#REDIRECT [[05000259/LER-1981-016, Updated LER 81-016/01T-1:on 810501,during Test,Fire Pump Automatic Start Logic Found Inoperable.Caused by Wiring Removed from Terminal Points in Main Relay Panel 52,during Mod of Panel.Permanent Wire Replaced.Work Plan Revised]]
| number = ML20004D566
| issue date = 06/05/1981
| title = Updated LER 81-016/01T-1:on 810501,during Test,Fire Pump Automatic Start Logic Found Inoperable.Caused by Wiring Removed from Terminal Points in Main Relay Panel 52,during Mod of Panel.Permanent Wire Replaced.Work Plan Revised
| author name =
| author affiliation = TENNESSEE VALLEY AUTHORITY
| addressee name =
| addressee affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
| docket = 05000259
| license number =
| contact person =
| document report number = LER-81-016-01T, LER-81-16-1T, NUDOCS 8106090537
| package number = ML20004D560
| document type = LICENSEE EVENT REPORT (SEE ALSO AO,RO), TEXT-SAFETY REPORT
| page count = 2
}}
 
=Text=
{{#Wiki_filter:~
1 1
I
    ""cro"              h      , Update R2 port - Prsvious Report Data                                        5/12/81                  U. S. NUCLE AR REGULATORY COMMISSION LICENSEE EVENT REPORT o
bCONTROL8tOCK;l                              l      l    l    l  l lh                  (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION) lo ltlatl >Al LlLICENSEE B l RlCODE      Fl 1 l@l 01$ l 0 l- l 0 l 0LICENSE le l 0 lNUMBER 0 l 0 l- l 0 l 0 l@l    25 426 l 1 LICENSE l 1 l 1TYPE  l 1JOl@l 57 CAT l 58 l@          l CON'T CL I1.J                [,n"C      l60L @l610 l 5 l 00CKET        0 l 0NUMBER l012 l 5 l 968 @l69 015EVENT        lo l1    l 811 74l@l75016REPORT        l 0 ] DATE 5 l 8 l180l@
    /        3                                                                                                          DATE EVENT DESCRl* TION AND PROBABLE CONSEQUENCES h l o l 2 l l During post-modification tests on a new sprinkler system. the fire oumo automatic                                                                                        I go l3; l start logic was found inoperable.                                                T.S. 3.11..A.l.b requires operable logic. One fire I
    .[ o l 4 ; Ipump was running at the time the inoperability was discovered. The pump was kept                                                                                          l I
io ls; l running while the automatic-start circuit was repaired. Manual start capability                                                                                            ]
Io is ] lwas operable. Units 1, 2, and 3 were affected. There was no danster to the health                                                                                            l lolij jor safety of the public. There are no redundant systems. There were no previous                                                                                              I iojg; lsimilar events.                                                                                                                                                              I i      a9                                                                                                                                                                      80 JYSTEM              CAUSE          CAUSE                                                    COMP.          VALV E CODE              CODE        SUSCODE                  COMPONENT CODE                    SUSCODE          SU8 CODE mp        el i A l B10 l@ l A l@ l X l @ l Z ] Z l Z l Z l Z l Z l@ [Z_J @ [Z_l 9                      11            12            13                            18          19              20
_                                          SEQUEN TI AL                      OCCURRENCE            REPORT                      REVISION LERiRO        EVENT YE4R                                REPORT No.                            CODE                TYPE                        N O.
                    @ aEPORT                l 8l 1l              l_l            l 0l 1l 6l              l/l          l0l1l                  l Tl          l-l        [1]
21        22          23            24            26        27          28        29          30            31          32 TAK N AC O                      O PLANT            MET                      HOURS 22        S8 i            FOR        8.      SUPPL E            MANUFAC RER lCl@l_Zj@                        lZ l@              l36 Zl@          l 0l 0l 0l 37 l  W@
43 l N lg            l43Z l@      l44Z l 9 ] 9 l 947 [@
JJ        J4                  JS                                                      40                    42 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS lijoll Wiring was removed from terminal points in main relay panel 52, interrupting power to I g,i,j l fire pump auto-start circuit, probably while performing a modification in the canel.                                                                                        I
      ,,,,,g P ermanent wire was replaced immediately. Workplan was revised to caution electriciansI g lco consult with cognizant engineer prior to removing existing wiring.                                                                                                            [
li t il i                                                                                                                                                                            l i      8 9                                                                                                                                                                      80 T1 s                TPOWER                          OTHE A STATUS              015 y RY                              DISCOVERY DESCRIPTION W [Z_j @ l Ol Ol 0lhl                                                  NA                    l    l,C.,_l@l            Soecin1 test                                                l A T:VirY CO TENT AELE ASED OF RELE ASE                            AMOUNT OF ACTIVITY                                                      LOCATION OF RELEASE W lZl@ W @l t      g 9                    10            13 NA 44 l          l 45 NA 80 l
PERSONNEL F APOSURES t                        NOPeR E R              TYPE        DESCRIPTION ^
l    li l il"10 l 010 l@l    '
Zi@l      ''
NA l
;                        PE nSO~~E'L IN;U'JiES
!                        NuMnER                  oESCRiPnON@
l NA 1
i M
                    ! O l 0 l 011 l(Jl12
                    't                                                                                                                                                                80 l
t O';5 OF OR OAMAGE TO FACILlTY TYPE        O f SCnt PTION                                                                                      *
;
W lZl@l i        4 1                TO NA 80 l
e tsuPfifjN NhC USE ONLY            ,
e "      e;;ui81 LN_                                          NA                                                                                    l    lllllllll[]llj l
t      4 1                to                                                                                                                  68 69                          80 ;
o S
NAME OF PREP ARER                                                                                      PHONE:
l 8106090 W
 
o.
            ~ Tcnnessee Valley Authority                                            Form BF-17 Browns Ferry Nuclear Plant                                                  BF 15.2 3/24/81 LER SUPPLEMENTAL INFORMATION BFRO 259 / 81016 R1 Technical Specification Involved      3.11.A.l.b Reported Under Technical Specification              6.7.2.a(2)
Date of Occurrence      5/8/81    Time of Occurrence 1550        Unit 1, 2, and 3 Identification and Description of Occurrence:
Power (120V AC preferred) lifted to fire pump auto-initiation. The exact duration the circuit had been inoperable could not be determined. However, it is probable that the wiring was removed during the modification activity, making the duration 2 weeks ur less.
Conditions Prior to Occurrence:
Unit 1 refueling outage.
Unit 2 at 99%.
Unit 3 at 100%.
Action specified in the Technical Specification Surveillance Requirements met due to inoperable equipment. Describe.
Reterminated power supply.
Apparent Cause of Occurrence:
Wiring was removed from terminal points in main relay panel 52 resulting in the interruption of power to the fire pump auto-start circuit. Although it could not definitely be determined how the wiring was removed, it is suspected that the wires were removed during performance of a molification in tne panel.
Analysis of Occurrence:
There was no danger to the health or safety of the public, no release of activity, no damage to the plant or equipment, and n) resulting significant chain of events.
I  -
l            Corrective Action:
l  ~
Replaced permanent wiring immediately. Precautions have been added to the l          workplan requiring the electricians to consu'; the cognizanc engineer prior to removing any existing wiring.
I l
Failure Data:
Notic
(