| title = Unit 2 Emergency Diesel Generators Inoperable Due | | title = Unit 2 Emergency Diesel Generators Inoperable Due to Missing Flood Control Barrier Seal | ||
| event text = D5 and D6 Diesel Generators (DG) were declared inoperable at 1400 CDT due to a missing internal flood control barrier seal. The missing flood control barrier seal is required to be installed with Unit 2 in Modes 1, 2, 3, and 4 when the MSIV's are open. | | event text = D5 and D6 Diesel Generators (DG) were declared inoperable at 1400 CDT due to a missing internal flood control barrier seal. The missing flood control barrier seal is required to be installed with Unit 2 in Modes 1, 2, 3, and 4 when the MSIV's are open. | ||
LCO 3.8.1 Condition B was entered for both DGs and LCO 3.8.1 Condition E was entered for two DGs inoperable on the same unit. The DGs could start and run if required at the time of entry. | LCO 3.8.1 Condition B was entered for both DGs and LCO 3.8.1 Condition E was entered for two DGs inoperable on the same unit. The DGs could start and run if required at the time of entry. |
Latest revision as of 21:03, 1 March 2018
Where | |
---|---|
Prairie Island Minnesota (NRC Region 3) | |
Reporting | |
10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor | |
Time - Person (Reporting Time:+-2.08 h-0.0867 days <br />-0.0124 weeks <br />-0.00285 months <br />) | |
Opened: | Stever Schmidt 16:55 Jul 20, 2012 |
NRC Officer: | Donald Norwood |
Last Updated: | Jul 20, 2012 |