Line 16: Line 16:
| event date = 05/04/2007 23:05 CDT
| event date = 05/04/2007 23:05 CDT
| last update date = 05/05/2007
| last update date = 05/05/2007
| title = Manual Reactor Scram On Loss Of Feedwater
| title = Manual Reactor Scram on Loss of Feedwater
| event text = The condensate prefilters isolated earlier in the day and the bypass valve automatically opened.  The computer controlling these valves was in the process of being replaced when the bypass valve shut.   
| event text = The condensate prefilters isolated earlier in the day and the bypass valve automatically opened.  The computer controlling these valves was in the process of being replaced when the bypass valve shut.   
Unit experienced a loss of feedwater due to condensate pre-filter valves going closed.  The reactor was manually scrammed and HPCI was used to restore reactor water level.  MSIVs closed and the U2 and U2/3 EDGs auto started on low level.
Unit experienced a loss of feedwater due to condensate pre-filter valves going closed.  The reactor was manually scrammed and HPCI was used to restore reactor water level.  MSIVs closed and the U2 and U2/3 EDGs auto started on low level.

Latest revision as of 21:16, 1 March 2018

ENS 43346 +/-
Where
Dresden Constellation icon.png
Illinois (NRC Region 3)
Reporting
10 CFR 50.72(b)(2)(iv)(A), System Actuation - ECCS Discharge

10 CFR 50.72(b)(2)(iv)(B), RPS Actuation

10 CFR 50.72(b)(3)(iv)(A), System Actuation
Time - Person (Reporting Time:+-1.87 h-0.0779 days <br />-0.0111 weeks <br />-0.00256 months <br />)
Opened: Chris Kent
02:13 May 5, 2007
NRC Officer: Mark Abramovitz
Last Updated: May 5, 2007
43346 - NRC Website
Loading map...