Line 6: Line 6:
| number = ML17317B374
| number = ML17317B374
| issue date = 07/25/1979
| issue date = 07/25/1979
| title = Forwards LER 79-022/03L-0
| title = LER 79-022/03L-0 on 790706:bistable 2PB-934B Tripped at Value Exceeding Tech Spec Limit by 0.104 Psi During Surveillance Test on Containment Pressure Protection.Caused by Drifting of Bistable Trip Set Point.Bistable Replaced
| author name = Rischling J
| author name = Rischling J
| author affiliation = INDIANA MICHIGAN POWER CO.
| author affiliation = INDIANA MICHIGAN POWER CO.

Latest revision as of 09:39, 7 March 2020

Forwards LER 79-022/03L-0
Date released: 05/31/2018 Download: ML17317B373


LER 79-022/03L-0 on 790706:bistable 2PB-934B Tripped at Value Exceeding Tech Spec Limit by 0.104 Psi During Surveillance Test on Containment Pressure Protection.Caused by Drifting of Bistable Trip Set Point.Bistable Replaced
ML17317B374
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 07/25/1979
From: Rischling J
INDIANA MICHIGAN POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17317B374 (4)
Forwards LER 79-022/03L-0
ML17317B372
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 07/25/1979
From: Shaller D
INDIANA MICHIGAN POWER CO.
To: KEPPLER J G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17317B372 (2)