ML021550529: Difference between revisions
StriderTol (talk | contribs) (StriderTol Bot insert) |
StriderTol (talk | contribs) (StriderTol Bot change) |
||
| Line 15: | Line 15: | ||
=Text= | =Text= | ||
{{#Wiki_filter:CONTAINMENT SYSTEMS 3/4.6.5 | {{#Wiki_filter:CONTAINMENT SYSTEMS 3/4.6.5 VACUUM RELIEF VALVES LIMITING CONDITION FOR OPERATION 3.6.5.1 Two vacuum relief lines shall be OPERABLE. | ||
APPLICABILITY: MODES 1, 2, 3 and 4. | APPLICABILITY: MODES 1, 2, 3 and 4. | ||
ACTION: | ACTION: | ||
With one vacuum relief line inoperable, restore the vacuum relief line to OPERABLE status within 72 hours or be in at least HOT STANDBY within the next 6 hours and in COLD SHUTDOWN within the following 30 hours. | With one vacuum relief line inoperable, restore the vacuum relief line to OPERABLE status within 72 hours or be in at least HOT STANDBY within the next 6 hours and in COLD SHUTDOWN within the following 30 hours. | ||
SURVEILLANCE REQUIREMENTS 4.6.5.1 | SURVEILLANCE REQUIREMENTS 4.6.5.1 Verify each vacuum relief line OPERABLE in accordance with the Inservice Testing Program. | ||
Amendment No. 90, 452, 4-53, 182 314 6-26 ST. LUCIE - UNIT I | |||
CONTAINMENT SYSTEMS 3/4.6.5 | CONTAINMENT SYSTEMS 3/4.6.5 VACUUM RELIEF VALVES LIMITING CONDITION FOR OPERATION 3.6.5 Two vacuum relief lines shall be OPERABLE. | ||
APPLICABILITY: MODES 1, 2, 3 and 4. | APPLICABILITY: MODES 1, 2, 3 and 4. | ||
ACTION: | ACTION: | ||
With one vacuum relief line inoperable, restore the vacuum relief line to OPERABLE status within 72 hours or be in at least HOT STANDBY within the next 6 hours and in COLD SHUTDOWN within the following 30 hours. | With one vacuum relief line inoperable, restore the vacuum relief line to OPERABLE status within 72 hours or be in at least HOT STANDBY within the next 6 hours and in COLD SHUTDOWN within the following 30 hours. | ||
SURVEILLANCE REQUIREMENTS 4.6.5 | SURVEILLANCE REQUIREMENTS 4.6.5 Verify each vacuum relief line OPERABLE in accordance with the Inservice Testing Program. | ||
Amendment No. 60,89,94-, 125 3'4 6-26 ST. LUCIE - UNIT 2}} | |||
Latest revision as of 18:12, 16 January 2025
| ML021550529 | |
| Person / Time | |
|---|---|
| Site: | Saint Lucie |
| Issue date: | 05/30/2002 |
| From: | Office of Nuclear Reactor Regulation |
| To: | |
| References | |
| Download: ML021550529 (2) | |
Text
CONTAINMENT SYSTEMS 3/4.6.5 VACUUM RELIEF VALVES LIMITING CONDITION FOR OPERATION 3.6.5.1 Two vacuum relief lines shall be OPERABLE.
APPLICABILITY: MODES 1, 2, 3 and 4.
ACTION:
With one vacuum relief line inoperable, restore the vacuum relief line to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
SURVEILLANCE REQUIREMENTS 4.6.5.1 Verify each vacuum relief line OPERABLE in accordance with the Inservice Testing Program.
Amendment No. 90, 452, 4-53, 182 314 6-26 ST. LUCIE - UNIT I
CONTAINMENT SYSTEMS 3/4.6.5 VACUUM RELIEF VALVES LIMITING CONDITION FOR OPERATION 3.6.5 Two vacuum relief lines shall be OPERABLE.
APPLICABILITY: MODES 1, 2, 3 and 4.
ACTION:
With one vacuum relief line inoperable, restore the vacuum relief line to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
SURVEILLANCE REQUIREMENTS 4.6.5 Verify each vacuum relief line OPERABLE in accordance with the Inservice Testing Program.
Amendment No. 60,89,94-, 125 3'4 6-26 ST. LUCIE - UNIT 2