- 05000423/LER-1986-042, :on 860725,Train a Safety Injection Actuation Occurred.Caused by Intermittent Resetting of Pressurizer Low Pressure Safety Injection Block.Switch Panel Lugs Adjusted (← links)
- 05000423/LER-1987-008, :on 870307,reactor Trip Occurred Due to lo-lo Steam Generator Level in Steam Generator D.Caused by Failure of Solenoid Valve.Solenoid Valve Replaced & Tested for Operability (← links)
- 05000423/LER-1986-008, :on 860202,turbine Bldg Ventilation Stack Radiation Monitors Out of Svc & 12 H Grab Samples Required by Tech Spec Action Statement 3.3.3.10 Not Taken.Caused by Chemistry Dept Error.Samples Taken (← links)
- 05000423/LER-1986-009, :on 860204,feedwater Isolation Occurred.Caused by Excessive Leakage Through motor-driven Feedwater Pump Balancing Valve.Air Set Moved to Nonvibrating Mount Adjacent to Valve & Copper Tubing Replaced (← links)
- 05000423/LER-1986-010, :on 860204,reactor Trip Occurred Due to Level Deviation in Steam Generator 2.Caused by Operator Error in Manually Controlling Steam Generator Level.Automatic Steam Generator Level Control Sys Operable (← links)
- 05000219/LER-1981-047-03, /03L-0:on 811005,during Diesel Surveillance Test, Diesel Failed to Automatically Increase Load Above 2,400 Kw. Caused by Operational Deterioration of Governor.Governor Replaced (← links)
- 05000219/LER-1981-044-03, /03L-0:on 810825,during 10-h Operability Test, Standby Gas Treatment Sys Fan Found to Be Excessively Noisy & Running W/Hot Bearings.Caused by Normal Wear.Bearings Replaced (← links)
- 05000219/LER-1982-005-03, /03L-0:on 820125,during Load Surveillance Test, Diesel Generator 1-1 Tripped on Engine Fault.Caused by Reduction of Water Inventory in Cooling Sys as Result of Radiator Tube Leak.Leaky Tubes Plugged (← links)
- 05000219/LER-1981-065-01, /01T-0:on 811209,shutdown Commenced to Investigate a Isolation Condenser Isolation Valve V-14-30 811203 & 04 Failure to Operate Properly.Caused by Excessive Stress on Valve Backseat & Damage to Stem Nut (← links)
- 05000219/LER-1981-053-03, /03L-0:on 811021,during Offgas Sys Isolation, Offgas Bypass Valve Failed to Open.Conduit Containing Power Fell from Wall Resulting in Loss of Control of Bypass & Loss of Automatic Isolation in Event of High Radiation Trip (← links)
- 05000219/LER-1981-048-03, /03L-0:on 811012,during Cleanup Sys Shutdown, Auxiliary Pump Isolation Valve Failed to Close.Caused by Dirty Torque Switch Which Prevented Remote Valve Operation. Switch Cleaned & Valve Cycled Properly (← links)
- 05000219/LER-1981-035-03, /03L-0:on 810721,nonfunctional Fire Barrier Discovered.Maint Personnel Erroneously Directed to Filled Penetration & Job Order Closed.Caused by Error in Communication.Fire Watch Established.Penetration Repaired (← links)
- 05000219/LER-1981-042-03, /03T-0:on 810828,stack Gas Pump B Found Tripped & Low Flow Alarm Did Not Annunciate.Caused by Automatic Lubrication Sys Malfunction & Component Failure on Low Flow Switch Alarm Card (← links)
- 05000219/LER-1981-033-01, /01T-0:on 810727,personnel Access Airlock Doors Found Ajar.Caused by Worn Interlock Plunger Mechanism That Became Loose.Plunger Mechanism Tightened (← links)
- 05000219/LER-1981-023-03, /03L-0:on 810603,drywell Vented to Reduce Drywell Torus Differential Pressure.Caused by Moisture Buildup in Sensing Line Resulting in Erroneous Indication of Increased Oxygen Concentration.Procedures Will Be Reviewed (← links)