05000338/LER-1982-039: Difference between revisions

From kanterella
Jump to navigation Jump to search
StriderTol Bot change
StriderTol Bot change
Line 1: Line 1:
{{Adams
#REDIRECT [[05000338/LER-1982-039, Forwards LER 82-039/03L-0]]
| number = ML20054H527
| issue date = 06/15/1982
| title = LER 82-039/03L-0:on 820517,steam Flow Channel IV Flow Indicator FI-1485 for Steam Generator 1B Discovered Reading Offscale Low.Cause Not Determined.Channel Placed in Trip Condition,Transmitter Calibr & Instrument Loop Checked
| author name = Cartwright W
| author affiliation = VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
| addressee name =
| addressee affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
| docket = 05000338
| license number =
| contact person =
| document report number = LER-82-039-03L, NUDOCS 8206240166
| package number = ML20054H524
| document type = LICENSEE EVENT REPORT (SEE ALSO AO RO), TEXT-SAFETY REPORT
| page count = 1
}}
{{LER
| Title = 
| Plant =
| Reporting criterion =
| Power level =
| Mode =
| Docket = 05000338
| LER year = 2082
| LER number = 39
| LER revision =
| Event date =
| Report date =
| ENS =
| abstract =
}}
 
=text=
{{#Wiki_filter:e    N
    '    b,                                                                      U.S. NUCLEAR REGULATORY COMMISSION LICENSEE EVENT REPORT CONTROL BLOCK / / / / / / / (1) (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION)
    /0/1/          /V/A/N/A/S/1/ (2)            /0/0/-/0/0/0/0/0/-/0/0/ (3)                /4/1/1/1[1/ (4)      /// (5)
LICENSEE CODE                    LICENSE NUMBFR                        LICENSE TYPE          CAT
    /0/1/          RE
                                          /0/5/0/0/0/3/3/8/              /0/5/1/7/8/2/ (8) /0/6/1/5/8/2/ (9)
O      [L/ (6)                              (7)
DOCKET NUMBER                EVENT DATE                  REPORT DATE EVENT DESCRIPTION AND PROBABLE CONSEQUENCES (10)
[0/2/      / On May 17, 1982, with Unit I at 17% power, Steam Flow Channel IV (Flow Indicator /
    /0/3/      / FI-1485 for Steam Generator IB) was removed from service for reading off scale                        /
    /0/4[      / (Low). Since the channel was placed in trip within one hour and one redundant                    /
    /0/5/      / channel remained available for Steam Generator IB, the public health and safety /
    /0/6/      / were not affected.        This event is contrary to T.S. 3.3.1.1 and 3.3.2 and it is /
    /0/7/      / reportable pursuant to T.S. 6.9.1.9.b.              There are no generic implications to              /
    /0/8/      / this event.                                                                                          /
SYSTEM          CAUSE        CAUSE                              COMP.            VALVE CODE            CODE      SUBCODE      COMPONENT CODE          SUBCODE          SUBCODE
    /0/9/          /I/A/ (11) [E/ (12) [E/ (13) /I/N/S/T/R/U/ (14) [X/ (15)                          [Z/ (16)
SEQUENTIAL            OCCURRENCE          REPORT          REVISION LER/R0    EVENT YEAR        REPORT NO.                CODE            TYPE              NO.
(17) REPORT NUMBER        /8/2/      [-/ /0/3/9/        [_1_/        /0/3/          [L/      [-/.    [0/
ACTION          FUTURE      EFFECT      SHUTDOWN                  ATTACHMENT NPRD-4          PRIME COMP. COMPONENT' TAKEN          ACTION      ON PLANT METIl0D        HOURS        SUBMITTED FORM SUB. SUPPLIER MANUFACTURER-
[E/ (18) [B/ (19) [Z/ (20) /Z/ (21) /0/0/0/0/ (22) /N/ (23) [N/ (24) [A/ (25) /R/3/6/9/ (26}
CAUSE DESCRIPTION AND CORRECTIVE ACTIONS (27)
    /1/0/      / The exact cause of this event is unknown. The failed channel was placed in the /
    /1/1/      / trip condition and the transmitter was calibrated and found satisfactory.                    The    /
    /1/2/      / entire instrument loop was checked and found to be operating properly. The                          /
    /1/3/      / instrument line valves will be examined for leakage and repaired prior to the                        /
    /1/4/      / end of the refueling outage.                                                                        /
l FACILITY                                                  METHOD OF STATUS          % POWER          OTHER STATUS                                DISCOVERY DESCRIPTION (32)
    /1/5/      [C/ (28)        /0/1/7/ (29) /        NA      / (30) DISCOVERY
[A/ (31) / Operator        Observation /
l            ACTIVITY          CONTENT l
RELEASED      OF RELEASE      AMOUNT OF ACTIVITY (35)                  LOCATION OF RELEASE (36) i  /1/6/        [Z/ (33)      [Z/ (34) /            NA                /    /            NA                        /
PERSONNEL EXPOSURES NUMBER            TYPE        DESCRIPTION (39)
    /1/7/ /0/0/0/ (37) LZ[ (38) /                  NA                                                                  /
l            PERSONNEL INJURIES NUMBER            DESCRIPTION (41)
,  /1/8/ /0/0/0/ (40) /                    NA                                                                        /
LOSS TYPE      OF OR  DAMAGE TO FACILITY (43)
DESCRIPTION
    /1/9/      /Z/ (42) /              NA                                                                            /
PUBLICITY ISSUED        DESCRIPTION (45)                                                  NRC USE ONLY
    /2/0/      /N/ (44) /              NA                                                    /////////////
NAME OF PREPARER          W. R. CARTWRIGHT                PHONE      (703) 894-5151 0206240166 820615 PDR ADOCK 05000339 S                        PDR                                                      ~
}}
 
{{LER-Nav}}

Revision as of 21:31, 18 March 2020