ENS 43895: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 16: | Line 16: | ||
| event date = 01/11/2008 16:22 CST | | event date = 01/11/2008 16:22 CST | ||
| last update date = 01/14/2008 | | last update date = 01/14/2008 | ||
| title = Tech. Spec. Required Shutdown Due | | title = Tech. Spec. Required Shutdown Due to Gas Voiding in Discharge Piping | ||
| event text = Gas intrusion into ECCS piping required entry into Technical Specification (TS) 3.0.3. | | event text = Gas intrusion into ECCS piping required entry into Technical Specification (TS) 3.0.3. | ||
Wolf Creek was operating at 100% power when gas voiding was discovered in RHR discharge piping common to both trains of ECCS. Due to void reoccurring in excess of predetermined limits both trains of ECCS were declared inoperable at 1525 CST. A TS required shutdown was commenced at 1622. | Wolf Creek was operating at 100% power when gas voiding was discovered in RHR discharge piping common to both trains of ECCS. Due to void reoccurring in excess of predetermined limits both trains of ECCS were declared inoperable at 1525 CST. A TS required shutdown was commenced at 1622. |
Latest revision as of 21:15, 1 March 2018
Where | |
---|---|
Wolf Creek Kansas (NRC Region 4) | |
Reporting | |
10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown | |
Time - Person (Reporting Time:+-4.48 h-0.187 days <br />-0.0267 weeks <br />-0.00614 months <br />) | |
Opened: | Jeff Isch 17:53 Jan 11, 2008 |
NRC Officer: | Joe O'Hara |
Last Updated: | Jan 14, 2008 |
43895 - NRC Website
| |