| | #REDIRECT [[05000321/LER-1981-052-03, /03X-1:on 810621,LPCI Inverter B R44-S003 Tripped, Resulting in Loss of Power to Suction & Discharge Valves & LPCI Injection Valve.Caused by Defective Thermal Temp Switch in Inverter Leg.Switch Replaced]] |
| | number = ML20009E713
| |
| | issue date = 07/09/1981
| |
| | title = /03L-0:on 810621,low Pressure Core Injection B Inverter R44-S003 Tripped on High Temp & Inverter 2R44-S003 Tripped While Backseating Recirculation Suction & Discharge Valves.Cause of R44-S003 Attributed to Defective Switch
| |
| | author name = Coggin C
| |
| | author affiliation = GEORGIA POWER CO.
| |
| | addressee name =
| |
| | addressee affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
| |
| | docket = 05000321
| |
| | license number =
| |
| | contact person =
| |
| | document report number = LER-81-052-03L-01, LER-81-52-3L-1, NUDOCS 8107280382
| |
| | package number = ML20009E704
| |
| | document type = LICENSEE EVENT REPORT (SEE ALSO AO RO), TEXT-SAFETY REPORT
| |
| | page count = 2
| |
| }}
| |
| {{LER
| |
| | Title = /03L-0:on 810621,low Pressure Core Injection B Inverter R44-S003 Tripped on High Temp & Inverter 2R44-S003 Tripped While Backseating Recirculation Suction & Discharge Valves.Cause of R44-S003 Attributed to Defective Switch
| |
| | Plant =
| |
| | Reporting criterion =
| |
| | Power level =
| |
| | Mode =
| |
| | Docket = 05000321
| |
| | LER year = 1981
| |
| | LER number = 52
| |
| | LER revision = 3
| |
| | Event date =
| |
| | Report date =
| |
| | ENS =
| |
| | abstract =
| |
| }}
| |
| | |
| =text=
| |
| {{#Wiki_filter:NRC FORM 366 U. S. NUCLEAR REGULATORY COMMISSION (7 77)
| |
| LICENSEE EVENT REPORT control block: l l
| |
| l l
| |
| l l lh (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION) 1 6
| |
| lo l i l l G l A l E l I l H l 1 l@l 0 l 0 l 10 l 0 l 0 l 0 l 0 l-l 0 l 0 l@l 4 Il l1 11 l 1 l@l l
| |
| l@
| |
| 7 8 9 LICENSEE CODE 14 15 LICENSE NUMBER 25 26 LICENSE TYPE 30 57 CAT 58 con'T "E" E I L l@l 015101010131211 l@l 01612 Il i 811 l@l 017 l Ol 918 l 1 l@
| |
| lolil S uR 7
| |
| 8 60 61 DOCKET NUMBER 68 69 EVENT DATE 74 75 REPORT DATE 80 EVENT oESCRIPTioN AND PROBABLE CONSEQUENCES h lo121l'B' LPCI inverter R44-S003 tripped on 4 separate occasions on high temp l [o i3i lresulting in loss of power to
| |
| 'B' recirc suction and discharge valves l
| |
| lo 141 land LPCI injection valve (making RHR B loop inop).
| |
| 'B' LPCI inverter l
| |
| Iolsi12R44-S003 tripped while separately backseating rectrc suction and dis-I lo is i Icha rae valves 2831-F023B and F0318. respectively.
| |
| The recirc valves andl 1o171ILPCI injection valve had no power making RHR B loop inop.
| |
| There were I
| |
| lol81 Ino effects upon public health and safety due to':iis. event.
| |
| I 80 7
| |
| 8 9 E
| |
| OE SU C E COMPON ENT CODE SUSCOD'E S
| |
| E Lol9l l E I D l@ l_E_j@ l G l@ lG lE IN lE lR lA l@ l F l@ l_Z_J @
| |
| '7 8
| |
| 9 10 11 12 13 18 19 20 SEQUENTIAL OCCURRENCS
| |
| :- REPORT REVISION EVENT YE AR R EPORT NO.
| |
| CODE TYPE N O.
| |
| @ y"LER/RO1811 l l-l l 01 Sl 21 W
| |
| l01 31 W
| |
| l-l l01 ug E
| |
| 21 22 23 24 26 27 28 29 30 31 32 K N AC ON P T
| |
| ME HOURS S8 i FC 8.
| |
| SUP L MANUF RER lAl@lEl@
| |
| lZl@
| |
| [Z j@
| |
| lo101010l l_,y.j @
| |
| (_L}@
| |
| l A l@
| |
| lE131515l@
| |
| 33 34 35 36 31 40 41 42 43 44 47 CAUSE DESCRIPT!oN AND CORRECTIVE ACTIONS 11101ITriooina of R44-S003 was attributed to defective switchles) in the in-l I
| |
| 11 111 Ivorter lools )
| |
| These switches will ha ronlaced tn nrovant recorronco lii2i lof this problem.
| |
| Cause for 2R44-S003 could not be determined since all I m l alarms were reset and not noted.
| |
| Further investigation will be per-l 12 141 Iformed when Unit 2 has an outage of sufficient duration to do so.
| |
| I 7
| |
| 8 9 80 ST
| |
| % POWER OTHER STATUS dis O RY DISCOVERY DESCRIPTION Ii I5 I lE_J@ 10 I 7 l 2 l@l NA l
| |
| l Al@l Operator Observation l
| |
| ACTIVITY CO TENT RELEASED OF RELEASE AMOUNT CF ACTIVITY LOCATION OF RELEASE I1 16l [_L} @ [Lj @ l NA l
| |
| l NA l
| |
| 7 8 9 10 11 44 45 80 PERSONNEL EXPOSURES NUMSER TYPE
| |
| | |
| ==DESCRIPTION==
| |
| li l 71 101 O l O l@l Z l@l NA l
| |
| 2 u
| |
| a PERSONee't iNau'R,,,
| |
| NUMBER DESCRIP TION li la l l Ol 01 Ol@l NA l
| |
| 7 8 9 11 12 80 TYPE DESCR PTION R l Zl@l NA l
| |
| 8 9 10 80 PUBLICITY 8107280382 810709 NRC USE ONLY ISSU ED PDR ADOCK 05000321 121 o ] [JJ@ DESCRIPTION l
| |
| S PDR l
| |
| l l l l l l l l l l l l I ;,
| |
| 7 8 9 10 68 69 80 5 NN
| |
| | |
| 5 O
| |
| i.
| |
| LER #:
| |
| 50-321/1981-052 Licensee:
| |
| Georgia Power Company Facility Name:
| |
| Edwin I. Hatch j
| |
| Docket #:
| |
| 50-321
| |
| | |
| =Narrative=
| |
| Report for LER 50-321/1981-052 The
| |
| 'B' LPCI inverter R44-S003 tripped on overtemperature on four (4) separate occasions.
| |
| These trips occurred on 6-10-81 at 0317 CDT, 6-18-81 at 0010 CDT, 6-18-81 at 1217 CDT, and 6-21-81 at 1850 CDT and were reported on deviation report numbers 1-81-119, 1-81-128, 1-81-130, and 1-81-134, respec-tively.
| |
| The cause of these trips was attributed to defective temperature switch (es) in the inverter leg (s).
| |
| All the i
| |
| temperature switches will be changed out to prevent recur-rence of this problem.
| |
| Following each trip the inverter was reset and returned to service.
| |
| The loss of this inverter resulting from an overtemperature trip was reported on LERs j
| |
| 50-321/1980-082, 092, 102, but was attributed to lack of cool-ing water to the inverter room air conditioner causing a high temperature in the inverter room.
| |
| The trip in this report. was attributed to defective temperature switches which is not a repetitive occurrence for this inverter.
| |
| I The
| |
| 'B' LPCI inverter 2R44-S003 tripped on two (2). occasions
| |
| ~
| |
| while separately backseating recirc suction and discharge 1
| |
| valves 2B31-F023B and
| |
| : F031B, respectively.
| |
| These trips occurred on 6-16-81 at 1315 CDT for 2B31-F023B and on 6-16-81 at 1422 CDT f or - 2B31-F031B and were reported on deviation report numbers 2-81-102 and 2-81-104.
| |
| The cause for these l
| |
| trips could not be determined since the alarms on the inverter I
| |
| were reset and not recorded.
| |
| A standing order was written.
| |
| l requiring operations personn.el to record all alarms prior to returning the inverter (s) to service.
| |
| This will give suffic-ient information in the future to determine the cause of an i
| |
| inverter trip.
| |
| When Unit 2 has an outage of sufficient dura-tion the above valves will be backseated at separate times in an attempt.to simulate the condition that caused this inverter to trip.
| |
| The loss of the inverter in the preceding manner is a nonrepetitive occurrence.
| |
| l An update report will be issued following the replacement of the temperature switches on R44-S003 and completion of the investigation into the tripping of 2R44-S003.
| |