ENS 43218: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 16: | Line 16: | ||
| event date = 03/05/2007 EST | | event date = 03/05/2007 EST | ||
| last update date = 03/07/2007 | | last update date = 03/07/2007 | ||
| title = Potential Defect | | title = Potential Defect in E7000 Relays | ||
| event text = Notification of limited E7000 relay recall (CII-010). | | event text = Notification of limited E7000 relay recall (CII-010). | ||
During our normal assembly processing of nuclear E7000 relays, Tyco Electronics experienced an issue with a component. A spring in the base assembly broke during the calibration process. An analysis of the spring revealed non-conforming heat treatment causing the spring to become brittle. Further investigation revealed that this condition was limited to one specific lot of springs. | During our normal assembly processing of nuclear E7000 relays, Tyco Electronics experienced an issue with a component. A spring in the base assembly broke during the calibration process. An analysis of the spring revealed non-conforming heat treatment causing the spring to become brittle. Further investigation revealed that this condition was limited to one specific lot of springs. |
Latest revision as of 21:17, 1 March 2018
Where | |
---|---|
Tyco Electronics Fairview, North Carolina (NRC Region 1) | |
Organization: | Tyco Electronics |
Reporting | |
10 CFR 21.21 | |
Time - Person (Reporting Time:+52.5 h2.188 days <br />0.312 weeks <br />0.0719 months <br />) | |
Opened: | Robert Villegas 09:30 Mar 7, 2007 |
NRC Officer: | Mark Abramovitz |
Last Updated: | Mar 7, 2007 |
43218 - NRC Website | |