCS Pressure in Safety Features Actuation Sys Channel 2 Failed Low After Monthly Test.Broken Wire Found on Test Switch Caused by Movement of Slightly Loose Switch in Panel.Switch Tightened & Wire Repaired