Category:Code Relief or Alternative
MONTHYEARML22196A1972022-07-28028 July 2022 Request for Relief Request N2-I4-LMT-004 Inservice Inspection Limitations ML22019A0022022-03-0808 March 2022 Regarding Request to Utilize Code Case OMN-28 ML20364A0402021-01-15015 January 2021 Request for Relief Request N1-I4-LMT-003 Inservice Inspection Limitations ML19135A3242019-05-21021 May 2019 Inservice Inspection Alternative Request N1-I4-CS-002 ML19092A4172019-04-15015 April 2019 Unit Nos.1 and 2 Inservice Inspection Alternative Requests N1-I5-NDE-001 and N2 I5 NDE 001 ML19039A2362019-02-14014 February 2019 Inservice Inspection Alternative N2-I4-NDE-007 ML18234A1332018-08-15015 August 2018 ASME Section XI Inservice Program Relief Requests N1-15-CMP-001 and N2-15-CMP-001 Proposed Alternative - Use of Paut in Lieu of Rt ML18029A1842018-02-0202 February 2018 Proposed Inservice Inspection Alternatives N1-I4-NDE-010 and N2-I4-NDE-005 (CAC Nos. MF9534 and MF9535; EPID L-2017-LLR-0029) ML18005A1092018-01-10010 January 2018 Relief Request (RR) N1-I4-LMT-002, Limited Coverage Examinations for the Fourth Ten-Year Inspection Interval (CAC No. MF9689; EPID L-2017-LLR-0024) ML17221A2522017-08-17017 August 2017 Proposed Alternative to Implement Code Case N-839 ML17053A2432017-07-21021 July 2017 Relief Request (RR) N1-I4-NDE-008, and N2-I4-NDE-003 Inservice Inspection Program ML17121A0362017-04-24024 April 2017 ASME Section XI Inservice Inspection Program Relief Request N1-I4-LMT-002 - Fourth Interval Period 2 Limited Examinations ML16028A4342016-03-0101 March 2016 Relief Request (RR) N1-I4-SPT-006, Inservice Inspection Program ML15091A6872015-06-25025 June 2015 Relief Request (RR) N2-I4-NDE-002, Inservice Inspection Program ML15023A2192015-02-0303 February 2015 Relief Request (RR) N2-I4-LMT-002, Limited Examinations for the Fourth Ten-Year Inspection Interval Period ML13234A3532013-08-30030 August 2013 Relief Request (RR) N1-I4-LMT-001, Limited Examinations for the Fourth Ten-Year Inspection Interval Period 1 ML12227A7732012-08-17017 August 2012 Relief Request N2-13-PRT-002, Limited Coverage Examinations for the Third 10-Year Inservice Inspection Interval ML11270A1222011-09-21021 September 2011 ASME Section Xl Inservice Inspection Program Relief Request N2-I3-PRT-002 - Limited Coverage Examinations Performed in the Third Ten-Year Inspection Interval ML1102600222011-01-28028 January 2011 Fourth 10-Year Inservice Inspection Interval, Relief Request N2-I4-CS-001 ML1100600112011-01-0707 January 2011 (Naps), Unit No. 1, Third 10-Year Inservice Inspection Interval (ISI) Program, Relief Request (RR) N1-13-PRT-004, Part a Through Part G ML1024602232010-09-30030 September 2010 Fourth 10-Year Interval Inservice Inspection (ISI) Program, Pumps and Valves ML1019303072010-07-12012 July 2010 Request for Relieft N1-13-PRT-004 ML1005604302010-02-23023 February 2010 ASME Section XI Inservice Inspection Program Relief Request N1-14-RI-001 and N2-14-RI-001 Request for Alternative - Implementation of a Risk-Informed Inservice Inspection Program Based on ASME Code Case N-716 ML0910705392009-04-17017 April 2009 Use of Alternative Class 1 Pressure Test Requirements Relief Request SPT-014 ML0814400142008-06-0909 June 2008 Third 10-Year Inservice Inspection Interval Relief Requests CMP-023 and CMP-024 ML0714403422007-08-0303 August 2007 Relief Request to Use Portion of 2001 Edition of American Society of Mechanical Engineers Code ML0604505172006-02-0909 February 2006 Unit No'S. 1 and 2 ASME Code Third 10-year ISI Program. (TAC No'S MC5588, MC5589, MC5590, MC5591, MC5592, MC5593, MC5594, MC5595, MC5599 and MC5600) ML0604405462006-02-0202 February 2006 Relief, Containment Relief Request IWL1 ML0522702752005-08-24024 August 2005 Relief Request, Snubber Visual Examination and Functional Testing (Tac No. MC5451, MC5452) ML0507000502005-03-10010 March 2005 RR, (Tac MC3317) ML0501804952005-01-10010 January 2005 ASME Section XI Inservice Inspection Program, End of Intervals System Pressure Testing ML0412700022004-05-0404 May 2004 Request to Use Code Case N-663 as an Alternative for Surface Examination of ASME Code Class 2 Piping Welds(Tac MC2489, MC2490, MC2491, MC2523 & MC2524) ML0331700242003-10-13013 October 2003 American Society of Mechanical Engineers Boiler and Pressure Vessel Code, Section XI Relief Request CMP-020 ML0326602352003-09-23023 September 2003 N. Anna, Units 1 & 2 - Risk-Informed Inservice Inspection Relief Request R-1 ML0316814082003-06-0505 June 2003 Risk-Informed ISI Relief Requests R-1 Response to Request for Additional Information ML0302303502003-01-23023 January 2003 Relief Request, Repair Technique for Reactor Vessel Head Penetrations ML0301500042003-01-14014 January 2003 Relief Request, ASME Section XI, Inservice Inspection Program, RR-IWE9 for Containment Testing ML0233303662002-11-14014 November 2002 ASME Section XI Inservice Inspection Program Relief Request IWE9 Containment Testing ML0215102442002-05-20020 May 2002 Code Relief Request, Alternative Repair Techniques for Reactor Vessel Heads CMP-16 & CMP-17 ML0213600242002-05-14014 May 2002 ASME Section XI Inservice Inspection (ISI) Program Relief Request Partial-1. Table - North Anna, Unit 2 - Reactor Vessel Outlet Nozzle to Shell Welds 10, 12 & 14 ML0204506472002-02-13013 February 2002 ASME Section XI Inservice Inspection (ISI) Program Relief Request NDE-Partial-2, TAC No. MB1129 2022-07-28
[Table view] Category:E-Mail
MONTHYEARML23320A1122024-01-18018 January 2024 NRC to Fws, Concurrence with Endangered Species Act Determinations for North Anna Power Station, Units 1 and 2, Subsequent License Renewal, Issuance of Draft Supplemental Environmental Impact Statement, and Opportunity for Public Comment ML23355A2722023-12-21021 December 2023 NRR E-mail Capture - Schedule Revision for Emergency Preparedness Staff Augmentation Times License Amendment Request ML23318A1172023-11-13013 November 2023 NRR E-mail Capture - Formal Issuance of RAIs for North Anna Technical Support Center (TSC) License Amendment Request (LAR) (L-2023-LLA-0006) ML23257A2092023-09-14014 September 2023 NRR E-mail Capture - Formal Issuance of 2nd Round RAIs for Surry Units 1&2 and North Anna Units 1&2 Emergency Plans LAR ML23243A9862023-08-31031 August 2023 NRR E-mail Capture - Draft RAIs for EP Staff Augmentation Times LAR (L-2022-LLA-0166) ML23219A1602023-08-0707 August 2023 003 Radiation Safety Baseline Inspection Information Request ML23171B0522023-06-20020 June 2023 NRR E-mail Capture - RAI for Review of Appendix F to DOM-NAF-2-P (Redacted) ML23075A0232023-03-15015 March 2023 NRR E-mail Capture - RAI - License Amend Req (LAR) to Revise Tech Spec (Ts) 3.6.8 Limiting Condition for Operation to Remove Refueling Water Chemical Addition Tank and Replace the Containment Sump Buffer North Anna, 1 and 2 (L-2022-LLA-0162 ML23067A2162023-03-0707 March 2023 NRR E-mail Capture - RAI for North Anna, 1 & 2, Surry 1 & 2, Millstone, 2 & 3, Request for Approval of App. F Fleet Report DOM-NAF-2-P, Qual of the Framatome ORFEO-GAIA and ORFEO-NMGRID CHF Correlations in the Dominion VIPRE-D Computer Code ML23060A0932023-03-0101 March 2023 NRR E-mail Capture - Formal Issuance of RAIs for Surry/North Anna Emergency Plans LAR ML23059A2282023-02-28028 February 2023 NRR E-mail Capture - Draft RAIs for Containment Buffer Change to Natb (L-2022-LLA-0162) ML23039A1712023-02-0808 February 2023 NRR E-mail Capture - Acceptance Review for Technical Support Center (TSC) Relocation (L-2023-LLA-0006) ML23018A0352023-01-17017 January 2023 NRR E-mail Capture - Acceptance Review for Fleet Report Re Appendix F of DOM-NAF-2-P (L-2022-LLT-0003) ML22342B1472022-12-0808 December 2022 NRR E-mail Capture - Acceptance Review for LAR Re NAPS Post LOCA Buffer Change (L-2022-LLA-0162) ML22335A4842022-12-0101 December 2022 NRR E-mail Capture - Acceptance Review for LAR North Anna Power Station - Units 1 and 2 and Surry Power Station - Units 1 and 2 Emergency Plan Staff Augmentation Times (L-2022-LLA-0166) ML22242A0452022-08-23023 August 2022 NRR E-mail Capture - Dominion GL 04-02 Response Draft RAIs (L-2017-LRC-0000) ML22174A3552022-06-23023 June 2022 NRR E-mail Capture - Acceptance Review for Dominion Fleet LAR to Implement TSTF-554 (L-2022-LLA-0078) ML22104A0252022-04-14014 April 2022 NRR E-mail Capture - Dominion Presentation Slides for April 21, 2022 Public Meeting on Emergency Preparedness Submittal for the North Anna Power Station and the Surry Power Station ML22083A2102022-03-24024 March 2022 NRR E-mail Capture - Draft RAI - Relief Request N2-14-LMT-003 Fourth Ten Year Inservice Inspection Interval ML22032A0962022-02-0101 February 2022 002 Radiation Safety Baseline Inspection Information Request ML22018A0272022-01-18018 January 2022 2022 All RFI Responses - Exercise and Program Inspections - Revl ML22007A2672022-01-0707 January 2022 NRR E-mail Capture - North Anna, Unit 2, ASME Section XI Inservice Inspection Program Relief Request N2-14-LMT-003 Fourth Interval Third Period Limited Examinations (L-2021-LLR-0088) ML21335A0812021-12-0101 December 2021 NRR E-mail Capture - Acceptance Review for OMN-28 Request Alternative to ISTC-3700, Position Verification Testing (L-2021-LLR-0086) ML21334A1922021-11-30030 November 2021 NRR E-mail Capture - Audit Plan for Reactor Core Thermal-Hydraulics Using the VIPRE-D Appendix E Review ML21327A3652021-11-23023 November 2021 NRR E-mail Capture - Draft RAI for TSTF-577 LAR ML21326A1502021-11-22022 November 2021 NRR E-mail Capture - Acceptance Review for Relocation of Unit Staff Requirements to the QAPD LAR (L-2021-LLA-0195) ML21322A0962021-11-18018 November 2021 Final Request for Additional Information Set 5 - North Anna SLRA Safety Review (EPID No. L-2020-SLR-0000) - Email ML21312A0082021-11-0404 November 2021 Enclosure 2 - NAPS Draft SER Table A.1-1 Markup ML21312A0112021-11-0404 November 2021 Enclosure 3 - NAPS Draft SER Section 3 Comments ML21312A0012021-11-0404 November 2021 Comments on North Anna Draft SER ML21306A3302021-11-0202 November 2021 NRR E-mail Capture - Acceptance Review for TSTF-569 LAR ML21286A7372021-10-13013 October 2021 Additional Element Included in the Implementation Plan for the Surry Fuel Melt Safety Limit (SL) LAR ML21274A0022021-09-30030 September 2021 NRR E-mail Capture - Acceptance Review for TSTF-577 LAR (L-2021-LLA-0158) ML21312A0022021-09-21021 September 2021 Enclosure 1 - E-mail - NAPS SLR SER Appendix a for Dominion Review ML21312A0072021-09-21021 September 2021 Enclosure 1 - E-mail - Enclosure B - NAPS SER App a - Dominion Comments 9-21-2021 ML21312A0032021-09-21021 September 2021 Enclosure 1 - E-mail - Enclosure a - Dominion Table A4.4-1 Clean Version ML21256A0672021-09-13013 September 2021 Final Request for Confirmation of Information Set 2 - North Anna SLRA Safety Review (EPID No. L-2020-SLR-0000) - Email ML21152A1722021-09-0707 September 2021 NRC to Fws, NRC Issuance of Draft Environmental Impact Statement for North Anna Subsequent License Renewal, Opportunity for Public Comment, and Endangered Species Act Determinations ML21238A0942021-08-25025 August 2021 Draft Request for Additional Information Set Z - North Anna SLRA Safety Review (EPID No. L-2020-SLR-0000) - Email ML21225A5512021-08-13013 August 2021 Discussion Point for Public Meeting Regarding Fire Protection Piping Cyclic Loading - Transmittal E-mail ML21195A2442021-07-13013 July 2021 NRR E-mail Capture - Draft RAI Appendix E to Topical Report DOM-NAF-2 Qualification of the Framatome BWU-I CHF Correlation in the Dominion Energy VIPRE-D Computer Code ML21188A1632021-07-0707 July 2021 Final Request for Additional Information Set 4 - North Anna SLRA Safety Review (EPID No. L-2020-SLR-0000) - Email ML21154A0152021-06-0101 June 2021 NRR E-mail Capture - Acceptance Review for Primary Grade Water LAR (L-2021-LLA-0082) ML21140A3682021-05-20020 May 2021 Response to North Anna Hardship (Temporary Staff Guidance Additional Guidance for FOF Inspections During the PHE) ML21140A3712021-05-19019 May 2021 FOF Discussion ML21123A2972021-05-0303 May 2021 Final Request for Additional Information Set 3 - North Anna SLRA Safety Review (EPID No. L-2020-SLR-0000) - E-mail ML21091A0022021-04-0101 April 2021 Final Request for Additional Information Set 2 - North Anna SLRA Safety Review (EPID No. L-2020-SLR-0000) - Email ML21076A4622021-03-17017 March 2021 NRR E-mail Capture - Draft RAI for Versatile Internals and Component Program for Reactors Vipre Code Review (L-2021-LLT-0000) ML21075A0032021-03-12012 March 2021 Emergency Preparedness Exercise Inspection Request for Information for - Brunswick, Catawba, North Anna, Oconee, Vogtle 1 & 2 ML21069A3522021-03-10010 March 2021 NRR E-mail Capture - Acceptance Review for Topical Report DOM-NAF-2 VIPRE-D 2024-01-18
[Table view] |
Text
From: Sreenivas, V Sent: Monday, July 12, 2010 1:37 PM To: 'david.heacock@dom.com' Cc: 'Tom Shaub'; 'david.sommers@dom.com'; Kulesa, Gloria
Subject:
NAPS-Unit No 1- Request for Relief (RR) N1-13-PRT-004 By letter dated February 1, 2010, the licensee, Virginia Electric and Power Company (Dominion),
submitted Request for Relief (RR) N1-13-PRT-004 from the requirements of the American Society of Mechanical Engineers Boiler and Pressure Vessel Code (ASME Code),Section XI, for North Anna Power Station, Unit 1. The request for relief applies to the third 10-year inservice inspection interval, in which the licensee adopted the 1989 Edition with no Addenda of ASME Code,Section XI as the Code of record.
REQUEST FOR ADDITIONAL INFORMATION 2.1 Request for N1-13-PRT-004, Part A, ASME Code,Section XI, Examination Category B-A, Items B1.11, B1.21, and B1.22, Pressure Retaining Welds in Reactor Vessel 2.1.1 Please submit detailed and specific information to support the bases for limited volumetric coverage for ASME Code,Section XI, Examination Category B-A components, and therefore, demonstrate impracticality.
a) As applicable, describe Nondestructive Examination (NDE) equipment (ultrasonic (UT) scanning apparatus), details of the listed obstructions (size, shape, proximity to the weld, etc.) to demonstrate accessibility limitations, and discuss whether alternative methods or advanced technologies could be employed to maximize ASME Code coverage.
b) Please state whether the examinations listed in ASME Code,Section XI, Examination Category B-A were conducted in accordance with the performance demonstration requirements described in ASME Code,Section XI, Appendix VIII. If not, please state the ASME Code requirements used for the UT examinations of these welds.
c) Fully clarify the wave modality and insonification angles used for all UT examinations.
d) Show cross-sectional coverage plots to describe ASME Code volumes examined.
e) State whether any indications were discovered as a result of ASME Code required examinations, and how these indications have been dispositioned.
f) Based on the limited information in the sketch provided by the licensee, it is assumed that these examinations were performed from the inside surface of the reactor pressure vessel (RPV). Discuss whether ASME Code volumetric coverage could be increased by applying NDE from the outside surface of the RPV.
2.1.2 For the third inspection interval, ASME Code coverage for Circumferential Shell and Head Welds, W04 and W08, had decreased by approximately 5% from the examinations performed in the second interval. Please explain why there was a decrease in coverage.
2.2 Request for N1-13-PRT-004, Part B, ASME Code,Section XI, Examination Category B-D, Item B3.110, Full Penetration Welded Nozzles in Vessels 2.2.1 Please submit detailed and specific information to support the bases for limited volumetric coverage in ASME Code,Section XI, Examination Category B-D components, and therefore, demonstrate impracticality.
a) As applicable, describe NDE equipment (UT scanning apparatus), details of the listed obstructions (size, shape, proximity to the weld, etc.) to demonstrate accessibility limitations, and discuss whether alternative methods or advanced technologies could be employed to maximize ASME Code coverage.
b) Fully clarify the wave modality and insonification angles used for all UT examinations.
c) State whether any indications were discovered as a result of ASME Code required examinations, and how these indications have been dispositioned.
2.2.2 For the third inspection interval, ASME Code coverage for Pressurizer Relief Nozzle Weld 13 had decreased by approximately 35% from volumetric examinations performed in the second interval. Please explain why there was a decrease in coverage.
2.2.3 Please state the material of construction and the wall thickness for the subject pressurizer nozzle-to-vessel welds.
2.3 Request for Relief N1-13-PRT-004, Part C, ASME code,Section XI, Examination Category B-K-1, Item B10.20, Integral Attachments for Piping, Pumps, and Valves 2.3.1 ASME Code,Section XI, 1989 Edition, Examination Category B-K-1, Item B10.20 requires a surface examination of integrally welded pump attachments. The description of the integrally welded attachment for this relief request is referring to a piping attachment which would correspond to ASME Code,Section XI, Item B10.10 of Category B-K-1. Please verify the correct item number and examination category applied to the pipe support integral attachment weld in this relief request.
The licensee may have invoked ASME Code Case N-509, Alternative Rules for the Selection and Examination of Class 1, 2, and 3 Integrally Welded Attachments,Section XI, Division 1, which lists Examination Category B-K, and states requirements for this,
and other integral attachment, welds. However, no mention of the use of ASME Code Case N-509 has been stated. ASME Code Case N-509, is conditionally acceptable according to an earlier revision of Regulation Guide 1.147, Inservice Inspection Code Case Acceptability, which may have been in effect at the start of the licensees second 10-year inspection interval. The NRC condition for acceptable use was that a minimum 10% sample of integrally welded attachments for each item in each ASME Code class shall be examined during each interval.
State whether ASME Code Case N-509 was invoked and confirm that the listed condition for acceptance was applied for all ASME Code, Class 1, 2 and 3 integral attachment welds.
2.3.2 Please state the material of construction and what type of surface examination was performed (liquid penetrant (PT) or magnetic particle (MT)).
2.4 Request for Relief N1-13-PRT-004, Part D, ASME Code,Section XI, Examination Category R-A, Item R1.11, Risk-Informed Piping Examinations 2.4.1 Please submit detailed and specific information to support the bases for limited volumetric coverage in ASME Code, Examination Category R-A piping welds, and therefore, demonstrate impracticality.
a) As applicable, describe NDE equipment (UT scanning apparatus), details of the listed obstructions (size, shape, proximity to the weld, etc.) to demonstrate accessibility limitations, and discuss whether alternative methods or advanced technologies could be employed to maximize ASME Code coverage.
b) Fully clarify the wave modality and insonification angles used for all UT examinations.
c) If not already provided in the licensees description, please state the materials of construction for each of the welds and base materials.
d) State whether any indications were discovered as a result of ASME Code-required examinations, and how these indications have been dispositioned.
2.4.2 Please confirm whether the examinations listed for all ASME Code, Examination Category R-A welds were conducted in accordance with the performance demonstration requirements of ASME Code,Section XI, Appendix VIII.
2.4.3 The licensee stated that in most cases a 100% surface examination was performed. Please state which welds received a surface examination and whether or not any indications were found as a result of these examinations being performed.
2.4.4 Please confirm that all of the subject ASME Code, Examination Category R-A welds are Item R1.11 (elements subject to thermal fatigue) per ASME Code Case N-577, as shown in the licensees table.
2.4.5 In the licensees table provided in Section 4.R.1 in its submittal, incorrect tables and figures are being referenced. Please clarify this table.
2.4.6 Further discuss whether additional welds could have been examined to augment the reduced volumetric coverage resulting from the limited examinations of the subject welds, or if alternate welds could be selected to achieve the required coverage.
2.5 Request for Relief N1-13-PRT-004, Part E, ASME code,Section XI, Examination Category C-B, Item C2.21, Pressure Retaining Nozzle Welds in Vessels 2.5.1 Please submit detailed and specific information to support the bases for limited volumetric coverage in Examination Category C-B components, and therefore, demonstrate impracticality.
a) As applicable, describe NDE equipment (UT scanning apparatus), details of the listed obstructions (size, shape, proximity to the weld, etc.) to demonstrate accessibility limitations, and discuss whether alternative methods or advanced technologies could be employed to maximize ASME Code coverage.
b) Fully clarify the wave modality and insonification angles used for all ultrasonic examinations.
c) State whether any indications were discovered as a result of ASME Code-required volumetric examinations, and how these indications have been dispositioned.
d) Please confirm that the required surface examinations (PT or MT) were performed for the subject welds, whether these surface examinations were full ASME Code examinations
(>90% coverage), and describe any indications that were detected.
2.5.2 Please state the materials of construction and the wall thickness for the boron injection tank and nozzle.
2.6 Request for Relief N1-13-PRT-004, Part F, ASME Code,Section XI, Examination Category C-C, Item C3.20, Integral Attachments for Vessels, Piping, Pumps, and Valves 2.6.1 Please state the material of construction and what type of surface examination was performed (PT or MT) for the integrally welded attachments to ASME Code, Class 2 piping.
2.7 Request for Relief N1-13-PRT-004, Part G, ASME Code, Examination Category C-F-1, Items C5.11 and C5.21, Pressure Retaining Welds in Austenitic Stainless Steel or High Alloy Piping 2.7.1 Please submit detailed and specific information to support the bases for limited volumetric coverage in ASME Code,Section XI, Examination Category C-F-1 piping welds, and therefore, demonstrate impracticality.
a) As applicable, describe NDE equipment (UT scanning apparatus), details of the listed obstructions (size, shape, proximity to the weld, etc.) to demonstrate accessibility limitations, and discuss whether alternative methods or advanced technologies could be employed to maximize ASME Code coverage.
b) Fully clarify the wave modality and insonification angles used for all UT examinations.
c) Please confirm that the required surface examinations (PT or MT) were performed for the subject welds, whether these surface examinations were full ASME Code examinations (>90%
coverage), and describe any indications that were detected.
d) Please state, if not already provided, whether the examinations listed in ASME Code,Section XI, Examination Category C-F-1 were conducted in accordance with the performance demonstration requirements described in ASME Code,Section XI, Appendix VIII. If not, please state the ASME Code requirements used for the UT examinations of these welds.
e) Further discuss whether additional welds could have been examined to augment the reduced volumetric coverage resulting from the limited examinations of the subject welds, or if alternate welds could be selected to achieve the required coverage.
Request your response by August 31, 2010. If you have any questions, please contact me at your earliest.
___________________________
V. Sreenivas, PH.D., C.P.M.,
Project Manager, Rm.#O8F6, LPL2-1 North Anna Power Reactors, Units 1 and 2 Division of Operating Reactor Licensing-NRR (301) 415-2597, v.sreenivas@nrc.gov
- This email message, and any files transmitted with it, may contain confidential, non-public, sensitive and proprietary data intended solely for the person(s) to whom this email message is directly addressed. Unauthorized use of the data contained in this message is prohibited. If you are not the intended recipient of this message or have received this message in error, please notify the sender immediately by telephone or email Reply and delete the original message and any attachments without keeping a copy***