ENS 46289: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 09/29/2010 EDT
| event date = 09/29/2010 EDT
| last update date = 09/29/2010
| last update date = 09/29/2010
| title = Potential Issues With Certain Regulator Model 77N-40 Air Regulators
| title = Potential Issues with Certain Regulator Model 77N-40 Air Regulators
| event text = Dresser Masoneilan initiated a 10 CFR Part 21 investigation because of the failure of three (3) Air Regulators (model number 77N-40) at the PSE&G Salem Station within three months of being installed.  Upon testing and evaluation, Dresser Masoneilan concluded that the internal O-ring used for pressure isolation in the Air Regulators were damaged during factory assembly contributing to the failure of the units to regulate pressure.  Dresser Masoneilan has developed a corrective action plan and an in-service test method and acceptance criteria to determine if a unit is experiencing pressure loss due to the issue.  Due to the volume, age and distribution of these models, Dresser Masoneilan is issuing a general notice to all utilities.
| event text = Dresser Masoneilan initiated a 10 CFR Part 21 investigation because of the failure of three (3) Air Regulators (model number 77N-40) at the PSE&G Salem Station within three months of being installed.  Upon testing and evaluation, Dresser Masoneilan concluded that the internal O-ring used for pressure isolation in the Air Regulators were damaged during factory assembly contributing to the failure of the units to regulate pressure.  Dresser Masoneilan has developed a corrective action plan and an in-service test method and acceptance criteria to determine if a unit is experiencing pressure loss due to the issue.  Due to the volume, age and distribution of these models, Dresser Masoneilan is issuing a general notice to all utilities.
Contact Bill Comeau of Dresser Masoneilan at (508) 941-5477 with any questions concerning this notification.
Contact Bill Comeau of Dresser Masoneilan at (508) 941-5477 with any questions concerning this notification.

Latest revision as of 21:08, 1 March 2018

ENS 46289 +/-
Where
Dresser Masoneilan
Avon, Massachusetts (NRC Region 1)
Organization: Dresser Masoneilan
Reporting
10 CFR 21.21
Time - Person (Reporting Time:+11 h0.458 days <br />0.0655 weeks <br />0.0151 months <br />)
Opened: Frank Wheelright
15:00 Sep 29, 2010
NRC Officer: Eric Simpson
Last Updated: Sep 29, 2010
46289 - NRC Website