ENS 49343: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 09/14/2013 02:00 CDT
| event date = 09/14/2013 02:00 CDT
| last update date = 09/14/2013
| last update date = 09/14/2013
| title = Liquid Penetration Examination Results In Indication On Reactor Vessel Head Penetration  
| title = Liquid Penetration Examination Results in Indication on Reactor Vessel Head Penetration  
| event text = On September 14, 2013, during the A1R17 Braidwood Station Unit 1 refueling outage, an inservice Liquid Penetration examination was performed on the previously repaired Penetration 69. This repair was performed during A1R16.  The PT [Penetrant Testing] examination revealed 22 recordable indication and 5 non-relevant indications. Rounded indications that exceed 3/16" are rejectable. All 22 indications are rounded and 13 of these indications exceed the 3/16" criteria.
| event text = On September 14, 2013, during the A1R17 Braidwood Station Unit 1 refueling outage, an inservice Liquid Penetration examination was performed on the previously repaired Penetration 69. This repair was performed during A1R16.  The PT [Penetrant Testing] examination revealed 22 recordable indication and 5 non-relevant indications. Rounded indications that exceed 3/16" are rejectable. All 22 indications are rounded and 13 of these indications exceed the 3/16" criteria.
This is reportable pursuant to 10 CFR 50.72(b)(3)(ii)(A) since the as found indication did not meet the applicable acceptance criteria referenced in ASME Code Case N-729-1 to remain in-service without repair.
This is reportable pursuant to 10 CFR 50.72(b)(3)(ii)(A) since the as found indication did not meet the applicable acceptance criteria referenced in ASME Code Case N-729-1 to remain in-service without repair.

Latest revision as of 21:00, 1 March 2018

ENS 49343 +/-
Where
Braidwood Constellation icon.png
Illinois (NRC Region 3)
Reporting
10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded
LER: 05000456/LER-2013-002
Time - Person (Reporting Time:+-1.22 h-0.0508 days <br />-0.00726 weeks <br />-0.00167 months <br />)
Opened: James Ledbetter
05:47 Sep 14, 2013
NRC Officer: Dong Park
Last Updated: Sep 14, 2013
49343 - NRC Website
Loading map...