Line 16: Line 16:
| event date = 08/21/2007 14:15 CDT
| event date = 08/21/2007 14:15 CDT
| last update date = 08/21/2007
| last update date = 08/21/2007
| title = Reactor  Scrammed Due To Reactor Water Level 3  Rps Actuation
| title = Reactor  Scrammed Due to Reactor Water Level 3  Rps Actuation
| event text = The 'A' Reactor Feed Pump controller failed downscale causing reactor water level to lower.  Feed pump was manually tripped as reactor water level passed through 20 inches (Narrow Range) in an attempt to stabilize level.
| event text = The 'A' Reactor Feed Pump controller failed downscale causing reactor water level to lower.  Feed pump was manually tripped as reactor water level passed through 20 inches (Narrow Range) in an attempt to stabilize level.
Reactor scrammed on Level 3 (11.4") as designed.  Mode switch placed in Shutdown.  Lowest level observed was -25".  All control rods fully inserted.  No ECCS initiations were received and all systems responded as designed.   
Reactor scrammed on Level 3 (11.4") as designed.  Mode switch placed in Shutdown.  Lowest level observed was -25".  All control rods fully inserted.  No ECCS initiations were received and all systems responded as designed.   

Latest revision as of 22:16, 1 March 2018

ENS 43584 +/-
Where
Grand Gulf Entergy icon.png
Mississippi (NRC Region 4)
Reporting
10 CFR 50.72(b)(2)(iv)(B), RPS Actuation
Time - Person (Reporting Time:+-2.28 h-0.095 days <br />-0.0136 weeks <br />-0.00312 months <br />)
Opened: Ernest Mathes
16:58 Aug 21, 2007
NRC Officer: John Knoke
Last Updated: Aug 21, 2007