ENS 46379: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 10/29/2010 16:21 CDT
| event date = 10/29/2010 16:21 CDT
| last update date = 10/29/2010
| last update date = 10/29/2010
| title = Degraded Condition - 71% Through Wall Indication On Reactor Recirc Nozzle
| title = Degraded Condition - 71% Through Wall Indication on Reactor Recirc Nozzle
| event text = Information from a Phased Array UT [Ultrasonic Testing] examination of RRA-F002A indicates that a linear indication 6.5" long and a maximum depth of 71 % through wall extent (ID [Inner Diameter] connected) exists. The Phased Array UT examination of RRA-F002A was performed as part of scheduled outage activities.
| event text = Information from a Phased Array UT [Ultrasonic Testing] examination of RRA-F002A indicates that a linear indication 6.5" long and a maximum depth of 71 % through wall extent (ID [Inner Diameter] connected) exists. The Phased Array UT examination of RRA-F002A was performed as part of scheduled outage activities.
TRM [Technical Requirements Manual] LCO [Limiting Condition for Operation] 3.7.3 for Structural Integrity, Condition B has been entered for the Recirc nozzle/piping.
TRM [Technical Requirements Manual] LCO [Limiting Condition for Operation] 3.7.3 for Structural Integrity, Condition B has been entered for the Recirc nozzle/piping.

Latest revision as of 22:08, 1 March 2018

ENS 46379 +/-
Where
Duane Arnold NextEra Energy icon.png
Iowa (NRC Region 3)
Reporting
10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded
LER: 05000331/LER-2010-004
Time - Person (Reporting Time:+-0.37 h-0.0154 days <br />-0.0022 weeks <br />-5.06826e-4 months <br />)
Opened: Dick Fowler
20:59 Oct 29, 2010
NRC Officer: Dong Park
Last Updated: Oct 29, 2010
46379 - NRC Website