05000366/LER-1980-045-01, Leak Rate Test Performed on Automatic Depressurization Sys Valves Revealed Unacceptable Leakage Rates.Probably Caused by Heat Damage from Installation Welding.Valves Will Be Replaced: Difference between revisions

From kanterella
Jump to navigation Jump to search
StriderTol Bot insert
 
StriderTol Bot change
 
Line 1: Line 1:
{{Adams
#REDIRECT [[05000366/LER-1980-045-01, /01X-1:on 800404,during Cold Shutdown,Leak Rate Test of Air Supply Accumulator Check Valves,For Automatic Depressurization Sys Valves Revealed Unacceptable Leakage Rate.Caused by Heat Damage from Installation Welding]]
| number = ML20004B957
| issue date = 05/27/1981
| title = Leak Rate Test Performed on Automatic Depressurization Sys Valves Revealed Unacceptable Leakage Rates.Probably Caused by Heat Damage from Installation Welding.Valves Will Be Replaced
| author name = Coggin C, Coggins C
| author affiliation = GEORGIA POWER CO.
| addressee name =
| addressee affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
| docket = 05000366
| license number =
| contact person =
| document report number = LER-80-045-01X, LER-80-45-1X, NUDOCS 8106010353
| package number = ML20004B951
| document type = LICENSEE EVENT REPORT (SEE ALSO AO RO), TEXT-SAFETY REPORT
| page count = 2
}}
{{LER
| Title = Leak Rate Test Performed on Automatic Depressurization Sys Valves Revealed Unacceptable Leakage Rates.Probably Caused by Heat Damage from Installation Welding.Valves Will Be Replaced
| Plant =
| Reporting criterion =
| Power level =
| Mode =
| Docket = 05000366
| LER year = 1980
| LER number = 45
| LER revision = 1
| Event date =
| Report date =
| ENS =
| abstract =
}}
 
=text=
{{#Wiki_filter:"~
LICENSEE EVENT REPORT con 1n,ot aLoc.:
l l
1 l
l l@
U ga,tg, g,p,q,j,gg W,luNiPtTik r oNu A1fois EGIALEIIlHI2l@l010l-1010I01010l-1010_l@l4IlIl1111l@l l
l@
a i a 9 LICENSLE t, ODE 14 15 LICENSE NUMutH 2b 2th LICEN5L T YPE Ju bl CA T bd CoiB'T l O l i $ ;T, s LLJ@l 015 101010131616 l@lo 14 lo la l a lo l@l of El 217 la Il G 7
8 60 61 DOCKET NUYuEH 68 69 EN ENT DATE 14
'/ b REPORT DATE
*J EVENT DESCRIPTION AND PRoRADLE CONSEcuENCES h o 2 IWith the unit in cold shutdown a leak rate test was performed qn the ADSI 1o: 31 I valves ' air supply accumulator, check valves.
The AE determined that thel inl41lleakage rates that were found were unacceptable and that a los of air I
o b isupply could lead to ADS inoperability.
This event caused no threat to I 10161 l publi c heal th o r s a f ety.
This is a nonrepetitive event for these volves.1 I
I O' l 71 1 I
10181 I SO C E CODE S SCO E COVPON ENT CODE SU8C dE SU ODE 1.O l o l l S I F l@ l B l@,1 Cl@ l V I Al L l V l E l X l@ l C l@ [A_j @
7 8
9 10 11 12 13 18 19 N
SE QUE N TI AL OCCU R R E NCE REPORT REVISION LE R EVENT YE AR RE PORT NO, CODE TYPE N O.
@ sgg.RO I al 01 l-l 1 01 al si l/l 10111 Lxj l-l 14I a
_ 21 22 23 24 2ti 27 28 29 30 31 32 AK r A TO ON PL NT E
HOURS SB IT D F Of 5 t, D.
PLIE MAN F CTLIER L_EJ@L_aj@
LZ ]@
l_z_j@
l 01 01 01 O l l Yl@
l fi l@
l Al@
lRl314l41@
33 34 3b 36 37 40 41 42 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS li10)ICause of this event is believed to be heat damage from i ns tall a ti on wel d-l
> Li_LtJ M.
These valves were to be replaced with sof t-seated valves durina i
sii3]Ithe Unit 2 refueling outage; however, parts were unavailable at that I
tilatltime, installation will be delayed until next refuelin g outage.
Proced-l 1 ' 14 I I ures for both uni ts have been revised to inform operntors of this failure mode._j 83 7
8 9
* POWER OT HER ST AT US 6tSC 1Y DISCOVEHY DESCRIPTION si s
NA l
(_CJ@l Special Test l
, Li 12.J l G l@ l o l o l o l@l Ac'iiviv Y C5hnT netE ctO OF nF LF ASE A.tOUNT OF ACilVITY LOCATION Of RELE ASE It IollZ! @ l_Zj @l NA l
l IlA I
J b
')
lu 11 44 4b bd PtitsO%g L FxPO5unES
\\t "Un u 1YPE D E SC nt P TION -
l It 1 I LOI 0 I 0j@l z l@l f1A
",w AS orsCniPriOnh n nsomt w. ni n l
i ITl l 01010181 rtA
.ie"' ""$d"^*"" @
hkhhk flA j
ITlL.ZJ@l
""c o a "m v Ldd Lt!f,3,,,in,Pno~@
1 N^
i i i iiiiiiiiii1-8.H 6.*t 4.0 s
ist 912-367-78'71 o,nig Am nC. L._Caggin. Supt. Plt. ErLq. Serv.
,,,,nn t.
8'1060/O ?/02
 
LER #
50-366/1980-045, Rev._4 Licensee Geo.gia Power Company Pacility Name:
Edwin I.
Hatch Docket #:
50-366
 
=Narrative=
Report for LER 50-366/J930-045, Rev. 4 W'ith the unit in cold shutdown a leak rate test was performed on the ADS valves air supply accumulator check valves in re ionse to IEB 80-01.
Results of this test were transmitted to the AE for analysis.
The AE determined that the leakage rates that were found were unacceptable and that a loss of air supply could lead to ADS inoperability.
The procedure that-dealt with the operator's response to an air supply low pres-sure alarm did not address this possibility.
These accumulator / check valve subsystems have no direct backup systems.
The air supply to the ADS valves can be obtained from the nitrogen inerting system or the instrument air system.
An automatic interlock has been installed which will line up the supply line to nitrogen in the event of an instrument air failure.
There is also a manual bypass line which can be used to supply nitrogen in the event of a failure of the automatic backup.
It is believed that this leakage was a result of heat damage to the valves which occurred during installation welding.
Replacement valves with extremely small leakage rates prior to installation showed unacceptable leakage after welding.
We were unable to obtain acceptable leakage rates for any of these valves.
The AE has specified a soft-seated model with an 0-ringed cap and longer nipples in order to alleviate the heat damage problem.
These soft-seated valves are on order and were to be installed during the current refueling outage.
There has been some degree of difficulty in obtaining the suitable valves.
Although the order has been expedited, delivery will not be made until after Unit 2 is restarted.
Replacement of these valves will be rescheduled for the next refueling outage.
The Unit 1 ADS air supply accumulator check 2
valves were leak rate tested during the 1981 refueling outage.
2 out of 7
valves exhibited unacceptable leakage rates.
Due to unavailabiU ty of parts during the 1981 refuel-ing outage, these valves will be replaced with soft-seated valves during the next Unit I refueling outage.
Procedures tor both u-it have been revised to call for declaration of ADS inoperability upon receipt of an air supply line low pressure alarm.
This provides assurance that a possibly unsafe condi-tion will be recognized and dealt with.in a
controlled manner.
This is a nonrepetitive occurrence.
This event poned no threat to public health or safety.
}}
 