Template:System actuation summary: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page with "==System Actuation Reporting Summary== {| class="wikitable" ! !! Valid !! Invalid |- | '''Moved''' | ENS + LER | LER (as 60 day ENS) |- | '''Not moved''' | ENS + LER | None |...") |
StriderTol (talk | contribs) No edit summary |
||
| Line 27: | Line 27: | ||
Allowance for invalid signals which actuated a system | Allowance for invalid signals which actuated a system | ||
* [[10 CFR 50.73(a)(1), Submit an LER]] | * [[10 CFR 50.73(a)(1), Submit an LER]] | ||
===System actuation list=== | |||
System Actuation Reporting contains a list of applicable systems | |||
* [[10 CFR 50.72(b)(3)(iv)(A), System Actuation|ENS-50.72(b)(3)(iv)(A)]] -> [[10 CFR 50.72#b3ivB|(b)(3)(iv)(B)]] | |||
* [[10 CFR 50.73(a)(2)(iv)(A), System Actuation|LER-50.73(a)(2)(iv)(A)]] -> [[10 CFR 50.73#a2ivA|(a)(2)(iv)(A)]] | |||
Both list include: | |||
:(1) [[Reactor protection system]] (RPS) including: Reactor scram and reactor trip. | |||
:(2) [[General containment isolation signal]]s affecting containment isolation valves in more than one system or multiple main steam isolation valves (MSIVs). | |||
:(3) [[Emergency core cooling system]]s (ECCS) for pressurized water reactors (PWRs) including: High-head, intermediate-head, and low-head injection systems and the low pressure injection function of residual (decay) heat removal systems. | |||
:(4) [[ECCS]] for boiling water reactors (BWRs) including: [[High-pressure core spray|High-pressure]] and low-pressure core spray systems; [[high-pressure coolant injection system]]; low pressure injection function of the [[residual heat removal system]]. | |||
:(5) BWR [[reactor core isolation cooling system]]; [[isolation condenser system]]; and [[feedwater coolant injection system]]. | |||
:(6) PWR [[auxiliary feedwater system|feedwater system]] or [[emergency feedwater system]]. | |||
:(7) [[Containment heat removal system|Containment heat removal]] and depressurization systems, including [[containment spray system|containment spray]] and [[fan cooler system]]s. | |||
:(8) [[Emergency ac electrical power system]]s, including: [[Emergency diesel generator]]s (EDGs); hydroelectric facilities used in lieu of EDGs at the Oconee Station; and BWR dedicated Division 3 EDGs. | |||
Only 50.73: (9) [[Emergency service water system]]s that do not normally run and that serve as ultimate heat sinks. | |||
Latest revision as of 18:50, 19 April 2023
System Actuation Reporting Summary
| Valid | Invalid | |
|---|---|---|
| Moved | ENS + LER | LER (as 60 day ENS) |
| Not moved | ENS + LER | None |
4-hour (ENS)
While Critical or RPS (ie Scram)
8-hour (ENS)
60-day (LER)
60-day (ENS)
Allowance for invalid signals which actuated a system
System actuation list
System Actuation Reporting contains a list of applicable systems
Both list include:
- (1) Reactor protection system (RPS) including: Reactor scram and reactor trip.
- (2) General containment isolation signals affecting containment isolation valves in more than one system or multiple main steam isolation valves (MSIVs).
- (3) Emergency core cooling systems (ECCS) for pressurized water reactors (PWRs) including: High-head, intermediate-head, and low-head injection systems and the low pressure injection function of residual (decay) heat removal systems.
- (4) ECCS for boiling water reactors (BWRs) including: High-pressure and low-pressure core spray systems; high-pressure coolant injection system; low pressure injection function of the residual heat removal system.
- (5) BWR reactor core isolation cooling system; isolation condenser system; and feedwater coolant injection system.
- (6) PWR feedwater system or emergency feedwater system.
- (7) Containment heat removal and depressurization systems, including containment spray and fan cooler systems.
- (8) Emergency ac electrical power systems, including: Emergency diesel generators (EDGs); hydroelectric facilities used in lieu of EDGs at the Oconee Station; and BWR dedicated Division 3 EDGs.
Only 50.73: (9) Emergency service water systems that do not normally run and that serve as ultimate heat sinks.