| title = Part 21 Report - Failure Of A Spare Limitorque Actuator Motor
| title = Part 21 Report - Failure of a Spare Limitorque Actuator Motor
| event text = On July 31, 2009, [Crystal River Unit 3] personnel performed a video probe inspection of a spare safety-related Limitorque SB-3/SMB-3 actuator motor magnesium rotor and end rings. Visual indications were observed in the outboard end of the motor which were cause for rejection based on specified acceptance criteria. The specific indication was a cracked weld with dislodged metal in the outboard end of the motor.  
| event text = On July 31, 2009, [Crystal River Unit 3] personnel performed a video probe inspection of a spare safety-related Limitorque SB-3/SMB-3 actuator motor magnesium rotor and end rings. Visual indications were observed in the outboard end of the motor which were cause for rejection based on specified acceptance criteria. The specific indication was a cracked weld with dislodged metal in the outboard end of the motor.  
In 2007, the spare safety-related Limitorque SB-3/SMB-3 actuator motor (Motor Serial Number 7497004-001T1AL: Limitorque Part No. R-403-F04-0821) was purchased as safety-related Quality level 1 (QL-1) from AREVA under Purchase Order No. 337566. Limitorque purchased the motor from the Baldor Electric Company, doing business as the Reliance Electric Company, as commercial grade and dedicated the motor to safety related.  
In 2007, the spare safety-related Limitorque SB-3/SMB-3 actuator motor (Motor Serial Number 7497004-001T1AL: Limitorque Part No. R-403-F04-0821) was purchased as safety-related Quality level 1 (QL-1) from AREVA under Purchase Order No. 337566. Limitorque purchased the motor from the Baldor Electric Company, doing business as the Reliance Electric Company, as commercial grade and dedicated the motor to safety related.  

Latest revision as of 22:11, 1 March 2018

ENS 45317 +/-
Where
Crystal River Duke Energy icon.png
Florida (NRC Region 2)
Reporting
10 CFR 21.21
Time - Person (Reporting Time:+14.42 h0.601 days <br />0.0858 weeks <br />0.0198 months <br />)
Opened: Joshua Morse
09:10 Sep 1, 2009
NRC Officer: Dong Park
Last Updated: Sep 1, 2009
45317 - NRC Website
Loading map...