| title = Forwards Response to NRC 800502 Ltr Re Violations Noted in IE Insp Repts 50-315/80-04 & 50-316/80-03.Corrective Actions:Procedure Changed to Prohibit Use of Hoses for Making Up Water to Spent Fuel Pit & Valves Locked Closed | | title = Forwards Response to NRC 800502 Ltr Re Violations Noted in IE Insp Repts 50-315/80-04 & 50-316/80-03.Corrective Actions:Procedure Changed to Prohibit Use of Hoses for Making Up Water to Spent Fuel Pit & Valves Locked Closed | ||
| author name = | | author name = Dolan J | ||
| author affiliation = INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG | | author affiliation = INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG | ||
| addressee name = | | addressee name = Keppler J | ||
| addressee affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) | | addressee affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) | ||
| docket = 05000315, 05000316 | | docket = 05000315, 05000316 | ||
Revision as of 15:32, 18 June 2019
| ML17326A700 | |
| Person / Time | |
|---|---|
| Site: | Cook |
| Issue date: | 05/30/1980 |
| From: | Dolan J INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG |
| To: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| Shared Package | |
| ML17326A701 | List: |
| References | |
| AEP:NRC:00413, AEP:NRC:413, NUDOCS 8007310284 | |
| Download: ML17326A700 (6) | |
See also: IR 05000315/1980004
Text
INDIANA L MICHIGAN ELECTRIC COMPANY P.O.BOX 18 80 WL IN 0 OR E EN ST ATION NEW YORK, N.Y.10004 Donald C.Cook Nuclear Plant Units No.1 and 2 Docket Nos.50-315 and 50-316 License Nos.DPR-58 and DPR-74 IE Inspection
Reports No.50-31'5/80-04
and No.50-316/80-03
Response to Notice of Violation May 30, 1980 AEP:NRC:00413
Mr.James G.Keppler, Regional Director U.S.Nuclear Regulatory
Commission
Office of Inspection
and Enforcement
Region III 799 Roosevelt Road Glen Ellyn, Illinois 60137 Dear Mr.Keppler: The Attachment
to this')etter is our response to the Notice of Violation cited in Appendix A to Mr.R.F.Heishman's
letter of May 2, 1980.On May 23, 1980 our Dr.Castresana
obtai.ned an extension to the due date of this submittal until May 30, 1980 from your Mr.Heishman.Very truly yours, ohn E.Dolan ice President JED:dfs Attachment
cc: R.C.Callen G.Charnoff RE S.Hunter R.M.Jurgensen D.V.Shaller-Bridgman 2'980
gP e r+ATTACHMENT
TO AEP:NRC:00413
y<o>ation 1 Technical Specification 6.8.1 requires implementation
of procedures,.
12-0HP-4021.018.004"Draining or Adjusting Level in the Spent Fuel.Pit" details the procedure for raising level in the SFP.'ontrary to the above, this procedure was not used for increasing
lev'el in the SFP between March 15, 1980 and March 17, 1980, when the pool was overfilled
and cross-contamination
of'the demineralized
water system occurred.~Res ense: During the fuel storage rack modification, demineralized
water was being used at the spent fuel pit for two purposes: 1)as a supply of clean water for decontamination
of the old racks being removed, and 2)as a source of priming water for a vacuum pump used for cleaning the spent fuel pi t fl oor.The demineralized
water system contamination
investigation
revealed that the cross contamination
of the demineralized
water header occurred through.the hose connection
used for the vacuum pump priming: The one end of the hose was found disconnected
from the vacuum pump and the free end left hanging submerged in the spent fuel pit.It is believed that the shut off valve at the demineralized
water header hose connection
had been left open.This would permit water to flow into the pit whenever the demineralized
water booster pump was running.The booster pump is required to supply water at this elevation.
When the booster pump was shut down, the low header pressure would.permit water to be siphoned from the spent fuel pit into the demineralized
water header.The daily spent fuel pit level readings show a gradual increase in level until the spent fuel pit was found overflowing
into the fuel transfer canal.The level was then lowered in accordance
with approved procedures.
During the time leading up to the cross contamination
of the demineralized
water header and the overflowing
of the spent fuel pit, there was no intentional
action to raise the level in the spent fuel pit and therefore the citation for failure to use an approved procedure for increasing
the level does not seem warranted.
- It is felt that the root cause for this entire incident, the increase in spent fuel pit level, the dilution of the boron concentration
below the required minimum, and the cross contamination
of the demineralized
water header, can be attributed
to a breakdown in the control of the activities
associated
with/the spent fuel rack modification.
Positive steps have been taken, as indicated below, to prevent the re-occurrence
of a similar event.
pctions Taken to Prevent Re-Occurence
A precaution
has been added to Procedure 12-0HP-4021-018.004
to prevent the use of hoses for making up water to the spent fuel pit.2.3.The demineralized
water valves in the vicinity of the spent fuel pit have been locked closed with Operations
Department
padlocks.This will assure notification
of the operators prior to future use of these valves.Check valves have been installed at the demineralized
water outlets in the vicinity of the spent fuel pit to prevent backflow and cross-contamination
of the demineralized
water system.s Controls have been imposed on the use of.demineralized
water from Laboratories
for human consumption
purposes.Violation 2: Amendment 832 to NRC Operating License Number DPR-58 and'mendment 8]3 to DPR-74 require a minimum of 2000 ppm Boron concentration
in the Spent Fuel Pit during changeout from old racks to new high density fuel storage.racks.Contrary to the above, on March 17, 1980, the SFP concentration
was found to be less than 2000 ppm (1954 ppm).~Res ense: The dilution of the spent fuel pit resulted from the un-intentional
addition of water to the spent fuel pit as described in Violation 1.Corrective
actions were immediately
initiated to increase boron concentration
to greater than 2000 ppm upon discovery of the low concentrati
on.s Actions Taken to Prevent Re-Occurence
'he specific requirements
of Amendment 832, to NRC Operating License DPR-58 and Amendment 5'13 to DPR-74, requiring a minimum of 2000 ppm boron in the spent fuel pit, no longer exist since the spent fuel storage rack modification
'is now complete.The prevent)ve
actions discussed under Violation 1 apply generically
to this condition.
JUN 2~gap