| Line 1: |
Line 1: |
| {{Adams
| | #REDIRECT [[05000339/LER-1981-038-03, /03L-0:on 810505,during Mode 1 Operation,Channel III Feedwater Flow Indication for Loop 2 Failed High.Caused by Failure of Loop Multiplier/Divider/Square Root Card.Card Replaced & Channel Recalibr & Returned to Svc]] |
| | number = ML20004D602
| |
| | issue date = 06/03/1981
| |
| | title = LER 81-038/03L-0:on 810505,during Mode 1 Operation,Channel III Feedwater Flow Indication for Loop 2 Failed High.Caused by Failure of Loop Multiplier/Divider/Square Root Card.Card Replaced & Channel Recalibr & Returned to Svc
| |
| | author name = Cartwright W
| |
| | author affiliation = VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
| |
| | addressee name =
| |
| | addressee affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
| |
| | docket = 05000339
| |
| | license number =
| |
| | contact person =
| |
| | document report number = LER-81-038-03L, LER-81-38-3L, NUDOCS 8106090570
| |
| | package number = ML20004D595
| |
| | document type = LICENSEE EVENT REPORT (SEE ALSO AO,RO), TEXT-SAFETY REPORT
| |
| | page count = 1
| |
| }}
| |
| | |
| =Text=
| |
| {{#Wiki_filter:.
| |
| U.S. NUCLEAR REGULATORY COMMISSION LICENSEE EVENT REPORT CONTROL BL0CK / / / / / / / (1) (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION)
| |
| /0/1/ /V/A/N/A/S/2/ (2) /0/0/-/0/0/0/0/0/-/0/0/ (3) /4/1/1/1/1/ (4) / / / (5)
| |
| LICENSE NUMBER LICENSE TYPE CAT
| |
| /0/1/ g LICENSEE P CODE g/ (6) /0/5/0/0/0/3/3/9/ (7) /0/5/0/5/8/1/ (8) /0/6/0/3/8/1/ (9)
| |
| DOCKET NUMBER EVENT DATE REPORT DATE EVENT DESCRIPTION AND PROBABLE CONSEQUENCES (10)
| |
| /0/2/ / On May 5, 1981, during Mode 1 operation, Channel III feedwater flow indication /
| |
| /0/3/ / for Loop 2 failed high. This condition would have prevented the channel from /
| |
| /0/4/ / generating a reactor trip signal on a steam flow / feed flow mismatch (FS>FW) /
| |
| /0/5/ / coincident with low steam generator level. The affected steam flow > feed flow /
| |
| /0/6/ / reactor trip bistable was placed in that tripped conditien in I hour by placing /
| |
| /0/7/ / the feed flow channel in " test". Therefore, the health and safety of the gener-/
| |
| /0/8/ / al public were not affected.This event is reportable pursuant to T.S.6.9.1.9.b./
| |
| SYSTEM CAUSE CAUSE COMP. VALVE CODE CODE SUBCODE COMPONENT CODE SUBCODE SUBCODE
| |
| /0/9/ /I/A/ (11) g/ (12) LG/ (13) /I/N/S/T/R/U/ (14) g/ (15) LZ/ (?6)
| |
| SEQUENTIAL OCCURRENCE REPORT REVISION LER/R0 EVENT YEAR REPORT NO. CODE TYPE NO.
| |
| (17) REPORT NLdBER /8/1/ L-/ /0/3/8/ /\/ /0/3/ LL/ /-/ /_0/
| |
| ACTION FUTURE EFFECT SHUTDOWN ATTACHMENT NPRD-4 PRIME COMP. COMPONENT TAKEN ACTION ON PLANT METHOD HOURS oUBMITTED FORM SUB. SUPPLIER MANUFACTURER g/ (18) g/ (19) LZ/ (20) LZ/ (21) /0/0/0/0/ (22) g/ (23) /_N/ (24) LN/ (25) /W/1/2/0/ (26' ,
| |
| CAUSE' DESCRIPTION aND CORRECTIVE ACTIONS (27)
| |
| /1/0/ / The feed flow channel failed high due to failure of the loop multiplier / /
| |
| /1/1/ / divider / square root card. The defective NMD card was replaced and the channel /
| |
| /1/2/ / was satisfactorily recalibrated and returned to service. /
| |
| l /1/3/ / /
| |
| /1/4/ / /
| |
| FACILITY METHOD OF STATUS % POWER OTHER STATUS DIS M RY DESCR M M (32) l /1/5/ /E/ (28) /1/0/0/ (29) / NA / (30)DISCOERY g/ (31) / OPERATOR OBSERVATION /
| |
| ACTIVITY CONTENT RELEASED OF RELEASE AMOUNT OF ACTIVITY (35) LOCATION OF RELEASE (36) l /1/6/ g/ (33) /_Z/ (34) / NA / / NA /
| |
| l PERSONNEL EXPOSURES
| |
| ! NUMBER TYPE DESCRIPTION (39) l /1/7/ /0/0/0/ (37) /Z/_ (38) / NA _ ~
| |
| /
| |
| [ PERSONNEL INJURIES l NUMBER DESCRIPTION (41) l
| |
| /1/8/ /0/0/0/ (40) / NA _ '
| |
| /
| |
| LOSS OF OR DAMAGE TO FACILITY (
| |
| ( TIPE DESCRIPTION
| |
| /
| |
| l /1/9/ /Z/ (42) / NA
| |
| ! PUBLICITY l- ISSUED DESCRIPTION (45) NRC USE ONLY
| |
| ! /2/0/ /N/ (44) L NA /////////////
| |
| NAME OF PREPARER W. R. CARTWRIGHT PdCN (703) 894-5151 0 _ _ _ _ _ _. _,
| |
| | |
| Virginia Electric and Power Company North Anna Power Station, Unit #2
| |
| | |
| ==Attachment:==
| |
| Page 1 of 1 Decket No. 50-339 Report No. LER 81-038/03L-0 Description of Event On May 5,1981, while operating at 100% power, it was observed that the Channel III indication for Loop 2 feedwater flow had failed high. This condition would have prevented a reactor trip signal from being generated by the channel on a steam flow / feed flow mismatch (steam flow > feed flow) coincident with low steam generator level.
| |
| This event is contrary to T.S. 3.3.1.1 and reportable pursuant to T.S.
| |
| 6.9.1.9.b.
| |
| Probable Consequences of Occurrence The consequences of this event were limited because the steam flow >
| |
| feed flow reactor trip bistable was placed in the tripped condition within I hour in accordance with the Action Statement of T.S. 3.3.1.1 and channel IV for Loop 2 feedwater flow remained operable. As a result, the health and safety of the general public were not affected. -
| |
| Cause of Event ,
| |
| The feed flow channel failed high due to failure of the multiplier /
| |
| divider / square root card (NMD card) in the loop circuitry.
| |
| , Immediate Corrective Action i The defective NMD card was removed and replaced with a new card.
| |
| The channel was then satisfactorily recalibrated per procedure and returned to service.
| |
| Scheduled Corrective Action No scheduled corrective action is required.
| |
| ( Actions Taken to Prevent Recurrence No further actions are required.
| |
| l Generic Implications There are no generic implications associated with this occurrence.
| |
| I l
| |
| I l
| |
| l i
| |
| I l
| |
| ~ - . , , _ _ ,-.,, _ , , . _
| |
| __,...y -, ._ . , . . _ . , - . , , . . -
| |
| . _ , . , -}}
| |