ENS 51747: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 02/20/2016 03:30 EST
| event date = 02/20/2016 03:30 EST
| last update date = 02/20/2016
| last update date = 02/20/2016
| title = Degraded Condition Discovered On Pressurizer Safety Relief Valve Weld
| title = Degraded Condition Discovered on Pressurizer Safety Relief Valve Weld
| event text = During the CCNPP [Calvert Cliff Nuclear Power Plant] Unit 1 Refueling, [an ultrasonic test] examination of the Unit 1 dissimilar metal weld (DMW) of the pressurizer safety relief valve RV-201 safe end weld found an indication that is approximately 80 percent though-wall, inside diameter connected axial flaw in weld #4-SR-1006-1.
| event text = During the CCNPP [Calvert Cliff Nuclear Power Plant] Unit 1 Refueling, [an ultrasonic test] examination of the Unit 1 dissimilar metal weld (DMW) of the pressurizer safety relief valve RV-201 safe end weld found an indication that is approximately 80 percent though-wall, inside diameter connected axial flaw in weld #4-SR-1006-1.
This is an ASME Class 1 component and Unit 1 has entered the requirements of Technical Requirements Manual (TRM) 15.4.3.A.  
This is an ASME Class 1 component and Unit 1 has entered the requirements of Technical Requirements Manual (TRM) 15.4.3.A.  

Latest revision as of 20:45, 1 March 2018

ENS 51747 +/-
Where
Calvert Cliffs Constellation icon.png
Maryland (NRC Region 1)
Reporting
10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded
LER: 05000317/LER-2016-002
Time - Person (Reporting Time:+0.7 h0.0292 days <br />0.00417 weeks <br />9.5886e-4 months <br />)
Opened: Ervin Lyson
09:12 Feb 20, 2016
NRC Officer: Howie Crouch
Last Updated: Feb 20, 2016
51747 - NRC Website
Loading map...