| | #REDIRECT [[05000324/LER-1980-026-03, /03L-0:on 800225,while Performing HPCI Steamline High Differential Pressure Channel Calibr and Functional Check,Main Streamline High Flow Instrument 2E41-DPIS-NOO4 Found Out of Tolerance.Caused by Setpoint Drift]] |
| | number = ML19323F339
| |
| | issue date = 05/12/1980
| |
| | title = During HPCI Steamline High Differential Pressure Channel Calibr Check,Main Steamline Instrument 2E41-DPIS-N004 Found Out of Tolerance. Caused by Instrument Drift.Instrument Recalibr
| |
| | author name = Tollison A
| |
| | author affiliation = CAROLINA POWER & LIGHT CO.
| |
| | addressee name =
| |
| | addressee affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
| |
| | docket = 05000324
| |
| | license number =
| |
| | contact person =
| |
| | document report number = LER-80-026-03L, LER-80-26-3L, NUDOCS 8005280795
| |
| | package number = ML19323F335
| |
| | document type = LICENSEE EVENT REPORT (SEE ALSO AO RO), TEXT-SAFETY REPORT
| |
| | page count = 2
| |
| }}
| |
| {{LER
| |
| | Title = During HPCI Steamline High Differential Pressure Channel Calibr Check,Main Steamline Instrument 2E41-DPIS-N004 Found Out of Tolerance. Caused by Instrument Drift.Instrument Recalibr
| |
| | Plant =
| |
| | Reporting criterion =
| |
| | Power level =
| |
| | Mode =
| |
| | Docket = 05000324
| |
| | LER year = 1980
| |
| | LER number = 26
| |
| | LER revision = 3
| |
| | Event date =
| |
| | Report date =
| |
| | ENS =
| |
| | abstract =
| |
| }}
| |
| | |
| =text=
| |
| {{#Wiki_filter:NRC FOIM 366 U. S. NUCLE AR REGULATORY COMMISSION UPDATE REPORT:
| |
| PREVIOUS LICENSEE EVENT REPORT REPORT DATE 3-13-80 CONrROL etOC(: l l
| |
| l l
| |
| l l
| |
| l@
| |
| (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION)
| |
| @ lNlClBlElPj 2 l@l 0 l0 l-l 0 l0 l0 l0 l 0 l - l 0 l 0 l@l 4l 1l ll 1l 1l@l l
| |
| l@
| |
| 7 8 9 LICENSEE COGE 14 LICENSE NuvtsEH 26 26 LICENSE TYPE Jo 5 7 CA T $8 CON'T 10IiI 5ERCE I b hl 0 l 5 l 0 l-l 0 l 3 l 2 l4 @l 0 l 2 l 2 l 5 l 8 l 0 l@l 0l S l 1l 21 8 l 0 l 7
| |
| 8 60 si DOCKET NUYSER 6a 63 EVENT DATE 14 75 REPORT QATE 80 EVENT DESCRIPTION AND PROBABLE CONSEQUENCES h ql While performing PT 2.1.lPC, HPCI Steamline High Differential Pressure Channel Cali-l bration and Functional Check, main steamline high flow instrument 2E41-DPIS-N004 was l gl gl found out of tolerance. The value found was 225 inches of water and the reportable l
| |
| g ; limit is greater than 219 inches of water (300% flow).
| |
| l l
| |
| l o 16 I I lo l 71 I I
| |
| I 10181 l 80 7
| |
| 8 9 E
| |
| Cout SUSC E COMPONENT CODE SUS ODE SU E
| |
| l S l F l@ W@ l G l@ l I l N l S l T l R l U l@ lS l@ [Zj @
| |
| o 9 7
| |
| 8 9
| |
| to 11 12 13 is
| |
| '9 20 SEQUENTIAL OCCURRENCE RE# CAT REVISION LER Ro EVENT YE AR R EPORT No.
| |
| CCCE TYPE No.
| |
| O asgr 18 10 I l_J l012l6l l-l l0 l3 l ltl l_1 l 11 su 21 22 23 24 26 27 29 9
| |
| 30 31 32 7 K N AC C ON PL NT hours 22 S SP t FOR 8.
| |
| S #8' if MANUFACTURER l E l@l A l@
| |
| Qj@
| |
| l Zl@
| |
| l 0l 0l 0l 0]
| |
| [Yj@
| |
| lYlg lNl@
| |
| lBl0l8l0l@
| |
| 33 34 35 36 3'
| |
| 40 44 42 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS lilo l l The out of tolerance setpoint was attributed to instrument drift. The instrument was-l l
| |
| [i j i j j recalibrated and returned to service.
| |
| This is considered an isolated event and no l
| |
| ,,,,,l further action is required. Although this is an isolated event on this instrument, i
| |
| it is scheduled to be replaced with an analog transmitter during a future outage.
| |
| l gl I
| |
| L'_Li.] I 7
| |
| 8 9 80 oT*ER STATUS @$iSEoNOY oiSCoVERY OESCRIPTION @
| |
| '^$IS" sPonER Sr Q [Ej@ l0l9l5l@l NAl l B l@] Periodic Test l
| |
| '8 8
| |
| A$TiviTY Co'0 TENT AuousTcF ACTIVITY @ l LOCATION CF RELE ASE f7T61 W @o or Rett *SElzl@l attEASE NA l
| |
| NA l
| |
| 7 8 9 10 11 44 45 80 PERSONNEL EupO5URES 1010 l o l@l z i@ DESCRIPTION NUMBER TYPE l
| |
| NA l
| |
| i i
| |
| ,E,,$oNNE'L,N,u A ES oESCRiPrioN@
| |
| NuunER l i l - l l 0 l 0 l 0 l@l NA l
| |
| 7 8 9 11 12 80 LOSS OF CH DA*.' AGE to F ACILtTY T4PE DESCns e tiCN I W lzl@l NA l
| |
| 10 80 1
| |
| .'>.l'""
| |
| L&.1 LNl,@f,'EC..1,0N @
| |
| 8005280'795 l
| |
| Nac Use ONtv l
| |
| N^
| |
| l i IIIIIIIIIIIl5 1
| |
| 1
| |
| *)
| |
| to 1A ti9 HU. 5
| |
| ^ c Totitsoa. Jr-em-m g,
| |
| (
| |
| NAuE OP RnE,anen Pe ON,.
| |
| | |
| LER ATTACHMENT - RO NO. 2-80-26 Facility: BSEP Unit No. 2 Event Date: February 25, 1980 During the 1980 Unit No. 2 refueling outage, several instruments were scheduled to be replaced with more reliable analog-type instrumentation.
| |
| Prior to the refueling outage, Carolina Power & Light Company contacted other utilities which had already made this conversion to learn of any problems they experienced.
| |
| From these conversations, it was decided that a thorough bench-testing program should be implemented before actual installation.
| |
| During this bench testing, several problems were ider.tified which we feel make these Lastruments unsuit-able for operation at this time. Upon completion of correcting these problems and thorough testing, this new analog instrumentation will be installed.
| |
| 6 A
| |