~89EASTAVENU@C1ROBERTCMECREOYVicePreridenr CinnaNuclearPioduclion August31,1994TELEPHONE rriiEACOOEPie 546-2TOOU.S.NuclearRegulatory Commission RegionalAdministrator, RegionIMr.ThomasT.Martin475Allendale RoadKingofPrussia,PA19406
Subject:
RequestForEnforcement Discretion R.E.GinnaNuclearPowerPlantDocketNo.50-244
Reference:
a.LetterfromR.C.Mecredy,RG&E,toT.T.Martin,NRC,
Subject:
"RequestForEnforcement Discretion,"
datedAugust30,1994.
DearMr.Martin,
Inaccordance with10CFRPart2,AppendixC,andusingtheguidancecontained inNRCInspection ManualPart9900,RG&Ehadrequested Enforcement Discretion onAugust30,1994withrespecttoGinnaStationTechnical Specification 3.4.2.1.a (Ref.a).Mlsrequestwasacontingency actionintheeventthatnecessary repairsandtestingofMotor-Driven Auxiliary Feedwater (MDAFW)PumpBcouldnotbecompleted withinthesevendayLCOlimitwhichexpiredonAugust31,1994at0530hours.Merequested Enforcement Discretion wasverballyapprovedbytheNRCduringaphoneconversation betweenMr.WilliamLazarusNRC,RegionI,andRobertMecredy,VicePresident, NuclearProduction atapproximately 1720ESTonAugust30,1994.RG&Esuccessfully completed repairsofMDAFWPumpBonAugust31,1994at0508hours.Thepumpparameters asdocumented inthepostmaintenance testingofMDAFWPumpBareprovidedinAttachment A.Therefore, theLCOwasexitedbeforetheexpiration ofthesevendayLCOlimitandtheNRCauthorized.
Enforcement Discretion wasnotrequiredorused.Verylyyours,cC'obertC.MecredXC:U.S.NuclearRegulatory Commission OfficeofNuclearReactorRegulation Assistant DirectorforRegionIReactorsMr.JoseA.CalvoWashington, D.C.20555GinnaStationSeniorResidentInspector II94gi030359
~4>02IPDRADDCK05000244PPDR ATTACHMENT A"B"MotorDrivenAuxiliary Feedwater PumpPerformance DataPre-Major Maintenance Test:(Degraded Condition)
TestDateDP(PSID)Acceptance Criteria(PSID)Flow(GPM)Vibration (MilsDisp)8/26/941123.21125.5InbdOutbdVertVert.08'10.12.14InbdOutbdHorizHorizPost-Major Maintenance Test:(RepairCompleted)
TestDateDP(PSID)Acceptance Criteria(PSID)Flow(GPM)Vibration (MilsDisp)8/31/941224.41125.5200InbdOutbdInbdVertVertHoriz.08.08.07OutbdHoriz.09