ENS 44028: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 16: | Line 16: | ||
| event date = 03/04/2008 08:16 EST | | event date = 03/04/2008 08:16 EST | ||
| last update date = 03/04/2008 | | last update date = 03/04/2008 | ||
| title = Erds Link Determined Inoperable | | title = Erds Link Determined Inoperable for 3 Hour Period | ||
| event text = On 3/04/08 at 0816 EST, the Control Room was notified that the ERDS Link was inoperable from 1815 to 2115 EST on 3/03/08. | | event text = On 3/04/08 at 0816 EST, the Control Room was notified that the ERDS Link was inoperable from 1815 to 2115 EST on 3/03/08. | ||
During the troubleshooting it was discovered that a fuse was blown on the ERDADS I/O Subsystem Chassis. The ability to activate the ERDS Link is done by the Tesselators which were locked up due to the blown fuse. Removing power fuse for inspection and replacing was completed, chassis resumed normal functions. The ERDS link was returned to operable 3/03/08 at 2115 EST. | During the troubleshooting it was discovered that a fuse was blown on the ERDADS I/O Subsystem Chassis. The ability to activate the ERDS Link is done by the Tesselators which were locked up due to the blown fuse. Removing power fuse for inspection and replacing was completed, chassis resumed normal functions. The ERDS link was returned to operable 3/03/08 at 2115 EST. |
Latest revision as of 22:14, 1 March 2018
Where | |
---|---|
Turkey Point ![]() Florida (NRC Region 2) | |
Reporting | |
10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness | |
Time - Person (Reporting Time:+-1.95 h-0.0813 days <br />-0.0116 weeks <br />-0.00267 months <br />) | |
Opened: | Jim Russell 11:19 Mar 4, 2008 |
NRC Officer: | Steve Sandin |
Last Updated: | Mar 4, 2008 |
44028 - NRC Website
| |