ML20004D602: Difference between revisions

From kanterella
Jump to navigation Jump to search
Created page by program invented by StriderTol
 
StriderTol Bot change
 
Line 1: Line 1:
{{Adams
#REDIRECT [[05000339/LER-1981-038-03, /03L-0:on 810505,during Mode 1 Operation,Channel III Feedwater Flow Indication for Loop 2 Failed High.Caused by Failure of Loop Multiplier/Divider/Square Root Card.Card Replaced & Channel Recalibr & Returned to Svc]]
| number = ML20004D602
| issue date = 06/03/1981
| title = LER 81-038/03L-0:on 810505,during Mode 1 Operation,Channel III Feedwater Flow Indication for Loop 2 Failed High.Caused by Failure of Loop Multiplier/Divider/Square Root Card.Card Replaced & Channel Recalibr & Returned to Svc
| author name = Cartwright W
| author affiliation = VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
| addressee name =
| addressee affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
| docket = 05000339
| license number =
| contact person =
| document report number = LER-81-038-03L, LER-81-38-3L, NUDOCS 8106090570
| package number = ML20004D595
| document type = LICENSEE EVENT REPORT (SEE ALSO AO,RO), TEXT-SAFETY REPORT
| page count = 1
}}
 
=Text=
{{#Wiki_filter:.
U.S. NUCLEAR REGULATORY COMMISSION LICENSEE EVENT REPORT CONTROL BL0CK / / / / / / / (1)              (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION)
    /0/1/          /V/A/N/A/S/2/ (2)              /0/0/-/0/0/0/0/0/-/0/0/ (3)                  /4/1/1/1/1/ (4)        / / / (5)
LICENSE NUMBER                        LICENSE TYPE            CAT
    /0/1/ g LICENSEE  P      CODE g/ (6)        /0/5/0/0/0/3/3/9/ (7)              /0/5/0/5/8/1/ (8) /0/6/0/3/8/1/ (9)
DOCKET NUMBER                    EVENT DATE                  REPORT DATE EVENT DESCRIPTION AND PROBABLE CONSEQUENCES (10)
    /0/2/      /    On May 5, 1981, during Mode 1 operation, Channel III feedwater flow indication /
    /0/3/      /    for Loop 2 failed high. This condition would have prevented the channel from /
    /0/4/      /    generating a reactor trip signal on a steam flow / feed flow mismatch (FS>FW)                          /
    /0/5/      /    coincident with low steam generator level. The affected steam flow > feed flow /
    /0/6/      /    reactor trip bistable was placed in that tripped conditien in I hour by placing /
    /0/7/      /    the feed flow channel in " test". Therefore, the health and safety of the gener-/
    /0/8/      /    al public were not affected.This event is reportable pursuant to T.S.6.9.1.9.b./
SYSTEM        CAUSE          CAUSE                                COMP.            VALVE CODE          CODE        SUBCODE        COMPONENT CODE            SUBCODE          SUBCODE
    /0/9/        /I/A/ (11) g/ (12) LG/ (13) /I/N/S/T/R/U/ (14) g/ (15)                                  LZ/ (?6)
SEQUENTIAL              OCCURRENCE          REPORT          REVISION LER/R0    EVENT YEAR            REPORT NO.                  CODE            TYPE                NO.
(17) REPORT NLdBER      /8/1/        L-/ /0/3/8/            /\/          /0/3/          LL/        /-/    /_0/
ACTION        FUTURE      EFFECT        SHUTDOWN                    ATTACHMENT NPRD-4            PRIME COMP. COMPONENT TAKEN        ACTION      ON PLANT METHOD              HOURS        oUBMITTED FORM SUB. SUPPLIER MANUFACTURER g/ (18) g/ (19) LZ/ (20) LZ/ (21) /0/0/0/0/ (22) g/ (23) /_N/ (24) LN/ (25) /W/1/2/0/ (26'                                ,
CAUSE' DESCRIPTION aND CORRECTIVE ACTIONS (27)
    /1/0/    /      The feed flow channel failed high due to failure of the loop multiplier /                              /
    /1/1/      /    divider / square root card. The defective NMD card was replaced and the channel /
    /1/2/    /      was satisfactorily recalibrated and returned to service.                                              /
l  /1/3/    /                                                                                                            /
    /1/4/    /                                                                                                            /
FACILITY                                                      METHOD OF STATUS          % POWER            OTHER STATUS                                  DIS M RY DESCR M M (32) l  /1/5/    /E/ (28)      /1/0/0/ (29) /            NA        / (30)DISCOERY g/ (31)        /    OPERATOR OBSERVATION        /
ACTIVITY          CONTENT RELEASED      OF RELEASE      AMOUNT OF ACTIVITY (35)                      LOCATION OF RELEASE (36) l  /1/6/        g/ (33)      /_Z/ (34) /              NA                  /    /            NA                          /
l            PERSONNEL EXPOSURES
!            NUMBER          TYPE          DESCRIPTION (39) l  /1/7/ /0/0/0/ (37) /Z/_ (38) /                  NA            _  ~
                                                                                                                            /
[            PERSONNEL INJURIES l            NUMBER          DESCRIPTION (41) l
    /1/8/ /0/0/0/ (40) /                  NA                _      '
                                                                                                                            /
LOSS OF OR DAMAGE TO FACILITY (
(            TIPE        DESCRIPTION
                                                                                                                            /
l  /1/9/    /Z/ (42) /              NA
!                    PUBLICITY l-          ISSUED        DESCRIPTION (45)                                                        NRC USE ONLY
!  /2/0/    /N/ (44) L              NA                                                        /////////////
NAME OF PREPARER            W. R. CARTWRIGHT                  PdCN      (703) 894-5151 0          _ _                _              _          _            _.                      _,
 
Virginia Electric and Power Company North Anna Power Station, Unit #2                   
 
==Attachment:==
Page 1 of 1 Decket No. 50-339 Report No. LER 81-038/03L-0 Description of Event On May 5,1981, while operating at 100% power, it was observed that the Channel III indication for Loop 2 feedwater flow had failed high. This condition would have prevented a reactor trip signal from being generated by the channel on a steam flow / feed flow mismatch (steam flow > feed flow) coincident with low steam generator level.
This event is contrary to T.S. 3.3.1.1 and reportable pursuant to T.S.
6.9.1.9.b.
Probable Consequences of Occurrence The consequences of this event were limited because the steam flow >
feed flow reactor trip bistable was placed in the tripped condition within I hour in accordance with the Action Statement of T.S. 3.3.1.1 and channel IV for Loop 2 feedwater flow remained operable. As a result, the health and safety of the general public were not affected.                                      -
Cause of Event                                ,
The feed flow channel failed high due to failure of the multiplier /
divider / square root card (NMD card) in the loop circuitry.
,                Immediate Corrective Action i                      The defective NMD card was removed and replaced with a new card.
The channel was then satisfactorily recalibrated per procedure and returned to service.
Scheduled Corrective Action No scheduled corrective action is required.
(                Actions Taken to Prevent Recurrence No further actions are required.
l Generic Implications There are no generic implications associated with this occurrence.
I l
I l
l i
I l
  ~ - . ,      ,  _                _ ,-.,,  _ , , . _
__,...y  -, ._          . , . . _ . , - . , , . .  -
                                                                                                              . _ , . , -}}

Latest revision as of 12:04, 23 December 2024