| title = LER 82-036/03L-0:on 820516,w/unit at 74% Power,Emergency Diesel Generator 1J Output Breaker Failed to Close During Periodic Surveillance Test.Caused by Failure of Undervoltage Relay 27X.Relay Replaced
| author name = Cartwright W
| author affiliation = VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
| addressee name =
| addressee affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
| docket = 05000338
| license number =
| contact person =
| document report number = LER-82-036-03L-01, LER-82-36-3L-1, NUDOCS 8206210312
| package number = ML20054G246
| document type = LICENSEE EVENT REPORT (SEE ALSO AO RO), TEXT-SAFETY REPORT
| page count = 2
}}
{{LER
| Title = 
| Plant =
| Reporting criterion =
| Power level =
| Mode =
| Docket = 05000338
| LER year = 2082
| LER number = 36
| LER revision =
| Event date =
| Report date =
| ENS =
| abstract =
}}
 
=text=
{{#Wiki_filter:,
-    M U.S. NUCLEAR REGULATORY COMMISSION LICENSEE EVENT REPORT CONTROL BLOCK / / / / / / / (1) (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION)
  /0/1/          /V/A/N/A/S/1/ (2)              /0/0/-/0/0/0/0/0/-/0/0/ (3)              /4/1/1/1/1/ (4)        // / (5)
LICENSEE CODE                        LICENSE NUMBER                      LICENSE TYPE            CAT S UR E  IL/ (6)
                                        /0/5/0/0/0/3/3/8/      (7)    /0/5/1/6/8/2/ (8)        h A /1 h A h / (9)
DOCKET NUMBER                EVENT DATE                  REPORT DATE EVENT DESCRIPTION AND PROBABLE CONSEQUENCES (10)
  /0/2/      / On May 16, 1982 with Unit No. I at 74% power, the IJ emergency diesel output                          /
  /0/3/      / breaker failed to close during a periodic surveillance test.                    The 111 diesel was /
  /0/4/      / verified to be operable and no loss of off-site power occurred; therfore, the                          /
f0/5/      / health and safety of the general public were not affected. This is contrary to /
  /0/6/      / the LCO but within the action for T.S. 3.8.1.1 and reportable pursuant to                              /
  /0/7/      / T.S. 6.9.1.9.b.                                                                                        /
  /0/8/      /                                                                                                        /
SYSTEM        CAUSE        CAUSE                                  COMP.          VALVE CODE          CODE        SUBCODE      COMPONENT CODE            SUBCODE        SUBCODE
  /0/9/          /E/E/ (11)    /E/ (12)      /A/ (13) /R/E/L/A/Y/X/      (14)    /D/ (15)          /Z/ (16)
SEQUENTIAL            OCCURRENCE          REPORT          REVISION LER/R0    EVENT YEAR          REPORT NO.                CODE          TYPE                  NO.
(17)    REPORT NUMBER      /8/2/        /-/ /0/3/6/        /  /        /0/3/          /L/      /-/      /0/
ACTION        FUTURE      EFFECT      SilUTDOWN                  ATTACllMENT NPRD-4        PRIME COMP. COMPONENT TAKEN          ACTION      ON PLANT METll0D          110URS      SUBMITTED FORM SUB. SUPPLIER            MANUFACTURER
  /C/ (18)      /Z/ (19)    /Z/ (20)    /Z/ (21) /0/0/0/0/ (22) /N/ (23) /Y/ (24) /A/ (25) /G/0/8/0/ (26)
CAUSE DESCRIPTION AND CORRECTIVE ACTIONS (27)
  /1/0/      / The undervoltage relay (27X) in the IJ emergency diesel output breaker circuit                        /
  /1/1/      / failed in the de-energized position.              This failure prevented the diesel output            /
  /1/2/      / breaker from closing. The lit diesel was verified to be operable, the defective /
  /1/3/      / relay was replaced and the breaker operation was verified.                                            /
  /1/4/      /                                                                                                      /
FACILITY                                                    METilOD OF STATUS          % POWER            OTilER STATUS        DISCOVERY              DISCOVERY DESCRIPTION (32)
  /1/5/      /E/ (28)      /0/7/4/ (29) /            NA        / (30)    /B/ (31)          / Periodic Surveillance /
ACTIVITY        CONTENT RELEASED      OF RELEASE        AMOUNT OF ACTIVITY (35)                  LOCATION OF RELEASE (36)
  /1/6/        /Z/ (33)    /Z/ (34)    /          NA                /    /          NA                          /
PERSONNEL EXPOSURES NUMBER          TYPE          DESCRIPTION (39)
  /1/7/    /0/0/0/ (37) /Z/ (38)        /      NA                                                                  /
PERSONNEL INJURIES NUMBER          DESCRIPTION (41)
  /1/8/    /0/0/0/ (40) /                NA                                                                          /
LOSS OF OR DAMAGE TO FACILITY TYPE        DESCRIPTION (43)
  /1/9/      /Z/ (42)    /          NA                                                                              /
PUBLICITY ISSUED        DESCRIPTION (45)                                                    NRC USE ONLY
  /2/0/      /N/ (44)    /          NA                                                    /////////////
NAME OF PREPARER            W. R. CARTURICllT              PHONE    (703) 894-5151 8206210312 820611 PDR ADOCK 05000338 S                      PDR
 
e 1
Virginia Electric and Power Company
          ' North Anna Power Station, Unit No. 1         
 
==Attachment:==
Page 1 of 1 Docket No. 50-338 Attachment to LER 82-036/03L-0 Description of Event on May 16, 1982 with Unit No. I at 74% power, the IJ emergency diesel output breaker failed to close during a periodic surveillance test.
Probable Consequences of Occurrence The operability of the remaining A.C. sources was verified as per T.S. 3.8.1.1 and no loss of off-site power occurred; therefore, the health and safety of the general public were not affected.
Cause of Event The undervoltage relay (27X) for the IJ diesel output breaker circuit failed in the de-energized position. This caused the breaker to be locked out due to open series contacts in the control circuit for the breaker closing mechanism.
Immediate Corrective Action The remaining A.C. power sources were verified to be operable. The 27X relay was replaced and the diesel output breaker was verified to be operable.
Scheduled Corrective Action No further corrective action is scheduled.
Action Taken To Prevent Recurrence No further action is required.
Generic Implications There are no generic implications associated with this event.