| event date = 10/31/2004 22:56 CDT
| event date = 10/31/2004 22:56 CDT
| last update date = 11/01/2004
| last update date = 11/01/2004
| title = Plant Had Auto Start Of The Division 1 Emergency Diesel Generator
| title = Plant Had Auto Start of the Division 1 Emergency Diesel Generator
| event text = Undervoltage conditions were experienced on Division 1 emergency switchgear with subsequent start and load of the respective diesel generator [EDG].  A preliminary investigation indicates that an unexpected undervoltage signal was generated when technicians inadvertently contacted the wrong terminals during preparations for the respective division ECCS surveillance testing.  All systems and equipment responded as required.
| event text = Undervoltage conditions were experienced on Division 1 emergency switchgear with subsequent start and load of the respective diesel generator [EDG].  A preliminary investigation indicates that an unexpected undervoltage signal was generated when technicians inadvertently contacted the wrong terminals during preparations for the respective division ECCS surveillance testing.  All systems and equipment responded as required.
Power is still being provided (as of event reporting time) by the Division 1 EDG while they are working to restore normal power.  
Power is still being provided (as of event reporting time) by the Division 1 EDG while they are working to restore normal power.  

Latest revision as of 21:22, 1 March 2018

ENS 41164 +/-
Where
River Bend Entergy icon.png
Louisiana (NRC Region 4)
Reporting
10 CFR 50.72(b)(3)(iv)(A), System Actuation
Time - Person (Reporting Time:+-1.72 h-0.0717 days <br />-0.0102 weeks <br />-0.00236 months <br />)
Opened: David Clymer
02:13 Nov 1, 2004
NRC Officer: Chauncey Gould
Last Updated: Nov 1, 2004
41164 - NRC Website
Loading map...