Forwards LER 80-093/03L-0
Date released: 12/21/2019 Download: ML19341A247


LER 80-093/03L-0:on 801219,demineralized Water Containment Isolation Valve DW6831B Did Not Close in Required Time. Caused by Dump Solenoid Orifice Too Small to Allow Adequate Bleedoff Flow.Solenoid to Be Replaced
ML19341A248
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 01/16/1981
From: Trautman D
TOLEDO EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML19341A248 (2)
Forwards LER 80-093/03L-0
ML19341A246
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 01/16/1981
From: Murray T
TOLEDO EDISON CO.
To: KEPPLER J G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML19341A246 (1)