ML17208A705: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(StriderTol Bot change)
 
Line 6: Line 6:
| number = ML17266A214
| number = ML17266A214
| issue date = 06/06/1980
| issue date = 06/06/1980
| title = Forwards LER 80-021/03L-0
| title = LER 80-021/03L-0:on 800507,during Normal Surveillance & post-maint testing,1A Diesel Generator Failed to Synchronize to Emergency Bus.Caused by Frequency Permissive Relay Being Set Incorrectly.Relay Setpoint Corrected
| author name = Schoppman M
| author name = Schoppman M
| author affiliation = FLORIDA POWER & LIGHT CO.
| author affiliation = FLORIDA POWER & LIGHT CO.

Latest revision as of 11:04, 8 March 2020

Forwards LER 80-021/03L-0
Date released: 01/25/2018 Download: ML17208A705


LER 80-021/03L-0:on 800507,during Normal Surveillance & post-maint testing,1A Diesel Generator Failed to Synchronize to Emergency Bus.Caused by Frequency Permissive Relay Being Set Incorrectly.Relay Setpoint Corrected
ML17266A214
Person / Time
Site: Saint Lucie NextEra Energy icon.png
Issue date: 06/06/1980
From: Schoppman M
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML17266A214 (2)
Forwards LER 80-021/03L-0
ML17208A704
Person / Time
Site: Saint Lucie NextEra Energy icon.png
Issue date: 06/06/1980
From: Schmidt A
FLORIDA POWER & LIGHT CO.
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML17208A704 (1)