ML19309F08811 April 1980RO 80-1:on 791009,during ECCS Tank TD-2 Monthly Flow Rate Verification,Flow Rate Observed to Be 8 Gpm.Caused by Loose Lock Nuts Which Fix handle-to-ball Operating Shaft. Surveillance Program Will Be Strengthened
ML19309F12414 April 1980RO 80-02:on 800305,low Flow Scram of Flow Recorder FRA-D1 Resulted in Reactor Trip & Subsequent Shutdown.Caused by Broken Teflon Gasket Pieces Restricting Flow.Gasket Repaired & Sys Refilled
ML19310A34523 May 1980Ro:On 800410,heavy-water Temp Recorder TRA-D1 Was Not Recalibr After Replacement of Worn Sliding Contacts on Scanner Select Switch.Cause Not Stated.Importance of Recalibr Emphasized to Personnel