ENS 40283: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 16: | Line 16: | ||
| event date = 10/29/2003 CST | | event date = 10/29/2003 CST | ||
| last update date = 10/29/2003 | | last update date = 10/29/2003 | ||
| title = 10 Cfr 21 Notification | | title = 10 Cfr 21 Notification for Ge Magne-Blast Breaker Tube and Piston Assemblies | ||
| event text = This notice is being sent within the two day period to inform you of a safety concern related to tube and piston assemblies for GE Magne-Blast breakers (model AM-4.16-350-2h medium voltage circuit breaker). | | event text = This notice is being sent within the two day period to inform you of a safety concern related to tube and piston assemblies for GE Magne-Blast breakers (model AM-4.16-350-2h medium voltage circuit breaker). | ||
The concern is specific to tube and piston assemblies supplied under part number Q0213X0343R094. All five assemblies supplied to AmerenUE contain a dimensional design error which would cause the assembly to interfere and bind with the circuit breaker movable contact assembly, which would render the breaker inoperative. | The concern is specific to tube and piston assemblies supplied under part number Q0213X0343R094. All five assemblies supplied to AmerenUE contain a dimensional design error which would cause the assembly to interfere and bind with the circuit breaker movable contact assembly, which would render the breaker inoperative. |
Latest revision as of 21:24, 1 March 2018
Where | |
---|---|
Callaway Missouri (NRC Region 4) | |
Reporting | |
10 CFR 21.21 | |
Time - Person (Reporting Time:+4.08 h0.17 days <br />0.0243 weeks <br />0.00559 months <br />) | |
Opened: | David M. Epperson 10:05 Oct 29, 2003 |
NRC Officer: | Steve Sandin |
Last Updated: | Oct 29, 2003 |
40283 - NRC Website
| |