| title = Loss | | title = Loss of Shutdown Cooling | ||
| event text = On 11/2/09 at 0712 shutdown cooling (SDC) was lost on Dresden Unit 2 when a recirculation loop temperature element (2-0260-13B) failed upscale. Unit 2 was in the process of initial cooldown for entry into a refueling outage. Recirculation loop temperature was approximately 224 degrees F based on alternate indications. The circuitry was jumpered out and SDC was restarted at 0748. The Recirculation loop temperature was at 260 degrees F upon restart. At 0835, the reactor entered Mode 4 (i.e., Recirculation loop temperature less than or equal to 212 degrees F and Mode Switch in Shutdown). This event is reportable under 10CFR 50.72(b)(3)(v)(B). This event is being reported based on lessons learned from industry experience and is undergoing further review. | | event text = On 11/2/09 at 0712 shutdown cooling (SDC) was lost on Dresden Unit 2 when a recirculation loop temperature element (2-0260-13B) failed upscale. Unit 2 was in the process of initial cooldown for entry into a refueling outage. Recirculation loop temperature was approximately 224 degrees F based on alternate indications. The circuitry was jumpered out and SDC was restarted at 0748. The Recirculation loop temperature was at 260 degrees F upon restart. At 0835, the reactor entered Mode 4 (i.e., Recirculation loop temperature less than or equal to 212 degrees F and Mode Switch in Shutdown). This event is reportable under 10CFR 50.72(b)(3)(v)(B). This event is being reported based on lessons learned from industry experience and is undergoing further review. | ||
The licensee notified NRC Resident Inspector. | The licensee notified NRC Resident Inspector. | ||
Latest revision as of 21:10, 1 March 2018
| Where | |
|---|---|
| Dresden Illinois (NRC Region 3) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat | |
| Time - Person (Reporting Time:+2.18 h0.0908 days <br />0.013 weeks <br />0.00299 months <br />) | |
| Opened: | Chris Kent 14:23 Nov 2, 2009 |
| NRC Officer: | Vince Klco |
| Last Updated: | Nov 2, 2009 |